Bryant Series C Installation, Start-up, And Operating Instructions Manual

Installation, Start-up, and Operating Instructions
MULTIPOISE OIL FURNACE
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
INTRODUCTION..........................................................................2
LOCATION....................................................................................3
General......................................................................................3
INSTALLATION...........................................................................3
Air for Combustion and Ventilation........................................3
General......................................................................................4
Unconfined Space.....................................................................4
Confined Space.........................................................................4
All Air from Inside the Structure .......................................4
All Air from Outside of Structure......................................4
Duct Work Recommendations............................................5
Venting.................................................................................5
Oil Burner............................................................................6
Oil Connections...................................................................6
Barometric Draft Control....................................................6
Electrical Connections.........................................................6
Horizontal or Downflow Installation..................................6
Filters ...................................................................................7
START-UP, ADJUSTMENT, AND SAFETY CHECKOUT......7
Operational Checkout ...............................................................7
Combustion Check....................................................................7
Fan Adjustment Check ...........................................................10
Limit Control Check...............................................................10
For Year-Round Air Conditioning.........................................10
Heating....................................................................................10
Cooling....................................................................................10
Constant Blower Switch.........................................................10
MAINTENANCE.........................................................................10
General....................................................................................10
Oil Burner ...............................................................................11
Heat Exchanger and Flue Pipe...............................................11
Blower Removal .....................................................................11
SAFETY CONSIDERATIONS
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VI­CINITY OF THIS OR ANY OTHER APPLIANCE. DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED, WHEN THE FURNACE IS FULL OF VAPOR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT.
369AAN
Series C
Cancels: II 369A-105-4 II 369A-105-5
11-03
A97247
Fig. 1—369AAN Multipoise Oil Furnace
WARNING: For use with grade 1 or 2 Fuel Oil. Do not
use Gasoline, Crankcase Oil, or any Oil containing Gasoline! Failure to follow this warning could lead to sooting, fire, explosion, and/or severe bodily harm.
CAUTION: Never burn garbage or paper in the heating system and never leave rags, paper, or any flammable items around the unit. Failure to follow this caution will result in minor unit or property damage.
CAUTION: These instructions are intended to be used by qualified personnel who have been trained in installing this type of furnace. Installation of this furnace by an unqualified person may lead to equipment damage and/or a hazardous condition which may lead to bodily harm.
All local and national code requirements governing installation of oil burning equipment, wiring, and flue connections must be followed. Some of the codes (issued by the Canadian Standards Association, the National Fire Protection Agency, and/or the American National Standards Institute) that may be applicable are:
—1—
A
TOP KNOCK-OUT FOR J DIAM VENT
19
3
E
20
G
KNOCK-OUT BOTH SIDES
FOR J DIAM VENT
VENT CONN
B
OIL INLET (BOTH SIDES)
19
PULL
C
2
D
L
H
ELECTRICAL CONNECTIONS (BOTH SIDES) .88 DIAM TYP
F
20
K
A98037
DIMENSIONS (IN.)
UNIT SIZE ABCDEFGHJKL
036105 35 48-3/4 30-1/4 16-5/8 20 22 12 14 5 1-1/2 1-3/4 060120 39-1/2 53 32-1/4 18-3/4 24 28 12-9/32 16 6 1-5/8 1-1/2
Fig. 2—Dimensional Drawing
Understand the signal words DANGER, WARNING, CAUTION
ANSI/NFPA 31:
ANSI/NFPA 211:
ANSI/NFPA 90B:
ANSI/NFPA 70: NATIONAL ELECTRICAL CODE
CSA B139:
CAS C22.1: CANADIAN ELECTRICAL CODE
INSTALLATION OF OIL BURNING EQUIPMENT
CHIMNEYS, FIREPLACES, VENTS, AND SOLID FUEL BURNING APPLIANCES
WARM AIR HEATING AND AIR CONDITIONING SYSTEMS
INSTALLATION CODE FOR OIL BURNING EQUIPMENT
Only the latest issues of these codes should be used, and are available from either The National Fire Protection Agency, Bat­terymarch Park, Quincy, MA 02269 or The Canadian Standards Association, 178 Rexdale Blvd., Rexdale, Ontario M9W 1R3
Recognize safety information. This is the safety-alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
.
and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
The model 369AAN Furnaces are available in 2 sizes. Each size unit is capable of 3 heat/airflow combinations by a simple nozzle change. Unit 036105 covers inputs of 70,000, 91,000, and 105,000 Btuh, and unit 060120 covers inputs of 119,000, 140,000 and 154,000 Btuh. This eliminates the need to stock 6 separate units
This furnace is a multipoise unit. It may be installed in the upflow, downflow or horizontal configuration.
The furnace is shipped as a packaged unit, complete with burner and controls. It requires a line voltage (115 vac) connection to control box, a thermostat hook-up as shown on wiring diagram, oil line connection(s), adequate duct work, and connection to a properly sized vent.
—2—
TABLE 1—MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS (IN.)
UNIT APPLICATION UPFLOW DOWNFLOW HORIZONTAL
Furnace 0 2 2
Sides
Back Service Clearance 0 1 0
Top
Bottom 00* 0* Flue
Pipe Front 88 24
* Use approved subbase for combustible floor. NOTE: Adequate service clearances should be provided over and above these dimensions as required.
The air handling capacity of this furnace is designed for cooling airflow. Refer to Table 12 for expected airflows at various external duct static pressures.
