Bryant Legacy 674D Installation Instructions Manual

Page 1
674D LEGACYt 13 SEER SINGLE--PACKAGED HYBRID HEAT DUAL FUEL SYSTEM WITH PURONR (R--410A) REFRIGERANT SINGLE AND THREE PHASE 2--5 NOMINAL TONS (SIZES 24--60)
Installation Instructions
NOTE: Read the entire instruction manual before starting the
NOTE: Installer: Make sure the Owner’s Manual and Service Instructions are left with the unit after installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1--2.......................
INTRODUCTION 2...................................
RECEIVING AND INSTALLA TION 2--13.................
Check Equipment 2..................................
Identify Unit 2....................................
Inspect Shipment 2.................................
Provide Unit Support 2...............................
Roof Curb 2......................................
Slab Mount 7.....................................
Field Fabricate Ductwork 7............................
Provide Clearances 7.................................
Rig and Place Unit 7.................................
Connect Condensate Drain 7...........................
Install Flue Hood 8...................................
Install Gas Piping 8..................................
Install Duct Connections 11............................
Configuring Units for Downflow (Vertical)
Discharge 11.....................................
Install Electrical Connections 12........................
High--Voltage Connections 12........................
Special Procedures for 208-- V Operation 12..............
Control Voltage Connections 12.......................
Balance Point Setting Thermidistat or Hybrid Heat
Thermostat 13....................................
Transformer Protection 13...........................
PRE--START--UP 13...................................
START--UP 14--17.....................................
Check for Refrigerant Leaks 14.........................
Unit Sequence of Operation 14.........................
Start--Up Heating and Make Adjustments 14...............
Checking Heating Control 15.........................
Check Gas Input 15................................
Adjust Gas Input 15................................
Check Burner Flame 16.............................
Start--Up Cooling and Make Adjustments 18...............
Physical Data 17....................................
Checking Cooling Control Operation 17................
Checking and Adjusting Refrigerant 17.................
Indoor Airflow and Airflow Adjustments 17.............
MAINTENANCE 29--34................................
Air Filter 29........................................
Indoor Blower and Motor 29...........................
Flue Gas Passageways 30..............................
Limit Switch 30.....................................
Burner Ignition 30...................................
Main Burners 30....................................
Outdoor Coil, Indoor Coil, & Condensate Drain Pan 30......
Outdoor Fan 31.....................................
Electrical Controls and Wiring 31.......................
Refrigerant Circuit 31.................................
Gas Input 32........................................
Indoor Airflow 32...................................
Check Defrost Thermostat 32...........................
PuronR Items 32....................................
TROUBLESHOOTING 35..............................
START--UP CHECKLIST 35............................
VERTICAL ECONOMIZER 39--56.......................
General 39.........................................
Accessories 39......................................
Installation 39-- 45...................................
Small Chassis 39-- 40...............................
Large Chassis 43--45...............................
CONFIGURATION 4 6--52..............................
OPERATION 53......................................
TROUBLESHOOTING 54..............................
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code
A09034
Fig. 1 -- Unit 674D ----A
1
Page 2
(NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the National Standards of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane Installation codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in per­sonal injury or death. CAUTION is used to identify unsafe practic­es which ma y result in minor personal injury or product and prop­erty damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
674D-- --A
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
A qualified installer or agency must use only factory--authorized kits or accessories when modifying this product.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 18) or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit.
INTRODUCTION
The 674D----A unit (see Fig. 1) is a fully self--contained, combination Category I gas heating/electric heating and cooling unit designed for outdoor installation (See Fig. 2 and 3 for unit dimensions). All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered. Units may be installed either on a rooftop, or on a cement slab (See Fig. 4 for roof curb dimensions). In gas heating mode, this unit is designed for a minimum continuous return--air temperature of 55_F(13_C) db and a maximum continuous return--air temperature of 80_F(27_C) db. Failure to follow these return--air temperature limits may affect reliability of heat exchangers, motors, and other components. Models with an N in the thirteenth position of the model number are dedicated Low NOx units designed for California installations. These models meet the California maximum oxides of nitrogen
(NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory and must be installed in California Air Quality Management Districts or any other regions in North America where a Low NOx rule exists.
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
.
IDENTIFY UNIT The unit model number and serial number are stamped on the unit
information plate. Check this information against shipping papers. INSPECT SHIPMENT
Inspect for shipping damage before removing packaging materials. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
If the unit is to be mounted on a curb in a downflow application, review Step 9 to determine which method is to be used to remove the downflow panels before rigging and lifting into place. The panel removal process may require the unit to be on the ground.
Step 2 — Provide Unit Support
For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate if required.
ROOF CURB Install accessory roof curb in accordance with instructions shipped
with curb (See Fig. 4). Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance.
Curb should be level to within 1/4 in. (6 mm). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
Installation on older “G” series roof curbs.
Two accessory kits are available to aid in installing a new “G” series unit on an old “G” roof curb.
1. Accessory kit number CPADCURB001A00, (small chassis) and accessory kit number CPADCURB002A00, (large chassis) includes roof curb adapter and gaskets for the perimeter seal and duct openings. No additional modifications to the curb are required when using this kit.
2. An alternative to the adapter curb is to modify the existing curb by removing the outer horizontal flange and use accessory kit number CPGSKTKIT001A00 which includes spacer blocks (for easy alignment to existing curb) and gaskets for the perimeter seal and duct openings. This kit is used when existing curb is modified by removing outer horizontal flange.
!
UNIT/STRUCTURAL DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Ensure there is sufficient clearance for saw blade when cutting the outer horizontal flange of the roof curb so there is no damage to the roof or flashing.
CAUTION
2
Page 3
674D-- --A
A09473
Fig. 2 -- 674D-- -- A24--36 Unit Dimensions
3
Page 4
674D-- --A
A09474
Fig. 3 -- 674D-- -- A42--60 Unit Dimensions
4
Page 5
HVAC unit base rails
Anchor screw
Flashing field supplied
Roofing material field supplied
Cant strip field supplied
HVAC unit basepan
Sealing Gasket
Roofcurb
Wood nailer*
Roofcurb*
Insulation (field supplied)
B
G
C
H
F
A
D
E
*Provided with roofcurb
ROOF CURB DETAIL
A
F
SMALL CURB
A09090
A09418
674D-- --A
B
C
G
H
E
D
LARGE CURB
UNIT SIZE
Small
Large
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16-- gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
CATALOG
NUMBER
CPRFCURB010A00 11 (279) CPRFCURB011A00 14 (356) CPRFCURB012A00 11 (279) CPRFCURB013A00 14 (356)
IMPORTANT: Do not install large base pan HYBRID HEAT units onto the small base pan (common curb). The center of gravity on a large base pan HYBRID HEAT unit could overhang the curb causing an unsafe condition. Before installing any large base pan unit onto the common curb, check the “Y” distance in the product
A
IN. (mm)BIN. (mm)*
C
IN. (mm)DIN. (mm)EIN. (mm)FIN. (mm)GIN. (mm)HIN. (mm)
10 (254)
16 (406)
14 (356)
47.8
(1214)
literature dimensional drawing to ensure that “Y” is greater than 14 in. (356 mm). Do not install any large base pan unit onto the common curb with a “Y” dimension (center of gravity) less than 14 in. (356 mm).
Fig. 4 -- Roof Curb Dimensions
5
A09415
32.4 (822)
43.9
(1116)
2.7 (69)
A09419
30.6 (778)
46.1 (1170)
42.2 (1072)
Page 6
CAUTION - NOTICE TO RIGGERS PRUDENCE - AVIS AUX MANIPULATEUR
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
DUCTS
MINIMUM HEIGHT: 36" (914.4 mm) HAUTEUR MINIMUM
SEAL STRIP MUST BE IN
UNIT HEIGHT HAUTEUR D'UNITÉ
674D-- --A
SEE DETAIL A VOIR DÉTAIL A
RIGGING WEIGHTS (SMALL CABINET) RIGGING WEIGHTS (LARGE CABINET)
Unit
Rigging
Weight
*For 460 Volt units add 14 lb (6.35 kg) to the rigging weight. NOTE: See dimensional drawing for corner weights.
24 30 36
lb kg lb kg lb kg lb kg lb kg lb kg
359 163 373 169 379 172
Rigging
Weight
VOIR DÉTAIL A
Unit
DETAIL A
461 209 482 219 507 230
PLACE BEFORE PLACING UNIT ON ROOF CURB
42 48 60
BANDE SCELLANT DOIT ÊTRE EN PLACE AVANT DE PLACER L'UNITÉ SUR LA BASE DE TOIT
50CY502286 2.0
A09051
Fig. 5 -- 674D-- -- A Suggested Rigging
6
Page 7
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102 mm) thick with 2 in. (51 mm) above grade. The slab should be flush on the compressor end of the unit (to allow condensate drain installation) and should extend 2 in. (51 mm) on the three remaining sides of the unit. Do not secure the unit to the slab except when required by local codes.
Step 3 — Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
See unit rating plate for any required clearances around ductwork. Cabinet return --air static shall not exceed --.2 IN. W.C.
Step 4 — Provide Clearances
The required minimum operating and service clearances are shown in Fig. 2 and 3.
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life.
The condenser fan pulls air through the condenser coil and discharges it through the top grille. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48--in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48--in. (1219 mm).
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. The unit may be installed on Class A, B, or C roof covering materials. Slab mounted units should be at least 4--in. (102 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.
Step 5 — Rig and Place Unit
!
WARNING
PERSONAL INJURY OR PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
When installing the unit on a rooftop, be sure the roof will support the additional weight.
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).
Only trained, qualified crane operators and ground support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work gloves.
Inspection
Prior to initial use, and at monthly intervals, all rigging shackles, clevis pins, and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Materials showing any kind of wear in these areas must not be used and should be discarded.
!
WARNING
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death.
Never stand beneath rigged units or lift over people.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above the unit top cover.
Rigging/Lifting of Unit (See Fig. 5)
Lifting holes are provided in base rails as shown in Fig. 2 and 3.
1. Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage.
2. Attach shackles, clevis pins, and straps to the base rails of the unit. Be sure materials are rated to hold the weight of the unit (See Fig. 5).
3. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.
After the unit is placed on the roof curb or mounting pad, remove the top skid.
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 674D ----A disposes of condensate water through a 3/4 in. NPT fitting which exits through the compressor access panel (See Fig. 2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field--supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. (25 mm) lower than the drain-- pan condensate connection to prevent the pan from overflowing (See Fig. 6). Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a 2--in. (51 mm) trap at the condensate connection to ensure proper drainage (See Fig. 6). Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the drain-- pan condensate connection. This prevents the pan from overflowing.
Prime the trap with water. Connect a drain tube -- using a minimum of 3/4--in. PVC or 3/4--in. copper pipe (all field--supplied) -- at the outlet end of the 2-- in. (51 mm) trap. Do not undersize the tube.
7
674D-- --A
Page 8
Pitch the drain tube downward at a slope of at least 1--in. (25 mm) for every 10 ft (3 m) of horizontal run. Be sure to check the drain tube for leaks.
