The FB4C fan coil has the proven technology of Bryant fan coil
units with Puron refrigerant as well as vertical and horizontal
applications. The design features contoured condensate pans with
rugged drain connections, ensuring that little water is left in the
unit at the end of the cooling duty cycle. The lack of standing
condensate and corrosion free pans improves IAQ and product life,
features homeowners appreciate.
Standard features include grooved tubing and louvered fins. Coil
circuiting has also been updated to make the most of all Bryant
heat pumps and air conditioners. Units come with solid state fan
controls, 1--inch (25mm) thick insulation with R--value of 4.2,
multi--speed motors, and fully--wettable coils. Units can
accommodate factory-- and/or field--installed heaters from 3 to 30
kW.
It also should be noted that the unique cabinet design of these fan
coils meet stringent regulations for cabinet air leakage -- a
requirement of 2% cabinet leakage rate when tested at 1.0 inches of
static pressure.
The FB4C fan coil design is loaded with popular features. These
fan coils utilize the latest in electronic commutation motor (ECM)
technology through the use of high efficiency, multi--tap ECM
motors allowing reliable air delivery with increased static pressure.
It comes in a pre--painted (taupe metallic) galvanized steel casing
and a factory--supplied power plug for ease of installation. The
FB4C unit is shipped with a factory--installed Teflon--ring piston
A10083
FB4CNF(018--048) or a Puron refrigerant TXV FB4CNF060,
FB4CNP(018--060).
AT ITS FINEST
Page 2
STANDARD FEATURES
S Multi--tap ECM (electronic commutating motor) motors -- all sizes
S Integrated motor controls, with 90--sec off TDR function, have replaced integrated circuit board
S Five available speed tags to meet a wide range of applications
S Large, grooved tube, louvered fin coils
S Efficient, quiet, time--tested blower housings and diffusers
S Sturdy, drainable condensate pans
S Cabinet construction features innovations designed to prevent cabinet sweating
S Tested for condensate disposal in much tougher conditions than Air Conditioning and Refrigeration Institute requirements
S Super--thick R--4.2 insulation with vapor barrier
S Pre--painted galvanized steel cabinet (taupe metallic)
S Cabinet design meets stringent regulations for 2% cabinet leakage rate when tested at 1.0 inches static pressure
S Installation--flexible, multipoise units
S Horizontal hanging provisions on cabinet
S No tools required to access filter
S Newly improved filter rack area filter door insulation added for improved air seal
S Factory--installed heater packages available on select models (5-- through 15--kW)
S 3-- through 30--kW accessory heaters -- field installed
S Factory--supplied power plug
S Easy plug--in provisions for heater installation
S Entry options for high and low voltage wiring hook--up
S Leak--preventing sweat connections
S Puron refrigeration factory--installed Teflon--ring pistons on all FB4CNF (018--048) coils
S Thermostatic expansion valve, TXV, on all FB4CNP coils and FB4CNF060
S Designed for manufactured housing applications.
ADDITIONAL FEATURES
S Factory--installed heater packages available on select models
2
Page 3
MODEL NUMBER NOMENCLATURE
123456789101112
FB4CNF018000
ProductHeating Size
F=FanCoil00 = No Heat
05 = 5 kW
Typ e75 = 7.5 kW
B = Base, Puron08 = 8 kW
018 = 18,000
Cabinet Style024 = 24,000
F = Single Piece with piston (TXV on FB4CNF060)030 = 30,000
P=TXV036 = 36,000
042 = 42,000
048 = 48,000
060 = 60,000
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
3
Page 4
DIMENSIONS
Fig. 1 -- FB4CNF -- English
4
A12512
Page 5
DIMENSIONS (cont.)
Fig. 2 -- FB4CNP -- English
5
A14026
Page 6
DIMENSIONS (cont.)
Fig. 3 -- FB4CNF and FB4CNP -- English
6
A12509
Page 7
DIMENSIONS (cont.)
Fig. 4 -- FB4CNF -- Metric
7
A12513
Page 8
DIMENSIONS (cont.)
