All rights reserved. This installation and commissioning guide, in whole and/or in part, is protected
by copyright. It may not be reproduced, nor may it be stored, processed, replicated or distributed
by electronic means, without written permission from Bucher Hydraulics AG.
Data is provided for the purpose of product description only, and must not be construed as warranted characteristics in the legal sense. No assertion regarding either a particular property or the
fitness for a particular intended purpose can be derived or deduced from this information. The information does not relieve users from the duty of conducting their own evaluations and tests.
Because the products are subject to continual improvement, we reserve the right to amend the
product specifications contained in this catalogue. The original language and legal terminology of
all Bucher Hydraulics AG documentation is exclusively German. Bucher Hydraulics AG cannot be
held liable for any possible errors in translation.
300−I−9010212−E−10/08.08
2/92
C−LRV lift control valve
ContentPage
0General5
0.1Target group
0.2Supplementary documents
0.3Specialist terms
1Product description
1.1Important notes
1.1.1Subassemblies7
1.1.2intended use8
1.1.3Conformity8
1.2Product identification9
1.2.1Nameplate9
1.2.2Test number9
1.2.3Model code10
1.3C−LRV lift control valve11
1.3.1Simplified hydraulic–electrical diagram12
1.3.2Factory settings13
1.3.3Description of function13
1.3.4Technical data16
1.3.5Pressure drop18
1.4C−DELCON electronic card20
1.4.1Factory settings20
1.4.2Description of function21
1.4.3Technical data22
1.4.4Travel and switching diagram for normal travel distance23
1.4.5Travel and switching diagram for short travel distances24
This guide is an integral part of the product. It describes the product´s
safe use in all phases of operation and is valid for all model series that
are referred to.
S Operator
S Installer
S Service engineer
S Repair technician
DescriptionDocument
Quick−start guide for valve300−P−9010169
0.3Specialist terms
TermDefinition
C−DELCONElectronic control card for C−LRV valve
300−I−9010212−E−10/08.08
5/92
C−LRV lift control valve
300−I−9010212−E−10/08.08
6/92
C−LRV lift control valveProduct description
0
1Product description
1.1Important notes
1.1.1Subassemblies
This guide differentiates between the following subassemblies:
C−LRV lift control valve
C−DELCON electronic control cardNTA−2 power supply unit
300−I−9010212−E−10/08.08
7/92
C−LRV lift control valveProduct description
1.1.2intended use
Lift control valve for operating hydraulically−driven passenger and goods
lifts.
The products must not be handled in any way by unauthorised persons.
1.1.3Conformity
The product was designed and developed in conformity with the following standards:
Standards
EMC standardsEN 12015
EN 81−2
EC 95/16
BS 5655 Part 2
SIA 370−11
EN 12016
IEC 1000−4
300−I−9010212−E−10/08.08
8/92
C−LRV lift control valveProduct description
1.2Product identification
1.2.1Nameplate
12
C−LRV 175 − 120 / 150 − 21 / 45
R 250 − K 251 / 6−80 / 55 bar
6789
345
1 Valve type= C−LRV 175
2 Flow rate UP= 120l/min
3 Flow rate DOWN= 150l/min
4 Minimum static pressure (empty car)
= 21bar
5 Maximum static pressure (full car)
= 45bar
6 Flow ring= R250
7 Spool= K251
8 Setting range= 6–80 bar
9 Set for maximum working pressure
= 55bar
1.2.2Test number
2
1
300−I−9010212−E−10/08.08
Legend12Test number
Nameplate
9/92
C−LRV lift control valveProduct description
1.2.3Model code
Valve type/size
= C−LRV 175
= C−LRV 350
= C−LRV 700
Flow range: flow rate/type
C−LRV 17515–45l/min= R 45
46–90l/min= R 90
91–250l/min= R 250
C−LRV 350251–500l/min = R 500
C−LRV 700400–1000l/min = R 1000
R 250K 251VND0////C−LRV 175
Spool: flow rate/type
C−LRV 17515–90l/min= K 91
91–250l/min= K 251
C−LRV 350251–500l/min = K 501
C−LRV 700400–1000l/min = K 1001
Manual emergency−lowering valve
Emergency−lowering valve with preload= VN
C−DELCON type
without C−DELCON= D0
with C−DELCON (SIU 1 + SIU 4)= D1
300−I−9010212−E−10/08.08
10/92
C−LRV lift control valveProduct description
1.3C−LRV lift control valve
Legend1
10
Z1
Z2
Z3
Maximum−pressure setscrew
2
Bypass−pressure setscrew
4
Pressure−relief valve
5
Pilot filter
6
Test point, G½
7
Pressure gauge
8
Pressure gauge shut−off screw
9
Air−bleed screw
Feedback sensor
11
Main filter
Pressure switch port
Pressure switch port
Hand pump port
Main filter
Flow−rate measuring system
Emergency−lowering valve
Pressure switch port
Pressure switch port
Hand pump port
P
Pump port
T
Tank port
Z
Cylinder port
M
14
DOWN spool
15
Check valve
16
UP spool
20
Pipe−rupture valve
21
Ball valve
22
Electrical emergency−lowering
valve (optional)
23
Pressure switch
24
Hand pump
R
to EN81−2, 12.4.1/12.4.2
1
R
to EN81−2, 12.4.1/12.4.2
2
A
C−DELCON
B
NTA−2
C
C−LRV
D
Control cabinet (customer’s)
300−I−9010212−E−10/08.08
12/92
C−LRV lift control valveProduct description
1.3.2Factory settings
All valves are factory−set to the values for the particular installation and
then tested.
S Pressure−relief valve set to the maximum working pressure
S Bypass pressure as per the calculated minimum static pressure
S Mechanical null point of the feedback sensor
S Emergency−lowering valve set to 5−10% of maximum DOWN speed
1.3.3Description of function
The lift control valve can be subdivided into 3 main functions.
1. Up section / pressure−relief valve
16
1
4
S Initial position:
UP spool (16) is open in the 0 position; pump flow goes directly to
tank
S Up travel / acceleration:
UP spool (16) is progressively closed by the electro−proportional
valve (UP solenoid); this results in smooth acceleration of the lift up to
maximum speed
S Deceleration:
UP spool (16) is progressively opened by the electro−proportional
valve (UP solenoid); this results in smooth deceleration of the lift to
standstill
S Overload:
pressure−relief valve (4) and UP spool (16) open when the maximum
working pressure set with screw (1) is reached
300−I−9010212−E−10/08.08
13/92
C−LRV lift control valveProduct description
2. DOWN section / emergency−lowering valve
14
13
The down section is constructed in a similar way to the up section.
