Bryant ZONE PERFECT PLUS ZONEBB2KIT, ZONE PERFECT PLUS ZONEBB8KIT, ZONE PERFECT PLUS ZONEBB4KIT Zoning Design Manual

zoning design guide
ZONE PERFECT PLUS
ZONEBB2KIT ZONEBB4KIT ZONEBB8KIT
Cancels: New AP17-2
4-98
TABLE OF CONTENTS
Page
INTRODUCTION........................................................................1
OVERVIEW OF ZONING.........................................................1
What is Zoning? .........................................................................1
Is a Zoning System Right for This Job? ...................................2
ZONE PERFECT PLUS FEATURES....................................2-3
Humidification Control...............................................................2
Dehumidification Control...........................................................2
Damper Control Scheme............................................................2
OUT Zones .................................................................................3
Eight-Zone Capacity...................................................................3
Ease of Installation and Installer Test .......................................3
ZONE PERFECT PLUS COMPONENTS............................3-4
User Interface..............................................................................3
Equipment Controller .................................................................4
Zone Sensors...............................................................................4
Remote Sensors.......................................................................4
Smart Sensors..........................................................................4
Equipment Sensors .....................................................................4
Zone Dampers.............................................................................4
DESIGNING A ZONE PERFECT PLUS
INSTALLATION ..................................................................4-10
Assigning Zones .........................................................................5
Task 1—Assess the homeowner’s goals
for comfort and energy savings...............................5
Task 2—Conduct a site survey and make
preliminary zone assignments..................................5
Conducting a Site Survey....................................................5
Making Preliminary Zone Assignments .............................5
Sizing the Equipment .................................................................6
Task 3—Calculate block load estimates
and zone load estimates...........................................6
Task 4—Size heating and cooling equipment .......................6
Task 5—Choose register and return locations.......................7
Determining the Number of Returns..................................7
Selecting Return Locations .................................................7
Selecting Register Locations...............................................7
Meeting Zoning Challenges in Two Story Homes ............7
Recording Return and Register Locations..........................7
Task 6—Determine Bypass Needs.........................................7
Task 7—Lay out supply ducts and locate dampers...............7
Task 8—Determine appropriate damper and duct sizes........8
Determining Duct Size Based on Damper Size.................8
Why Oversized Ducts are not a Problem
with Zone Perfect Plus........................................................8
Task 9—Choose locations for zone sensors..........................9
Considerations When Retrofitting an Installation .....................9
Installing the System..................................................................9
COMPONENTS REQUIRED FOR
SPECIFIC APPLICATIONS..................................................10
Thermostatic Expansion Valve ................................................10
Heat Pump Temperature Sensor ..............................................10
Outdoor Temperature Sensor ...................................................10
SPECIAL APPLICATIONS USING
ZONE PERFECT PLUS ....................................................10-12
Understanding the Requirements of Setback with Zoning .....10
Using Multi-Stage Equipment with Zoning.......................10-11
Bypassing with Zoning .......................................................11-12
Bypassing to an Unconditioned Space.................................11
Bypassing to a Conditioned Space.......................................11
Bypassing Directly to the Air Return ..................................11
Bypassing Using OUT Zones...............................................12
GLOSSARY...........................................................................12-13
APPENDIX—WORKSHEETS............................................13-17
Zoning Design Checklist..........................................................14
Homeowner Survey.............................................................15-16
Floor Plan Worksheet...............................................................17
INTRODUCTION
This guide provides information to help you design a Zone Perfect Plus installation. It discusses general topics related to designing a residential zoning control system, as well as specific information about Zone Perfect Plus.
Use this guide to help you design a zoning system that will:
• Meet or exceed the homeowner’s expectations regarding the system’s capabilities. This goal will result in improved cus­tomer perception of your company, as well as repeat business and referrals.
• Protect the heating and cooling equipment used in the system. This goal will result in improved system reliability, longer life of heating and cooling equipment, and reduced warranty costs.
To design a zoning system to perform well under all conditions, it is essential to view the system as a whole at the design stage, rather than to begin selecting and installing individual components without a careful assessment of how they will work together. Be sure to perform all of the tasks described in this guide before you begin to install components.
This guide assumes that you have experience designing residential heating and air conditioning systems. The information in this guide is intended to supplement that experience. This guide does not address commercial applications of Zone Perfect Plus.
OVERVIEW OF ZONING
Residential zoning systems bring the possibility of total comfort control to the homeowner by providing exactly the right amount of heating or cooling to each living space. Comfort can be described as the absence of sensation. Ideally, a zoning system should keep the occupants of the home comfortable without them being aware of the system.
A. What is Zoning?
A zone is a conditioned space (one room or a group of rooms) that is separately controlled by its own sensor. There are as many zones in a home as there are sensors. A zoning system is a heating and cooling control system that maintains each zone of a home at a predetermined temperature and that maintains the home at a predetermined humidity. In addition to meeting these basic goals, Zone Perfect Plus is designed to:
—1—
• Direct conditioned air proportionately based on the needs of each zone, so that the zone(s) with the greatest demand receive relatively more conditioned air.
• Keep the sound produced by the system low enough that residents will not find it objectionable.
• Conveniently interface with and protect the home’s heating and cooling equipment.
• Maintain at least the minimum airflow necessary to keep heating and cooling equipment running efficiently.
B. Is a Zoning System Right for This Job?
When designing a zoning system, it is important to keep in mind what a zoning system can and cannot do. A zoning system is only part of a complete heating and cooling system for a residence. A home’s heating and cooling system has a limited heating and cooling capacity. A zoning system cannot increase that capac-
ity.
A zoning system reduces the effective size of the air distribution system as dampers are adjusted and closed to meet the needs of zones. The primary challenge when designing a zoning system is to make sure that the air distribution system cannot become so effectively small that the reduction in airflow causes one of the following problems:
• Air noise becomes excessive.
• The heating or cooling equipment is shut down because temperature limits are exceeded.
• The life of the equipment is reduced because of stresses related to excess temperatures.
The addition of a zoning system will not correct existing duct problems. A zoning system will compensate for oversized ducts,
but might make a bad situation worse in the case of undersized ducts. There are many ways to make a marginal duct system perform better. Most of these approaches involve changing ducts, registers, and/or heating or cooling equipment.
PLUS
ZONE PERFECT
This section briefly describes features that are new in the Zone Perfect Plus system and that distinguish this system from both Zone Perfect and other residential zoning systems.
Zone Perfect Plus’s innovative features include:
• Humidification control
• Dehumidification control
• Sophisticated damper control scheme
• OUT zones
• Bryant Access Home Zoning Software
• Eight-zone capacity
• Improved ease of installation and installer testing.
A. Humidification Control
If a humidifier is included in the heating and cooling system, Zone Perfect Plus can directly control it. A solid-state humidity sensor is built into the User Interface to monitor and control humidity in the home. The Equipment Controller’s HUM output controls any humidifier with a 24-vac input.
The homeowner can set a humidify set point to any value between 10 percent and 45 percent relative humidity, or can turn off the humidify feature. When the humidity drops 2 percent below the set point in the heating mode, the system activates the HUM output to turn on the humidifier. When the humidity rises 2 percent above the set point in the heating mode, the system turns off the HUM output. Humidification is provided only in the heating mode.