Fig. 5 -- FB4CNP -- Metric
8
A14027
Page 9
DIMENSIONS (cont.)
Fig. 6 -- FB4CNF and FB4CNP -- Metric
9
A12511
Page 10
PHYSICAL DATA
ORDERING NO.
FB4CN(F,P)018(0,T,L)18,000
FB4CN(F,P)024(0,T,L)24,000
FB4CN(F,P)030(0,T,L)30,000
FB4CN(F,P)036(0,T,L)36,000
FB4CN(F,P)042(0,T,L)42,000
FB4CN(F,P)048(0,T,L)48,000
FB4CN(F,P)060(0,T,L)60,000
NOMINAL COOLING
CAPACITY (Btuh)
HeightWidthDepth
42--- 11/16 in.
1084mm
42--- 11/16 in.
1084mm
49--- 5/8 in.
1260mm
49--- 5/8 in.
1260mm
49--- 5/8 in.
1260mm
49--- 5/8 in.
1260mm
53--- 7/16 in.
1357mm
DIMENSIONS
14--- 5/16 in.
363mm
14--- 5/16 in.
363mm
17--- 5/8 in.
447mm
17--- 5/8 in.
447mm
21--- 1/8 in.
536mm
21--- 1/8 in.
536mm
21--- 1/8 in.
536mm
22--- 1/16 in.
560mm
22--- 1/16 in.
560mm
22--- 1/16 in.
560mm
22--- 1/16 in.
560mm
22--- 1/16 in.
560mm
22--- 1/16 in.
560mm
22--- 1/16 in.
560mm
SHIPPING
WEIGHT
112 lb
51 kg
112 lb
51 kg
122 lb
55 kg
122 lb
55 kg
157 lb
71 kg
157 lb
71 kg
175 lb
79 kg
SPECIFICATIONS
FB4C18243036424860
EVAPORATOR COIL
Face Area (sq. ft)2.232.974.455.93
ConfigurationSlopeA
FB4CNF
Metering Device
( Te f l o n --- r i n g pi s t o n )
Puron Refrigerant
1. Airflow based upon dry coil at 230v with factory ---approved filter and electric heater (2 element heater sizes 018 through 036, 3 element
heater sizes 042 through 060). For FB4C models, airflow at 208 volts is approximately the same as 230 volts because the multi ---tap ECM
motor is a constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
2. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 042 --- 060 sizes must have supply static greater than 0.20 in. wc.
3. Airflow above 400 cfm/ton on 048--- 060 size could result in condensate blowing off coil or splashing out of drain pan.
Tap 3701660616581537499
Tap 2614569534486436398
Tap 1614569534486436398
Tap 5969936892835763676
Tap 4826795766743706660
Tap 3826795766743706660
Tap 2701660616581537499
Tap 1617592552507472420
Tap 511081090106510341009974
Tap 410261000969938899865
Tap 310261000969938899865
Tap 2909873842799762724
Tap 1825795757722674634
Tap 5130112761245121811761121
Tap 4122711911169114311051074
Tap 3122711911169114311051074
Tap 21087106210301001966930
Tap 110261000969938899865
Tap 5156015441507146414241358
Tap 4141913971358132012791239
Tap 3141913971358132012791239
Tap 2124912201184114210931052
Tap 1124212051158111010691026
Tap 5174317121679164216101574
Tap 4166916341599156415311499
Tap 3166916341599156415311499
Tap 2145214131377133913081271
Tap 1130012561221118211421101
Tap 5189718671836180817741736
Tap 4181717851757172416931655
Tap 3181717851757172416931655
Tap 2165716211589155715181474
Tap 1144314121377133212861243
CFM --- C u b i c F t p e r M i n u t eEWB --- Entering Wet Bulb _F(_C) LWB --- Le a v i n g W e t B u l b _F(_C)TC --- Gross Cooling Capacity 1000 Btuh
SHC --- Gross Sensible Capacity 1000 Btuh BF --- By p a s s Fa c t o rMBH --- 1000 Btuh
12
Page 13
PERFORMANCE DATA (cont.)