TRAP OUTLET
1-in. (25 mm) min.
2-in. (51 mm) min.
A09052
Fig. 6 -- Condensate Trap
Step 7 — Install Flue Hood
The flue assembly is secured and shipped in the return air duct. Remove duct cover to locate the assembly (See Fig. 8 and 9).
NOTE: Dedicated low NOx models MUST be installed in California Air Quality Management Districts where a Low NOx rule exists.
674D-- --A
These models meet the California maximum oxides of nitrogen (NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory.
NOTE: Low NOx requirements apply only to natural gas installations.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicted in this section of the unit installation instructions.
Install the flue hood as follows:
1. This installation must conform with local building codes and with the National Fuel Gas Code (NFGC) NFPA 54 / ANSI Z223.1, (in Canada, CAN/CGA B149.1, and B149.2) latest revision. Refer to Provincial and local plumbing or wastewater codes and other applicable local codes.
2. Remove flue hood from shipping location (inside the return section of the blower compartment--see Fig. 8 and 9). Re­move the return duct cover to locate the flue hood. Place flue hood assembly over flue panel. Orient screw holes in flue hood with holes in the flue panel.
3. Secure flue hood to flue panel by inserting a single screw on the top flange and the bottom flange of the hood.
Step 8 — Install Gas Piping
The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/2--in. (12.7 mm) FPT gas inlet on the gas valve.
Install a gas supply line that runs to the heating section. Refer to Table 2 and the NFGC for gas pipe sizing. Do not use cast--iron pipe. It is recommended that a black iron pipe is used. Check the
local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 IN. W.C. maximum pressure drop. Never use pipe smaller than the 1/2--in. (12.7 mm) FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 IN. W.C. or greater than 13 IN. W.C. while the unit is operating. For propane applications, the gas pressure must not be less than 11.0 IN. W.C. or greater than 13 IN. W.C. at the unit connection.
A 1/8-- in. (3.2 mm) NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the gas valve.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC NFPA 54/ANSI Z223.1 latest edition (in Canada, CAN/CGA B149.1).
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. (6.35 mm) for every 15 ft (4.6 m) of length to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than 1/2 in., (12.7 mm) follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. Never use Teflon tape.
4. Install sediment trap in riser leading to heating section (See Fig. 7). This drip leg functions as a trap for dirt and condensate.
5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft (1.8 m) of heating section.
6. Install ground--joint union close to heating section between unit manual shutoff and external manual main shut--off valve.
7. Pressure test all gas piping in accordance with local and national plumbing and gas codes before connecting piping to unit.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground--joint union.
8
Page 9
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
--Connect gas pipe to unit using a backup wrench to avoid damaging gas controls.
--Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
--Use proper length of pipe to avoid stress on gas control manifold.
--If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum of 2 in. (51 mm) outside furnace casing.
been completed. Use a commercially available soap solution made specifically for the detection of leaks (or method specified by local codes and/or regulations).
IN
TEE
OUT
NIPPLE
--If codes allow a flexible connector, always use a new connector. Do not use a connector which has previously
CAP
serviced another gas appliance.
8. Check for gas leaks at the field--installed and
Fig. 7 -- Sediment Trap
C99020
factory--installed gas lines after all piping connections have
Table 1 – Physical Data -- Unit 674D----A
UNIT SIZE 674D --- ---A 24040 24060 30040 30060 36060 36090 42060 42090
NOMINAL CAPACITY --- ton 2 2 2 --- 1 / 2 2 --- 1 / 2 3 3 3 --- 1 / 2 3 --- 1 / 2
SHIPPING WEIGHT --- lb.
COMPRESSORS Scroll
Quantity 1
REFRIGERANT (R --- 410A)
Quantity --- lb
REFRIGERANT METERING
Nominal Cooling Airflow--- (CFM)
Natural Gas Qty...Drill Size (Factory Installed)
Propane GasQty...Drill Size
HIGH --- PRESSURE SWITCH
LOW--- PRESSURE SWITCH
RETURN--- AIR FILTERS † }
*Based on altitude of 0 to 2000 ft (0 ---610 m). {Required filter sizes shown are based on the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow
velocity of 300 ft/minute for high ---capacity type. Air filter pressure drop for non --- standard filters must not exceed 0.08 IN. W.C. } If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.
DEVICE
OUTDOOR ORIFICE
in. (qty)
(mm)
OUTDOOR COIL
Rows...Fins/in. F a c e A r e a --- s q f t OUTDOOR FAN
Nominal Cfm Diameter--- in.
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in. F a c e A r e a --- s q f t
INDOOR BLOWER
S i z e --- i n .
M o t o r --- h p
FURNACE SECTION*
Burner Orifice
( p s i g ) C u t --- o u t
Reset (Auto)
L O S S --- O F --- C H A R G E /
(Liquid Line) (psig)
C u t --- o u t
Reset (auto)
Throwaway (in.)
(kg)
(kg)
(mm)
(mm)
(mm)
359 163
8.3
3.8
0.032 ( 2)
2...21
11.9
2000
24
610
1/5 (810)
3...17
3.7
800
10x10
254x254
1/2
2...44
2...55
20x20x1
508x508x25
.81
359 163
8.3
3.8
2...21
11.9
2000
24
610
1/5 (810)
3...17
3.7
800
10x10
254x254
1/2
2...38
2...53
373 169
10.2
4.6
0.035 ( 2)
2...21
11.9
2700
24
610
1/5 (810)
3...17
3.7
1000
10x10
254x254
1/2
2...44
2...55
20x24x1
508x610x25
373 169
10.2
4.6
I n d o o r --- T X V, O u td oo r --- A c c u r a t e r
.89
2...21
11.9
2700
24
610
1/5 (810)
3...17
3.7
1000
10x10
254x254
1/2
2...38
2...53
650 +/ ---15 420 +/ ---25
2 0 + / --- 5
45 +/ ---10
379 172
7.9
3.6
2...21
11.9
2700
24
610
1/5 (810)
3...17
3.7
1200
11x10
279x254
3/4
2...38
2...53
0.037 (2) .94
379 172
7.9
3.6
2...21
11.9
2700
24
610
1/5 (810)
3...17
3.7
1200
11x10
279x254
3/4
3...38
3...53
610x762x25
24x30x1
461 209
10.0
4.5
0.038 ( Left)
0.040(Right)
2...21
13.6
3100
26
660
1/5 (810)
3...17
4.7
1400
11x10
279x254
3/4
2...38
2...53
.97/1.02
1/5 (810)
279x254
461 209
10.0
4.5
2...21
13.6
3100
26
660
3...17
4.7
1400
11x10
3/4
3...38
3...53
674D-- --A
9
Page 10
Table 1 -- Physical Data -- Unit 674D----A (Cont’d)
NUMBER
OF
MANIFOLD
PRES
SURE
ORIFICES
UNIT SIZE 674D --- ---A 48090 48115 48130 60090 60115 60130
NOMINAL CAPACITY --- ton 4 4 4 5 5 5
OPERATING WEIGHT--- lb
COMPRESSORS Scroll
Quantity 1
REFRIGERANT (R --- 410A)
Quantity --- lb
REFRIGERANT METERING DEVICE TXV
OUTDOOR ORIFICE --- in. (qty)
OUTDOOR COIL
Rows...Fins --- in. F a c e A r e a --- s q f t
OUTDOOR FAN
Nominal Cfm
Diameter--- in.
M o t o r H p --- R p m
INDOOR COIL Rows...Fins --- in. F a c e A r e a --- s q f t
INDOOR BLOWER
Nominal Cooling Airflow--- (CFM)
674D-- --A
Natural Gas Qty...Drill Size (Factory Installed)
*Based on altitude of 0 to 2000 ft (0 ---610 m). {Required filter sizes shown are based on the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow
velocity of 300 ft/minute for high ---capacity type. Air filter pressure drop for non --- standard filters must not exceed 0.08 IN. W.C. } If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.
Propane GasQty...Drill Size
HIGH --- PRESSURE SWITCH (psig) Cut --- out
LOW--- PRESSURE SWITCH
S i z e --- i n .
M o t o r --- h p
FURNACE SECTION*
Burner Orifice
Reset (Auto)
L O S S --- O F --- C H A R G E /
(Liquid Line) (psig)
C u t --- o u t
Reset (auto)
RETURN--- AIR FILTERS †
Throwaway (in.)
(mm)
(kg)
(kg )
(mm)
(mm)
(mm)
482 219
2...21
13.6
3100
26
660
1/5 (810)
3...17
4.7
1600
11x10
279x254
1.0
3...38
3...53
482 219
9.6
4.4
0.046 (2)
1.2
2...21
13.6
3100
26
660
1/5 (810)
3...17
4.7
1600
11x10
279x254
1.0
3...33
3...51
482 219
2...21
13.6
3100
26
660
1/5 (810)
3...17
4.7
1600
11x10
279x254
1.0
3...31
3...49 650 +/ ---15 420 +/ ---25
2 0 + / --- 5
45 +/ ---10
24x36x1
(610x914x25)
507 230
2...21
17.5
3500
26
660
1/5 (810)
3...17
5.7
1850
11x10
279x254
1.0
3...38
3...53
507 230
12.3
5.6
0.052 (2)
1.3
2...21
17.5
3500
26
660
1/5 (810)
3...17
5.7
1850
11x10
279x254
1.0
3...33
3...51
507 230
2...21
17.5
3500
26
660
1/5 (810)
3...17
5.7
1850
11x10
279x254
1.0
3...31
3...49
Table 2 – Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE (IN.)
1/2 .622 175 120 97 82 73 66 61 57 53 50 44 40 3/4 .824 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 1 --- 1 / 4 1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280 1 --- 1 / 2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
* Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5 ---IN. W.C. (based on a 0.60 specific gravity gas). Refer toTable2 and National Fire Protection Association NFPA 54/ANSI Z223.1. † This length includes an ordinary number of fittings.
INTERNAL
DIAMETER
(IN.)
10
(3.1)20(6.1)30(9.1)40(12.2)50(15.2)60(18.3)70(21.3)80(24.4)90(27.4)
LENGTH OF PIPE, FT† (m)
100
(30.5)
125
(38.1)
150
(46.0)
175
(53.3)
Table 3 – Heating Inputs
HEATING INPUT
(BTUH)
GAS SUPPLY PRESSURE (IN. W.C.)
Natural{ Propane*{
Min Max Min Max Natural{ Propane*†
40,000 2 4.0 13.0 11.0 13.0 3.23.8 10.0∼11.0 60,000 2 4.0 13.0 11.0 13.0 3.23.8 10.0∼11.0
90,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0∼11.0 115,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0∼11.0 130,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0∼11.0
*When a unit is converted to propan e, differen t size orifices must be used. See separate, natural --- to ---propane conversion kit instructions.
{Based on altitudes from sea level to 2000 ft (610 m) above sea level. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each addi-
tional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.
MANIFOLD PRESSURE
(IN. W.C.)
200
(61.0)
10
Page 11
Step 9 — Install Duct Connections
The unit has duct flanges on the supply-- and return--air openings on the side and bottom of the unit. For downshot applications, the ductwork connects to the roof curb (See Fig. 2 and 3 for connection sizes and locations).