I. GENERAL
Supply Plenum and Warm-Air Duct Within 6 ft of Furnace
Furnace Casing or Plenum 2 2 2 Horizontal Warm-Air Duct Within 6 ft of
Furnace
Horizontally or Below Pipe 4 4 4 Vertically Above Pipe 9 9 9
12 1
22 3
The furnace should be located as close as possible to chimney or vent in order to keep vent connections short and direct. The furnace should also be located as near as possible to center of air
LOCATION
distribution system.
II. LOCATION RELATIVE TO COOLING EQUIPMENT
WARNING: This furnace is not water tight and is not
designed for outdoor installation. This furnace shall be installed in such a manner as to protect electrical com­ponents from water. Outdoor installation would lead to a hazardous electrical condition and to premature furnace failure.
WARNING: Do not use this furnace as a construction heater. Use of this furnace as a construction heater exposes furnace to abnormal conditions, contaminated combustion air, and lack of air filters. Failure to follow this warning can lead to premature furnace failure and/or vent failure which could result in a fire hazard and/or bodily harm.
CAUTION: For attic installation, it is important to keep insulation 12 in. or more away from any furnace open­ings. Some types of insulating materials may be combus­tibles and may cause a fire hazard and property damage.
This furnace is approved for reduced clearances to combustible construction, therefore, it may be installed in a closet or similar enclosure. Since this unit may be installed in an upflow, counter­flow, or horizontal position, it may be located in a basement or on the same level as area to be heated. In any case, unit should always be installed level.
In a basement, or when installed on floor (as in a crawlspace), it is recommended that unit be installed on a concrete pad that is 1 in. to 2 in. thick.
When installed in counterflow position, furnace must not be installed on combustible flooring, unless approved subbase is used. Also, since flue pipe is in a counterflow position, Downflow Conversion/Vent Guard Kit MUST be used. (Also, read page 9.)
When installed in a horizontal position, furnace may be suspended by using an angle iron frame, as long as total weight of both furnace and frame are allowed for in support calculations. (Other methods of suspending are acceptable.) When installed in the Horizontal Position, this furnace must not be installed on combus­tible flooring, unless the approved Horizontal Subbase is used.
The required minimum clearances for furnace are specified in Table 1.
When installing furnace with cooling equipment for year-round operation, the following recommendations must be followed for series or parallel airflow:
1. In series airflow applications, coil is mounted after furnace in an enclosure in supply-air stream. The furnace blower is used for both heating and cooling airflow.
WARNING: The coil MUST be installed on air dis­charge side of furnace. Under no circumstances should airflow be such that cooled, conditioned air can pass over furnace heat exchanger. This will cause condensation in heat exchanger and possible failure of heat exchanger which could lead to a fire hazard and/or a hazardous condition which may lead to bodily harm. Heat exchanger failure due to improper installation may not be covered by warranty.
2. In parallel airflow applications, dampers must be provided to direct air over furnace heat exchanger when heat is desired and over cooling coil when cooling is desired.
IMPORTANT: The dampers should be adequate to prevent cooled air from entering furnace. If manually operated, dampers must be equipped with a means to prevent operation of either cooling unit or furnace unless damper is in full cool or heat position.
INSTALLATION
I. AIR FOR COMBUSTION AND VENTILATION
WARNING: Installation of this furnace in an area where
it will receive contaminated combustion air must be avoided. Such contamination would include the follow­ing: ammonia, chlorine, hydrogen sulfide, halogenated hydrocarbons, carbon tetrachloride, cleaning solvents, hydrochloric acid, water softening chemicals, and similar chemicals. Failure to follow this warning will lead to premature rusting of heat exchanger and possible prema­ture furnace failure and/or vent failure which could result in fire hazard and/or bodily harm.
—3—
WARNING: Do not block combustion-air openings in the furnace. Any blockage will result in improper com­bustion which may result in a fire hazard and/or cause bodily harm.
II. GENERAL
This furnace should be installed in a location in which facilities for ventilation permit satisfactory combustion of oil, proper venting, and maintenance of ambient temperature at safe limits under normal conditions of use. The location should not interfere with proper circulation of air within the confined space. (See NFPA-31, Section 1.5.)
In addition to air needed for combustion, process air shall be provided as required for: cooling of equipment or material, controlling dew point, heating, drying, oxidation or dilution, safety exhaust, and odor control.
In addition to air needed for combustion, air shall be supplied for ventilation, including all air required for comfort and proper working conditions for personnel.
The barometric draft regulator (included with furnace) shall be installed in same room or enclosure as furnace in such a manner as to prevent any difference in pressure between regulator and combustion-air supply.
Air requirements for operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion-air requirements.
The lack of a proper amount of combustion air can lead to serious furnace operational problems. Some of these problems are:
1. Excessive oil burner after-drip, and oil fumes.
2. Sooting.
3. Melted oil burner ignitor/relay control.
4. Air band or air turbulator settings more open than normal.
5. Lockouts on start-up.
The requirements for combustion and ventilation air depend upon whether furnace is located in a CONFINED or UNCONFINED space.
III. UNCONFINED SPACE
An unconfined space must have at least 50 cu ft for each 1000 Btuh of total input for all the appliances (such as furnaces, clothes dryers, water heaters, etc.) in the space.
