Bryant T6-NHP, T6-PAC, T6-NAC, T6-PHP User Manual

T6PAC, T6−PHP, T6NAC, T6NHP PREFERREDt SERIES AC / HP THERMOSTAT
Installation Instructions
A07045 A07044
Programmable Control Non-Programmable Control
Designed and Assembled in the U.S.A.
US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION CONSIDERATIONS 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYSTEM STARTUP AND CHECKOUT 38. . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATIONAL INFORMATION 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WIRING DIAGRAMS 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THERMOSTAT CONFIGURATION RECORD 58. . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage AC/HP Control.
Recognize safety information. This is the safetyalert symbol . When you see this symbol on the equipment and in the instruction manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1
INTRODUCTION
Bryant’s 7day, 5/2day, 1day programmable and non−programmable Preferred Series Thermostat Control is a wall−mounted, low−voltage temperature control in either a single unit or a twopiece unit. In two−piece configuration, the relays are located near the equipment and a two−wire connection is used between the Display Module and the Equipment Control Module. Singlepiece installation requires more wiring and results in a higher profile. The Preferred Series Thermostat has no need for batteries to store userconfigured settings in memory. During power loss its internal memory saves settings for unlimited time, and the clock continues to run for at least 24 hours. An extension of Bryant’s proven line of thermostats; it provides separate setpoints for heating and cooling.
In the control’s programmable configuration, different heating and cooling setpoints and times are programmable for 4 periods per day or 2 periods per day. Programming can be done for 7 days per week, 5/2 days per week, or 1 day. The programmable Thermostat Control can also be user configured as a nonprogrammable Thermostat Control.
The nonprogrammable Thermostat Control features Touch ’N’ Go settings for quick and easy temperature change without complicated programming schedules. And, its Touch ’N’ Go technology enables the user to switch between three different userconfigurable settings through intuitive buttons located just below the display.
2
INSTALLATION CONSIDERATIONS
Power
This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the lowvoltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. See Fig. 1. For applications using two 24VAC transformers, one in the indoor unit and one in the outdoor unit, connect the common from each to the C terminal. Connect R from the indoor unit to the Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break jumper on the circuit board. The W signal is taken from the Rh power and the G signal is taken from the Rc power. If thermostat has been installed in a twotransformer application that is later changed to a single−transformer installation, installer must install a field supplied jumper between Rc and Rh. Depending on the installation, up to 14 wires may be required. Installation as twopiece unit is recommended. Only 2 wires are required for connection between Display Module and Equipment Control Module. These two wires (V+ and Vg) do not provide ordinary 24VAC. They carry a combination of power and communications data that is unique to these products.
3
A07052
Fig. 1 PCB Breakout Jumper
Models
There are programmable and nonprogrammable models for all applications. They can be configured for AC or HP installations, allowing it to be used in place of all Bryant thermostats. Programmable thermostats may be configured as nonprogrammable if user desires.
Outdoor Temperature Sensor
The outdoor air temperature sensor is not included with the AC/HP Control. It is available as an accessory, part number TSTATBBSEN01B. Optimum performance is obtained when an outdoor temperature sensor is used with the AC/HP Control. Plan installation so that 2 wires can be run from Equipment Control Module to an outdoor location, preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection. Sensor can be mounted to outdoor unit and existing
4
dedicated sensor wires may be used for its connection. Details are provided in sensor instructions.
Remote Indoor Temperature Sensor
A remote temperature sensor may be used with the programmable heat pump and programmable air conditioner thermostats where it is desirable to install the thermostat in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor.
Two−Piece Thermostat Configuration
The Preferred Series AC/HP Control can be installed in one of two configurations. The control may be installed as a singlepiece thermostat or it may be split into two pieces and mounted in separate locations. As a singlepiece unit, all required wiring must be brought to the Equipment Control Module for connection to the terminal strip. In twopiece configuration, the Display Module can be mounted in the living space while the Equipment Control Module may be mounted near the indoor furnace or fan coil. Connection from the display to the Equipment Control Module requires only two wires. All other control wires are connected to the Equipment Control Module from the HVAC equipment. This configuration results in a slimmer display and locates the Equipment Control Module containing the switching relays away from the main living space where relay clicking will not be heard.
The model numbers on the Display Module and the Equipment Control Module (ECM) must match or unpredictable results may occur.
Two wire pigtail replacement part number is TX2WR05.
5
Wiring
Wire length should be no more than 250 ft (76m). Use 22 AWG for normal wiring applications. Continuous wire lengths over 100 ft (30.5m) should use 20 AWG or larger.
INSTALLATION
Carton contains the following components. See Fig. 2 for programmable models or Fig. 3 for nonprogrammable models.
