Bryant TSTATBBPCM01-A User Manual

installation, start-up and operating instructions
COMMERCIAL THERMOSTAT (P/N TSTATBBPCM01-A)
Cancels: New II TSTAT-1
6/15/96
IMPORTANT: Read entire instructions before starting the installation.
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wir­ing or installation may damage thermostat.
Recognize safety information. This is the safety alert symbol
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety alert symbol. DANGER identifies the most serious hazards which will re­sult in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAU­TION is used to identify unsafe practices which would result in minor personal injury or property damage.
GENERAL
Bryant’s 7-day, commercial, programmable thermostats are wall-mounted, low-voltage thermostats which maintain room temperature by controlling the operation of an HVAC (heat­ing, cooling and ventilation) system. Separate heating and cooling set points and auto-changeover capability allow occu­pied and unoccupied programming for energy savings.
All thermostats allow up to 4 time/temperature settings to be programmed per 24-hr period. Each thermostat stores pro­grams for 7 independent days. Batteries are not required. Dur­ing power interruption the internal memory stores comfort schedules for an unlimited time while the clock continues to run for at least 72 hours.
The thermostat can be configured to accept several different equipment configurations, from single-stage heating and cool­ing to 3 stages of heating and 2 stages of cooling. The ther­mostat comes factory configured for 1 stage of cooling and 1 stage of heating.
INSTALLATION
I. THERMOSTAT LOCATION
The thermostat should be mounted:
• approximately 5 ft from the floor
• close to or in a frequently used room, preferably on an in-
side partitioning wall
• on a section of wall without pipes or ductwork The thermostat should not be mounted:
• close to a window, on an outside wall, or next to a door
leading to the outside
• where exposed to direct light and heat from a lamp, the
sun, a fireplace, or any other temperature-radiating object which may cause a false reading
• close to or in direct airflow from supply registers or return
air grilles
• in areas with poor air circulation (such as behind a door or
in an alcove)
II. SET DIP SWITCHES
There are 4 small switches on the back of the circuit board which must be configured by the installer. The ON position is indicated by small letters on the switch. Ignore the num­bers (1-4) on theswitch.Theswitchdesignation(A-D)isprinted on a sticker next to the switch. To change a switch position, use the corner of a small screwdriver to slide the switch ON or OFF. Set the DIP switches before installing the thermostat.
A. Air Conditioner or Heat Pump Selection (Switch A)
Use switchAto select between air conditioning and heat pump applications.A heat pump application uses a reversing valve. Set switch A to OFF for air conditioning applications (no re­versing valve). Set switch A to ON for heat pump applica­tions (O is used to energize the reversing valve). The factory setting is OFF.
B. Compressor Stage Selection (Switch B)
Switch B is used to select between a single-stage and a 2-stage compressor. Set switch B to OFF for a single-stage compres­sor.Set switch B to ON for a 2-stage compressor. The factory setting is OFF.
C. Outdoor Air or Remote Room Sensor (Switch C)
Switch C is used to configure the thermostat to work with either a outdoor air sensor or a remote room sensor. The sen­sor for the application must be connected to terminals S1 and S2 of the thermostat. Set switch C to OFF for a outdoor air sensor.Set switch C to ON for a remote room sensor.The fac­tory setting is OFF.
D. Averaging of Sensors (Switch D)
Switch D isusedif a remote room sensor is being used (switch C set to ON). The remote room sensor reading can be averaged with the sensor reading of the thermostat. Set switch D to OFF if averaging is not required. To average the readings of the thermostat and remote room sensors, set switch D to ON. The factory setting is OFF.
III. INSTALL THERMOSTAT
WARNING:
power to the unit. There may be more than one power disconnect. Electrical shock can cause injury or death.
1. Turn off all power to unit.
2. If an existing thermostat is being replaced: a. Remove existing thermostat from the wall. b. Disconnect wires from existing thermostat. Do not
allow wires to fall back into the wall. As each wire is disconnected, record wire color and terminal connection.
c. Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and must be disposed of properly.