If the system includes an outdoor temperature (ODT) sensor, the installer or homeowner can select an automatic humidity level adjustment. This selection provides a 1 percent reduction in the
FEATURES
humidify set point for every 2°F reduction in outdoor temperature. The homeowner can change the system’s humidify set point at any time, and the system automatically adjusts the set point in response to the outdoor temperature. This feature helps prevent sweating of windows in very cold weather while allowing higher humidity levels in warmer weather.
The system can be set to provide humidification only when there is a humidify demand and any heat output (heat pump, furnace, or auxiliary heat) is on. Alternatively, the system can be set to turn on the HUM output and the blower when there is a humidify demand. This selection allows humidification when there is no heat de­mand.
B. Dehumidification Control
The Equipment Controller’s dehumidify output can be used to control any 24-vac device that decreases humidity when its control signal is removed. Zone Perfect Plus includes an extensive set of features for enhancing and controlling dehumidification, particu­larly when used with a variable-speed (ICM) blower.
The homeowner can set a dehumidify set point, separate from the humidify set point, between 50 percent and 90 percent relative humidity, or can turn off the dehumidify feature. When the humidity rises 2 percent above the set point in the cooling mode, the system turns off the dehumidify output. When the humidity falls 2 percent below the set point in the cooling mode, the system turns on the dehumidify output, supplying 24vac. Dehumidifica­tion is provided only in the cooling mode.
Zone Perfect Plus provides the following modes of humidification control:
Mode 1: When an ICM blower with a dehumidify input is used
with the system, the Equipment Controller’s dehumidify output can be connected to it. This connection provides reduced cooling airflow while dehumidification is needed, yielding better moisture removal from cooling air.
Mode 2: If the system has a 2-speed compressor and a PSC
blower, a dehumidify demand makes the compressor operate at high speed only for any cooling demand. High-speed operation provides better water removal than low-speed operation under these circumstances.
Mode 3: In a standard system with a PSC blower, Zone Perfect
Plus lowers the cooling set point up to 3°F in response to dehumidify demand. This feature increases the equipment’s run time and lowers the evaporator coil temperature.
Mode 4: The vacation mode optional feature provides humidity
control by operating the cooling system when cooling is not required. If the humidity rises above the dehumidify set point, the system executes a special dehumidification routine. As long as zone temperatures are not less than 70°F, a dehumidify demand turns on the cooling equipment, limiting its ON time to no more than 7 minutes at a time.
C. Damper Control Scheme
Up to 3 dampers can be wired in parallel and connected to 1 zone output. A multi-damper enabler is not needed.
Using the set points and temperatures for each zone within the system. Zone Perfect Plus determines whether active heating or cooling is required, the zoning system:
1. Fully opens 1 or more dampers and positions others so that all zones will be conditioned back to their set points at the same time. Based on experience, the system learns the best damper positions for meeting the home’s current demand for heating and cooling and starts from these positions when it determines that heating or cooling is required.
2. Turns on the necessary heating or cooling equipment.
3. While the equipment is on, once every 2 minutes makes small adjustments in damper positions so that all zones converge on their set points at the same time.
—2—
4. Turns off the equipment when all zones reach their set points.
5. Leaves dampers in their final positions while the equipment is off.
6. If the equipment does not run for 2 hours, fully opens all dampers.
Thus, the zoning system controls the damper(s) for each zone based on the overall needs of the home and the relative need of the zone. This scheme makes smooth and efficient use of the system’s heating and cooling capacity.
When all zones require conditioning and all dampers are fully open, there is some reduction in airflow velocity and the air distribution system might not throw air as well as one might want. The zoning system compensates for this reduction in airflow velocity by partially closing dampers to zones that are improving more quickly than others. This feature allows increased airflow velocity in the remaining ducts, helping those zones become conditioned more quickly than would otherwise be the case.
D. OUT Zones
Zone Perfect Plus has a new feature that lets the homeowner assign OUT status to any zone with the touch of a button. By assigning OUT status to a zone, the homeowner tells the system that the selected zone is unoccupied and does not require conditioning. The homeowner can set zones to OUT at any time, or OUT can be programmed according to a schedule, like temperature set points are programmed.
The system normally supplies no conditioning to an OUT zone. If the temperature in an OUT zone exceeds 85°F or falls below 60°F, the system supplies conditioning to maintain the zone within these limits.
The system uses OUT zones to relieve the heating or cooling equipment under equipment overload conditions. If the total demand from all zones is such that the airflow is insufficient (or bypassing is excessive), the leaving air temperature (LAT) sensor or heat pump temperature (HPT) sensor detects this condition. When temperatures begin to approach their limits, the system first begins to open dampers in the OUT zones to relieve the overload condition.
The system also monitors temperatures in the OUT zones and never lets OUT zones become cooler than the coolest zone (in cooling) or warmer than the warmest zone (in heating). This feature prevents over conditioning of OUT zones while still using them to relieve overload conditions.
Also, when a zone is set to OUT and the system is set up for dehumidification, the OUT zone can be used to help remove humidity by cooling it as much as possible. When there is a dehumidify demand without a cooling demand, the system fully opens the dampers in any zones set to OUT. The zones can be cooled to as low as 70°F. If an OUT zone reaches 70°F, its damper closes.
When all zones are set to OUT, the house is in vacation mode. The cooling equipment comes on either to maintain the house below 85°F or to maintain the dehumidify set point by cooling the house to as low as 70°F. This feature is extremely useful for unoccupied homes in hot and damp climates.
E. Bryant Access Home Zoning Software
Bryant provides a software utility—Bryant Access Home Zoning Software—that installers can use to assist them during a Zone Perfect Plus installation. This software is provided free of charge on the Zone Perfect Plus Introduction CD-ROM. It can be run under Windows 3.1 or Windows’95 on a portable computer.
This software lets the installer:
• Monitor the zoning system during installation.
• Program the comfort schedule for the system.
• Perform additional setup tasks, if necessary.
F. Eight-Zone Capacity
Zone Perfect Plus is available in 2-zone, 4-zone, and 8-zone models. Of course, not all zones have to be used in an installation for the system to operate properly. For example, an 8-zone model can be used for a system with 2 to 8 zones.
G. Ease of Installation and Installer Testing
Zone Perfect Plus has been designed to make it easy to install. For example, connections on the Equipment Controller are color coded to make them easy to identify.
Zone Perfect Plus provides an installer setup mode that makes it easy to test the system during installation. By pressing buttons on the User Interface, the installer can:
• Fully open a selected zone’s damper(s) and close all other dampers.
• View the current temperature of any zone.
• Turn the blower on or off.
• Operate heating, cooling, or auxiliary heating for 2 minutes.
PLUS
ZONE PERFECT
COMPONENTS
The main components of a Zone Perfect Plus system are:
• A User Interface
• An Equipment Controller
• Zone sensors
• Equipment sensors
• Zone dampers
Each of these components is described in the following sections.
A. User Interface
The User Interface, show in Fig. 1, is the command center or "brains" for the entire zoning system. Through the User Interface, the homeowner can program the temperature and schedule require­ments for each zone, and can view the actual temperatures for each zone. The User Interface usually is located in the main living area for convenient access.