Configuring Units for Downflow (V ertical) Discharge
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch.
1. Open all electrical disconnects before starting any service
work.
2. Remove horizontal (metal) duct covers to access vertical
(downflow) discharge duct knockouts in unit basepan. (See Fig. 8.)
WARNING
4. All units must have field-- supplied filters or accessory filter rack installed in the return-- air side of the unit. Recommended sizes for filters are shown in Table 1.
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration--isolate all openings in building structure in accordance with local codes and good building practices.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
To remove downflow return and supply knockout covers, break front and right side connecting tabs with a screwdriver and hammer. Push cover down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an electrical knockout. Reinstall horizontal duct covers (Fig. 8) shipped on unit from factory. Insure openings are air and watertight.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Units are shipped for horizontal duct installation (by removing duct covers).
2. Select and size ductwork, supply--air registers, and return-- air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weather tight and airtight seal.
Basepan Downflow (Vertical) Supply Knockout
Horizontal Duct Covers
Fig. 8 -- Supply and Return Duct Opening
A09061
Basepan Downflow (Vertical) Return Knockout
A09060
674D-- --A
11
Page 12
Step 10 — Install Electrical Connections
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduitapprovedfor electricalground when installed in accordance with NEC, NFPA 70 National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being installed.
1. Make all electrical connections in accordance with NEC
674D-- --A
NFPA 70 (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field--supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high--voltage power to unit is within operating voltage range indicated on unit rating plate. On 3--phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.
4. Insulate low-- voltage wires for highest voltage contained within conduit when low--voltage control wires are in same conduit as high--voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
High--Voltage Connections
When routing power leads into unit, use only copper wire between disconnect and unit. The high voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight.
The unit must have a separate electrical service with a field--supplied, waterproof disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.
The field-- supplied disconnect switch box may be mounted on the unit over the high--voltage inlet hole when the standard power and low-- voltage entry points are used (See Fig. 2 and 3 for acceptable location).
NOTE: Field supplied disconnect switch box should be positioned so that it does not cover up any of the unit gas combustion supply air louvers.
See unit wiring label (Fig. 14 and 15) and Fig. 9 for reference when making high voltage connections. Proceed as follows to complete the high--voltage connections to the unit.
WARNING
CAUTION
Single phase units:
1. Run the high--voltage (L1, L2) and ground lead into the control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side of the contactor.
4. Connect field L1 to black wire on connection 11 of the compressor contactor.
5.ConnectfieldwireL2toyellowwireonconnection23of the compressor contactor.
Three-- phase units:
1. Run the high--voltage (L1, L2, L3) and ground lead into the control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side of the contactor.
4. Connect field L1 to black wire on connection 11 of the compressor contactor.
5.ConnectfieldwireL3toyellowwireonconnection13of the compressor contactor.
6. Connect field wire L2 to blue wire from compressor.
Special Procedures for 208--V Operation
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Make sure the power supply totheunit is switchedOFF before making any wiring changes. Tag the disconnect switch with a suitable warning label. With disconnect switch open, move black wire from transformer (3/16 in.) terminal marked 230 to terminal marked 200. This retaps transformer to primary voltage of 208 vac.
!
WARNING
ELECTRICAL SHOCK AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Beforemaking any wiring changes,make sure the gassupply is switched off first. Then switch off the power supply to the unit and install lockout tag.
Control Voltage Connections
Do not use any type of power--stealing thermostat. Unit control problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated (35_C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as measured along the control voltage wires), use no. 16 AWG color--coded, insulated (35_C minimum) wires.
Locate the seven (eight on 3 -- phase) low voltage thermostat leads in 24 volt splice box. See Fig. 9 for connection diagram. Run the low--voltage leads from the thermostat, through the control wiring inlet hole grommet (Fig. 2 and 3), and into the low-- voltage splice box. Provide a drip loop before running wires through panel. Secure and strain relief all wires so that they do not interfere with operation of unit. A gray wire is standard on 3--phase unit for connection to an economizer.
12
Page 13
HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
CONTROL BOX
LOW-VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)
EQUIP GR
SPLICE BOX
FIELD-SUPPLIED FUSED DISCONNECT
WHT(W1)
YEL(Y)
GRN(G)
RED(R)
BRN(C)
ORN(O)
BLU (DH)
GRA (Y2)
W
Y
G
R
C
O
DH
3-Phase Only
POWER SUPPLY
THERMOSTAT (TYPICAL)
A09067
Fig. 9 -- High and Control--Voltage Connections
Balance Point Setting--Thermidistat or Hybrid Thermostat
BALANCE POINT TEMPERATURE--The “balance point” temperature is a setting which affects the operation of the heating mode. This is a field--selected input temperature (range 5 to 55_F) (--15to12_C) where the Thermidistat or dual fuel thermostat will monitor outdoor air temperature and decide whether to enable or disable the heat pump. If the outdoor temperature is above the “balance point”, the heat pump will energize first to try to satisfy the indoor temperature demand. If the heat pump does not make a sufficient improvement within a reasonable time period (i.e. 15 minutes), then the gas furnace will come on to satisfy the indoor temperature demand. If the outdoor temperature is below the “balance point”, the heat pump will not be allowed to operate (i.e. locked out), and the gas furnace will be used to satisfy the indoor temperature. There are three separate concepts which are related to selecting the final “balance point” temperature. Read each of the following carefully to determine the best “balance point” in a hybrid installation:
1. Capacity Balance Temperature: This is a point where the heat pump cannot provide sufficient capacity to keep up with the indoor temperature demand because of declining outdoor temperature. At or below this point, the furnace is needed to maintain proper indoor temperature.
2. Economic Balance Temperature: Above this point, the heat pump is the most cost efficient to operate, and below this point the furnace is the most cost efficient to operate. This can be somewhat complicated to determine and it involves knowing the cost of gas and electricity, as well as the efficiency of the furnace and heat pump. For the most economical operation, the heat pump should operate above this temperature (assuming it has sufficient capacity) and the furnace should operate below this temperature.
3. Comfort Balance Te mperature: When the heat pump is operating below this point, the indoor supply air feels uncomfortable (i.e. too cool). This is purely subjective and will depend on the homeowner’s idea of comfort. Below this temperature the gas furnace should operate in order to satisfy the desire for indoor comfort.
Transformer Protection
The transformer is of the energy--limiting type. It is set to withstand a 30--sec. overload or shorted secondary condition. If an overload or short is present, correct overload condition and check for blown fuse on gas control board or Interface Fan Board. Replace fuse as required with correct size and rating.
PRE--START--UP
!
WARNING
FIRE,EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected and tagged.
4. Relieve and recover all refrigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power to unit and install lockout
tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to inspect and prepare the unit for initial start--up:
1. Remove access panels (see Fig. 18).
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a refrigerant leak.
c. Leak test all refrigerant tubing connections using
electronic leak detector, halide torch, or liquid-- soap solution. If a refrigerant leak is detected, see the Check for Refrigerant Leaks section.
d. Inspect all field-- and factory--wiring connections. Be
sure that connections are completed and tight.
e. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
f. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Do not purgegas supply intothe combustionchamber.Do not use a match or other open flame to check for gas leaks. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
674D-- --A
13
Page 14
4. Verify the following conditions:
a. Make sure gas line is free of air. Before lighting the unit
for the first time, perform the following with the gas valve in the “OFF” position:
NOTE: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the ground joint union be loosened, and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines into a combustion chamber. Immediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit.
b. Make sure that condenser-- fan blade is correctly
positioned in fan orifice. Leading edge of condenser-- fan blade should be 1/2 in. (12 mm) maximum from fan orifice.
c. Make sure that air filter(s) is in place.
d. Make sure that condensate drain trap is filled with water
to ensure proper drainage.
e. Make sure that all tools and miscellaneous loose parts
have been removed.
START--UP
Step 1 — Check for Refrigerant Leaks
674D-- --A
Proceed as follows to locate and repair a refrigerant leak and to charge the unit:
1. Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high-- and low-- pressure ports.
2. Repair leak following Refrigerant Service procedures.
NOTE: Install a bi--flow filter drier whenever the system has been opened for repair.
3. Add a small charge of R --410A refrigerant vapor to system and leak--test unit.
4. Recover refrigerant from refrigerant system and evacuate to 500 microns if no additional leaks are not found.
5. Charge unit with Puron (R--410A) refrigerant, using an electronic scale. Refer to unit rating plate for required charge.
Step 2 — Unit Sequence of Operation
674D----A Sequence of Operation
a. CONTINUOUS FAN
(1.) Thermostat closes circuit R to G energizing the
blower motor for continuous fan.
b. COOLING MODE
(1.) If indoor temperature is above temperature set
point thermostat closes circuits R to G, R to Y and R to O--The unit delivers cooling airflow.
c. HEAT PUMP HEATING MODE
Outdoor temperature above balance point setpoint of thermostat.
(1.) On a call for heating, terminals “Y” and “G“ of the
Hybrid thermostat are energized. The “Y“ signal is sent to the Defrost Board (DB) terminal “Y”. The DB has a built in five minute anti--short cycle timer which will not allow the compressor to restart before the time delay has expired.
(2.) “T2” energizes the compressor contactor via the
High Pressure Switch (HPS) and Low Pressure Switch (LPS). The compressor and outdoor fan start. Thermostat “G” energizes the Interface Fan Board terminal “G”. The blower motor is energized through contacts of the IFB.
(3.) When the thermostat removes the “Y” and “G”
calls, the compressor contactor and outdoor fan are
Heating Sequence of Operation
(See Fig. 14 and 15 and unit wiring label.) On a call for heating, terminal W of the thermostat is energized,
starting the induced--draft motor. When the pressure switch senses that the induced--draft motor is moving sufficient combustion air, the burner sequence begins. This function is performed by the integrated gas unit controller (IGC). The indoor (evaporator)--fan motor is energized 45 sec after flame is established. When the thermostat is satisfied and W is de--energized, the burners stop firing and the indoor (evaporator) fan motor shuts off after a 45-- sec time--off delay. Please note that the IGC has the capability to automatically reduce the indoor fan motor on delay and increase the indoor fan motor off delay in the event of high duct static and/or partially-- clogged filter.
NOTE: An LED (light--emitting diode) indicator is provided on the control board to monitor operation. The control board is located by removing the burner access panel (see Fig. 18). During normal operation, the LED is continuously on.
Step 3 — Start--up Heating and Make Adjust­ments
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being installed.
Completethe required procedures given in the Pre--Start-- Up section before starting the unit. Do not jumper any safety devices when operating the unit.
Complete the required procedures given in the Pre--Start--Up section before starting the unit. Do not jumper any safety devices when operating the unit. Make sure that burner orifices are properly aligned. Unstable operation my occur when the burner orifices in the manifold are misaligned.
Follow the lighting instructions on the heating section operation label (located on the inside of the control access panel) to start the heating section.
NOTE: Make sure that gas supply has been purged, and that all gas piping has been checked for leaks.