S Initial position:
DOWN spool (14) is closed leak−free in the 0 position
S Down travel / acceleration:
DOWN spool (14) is progressively opened by the electro−proportional
valve (DOWN solenoid); this results in smooth acceleration
S Deceleration:
DOWN spool (14) is progressively closed by the electro−proportional
valve (DOWN solenoid); this results in smooth deceleration of the lift
to standstill
S Power failure / evacuation:
With the electrical emergency−lowering valve (optional), the car can
be lowered using DC voltage (⇒ 4.2.4)
S The car can be lowered slowly with the manual emergency−lowering
valve (13)
300−I−9010212−E−10/08.08
14/92
C−LRV lift control valveProduct description
3. Flow−rate measuring system
10
12
S The oil flows through the flow meter (12) in both the up and down
directions
S The baffle−disc is displaced axially as a function of the flow rate
S This axial displacement is converted by a non−contacting feedback
transducer (10) into an electrical DC signal (the feedback signal),
which is then sent to the C−DELCON
S The output signal (the feedback) is proportional to the flow rate
S The controller in the C−DELCON works to match the feedback value
* Note the viscosity range and minimum oil temperature. For detailed information, see 6.2, page 90
300−I−9010212−E−10/08.08
17/92
C−LRV lift control valveProduct description
1.3.5Pressure drop
C−LRV 175
R45
15.0
12.5
10.0
A
7.5
Spool K 91
5.0
2.5
R90
R250
Spool K 251
Flow ring (R)
DOWN (Z−T)
UP (P−Z)
0.0
205090 100150180200250
B
C−LRV 350
15.0
12.5
10.0
R500
Spool K 501
A
7.5
5.0
2.5
0.0
250275300325350375400425450475500
Flow ring (R)
DOWN (Z−T)
UP (P−Z)
B
LegendABPressure drop [bar] Min. required dyn. pressure
Flow rate Q [l/min.]
300 cSt (HLP 46)
75 cSt (HLP 46)
300−I−9010212−E−10/08.08
18/92
C−LRV lift control valveProduct description
C−LRV 700
15
12.5
10
R1000
Spool K 1001
A
7.5
5
2.5
0
4004505005506006507007508008509009501000
B
LegendABPressure drop [bar] Min. required dyn. pressure
Flow rate Q [l/min.]
Flow ring (R)
DOWN (Z−T)
UP (P−Z)
300 cSt (HLP 46)
75 cSt (HLP 46)
300−I−9010212−E−10/08.08
19/92
C−LRV lift control valveProduct description
1.4C−DELCON electronic card
The C−DELCON controls the oil flow − and therefore the lift’s travel profile − in accordance with a preset curve.
Electrostatic discharge (ESD)
The C−DELCON can be damaged by incorrect handling.
Always keep the DELCON in its ESD protective bag and only hold it by
the spacer studs (4).
6
Attention
4
3
Legend1
5
Nameplate
2
Label with Test number
3
Label with description of LED functions
4
Spacer studs M2.5x10
5
Label with Demand values
6
RESET button (restarts the program in the C−DELCON electronic card)
1
2
300−2−10012279
1.4.1Factory settings
300−I−9010212−E−10/08.08
S Maximum UP and DOWN speeds
S Slow speed set to 5−10 % of maximum speed
S Acceleration/deceleration set to mid−range value
S Inspection travel speed set to 50 % of maximum speed
20/92
C−LRV lift control valveProduct description
1.4.2Description of function
S The lift control system sends the command signals to the C−DELCON
via potential−free relay contacts or semiconductors (K1−K4)
S The feedback value is compared with the demand travel curve
throughout the whole travel.
S Deviations from the demand curve are corrected by the UP and
DOWN proportional solenoids
S The closed−loop control ensures that the travel characteristics are
independent of load and temperature
S The inspection speed can be set through contact K5 of the lift control
system (there is no SIU−1 monitoring during inspection speed with
K5!)
S Reduced speeds for short travel distances are also possible via
K6−K8
S The C−DELCON enables soft−stopping (gentle halt) with very accu-
rate positioning (±3 mm)
Features
S The travel curve for the up and down directions is set and adjusted
with the Handterminal or a PC
S The demand curve can be set and checked at the C−DELCON while
the lift is at standstill
S Measured values can be checked with the Handterminal
S The C−DELCON card is easy to exchange (1 card for all valves),
which means that rapid fault−fixing is ensured
Important: If the C−DELCON is exchanged, the installation−specific
parameters must be replicated in the new card.
300−I−9010212−E−10/08.08
21/92
C−LRV lift control valveProduct description
1.4.3Technical data
Weight:150g
General description
300−2−10012279
S Digital electronic card for the C−LRV valve
S Conforms to the European format (100 mm x 160 mm)
S Enhanced ride comfort
S Automatic reduction of demand signal if nominal speed is not at-
tained
S Extended functions
S Simple set−up
S Easy to trouble−shoot
New installations
S Factory settings permanently stored
Replacement cards
S Contain basic settings.
For installation−specific settings, ⇒ Section 5.1
300−I−9010212−E−10/08.08
22/92
C−LRV lift control valveProduct description
1.4.4Travel and switching diagram for normal travel distance
*Y−
N
* motor run−on time of 0.5 ... 1s
** Drop−out delay of 0.5 ... 1s
Legend1
Motor contactor ON
2
Safety relay R2 closed
3
K2 "Slow UP" closed
4
K1 "Fast UP" closed
N Normal distance between floors
Y−Δ Y starting time of up to approx.
3s with Y−Δ,
K1 and K2 not until Δ connection
5
K3 "Fast DOWN" closed
6
K4 "Slow DOWN" closed
7
Safety relay R1 closed
**
300−I−9010212−E−10/08.08
23/92
C−LRV lift control valveProduct description
1.4.5Travel and switching diagram for short travel distances
The electronics of the C−LRV valve make it possible to control stops at
mezzanines and similar short travel distances with the same ride comfort
as in normal travel.
Important: The maximum speed should be reduced to a value that,
despite the short travel distance, can actually be attained.
Short distance between floors with normal speed
(slow−speed travel distance too long)
XZ
N
ZX
K
Short distance between floors with reduced speed
(K6)
N
ZY
K
Y**
**
ZY
Motor run−on time of 0.5 ... 1s
*
Drop−out delay of 0.5 ... 1s, after drop out of K4 + K6
**
K2 and K2 not until Δ connection
***
Adjust the speed to suit the circumstances (e.g. 50%)
V
Legend1
Motor contactor ON
2
Safety relay R2 closed
3
K2 + K6 closed
4
K1 closed
N Normal distance between floorsKShort distance between floors
Deceleration switch at normal speed
X
Deceleration switch at reduced speed
Y
Soft−Stop is not separately adjustable
Z
5
K3 closed
6
K4 + K6 closed
7
Safety relay R1 closed
300−I−9010212−E−10/08.08
24/92
C−LRV lift control valveProduct description
S By using relays K6, K7 or K8, various reductions in the nominal
speed can be achieved (e.g. for different floor spacings)
S The speed reduction can be adjusted between 20–100% of nominal
speed
S Speed can be set by means of parameter "K6 speed" (or "K7 speed" /
"K8 speed") in the Options menu to match the floor spacing (distance
between stops)
S Acceleration can be adjusted separately via parameters "K6 acceler-
ation" (or "K7 acceleration" / "K8 acceleration") in the Options menu
S Deceleration can be adjusted separately via parameters "K6 deceler-
ation" (or "K7 deceleration" / "K8 deceleration") in the Options menu
300−I−9010212−E−10/08.08
25/92
C−LRV lift control valveProduct description
1.5NTA−2 power supply unit
The NTA−2 power supply unit provides both power supply and physical
support for the C−DELCON.
300−1−10008856
Legend1
Mains voltage terminals
2
Socket for feedback cable
3
Terminal block
(screwless)
4
Jumper JP2 (connects Earth
and Signal GND)
5
Terminal block for SIU connection
6
Terminal block for emergency
power supply
7
Jumper JP1 (demand/feedback monitoring − SIU)
8
Transformer
9
Card−holder
300−I−9010212−E−10/08.08
26/92
C−LRV lift control valveProduct description
1.5.1Description
The power supply unit is connected directly to the main supply or the
control system supply.
The control signals for the C−DELCON are connected to the terminal
block (3).
Through the terminals 18–17a (N.O. make contact)
a relay output is provided.
