Bryant-Carrier FB4C, FY5B Installation Manual

FB4C FY5B
FAN COIL UNITS
FOR PURONr REFRIGERANT
SIZES 018 TO 060
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
PAGE
SAFETY CONSIDERATIONS 1........................
INTRODUCTION 1..................................
HEATER PACKAGES 2..............................
INSTALLATION 2...................................
Step 1 — Check Equipment 2.........................
Step 2 — Mount Unit 2..............................
Step3—AirDucts 4...............................
Step 4 — Electrical Connections 4.....................
Step 5 — Refrigerant Tubing Connection and Evacuation 7..
Step 6 — Refrigerant Flow--Control Device 7.............
Step 7 — Condensate Drains 8........................
Step 8 — Accessories 9..............................
Step 9 — Sequence of Operation 10....................
START--UP PROCEDURES 10.........................
CARE AND MAINTENANCE 10.......................
AIRFLOW PERFORMANCE TABLES 11................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instruction manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
.
which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing unit, always turn off all power to unit. There may be more than 1 disconnect switch. Turn off accessory heater power if applicable. Lock out and tag switch with a suitable warning label.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when handling parts.
INTRODUCTION
Models FB4C and FY5B are Puron Fan Coils designed for installation flexibility. These units are designed to meet the low air leak requirements currently in effect.
FB4C uses a refrigerant piston metering device (018 thru 048) and TXV (060) with an X13 integral electronically commutated motor for efficiency. These units have be designed for upflow, downflow (kit required), and horizontal orientations, including manufactured and mobile home applications.
FY5B uses a refrigerant piston metering device (018 thru 048) with 2--speed PSC (permanent split capacitor) motors and TXV with 3--speed PSC motor for the 060 size, These units can be used for upflow or downflow (kit required) orientations, including manufactured and mobile homes applications.
These units require a field supplied air filter, and are designed specifically for Puron refrigerant air conditioners and heat pumps as shipped. These units are available for systems of 18,000 through 60,000 Btuh nominal cooling capacity. Factory--authorized, field -­installed electric heater packages are available in sizes 5 through 30kW. See Product Data literature for all available accessory kits.
HEATER PACKAGES
This unit may or may not be equipped with an electric heater package. For units not equipped with factory--installed heat, a factory--approved, field--installed, UL listed heater package is available from your equipment supplier. See unit rating plate for a list of factory--approved heaters. Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty. If fan coil contains a factory--installed heater package, minimum circuit ampacity (MCA) and maximum fuse/breaker may be different than units with a same size field--installed accessory heater. The differences is not an error and is due to calculation difference per UL guidelines.
INSTALLATION
Step 1 — Check Equipment
Unpack unit and move to final location. Remove carton taking care not to damage unit. Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete.
Locate unit rating plate which contains proper installation information. Check rating plate to be sure unit matches job specifications.
FB4C / FY5B
Step 2 — Mount Unit
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.
IMPORTANT: When unit is installed over a finished ceiling and/or living area, building codes may require a field--supplied secondary condensate pan to be installed under the entire unit. Some localities may allow as an alternative, the running of a separate, secondary condensate line. Consult local codes for additional restrictions or precautions.
A. Upflow Installation
If return air is to be ducted through a floor, set unit on floor over opening and use 1/8 to 1/4--in (3 to 6 mm) thick fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per dimensions. (See Fig. 1.) A field--supplied bottom closure is required.
018 - 048 21" (533 mm) FRONT SERVICE 060 - 060 24" (610mm) CLEARANCE
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
B. Downflow Installation
In this application, field conversion of the evaporator is required using accessory downflow kit along with an accessory base kit. Use fireproof resilient gasket, 1/8 to 1/4--in (3 to 6 mm) thick, between duct, unit, and floor.
POWER ENTRY
OPTIONS
UNIT
018
A COIL
UNITS
PRIMARY DRAIN
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
024 - 030 036 19" (483 mm)
1.5" (38 mm) 19" (483 mm)
2.5" (64 mm)
Fig. 1 -- Slope Coil Unit in Upflow Application
FIELD SUPPLIED SUPPLY DUCT
LOW VOLT ENTRY OPTIONS
A 12" (305 mm) 17" (432 mm)
FIELD MODIFIED SIDE RETURN
A
LOCATION FOR SLOPE COIL UNITS ONLY
FIELD SUPPLIED RETURN PLENUM
A07565
!
CAUTION
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A--coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.
NOTE: To convert units for downflow applications, refer to Installation Instructions supplied with kit for proper installation. For slope fan coils, use kit Part No. KFADC0201SLP. For A--coils, use kit Part No. KFADC0401ACL. Use fireproof resilient gasket, 1/8 to 1/4--in (3 to 6 mm) thick, between duct, unit, and floor.
NOTE: Gasket kit number KFAHD0101SLP is also required for all downflow applications to maintain low air leak/low sweat performance.