Pipe Plug
de--energized. The evaporator motor is de--ener­gized after a 90 sec. delay.
d. GAS HEATING MODE
Outdoor temperature below balance point setpoint of thermostat.
!
CAUTION
Manifold
Fig. 10 -- Burner Assembly
A07679
14
Page 15
BURNER FLAME
BURNER
MANIFOLD
C99021
Fig. 11 -- Monoport Burner
Check Heating Control
Start and check the unit for proper heating control operation as follows (see furnace lighting instructions located on the inside of the control access panel):
1. Place room thermostat SYSTEM switch in the HEAT position and the fan switch is placed in AUTO position.
2. Set the heating temperature control of the thermostat above room temperature.
3. The induced--draft motor will start.
4. On a call for heating, the main burner should light within 5 sec. of the spark being energized. If the burners do not light, there is a 22--sec. delay before another 5-- sec. try. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break the 24--v power to W.
5. The evaporator fan will turn on 45 sec. after the flame has been established. The evaporator fan will turn off 45 sec. after the thermostat has been satisfied. Please note that the integrated gas unit controller (IGC) has the capability to automatically reduce the evaporator “ON” delay and in­crease the evaporator “OFF” delay in the event of high duct static and/or partially--clogged filter .
Check Gas Input
Check gas input and manifold pressure after unit start--up (See Table 3). If adjustment is required proceed as follows:
S The rated gas inputs shown in Table 3 are for altitudes from sea
level to 2000 ft (610 m) above sea level. These inputs are based
3
on natural gas with a heating value of 1025 Btu/ft
specific gravity, or propane gas with a heating value of 2500
3
at 1.5 specific gravity.
Btu/ft
IN THE U.S.A.:
The input rating for altitudes above 2,000 ft (610 m) must be reduced by 4% for each 1,000 ft (305 m) above sea level.
For installations below 2,000 ft (610 m), refer to the unit rating plate.
For installations above 2,000 ft (610 m) multiply the input by on the rating plate by the derate multiplier in Table 4 for correct input rate.
at 0.60
Table 4 – Altitude Derate Multiplier for U.S.A.*
ALTITUDE FT (M) P ERCENT O F DERATE
0--- 2000 (0--- 610)
2001--- 3000*
(610--- 914)
3001--- 4000
(315--- 1219)
4001--- 5000
(1220--- 1524)
5001--- 6000
(1524--- 1829)
6001--- 7000
(1829--- 2134)
7001--- 8000
(2134--- 2438)
8001--- 9000
(2439--- 2743)
9001--- 10,000 (2744--- 3048)
*In Canada see Canadian Altitude Adjustment. {Derate multiplier factors are based on midpoint altitude for altitude range.
0 1.00
8 --- 1 2 0.90
12--- 16 0.86
16--- 20 0.82
20--- 24 0.78
24--- 28 0.74
28--- 32 0.70
32--- 36 0.66
36--- 40 0.62
DERATE MULTIPLIER
FACT OR{
IN CANADA: The input rating for altitudes from 2,000 to 4,500 ft (610 m to
1372 m) above sea level must be derated 10% by an authorized Gas Conversion Station or Dealer.
EXAMPLE: 90,000 Btu/hr Input Furnace Installed at 4300 ft (1311 m).
Furnace Input Rate at Sea Level
90,000 X 0.90 = 81,000
XDerateMultiplier
Facto r
= Furnace Input Rate at
Installation Altitude
When the gas supply being used has a different heating value or specific gravity, refer to national and local codes, or contact your distributor to determine the required orifice size.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced unit and/or component life.
Do No t redrill an orifice. Improper drilling (burrs, out--of--round holes, etc.) can cause excessive burner noise and misdirection of burner flame. If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size.
Adjust Gas Input
The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The manifold pressure must be measured to determine the input of propane gas units.
Measure Gas Flow (Natural Gas Units)
Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be maintained between 3.2 and 3.8 IN. W.C.
If larger adjustments are required, change main burner orifices following the recommendations of national and local codes.
NOTE: All other appliances that use the same meter must be turned off when gas flow is measured at the meter.
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (See Fig. 10) and connect manometer. Turn on gas supply to unit.
3. Record number of seconds for gas meter test dial to make one revolution.
674D-- --A
15
Page 16
4. Divide number of seconds in Step 3 into 3600 (number of seconds in one hr).
5. Multiply result of Step 4 by the number of cubic feet (cu ft) shown for one revolution of test dial to obtain cubic feet (cu ft) of gas flow per hour.
6. Multiply result of Step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value with heating input shown in Table 3 (Consult the local gas supplier if the heating value of gas is not known).
EXAMPLE: Assume that the size of test dial is 1 cu ft, one revolution takes 32 sec, and the heating value of the gas is 1050
3
. Proceed as follows:
Btu/ft
1. 32 sec. to complete one revolution.
2. 3600 ÷ 32 = 112.5.
3. 112.5x1=112.5ft
3
of gas flow/hr.
4. 112.5 x 1050 = 118,125 Btuh input.
If the desired gas input is 115,000 Btuh, only a minor change in the manifold pressure is required.
Observe manifold pressure and proceed as follows to adjust gas input:
1. Remove regulator cover screw over plastic adjustment screw on gas valve (See Fig. 12).
674D-- --A
2. Turn plastic adjustment screw clockwise to increase gas input, or turn plastic adjustment screw counterclockwise to decrease input (See Fig. 12). Manifold pressure must be between 3.2 and 3.8 IN. W.C.
REGULATOR COVER SCREW
PLASTIC
ADJUSTMENT
ON/OFF SWITCH
INLET PRESSURE TAP
SCREW
REGULATOR SPRING (PROPANE - WHITE) (
NATURAL - SILVER)
GAS PRESSURE REGULATOR ADJUSTMENT
MANIFOLD PRESSURE TAP
A07751
Fig. 12 -- Single--Stage Gas Valve
!
WARNING
FIRE AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure is outside this range.
3. Replace regulator cover screw on gas valve (See Fig. 12).
4. Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. (See Fig.
10.) Turn on gas to unit and check for leaks.
Measure Manifold Pressure (Propane Units)
Refer to propane kit installation instructions for properly checking gas input.
NOTE: For installations below 2,000 ft (610 m), refer to the unit
the same for each burner. Propane will have blue flame (See Fig.
11). Refer to the Maintenance section for information on burner removal.
Normal Operation
An LED (light--emitting diode) indicator is provided on the integrated gas unit controller (IGC) to monitor operation. The IGC is located by removing the control access panel (see Fig. 18). During normal operation, the LED is continuously on (See Table 5 for error codes).
Airflow and Temperature Rise
The heating section for each size unit is designed and approved for heating operation within the temperature--rise range stamped on the unit rating plate.
Table 10 shows the approved temperature rise range for each heating input, and the air delivery cfm at various temperature rises for a given external static pressure. The heating operation airflow must produce a temperature rise that falls within the approved range.
Refer to Indoor Airflow and Airflow Adjustments section to adjust heating airflow when required.
Limit Switches
Normally closed limit switch (LS) completes the control circuit. Should the leaving--air temperature rise above the maximum allowable temperature, the limit switch opens and the control circuit “breaks.” Any interruption in the control circuit instantly closes the gas valve and stops gas flow to the burners. The blower motor continues to run until LS resets.
When the air temperature at the limit switch drops to the low-- temperature setting of the limit switch, the switch closes and completes the control circuit. The direct--spark ignition system cycles and the unit returns to normal heating operation.
Table 5 – LED Indications
STATUS CODE LED INDICATION
Normal Operation
No Power or Hardware Failure Off
Limit Switch Fault 2 Flashes
Flame Sense Fault 3 Flashes
Four Consecutive Limit Switch Faults 4 Flashes
Ignition Lockout Fault 5 Flashes Pressure Switch Fault 6 Flashes
Rollout Switch Fault 7 Flashes
Internal Control Fault 8 Flashes
Temporary 1 hr auto reset
NOTES:
1.This code indicates an internal processor fault that will reset itself in one hr. Fault can be caused by stray RF signals in the structure or nearby. Th is is a UL requirement.
2. LED indicates acceptable operation. Do not change ignition control board.
3. When W is energized the burners will remain on for a minimum of 60 sec.
4.IfmorethanoneerrormodeexiststheywillbedisplayedontheLEDin sequence.
2
1
On
9 Flashes
Rollout Switch
The function of the rollout switch is to close the main gas valve in the event of flame rollout. The switch is located above the main burners. When the temperature at the rollout switch reaches the maximum allowable temperature, the control circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor (evaporator) fan motor (IFM) and induced draft motor continue to run until switch is reset. The IGC LED will display FAULT CODE
7. rating plate for proper propane conversion kit. For installations above 2,000 ft (610 m), contact your distributor for proper propane conversion kit.
Check Burner Flame
With control access panel (see Fig. 18) removed, observe the unit heating operation. Watch the burner flames to see if they are light blue and soft in appearance, and that the flames are approximately
16
Page 17
Step 4 — Start--up Cooling and Make Adjust­ments
Complete the required procedures given in the Pre--Start--Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature is below 40°F(4.4°C) (unless accessory low--ambient kit is installed). Do not rapid--cycle the compressor. Allow 5 minutes between on cycles to prevent compressor damage.
Checking Cooling Control Operation
Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts wh en FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evaporator fan will continue to run for 90 sec.
IMPORTANT: Three--phase, scroll compressors units are direction oriented. Unit must be checked to ensure proper compressor 3--phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3--phase power leads to the unit must be reversed to correct rotation. When turning backwards, the difference between compressor suction and discharge pressures will be near zero.
Checking and Adjusting Refrigerant Charge
The refrigerant system is fully charged with PuronR (R--410A) refrigerant and is tested and factory sealed. Allow system to operate a minimum of 15 minutes before checking or adjusting charge.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper PuronR (R--410A) charge.
The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label is attached to the inside of the compressor access panel (see Fig. 18). The chart includes the required liquid line temperature at given discharge line pressures and outdoor ambient temperatures.
An accurate thermocouple-- or thermistor--type thermometer, and a gauge manifold are required when using the subcooling charging method for evaluating the unit charge. Do not use mercury or small dial--type thermometers because they are not adequate for this type of measurement.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
CAUTION
Proceed as follows:
1. Remove caps from low-- and high--pressure service fittings.
2. Using hoses with valve core depressors, attach low-- and high--pressure gauge hoses to low-- and high--pressure service fittings, respectively.
3. Start unit in Cooling Mode and let unit run until system pressures stabilize.
4. Measure and record the following:
a. Outdoor ambient-- air temperature (°F[°C] db).
b. Liquid line temperature (°F[°C]).
c. Discharge (high--side) pressure (psig).
d. Suction (low--side) pressure (psig) (for reference only).
5. Using “Cooling Charging Charts,” compare outdoor--air temperature(°F[°C] db) with the discharge line pressure (psig) to determine desired system operating liquid line temperature (See Fig. 16).
