Bryant-Carrier PA13NA, PA13PA User Manual

PA13NA PA13PA
13 SEER Split ---System Air Conditioner
With R ---410A Refrigerant
Single & Three Phase
1 --- 1 / 2 To 5 Ton s
Product Data
FEATURES AND BENEFITS
Nominal sizes are available from 018 through 060 to meet the needs of residential and light commercial applications.
CERTIFICATION:
All models are listed with UL, (U.S. and Canada), AHRI, and CEC.
ELECTRICAL RANGE:
Units offered in single phase 208/230v are 018--060, three phase 208/230v in 036, 048 and 060, and three phase 460v in 060.
FAN MOTOR:
The totally enclosed fan motor provides greater reliability under adverse conditions and dependable performance for many years. The permanent split capacitor type motor was designed for optimum efficiency. The motor was then qualified under extreme conditions to help ensure a long, reliable life.
CABINET:
A weather protective cabinet of prepainted steel is protected underneath by a galvanized coating and treated with a layer of zinc phosphate for a finish that will last for many years. All screws on cabinet exterior are coated for a long--lasting, rust--resistant, quality appearance.
UNIT DESIGN:
The copper tube, enhanced sine wave, aluminum fin coil is designed for optimum heat transfer. Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage. The base pan is designed for easy removal of water, dirt, and leaves.
COMPRESSOR:
Each compressor is protected with internal temperature-- and current--sensitive overloads. An internal pressure relief valve provides high pressure protection to the refrigerant system. For improved serviceability, all models are equipped with a compressor terminal plug.
SERVICE VALVES:
Both service valves are brass, front seating type with sweat connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures.
SERVICEABILITY:
One access panel provides access to electrical controls. Removal of top gives access to fan motor, compressor, and condenser coil.
PRODUCT NUMBER NOMENCLATURE
13 SEER Air Conditioner with R --- 410A Refrigerant
PA1 3 N
A
018
000
B
A
Series
AA
Variatio ns
Electrical Supply
Variatio ns
N --- 208/230 --- 60 ---1 P --- 208/230 ---60 --- 3
Nominal Capacity 018 --- 1 --- 1 / 2 To n 024 --- 2 To n s
A --- R---410A
ISO 9001:2000
PA13NA / PA13PA
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
REGISTERED
®
030 --- 2 --- 1 / 2 To n s 036 --- 3 To n s 042 --- 3 --- 1 / 2 To n s 048 --- 4 To n 060 --- 5 To n
000 --- V a r i a t i o n s
This produ ct has been designed and man ufactur ed t o meet Energy S tar® criteria for energy efficiency when matched wi th appropriate coi l components. However, proper refr igerant char ge an d proper air fl ow are crit ical to achieve rated capacity and efficiency. Installation of this product should f ollow all manufacturing refrigerant charging and air flow instructions. Failure to confirm
proper charge and air flow may reduce energy efficiency and shorten equ ipment l i fe.
2
66 / 63
(20.1 / 19.2)
89 / 82
(27.1 / 25.0)
70 / 66
115 / 109
83 / 79
70 / 67
70 / 66
1/4 PSC and 1100
(21.3 / 20.1)
(35.1 / 33.2)
(25.3 / 24.1)
1100
1/5 PSC and
PA13NA / PA13PA
(21.3 / 20.4)
TSTATPPPAC01
TSTATPPBAC01
(21.3 / 20.1)
TSTATXXPBP01
74 / 70
(22.6 / 21.3)
70 / 66
(21.3 / 20.1)
66 / 62
(20.1 / 18.9)
Locked Rotor A mps 48.0 58.3 64.0 77.0 71.0 112.0 109.0 83.1 134.0 110.0
UNIT SIZE 018 024 030 036 042 048 060
SERIES B B B B B D B
ELECTRI CAL
Unit Volts—Hertz—Phase 208/230—60—1 208/230---60 ---1 208/230---60 ---3 208/230---60 ---1 208/230---60 ---1 208/230---60 ---3 208/230---60 --- 1 208/230---60 ---3
Operating Voltage Range* 187—253
Compresso r—Rated Load Amps 9.0 13.5 12.8 14.1 9.0 17.9 19.9 13.1 26.4 16.0
Condenser Fan Motor— Full Load Amps 0.5 0.8 0.8 1.4 1.4 1.1 1.4 1.4 1.4 1.4
Min Uni t Ampacity for Wire Sizing 11.7 17.6 16.8 19.0 12.7 23.5 26.2 17.8 34.4 21.4
Min Wire Size (60°/75° Copper) AWG** 14 12 12 12 14 10 8 12 8 12
Max Wire Length (60°/75°)ft(m)‡
Max Branch Circuit Fuse Size† 20 25 25 30 20 40 40 30 50 30
COMPRESSOR AND REFRIGERANT
SPECIFICATIONS
Typ e Scroll
3/4 and 3/8 7/8 and 3/8 1--- 1/8 and 3/8