A98337
Fig. 1—User Interface
The main function of the User Interface is to monitor signals from the temperature sensors, determine what actions need to be taken to maintain each zone at the temperature programmed for it, and send the appropriate control signals to the zone dampers and the heating or cooling equipment.
The User Interface also includes a temperature sensor, which usually is used to monitor the temperature in its zone (Zone 1), as well as a humidity sensor. In some cases, the need to mount the User Interface in a location convenient for the homeowner might make its location unsuitable for accurately sensing the zone temperature. In such cases, a Remote Sensor can be used for the zone instead of the User Interface’s built-in sensor.
—3—
B. Equipment Controller
Fig. 2—Equipment Controller
The Equipment Controller, shown in Fig. 2, is essentially a junction box for connecting all of the temperature sensor inputs, and all of the outputs to the zone dampers and to the heating and cooling equipment. It contains circuits and relays that provide control of the zoning system, as well as control of the heating and cooling equipment. The Equipment Controller operates under the control of the User Interface.
C. Zone Sensors
Zone Perfect Plus kits include Remote Sensors. Optional Smart Sensors also are available for use with the Zone Perfect Plus system. Each of these types of sensors is described below.
REMOTE SENSORS
Remote Sensors, shown in Fig. 3, are used to measure the temperature in each zone. A Remote Sensor does not provide a means to view or adjust the zone temperature; the User Interface provides a means to view and adjust temperatures for all zones.
A98338
• Zone Perfect Plus installations must include a LAT (leaving
air temperature) sensor.
• If the installation includes a heat pump, an HPT (heat pump temperature) sensor also must be installed.
•AnODT (outdoor temperature) sensor is optional in most applications.
For more information about equipment sensors, see the section "Components Required for Specific Applications."
E. Zone Dampers
Each zone must have at least 1 zone damper, shown in Fig. 4. If more than 1 duct serves a single zone, up to 3 dampers may be wired in parallel to a single output on the Equipment Controller.
Each zone damper is operated by an electric motor actuator, which receives signals from the Equipment Controller. Dampers have 15 positions, ranging from fully closed to fully open. The position selected for each damper at any given time is based on the relative conditioning needs of each zone in the current mode.
A98339
Fig. 3—Remote Sensor
SMART SENSORS
The Smart Sensor measures and displays the temperature in the zone. It also provides a means to adjust the temperature in that zone only.
D. Equipment Sensors
The following equipment sensors are used in Zone Perfect Plus installations:
—4—
A98340
Fig. 4—Zone Damper
PLUS
DESIGNING A ZONE PERFECT
INSTALLATION
The main objective when designing a zoning system is to maintain at least the minimum airflow through the system when only 1 zone requires conditioning, yet still provide sufficient airflow when all zones require conditioning. The tasks described below provide step-by-step instructions for designing an effective zoning system. These tasks are grouped into the following phases:
N
Bath
Bath
Bedroom
Large 
WIndow
Master
Bedroom
Bedroom
Fig. 5—Example of a Floor Plan
• Assigning Zones Task 1—Assess the homeowner’s goals for comfort and energy savings. Task 2—Conduct a site survey and make preliminary zone assignments.
• Sizing the Equipment Task 3—Calculate block load estimates and zone load esti­mates. Task 4—Size the heating and cooling equipment.
• Laying Out and Sizing the Duct System Task 5—Choose register and return locations. Task 6—Determine bypass needs. Task 7—Lay out supply ducts and locate dampers. Task 8—Determine appropriate damper and duct sizes.
• Laying Out Zone Components Task 9—Choose locations for zone sensors.
A. Assigning Zones
TASK 1—ASSESS THE HOMEOWNER’S GOALS FOR COMFORT AND ENERGY SAVINGS
For a zoning system to be successful, it must meet the homeown­er’s goals for comfort and/or energy savings. Therefore, it is essential to understand the homeowner’s goals before beginning to design the system. In some situations, a homeowner’s expectations might not be realistic and it would be impossible to design a system to meet those expectations. By identifying this problem from the start, you can help the homeowner revise these expecta­tions and avoid creating a dissatisfied customer.
In addition to understanding the homeowner’s general goals for the zoning system, you need to understand exactly how the home’s occupants will use each room or area in the home. Use the Homeowner Survey provided in the Appendix to help you gather information from the homeowner.
TASK 2—CONDUCT A SITE SURVEY AND MAKE PRELIMINARY ZONE ASSIGNMENTS
Conducting a Site Survey
The purpose of conducting a site survey is to gather the informa­tion that you need to:
Make zone assignments. Use the Floor Plan Worksheet provided in the Appendix to draw a floor plan of the home. Follow these guidelines:
Kitchen
Informal
Dining Room
Living Room
Shaded
Family Room
Utility
Room
Shaded
— Provide the rough dimensions of each area or room. — Indicate the location and relative size of doors, windows, and skylights. In particular, identify any large glass areas (exceeding 30 percent of the wall area). — Indicate whether any trees or buildings cast shade on any of the home’s exposures. — Indicate the orientation of the home so you can determine whether there are any rooms or areas facing south or west where the solar heat load might be a factor when making zone assignments. Fig. 5 shows an example of a floor plan for a home, drawn as part of a site survey.
Calculate heating and cooling load estimates for the home
(Task 3). Gather the information required to use the method of your choice for calculating these loads. If you have a worksheet that you generally use to gather this information, feel free to use it.
Choose register and return locations (Task 5). Generally, the
Floor Plan Worksheet will provide sufficient information for choosing register and return locations. In a retrofit installation, indicate the location of existing duckwork, as well as heating and cooling equipment.
Lay out ducts and locate dampers (Task 6). Gather the
information about the home required to lay out ducts and locate dampers using the method of your choice. If you have a worksheet that you generally use to gather this information, feel free to use it.
Making Preliminary Zone Assignments
The homeowner’s goals regarding comfort and energy savings affect how many zones are appropriate for the system:
• In a system designed primarily for comfort, all zones usually have comfort set points that remain relatively constant and that have similar time schedules. Such a system may have a large number of zones (5 to 8) of a relatively small size.
• In a system designed primarily for energy savings, there are zones that are not used much of the time. Such a system must have even larger ducts to guarantee proper airflow to the zones that remain in use when some zones are unused. Such a system generally must have a smaller number of zones of a relatively larger size. In this case, you must be careful not to "over zone" (assign too many zones).
When making zone assignments, use the information that you gathered when conducting the site survey. Group areas that:
A98341
—5—
N
Bath
Bath
Bedroom
Large 
WIndow
Master
Bedroom
Bedroom
Fig. 6—Example of Zoning Assignments
• Are in use around the same time of day. For example, it often makes sense to assign all bedrooms to a single zone because they are occupied only during the night time when other rooms in the home are not occupied.
• Have similar heating and cooling needs.
• Are physically separated from other areas.
• Are on the same level of the home. For example, the rooms on the upstairs level often have a different heating or cooling demand when compared to rooms downstairs. The differences can be due to the tendency for heat to rise, different use of occupancy, and the roof heat load.
• Have similar exposures to external heating gains and losses. For example, it often makes sense to assign rooms with large amounts of glass and western or southern exposure to the same zone.
