Installation and Start-Up Instructions
Evolution™ Zone Control
SYSTXBBUIZ01
ZONE
HEAT
HOLD
EVOLUTION
™
SYSTEM
Evolution™ Zone Control
SYSTXBBUIZ01
NOTE: Read the entire instruction manual before starting the
installation.
This symbol → indicates a change since the last issue.
COOL
OFF
A04031
Cancels: NewII UIZ01-0-1
03-04
WARNING signifies a hazard, which could result in personal
injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and property
damage. NOTE is used to highlight suggestions which may result
in enhanced installation, reliability, or operation.
INTRODUCTION
The Evolution Zone System consists of several intelligent communicating components which includes the Evolution Zone Control (or User Interface), Smart Sensors, Damper Control Module,
variable- speed furnace or FE fan coil, 2-speed AC or HP, which
continually communicate with each other via a four-wire connection called the ABCD bus. Commands, operating conditions, and
other data are passed continually between components over the
ABCD bus. The result is a new level of comfort, versatility, and
simplicity.
All furnaces or fan coils are variable-speed and multi stage for
maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either a dual capacity (communicating), or a standard
24 vac controlled outdoor unit may be used.
When using conventional outdoor units, the variable-speed furnace
or fan coil provides the 24 volt signals needed to control them.
Also,theEvolution™DamperControlModule(P/N
SYSTXBB4ZC01) allows connection of a conventional HRV or
ERV without the need for a separate wall control.
All system components are controlled through the wall mounted
Evolution™ Zone Control, which replaces the conventional thermostat and provides the homeowner with a single wall control for
all features of the system.
Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installation may damage the Evolution™ Zone System. Recognize safety
information. This is the safety-alert symbol
. When you see this
symbol on the equipment and in the instruction manual, be alert to
the potential for personal injury. Understand the signal words
DANGER, WARNING, and CAUTION. These words are used
with the safety-alert symbol. DANGER identifies the most serious
hazards, which will result in severe personal injury or death.
INSTALLATION AND START-UP OVERVIEW
This instruction covers installation of the Evolution™ Zone
Control only. Physical installation instructions for the indoor and
outdoor equipment, Damper Control Module, and accessories are
provided with each unit.
Setup, commissioning, operation, and troubleshooting of the
Evolution Zone System is covered only in this installation instruction. It is the guide to connecting the system components and
commissioning the system once all physical components are
installed. Special screen prompts and start-up capabilities are
provided in the Evolution System to simplify and automate the
initial commissioning of the system.
• Install Evolution™ Zone Control according to this instruction.
• Install indoor unit, outdoor unit, and accessories according to
their instructions.
• Wire complete system according to this instruction.
• Setup, commission, and operate system according to this
instruction to assure a smooth and trouble free start-up.
INSTALLATION
A. Step 1 — Check Equipment and Job Site
INSPECT EQUIPMENT — File claim with shipping company,
prior to installation, if shipment is damaged or incomplete.
—1—
B. Step 2 — Evolution Zone Control™ Location and
Wiring Considerations
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or possible equipment damage.
Disconnect Power before routing control wiring.
All wiring must comply with national, local, and state codes.
EVOLUTION™ ZONE CONTROL LOCATION— The Evolu-
tion Zone Control™ User Interface is the command center for the
Evolution Zone System and is typically located in Zone 1 to sense
and control temperature in this zone. It should be located where it
is easily accessible and visible to the adult homeowner or end user.
For accurate temperature measurement, the following guidelines
should be followed:
The Evolution™ Zone Control and Room Sensors should be
mounted:
• Approximately 5 feet (1.5 meters) from the floor.
• Close to or in a frequently used room, preferably on an inside
partitioning wall.
• On a section of wall without pipes or ductwork.
The Evolution™ Zone Control and Room Sensors should NOT be
mounted:
• Close to a window, on an outside wall, or next to a door leading
to the outside.
• Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature-radiating objects which could cause a false
reading.
• Close to or in direct airflow from supply registers.
• In areas with poor air circulation, such as behind a door or in
an alcove.
REMOTE ROOM SENSOR OPTION — A remote room sensor
can be used with the Evolution™ Zone Control to take the place of
the User Interface internal temperature sensor. This allows the
Evolution™ Zone Control to be mounted in areas with less than
optimal airflow (such as near an exterior door, window or in a
closet). The remote sensor can be wired to the terminal block
connectors labeled S1 and S2 at the User Interface backplate, or
the OS1 and OS1C connection at the Damper Control Module. In
either case, the Evolution Zone Control will automatically detect
the remote room sensor and ignore its internal temperature sensor.
It is also important to note the humidity sensor cannot be remotely
located, so do not locate the Evolution Zone Control in an area
where humidity sensing may not be accurate.