Before installing thermostat, turn off all
3. Open thermostat rear door (mounting base) to expose mounting holes.
4. Route thermostat wires through large hole in mount­ing base. Remove outer sheath from wires for added flexibility.
5. Level mounting baseagainstwall and mark wall through the 2 mounting holes in base.
3
6. Drill two
CAUTION:
⁄16-in. mounting holes in wall where marked.
Be careful not to drill into wiring in wall.
Electrical shock could result.
7. Secure mounting base to wall with 2 screws and an­chors provided. Ensure all wires exit through hole in mounting base.
8. Adjust wire length and routing to allow proper closure of the thermostat. Strip each wire at the end no more
1
⁄4-in. to prevent adjacent wires from shorting to-
than gether. Match and connect wires to terminals on the thermostat. See Fig. 1-4.
CAUTION:
Improper wiring or installation maycause damage to the thermostat. Check to ensure wiring is correct before proceeding with installation of unit.
9. Push excess wiring into wall. Seal hole in wall to pre­vent drafts.
10. Close thermostat door.
11. Turn on power to unit. The thermostat will receive power from the unit.
On power up the thermostat display shows the selected setup mode (AC - single-stage air-conditioner,HP - single-stage heat pump, A2 - 2-stage air conditioner, H2 - 2-stage heat pump) for a few seconds, depending on DIP switch settings.
IV. SET THERMOSTAT CONFIGURATION
Configuration options, like DIP switch settings, are intended to be selected at installation and are not normally modified by the user. These options are not discussed in the owner’s manual and must be done as part of the installation. A spe­cial procedure for the thermostat allows entry into the con­figuration mode. To enter configuration mode, press and hold the fan button for approximately 10 seconds. The room tem­perature display will disappear and dashes (--) will be dis­played on the thermostat screen. The thermostat will auto­matically exit configuration mode if no button is pressed for 10 seconds. Seven different configurations can be set in con­figuration mode.
A. Fahrenheit or Celsius Selection
The thermostat can be set to use a Celsius or Fahrenheit tem­perature display. Press the Change Day button in configura­tion mode to access the parameter. Use the Up and Down buttons on the thermostat to change the setting between F (Fahrenheit) and C (Celsius). The default value is F.
B. Fan ON or OFF When Heat is Energized Selection
The thermostat can be set to turn the fan (G output) on or off when the heat input (terminal W) is energized. Press the Hold button while in configuration mode to access the parameter. Use the Up and Down buttons to toggle between OF (fan off during heating) and ON (fan on during heating). The default value is OF.
C. High Ambient Electric Heat Lockout Selection
If DIP switch Ais set to ON (heat pump application) and DIP switch C is set to OFF (an outdoor temperature sensor is
present), electric heat can be locked out if the outdoor ambi­ent temperature rises above the user-defined value. Tempera­tures of 15 to 55 F (in 5-degree increments) can be selected. The lockout can also be disabled. The default is OF (dis­abled). Emergency heat mode disables this function. Press the Copy Previous Day button in the configuration mode to ac­cess the parameter. Use the Up and Down buttons to in­crease or decrease the setting.
D. Clean Filter Timer Selection
The clean filter selection determines how many hours of blower operation will pass before the Clean Filter message is dis­played.A timer in the thermostat accumulates the total blower operation hours. The range of values is 400 to 3600 hours (in 400-hour increments).
• a ‘‘1’’ will be displayed for 400 hours of operation
• a ‘‘2’’ will be displayed for 800 hours of operation
• a ‘‘3’’ will be displayed for 1200 hours of operation
• a ‘‘4’’ will be displayed for 1600 hours of operation
• a ‘‘5’’ will be displayed for 2000 hours of operation
• a ‘‘6’’ will be displayed for 2400 hours of operation
• a ‘‘7’’ will be displayed for 2800 hours of operation
• a ‘‘8’’ will be displayed for 3200 hours of operation
• a ‘‘9’’ will be displayed for 3600 hours of operation The selection can also be set to OF (disabled). Press the
Reset Filter button in the configuration mode to access the parameter. Use the Up and Down buttons to change the set­ting. The default is 2 (800 hours).
