Bucher C-LRV Series, C-LRV 175, C-LRV 350, C-LRV 700 Installation And Startup Manual

Installation and startup guide
Issue: 08.08
−LRV Lift Control Valve, Size 175 / 350 / 700
NTA−2 power supply unit and C−DELCON
Reference: 300−I−9010212−E−10/08.08
1/92Classification: 450.500.500
Published
Bucher Hydraulics AG Industriestrasse 15 CH−6345 Neuheim
Phone +41 41 757 03 33 Fax +41 41 757 05 00 Emailinfo.nh@bucherhydraulics.com Internet www.bucherhydraulics.com
E 2008 by Bucher Hydraulics AG, CH−6345 Neuheim
All rights reserved. This installation and commissioning guide, in whole and/or in part, is protected by copyright. It may not be reproduced, nor may it be stored, processed, replicated or distributed by electronic means, without written permission from Bucher Hydraulics AG. Data is provided for the purpose of product description only, and must not be construed as war­ranted characteristics in the legal sense. No assertion regarding either a particular property or the fitness for a particular intended purpose can be derived or deduced from this information. The in­formation does not relieve users from the duty of conducting their own evaluations and tests. Because the products are subject to continual improvement, we reserve the right to amend the product specifications contained in this catalogue. The original language and legal terminology of all Bucher Hydraulics AG documentation is exclusively German. Bucher Hydraulics AG cannot be held liable for any possible errors in translation.
300−I−9010212−E−10/08.08
2/92
Content Page
0 General 5
0.1 Target group
0.2 Supplementary documents
0.3 Specialist terms
1 Product description
1.1 Important notes
1.1.1 Subassemblies 7
1.1.2 intended use 8
1.1.3 Conformity 8
1.2 Product identification 9
1.2.1 Nameplate 9
1.2.2 Test number 9
1.2.3 Model code 10
1.3 C−LRV lift control valve 11
1.3.1 Simplified hydraulic–electrical diagram 12
1.3.2 Factory settings 13
1.3.3 Description of function 13
1.3.4 Technical data 16
1.3.5 Pressure drop 18
1.4 C−DELCON electronic card 20
1.4.1 Factory settings 20
1.4.2 Description of function 21
1.4.3 Technical data 22
1.4.4 Travel and switching diagram for normal travel distance 23
1.4.5 Travel and switching diagram for short travel distances 24
1.5 NTA−2 power supply unit 26
1.5.1 Description 27
1.5.2 Technical data 28
1.5.3 Terminal assignments 29
1.6 IWK−1 feedback cable 31
1.7 Surroundings
1.8 Emissions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
32
5
5
5
7
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Safety information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Operating controls and indicators
3.1 Emergency−lowering valve
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Display of the operating status
3.3 Handterminal
3.4 WinDelta32 − PC program
3.4.1 General description 41
3.4.2 PC requirements 42
3.4.3 Installation on PC / Laptop 42
3.4.4 Connect DELCON to PC / Laptop 45
300−I−9010212−E−10/08.08
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
35
36
36
37
41
3/92
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Installation and commissioning 47
4.1 Installation
4.2 Assembly
4.2.1 Hose or pipe 48
4.2.2 Power supply unit
4.2.3 Wiring the power supply unit 49
4.2.4 Electrical emergency−lowering 2 x 24 VDC 50
4.2.5 Electrical emergency−lowering 1 x 12 or 1 x 24 VDC (option) 51
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Commissioning/settings 52
4.3.1 Checking the test numbers 52
4.3.2 Checking the minimum static pressure 52
4.3.3 The bypass pressure setting 53
4.3.4 The maximum pressure setting 56
4.3.5 The demand/feedback response difference, SIU−1 56
4.3.6 Speed−monitoring in the door zone, SIU−4 57
4.3.7 The inspection−travel speed setting 57
4.3.8 Positioning the shaft switches for the deceleration distance 58
4.3.9 Required deceleration distance 59
4.3.10 Setting the mechanical null point 60
4.3.11 Pilot filters 61
4.3.12 The pipe−rupture valve test 62
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Operation 65
5.1 Handterminal
5.1.1 Parameter overview 65
5.1.2 Overview of travel curve 66
5.1.3 Overview of control parameters (PID) 66
5.1.4 Description of parameters 67
5.2 Calculating the demand values for maximum speed 79
5.3 Faults / Fault−finding
5.3.1 Check list for fault correction 80
5.3.2 Fault description 84
5.3.3 Code for further details 87
6 Maintenance 89
6.1 Maintenance schedule
6.2 Operating materials and aids
6.3 Installation guide for DOWN pilot valve
6.4 Customer service information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65
80
89
90
91
92
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
300−I−9010212−E−10/08.08
4/92
0 General
0.1 Target group
0.2 Supplementary documents
This guide is an integral part of the product. It describes the product´s safe use in all phases of operation and is valid for all model series that are referred to.
S Operator
S Installer
S Service engineer
S Repair technician
Description Document
Quick−start guide for valve 300−P−9010169
0.3 Specialist terms
Term Definition
C−DELCON Electronic control card for C−LRV valve
300−I−9010212−E−10/08.08
5/92
300−I−9010212−E−10/08.08
6/92
CLRV lift control valve Product description
0
1 Product description
1.1 Important notes
1.1.1 Subassemblies
This guide differentiates between the following subassemblies:
C−LRV lift control valve
C−DELCON electronic control card NTA−2 power supply unit
300−I−9010212−E−10/08.08
7/92
CLRV lift control valve Product description
1.1.2 intended use
Lift control valve for operating hydraulically−driven passenger and goods lifts.
The products must not be handled in any way by unauthorised persons.
1.1.3 Conformity
The product was designed and developed in conformity with the follow­ing standards:
Standards
EMC standards EN 12015
EN 81−2 EC 95/16 BS 5655 Part 2 SIA 370−11
EN 12016 IEC 1000−4
300−I−9010212−E−10/08.08
8/92
CLRV lift control valve Product description
1.2 Product identification
1.2.1 Nameplate
12
C−LRV 175 − 120 / 150 − 21 / 45
R 250 − K 251 / 6−80 / 55 bar
6789
345
1 Valve type = C−LRV 175
2 Flow rate UP = 120l/min
3 Flow rate DOWN = 150l/min
4 Minimum static pressure (empty car)
= 21bar
5 Maximum static pressure (full car)
= 45bar
6 Flow ring = R250
7 Spool = K251
8 Setting range = 6–80 bar
9 Set for maximum working pressure
= 55bar
1.2.2 Test number
2
1
300−I−9010212−E−10/08.08
Legend 12Test number
Nameplate
9/92
CLRV lift control valve Product description
1.2.3 Model code
Valve type/size
= C−LRV 175 = C−LRV 350 = C−LRV 700
Flow range: flow rate/type
C−LRV 175 15–45l/min = R 45
46–90l/min = R 90 91–250l/min = R 250
C−LRV 350 251–500l/min = R 500
C−LRV 700 400–1000l/min = R 1000
R 250 K 251 VN D0////C−LRV 175
Spool: flow rate/type
C−LRV 175 15–90l/min = K 91
91–250l/min = K 251
C−LRV 350 251–500l/min = K 501
C−LRV 700 400–1000l/min = K 1001
Manual emergency−lowering valve
Emergency−lowering valve with preload = VN
C−DELCON type
without C−DELCON = D0 with C−DELCON (SIU 1 + SIU 4) = D1
300−I−9010212−E−10/08.08
10/92
CLRV lift control valve Product description
1.3 C−LRV lift control valve
Legend 1
10
Z1 Z2 Z3
Maximum−pressure setscrew
2
Bypass−pressure setscrew
4
Pressure−relief valve
5
Pilot filter
6
Test point, G½
7
Pressure gauge
8
Pressure gauge shut−off screw
9
Air−bleed screw Feedback sensor
11
Main filter
Pressure switch port Pressure switch port Hand pump port
12
Flow−rate measuring system
13
Emergency−lowering valve
14
DOWN spool
15
Check valve
16
UP spool
17
UP damping jet
18
DOWN damping jet
20
Ball valve
22
Hand pump
P
Pump port
T
Tank port
Z
Cylinder port
D
Control cabinet (customer’s)
300−I−9010212−E−10/08.08
11/92
CLRV lift control valve Product description
1.3.1 Simplified hydraulic–electrical diagram
Legend 4
10
12 13
Z1 Z2 Z3
Pressure−relief valve
6
Test point, G½
7
Pressure gauge
8
Pressure gauge shut−off screw Feedback sensor (non−contacting)
11
Main filter Flow−rate measuring system Emergency−lowering valve
Pressure switch port Pressure switch port Hand pump port
P
Pump port
T
Tank port
Z
Cylinder port
M
14
DOWN spool
15
Check valve
16
UP spool
20
Pipe−rupture valve
21
Ball valve
22
Electrical emergency−lowering valve (optional)
23
Pressure switch
24
Hand pump
R
to EN81−2, 12.4.1/12.4.2
1
R
to EN81−2, 12.4.1/12.4.2
2
A
C−DELCON
B
NTA−2
C
C−LRV
D
Control cabinet (customer’s)
300−I−9010212−E−10/08.08
12/92
CLRV lift control valve Product description
1.3.2 Factory settings
All valves are factory−set to the values for the particular installation and then tested.
S Pressure−relief valve set to the maximum working pressure
S Bypass pressure as per the calculated minimum static pressure
S Mechanical null point of the feedback sensor
S Emergency−lowering valve set to 5−10% of maximum DOWN speed
1.3.3 Description of function
The lift control valve can be subdivided into 3 main functions.
1. Up section / pressure−relief valve
16
1
4
S Initial position:
UP spool (16) is open in the 0 position; pump flow goes directly to tank
S Up travel / acceleration:
UP spool (16) is progressively closed by the electro−proportional valve (UP solenoid); this results in smooth acceleration of the lift up to maximum speed
S Deceleration:
UP spool (16) is progressively opened by the electro−proportional valve (UP solenoid); this results in smooth deceleration of the lift to standstill
S Overload:
pressure−relief valve (4) and UP spool (16) open when the maximum working pressure set with screw (1) is reached
300−I−9010212−E−10/08.08
13/92
CLRV lift control valve Product description
2. DOWN section / emergency−lowering valve
14
13
The down section is constructed in a similar way to the up section. S Initial position:
DOWN spool (14) is closed leak−free in the 0 position
S Down travel / acceleration:
DOWN spool (14) is progressively opened by the electro−proportional valve (DOWN solenoid); this results in smooth acceleration
S Deceleration:
DOWN spool (14) is progressively closed by the electro−proportional valve (DOWN solenoid); this results in smooth deceleration of the lift to standstill
S Power failure / evacuation:
With the electrical emergency−lowering valve (optional), the car can be lowered using DC voltage ( 4.2.4)
S The car can be lowered slowly with the manual emergency−lowering
valve (13)
300−I−9010212−E−10/08.08
14/92
CLRV lift control valve Product description
3. Flow−rate measuring system
10
12
S The oil flows through the flow meter (12) in both the up and down
directions
S The baffle−disc is displaced axially as a function of the flow rate
S This axial displacement is converted by a non−contacting feedback
transducer (10) into an electrical DC signal (the feedback signal), which is then sent to the C−DELCON
S The output signal (the feedback) is proportional to the flow rate
S The controller in the C−DELCON works to match the feedback value
to the demand signal
300−I−9010212−E−10/08.08
15/92
CLRV lift control valve Product description
1.3.4 Technical data
A
H*
L*
R*
Legend 1
Flow−rate measuring system
2
Pressure−relief valve
3
DOWN solenoid
4
UP solenoid
a
300−7−10015573
5 6 7 a View A
300−I−9010212−E−10/08.08
Z1
Pressure switch port
Z2
Pressure switch port
Z3
Hand pump port
P
Pump port
T
Tank port
Z
Cylinder port
Orientation of Z port
(specify when ordering!)