Its function is defined in the C−DELCON by the settings of the "SIU type"
and "Relay function" parameters.
Parameter SIU type"
0Off
1SIU−1: relay switches when the demand/feedback differ-
4SIU−4: relay switches when the speed threshold is ex-
1+4SIU−1 and SIU−4 active, functions as above
18–17b (N.C. break contact)
ence is exceeded (there is no SIU−1 monitoring during inspection speed with K5 !).
ceeded (e.g. 0.3m/s in the door zone)
Parameter "Relay function"
only SIU
The relay on the power supply unit switches only when
there is an SIU fault
all errors
The relay on the power supply unit switches with any fault
JP1 selects the relay’s passive state.
1−2Current flows through the relay in its passive state (no cur-
rent when function is activated)
2−3No current through the relay in its passive state (current
flows when function is activated)
We recommend that the safety circuit be switched through an auxiliary
contactor.
The jumper JP2 connects the Signal GND to Earth potential (default setting).
Important:with Jumper JP2 inserted (Signal GND connected to Earth),
then − dependent on the wiring − there is a risk that an earth loop may
exist. To prevent earth loops and the associated possible malfunctions,
consult the installation circuit drawing.
Ground/reference potential (GND) for command inputs (K1...K8)
Ground/reference potential (GND) for command inputs (K1...K8)
Common, DOWN solenoid
Output, DOWN solenoid
Common, UP solenoid
Output, UP solenoid
Demand / feedback monitoring
17a
18
SIU−1 (demand/feedback monitoring), SIU−4 (v ≤0.3m/s)⇒ 1.5.1
17b
Connection for feedback cable
9
10
11
12
Emergency power supply
19
12
20
Stabilised voltage supply +15V
Feedback signal (input)
Stabilised voltage supply −15V
Ground, Hall−effect sensor (GND)
+24V emergency power supply
Ground, emergency power supply (GND)
−24V emergency power supply
300−I−9010212−E−10/08.08
30/92
C−LRV lift control valveProduct description
1.6IWK−1 feedback cable
Important: The feedback cable must be run from the lift control valve
directly to the NTA−2 power supply unit without any intermediate terminals. Any discontinuity in the feedback cable (break, kink, etc.) can
endanger trouble−free operation.
It is essential that connection 2 is ground−bonded to terminal 12, otherwise the null point of the sensor will not be stable.
If you cut the cable to length and terminate it yourself, be sure to wire it
correctly in accordance with the following diagram:
LegendA
ColoursIKBrown
Line socket with PG7 gland
B
NTA−2 connector
C
WAGO plug
D
Screen
Green
E
Supply +15V
F
Signal 0...±13.4V
G
Supply −15V
H
Ground
LMWhite
Yellow
300−I−9010212−E−10/08.08
31/92
C−LRV lift control valveProduct description
1.7Surroundings
For reliable operation, the following conditions must be maintained in the
surroundings:
SurroundingsRequirement
Machine room temperature
Oil temperature2…60°C
Relative air humiditymax. 90% (non−condensing)
2…40°C
1.8Emissions
The following emissions can occur during operation:
EmissionCorrective action / Note
HeatEnsure fresh−air supply and warm−air extraction
NoiseSound−proof the entrance to lift shaft (noise transmission)
300−I−9010212−E−10/08.08
32/92
C−LRV lift control valveSafety information
2Safety information
It is essential to take note of the important safety information contained
in this document (guide).
Denotes a potentially harmful situation. If it is not prevented, the product or its surroundings may be damaged.
Denotes a potentially dangerous situation. If it is not prevented, it may
result in slight or minor injuries to people.
Attention
Caution
Warning
Denotes a potentially dangerous situation. If it is not prevented, it may
result in death or serious injuries to people.
Danger
This denotes a directly imminent danger. If it is not attended to, it will
result in death or serious injuries to people.
300−I−9010212−E−10/08.08
33/92
C−LRV lift control valveSafety information
300−I−9010212−E−10/08.08
34/92
C−LRV lift control valveOperating controls and indicators
3Operating controls and indicators
It.DescriptionTools
1Maximum−pressure setscrew
(Screw À)
2Bypass−pressure setscrew
(Screw Á)
1 x open−ended spanner, 13 A/Fmm
Allen key, 4mm A/F
Open−ended spanner, 10 A/Fmm
Allen key, 5mm A/F
8Pressure gauge shut−off screwAllen key, 4mm A/F
9Filter screw, UPOpen−ended spanner, 22 A/Fmm
10UP solenoidAllen key, 3mm A/F
11DOWN solenoidAllen key, 3mm A/F
12Filter screw, DOWNOpen−ended spanner, 22 A/Fmm
13Pilot plateAllen key, 6mm A/F
14Adjusting/clamp screw for Hall sensor / mech.
Allen key, 3mm A/F
null point
300−7−10012261
300−I−9010212−E−10/08.08
35/92
C−LRV lift control valveOperating controls and indicators
3.1Emergency−lowering valve
Pressing lever = lowering the car
The car is lowered by pressing the lever of the emergency−lowering
valve.
Important: The minimum preload pressure of 6–10 bar continues to
exist (prevents slack−rope build−up as per EN 81−2)
Danger
Car descent
People may suffer injury and materials may be
damaged.
Before operating the emergency−lowering
valve, make sure that there are no people or
materials in the lift shaft.
3.2Display of the operating status
Legend for the LEDs
1 RUN
Ready for operation (green). Lights when ready for travel; off during
parameterisation
2UP
UP travel (yellow). Lights during upwards travel (fast and slow)
3 DOWN
DOWN travel (yellow). Lights during downwards travel (fast and slow)
4 ERROR
Fault indication (red). Lights when a fault has occurred; no travel is
possible
5 SIU−1
SIU−1 display (yellow). Lights when demand/feedback difference is
exceeded
6 RELAY
Relay display (yellow). Lights when relay on power supply unit is open
300−I−9010212−E−10/08.08
36/92
C−LRV lift control valveOperating controls and indicators
3.3Handterminal
General description
Keys
1Demand values menu
2Options menu
3Null point display
4Menu − Information
↑Steps to previous parameter
↓Steps to next parameter
+Increases the value of the
current parameter
−Decreases the value of the
current parameter
S Easy set−up of the travel curve
S Command, feedback value and control voltage are displayed during
travel
S Null−point adjustment
S Fault memory can be called up
Connection
S Connect the Handterminal to the C−DELCON using the cable
provided
S Connecting cable is standard Ethernet network cable
300−I−9010212−E−10/08.08
37/92
C−LRV lift control valveOperating controls and indicators
Description of function
S By pressing any of the keys 1 to 4, the C−DELCON switches into
parameterisation mode. No travel is possible; the green RUN LED on
the C−DELCON goes out
S Select the desired parameter using the ↑ or ↓ key
S Increase value with + key, decrease value with − key
S With ↑ or ↓ key, save the value and return to parameter selection
S With keys 1, 2, 3 or 4, do not save the value and return to parameter-
isation mode
S If no key pressed within 5 minutes, the DELCON automatically quits
parameterisation mode (changes to the currently displayed parameter
are not saved)
Important: In order to quit parameterisation mode:
S either press keys ↑ and ↓ simultaneously (changes to the cur-
rently displayed parameter are saved)
or
S unplug cable and wait for about 3 seconds (changes to the cur-
rently displayed parameter are NOT saved)
C−DELCON will return to RUN mode.
300−I−9010212−E−10/08.08
38/92
C−LRV lift control valveOperating controls and indicators
Password
The C−DELCON’s parameters and functions can be password−protected.