NOTE: During the selection procedure, the Clean Filter mes­sage will be displayed, even if OF (disabled) is chosen.
E. Anticipator Adjustment Selection
The anticipator adjustment controls the sensitivity and cycle rate of the thermostat. Higher numbers decrease the sensi­tivity and slow the cycle rate. Lower numbers increase sen­sitivity and speed up the cycle rate. A limiting feature of the thermostat will not allow more than 4 equipment cycles per hour, regardless of the anticipator setting. Values can range from 1 to 9. The default is 3. The default selection will pro­vide optimum performance in nearly all installations. Do not change the setting unless there is a need to do so. Press the Mode button during configuration mode to change the set­ting. Use the Up and Down buttons to increase or decrease the value.
Unlike conventional thermostat anticipators, the setting is not determined by current draw. There is no need to mea­sure, know, or compensate for the current. There is no need to ‘‘droop’’ with this thermostat, regardless of the anticipator setting.
F. Keypad Lockout Selection
The thermostat has a lockout feature which will not acknowl­edge configuration buttons until the lockout code is entered. After the lockout code has been entered, the keypad will re­main unlocked until the user has stopped pressing keys for 2 minutes. The Lockout selection can be set to ON or OF (dis­abled). Press the Set Timekeyinconfigurationmodetochange the setting. Use the Up or Down buttons to toggle between off and on. The default is OF.
NOTE: If the lockout function is enabled, the user can only disable the lockout by pressing the correct buttons, in order, within a 10-second time period. The button sequence is: press the Mode button; press the Copy Previous Day button; press the Set Time button; and press the Hold button. The lockout will then be disabled until the user stops pressing buttons for 2 minutes.
—2—
CONNECTION BOARD
O/W2
Y1
R
G
Y/Y2
W/W1
C
B
548D036-120 549B036-120 551B036-150 558D036-150 580D036-150 581B036-150
DO NOT USE
S1 S2
COMMERCIAL THERMOSTAT
L
*Does not apply to 558D and 580D036-150 units.
NOTES:
1. 558D and 580D036-072 units only have one stage of cooling, but can have 2 stages of heat. In these applications set DIP switch B to ON for 2-stage operation.
2. For 548D and 549B heat pump applications, set switch A to OFF (air conditioning). The 548D and 549B units do not have an ‘‘O’’ terminal.
Fig. 1 — Thermostat Wiring (548D036-120; 549B036-120; 551B036-150;
558D036-150; 580D036-150; 581B036-150)
R Y1
Y2
W1 W2
G
C
X
*
O/W2
Y1
Y/Y2
W/W1
DO NOT USE
S1
S2
COMMERCIAL THERMOSTAT
TB2
W2 W1
R G
C B L
R
C
Y1
Y2
G
X
551A155-240 559E180-240 559F180-300 579E180-240 579F180-300 581A155-240
Fig. 2 — Thermostat Wiring (551A155-240; 559E180-240; 559F180-300;
579E180-240; 579F180-300; 581A155-240)
—3—
O/W2
Y1
Y/Y2
W/W1
DO NOT USE
S1 S2
COMMERCIAL THERMOSTAT
TB2
RC
R
G
C B L
RH
W1
W2
Y1
Y2
G
C
X
11
2
4
C2
FIELD RELAY
C1
FIELD RELAY
542J150 and 180
NOTES:
1. Field relay P/N HN61KK224.
2. Setswitch Ato OFF (air conditioning). The 542J units do not have an ‘‘O’’ terminal.
Fig. 3 — Thermostat Wiring (542J150 and 180)
O/W2
Y1
Y/Y2
W/W1
DO NOT USE
S1 S2
COMMERCIAL THERMOSTAT
TB3
W2
W1
R
G
C B
L
558G,H240-360 580G,H240-360
R
C
Y1
Y2
G
X
Fig. 4 — Thermostat Wiring (558G,H240-360 and 580G,H240-360)
—4—
G. Low Ambient Cooling Lockout Selection
The Low Ambient Cooling Lockout feature will lock out cool­ing mode if the outdoor-air temperature is below the lockout cooling temperature (user-configured).