C. Horizontal Installation (FB4C only)
Units must not be installed with access panels facing up or down. All other units are factory built for horizontal left installation. (See Fig. 2 and 3.) When suspending unit from ceiling, dimples in casing indicate suitable location of screws for mounting metal support straps. (See Fig. 2.)
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
For optimum condensate drainage performance in horizontal installations, unit should be leveled along its length and width.
For horizontal applications having high return static and humid return air, the Water Management Kit, KFAHC0125AAA, may need to be used to assist in water management.
A-COIL
HORIZONTAL LEFT
PRIMARY DRAIN
018-048 21" (533 mm) 060-060 24" (610 mm) FRONT SERVICE CLEARANCE (FULL FACE OF UNIT)
1.75" (44 mm) FILTER ACCESS CLEARANCE
A07566
LOW VOLT ENTRY OPTIONS
POWER ENTRY OPTIONS
UNIT
FIELD SUPPLIED HANGING STRAPS
SECONDARY DRAIN
PRIMARY DRAIN
SECONDARY DRAIN
Fig. 2 -- Slope Coil Unit in Horizontal Left Application
(FB4C only)
2
DRAIN PAN
SUPPORT BRACKET
A
FACT ORY SHIPPED HORIZONTAL LEFT
APPLICATION
B C
HORIZONTAL
DRAIN PAN
AIR SEAL ASSEMBLY
REFRIGERANT
CONNECTIONS
Fig. 3 -- A--Coil in Horizontal Left Application
(Factory Ready FB4C only)
NOTE: Modular units can be disassembled and components
moved separately to installation area for reassembly. This process accommodates small scuttle holes and limiting entrances to installation sites. (See Fig. 4.)
BLOWER BOX
2 SCREWS
REAR CORNER BRACKET
2 SCREWS
COIL BOX
2 SCREWS
Fig. 4 -- Removal of Brackets on Modular Units Horizontal
Right Conversion of Units With Slope Coils (FB4C only)
NOTE: Gasket kit number KFAHD0101SLP is required for
horizontal slope coil conversion to maintain low air leak/low sweat performance.
1. Remove blower and coil access panel and fitting panel. (See Fig. 5.)
2. Remove coil mounting screw securing coil assembly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down. (See Fig. 5.)
5. Attach coil to casing flange using coil mounting screw pre­viously removed.
6. Make sure the pan cap in the fitting door is properly seated on the fitting door to retain the low air leak rating of the unit.
7. Add gaskets from kit KFAHD per kit instructions.
8. Align holes with tubing connections and condensate pan connections, and reinstall access panels and fitting panel.
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install after brazing.
COIL
BRACKET
COI L
SUPPORT
RAIL
DRAIN PAN
SUPPORT BRACKET
COIL
BRACKET
PRIMARY DRAIN
HORIZONTAL LEFT
SECONDARY DRAIN
HORIZONTAL LEFT
A00072
A95293
COIL
SUPPORT
RAIL
SLOPE COIL
COIL MOUNTING SCREW
SKI
DRAINPAN
REFRIGERANT CONNECTIONS
PRIMARY DRAIN
SECONDARY DRAIN
BLOWER ASSEMBLY
Fig. 5 -- Conversion for Horizontal Right Applications
Using a Slope Coil (FB4C only)
Horizontal Right Conversion of Units With A--Coils
1. Remove blower and coil access panels. (See Fig. 6.)
A
B C
COIL
SUPPORT
RAIL
COIL
BRACKET
DRAIN PAN
SUPPORT BRACKET
COIL
SUPPORT
RAIL
BRACKET
HORIZONTAL
PRIMARY DRAIN
HORIZONTAL RIGHT
SECONDARY DRAIN HORIZONTAL RIGHT
REFRIGERANT
CONNECTIONS
COIL
DRAIN PAN
AIR SEAL ASSEMBLY
Fig. 6 -- Conversion for Horizontal Right Applications
Using A--Coil (FB4C only)
2. Remove metal clip securing fitting panel to condensate pan. Remove fitting panel.
3. Remove 2 snap--in clips securing A--coil in unit.
4. Slide coil and pan assembly out of unit.
5. Remove horizontal drain pan support bracket from coil sup­port rail on left side of unit and reinstall on coil support rail on right side of unit. (See Fig. 7.)
DRAIN PAN
SUPPORT BRACKET
Fig. 7 -- Drain Pan Support Bracket
6. Convert air--seal assembly for horizontal right.
a. Remove air--seal assembly from coil by removing 4
screws.(SeeFig.6.)
b. Remove air splitter (B) from coil seal assembly by re-
moving 3 screws. (See Fig. 3--factory shipped inset.)
A03001
HORIZONTAL
RIGHT
APPLICATION
A00071
A07571
FB4C / FY5B
3
Loading...
+ 7 hidden pages