A07756
Fig. 2 T6PAC / T6−PHP Carton Contents
1. Display Module
2. Standoff for Equipment Control Module
3. Screws and pig tail
4. Equipment Control Module
6
Fig. 3 T6NAC / T6NHP Carton Contents
1. Display Module
2. Standoff for Equipment Control Module
3. Screws and pig tail
4. Equipment Control Module
AC/HP Control Location
AC/HP Control should be mounted:
Approximately 5 ft (1.5m) from floor. Close to or in a frequently used room, preferably on an inside parti-
tioning wall.
On a section of wall without pipes or duct work.
7
A07757
AC/HP Control should NOT be mounted:
Close to a window, on an outside wall, or next to a door leading to the
outside.
Exposed to direct light or heat from a lamp, sun, fireplace, or other
temperatureradiating objects which could cause a false reading.
Close to or in direct airflow from supply registers and return−air regis-
ters.
In areas with poor air circulation, such as behind a door or in an al-
cove.
Installer should determine whether control will be installed as singlepiece or twopiece. In singlepiece configuration, as many as 14 wires may need to run to wall mounting location for connection to the control. In two−piece configuration, the Display Module and Equipment Control Module are connected by two wires.
Install AC/HP Control
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing AC/HP Control, turn off all power to equipment. There may be more than 1 power disconnect.
WARNING
8
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power.
1. Turn off all power to equipment.
2. If an existing thermostat is being replaced a. Remove existing thermostat from wall.
b. Disconnect wires from existing thermostat, 1 at a time.
c. As each wire is disconnected, record wire color and terminal marking.
d. Discard or recycle old thermostat.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly.
9
TwoPiece Installation
The following steps should be followed for the installation of the two−piece configuration.
NOTE: The 2−wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals.
1. Remove mounting plate from back of Display Module by pressing the two tabs on the bottom edge and pulling away. See Fig. 4 and 5.
A07225
Fig. 4 Press Tabs to Remove Backplate
10
A07226
Fig. 5 Take Apart
2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be lev­eled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and an­chors. See Fig. 6.
11
A07165
Fig. 6 Backplate Mounting
3. Drill two 3/16−in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box, if desired. Hole pattern on ther­mostat mounting base matches junction box mounting holes.
4. Secure rear plastic mounting base to wall with 4 screws and anchors pro­vided. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors Make sure all wires extend through hole in mounting base.
5. Adjust length and routing of each wire to reach proper connector block and terminal on mounting base with 1/4−in. (6mm) extra wire.
6. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrect­ly, the Display Module will not operate. See Fig. 7, 8 and 9.
12
Control Module Wiring Guide
Control Module Wiring Guide
Relays
Relays
OAT
OAT
OAT /
OAT /
RRS
RRS
RRS
RRS return
return
{
{
SRTN
SRTN
HUM
HUM
D1
D1
dry
dry contact
contact
D2
D2
connect
connect
V+
V+
to user
to user
Vg
Vg
interface
interface
Fig. 7 Control Module Wiring Guide
HUM terminal is not used on this model.
Red is V+
Black is Vg
13
Rc
Rc
Rh
Rh W / W1
W / W1
G
G Y/Y2
Y/Y2
C
C O/W2/B
O/W2/B Y1
Y1
Y1 used for
Y1 used for multi-speed
multi-speed cooling
cooling Y1 = stage 1
Y1 = stage 1 Y2 = stage 2
Y2 = stage 2
Y used for
Y used for single stage
single stage cooling
cooling
A07687
Fig. 8 Secure Wires to Terminal Strip
Fig. 9 Connect Pigtail Wires to Display Module
14
A07166
A07167
NOTE: The 2−wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals.
Red is V+
Black is Vg
7. Push any excess wire into wall and against mounting base. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
8. Make sure to attach 2−wire pigtail to Display Module mounting base. It is packed loose in the box from the factory. Then attach 2wire pigtail to the back of the Display Module via 2 pin, keyed connector.
9. Reattach Display Module body to mounting base by first setting on at top of mounting base and then push bottom corners of Display Module to snap into place. See Fig. 10.
A07169
Fig. 10 Attach Display to Backplate
15
10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 11.
IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.).
A07217
Fig. 11 Equipment Control Module on Equipment
11. Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 12.
16
A07227
Fig. 12 Standoff
NOTE: Standoffs are provided as an aid when installing Equipment Control
Module on inside equipment or a solid wall.
12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrect­ly, the Display Module will not operate. See Fig. 7, 8 and 9.
13. Snap cover over top of Equipment Control Module. See Fig. 13.
17
A07218
Fig. 13 Cover on Equipment Control Module
14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33.
a. AC — 1stage air conditioner, AC, with furnace or fan coil
b. HP — 1stage heat pump, HP only with fan coil
c. H — heating only system, furnace only or fan coil with electric
heat only
d. C — cooling only system, AC with fan coil
e. H2 — 2stage heat pump with fan coil
f. A2 — 2stage air conditioner with fan coil or furnace
18
Loading...
+ 44 hidden pages