Bticino HD4891, HC4891, HS4891, L4891, N4891 Technical Sheet

...
Page 1
Description
Local Display is a device that gives the possibility of 4 home automation functions by means of simple and intuitive icons displayed on a 1.2” OLED display with touch screen technology. It can be used to manage the temperature control, sound system, energy management, and scenario functions. The back of Local Display has a USB socket, which can be used to connect the device to a PC, to update the configuration, the set of characters, and the icon, as well as the firmware.
HD4891 - HC4891 - HS4891
L4891 - N4891 - NT4891Local display
1
Technical data
- Power supply from BUS: 18 – 27 Vdc
- Stand-by Absorption: max 10 mA @ 27 Vdc max 15 mA @ 18 Vdc
- Operating absorption: max 50 mA @ 27 Vdc max 70 mA @ 18 Vdc
- Operating temperature: 5 – 35 °C
- Size: 2 ush mounted modules
Conguration
Local Display may be configured in two ways:
- physical conguration, by connecting the congurators to the appropriate sockets. This mode gives the possibility of configuring with basic parameters only 1 function to manage, among the ones listed below. For the configuration of the advanced parameters use the TiLocalDisplay software.
Funzioni gestibili
- Scenario control
- Temperature control with external probe 3457
- Temperature control with probe HD/HC/HS4693, L4693, N4693, NT4693.
- Sound system
- Consumption display
- Load management
- Advances scenarios (with MH200N programmer installed in the system), to be configured using the software only
Front view
5
Rear view
Legend
1. OLED technology Touch Screen
2. Congurator socket
3. BUS clamp
4. Clamp for the connection of the external temperature probe
5. USB connector
2
3
4
Technical sheets - Automation MY HOME
BT00517-a-UK
1
Page 2
HD4891 - HC4891 - HS4891
L4891 - N4891 - NT4891
Installation
Local Display is installed using a traditional procedure, using a box, support, and AXOLUTE or LIVINGLIGHT cover plate; the device is not tted with a temperature probe. Therefore, it will not be necessary to comply with the probe installation requirements. The recommended installation height is 150 - 160 cm.
Local Display physical conguration
- Scenario control mode - FUN = 1
Thanks to this mode, it will be possible to manage and change 4 dierent associated scenarios of the F420 scenario module, and activate them by pressing one of the 4 icons shown on the display.
A Room 0 – 9, room of the scenario module
item
PL Light point 1 – 9, light point of the scenario
module item F420
MOD Mode 1 – 4, scenario number (*)
FUN Function 1
(*) Correspondence among the 4 icons and the numbers of the scenarios that can be saved in the F420 module
Configurator MOD Icon 1 Icon 2
1 Scenario 1 Scenario 2
2 Scenario 5 Scenario 6
3 Scenario 9 Scenario 10
4 Scenario 13 Scenario 14
Main functions that can be set using the Tilocal Display software
Main possible functions using the software:
- selection of the operating mode to set for the device, temperature control, scenarios, sound system, load management, consumption display.
- conguration of the settings of the probe and of its parameters;
- denition of the type of temperature central unit;
- parameters for the measurement of energy production, or consumption costs;
- conguration of the general device parameters;
- icon style denition.
scenario 1
scenario 2
1 2
Configurator MOD Icon 3 Icon 4
1 Scenario 3 Scenario 4
2 Scenario 7 Scenario 8
3 Scenario 11 Scenario 12
4 Scenario 15 Scenario 16
Scenario programmer
In order to program, change or cancel a scenario, it is necessary to enable the programming mode of the Module item F420 so that the status LED is green (press the
BT00517-a-UK
lock/unlock key on the Scenario Module for at least 0.5 seconds); continue with the following operations:
1) press one of the four control keys the scenario should be associated to for 3 seconds. The screen shows the name and icon of the selected scenario and
the programming bar, to indicate that the learning procedure has started If the device does not receive any input for 30 minutes from the start of the learning procedure, programming will automatically be interrupted;
2) set the scenario using the corresponding controls for the various Automation, Temperature control, Sound system, etc. functions;
3) conrm the scenario by quickly pressing the display
4) to change or create new scenarios to be linked to the other keys, repeat the procedure starting from point 1.
To call a set scenario just press its pushbutton on the control quickly.
MY HOME Technical sheets - Automation
2
scenario 3
scenario 4
3 4
NOTE: Once the operations have been performed lock the programming, pressing the lock/unlock pushbutton, of the senario module, for at least 0.5 seconds, so that the corresponding LED becomes red.
To delete a scenario, proceed as follows:
1) the scenario module must be enabled for programming.
2)
press the pushbutton of the scenario you want to cancel for at least 7 seconds The display will conrm that the scenario has been deleted and return to the main screen. To erase the entire memory keep the DEL pushbutton on the Scenario module pressed for 10 seconds, the yellow “reset scenarios” LED ashes quickly.