3.15 (1.43) 3.15 (1.43) 3.63 (1.65) 4.67 (2.12) 6.07 (2.75) 7.00 (3.18) 8.00 (3.63)
AmountLb(kg)@15ft(4.6m)
Temperature and Current P rotectio n Internal Line Brea k
R--- 410A Refrigerant—
Refrigerant Tubes (In. OD)
}} Rated Vapor and Maximum Liquid
CONDENSER COIL AND FAN
Coil Face Area (Sq Ft) 8.4 8.4 9.8 12.60 17.3 19.29 15.14
Fan Motor—HP, Type, and RPM 1/12 PSC and 1100 1/ 10 PSC and 1100 1/4 PSC and 1100
Vol ts— Hertz—Ph ase 208/230—60—1
Condenser Airflow (CFM) 1700 2000 2000 2500 3000 3400 3400
OPTIONAL EQUIPMENT
Cycle Protector KSACY0101AAA
Start A ssist—PTC Type KAACS0201PTC N/A KAACS0201PTC N/A KAACS0201PTC N/A
Start Assist—Capacitor/Relay Type KSAHS1501AAA KSAHS1701AAA KSAHS1501AAA N/A KSAHS1501AAA N/A KSAHS1501AAA N/A
MotorMaster® Control KSALA0601AAA
Ball Bearing Fan Motor (RCD) HC32GE234 HC34GE239 HC40GR232 HC38GE219 HC40GE226
L o w --- P r e s s u r e S w i t c h KAALP0401PUR
H i g h --- P r e s s u r e S w i t c h KAAHI0501PUR
Compressor Sound Hood KSASH1801COP KSASH0601COP KSASH2101COP
T i m e --- D e l a y R e l a y KAATD0101TDR
Low--- Ambient Pressure Switch Kit KSALA0301410
Winter Start Control KAAWS0101AAA
Evaporator Freeze Thermostat KAAFT0101AAA
Compresso r Crankcase He ater KAACH1401AAA KAACH1201AAA
Liquid Line Solenoid Valve†† KAALS0201LLS
TXV (Hard Shutoff)†† KSATX0201PUR KSATX0301PUR KSATX0401PUR KSATX0501PUR
Standard Thermostat, Manual
Changeover, Non---Programmable, °F/°C,
1 --- St a g e H e a t , 1 --- St a g e C o o l
Thermostat, Auto C hangeover, 7 --- Day
Progra mmable , °F/°C , 1 --- S t a g e H e a t ,
1 --- St a g e C o o l
Outdoor Sensor TSTATXXSEN01---B
Liquid Line Fil ter Dri er KH43LG073 KH43LG074
Backplate for Standard Thermostat TSTATXXBBP01
Backplate for Programmable
Thermostat
N/A --- Not applicable in this application.
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
Article 336 --- 26.
{ Time---delay fuse or circuit breaker.
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** If wire is applied at ambient greater than 30°C, consult Table 310 --- 16 of the NEC (NFPA 70). The ampacity of nonmetallic--- sheathed cable (NM), trade name ROMEX, shall be that of 60° C conductors, per the NEC (NFPA 70)
{{ Do not use hard shutoff TXV with liquid solenoid valve.
}} Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
3
PA13NA / PA13PA
DIMENSIONS -- ENGLISH
4
PA13NA / PA13PA
DIMENSIONS -- SI
5
Wall
6”
(152.4)
24”
(609.6)
Wall
PA13NA / PA13PA
Service
12”
(304.8)
12”
(304.8)
24”
(609.6)
Service
18”
(457.2)
24”
(609.6)
Service
18”
(457.2)
Clearances (various examples)
12”
(304.8)
6”
Wall
(152.4)
Wall
12”
(304.8)
CLEARANCES
24”
(609.6)
Service
24”
(609.6)
Service
18”
(457.2)
6
Note: Numbers in ( ) = mm
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
REFRIGERANT CHARGE ADJUSTMENTS
Liquid Line Size R --- 410A Charge oz/ft
3/8
5/16 0.40
1/4 0.27
(Factory charge for lineset = 9 oz)
0.60
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or diameter liquid lines, charge adjustments are required per the chart above.
Charging
Formula:
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?
Formula: (.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz. Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?
Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz. Net result is to add 9 oz of refrigerant to the system
LONG LINE APPLICATIONS
An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH R--410A REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor
1/4
5/16 120 (36.6) 50 (15.2) 120 (36.6)
3/8 80 (24.4) 35 (10.7) 80 (24.4)
Note: SeeLongLineGuidelinefordetails
No accessories needed within allowed lengths
No accessories needed within allowed lengths
175 (53.3)
PA13NA / PA13PA
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with R--410A refrigerant:
Unit
Nominal
Size (Btuh)
18000 1Stage AC with
R --- 410A
24000 1Stage AC with
R --- 410A
30000 1Stage AC with
R --- 410A
36000 1Stage AC with
R --- 410A
42000 1Stage AC with
R --- 410A
48000 1Stage AC with
R --- 410A
60000 1Stage AC with
R --- 410A
Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.