The password consists of four numbers. Password 0000" means that
password protection is not activated (this is the factory setting).
The password is entered one number at a time:
S Increase the value with the + key, decrease it with the − key
S With ↑ or ↓ key, change to the adjacent number
S Press ↑ and ↓ keys simultaneously to save the number
If a password has been set, the user must login in order to change parameters. The user logs in by entering the password. The user can logout
at any time, but will be logged out automatically after 8 hours at the
latest.
Important: If an attempt is made to change a password−protected parameter, the message not allowed" is displayed.
Important: If the power supply unit is wired into the safety circuit, the
user is not logged out automatically
300−I−9010212−E−10/08.08
39/92
C−LRV lift control valveOperating controls and indicators
e.g.
K1−K811000000
C: +3.45F: +4.18
e.g.
Fast speed ^
7.50 V
e.g.
1) Err:SIU−1
1x51965 h
Display during travel
S 1st line: status of command inputs K1 to K8
0:no command
1:command is present
S 2nd line: existing control voltage (C) and
feedback value (F) in volts
Display during parameterisation
S 1st line: parameter name
S 2nd line: value of parameter, including unit
Fault code
S 1st line: fault memory read−out, fault
description
S 2nd line:total number of occurrences of this
fault; last occurrence was at operating
hours h
300−I−9010212−E−10/08.08
40/92
C−LRV lift control valveOperating controls and indicators
3.4WinDelta32 − PC program
Software, adapter and cable can be ordered as Part No. 7010867
The software can be downloaded free of charge from:
http://www.bucherhydraulics.com
3.4.1General description
Parameterisation
S C−DELCON parameters can be read off and set via PC
S Parameter sets can be saved
S Comments can be added to parameter sets
S Print function
Display of curves
S Curves (demand signal / feedback value / control voltage) displayed
in real time
S Display of commands K1−K8
S Zoom function / Print function
300−I−9010212−E−10/08.08
41/92
C−LRV lift control valveOperating controls and indicators
3.4.2PC requirements
S Operating system:
Windows 95/98/ME/NT/2000/XP/Vista
S Processor: 133 MHz or faster
S RAM: 32 MByte
S Free hard disc space: min. 10 MByte for the program and min. 5
MByte for saving curves
S Serial port (RS232, 19200 Baud)
3.4.3Installation on PC / Laptop
Important: Please read the following installation instructions carefully
and follow the recommended steps!
If an old version of WinDelta32 is already installed on your computer,
carry out the following steps before installing the new version:
1.Start the old version of WinDelta32
2.In the Options/Configuration menu, open the Serial Port page
I Note the COM port displayed to the right of Default (e.g. COM1).
If you want to keep the parameter sets stored with the old version of
WinDelta32:
3.Select the menu Parameters/LRV and export all existing parameter
sets (click Export => All parameter sets). Save the file to the
folder C:\Temp (for example under the name Para_LRV.prm).
4.Close the window
5.Select the menu Parameters/VF−LRV and export all existing parameter sets (click Export => All parameter sets). Save the file to
the folder C:\Temp (for example under the name
Para_VFLRV.prm).
6.Close the window
300−I−9010212−E−10/08.08
42/92
C−LRV lift control valveOperating controls and indicators
Removing the old version:
7.Exit and close all programmes
8.Remove the old version of WinDelta32 (refer to the Windows help
for information about how to remove a programme)
Installing the new version (the following steps may take a few minutes):
1.Navigate to the installation file Install_WinDelta32_1pXX_EN.exe
(XX = programme version) either by clicking the Windows Start but-
ton and selecting Run then Browse, or by using the Windows Explorer
2.Double−click the installation file Install_WinDelta32_1pXX_EN.exe .
After a few moments, an installation dialog will be displayed.
3.Click the button Next (or Install / Finish) until the installation is terminated. A shortcut will automatically be placed on the desktop.
Configuring WinDelta32:
1.Start the new programme
2.To determine the serial port used for data communication between
the WinDelta32 programme (PC) and DELCON (electronics card),
in the menu Options / Configuration, call up the Serial Port page,
select the port you wrote down or a port from the list of available
ports and check the box Default in order to store the current settings.
3.Open the window Curves / Collect. If the temporary file Data-File.dat includes more than 200 curves, these curves will be saved
automatically to a file named YYMMDDHHMM.dat (with YY=Year /
MM=Month / DD=Day / HH=Hour / MM=Minute) and a new empty
file will be opened.
300−I−9010212−E−10/08.08
43/92
C−LRV lift control valveOperating controls and indicators
If you wish to reuse the parameter sets that you previously exported:
1.Select the menu Parameters/LRV and import (click Import => Allparameter sets) the stored file (e.g. the file Para_LRV.prm from
the folder C:\Temp)
2.Click the button (Refresh data)
3.Close the window
4.Select the menu Parameters/VF−LRV and import (click Import =>All parameter sets) the stored file (e.g. the file Para_VFLRV.prm
from the folder C:\Temp)
5.Click the button (Refresh data)
6.Close the window
Important: Refer to the integrated on−line help (Menu Help / Contents
and Index / Contents / WinDelta32 / Settings) for further information
about settings.
300−I−9010212−E−10/08.08
44/92
C−LRV lift control valveOperating controls and indicators
3.4.4Connect DELCON to PC / Laptop
Possibilities for connecting DELCON to PC / Laptop
Never connect DELCON to an Ethernet port!
300−I−9010212−E−10/08.08
45/92
C−LRV lift control valveOperating controls and indicators
Connecting to serial port using Bucher adaptor
Connecting to USB port using a USB−RS232 converter (with Bucher
adaptor)
300−I−9010212−E−10/08.08
46/92
C−LRV lift control valveInstallation and commissioning
4Installation and commissioning
4.1Installation
Orientation of the ball−valve outlet
As standard, the ball−valve outlet is rear−facing (code H)
Alteration to left (L) or right (R) is possible.
Important: the ball−valve outlet must not be turned to a new position
unless the hose is first disconnected.
Reorienting the ball−valve outlet
1.Unscrew cap screws on head of valve
2.Remove the screws
Attention
Risk of damage to the flow−rate
When orienting the ball−valve outlet, never lift up the head of the valve.
3.Turn head of valve to desired ball−valve position
4.Insert the cap screws and tighten them.
I Tightening torque forC−LRV 175 = 25 Nm
C−LRV 350 = 50 Nm
C−LRV 700 = 80 Nm
5.Check the mechanical null point
I Readjustment may be necessary (see Page 60, Section 4.3.10)
The ball−valve outlet is now correctly oriented
300−I−9010212−E−10/08.08
47/92
C−LRV lift control valveInstallation and commissioning
4.2Assembly
4.2.1Hose or pipe
Contamination in the line
Contamination adversely affects the valve’s function. This can lead to
a dangerous system condition.
Preventive measures:
S Clean the hose or pipe before fitting it
S Leave sealing caps/plugs in place until assembly
S Check that all fittings are assembled correctly
4.2.2Power supply unit
Caution
Feedback cable
⇒ Page 31
Terminals X3
1
300−1−10009293
Danger
Dangerous voltage
Can cause serious injuries or death.
Before fitting the power supply unit, disconnect all power to the control
cabinet.
S The NTA−2 power supply unit must be installed in the control system
cabinet
S There must be no voltage at the power supply unit when working on
its connections or exchanging the C−DELCON.
Important: Set jumper JP2 to connect earth and signal−GND.