H*
rear (standard)
L*
left
R*
right
16/92
CLRV lift control valve Product description
Type Ports Ports Weight Max. press.
Z, T, P Z1, Z2, Z3 [kg] [bar]
C−LRV 175 G1 8 80
C−LRV 350 G1½ 11 80
C−LRV 700 G2, G2½, G2 G¼, G¼, G3/
8
22.5 67
Type Dimensions [mm]
b c d e k L m n p1 p2 s1 s2 t v1 v2
C−LRV 175 199 325 167 207 50 47 55 175 21 27 75 15 M8 9 23
C−LRV 350 219 355 190 207 65 48 63 200 35 38 85 25 M10 14 28
C−LRV 700 297 428 255 225 80 87 83 265 48 56 124 41 M10 30 30
Type Flow range Spool (K) Viscosity range* Max. oil temperature*
Q [l/min] Ring R Q [l/min.] K [cSt] (mm@/s) [°C]
C−LRV 175
15–45 46–90
91–250
R45 R90
R 250
15−90
91−250
K 91
K 251
30–300 0 ... 60
C−LRV 350 251–500 R500 251–500 K 501 30–300 0 ... 60
C−LRV 700 400–1000 R1000 400–1000 K 1000 30–300 0 ... 60
* Note the viscosity range and minimum oil temperature. For detailed information, see 6.2, page 90
300−I−9010212−E−10/08.08
17/92
CLRV lift control valve Product description
1.3.5 Pressure drop
C−LRV 175
R45
15.0
12.5
10.0
A
7.5
Spool K 91
5.0
2.5
R90
R250
Spool K 251
Flow ring (R)
DOWN (Z−T)
UP (P−Z)
0.0 20 50 90 100 150 180 200 250
B
C−LRV 350
15.0
12.5
10.0
R500
Spool K 501
A
7.5
5.0
2.5
0.0 250 275 300 325 350 375 400 425 450 475 500
Flow ring (R)
DOWN (Z−T)
UP (P−Z)
B
Legend ABPressure drop [bar] Min. required dyn. pressure
Flow rate Q [l/min.]
300 cSt (HLP 46)
75 cSt (HLP 46)
300−I−9010212−E−10/08.08
18/92
CLRV lift control valve Product description
C−LRV 700
15
12.5
10
R1000
Spool K 1001
A
7.5
5
2.5
0
400 450 500 550 600 650 700 750 800 850 900 950 1000
B
Legend ABPressure drop [bar] Min. required dyn. pressure
Flow rate Q [l/min.]
Flow ring (R)
DOWN (Z−T)
UP (P−Z)
300 cSt (HLP 46)
75 cSt (HLP 46)
300−I−9010212−E−10/08.08
19/92
CLRV lift control valve Product description
1.4 C−DELCON electronic card
The C−DELCON controls the oil flow − and therefore the lift’s travel pro­file − in accordance with a preset curve.
Electrostatic discharge (ESD)
The C−DELCON can be damaged by incorrect handling. Always keep the DELCON in its ESD protective bag and only hold it by
the spacer studs (4).
6
Attention
4
3
Legend 1
5
Nameplate
2
Label with Test number
3
Label with description of LED functions
4
Spacer studs M2.5x10
5
Label with Demand values
6
RESET button (restarts the program in the C−DEL­CON electronic card)
1
2
300−2−10012279
1.4.1 Factory settings
300−I−9010212−E−10/08.08
S Maximum UP and DOWN speeds
S Slow speed set to 5−10 % of maximum speed
S Acceleration/deceleration set to mid−range value
S Inspection travel speed set to 50 % of maximum speed
20/92
CLRV lift control valve Product description
1.4.2 Description of function
S The lift control system sends the command signals to the C−DELCON
via potential−free relay contacts or semiconductors (K1−K4)
S The feedback value is compared with the demand travel curve
throughout the whole travel.
S Deviations from the demand curve are corrected by the UP and
DOWN proportional solenoids
S The closed−loop control ensures that the travel characteristics are
independent of load and temperature
S The inspection speed can be set through contact K5 of the lift control
system (there is no SIU−1 monitoring during inspection speed with K5!)
S Reduced speeds for short travel distances are also possible via
K6−K8
S The C−DELCON enables soft−stopping (gentle halt) with very accu-
rate positioning (±3 mm)
Features
S The travel curve for the up and down directions is set and adjusted
with the Handterminal or a PC
S The demand curve can be set and checked at the C−DELCON while
the lift is at standstill
S Measured values can be checked with the Handterminal
S The C−DELCON card is easy to exchange (1 card for all valves),
which means that rapid fault−fixing is ensured
Important: If the C−DELCON is exchanged, the installation−specific parameters must be replicated in the new card.
300−I−9010212−E−10/08.08
21/92
CLRV lift control valve Product description
1.4.3 Technical data
Weight: 150g
General description
300−2−10012279
S Digital electronic card for the C−LRV valve
S Conforms to the European format (100 mm x 160 mm)
S Enhanced ride comfort
S Automatic reduction of demand signal if nominal speed is not at-
tained
S Extended functions
S Simple set−up
S Easy to trouble−shoot
New installations
S Factory settings permanently stored
Replacement cards
S Contain basic settings.
For installation−specific settings, Section 5.1
300−I−9010212−E−10/08.08
22/92
CLRV lift control valve Product description
1.4.4 Travel and switching diagram for normal travel distance
*Y
N
* motor run−on time of 0.5 ... 1s
** Drop−out delay of 0.5 ... 1s
Legend 1
Motor contactor ON
2
Safety relay R2 closed
3
K2 "Slow UP" closed
4
K1 "Fast UP" closed
N Normal distance between floors
Y−Δ Y starting time of up to approx.
3s with Y−Δ, K1 and K2 not until Δ connection
5
K3 "Fast DOWN" closed
6
K4 "Slow DOWN" closed
7
Safety relay R1 closed
**
300−I−9010212−E−10/08.08
23/92
CLRV lift control valve Product description
1.4.5 Travel and switching diagram for short travel distances
The electronics of the C−LRV valve make it possible to control stops at mezzanines and similar short travel distances with the same ride comfort as in normal travel.
Important: The maximum speed should be reduced to a value that, despite the short travel distance, can actually be attained.
Short distance between floors with normal speed (slow−speed travel distance too long)
XZ
N
ZX
K
Short distance between floors with reduced speed (K6)
N
ZY
K
Y **
**
ZY
Motor run−on time of 0.5 ... 1s
*
Drop−out delay of 0.5 ... 1s, after drop out of K4 + K6
**
K2 and K2 not until Δ connection
***
Adjust the speed to suit the circumstances (e.g. 50%)
V
Legend 1
Motor contactor ON
2
Safety relay R2 closed
3
K2 + K6 closed
4
K1 closed
N Normal distance between floors K Short distance between floors
Deceleration switch at normal speed
X
Deceleration switch at reduced speed
Y
Soft−Stop is not separately adjustable
Z
5
K3 closed
6
K4 + K6 closed
7
Safety relay R1 closed
300−I−9010212−E−10/08.08
24/92
CLRV lift control valve Product description
S By using relays K6, K7 or K8, various reductions in the nominal
speed can be achieved (e.g. for different floor spacings)
S The speed reduction can be adjusted between 20–100% of nominal
speed
S Speed can be set by means of parameter "K6 speed" (or "K7 speed" /
"K8 speed") in the Options menu to match the floor spacing (distance between stops)
S Acceleration can be adjusted separately via parameters "K6 acceler-
ation" (or "K7 acceleration" / "K8 acceleration") in the Options menu
S Deceleration can be adjusted separately via parameters "K6 deceler-
ation" (or "K7 deceleration" / "K8 deceleration") in the Options menu
300−I−9010212−E−10/08.08
25/92
CLRV lift control valve Product description
1.5 NTA−2 power supply unit
The NTA−2 power supply unit provides both power supply and physical support for the C−DELCON.
300−1−10008856
Legend 1
Mains voltage terminals
2
Socket for feedback cable
3
Terminal block (screwless)
4
Jumper JP2 (connects Earth and Signal GND)
5
Terminal block for SIU con­nection
6
Terminal block for emergency power supply
7
Jumper JP1 (demand/feed­back monitoring − SIU)
8
Transformer
9
Card−holder
300−I−9010212−E−10/08.08
26/92
CLRV lift control valve Product description
1.5.1 Description
The power supply unit is connected directly to the main supply or the control system supply.
The control signals for the C−DELCON are connected to the terminal block (3).
Through the terminals 18–17a (N.O. make contact)
a relay output is provided.
Its function is defined in the C−DELCON by the settings of the "SIU type" and "Relay function" parameters.
Parameter SIU type"
0Off
1 SIU−1: relay switches when the demand/feedback differ-
4 SIU−4: relay switches when the speed threshold is ex-
1+4 SIU−1 and SIU−4 active, functions as above
18–17b (N.C. break contact)
ence is exceeded (there is no SIU−1 monitoring during in­spection speed with K5 !).
ceeded (e.g. 0.3m/s in the door zone)
Parameter "Relay function"
only SIU
The relay on the power supply unit switches only when there is an SIU fault
all errors
The relay on the power supply unit switches with any fault
JP1 selects the relay’s passive state.
1−2 Current flows through the relay in its passive state (no cur-
rent when function is activated)
2−3 No current through the relay in its passive state (current
flows when function is activated)
We recommend that the safety circuit be switched through an auxiliary contactor.
The jumper JP2 connects the Signal GND to Earth potential (default set­ting).
Important:with Jumper JP2 inserted (Signal GND connected to Earth), then − dependent on the wiring − there is a risk that an earth loop may exist. To prevent earth loops and the associated possible malfunctions, consult the installation circuit drawing.