Maximum
Liquid Line
Diameters
(In. OD)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapo r Line
Diameters
(In. OD)
1/2 1 2 3 5 6 7 8 9 11
5/8 0 1 1 1 2 2 2 3 3
3/4 0 0 0 0 1 1 1 1 1
5/8 0 1 2 2 3 3 4 5 5
3/4 0 0 1 1 1 1 1 2 2
7/8 0 0 0 0 0 1 1 1 1
5/8 1 2 3 3 4 5 6 7 8
3/4 0 0 1 1 1 2 2 2 3
7/8 0 0 0 0 1 1 1 1 1
5/8 1 2 4 5 6 8 9 10 12
3/4 0 1 1 2 2 3 3 4 4
7/8 0 0 0 1 1 1 1 2 2
3/4 0 1 2 2 3 4 4 5 6
7/8 0 0 1 1 1 2 2 2 3
11/8 0 0 0 0 0 0 0 0 0
3/4 0 1 2 3 4 5 5 6 7
7/8 0 0 1 1 2 2 2 3 3
11/8 0 0 0 0 0 0 0 1 1
3/4 1 2 4 5 6 7 9 10 11
7/8 0 1 2 2 3 4 4 5 5
11/8 0 0 0 1 1 1 1 1 1
26--- 50
(7.9--- 15.2)
51--- 80
(15.5--- 24.4)
81--- 100
(24.7--- 30.5)
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
101--- 125
(30.8--- 38.1)
126--- 150
(38.4--- 45.7)
151--- 175
(46.0--- 53.3)
176--- 200
(53.6--- 61.0)
201--- 225
(61.3--- 68.6)
226--- 250
(68.9--- 76.2)
7
A--WEIGHTED SOUND POWER (dBA)
U N I T S I Z E ---
SERIES
018--- B 76 49.5 59.0 63.0 66.5 62.5 58.5 54.0
024--- B 76 50.5 61.0 67.0 68.0 65.0 60.0 55.5
030--- B 76 52.0 59.5 65.0 65.0 62.0 58.5 50.5
036--- B 77 61.5 63.5 68.5 72.0 68.5 63.0 56.5
042--- B 80 56.0 64.5 69.5 71.0 66.0 64.0 59.0
048--- D 80 57.5 65.5 70.5 72.0 68.5 67.0 61.5
060--- B 80 59.5 69.5 72.5 73.5 71.0 68.0 63.5
NOTE: T ested in accordance with AHRI Standard 270 ---95 (not listed in AHRI).
Standard
Rating (dBA)
125 250 500 1000 2000 4000 8000
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
METERING DEVICE
UNIT SIZE--- SERIES INDOOOR REQUIRED SUBCOOLING _F(_C)
018 --- B 024 --- B 030 --- B 036 --- B 042 --- B 048 --- D
PA13NA / PA13PA
* TXV must be ordered separately when indoor coil is not equipped with a TXV. TXV must be hard ---shutoff type.
060 --- B
TXV* 10(5.6)
8
ACCESSORY USAGE GUIDELINE
REQUIRED FOR LOWMBIENT
ACCESSORY
Ball Bearing Fan Motor Yes{ No No
Compressor Start Assist Capacitor and Relay Yes Yes No
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat Ye s No No
H a r d S h u t --- O f f T X V Yes Yes Yes
Liquid Line Solenoid Valve No
Low Ambient Kit (Pressure Switch) Yes No No
Support Feet Recommended No Recommended
* For tubing line sets between 80 and 200 ft. (24.4 and 76.2 m) and/or 20 ft. (6.1 m) vertical differential, refer to Residential Split--- System Longline Application
Guideline.
{ Required for Low Ambient Controller (full modulation feature) and MotorMasterr Control only.
Winter Start Control Yes No No
COOLING APPLICATIONS
(Below 55°F / 22.8°C)
REQUIRED FOR
LONG LINE
APPLICATIONS*
(Over80Ft./24.4m)
S e e L o n g --- L i n e A p -
plication Guideline
Accessory Description and Usage (Listed Alphabetically)
1. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the following applications:
Long line Low ambient cooling Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the following applications:
Long line Low ambient cooling
Suggested for all compressors in areas with a history of low voltage problems.
2. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
3. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications. Required in long line applications.
4. Cycle Protector
The cycle protector is designed to prevent compressor short cycling. This control provides an approximate 5--minute delay after power to the compressor has been interrupted for any reason, including power outage, protector control trip, thermostat jiggling, or normal cycling.
Suggested in all commercial applications.
5. Evaporator Freeze Thermostat
An SPST temperature actuated switch that stops unit operation when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
6. Low Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low ambient temperatures down to 0_F/--17.8_C when properly installed.
Usage Guideline:
A Low Ambient Pressure Switch or MotorMasterr Low Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).
Suggested for all commercial applications.
7. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.
Usage Guideline: Suggested in the following applications:
Coastal installations. Windy areas or where debris is normally circulating. Rooftop installations. For improved sound ratings.
8. Thermostatic Expansion Valve (TXV)
A modulating flow--control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist Capacitor and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner long line applications.
Required for use on all zoning systems.
9. Winter Start Control
This control is designed to alleviate nuisance opening of the low--pressure switch by bypassing it for the first 3 minutes of operation.
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within2miles/3.2km)
No
PA13NA / PA13PA
9
Loading...
+ 19 hidden pages