;
Page 3
HD4891 - HC4891 - HS4891
L4891 - N4891 - NT4891
– Sound system control mode - FUN = 2
With this mode, for the associated amplier the user can control the switching ON or OFF, the volume, the cycling through the sources, and their management (where allowed). Information on the currently active source is also displayed. In this mode the parameters that can be congured are the local address of the display (which must coincide with the A/Pf address, and the M1 mode of the associated amplier), and the name of the sources that can be controlled.
A Room 0 – 9, amplifier room PF Loudspeaker 1 – 9, Amplifier loudspeaker MOD Mode 0 – 8, Source switching ON (*) FUN Function 2
NOTA (*): If M=0, source 1 is switched on without first switching OFF the sources (follow-me mode).
Functions
A quick pressure of keys 5 and 7 will respectively switch ON and OFF the associated amplier. If the associated amplier is on, an extended pressure of keys 5 and 7 may be used to adjust the volume, the intensity of which will be displayed by means of an icon
5. A short pressure of keys 2 and 4, will respectively cycle through the sources installed in the system, and launch a control for the currently activ amplier is o and no source is on, the screen will not show any information. Press key 4 for 3 seconds to congure the alarm clock (see the user manual for details).
e source. If the associated
1
7
ON
RDS
6
5
Legend
1. Indication of the amplier status or radio frequency
2. Cycling of sources (radio/aux)
3. Active source indication
4. Change radio station
5. Associated amplier OFF and volume decrease
6. Volume level indication
7. Associated amplier ON and volume increase
106.70
OFF
2
2
3
4
Technical sheets - Automation MY HOME
BT00517-a-UK
3
Page 4
HD4891 - HC4891 - HS4891
L4891 - N4891 - NT4891
- Temperature control probe mode with external probe ­FUN = 3
Warning: the physical conguration can only be performed if the system includes a 99-zone temperature central unit.
An external temperature probe, item 3457, with the following characteristics, can be connected on the back of Local Display:
- 10 KΩ at 25 °C BETA 3435
- max. length of the connection 10 metres
Local Display shows the temperature value measured by the external probe, the set temperature value, and the local selector adjustment. The operations that may be performed by user are:
- variation of the temperature set using the local selector,
- FAN-COIL speed management,
- operating mode management.
ZA Zone address 0 – 9, Local Display address
ZB Zone address 1 – 9, Local Display address
MOD Mode 0 – 8, Slave probe number
FUN Function 3
temperature probe
BUS - SCS
For simple systems, where each zone controls at most one heating actuator and one air conditioning actuator, both of the ON/OFF type, and on a system with only one pump per function, the con guration of the system can be performed by simply connecting the con gurators that identify the address of the device and, in case of probe, indicate the number of slaves present.
1. Set temperature
2. Fan-Coil adjustment
3. Fan-Coil speed indication
4. Temperature variation indication
5. Fan-Coil operation indication
6. Change operating mode
7. Measured temperature
8. Decrease temperature
9. Operating mode indication
10. System status indication
11. Increase the temperature
BT00517-a-UK
A short pressure of keys 8 and 11 can be used to locally change the temperature by +/-3 °C, in relation to the settings received from the central unit. A short pressure of key 6 can be used to select the mode of operation, cycling through the OFF, antifreeze/ thermal protection, and automatic statuses respectively. Each mode of operation is identi ed by a di erent icon. A short pressure of key 2 will force the speed the fan-coils, cycling through speed 1, 2, 3 or automatic.
Legend
Functions
For more complex systems, the probe can memorize the actuators to activate, and the pumps to control on the BUS. The programming operation must be completed directly from the central unit. The central unit can also be used for the calibration of the probe. During the system setting stage, it will be necessary to specify the actuators used for the heating system, and those used for the air conditioning system, as they operate in a complementary way.
11
10
9
8
25.5°
26.3°
7
+ 2
2
2
3
4
5
6
MY HOME Technical sheets - Automation
4
Page 5
HD4891 - HC4891 - HS4891
L4891 - N4891 - NT4891
- Temperature control probe mode with item HC4693, HS4693, L4693, N4693, NT4693 probe - FUN = 4
Warning: physical conguration can only be used if a 99-zone temperature control central unit is installed in the system
This mode is dierent from the previous one in the fact that the external probe is not connected to Local Display. Being unable to autonomously establish the temperature, it must be associated to at least one probe, items HC4693, HS4693, L4693, N4693, or NT4693. The user is shown the temperature value measured by the associated probes, the set temperature value, and the adjustment of the local selector.
ZA Zone address 0 – 9, probe address
ZB Zone address 1 – 9, probe address
MOD Mode 1 – 8, Slave probe number
FUN Function 4
The possible operations for the user are the adjustment of the set temperature using the local selector, and the change of status of the probe. In this mode, the parameters that can be congured are the local display address (which must coincide with the ZA/ZB address of the associated probe), the type of control of the pump, the type of mode, and the number of slave probes.