300−I−9010212−E−10/08.08
27/92
CLRV lift control valve Product description
1.5.2 Technical data
110
100
100
Weight 0.675kg
Mains voltage NTA−2/115 100/(110)115/120VAC
NTA−2/230 220/230/240VAC ±10% NTA−2/400 380/(400)415/440VAC
812
M4
110
151.7
300−1−10008856
Frequency 50/60Hz ±10%
Power consumption 20W during travel,
approx. 8W at standstill
EMC standards EN−50081, EN−50082, EN−50011/22, IEC 1000−4
Protection class IP 00
Relay contacts
l
= 10mA
min
l
max
= 3A
Command present U < 2.5V
Command inputs
Command current 6mA
Command not present U > 10V
300−I−9010212−E−10/08.08
28/92
CLRV lift control valve Product description
1.5.3 Terminal assignments
A B
1234521222312126a76b
19
E
12
20
17b
18
17a
8
91011
12
L1c/L2c
L1b/L2b
L1a/L2a
PE
N/L1
C
D
Legend A
B
C
Terminal Description
Mains Voltage Connection
NTA−2/115 NTA−2/230 NTA−2/400
N/L1 Neutral (N) Neutral (N) Phase (L1)
L1a/L2a* L1b/L2b* L1c/L2c*
Phase (L1): 120V Phase (L1): (110)/115V Phase (L1): 100V
*connect only one of the 3 terminals
PE Earth conductor
Control signals Connection for feedback cable
Mains voltage connection
Phase (L1): 240V Phase (L1): 230V Phase (L1): 220V
DEDemand / feedback monitoring
Emergency power supply
Phase (L2): 440V Phase (L2): 400/(415)V Phase (L2): 380V
300−I−9010212−E−10/08.08
29/92
CLRV lift control valve Product description
Terminal Description
Control signals
1 2
3
4
5
21 22
23
12
12
6a
7
6b
8
K1 Fast UP K2 Slow UP
K3 Fast DOWN
K4 Slow DOWN
K5 Inspection speed
K6 Speed reduction (auxiliary speed) K7 Speed reduction (auxiliary speed)
K8 Speed reduction (auxiliary speed)
Ground/reference potential (GND) for command inputs (K1...K8)
Ground/reference potential (GND) for command inputs (K1...K8)
Common, DOWN solenoid Output, DOWN solenoid
Common, UP solenoid
Output, UP solenoid
Demand / feedback monitoring
17a
18
SIU−1 (demand/feedback monitoring), SIU−4 (v ≤0.3m/s) 1.5.1
17b
Connection for feedback cable
9 10
11
12
Emergency power supply
19 12
20
Stabilised voltage supply +15V Feedback signal (input)
Stabilised voltage supply −15V
Ground, Hall−effect sensor (GND)
+24V emergency power supply Ground, emergency power supply (GND)
−24V emergency power supply
300−I−9010212−E−10/08.08
30/92
CLRV lift control valve Product description
1.6 IWK−1 feedback cable
Important: The feedback cable must be run from the lift control valve
directly to the NTA−2 power supply unit without any intermediate ter­minals. Any discontinuity in the feedback cable (break, kink, etc.) can endanger trouble−free operation.
It is essential that connection 2 is ground−bonded to terminal 12, other­wise the null point of the sensor will not be stable.
If you cut the cable to length and terminate it yourself, be sure to wire it correctly in accordance with the following diagram:
Legend A
Colours IKBrown
Line socket with PG7 gland
B
NTA−2 connector
C
WAGO plug
D
Screen
Green
E
Supply +15V
F
Signal 0...±13.4V
G
Supply −15V
H
Ground
LMWhite
Yellow
300−I−9010212−E−10/08.08
31/92
CLRV lift control valve Product description
1.7 Surroundings
For reliable operation, the following conditions must be maintained in the surroundings:
Surroundings Requirement
Machine room tempera­ture
Oil temperature 260°C
Relative air humidity max. 90% (non−condensing)
240°C
1.8 Emissions
The following emissions can occur during operation:
Emission Corrective action / Note
Heat Ensure fresh−air supply and warm−air extraction
Noise Sound−proof the entrance to lift shaft (noise transmission)
300−I−9010212−E−10/08.08
32/92
CLRV lift control valve Safety information
2 Safety information
It is essential to take note of the important safety information contained in this document (guide).
Denotes a potentially harmful situation. If it is not prevented, the pro­duct or its surroundings may be damaged.
Denotes a potentially dangerous situation. If it is not prevented, it may result in slight or minor injuries to people.
Attention
Caution
Warning
Denotes a potentially dangerous situation. If it is not prevented, it may result in death or serious injuries to people.
Danger
This denotes a directly imminent danger. If it is not attended to, it will result in death or serious injuries to people.
300−I−9010212−E−10/08.08
33/92
CLRV lift control valve Safety information
300−I−9010212−E−10/08.08
34/92
CLRV lift control valve Operating controls and indicators
3 Operating controls and indicators
It. Description Tools
1 Maximum−pressure setscrew
(Screw À)
2 Bypass−pressure setscrew
(Screw Á)
1 x open−ended spanner, 13 A/Fmm Allen key, 4mm A/F
Open−ended spanner, 10 A/Fmm Allen key, 5mm A/F
8 Pressure gauge shut−off screw Allen key, 4mm A/F
9 Filter screw, UP Open−ended spanner, 22 A/Fmm
10 UP solenoid Allen key, 3mm A/F
11 DOWN solenoid Allen key, 3mm A/F
12 Filter screw, DOWN Open−ended spanner, 22 A/Fmm
13 Pilot plate Allen key, 6mm A/F
14 Adjusting/clamp screw for Hall sensor / mech.
Allen key, 3mm A/F
null point
300−7−10012261
300−I−9010212−E−10/08.08
35/92
CLRV lift control valve Operating controls and indicators
3.1 Emergency−lowering valve
Pressing lever = lowering the car The car is lowered by pressing the lever of the emergency−lowering
valve.
Important: The minimum preload pressure of 6–10 bar continues to exist (prevents slack−rope build−up as per EN 81−2)
Danger
Car descent
People may suffer injury and materials may be damaged.
Before operating the emergency−lowering valve, make sure that there are no people or materials in the lift shaft.
3.2 Display of the operating status
Legend for the LEDs
1 RUN
Ready for operation (green). Lights when ready for travel; off during parameterisation
2UP
UP travel (yellow). Lights during upwards travel (fast and slow)
3 DOWN
DOWN travel (yellow). Lights during downwards travel (fast and slow)
4 ERROR
Fault indication (red). Lights when a fault has occurred; no travel is possible
5 SIU−1
SIU−1 display (yellow). Lights when demand/feedback difference is exceeded
6 RELAY
Relay display (yellow). Lights when relay on power supply unit is open
300−I−9010212−E−10/08.08
36/92
CLRV lift control valve Operating controls and indicators
3.3 Handterminal
General description
Keys
1 Demand values menu 2 Options menu 3 Null point display 4 Menu − Information
Steps to previous parameter Steps to next parameter
+ Increases the value of the
current parameter
Decreases the value of the current parameter
S Easy set−up of the travel curve
S Command, feedback value and control voltage are displayed during
travel
S Null−point adjustment
S Fault memory can be called up
Connection
S Connect the Handterminal to the C−DELCON using the cable
provided
S Connecting cable is standard Ethernet network cable
300−I−9010212−E−10/08.08
37/92
CLRV lift control valve Operating controls and indicators
Description of function
S By pressing any of the keys 1 to 4, the C−DELCON switches into
parameterisation mode. No travel is possible; the green RUN LED on the C−DELCON goes out
S Select the desired parameter using the or key
S Increase value with + key, decrease value with − key S With or key, save the value and return to parameter selection
S With keys 1, 2, 3 or 4, do not save the value and return to parameter-
isation mode
S If no key pressed within 5 minutes, the DELCON automatically quits
parameterisation mode (changes to the currently displayed parameter are not saved)
Important: In order to quit parameterisation mode: S either press keys ↑ and simultaneously (changes to the cur-
rently displayed parameter are saved)
or S unplug cable and wait for about 3 seconds (changes to the cur-
rently displayed parameter are NOT saved)
C−DELCON will return to RUN mode.
300−I−9010212−E−10/08.08
38/92
CLRV lift control valve Operating controls and indicators
Password
The C−DELCON’s parameters and functions can be password−protected. The password consists of four numbers. Password 0000" means that password protection is not activated (this is the factory setting).
The password is entered one number at a time:
S Increase the value with the + key, decrease it with the − key S With or key, change to the adjacent number S Press and keys simultaneously to save the number
If a password has been set, the user must login in order to change para­meters. The user logs in by entering the password. The user can logout at any time, but will be logged out automatically after 8 hours at the latest.
Important: If an attempt is made to change a password−protected para­meter, the message not allowed" is displayed.
Important: If the power supply unit is wired into the safety circuit, the user is not logged out automatically
300−I−9010212−E−10/08.08
39/92
CLRV lift control valve Operating controls and indicators
e.g.
K1−K8 1100 0000 C: +3.45 F: +4.18
e.g.
Fast speed ^
7.50 V
e.g.
1) Err:SIU−1 1x 51965 h
Display during travel
S 1st line: status of command inputs K1 to K8
0: no command 1: command is present
S 2nd line: existing control voltage (C) and
feedback value (F) in volts
Display during parameterisation
S 1st line: parameter name
S 2nd line: value of parameter, including unit
Fault code
S 1st line: fault memory read−out, fault
description
S 2nd line:total number of occurrences of this
fault; last occurrence was at operating hours h
300−I−9010212−E−10/08.08
40/92
CLRV lift control valve Operating controls and indicators
3.4 WinDelta32 − PC program
Software, adapter and cable can be ordered as Part No. 7010867 The software can be downloaded free of charge from: http://www.bucherhydraulics.com
3.4.1 General description
Parameterisation
S C−DELCON parameters can be read off and set via PC
S Parameter sets can be saved
S Comments can be added to parameter sets
S Print function
Display of curves
S Curves (demand signal / feedback value / control voltage) displayed
in real time
S Display of commands K1−K8
S Zoom function / Print function
300−I−9010212−E−10/08.08
41/92
CLRV lift control valve Operating controls and indicators
3.4.2 PC requirements
S Operating system:
Windows 95/98/ME/NT/2000/XP/Vista
S Processor: 133 MHz or faster
S RAM: 32 MByte
S Free hard disc space: min. 10 MByte for the program and min. 5
MByte for saving curves
S Serial port (RS232, 19200 Baud)
3.4.3 Installation on PC / Laptop
Important: Please read the following installation instructions carefully
and follow the recommended steps!
If an old version of WinDelta32 is already installed on your computer, carry out the following steps before installing the new version:
1. Start the old version of WinDelta32
2. In the Options/Configuration menu, open the Serial Port page
I Note the COM port displayed to the right of Default (e.g. COM1).
If you want to keep the parameter sets stored with the old version of WinDelta32:
3. Select the menu Parameters/LRV and export all existing parameter sets (click Export => All parameter sets). Save the file to the folder C:\Temp (for example under the name Para_LRV.prm).