In unconfined spaces in buildings of conventional frame, brick, or stone construction, infiltration MAY be adequate to provide air for combustion, ventilation, and dilution of flue gases. This determi­nation must be made on an individual installation basis and must take into consideration the overall volume of unconfined space, the number of windows and ventilation openings, the number of doors to the outside, internal doors which can close off unconfined space, and overall tightness of building construction. Consideration must also be given to the amount of storage items (furniture, boxes, etc.) within the unconfined space which take away from the air volume. (See Table 2.)
Many new buildings and homes (and older ones that have been weatherized) MUST BE considered as being of tight construction, therefore, infiltration will not be sufficient to supply necessary air for combustion and ventilation.
TABLE 2—MINIMUM FLOOR AREA
FOR UNCONFINED SPACE
369AAN FURNACE
INPUT BTUH
70,000 467
91,000 607 105,000 700 119,000 793 140,000 933 154,000 1026
MINIMUM SQ FT WITH
7-1/2 FT CEILING
A building can be considered as being of tight construction when:
• Walls and ceilings exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed or sealed, and/or
• Weatherstripping has been added on operable windows and doors, and/or
• Caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetra­tions for plumbing, electrical, and fuel lines, and at other openings.
If combustion and ventilation air must be supplied to an uncon­fined space from outside, an opening with a FREE AREA of not less than 1 sq in. per 1000 Btuh of total input of all appliances within unconfined space (but not less than 100 sq in.) must be provided. This opening must be located such that it cannot be blocked at any time.
IV. CONFINED SPACE
A confined space has a volume of less than 50 cu ft per 1000 Btuh of the total input rating for all appliances installed in that space.
When furnace is installed in a closet or enclosure, 2 ventilation openings, with OPEN AREA as dimensioned in example below are required for combustion air. The openings should be located about 6 in. from top and bottom of enclosure at front of furnace. (See Table 3.)
TABLE 3—COMBUSTION AIR
FROM CONFINED SPACE
369AAN FURNACE
INPUT BTUH
70,000-105,000 16 8
119,000 20 10
LENGTH
(IN.)
HEIGHT
(IN.)
NOTE: In calculating free area, consideration shall be given to
blocking effect of louvers, grilles, or screens protecting openings. Screens used shall not be smaller than 1/4-in. mesh and shall be readily accessible for cleaning. If free area through a louver or grille is known, it shall be used in calculating size and free area specified. If design and free area are not known, it may be assumed that wood louvers have 20 percent free area and metal louvers and grilles have 60 percent free area. Louvers shall be fixed in open position or interlocked with furnace so they open automatically at furnace start-up and remain open during furnace operation.
The size of the openings depends upon whether the air comes from outside of the structure or an unconfined space inside the structure.
A. All Air from Inside the Structure
For a confined space, where air is taken from an interior space, 2 permanent openings of equal area are required. One opening must be within 12 in. of ceiling and the other within 12 in. of floor. Each opening must have a free area of at least 1 sq in. per 1000 Btuh of total input rating but not less than 100 sq in. (See Table 4.)
B. All Air from Outside of Structure
If outside air is supplied to a confined space, then the 2 openings must be equal and located as above.
—4—
TABLE 4—COMBUSTION AIR
FROM UNCONFINED SPACE
369AAN FURNACE
INPUT BTUH
70,000 100
91,000 100 105,000 105 119,000 119 140,000 140 154,000 154
FREE AREA PER
OPENING
(SQ IN.)
1. If combustion air is taken through a permanent opening directly communicating with the outdoors, the opening shall have a minimum free area of 1 sq in. per 4000 Btuh of total input rating for all equipment in the enclosure.
2. If combustion air is taken from outdoors through vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of the total input for all equipment within the confined space. (See Table 5.)
TABLE 5—COMBUSTION AIR FROM OUTDOORS
THROUGH VERTICAL DUCTS
369AAN FURNACE
INPUT BTUH
70,000 17.5 5
91,000 22.8 6 105,000 26.3 6 119,000 29.8 6 140,000 35.0 6 154,000 38.5 6
FREE AREA PER
OPENING
(SQ IN.)
ROUND PIPE
(IN. DIAM)
3. If combustion air is taken from outdoors through horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of the total input for all equipment within the confined space. (See Table 6.)
TABLE 6—COMBUSTION AIR FROM OUTDOORS
THROUGH HORIZONTAL DUCTS
369AAN FURNACE
INPUT BTUH
70,000 35.0 7
91,000 45.5 8 105,000 52.5 9 119,000 59.5 9 140,000 70.0 10 154,000 77.0 10
FREE AREA PER OPENING
(SQ IN.)
ROUND PIPE
(IN. DIAM)
When ducts are used to supply air, they must be of the same cross sectional area as free area of openings to which they connect.
The minimum dimension of rectangular air ducts must not be less than 3 in.
C. Duct Work Recommendations
WARNING: When supply ducts carry air circulated by
furnace to areas outside spaces containing furnace, return air MUST also be handled by a duct sealed to furnace casing and terminating outside space containing furnace. Incorrect duct work termination and sealing will create a hazardous condition which could lead to bodily harm.
CAUTION: Return-air grilles and warm air registers MUST NOT be obstructed. Failure to follow this caution will result in premature failure of heat exchanger.
The proper sizing of warm air ducts is necessary to ensure satisfactory furnace operation. Duct work should be in accordance with the latest editions of NFPA-90A (Installation of Air Condi­tioning and Ventilating Systems) and NFPA-90B (Warm Air Heating and Air Conditioning Systems) or Canadian equivalent.