6. Compare actual liquid line temperature with desired liquid line temperature. Using a tolerance of ± 2°F(±1.1°C), add refrigerant if actual temperature is more than 2°F(1.1°C) higher than proper liquid line temperature, or remove refrigerant if actual temperature is more than 2°F(1.1°C) lower than required liquid line temperature.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to the Check for Refrigerant Leaks section.
Indoor Airflow and Airflow Adjustments
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.
NOTE: Be sure that all supply--and return--air grilles are open, free from obstructions, and adjusted properly.
!
WARNING
ELECTRICAL SHOCK AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Before making any indoor wiring adjustments, shut off gas supply. Then disconnect electrical power to the unit and install lockout tag before changing blower speed.
This unit has independent fan speeds for gas heating and cooling. In addition, this unit has the field-selectable capability to run two different cooling fan speeds: A normal cooling fan speed (350~400 CFM/Ton) and an enhanced dehumidification fan speed (As low as 320 CFM/Ton) for use with either a dehumidistat or a thermostat that supports dehumidification.
This unit is factory-set up for use with a single cooling fan speed. The cooling speed is marked “LOW” on the interface fan board (IFB) (See Fig. 13). The factory-shipped settings are noted in Table 10. There are 3 additional speed tap wires available for use in either gas heating or cooling (For color coding on the indoor fan motor leads, see Table 6). The additional 3 speed tap wires are shipped loose with vinyl caps and are located in the control box, near the interface fan board (IFB) (See Fig. 13).
674D-- --A
17
Page 18
Gas Heating Fan Speed Set-up
To change the gas heating speed:
1. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Table 10 shows the temperature rise associated with each fan speed for a given static pressure. Make sure that the speed chosen delivers a temperature rise within the rise range listed on the unit rating plate.
2. Remove the current speed tap wire from the “GAS HEAT” terminal on the interface fan board (IFB) (Fig.14) and place vinyl cap over the connector on the wire.
3. Connect the desired speed tap wire to the “GAS HEAT” terminal on the interface fan board (IFB).
Single Cooling Fan Speed Set-up (Dehumidification feature not
To change cooling speed:
1. Remove the vinyl cap off of the desired speed tap wire
674D-- --A
2. Remove the current speed tap wire from the “LOW”
3. Connect the desired speed tap wire to the “LOW” terminal
used)
(Refer to Table 6 for color coding). Add the wet coil pressure drop in Table 8 to the system static to determine the correct cooling airflow speed in Table 10 that will deliver the nominal cooling airflow as listed in Table 1 for each size.
terminal on the interface fan board (IFB) (See Fig. 13) and place vinyl cap over the connector on the wire.
5. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the dehumidification cooling fan speed and place desired speed tap wire on the “LOW” connection on the interface board (IFB). Verify that static pressure is in the acceptable range for the speed tap to be used for dehumidification cooling.
6. Use any spare vinyl plugs to cap any unused speed tap wires.
Continuous Fan Operation
When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB “LOW” speed when the DH control lead is not energized, or IFB “HIGH” speed when the DH lead is energized (see Fig. 13).
NOTE: For heat pump operation, the recommended airflow is 350 to 450 CFM for each 12,000 Btuh of rated cooling capacity.
Table 6 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
Orange = Med--- High Speed
Red=MedSpeed
P i n k = M e d --- Lo w S p e ed
Blue = Low Speed
GAS HEAT
QC6 QC7 QC4 QC3
K2 K1
COMLOWHIGH
DCR QCR
on the interface fan board (IFB).
Two Cooling Fan Speeds Set-up (Dehumidification feature
IMPORTANT: Dehumidification control must open control
circuit on humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of either a 24 VAC dehumidistat or a thermostat which includes control of a 24 VAC dehumidistat connection. In either case, the dehumidification control must open the control circuit on humidity rise above the dehumidification set point. Dehumidification controls are available with the reverse logic; these must not be used.
used)
1. Remove fan speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 13).
2. Determine correct normal cooling fan speed for unit and application. Add the wet coil pressure drop in Table 8 to the system static to determine the correct cooling airflow speed in Table 10 that will deliver the nominal cooling airflow as listed in Table 1 for each size.
3. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the normal cooling fan speed and place desired speed tap wire on “HIGH” on the interface board.
R9 AB A15
U1
R3 R5 R6
P2
JW1
Y2/ Y1/
W2
Q1R1LC8RL3
JM6
Q3
G1
G2
C3
P1
GCR
YDH
SDL
RI0
C9
C4
D4D6C2OILL
A7
D3D5
P3
JW7
SSTZ-8
C7
R2
QCB
Y
YRUC24VAC
Fig. 13 -- Interface Fan Board (IFB)
JM5
JW3
D2
RI DL
R4 RL4
JW2
CDM/C
C
QC1
RI2
24VAC/R
3 AMP
F1
C0
JW4
A09058
4. Refer to airflow tables (Table 10) to determine allowable speeds for the dehumidification cooling fan speed. In Table 10, speeds that are not allowed for dehumidification cooling are shaded.
18
Page 19
FILTER SIZE
in. (mm)
20X20X1
(508X508X25)
20X24X1
(508X610x25 )
24X30X1
(610X762x25)
24X36X1
(610X914X25)
Table 7 – Filter Pressure Drop Table (IN. W.C.)
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15
0.09 0.10 0.11 0.13 0.14 0.15 0.16
0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.10
0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14 0.14
Table 8 – 674D-- -- A Wet Coil Pressure Drop (IN. W.C.)
Unit Size
24 0.06 0.07 0.08 0.09 0.10 30 0.12 0.15 0.19 0.23 0.27 36 0.07 0.11 0.18 0.26 0.35 42 0.04 0.07 0.10 0.15 0.21 48 0.11 0.14 0.17 0.22 0.28 60 0.10 0.17 0.23 0.31 0.36
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
Standard CFM (S.C.F.M)
Table 9 – Wet Coil Air Delivery (CFM) -- Downflow -- High Speed with 1--in. (25 mm) Filter and Economizer
UNIT SIZE
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 36 1333 1289 1256 1214 1152 1118 1076 1035 997 950 42 1612 1569 1527 1481 1451 1393 1351 1317 1278 1242 48 2166 2085 2002 1919 1798 1709 1582 1467 1270 988 60 2298 2239 2180 2110 2044 1951 1862 1777 1697 1591
EXTERNAL STATIC PRESSURE (IN. W.C.)
Table 10 – Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 674D----A24 -- 60
UNIT
674D(N,P,E)WA24040
674D(N,P,E)WA24060
HEATING
RISE RANGE
30 --- 60oF
o
( 1 7 --- 3 3
( 1 4 --- 3 1
25 --- 55oF
C)
o
C)
MOTOR
SPEED
Low Blue
M e d --- L o w Pink
Medium
M e d ---
High
High Black
Low Blue
M e d --- L o w Pink
Medium
M e d --- H i g h Orange
High
WIRE
COLOR
2
Red
Orange
1
2
Red
1
Black
CFM 754 650 538 429 --- --- --- --- --- --- --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 851 777 675 591 475 --- --- --- --- --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 941 851 774 684 576 479 --- --- --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 1009 917 840 759 667 577 447 --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 1241 1167 1111 1036 969 881 818 731 640
Heating
Rise (
Heating
Rise (
CFM 754 650 538 429 --- --- --- --- --- --- --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 851 777 675 591 475 --- --- --- --- --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 941 851 774 684 576 479 --- --- --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 1009 917 840 759 667 577 447 --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 1241 1167 1111 1036 969 881 818 731 640
Heating
Rise (
Heating
Rise (
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
40 46 56 NA NA NA NA NA NA
o
F)
22 26 31 NA NA NA NA NA NA
o
C)
36 39 45 51 NA NA NA NA NA
o
F)
20 22 25 28 NA NA NA NA NA
o
C)
32 36 39 44 52 NA NA NA NA
o
F)
18 20 22 25 29 NA NA NA NA
o
C)
30 33 36 40 45 52 NA NA NA
o
F)
17 18 20 22 25 29 NA NA NA
o
C)
NA NA NA NA 31 34 37 41 47
o
F)
NA NA NA NA 17 19 21 23 26
o
C)
NA NA NA NA NA NA NA NA NA
o
F)
NA NA NA NA NA NA NA NA NA
o
C)
52 NA NA NA NA NA NA NA NA
o
F)
29 NA NA NA NA NA NA NA NA
o
C)
47 52 NA NA NA NA NA NA NA
o
F)
26 29 NA NA NA NA NA NA NA
o
C)
44 48 53 NA NA NA NA NA NA
o
F)
24 27 29 NA NA NA NA NA NA
o
C)
36 38 40 43 46 50 54 NA NA
o
F)
20 21 22 24 25 28 30 NA NA
o
C)
EXTERNAL STATIC PRESSURE (IN. W.C.)
674D-- --A
19
Page 20
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 674D----A24--60
UNIT
674D(N,P,E)WA30040
HEATING
RISE RANGE
30 --- 60oF ( 1 7 --- 3 3
674D-- --A
674D(N,P,E)WA30060
674D(N,P,E)WA36060
25 --- 55oF
( 1 4 --- 3 1
25 --- 55oF
( 1 4 --- 3 1
o
C)
o
C)
o
C)
MOTOR
SPEED
WIRE
COLOR
Low Blue
M e d ---
Low
1
Pink
Medium Red
M e d --­High
Orange
2
High Black
Low Blue
M e d ---
Low
Pink
Medium Red
M e d --­High
High
Low
M e d ---
Low
Medium
M e d ---
High
Orange
2
1
Black
1
Blue
Pink
2
Red
Orange
High Black
CFM 741 638 547 415 --- --- --- --- --- --- --- --- --- ---
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Heating
Rise (
Heating
Rise (
CFM 973 887 823 733 665 538 451 --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 1088 1023 954 881 800 723 658 563 461
Heating
Rise (
Heating
Rise (
CFM 1140 1064 996 915 840 758 687 564 480
Heating
Rise (
Heating
Rise (
CFM 1202 1140 1082 1015 961 881 810 732 631
Heating
Rise (
Heating
Rise (
CFM 741 638 547 415 --- --- --- --- --- --- --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 973 887 823 733 665 538 451 --- --- --- ---
Heating
Rise (
Heating
Rise (
CFM 1088 1023 954 881 800 723 658 563 461
Heating
Rise (
Heating
Rise (
CFM 1140 1064 996 915 840 758 687 564 480
Heating
Rise (
Heating
Rise (
CFM 1202 1140 1082 1015 961 881 810 732 631
Heating
Rise (
Heating
Rise (
CFM 1234 1168 1093 1021 961 894 825 759 687
Heating
Rise (
Heating
Rise (
CFM 1290 1223 1154 1090 1027 977 894 828 762
Heating
Rise (
Heating
Rise (
CFM 1354 1290 1226 1158 1102 1046 981 918 843
Heating
Rise (
Heating
Rise (
CFM 1606 1546 1489 1430 1371 1316 1258 1208 1140
Heating
Rise (
Heating
Rise (
CFM 1630 1580 1517 1463 1407 1339 1277 1210 1131
Heating
Rise (
Heating
Rise (
41 47 55 NA NA NA NA NA NA
o
F)
23 26 31 NA NA NA NA NA NA
o
C)
31 34 37 41 45 56 NA NA NA
o
F)
17 19 20 23 25 31 NA NA NA
o
C)
NA 30 32 34 38 42 46 54 NA
o
F)
NA 16 18 19 21 23 26 30 NA
o
C)
NA NA 30 33 36 40 44 54 NA
o
F)
NA NA 17 18 20 22 24 30 NA
o
C)
NA NA NA 30 31 34 37 41 48
o
F)
NA NA NA 17 17 19 21 23 27
o
C)
NA NA NA NA NA NA NA NA NA
o
F)
NA NA NA NA NA NA NA NA NA
o
C)
46 50 54 NA NA NA NA NA NA
o
F)
25 28 30 NA NA NA NA NA NA
o
C)
41 43 47 50 NA NA NA NA NA
o
F)
23 24 26 28 NA NA NA NA NA
o
C)
39 42 45 49 53 NA NA NA NA
o
F)
22 23 25 27 29 NA NA NA NA
o
C)
37 39 41 44 46 50 55 NA NA
o
F)
21 22 23 24 26 28 30 NA NA
o
C)
36 38 41 44 46 50 54 NA NA
o
F)
20 21 23 24 26 28 30 NA NA
o
C)
34 36 39 41 43 45 50 54 NA
o
F)
19 20 21 23 24 25 28 30 NA
o
C)
33 34 36 38 40 42 45 48 53
o
F)
18 19 20 21 22 24 25 27 29
o
C)
28 29 30 31 32 34 35 37 39
o
F)
15 16 17 17 18 19 20 20 22
o
C)
27 28 29 30 32 33 35 37 39
o
F)
15 16 16 17 18 18 19 20 22
o
C)
EXTERNAL STATIC PRESSURE (IN. W.C.)