Screwless terminals
Feedback cable plug
2
1
2
S Quick to wire up, thanks to screwless terminals
S Only one core per terminal point (if neces−sary,
combine two cores in a terminating sleeve)
S Insert a screwdriver as far as the stop (1)
S Open the clamp spring by gently pressing down
or turning the screwdriver, and insert the core (2)
into the terminal point
S Remove the screwdriver − the conductor is now
safely clamped
S Use a size 0 screwdriver (2.5 mm)
300−I−9010212−E−10/08.08
Important: to prevent damage, the NTA−2 must only be wired when the
C−DELCON card has been removed.
48/92
C−LRV lift control valveInstallation and commissioning
4.2.3Wiring the power supply unit
Legend
1
Fast UP
2
Slow UP
3
Fast DOWN
4
Slow DOWN
5
Inspection speed
21
Speed reduction
22
Speed reduction
23
Speed reduction
6a/6b
Common
7
DOWN solenoid
8
UP solenoid
9
Stabilised voltage supply
+15V
10
Feedback signal
(input)
11
Stabilised voltage supply
−15V
12
GND, test/measurement
20
−24 V emergency power
supply
19
+24 V emergency power
supply
* When contact K5 closes, the C−DELCON’s two "fast"
speeds drop to a preset percentage of their nominal
values. The setting is adjustable between 20−80%
LegendA
300−I−9010212−E−10/08.08
C−DELCON
B
NTA−2
C
C−LRV
D
Control cabinet (customer’s)
300−1−10009300
** When contacts K6, K7 or K8 close, the C−DELCON´s
two "fast" speeds drop to a preset percentage of their n
ominal values. The settings are adjustable between
20−100%
K1−K8, potential−free contacts or semiconductors
R1+R2 as per EN81−2, 12.4.1/12.4.2
E
DOWN solenoid
F
UP solenoid
G
SIU−1 demand/feedback monitoring
SIU−4 v ≤0.3m/s
49/92
C−LRV lift control valveInstallation and commissioning
4.2.4Electrical emergency−lowering 2 x 24 VDC
Important: the operator must undertake any further measures required
to ensure short−circuit and overvoltage protection.
If a mains (line) failure occurs, the power supply unit can be powered by
an external battery supply (2 x 24 V) through terminals 12, 19 and 20.
S Relay R
mally−closed contacts R
I Inputs 19 and 20 have diode−protection from polarity reversal or feed-
S The lift can be lowered to a predefined stopping position by means of
"Slow DOWN" or auxiliary speed K6...K8 (travel signals are generated by the lift control system).
Important: only possible with 2 x 24V (or 4 x 12V) batteries
drops out when there is a power failure and the two nor-
N
back to the battery
−1
N
and R
−2
connect to the battery
N
Slow DOWNAuxiliary speed
K6/K7/K8
Legend1 NTA−2 power supply unit
2 Supplied by customer
3 DOWN solenoid
21/22/23
300−I−9010212−E−10/08.08
50/92
C−LRV lift control valveInstallation and commissioning
4.2.5Electrical emergency−lowering 1 x 12 or 1 x 24 VDC (option)
Do not activate the electrical emergency−lowering valve unless the
safety circuit is closed!
In an emergency the lift car can be lowered by operating the emergency
lowering valve electrically.
Depending on the external battery voltage, 12V and 24V spool valve
versions are available.
Wiring diagram
Warning
12 / 24 VDC
Setting the lowering speed
1.Energize emergency−lowering valve (1)
I The car sinks
2.Slacken locknut
3.Turn adjusting screw (2) counterclockwise (faster) or clockwise
(slower)
4.Re−tighten locknut
2
1
300−I−9010212−E−10/08.08
Legend1 Electrical emergency−lowering valve
2 Adjusting screw
51/92
C−LRV lift control valveInstallation and commissioning
4.3Commissioning/settings
4.3.1Checking the test numbers
S The valve test number is stamped on the body (below the manual
emergency−lowering valve) ⇒ 1.2.2.
S The C−DELCON test number is on a label on the connector ⇒ 1.4.
Important: always quote the test number when making enquiries. This
makes it easier for the factory to help you!
Important: the test numbers on the C−DELCON and the valve must be
the same to avoid the need for resetting.
4.3.2Checking the minimum static pressure
To check the minimum static pressure (with empty car):
1.Open pressure gauge shut−off valve
2.Read the minimum static pressure on the pressure gauge
3.Compare minimum static pressure on rating plate with actual
minimum static system pressure on the pressure gauge
I ⇒ Page 9, Section 1.2.1, Item (4)
4.If the difference is more than 5bar, the maximum pressure setting
must be increased by the amount of the difference (⇒ 4.3.4)
I Bypass pressure too high: car travels past landing
I Bypass pressure too low: UP starting jolt
The minimum static pressure shown is correct
Important: if the difference is more than > 10bar, please contact
Customer Services.
300−I−9010212−E−10/08.08
52/92
C−LRV lift control valveInstallation and commissioning
4.3.3The bypass pressure setting
Important: the car must be empty
Setting the bypass pressure with the Handterminal
(car out of sight)
1.Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting
I ⇒ Page 71, Section 5.1.4.2
2.Remove the UP solenoid plug (10)
3.Slacken the locknut for bypass−pressure setscrew (2)
9.With motor running, slowly turn bypass−pressure setscrew (2)
clockwise until pressure is approx. 3bar below the min. static
pressure previously read
10. Tighten the locknut for bypass−pressure setscrew (2)
11. Cancel the UP command
12. Refit the UP solenoid plug (10)
13. Open the ball valve.
14. Reset the "SIU Type" parameter in the C−DELCON to the setting
noted down in Step 1.
The bypass pressure is now set
300−I−9010212−E−10/08.08
54/92
C−LRV lift control valveInstallation and commissioning
Setting the bypass pressure with the car in sight
1.Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting
I ⇒ Page 71, Section 5.1.4.2
2.Remove the UP solenoid plug (10)
3.Slacken the locknut for bypass−pressure setscrew (2)
SIU−1: if the value of the demand/feedback difference becomes too
large, the lift is stopped
S When the demand/feedback difference is exceeded, the LED on the
C−DELCON lights and the relay activates
S The response difference can be set with the Handterminal or PC
software
300−I−9010212−E−10/08.08
56/92
C−LRV lift control valveInstallation and commissioning
4.3.6Speed−monitoring in the door zone, SIU−4
The SIU−4 function monitors the speed in the door zone and during
relevelling. If the speed setting is exceeded, the lift is stopped (per EN
81−2, max. 0.3 m/s)
S When the speed setting is exceeded, the relay activates
S The speed can be set with the Handterminal or PC software
4.3.7The inspection−travel speed setting
To set the inspection−travel speed, see the Options menu ⇒ 5.1.4.2, the
parameter "Inspection speed".
300−I−9010212−E−10/08.08
57/92
C−LRV lift control valveInstallation and commissioning
4.3.8Positioning the shaft switches for the deceleration distance
The spacing of the shaft switches depends on the car speed
⇒ 4.3.9
Z
ZY
X
Time t
YZ
ZX
Aux. speed e.g.
v=50%
v=100%v=100%
v=50%
X Deceleration distance (shaft switches) for maximum speed
Y Deceleration distance (shaft switches) for auxiliary speed (for example, 50% of
maximum speed; adjustable in C−DELCON from 20–100%)
Z Stop−switch before landing (20–30mm) (soft−stop travel is controlled by the
C−DELCON)
300−I−9010212−E−10/08.08
58/92
C−LRV lift control valveInstallation and commissioning
4.3.9Required deceleration distance
Guidelines for positioning the deceleration switches.