4. Close the window
5. Select the menu Parameters/VF−LRV and export all existing para­meter sets (click Export => All parameter sets). Save the file to the folder C:\Temp (for example under the name Para_VFLRV.prm).
6. Close the window
300−I−9010212−E−10/08.08
42/92
CLRV lift control valve Operating controls and indicators
Removing the old version:
7. Exit and close all programmes
8. Remove the old version of WinDelta32 (refer to the Windows help for information about how to remove a programme)
Installing the new version (the following steps may take a few minutes):
1. Navigate to the installation file Install_WinDelta32_1pXX_EN.exe (XX = programme version) either by clicking the Windows Start but- ton and selecting Run then Browse, or by using the Windows Ex­plorer
2. Double−click the installation file Install_WinDelta32_1pXX_EN.exe . After a few moments, an installation dialog will be displayed.
3. Click the button Next (or Install / Finish) until the installation is ter­minated. A shortcut will automatically be placed on the desktop.
Configuring WinDelta32:
1. Start the new programme
2. To determine the serial port used for data communication between the WinDelta32 programme (PC) and DELCON (electronics card), in the menu Options / Configuration, call up the Serial Port page, select the port you wrote down or a port from the list of available ports and check the box Default in order to store the current set­tings.
3. Open the window Curves / Collect. If the temporary file Data- File.dat includes more than 200 curves, these curves will be saved automatically to a file named YYMMDDHHMM.dat (with YY=Year / MM=Month / DD=Day / HH=Hour / MM=Minute) and a new empty file will be opened.
300−I−9010212−E−10/08.08
43/92
CLRV lift control valve Operating controls and indicators
If you wish to reuse the parameter sets that you previously exported:
1. Select the menu Parameters/LRV and import (click Import => All parameter sets) the stored file (e.g. the file Para_LRV.prm from the folder C:\Temp)
2. Click the button (Refresh data)
3. Close the window
4. Select the menu Parameters/VF−LRV and import (click Import => All parameter sets) the stored file (e.g. the file Para_VFLRV.prm from the folder C:\Temp)
5. Click the button (Refresh data)
6. Close the window
Important: Refer to the integrated on−line help (Menu Help / Contents and Index / Contents / WinDelta32 / Settings) for further information
about settings.
300−I−9010212−E−10/08.08
44/92
CLRV lift control valve Operating controls and indicators
3.4.4 Connect DELCON to PC / Laptop
Possibilities for connecting DELCON to PC / Laptop
Never connect DELCON to an Ethernet port!
300−I−9010212−E−10/08.08
45/92
CLRV lift control valve Operating controls and indicators
Connecting to serial port using Bucher adaptor
Connecting to USB port using a USB−RS232 converter (with Bucher adaptor)
300−I−9010212−E−10/08.08
46/92
CLRV lift control valve Installation and commissioning
4 Installation and commissioning
4.1 Installation
Orientation of the ball−valve outlet
As standard, the ball−valve outlet is rear−facing (code H) Alteration to left (L) or right (R) is possible.
Important: the ball−valve outlet must not be turned to a new position unless the hose is first disconnected.
Reorienting the ball−valve outlet
1. Unscrew cap screws on head of valve
2. Remove the screws
Attention
Risk of damage to the flow−rate
When orienting the ball−valve outlet, never lift up the head of the valve.
3. Turn head of valve to desired ball−valve position
4. Insert the cap screws and tighten them.
I Tightening torque for C−LRV 175 = 25 Nm
C−LRV 350 = 50 Nm C−LRV 700 = 80 Nm
5. Check the mechanical null point
I Readjustment may be necessary (see Page 60, Section 4.3.10)
The ball−valve outlet is now correctly oriented
300−I−9010212−E−10/08.08
47/92
CLRV lift control valve Installation and commissioning
4.2 Assembly
4.2.1 Hose or pipe
Contamination in the line
Contamination adversely affects the valve’s function. This can lead to a dangerous system condition.
Preventive measures:
S Clean the hose or pipe before fitting it S Leave sealing caps/plugs in place until assembly
S Check that all fittings are assembled correctly
4.2.2 Power supply unit
Caution
Feedback cable Page 31
Terminals X3
1
300−1−10009293
Danger
Dangerous voltage
Can cause serious injuries or death. Before fitting the power supply unit, disconnect all power to the control
cabinet.
S The NTA−2 power supply unit must be installed in the control system
cabinet
S There must be no voltage at the power supply unit when working on
its connections or exchanging the C−DELCON.
Important: Set jumper JP2 to connect earth and signal−GND.
Screwless terminals
Feedback cable plug
2
1
2
S Quick to wire up, thanks to screwless terminals S Only one core per terminal point (if neces−sary,
combine two cores in a terminating sleeve)
S Insert a screwdriver as far as the stop (1)
S Open the clamp spring by gently pressing down
or turning the screwdriver, and insert the core (2) into the terminal point
S Remove the screwdriver − the conductor is now
safely clamped
S Use a size 0 screwdriver (2.5 mm)
300−I−9010212−E−10/08.08
Important: to prevent damage, the NTA−2 must only be wired when the C−DELCON card has been removed.
48/92
CLRV lift control valve Installation and commissioning
4.2.3 Wiring the power supply unit
Legend
1
Fast UP
2
Slow UP
3
Fast DOWN
4
Slow DOWN
5
Inspection speed
21
Speed reduction
22
Speed reduction
23
Speed reduction
6a/6b
Common
7
DOWN solenoid
8
UP solenoid
9
Stabilised voltage supply +15V
10
Feedback signal (input)
11
Stabilised voltage supply
−15V
12
GND, test/measurement
20
−24 V emergency power supply
19
+24 V emergency power supply
* When contact K5 closes, the C−DELCON’s two "fast"
speeds drop to a preset percentage of their nominal values. The setting is adjustable between 20−80%
Legend A
300−I−9010212−E−10/08.08
C−DELCON
B
NTA−2
C
C−LRV
D
Control cabinet (customer’s)
300−1−10009300
** When contacts K6, K7 or K8 close, the C−DELCON´s
two "fast" speeds drop to a preset percentage of their n ominal values. The settings are adjustable between 20−100%
K1−K8, potential−free contacts or semiconductors
R1+R2 as per EN81−2, 12.4.1/12.4.2
E
DOWN solenoid
F
UP solenoid
G
SIU−1 demand/feedback moni­toring SIU−4 v ≤0.3m/s
49/92
CLRV lift control valve Installation and commissioning
4.2.4 Electrical emergency−lowering 2 x 24 VDC
Important: the operator must undertake any further measures required
to ensure short−circuit and overvoltage protection.
If a mains (line) failure occurs, the power supply unit can be powered by an external battery supply (2 x 24 V) through terminals 12, 19 and 20.
S Relay R
mally−closed contacts R
I Inputs 19 and 20 have diode−protection from polarity reversal or feed-
S The lift can be lowered to a predefined stopping position by means of
"Slow DOWN" or auxiliary speed K6...K8 (travel signals are gener­ated by the lift control system).
Important: only possible with 2 x 24V (or 4 x 12V) batteries
drops out when there is a power failure and the two nor-
N
back to the battery
−1
N
and R
−2
connect to the battery
N
Slow DOWN Auxiliary speed
K6/K7/K8
Legend 1 NTA−2 power supply unit
2 Supplied by customer
3 DOWN solenoid
21/22/23
300−I−9010212−E−10/08.08
50/92
CLRV lift control valve Installation and commissioning
4.2.5 Electrical emergency−lowering 1 x 12 or 1 x 24 VDC (option)
Do not activate the electrical emergency−lowering valve unless the safety circuit is closed!
In an emergency the lift car can be lowered by operating the emergency lowering valve electrically.
Depending on the external battery voltage, 12V and 24V spool valve versions are available.
Wiring diagram
Warning
12 / 24 VDC
Setting the lowering speed
1. Energize emergency−lowering valve (1)
I The car sinks
2. Slacken locknut
3. Turn adjusting screw (2) counterclockwise (faster) or clockwise (slower)
4. Re−tighten locknut
2
1
300−I−9010212−E−10/08.08
Legend 1 Electrical emergency−lowering valve
2 Adjusting screw
51/92
CLRV lift control valve Installation and commissioning
4.3 Commissioning/settings
4.3.1 Checking the test numbers
S The valve test number is stamped on the body (below the manual
emergency−lowering valve) 1.2.2.
S The C−DELCON test number is on a label on the connector ⇒ 1.4.
Important: always quote the test number when making enquiries. This makes it easier for the factory to help you!
Important: the test numbers on the C−DELCON and the valve must be the same to avoid the need for resetting.
4.3.2 Checking the minimum static pressure
To check the minimum static pressure (with empty car):
1. Open pressure gauge shut−off valve
2. Read the minimum static pressure on the pressure gauge
3. Compare minimum static pressure on rating plate with actual minimum static system pressure on the pressure gauge
I ⇒ Page 9, Section 1.2.1, Item (4)
4. If the difference is more than 5bar, the maximum pressure setting must be increased by the amount of the difference ( 4.3.4)
I Bypass pressure too high: car travels past landing
I Bypass pressure too low: UP starting jolt
The minimum static pressure shown is correct
Important: if the difference is more than > 10bar, please contact
Customer Services.
300−I−9010212−E−10/08.08
52/92
CLRV lift control valve Installation and commissioning
4.3.3 The bypass pressure setting
Important: the car must be empty
Setting the bypass pressure with the Handterminal (car out of sight)
1. Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting I Page 71, Section 5.1.4.2
2. Remove the UP solenoid plug (10)
3. Slacken the locknut for bypass−pressure setscrew (2)
4. Unscrew bypass−pressure setscrew (2) approx. 2 turns counterclockwise
5. Connect the Handterminal to the C−DELCON and press key 3 on Handterminal => null point or feedback value will be displayed
6. Send UP command
7. With motor running, slowly turn bypass−pressure setscrew (2) clockwise until feedback value rises (visible on the Handterminal display)
8. Turn bypass−pressure setscrew (2) back by half a turn counterclockwise
9. Tighten the locknut for bypass−pressure setscrew (2)
10. Cancel the UP command
11. Refit the UP solenoid plug (10)
12. Reset the "SIU Type" parameter in the C−DELCON to the setting noted down in Step 1.
The bypass pressure is now set
300−I−9010212−E−10/08.08
53/92
CLRV lift control valve Installation and commissioning
Setting the bypass pressure with a pressure gauge (car out of sight)
1. Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting I Page 71, Section 5.1.4.2
2. Read the minimum static pressure on the pressure gauge
3. Close the ball valve
4. Press emergency−lowering lever (vents pressure in the valve)
I ⇒ Page 36, Section 3.1
5. Remove the UP solenoid plug (10)
6. Slacken the locknut for bypass−pressure setscrew (2)
7. Unscrew bypass−pressure setscrew (2) approx. 2 turns counterclockwise
8. Send UP command
9. With motor running, slowly turn bypass−pressure setscrew (2) clockwise until pressure is approx. 3bar below the min. static pressure previously read
