Bryant Series J Installation, Start-up, And Operating Instructions Manual

Page 1
installation, start-up, and operating instructions
4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE
A93040
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue. Index Page
DIMENSIONAL DRAWING........................................................3
SAFETY CONSIDERATIONS..................................................1-2
Clearances to Combustibles......................................................4
CODES AND STANDARDS ....................................................4-5
INTRODUCTION..........................................................................6
APPLICATIONS ......................................................................6-12
General......................................................................................6
Upflow Applications..............................................................6-8
Downflow Applications.........................................................8-9
Horizontal Left (Supply-Air Discharge) Applications ..........10
Horizontal Right (Supply-Air Discharge) Applications...10-12
LOCATION ............................................................................12-14
General...............................................................................12-13
Furnace Location Relative to Cooling Equipment................13
Hazardous Locations...............................................................14
INSTALLATION.........................................................................14
Leveling Legs (If Desired).....................................................14
Installation In Upflow or Downflow Applications................14
Installation In Horizontal Applications..................................14
AIR DUCTS............................................................................14-19
General Requirements .......................................................14-16
Ductwork Acoustical Treatment .......................................16-17
Supply Air Connections..........................................................17
Return Air Connections..........................................................17
Filter Arrangement..................................................................17
Bottom Closure Panel.............................................................18
Gas Piping..........................................................................18-19
ELECTRICAL CONNECTIONS...........................................19-22
115-v Wiring...........................................................................20
24-v Wiring.............................................................................20
Wiring Diagram......................................................................21
Accessories ........................................................................20-22
DIRECT VENTING ...............................................................22-34
Removal of Existing Furnaces from
Common Vent Systems.....................................................22
Combustion-Air and Vent Piping .....................................22-30
Concentric Vent and Combustion-Air Termination
Kit Installation..............................................................30-31
Multiventing and Vent Termination .................................31-34
CONDENSATE DRAIN..............................................................34
General....................................................................................34
340MAV
Series J
Cancels: II 340M-40-10 II 340M-40-11
10-03
Application..............................................................................34
Condensate Drain Protection..................................................34
SEQUENCE OF OPERATION..............................................35-36
Heating Mode...............................................................................35
Cooling Mode...............................................................................35
Continuous Blower Mode............................................................35
Heat Pump Mode....................................................................35-36
Component Test ...........................................................................36
START-UP PROCEDURES ..................................................36-44
General....................................................................................36
Prime Condensate Trap With Water......................................36
Purge Gas Lines......................................................................36
Adjustments .......................................................................36-44
Set Gas Input Rate ............................................................36-44
Set Temperature Rise..............................................................44
Blower Off Delay (Heat Mode).............................................44
Set Thermostat Heat Anticipator............................................44
CHECK SAFETY CONTROLS ............................................44-45
Check Primary Limit Control.................................................45
Check Pressure Switch ...........................................................45
CHECKLIST................................................................................45
ama
As an ENERGY STAR® Partner, Bryant Heating & Cooling Systems Com­pany has determined that this product meets the EN­ERGY STAR® guidelines for energy efficiency.
CAUTION: Application of this furnace should be in­doors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing. Improper installation or misapplication of furnace can require excessive servicing or cause prema­ture component failure.
REGISTERED QUALITY SYSTEM
SAFETY CONSIDERATIONS
CERTIFIED
—1—
Page 2
AIRFLOW
UPFLOW
HORIZONTAL
RIGHT
AIRFLOW
A93041
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
AIRFLOW
Fig. 1—Multipoise Orientations
WARNING: Improper installation, adjustment, alter-
ation, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as clean­ing and replacing air filters. All other operations must be per­formed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.
These instructions cover the minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.
CAUTION: Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts. Failure to follow this caution could result in personal injury.
Understand these signal words DANGER, WARNING, CAU­TION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
The 340MAV Multipoise Condensing Gas-Fired Furnaces are CSA (formerly AGA and CGA) design-certified for natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. A CSA (formerly AGA and CGA) listed gas conversion kit is required to convert furnace for use with propane gas.
See Fig. 3 for required clearances to combustibles. Maintain a 1-in. clearance from combustible materials to supply air
ductwork for a distance of 36 inches horizontally from the furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used.
The 340MAV 040 through 120 size units are CSA (formerly AGA and CGA) design-certified for use in manufactured (mobile) homes when factory accessory conversion kit is used. The 140 size unit is NOT design-certified for use in manufactured (mobile) homes. These furnaces are suitable for installation in a structure built on site or a manufactured building completed at final site. The design of this furnace line is NOT CSA (formerly AGA and CGA) design-certified for installation in recreation vehicles or outdoors.
This furnace is designed for continuous return-air minimum temperature of 60°F db or intermittent operation down to 55°F db such as when used with a night setback thermostat. Return-air temperature must not exceed 85°F db. Failure to follow these return-air limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 4.)
These furnaces are shipped with the drain and pressure tubes connected for UPFLOW applications. Minor modifications are required when used in DOWNFLOW, HORIZONTAL RIGHT, or HORIZONTAL LEFT (supply-air discharge direction) applica­tions as shown in Fig. 1. See details in Applications section.
This furnace must be installed with a direct-vent (combustion air and flue gas) system and a factory accessory termination kit. In a direct-vent system, all air for combustion is taken directly from the outdoor atmosphere and flue gases are discharged to the outdoor atmosphere. See furnace and factory accessory termination kit instructions for proper installation.
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
—2—
Page 3
A02147
"
8
"
16
"
16
13
5
"
8
5
7
39
1"
"
"
16
16
7
11
"
16
5
19"
"
22
4
1
"
16
15
"
2
26
1
28
AIRFLOW
OUTLET
26
A
2-IN. COMBUSTION-
"
16
9
TYP
TRAP LOCATION
"
16
/
CONDENSATE DRAIN
13
D
OUTLET
"
16
/
13
2-IN. DIA
1
GAS CONN
AIR CONN
(DOWNFLOW &
OR ALTERNATE
-IN. DIA GAS CONN
2
1
HORIZONTAL RIGHT)
8-IN. DIA
POWER CONN
7
"
4
1
TYP
33
2-IN. DIA
THERMOSTAT ENTRY
1
"
8
5
TYP
32
"
16
13
30
"
2
1
30
2-IN. VENT CONN
"
16
11
29
TYP
5
"
16
11
22
SIDE INLET
"
4
1
18
1
" TYP
4
22
"
16
3
24
(UPFLOW)
BOTTOM INLET
HANGING
CONDENSATE
DRAIN LOCATION
FOR HORIZONTAL
DIMPLE LOCATORS
"
16
/
11
INLET
E
"
16
/
11
-in. rectangle.
-in. rectangle.
2
4
/
/
1
1
x 19
x 23
2
2
/
/
x 12-in. rectangle.
1
1
2
/
1
DIMENSIONS (IN.)
Fig. 2—Dimensional Drawing
"
8
27
"
16
9
TYP
"
27
2
1
24
"
16
5
17
see flex duct manufacturer’s recommendations for equivalent diameters.
2. Minimum return-air opening at furnace:
literature for specific use of single side inlets. The use of both side inlets, a
c. For 1600 CFM–22-in. round or 14
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
b. For 1200 CFM–20-in. round or 14
a. For 800 CFM–16-in. round or 14
combination of 1 side and the bottom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM at 0.5” W.C. ESP.
8-IN. DIA
POWER CONN
7
CONDENSATE
CONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL LEFT)
"
16
"
15
4
1
"
26
2
1
26
"
16
24
5
22
2-IN. COMBUSTION-
AIR CONN
2-IN. DIA
1
GAS CONN
2-IN. VENT CONN
ENTRY
2-IN. DIA THERMOSTAT
1
7
11
8-IN. DIA
"
16
22
ACCESSORY
POWER ENTRY
DRAIN TRAP
LOCATION
(ALTERNATE
UPFLOW)
SIDE INLET
"
2
1
TYP
14
"
16
7
TYP
CONDENSATE
DRAIN LOCATION
1
"
4
1
1
(UPFLOW)
" TYP
" TYP
16
4
15
23
SIDE INLET
26
1"
9
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
024040 17-1/2 15-7/8 16
036040 17-1/2 15-7/8 16
024060 17-1/2 15-7/8 16
036060 17-1/2 15-7/8 16
048060 17-1/2 15-7/8 16
036080 17-1/2 15-7/8 16
048080 17-1/2 15-7/8 16
060080 21 19-3/8 19-1/2
048100 21 19-3/8 19-1/2
060100 21 19-3/8 19-1/2
060120 24-1/2 22-7/8 23
UNIT SIZE A D E
060140 24-1/2 22-7/8 23
—3—
Page 4
These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.
Installer Packet includes:
Installation, Startup, and Operating Instructions Service and Maintenance Instructions User’s Information Manual Warranty Certificate
Loose Parts Bag includes: Quantity
Pressure tube extension 1 Collector Box or condensate trap extension tube 1 Inducer housing drain tube 1 1/2-in CPVC street elbow 2 Drain tube coupling 1 Drain tube coupling grommet 1 Vent and combustion-air pipe support 2 Condensate trap hole filler plug 3 Vent and combustion-air intake hole filler plug 2 Combustion-air pipe perforated disk assembly 1
Vent Pipe Extension 1*
* ONLY supplied with some furnaces.
For accessory installation details, refer to accessory installation instructions.
CODES AND STANDARDS
Follow all national and local codes and standards inadditionto these instructions. The installation must comply with regulations
of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
I. SAFETY
• US: National Fuel Gas Code (NFGC) NFPA 54-2002/ANSI Z223.1-2002 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
• CANADA: National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC) CSA B149.1-00.
II. GENERAL INSTALLATION
• US: NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada
III. COMBUSTION AND VENTILATION AIR
• US: Section 8.3 of the NFGC, Air for Combustion and Ventilation
• CANADA: Part 7 of the NSCNGPIC, Venting Systems and Air Supply for Appliances
IV. DUCT SYSTEMS
• US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Con­tractors National Association (SMACNA), or American Soci­ety of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34.
V. ACOUSTICAL LINING AND FIBROUS GLASS DUCT
• US and CANADA: current edition of SMACNA, NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
VI. GAS PIPING AND GAS PIPE PRESSURE TESTING
• US: NFGC; chapters 5, 6, 7, and 12 and national plumbing codes
• CANADA: NSCNGPIC Parts 3, 4, 5, A, B, E, and H.
This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 ft. (0 - 2,135m). An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications. This furnace is for indoor installation in a building constructed on site. This furnace ma y be installed in a manufactured (mobile) home when stated on rating plate and using factory authorized kit. This furnace may be installed on comb ustible flooring in alcove or closet at This furnac e req uires a s pe cial ve nting sy ste m . Refe r to the installation in struc tions for parts list and m e thod of installatio n. This furnace is for use with schedule-40 PVC, PVC-DWV, CPVC , or ABS-DWV pipe, and must not be vented in common with other gas-fired appliances. Construction through w hich vent/air intake pipes may be installed is maximum 24 inches (600 mm), minimum 3/4 inches (19 mm) thickness (including roofing materials).
For upflow and downflow applications, furnace must be installed level, or pitched within 1/2" of level. For a horizontal application, the furnace must be pitched minimum 1/4" to maximum of 1/2" forward for proper drainage. See Installation Manual for IMPO R TANT unit support details on horizontal applications.
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
ALL POSITIONS:
Minimum front clearance for service 30 inches (762mm).
*
140 size furnaces require 1 inch back clearance to combustible materials.
DOWNFLOW POSITIONS:
For installation on combustible floors only when installed on special base No. KGASB0201ALL, Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
HORIZONTAL POSITIONS:
Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket, and b uilding joists, studs, or framing. Clearance shown is for air inlet and air outlet ends.
§
120 and 140 size furnaces require 1 inch bottom clearance to combustible materials.
Ø
INST ALLATION
Minimum Inches Clearance To Combustible Construction
LEVEL (0")
1/2" MAX
UPFLOW OR DOWNFLO W
This furnace is approved for UPFLOW, DOWNFLOW and HORIZONTAL installations.
Clearance arrows do not change with furnace orientation.
0"
B
A
C
K
I
S
0"
§
328066-201 REV. A LIT -TO P
Clearance in inches.
TO
E
D
as described below.
MIN 1/4" TO 1/2" MAX
FRONT
1"
TOP/PLENUM
E
C
A
N
R
U
F
N
O
R
F
F
R
O
N
BOTTOM
0"
Ø
FRONT
HORIZONTAL
I
S
T
S
E
R
T
3"
Vent clearance to combustibles 0".
D
§
0"
E
V
I
C
E
*
30
MIN
A02248
Fig. 3—Clearances to Combustibles
—4—
Page 5
BLOWER SHELF
CONDENSATE TRAP (INSIDE)
ALTERNATE DRAIN TUBE LOCATION
CONDENSATE TRAP
DRAIN TUBE LOCATION
UPFLOW APPLICATIONS
FURNACE DOOR
FIELD
DRAIN
CONN
EXTERNAL UPFLOW APPLICATIONS
SLOT FOR SCREW
HORIZONTAL
APPLICATION
(OPTIONAL)
1
1
2
3
4
WIRE TIE GUIDES (WHEN USED)
CONDENSATE TRAP
FURNACE
SIDE
7
4
8
1
26
4
1
1
2
FURNACE DOOR
FIELD
DRAIN
CONN
FURNACE SIDE
4
3
5
4
4
1
26
4
3
5
3
4
SIDE VIEW FRONT VIEW END VIEW FRONT VIEW
DOWNFLOW AND ALTERNATE
1
7
8
3
1
4
7
8
1
2
4
1
4 OD COLLECTOR BOX TO TRAP RELIEF PORT
1
2 OD INDUCER HOUSING DRAIN CONNECTION
5
8 OD COLLECTOR BOX DRAIN CONNECTION
SCREW HOLE FOR UPFLOW OR DOWN­FLOW APPLICATIONS (OPTIONAL)
1
2-IN. PVC OR CPVC
HORIZONTAL
APPLICATIONS
4
FRONT VIEW SIDE VIEW
Fig. 5—Condensate Trap
VII. ELECTRICAL CONNECTIONS
• US: National Electrical Code (NEC) ANSI/NFPA 70-2002
• CANADA: Canadian Electrical Code CSA C22.1
A94163
Fig. 4—Return-Air Temperature
A93026
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electro­static potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
—5—
Page 6
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FACTORY-SUPPLIED
1
2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
FIELD-INSTALLED
FACTORY-SUPPLIED
COUPLING (RIGHT
DRAIN OPTION)
CONDENSATE TRAP
DRAIN TUBE
Fig. 6—Factory-Shipped Upflow Tube Configuration
(Shown With Blower Access Panel Removed)
A00288
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (BLUE)
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
Fig. 7—Alternate Upflow Tube Configuration and
Trap Location
A00289
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
INTRODUCTION
The model 340MAV 4-way multipoise, Gas-Fired, Category IV, direct-vent condensing furnace is available in model sizes ranging in input capacities of 40,000 to 138,000 Btuh.
