50ZHC
14 SEER Single P ackaged Heat Pump System
with Puronr (R---410A) Refrigerant
Single Phase
2 to 5 Nominal Tons (024 ---060)
Product Data
Single--Packaged Heat Pump Units with:
S Easy installation design
S Corrosion--proof unit base
S Class leading sound ratings
S Sloped drain for improved indoor air quality
S Scroll compressors
S Front and side service access
S Louvered panel coil protection
S Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1--in. W.C with all present air
inlets, air outlets, and condensate drain port(s) sealed.
This unit is a packaged heat pump for manufactured housing,
residential, and light commercial applications. Factory assembled
package is a compact, horizontal supply and return unit, combining
easy installation and maintenance with efficient performance.
EASY TO INSTALL—The units are lightweight, compact single
A10165
024--048 Size
A150067
060 Size
Fig. 1 -- Unit 50ZHC
package units that are easy to handle. Every size unit has an
identical 32 by 51--in. (813 by 1295 mm) footprint to make job
site planning simple. The efficient design uses less sheet metal and
makes the 50ZHC units lighter than competitive units. The unit can
be easily positioned on the job site with the hand-- holds built into
the unit basepan.
AERODYNAMIC FAN BLADE DESIGN reduces overall sound
by up to 3dBA; low as 73dBA.
SERVICE ACCESS—The units are designed to be serviced from
both front and side. Routine maintenance tasks, such as coil
cleaning, are sped up with the multiple side panels design.
CORROSION PROOF UNIT BASE—The unit features a tough,
high--tech, single--piece composite material unit base with an
integrated drain. The composite material eliminates the potential
problem of rust and premature replacement which are common
with standard metal pans. Each unit base is sloped to eliminate
standing water. This feature minimizes the amount of standing
water inside the unit, which limits mold and mildew growth.
DURABLE STEEL CABINET—The watertight construction
and corrosion--resistant finish will keep it looking like new for
years. A specialized paint treatment process ensures quality
protection against the elements. A compact, low--profile design
utilizes a louvered coil enclosure for maximum protection against
hail damage and vandalism.
SCROLL COMPRESSORS—Each unit comes standard with a
scroll compressor. Each scroll compressor is hermetically sealed
against contamination to help promote longer life and dependable
operation. All scroll compressors have internal high--pressure and
overcurrent protection.
COIL EFFICIENCY—Indoor and outdoor coils are computer
designed for optimum heat transfer and cooling efficiency.
DEFROSTSYSTEM—Thesystemprovidestime/
temperature--based defrost cycles to maintain unit efficiency. This
1
FEATURES/BENEFITS
Page 2
highly reliable system monitors coil temperature and initiates a
defrost cycle only if it is required. The defrost cycle ends as soon as
defrosting is complete.
ACCESSORY ELECTRIC HEATERS —A variety of accessory
electric heaters are available for these units. These heaters are
comprised of a separate heater module mounted on the blower inlet
and remote mounted controls located in the unit control box.
Single point electrical connections are provided for powering both
the heater and the unit.
START COLLARS—Start collars are provided with each unit to
provide easy connection to the structure ductwork.
MODEL NUMBER NOMENCLATURE
DEPENDABLE COMPONENTS—Direct--drive, multi--speed
blower motor is standard on all models.
DIRECT--DRIVE, PSC OUTDOOR--FAN MOTORS are
designed to help reduce energy consumption and provide for
cooling operation down to 40F(4.4C). It’s high efficiency design
ensures high performance with most duct systems.
REFRIGERANT SYSTEM is designed to provide dependability.
Liquid refrigerant filter driers are used to promote clean,
unrestricted operation. Each unit leaves the factory with a full
refrigerant charge and is fully run tested. Refrigerant service
connections make checking operating pressure easier.
LEGEND
dB---Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP---Coefficient of Performance
* Air Conditioning Heating & Refrigeration Institute
† At "A" conditions--80°F (26.7°C) indoor db/67°F (19.4°C) indoor wb & 95°F (35°C) outdoor db.