10. Tighten the locknut for bypass−pressure setscrew (2)
11. Cancel the UP command
12. Refit the UP solenoid plug (10)
13. Open the ball valve.
14. Reset the "SIU Type" parameter in the C−DELCON to the setting noted down in Step 1.
The bypass pressure is now set
300−I−9010212−E−10/08.08
54/92
CLRV lift control valve Installation and commissioning
Setting the bypass pressure with the car in sight
1. Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting I Page 71, Section 5.1.4.2
2. Remove the UP solenoid plug (10)
3. Slacken the locknut for bypass−pressure setscrew (2)
4. Unscrew bypass−pressure setscrew (2) approx. 2 turns counterclockwise
5. Send UP command
6. With motor running, slowly turn bypass−pressure setscrew (2) clockwise until the car moves
7. Turn bypass−pressure setscrew (2) half a turn counterclockwise
8. Tighten the locknut for bypass−pressure setscrew (2)
9. Cancel the UP command
10. Refit the UP solenoid plug (10)
11. Reset the "SIU Type" parameter in the C−DELCON to the setting noted down in Step 1.
The bypass pressure is now set
300−I−9010212−E−10/08.08
55/92
CLRV lift control valve Installation and commissioning
4.3.4 The maximum pressure setting
Adjusting the maximum pressure
1. Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting I Page 71, Section 5.1.4.2
2. Close the ball valve
3. Press emergency−lowering lever
4. Slacken the locknut for screw (1)
5. Turn screw (1) approx. 2 turns counterclockwise
6. Bypass the overload pressure switch (DZ)
7. Send UP command
8. Slowly turn screw (1) clockwise until calculated pressure is reached
9. Tighten locknut for screw (1)
10. Cancel the UP command
11. Write new settings on the existing rating plate (overwrite old values)
I ⇒ Page 9, Section 1.2.1, Item (5)
12. Remove the bypass from the overload pressure switch (DZ)
13. Open the ball valve.
14. Reset the "SIU Type" parameter in the C−DELCON to the setting noted down in Step 1.
The maximum pressure has been adjusted for the new situation
4.3.5 The demand/feedback response difference, SIU−1
SIU−1: if the value of the demand/feedback difference becomes too large, the lift is stopped
S When the demand/feedback difference is exceeded, the LED on the
C−DELCON lights and the relay activates
S The response difference can be set with the Handterminal or PC
software
300−I−9010212−E−10/08.08
56/92
CLRV lift control valve Installation and commissioning
4.3.6 Speed−monitoring in the door zone, SIU−4
The SIU−4 function monitors the speed in the door zone and during relevelling. If the speed setting is exceeded, the lift is stopped (per EN 81−2, max. 0.3 m/s)
S When the speed setting is exceeded, the relay activates
S The speed can be set with the Handterminal or PC software
4.3.7 The inspection−travel speed setting
To set the inspection−travel speed, see the Options menu 5.1.4.2, the parameter "Inspection speed".
300−I−9010212−E−10/08.08
57/92
CLRV lift control valve Installation and commissioning
4.3.8 Positioning the shaft switches for the deceleration distance
The spacing of the shaft switches depends on the car speed 4.3.9
Z
ZY
X
Time t
YZ
ZX
Aux. speed e.g.
v=50%
v=100% v=100%
v=50%
X Deceleration distance (shaft switches) for maximum speed
Y Deceleration distance (shaft switches) for auxiliary speed (for example, 50% of
maximum speed; adjustable in C−DELCON from 20–100%)
Z Stop−switch before landing (20–30mm) (soft−stop travel is controlled by the
C−DELCON)
300−I−9010212−E−10/08.08
58/92
CLRV lift control valve Installation and commissioning
4.3.9 Required deceleration distance
Guidelines for positioning the deceleration switches.
Examples 1 Deceleration distance "X" for direct (1:1) drive
e.g.: v=0.4m/s → x1=0.4m
2 Deceleration distance "X" for indirect (2:1) drive
e.g.: v=0.63m/s → x2=0.71m
3 Deceleration distance "Y" for direct (1:1) drive (auxiliary speed)
e.g.: v=0.4m/s : 2 = 0.2m/s → y3=0.2m
4 Deceleration distance "Y" for indirect (2:1) drive (auxiliary speed)
e.g.: v=0.63 m/s : 2 → y4=0.32 m
Legend A
Direct drive (1:1)
B
Indirect drive (2:1)
C
Car speed [m/s]
D
Distance of deceleration switches before landing [m]
300−I−9010212−E−10/08.08
59/92
CLRV lift control valve Installation and commissioning
4.3.10 Setting the mechanical null point
The null point is factory−set.
With Handterminal, see Page 37, Section 3.3
This can be checked with the Handterminal (or PC). If, on commission­ing, the reading is outside the range ±0.05V, then the null point must be reset.
Setting the null point
1. Close the ball valve
2. Connect the Handterminal to the C−DELCON and press key 3 on Handterminal => null point or feedback value will be displayed
3. Using a 3mm Allen key, slacken the adjusting/clamp screw (14) a little
4. Remove Allen key (it has a magnetic influence)
5. Hold the feedback sensor by the plug and move it axially until the feedback reading is less than ±0.05V
6. Tighten adjusting/clamp screw (14)
7. Return to RUN mode by pressing the and on the Handterminal simultaneously.
8. Open the ball valve.
The null point is now correctly set
Checking null point after maintenance work
The error memory of the C−DELCON should be checked each time maintenance work is carried out. If there is a warning with regard to null­point deviation or, if the actual value for the null point is outside the range ±0.2V, then the null point has to be reset.
300−I−9010212−E−10/08.08
60/92
CLRV lift control valve Installation and commissioning
4.3.11 Pilot filters
Filter−strainers are positioned upstream of the lowering and lifting valves in accordance with the international standards for lifts. The filters are easily accessible from outside the valve.
Contamination in valve (filter)
This can cause leakage. Never operate the lift without the pilot filter installed.
Carry out regular maintenance as per maintenance plan Page 89
Cleaning the pilot filter
1. Switch main switch OFF
2. Close the ball valve
3. Press emergency−lowering lever (vents pressure in the valve)
I the pressure in the valve is vented
Caution
Note the maintenance plan on Page 89
4. Unscrew the filter screw
I with a 22 A/F open−ended spanner
5. Remove filter
6. Clean or exchange the filter
7. Insert the filter
8. Screw in the filter screw
9. Open the ball valve.
10. Switch main switch ON
The pilot filter is now clean
300−I−9010212−E−10/08.08
61/92
CLRV lift control valve Installation and commissioning
4.3.12 The pipe−rupture valve test
A precondition for testing the pipe−rupture valve is that the lift must be working properly, without any faults.
Uncontrolled descent (free fall)
People may suffer injury and materials may be damaged. Before testing the pipe−rupture valve, make sure that there are no
people or materials in the lift shaft.
Uncontrolled descent (free fall)
Can cause damage to the support frame and car. The elevator car must come to rest within 3 ... 5 metres.
If it does not, immediately switch off the main switch for the lift control system (and repeat the test).
Danger
Attention
Preparing to test the pipe rupture valve
1. Load the car to half of its rated capacity
2. Drive the car to the top floor
Important: do not carry out the test if the car is too close to the lowest floor.
3. Prepare the handterminal or an computer with WinDelta32
300−I−9010212−E−10/08.08
62/92
CLRV lift control valve Installation and commissioning
Testing the pipe−rupture valve (for C−DELCON software version
2.110 or higher)
1. On the Handterminal, select the Pipe rupture" function in the In­formation (4) menu under Commands"
I ⇒ Page 76, Section 5.1.4.4
2. Press and hold the + key on the Handterminal; the "DOWN" LED on the C−DELCON will start to flash
3. Send DOWN command
4. Wait until the car is accelerating
5. When the triggering speed is reached, the pipe rupture valve closes and travel stops.
Important: Releasing the + key on the Handterminal stops the travel, and the maximum feedback value is displayed. If the DOWN command is still present on quitting the menu, travel will resume normally.
Important: after the pipe rupture valve has closed, pressure can again build up between the C−LRV and the pipe−rupture valve, causing the pipe−rupture valve to re−open. If the pipe rupture valve is to remain closed for a long period, this pressure must be vented through the man­ual emergency−lowering valve on the C−LRV. If the hose/pipe is actually burst, the pipe−rupture valve will always remain closed. Very slight leakage through the pipe−rupture valve is permissible.
The pipe−rupture valve has been successfully tested
6. In order that the pipe rupture valve re−opens and the elevator is ready for service: build up pressure using the hand pump or carry out an upwards travel.
The system is once again ready for use
300−I−9010212−E−10/08.08
63/92
CLRV lift control valve Installation and commissioning
Testing the pipe−rupture valve (up to C−DELCON software version
2.100 or with WinDelta32 PC program)
1. Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting I Page 71, Section 5.1.4.2
2. Set the "Demand val. red." parameter in the C−DELCON to "Off"
I make a note of the existing setting I Page 71, Section 5.1.4.2
3. Send a "Down" command to the controller
4. Wait until the car is accelerating
5. Remove the feedback plug (25) from the Hall sensor
6. When the triggering speed is reached, the pipe rupture valve closes and travel stops.
Important: after the pipe rupture valve has closed, pressure can again build up between the C−LRV and the pipe−rupture valve, causing the pipe−rupture valve to re−open. If the pipe rupture valve is to remain closed for a long period, this pressure must be vented through the manual emergency−lowering valve on the C−LRV. If the hose/pipe is actually burst, the pipe−rupture valve will always remain closed. Very slight leakage through the pipe−rupture valve is permissible.
The pipe−rupture valve has been successfully tested
7. Cancel the DOWN command
8. Refit the feedback plug (25) to the Hall sensor
9. Reset the "SIU Type" parameter in the C−DELCON to the setting noted down in Step1.
10. Reset the "Demand val. red" parameter in the C−DELCON to the setting noted down in Step 2.
11. In order that the pipe rupture valve re−opens and the elevator is ready for service: build up pressure using the hand pump or carry out an upwards travel.
300−I−9010212−E−10/08.08
The system is once again ready for use
64/92
CLRV lift control valve Operation
5 Operation
5.1 Handterminal
5.1.1 Parameter overview
Handterminal
Demand values (1)
5.1.4.1
Demand
values UP
− Start speed − Start speed − Valve type − Null point − Language/Sprache − 1) Error
− Min. pressure − Offset sol. − SIU type − Load parameter − 2) Error
− Acceleration − Acceleration − SIU−1 difference − Save parameter − 3) Error
− Fast speed − Fast speed − SIU−4 threshold − Password − 4) Error
− Deceleration − Deceleration − Accel. Inspection − Delete errors − 5) Error
− Slow speed − Slow speed − Inspection speed − Pipe rupture − 6) Error
− Soft−stop − Soft−stop − Decel. inspection − 7) Error
− Relevelling − Relevelling − K6 acceleration − 8) Error
− P sol. static − P sol. static − K6 speed − Software version
− I sol. static − I sol. static − K6 deceleration − Hardware version
− D sol. − D sol. − K7 acceleration − Serial number
− P sol. dynamic − P sol. dynamic − K7 speed − Check number
− I sol. dynamic − I sol. dynamic − K7 deceleration − Power on
− Calibr. factor − Calibr. factor − K8 acceleration − Drive up
Demand
values DOWN
Options (2)
5.1.4.2
Hall sensor (3)
5.1.4.3
Informationen (4)
5.1.4.4
Commands Information list
− K8 speed − Drive down
− K8 deceleration − Operation hour
− Decel. emergency − + unstab voltage
− Pulsation sol. − − unstab voltage
− Demand val. red.