—6—
APPLICATIONS
CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling. Failure to follow this caution will result in minor property damage.
I. GENERAL
Some assembly and modifications are required for furnaces installed in any of the 4 applications shown in Fig. 1. All drain and pressure tubes are connected as shown in Fig. 6. See appropriate application instructions for these procedures.
II. UPFLOW APPLICATIONS
An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned air is discharged upwards.
A. Condensate Trap Location (Factory-Shipped Orientation)
The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications. A factory-supplied tube is used to extend the condensate trap drain connection to the
Page 7
desired furnace side for field drain attachment. See Condensate Trap Tubing (Factory-Shipped Orientation) section for drain tube extension details. (See Fig. 5.)
B. Condensate Trap Tubing (Factory-Shipped Orientation)
NOTE: See Fig. 6 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port,
and Pressure Switch Tubes These tubes should be factory attached to condensate trap
and pressure switch ready for use in UPFLOW applications. These tubes can be identified by their connection location and also by a color label on each tube. These tubes are identified as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label).
2. Condensate Trap Drain Tube
The condensate trap drain connection must be extended for field attachment by doing the following:
a. Determine location of field drain connection. (See Fig. 2
or 6.)
NOTE: If internal filter is used, drain tube should be located to opposite side of casing from return duct attachment to assist in filter removal.
b. Remove and discard casing drain hole plug button from
desired side.
c. Install drain tube coupling grommet (factory-supplied in
loose parts bag) in selected casing hole.
d. Slide drain tube coupling (factory-supplied in loose parts
bag) through grommet ensuring long end of coupling faces blower.
e. Cement 2 factory-supplied 1/2-in. street CPVC elbows to
the rigid drain tube connection on the condensate trap. (See Fig. 6.) These elbows must be cemented together and cemented to condensate trap drain connection.
NOTE: Failure to use CPVC elbows may allow drain to kink and prevent draining.
f. Connect larger diameter drain tube and clamp (factory-
supplied in loose parts bag) to condensate trap and clamp
securely. g. Route tube to coupling and cut to appropriate length. h. Attach tube to coupling and clamp securely.
C. Condensate Trap Location (Alternate Upflow Orientation)
An alternate location for the condensate trap is the left-hand side of casing. (See Fig. 2 and 7.)
NOTE: If the alternate left-hand side of casing location is used, the factory-connected drain and relief port tubes must be discon­nected and modified for attachment. See Condensate Trap Tubing (Alternate Upflow Orientation) section for tubing attachment.
To relocate condensate trap to the left-hand side, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING: Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated. Failure to follow this warning could result in electrical shock, fire, personal injury or death.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
D. Condensate Trap Tubing (Alternate Upflow Orientation)
NOTE: See Fig. 7 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain Tube Connect collector box drain tube (blue label) to condensate
trap.
NOTE: On 17-1/2-in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks from occurring.
2. Inducer Housing Drain Tube a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to conden­sate trap.
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the con-
densate trap. c. Determine appropriate length, cut, and connect tube. d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Connect relief port tube (green label) to condensate trap. b. Extend this tube (if required) by splicing to small
diameter tube (factory-supplied in loose parts bag).
c. Determine appropriate length, cut, and connect tube.
E. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
F. Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door to check for proper connections.
G. Upper Collector Box and Inducer Housing (Unused) Drain Connections
UPPER COLLECTOR BOX DRAIN CONNECTION
Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door to check for proper connections.
UPPER INDUCER HOUSING DRAIN CONNECTION
Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door to check for proper connections.
—7—
Page 8
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX EXTENSION TUBE
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
A00262
Fig. 8—Downflow Tube Configuration
(Left-Hand Trap Installation)
H. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommenda­tions and procedures.
III. DOWNFLOW APPLICATIONS
A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2, 8, or 9.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING: Casing hole filler cap must be installed in blower shelf when condensate trap is relocated. Failure to follow this warning could result in electrical shock, fire, personal injury or death.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
B. Condensate Trap Tubing NOTE: See Fig. 8 or 9 or tube routing label on main furnace door
to check for proper connections.
PLUG CAP
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
COLLECTOR BOX EXTENSION TUBE
INDUCER HOUSING DRAIN TUBE (VIOLET)
CONDENSATE TRAP
COLLECTOR BOX EXTENSION
DRAIN TUBE COUPLING
DRAIN TUBE
Fig. 9—Downflow Tube Configuration
(Right-Hand Trap Installation)
1. Collector Box Drain Tube a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to condensate trap.
c. Connect LOWER collector box drain connection to
condensate trap. (1.) Condensate Trap Located on Left Side of Casing
(a.) Connect LOWER collector box drain tube
(blue and white striped label) to condensate trap. Tube does not need to be cut.
(b.) Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
(a.) Install drain tube coupling (factory-supplied in
loose parts bag) into collector box drain tube (blue and white striped label) which was pre­viously plugged.
(b.) Connect larger diameter drain tube (factory-
supplied in loose parts bag) to drain tube coupling, extending collector box drain tube for connection to condensate trap.
(c.) Route extended collector box drain tube di-
rectly from collector box drain to condensate
trap as shown in Fig. 9. (d.) Determine appropriate length and cut. (e.) Connect to condensate trap. (f.) Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
A00296
—8—
Page 9
AUXILIARY "J" BOX
PLUG
CAP
COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED)
CONDENSATE
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
TRAP
COLLECTOR
BOX EXTENSION
DRAIN TUBE
040, 060, AND 080 HEATING INPUT FURNACES
Fig. 10—Horizontal Left Tube Configuration
a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to conden­sate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and factory-
supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.
e. Connect inducer housing drain connection to condensate
trap. (1.) Condensate Trap Located on Left Side of Casing
(a.) Determine appropriate length and cut. (b.) Connect tube to condensate trap. (c.) Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
(a.) Route inducer housing drain tube (violet label)
directly from inducer housing to condensate
trap as shown in Fig. 9. (b.) Determine appropriate length and cut. (c.) Connect tube to condensate trap. (d.) Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection
procedure.
C. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
COLLECTOR BOX
EXTENSION TUBE
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
D. Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
NOTE: See Fig. 8 or 9 or tube routing label on main furnace door to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connec­tion by splicing to small diameter tube (factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to pres­sure switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was previously connected to pressure switch by splicing to remaining small diameter tube (factory-supplied in loose parts bag).
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
E. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommenda­tions and procedures.
COLLECTOR BOX TUBE (GREEN)
INDUCER HOUSING DRAIN TUBE (VIOLET)
COLLECTOR BOX DRAIN TUBE (BLUE)
A00215
—9—
Page 10
IV. HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE) APPLICATIONS
A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.
NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 10.) See Electrical Connection section for J-Box relocation.
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 10.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING: Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated. Failure to follow this warning could result in electrical shock, fire, personal injury or death.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
B. Condensate Trap Tubing NOTE: See Fig. 10 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube a. Install drain tube coupling (factory-supplied in loose
parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.
b. Connect large diameter drain tube and clamp (factory-
supplied in loose parts bag) to drain tube coupling, extending collector box drain tube.
c. Route extended tube (blue label) to condensate trap and
cut to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to conden­sate trap.
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the con-
densate trap. c. Determine appropriate length, cut, and connect tube. d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Extend collector box tube (green label) which was
previously connected to the condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag).
b. Route extended collector box pressure tube to relief port
connection on the condensate trap.
c. Determine appropriate length, cut, and connect tube. d. Clamp tube to prevent any condensate leakage.
C. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
D. Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended, rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications.
NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections.
Modify tube as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1.
3. Route extended tube: a. Behind inducer housing.
b. Between blower shelf and inducer housing. c. Behind inducer motor bracket. d. Between inducer motor and pressure switch.
4. Determine appropriate length, cut, and reconnect tube to pressure switch connection labeled COLLECTOR BOX.
E. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommenda­tions and procedures.
F. Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 11.)
CAUTION: The condensate trap MUST be installed below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain. Failure to follow this caution will result in intermittent unit operation.
NOTE: Combustion-air and vent pipes are restricted to a mini­mum length of 5 ft. (See Table 7.)
NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 11 or 34.)
V. HORIZONTAL RIGHT (SUPPLY-AIR DISCHARGE) APPLICATIONS
A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.
CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in attic application or over a finished ceiling. Failure to follow this caution will result in minor property damage.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC Installation Codes and/or local codes. NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 12.) See Electrical Connection section for J-Box relocation.
—10—
Page 11
MANUAL
SHUTOFF
GAS VALVE
COMBUSTION – AIR
SEDIMENT TRAP
INTAKE
3
5
⁄4″
CONDENSATE TRAP
VENT
30 MIN WORK AREA
DRAIN
A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
ACCESS OPENING FOR TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
Fig. 11—Attic Location and Working Platform
CAP
PLUG
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
A93031
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX TUBE (PINK)
AUXILARY “J” BOX RELOCATED HERE
CONDENSATE TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
A00214
Fig. 12—Horizontal Right Tube Configuration
—11—
Page 12
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 12.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING: Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated. Failure to follow this warning could result in electrical shock, fire, personal injury or death.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
B. Condensate Trap Tubing NOTE: See Fig. 12 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was previously con­nected to condensate trap.
c. Connect LOWER collector box drain tube (blue and
white striped label) to condensate trap. Tube does not need to be cut.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to conden­sate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to conden­sate trap.
e. Determine appropriate length, cut, and connect tube to
condensate trap.
f. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection
procedure.
C. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
D. Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the
condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
NOTE: See Fig. 12 or tube routing label on main furnace door to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connec­tion by splicing to small diameter tube (factory-supplied in loose parts bag).
3. Route extended collector box pressure tube behind inducer motor bracket then between inducer motor and pressure switch.
4. Connect collector box pressure tube (green label) to pres­sure switch connection labeled COLLECTOR BOX.
5. Use remaining smaller diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (pink label) which was previously connected to pressure switch.
6. Route this extended tube (pink label) to condensate trap relief port connection.
7. Determine appropriate length, cut, and connect tube.
8. Clamp tube to relief port connection.
E. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommenda­tions and procedures.
F. Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 11.)
CAUTION: The condensate trap MUST be installed below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain. Failure to follow this caution will result in intermittent unit operation.
NOTE: Combustion-air and vent pipes are restricted to a mini­mum length of 5 ft. (See Table 7.)
NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 11 or 34.)
LOCATION
I. GENERAL
This furnace must
• be installed so the electrical components are protected from water.
• not be installed directly on any combustible material other than wood flooring (refer to SAFETY CONSIDERATIONS).
• be located so combustion-air and vent pipe maximum lengths are not exceeded. Refer to Table 7.
• be located where available electric power and gas supplies meet specifications on the furnace rating plate.
• be attached to an air distribution system and be located as close to the center of the distribution system as possible. Refer to Air Ducts section.
• be provided with ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown on the furnace clearance to combustible label.
—12—
Page 13
NOTE: For upflow/downflow applications install furnace so that it is level or pitched forward within 1/2-in. for proper furnace operation. For horizontal applications pitch 1/4-in. minimum to 1/2-in. maximum forward to ensure proper condensate drainage from secondary heat exchangers. (See Fig. 13.)
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to furnace casing and terminating outside the space containing the furnace to ensure there will not be a negative pressure condition within
LEVEL (0)
TO
1
2 MAX
UPFLOW OR DOWNFLOW HORIZONTAL
FRONT
MIN
TO
1
2 MAX
1
4
FRONT
equipment room or space. This furnace may be located in a confined space without special
provisions for dilution or ventilation air.
Fig. 13—Furnace Location for Proper Condensate
Drainage
CAUTION: This gas furnace may be used for construction heat provided that:
-The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
-The furnace is controlled by a thermostat. It may not be hot wiredto provide heat continuously to the structure without thermostatic control.
-Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is no less than 55°F, with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed ot thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
A02146
FRONT
B A C K
BACK
FRONT
A93043
Fig. 14—Prohibit Installation on Back
WARNING: Do not install furnace on its back. Safety
control operation will be adversely affected. Never con­nect return-air ducts to back of furnace. Failure to follow this warning could result in fire, personal injury, or death. (See Fig. 14.)
CAUTION: If these furnaces are installed in an uncon­ditioned space where the ambient temperatures may be 32°F or lower, freeze protection measures must be taken. Failure to follow this caution will result in minor property or unit damage. (See Fig. 15.)
32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
A93058
Fig. 15—Freeze Protection
II. FURNACE LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to control flow of air shall prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless damper is in full-heat or full-cool position.
—13—
Page 14
III. HAZARDOUS LOCATIONS
18-IN. MINIMUM
TO BURNERS
Fig. 16—Installation in a Garage
WARNING: When furnace is installed in a residential
garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accor­dance with NFGC or NSCNGPIC. (See Fig. 16.)
A93044
2. For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section.
II. INSTALLATION IN UPFLOW OR DOWNFLOW APPLICATIONS
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when special base (available from manufacturer) Part No. KGASB0201ALL is used. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or Coil Box Part No. KCAKC is used.
1. Determine application being installed from Table 1.
2. Construct hole in floor per dimensions specified in Table 1 and Fig. 18.
3. Construct plenum to dimensions specified in Table 1 and Fig. 18.
4. If downflow subbase (KGASB) is used, install as shown in Fig. 19. If coil assembly CD5 or CK5 or Coil Box KCAKC is used, install as shown in Fig. 20.
NOTE: Remove furnace perforated, discharge duct flanges when they interfere with mating flanges on coil on downflow subbase. To remove furnace perforated, discharge duct flange, use wide duct pliers or duct flange tool to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 21.)
INSTALLATION
I. LEVELING LEGS (IF DESIRED)
When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 17.) Install field-supplied, corrosion-resistant 5/16-in. machine bolts and nuts.