NOTE: S1 & S2 connection on UI backplate is now used for
Remote Room Sensor, NOT for OAT Sensor hookup.
In addition, the Remote Room Sensor is a temperature sensor only,
having no additional user inputs. This sensor is typically connected
to the Damper Control Module and used to sense and control
temperature in each zone.
SMART SENSOR — Any zone may use a Smart Sensor. It
provides a temperature display and buttons to adjust the desired
temperature in that zone only. It also displays outdoor temperature
and indoor humidity. If a Smart Sensor is used in a zone, a Remote
Room Sensor may also be used in the same zone. The Remote
Room Sensor has priority over the Smart Sensor.
WIRING CONSIDERATIONS — Ordinary thermostat wire is
recommended. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or
larger.
NOTE: ABCD bus wiring only requires a four-wire connection;
however, it is good practice to run thermostat cable having more
than four wires in the event of a damaged or broken wire during
installation.
Each communicating device in the Evolution Zone System has a
four-pin connector labeled ABCD. It is recommended that the
following color code be used when wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each
ABCD connector in the system MUST be wired consistently.
LOCATING DAMPER CONTROL MODULE — All wiring is
run back to the Damper Control Module. Select a location near the
furnace or fan coil where wiring from the User Interface, each
Remote Room Sensor or Smart Sensor, each damper actuator, and
the equipment itself can come together easily.
The Damper Control Module is approved for indoor use only and
should never be installed with any of its components exposed to
the elements. The Damper Control Module (and zone dampers)
may be installed in any area where the temperature remains
between -4°F. to 158° F. (-20°Cto70°C), and there is no
condensation. The cover must be installed to prevent damage from
other sources. Do not locate where it will be accessible to children.
It may be mounted in either vertical or horizontal position.
Remember that wiring access is likely the most important consideration.
CAUTION: ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
To prevent possible damage to the Damper Control
Module, DO NOT mount on plenum, ductwork, or flush
against furnace or fan coil.
MOUNTING EVOLUTION™ ZONE CONTROL — There are
two options for mounting the Evolution Zone Control™ to the
wall. First, become familiar with all plastic assembly pieces shown
in Fig. 2 through 9. The User Interface will snap together with
either the Recess Mount or the Surface Mount backplate.
RECESS MOUNT — This provides the thinnest mounting configuration (See Fig. 3). The backplate containing the recessed
terminal block can be mounted directly to the wall by cutting a
hole 1 ½″ wide by 2 1/8″ high. Mark location and cut hole in wall.
NOTE: Always ensure the Evolution Zone Control™ location is
acceptable before cutting any holes in wall.
SURFACE MOUNT — This provides surface mounting configuration, which allows use of a small hole in the wall. A surface
mount backplate is supplied (See Fig. 4). Attach backplate as
shown in Fig. 7, and the assembly will mount directly to the wall
requiring only a small hole in the wall allowing a four wire
connection to pass through.
NOTE: Once Evolution Zone Control™ is secured to wall with
the backplate assembly (snapped together), care must be taken not
to bend or break the interlocking tabs when removing. Gently
remove Evolution Zone Control by rocking up/down until interlocking tabs release.
DECORATIVE BACKPLATE — Supplied is a thin decorative
backplate (see Fig. 5), to hide any marks/screw holes left from the
previous thermostat. This decorative backplate (or beauty ring) can
be used in either the recess or surface mount installation by
snapping it onto back of recessed mount backplate or surface
mount backplate before securing to wall. See Fig. 8 and 9 for a
larger decorative backplate P/N SYSTXXOLBP01 (5.75″ wide X
6″ tall), which can be ordered separately.
—2—
Fig. 5—Thin Decorative Backplate
A04017
Fig. 2—Evolution Zone Control
Fig. 3—Recessed Mount Backplate
A03185
A03186
Recessed terminal
block in wall 11/2˝
wide by 2 1/8˝ high
Recessed Mount
Interlocking T abs (4)
Fig. 6—Recessed Mount Assembly
Surface Mount
Backplate to wall
A03190
Fig. 4—Surface Mount Backplate
C. Step 3 — Installing Evolution Zone Control™
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing Evolution Zone Control™, turn off all
power to equipment. There may be more than one power
source to disconnect.
1. Turn off all power to equipment.
2. If an existing User Interface or control is being replaced:
a. Remove existing control from wall.
b. Disconnect wires from existing control.
A03187
Interlocking T abs (4)
A03191
Fig. 7—Surface Mount Assembly
c. Discard or recycle old control.
NOTE: Mercury is a hazardous waste, if existing control contains
any mercury, it MUST be disposed of properly.
3. Select Evolution Zone Control™ mounting plastic (recess
mount or surface mount and decorative backplate if desired).