Examples1Deceleration distance "X" for direct (1:1) drive
e.g.: v=0.4m/s → x1=0.4m
2Deceleration distance "X" for indirect (2:1) drive
e.g.: v=0.63m/s → x2=0.71m
3Deceleration distance "Y" for direct (1:1) drive (auxiliary speed)
e.g.: v=0.4m/s : 2 = 0.2m/s → y3=0.2m
4Deceleration distance "Y" for indirect (2:1) drive (auxiliary speed)
e.g.: v=0.63 m/s : 2 → y4=0.32 m
LegendA
Direct drive (1:1)
B
Indirect drive (2:1)
C
Car speed [m/s]
D
Distance of deceleration switches before landing [m]
300−I−9010212−E−10/08.08
59/92
C−LRV lift control valveInstallation and commissioning
4.3.10Setting the mechanical null point
The null point is factory−set.
With Handterminal, see
Page 37, Section 3.3
This can be checked with the Handterminal (or PC). If, on commissioning, the reading is outside the range ±0.05V, then the null point must be
reset.
Setting the null point
1.Close the ball valve
2.Connect the Handterminal to the C−DELCON and press key 3 on
Handterminal => null point or feedback value will be displayed
3.Using a 3mm Allen key, slacken the adjusting/clamp screw (14) a
little
4.Remove Allen key (it has a magnetic influence)
5.Hold the feedback sensor by the plug and move it axially until the
feedback reading is less than ±0.05V
6.Tighten adjusting/clamp screw (14)
7.Return to RUN mode by pressing the ↑ and ↓ on the Handterminal
simultaneously.
8.Open the ball valve.
The null point is now correctly set
Checking null point after maintenance work
The error memory of the C−DELCON should be checked each time
maintenance work is carried out. If there is a warning with regard to nullpoint deviation or, if the actual value for the null point is outside the
range ±0.2V, then the null point has to be reset.
300−I−9010212−E−10/08.08
60/92
C−LRV lift control valveInstallation and commissioning
4.3.11Pilot filters
Filter−strainers are positioned upstream of the lowering and lifting valves
in accordance with the international standards for lifts. The filters are
easily accessible from outside the valve.
Contamination in valve (filter)
This can cause leakage.
Never operate the lift without the pilot filter installed.
Carry out regular maintenance as per maintenance plan ⇒ Page 89
Cleaning the pilot filter
1.Switch main switch OFF
2.Close the ball valve
3.Press emergency−lowering lever (vents pressure in the valve)
I the pressure in the valve is vented
Caution
Note the maintenance
plan on Page 89
4.Unscrew the filter screw
I with a 22 A/F open−ended spanner
5.Remove filter
6.Clean or exchange the filter
7.Insert the filter
8.Screw in the filter screw
9.Open the ball valve.
10. Switch main switch ON
The pilot filter is now clean
300−I−9010212−E−10/08.08
61/92
C−LRV lift control valveInstallation and commissioning
4.3.12The pipe−rupture valve test
A precondition for testing the pipe−rupture valve is that the lift must be
working properly, without any faults.
Uncontrolled descent (free fall)
People may suffer injury and materials may be damaged.
Before testing the pipe−rupture valve, make sure that there are no
people or materials in the lift shaft.
Uncontrolled descent (free fall)
Can cause damage to the support frame and car.
The elevator car must come to rest within 3 ... 5 metres.
If it does not, immediately switch off the main switch for the lift control
system (and repeat the test).
Danger
Attention
Preparing to test the pipe rupture valve
1.Load the car to half of its rated capacity
2.Drive the car to the top floor
Important: do not carry out the test if the car is too close to the lowest
floor.
3.Prepare the handterminal or an computer with WinDelta32
300−I−9010212−E−10/08.08
62/92
C−LRV lift control valveInstallation and commissioning
Testing the pipe−rupture valve (for C−DELCON software version
2.110 or higher)
1.On the Handterminal, select the Pipe rupture" function in the Information (4) menu under Commands"
I ⇒ Page 76, Section 5.1.4.4
2.Press and hold the + key on the Handterminal; the "DOWN" LED on
the C−DELCON will start to flash
3.Send DOWN command
4.Wait until the car is accelerating
5.When the triggering speed is reached, the pipe rupture valve closes
and travel stops.
Important: Releasing the + key on the Handterminal stops the travel,
and the maximum feedback value is displayed. If the DOWN command
is still present on quitting the menu, travel will resume normally.
Important: after the pipe rupture valve has closed, pressure can again
build up between the C−LRV and the pipe−rupture valve, causing the
pipe−rupture valve to re−open. If the pipe rupture valve is to remain
closed for a long period, this pressure must be vented through the manual emergency−lowering valve on the C−LRV.
If the hose/pipe is actually burst, the pipe−rupture valve will always
remain closed.
Very slight leakage through the pipe−rupture valve is permissible.
The pipe−rupture valve has been successfully tested
6.In order that the pipe rupture valve re−opens and the elevator is
ready for service: build up pressure using the hand pump or carry
out an upwards travel.
The system is once again ready for use
300−I−9010212−E−10/08.08
63/92
C−LRV lift control valveInstallation and commissioning
Testing the pipe−rupture valve (up to C−DELCON software version
2.100 or with WinDelta32 PC program)
1.Set the "SIU Type" parameter in the C−DELCON to "Off"
I make a note of the existing setting
I ⇒ Page 71, Section 5.1.4.2
2.Set the "Demand val. red." parameter in the C−DELCON to "Off"
I make a note of the existing setting
I ⇒ Page 71, Section 5.1.4.2
3.Send a "Down" command to the controller
4.Wait until the car is accelerating
5.Remove the feedback plug (25) from the Hall sensor
6.When the triggering speed is reached, the pipe rupture valve closes
and travel stops.
Important: after the pipe rupture valve has closed, pressure can again
build up between the C−LRV and the pipe−rupture valve, causing the
pipe−rupture valve to re−open. If the pipe rupture valve is to remain
closed for a long period, this pressure must be vented through the
manual emergency−lowering valve on the C−LRV.
If the hose/pipe is actually burst, the pipe−rupture valve will always
remain closed.
Very slight leakage through the pipe−rupture valve is permissible.
The pipe−rupture valve has been successfully tested
7.Cancel the DOWN command
8.Refit the feedback plug (25) to the Hall sensor
9.Reset the "SIU Type" parameter in the C−DELCON to the setting
noted down in Step1.
10. Reset the "Demand val. red" parameter in the C−DELCON to the
setting noted down in Step 2.
11. In order that the pipe rupture valve re−opens and the elevator is
ready for service: build up pressure using the hand pump or carry
out an upwards travel.
Flow rate UP:
120[l/min] / 29.1[l/min] = 4.12V Fast UP
Flow rate DOWN:
150[l/min] / 29.1[l/min] = 5.15V Fast DOWN
→ Settings in the C−DELCON
C−LRV 175 − 120 / 150 − 21 / 45
R 250 − K 251 / 6−80 / 55 bar
* These values are taken from the above table.