5
16
5
16
1 3⁄4
3
4
1
5
16
5
16
1 3⁄4
1 3⁄4
A89014
Fig. 17—Leveling Legs
NOTE: The maximum length of bolt should not exceed 1-1/2 in.
1. Position furnace on its back. Locate and drill a 5/16-in. diameter hole in each bottom corner of furnace. (See Fig.
12.) Holes in bottom closure panel may be used as guide locations.
WARNING: Do not bend duct flanges inward as shown in Fig. 21. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210° as shown in Fig. 21.
NOTE: For 140 size unit when installed in downflow orientation, cut the white jumper wire off between terminals PL1-7 and PL1-9. Do not cut white jumper between terminals PL1-7 and PLI-11. Refer to Fig. 30 for location of jumper. Cut jumper close to connector and remove wire to avoid a short circuit.
III. INSTALLATION IN HORIZONTAL APPLICATIONS
CAUTION: The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf area. Failure to follow this caution will result in intermittent unit operation or per­formance satisfaction.
These furnaces can be installed horizontally in either horizontal left or right discharge position. In a crawlspace, furnace can either be hung from floor joist or installed on suitable blocks or pad. Furnace can be suspended from each corner by hanger bolts and angle iron supports. (See Fig. 22.) Cut hanger bolts (4 each 3/8-in. all-thread rod) to desired length. Use 1 X 3/8-in. flat washers, 3/8-in. lockwashers, and 3/8-in. nuts on hanger rods as shown in Fig. 22. Dimples are provided for hole locations. (See Fig. 2.)
AIR DUCTS
I. GENERAL REQUIREMENTS
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and
—14—
Page 15
A
PLENUM
OPENING
B
C
FLOOR
OPENING
D
A96283
Fig. 18—Floor and Plenum Opening Dimensions
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Fig. 19—Furnace, Plenum, and Subbase
Installed on a Combustible Floor
FURNACE
CASING
WIDTH
Upflow Applications 16 24-1/8 16-5/8 24-3/4
Downflow Applications on Non-Combustible Flooring 15-7/8 19 16-1/2 19-5/8
17-1/2
21
24-1/2
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
Upflow Applications 19-1/2 24-1/8 20-1/8 24-3/4
Downflow Applications on Non-Combustible Flooring 19-3/8 19 20 19-5/8
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
Upflow Applications 23 24-1/8 23-5/8 24-3/4
Downflow Applications on Non-Combustible Flooring 22-7/8 19 23-1/2 19-5/8
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5 or CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5 or CK5 Coil Assembly or KCAKC Coil Box
TABLE 1—OPENING DIMENSIONS (IN.)
APPLICATION
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A96284
Fig. 20—Furnace, Plenum, and Coil
Assembly or Coil Box Installed
on a Combustible Floor
PLENUM OPENING FLOOR OPENING
ABCD
15-1/8 19 16-3/4 20-3/8
15-1/2 19 16-1/2 20
18-5/8 19 20-1/4 20-3/8
19 19 20 20
22-1/8 19 23-3/4 20-3/8
22-1/2 19 23-1/2 20
—15—
Page 16
PERFORATED DISCHARGE DUCT FLANGE
NO
YES
210° MIN
YES
Fig. 21—Duct Flanges
A93029
Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guide- lines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
II. DUCTWORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used
ANGLE IRON OR EQUIVALENT
(B)
(A) ROD LOCATION
USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS)
(A) PREFERRED ROD LOCATION (B) ALTERNATE ROD LOCATION
3
5
4
(B)
(A)
DRAIN
(A)
(B)
3
/8-IN. HEX NUT
& WASHER (4)
REQD PER ROD
NOTES:
(A)
1. A 1 In. clearance minimum between top of furnace and combustible material.
2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
(B)
13
ALTERNATE SUPPORT LOCATION FROM BACK
Fig. 22—Crawlspace Horizontal Application
/16-IN. MAX
3
8-IN. ROD
ALTERNATE SUPPORT LOCATION 4-IN. MIN 8-IN. MAX
A93304
—16—
Page 17
if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
III. SUPPLY AIR CONNECTIONS A. Upflow Furnaces
Connect supply-air duct to 3/4-in. flange on furnace supply-air outlet. The supply-air duct attachment must ONLY be connected to furnace supply-/outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accesso­ries MUST be connected external to furnace main casing.
B. Downflow Furnaces
Connect supply-air duct to supply-air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material. When installed on combus­tible material, supply-air duct attachment must ONLY be con­nected to an accessory subbase or factory approved air condition­ing coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
C. Horizontal Furnaces
Connect supply-air duct to supply air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
IV. RETURN AIR CONNECTIONS
The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating fan cannot affect another appliance’s combustion air supply or act to mix products of combustion with circulating air, and that the air circulating fan of the furnace, if installed in an enclosure commu­nicating with another fuel-burning appliance not of the direct-vent type, shall be operable only when any door or panel covering an opening in the furnace fan compartment or in a return air plenum on ducts in the closed position.
V. FILTER ARRANGEMENT
CAUTION: Never operate a unit without a filter or with filter access door removed. Failure to follow this caution will result in minor unit operation or performance satis­faction.
Factory-supplied washable framed filters are shipped in blower compartment. Determine location for filter and relocate filter retaining wire if necessary. See Table 2 to determine correct filter size for desired filter location. Table 2 indicates filter size, location, and quantity shipped with this furnace. See Fig. 2 for location and size of bottom and side return-air openings.
CAUTION: Use care when cutting support rods in filters to protect against flying pieces and sharp rod ends. Wear safety glasses, gloves, and appropriate protective cloth­ing. Failure to follow this caution could result in minor personal injury.
CAUTION: For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM. Failure to follow this caution will result in minor unit operation or perfor­mance satisfaction.
NOTE: Side return-air openings can ONLY be used in UPFLOW configurations. Install filter(s) as shown in Fig. 23. Bottom return-air opening may be used with all 4 orientations. Filter may need to be cut to fit some furnace widths. Install filter as shown in Fig. 24.
WARNING: Never connect return-air ducts to the back of the furnace. Return-air duct connections on furnace side(s) permitted in upflow applications only. A failure to follow this warning could result in fire, personal injury, or death.
A. Upflow Furnaces
The return-air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 2. Bypass humidifier may be attached into unused side return air portion of the furnace casing. DO NOT connect any portion of return-air duct to back of furnace casing.
B. Downflow and Horizontal Furnaces
The return-air duct must be connected to return-air opening provided as shown in Fig. 2. DO NOT cut into casing sides or back to attach any portion of return-air duct. Bypass humidifier connec­tions should be made at ductwork or coil casing sides exterior to furnace.
—17—
Fig. 23—Filter Installed for Side Inlet
A00217
NOTE: Remove and discard bottom closure panel when bottom inlet is used.
TABLE 2—FILTER INFORMATION
FURNACE
CASING
WIDTH (IN.)
17-1/2 (1) 16 X 25 X 1† (1) 16 X 25 X 1 Cleanable
21 (1) 16 X 25 X 1* (1) 20 X 25 X 1† Cleanable
24-1/2 (1 or 2) 16 X 25 X 1* (1) 24 X 25 X 1† Cleanable
* Filters can be field modified by cutting frame as marked and folding to
desired size. Alternate sizes can be ordered from your distributor or dealer.
† Factory-provided with furnace.
FILTER SIZE (IN.)
Side Return Bottom Return
FILTER TYPE
FRAMED
Page 18
171⁄2-IN. WIDE CASINGS ONLY:
INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.
3
1
24
/2″
1
21-IN. WIDE CASINGS ONLY:
SUPPORT RODS (3) EXTEND 1/4" ON EACH SIDE OF FILTER AND REST ON CASING FLANGE
BOTTOM CLOSURE PANEL
FRONT FILLER PANEL
Fig. 25—Removing Bottom Closure Panel
A93047
WASHABLE FILTER
FILTER SUPPORT
Fig. 24—Bottom Filter Arrangement
FILTER RETAINER
A00290
VI. BOTTOM CLOSURE PANEL
These furnaces are shipped with bottom enclosure panel installed in bottom return-air opening. This panel MUST be in place when side return air is used.
To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove 2 screws holding front filler panel. (See Fig. 25.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall front filler panel and screws.
VII. GAS PIPING
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the United States. Canadian installations must be made in accordance with NSCNG­PIC and all authorities having jurisdiction. Gas supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 3 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.
CAUTION: Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls. Failure to follow this caution will result in intermittent unit operation or performance satisfaction.
WARNING: Gas valve shutoff switch MUST be facing forward or tilted upward. Failure to follow this warning could result in property damage or death.
WARNING: Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A failure to follow this warning could result in fire, explo­sion, personal injury, or death.
WARNING: Use proper length of pipe to avoid stress on gas control manifold. Failure to follow this warning could result in a gas leak resulting in fire, explosion, personal injury, or death.
TABLE 3—MAXIMUM CAPACITY OF PIPE*
NOMINAL
IRON
PIPE SIZE
(IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1-1/4 1.380 1400 950 770 660 580 1-1/2 1.610 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and
a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 12.2 NFPA 54-2002.
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight-through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 26.)
—18—
Page 19
GAS SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT TRAP
UNION
Fig. 26—Typical Gas Pipe Arrangement
CAUTION: If a flexible connector is required or al­lowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum of 2 in. outside furnace casing. Failure to follow this caution will result in intermittent unit opera­tion or performance satisfaction.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance.
A93324
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damege, per­sonal injury or loss of life.
An accessible manual shutoff valve MUST be installed external to furnace casing and within 6 ft of furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve.
NOTE: The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas valve. (See Fig. 50.)
Piping should be pressure and leak tested in accordance with NFGC in the United States or NSCNGPIC in Canada, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on furnace gas control valve and accessible manual shutoff valve before test.
The gas supply pressure shall be within the maximum and minimum inlet supply pressure marked on the rating plate with the furnace burners ON and OFF.
ELECTRICAL CONNECTIONS
See Fig. 27 for field wiring diagram showing typical field 115-v and 24-v wiring. Check all factory and field electrical connections for tightness.
FIVE WIRE
THREE-WIRE
HEATING-ONLY
BLOWER DOOR SWITCH
BLK
WHT
115-V FIELD-
SUPPLIED
DISCONNECT
GND
BLK
WHT
GND
AUXILIARY J-BOX
TERMINAL
FURNACE
Fig. 27—Typical Heating and Cooling Application Wiring Diagram
NOTE 2
W
C
R
O N
T
G
R O
COM
L
Y
24-V
BLOCK
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING
WCR GY
NOTE 1
NOTES: Connect Y-terminal in furnace as shown for proper blower operation.
1.
2.
3.
THERMOSTAT TERMINALS
CONDENSING UNIT
TWO WIRE
Some thermostats require a "C" terminal connection as shown. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
FIELD-SUPPLIED DISCONNECT
GND
208/230- OR 460-V THREE PHASE
208/230-V SINGLE PHASE
—19—
A02174
Page 20
Field-supplied wiring shall conform with the limitations of 63°F (35°C) rise.
WARNING: Blower access panel door switch opens 115-v power to control center. No component operation can occur. Do not bypass or close switch with panel removed. Failure to follow this warning could result in personal injury or death.
CAUTION: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw. Failure to follow this caution will result in intermittent unit operation.
I. 115-V WIRING
Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by power supply is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 4 for equipment electrical specifi­cations.
Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2002 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.
Use a separate, fused branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 4 for wire size and fuse specifications. A disconnecting means must be located within sight from and readily accessible to furnace.
CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 28.) Failure to follow this caution will result in intermittent unit operation or performance satisfaction.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control center LED status indicator light will flash rapidly and furnace will NOT operate.
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
Fig. 26—Bottom Filter Arrangement
A00290
ALTERNATE
FIELD
LOCATION
FACTORY INSTALLED LOCATION
Fig. 29—Relocating J-Box
WARNING: The cabinet MUST have an uninterrupted
or unbroken ground according to NEC ANSI/NFPA 70-2002 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.
J-BOX RELOCATION
1. Remove 2 screws holding auxiliary J-box. (See Fig. 29.)
2. Rotate J-box 180° and attach box to right side, using holes provided.
CAUTION: If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components. Failure to follow this caution will result in intermittent unit operation or performance satisfaction.
II. 24-V WIRING
Make field 24-v thermostat connections at 24-v terminal block on furnace control. For proper cooling operation, Y wire from thermostat MUST be connected to Y terminal on furnace control center, as shown in Fig. 27. The 24-v terminal block is marked for easy connection of field wiring. (See Fig. 30.) The 24-v circuit contains a 3-amp, automotive-type fuse located on furnace control. (See Fig. 31.) Any electrical shorts of 24-v wiring during instal­lation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (3 amp) and type. The control will flash code 24 when fuse needs replacement.
NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.
III. ACCESSORIES
1. Electronic Air Cleaner (EAC) Two quick-connect terminals marked EAC-1 and EAC-2
are provided for EAC connection. (See Fig. 31.) These terminals are energized with 115v (1.0-amp maximum) during blower motor operation.
A00212
—20—
Page 21
SCHEMATIC DIAGRAM
(NAT UR AL GAS & P RO PANE)
L2
NOTE #2
TO 115VA C FIELD DISCONNECT
EQUIPMENT GROUND
GND
L1
L2
CAP-1
LO
ILK
EAC-2
IDM
BLWM
START
OL
COM
HI
MED LO
MED HI
NOTE #10
COOL
HEAT
SPARE-1
SPARE-2
HI/LO
HSIR
EAC-1
BLWR
L1
AUX
OL
M
1
3
HSI
2
1
PL3
2
1
PL2
115VAC
PR1
IDR
PL4
24VAC
TRAN
CAP - 2
2
NOTE #6
F U 1
TEST/TWIN
PRINTED CIRCIUT BOARD
LS
NOTE #3
GV
FRS
SEC-2
SEC-1
(WHEN USED)
NOTE #11
PRS
LGPS
6
2
8
PL1
R
W
HUM
C
328150-101 REV. A
M
5
4
10
GVR-1
CPU
Y
FSE
7
3
9
1
G
11
NOTE #5
PCB
OM
24V
C
1. If any of the original equipment wire is replaced use wire rated for 105°C.
2. Use only copper wire between the disconne ct sw itch and the furnac e junc tion box (JB ).
3. This wire must be connected to furnace sheet metal for control to prove flame.
4. Symbols are electrical representation only.
NOTES:
optimum speed selection.
auto-r es et after th r ee hours .