The supply duct work should be attached to flanged front opening provided at discharge end of furnace. The return-air duct work should be attached to flanged rear opening of furnace. See Fig. 2 for dimensions of these openings.
NOTE: The back (blower access opening) should not be used for return air.
The following recommendations should be followed when install­ing duct work:
1. Install locking-type dampers in all branches of individual ducts to balance out system. Dampers should be adjusted to impose proper static at outlet of furnace
2. A flexible duct connector of noncombustible material should be installed at unit on both supply- and return-air systems. In applications where extremely quiet operation is necessary, the first 10 ft (if possible) of supply and return ducts should be internally lined with acoustical material.
3. In cases where return-air grille is located close to fan inlet, there should be at least one 90° air turn between fan inlet and grille. Further reduction in sound level can be accom­plished by installing acoustical air turning vanes or lining duct as described in item 2 above.
4. When a single air grille is used, duct between grille and furnace must be the same size as return opening in furnace.
D. Venting
Venting of furnace should be to the outside and in accordance with local codes or requirements of local utility.
OIL-FIRED APPLIANCES SHALL BE CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIANCE.
For additional venting information, refer to ANSI/NFPA 211 Chimney, Fireplaces, Vents, and Solid Fuel Burning Appliances and/or CSA B139 Installation Code.
This furnace is certified for use with Type Lvent (maximum flue gas temperature 575°F).
VENT SYSTEM INSPECTION
Before furnace is installed, it is highly recommended that any existing vent system be completely inspected.
For any chimney or vent, this should include the following:
1. Inspection for any deterioration in chimney or vent. If deterioration is discovered, chimney must be repaired or vent must be replaced.
2. Inspection to ascertain that vent system is clear and free of obstructions. Any blockage must be cleared before install­ing furnace.
3. Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace.
4. Confirming that all unused chimney or vent connections are properly sealed.
5. Verification that chimney is properly lined and sized per the applicable codes. (Refer to list of codes in Safety Consid­erations section.)
—5—
TABLE 7—ELECTRICAL DATA
UNIT SIZE
036105 115—60—1 132 104 12.2 14 26 15 060120 115—60—1 132 104 15.7 12 26 20
* Permissible limits of voltage range at which unit will operate satisfactorily. † Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ‡ Time-delay fuse is recommended.
VOLTS— HERTZ— PHASE—
OPERATING
VOLTAGE RANGE
Max.* Min.*
MAX UNIT
AMPS
MIN
WIRE
GAGE
MAX WIRE
LENGTH (FT)
MAX FUSE OR
CKT BKR AMPS
MASONRY CHIMNEYS
This furnace can be vented into an existing masonry chimney. This furnace must not be vented into a chimney servicing a solid fuel burning appliance. Before venting furnace into a chimney, the chimney MUST be checked for deterioration and repaired if necessary. The chimney must be properly lined and sized per local or national codes.
If furnace is vented into a common chimney, the chimney must be of sufficient area to accommodate the total flue products of all appliances vented into chimney.
The following requirements are provided for a safe venting system:
1. Be sure that chimney flue is clear of any dirt or debris.
2. Be sure that chimney is not servicing an open fireplace.
3. Never reduce pipe size below the outlet size of furnace. (See Fig. 2.)
4. All pipe should be supported using proper clamps and/or straps. These supports should be at least every 4 ft.
5. All horizontal runs of pipe should have at least 1/4-in. per ft of upward slope.
6. All runs of pipe should be as short as possible with as few turns as possible.
7. Seams should be tightly joined and checked for leaks.
8. The flue pipe must not extend into chimney but be flush with inside wall.
9. The chimney must extend 3 ft above highest point where it passes through the roof of a building and at least 2 ft higher than any portion of a building within a horizontal distance of 10 ft. It shall also be extended at least 5 ft above highest connected equipment flue collar.
10. Check local codes for any variance.
FACTORY-BUILT CHIMNEYS
Listed factory-built chimneys may be used. Refer to chimney manufacturer’s instructions for proper installation.
E. Oil Burner
This furnace is supplied with a high-pressure atomizing retention head-type burner (for use with grade 1 or 2 fuel oil). The mounting flange is fixed to burner air tube and no adjustment is required for insertion length.
F. Oil Connections
Complete instructions for installing fuel oil piping can be found in oil burner Installation Instructions included with furnace.
Oil line entry holes are provided in side panels. Two holes are provided in each location so that a 2-pipe system may be used if desired.
An oil filter should be used with all oil burners and should be installed as close to burner as possible.
G. Barometric Draft Control
The barometric draft control shipped with furnace MUST be used with furnace to ensure proper operation. Instructions for installing control are packed with control.
H. Electrical Connections
WARNING: The unit cabinet must have an uninter-
rupted or unbroken electrical ground to minimize per­sonal injury if an electrical fault should occur. A green ground screw is provided in control box for this connec­tion.
115-V WIRING
Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 for equipment electrical specifications. Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2001 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or subauthorities having jurisdiction.
CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. Failure to follow this caution will lead to intermittent electrical operation and/or fire hazard.
The control system depends on correct polarity of power supply. Connect HOT wire (H) and NEUTRAL wire (N) as shown in Fig. 3or4. A separate line voltage supply MUST be used with a fused disconnect switch or circuit breaker between main power panel and unit. (See Fig. 3 or 4.) Metallic conduit (where required/used) may terminate at side panel of unit. It is not necessary to extend conduit inside unit from side panel to control box. When replacing any original furnace wiring, use only 105°C No. 14 AWG copper wire.