20
Page 21
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 674D----A24--60
UNIT
674D(N,P,E)WA36090
674D(N,P,E)WA42060
674D(N,P,E)WA42090
HEATING
RISE RANGE
35 --- 65oF
( 1 9 --- 3 6
25 --- 55oF
( 1 4 --- 3 1
35 --- 65oF
( 1 9 --- 3 6
MOTOR
SPEED
M e d --- L o w Pink
o
Medium
C)
M e d --- H i g h Orange
M e d --- L o w Pink
C)
Medium Red
o
M e d --- L o w Pink
o
Medium
C)
WIRE
COLOR
Low Blue
2
Red
1
High
Low
M e d ---
High
1
Black
Blue
Orange
2
High Black
Low Blue
1
Red
M e d ---
High
Orange
2
High Black
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
EXTERNAL STATIC PRESSURE (IN. W.C.)
CFM 1234 1168 1093 1021 961 894 825 759 687
Heating
Rise (
Heating
Rise (
CFM 1290 1223 1154 1090 1027 977 894 828 762
Heating
Rise (
Heating
Rise (
CFM 1354 1290 1226 1158 1102 1046 981 918 843
Heating
Rise (
Heating
Rise (
CFM 1606 1546 1489 1430 1371 1316 1258 1208 1140
Heating
Rise (
Heating
Rise (
CFM 1630 1580 1517 1463 1407 1339 1277 1210 1131
Heating
Rise (
Heating
Rise (
CFM 1295 1234 1182 1126 1075 1016 955 898 857
Heating
Rise (
Heating
Rise (
CFM 1345 1282 1235 1194 1140 1095 1027 974 921
Heating
Rise (
Heating
Rise (
CFM 1505 1452 1413 1358 1323 1282 1234 1169 1130
Heating
Rise (
Heating
Rise (
CFM 1545 1492 1449 1411 1362 1313 1278 1231 1188
Heating
Rise (
Heating
Rise (
CFM 1705 1643 1607 1568 1518 1483 1448 1404 1360
Heating
Rise (
Heating
Rise (
CFM 1295 1234 1182 1126 1075 1016 955 898 857
Heating
Rise (
Heating
Rise (
CFM 1345 1282 1235 1194 1140 1095 1027 974 921
Heating
Rise (
Heating
Rise (
CFM 1505 1452 1413 1358 1323 1282 1234 1169 1130
Heating
Rise (
Heating
Rise (
CFM 1545 1492 1449 1411 1362 1313 1278 1231 1188
Heating
Rise (
Heating
Rise (
CFM 1705 1643 1607 1568 1518 1483 1448 1404 1360
Heating
Rise (
Heating
Rise (
55 58 62 NA NA NA NA NA NA
o
F)
31 32 35 NA NA NA NA NA NA
o
C)
53 56 59 62 NA NA NA NA NA
o
F)
29 31 33 35 NA NA NA NA NA
o
C)
50 53 55 59 62 65 NA NA NA
o
F)
28 29 31 33 34 36 NA NA NA
o
C)
42 44 46 48 50 52 54 56 60
o
F)
24 24 25 26 28 29 30 31 33
o
C)
42 43 45 46 48 51 53 56 60
o
F)
23 24 25 26 27 28 30 31 33
o
C)
34 36 38 39 41 44 47 49 52
o
F)
19 20 21 22 23 24 26 27 29
o
C)
33 35 36 37 39 41 43 46 48
o
F)
18 19 20 21 22 23 24 25 27
o
C)
30 31 31 33 34 35 36 38 39
o
F)
16 17 17 18 19 19 20 21 22
o
C)
29 30 31 31 33 34 35 36 37
o
F)
16 17 17 17 18 19 19 20 21
o
C)
26 27 28 28 29 30 31 32 33
o
F)
14 15 15 16 16 17 17 18 18
o
C)
53 55 58 60 63 NA NA NA NA
o
F)
29 31 32 34 35 NA NA NA NA
o
C)
51 53 55 57 60 62 NA NA NA
o
F)
28 29 31 32 33 35 NA NA NA
o
C)
45 47 48 50 51 53 55 58 60
o
F)
25 26 27 28 29 29 31 32 33
o
C)
44 46 47 48 50 52 53 55 57
o
F)
24 25 26 27 28 29 30 31 32
o
C)
40 41 42 43 45 46 47 48 50
o
F)
22 23 24 24 25 25 26 27 28
o
C)
674D-- --A
21
Page 22
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 674D----A24--60
UNIT
674D(N,P,E)WA48090
HEATING
RISE RANGE
35 --- 65oF
o
( 1 9 --- 3 6
674D-- --A
674D(N,P,E)WA48115
674D(N,P,E)WA48130
30 --- 60oF
( 1 7 --- 3 3
35 --- 65oF
( 1 9 --- 3 6
o
o
MOTOR
SPEED
Low
M e d ---
Low
Medium
C)
M e d ---
High
High Black
Low Blue
M e d ---
Low
Medium
C)
M e d ---
High
High Black
Low Blue
M e d ---
Low
Medium
C)
M e d ---
High
High Black
WIRE
COLOR
CFM 1402 1351 1311 1263 1224 1172 1136 1080 1041
1
Blue
Heating
Rise (
Heating
Rise (
CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104
Heating
Pink
Rise (
Heating
Rise (
CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381
2
Red
Heating
Rise (
Heating
Rise (
CFM 2149 2111 2062 2026 1980 1945 1905 1864 1793
Heating
Orange
Rise (
Heating
Rise (
CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803
Heating
Rise (
Heating
Rise (
CFM 1402 1351 1311 1263 1224 1172 1136 1080 1041
Heating
Rise (
Heating
Rise (
CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104
Heating
Pink
Rise (
Heating
Rise (
CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381
2
Red
Heating
Rise (
Heating
Rise (
CFM 2149 2111 2062 2026 1980 1945 1905 1864 1793
Heating
Orange
1
Rise (
Heating
Rise (
CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803
Heating
Rise (
Heating
Rise (
CFM 1402 1351 1311 1263 1224 1172 1136 1080 1041
Heating
Rise (
Heating
Rise (
CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104
Heating
Pink
Rise (
Heating
Rise (
CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381
2
Red
Heating
Rise (
Heating
Rise (
CFM 2149 2111 2062 2026 1980 1945 1905 1864 1793
Heating
Orange
1
Rise (
Heating
Rise (
CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803
Heating
Rise (
Heating
Rise (
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
49 50 52 54 56 58 60 63 65
o
F)
27 28 29 30 31 32 33 35 36
o
C)
47 48 50 52 53 55 57 59 62
o
F)
26 27 28 29 29 31 32 33 34
o
C)
39 40 41 42 44 45 46 48 49
o
F)
22 22 23 24 24 25 26 26 27
o
C)
NA NA NA NA NA 35 36 36 38
o
F)
NA NA NA NA NA 19 20 20 21
o
C)
NA NA NA NA NA NA NA 36 38
o
F)
NA NA NA NA NA NA NA 20 21
o
C)
NA NA NA NA NA NA NA NA NA
o
F)
NA NA NA NA NA NA NA NA NA
o
C)
60 NA NA NA NA NA NA NA NA
o
F)
33 NA NA NA NA NA NA NA NA
o
C)
50 51 53 54 56 57 59 NA NA
o
F)
28 28 29 30 31 32 33 NA NA
o
C)
40 41 42 43 44 45 46 47 48
o
F)
22 23 23 24 24 25 25 26 27
o
C)
37 38 38 39 41 42 44 46 48
o
F)
21 21 21 22 23 23 24 25 27
o
C)
NA NA NA NA NA NA NA NA NA
o
F)
NA NA NA NA NA NA NA NA NA
o
C)
NA NA NA NA NA NA NA NA NA
o
F)
NA NA NA NA NA NA NA NA NA
o
C)
55 57 59 60 62 64 NA NA NA
o
F)
31 32 33 33 34 35 NA NA NA
o
C)
45 46 47 48 49 50 51 52 54
o
F)
25 25 26 26 27 28 28 29 30
o
C)
41 42 43 44 45 47 48 51 53
o
F)
23 23 24 24 25 26 27 28 30
o
C)
EXTERNAL STATIC PRESSURE (IN. W.C.)
22
Page 23
Table 10 (cont) -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 674D----A24--60
UNIT
674D(N,P,E)WA60090
674D(N,P,E)WA60115
674D(N,P,E)WA60130
* Air delivery values a r e without air filter and a re for dry coil (See Table 8 --- 674D --- A Wet Coil Pressure Drop table).
