ELECTRICAL RANGE —All units are single phase 208/230v.
COMPRESSOR —This unit features a scroll compressor,
which is significantly more efficient than conventional compressors. Its simple design offers improved reliability. Each
compressor is mounted on rubber isolators for additional
sound reduction. The scroll compressor starts under most
system loads, thus eliminating the need for start assistance
components. For improved serviceability, the 018 through
042 models are equipped with a compressor terminal plug.
Continuous operation is approved down to –30 ° F (–34.4 ° C)
in the heating mode and down to 55 ° F (12.8 ° C) in the cooling
mode. (See heating and cooling performance tables.) The
scroll compressor is covered with a standard 10-year limited
warranty.
BUILT-IN-RELIABLE COMPONENTS —All units include a suc-
tion tube accumulator that minimizes the amount of liquid refrigerant that reaches the compressor; a high-pressure
switch for high-pressure protection; and a low-pressure
switch for loss of charge protection.
DEFROST CONTROL BOARD —Incorporates a built-in 5-
minute compressor time-delay relay, defrost relay, defrost
timer, and low-voltage terminal board. The defrost control is a
time/temperature initiation/termination control, which includes
3 field-selectable time periods of 30, 50, and 90 minutes.
THERMOSTATIC EXPANSION VALVE (TXV) —This unit
must be installed with a TXV on the indoor coil. The FC4 and
FK4 indoor fan coils come factory equipped with a bi-flow
TXV. When installed in this application, no further change is
required. If any other indoor fan coil or furnace coil is used,
an accessory bi-flow TXV must be installed. See accessory
list in this publication for correct part no.
WEATHER-PROTECTIVE CABINET —Steel is galvanized and
coated with a layer of zinc phosphate. A coat of modified
polyester powder coating is then applied and baked-on, pro-
The
AeroQuiet System (AQS)
achieve ultra-low sound ratings.
Aerocoustic Design featuring the Aeromax opening and wire
dome top results in quieter and more efficient operation.
Energy-Efficient Fan and Fan Motor provide a slower fan oper-
ation, thus reducing noise and improving efficiency.
Sound Hood muffles noise from operation.
Discharge Muffler minimizes low frequency sound and pres-
sure pulsation generated by compressor discharge gas.
The 697C Outdoor Sections of Split-System Heat Pumps are
designed for quiet, reliable heating during the winter and
cooling during the summer. These heat pump systems provide economy of operation through energy conservation with
SEER up to 14.0 and HSPF up to 9.0. They recover heat for
indoor comfort from outdoor air during the heating season
and, by automatically reversing the refrigerant system, remove indoor heat and excess humidity during the cooling
season. All models are listed with UL, c-UL, ARI, and CEC.
consists of 4 design features to
viding each unit with a hard, smooth finish that will last for
many years.
All screws on cabinet exterior are coated for a long-lasting,
rust-resistant, quality appearance.
UNIT DESIGN —All units are equipped with totally enclosed
fan motors for greater reliability under rain and snow conditions. The large, wraparound coil uses copper tube and enhanced aluminum fin and is designed for optimum heat
transfer during heating and cooling. The vertical air discharge
carries the sound and air up and away from adjacent patio areas and foliage. Rows of composite coils can be cleaned with
a common garden hose.
EXTERNAL SERVICE VALVES —Both service valves are
brass, back seating type with sweat connections. Each valve
has a service port for ease of checking operating refrigerant
pressures. The suction service port provides for ease of
checking operating pressure in the heating mode.
LIMITED WARRANTY —Standard 1-year warranty on all
parts, with an additional 9-year warranty on compressor.
Form No. PDS 697C.18.3B
DIMENSIONS
A94148
B
ACCESS
DIA (22.22)
/8 IN.
7
DIA (34.92) KNOCKOUT
/8 IN.
1
DIA KNOCKOUT
/8 IN.
