Bryant SYSTMBBSAM01 User Manual

Installation and Start-Up Instructions
EVOLUTION SYSTEM ACCESS MODULE SYSTMBBSAM01
Cancels: NEW II SAM01-0-1
05-05
Evolution System Access Module
SYSTMBBSAM01
A97038
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................1
INSTALLATION CONSIDERATIONS .......................................1
INTRODUCTION..........................................................................1
INSTALLATION........................................................................1-3
Component Location and Wiring Considerations ..............2
Connect Power Source ........................................................2
Radio Test............................................................................2
Install Components..............................................................2
Connect Water Sensor.........................................................2
System Start-Up...................................................................3
PIN Number.........................................................................3
RS-232 Connector..........................................................................3
Updating System Profile................................................................3
Troubleshooting..............................................................................3
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause fire, electrical shock, or other conditions that may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for infor­mation or assistance. The qualified installer or agency must use factory authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes and wear safety glasses. Have fire extinguisher available. Read these in­structions thoroughly and follow all warnings or cautions attached to the unit. Consult local and state building codes and Sheet Metal and Air Conditioning National Association (SMACNA) for special installation requirements.
This is the safety-alert symbol the equipment and in the instruction manual, be alert to the potential for personal injury. Understand the signal words DAN- GER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies a hazard, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INSTALLATION CONSIDERATIONS
Before the actual installation of a System Access Module can begin, determine the mounting location. A radio test must be performed with the System Access Module in the intended mounting location. See below on how to perform a radio test. The System Access Module is powered with a 24 VAC transformer (included). A 120VAC supply must be near the mounting location of the System Access Module. Provisions must be made to secure the transformer to the outlet. The D-wire (24 VAC) from the Evolution system MUST NOT be used to power the System Access Module. Use this instruction to guide the actual installation process after the Evolution system(s) have been installed. One System Access Module is capable of handling two Evolution systems.
INTRODUCTION
An Evolution System Access Module allows remote connectivity for up to two Evolution systems within the same building. The Evolution system owner as well as authorized dealer can monitor and control the system via the internet as well as by telephone. The System Access Module communicates through a two-way radio via the Skytel paging network. Please visit: http://www.skytel.com/coverage/telemetry_coverage.htm to check coverage for the installation site. The coverage must be listed as Full Servicefor the System Access Module to function properly. Please note that Skytel is continuously expanding their service area so coverage may not be indicated by the web site. The System Access Module can also monitor a dry-contact sensor to provide a warning for the presence of water in the building, or some other use. If the sensor is active, the Evolution system will not be disabled or shut down.
INSTALLATION
I. CHECK EQUIPMENT AND JOB SITE
INSPECT EQUIPMENT — File claim with shipping company, prior to installation, if shipment is damaged or incomplete.
. When you see this symbol on
—1—
II. COMPONENT LOCATION AND WIRING CONSIDER­ATIONS
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or possible equipment damage. Disconnect supply power before routing wire.
NOTE: All wiring must comply with national, state, and local codes.
LOCATING SYSTEM ACCESS MODULE
— Since the System Access Module (SAM) uses two-way radio, choose a potential mounting location that is as high and as close to outside walls or windows as possible to attempt to maximize radio coverage. The coverage is dependent on where the Skytel trans­ceivers are located. If one location does not work, try the opposite side to get the device in closer directional proximity. Temporarily mount the System Access module in the intended permanent mounting location until the radio test has passed 100%.
The System Access Module is approved for indoor use only and should never be installed with any of its components exposed to the elements. The System Access Module may be installed in any area where the temperature remains between -4° and 158°F and there is no condensation. The cover must be installed to prevent damage from other sources. Do not locate where it will be accessible to children. The SAM should be mounted in the vertical position. Remember that wiring access and Skytel reception are the most important considerations.
Select a location near the Evolution furnace or fan coil where wiring from the User Interface, each Remote Room Sensor or Smart Sensor, each damper actuator, and the equipment itself can come together easily.