NOTES:
1. Contact manufacturer for cooling capacities at conditions
other than shown in table.
2. Formulas:
Leaving db = entering db --sensible heat cap.
1.09 x CFM
Leaving wb = wb corresponding to enthalpy of air leaving
coil (h
h
)
lwb
lwb=hewb
--total capacity (Btuh)
4.5xCFM
where h
= enthalpy of air entering coil. Direct interpola-
ewb
tion is permissible. Do not extrapolate.
3. SHC is based on 80_F(27_C) db temperature of air enter-
ing coil. Below 80_F(27_C) db, subtract (Correction Factor
x CFM) from SHC. Above 80_F(27_C) db, add (Correc-
BYPASS
FACTOR
0.10.0981.962.943.924.91
0.200.871.742.623.494.36
0.300.761.532.293.053.82
Interpolation is permissible.
Correction Factor = 1.09 x (1 --- BF) x (db --- 80)
SHC CORRECTION FACTOR
ENTERING AIR DRY-- BULB TEMPERATURE (_F)
7978777675Under 75
8182838485Over 85
ENTERING AIR DRY-- BULB TEMPERATURE (_C)
2625252424Under 75
2728282929Over 85
Correction Factor
Use
formula
shown
below
tionFactorxCFM)toSHC.
4. Bypass Factor = 0 indicates no psychometric solution. Use
bypass factor of next lower EWB for approximation.
FB4C AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (in wc) AT
INDICATED AIRFLOW (DRY TO WET COIL)
The airflow performance data was developed using fan coils with 10--- kW electric heaters (2 elements) in the 018 through 036 size units and
15---kW heaters (3 elements) in the 042 through 060 size units. For fan coils with heaters of a different number of elements, the external available static at a given CFM from the curve may be corrected by adding or subtracting available external static pressure as indicated above.
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
HEATER
ELEMENTS
FB4C
042 --- 060
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
MINIMUM CFM AND MOTOR SPEED SELECTION
FB4C
018525525525—600—————
024700700700—700775————
030—875875—875875—1060——
036—1050970970970920—1040——
042——122512251225122512251225——
048——14001400140014001400140014001400
060——17501750175017501750175017501750
Speed Tap 4 (white wire) is used for electric heat only. White wire must remain on tap 4.
3589101518202430
HEATER kW
13
Page 14
PERFORMANCE DATA (cont.)
FIELD--INSTALLED FILTER STATIC PRESSURE DROP (in wc)
*Usecopperwireonly.Use75_C only in this application. When using non --- metallic (NM) sheathed cable, wire size required should be based on that of 60_C
conductors, instead of wire sizes shown in table above per NEC Article 336--- 26.
NOTE: If branch circuit wire length exceeds 100 ft (30 m), consult NEC 215 ---2 to determine maximum wire length. Use 2% voltage drop.
FLA --- Fu l l L o a d A m p s
15
Page 16
Dual Circ uit
208/230V (Ft)‡
Max Wire Length
Single
Circuit
Dual Circ uit
208/230V
Single
Max Fuse/Ckt Bkr Amps
Circuit
208/230V (FT)‡
MAX WIRE L ENGTH
AMPS
208/230V
MAX FUSE/CKT BKR
Dual Circ uit
208/230V
Min Gnd Wire Size
Single
Min Wire Size (AWG)
Min Ampacity
208/230V
Circuit
Dual Circui t
208/230V†
Single
Circuit
Dual Circ uit
208/230V*
Single
Circuit
Dual Circui t
Single
Circuit
BRANCH CIRCUIT
HEATER AMPS
MIN WIRE SIZE (AWG)
MIN AMPACITY
HEATER AMPS
MIN GND
WIRE SI ZE
208/230V†
208/230V*
208/230V
208/230V
ACCESSORY ELECTRIC HEATER ELECTRICAL DATA
INTERNAL
PHA
kW
FIELD MULTIPOINT WIRING OF 24--AND 30--kW SINGLE PHASE
*Includes blower motor amps of largest fan coil used with heater.
