Bryant T1-NHP, T1-NAC User Manual

T1--NAC T1--NHP LEGACY LINE--RNC NON--PROGRAMMABLE THERMOSTAT
Installation Instructions
A07110
L e g a c y L i n e --- R N C N o n --- P r o g r a m m a b l e T h e r m o s t a t
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1...................................
INSTALLATION CONSIDERATIONS 1...................
INSTALLATION 1....................................
Step 1 — Thermostat Location 1........................
Step 2— Install Thermostat 2...........................
Step 3 — Set Thermostat Configuration 2.................
Step 4 — Thermostat Operation 3........................
Step 5 — Check Thermostat Operation 3..................
WIRING DIAGRAMS 4................................
SAFETY CONSIDERAT IONS
Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage thermostat.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the equipment and in the instruction manual, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING,andCAUTION.
These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury
or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
The Legacy Line--RNC Series thermostat is an electronic 24VAC, non--programmable, manual changeover wall mount thermostat. This thermostat uses a single setpoint to maintain and control room temperature in both the heating and air conditioning modes. The thermostat is designed to maintain +/-- 2_F accuracy. No batteries are required; temperature, fan, mode, and installer configuration settings are preserved with power off.
INSTALLATION CONSIDERATIONS
Air Conditioner Model
T1--NAC, Legacy Line--RNC Series Model air conditioner thermostat, may be wired with or without connecting a common wire between the indoor equipment and the thermostat. However, it is recommended to use a common wire whenever possible. Without a common wire this thermostat becomes “power stealing.” This means it will need to steal a small amount of power from the equipment to which it is connected.
NOTE: Not all HVAC equipment is compatible with power stealing type thermostats. All Bryant equipment is directly compatible with this thermostat except the Thermostat Conversion Kit, Part #TSTATXXCNV10. For all non-- Bryant equipment, consult the system equipment Installation Instructions before applying this thermostat in a power stealing manner.
Heat Pump Model
T1--NHP, Legacy Line--RNC Series Model heat pump thermostat, is compatible with all Bryant heat pump systems. It is NOT power stealing and MUST have both the R and C terminals connected to operate properly. This thermostat uses a green LED to indicate auxiliary heat and emergency heat operation.
INSTALLATION
Step 1 — Thermostat Location
Thermostat should be mounted:
S Approximately 5 ft (1.5m) from floor. S Close to or in a frequently used room, preferably on an
inside partitioning wall.
S On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
.
S Close to a window, on an outside wall, or next to a door
leading to the outside.
S Exposed to direct light and heat from the sun, a lamp,
fireplace, or other heat--radiating object which may cause a false reading.
S Close to or in direct airflow from supply registers and
return--air grilles.
S In areas with poor air circulation, such as behind a door
or in an alcove.
Step 2 — Install Thermostat
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing thermostat, turn off all power to unit. There may be more than 1 disconnect.
1. Turn OFF all power to unit.
2. If an existing thermostat is being replaced:
a. Remove existing thermostat from wall.
b. Disconnect wires from existing thermostat, one at a
time. Be careful not to allow wires to fall back into wall.
c. As each wire is disconnected, record wire color and
terminal marking.
d. Discard or recycle old thermostat.
!
CAUTION
ENVIRONMENTAL HAZARD
T1--NAC / T1--NHP
Failure to follow this caution may result in environmental damage.
Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly.
3. Separate front and back (mounting base) assembly of thermostat.
4. Route thermostat wires through hole in mounting base. Level mounting base against wall (for aesthetic value only, thermostat need not be level for proper operation) and mark wall through 2 mounting holes.
5. Drill two 3/16--in. mounting holes in wall where marked.
6. Secure mounting base to wall with 2 anchors and screws provided making sure all wires extend through hole in plastic.
7. Strip 1/4 in. insulation from thermostat wire and adjust length to reach terminal block connector on mounting base. Match and connect proper wiring in accordance with wiring diagrams.
8. Push any excess wire back into wall. Seal hole in wall to prevent air leaks. Leaks can affect thermostat operation. Any excess wire left inside thermostat casing may also affect thermostat operation by interfering with airflow across the temperature sensor.
