Bryant-Carrier PH4Z Installation Manual

PH4Z
14 SEER SINGLE---PACKAGED HEAT PUMP SYSTEM
Installation Instructions
IMPORTANT: Effective January 1, 2015, all split system and
NOTE: Read the entire instruction manual before starting the installation.
NOTE: Installer: Make sure the Owner’s Manual and Service Instructions are left with the unit after installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 2.........................
INTRODUCTION 2...................................
RECEIVING AND INSTALLATION 2--10.................
Check Equipment 2..................................
Identify Unit 2....................................
Inspect Shipment 2.................................
Provide Unit Support 2...............................
Slab Mount 2.....................................
Ground Mount 2..................................
Provide Clearances 2.................................
Place Unit 3........................................
Select and Install Ductwork 3...........................
Installing factory--supplied duct flanges 3...............
Configuring Units for Downflow (Vertical) Discharge 9....
Connect Condensate Drain 9...........................
Install Electrical Connections 9.........................
High--Voltage Connections 9.........................
Routing Power Leads Into Unit 9......................
Connecting Ground Lead to Unit Ground 10.............
Routing Control Power Wires 10.....................
Accessory Electric Heat Wiring 10.....................
PRE--START--UP 10...................................
START--UP 11--14.....................................
Check for Refrigerant Leaks 11.........................
Start--Up Cooling and Make Adjustments 11...............
Checking Cooling and Heating Control Operation 11......
Refrigerant Charge 11................................
No Charge 11.....................................
Low Charge Cooling 11.............................
Heating Mode Charge 12............................
Indoor Airflow and Airflow Adjustments 14...............
Sequence of Operation 14.............................
Fan Operation 14..................................
Cooling Operation 14...............................
Heating Operation 14...............................
Continuous Fan 14.................................
WITH R ---410A REFRIGERANT
SINGLE PHASE
2 --- 5 N O M I N A L T ON S ( S I Z E S 2 4 --- 6 0 )
A05165
PH4Z 024--048
A150067
PH4Z 060
Fig. 1 -- PH4Z
Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1--in. W.C. with all present air
inlets, air outlets, and condensate drain port(s) sealed.
Defrost 14.......................................
Electric Resistance Heating 14........................
MAINTENANCE 18--21................................
Air Filter 18........................................
Unit Top Removal 18.................................
Indoor Blower and Motor 19...........................
Outdoor Coil, Indoor Coil, and Condensate Drain Pan 19.....
Outdoor Fan Adjustment 19............................
Electrical Controls and Wiring 20.......................
Refrigerant Circuit 20.................................
Indoor Airflow 20...................................
1
Metering Devices 20.................................
High Flow Valves 20.................................
High Pressure Switch 20..............................
Loss of Charge Switch 20.............................
R--410A Compressor 20...............................
Refrigerant 20......................................
Compressor Oil 21...................................
Servicing Systems on Roofs with Synthetic Materials 21......
Synthetic Roof Precautionary Procedure 21................
Liquid Line Filter Drier 21.............................
R--410A Refrigerant Charging 21.......................
TROUBLESHOOTING 21..............................
START--UP CHECKLIST 21............................
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to relieve system pressure could result in personal injury and/or death.
1. Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal. Use all service ports and open all flow--control devices, including solenoid valves.
2. Federal regulations require that you do not vent refrigerant into the atmosphere. Recover during system repair or final unit disposal.
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such
PH4Z
as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. W ear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Electrical Code (NEC) NFPA 70 and NFPA 90B--Installation Warm Air Heating and A/C Systems (Residential). In Canada refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in per­sonal injury or death. CAUTION is used to identify unsafe practic­es which may result in minor personal injury or product and prop­erty damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing.
CAUTION
INTRODUCTION
This packaged heat pump is fully self-- contained and designed for outdoor installation (See Fig. 1). Standard units are shipped in a horizontal--discharge configuration for installation on a ground--level slab or directly on the ground if local codes permit. Standard units can be converted to downflow (vertical) discharge configurations for rooftop applications with a field supplied plenum.