• The homeowner intends to "set back" at the same time.
• Let you avoid extremely small zones that would cause the airflow through the unit to become extremely low when only 1 zone requires conditioning.
If possible, discuss these considerations with the homeowner. Get the homeowner’s input before making initial zone assignments.
Mark your preliminary zone assignments on the Floor Plan Worksheet provided in the Appendix. Fig. 6 shows an example of zoning assignments marked on a floor plan worksheet.
At this point, consider your zone assignments to be preliminary. The next task helps you check whether the zone assignments are feasible.
B. Sizing the Equipment
TASK 3—CALCULATE BLOCK LOAD ESTIMATES AND ZONE LOAD ESTIMATES
Using the information that you gathered in Task 2, calculate both heating and cooling load estimates for the entire home. These estimates are used primarily for sizing the heating and cooling equipment for the system.
Kitchen
Shaded
Utility
Room
Zone 1
Zone 2
Zone 3
Zone 4
A98342
Informal
Dining Room
Living Room
Shaded
Family Room
The standard Btu load calculations used for non-zoned systems apply equally well to zoned systems. Use a reliable method with which you are comfortable.
After you have tentatively defined the zones for a home, calculate individual peak heating and cooling load estimates (in Btu’s) for each of the zones. Use a reliable method with which you are comfortable to calculate the peak zone load estimates. Refer to the information that you gathered in Task 2.
The peak zone load estimates are used to determine whether the zone assignments you have made make sense. They also are used to size the zone dampers and ductwork.
When a zone is recovering from being set back, the system must supply additional capacity beyond the zone’s losses to change the temperature. The farther the desired setback, the more capacity must be added.
For zones that will be set back and that need reliable recovery, multiply their calculated zone loss by a recovery factor of 1.25. Use the larger zone load estimate when determining the size of the damper and duct required for the zone.
TASK 4—SIZE HEATING AND COOLING EQUIPMENT
Zone Perfect Plus is designed for use with a furnace or fan coil in conjunction with a condensing unit or heat pump with a thermo­static expansion valve (TXV). Zone Perfect Plus operates within an airflow range of 1.5 to 6 tons in the cooling mode.
How to determine the appropriate size of heating and cooling equipment is a challenge that is subject to much debate. In a residential zoning system, there is a very good possibility that a system will use all zones on a given day. For that reason, we recommend that you select the size of heating and air conditioning units based on either the home’s block heating load or block cooling load (whichever is greatest). Select the size of the air handling unit based on the unit with the largest required CFM. However, because the system has the capability to not condition some zones at any given time, and because it is essential to
—6—
maintain minimum airflow through the system at all times, it is better to use slightly undersized equipment than slightly oversized equipment in a zoning system.
Select heating and cooling equipment to meet the peak heating and cooling block load estimates that you calculated in Task 3. Use the Product Data Sheets for the equipment that you are considering to determine whether the equipment can meet the system’s needs. Verify that the selected indoor air handler can meet the heating and cooling airflow requirements, as well as the system’s external static pressure requirements.
NOTE: When you design the air distribution system, you need the Product Data for the indoor air handler’s performance character­istics.
In a zoning system, it is especially important to select heating and cooling equipment that is not too large. Equipment that is larger than necessary compounds the problem of keeping the airflow in the system above the minimum required by the equipment when few zones require conditioning. Because the system shuts down the equipment if the duct temperature falls outside the minimum or maximum temperature limits, and limits the number of times the equipment can restart to 4 times per hour, the actual capacity provided by the system can be smaller with larger equipment.
To help avoid such problems, size the equipment based on the calculated peak heating or cooling airflow (whichever is larger) of the home. Do not add a fudge factor. Under even the heaviest loads, the system has the capability to send its entire capacity to less than the entire home. To redirect capacity where it is most needed, the homeowner can easily set back some zones.
For information about the different types of heating and cooling equipment that can be used with zoning systems, see the section "Special Applications Using Zone Perfect Plus."
TASK 5—CHOOSE REGISTER AND RETURN LOCATIONS
Determining the Number of Returns
Each zone should have a separate return with sufficient capacity to return all of the air that is delivered to that zone. If you cannot provide a separate return for a zone, use one of the following methods to maintain airflow to that zone:
• Leave space under doors.
• Install grilles into or above doors.
• Provide a connection from the zone to another area that has an
adequate return.
When the air leaving a zone must pass into another zone, cross conditioning occurs and it becomes difficult to maintain different temperatures in the 2 zones. For this reason, a zone that is significantly "set back" at times needs its own return.
Selecting Return Locations
The location of the returns for a zone significantly affects the capacity that can be delivered to that zone. A high return removes warmer air from the ceiling and a low return removes cooler air from the floor. For a 2-story home, it is best to have both high and low returns.
The location of the returns for a zone also has a significant effect on the comfort in that zone. Because our feet are generally on the floor and our heads are never closer than about 2 ft from the ceiling. It is more important to keep the floor at a comfortable temperature. In both cooling and heating, floors can become uncomfortably cool and a low return can help alleviate this problem.
In homes where the air handler is located in the basement, a return near the basement floor will help avoid overcooling of the basement. A low return also helps with the removal of dampness and radon from the basement. However, a low return in the basement lowers the return temperature cooling, increasing the size of ducts required for proper operation of the system.
For homes with cathedral ceilings or multi-story rooms, a return at the highest point can enhance both efficiency and comfort, particularly during heating.
Selecting Register Locations
The general issues related to selecting register locations are the same in zoned systems as they are in non-zoned systems. The only exception is that the velocity of air leaving a register is likely to be higher in a zoned system. Locate the register to take advantage of the greater mixing of air that can be provided by the higher air velocity and to minimize the discomfort caused downwind from the register. As always, select register and return locations to avoid stratification of air in the room and to maximize the mixing that occurs when air swirls through a room.
Meeting Zoning Challenges in 2-Story Homes
In a 2-story home where cooling is the primary challenge, keep in mind the principle of buoyancy—the tendency for cool air to sink and warm air to rise. The lower level might tend to be over conditioned or the upper level might tend to be under conditioned. To help avoid such problems, on the upper level you can:
• Use high registers to mix the cooled air with the warm air near the ceiling.
• For registers, direct or deflect the air upward and maintain high grille velocity.
• Install returns near the ceiling.
• Close doors to rooms and minimize space below doors when possible, but only if each room has its own return.
• Install a ceiling fan in each room.
Recording Return and Register Locations
You can mark the locations for returns and registers on the Floor Plan Worksheet for the home. Indicate the approximate height of each return and register.
TASK 6—DETERMINE BYPASS NEEDS
Bypass dampers have become a standard component in many zoning systems produced today. When multi-stage equipment with an ICM blower motor is used in a properly sized duct system, a bypass is not always necessary.
The use of a bypass to add load to a system is most common in commercial applications. In residential applications, a direct by­pass is most common. Without proper precautions, the use of a direct bypass can lead to poor comfort and/or equipment failure.
A direct bypass recycles either the coldest or hottest air in the system back into the return air inlet when it is needed the least. In cooling, the direct bypass can cause the coil to freeze and the equipment to shut down due to the low temperature limit. In heating, the direct bypass can cause overheating and the equipment to shut down due to the high temperature limit. Either of these situations reduces the comfort that the system can provide.