9. Snap thermostat together making sure terminal block connector aligns, and assembly is secure.
10. Turn on power to unit.
On power up, depending on the thermostat model being used, the LCD readout will display either, AC or PC for air conditioner model (1-- stage heat/1--stage cool), or HP or PH for heat pump model (2--stage heat/1--stage cool).
Step 3 — Set Thermostat Configuration
Configuration options allow the installer to configure the thermostat for a particular installation. These selections are intended to be made at installation and normally are not modified by the homeowner. Below is a list of available options followed by a description of each one.
Option 01 -- Equipment Type Option 03 -- Fahrenheit or Centigrade operation
Option 04 -- Enable fan (G) ON with heat (W)
Option 10 -- O (reversing valve) On with Heat or Cool (present
on Heat Pump model only)
Option 13 -- Room temperature offset adjustment Note that not all configuration option numbers are used in this
product.
To Enter The Configuration Mode:
Press and hold FAN button for approximately 10 sec until room temperature disappears and the display reads “01”. You are now in configuration mode.
NOTE: If FAN button is pressed again, or if no button is pressed for 3 minutes, the thermostat will exit configuration mode and return to normal operation. To re--enter configuration mode, the FAN button must be pressed and held for 10 sec again.
While in the configuration mode, the temperature display is used to show both the option number and the selected choice within each option. Each press of the H/C button alternates between the option number and the selection within that option. When the configuration mode is first entered, option 01 is displayed. The up and down buttons now move between the available option numbers. Once an option number is selected, press the H/C button once to display the currently selected choice within that option. The up and down buttons now move between the available choices within that option. After the new choice is made, press the H/C button again to return to the option number display. When finished with option selections, press FAN button once to exit the configuration mode.
Option 01 — Equipment Type
Selections: with HP thermostat: HP, AC, PH, or PC
with AC thermostat: AC or PC
Meanings:
PH or PC selects PTAC units (Packaged Terminal Air Conditioners) which are used in motel rooms and other rented spaces. When this option is selected, the display shows only the setpoint, not the room temperature. Also the compressor timeguard is disabled, allowing the compressortoturnonimmediatelywhenademandis established.
HP or PH controls 1 speed heat pump with 1 stage of aux heat. AC or PC controls 1 speed air conditioner with one stage of heat. Note that this option allows a HP thermostat to be converted to
control an AC system.
Option 03 — Fahrenheit/Centigrade Selection
This selection operates the thermostat in either Fahrenheit or Centigrade. Factory default is F .
Available Selection:
Use UP and DOWN buttons to change between F and C.
Option 04 — G (fan) ON with W (Heat) Selection
This selection determines whether G (fan) output is to be ON or OFF when W (furnace or strip heat) output is ON. Most furnaces and fan coils manage their own blowers and do not require a separate G signal. For these applications, select OFF. Some auxiliary heaters require a separate G signal from the thermostat to turn on the blower. In this case, select ON. Factory default is OF (off).
Available Selection:
Use UP and DOWN buttons to change between ON and OFF.
Option 10 — O (reversing valve) On with Heat or Cool Selection
This selection is only available on heat pump model thermostats. This selection determines whether the reversing valve is energized in the heating or cooling mode. Factory default is C.
2
Available Selection:
Use UP and DOWN buttons to change between H and C.
Option 13 — Room Temperature Offset Adjustment
This option allows calibration (or deliberate miscalibration) of the room temperature sensor. There are various reasons why homeowners may want to have displayed temperature adjusted to a higher or lower value. The selected number is the number of degrees, plus or minus, which will be added to actual temperature.
The numbers can range between --5 and +5. Factory default is 0.
Available Selection:
Use UP and DOWN buttons to now move between --5 and +5 in increments of 1.
Step 4 — Thermostat Operation
Temperature Display
Thermostat will display room temperature until UP or DOWN button is pressed. The word SET appears when these buttons are pressed and the current setpoint is displayed. If no buttons are pressed for 5 sec, the display will change back to show room temperature.