1
Factory---shipped gas heating speed
2
Factory --- shipped heat pump speed
HEATING
RISE RANGE
35 --- 65oF
o
( 1 9 --- 3 6
30 --- 60oF
o
( 1 7 --- 3 3
35 --- 65oF
o
( 1 9 --- 3 6
MOTOR
SPEED
Low
M e d --- L o w Pink
Medium
C)
M e d --- H i g h Orange
High Black
Low Blue
M e d --- L o w Pink
Medium
C)
M e d ---
High
High Black
Low Blue
M e d --- L o w Pink
Medium
C)
M e d ---
High
High Black
WIRE
COLOR
CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
1
Blue
Heating
Rise (
Heating
Rise (
CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Heating
Rise (
Heating
Rise (
CFM 1927 1893 1858 1824 1791 1759 1720 1689 1640
2
Red
Heating
Rise (
Heating
Rise (
CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Heating
Rise (
Heating
Rise (
CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Heating
Rise (
Heating
Rise (
CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
Heating
Rise (
Heating
Rise (
CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Heating
Rise (
Heating
Rise (
CFM 1927 1893 1858 1824 1791 1759 1720 1689 1640
2
Red
Heating
Rise (
Heating
Rise (
CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Heating
Orange
1
Rise (
Heating
Rise (
CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Heating
Rise (
Heating
Rise (
CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
Heating
Rise (
Heating
Rise (
CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Heating
Rise (
Heating
Rise (
CFM 1927 1893 1858 1824 1791 1759 1720 1689 1640
2
Red
Heating
Rise (
Heating
Rise (
CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Heating
Orange
1
Rise (
Heating
Rise (
CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Heating
Rise (
Heating
Rise (
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
47 49 51 53 55 57 60 63 NA
o
F)
26 27 28 29 31 32 33 35 NA
o
C)
41 42 42 44 45 46 47 48 50
o
F)
23 23 24 24 25 26 26 27 28
o
C)
35 36 37 37 38 39 40 40 41
o
F)
20 20 20 21 21 21 22 22 23
o
C)
NA NA NA NA NA 35 36 37 38
o
F)
NA NA NA NA NA 19 20 20 21
o
C)
NA NA NA NA NA NA NA 35 36
o
F)
NA NA NA NA NA NA NA 19 20
o
C)
60 NA NA NA NA NA NA NA NA
o
F)
33 NA NA NA NA NA NA NA NA
o
C)
52 53 54 56 57 59 60 NA NA
o
F)
29 30 30 31 32 33 34 NA NA
o
C)
45 46 47 48 49 49 51 51 53
o
F)
25 26 26 26 27 27 28 29 29
o
C)
41 42 42 43 44 45 46 47 49
o
F)
23 23 23 24 24 25 26 26 27
o
C)
35 36 37 38 40 41 42 44 46
o
F)
20 20 21 21 22 23 23 25 26
o
C)
NA NA NA NA NA NA NA NA NA
o
F)
NA NA NA NA NA NA NA NA NA
o
C)
57 59 60 62 64 65 NA NA NA
o
F)
32 33 33 34 35 36 NA NA NA
o
C)
50 51 52 53 54 55 56 57 59
o
F)
28 28 29 29 30 30 31 32 33
o
C)
45 46 47 48 49 50 51 52 54
o
F)
25 26 26 27 27 28 28 29 30
o
C)
39 40 41 42 44 45 47 49 51
o
F)
22 22 23 23 24 25 26 27 29
o
C)
NA --- Not allowed for heating speed Note: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting. Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
EXTERNAL STATIC PRESSURE (IN. W.C.)
674D-- --A
23
Page 24
674D-- --A
Fig. 14 -- 208/230--1-- 60 Connection Wiring Diagram, Unit 674D
A10207C
24
Page 25
674D-- --A
Fig. 14 Cont -- 208/230--1--60 Ladder Wiring Diagram, Unit 674D----A
A10207L
25
Page 26
674D-- --A
Fig. 15 -- 208/230--3-- 60 Connection Wiring Diagram, Unit 674D-- -- A
A10208C
26
Page 27
674D-- --A
Fig. 15 Cont. -- 208/230--3--60 Ladder Wiring Diagram, Unit 674D----A
A10208L
27
Page 28
674D-- --A
A08019
Fig. 16 -- Cooling Charging Table--Subcooling
28
Page 29
MAINTENANCE
To ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This combination heating/cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot cooling or heating of units, refer to Tables 10, 11 and 12.
NOTE: Consult your local dealer about the availability of a maintenance contract.
!
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and unit component damage.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possessthese, do not attemptto perform any maintenance on this equipment,other than those procedures recommended in the Owner’s Manual.
!
ELECTRICAL SHOCK AND EXPLOSION HAZARD
Failure to follow these warnings could result in personal injury or death:
1. Turn off electrical power to the unit and install a lockout tag before performing any maintenance or service on this unit.
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact with the unit.
4. Should overheating occur or the gas supply fail to shut off, turn off external main manual gas valve to the unit. Then shut off electrical supply.
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 18) or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit.
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper operation.
Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing.
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary. Certain geographical locations may require more frequent inspections.
2. Inspect indoor coil, outdoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
WARNING
WARNING
!
CAUTION
!
CAUTION
3. Inspect blower motor and wheel for cleanliness at the beginning of each heating and cooling season. Clean when necessary. For first heating and cooling season, inspect blower wheel bi--monthly to determine proper cleaning frequency.
4. Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary. Ensure electrical wiring is not in contact with refrigerant tubing or sharp metal edges.
5. Check and inspect heating section before each heating season. Clean and adjust when necessary.
6. Check flue hood and remove any obstructions, if necessary.
Air Filter
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the same dimensional size and type as originally installed. (See Table 1 for recommended filter sizes.)
Inspect air filter(s) at least once each month and replace (throwaway--type) or clean (cleanable--type) at least twice during each heating and cooling season or whenever the filter(s) becomes clogged with dust and/or lint.
Indoor Blower and Motor
NOTE: All motors are prelubricated. Do not attempt to lubricate
these motors.
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect and install lockout tag on electrical power to the unit before cleaning and lubricating the blower motor and wheel.
Cleaning the Blower Motor and Wheel
1. Remove and disassemble blower assembly as follows:
a. Remove blower access panel (see Fig. 18).
b. Disconnect 5 pin plug and 4 pin plug from indoor
blower motor. Remove capacitor if required.
c. On all units, remove blower assembly from unit.
Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft.
Remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.
2. Remove and clean blower wheel as follows:
a. Ensure proper reassembly by marking wheel orientation.
b. Lift wheel from housing. When handling and/or
cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.
c. Remove caked--on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing.
e. Reassemble motor into housing. Be sure setscrews are
tightened on motor shaft flats and not on round part of shaft. Reinstall blower into unit. Reinstall capacitor.
29
674D-- --A
Page 30
f. Connect 5 pin plug and 4 pin plug to indoor blower
motor.
g. Reinstall blower access panel (see Fig. 18).
3. Restore electrical power to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.
Integrated Gas Unit Controller (IGC)
Auto Transformer fuses used on 460 volt units only. (Hidden)
Interface Fan Board (IFB)
Induced Draft Motor
1. Remove the induced draft blower assembly according to directions in the Induced Draft Blower Assembly section.
2. Remove the 11 screws holding the flue collector box cover (See Fig. 17) to the heat exchanger assembly. Inspect the heat exchangers.
3. Clean all surfaces, as required, using a wire brush.
Limit Switch
Remove blower access panel (see Fig. 18). Limit switch is located on the fan partition.
Burner Ignition
Unit is equipped with a direct spark ignition 100 percent lockout system. Ignition module (IGC) is located in the control box (See Fig. 17). Module contains a self--diagnostic LED. During servicing, refer to label diagram or Table 5 in these instructions for LED interpretation.
If lockout occurs, unit may be reset by either momentarily
Fan Partition Mounting Bracket
Flue Collector Box
Inducer Blower Housing
Burner Rack
Mounting Screw
Rollout Switch
Fig. 17 -- Blower Housing and Flue Collector Box
A09193
interrupting power supply to unit or by turning selector switch to OFF position at the thermostat.
Main Burners
At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.
674D-- --A
Removal of Gas T
rain
To remove the gas train for servicing:
1. Shut off main gas valve.
2. Shut off power to unit and install lockout tag.
3. Remove control access panel (See Fig. 18).
4. Disconnect gas piping at unit gas valve.
5. Remove fan partition mounting bracket (2 screws located on the left side of the control compartment on the fan parti­tion panel). Slide bracket forward, bottom first, to remove (See Fig. 17).
6. Remove wires connected to gas valve. Mark each wire.
7. Remove the mounting screw that attaches the burner rack to
CONTROL ACCESS PAN EL
A09207
COMPRESSOR ACCESS PANEL
BLOWER ACCESS PAN EL
Fig. 18 -- Unit Access Panels
Induced Draft (combustion air) Blower Assembly
The induced--draft blower assembly consists of the inducer motor, the blower housing, and the induced--draft blower wheel.
Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during the heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove induced--draft blower assembly as follows:
1. Remove control access panel (See Fig. 18).
2. Remove the 5 screws that attach induced--draft blower as­sembly to the flue collector box cover.
3. Slide the assembly out of the unit. (See 20). Clean the blower wheel. If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower wheel, remove 2 setscrews.
5. To remove inducer motor, remove screws that hold the inducer motor to the blower housing.
6. To reinstall, reverse the procedure outlined above.
Flue Gas Passageways
To inspect the flue collector box and upper areas of the heat
the unit base (See Fig. 17).
8. Partially slide the burner rack out of the unit (see Fig. 17 and 20). Remove ignitor and sensor wires at the burner as­sembly. Remove rollout switch wires.
9. Slide the burner rack out of the unit (See Fig. 17 and 20).
10. T o reinstall, reverse the procedure outlined above.
Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the outdoor coil, indoor coil, and condensate drain pan at least once each year. The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent--and--water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray outdoor coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a “plumbers snake” or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.
exchanger:
30
Page 31
BLOWER HOUSING
2 SETSCREWS (HIDDEN)
Fig. 19 -- Removal of Motor and Blower Wheel
Fig. 20 -- Burner Rack Removed
FEEDER TUBE
STUB TUBE
DEFROST THERMOSTAT
Fig. 21 -- Defrost Thermostat Location
C99085
A07680
C99029
A07680
Fig. 22 -- Burner Rack Removed
Outdoor Fan
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components.
Keep the outdoor fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit.
1. Remove 6 screws holding outdoor grille and motor to top cover.
2. Turn motor/grille assembly upside down on top cover to expose the fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the fan off the motor shaft.
5. When replacing fan blade, position blade back to the same position as before.
6. Ensure that setscrew engages the flat area on the motor shaft when tightening.
7. Replace grille.
CAUTION
Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn off the gas supply, and then the electrical power to the unit.
Remove access panels (see Fig. 18) to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any discolored or burned connections are noticed, disassemble the connection, clean all the parts, re--strip the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace the access panels (see Fig. 18). Start the unit, and observe at least one complete heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in any operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of operation in this publication as an aid in determining proper control operation.
Refrigerant Circuit
Annually inspect all refrigerant tubing connections and the unit base for oil accumulations. Detecting oil generally indicates a refrigerant leak.
674D-- --A
31
Page 32
T2 C C O
OF1
OF2
DFT
O R W
T1 Y
2
Y C
P1
SPEEDUP
30
60
J1
674D-- --A
P3
DFT
INTERVAL TIMER
90
OFF
30
SHIFT
120
60
ON
QUIET
Speedup Pins
!
EXPLOSION, PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
System under pressure. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow--control devices, including solenoid valves.
If oil is detected or if low cooling performance is suspected, leak-- test all refrigerant tubing using an electronic leak--detector, halide torch, or liquid--soap solution. If a refrigerant leak is detected, refer to the Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is suspected, refer to the Checking and Adjusting Refrigerant Charge section.