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY UNIT
The unit model number and serial number are printed on the unit informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.
.
Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
Step 2 — Provide Unit Support
For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate, if required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102 mm) thick with 2 in. (51 mm) above grade. The slab should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit. Do not secure the unit to the slab except when required by local codes.
A 6--in. (152 mm) wide gravel apron should be used around the flat surface to prevent airflow blockage by grass or shrubs. The unit should be level within 1/4 in. (6 mm). This is necessary for the unit drain to function properly.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the ground if local codes permit. Place the unit on level ground prepared with gravel for condensate discharge.
Step 3 — Provide Clearances
The required minimum service clearances are shown in Fig. 4--6. Adequate ventilation and outdoor air must be provided.
The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48
2
in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab--mounted units should be at least 4 in. (102 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.
Step 4 — Place Unit
Unit can be moved with the rigging holds provided in the unit base. Refer to Table 1 for operating weights. Use extreme caution to prevent damage when moving the unit. Unit must remain in an upright position during all moving operations. The unit must be level with in 1/4 in. (6 mm) for proper condensate drainage; the ground--level pad must be level before setting the unit in place. When a field-- fabricated support is used, be sure that the support is level and that it properly supports the unit.
Step 5 — Select and Install Ductwork
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non--residence type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply-- air registers, and return air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply-- and return-- air openings on the side of the unit. See Fig. 4--6 for connectio n sizes and locations. The 14--in. (356 mm) round or 14 x 20 in. (356 x
508 mm) rectangular duct collars are shipped inside the unit attached to the base pan in the indoor blower compartment. They are field--installed and must be removed from the indoor blower compartment prior to start--up, even if they are not used for installation. If a corrugated shipping block is used under the blower housing, remove and discard the block and label.
When designing and installing ductwork, consider the following:
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components.
When connecting ductwork to units, do not drill deeper than 3/4 in. (19 mm) in shaded area shown in Fig. 2 or coil may be damaged.
19.17 in. (487 mm)
Fig. 2 -- Area Not to be Drilled More Than 3/4--in. (19 mm)
1. All units should have field--supplied filters or accessory filter rack installed in the return--air side of the unit. Recommended sizes for filters are shown in Table 1.
2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24--in. (610 mm) from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof, and vibration--isolate duct openings in wall or roof according to good construction practices.
Fig. 7 shows a typical duct system with unit installed.
3.92 in.
(100 mm)
Deep
A10021
Installing factory--supplied duct flanges;
For 24, 30, and 36 sizes:
S Two round 14--in. (356 mm) duct collars are factory supplied. S Line up the 6 holes in the duct collar with the pre--drilled holes
in the side panel.
S Fasten duct collar to side panel using field--supplied screws.
For 42, 48 and 60 sizes (See Fig. 3):
S One round 14--in. (356 mm) duct collar for the supply air
connections and two “L” brackets for the 14--in. x 20 --in. (356 x
508 mm) return air connection are factory--supplied.
S Line up the 6 holes in the supply duct collar with the pre--drilled
holes in the side panel. Fasten duct collar to side panel using
field--supplied screws.
S For the return, remove the 4 screws on the left side of the return
and install one of the “L” flanges on the left side by replacing
the 4 screws. Using the 2 dimples below the return, align the
PH4Z
3
bottom of the “L” flange with the two dimples and attach using
filed--supplied thread--cutting screws.
For the second “L” flange, align flange with the three dimples to
the right of the return and the two dimples above the return and
attach using field--supplied thread--cutting screws.
NOTE: The factory--installed screws to the right of the return should not be removed in this process.
PH4Z
3 Factory Installed Screws (Must not be removed)
Remove 4 screws from left side of duct opening and reuse to install the left half of duct flange.
Install supply duct flange as shown into existing holes with field-supplied screws.
X = Factory dimples for duct flange attachment.