5. Solid lines inside PCB are printed circuit board conductors and are not included in legend.
6. Replace only with a 3 amp fuse.
7. Inducer (IDM) and blower (BL W M) motors contain internal auto-reset thermal overload s w itches (O L).
8. Neutral connections are interchangeable within the NEUTRAL connector block.
9. Blower motor speed selections are for average conditions, see installation instructions for details on
10. YELLOW lead no t on all motors.
90 seconds or 5 seconds when J2 is cut.
11. Factory connected when LG P S is not use d.
12. Ig n itio n-locko ut will occur after f our con secutive unsuc c e ssful trials-for-ignition. Control will
13. Blower-on delay: gas heating 60 seconds, cooling or heat pump 2 seconds.
14. Blower-off delay: gas heating selections are 90, 120, 150 or 180 seconds, cooling or heat pump
A02271
LGPS
(WHEN USED)
NOTE #11
PRS
ORN
PCB
120
90
BLOWER OFF DELAY
150
JUMPER SELECT
J2
G
PRINTED CIRCIUT BOARD
YEL
GRN/YEL
GV
C
NOTE #3
M
BLU
FRS
RED
RED
LS
RED
ORN
BLU
180
J1
HUM
TEST/TWIN
om
Y
R
W
24V
C
FU1
NOTE #6
GRN/YEL
WHT
11
SEC-1
WHT
BLK
CAP -2
TRAN
WHT
BLU
RED
RED
RED
GRN/YEL
WHT
L2
LED 1
EAC-2
SEC-2
GRN/YEL
NOTE #8
BRN
BRN
PL4
YEL
NEUTRAL
IDM
AUX
M
WHT
GRN/YEL
321
FSE
WHT
PL1
12345678910
BLW
HSI
WHT
OL
2
1
PL3
BLK
WHT
BLK
BLK
BLK
1
PL2
2
EAC-1
SPAR E 2
L1
BHT/CLR BLWR
COOL
HEAT
SPA RE 1
FUSED OR CIRCUIT BREAKER
WHT
BLK
WHT (COM)
PR1
BLWM
BLK (HI)
WHT
(COM )
L1
NEUTRAL
Fig. 30—Wiring Diagram
NOTE #2
FU2
BLK
WHT
DISCONNECT SWITCH (WHEN REQ’D)
JB
GRN/YEL
BRN
YEL
(MED HI)
GND
TEMPERATURE SWITCH (N.C.)
OL AUTO-RESET INTERNAL MOTOR OVERLOAD
PCB PRINTED CIRCUIT BOARD CONTROL
PL1 11-CIRCUIT PCB CONNECTOR
PL2 2-CIRCUIT CONNECTOR
PL3 2-CIRCUIT HSI, CONNECTOR
ILK
BLK
WHT
CAP -1
BRN
STAR T
OL
RED (LO)
NOTE #10
BLU
(MED LO)
BHT/CLR BLOWER MOTOR SPEED CHANGE RELAY, SPDT
BLWR BLOWER MOTOR RELAY, SPST -( N .O.)
BLWM BLOWER MOTOR, PERMANENT-SPLIT-CAPACITOR
CAP 1,2 CAPACITOR
CPU MICROPROCESSOR AND CIRCUITRY
EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.)
LEGEN
PL4 3-CIRCUIT IDM EXTENSION CONNECTOR
EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON)
D
JUNCTION
UNMARKED TERMINAL
PCB CONTROL TERMINAL
FACTOR Y WIRING (115V AC)
FACTOR Y WIRING (24V A C )
FIELD WIRING (115VAC)
FIELD WIRING (24VAC)
CONDUCTOR ON CONTROL PCB
FIELD WIRING SCREW TERMINAL
FIELD EARTH GROUND
EQUIPMENT GROUND
FIELD SPLICE
PLUG RECEPTACLE
PRS PRESSURE SWITCH, SPST-(N.O.)
TEST/TWIN COM PONENT TEST & TWIN TERMINAL
TRAN TRANSFORMER-115VAC/24VAC
(FIELD INSTALLED & SUPPLIED)
FRS FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)
FSE FLAME-PROVING ELECTRODE
FU 1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
FU 2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
GND EQUIPMENT GROUND
GV GAS VALVE-REDUNDANT
GVR 1, 2 GAS VAL VE RELAY, DPST-(N.O.)
HSI HOT SURFACE IGNITER (115 VAC)
HSIR HOT SURFACE IGNITER RELAY, SPST-(N.O.)
HUM 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.)
IDM INDUCED DRAFT MOTOR, PSC
IDR INDUCED DRAFT MOTOR RELAY, SPST-(N.O.)
ILK BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.)
J1 BLOWER - OFF DELAY JUMPER SELECTOR
J2 COOLING - OFF DELAY JUMPER
JB JUNCTION BOX
LED LIGHT-EMITTING DIODE FOR STATUS CODES - RED
LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.)
LS LIMIT SWITCH, AUTO-RESET, SPST (N.C.)
—21—
Page 22
TABLE 4—ELECTRICAL DATA
UNIT SIZE
024040 115—60—1 127 104 6.1 8.4 14 44 15 036040 115—60—1 127 104 7.3 10.0 14 37 15 024060 115—60—1 127 104 6.1 8.4 14 44 15 036060 115—60—1 127 104 7.1 9.8 14 38 15 048060 115—60—1 127 104 9.5 12.8 14 29 15 036080 115—60—1 127 104 7.6 10.4 14 36 15 048080 115—60—1 127 104 10.0 13.4 14 28 15 060080 115—60—1 127 104 14.1 18.4 12 31 20 048100 115—60—1 127 104 10.2 13.5 14 27 15 060100 115—60—1 127 104 14.8 19.3 12 30 20 060120 115—60—1 127 104 14.6 19.1 12 30 20 060140 115—60—1 127 104 14.3 18.8 12 30 20
* Permissible limits of voltage range at which unit will operate satisfactorily. † Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load
amps. ‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended.
VOLTS— HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
Max* Min*
MAX UNIT
AMPS
UNIT
AMPACITY†
MIN
WIRE
GAGE
MAX WIRE
LENGTH
(FT)‡
MAX FUSE
OR CKT BKR
AMPS**
NOTE: DO NOT connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermidistat™, Zone Controller or simi­lar device. See Thermidistat™, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.
2. Humidifier (HUM) A quick-connect terminal (HUM) and screw terminal (C
OM
24-v) are provided for 24-v humidifier connection. (See Fig.
30.) HUM terminal is energized with 24v (0.5-amp maxi­mum) when gas valve is energized.
NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.
The 340MAV Furnaces require a dedicated (one 340MAV furnace only) direct-vent system. In a direct-vent system, all air for combustion is taken directly from outdoor atmosphere, and all flue gases are discharged to outdoor atmosphere.
I. REMOVAL OF EXISTING FURNACES FROM COMMON VENT SYSTEMS
When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the remaining attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, spillage of combustion products into the living space, etc.
DIRECT VENTING
WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1-2002/NFPA 54-2002 or the CSA B149.1, Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1-2002/NFPA 54-2002 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired appliance to their previous conditions of use.
Vent system or vent connectors may need to be resized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSC­NGPIC.
II. COMBUSTION-AIR AND VENT PIPING A. General
Combustion-air and vent pipe, fittings, primers, and solvents must conform to American National Standards Institute (ANSI) stan­dards and American Society for Testing and Materials (ASTM) standards. See Table 6 for approved materials for use in the U.S.A.
—22—
Page 23
BLOWER OFF-DELAY
J2 JUMPER
24-V THERMOST AT
TERMINALS
G Com W Y R
24V
BLOWER OFF-DELAY
90 150
J2
120 180
TWINNING AND/OR COMPONENT TEST
TERMINAL
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
3-AMP FUSE
LED OPERATION &
DIAGNOSTIC LIGHT
115-VAC(L2)NEUTRAL
CONNECTIONS
COOL
HEAT
BLOWER SPEED
SELECTION TERMINALS
STATUS CODE LED
NUETRAL
BLW
COOL HEAT
SPARE-1
SPARE-2
TEST/TWIN
0.5 AMP@24VAC
FUSE 3-AMP
SEC-2 SEC-1
EAC-2 L2
SPARE-1 SPARE-2
PLT
HUM
PLT 1
1-AMP@
EAC-1
115VAC
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
L1
PR-1
PL2 1
115 VAC (L1) LINE
VOLTAGE CONNECTION
TRANSFORMER 24-VAC
CONNECTIONS
PL1-LOW VOLT AGE MAIN HARNESS CONNECTOR
PL2-HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A02100
Fig. 31—Control Center
—23—
Page 24
and Canada. In Canada construct all combustion-air and vent pipes for this unit of CSA or ULC listed schedule-40 PVC, PVC-DWV or ABS-DWV pipe and pipe cement. SDR pipe is NOT approved in Canada.
See Table 7 for maximum pipe lengths and Fig. 36, 37, 38, 39, and 40 for exterior piping arrangements.
NOTE: Furnace combustion-air and vent pipe connections are sized for 2-in. pipe. Any pipe size change should be made outside furnace casing in vertical pipe. (See Fig. 32.) This allows proper drainage of vent condensate.
Combustion-air and vent pipes must terminate together in same atmospheric pressure zone, either through roof or sidewall (roof termination preferred), using accessory termination kit. See Table 5 for required clearances.
Furnace combustion-air and vent pipe connections must be at­tached as shown in Fig. 27. Combustion-air intake plug fitting and inducer housing alternate vent cap may need to be relocated in some applications.
NOTE: Slope combustion-air and vent pipes a minimum of 1/4 in. per linear ft with no sags between hangers.
CAUTION: When combustion-air pipe is installed above a suspended ceiling, pipe must be insulated with 3/8-in. thick Armaflex-type insulation. Combustion-air pipe should also be insulated when it passes through warm, humid space.
CAUTION: Combustion air must not be taken from inside structure because inside air is frequently contami­nated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household prod­ucts. Locate combustion-air inlet as far as possible from swimming pool and swimming pool pump house. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
WARNING: Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes. Failure to follow this warning could result in fire, property damage, personal injury, or death.
WARNING: All combustion-air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig. 36, 37, 38, 39, or 40. Failure to follow this warning could result in property damage, personal injury, or death.
CAUTION: When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 8 with Armaflex-type insulation. Failure to follow this caution will result in intermittent unit operation.
An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion-air and vent pipes. Each furnace must have its own set of combustion-air and vent pipes and be terminated individually, as shown in Fig. 42.
Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the NFGC or NSCNGPIC, and the vent or liner manufacturer’s Installation Instructions. Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances.
FURNACE
NOT IN HORIZONTAL SECTION
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
Fig. 32—Combustion-Air and Vent Pipe Diameter
Transition Location and Elbow Configuration
A93034
TABLE 5—COMBUSTION-AIR AND VENT PIPE
TERMINATION CLEARANCES
LOCATION
Above grade level or above antici-
From any mechanical fresh air intake See Note 4 6
For furnaces with an input capacity Btuh—from any non-mechanical air
supply (windows or doors which can
be opened) or combustion-air opening
For furnaces with an input capacity greater than 100,000 Btuh-from any
nonmechanical air supply (windows or
From service regulator vent, electric
and gas meters, and relief equipment Above grade when adjacent to public
† 18 in. above roof surface in Canada. NOTES:
1. If installing 2adjacent Furnaces,refer to Multiventing and Vent Terminations section for proper vent configurations.
2. When locating combustion-air and vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the appliance’s own flue products or the flue products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of heat exchangers.
3. Vent termination can not terminate less than 2 ft horizontal and 7 ft above public walkway or where condensate vapor or droplets may be a hazard.
4. Vent termination must be at least 3 feet above any forced draft inlets within 10 feet horizontal. Vent termination must be at least 3 feet horizontal from other direct vent appliances intake unless otherwise specified by manufac­turer.
5. 3 ft radius of furnace air-intake terminal and 1 ft horizontally from vertical centerline of furnace air-intake terminal.
6. Above a meter/regulator within 3 feet horizontally of vertical centerline of meter/regulator vent outlet to a maximum vertical distance of 15 feet.
pated snow depth
Water heater/Dryer vent See Note 5 See Note 5
From plumbing vent stack 33
equal to or less than 100,000
doors which can be opened) or
combustion-air opening
walkway
CLEARANCE (FT)
U.S.A. Canada
11
11
13
See Note 6 See Note 6
Note 3 Note 3
—24—
Page 25
TABLE 6—APPROVED COMBUSTION-AIR AND VENT PIPE, FITTING AND CEMENT MATERIALS
ASTM SPECIFICATION
(MARKED ON MATERIAL)
D1527 ABS Pipe Schedule-40 D1785 PVC Pipe Schedule-40
D2235 For ABS D2241 PVC Pipe SDR-21 & SDR-26
D2466 PVC Fittings Schedule-40 D2468 ABS Fittings Schedule-40
D2564 For PVC D2661 ABS Pipe Fittings DWV at Schedule-40 IPS sizes
D2665 PVC Pipe Fittings DWV
F438 CPVC Fittings Schedule-40 F441 CPVC Pipe Schedule-40 F442 CPVC Pipe SDR
F493 For CPVC F628 ABS Pipe Cellular Core DWV at Schedule-40 IPS sizes
F656 For PVC Primer For PVC F891 PVC Pipe Cellular Core Schedule-40 & DWV
MATERIAL PIPE FITTINGS SOLVENT CEMENT AND PRIMERS DESCRIPTION
Solvent Cement
Solvent Cement
Solvent Cement
For ABS
For PVC
For CPVC
NOTE: The minimum combustion-air and vent pipe length (each) for these furnaces is 5 ft. Short pipe lengths (5-8 ft) may discharge water droplets. These droplets may be undesirable, and a 12-in. minimum offset pipe section is recommended, as shown in Fig. 34, to reduce excessive droplets from exiting vent pipe outlet.
B. Combustion-Air and Vent Pipe Diameter
Determine combustion-air and vent pipe diameter.
1. Using Table 7, individually determine the smallest combustion-air and vent pipe diameters permitted for each pipe. Pick the larger of these 2 pipe diameters and use this diameter for both combustion-air and vent pipes.
NOTE: Select 1 vent pipe connection and
Select 1 vent pipe connection and 1 combustion-air pipe connection.