** Rated in accordance with U.S. Government DOE Department of Energy) test procedures and/or AHRI Standards 210/240.
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F (26.7°C) db, 67°F wb (19.4°C) indoor entering---air temperature and 95°F db (35°C) outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
CAPACITY AT 47° F
(8.3° C) (Btuh)
COP @ 47° F
(8.3° C)
NET COOLING CAPA-
CITY AT 95° F (35° C)
(Btuh)
NET HEATING
CAPACITY AT 17° F
(-8.3° C) (Btuh)
EER†SEER**
COP @ 17° F
(-8.3° C)
HSPF**
50ZHC
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
1252505001000200040008000
3
Page 4
PHYSICAL DATA
UNIT SIZE024030036042048060
NOMINAL CAPACITY (ton)22.533.545
SHIPPING WEIGHT (lb)
COMPRESSOR TYPESCROLL
REFRIGERANTR-410A
REFRIGERANT QUANTITIY (lb)
OUTDOOR METERING DEVICETXVPistonTXVPiston
ORIFICE ID (in.)
OUTDOOR COIL
ROWS...FINS/in.
FACE A REA ( sq . f t)
OUTDOOR FAN
NOMINAL AIRFLOW (cfm)
DIAMETER (in.)
DIAMETER (mm)
MOTOR HP (RPM)
50ZHC
*Required filter sizes shown are based on the AHRI (Air Conditionin g, Heating & Refrigeration Institute) rated airflow at a velocity of 300 ft/min (91 m) for throwaway type or 450 ft/min (137 m) for high capacity type. Recommended filters are 1 --- in. (25 mm) thick.
INDOOR METERING DEVICEPistonTXVTXV
ORIFICE ID (in.)
INDOOR COIL
ROWS...FINS/in.
FACE A REA ( sq . f t)
NOMINAL COOLING AIRFLOW (cfm)
INDOOR BLOWER
NOMINAL SIZE D x L (in.)
MOTOR (HP)
HIGH-PRESSURE SWITCH (psig)
LOW-PRESSURE SWITCH (psig)
CUTOUT
RESET (AUTO)
CUTOUT
RESET (AUTO)
RETURN-AIR FILTERS
THR OWAWAY (in.)
(kg)
QUANTITY (kg)
(mm)
(mm)
(mm)
(mm)
312
142
7.00
3.18
---
---
2...20
9.1
2000
20
508
1/8 (825)
0.059
1.499
3...12
4.3
800
10 x 8
254 x 203
1/3
20x20x1
508x508x25
333
151
7.20
3.27
0.049
1.245
2...20
10.2
2000
20
508
1/8 (825)
0.059
1.499
3...14
4.3
1000
11 x 9
279 x 229
1/3
610x762x25
24x30x1
334
152
6.30
2.86
0.057
1.448
2...20
10.2
2800
20
508
1/4 (1100)
0.067
1.702
3...12
4.9
1200
11 x 9
279 x 229
1/2
650 +/- 15
420 +/- 25
20 +/- 5
45 +/- 10
388
177
9.10
4.13
0.059
1.499
2...20
13.0
3100
20
508
1/4 (1100)
0.076
1.9304
3...14
4.9
1400
11 x 9
279 x 229
1/2
407
185
7.70
3.49
---
---
2...20
15.5
3100
20
508
1/4 (1100)
---
---
3...14
4.9
1600
11 x 9
279 x 229
3/4
24x36x1
610x914x25
475
215
11.5
5.22
0.070
1.778
2...20
15.5
3300
20
508
1/3 (1100)
---
---
3...14
4.9
1700
12 x 11
305 x 279
1
4
Page 5
OPTIONS AND ACCESSORIES
FACTOR Y
ITEMDESCRIPTION
Coil OptionsBase u nit with tin plated indoor coil hairpinsX
Compressor Start Kit
Corporate Thermostats
Crankcase Heater
Electric HeatersElectric Heat SupplementX
Low Ambient Kit
Time Guard II
Refer to Price Pages for available accessories.
