The contents of this document are subject to revision without notice due to continued progress
in methodology, design, and manufacturing. BTG shall have no liability for any error or
damages of any kind resulting from the use of this document.
All rights reserved. No part of this document may be copied, photocopied, published,
reproduced, translated or converted into electronic or machine-readable form
without written permission of BTG Instruments AB.
This user manual contains all necessary instructions for installation,
maintenance, and basic service of the Communication Platform (CPM).
Safety instructions and regulations for installation and service are found in the
BTG Safety Manual, M2076.
NOTE!
Always read the safety instructions before installation and service of the
instrument!
NOTE!
If the CPM is used in a manner not specified by BTG the protection provided
by the equipment may be impaired.
For operation instructions, see the CPM operation manual for the appropriate
instrument. CPM operation manuals are available for the following
instruments:
Recycle the instrument and all replaced parts according to local, first and
foremost national, laws and regulations. Contact BTG to get detailed
information on how to disassemble and recycle the instrument safely. BTG
should have no liability for any error or damage of any kind due to disassembly
or recycle work done.
the unit is not falling under the RoHS/WEEE CE-directives according to:
RoHSAccording to Article 2 (4) and (4e) alt. (4d) and
according to Article 3 (3) alt. (4), the unit shall not
apply to RoHS.
WEEEAccording to Article 2 (3b) and (4c; f), and according
to Article 3 (1b) and (1c, I, II, III), the unit shall not
apply to WEEE.
Fulfills all relevant CE-directive requirements and all Australian TIC requirements.
Function Specifications
Communication Modules:
HCM-8000/8010
Hart communication module using HART® protocol.
Equipped with slot for SD memory card.
Analog output (AO1- AO5)
4 - 20 mA. Galvanic isolated. Current limited to min. 3.9 and max. 20.5 mA.
Loop load signal: Voltage supply/load 24 V DC
Active or passive output for HCM-8000
Active output only for HCM-8010
Superimposed signal over 4 - 20 mA current loop according to standard HART® protocol.
Analog input (AI1 - AI4)
4 - 20 mA 250 Ω input resistance
Digital input (DI1 - DI4)
Galvanic isolated
High-ohmic = logical 0
+24 V ≥ 12 mA = logical 1
Digital output (DO1 - DO2)
Galvanic isolated
Maximum 120 mA
Maximum 30 V DC
Solenoid valve (SV1 - SV5)
Open drain output for solenoids
Maximum 500 mA
Maximum 30 V DC
FCM-8000/8010
Fieldbus communication module programmed for PROFIBUS.
Equipped with slot for SD memory card.
Output / Input signal
PROFIBUS (PA)
User Interface
Illuminated display. Key pad for adjustment of instrument settings.
Power supply unit 100 - 240 V AC, 50-60 Hz.
AC input range: 90 - 264 V continuous operation.
Disconnecting Device
An external 2-pole switch close to the CPM is required. The switch must be approved in
accordance with the IEC 60947-2 and IEC 60947-3 requirements.
Power Consumption
Maximum: 135 VA (CPM-1300), 515 VA (CPM-1400), 160 VA (CPM-1500)
Altitude
0 to 2000 m (0-6560ft) without any restrictions.
2000 to 6000 m (6560 to 20000ft) reduce output power or ambient temperature.
Altitude de-rating = 5 W / 1000 m or 5 °C / 1000 m.
Humidity
5 to 95% r.h (IEC 60068-2-30)
Over-voltage Category
Category III: IEC 62103, EN 50178, altitudes up to 2000 m
Category II: altitudes from 2000 m to 6000 m
BTG Instruments AB
Industrigatan 1-3
66129 Säffle
SWEDEN
PRODUCT
VOLTAGE
FREQUENCY
NO
TYPE
3068754
INSTALLATION CATEGORY
FACTORY IDENTIFICATION
APPARENT POWER
Fig4 Type plate
HA/Q0/C0/S/10/I230 A
123456
50-60 Hz
12345
6
7
8
9
1011
12
50 W
III
CPM-1300
100-240 V AC
15
13
14
16
1.4Type Plate Explanations
1. Manufacturer
2. CE-marking
The CPM is approved in accordance with CE directives.
3. C-TIC marking
The CPM is approved in accordance with Australian C-TIC N1619
directives.
4. ETL-marking
The CPM is approved by ETL.
5. Warning sign
The CPM is designed for industrial use. Installation, handling and service
must only be carried out by trained and authorized personnel and in
accordance with relevant standards. Read the manual for detailed
information and pay particular attention to the warning signs!
Name: Björn Fahlin…………………………………...Position: Director of Operations
1.5CE-Declaration
When using the units in combinations other than those tested for, BTG can not
guarantee CE-directive conformity.
The units in combination with customer-installed external devices may conform
with EMC and safety requirements when properly installed and CE-marked
equipment is used.
The system operator is responsible for CE-directive conformity.
Conformity must be verified by inspection.
The protection cover is equipped with a slot for the Quick Reference Guide
(QRG) card, which is enclosed with certain transmitters. If a QRG card of the
type shown in Fig 5 is enclosed with your transmitter, place it in the slot as
shown in Fig 5.
The Hart communication module (HCM-80xx) is using HART® protocol.
NOTE!
Before installation, ensure that all power to the system has been turned off.
Cable connections must be made by authorized personnel.
NOTE!