AIR
COMBUSTION-
AIR
VENT
COMBUSTION-
AIR
FLOW
HORIZONTAL-LEFT DISCHARGE HORIZONTAL-RIGHT DISCHARGE
FLOW
COMBUSTION-
UPFLOW DOWNFLOW
AIR
VENT
AIR
VENT
NOTE:
1 combustion-air pipe connection.
VENT
COMBUSTION-
AIR
AIR
FLOW
COMBUSTION-
VENT
VENT
COMBUSTION-
AIR
AIR
AIR
FLOW
A96187
Fig. 33—Combustion-Air and Vent Pipe Connections
2. When installing vent systems of short pipe length, use the smallest allowable pipe diameter. Do not use pipe size greater than required or incomplete combustion, flame disturbance, or flame sense lockout may occur.
NOTE: Do not count elbows or pipe sections in terminations or within furnace. See shaded areas in Fig. 36, 37, 38, 39, and 40.
EXAMPLE: An 036080 size furnace located in Indianapolis, elevation 650 ft above sea level, could be installed in an application requiring 3 elbows and 32 ft of vent pipe, along with 5 elbows and 34 ft of combustion-air pipe. Table 7 indicates this application would allow a 2-in. diameter vent pipe, but require a 2-1/2 in. diameter combustion air pipe (2-in. pipe is good for 35 ft with 3 elbows, but only 30 ft with 5 elbows). Therefore, 2-1/2 in. diameter pipe must be used for both vent and combustion-air pipes since larger required diameter must always be used for both pipes. If same installation were in Albuquerque, elevation 5250 ft above sea level, installation would require 2-1/2 in. vent pipe and combustion-air pipe. At 5001- to 6000-ft elevation, 2-in. pipe is only good for 17 ft with 5 elbows, and 2-1/2 in. pipe is good for 70 ft with 5 elbows.
C. Combustion-Air and Vent Pipe Attachment NOTE: All pipe joints must be cemented except attachment of
combustion-air pipe to inlet housing connection, since it may be necessary to remove pipe for servicing.
1. Attach combustion-air pipe as follows: a. Determine location of combustion-air intake pipe con-
nection to combustion-air intake housing as shown in Fig. 33 for application.
b. Reposition combustion-air intake housing plug fitting in
appropriate unused intake housing connection.
c. If required per Table 7, insert perforated disk assembly
(factory-supplied in loose parts bag) in intake housing where combustion-air intake pipe will be connected. If half disk set is required, install with shoulder of disk against stop in combustion-air inlet.
—25—
Page 26
12 MIN
12 MIN
VENT PIPE
HORIZONTAL TO ROOF HORIZONTAL TO SIDEWALL
COMBUSTION-AIR PIPE
12 MIN
VENT PIPE
COMBUSTION-AIR PIPE COMBUSTION-AIR PIPE
COMBUSTION-AIR PIPE
VENT PIPE
12 MIN
VENT PIPE
NOTE: A 12 In. minimum offset pipe section is recommended with
short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe.
Fig. 34—Short Vent (5 to 8 Ft) System
d. Install pipe support (factory-supplied in loose parts bag)
into selected furnace casing combustion-air pipe hole. Pipe support should be positioned at bottom of casing hole.
e. Insert 2-in. diameter pipe into intake housing.
NOTE: A 2-in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing.
f. Install casing hole filler cap (factory-supplied in loose
parts bag) in unused combustion-air pipe casing hole.
g. Drill a 1/8-in. hole in 2-in. combustion-air pipe using
hole in intake housing as a guide.
h. Install a field-supplied No. 6 or No. 8 sheet metal screw
into combustion-air pipe.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur.
NOTE: Do not attach combustion-air intake pipe permanently to combustion-air intake housing since it may be necessary to remove pipe for service of ignitor or flame sensor.
COMBUSTION-AIR INTAKE HOUSING PLUG FITTING
VERTICAL TO SIDEWALLVERTICAL TO ROOF
A96230
The combustion-air intake plug fitting must be installed in unused combustion-air intake housing. This fitting must be attached by using RTV sealant, or by drilling a 1/8-in. hole in fitting, using hole in intake housing as a guide. Install a field-supplied No. 6 or No. 8 sheet metal screw.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for use when moisture is found in combustion-air intake pipe and combustion box.
NOTE: Moisture in combustion-air intake may be result of improper termination. Ensure combustion-air intake pipe termina­tion is similar to that shown in Fig. 36, 37, 38, 39, and 40 so it will not be susceptible to areas where light snow or other sources of moisture could be pulled in.
If use of this drain connection is desired, drill out fitting’s tap plug with a 3/16-in. drill and connect a field-supplied 3/8-in. tube. This tube should be routed to open condensate drain for furnace and A/C (if used), and should be trapped. (See Fig. 35.)
2. Attach vent pipe as follows: a. Determine location of vent pipe connection to inducer
housing as shown in Fig. 33 for application.
—26—
Page 27
ALTITUDE (FT) UNIT SIZE
0 to 2000
ALTITUDE (FT) UNIT SIZE
2001 to 3000
ALTITUDE (FT) UNIT SIZE
3001 to 4000
See notes at end of table
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120
060140
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120
060140
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120
060140
TABLE 7—MAXIMUM ALLOWABLE PIPE LENGTH (FT)
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1 5 NA NA NA NA NA
1-1/2 70 70 65 60 60 55
2 707070707070
1-1/2 20 15 10 5 NA NA
2 707070707070
1-1/2 10 NA NA NA NA NA
2 555035303020
2-1/2 70 70 70 70 70 70
2 5 NA NA NA NA NA
2-1/2 40 30 20 20 10 NA
3 707070707070
2-1/2 one disk 10 NA NA NA NA NA
3† 45 40 35 30 25 20
3† no disk 70 70 70 70 70 70
2-1/2 one disk 5 NA NA NA NA NA
3† one disk 40 35 30 25 20 15
3† no disk 60 56 52 48 44 40 4† no disk 70 70 70 70 70 70
PIPE DIA
(IN.)* 1-1/2 67 62 57 52 52 47
2 707070707070
1–1/2 17 12 7 NA NA NA
2 706766616161
2 494430252515
2-1/2 70 70 70 70 70 70
2–1/2 35 26 16 16 6 NA
3 707070706661
3 14 9 NA NA NA NA 3† no disk 70 70 63 56 50 43 4† no disk 70 70 70 70 70 70
3† one disk 20 15 10 5 NA NA
3† no disk 39 35 31 27 23 19 4† no disk 70 70 70 70 70 70
PIPE DIA
(IN.)* 1-1/2 64 59 54 49 48 43
2 707070707070
1–1/2 16 11 6 NA NA NA
2 686362575756
2 464128232213
2-1/2 70 70 70 70 70 70 2-1/2 33 24 15 14 5 NA
3 707070666156 3† no disk 65 58 51 44 38 31 4† no disk 70 70 70 70 70 70
3† one disk 11 6 NA NA NA NA
3† no disk 30 26 22 18 14 10 4† no disk 70 70 70 70 70 70
123456
123456
123456
NUMBER OF 90° ELBOWS
NUMBER OF 90° ELBOWS
NUMBER OF 90° ELBOWS
—27—
Page 28
ALTITUDE (FT) UNIT SIZE
4001 to 5000‡
ALTITUDE (FT) UNIT SIZE
5001 to 6000‡
ALTITUDE (FT) UNIT SIZE
6001 to 7000‡
ALTITUDE (FT) UNIT SIZE
7001 to 8000‡
See notes at end of table
TABLE 7—MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)
TERMINATION
TYPE
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120
060140
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120
060140
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120
060140
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120 060140 NA
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1-1/2 60 55 50 45 44 39
2 707070707070
1-1/2 15 10 5 NA NA NA
2 645958535252 2 443926212011
2-1/2 70 70 70 70 70 70 2-1/2 31 22 13 12 NA NA
3 707067625752 3† no disk 53 46 40 33 26 20 4† no disk 70 70 70 70 70 70 3† no disk 21 17 13 9 5 NA 4† no disk 69 64 59 54 49 44
PIPE DIA
(IN.)*
1-1/2 57 52 47 42 40 35
2 707070707070
1-1/2 14 9 NA NA NA NA
2 605554494847
2 4136231817 8
2-1/2 70 70 70 70 70 70 2-1/2 29 21 12 11 NA NA
3 706762575247 3† no disk 42 35 29 22 15 9 4† no disk 70 70 70 70 70 70 3† no disk 12 8 NA NA NA NA 4† no disk 42 37 32 27 22 17
PIPE DIA
(IN.)*
1-1/2 53 48 43 38 37 32
2 707068676664
1-1/2 13 8 NA NA NA NA
2 575250454443
2 3833211615 6
2-1/2 70 70 68 67 66 64 2-1/2 27 19 10 9 NA NA
3 686358534843 3† no disk 31 24 18 11 NA NA 4† no disk 70 70 70 70 67 62
4† no disk 17 12 7 NA NA NA
PIPE DIA
(IN.)*
1-1/2 49 44 39 34 33 28
2 666563626059
1-1/2 12 7 NA NA NA NA
2 534846414038
2 3631191412NA
2–1/2 66 65 63 62 60 59 2–1/2 25 17 8 7 NA NA
3 635853484338 3† no disk 20 13 7 NA NA NA 4† no disk 61 56 51 46 41 36
123456
123456
123456
123456
NUMBER OF 90° ELBOWS
NUMBER OF 90° ELBOWS
NUMBER OF 90° ELBOWS
NUMBER OF 90° ELBOWS
—28—
Page 29
TABLE 7—MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)
ALTITUDE (FT) UNIT SIZE
024040 036040
024060 036060 048060
036080
8001 to 9000‡
ALTITUDE (FT) UNIT SIZE
9001 to 10,000‡
Disk usage-Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag). If one disk is stated, separate 2 halves of perforated disk assembly and use shouldered disk half. When using shouldered disk half, install screen side toward inlet box. †Wide radius elbow. ‡Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NA-Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.
3. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
6. Use 3-in. diameter vent termination kit for installations requiring 4-in diameter pipe.
048080 060080
048100 060100
060120 060140 NA
024040 036040
024060 036060 048060
036080 048080 060080
048100 060100
060120 060140 NA
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1-1/2 46 41 36 31 29 24
2 626058565553
1-1/2 11 6 NA NA NA NA
2 494442373534 2 3328171210NA
2-1/2 62 60 58 56 55 53 2-1/2 23 15 7 5 NA NA
3 595449443934 3† no disk 10 NA NA NA NA NA 4† no disk 35 30 25 20 15 10
PIPE DIA
(IN.)* 1-1/2 42 37 32 27 25 20
2 575553514947
2 454038333129
230251497NA
2-1/2 57 55 53 51 49 47 2-1/2 21 13 5 NA NA NA
3 544944393429 4† no disk 10 5 NA NA NA NA
123456
123456
NUMBER OF 90° ELBOWS
NUMBER OF 90° ELBOWS
COMBUSTION – AIR
3/8" ID TUBE
3/16"
DRILL
INTAKE HOUSING
BURNER BOX
COMBUSTION – AIR PIPE
4
TRAP
TO OPEN
MIN
DRAIN
Fig. 35—Air Intake Housing Plug Fitting Drain
b. Reposition elastometric (rubber) inducer housing outlet
cap and clamp to appropriate unused inducer housing connection. Tighten clamp.
A93035
WARNING: Inducer housing outlet cap must be in­stalled and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
c. Install pipe support (factory-supplied in loose parts bag)
into selected furnace casing vent pipe hole. Pipe support should be positioned at bottom of casing hole.
WARNING: Vent pipe must be installed and fully seated against inducer housing internal stop. Clamp must be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
NOTE: A 2-in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing.
d. Be certain that mating surfaces of inducer housing
connection, elastomeric coupling, and 2-in. diameter vent pipe are clean and dry. Assemble the elastomeric (rubber) vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2-in. diameter vent pipe through the elastomeric (rubber) coupling and
—29—
Page 30
fully into inducer housing connection until it bottoms on the internal stop. Tighten both clamps to secure the pipe to inducer housing. Tighten the clamp screws to 15 in.-lb. of torque.
e. Install casing hole filler cap (factory-supplied in loose
parts bag) in unused vent pipe casing hole.
VENT EXTENSION PIPE Some furnaces are supplied with a PVC vent extension pipe
(2-in. diameter by 12-in. long). This pipe has a built-in channel to assist vent condensate disposal. When this vent extension pipe is supplied, it must be used to connect the field vent pipe to furnace inducer housing on ALL upflow and downflow applications.
NOTE: See label on vent extension pipe for proper installation. This pipe may be shortened if an elbow is used to connect vent extension tube to field-installed vent pipe.
3. Working from furnace to outside, cut pipe to required length(s).
4. Deburr inside and outside of pipe.
5. Chamfer outside edge of pipe for better distribution of primer and cement.
6. Clean and dry all surfaces to be joined.
7. Check dry fit of pipe and mark insertion depth on pipe.
NOTE: It is recommended that all pipes be cut, prepared, and preassembled before permanently cementing any joint.
8. After pipes have been cut and preassembled, apply gener­ous layer of cement primer to pipe fitting socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.
9. While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is fully inserted into fitting socket.
10. Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made joint.
11. Handle pipe joints carefully until cement sets.
12. Support combustion-air and vent piping a minimum of every 5 ft (3 ft for SDR-21 or -26 PVC) using perforated metal hanging strap.
13. Slope combustion-air and vent pipes downward toward furnace a minimum of 1/4 in. per linear ft with no sags between hangers.
14. Use appropriate methods to seal openings where vent and combustion-air pipes pass through roof or side wall.
III. CONCENTRIC VENT AND COMBUSTION-AIR TERMINATION KIT INSTALLATION
NOTE: If these instructions differ from those packaged with
termination kit, follow kit instructions. Combustion-air and vent pipes must terminate outside structure. A
factory accessory termination kit must be installed in 1 of the installations shown in Fig. 36, 37, 38, 39, and 40. Four termination kits are available.
1. The 2-in. termination bracket kit is for 1-in., 1-1/2 in., and 2-in. diameter 2-pipe termination systems.
2. The 3-in. termination bracket kit is for 2-1/2 in., 3-in., and 4-in. diameter 2-pipe termination systems.
3. The 2-in. concentric vent/air termination kit is for 1-in., 1-1/2 in., 2-in., and 2-1/2 in. diameter pipe systems when single penetration of wall or roof is desired.
4. The 3-in. concentric vent/air termination kit is for 2-1/2 in., 3-in., and 4-in. diameter pipe systems when single penetra­tion of wall or roof is desired.