Fig. 3 -- Installing Factory--Supplied Duct Flanges
A10081
4
PH4Z
Fig. 4 -- Unit Base Dimensions, 024--036
5
A1456
PH4Z
Fig. 5 -- Unit Base Dimensions, 042--048
6
A14557
PH4Z
Fig. 6 -- Unit Base Dimensions, 060
7
A150072
RETURN AIR
INDOOR THERMOSTAT
FROM POWER SOURCE
DISCONNECT PER NEC (UNIT AND ELECTRIC HEATER)
PH4Z
TOP COVER
Power Wiri ng
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND LOW-VOLTAGE ENTRY
COMPOSITE RUST-PROOF BASEPAN
CONDENSATE DRAIN CONNECTION
Fig. 7 -- Typical Installation
Table 1 – Physical Data
UNIT SIZE 024 030 036 042 048 060
NOMINAL CAPACITY (ton) 2 2.5 3 3.5 4 5
SHIPPING WEIGHT (lb)
(kg)
COMPRESSOR TYPE SCROLL
REFRIGERANT R-410A
REFRIGERANT QUANTITIY (lb)
QUANTITY (kg)
OUTDOOR METERING DEVICE TXV Piston TXV Piston
ORIFICE OD (in.)
(mm) OUTDOOR COIL ROWS...FINS/in.
FACE A REA (sq. ft)
OUTDOOR FAN
NOMINAL AIRFLOW (cfm)
DIAMETER (in.)
DIAMETER (mm)
MOTOR HP (RPM)
INDOOR METERING DEVICE Piston TXV TXV
ORIFICE OD (in.)
(mm)
INDOOR COIL
ROWS...FINS/in.
FACE A REA (sq. ft)
INDOOR BLOWER
NOMINAL COOLING AIRFLOW (cfm)
NOMINAL SIZE D x L (in.)
(mm)
MOTOR (HP)
HIGH-PRESSURE SWITCH (psig)
CUTOUT
RESET (AUTO)
LOW-PRESSURE SWITCH (psig)
CUTOUT
RESET (AUTO)
RETURN-AIR FILTERS
THR OWAWAY (in.)
*Required filter sizes shown are based on the AHRI (Air Condition ing, Heating & Refrigeration Institute) rated airflow at a velocity of 300 ft/min (91 m) for throw­away type or 450 ft/ min (137 m) for high capacity type. Recommended filters are 1 ---in. (25 mm) thick.
(mm)
312 142
7.00
3.18
---
---
2...20
9.1
2000
20
508
1/8 (825)
0.059
1.499
3...12
4.3
800
10 x 8
254 x 203
1/3
20x20x1
508x508x25
333 151
7.20
3.27
0.049
1.245
2...20
10.2
2000
20
508
1/8 (825)
0.059
1.499
3...14
4.3
1000
11 x 9
279 x 229
1/3
610x762x25
24x30x1
334 152
6.30
2.86
0.057
1.448
2...20
10.2
2800
20
508
1/4 (1100)
0.067
1.702
3...12
4.9
1200
11 x 9
279 x 229
1/2
650 +/- 15 420 +/- 25
20 +/- 5
45 +/- 10
388 177
9.10
4.13
0.059
1.499
2...20
13.0
3100
20
508
1/4 (1100)
0.076
1.9304
3...14
4.9
1400
11 x 9
279 x 229
1/2
407 185
7.70
3.49
---
---
2...20
15.5
3100
20
508
1/4 (1100)
---
---
3...14
4.9
1600
11 x 9
279 x 229
3/4
24x36x1
610x914x25
A08207
475 215
11.5
5.22
0.070
1.778
2...20
15.5
3300
20
508
1/3 (1100)
---
---
3...14
4.9
1700
12 x 11
305 x 279
1
Table 2 – Minimum Airflow for Safe Electric Heater Operation
HP Unit
Size
5kW 7.5 kW 10 kW 15 kW 20 kW 24 750 800 800 X X 30 750 800 800 X X 36 750 800 800 1200 X 42 750 800 800 1200 X 48 750 800 800 1200 1800 60 750 800 800 1200 1800
X = NOT APPROVED COMBINATION
Minimum Airflow (CFM)
8
Loading...
+ 16 hidden pages