3
HOLE WITH 1
AND 1
FIELD POWER SUPPLY CONN
FIELD CONTROL
SUPPLY CONN
"
"
/16
/2
9
1
1
2
PANEL
A
DIA HOLE
DIA SUCTION
LINE CONN
H
/8 IN.
7
G
F
DIA LIQUID
/8 IN.
LINE CONN
3
"
/4
1
1
PAD DIMENSIONS
MINIMUM MOUNTING
M
"
/2
1
10
"
4
"
/4
3
1
N
C
AIR DISCHARGE
DIA (9.5) TIEDOWN KNOCKOUTS
/8 IN.
3
(2) PLACES IN BASEPAN
clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side,
and 24 in. between units for proper airflow.
Minimum outdoor operating ambient in cooling mode is 55°F (unless low ambient control is used) max 125°F.2.
Maximum outdoor operating ambient in heating mode is 66°F.3.
Series designation is the 14th position of the unit model number.4.
1. Allow 30 in.
Center of gravity .5.
AIR IN
L
K
D
E
L
C
"
/16
3
8
AIR IN
NOTES:
DIMENSIONS (IN.)
UNIT DIMENSIONS
ABCDEFGHKLMSupport FeetSnow Stand
018B33-13/1630335-1/169-11/1621-15/1628-3/85/816-13/1620-1/21426 x 3231 x 35
024B33-13/1630335-1/169-11/1621-15/1628-3/83/416-13/1620-1/21426 x 3231 x 35
030B33-13/1630335-1/169-11/1621-15/1628-3/83/416-1/220-3/81526 x 3231 x 35
036B39-13/1630335-1/169-11/1627-15/1634-3/87/816-1/220-3/81626 x 3231 x 35
SIZESERIES
UNIT
042B33-13/1630335-1/169-11/1621-15/1628-3/87/816-1/220-3/81526 x 3231 x 35
048A39-13/1630335-1/169-11/1627-15/1634-3/87/815-13/1619-7/81626 x 3231 x 35
060A39-13/1638-5/842-1/167-1/812-1/827-15/1634-3/87/819-7/82617-1/232 x 4236 x 46
AIR DISCHARGE
AIR IN
AIR DISCHARGE
—2—
RECOMMENDED TUBE DIAMETERS
UNIT
SIZE
018
024, 0303/4
036-0487/8
0601-1/8
* For tube set over 50 ft, consult Long-Line Application Guideline.
* TXV must be installed when indoor coil is not equipped with a TXV. TXV listed is for any approved
coil combination. All TXVs are bi-flow, hard shutoff.
OUTDOOR
PISTON
INDOOR
TXV*
T
O
D
E
A
I
R
F
I
I
T
A
R
S
E
C
R
E
R
U
T
C
N
A
U
F
U
N
A
M
A
R
C
O
M
H
P
E
A
Y
R
A
T
I
I
S
T
L
T
Y
P
I
U
N
M
G
P
W
I
T
H
®
E
T
Q
N
U
E
I
P
M
0
4
2
D
A
R
N
A
D
CERTIFICATION APPLIES ONLY WHEN THE
COMPLETE SYSTEM IS LISTED WITH ARI.
As an ENERGY STAR
Partner. Bryant has
determined that this
product meets the
ENERGY STAR guidelines
for energy efficiency.
SM
CERTIFICATION OF MANUFACTURING SITE.
—3—
°
°
° F/ °
° F/ °
°
° F/ °
SPECIFICATIONS
UNIT SIZE-SERIES
Operating Weight (Lb)198198221211231
ELECTRICAL
Unit Volts-Hertz-Phase208/230-60-1
Operating Voltage Range187—253
Unit Ampacity for Wire Sizing16.117.518.721.032.0
Min Wire Size (60
Maximum Length (60
Max. Branch Circuit Fuse Size (Amps)‡2525303050
Compressor Rated Load Amps12.513.614.216.024.9
Locked Rotor Amps47.061.072.588.0104.0
Fan Motor HP and RPM1/15 and 8201/15 and 8201/8 and 8201/8 and 8201/8 and 820
Full Load Amps1.01.01.01.01.0
COMPRESSOR AND REFRIGERANT
Compressor TypeScroll
Refrigerant—Type and Amount (Lb)†R-22 and 5.63R-22 and 8.88R-22 and 7.13R-22 and 10.88
OUTDOOR COIL AND FAN
Coil Face Area (Sq Ft)15.15
Rated Airflow (CFM)250024002900
Thermostat, Auto Changeover,
Non-Programmable,
Dual Fuel Thermostat. Must be used with
Outdoor Sensor (TSTATBBSEN01)TSTATBHPDF01-A†††
Outdoor SensorTSTATBBSEN01
See notes on page 5.