Timeguard Timer
A 5-- minute timeguard is built into the thermostat immediately upon power up, and any time the compressor turns off. The compressor will not turn on until the timeguard has expired. The timeguard affects only compressor operation. Pressing UP and FAN buttons simultaneously will override the timeguard for 1 cycle. With PH or PC selected under Option 01, this timer is defeated.
Cycle Timer
In normal heating and cooling operation the thermostat will not allow more than 4 equipment cycles per hour (or 1 cycle every 15 minutes). Both the Y and W outputs have a 15--minute timer that starts counting down when the output is turned on, (e.g., if Y output is turned on for 9 minutes and then satisfies, it cannot turn back on for another 6 minutes regardless of demand). However, pressing UP and FAN buttons simultaneously or changing the setpoint will override the timer for 1 cycle.
Minimum on Timer
Once the equipment has turned on, it will remain on for a minimum of 3 minutes regardless of demand. However, the equipment can turn off in less than 3 minutes if a change in setpoint or a change in mode occurs.
Staging Timer
If the thermostat is a heat pump model, it has 2--stage heat capability. With HP operation, there is a 15--minute delay between the first and second stages of heat. The Y output will energize first, then 15 minutes later, W is allowed to come on if the thermostat determines it is not satisfying the demand.
However, if the heating demand is greater than 5_F, there will be only a 30 second delay before bringing on W.
Auxiliary Heat Indicator
A green LED indicates the use of auxiliary heat or emergency heat.
Error Messages
“----” (two dashes) will be displayed if the thermostat cannot properly read room temperature. If “-- --” appears, replace thermostat.
E4 will be displayed if the thermostat has an internal memory failure. If E4 appears, replace thermostat.
Step 5 — Check Thermostat Operation
Fan Operation
1. Press FAN button. This will start continuous fan operation. FAN annunciator will turn on.
2. Press FAN button again. This will stop continuous fan operation. FAN annunciator will turn off.
Heating Operation
1. Press H/C button until HEAT is displayed.
2. Press UP button until LCD readout reads 3_F above room temperature. Press UP and FAN buttons simultaneously to defeat timers. Heating system should begin to operate immediately.
3. For HP thermostats only, press H/C button until EMHT (emergency heat) appears. Press UP and FAN buttons simultaneously to defeat timers. Emergency heating (W is ON, Y is OFF) should begin immediately.
Cooling Operation
1. Press H/C button until COOL is displayed.
2. Press DOWN button until LCD readout reads 3_Fbelow room temperature. Press UP and FAN buttons simultaneously to defeat timers. Cooling system should begin to operate immediately.
Table 1 shows the thermostat outputs for each available stage of heating or cooling. It may be useful in checkout or troubleshooting.
T1--NAC / T1--NHP
Table 1 – Outputs
EQUIPMENT
CONFIGURATION
OPTION #1
AC, PC AC, HP Y, G W --- --- --- ---
HP, PH
RVS = C
HP, PH
RVS = H
THERMOSTAT
FACTORY
CONFIGURATION
HP Y, G , O / B Y, G Y, G , W W
HP Y, G Y, G , O / B Y, G , W, O / B W
COOL
STAGE 1
HEAT
STAGE 1
HEAT
STAGE 2
3
EM HEAT
WIRING DIAGRAMS
Fig. 1 -- A/C Thermostat Typical Installation
A06566
Fig. 2 -- HP Thermostat Typical Installation
A06567
T1--NAC / T1--NHP
E2007 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/07
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
4
Catalog No. IIT1 --- NAC --- 0 2
R e p l a c e s : I I T 1 --- N A C --- 0 1
TB--NAC TB--NHP LEGACY LINE--RNC NON--PROGRAMMABLE THERMOSTAT
Homeowner’s Guide
A07110
1. To Select the Mode: Use the H/C button to move between the choices. OFF, HEAT, COOL, or EMHT will appear on the display. EMHT will only appear on heat pump models.
2. To Select the Fan Operation: Use the FAN button to move between continuous fan (indicated by the FAN ON icon) and auto fan operation.