300−I−9010212−E−10/08.08
79/92
C−LRV lift control valveOperation
5.3Faults / Fault−finding
5.3.1Check list for fault correction
FaultCauseCorrective actionPage (Chapter)
No UP travelS Motor / pump not runningS Check connection
S Wiring faultS Check wiring49 (4.2.3)
S Electrics − control cabinet
S Motor running on 2
phases
S Motor− and/or oil−PTC
thermistor has operated
S Electronic soft−starter not
connected properly
S UP solenoid not
energised
S Contacts K1/K2 and/or
R2 not closed
S SIU (demand/feedback
monitoring) is actuated,
LED SIU−1" on C−DELCON lights up
S DOWN solenoid is
energised
S UP pilot filter dirtySClean filter. If necessary,
S Check power supply49 (4.2.3)
S Connect in accordance
with diagram
S Check solenoid output
and R2
S Check connections after
power supply unit
S Check control of power
supply unit
S Check mechanical null
point
S Correct the wiring fault
S NTA−2, terminals 7+8
crossed?
filter oil
49 (4.2.3)
60 (4.3.10)
49 (4.2.3)
61 (4.3.11)
Car does not reach
speed
Cannot lift maximum loadS Pressure−relief valve set
UP−travel starting
problems
Car does not reach
storey
S Pressure−relief valve set
too low
too low
S Overload switch DZ has
activated
S Leakage between pump
and valve
S Jolt when startingS Reset bypass−pressure
S Travels UP without any
command
S Oil level in power unit is
below minimum
S Leakage: valve − cylinderSCheck for leakage
S Check pressures/consult
factory
S Check pressures/consult
factory
S Reduce the load
S Eliminate the leakage
setscrew Á on the valve
S Bypass−pressure
setscrew Á on the valve
is set too high. Reset it.
S Top−up when car is at
lowest landing
56 (4.3.4)
56 (4.3.4)
53 (4.3.3)
53 (4.3.3)
52 (4.3.2)
300−I−9010212−E−10/08.08
80/92
C−LRV lift control valveOperation
S Mechanical null point is
displaced
S Plunger cylinder is at
end−stop
S Extension of telescopic
cylinder is not
synchronised
S Ratio of top− to
bottom−overtravel is
wrong
Page (Chapter)Corrective actionCauseFault
S Check60 (4.3.10)
S Cylinder pillar is too short
S Check cylinder stroke
S Check cylinder stroke
S Telescopic cylinder is
sitting too low; raise it
S 2−stage: 1/2 bottom / 1/
top
S 3−stage: 1/3 bottom / 2/
See document
2
300−P−9010023
3
top
Car overshoots landing
during UP travel
S Deceleration switches
wrongly positioned
S Mechanical null point is
displaced
S Deceleration time is too
short
S Bypass pressure set too
high
No DOWN travelS Car overloaded, pressure
switch has activated
S Contacts K3/K4 and/or
R1 not closed
S No current from power
supply unit
S UP solenoid is energisedS Correct the wiring fault
S DOWN solenoid not
energised
S Position correctly58 (4.3.8)
S Check60 (4.3.10)
S Increase deceleration in
C−DELCON
S Reset it
S Reduce the load
S Check the safety relay
S Test the voltage;
49 (4.2.3)
exchange unit
S Exchange solenoid plug
on valve
S Check voltage at terminal
7
S Check connection from
terminal 7 to DOWN
solenoid (safety relay R1)
Lift starts DOWN, then
stops
S SIU (demand/feedback
monitoring) is actuated,
S C−DELCON settings are
too low
LED SIU−1" on C−DELCON lights up
S Acceleration is too highSDecrease the
acceleration setting
S Fast DOWN set too high
S Reduce Fast DOWN79 (5.2)
in C−DELCON
S Flow rating of
S Reduce Fast DOWN
pipe−rupture valve too low
DOWN speed is too slowS Car is too lightSAdd weight to the car
300−I−9010212−E−10/08.08
81/92
C−LRV lift control valveOperation
S Hydraulic line to the
cylinder is too small
S Oil is too coldS Use multigrade oil
S Too much friction in
system
Page (Chapter)Corrective actionCauseFault
S Fit larger line
S Install oil heater
S Provide parking circuitry
S Align cylinder and rails
Car overshoots landing
during DOWN travel
Car overshoots landing
during DOWN travel
Leakage in hydraulic
system (test only when
oil is cold)
S Deceleration switches
S Set as per page(s)58 (4.3.8)
wrongly positioned
S Safety relay R1 drops out
S Set as per page(s)23 (1.4.4)
too early, or without a
delay
S Deceleration time too
short
S Deceleration switches in
S Increase deceleration in
C−DELCON
S Set as per page(s)58 (4.3.8)
shaft wrongly positioned
S Feedback sensor (Hall
sensor) GND not
S Connect GND to terminal
12
connected
S Demand values set too
S Set as per page(s)79 (5.2)
high
S DOWN pilot valve
S Clean pilot valve61 (4.3.11)
contaminated
S Oil is too coldS Consider installing oil
heater; providing parking
circuitry
S Pressure drop in approx.
S None, valve is leak−tight!
3 minutes is not more
than 5bar (with ball valve
closed)
49 (4.2.3)
300−I−9010212−E−10/08.08
82/92
C−LRV lift control valveOperation
S DOWN pilot pin is bentS Exchange DOWN pilot
Attention
The UP and DOWN
spools are not
interchangeable!
S Emergency−lowering
valve leaking
S Check valve is leakingS Replace seal11 (1.3)
S Pressure falls rapidlyS DOWN spool leaking;
valve
S Operate it several times
during UP command
clean seat and re−lap
Page (Chapter)Corrective actionCauseFault
36 (3.1)
Car sinks (with ball valve
closed)
S Oil is just cooling down!S None
S Leak in cylinder or
connecting line
S Check/tighten connecting
hose. Renew seals, if
necessary
300−I−9010212−E−10/08.08
83/92
C−LRV lift control valveOperation
5.3.2Fault description
Display on
Handterminal
CauseRemedy
Err:NoneNo fault
Warn:
Board−T.