C/75 ° C Copper) (AWG)*14/1414/1414/1412/128/10
C/75 ° C) (Ft)**46/4444/4241/3960/5797/59
C,
C,
F,
C,
018-B024-B030-B036-B042-B
—4—
°
°
°
°
° F/ °
° F/ °
°
° F/ °
SPECIFICATIONS Continued
UNIT SIZE-SERIES
Operating Weight (Lb)265327
ELECTRICAL
Unit Volts-Hertz-Phase208/230-60-1
Operating Voltage Range187—253
Unit Ampacity for Wire Sizing34.045.0
Min Wire Size (60
Maximum Length (60
Max. Branch Circuit Fuse Size (Amps)‡5060
Compressor Rated Load Amps26.534.9
Locked Rotor Amps129.0169.0
Fan Motor HP and RPM1/8 and 8201/5 and 820
Full Load Amps1.01.4
COMPRESSOR AND REFRIGERANT
CompressorScroll
Refrigerant—Type and Amount (Lb)†R-22 and 11.88R-22 and 14.88
OUTDOOR COIL AND FAN
Coil Face Area (Sq Ft)18.1824.89
Rated Airflow (CFM)29003600
Thermostat, Auto Changeover,
Non-Programmable,
Dual Fuel Thermostat. Must be used with
Outdoor Sensor (TSTATBBSEN01)TSTATBHPDF01-A†††
Outdoor SensorTSTATBBSEN01
* If wire is applied at ambient greater than 30 ° C (86 ° F), consult Table 310-16 of the NEC (ANSI/NFPA 70). If other than uncoated (non-plated), 60 ° or 75 ° C
or 167 ° F) insulation, copper wire (solid wire for 10 A WG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tab les of the
(140
NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60
(ANSI/NFPA 70) Article 336-30.
† The factory refrigerant charge is for 15 ft of interconnecting tubing. For tubing lengths other than 15 ft, see Long-Line Application Guideline for additional
refrigerant requirements.
‡ Time-delay fuse or HACR breaker.
** Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
†† For indicator light function, thermostat specified must be used and wired according to efficiency service alarm Installation Instructions.
‡‡ Used with low-ambient controller.
*** Fan motor with ball bearings required.
††† High-pressure switch must be added if not supplied with the system.
‡‡‡ Outdoor thermostat required.
N/A—Not Applicable
C/75 ° C Copper) (AWG)*8/106/8
C/75 ° C) (Ft)**91/56116/66
C,
C,
F,
C,
048-A060-A
C (140 ° F) conductors, per the NEC
—5—
°
°
°
°
°
°
°
ACCESSORY USAGE GUIDELINE
REQUIRED FOR
LOW-AMBIENT
ACCESSORY
APPLICATIONS
(Below 55 ° F)
Crankcase HeaterYesYesYesNo
Evaporator Freeze ThermostatYesNoNoNo
Winter Start ControlYes‡NoNoNo
AccumulatorNoNoYesNo
Compressor Start Assist
Capacitor and RelayYesYesYes No
Low Ambient Controller
MotorMaster® ControlYesNoNoNo
or
Wind Baffle
See Low-Ambient
Instructions
Coastal FilterNoNoNoYes
Support FeetRecommendedNoNoRecommended
Liquid-Line Solenoid Valve
or
Hard Shutoff TXVNo
Ball Bearing Fan MotorYesNoNoNo
* For tubing line sets between 50 and 175 ft, refer to Residential’s Split System Long-Line Application Guidelines.