− Start delay
− Relay function
− Command input
− Auxiliary curve
300−I−9010212−E−10/08.08
65/92
CLRV lift control valve Operation
5.1.2 Overview of travel curve
Legend 1
5.1.3 Overview of control parameters (PID)
Dynamic
P sol. dynamic I sol. dynamic D sol
Start speed
2
Acceleration
3
Fast speed
4
Deceleration
5
Slow speed
6
Soft−Stop (steepness)
7
Minimum pressure / offset sol.
Static
P sol. static I sol. static D sol
89Demand signal
Control voltage (prop. sol.)
Dynamic
P sol. dynamic I sol. dynamic D sol
300−I−9010212−E−10/08.08
66/92
CLRV lift control valve Operation
5.1.4 Description of parameters
5.1.4.1 Demand values Up / Down (1)
Setting "Start speed"
S Higher value: faster starting speed, shorter starting time, harsher
start−up jolt
S Setting range: 0.05–0.50V
S Standard: 0.30V
Important: low settings for "Start speed" may cause long starting times
Setting "Min. pressure" (UP)
S Operative during Up travel
S Higher value: higher solenoid starting voltage, shorter starting time
S Setting range: 5.0–100.0bar
S Standard: 20.0bar
Important: high settings may cause a start−up jerk.
Setting "Offset sol." (DOWN)
S Operative during Down travel
S Higher value: higher solenoid starting voltage, shorter starting time
S Setting range: 1.00–7.00V
S Standard: 4.00V
Important: high settings may cause a start−up jerk.
Setting "Acceleration"
S Higher value: greater acceleration, i.e. shorter acceleration distance
S Setting range: 0.30–5.00V/s
S Standard: 2.00V/s
300−I−9010212−E−10/08.08
67/92
CLRV lift control valve Operation
Setting "Fast speed"
S Higher value: faster travel speed
S Setting range: 1.00–10.00V
S Standard: 7.00V S Example of litres <=> volts conversion, Page 79
Setting "Deceleration"
S Higher value: greater deceleration, i.e. shorter deceleration distance
S Setting range: 0.30–5.00V/s
S Standard: 3.00V/s
Setting "Slow speed"
S Operative after fast travel
S Higher value: faster travel speed
S Setting range: 0.20–2.50V
S Standard: 0.40V
Important: low settings for "Slow speed" may cause slow travel to be uneven due to static friction in the cylinder and car guides
Important: low settings for "Slow speed" and "Soft−Stop" may cause slight variations in levelling accuracy.
Setting "Soft−Stop"
S Higher value: greater deceleration, i.e. shorter stopping distance,
harsher stopping jolt
S Setting range: 0.20–5.00V/s
S Standard: 1.00V/s
S To disable : set to 5.00V/s
Important: low settings for "Slow speed" and "Soft−Stop" may cause slight variations in levelling accuracy.
300−I−9010212−E−10/08.08
68/92
CLRV lift control valve Operation
Setting "Relevelling"
S Operative during fine adjustment
S Higher value: faster travel speed
S Setting range: 0.20–1.50V
S Standard: 0.40V
Important: low settings for "Relevelling" may cause slow travel to be uneven due to static friction in the cylinder and car guides
Important: low settings for "Relevelling" and "Soft−Stop" may cause slight variations in levelling accuracy.
Setting "P sol. static"
S Operative in steady−state control processes (constant−speed travel)
S Higher value: higher solenoid control gain
S Setting range: 0.20–1.50
S Standard: UP 0.80
DOWN 0.70
Important: high settings may cause oscillations.
Setting "I sol. static"
S Operative in steady−state control processes (constant−speed travel)
S Higher value: longer solenoid reset time
S Setting range: 100–1000ms
S Standard: UP 900ms
DOWN 700ms
Important: low settings may cause oscillations.
Setting "D sol."
S Higher value: longer solenoid derivative time
S Setting range: 0–100ms
S Standard: 20ms
S To disable, set to: 0ms
Important: high settings may cause oscillations.
300−I−9010212−E−10/08.08
69/92
CLRV lift control valve Operation
Setting "P sol. dynamic"
S Operative in dynamic control processes (acceleration, deceleration)
S Higher value: higher solenoid control gain
S Setting range: 0.20–1.50
S Standard: UP 0.80
Important: high settings may cause oscillations.
Setting "I sol. dynamic"
S Operative in dynamic control processes (acceleration, deceleration)
S Higher value: longer solenoid reset time, greater control error in
dynamic processes
S Setting range: 100–1000ms
S Standard: UP 450ms
DOWN 0.70
DOWN 350ms
Important: low settings may cause oscillations.
Setting "Calibr. factor"
S Valve calibration (feedback)
S Setting range: 0.90 − 1.30
S Standard: 1.00
300−I−9010212−E−10/08.08
70/92
CLRV lift control valve Operation
5.1.4.2 Options menu (2)
Setting "Valve type"
S Selection of valve type
S Overwrites the current control parameters (PID) with the factory
settings for this valve
S Setting range:
− C−LRV 175
− C−LRV 350
− C−LRV 700
Setting "SIU type"
S Off: monitoring is switched off
S 1: SIU−1, if the setting for the demand/feedback difference is
exceeded, then:
− Lift is stopped with emergency−stop deceleration
− The relay switches 1.5.1
− LED SIU−1 lights
− If the Relay function" setting is only SIU": reset operation after there is no longer any travel command. Otherwise: delay of 2s.
S 4: SIU−4, if the speed setting (feedback threshold) is exceeded in the
door zone, then:
− The relay switches 1.5.1
S 1+4: SIU−1 and SIU−4 active; functions as above
S Standard: 1, i.e. SIU−1
Function Display on Handterminal
none Off
SIU−1 1
SIU−4 4
SIU−1 + SIU−4 1+4
Important: there is no SIU−1 monitoring during inspection speed with K5!
300−I−9010212−E−10/08.08
71/92
CLRV lift control valve Operation
Setting "SIU−1 difference"
S Demand/feedback difference − only operative when SIU−1 is activated
S Setting range: 20–50% of fast travel speed
S Standard: 25%
Setting "SIU−4 threshold"
S Feedback threshold − only operative when SIU−4 is activated
S Setting range: 2.0–5.0V
S Standard: 2.5V
Determining the SIU−4 threshold:
Dem. value Fast UP
Setting "Accel. inspection"
S Only operative with inspection speed (K5)
S Higher value: greater acceleration, i.e. shorter acceleration distance
S Setting range: 0.30–5.00V/s
S Standard: 2.00V/s
Speed in door zone
x = ... [Volt]
Car speed Fast UP
Setting "Inspection speed"
S K5 gives inspection speed
S Higher value: faster travel speed
S Setting range: 20–80% of fast travel speed
S Standard: 50%
Important: only operative with fast travel speed
Setting "Decel. inspection"
S Only operative with inspection speed (K5)
S Higher value: greater deceleration, i.e. shorter deceleration distance
S Setting range: 0.30–10.00V/s
S Standard: 4.00V/s
300−I−9010212−E−10/08.08
72/92
CLRV lift control valve Operation
Setting "K6/K7/K8 acceleration"
S Only operative with auxiliary speeds (K6, K7, K8)
S Higher value: greater acceleration, i.e. shorter acceleration distance
S Setting range: 0.30–5.00V/s
S Standard K6: 0.80V/s
S Standard K7: 1.20V/s
S Standard K8: 1.60V/s
Setting "K6/K7/K8 speed"
S Fast speed is reduced with K6, K7, K8
S Higher value: faster travel speed
S Setting range: 20–100% of fast speed
S Standard K6: 20%
S Standard K7: 30%
S Standard K8: 40%
Important: only operative with fast travel speed
Setting "K6/K7/K8 deceleration"
S Only operative with auxiliary speeds (K6, K7, K8)
S Higher value: greater deceleration, i.e. shorter deceleration distance
S Setting range: 0.30–5.00V/s
S Standard K6: 1.20V/s
S Standard K7: 1.80V/s
S Standard K8: 2.40V/s
Setting "Decel. emergency"
S Only operative for emergency stop (reasons for emergency stop:
activation of SIU−1, timeout error, fault)
S Higher value: greater deceleration, i.e. shorter deceleration distance
S Setting range: 5.00–10.00V/s
S Standard: 10.00V/s
300−I−9010212−E−10/08.08
Setting "Pulsation sol."
S Higher value: higher solenoid pulse frequency (dither)
S Setting range: 120–220Hz
S Standard: 220Hz
73/92
CLRV lift control valve Operation
Setting "Demand val. red."
S Setting the sensitivity of the automatic demand−signal reduction
S Standard: Normal
S Functions
−Off
− Few sensitivity
− Normal
− Sensitive
Setting "Start delay"
S Pause between command and start of travel
S Higher value: longer pause
S Setting range: 0.1–1.0s
S Standard: 0.1s
Setting "Relay function"
S Either the relay on the power supply unit switches (⇒ 1.5.1) only
when there is an SIU fault, or it switches with any fault
S Standard: only SIU
S Functions
− only SIU
− all errors
300−I−9010212−E−10/08.08
74/92
CLRV lift control valve Operation
Setting "Command input"
S Selection of command evaluation
S Standard: Bucher K1 ... K8
S Setting range:
− Bucher K1...K8
− ELRV K1...K8
− binary B1...B4
− 3 Sign. K1...K8
Important: On the control side it must be guaranteed that a command change is concluded within 20ms
Bucher K1K8 ELRV K1K8 binary
3 Sign. K1 ... K8 **
Command input
B1...B4
23 22 21 5 4 3 2 1 23 22 21 5 4 3 2 1 4 3 2 1 23 22 21 5 4 3 2 1
K8 K7 K6 K5 K4 K3 K2 K1 K8 K7 K6 K5 K4 K3 K2 K1 B4 B3 B2 B1 K8 K7 K6 K5 K4 K3 K2 K1
0 0 0 0 0 0 0 0 0 0 0 1 0 0 − Standstill
0 0 1* 0 1 0 0 1 0 0 0 1 1 0 0 1* 0 Relevelling
0 0 1* 0 0 0 0 1 0 0 1 0 1 0 0 1* 0 Slow speed
1 0 0 1 1 0 0 1 0 1 1 1 1 0 1 1 Insp. speed
1 0 0 0 1 1 0 0 0 1 1 0 0 1 1 0 0 1 1 V K6
1 0 0 0 0 1 1 0 0 0 0 1 1 0 1 1 1 0 0 0 1 1 V K7
1 0 0 0 0 0 1 1 0 0 0 0 0 1 1 1 0 1 1 0 0 0 0 1 1 V K8
0 0 0 0 0 0 1 0 0 0 0 0 0 1 1 1 1 1 0 0 0 0 0 1 1 Fast speed
0 0 0 0 0 0 0 0 0 0 0 0 0 0 − Standstill
− 1* 0 0 0 1 1 0 0 0 0 0 1 0 − 1* 0 0 0 Relevelling
− 1* 0 0 0 0 1 0 0 0 0 1 0 0 − 1* 0 0 0 Slow speed
1 1 0 0 1 1 0 0 0 1 1 0 1 1 0 1 Insp. speed
1 0 1 0 0 1 0 1 0 0 1 0 0 0 1 0 1 0 1 V K6
1 0 0 1 0 0 1 0 0 1 0 0 1 0 1 0 1 0 0 1 0 1 V K7
1 0 0 0 1 0 0 1 0 0 0 1 0 0 1 1 0 0 1 0 0 0 1 0 1 V K8
0 0 0 0 1 0 0 0 0 0 0 1 0 0 1 1 1 0 0 0 0 0 1 0 1 Fast speed
Terminal
Command
up
down
* After a standstill, relevelling is implemented; after fast speed, slow speed.