NOTE: Shaded parts in Fig. 36, 37, 38, 39, and 40 are considered to be termination. These components should NOT be counted when determining pipe diameter. Roof termination is preferred since it is less susceptible to damage, has reduced chances to take in contaminants, and has less visible vent vapors. (See Fig. 36 or
37.) Sidewall termination may require sealing or shielding of building surfaces with a corrosive resistance material due to corrosive combustion products of vent system.
A. Extended Exposed Sidewall Pipes
Sidewall combustion-air and vent pipe terminations may be extended beyond area shown in Fig. 39 or 40 in outside ambient by insulating pipes as indicated in Table 8.
1. Determine combustion-air and vent pipe diameters, as stated above, using total pipe length and number of elbows.
2. Using winter design temperature (used in load calculations), find appropriate temperature for your application and fur­nace model.
3. Determine required insulation thickness for exposed pipe lengths.
NOTE: Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 7.
B. Two-Pipe Termination Kit
1. Determine location for termination. Consideration of the following should be made when
determining an appropriate location for termination kit. a. Comply with all clearance requirements as stated in
Table 5.
b. Termination kit should be positioned where vent vapors
will not damage plants/shrubs or air conditioning equip­ment.
c. Termination kit should be positioned so that it will not be
affected by wind eddy (such as inside building corners) or allow recirculation of flue gases, airborne leaves, or light snow.
d. Termination kit should be positioned where it will not be
damaged by or subjected to foreign objects, such as stones, balls, etc.
e. Termination kit should be positioned where vent vapors
are not objectionable.
2. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size being used.
3. Loosely install elbow in bracket and place assembly on combustion-air pipe.
Roof terminations—Loosely install pipe coupling on prop­erly cut vent pipe. Coupling must be positioned so bracket will mount as shown in Fig. 36.
For applications using combustion-air pipe option, indi­cated by dashed lines in Fig. 36, install 90° street elbow into 90° elbow, making U-fitting. A 180° U-fitting may be used.
Sidewall terminations—Install bracket as shown in Fig. 39 or 40.
For applications using vent pipe option indicated by dashed lines in Fig. 39, rotate vent elbow 90° from position shown in Fig. 39.
4. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
—30—
Page 31
TABLE 8—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH AND WITHOUT INSULATION IN WINTER
DESIGN TEMPERATURE AMBIENT*
FURNACE
SIZE
040
060
080
100
120
140
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in Table 7. † Insulation thickness based on R value of 3.5 per in.
WINTER DESIGN
TEMPERATURE
(°F)
20 1.5 51 70
0 1.5 28 70
-20 1.5 16 70 20 2 45 70
0 2 22 70
-20 2 10 58 20 2 65 70
0 2 35 70
-20 2 20 70 20 2 55 55
0 2 48 55
-20 2 30 55 20 2.5 70 70
0 2.5 47 70
-20 2.5 28 70 20 2.5 40 40
0 2.5 40 40
-20 2.5 38 40 20 3 70 70
0 3 50 70
-20 3 28 70 20 3 70 70
0 3 61 70
-20 3 37 70 20 4 70 70
0 4 48 70
-20 4 23 70 20 3 60 60
0 3 60 60
-20 3 44 60 20 4 70 70
0 4 57 70
-20 4 30 70
MAX PIPE
DIAMETER
(IN.)
WITHOUT
INSULATION
WITH 3/8–IN. OR
THICKER INSULATION†
5. Check required dimensions as shown in Fig. 36, 39, or 40.
C. Concentric Vent/Air Termination Kit
1. Determine location for termination. Consideration of the following should be made when
determining an appropriate location for termination kit. a. Comply with all clearance requirements as stated in
Table 5.
b. Termination kit should be positioned where vent vapors
will not damage plants/shrubs or air conditioning equip­ment.
c. Termination kit should be positioned so it will not be
affected by wind eddy (such as inside building corners) or that may allow recirculation of flue gases, airborne leaves, or light snow.
d. Termination kit should be positioned where it will not be
damaged by or subjected to foreign objects, such as stones, balls, etc.
e. Termination kit should be positioned where vent vapors
are not objectionable.
2. Cut one 4-in. diameter hole for 2-in. kit, or one 5-in. diameter hole for 3-in. kit.
3. Loosely assemble concentric vent/air termination compo­nents together using instructions in kit.
4. Slide assembled kit with rain shield REMOVED through hole.
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
Roof terminations—Locate assembly through roof to ap­propriate height as shown in Fig. 37.
Sidewall terminations—Locate assembly through sidewall with rain shield positioned no more than 1-in. from wall as shown in Fig. 38.
5. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
6. Check required dimensions as shown in Fig. 37 or 38.
IV. MULTIVENTING AND VENT TERMINATIONS
When 2 or more 340MAV Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or breach vent 340MAV furnaces. When 2 or more 340MAV furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 41, 42, 43, 44, and 45, but next vent termination must be at least 36 in. away from first 2 terminations.
—31—
Page 32
VERTICAL SEPARATION
BETWEEN COMBUSTION
MAXIMUM OF 24 IN. ABOVE ROOF.
AIR AND VENT
8 3/
FOR 3″ KIT
4
6 3/
FOR 2″ KIT
4
MAINTAIN 12 IN. MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
COUPLING
VENT
ROOF
18″ MAXIMUM
BRACKET
COMBUSTION AIR
Fig. 36—Roof Termination (Preferred)
VENT
COMBUSTION AIR
MAINTAIN 12 IN. (18 IN. FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF.
Fig. 37—Concentric Vent and Combustion-Air Roof
Termination (Preferred)
OVERHANG OR ROOF
A93054
OVERHANG OR ROOF
12
MINIMUM
1MAXIMUM
COMBUSTION-AIR
VENT
MAINTAIN 12 IN. CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER.
Fig. 38—Concentric Vent and Combustion-Air Side
Termination
OVERHANG OR ROOF
A87224
A93055
12MINIMUM
VENT
BRACKET
90°
COMBUSTION-AIR
12 IN. SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12 IN. CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER.
Fig. 39—Sidewall Termination of 12 in. or More
A87225
—32—
12MINIMUM
VENT
BRACKET
COUPLING
90°
COMBUSTION-AIR (ELBOW PARALLEL TO WALL)
12 IN. SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12 IN. CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER.
Fig. 40—Sidewall Termination of Less than 12 in.
A87226
Page 33
A
C
Fig. 41—Rooftop Termination (Dimension "A" is Touching or 2-In. Maximum Separation)
A96128
VENT
VENT
A
COMBUSTION AIR
A93056
Fig. 42—Concentric Vent and Combustion-Air
Roof Termination
(Dimension "A" is Touching or 2-In. Maximum Separation)
VENT
1MAXIMUM (TYP)
COMBUSTION AIR
VENT
A
VENT
A93057
Fig. 43—Concentric Vent and Combustion-Air
Side Termination
(Dimension "A" is Touching or 2-In. Maximum Separation)
VENT
COMBUSTION AIR
A
Fig. 44—Sidewall Termination of 12 in. or Less
(Dimension "A" is Touching or 2-In. Maximum Separation)
COMBUSTION AIR
A96129
—33—
OMBUSTION AIR
A
COMBUSTION AIR
A96130
Fig. 45—Sidewall Termination of More Than 12 in.
(Dimension "A" is Touching or 2-In. Maximum Separation)
Page 34
It is important that vent terminations be made as shown to avoid recirculation of flue gases. Dimension "A" in Fig. 41, 42, 43, 44, and 45 represents distance between pipes or rain shields, as touching or 2-in. maximum separation.
CONDENSATE DRAIN
I. GENERAL
Condensate trap is shipped installed in the blower shelf and factory connected for UPFLOW applications. Condensate trap must be RELOCATED for use in DOWNFLOW and HORIZONTAL applications.
Condensate trap MUST be used for all applications. An external trap is not required when connecting the field drain to
this condensate trap. The field drain connection (condensate trap or drain tube coupling)
is sized for 1/2-in. CPVC, 1/2-in. PVC, or 5/8-in. ID tube connection.
Drain pipe and fittings must conform to ANSI standards and ASTM D1785, D2466 or D2846. CPVC or PVC cement must conform to ASTM D2564 or F493. Primer must conform to ASTM F656. In Canada, use CSA or ULC listed schedule 40 CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is approved for condensing furnace applications. To avoid conden­sate spillage, select a pump with an overflow switch.
CAUTION: Unit must not be installed, operated, and then turned off and left in an unoccupied structure during cold weather when temperature drops to 32°F and below unless drain trap and drain line have adequate freeze protection. See Service and Maintenance Instructions for winterizing procedure. (See Fig. 15.) Failure to follow this caution will result in minor unit operation.
Furnace condensate is mildly acidic, typically in the pH range of
3.2 to 4.5. Due to corrosive nature of this condensate, a condensate pH neutralizing filter may be desired. Check with local authorities to determine if a pH neutralizer is required.
II. APPLICATION
The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external, field­supplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment’s drain.
See Fig. 46 for example of possible field drain attachment using 1/2-in. CPVC or PVC tee for vent and A/C or humidifier drain connection.
Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining.
WARNING: Caution should be taken to prevent drain­ing where slippery conditions may cause personal inju­ries. Excessive condensate draining may cause saturated soil conditions which may result in damage to plants.
OPEN STAND
PIPE FOR
A/C OR
HUMIDIFIER
DRAIN
TEE
TO OPEN DRAIN
A94054
Fig. 46—Example of Field Drain Attachment
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back. (See Fig. 47.)
3. Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig.
47.)
4. Wrap field drain pipe with remaining heat tape, approxi­mately 1 wrap per ft.
5. When using field-supplied heat tape, follow heat tape manufacturer’s instructions for all other installation guide­lines.
CONDENSATE TRAP
WIRE TIE(S)
III. CONDENSATE DRAIN PROTECTION
Freezing condensate left in condensate trap and drain line may cause cracks, and possible water damage may occur. If freeze protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft at 120v and 40°F self-regulating, shielded, and waterproof heat tape. See Installation Instructions supplied with accessory or heat tape manufacturer’s recommenda­tions.
—34—
(3 WRAPS MINIMUM)
HEAT TAPE
Fig. 47—Condensate Trap Heat Tape
A93036
Page 35
SEQUENCE OF OPERATION
CAUTION: Furnace control must be grounded for proper operation, or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw. Failure to follow this caution will result in intermittent unit operation.
Using schematic diagram, follow sequence of operation through different modes. (See Fig. 30.) Read and follow wiring diagram carefully.
NOTE: If a power interruption occurs during a call for heat (W), the control will start a 90-second blower-only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The red LED light will flash code 12 during the 90-second period, after which the LED will be ON continuous, as long as no faults are detected. After the 90-second period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot-surface igniter HSI, and gas valve GV.
I. HEATING MODE
(See Fig. 27 for thermostat connections.)
The wall thermostat calls for heat, closing the R to W circuit. The furnace control performs a self-check, verifies the pressure switch contacts PRS are open, and starts the inducer motor IDM.
a. Inducer Prepurge Period- As the inducer motor IDM
comes up to speed, the pressure switch contacts PRS close, 24 vac power is supplied for a field installed humidifier at the HUM terminal and the control begins a 15-second prepurge period.
b. Igniter Warm-Up- At the end of the prepurge period,
the Hot-Surface Igniter HSI is energized for a 17-second igniter warm-up period.
c. Trial-for-Ignition Sequence- When the igniter
warm-up period is completed the main gas valve relay contacts GVR close to energize the gas valve GV, the gas valve opens. The gas valve GV permits gas flow to the burners where it is ignited by the Hot Surface Igniter HSI. Five seconds after the GVR closes, a 2-second flame period begins. The HSI igniter will remain ener­gized until the flame is sensed or until the 2-second flame proving period begins.
d. Flame-Proving- When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control CPU begins the blower-ON delay period and continues to hold the gas valve GV open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV, and the control CPU will repeat the ignition sequence for up to three more Trials-For­Ignition before going to Ignition-Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting 115 vac power to the furnace, or by inter­rupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at W, G, R, etc.)
If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas-Heating mode and operate the inducer motor IDM until flame is no longer proved.
e. Blower-On Delay- If the burner flame is proven, the
blower motor is energized on HEAT speed 66 seconds (040 through 120 sizes) or 45 seconds (140 size) after the
gas valve GV is energized. Simultaneously, the electronic air cleaner terminal EAC-1 is energized and remains energized as long as the blower motor BLWM is energized.
f. Blower-Off Delay- When the thermostat is satisfied, the
R-to-W circuit is opened, de-energizing the gas valve GV, stopping gas flow to the burners, and de-energizing the humidifier terminal HUM. The inducer motor IDM will remain energized for a 15-second (040 through 120 sizes) or 5-second (140 size) post-purge period. The blower motor BLWM and air cleaner terminal EAC-1 will remain energized for 90, 120, 150, or 180 seconds (depending on the blower-OFF delay selection). The furnace control CPU is factory-set for a 120-second blower-OFF delay.
II. COOLING MODE
(See Fig. 27 for thermostat connections) The thermostat closes the R-to-G-and-Y circuits. The R-to-Y
circuit starts the outdoor unit, and the R-to-G and Y circuits start the furnace blower motor BLWM on COOL speed. The electronic air cleaner terminal EAC-1 is energized with 115 vac when the blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating on the COOL speed for an additional 90 seconds. Cut jumper J2 to reduce the cooling off-delay to 5 seconds.
III. CONTINUOUS BLOWER MODE
When the R-to-G circuit is closed by the thermostat, the blower motor BLWM will operate on continuous-blower speed (same as HEAT speed). Terminal EAC-1 is energized as long as the blower motor BLWM is energized. During a call for heat, the blower BLWM will stop during igniter warm-up (17 seconds), ignition (7 seconds), and blower-ON delay (66 or 45 seconds for 040 through 120 sizes or for 140 size), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower-ON delay period at HEAT speed. In heating, the furnace control CPU will continue running the blower motor BLWM at HEAT speed after the selected blower­OFF delay period is completed. When the thermostat calls for cooling, the blower motor BLWM will operate at COOL speed. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds on COOL speed before reverting back to HEAT speed. Jumper J2 can be cut to reduce the cooling off-delay to 5 seconds. (See Fig. 31.) When the R-to-G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
IV. HEAT PUMP MODE
When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. When the R-to-W-and-Y or R-to-W-and­Y-and-G circuits are energized the furnace control CPU will continue to turn on the blower motor BLWM at HEAT speed, and begin a heating cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 seconds then come back on at HEAT speed. When the W input signal disappears, the furnace control begins a normal inducer post-purge period and the blower switches to COOL speed after a 3 second delay. If the R-to-W-and-Y-and-G signals disappear at the same time, the blower motor BLWM will remain on for the selected blower-OFF delay period. If the R-to-W-and-Y signals disappear, leaving the G signal, the blower motor BLWM will continue running the blower motor BLWM at HEAT speed after the selected blower-OFF delay period is completed.