3. To Read the Room Temperature: The large display reads room temperature until a button is pressed.
4. To Adjust the Setpoint: In normal operation, the large display shows room temperature. At the first press of the UP or DOWN button, the large display shows the current setpoint and the SET TEMP icon is turned on. Further presses of the UP or DOWN button adjust the setpoint upward or downward. Five seconds after the last button press, the display returns to the room temperature and the SET TEMP icon turns off.
L e g a c y L i n e --- R N C N o n --- P r o g r a m m a b l e T h e r m o s t a t
TROUBLESHOOTING
What if there is a green light on in the upper corner of the display area?
This thermostat uses a green LED to indicate auxiliary heat and emergency heat operation on the Heat Pump model. This green light means one of two things.
1. Auxiliary Heat is on: This light turns on automatically when the system determines that it’s too cold outside for your heat pump to heat the house without help. So, it’s getting help from the electric heaters.
NOTE: This indicator does not reflect a problem with your system.
2. Emergency Heat is on: If the heat pump is not working properly, you can manually select the emergency heat for extra help in heating. You’ll know there’s a problem if the house can’t seem to get warm when it’s cold outside. You want to avoid using emergency heat, though, because it’s the most expensive option. And, of course, if you suspect a problem with your heat pump, call your heating and cooling dealer immediately.
BRYANT HEATING & COOLING SYSTEMS
FOR SERVICE OR REPAIR, FOLLOW THESE STEPS IN ORDER:
FIRST: Contact the installer. You may find their name on the furnace or in your Homeowner’s Packet. If the installer’s name is not known, call your builder or home retailer if yours is a new residence.
SECOND: Contact the nearest distributor. (See telephone yellow pages.) THIRD: Contact:
Bryant Heating and Cooling Systems Consumer Relations
P.O. Box 4808 Syracuse, New York 13221 Phone: 1--800 --428--4326
Model No. ____________________________________________ Unit Serial No. _________________________________________
Date of Installation ______________________________________ Installed by ___________________________________________
Name of Owner ________________________________________ Address of Installation ___________________________________
THERMOSTAT LIMITED WARRANTY
FIVE--YEAR LIMITED WARRANTY -- Bryant Heating and Cooling Systems (hereinafter referred to as “Company”) warrants this product to be free from defects in material and workmanship. If a defect is found within five years from date of original installation of product (whether or not actual use begins on that date) Company will provide a new or remanufactured part, at Company’s sole option, to replace any defective part, without charge for the part itself.
This warranty does not include labor or other costs incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either defective parts or replacement parts.
WARRANTY CONDITIONS:
1. Warranties apply only to products in their original installation location.
2. Installation, use, care, and maintenance must be normal and in accordance with instructions contained in the Owner’s Manual and Company’s service information.
3. Defective parts must be returned to the distributor through a registered servicing dealer for credit.
4. All work shall be performed during normal working hours.
LIMITATIONS OF WARRANTIES -- ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE) ARE HEREBY LIMITED IN DURATION TO PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN AND APPLIES. SOME STATES DO NOT LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON, WHA
COMPANY WILL NOT BE RESPONSIBLE
1. Normal maintenance as outlined in the installation and servicing instructions or Owner’s Manual, including filter cleaning and/or replacement and lubrication.
2. Damage or repairs required as a consequence of faulty installation, misapplication, abuse, improper servicing, unauthorized alteration or improper operation.
3. Failure to start due to voltage conditions, blown fuses, open circuit breakers, or damages due to the inadequacy or interruption of electrical service.
4. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environments or other conditions beyond the control of Company.
5. Parts not supplied or designated by Company, or damages resulting from their use.
6. Company products installed outside the continental U.S.A., Alaska, Hawaii, and Canada.
7. Electricity or fuel costs, or increases in electricity or fuel costs from any reason whatsoever, including additional or unusual use of supplemental electric heat.
8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY NA
WHATSOEVER
apply to you.
This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
. Some states do not allow the exclusion of incidental or consequential damages, so the above limitation may not
FOR:
TSOEVER.
ENLARGED,
OF
THE
ALLOW
THE
TURE
Catalog No. 13TS--TA61 39004DP272 1--03