** Control possibilities K1, K3 or K1+K3
Legend 0
1
Inactive Active Any
Setting "Auxiliary curve"
S Used in fault finding
S Use only after consultation with factory
S Setting range: 0–20
S Standard: 0
300−I−9010212−E−10/08.08
75/92
CLRV lift control valve Operation
5.1.4.3 Null point / Hall sensor menu (3)
S Displays the current feedback value
5.1.4.4 Information menu / Commands" (4)
Setting "Language/Sprache"
S Selection of the user language
S Possible languages
− German
− English
− French
− Italian
S Standard: German
Command "Load parameter"
S Overwrites the current parameters with the internally−saved
parameters
S Possible parameter sets
− Factory (factory settings)
− User
Command "Save parameter"
S Saves the current C−DELCON parameters as the User parameter set
Setting "Password"
S Prevents unauthorised changes to parameters
S Consists of any 4 numbers
S Password 0000" means: protection not activated (factory setting).
Command "Delete errors"
S Deletes the error list
Command "Pipe rupture"
S Simplified test procedure for the pipe−rupture valve, see page 62
300−I−9010212−E−10/08.08
76/92
CLRV lift control valve Operation
5.1.4.5 Information menu / Information list" (4)
Errors / Warnings / Info
For explanation of errors, see Page 84
S Fault memory for the last 8 faults, with operating−hours count
"Software version"
S Software version
S Example: 2.130
"Hardware version"
S C−DELCON version
S Example: 2.030
"Serial number"
S Serial number of the C−DELCON
S Format: year/month−sequential number
S Example: 0510−09489
"Check number"
S Valve test number
S Format: year/month−sequential number
S Example: 0510−00495
Important: It is essential that the C−DELCON be operated with the correct valve (with the same check number)
"Power on"
S Number of C−DELCON switch−ons, including reset−key presses
S max. 1.3 million
"Drive up"
S Number of Up travels
S Max. 1.3 million
Important: Relevelling Up operations are not counted
300−I−9010212−E−10/08.08
77/92
CLRV lift control valve Operation
"Drive down"
S Number of Down travels
S Max. 1.3 million
Important: Relevelling Down operations are not counted
"Operation hour"
S C−DELCON operating−hours counter
S Max. 65535 hrs
"+ unstab voltage"
Positive unstabilised voltage from the power supply unit S Range: +17 ... +41V
"− unstab voltage"
Negative unstabilised voltage from the power supply unit S Range: −17 ... −41V
300−I−9010212−E−10/08.08
78/92
CLRV lift control valve Operation
5.2 Calculating the demand values for maximum speed
The demand values are shown on a label on the C−DELCON’s microprocessor
The demand values for the maximum UP and DOWN speeds can be calculated from the following table:
Valve type Flow range, Q
Flow ring Conversion
[l/min.]
C−LRV 175
15–45 46–90
91–250
R45 R90
R250
1V <=> 4.8l/min. 1V <=> 9.7l/min.
1V <=> 29.1l/min.
C−LRV 350 251–500 R500 1V <=> 52.2l/min.
C−LRV 700 400–1000 R1000 1V <=> 112.0l/min.
Calculation example
Flow rate UP (Q) 120l/min. Flow rate DOWN (Q) 150l/min.
Valve selection:
Valve type C−LRV 175 Flow range 91–250l/min. * Flow ring R250 Conversion 1V <=> 29.1l/min. *
Conversion:
Flow rate UP: 120[l/min] / 29.1[l/min] = 4.12V Fast UP
Flow rate DOWN: 150[l/min] / 29.1[l/min] = 5.15V Fast DOWN
Settings in the C−DELCON
CLRV 175 120 / 150 21 / 45 R 250 K 251 / 680 / 55 bar
* These values are taken from the above table.
300−I−9010212−E−10/08.08
79/92
CLRV lift control valve Operation
5.3 Faults / Fault−finding
5.3.1 Check list for fault correction
Fault Cause Corrective action Page (Chapter)
No UP travel S Motor / pump not running S Check connection
S Wiring fault S Check wiring 49 (4.2.3)
S Electrics − control cabinet S Motor running on 2
phases
S Motor− and/or oil−PTC
thermistor has operated
S Electronic soft−starter not
connected properly
S UP solenoid not
energised
S Contacts K1/K2 and/or
R2 not closed
S SIU (demand/feedback
monitoring) is actuated, LED SIU−1" on C−DEL­CON lights up
S DOWN solenoid is
energised
S UP pilot filter dirty S Clean filter. If necessary,
S Check power supply 49 (4.2.3)
S Connect in accordance
with diagram
S Check solenoid output
and R2
S Check connections after
power supply unit
S Check control of power
supply unit
S Check mechanical null
point
S Correct the wiring fault S NTA−2, terminals 7+8
crossed?
filter oil
49 (4.2.3)
60 (4.3.10)
49 (4.2.3)
61 (4.3.11)
Car does not reach speed
Cannot lift maximum load S Pressure−relief valve set
UP−travel starting problems
Car does not reach storey
S Pressure−relief valve set
too low
too low
S Overload switch DZ has
activated
S Leakage between pump
and valve
S Jolt when starting S Reset bypass−pressure
S Travels UP without any
command
S Oil level in power unit is
below minimum
S Leakage: valve − cylinder S Check for leakage
S Check pressures/consult
factory
S Check pressures/consult
factory
S Reduce the load
S Eliminate the leakage
setscrew Á on the valve
S Bypass−pressure
setscrew Á on the valve is set too high. Reset it.
S Top−up when car is at
lowest landing
56 (4.3.4)
56 (4.3.4)
53 (4.3.3)
53 (4.3.3)
52 (4.3.2)
300−I−9010212−E−10/08.08
80/92
CLRV lift control valve Operation
S Mechanical null point is
displaced
S Plunger cylinder is at
end−stop
S Extension of telescopic
cylinder is not synchronised
S Ratio of top− to
bottom−overtravel is wrong
Page (Chapter)Corrective actionCauseFault
S Check 60 (4.3.10)
S Cylinder pillar is too short S Check cylinder stroke
S Check cylinder stroke S Telescopic cylinder is
sitting too low; raise it
S 2−stage: 1/2 bottom / 1/
top
S 3−stage: 1/3 bottom / 2/
See document
2
300−P−9010023
3
top
Car overshoots landing during UP travel
S Deceleration switches
wrongly positioned
S Mechanical null point is
displaced
S Deceleration time is too
short
S Bypass pressure set too
high
No DOWN travel S Car overloaded, pressure
switch has activated
S Contacts K3/K4 and/or
R1 not closed
S No current from power
supply unit
S UP solenoid is energised S Correct the wiring fault
S DOWN solenoid not
energised
S Position correctly 58 (4.3.8)
S Check 60 (4.3.10)
S Increase deceleration in
C−DELCON
S Reset it
S Reduce the load
S Check the safety relay
S Test the voltage;
49 (4.2.3)
exchange unit
S Exchange solenoid plug
on valve
S Check voltage at terminal
7
S Check connection from
terminal 7 to DOWN solenoid (safety relay R1)
Lift starts DOWN, then stops
S SIU (demand/feedback
monitoring) is actuated,
S C−DELCON settings are
too low LED SIU−1" on C−DEL­CON lights up
S Acceleration is too high S Decrease the
acceleration setting
S Fast DOWN set too high
S Reduce Fast DOWN 79 (5.2)
in C−DELCON
S Flow rating of
S Reduce Fast DOWN
pipe−rupture valve too low
DOWN speed is too slow S Car is too light S Add weight to the car
300−I−9010212−E−10/08.08
81/92
CLRV lift control valve Operation
S Hydraulic line to the
cylinder is too small
S Oil is too cold S Use multigrade oil
S Too much friction in
system
Page (Chapter)Corrective actionCauseFault
S Fit larger line
S Install oil heater
S Provide parking circuitry
S Align cylinder and rails
Car overshoots landing during DOWN travel
Car overshoots landing during DOWN travel
Leakage in hydraulic system (test only when oil is cold)
S Deceleration switches
S Set as per page(s) 58 (4.3.8)
wrongly positioned
S Safety relay R1 drops out
S Set as per page(s) 23 (1.4.4)
too early, or without a delay
S Deceleration time too
short
S Deceleration switches in
S Increase deceleration in
C−DELCON
S Set as per page(s) 58 (4.3.8)
shaft wrongly positioned
S Feedback sensor (Hall
sensor) GND not
S Connect GND to terminal
12 connected
S Demand values set too
S Set as per page(s) 79 (5.2)
high
S DOWN pilot valve
S Clean pilot valve 61 (4.3.11)
contaminated
S Oil is too cold S Consider installing oil
heater; providing parking
circuitry
S Pressure drop in approx.
S None, valve is leak−tight!
3 minutes is not more than 5bar (with ball valve closed)
49 (4.2.3)
300−I−9010212−E−10/08.08
82/92
CLRV lift control valve Operation
S DOWN pilot pin is bent S Exchange DOWN pilot
Attention
The UP and DOWN spools are not interchangeable!
S Emergency−lowering
valve leaking
S Check valve is leaking S Replace seal 11 (1.3)
S Pressure falls rapidly S DOWN spool leaking;
valve
S Operate it several times
during UP command
clean seat and re−lap
Page (Chapter)Corrective actionCauseFault
36 (3.1)
Car sinks (with ball valve closed)
S Oil is just cooling down! S None
S Leak in cylinder or
connecting line
S Check/tighten connecting
hose. Renew seals, if
necessary
300−I−9010212−E−10/08.08
83/92
CLRV lift control valve Operation
5.3.2 Fault description
Display on
Handterminal
Cause Remedy
Err:None No fault
Warn:
Board−T.