Temperature of C−DELCON exceeds 70°C
S Ambient temperature is too highS Lower the ambient temperature
S Poor ventilation in control cabinetS Improve control cabinet ventila-
Err:
Input−V.+
Positive voltage from power supply unit is outside of +17V...+41V
S Positive voltage is too low or too
high
S Incorrect power supply unit for
the C−DELCON (transformer
code 280−G21 /281−G21 /
282−G21
Err:SIU−1Demand/feedback difference too
large
S SIU demand/feedback monitoring
(LED lights up)
Further details (code,
see 5.3.3)
Warning message, not a fault102, 301,
403
tion
103, 104,
201, 301,
S Check the incoming mains volt-
403
age
S Choose the correct power supply
unit to suit the mains voltage
S Replace the power supply unit
104, 105,
107, 202,
S The C−DELCON settings are too
301, 404
low
Err:
Command
Err:
Zero−point
Err:
WrongSW
Info:
New vers
Info:
Default
S Acceleration is too highS Decrease the acceleration setting
S Fast DOWN is set too high on
S Decrease the fast DOWN setting
the C−DELCON
S Flow rating of pipe−rupture valve
S Decrease the fast DOWN setting
is too low
Incorrect combination of commands
S e.g. Up and Down simultaneously S Ensure correct commands are
103, 104,
105, 201,
301, 403
signalled
Null point outside of ±1.00V103, 105,
S Mechanical null point is wrongly
set
S Reset the mechanical null point
201, 301,
402
S Bypass pressure is too highS Set the bypass screw on the
valve correctly (unscrew it
slightly)
Software fault106, 201,
S Wrong EPROM installed
(software initialisation fault)
S Change the EPROM
S Replace the C−DELCON
301, 403
New software version installedInformation106, 301,
S New EPROM has been installedS No fault, just information
401
Factory settings loadedInformation102, 301,
S The default factory settings have
S No fault, just information
401
been loaded
300−I−9010212−E−10/08.08
84/92
C−LRV lift control valveOperation
Display on
Handterminal
Warn:
0 Point
Err:
0−Point+
Err:
0−Point−
Warn:
A0 Point
Further de-
RemedyCause
tails (code,
see 5.3.3)
Null point outside of ±0.20VWarning message, not a fault103, 301,
S Mechanical null point is wrongly
S Reset the mechanical null point
401
set
S Bypass pressure is too highS Set the bypass screw on the
valve correctly (unscrew it
slightly)
Automatic null point adjustment
outside of +1.00V
S Bypass pressure is too highS Set the bypass screw on the
103, 105,
201, 301,
402
valve correctly (unscrew it
slightly)
Automatic null point adjustment
outside of −1.00V
S Emergency lowering valve actu-
103, 105,
201, 301,
402
ated
S Leakage
Null point outside of 1.00V during relevelling
Warning message, not a fault103, 105,
301, 401
Err:
Unknown
Warn:
Demand
Err:
Input−V.−
S Mechanical null point is wrongly
set
S Bypass pressure is too high
S Emergency lowering valve actu-
S Reset the mechanical null point
S Set the bypass screw on the
valve correctly (unscrew it
slightly)
ated
Unknown fault
S Internal software faultS Upgrade/reinstall software
Automatic demand signal reduc-
Warning message, not a fault104, 107,
tion was invoked, maximum
speed was reduced for this travel
S Maximum speed too highS Decrease the maximum speed
S Oil temperature too lowS Install an oil heater, or use
thinner oil
S Too heavy a load with hot oilS Install an oil cooler, do not over-
load the car
Negative voltage from power supply unit is outside of −17V...−34V
S Negative voltage is too low or too
high
S Unsuitable power supply unit for
the C−DELCON (Transformer
code:
S Check the incoming mains volt-
age
S Choose the correct power supply
unit to suit the mains voltage
S Replace the power supply unit
280−G21/281−G21/282−G21)
301, 401
103, 104,
201, 301,
403
Info:
Cmd−Dir.
300−I−9010212−E−10/08.08
Command direction changed during travel
S Fault on K1 to K4
(Terminals 1 to 4)
Information103, 104,
105, 301,
S Cure the cause of the fault
403
85/92
C−LRV lift control valveOperation
Display on
Handterminal
Warn:
Bypass pre
Warn:
Leakage
Warn:
Timeout
RemedyCause
Automatic null point adjustment
Warning message, not a fault103, 105,
outside of +0.20V
S Hand pump activated
S Bypass pressure is too highS Set the bypass screw on the
valve correctly (unscrew it
slightly)
Automatic null point adjustment
Warning message, not a fault103, 105,
outside of −0.20V
S Emergency lowering valve actu-
ated
S Leakage
Relevelling up/down takes longer
Warning message, not a fault104, 105,
than 2 minutes
S Emergency lowering valve actu-
ated
Further de-
tails (code,
see 5.3.3)
301, 401
103, 105,
301, 401
301, 401
203, 301,
401
300−I−9010212−E−10/08.08
86/92
C−LRV lift control valveOperation
5.3.3Code for further details
CodeMeaning
Monitoring
101Constantly
102At standstill
103At start of travel
104During travel
105Not monitored during inspection travel
106When the program is started
107Dependent on parameterisation
Effect
201Travel is disabled
202Travel is aborted (relay is opened)
203Travel is aborted (relay is NOT opened)
204Travel is aborted (dependent on parameterisation, relay may be opened)
Save
301If at standstill, immediately; if travelling, at end of travel
302Delay of 2s
303Is not saved during inspection travel
Reset
401Immediately (save only)
402Delay of 2
403When the cause has been removed
404If the "Relay function" setting is "only SIU": reset operation after there is no longer any travel
command. Otherwise: delay of 2s
300−I−9010212−E−10/08.08
87/92
C−LRV lift control valveOperation
300−I−9010212−E−10/08.08
88/92
C−LRV lift control valveMaintenance
6Maintenance
6.1Maintenance schedule
This service plan is just a guide. Adjustments or changes should be undertaken by the installation company.
Work to be carried outTime
Before commission-
ing
ValveCheck internal leakageXXX
First service after
commi−ssioning, not
During commissioning
later than after 3 months
At every service, at
least 2 x per year
Annually
After 5 years
After 10 years
Pipe
Hose
Check external leakageXXX
Check the maximum pressure setting
(pressure−relief valve / screw)
Check mechanical null point (Hall sensor)XXX
Clean pilot filtersXXX
Clean main filterX –– X
Renew O−rings
(when valve is dismantled, or as required)
Check for leakageXXXX
Carry out checks in accordance with the
Installation and Maintenance Guide
XX
XXXX
X –– X
300−I−9010212−E−10/08.08
89/92
C−LRV lift control valveMaintenance
6.2Operating materials and aids
Hydraulic oil (code)Viscosity
[mm2/s] (cSt)
Permissible
temperature range
to DIN 51525to ISO 6074at 40°Cmin. °Cmax. °C
H−LP 32ISO VG 3232142
H−LP 46ISO VG 46 *46850
H−LP 68ISO VG 68681559
H−LP 100ISO VG 1001002160
Shell Tonna S3232142
Shell Tonna S68681570
* This oil can be used in most applications. For frequently−used passenger lifts, the thicker VG 68 oil should be used.
The type of oil actually used to fill the system must be recorded by the lift manufacturer in the designated field on the
nameplate of the submersed motor/pump power unit.
Tested and approved hydraulic fluids with
biodegradable characteristics
TypePanolin HLP
32/46 Synth
HF−E 46Rivolta
S.B.H.23
Avia Syntofluid
F 32 or 46
Megol
HEES46
Supplier
Viscosity 40°C
mm@/s
(cSt)
Panolin AH
Medetswil (CH)
Shell
Bremer+Leguil
GmbH
Avia
Avia−Kühmichel
32/46464632/4648
Liqui Moly GmbH
Ulm (D)
BaseEsterEsterEsterEsterEster
Water−hazard classnwg/11nwgnwg1
Biodegradability>90%>90%>97%>90%>90%
Flashpoint°C240210240310320
(Water hazard classified in accordance with the German standard dated 1999)
nwg = not hazardous to waters
300−I−9010212−E−10/08.08
90/92
C−LRV lift control valveMaintenance
6.3Installation guide for DOWN pilot valve
Exchanging the DOWN pilot valve
1.Switch main switch OFF
2.Close the ball valve
3.Vent all pressure in the valve block (manual lowering valve)
4.Remove solenoid and the A and C parts
5.Assemble the A parts and insert them in the bore
6.Insert O−ring (B)
7.Assemble the C parts, then insert the unit in the bore. Make sure
that the stem of the cone (3) is clearly engaged in the spring
8.Insert O−ring (D) and fit the solenoid
I If needle (1) slips out of the bush (2), start again from step 7.
9.Open the ball valve.
10. Switch main switch ON
The new DOWN pilot valve is ready for use
300−2−10006634
300−I−9010212−E−10/08.08
91/92
C−LRV lift control valveMaintenance
6.4Customer service information
World WideBucher Hydraulics AG
Industriestrasse 15
CH−6345 Neuheim
Tel.: +41 41 757 03 33
Fax: +41 41 757 03 19
elevator@bucherhydraulics.com
Germany
Service South−East
Germany
Service North−West
Germany
Spare Parts Center
Bucher Hydraulics AG
Jürgen Zehrer
Franz Schubert Strasse 13
D−90768 Fürth