—35—
Page 36
Control initiates a 90-sec blower only on period before starting another heat pump cycle if there is a power interruption. Anytime control senses false flame, control locks out of heating mode. This reaction occurs because control ignores W input due to false flame signal and, as a result, sees only Y input and goes into cooling mode blower off delay. All other control functions remain in standard format. NOTE: EAC-1 terminal is energized whenever blower operates. HUM terminal is only energized when gas valve is energized.
V. COMPONENT TEST NOTE: The furnace control component test allows all compo-
nents to run for a short time; except the gas valve and humidifier terminal HUM are not energized for safety reasons. The EAC-1 terminal is energized when the blower is energized. This feature helps diagnose a system problem in case of a component failure. The component test feature will not operate if any thermostat signal is present ant the control and not until all time delays are completed. NOTE: Record the status code BEFORE opening the blower access door and before shutting off power to the furnace. Opening the blower access door will open the blower door switch and shut off power within the furnace. When power to the furnace is shut off by either method, the status code will be lost because the code is not stored while power is removed for any reason. To Begin Component Self-Test:
WARNING: Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warning could result in electrical shock, personal injury, or death.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control center LED status light will flash rapidly and furnace will not operate.
2. Thermostat wire connections at terminals R, W, G, and Y must be made at 24-v terminal block on furnace control.
3. Natural gas service pressure must not exceed 0.5 psig (14-in. wc), but must be no less than 0.16 psig (4.5-in. wc).
4. Blower access panel must be in place to complete 115-v electrical circuit to furnace.
CAUTION: These furnaces are equipped with a manual reset limit switch in burner box. This switch will open and shut off power to gas control if an overheat condition (flame rollout) occurs in burner enclosure. Correct inad­equate combustion-air supply or improper venting condi­tion and reset switch. DO NOT jumper this switch. Failure to follow this caution will result in intermittent unit operation or performance satisfaction.
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
II. PRIME CONDENSATE TRAP WITH WATER
CAUTION: Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has 2 internal chambers which can ONLY be primed by pour­ing water into the inducer drain side of condensate trap. Failure to follow this caution will result in intermittent unit operation or performance satisfaction.
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control.
3. Manually close blower door switch.
4. For approximately 2 sec, short (jumper) the C
OM-24v
terminal on control to the TEST/TWIN 3/16-inch quick­connect terminal on control until the LED goes out. Remover jumper from terminals. (See Fig. 31.)
NOTE: If TEST/TWIN and C
OM-24v terminals are jumpered
longer than 2 sec, LED will flash rapidly and ignore component test request. Component test sequence is as follows:
a. LED will display previous status code 4 times. b. Inducer motor starts and continues to run until Step f of
component test sequence.
c. After 7 seconds the hot surface igniter is energized for 15
sec, then off. d. Blower motor operates on HEAT speed for 10 sec. e. Blower motor operates on COOL speed for 10 sec. f. Inducer motor stops.
5. Reconnect R lead to furnace control, remove tape from blower door switch, and re-install blower door.
6. Operate furnace per instruction on outer door.
7. Verify furnace shut down by lowering thermostat setting below room temperature.
8. Verify that furnace restarts by raising thermostat setting above room temperature.
START-UP PROCEDURES
I. GENERAL
1. Furnace must have a 115-v power supply properly con­nected and grounded. Proper polarity must be maintained for correct operation.
1. Remove upper inducer housing drain connection cap. (See Fig. 48)
2. Connect field-supplied 1/2-in. ID tube to upper inducer housing drain connection.
3. Insert field-supplied funnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run through inducer housing, overfill condensate trap, and flow into open field drain. (See Fig. 49.)
5. Remove funnel and tube from inducer housing and replace drain connection cap and clamp.
III. PURGE GAS LINES
WARNING: Never purge a gas line into a combustion
chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. Failure to follow this warning could result in fire, explosion, personal injury, or death.
If not previously done, purge lines after all connections have been made and check for leaks.
IV. ADJUSTMENTS A. Set Gas Input Rate
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft.
In the U.S.A., the input ratings for altitudes above 2000 ft must be reduced by 2 percent for each 1000 ft above sea level.
In Canada, the input ratings must be derated by 5 percent for altitudes of 2000 ft to 4500 ft above sea level.
Furnace input rate must be within ±2 percent of input on furnace rating plate adjusted for altitude.
—36—
Page 37
c. Verify furnace model and size. Table 9 can only be used
for model 340MAV furnaces with heating sizes of 040 through 120. Table 10 can only be used for model 340MAV furnaces with a heating size of 140.
d. Find installation altitude in Table 9 or 10.
NOTE: For Canada altitudes of 2000 to 4500 ft, use U.S.A. altitudes of 2001 to 3000 ft in Table 9 or 10.
e. Find closest natural gas heat value and specific gravity in
Table 9 or 10.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and manifold pressure settings for proper operation.
REGULATOR SEAL CAP
REGULATOR ADJUSTMENT SCREW
ON/OFF SWITCH
Fig. 48—Inducer Housing Drain Cap
A99118
INLET PRESSURE T AP
REGULATOR SPRING (PROPANE - WHITE, 6 TURNS NATURAL - SILVER, 10 TURNS)
GAS PRESSURE REGULATOR ADJUSTMENT
MANIFOLD PRESSURE T AP
Fig. 50—Redundant Automatic Gas Valve
A03142
Fig. 49—Filling Condensate Trap
1. Determine natural gas orifice size and manifold pressure for correct input.
a. Obtain average gas heat value (at installed altitude) from
local gas supplier.
b. Obtain average gas specific gravity from local gas
supplier.
A99119
BURNER
ORIFICE
A93059
Fig. 51—Burner Orifice
CAUTION: DO NOT redrill orifices. Improper drilling
(burrs, out-of-round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of burners and heat exchang­ers causing failures. (See Fig. 51.)
—37—
Page 38
TABLE 9—MODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT
FOR USE WITH 040 THROUGH 120 SIZE FURNACES ONLY
(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
0 925 44 3.5 44 3.7 44 3.8 43 3.4 43 3.5
to 975 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6
2000 1025 45 3.5 45 3.6 45 3.7 44 3.2 44 3.3
U.S.A. and Canada
0% 1075 45 3.2 45 3.3 45 3.4 45 3.5 45 3.6
derate 1100 47 3.6 47 3.7 45 3.2 45 3.4 45 3.5
ALTITUDE
RANGE
(FT)
U.S.A. 775 43 3.8 42 3.2 42 3.3 42 3.4 42 3.5
Altitudes 800 43 3.5 43 3.7 43 3.8 42 3.2 42 3.3
2001 to 825 44 3.8 43 3.4 43 3.6 43 3.7 43 3.8
3000 850 44 3.6 44 3.7 44 3.8 43 3.5 43 3.6
or 875 44 3.4 44 3.5 44 3.6 44 3.7 43 3.4
Canada 900 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6
Altitudes 925 45 3.7 45 3.8 44 3.2 44 3.3 44 3.4
2001 to 950 45 3.5 45 3.6 45 3.7 45 3.8 44 3.3
U.S.A. and Canada
4500 975 45 3.3 45 3.4 45 3.5 45 3.6 45 3.8
5% 1000 45 3.1 45 3.2 45 3.4 45 3.5 45 3.6
derate 1025 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
ALTITUDE
RANGE
(FT)
3001 825 44 3.5 44 3.6 44 3.8 43 3.4 43 3.5
to 875 45 3.8 44 3.2 44 3.3 44 3.5 44 3.6
U.S.A. Only
4000 925 45 3.4 45 3.5 45 3.6 45 3.7 44 3.2
7% 975 45 3.0 45 3.2 45 3.3 45 3.4 45 3.5
derate 1000 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3
*Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
850 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 875 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2 900 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7
950 44 3.4 44 3.5 44 3.6 44 3.7 44 3.8
1000 45 3.7 45 3.8 44 3.2 44 3.4 44 3.5
1050 45 3.3 45 3.4 45 3.6 45 3.7 45 3.8
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
750 43 3.7 43 3.8 42 3.3 42 3.4 42 3.5 775 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2 800 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7
850 44 3.3 44 3.4 44 3.5 44 3.7 44 3.8
900 45 3.6 45 3.7 45 3.8 44 3.3 44 3.4
950 45 3.2 45 3.3 45 3.4 45 3.5 45 3.7
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—38—
Page 39
TABLE 9—MODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT (Continued)
FOR USE WITH 040 THROUGH 120 SIZE FURNACES ONLY
(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
4001 775 44 3.7 44 3.8 43 3.4 43 3.5 43 3.7
to 825 44 3.2 44 3.4 44 3.5 44 3.6 44 3.7
5000 875 45 3.5 45 3.6 45 3.7 44 3.2 44 3.3
U.S.A. Only
0% 925 45 3.1 45 3.2 45 3.3 45 3.4 45 3.6
derate 950 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
ALTITUDE
RANGE
(FT)
5001 800 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6
to 850 45 3.4 45 3.5 45 3.6 45 3.8 44 3.2
U.S.A. Only
6000 900 45 3.0 45 3.1 45 3.3 45 3.4 45 3.5
11% 975 45 2.6 45 2.7 45 2.8 45 2.9 45 2.9
derate 1000 45 2.5 45 2.5 45 2.6 45 2.7 45 2.8
ALTITUDE
RANGE
(FT)
6001 700 44 3.8 43 3.4 43 3.6 43 3.7 43 3.8
to 750 44 3.3 44 3.4 44 3.6 44 3.7 44 3.8
7000 800 45 3.5 45 3.7 45 3.8 44 3.2 44 3.3
U.S.A. Only
13% 850 45 3.1 45 3.2 45 3.4 45 3.5 45 3.6
derate 875 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
*Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
725 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 750 43 3.4 43 3.5 43 3.7 43 3.8 42 3.2
800 44 3.5 44 3.6 44 3.7 44 3.8 43 3.4
850 45 3.7 45 3.8 44 3.3 44 3.4 44 3.5
900 45 3.3 45 3.4 45 3.5 45 3.6 45 3.8
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
700 43 3.6 43 3.7 42 3.2 42 3.3 42 3.4 725 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8 750 44 3.6 44 3.7 43 3.4 43 3.5 43 3.6 775 44 3.4 44 3.5 44 3.6 44 3.7 43 3.4
825 45 3.6 45 3.7 44 3.2 44 3.3 44 3.4
875 45 3.2 45 3.3 45 3.4 45 3.6 45 3.7
925 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3 950 45 2.7 45 2.8 45 2.9 45 3.0 45 3.1
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
650 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6 675 43 3.6 43 3.7 43 3.8 42 3.2 42 3.3
725 44 3.6 44 3.7 44 3.8 43 3.4 43 3.5
775 45 3.8 44 3.2 44 3.3 44 3.4 44 3.5
825 45 3.3 45 3.4 45 3.6 45 3.7 45 3.8
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—39—
Page 40
TABLE 9—MODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT (Continued)
FOR USE WITH 040 THROUGH 120 SIZE FURNACES ONLY
(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
7001 675 44 3.8 43 3.4 43 3.5 43 3.6 43 3.7
to 725 44 3.3 44 3.4 44 3.5 44 3.6 44 3.7
8000 775 45 3.5 45 3.6 45 3.7 45 3.8 44 3.3
U.S.A. Only
15% 825 45 3.1 45 3.2 45 3.3 45 3.4 45 3.5
derate 850 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3
ALTITUDE
RANGE
(FT)
8001 625 43 3.5 43 3.6 43 3.8 42 3.2 42 3.3
to 675 44 3.5 44 3.6 44 3.7 44 3.8 43 3.4
9000 725 45 3.6 45 3.8 44 3.2 44 3.3 44 3.4
U.S.A. Only
17% 775 45 3.2 45 3.3 45 3.4 45 3.5 45 3.6
derate 800 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
ALTITUDE
RANGE
(FT)
9001 600 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3
to 650 44 3.4 44 3.5 44 3.7 44 3.8 43 3.4
10,000 700 45 3.6 45 3.7 45 3.8 44 3.3 44 3.4
U.S.A. Only
19% 750 45 3.1 45 3.2 45 3.3 45 3.4 45 3.5
derate 775 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3
*Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
625 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6 650 43 3.5 43 3.7 43 3.8 42 3.2 42 3.3
700 44 3.5 44 3.6 44 3.8 43 3.4 43 3.5
750 45 3.7 45 3.8 44 3.3 44 3.4 44 3.5
800 45 3.3 45 3.4 45 3.5 45 3.6 45 3.7
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
600 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6
650 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7
700 44 3.2 44 3.3 44 3.4 44 3.6 44 3.7
750 45 3.4 45 3.5 45 3.6 45 3.8 44 3.2
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
575 43 3.8 42 3.2 42 3.3 42 3.5 42 3.6
625 44 3.7 44 3.8 43 3.5 43 3.6 43 3.7
675 45 3.8 44 3.3 44 3.4 44 3.5 44 3.6
725 45 3.3 45 3.4 45 3.6 45 3.7 45 3.8
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—40—
Page 41
TABLE 10—MODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT
FOR USE WITH 140 SIZE FURNACES ONLY
(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
0 925 42 3.4 42 3.5 42 3.6 42 3.7 42 3.8
to 975 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
2000 1025 43 3.3 43 3.4 43 3.6 43 3.7 43 3.8
U.S.A. and Canada
0% 1075 44 3.5 44 3.6 43 3.2 43 3.3 43 3.4
derate 1100 44 3.3 44 3.4 44 3.5 43 3.2 43 3.3
ALTITUDE
RANGE
(FT)
U.S.A. 775 41 3.7 41 3.8 40 3.6 40 3.7 39 3.6
Altitudes 800 42 3.8 41 3.6 41 3.7 41 3.8 40 3.6
2001to 825 42 3.6 42 3.7 41 3.5 41 3.6 41 3.7
3000 850 42 3.4 42 3.5 42 3.6 42 3.7 41 3.5
or 875 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6 Canada 900 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 Altitude 925 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3 2001 to 950 43 3.3 43 3.4 43 3.5 43 3.7 43 3.8
U.S.A. and Canada
4500 975 43 3.1 43 3.3 43 3.4 43 3.5 43 3.6
5% 1000 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
derate 1025 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
ALTITUDE
RANGE
(FT)
3001 825 42 3.3 42 3.4 42 3.6 42 3.7 42 3.8
to 875 43 3.6 43 3.7 42 3.2 42 3.3 42 3.4
U.S.A. Only
4000 925 43 3.2 43 3.3 43 3.5 43 3.6 43 3.7
7% 975 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
derate 1000 43 2.8 43 2.9 43 3.0 43 3.0 43 3.1
*Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
850 41 3.6 41 3.7 41 3.8 40 3.6 40 3.8 875 42 3.8 41 3.5 41 3.6 41 3.7 41 3.8 900 42 3.5 42 3.7 42 3.8 41 3.5 41 3.6
950 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6
1000 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3
1050 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
750 41 3.6 41 3.8 40 3.6 40 3.7 40 3.8 775 42 3.8 41 3.5 41 3.6 41 3.7 40 3.6 800 42 3.5 42 3.7 42 3.8 41 3.5 41 3.6
850 43 3.8 42 3.2 42 3.4 42 3.5 42 3.6
900 43 3.4 43 3.5 43 3.6 43 3.8 42 3.2
950 43 3.1 43 3.2 43 3.3 43 3.4 43 3.5
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—41—
Page 42
TABLE 10—MODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT (Continued)
FOR USE WITH 140 SIZE FURNACES ONLY
(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(FT)
4001 775 42 3.5 42 3.6 42 3.7 42 3.8 41 3.6
to 825 43 3.7 42 3.2 42 3.3 42 3.4 42 3.5
5000 875 43 3.3 43 3.4 43 3.6 43 3.7 43 3.8
U.S.A. Only
9% 925 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
derate 950 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
ALTITUDE
RANGE
(FT)
5001 800 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
to 850 43 3.3 43 3.4 43 3.5 43 3.6 43 3.7
U.S.A. Only
6000 900 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
11% 975 43 2.5 43 2.6 43 2.6 43 2.7 43 2.8
derate 1000 43 2.3 43 2.4 43 2.5 43 2.6 43 2.7
ALTITUDE
RANGE
(FT)
6001 700 42 3.6 42 3.7 41 3.5 41 3.6 41 3.7
to 750 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6
7000 800 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8
U.S.A. Only
13% 850 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
derate 875 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
*Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
725 41 3.6 41 3.7 41 3.8 40 3.6 40 3.8 750 42 3.7 42 3.8 41 3.6 41 3.7 41 3.8
800 42 3.3 42 3.4 42 3.5 42 3.6 42 3.7
850 43 3.5 43 3.6 43 3.8 42 3.2 42 3.3
900 43 3.1 43 3.3 43 3.4 43 3.5 43 3.6
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
700 41 3.5 41 3.7 41 3.8 40 3.6 40 3.7 725 42 3.7 42 3.8 41 3.5 41 3.6 41 3.8 750 42 3.4 42 3.5 42 3.7 42 3.8 41 3.5 775 42 3.2 42 3.3 42 3.4 42 3.5 42 3.7
825 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2
875 43 3.1 43 3.2 43 3.3 43 3.4 43 3.5
925 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1 950 43 2.6 43 2.7 43 2.8 43 2.9 43 3.0
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
650 41 3.8 40 3.6 40 3.7 40 3.8 39 3.7 675 41 3.5 41 3.6 41 3.7 40 3.6 40 3.7
725 42 3.4 42 3.5 42 3.6 42 3.7 42 3.8
775 43 3.6 43 3.7 43 3.8 42 3.3 42 3.4
825 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—42—
Page 43
EXAMPLE: (0—2000 ft altitude using Table 9) Heating value = 1050 Btu/cu ft Specific gravity = 0.62 Therefore: Orifice No. 45
Manifold pressure 3.6-in. wc * Furnace is shipped with No. 45 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain the proper input rate.
Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE; ALWAYS CHECK AND VERIFY.
2. Adjust manifold pressure to obtain input rate.
NOTE: Manifold pressure must always be measured with burner enclosure front REMOVED. Gas meter must always be clocked with burner enclosure front INSTALLED.
a. Remove burner enclosure front. b. Remove cap that conceals adjustment screw for gas
valve regulator. (See Fig. 50.)
c. Jumper R and W thermostat connections on control to
start furnace operation.
d. Turn adjusting screw, counterclockwise (out) to decrease
manifold pressure or clockwise (in) to increase manifold pressure.
NOTE: This furnace has been approved for a manifold pressure of 3.2 in. wc to 3.8 in. wc when installed at altitudes up to 2000 ft. For altitudes above 2000 ft, the manifold pressure can be adjusted from 2.0 in. wc to 3.8 in. wc. If manifold pressure is outside this range, change burner orifices to obtain pressure in this range.
CAUTION: DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.
e. Replace gas valve regulator adjustment screw cap. f. Replace burner enclosure front and verify adjusted gas
input rate using method outlined in item 3.
g. Look through sight glass in burner enclosure and check
burner flame. Burner flame should be clear blue, almost transparent. (See Fig. 52.)
h. Remove jumper from R and W.
BURNER FLAME
BURNER
TABLE 11—ALTITUDE DERATE MULTIPLIER
ALTITUDE (FT)
0—2000 0 1.00 2001—3000 4—6 0.95 3001—4000 6—8 0.93 4001—5000 8—10 0.91 5001—6000 10—12 0.89 6001—7000 12—14 0.87 7001—8000 14—16 0.85 8001—9000 16—18 0.83 9001—10,000 18—20 0.81
* Derate multiplier factor is based on midpoint altitude for altitude range.
%OF DERATE
DERATE MULTIPLIER FACTOR FOR U.S.A.*
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion-air and vent pipes, and burner enclosure front are in place when checking input by clocking gas meter.
a. Calculate high-altitude adjustment (if required).
UNITED STATES At altitudes above 2000 ft, this furnace has been ap-
proved for a 2% derate for each 1000 ft above sea level. See Table 11 for derate multiplier factor.
EXAMPLE: 100,000 BTUH INPUT FURNACE INSTALLED AT
4300 FT.
Furnace Input Rate
at Sea Level
100,000 X 0.91 = 91,000
X
Derate
Multiplier
Factor
Furnace Input Rate
=
at Installation
Altitude
CANADA At installation altitudes from 2000 to 4500 ft, this
furnace must be derated 5% by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example above and use 0.95 as derate multiplier factor.
b. Reinstall burner box cover. c. Gas valve regulator seal cap MUST be installed. d. Turn off all other gas appliances and pilots. e. Start furnace and let operate for 3 minutes. f. Measure time (in sec) for gas meter test dial to complete
1 revolution. g. Refer to Table 12 for cu ft of gas per hr. h. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)
using natural gas heating value from local gas utility/supplier.
MANIFOLD
Fig. 52—Burner Flame
A89020
—43—
Page 44
EXAMPLE: (0—2000 ft altitude) Furnace input from rating plate is 100,000 Btuh. Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 975 Btu/cu ft Time for 1 revolution of 2-cu ft dial = 70 sec Gas rate = 103 cu ft/hr (from Table 12) Btu heating input = 103 X 975 = 100,425 Btuh In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate.
TABLE 13—SPEED SELECTOR
COLOR SPEED
Black High Cool
Yellow (When Present) Medium High Spare
Blue Medium Low Heat
Red Low Spare
White Common C
FACTORY­SHIPPED CONNECTION
OM
B. Set Temperature Rise
CAUTION: Temperature rise must be within limits
specified on furnace rating plate. Recommended opera­tion is at midpoint of rise range or slightly above. Failure to follow this caution may result in primary and second­ary heat exchangers failure.
Determine and adjust air temperature rise as follows:
1. Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings. This practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.
3. Adjust temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise.
TABLE 12—GAS RATE (CU FT/HR)
SECONDS FOR 1 REVOLUTION 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49
SIZE OF TEST DIAL
1 cu ft2cu ft5cu ft 360
720
327
655
300
600
277
555
257
514
240
480
225
450
212
424
200
400
189
379
180
360
171
343
164
327
157
313
150
300
144
288
138
277
133
267
129
257
124
248
120
240
116
232
113
225
109
218
106
212
103
206
100
200
97
195
95
189
92
185
90
180
88
176
86
172
84
167
82
164
80
160
78
157
76
153
75
150
73
147
1800 1636 1500 1385 1286 1200 1125 1059 1000 947 900 857 818 783 750 720 692 667 643 621 600 581 563 545 529 514 500 486 474 462 450 439 429 419 409 400 391 383 375 367
SECONDS FOR 1 REVOLUTION 50 51 52 53 54 55 56 57 58 59 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 116 120 124
SIZE OF TEST DIAL
1 cu ft2cu ft5cu ft 72
144
71
141
69
138
68
136
67
133
65
131
64
129
63
126
62
124
61
122
60
120
58
116
56
112
54
109
53
106
51
103
50
100
48
97
47
95
46
92
45
90
44
88
43
86
42
84
41
82
40
80
39
78
38
76
38
75
37
74
36
72
35
71
35
69
34
68
33
67
33
65
32
64
31
62
30
60
29
58
360 355 346 340 333 327 321 316 310 305 300 290 281 273 265 257 250 243 237 231 225 220 214 209 205 200 196 192 188 184 180 178 173 170 167 164 161 155 150 145
TABLE 14–BLOWER OFF DELAY SETUP POSITION
PINS 1 AND 2 2 AND 3 3 AND 4 4 AND 5
Time (in sec) 90 120 150 180
WARNING: Disconnect 115-v electrical power before
changing speed tap. Failure to follow this warning could result in personal injury.
4. To change blower motor speed selections for heating mode, remove blower motor lead from control center HEAT terminal. (See Fig. 31.) Select desired blower motor speed lead from 1 of the other motor leads and relocate it to HEAT terminal. See Table 13 for lead color identification. Recon­nect original lead on SPARE terminal.
Follow this same procedure for proper selection of COOL speed selection.
C. Blower Off Delay (Heat Mode)
The blower off delay has 4 adjustable settings from 90 sec to 180 sec. (See Table 14.) The blower off delay jumpers are located on the furnace control board (See Fig. 31). To change the blower off delay setting, move the jumper from one set of pins on the control board to the pins used for the desired blower off delay. Factory blower off delay setting is 120 sec.
D. Set Thermostat Heat Anticipator
When using a nonelectronic thermostat, the thermostat heat anticipator must be set to match amp draw of the electrical components in R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 53 illustrates an easy method of obtaining actual amp draw. The amp reading should be taken after blower motor has started and furnace is heating. Connect ammeter wires as shown in Fig. 53.
The thermostat anticipator ahould NOT be in the circuit while measuring current. If thermostat has no subbase, the thermostat must be disconnected from R and W wires during current measurement. See thermostat manufacturer’s instructions for ad­justing heat anticipator and for varying heating cycle length.
For an electronic thermostat, set cycle rate for 3 cycles per hour.
CHECK SAFETY CONTROLS
This section covers the safety controls that must be checked before the installation is complete. The flame sensor, gas valve, and pressure switch were all checked in the Start-up procedure section as part of normal operation.
—44—
Page 45
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED
HOOK-AROUND
VOLT/AMMETER
R Y W G
10 TURNS
FROM UNIT 24-VOLT TERMINAL BLOCK
CHECKLIST
1. Put away tools and instruments. Clean up debris.
2. Verify flame rollout manual reset switch has continuity.
3. Verify that blower and main access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instruc­tions.
6. Review User’s Guide with owner.
7. Leave literature packet near furnace.
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
= 0.5 AMPS FOR THERMOSTAT SETTING
A80201
Fig. 53—Amp Draw Check with Ammeter
I. CHECK PRIMARY LIMIT CONTROL
This control shuts off gas control system and energizes air­circulating blower motor if furnace overheats. Recommended method of checking this limit control is to gradually block off return air after furnace has been operating for a period of at least 5 minutes. As soon as limit control has shut off burners, return-air opening should be unblocked to permit normal air circulation. By using this method to check limit control, it can be established that limit is functioning properly and operates if there is a restricted return-air duct or motor failure. If limit control does not function during this test, cause must be determined and corrected.
II. CHECK PRESSURE SWITCH
This control proves operation of draft inducer. Check switch operation as follows:
1. Turn off 115-v power to furnace.
2. Remove main furnace door and disconnect inducer motor lead wires from wire harness.
3. Turn on 115-v power to furnace.
4. Set thermostat to call for heat and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow, and control status code LED flashes a Status Code 31. If hot surface igniter glows when inducer motor is disconnected, shut furnace down immediately. Determine reason pressure switch did not function properly and correct condition.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor leads, reinstall main furnace door, and turn on 115-v power supply.
—45—
Page 46
LOAD CALCULATION
CHECKLIST—INSTALLATION
Condensate Drain
____________ Heating Load (Btuh)
____________ Cooling Load (Btuh)
____________ Furnace Model Selection
COMBUSTION AIR VENT PIPING
Termination Location
________ Roof or Sidewall
________ Termination Kit-2 Pipe or Concentric
________ Combustion-Air Pipe Length
________ Combustion-Air Elbow Quantity
________ Vent Pipe Length
________ Vent Pipe Elbow Quantity
________ Pipe Diameter Determined from Sizing Table
________ Pipe Sloped To Furnace
________ Unit Level or Pitched Forward
________
________
________ Condensate Trap Primed before Start-Up
________ Heat Tape Installed if Required
________
________ Temperature Rise Adjusted
________ Anticipator Setting Adjusted or
________ Cycle Rate (3 Cycles per Hr) Selected
Internal Tubing Connections Free of Kinks and Traps
External Drain Connection Leak Tight and Sloped
CHECKLIST—START-UP
Gas Input Rate (Set Within 2 percent of Rating Plate)
Thermostat Anticipator
Safety Controls Check Operation
Pipe Insulation
________ Over Ceilings
________ Low-Ambient Exposed Pipes
________ Primary Limit
________ Pressure Switch
—46—
Page 47
—47—
Page 48
© 2003 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—48—
Printed in U.S.A. 340m4011 Catalog No. 5334-016
Loading...