4. Route wires through large hole in mounting plastic. Level
rear plastic against wall (for aesthetic value only - Evolution
Zone Control™ need not be level to operate properly) and
mark wall through two mounting holes.
5. Drill two 3/16 inch mounting holes in wall where marked.
6. Secure mounting plastic to wall using two screws and
anchors provided.
7. Adjust length and routing of each wire to reach each wire
entry on the connector backplate. Strip ¼ inch of insulation
from each wire.
—3—
11. Perform installation of all other system equipment (i.e. zone
sensors, dampers, humidifier, ventilator, UV lights, etc.)
12. Turn on power to equipment.
A03188
Fig. 8—Large Decorative Backplate
A03192
Fig. 9—Decorative Backplate Assembly
8. Match and connect thermostat wires to proper terminals on
User Interface backplate. See wiring diagram Fig. 12, 13,
and 14.
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
NOTE: It is not mandatory that the above color code be used, but
each ABCD connection in the system MUST be wired consistently. A separate ABCD Connector comes inside packaging and
should be used when connecting to furnace (or fan coil). Ensure
connector is inserted properly into circuit board. (See Fig. 10)
ABCD
A03193
Fig. 10—4–Wire ABCD Connector
CAUTION: ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Improper wiring of the ABCD connector will cause the
Evolution Zone System to operate improperly. Check to
make sure all wiring is correct before proceeding with
installation or turning on power.
9. Push any excess wire into the wall. Seal hole in wall to
prevent any air leaks. Leaks can affect operation.
10. Attach Evolution Zone Control™ to the mounting plastic by
lining up the plastic guides on the back of the control with
the opening on the mounting plastic and push on.
Zone
Button
Left-Side
Button
Time (+/-)
Button
Hold
Button
Schedule & Vacation
Program Buttons
Up/Down
Scroll Buttons
ZONE
HOLD
SCHEDULE VACATION
PROGRAM
Schedule
to program
temperature
schedule
Vacation
to start/end
vacation
SCROLL
Scroll
up & down
BASIC
Basic
to set time,
humidity
SETUPS
ADVANCED
Advanced
for all other
settings
HEAT
COOL
Fan Button
Display Screen
(LCD)
Right-Side
Button
Heat Button
Cool Button
Temperature
(+/-) Button
System
On/Off Button
Basic & Advanced
Setup Buttons
Flip Down
Door
A04038
Fig. 11—Functional Overview
EQUIPMENT WIRING DIAGRAMS:
See wiring diagrams Fig. 12, 13, and 14 for connecting the
Evolution Zone Control and Smart Sensors to the Damper Control
Module. More information regarding Damper Control set-up and
wiring can be found in Damper Control Module Installation
Instructions.
See wiring diagram Fig. 12 which includes a variable-speed indoor
communicating furnace or FE fan coil, with a 2-speed Puron™
communicating outdoor unit. No additional OAT (outdoor air
temperature) sensor is required because the Evolution Zone
Control will use the temperature sensor inside the 2-speed unit.
See wiring diagram Fig. 13 for connecting a variable-speed indoor
communicating furnace or FE fan coil with a 1-speed air conditioning unit (non-communicating outdoor). An Outdoor Air Temperature (OAT) sensor may be installed (but is not required) at the
indoor furnace or fan coil OAT terminals. When OAT sensor is
applied, the Evolution System will provide enhanced system
features and benefits.
See wiring diagram Fig. 14 for connecting an FE fan coil with a
1-speed heat pump (non-communicating outdoor unit). When OAT
is applied, the Evolution system will provide enhanced system
features and benefits.
NOTE: For other applications not listed, refer to the Network
Interface Module (NIM) Installation Instructions.
HUMIDIFIER CONNECTION — A 24vac bypass or fan
powered humidifier may be installed.
NOTE: Do Not Use a traditional humidistat to control humidifier
operation. If a humidifier is installed, let the Evolution™ Zone
Control operate humidifier.
Bypass Humidifiers — A bypass humidifier should be wired
directly to the furnace or fan coil HUM and 24vac COM terminals.
The Evolution Zone Control will automatically energize the HUM
output during a call for humidification.