CAUTION: ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation. To prevent possible damage to the System Access Mod­ule, do not mount on plenum, duct work, or flush against furnace.
WIRING CONSIDERATIONS — Ordinary thermostat wire is ideal when wiring the System Access Module (shielded cable is not necessary). Use 22 AWG or larger for normal wiring. Lengths over 100 ft. should use 20 AWG or larger wire.
III. CONNECT POWER SOURCE AND ANTENNA
Screw the antenna to the radio connector. See Fig. 3 for antenna attachment location.
A separate 24 VAC transformer is included to power the System Access Module. DO NOT connect the D-wire (24 VAC hot) from the Evolution system.
The transformer is heavy. Make sure it is secured to the power outlet with an appropriate screw through the boss on the trans­former.
IV. RADIO TEST
The purpose of this test is to verify effective 2-way communica­tions at the installation site. The test must pass 100% before the installation of the SAM can continue.
Press and hold the RADIO TEST button for at least 5 seconds. A flashing Yellow LED will indicate the test is in progress. A flashing Yellow and Green LED means the transmission is complete and the System Access Module is waiting for a reply. A constant Green LED means the radio test has passed. The radio will perform three message tests, so this sequence will occur three times. If the System Access Module has errors during the process, the test could take up to 15 minutes.
If the Red LED is lit solid, then the System Access Module failed to send the message. Try a new mounting location for the System Access Module.
If the Yellow LED is lit solid, then the System Access Module sent its message but did not receive a reply. The Bryant server may be down or the received signal is weak. Try a new mounting location for the System Access Module.
Aborting Test - There is no method to abort a radio test once it is started, other than to remove power.
The LEDs will maintain their state for 1 hour after the test. Pressing the Radio Test button momentarily will clear the LEDs. Pressing the Radio Test button again for five seconds will repeat the radio test. See Fig. 2 for a description of the radio test and LED sequence.
V. INSTALL COMPONENTS
INSTALL SYSTEM ACCESS MODULE — Once the radio test has passed, the System Access Module can be permanently installed. The System Access Module is designed so that wires can enter it from behind, above, or below. Plan wire routing before mounting.
1. Remove cover to access mounting holes.
2. Mount back plate to wall using screws and wall anchors provided.
3. Level back plate and tighten screws.
VI. CONNECT EVOLUTION SYSTEMS
CAUTION: UNIT OPERATION HAZARD
Failure to follow this caution may result in improper unit operation. Improper wiring of the ABC connector will cause the System Access Module to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on power.
Connect the A, B, and C wires from the Evolution System to terminals labeled A1, B1, and C1. Connect the second Evolution System (if present) to the terminals labeled A2, B2, and C2.
ABC bus wiring only requires a three wire connection; however, it is good practice to run thermostat cable greater than three wires in the event of a damaged or broken wire during the installation.
It is recommended that the following color code be used when wiring each ABC connector: A — Green Data A B — Yellow Data B C — White 24VAC (Com)
NOTE: The D-wire (red - 24 VAC hot) from the Evolution system is not connected to the System Access Module.
It is not mandatory that the above color code be used, but each ABC connector in the system MUST be wired consistently.
VII. CONNECT AUXILIARY SENSOR (OPTIONAL)
The System Access Module will support a dry contact sensor for use with water detection or some other use as seen fit. Connect one side of the contacts to connector AUXC (common) and the other side to connector AUX (input). The sensor input can provide up to 20mA at 5 volts d.c. If the sensor input is active, it will not shut down or affect operation of the HVAC system(s). A pop-up message will appear on the user interface indicating the auxiliary sensor is active. The home owner will also be notified via e-mail and/or phone if so chosen on the internet web interface.
VIII. SYSTEM START-UP
After a successful radio test has occurred, power may be applied to the Evolution System(s). The user interface of the Evolution System will automatically find the System Access Module at
—2—