24-V WIRING
Instructions for wiring thermostat (field supplied) are packed in thermostat box. Make thermostat connections as shown in Fig. 3 or 4 at 24-v terminal board on fan timer board.
ACCESSORIES
When installing optional accessories to this appliance, follow manufacturer’s Installation Instructions included with accessory. Other than wiring for thermostat, wire with a minimum of type T insulation (63°F rise) must be used for accessories.
I. Horizontal or Downflow Installation
For horizontal installation, determine which sidewill become thetop, when the unit is laid down. Remove the flue pipe clearance
knock-out from the top of that side panel. Install the flue elbow so that it exits the cabinet of the furnace through that opening. For counterflow installation, the flue pipe must exit the cabinet through 1 of the side panel openings (as above), then extended up the side of the furnace. Insure that adequate clearances to com­bustibles are observed. Downflow Conversion/Vent Guard Kit MUST be used.
—6—
Remove burner by loosening mounting nuts and turn oil burner slightly counterclockwise to unlock the key hole burner flange. Prevent putting undue strain on burner wiring. (It may be neces­sary to disconnect burner wiring in some cases.)
To reinstall burner, insert on the four burner studs on key hole burner flange and turn it clockwise to lock it and tighten nuts.
IMPORTANT: Burner must always be installed in the upright position with ignition control on top.
J. Filters
WARNING: Never operate unit without a filter or with
filter access door removed. Failure to adhere to this warning could lead to a hazardous condition which could lead to equipment damage and bodily harm.
An external filter rack is provided as standard equipment with furnace. A sufficient clearance should be provided for air filter access. Refer to Table 8 for filter rack flange dimensions for return air duct.
2. The proper smoke number has been established by engi­neering tests to be between 0 and 1. This degree of smoke emission is commonly referred to as a traceof smoke. It is recommended to use a Bacharach true spot smoke test set or equivalent.
3. In order to ensure proper draft through furnace, a baromet­ric draft regulator (supplied with furnace) must be installed.
In order for this device to function properly, barometric damper must be mounted with hinge pins horizontal and face of damper vertical. (See instructions included with damper.) The draft regu­lator should be adjusted after furnace has been firing for at least 5 minutes, and set between -0.025 and -0.035 in. wc. (See Table 9.)
4. The over-fire draft, which is taken through observation door (located in center line above burner in front panel of furnace), is a measurement necessary to determine if there is a blockage between oil burner and flue outlet.
There should be a total pressure drop of between 0.020 and 0.05 in. wc through furnace as shown in Table 9. The over-fire draft must be set within the range shown in Table 9.
TABLE 8—FILTER AND FLANGE (IN.)
UNIT SIZE
036105
060120 20X30X1 19X29
AIR FILTER
SIZE
16x24x1
or
16X25X1
FLANGE OPENING
SIZE
15X23
START-UP, ADJUSTMENT, AND SAFETY CHECKOUT
I. OPERATIONAL CHECKOUT
WARNING: DO NOT TAMPER WITH UNIT OR
CONTROLS—CALL YOUR SERVICE TECHNICIAN. Failure to follow this warning could result in personal and/or property damage.
Installation of furnace is now complete. Run through the following checkout and ensure each item has been performed.
1. Correct nozzle size has been selected for desired input rate.
2. Blower wheel support is removed.
3. Electrical wiring is completed according to Fig. 3 or 4.
4. Blower access door is secured in place.
5. Valve on oil supply line is open.
6. RESET BUTTON on primary control is pushed down.
7. Flame observation door and 2 cleanout access doors located at front of unit are closed.
8. Thermostat is set for heating mode and set above room temperature.
If all of the above items have been performed, set main electrical switch to ON position and burner should start. When burner starts, proceed to Combustion Check section.
II. COMBUSTION CHECK
In order to obtain optimum performance from oil burner, the following setup procedures must be followed:
1. A test kit to measure smoke, stack draft, over-fire draft, oil pump pressure, CO
, and stack temperatures MUST be used
2
in order to obtain proper air band setting. Although all of the above measurements are required for optimum setup and efficiency data, the most important readings that must be taken are smoke number, over-fire draft, stack draft, and pump pressure.
TABLE 9—FURNACE DRAFT CONDITIONS (IN. WC)
FURNACE
INPUT
(BTUH)
70,000 -0.025 0.010 0.020 to 0.035
91,000 -0.025 0.020 0.030 to 0.045 105,000 -0.025 0.025 0.035 to 0.050 119,000 -0.025 0.025 0.035 to 0.050 140,000 -0.025 0.025 0.035 to 0.050 154,000 -0.025 0.025 0.035 to 0.050
FLUE
DRAFT
MINIMUM
OVER-FIRE
DRAFT
MAXIMUM
TOTAL RESTRICTION
THROUGH
HEAT EXCHANGER
A reading outside the range shown in Table 9 (for example +0.1 in. wc) would indicate that furnace is in an extremely high-pressure condition in primary section. This condition may be caused by any of the following problems:
a. Excessive combustion air due to air shutter being too
wide open.
b. A lack of flue draft (chimney effect) or some other
blockage, such as soot, in secondary section of heat
exchanger. c. Use of an oversized nozzle input. d. Pump pressure over values listed in Table 10.
5. The CO
and stack temperature instruments enable you to
2
obtain data required to determine thermal efficiency of furnace.