A direct bypass with Zone Perfect Plus using the out zone feature is an excellent option. The bypass reduces air noise under minimum load and the out zone feature keeps the equipment from shutting down.
TASK 7—LAY OUT SUPPLY DUCTS AND LOCATE DAMPERS
The supply air duct system for a zoning system has a different layout than one designed for a conventional single zone system. Provide a separate zone duct to carry all of the air for each zone. The zone damper for each zone is located in its zone duct. Branch ducts connect to each zone duct, downstream from the zone damper. They supply conditioned air to individual rooms or areas in the zone.
In some systems, it might not be convenient to connect all of the branch ducts for a zone to a single zone damper. In such a case, multiple branch ducts can be fed through multiple (up to 3) zone dampers. All of the zone dampers for the zone are wired in parallel so that they open and close the same amount at the same time.
—7—
N
Bath
Bath
Bedroom
Large 
WIndow
Master
Bedroom
Bedroom
Zone Damper
Fig. 7—Example of Supply Duct Layout and Damper Locations
You can mark the supply duct layout and damper location on the Floor Plan Worksheet for the home. Fig. 7 shows an example of supply duct layout and damper locations marked on a floor plan worksheet.
TASK 8—DETERMINE APPROPRIATE DAMPER AND DUCT SIZES
Airflow is the way that a zoning system moves heating or cooling Btu’s to the load (the demand for heating or cooling in the home) and back to the heating or cooling equipment. For the equipment to perform properly, the system must maintain a minimum load on the equipment. In a residential system, the necessary airflow usually is measured in cubic feet per minute (CFM) exiting the duct system. For most zoning systems, the system must maintain a minimum of 300 CFM per ton exiting the duct system (not recirculated).
A zoning system distributes air based on the differing load in each zone. Most of the time, some of the dampers are partially closed; some dampers may be completely closed. By using a larger duct size for a zoning system that you would use in a non-zoned system, you help assure that air flows at an appropriate velocity where it is needed and that the sound level remains acceptable.
Because Zone Perfect Plus controls airflow based on the propor­tional needs of each zone, the logic used for selecting appropriate damper and duct sizes is different than the logic you would use for other zoning systems or a non-zoned system. It is not reasonable to attempt to design an air distribution system that can handle 100 percent of the system’s airflow capacity through 1 zone. However, it is reasonable to design the air distribution system to be able to move the minimum airflow with one-third of the zones’ dampers fully open.
NOTE: The use of multi-stage heating and/or cooling equipment can significantly reduce the size of dampers and ducts required for an installation. For more information, see the section "Using Multi-Stage Equipment with Zoning."
Determining Duct Size Based on Damper Size
Kitchen
Informal
Dining Room
Living Room
Shaded
Unit in
Basement
Family Room
Shaded
Utility
Room
Zone 1
Zone 2
Zone 3
Zone 4
A98343
The most logical way to determine the damper and duct size requirements for a zoning system is to first determine the zone duct size required for each zone. Select the damper size that will move 500 CFM per ton at the desired velocity as you normally would. Do not undersize these dampers! Then, size ducts based on 500 CFM per ton of load to each zone. Zone ducts should always be as large or larger than the selected damper.
NOTE: For zones that need quiet operation and fast setback recovery, use 600 CFM per ton to size zone dampers and ducts.
Larger ducts are always better with an ICM blower system. With a non-ICM blower in the system and excessively large ducts, one or both of the following problems might occur:
• Humidity removal might suffer.
• Register "throw" might be reduced. Continuous fan use and good register and return placement can solve this problem.
The combination of larger ducts and an ICM blower eliminates many problems that can occur in a zoning installation.
It is wise to oversize the ducts for small zones so that the heating and cooling equipment can continue to operate when only the small zones need conditioning. The zoning system will maintain proper temperature control even if the ducts are oversized.
When determining the duct size for a zoned system, keep in mind that duct balancing, which is an important concept for designing non-zoned systems, is not necessary in a zoned system. The zoning system itself will balance the ducts.
Why Oversized Ducts Are Not a Problem with Zone Perfect Plus
Example 1: When the air handling equipment is used on a system
with oversized ducts, it delivers less air through the ductwork. This reduction in volume and velocity can cause conditioned air to stratify and not reach the zone sensor in a zone. When this situation occurs, the system assumes there is a greater demand in that zone and opens the zone damper to increase airflow to that zone.
—8—
User Interface
N
Large 
WIndow
Master
Bedroom
Bedroom
Zone Damper
Fig. 8—Example of Zone Sensor Locations
Bath
Bath
X
Kitchen
X
Bedroom
= Zone Sensor Locations
X
Informal
Dining Room
Living Room
Shaded
Basement
X
X
Unit in
Family Room
Shaded
Utility
Room
Zone 1
Zone 2
Zone 3
Zone 4
A98344
Example 2: In a 2-stage system the unit starts in low speed, the system reacts the same as in Example 1 except, when more zones demand conditioning and other zone dampers open, the system switches the equipment to 2-stage mode, increasing the system capacity and the airflow to the zones requiring conditioning.
TASK 9—CHOOSE LOCATIONS FOR ZONE SENSORS
One zone sensor is required for each zone. Generally, the User Interface’s internal sensor serves as the zone sensor for its zone (Zone 1). A Smart Sensor or Remote Sensor may be used in any zone, except a Smart Sensor may not be used in Zone 1.
For proper operation of the Zone Perfect Plus system, each sensor must accurately measure the temperature within its zone. Consid­erations for selecting a location for a sensor are essentially the same as the considerations for selecting a location for any thermostat.
When selecting a location for a sensor, follow these guidelines:
• Select a location close to the center of the sensor’s zone, on an inside wall. In particular, avoid locations where the air from another zone mixes with the air in the zone you are trying to monitor. If the target temperatures for the 2 zones are different, the system might not be able to determine the necessary amount of conditioning to supply to each zone.
• Plan to mount the sensor approximately 5 ft (1.5 m) above the floor.
• Select a section of wall without pipes or ductwork.
• If there are 2 or 3 bedrooms in a single zone, locate the sensor in the hallway connecting the bedrooms, near the return grille but not directly in the return airflow.
•Donot select a location: — on an outside wall, close to a window, or next to a door leading outside. — exposed to direct light and heat from a lamp, the sun, a fireplace, or any other heat-radiating object that might cause a
false reading. — in direct airflow from supply registers and return grilles. — in areas with poor circulation, such as behind a door or in an alcove.
You can mark the locations for zone sensors on the Floor Plan Worksheet for the home. Fig. 8 shows an example of zone sensor locations marked on a floor plan worksheet.
C. Considerations When Retrofitting an Installation
It is a far greater challenge to design a retrofitted zoning system than it is to design a system for a new home. For a zoning system to operate properly in a retrofitted installation, it usually is necessary to use 1 or more of the following approaches to compensate for an air distribution system that is too small for the zoning system:
• Modify the existing ductwork and dampers to handle additional airflow.
• Set mechanical minimum damper positions in some zones.
• Improve the home’s insulation to reduce the home’s demand for heating and cooling (load) so that lower capacity equipment can be used effectively in the installation.