NOTE: This configuration is not available if DIP switch C (Re­mote Room Sensor) is set to ON or if the outdoor-air sensor is in error.
The default is OF (disabled). The lockout temperature can be set to OF (disabled) or 20 to 60 F in 5-degree increments (en­abled). To configure the selection, press the Program button in the configuration mode. Use the Up and Down buttons to increase or decrease the setting.
V. CHECK THERMOSTAT OPERATION
Perform the following procedure to check thermostat operation:
1. Press the Hold button. This will prevent the set point from changing until the desired time and temperature schedule is entered.
2. Press the Fan button to switch the fan annunciator from AUTO to ON. The fan should run continuously. Check fan operation. Press the fan button again to switch back to AUTO.
3. Press the mode button repeatedly until HEAT is dis­played in the mode annunciator. Press the Up button until the set point reads 10 degrees above room tem­perature. The heating system should begin to operate within 5 minutes.
4. Press the mode button repeatedly until COOL is dis­played in the mode annunciator.Press the Down button until the set point reads 10 degrees below room tem­perature. The cooling system should begin to operate within 5 minutes.
VI. SELECT THERMOSTAT OPERATION SETTINGS
Thermostat operation should be configured. Set the Fan and Mode configurations to their desired settings. Press the Up and Down buttons to select the desired comfort temperature.
NOTE: Daily schedules can be programmed by the installer or the user. A detailed explanation of the schedule program­ming is in the Owner’s Guide. If the daily schedules of the thermostat are being configured, refer to the thermostat own­er’s guide literature.
VII. FINAL CHECKLIST
1. Put away tools and instruments. Clean up debris and packaging.
2. Review Owner’s Guide with occupant or owner.
3. Leave Owner’s Guide with occupant or owner.
OPERATION
I. HOLD, FAN, AND MODE BUTTON OPERATION
Pressing the Hold button disables the time and temperature schedule and holds the current desired temperature set point. When a Hold is active, the HOLD annunciator is displayed on the thermostat screen. To release the Hold, press the Hold button a second time.
The Fan button selects fan operation. When the fan is set to ON, the fan willruncontinuously.When the fan is set to AUTO, the fan will run during heating and cooling operation only.
The Mode button selects the operating mode of the thermo­stat. If OFF is selected, the thermostat will not enter heating or cooling mode. If HEAT is selected, the thermostat will only enter heating mode (if the room temperature is below the
heating set point). If COOL is selected, the thermostat will only enter cooling mode (if the room temperature is above the cooling set point). If AUTO is selected, the thermostat will enter heating or cooling mode based on the room tempera­ture and the heating and cooling set points. Heat pumps also have an EHEATselection. If EHEATis selected, the heat pump will use the second stage of heating to provide heat when needed. The annuciator for each selection will be displayed on the thermostat when selected.
II. FIVE-MINUTE COMPRESSOR SHORT-CYCLE PROTECTION
The timer prevents the compressor from starting until it has been offfor at least 5 minutes. The short-cycle protection func­tion can be disabled (for one cycle only) by simultaneously pressing the Fan button and the Up button.
III. FIFTEEN-MINUTE CYCLE TIMER
The cycle timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle. This function keeps the equipment from being cycled more than 4 times in one hour. The cycle timer can be disabled (for one cycle only) by either changing the temperature set point or by simultaneously pressing the Fan button and the Up button.