{Copper wire must be used. If other than uncoated (non--- plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code
(ANSI/NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop n ot to exceed 2%.
**Field convertible to 3 phase.
{{Field convertible to 1 phase, single or multiple suppl y circuit.
NOTES:
1. For fan coil sizes 018---036.
2. For fan coil sizes 042---060.
3. Single circuit application of F15 and F20 heaters requires single ---point wiring kit accessory.
When using units with 20--, 24--, and 30--kW electric heaters, maintain a 1--in. (25mm) clearance from combustible materials to discharge
plenum and ductwork and maintain a distance of 36--in. (914mm) from the unit. Use an accessory downflow base to maintain proper
clearance on downflow installations. Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric
heater is installed, use heat resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing
through unconditioned space must be insulated and covered with vapor barrier
CKT BKR*
QTY/SIZE
ACCESSORIES
ITEMACCESSORY PART NO.*FAN COIL SIZE USED WITH
1.Disconnect KitKFADK0201DSCCooling controls and heaters 3--- through 10 --- kW
Accessory Kits Description Suggested and Required Use
1. Disconnect Kit
The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.
SUGGESTED USE: Units for 3-- through 10--kW electric resistance heaters and cooling controls.
2. Downflow Base Kit
This kit is designed to provide a 1--in. (25mm) minimum clearancebetween unit discharge plenum, ductwork, and combustible materials. It also provides a gap--free seal with the floor.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
3. Downflow Conversion Kit
Fan coils are shipped from the factory for upflow or horizontal--left applications. Downflow conversion kits provide proper condensate
water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A--coils.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
4. Downflow/Horizontal Conversion Gasket Kit
This kit provides the proper gasketing of units when applied in either a downflow or horizontal application.
REQUIRED USE: Fan coils in either downflow or horizontal applications.
5. Horizontal Applications -- Water Management Kit
This kit provides proper installation of fan coils under conditions of high static pressure and high relative humidity.
SUGGESTED USE: All fan coils.
6. Single Point Wiring Kit
The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run
two heavy--gauge, high--voltage wires into the fan coil rather than 4 light--gauge, high--voltage wires.
SUGGESTED USE: Fan coils with 15-- and 20--kW fused heaters only.
7. Filter Kit (12 pack)
The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and
prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and, in turn, the
efficiency of the system.
SUGGESTED USE: To replace filters in fan coils.
REQUIRED USE: All units unless a filter grille is used.
8. Fan Coil Filter Cabinet
This cabinet is mounted to the fan coil on the return air end and designed to slip over the outer fan coil casing. The cabinets are
insulated using the same insulation as production fan coils. They are designed for the removal of particulates from indoor air using
FILXXFNC00(14, 17, 21, 24) media filter cartridges. These fan coil media filter cartridge kits are designed for the removal of particles
from indoor air. The cartridge is installed in the return air duct next to the air handler or further upstream.
SUGGESTED USE: All fan coils.
9. Condensate Drain Trap Kit
This kit consists of 50 PVC condensate traps. Each trap is pre--formed and ready for field installation. This deep trap helps the system
make and hold proper condensate flow even during blower initiation.
SUGGESTED USE: All fan coils.
10. Air Cleaner 240--volt Conversion Kit
The AIRA electronic air cleaner comes ready for 115--v operation.
REQUIRED USE: This kit is required when running 240--volt circuit to air cleaner.
11. Standard Filter Rack Kit
This kit mounts in fan coil filter rack area and modifies the existing filter rack to support standard 1--in. filter sizes.
SUGGESTED USE: Fan coils using standard filter sizes.
E2014 Bryant Heating & Cooling Systems D 7310 W. Mo rris St. D Indianapolis, IN 46231Edition Date: 02/14 U.S. Export Classification: EAR99.
Manufacturer reserves the right to dis continue, or change at any time, specifications or designs without notice and without incurring obligations.
18
Catalog No. PDSFB4CNF--- 08
Replaces: PDSFB4CNF---07
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.