Fig 8 shows resistance as a function of supply voltage. The grey area is
accepted. The resistance is the sum of cable- and power source- resistance in
the current loop. The HART
250
®
communication requires a minimum resistance of
1. Insert the signal cable through the cable gland.
2. Connect the cable to the HCM-80xx as shown in Fig 11 or Fig 13.
NOTE!
The connection blocks can be released from the connection module for easier
access, as shown in Fig 9 below.
3. Connect the shield to the upper connection point on the shield filter module
(SFM-8000).
CAUTION!
The cable shield must always be connected to the upper connection point on
the shield filter module, and kept separated from the transmitter cable shield.
Passive4-20 mAAnalog Out
Supplied with 14 - 35 V DC
AO1
P3
AI1
+24 V
+
-
LOAD
+24 V
Fig 11 Connection of HCM-
8000 cable
CAUTION
Always connect
the cable shield!
CAUTION!
The cable shield must always
be connected to the upper
connection point on the shield
filter module, and kept
separated from the transmitter
cable shield.
NOTE!
Note the polarity for
Passive or Active
Analog Out (AO).
If the analog output
signal (4-20 mA) is
passive, an external
source of current must
be used (14-35 V DC)
2.5.2.1HCM-8000 Connections
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for HCM-8000 in section 5: Appendix
The cable shield must always
be connected to the upper
connection point on the shield
filter module, and kept
separated from the transmitter
cable shield.
NOTE!
For HCM-8010, only active
analog output is available.
2.5.2.2HCM-8010 Connections
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for HCM-8010 in section 5: Appendix
Before installation, ensure that all power to the system has been turned off.
Cable connections must be made by authorized personnel.
1. Insert the signal cables through the cable glands.
2. Connect the cables to the FCM-80xx as shown in Fig 11 or Fig 13.
NOTE!
The connection blocks can be released from the connection module for easier
access, as shown in Fig 14 below.
3. Connect the shield to the upper connection point on the shield filter module.
CAUTION!
The cable shield must always be connected to the upper connection point on
the shield filter module, and kept separated from the transmitter cable shield.
The cable shield must always
be connected to the upper
connection point on the shield
filter module, and kept
separated from the transmitter
cable shield.
2.5.3.1FCM-8000 Connections
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for FCM-8000 in section 5: Appendix
The cable shield must always
be connected to the upper
connection point on the
shield filter module, and kept
separated from the
transmitter cable shield.
2.5.3.2FCM-8010 Connections
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for FCM-8010 in section 5: Appendix
These connection instructions are only valid for DRT-5500. Other instruments
equipped with the SCM-8000 have all connections to the SCM unit pre-wired
at delivery.
NOTE!
Before installation, ensure that all power to the system has been turned off.
Cable connections must be made by authorized personnel.
Fig 21 shows the transmitter cable-connection inside the CPM-1400
(for MEK-3000).
Installation Instructions
N
L
++
--
AC
100-120/
200-240 V
2
3
4S
SAB
On/Off
Fig 22 24 V On/Off switch
2.5.624 V On/Off Switch
Some CPM models are equipped with a fuse used as an On/Off switch for the
24 V supply to the CPM and the transmitter. Fig 22 shows the 24 V On/Off
switch in the CPM-1400 for MEK-3000.
The HCM-8000 and FCM-8000 is equipped with a slot for a memory card of
the type Secure Digital (SD). A SD card is not included in a CPM delivery.
All transmitter settings, transmitter data, and calibration data can be stored on
a SD card. The SD card reader is located on the communication module card,
and can be accessed by opening the front cover of the CPM (see Fig 23).
Filtrate charge
(Channel 1) output
value
4 - 20 mA
Configurable
(Channel 1) output
value
4 - 20 mA
Kappa
LRV - URV
output value
4 - 20 mA
Calibration set
Input A
Calibration set
Input B
Total consistency
(Channel 1) output
value
4 - 20 mA
Not usedNot usedNot usedNot used
White water charge
(Channel 2) output
value
4 - 20 mA
Start streaming
potential for filtrate
(Channel 1)
Start streaming
potential for white
water (Channel 2)
Configurable
(Channel 2) output
value
4 - 20 mA
Configurable
(Channel 3) output
value
4 - 20 mA
Internally pre-
(a)
wired
RMS 0-0.0015 V
output value
4 - 20 mA
CwZ 0-1.65 V
output value
4 - 20 mA
CwT 0-0.165 V
output value
4 - 20 mA
Mean Kappa
LRV - URV
output value
4 - 20 mA
(b)
Ash consistency
(Channel 2) output
value
4 - 20 mA
Not used
Not used
Analog input
AI2Analog In 2
P6
AI3Analog In 3
signals from
external equipment
4 - 20 mA
Not used
Internally pre-
(a)
wired
Internally
pre-wired
Not used
AI4Analog In 4Not used
DI4Digital In 4
P7
DO2
SV4Sol. valve 4
P8
SV5Sol. valve 5
SV1Sol. valve 1
P9
SV2Sol. valve 2
Digital Out 2
Floating DC
switch max 30 V,
100 mA
Not used
Not used
Data ready
Channel 1
Not usedNot used
Data ready
Channel 2
Not used
Not used
Internally pre-
(a)
wired
Sample Input
Not usedData Ready
Internally pre-
(a)
wired
Internally pre-wired
Not used
Internally pre-
(a)
wired
Internally pre-wired
SV3Sol. valve 3
(a) For more information about internally pre-wired connections, see the installation drawing for the transmitter
(b) Average since last start. Normally only used for batch applications