• Use multi-stage heating and cooling equipment so the equip­ment capacity can match the load when only a limited number of zones require conditioning.
• Select an air handler that is designed to overcome the high static pressure in the ductwork and force more air through the system. A unit with an ICM blower is a good choice.
When selecting the appropriate approach for a retrofitted system, be sure to inform the homeowner of the tradeoffs between cost and comfort when comparing approaches.
D. Installing the System
To install each component, follow the Zone Perfect Plus Installa­tion Instructions provided with the Zone Perfect Plus kit and the
—9—
Installation Instructions provided by Bryant with the selected heating and cooling equipment. Thoroughly test the installation, following the instructions provided, to ensure that it is installed and set up properly.
COMPONENTS REQUIRED FOR SPECIFIC
APPLICATIONS
The following components are required in all Zone Perfect Plus installations:
• a TXV (thermostatic expansion valve)
• a LAT (leaving air temperature) sensor, provided with all Zone Perfect Plus kits
In a heat pump installation (not a dual fuel application), an HPT (heat pump temperature) sensor is required.
In a dual fuel application, or any installation using the low temperature lockout feature, the auxiliary heat lockout feature, and/or the automatic humidity level adjustment feature, an ODT (outdoor temperature) sensor is required. In other Zone Perfect Plus applications, this sensor is optional.
Information about each of these components is provided in the following sections.
A. Thermostatic Expansion Valve
A TXV is required in all Zone Perfect Plus installations. The TXV replaces the fixed metering orifice, which regulates the amount of liquid refrigerant entering the indoor evaporator. The TXV assures that no liquid refrigerant leaves the evaporator, possibly returning to the compressor and causing damage.
The likelihood of incomplete refrigerant evaporation is much greater in a zoning system than in a non-zoned system because of the reduced airflow when only a few zones require conditioning. Thus, the TXV protects the compressor from possible damage when airflow is very low.
NOTE: The purpose of the TXV is not to protect the coil from freezing. The leaving air temperature (LAT) sensor performs this function.
B. Leaving Air Temperature Sensor
A LAT sensor is required for all types of equipment. When used with fossil fueled furnaces and air conditioned systems, locate the LAT sensor in the air supply duct downstream of the furnace and cooling coil. The LAT sensor must be upstream of the bypass damper, if one is included in the system, or the first zone damper.
The LAT sensor monitors the leaving air temperature during both heating and cooling. The User Interface is programmed with temperature limits and prevents equipment operation if the leaving air temperature exceeds the upper limit during heating or falls below the lower limit during cooling.
When used with a heat pump, locate the LAT sensor downstream of the accessory electric heaters. The LAT sensor monitors the air temperature leaving the accessory electric heaters during heating, as well as the temperature leaving the indoor coil during cooling.
C. Heat Pump Temperature Sensor
An HPT sensor is required in a heat pump installation, unless it is a dual fuel application. Locate the HPT sensor in the air stream between the indoor coil and the accessory heaters.
This sensor serves a similiar purpose to the LAT sensor, but does not sense the temperature of the air leaving the electric heaters. The HPT sensor monitors the air temperature leaving the indoor coil during heating by the heat pump, and prevents the operation of the heat pump if the leaving air temperature exceeds the fixed temperature limit of 115°F.
D. Outdoor Temperature Sensor
An ODT sensor is required in all dual fuel applications. An ODT sensor also is required to use the low temperature lockout feature, the auxiliary heat lockout feature, and/or the automatic humidity level adjustment feature in any installation.
For dual fuel systems, this sensor is used to control the switch from electric to fossil fuel operation when the outdoor temperature reaches the preset temperature. When used with the low tempera­ture lockout feature, the ODT sensor is used to prevent equipment operation during cooling when the outdoor temperature falls below the preset lower limit. When used with the auxiliary heat lockout feature, the ODT sensor is used to prevent electric heat operation in a heat pump installa­tion when the outdoor temperature rises above the preset limit. When used with the automatic humidity level adjustment feature during heating, the system automatically reduces the humidity set point by 1 percent for every 2°F reduction in outdoor temperature. In other Zone Perfect Plus applications, this sensor is optional.
SPECIAL APPLICATIONS USING ZONE PERFECT
This section discusses special Zone Perfect Plus applications that:
• Emphasize energy savings or "setback."
• Include multi-stage equipment.
• Include variable-speed blowers.
• Include a barometric bypass damper.
A. Understanding the Requirements of Setback with Zoning
If you are designing a zoning system for energy savings, it is important to understand the additional challenges that you face before you begin to design the air distribution system. The energy savings achieved by setting zone temperatures back (lower for heating or higher for cooling) can be substantial. However, "setback" brings additional requirements to the system. The zones that are not set back might be surrounded by zones that are. This situation results in the need to deliver additional capacity to the zone that is not set back since the zone duct and damper need to deliver the capacity required to meet the zone’s needs and to compensate for the conditioning that spills over to the neighboring zones that are set back. Thus, the effective block load of any zone increases above the value normally calculated for it when its neighboring zones are set back. The amount of the increased load depends on the extent to which the neighboring zones are set back. This need for additional capacity increases the size of damper and duct required for the zone. When a zone has been set back, the system eventually must return the zone to a more comfortable conditioning level. This need increases the capacity that must be delivered to the zone. The amount of additional capacity that is necessary is the capacity required to match the zone’s load plus the capacity required to implement recovery within a reasonable time period. The amount of capacity required for recovery depends on the extent to which the zone had been set back and the desired recovery time. Again, this need for additional capacity increases the size of damper and duct required for the zone. The improved insulation found in today’s homes compounds the demands imposed by setback. The better insulated the home, the smaller the size of heating and cooling equipment required for the home. However, the requirements of setback recovery are deter­mined by the heat capacity of the zone, not by its losses, and heat capacity is not changed by insulation. Improved insulation also increases the challenge of maintaining different temperatures between zones since the interior walls appear more transparent to heat flow when the outer walls are better insulated. The opportu­nity for energy savings in addition to the savings already achieved through better insulation is reduced in a well insulated home.
B. Using Multi-Stage Equipment with Zoning
When dampers are closed in some zones and the air distribution system becomes effectively smaller in a system with single-stage equipment, airflow may drop below the system’s minimum, causing the equipment to shut down. In this situation, it is difficult to maintain comfort in the home due to excessive equipment cycling.
PLUS
—10—
In contrast, multi-stage equipment shifts to low-stage operation (typically 60 percent of total capacity) when the air distribution system becomes effectively smaller. Because the equipment re­duces its minimum airflow limit, it is able to continue to operate. The reduced capacity generally is adequate to supply the necessary conditioning since only 1 or 2 zones need conditioning under these circumstances.
The following multi-stage equipment can be used with the zoning system:
• Two-speed air conditioners.
• Two-speed heat pumps.
• Two-stage furnaces.
• Two-stage electric heat used without a heat pump. NOTE: When using multi-stage heating or cooling equipment
with Zone Perfect Plus, the zoning system must be allowed to control the equipment staging. Therefore, there must be separate inputs for low-stage and high-stage operation, and the equipment must be configured to operate from these inputs only. Outdoor temperature switches, staging algorithms, and so forth should not be used.