Compressor Start K it assists compressor start ---up by providing
additional starting torque.
Thermostats provide control for the system heating and cooling
functions.
Crankcase Heater provides anti ---floodback protection for low --load coolin g applications.
Low Ambient Kit (Motormaster II Control) allows the use of mechanical cooling down to outdoor temperatures as low as 0°F
( --- 18° C) when properly installed.
Automatically prevents the compressor from restarting for at least
4 minutes and 45 seconds after shutdown of the compressor. Not
required when a corporate programmable thermostat is applied.
The required heating capacity is 28,550 Btuh. Therefore, 11,810
Btuh (28,550 -- 16,740) additional electric heat is required.
Determine additional electric heat capacity in kW.
11,810 Btuh
3414 Btuh/kW
3.46 kW of heat required
=
Enter the Accessory Electric Heater Usage table on page 4 for
208/240v. single--phase, 030 unit. The 5--kW heater at 240v most
closely satisfies the heating required. To calculate kW at 230v,
multiply the heater kW by multiplication factor 0.92 found in the
Multiplication Factors table on page 4.
5 kW x 0.92 = 4.6 kW
4.6 x 3414 = 15,704 Btuh
To calculate kW at 208 v, see Multiplication Factors table on page
4.
Total unit heating capacity is 32,444 Btuh (16,740 +15,704).
II. SELECT UNIT BASED ON REQUIRED COOLING
CAPACITY
Enter Cooling Capacities table at condenser entering temperature
of 95F(35C), indoor air entering at 1000 cfm and 67F (19.4C)
ewb (entering wet bulb). The 030 unit will provide a total cooling
capacity of 28,800 Btuh and a sensible heat capacity of 21,600
Btuh.
For indoor--air temperature other than 80F edb (entering dry
bulb), calculate sensible heat capacity correction, as required, using
the formula found in Note 3 following the cooling capacities
tables.
NOTE: Unit ratings are net capacities.
III. SELECT ELECTRIC HEAT
Enter the 030 Heating Capacities table at 1000 CFM. At 70F
(21.1C) return indoor air and 20F(--6.7C) air entering outdoor
coil, the integrated heating capacity is 16,740 Btuh. (Select
integrated heating capacity value since deductions for outdoor--coil
frost and defrosting have already been made. No correction is
required.)
IV.DETERMINEFANSPEEDANDPOWER
REQUIREMENTS AT DESIGN CONDITIONS
Before entering the air delivery tables, calculate the total static
pressure required. From the given, the Accessory Electric Heat
Pressure Drop table, and the Filter Pressure Drop table, find:
External static pressure0.20 IN. W.C.
Filter0.09 IN. W.C.
Electric heat0.04
IN. W.C.
Total static pressure0.33 IN. W.C.
Enter the table for Dry Coil Air Delivery — Horizontal Discharge
at 1000 CFM and 230v high speed. The blower will deliver 1036
CFM @ 0.40 IN W.C. static pressure. This will adequately handle
job requirements.
50ZHC
9
Page 10
kW
BASED ON INDOOR ENT. AIR
AT 70 ºF AND AT RATED CFM
0.0
8.8
24
48
14.6
42
23.4
50ZHC
20.5
60
17.6
36
11.7
30
5.9
2.9
BALANCE POINT WORKSHEET
80
70
60
50
40
30
OUTDOOR TEMPERATURE, ºF
-10010203040506070
20
10
0
MBTUH
BUILDING HEAT LOSS, UNIT INTEGRATED HEATING CAPACITY,
Wet Coil Air Delivery*
(Deduct 10 percent for 208 Volt Operation)
230 VOLT HORIZONTAL DISCHARGE
50ZHC
UNIT
SIZE
024
030
036
042
048
060
*Air delivery values a r e based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric h ea ter pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occuratairflows below this point.