For simple systems, where each zone controls at most one heating actuator and one air conditioning actuator, both of the ON/OFF type, and on a system with only one pump per function, the con guration of the system can be performed by simply connecting the con gurators that identify the address of the device and, in case of probe, indicate the number of slaves present.
Example of conguration of a zone (address 47) with Local Display and probe item HC4693, HS4693, L4693, N4693, NT4693
Local display
Functions
A short pressure of keys 8 and 11 can be used to locally change the temperature by +/-3°C, in relation to the settings received from the central unit. A short pressure of key 6 can be used to select the mode of operation, cycling through the OFF, antifreeze/ thermal protection, and automatic statuses respectively.
Slave probe
For more complex systems, the probe can memorize the actuators to activate, and the pumps to control on the BUS. The programming operation must be completed directly from the central unit. The central unit can also be used for the calibration of the probe. During the system setting stage, it will be necessary to specify the actuators used for the heating system, and those used for the air conditioning system, as they operate in a complementary way.
Local Display (HC/HS/L/N/NT4891)
Socket Congurator Socket Congurator
ZA 4 ZA 4
ZB 7 ZB 7
MOD 1 MOD SLA
FUN 4 SLA 1
Sonda Slave (HC/HS/L/N/NT4693)
Each mode of operation is identied by a dierent icon. A short pressure of key 2 will force the speed the fan-coils, cycling through speed 1, 2, 3 or automatic.
Technical sheets - Automation MY HOME
BT00517-a-UK
5
Page 6
HD4891 - HC4891 - HS4891
- Energy Management Mode – consumption display FUN=5
It is possible to display the consumptions and the production of several energies of the system, with monitoring of up to a maximum of ten lines.
Warning: with physical conguration, only the consumptions of one line can be displayed.
ZA Line address 0 – 9
ZB Line address 1 – 9
MOD Type 0 = ELECTRICITY
FUN Function 5
For each line, the consumptions and the instantaneous, daily, monthly, and annual economic evaluation are displayed. It will be possible to set two maximum consumption values, with the device emitting visual and sound notications if these are exceeded. In this case, the displayed value will be green when below both limits, yellow when one has been exceeded, and red when both have been exceeded.
1 = WATER 2 = GAS 3 = DHW 4 = HEATING/COOLING
L4891 - N4891 - NT4891
Once the device has been congured, it will be possible to scroll through the various lines using icon 4. For each measurement interface, by pressing briey icon 3 it will then be possible to display the consumptions or the economic evaluation. Press and hold down icon 3 to access a submenu where it will be possible to change the basic value of the economic evaluation. Consumption and economic evaluations are themselves split into: instantaneous, daily (D), monthly (M), annual (Y). It is possible to scroll through these settings using icon 1. Press and release icon 2 to access a submenu that can be used to set the time, the date, the threshold levels (if enabled), and the possibility of enabling or disabling the beep emitted when the threshold is exceeded.
BT00517-a-UK
Functions
4
m
3
Kw
D/M/Y
Total
115.4
kwh
3
Legend
1. selection of display times
2. setting of the functions (time, date, max. power, etc.)
3. economic display of the consumptions
4. selection of the lines to display
$
1
D
2
MY HOME Technical sheets - Automation
6
Page 7
i
- LOAD MANAGEMENT mode
This mode, only available if Local Display is congured using the software, gives the possibility of displaying loads, with their priority levels, and force their activation. The device can manage up to 20 loads; if these are connected to actuators with current sensor it will be possible to display other load information, like the instantaneous power consumption. When the central unit for load management intervenes on a load, the device (if enabled during the conguration) noties the event with an indication on the display and an audible notication.
HD4891 - HC4891 - HS4891
L4891 - N4891 - NT4891
4
ON
1
6
Oven
Functions
After the conguration of the device it will be possible to select the various loads using icon 1. Icon 4 is disabled until the moment the central unit disables the load; when this happens, the icon becomes active, and can be selected to force the activation of the load. In this condition, icon 3, used to intervene on the status of the load, is disabled. However, if icon 4 is disabled, it will be possible to select icon 3 to pre-force the load, and avoid disconnection in case of intervention of the central unit when consumptions are exceeded. If the loads are connected to actuators with current sensor, use icon 2 to access a submenu that can be used to display the instantaneous power consumption, as well as information form the line total consumption meters. While in this submenu, you can use the RESET icon to reset the meters. Press key 2 for 3 seconds to access the menu used for setting the time, the date, and the sound notication (beep).
- Advanced CEN SCENARIO mode
For systems with MH200N scenario programmers, Local Display can be used to enable 1 of the 4 scenarios displayed. This is done using the associated icons. This function is only available if Local Display has been congured using the software.
3
Legend
1. selection of the load to control
2. display of consumption data and device setup
3. activation/deactivation of the load
4. forced activation of the load disconnected by the energy management central unit, due to consumptions being exceeded.
1
2
1 2 3 4
Legend
1. scenario indication icon
Technical sheets - Automation MY HOME
BT00517-a-UK
7
Loading...