C. Using Variable-Speed Blowers with Zoning
PSC blowers are single-speed blowers. A PSC blower runs at a fixed speed and cannot change speed as the dampers move. A PSC blower usually can produce about 0.5 in. of static pressure.
In contrast, ICM blowers are variable-speed blowers. Air handlers using ICM blowers are designed to supply a fixed quantity of air into a duct system regardless of the external static pressure. The air handler can "sense" the external static pressure and change the motor speed to deliver the desired airflow. An ICM blower typically can produce about 0.9 in. of static pressure.
In a properly-designed system, the use of an ICM blower can help assure adequate airflow through the system regardless of damper positions. Air handlers using ICM blowers typically are pro­grammed to produce 325 CFM per ton (of equipment capability). The use of such an air handler does not reduce the damper or duct size requirements of a system, but does help the system run properly and quietly without a bypass.
D. Bypassing with Zoning
When only 1 zone requires conditioning, airflow through the ductwork can fall below the system’s minimum requirements. This situation can cause problems for the system’s equipment and can lead to discomfort for the home’s occupants.
There are 3 standard methods that have been developed to maintain minimum airflow, reduce duct velocity, and reduce duct noise:
• Bypass air to an unconditioned space.
• Bypass air to a conditioned space.
• Bypass air directly to the return. The term "bypass" means to allow additional air through the system that bypasses the zone dampers, the zones, or both. The 3 methods described above use a bypass damper, which receives air from the supply plenum. A barometric damper, which opens when the supply air pressure reaches a preset value, generally is used for the bypass. Thus, the barometric bypass damper acts as a pressure regulator, releasing enough air to reduce the supply plenum pressure to an appropriate level. In addition to the 3 standard bypass methods, Zone Perfect Plus provides an additional bypassing method—OUT zones. OUT zones can serve as an excellent bypassing method. You can think of an OUT zone as a temporary dump zone. Ideally, an OUT zone should be available in the system at all times. Each of the conventional bypass methods, as well as bypassing using OUT zones, is discussed in the sections below. As you evaluate the usefulness of these methods for a particular installa­tion, keep in mind that bypassing using OUT zones can work well in conjunction with a barometric bypass.
NOTE: A bypass damper reduces air noise by reducing airflow velocity in the ducts. A direct bypass to the return does not add load to the system.
BYPASSING TO AN UNCONDITIONED SPACE
Conditioned air can be bypassed to an unconditioned space. This type of bypass is considered an indirect bypass.
Although there is no limit on the amount of air that can be bypassed using this method, this type of bypass wastes energy. In addition, this method creates negative indoor pressure, which pulls unconditioned air into the home. This method is rarely used in zoning installations and we do not recommend it.
BYPASSING TO A CONDITIONED SPACE
Conditioned air also can be bypassed to a conditioned space, called a dump zone. This type of bypass also is considered an indirect bypass.
Although there is no limit on the amount of air that can be bypassed using this method, this type of bypass reduces the effectiveness of the zoning system. The dump zone tends to be over conditioned and uncomfortable.
This method is acceptable if you have a zone that can function as a dump zone, such as a large basement. However, there rarely is a zone suitable for this use.
BYPASSING DIRECTLY TO THE AIR RETURN
There are advantages and disadvantages to bypassing directly to the air return using a barometric damper. The advantages of a direct barometric bypass include:
• A direct bypass serves as a pressure regulator, bypassing enough air to hold the static pressure in the plenum to a safe level. Thus, a direct bypass prevents excessive air velocities, which can cause noise and drafts.
• Because a direct bypass returns conditioned air back into the air handler, it makes the leaving air colder in cooling and warmer in heating. A direct bypass increases the Btu content of the air entering the duct system while airflow (CFM) remains at the same level. The result is that more capacity can be forced into the system without increasing the airflow.
• During cooling, the process of making the leaving air colder removes more water from the air. When a system is bypassing a large amount of air (only a small portion of the zones require conditioning), there is relatively little total demand on the system. During such periods of light load, humidity often can be a problem. The direct bypass automatically increases the removal of water when it is most needed.
The disadvantages of a direct barometric bypass include:
• It is very difficult, if not impossible, to determine how much air is being bypassed under a given condition. Traditional calcu­lation methods can assure that the bypass is large enough, but do not prevent the bypass from becoming too large. The amount of air that can be bypassed often is greater than the amount that the equipment can tolerate.
NOTE: The dimensions and attachment points of the bypass ductwork have more influence on the amount of air that is bypassed than the ratings of the bypass damper.
• Airflow into the ductwork might be reduced excessively, resulting in insufficient conditioning.
• Because too much air can be bypassed, entering and leaving air temperatures can range outside safe values for the heating and cooling equipment, possibly resulting in equipment failures or shortened equipment life. A direct bypass, unlike an indirect bypass, does not remove Btu’s from the equipment, although it does allow more airflow through the equipment. Although it is commonly believed that the equipment is protected as long as proper airflow is maintained, this belief is true for an indirect bypass but not for a direct bypass. A direct
—11—
bypass provides no protection for the equipment even though it increases the airflow through it. Particularly for furnaces, a direct bypass can harm rather than help by overheating internal components. Therefore, the amount of air bypassed during heating with a direct bypass must be limited.
• If bypassing results in excessive temperature in the supply duct and a limit is tripped, the equipment shuts down. To protect the equipment, the zoning system does not allow the equipment to be turned on more than 4 times per hour. If the limit is tripped repeatedly, the amount of heating or cooling delivered to the zones might decrease dramatically. Thus, a direct bypass might initially help the performance of a system during a period of limited demand, but it might eventually result in an abrupt loss of conditioning.
NOTE: A leaving air temperature (LAT) sensor is required in every Zone Perfect Plus system. If the system is programmed properly, this sensor ensures that the equipment turns off when the leaving air temperature exceeds a safe range. Although it might be tempting to omit the LAT sensor to increase the system’s perfor­mance, you risk eventual equipment failure. The equipment’s internal limits are not intended to be tripped repeatedly.
Similarly, if the LAT range is not programmed properly, you can cause the equipment’s internal limits to trip repeatedly. Again, you risk eventual equipment failure.
BYPASSING USING OUT ZONES
Although the OUT zone feature can be used to provide energy savings to the homeowner, its primary use is to give the system a place to direct excess airflow to avoid tripping limits that protect the heating or cooling equipment when the airflow falls below the minimum required to operate safely. By closing an OUT zone’s damper(s) if the zone becomes cooler than the coolest zone (in cooling) or warmer than the warmest zone (in heating), the system avoids over conditioning the OUT zone. Thus, using OUT zones for bypassing provides the advantages of bypassing to a dump zone, but avoids the disadvantages.
The following scenario illustrates bypassing in a system that has both a direct barometric bypass damper and several OUT zones. This example illustrates the operation of the system in the cooling mode. Keep in mind that the system would operate similarly in the heating mode.
Imagine a zoning system is running in cooling mode and less than 1/3 of the zones have a cooling demand. The air pressure in the ducts starts to build and the barometric bypass damper starts to open. As the air recirculates to the return of the air handler and into the evaporator coil, the leaving air temperature drops.