† For buried line applications, refer to Residential’s Split Systems Buried Line Application Guidelines.
‡ Only when low-pressure switch is used.
REQUIRED FOR
LONG-LINE
APPLICATIONS*
(Over 50 Ft)
REQUIRED FOR
BURIED LINE
APPLICATIONS†
(Over 3 Ft)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 Miles)
NoNoNo
See
Long-Line
Application GuidelineYesNo
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where low-ambient controller (full modulation feature) or MotorMaster® Control has been added.
2. Compressor Start Assist-Capacitor/Relay Type
Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft. Installations where outdoor design temperature exceeds 105
3. Compressor Start Assist-PTC Type
Solid-state electrical device which gives a “soft” boost to the compressor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on
restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
5. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: With low-ambient controller.
6. Filter Drier—Bi-flow
A device for removing contaminants from refrigerant circulating in a heat pump system; 2-direction flow for heat pumps.
SUGGESTED USE: Split-system heat pumps.
7. Interface Control
An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predetermined economic balance point temperature, then switches to allow furnace operation only below that temperature. Requires outdoor thermostat (Item 12) to
be adjusted for economic balance point temperature.
SUGGESTED USE: For heat pump and gas- or oil-fired furnace combination systems.
8. Isolation Relay
An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.
SUGGESTED USE: All heat pumps where low-ambient controller has been added.
9. Liquid Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation.
Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
SUGGESTED USE: In certain long-line applications. (Refer to Long-Line Application Guideline.)
10. Low-Ambient Controller
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the
outdoor fan motors in order to maintain condensing temperature within normal operating limits (approximately 130 to 110
will maintain working head pressure at low-ambient temperatures down to 0
SUGGESTED USE: Cooling operation at outdoor temperatures below 55
11. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to –20
SUGGESTED USE: Cooling operation at outdoor temperatures below 55
12. Outdoor Thermostat
An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.
SUGGESTED USE: Heat pump installations with multiple-stage supplemental heaters.
Replacement installations with hard shutoff expansion valve on indoor coil. Units installed with low-ambient controller. Units installed with liquid
solenoid valve.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
When unit will be operated below 55
All commercial installations.
F (12.8 ° C) outdoor air temperature. (Use with low-ambient controller.)
F high, 70 to 50 ° F low). The control
F when properly installed.
F (12.8 ° C).
F, it maintains condensing temperature at 100 ° F ± 10 ° F.
F.
F (40.6 ° C).
—6—
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued
13. Secondary Outdoor Thermostat
An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the secondstage set point.
SUGGESTED USE: Heat pump installations where 3-stage operation of supplemental heaters is desired.
14. Service Alarm
A current-sensing lockout relay which provides immediate notification that compressor is not operating during a call for heating or cooling. Used with proper
room thermostat, the thermostat light is turned on signifying service is required. This can minimize electrical cost increase due to operation of supplemental
heaters only.
SUGGESTED USE: As a feature to notify owner immediately when the system is not operating most efficiently.
15. Snow Stand
Coated wire rack which supports unit 18 in. above mounting pad to allow for drainage from unit base.
SUGGESTED USE: Heat pump installations in heavy snowfall areas.
16. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces unit sound level by about 2 dBA.
SUGGESTED USE: Unit installed closer than 15 ft to quiet areas—bedrooms, etc.
17. Support Feet
Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes
corrosion.
SUGGESTED USE: Coastal installations.
18. Thermostatic Expansion Valve (TXV)—Bi-flow
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube.
SUGGESTED USE: Required for improved system performance. (Refer to ARI Unitary Directory.)
19. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)
Heat pump installations in snowdrift locations.
Heat pump installations in areas of prolonged subfreezing temperatures.
All commercial installations.
Unit installed between 2 houses less than 10 ft apart.
Windy areas or where debris is normally circulating.
Rooftop installations.