Temperature of C−DELCON ex­ceeds 70°C
S Ambient temperature is too high S Lower the ambient temperature
S Poor ventilation in control cabinet S Improve control cabinet ventila-
Err:
Input−V.+
Positive voltage from power sup­ply unit is outside of +17V...+41V
S Positive voltage is too low or too
high
S Incorrect power supply unit for
the C−DELCON (transformer code 280−G21 /281−G21 / 282−G21
Err:SIU−1 Demand/feedback difference too
large
S SIU demand/feedback monitoring
(LED lights up)
Further de­tails (code,
see 5.3.3)
Warning message, not a fault 102, 301,
403
tion
103, 104, 201, 301,
S Check the incoming mains volt-
403
age
S Choose the correct power supply
unit to suit the mains voltage
S Replace the power supply unit
104, 105, 107, 202,
S The C−DELCON settings are too
301, 404
low
Err:
Command
Err:
Zero−point
Err:
WrongSW
Info:
New vers
Info:
Default
S Acceleration is too high S Decrease the acceleration setting
S Fast DOWN is set too high on
S Decrease the fast DOWN setting
the C−DELCON
S Flow rating of pipe−rupture valve
S Decrease the fast DOWN setting
is too low
Incorrect combination of com­mands
S e.g. Up and Down simultaneously S Ensure correct commands are
103, 104, 105, 201,
301, 403
signalled
Null point outside of ±1.00V 103, 105,
S Mechanical null point is wrongly
set
S Reset the mechanical null point
201, 301,
402
S Bypass pressure is too high S Set the bypass screw on the
valve correctly (unscrew it slightly)
Software fault 106, 201,
S Wrong EPROM installed
(software initialisation fault)
S Change the EPROM S Replace the C−DELCON
301, 403
New software version installed Information 106, 301,
S New EPROM has been installed S No fault, just information
401
Factory settings loaded Information 102, 301,
S The default factory settings have
S No fault, just information
401
been loaded
300−I−9010212−E−10/08.08
84/92
CLRV lift control valve Operation
Display on
Handterminal
Warn:
0 Point
Err:
0−Point+
Err:
0−Point−
Warn:
A0 Point
Further de-
RemedyCause
tails (code,
see 5.3.3)
Null point outside of ±0.20V Warning message, not a fault 103, 301,
S Mechanical null point is wrongly
S Reset the mechanical null point
401
set
S Bypass pressure is too high S Set the bypass screw on the
valve correctly (unscrew it slightly)
Automatic null point adjustment outside of +1.00V
S Bypass pressure is too high S Set the bypass screw on the
103, 105, 201, 301,
402
valve correctly (unscrew it slightly)
Automatic null point adjustment outside of −1.00V
S Emergency lowering valve actu-
103, 105, 201, 301,
402
ated
S Leakage
Null point outside of 1.00V dur­ing relevelling
Warning message, not a fault 103, 105,
301, 401
Err:
Unknown
Warn:
Demand
Err:
Input−V.−
S Mechanical null point is wrongly
set
S Bypass pressure is too high
S Emergency lowering valve actu-
S Reset the mechanical null point S Set the bypass screw on the
valve correctly (unscrew it slightly)
ated
Unknown fault
S Internal software fault S Upgrade/reinstall software
Automatic demand signal reduc-
Warning message, not a fault 104, 107, tion was invoked, maximum speed was reduced for this travel
S Maximum speed too high S Decrease the maximum speed
S Oil temperature too low S Install an oil heater, or use
thinner oil
S Too heavy a load with hot oil S Install an oil cooler, do not over-
load the car
Negative voltage from power sup­ply unit is outside of −17V...−34V
S Negative voltage is too low or too
high
S Unsuitable power supply unit for
the C−DELCON (Transformer code:
S Check the incoming mains volt-
age
S Choose the correct power supply
unit to suit the mains voltage
S Replace the power supply unit
280−G21/281−G21/282−G21)
301, 401
103, 104, 201, 301,
403
Info:
Cmd−Dir.
300−I−9010212−E−10/08.08
Command direction changed dur­ing travel
S Fault on K1 to K4
(Terminals 1 to 4)
Information 103, 104,
105, 301,
S Cure the cause of the fault
403
85/92
CLRV lift control valve Operation
Display on
Handterminal
Warn:
Bypass pre
Warn:
Leakage
Warn:
Timeout
RemedyCause
Automatic null point adjustment
Warning message, not a fault 103, 105, outside of +0.20V
S Hand pump activated
S Bypass pressure is too high S Set the bypass screw on the
valve correctly (unscrew it slightly)
Automatic null point adjustment
Warning message, not a fault 103, 105, outside of −0.20V
S Emergency lowering valve actu-
ated
S Leakage
Relevelling up/down takes longer
Warning message, not a fault 104, 105, than 2 minutes
S Emergency lowering valve actu-
ated
Further de-
tails (code,
see 5.3.3)
301, 401
103, 105,
301, 401
301, 401
203, 301,
401
300−I−9010212−E−10/08.08
86/92
CLRV lift control valve Operation
5.3.3 Code for further details
Code Meaning
Monitoring
101 Constantly
102 At standstill
103 At start of travel
104 During travel
105 Not monitored during inspection travel
106 When the program is started
107 Dependent on parameterisation
Effect
201 Travel is disabled
202 Travel is aborted (relay is opened)
203 Travel is aborted (relay is NOT opened)
204 Travel is aborted (dependent on parameterisation, relay may be opened)
Save
301 If at standstill, immediately; if travelling, at end of travel
302 Delay of 2s
303 Is not saved during inspection travel
Reset
401 Immediately (save only)
402 Delay of 2
403 When the cause has been removed
404 If the "Relay function" setting is "only SIU": reset operation after there is no longer any travel
command. Otherwise: delay of 2s
300−I−9010212−E−10/08.08
87/92
CLRV lift control valve Operation
300−I−9010212−E−10/08.08
88/92
CLRV lift control valve Maintenance
6 Maintenance
6.1 Maintenance schedule
This service plan is just a guide. Adjustments or changes should be un­dertaken by the installation company.
Work to be carried out Time
Before commission-
ing
Valve Check internal leakage X X X
First service after
commi−ssioning, not
During commissioning
later than after 3 months
At every service, at
least 2 x per year
Annually
After 5 years
After 10 years
Pipe Hose
Check external leakage X X X
Check the maximum pressure setting (pressure−relief valve / screw)
Check mechanical null point (Hall sensor) X X X
Clean pilot filters X X X
Clean main filter X –– X
Renew O−rings (when valve is dismantled, or as required)
Check for leakage X X X X
Carry out checks in accordance with the Installation and Maintenance Guide
X X
X X X X
X –– X
300−I−9010212−E−10/08.08
89/92
CLRV lift control valve Maintenance
6.2 Operating materials and aids
Hydraulic oil (code) Viscosity
[mm2/s] (cSt)
Permissible
temperature range
to DIN 51525 to ISO 6074 at 40°C min. °C max. °C
H−LP 32 ISO VG 32 32 1 42
H−LP 46 ISO VG 46 * 46 8 50
H−LP 68 ISO VG 68 68 15 59
H−LP 100 ISO VG 100 100 21 60
Shell Tonna S32 32 1 42
Shell Tonna S68 68 15 70
* This oil can be used in most applications. For frequently−used passenger lifts, the thicker VG 68 oil should be used.
The type of oil actually used to fill the system must be recorded by the lift manufacturer in the designated field on the nameplate of the submersed motor/pump power unit.
Tested and approved hydraulic fluids with biodegradable characteristics
Type Panolin HLP
32/46 Synth
HF−E 46 Rivolta
S.B.H.23
Avia Syntofluid
F 32 or 46
Megol
HEES46
Supplier
Viscosity 40°C
mm@/s
(cSt)
Panolin AH
Medetswil (CH)
Shell
Bremer+Leguil
GmbH
Avia
Avia−Kühmichel
32/46 46 46 32/46 48
Liqui Moly GmbH
Ulm (D)
Base Ester Ester Ester Ester Ester
Water−hazard class nwg/1 1 nwg nwg 1
Biodegradability >90% >90% >97% >90% >90%
Flashpoint °C 240 210 240 310 320
(Water hazard classified in accordance with the German standard dated 1999)
nwg = not hazardous to waters
300−I−9010212−E−10/08.08
90/92
CLRV lift control valve Maintenance
6.3 Installation guide for DOWN pilot valve
Exchanging the DOWN pilot valve
1. Switch main switch OFF
2. Close the ball valve
3. Vent all pressure in the valve block (manual lowering valve)
4. Remove solenoid and the A and C parts
5. Assemble the A parts and insert them in the bore
6. Insert O−ring (B)
7. Assemble the C parts, then insert the unit in the bore. Make sure that the stem of the cone (3) is clearly engaged in the spring
8. Insert O−ring (D) and fit the solenoid
I If needle (1) slips out of the bush (2), start again from step 7.
9. Open the ball valve.
10. Switch main switch ON
The new DOWN pilot valve is ready for use
300−2−10006634
300−I−9010212−E−10/08.08
91/92
CLRV lift control valve Maintenance
6.4 Customer service information
World Wide Bucher Hydraulics AG
Industriestrasse 15 CH−6345 Neuheim
Tel.: +41 41 757 03 33 Fax: +41 41 757 03 19
elevator@bucherhydraulics.com
Germany Service South−East
Germany Service North−West
Germany Spare Parts Center
Bucher Hydraulics AG
Jürgen Zehrer Franz Schubert Strasse 13 D−90768 Fürth
Tel.: +49 911 72 06 45 Fax: +49 911 72 06 51 Mobile:+49 172 810 51 06
juergen.zehrer@bucherhydraulics.com / j−zehrer@t−online.de
Bucher Hydraulics AG
Philippe Roose Blumenstrasse 24 D−65366 Geisenheim
Tel.: +49 672 27 53 72 Fax: +49 672 27 53 61 Mobile:+49 172 610 46 36
philippe.roose@bucherhydraulics.com
Bucher Hydraulics AG
Susanne Sieber Loferer Weg 3a D−82140 Olching
Tel.: +49 8142 4870 36 Fax: +49 8142 4870 37
susanne.sieber@bucherhydraulics.com
UK Bucher Hydraulics Ltd
Alan Rolley UK Service Engineer − Elevator Unit 9, Eastboro Fields Hemdale, Nuneaton GB−Warwickshire CV11 6GL
Tel.: +44 (0) 2476 35 35 61 Fax: +44 (0) 2476 35 35 72 Mobile:+44 (0) 7709 46 09 12
alan.rolley@bucherhydraulics.com
300−I−9010212−E−10/08.08
92/92
Loading...