When the leaving air temperature, as measured by the leaving air temperature (LAT) sensor, falls to 46°F, the system opens all OUT zone dampers 3 positions. This action relieves the duct pressure and may allow the bypass to close. If the temperature drops another degree, the OUT zone dampers open another 3 positions. The system continues to progressively open the OUT zone dampers as the temperature falls until 1 of the following events occurs:
• The leaving air temperature stabilizes and the OUT zone dampers maintain position. (This result is the most common.)
• The demand is met for all zones and the system shuts down.
• The OUT zone dampers are fully open (position 15).
• The OUT zones become colder than the lowest cooling system set point and their dampers close.
• In extreme cases, the leaving air temperature can fall to 40°F. Usually this situation is caused by factors outside the heating and cooling system, such as doors and windows left open when the rest of the home is satisfied. In this extreme case, the limit for the system is reached and the system shuts down the cooling equipment.
GLOSSARY
Barometric Bypass Damper
Device used to control noise and maintain airflow in a heating or cooling system during minimum airflow. When the supply airflow reaches a preset value, the barometric bypass damper opens.
Block Load
Heating or cooling load of the home as 1 space.
Btu
British thermal unit. A standard unit of heat—the amount of heat required to raise the temperature of 1 lb of water 1°F.
Bypass
Configuration that allows additional air through the system that bypasses the zone dampers, the zones, or both.
Cooling Demand
The difference between the current temperature in a zone and the zone’s cooling set point (when the temperature is higher than the cooling set point).
Condition
Process of ventilating, heating, or cooling (and sometimes humidi­fying or dehumidifying) an area.
Dump Zone
Conditioned zone to which air is bypassed.
Equipment Controller
Device that interfaces with the home’s heating and cooling equipment so Zone Perfect Plus can control that equipment.
External Static Pressure
Measured static in inches wc from the inlet to the outlet of the air handling unit.
Heat Pump Temperature (HPT) Sensor
Device that measures the temperature of air leaving the indoor coil. Zone Perfect Plus uses this temperature under certain circum­stances to adjust the operation of the heating or cooling system.
Heating Demand
The difference between the current temperature in a zone and the heating set point (when the temperature is lower than the heating set point.)
ICM (Integral Control Motor) Blower
Variable-speed blower. Air handlers using ICM blowers are designed to supply a fixed quantity of air into a duct system regardless of the external static pressure.
Leaving Air Temperature (LAT) Sensor
Device that measures the temperature of air leaving the air handler in heating or cooling. Zone Perfect Plus uses this temperature under certain circumstances to adjust the operation of the heating or cooling system.
Multi-Stage Equipment
Heating or cooling equipment that can adjust the capacity in response to the demand of the zoning system.
OUT Zones
Zones (usually unoccupied) that have been selected to receive no conditioning for a period of time unless the temperature exceeds 85°F or falls below 60°F. Zone Perfect Plus also uses OUT zones to relieve the heating or cooling equipment under overload conditions.
Outdoor Temperature (ODT) Sensor
Device that measures the temperature of the air outside. Zone Perfect Plus uses this temperature under certain circumstances to adjust the operation of the heating or cooling system.
PSC (Permanent Split Capacitor) Blower
Single-speed blower. A PSC blower runs at a fixed speed and cannot change speed as the dampers move.
—12—
Remote Sensor
Device that measures the temperature in a zone, but does not provide a means to view or adjust the temperature.
Set Points
Temperatures selected to determine the acceptable temperature range for each zone. The zone’s higher set point determines when the zone needs to be cooled. The zone’s lower set point determines when the zone needs to be heated.
Set Back
Process of significantly reducing the set point of a zone during heating or increasing the set point of a zone during cooling to reduce the amount of conditioning required in the zone.
Smart Sensor
Device that measures the temperature in a zone, and that provides a means to view and adjust the temperature in that zone.
Thermostatic Expansion Valve (TXV)
Device that senses both the pressure and temperature at the outlet of the evaporator, and adjusts the refrigerant flow into the evaporator. The TXV ensures that no liquid refrigerant leaves the evaporator, possibly returning to the compressor and causing damage.
Ton
Measurement of heating or cooling equipment capacity equivalent to 12,000 Btu’s per hour.
User Interface
Command center of Zone Perfect Plus. Includes displays and buttons that let the homeowner select features and see information about the system.
Zone
Distinct area within a building where the airflow is controlled by a zone damper.
Zone Damper
Motorized air volume control damper, which regulates the flow of conditioned air into the zone.
Zone Duct
The main air supply duct to a zone, which carries all of the air and contains the Zone Damper for the zone.
Zone Load
Heating or cooling load of a single zone.
Zoning System
Equipment that allows cooling and/or heating equipment to regu­late the temperature independently in different areas of a home.
APPENDIX—WORKSHEETS
This appendix provides the following worksheets for you to copy and use when designing a Zone Perfect Plus installation:
• Zoning Design Checklist
• Homeowner Survey
• Floor Plan Worksheet
—13—
A. Zoning Design Checklist
Use this checklist to make sure that you have completed each necessary task when designing a Zone Perfect Plus installation.
Assigning Zones
[] Task 1—Assess the homeowner’s goals for comfort and energy savings. [] Task 2—Conduct a site survey and make preliminary zone assignments.
Sizing the Equipment
[] Task 3—Calculate block load estimates and zone load estimates. [] Task 4—Size the heating and cooling equipment.
Laying Out and Sizing the Duct System
[] Task 5—Determine bypass needs. [] Task 6—Choose register and return locations. [] Task 7—Lay out supply ducts and locate dampers. [] Task 8—Determine appropriate damper and duct sizes.
Laying Out Zone Components
[] Task 9—Choose locations for zone sensors.
—14—
Homeowner Survey
1. How many members are there in your household?
2. Describe the activities in your household on an unusual day. In particular, are  there activities that might require extra cooling or heating?
3. Describe the typical usage of the various areas of your home throughout the day.
4. What areas, if any, in your home that are used infrequently, such as a formal dining  room, or that are unoccupied for large periods of time during the day or night?
5. What areas, if any, in your home that are closed off from the rest of the house  (for example, a room where you always keep the door closed?)
6. Is there an area in your home that will be used for exercise?
7. Describe the entertaining that you do in your home:  How often do you entertain in the summer? In the winter?
During what times of the day do you typically entertain?
How many people do you usually entertain?
What areas of your home do you use when you entertain?
Are there times when people go in and out of the house frequently (for example,  if you entertain outdoors)?
—15—
A98345
8. What temperature do you normally want to maintain in your home during the day
in the summer? The night in the summer? The day in the winter? The night in the  winter?
9. Are there any times when you want significantly different temperatures in all or  part of your home? If so, in what areas or rooms? How quickly do you want the  temperature change to occur?
10. To what extent do you want to be able to control the temperature in your home?
11. What do you expect from your indoor comfort system?
Additional Questions for an Existing Home
1. Are there any areas or rooms in your home that are too hot or cold in the winter?  In the summer?
2. Do you have a humidity problem in your home? Too much? Too little?
3. How long do you plan to live in your present home?
4. What do you like about your present heating and cooling system? What do you  dislike?
A98346
—16—
Floor Plan Worksheet
—17—
A98347
© 1998 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—18—
Printed in U.S.A. ap172 Catalog No. BY-809-650
Loading...