LEGEND
F L A --- F u l l L o a d Am p s
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
RLA --- Rated Load Amps
NOTES:
1. In compliance with NEC (National El ectrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be Power Supply fuse or circuit breaker.
2. Minimum wire size is based on 60_Ccopperwire.Ifotherthan60_C wire is used, or if length exceeds wire len gth in tabl e, determine size from NEC.
*Heater capacity (kW) based on heater vol tage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
When power is supplied to unit, the transformer (TRAN) is
energized.
Cooling Operation — With a call for cooling (O,Y,G), the
reversing valve, contactor, and indoor fan are energized. When the
cooling demand is met, Y and G are de--energized, shutting off the
contactor (compressor, outdoor fan). The indoor fan stops after a
60 second delay.
Heating Operation — With a call for heating (Y,G), the contactor
and indoor fan are energized. When the heating demand is met, Y
and G are de--energized, shutting off the contactor (compressor,
outdoor fan). The indoor fan stops after a 60 second delay.
Continuous Fan — With the continuous indoor fan option
selected on the thermostat, G is continuously energized keeping the
indoor fan running at all times.
Defrost — The defrost control is a time/temperature control which
includes a field--selectable time period between defrost cycles of
30, 60, and 90 minutes. Electronic timer and defrost cycle start
only when contactor is energized and defrost thermostat (DFT) is
closed.
Defrost mode is identical to cooling mode, except outdoor fan
motor stops and a bank of optional electric heat turns on to warm
air supplying the conditioned space.
A14444
APPLICATION DATA
Condensate trap — A 2 --in. (51 mm) condensate trap must be field
supplied.
1” (25 mm) MIN
Maximum cooling airflow — To minimize the possibility of
condensate blow--off from the evaporator, airflow through the units
should not exceed 450 CFM/ton.
Minimum cooling airflow — The minimum cooling airflow is
350 cfm/ton.
Minimum cooling operating outdoor air temperature —All
standard units have a minimum ambient operating temperature of
40F(4.4C). With accessory low ambient temperature kit, units
can operate at temperatures down to 0F (--17.8C).
Maximum operating outdoor air temperature —Maximum
outdoor operating air temperature for cooling is 125F (51.7C).
.
TRAP
OUTLET
2” (51 mm) MIN.
23
Page 24
GUIDE SPECIFICATIONS
SMALL PACKAGED PRODUCT AIR--TO--AIR
HEAT PUMP CONSTANT VOLUME APPLICATION
HVAC GUIDE SPECIFICATIONS
SIZE RANGE:2 TO 5 TONS, NOMINAL (COOLING)
PART I -- GENERAL
SYSTEM DESCRIPTION
Outdoor packaged, electrically controlled, air--to--air heat
pump utilizing a scroll compressor for heating and cooling
duty. Unit shall discharge supply air horizontally as shown on
contract drawings.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with AHRI Standards
210/240, and 270. Designed in accordance with UL
Standard 1995.
B. Unit shall be designed to conform to ASHRAE 15 .
C. Unit shall be UL listed as a total package for safety
requirements.
D. Insulationandadhesive shallmeet NFPA 90A
50ZHC
requirements for flame spread and smoke generation.
DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
PART 2-- PRODUCTS
EQUIPMENT
A. General:
Factory--assembled, single piece, air-- to--air heat pump.
Contained within the unit enclosure shall be all factory wiring,
piping, controls, and refrigerant charge (R--410A).
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated,
bonderized, zinc--coated, prepainted steel.
2. Basepan shall be made of a single--piece non--corrosive,
composite material.
3. Indoor fan compartment cabinet surfaces shall be insulated
with a minimum 1/2 in. (12.7 mm)thick, flexible
insulation, coated on the air side, with aluminum foil--faced
insulation.