6. An oil filter should be installed as close to burner as possible with ALL oil burners and is essential on lower firing rate burners. We recommend the use of a low pressure drop oil filter such as the General Filter, Inc. model #1A-25A or equivalent.
7. The oil pressure regulator is factory set to give oil pressure of 130 psig for the model having 105,000 BTUH input and 130 psig for the model having 119,000 BTUH input. The firing rate noted on nameplate may be obtained using the nozzles and pump pressures indicated in Table 10.
8. On a new installation, air entrapped in oil line leading from tank to nozzle must be thoroughly purged in order to prevent excessive after drip. The oil pump is provided with a special fitting which allows purging of any air between tank and oil pump. The proper procedure for performing this operation is as follows:
a. Place a piece of clear plastic 1/4 in. diameter tubing over
purge fitting on oil pump.
—7—
N3
L2(N)
N6
HI
ELECTRONIC
AIR CLEANER
COOL (BLUE)
K2
EAC
GND
115 VAC 10 60Hz POWER SUPPLY
(FUSED DISCONNECT ON HOT LEG)
L1(H)
S2
JUMPER
HEAT
*
CMH
LO
ML
K2
K1
BLOWER
CIRCULATION
(BLACK)
(RED)
CONT
CN6-1 CN6-2 CN6-4
UNUSED MOT. LEAD
K1
CN6-9
L1 L2
OIL PRIM
CONTROL
CN6-7
LIMIT
1
CN6-4
BURNER
MOTOR &
TRANSFO.
HUMIDIFIER
CN6-8
HUM N7
(2)
S3 N4
120VAC
TRANSFO.
R
24VAC
CX
Y
W
LIMIT SENSE
CIRCULATION
PRIM
CN6-6
T1
THERMOSTAT
G
BLOWER
K1 K2
K3
CONTROL
CN6-3
T2
PRIMARY
2
C
CIRCULATION
CMH
HI
LO
ML
HEAT
(RED)
COOL (BLUE)
ST9103A ELECTR. FAN TIMER
3
BLOWER
(BLACK)
CONT
COOL (BLUE)
UNUSED MOT. LEAD
HI
MH
BLOWER
CIRCULATION
CML
LO
HEAT
(RED)
UNUSED MOT. LEAD
(BLACK)
A98060
CONT
2
CAPACITOR
LO
ML
1
GND
FAN CIRCULATING
CAPACITOR
WHITE
BLACK
HI
MH
120 VAC POWER SUPPLY
L1 (H)
L2 (N)
120 VAC 24 VAC
FUSE
BLACK
BLACK
FAN CIRCULATING
H
U
ST9103
R99G001
45
1233
UNUSED
WHITE
C
CONSTANT LOW SPEED SWITCH
TRANSFO.
VIOLET
MOTOR/
BURNER
TRANSFORMER
WHITE
BLACK
WHITE
M
7
6
N
H
C
CON
E
2
S
LEADS
ST9103
R99G001
45
1233
UNUSED
E
O
A
T
A
L
O
T
C
BLACK
X
H
U
BLACK
M
N
S
LEADS
HUM
IS 115V
TERMINAL
RED
BLUE
LIMIT
CONTROL
WHITE
RED
C
7
6
T
E
A
H
L
C
O
O
T
CON
E
A
C
2
3
2 TO
1
CAPACITOR
FAN CIRCULATING
ML
MH
F
F
O
ON
12
HI
OIL PRIMARY
CONTROL
GWRYC
LO
3 TONS MAX.
OIL INPUT : 0.65 USGPH
COOLING CAPACITY : 2
T
L1TL2
YELLOW
BLUE
RED
BLACK
WHITE
ORANGE
*JUMPER
HUM TERMINAL IS 115V
H
ST9103
R99G001
45
WHITE
1233
BLACK
UNUSED
WHITE
C
CONSTANT LOW SPEED SWITCH
CAD CELL
U
M
N
LEADS
HUM
7
6
H
C
CON
E
2
S
E
O
A
O
A
T
L
T
C
IS 115V
TERMINAL
RED
BLUE
BLACK
OIL INPUT : 0.50 USGPH
COOLING CAPACITY : 2 TONS
Fig. 3—Wiring Diagram (036105)
ML
MH
HI
LO
C
RED
CONSTANT LOW SPEED SWITCH
BLACK
BLUE
—8—
THERMOSTAT
G
WY R
STANDARD HEAT / COOL WIRING DIAGRAM
WITH ST9103 ELECTRONIC FAN TIMER
JUMPER: USE JUMPER ONLY WHEN THE COOLING
OIL INPUT : 0.75 USGPH
COOLING CAPACITY; 3 TONS MAX.
*
AND HEATING SPEEDS ARE SAME
N3
L2(N)
N6
HI
MH
ELECTRONIC
AIR CLEANER
COOL
K2
EAC
GND
115 VAC 10 60Hz POWER SUPPLY
(FUSED DISCONNECT ON HOT LEG)
L1(H)
S2
BLOWER
CIRCULATION
C
LO
ML
HEAT
K2
UNUSED MOT. LEAD
K1
CONT
K1
CN6-1 CN6-2 CN6-4
CN6-9
L1 L2
OIL PRIM
CONTROL
LIMIT(S)
CN6-7
BURNER
MOTOR &
TRANSFO.