Fan Powered Humidifiers — Most fan powered humidifiers
produce internal 24vac in order to energize upon a switch or
contact closure. For this application, a 24vac N.O. Isolation Relay
(DPST) MUST be used to prevent mixing the internal humidifier
power with the indoor equipment transformer. Applying 24vac
—4—
Indoor
Zone Control
User Interface &
Smart Sensor(s)
A B C D
A B C DA B C D
Damper
Control
module
Green
Yellow
White
Red
Humidifier
Connection
Unit
HUM
COM
24V
OAT
A
B
C
D
2-Spd. AC or HP
A
B
C
D
OAT
Sensor
(Optional)
Fig. 12 — Communicating Indoor Unit w/2-Speed Pu-
ron™ Communicating Outdoor Unit
1-Spd. AC
C
Y
OAT
Sensor
A04018
Zone Control
User Interface &
Smart Sensor(s)
A B C D
A B C DA B C D
Damper
Control
module
Green
Yellow
White
Red
Humidifier
Connection
Indoor
Unit
A
B
C
D
HUM
COM
24V
Y/Y2
OAT
Fig. 13 — Connection Diagram for Furnace or FE Fan
Coil with 1-Speed AC
A04019
Green
Yellow
White
Red
Humidifier
Connection
Variable-Speed
Fan Coil
A
B
C
D
HUM
C
R
O
W
Y
OAT
1-Spd. HP
C
R
O
W2
Y
OAT
Sensor
Zone Control
User Interface &
Smart Sensor(s)
A B C D
A B C DA B C D
Damper
Control
module
Fig. 14 — Connection Diagram for FE Fan Coil with
1-Speed HP
A04020
isolation relay coil to furnace or fan coil HUM and COM terminals
will allow the Evolution Zone Control to automatically energize
the HUM output during a call for humidification. The N.O. relay
contacts will be used to energize the humidifier. See fan powered
humidifier installation instructions for more details.
WARNING: FIRE OR EQUIPMENT HAZARD
Failure to follow this warning could result in equipment
damage or fire.
Do not apply 24vac fan powered humidifier (with internal
power supply) direct to indoor unit HUM and COM
terminals.
INITIAL POWER-UP
NOTE: Refer to Functional Overview (Fig. 11) to become
familiar with key function buttons such as ″System On/Off″,
″Zone″, ″Fan″, ″Left-Side″ and ″Right-Side″ buttons, etc. These
function buttons will be used frequently during setup.
A. Section 1 — Power Up Sequence
ESTABLISHING
COMMUNICATIONS
WITH EQUIPMENT
PLEASE WAIT
SOFTWARE
VERSION
INDOOR UNIT
SEARCHING FOR
INDOOR EQUIPMENT
WORKING
OUTDOOR UNIT
SEARCHING FOR
OUTDOOR EQUIPMENT
WORKING
A03195
Fig. 15 — Power Up Sequence
This section addresses initial power up (or commissioning) of a
new Evolution Zone Control™. The User Interface will communicate and identify all Evolution components in the system. The
following is a typical example for a communicating VariableSpeed Furnace / Fan Coil with a 2-spd. Air Conditioner / Heat
Pump (including Dual Fuel).
The User Interface display will light up and indicate that it is now
″ESTABLISHING COMMUNICATIONS WITH EQUIPMENT
PLEASE WAIT″. The User Interface will automatically continue
by ″SEARCHING FOR INDOOR EQUIPMENT″, followed by
″SEARCHING FOR OUTDOOR EQUIPMENT″ (See Fig. 15).
Once the indoor and outdoor equipment has been found, the
Installer will be asked to select Accessories. Proceed to Section 4.
Selecting Accessories.
NOTE: If the variable-speed indoor equipment (furnace or fan
coil) cannot be found, the User Interface will display ″CANNOT
COMMUNICATE WITH INDOOR UNIT″. This MUST be
corrected before the initial power up sequence can continue. If
indoor unit is found, but outdoor unit is not found, ″OUTDOOR
UNIT NOT IDENTIFIED″ will appear. Proceed to the next section
for Outdoor Unit Identification.
B. Section 2 — Selecting Outdoor Unit
OUTDOOR UNIT
NOT IDENTIFIED
SELECT TYPE: NONE
NONE, AC, HP
PRESS +/- TO MAKE
SELECTION
CONTINUE
OUTDOOR UNIT
ENTER HEAT PUMP
SIZE 36000 BTU
18000 TO 60000 BTU
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
OUTDOOR UNIT
HEAT PUMP
ENTER NUMBER OF
SPEEDS, 1 or 2: 1
PRESS +/- TO MAKE
SELECTION
BACK CONTINUE
A03196
Fig. 16—Selecting Outdoor Unit
If there is no communicating outdoor unit, the screen, shown in
Fig. 16, will appear. Press either Time or Temp +/- buttons to
select AC (air conditioner), HP (heat pump), or None (no unit
installed). Press right-side button to continue to next screen.
If either AC or HP has been selected as the outdoor unit type, the
middle screen will appear (See Fig. 16). Press either Time or Temp
+/- buttons to select appropriate Btu size of outdoor unit, then press
right side button to continue. If a NIM (Network Interface Module)
is applied for non-communicating two-speed outdoor equipment,
select 1 or 2-speed compressor operation , and press right-side
button to continue.
—5—
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.