IV. FIFTEEN-MINUTE STAGING TIMER
When multi-stage heating or cooling is used, the staging timer prevents any higher stage from energizing until at least 15 minutes has passed from the start of the previous stage. The timer is disabled if the temperature demand is greater than 5 degrees.
V. TWO-MINUTE MINIMUM ON TIME
In normal operation, when a stage is energized, it must re­main on for at least 2 minutes.
VI. HEATING/COOLING SET POINT MINIMUM DIFFERENCE
A minimum difference of 3 degrees is enforced between the heating and cooling set points. The thermostat will not allow the set points to be set within 3 degrees of each other.
VII. AUTO-CHANGEOVER TIMER
When the auto-changeover mode is selected, the thermostat will not change from heating to cooling or cooling to heating until an opposite demand has existed for a minimum of 10 minutes. The timer is disabled if the heating or cooling set point is changed.
VIII. POWER-ON THERMOSTAT CHECK
When power is applied to the thermostat, all possible display annunciators are turned on for a few seconds. The thermo­stat then indicates the current mode and configuration infor­mation with a 2-digit code. The following codes can be dis­played: AC — single-speed air conditioner, HP — single­speed heat pump, A2 — two-speed air conditioner, and H2 — two-speed heat pump.
IX. ERROR CODES
The thermostat will display the following error codes if er­rors are detected:
E1 — If the thermostat cannot properly read room tempera­ture, the thermostat will display an E1 and all outputs (ex­cept the fan if on), will be deenergized.
E2 — If the AC line voltage drops below the minimum level, all outputs are deenergized and the thermostat will display an E2. The E2 error will remain until proper line voltage has
—5—
been restored (plus 15 seconds). If the line voltage is com­pletely interrupted, the thermostat display will immediately go blank.
X. SMART RECOVERY (Heating Mode Only)
unoccupied). The Smart Recovery function begins 1.5 hours before the scheduled occupiedmodeand gradually adjusts room temperature so the temperature is at the occupied mode set point when the occupied time period begins.
The thermostat has 2 programmed schedule modes, normal occupied mode and setback mode (a time when the space is
TROUBLESHOOTING
PROBLEM SOLUTION
LCD display on thermostat not illuminated Check for 24 vac between R and C at terminal connections. Both R and ‘‘E2’’ displayed on thermostat Brownout condition or voltage is too low to thermostat. Check wiring and
‘‘E1’’ displayed on thermostat Temperature sensor reading is out of range. Check the sensor for dam-
‘‘Clean Filter’’ is displayed on thermostat After the configured number of blower operating hours, the Clean Filter
‘‘--’’ displayed on thermostat If the outdoor thermostat is in error, not connected, or shorted, ‘‘--’’ will be Cooling will not energize Select COOL mode. Decrease cooling set point to 10 degrees below
Heating will not energize Select HEAT mode. Increase heating set point to 10 degrees above room
C must be connected for proper thermostat operation. check for 24 vac at R and C. The E2 error will clear 15 seconds after
acceptable power levels are restored. age. Check sensor wiring. Cycle power to thermostat. If display is not
cleared, replace thermostat . message will be displayed. This reminds the owner to replace the filter.
Press the Reset Filter button to reset the blower operation timer to 0 hours.
displayed. Check outdoor thermostat wiring and replace if necessary. room temperature. Simultaneously press Fan and Up buttons to disable
timers. Check for 24 vac at Y/Y2 terminal. If present, thermostat is oper­ating correctly and problem is with wiring or equipment. If 24 vac is not present, replace the thermostat.
temperature. Simultaneously press Fan and Up buttons to disable timers. Check for 24 vac at Y/Y2 terminal (for heat pump) or W/W1 terminal (for gas/electric heat unit). If present, thermostat is operating correctly and problem is with wiring or equipment. If 24 vac is not present, replace the thermostat.
—6—
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover:
• Unit Familiarization
• Installation Overview
• Maintenance
• Operating Sequence
A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included.
Copyright 1996 Carrier Corporation CATALOG NO. BDP-809-641
Loading...