CN6-4
CN6-8
HUMIDIFIER
HUM N7
1
R
TRANS
24VAC
120VAC
S3 N4
CX
Y
W
LIMIT SENSE
CIRCULATION
PRIM
CN6-6
T1
THERMOSTAT
G
BLOWER
K1 K2
K3
CONTROL
CN6-3
T2
PRIMARY
2
C
CIRCULATION
CMH
HI
LO
ML
HEAT
COOL
ST9103A ELECTR. FAN TIMER
3
BLOWER
COOL
CONT
UNUSED MOT. LEAD
HI
C
MH
HEAT
BLOWER
CIRCULATION
LO
ML
A98061
CONT
UNUSED MOT. LEAD
* JUMPER
2
CAPACITOR
FAN CIRCULATING
LO
1
GND
CAPACITOR
FUSE
WHITE
BLACK
WHITE
C
HI
ML
MH
120 VAC POWER SUPPLY
L2 (N)
BLACK
FAN CIRCULATING
TRANS
120 VAC 24 VAC
BLACK
L1 (H)
H
U
M
7
6
N
ST9103
R99G001
45
E
H
C
O
CON
1233
E
2
S
LEADS
UNUSED
CONSTANT LOW SPEED SWITCH
VIOLET
MOTOR/
BURNER
ST9103
TRANSFORMER
R99G001
45
WHITE
1233
BLACK
WHITE
UNUSED
A
O
A
C
BLACK
X
H
T
L
T
U
M
HUM
TERMINAL
BLUE
BLACK
LIMIT
CONTROL
WHITE
C
7
6
N
E
H
C
O
CON
E
A
2
S
LEADS
3
IS 115V
CAPACITOR
FAN CIRCULATING
BLACK
T
L1TL2
WHITE
LO
F
ORANGE
RED
OIL INPUT : 1.00 USGPH
COOLING CAPACITY : 4 TO 5
TONS MAX.
YELLOW
BLUE
RED
RED
T
A
L
O
T
C
HUM TERMINAL IS 115V
WHITE
BLACK
WHITE
HI
ML
MH
F
O
OIL PRIMARY
CONTROL
ON
12
GWRYC
H
U
M
N
ST9103
R99G001
45
1233
S
LEADS
UNUSED
C
RED
CONSTANT LOW SPEED SWITCH
CAD CELL
7
HUM
E
O
A
O
A
T
L
T
C
IS 115V
TERMINAL
BLUE
BLACK
* JUMPER
OIL INPUT : 1.10 USGPH
COOLING CAPACITY : 5 TONS
6
H
C
CON
E
2
Fig. 4—Wiring Diagram (060120)
ML
MH
HI
LO
C
BLUE
BLACK
CONSTANT LOW SPEED SWITCH
RED
—9—
THERMOSTAT
G
WY R
STANDARD HEAT / COOL WIRING DIAGRAM
WITH ST9103 ELECTRONIC FAN TIMER
JUMPER: USE JUMPER ONLY WHEN THE COOLING
OIL INPUT : 0.85 USGPH
COOLING CAPACITY; 4 TONS MAX.
*
AND HEATING SPEEDS ARE SAME
b. Start oil burner, then open purge fitting and allow burner
to run until purge tube is completely free of air bubbles.
c. Tighten purge fitting. Allow oil to run to nozzle and fire
burner.
TABLE 10—BURNER INPUT AND NOZZLE SIZE AND
PUMP PRESSURE
FURNACE
INPUT
(BTUH)
70,000 0.50 0.50-70W 100 100
91,000 0.65 0.55-70B 140 140 105,000 0.75 0.65-70B 133 130 120,000 0.85 0.75-70B 128 130 140,000 1.00 0.85-70B 138 140 155,000 1.10 0.85-70B 167 170
INPUT
USGPH
NOZZLE
REAL PUMP
PRESSURE
SPECIFICATION
PUMP PRESSURE
d. If purging takes longer than 15 sec and no flame has
been established, burner stops. Push reset button on front of primary control to restart burner.
TABLE 11—SPEED SELECTION
UNIT
SIZE
036105/
060120
FURNACE
INPUT
(BTUH)
70,000/119,000 Med-Low 91,000/140,000 Med-High
105,000/154,000 High
RECOMMENDED
BLOWER
SPEED
12
60 Sec
DELAY OFF DIP SWITCH SETTINGS
12
12 1212
90 Sec
120 Sec
12
150 Sec
A95115
Fig. 5—Fan Off Time DIP Switch Settings
(Black Box Represents Switch Position)
VI. HEATING
The blower speed is factory set to deliver required airflow at normal duct static pressure.
VII. COOLING
The blower speed may be field adjusted to deliver required airflow for cooling application. (See Table 12.)
VIII. CONSTANT BLOWER SWITCH
This furnace is equipped with a constant low-speed blower option. Whenever room thermostat is not calling for heating or cooling, blower runs on low speed in order to provide air circulation. If constant blower option is not desired, the rocker switch on top of cabinet may be used to turn off constant speed.
MAINTENANCE
e. For detailed information on operation of primary control,
refer to instructions included with furnace.
After all the setup procedures mentioned above have been com­pleted, the burner should be allowed to operate and an inspection mirror should be used to observe the flame pattern at tip of nozzle. Any irregularities such as burning to 1 side or pulsating flame patterns should be corrected by changing nozzle.
III. FAN ADJUSTMENT CHECK
This furnace is equipped with a 4-speed direct-drive motor to deliver a temperature rise within range specified on rating plate, between return and supply plenums, at external duct static pressure noted on rating plate.