4. Cabinet panels shall be easily removable for servicing.
5. Unit shall have a factory-- installed, sloped, noncorrosive,
condensate drain.
6. Unit insulation conforms to ASHRAE 62P.
C. Fans:
1. Indoor Blower (Indoor Fan):
a. Fan shall be multispeed, direct drive as shown on the
equipment drawings.
b. Fan wheel shall be made from steel, be double--inlet
type. It shall have forward--curved blades with a
corrosion--resistant finish and shall be dynamically
balanced.
2. Outdoor fan shall be of the direct--driven propeller type
with aluminum blades, riveted to corrosion--resistant steel
spiders. It shall be dynamically balanced, and shall
discharge air upwards.
D. Compressor:
Fully--hermetic scroll type with external vibration isolation.
E. Coils:
1. Indoor and outdoor coils shall have aluminum--plate fins
mechanically bonded to seamless copper tubes with all
joints brazed.
2. Tube sheet openings shall be bellied to prevent tube wear.
3. Outdoor coil shall be protected by metal louvered panels.
F. Refrigerant Components:
1. TXV and AccuRater feed system.
2. Service gauge connections on suction and discharge lines.
3. Equipped with liquid line filter drier.
4. Equipped with accumulators on all sizes.
G. Controls and Safeties:
1. Unit Controls:
a. Unit shall be complete with self--contained low voltage
control circuit.
b. Unit shall incorporate an outdoor coil defrost system to
prevent excessive frost accumulation during heating
cycle and shall be controlled as follows:
(1.) Defrost shall be initiated on the basis of time and
coil temperature.
(2.) A 30/60/90-- minute timer shall activate defrost
cycle only if coil temperature is low enough to
indicate a heavy frost condition.
(3.) Defrost cycle shall terminate when defrost
thermostat is satisfied or shall have a positive
termination time of 10 minutes.
2. Safeties:
a. High Pressure Switch
b. Loss of Charge Switch
H. Operating Characteristics:
1. Unit shall be capable of starting and running at 125F
(51.7C) ambient outdoor temperature (60 size max ambient is 115F [46.1C]).
2. Compressor with standard controls shall be capable of
operation down to 40F(4.4C) ambient outdoor
temperature in cooling duty.
3. Compressor shall be capable of operation in heating cycle
down to --20F (--28.9C) ambient outdoor--air temperature.
4. Unit shall be capable of simultaneous heating duty and
defrost cycle operation when using electric heaters indicated
in Section L, Special Features.
I. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single
location.
J. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings
and inherent automatic--reset thermal overload protection.
3. Outdoor-- fan motor shall be totally enclosed.
24
Page 25
GUIDE SPECIFICATIONS (CONT)
K. Grille
1. Louvered Grille:
Louvered grille shall be standard on all units.
L. Special Features Available
1. Coil Options:
Shall include factory--installed optional tin--plated indoor
coil.
2. Thermostat:
To provide for two-- stage heating and one--stage cooling in
addition to manual or automatic changeover and indoor fan
control.
3. Low--Ambient Package:
Shall consist of a solid-- state control and outdoor coil
temperature sensor for controlling outdoor fan motor
operation, which shall allow unit to operate down to 0F
(--17.8C) outdoor ambient temperature in cooling.
4. Crankcase Heater:
Shall provide anti--floodback protection for low--load
cooling applications.
5. Electric heaters:
a. Electric heater shall be available as a field--installed
option.
b. Heater elements shall be open wire type, adequately
supported and insulated with ceramic bushings.
c. Electric heater packages must provide single point
power connection capability.
6. Compressor Start Kit:
Shall be available to give a boost to the compressor motor
at each start--up.
7. Outdoor Thermostat Kit:
Thermostat allows for staging of electric heaters based on
outdoor air temperature.
50ZHC
25
Page 26
50ZHC
Copyright 2015 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231Edition Date: 04/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
Catalog No: 50ZHC--- 02PD
Replaces: 50ZHC ---01PD
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.