WARNING: When operating furnace in heating mode, static pressure and temperature rise (supply-air tempera­ture minus return-air temperature) must be within those limits specified on rating label. Failure to follow this warning could lead to severe furnace damage.
Adjust fan speed ACCORDING TO OIL INPUT SELECTED so that temperature rise is within rise range specified on rating plate. (See Table 11.) Consult wiring diagram for speed changes on direct-drive motor. To adjust fan off time, set DIP switches on control board to obtain desired timing. (See Fig. 5.)
IV. LIMIT CONTROL CHECK
After furnace has been in operation for at least 15 minutes, restrict return-air supply by blocking filters or closing return registers and allow furnace to shut down on high limit. The burner should shut off, and main blower should continue to run. Remove restriction, and burner should come back on in a few minutes.
V. FOR YEAR-ROUND AIR CONDITIONING
This furnace is designed for use in conjunction with cooling equipment to provide year-round air conditioning. The blower has been sized for both heating and cooling, however, fan motor speed may need to be changed to obtain necessary cooling airflow.
WARNING: The ability to properly perform mainte­nance on this equipment requires certain expertise, me­chanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recom­mended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS PER­SONAL INJURY, OR DEATH.
WARNING: Before performing any service functions, unless operations specifically require power to be on, make sure all utilities are turned off upstream of appli­ance. Failure to comply with this warning will cause a fire hazard and/or bodily harm.
WARNING: To avoid personal injury, make sure elec­trical supply power is off before servicing. Failure to follow this warning could lead to electrical shock, fire, or death.
I. GENERAL
In order to keep this furnace in good operating condition and to maintain its warranty, the furnace MUST be serviced on an annual basis. This servicing includes a nozzle change, a burner inspection, a visual check of tube passages through flue outlet and cleanout ports, and a visual inspection of combustion chamber when burner is removed.
Depending on above inspection, service could also include a cleaning and vacuuming of heat exchanger tubes and possibly the heat exchanger drum section.
Removal of any heat exchanger components which are sealed by gaskets requires replacement of gasket.
—10—
TABLE 12—AIRFLOW DATA (CFM)
UNIT SIZE
036105
060120
NOTES:
1. Airflow values in cubic ft per minute (CFM) rounded to nearest 5 CFM.
2. Data taken with filters in place.
BLOWER
SPEED
High 1425 1350 1305 1250 1170 1030 925 805
Med-High 1130 1045 1000 950 885 820 745 670
Med-Low 840 810 770 740 685 635 580 500
Low 725 730 740 745 730 715 690 665 High 2080 2041 1965 1864 1702 1576 1474 1336
Med-High 1892 1859 1770 1675 1550 1449 1330 1217
Med-Low 1556 1475 1394 1318 1211 1134 1051 938
Low 1221 1164 1081 998 926 855 782 653
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
EXTERNAL STATIC PRESSURE IN. WC
WARNING: Failure to replace any heat exchanger gas-
kets with new gaskets when any heat exchanger plates or covers are removed could lead to heat exchanger leakage, sooting, and/or a hazardous condition capable of causing bodily harm.
This furnace should never be operated without an air filter. Disposable filters should be replaced at least once a year. If equipped to provide cooling, filters should be replaced a minimum of twice a year. Permanent filters should be cleaned at least twice a year.
ALWAYS KEEP MAIN OIL VALVE TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME.
II. OIL BURNER
For optimum performance, oil burner nozzle should be replaced once a year. Contact your service technician if you are unsure of this procedure.
The procedure for nozzle installation and/or replacement is out­lined in oil burner instruction manual which came with furnace.
After replacement of nozzle, burner should be adjusted in accor­dance with Combustion Check section of this instruction.
III. HEAT EXCHANGER AND FLUE PIPE
Ordinarily, it is not necessary to clean heat exchanger or flue pipe every year, but it is necessary to have your service technician check unit before each heating season to determine whether cleaning or replacement of parts is required.
If cleaning is necessary, the following steps should be performed:
1. Turn off all oil and electrical supplies upstream of furnace.
CAUTION: If furnace has been in operation, some surfaces may be hot. Allow time for unit to cool down or personal injury will result.
2. Disconnect flue pipe.
3. Remove flue collar panel located in front part of furnace.
4. Remove baffle from secondary heat exchanger.
5. Disconnect oil line and remove oil burner from furnace.
6. Open 2 cleanout doors located in upper part of front panel of furnace.
7. Clean secondary tubes, and primary cylinder with stiff brush and vacuum cleaner.
8. Before re-assembly, the heat exchanger and combustion chamber should be inspected to determine if replacement is required.
9. After cleaning, replace baffle, flue collar plate, oil burner, and close the 2 cleanout access doors. Reconnect flue pipe and oil line.
10. Re-adjust burner for proper operation.
IV. BLOWER REMOVAL
To remove blower from furnace:
1. Turn off all oil and electrical supplies upstream of furnace.
2. Remove burner access and blower door.
3. Remove blower retaining screw (on blower shelf).
4. Remove cover from control box and disconnect thermostat and power wires from the board.
5. Slide blower forward on rails toward front of unit.
6. Reverse items 1 through 5 to re-install blower. Refer to wiring diagram (Fig. 3 or 4) of these instructions or diagram located on inside of blower door to properly rewire unit.
—11—
© 2003 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—12—
Printed in U.S.A. ii369a1055 Catalog No. 5336–911
Loading...