WARNING
Quiet Shift
Fig. 23 -- Defrost Control
Gas Input
The gas input does not require checking unless improper heating performance is suspected. If a problem exists, refer to the Start--Up section.
Indoor Airflow
The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply-- and return--air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to
Defrost interval DIP switches
the Indoor Airflow and Airflow Adjustments section to check the system airflow.
Check Defrost Thermostat
The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil (see Fig. 21). The thermostat closes at 32_F(0_C) and opens at 65_F(18_C).
Puron Items Metering Device
Piston)
This unit uses both a hard shutoff, balance port TXV in the indoor coil and a piston in each side of the outdoor coil. The TXV maintains a constant superheat at the evaporator coil exit (cooling mode) resulting in higher overall system efficiency.
Pressure Switches
Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron (R--410A) systems. R--22 pressure switches must not be used as replacements for the Puron (R--410A) system.
Loss of Charge Switch
This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 20 psig. If system pressure is above this, switch should be closed. To check switch:
1. Turn off all power to unit.
(Thermostatic Expansion Valve &
A08020
32
Page 33
Fig. 24 -- Refrigerant Circuit
674D-- --A
C99097
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have continuity on a good switch.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system without breaking vacuum with dry nitrogen.
High--Pressure Switch
The high--pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at 650 psig.
High pressure may be caused by a dirty outdoor coil, failed fan motor, or outdoor air recirculation. To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have continuity on a good switch.
Copeland Scroll Compressor (Puron Refrigerant)
The compressor used in this product is specifically designed to operate with Puron (R--410A) refrigerant and cannot be interchanged.
The compressor is an electrical (as well as mechanical) device. Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most troubleshooting techniques. Refrigerants present additional safety hazards.
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with an internal pressure relief port. The pressure relief port is a safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550 and 625 psig differential pressure.
33
Page 34
HP S
ACCUMULATOR
COMPRESSOR
LEGEND
HPS – High Pressure Switch LCS – Loss of Charge Switch
Accurater
®
Metering De vice
Arrow indicates direction of flo w
OUTDOOR COIL
Bypass
Position
TXV in Metering
Position
LCS
INDOOR COIL
674D-- --A
C03011
Fig. 25 -- Typical Heat Pump Operation, Cooling Mode
INDOOR COIL
ACCUMULATOR
HP S
COMPRESSOR
OUTDOOR COIL
Metering
Position
TXV in Bypass
Position
LCS
LEGEND
HPS – High Pressure Switch LCS – Loss of Charge Switch
®
Accurater
Metering De vice
Arrow indicates direction of flo w
C03012
Fig. 26 -- Typical Heat Pump Operation, Heating Mode
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
This system uses Puron (R --410A) refrigerant which has higher operating pressures than R--22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses,and recovery systemmustbe designedto handle Puron. If you are unsure, consult the equipment manufacturer.
Refrigerant System
This information covers the refrigerant system of the 674D ----A, including the compressor oil needed, servicing systems on roofs containing synthetic materials, the filter drier and refrigerant charging.
Compressor Oil
If additional oil is needed use Uniqema RL32--3MAF. If this oil is not available, use Copeland Ultra 32CC or Mobil Artic EAL22CC. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.
34
Page 35
Servicing Systems on Roofs and with Synthetic materials
POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve.
Synthetic Roof Precautionary Procedure
1. Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10x10 ft (3x3 m) area.
2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent run--offs, and protect drop cloth from tears caused by tools or components.
3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run--offs through the louvered openings in the unit base.
4. Perform required service.
5. Remove and dispose of any oil contaminated material per local codes.
Liquid Line Filter Drier
This filter drier is specifically designed to operate with Puron. Use only factory--authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system.
Puron (R--410A) Refrigerant Charging
Refer to unit information plate and charging chart. Some R--410A refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position. For cylinders equipped with a dip tube, charge Puron units with cylinder in upright position and a commercial metering device in manifold hose. Charge refrigerant into suction--line.
TROUBLESHOOTING
Use the Troubleshooting Guides (See Tables 10--12) if problems occur with these units.
START--UP CHECKLIST
Use Start-- Up checklist to ensure proper start--up procedures are followed.
674D-- --A
PURONR (R--410A) QUICK REFERENCE GUIDE
S Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S Puron refrigerant cylinders are rose colored. S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. S Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low--side retard. S Use hoses with minimum 700 psig service pressure rating. S Leak detectors should be designed to detect HFC refrigerant. S Puron, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil. S Do not use liquid--line filter driers with rated working pressures less than 600 psig. S Do not leave Puron suction line filter driers in line longer than 72 hrs. S Do not install a suction-- line filter drier in liquid line. S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing.
S A factory approved liquid--line filter drier is required on every unit. S Do NOT use an R--22 TXV. S Never open system to atmosphere while it is under a vacuum. S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S Do not vent Puron into the atmosphere. S Observe all warnings, cautions,andbold text. S All indoor coils must be installed with a hard shutoff Puron TXV metering device.
35
Page 36
Table 11 – Troubleshooting Guide -- Cooling or Heat Pump Heating Mode
SYMPTOM CAUSE REMEDY
Compressor and Outdoor fan will not start.
Compressor will not start but Outdoor fan runs.
Three--- phase scroll compressor makes excessive noise, and there may be a low pressure differential.
Compressor cycles (other than normally satisfying thermostat).
674D-- --A
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Compressor runs but outdoor fan does not
Powe r Failure Call power company. Fuse blown or circuit breaker tripped Replacefuseorresetcircuitbreaker. Defective thermostat, contactor, transformer, or control relay Insufficient line voltage Determine cause and correct. Incorrect or faulty wiring Check wirin g diagram and rewire correctly. Thermostat setting too high Lower thermostat setting below room temperature. Faulty wiring or loose connections in compressor circuit Check wiring and repair or replace. Compressor motor burned out, seized, or internal over­load open Defective run/start capacitor, overload, start relay Determine cause and replace.
Onelegof3---phasepowerdead
Scroll compressor is rotating in the wrong direction
Refrigerant overcharge or undercharge
Defective compressor Replace and determine cause. Insufficient line voltage Determine cause and correct. Blocked Outdoor Determine cause and correct. Defective run/start capacitor, overload or start relay Determine cause and replace. Defective thermostat Replace thermostat. Faulty Outdoor--- fan motor or capacitor Replace. Damaged reversing valve Determine cause and correct Restriction in refrigerant system Locate restriction and remove. Dirty air filter Replace filter. Unit undersized for load Decrease load or increase un it size. Thermostat set too low Reset thermostat. Low refrigerant charge Locate leak, repair, and recharge. Mechanical damage in compressor. Replace compressor. Air in system Recover refrigerant, evacuate system, and recharge.
Frosted coil with incorrect defrost operation
Outdoor coil dirty or restricted Clean coil or r emove restriction . Dirty air filter Replace filter. Dirty Indoor or Outdoor coil Clean coil. Refrigerant overcharged Recover excess refrigerant. Air in system Recover refrigerant, evacuate system, and recharge. Indoor or Outdoor air restricted or air short --- cycling Determine cause and correct. Low refrigerant charge Check for leaks, repair, and recharge. Compressor IPR leaking Replace compressor. Restrictioninliquidtube Remove restriction. High heat load Check for source and eliminate. Compressor IPR l eaking Replace compressor. Refrigerant overcharged Recover excess refrigerant. Reversing valve hung up or leaking internally Replace valve Dirty air filter Replace Filter. Low refrigerant charge Check for leaks, repair, and recharge. Metering device or low side restricted Remove source of restriction.
Insufficient Indoor airflow
Temperature too low in conditioned ar ea Reset thermostat. Outdoor ambient below 55°F (12.8°C) Install low --- ambient kit. Field ---installed filter ---drier restr icted Replace.
(Heat) Outdoor coil frosted
NC (normally closed) contacts on defrost board open
Replace component.
Determine cause Replace compressor.
Replace fuse or reset circuit breaker. D etermine cause.
Correct the direction of rotation by reversing the 3--- phase power leads to the unit.
Recover refrigerant, evacuate system, and recharge to capacities shown on nameplate.
Check defrost time settings, Reset as necessary Check defrost temperature switch, Replace as nec­essary
Increase air quantity. Check filter — replace if neces­sary.
Move timer on control board to 30 minutes between defrost cycles Check condition of relay on board Replace if neces­sary
36
Page 37
Table 12 – Troubleshooting Guide–Heating
SYMPTOM CAUSE REMEDY
Burners will not ignite
Inadequate heating
Poor flame characteristics
Water in gas line Drain. Install drip leg. No power to furnace Check power supply fuses, wiring or circuit breaker.
No 24--v power supply to control circuit
Mis--wired or loose connections Check all wiring and wire nut connections
Misaligned spark electrodes
No gas at main burners
Dirty air filter Clean or replace filter as necessary Gas input to furnace too low Check gas pressure at manifold match with that on unit nameplate Unit undersized for application Replace with proper unit or add additional unit Restricted airflow Clean or replace filter. Remove any restriction.
Limit switch cycles main burners
Incomplete combustion results in: Aldehyde odors, carbon monoxide, sooting flame, floating flame
Check transformer. NOTE: Some transformers have internal over-- current protection that requires a cool--down period to reset.
Check flame ignition and sense electrode positioning. Adjust as necessary.
1. Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate be­fore attempting to light unit.
2. Check gas valve.
Check rotation of blower, temperature rise of unit. Adjust as neces­sary.
1. Tighten all screws around burner compartment
2. Cracked heat exchanger. Replace.
3. Unit over --fired. Reduce input (change orifices or adjust gas line or manifold pressure).
4. Check burner alignment.
5. Inspect heat exchanger for blockage. Clean as necessary.
Table 13 – Troubleshooting Guide–LED Error Codes
SYMPTOM CAUSE REMEDY
No Power or Hardware fail­ure (LED OFF)
Limit switch faults (LED 2 flashes)
Flame sense fault (LED 3 flashes)
4 consecutive limit switch faults (LED 4 flashes)
Ignition lockout (LED 5 flashes)
Pressure Switch Fault (LED 6 flashes)
Rollout switch fault (LED 7 flashes)
Internal control fault (LED 8 flashes)
Temporary 1 hr auto reset (LED 9 flashes)
*WARNING : If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that my be present before handling new control board. The IGC is sensitive to static electricity and my be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to Table 11 - -- Troubleshooting Guide --- Heating for additional troubleshooting analysis. LEGEND
IGC—Integrated Gas Unit Controller LED—Light--- Emitting Diode
Loss of power to control module (IGC)*.
High temperature limit switch is open.
The IGC* sensed flame that should not be present. Reset unit. If problem persists, replace control board.
Inadequate airflow to unit.
Unit unsuccessfully attempted ignition for 15 minutes.
Open pressure switch.
Rollout switch has opened.
Microprocessor has sensed an error in the software or hardware.
Electrical interference impeding IGC software
Check 5-- amp fuse son IGC*, power to unit, 24-- v circuit breaker, and transformer. Units without a 24--v circuit breaker have an internal overload in the 24--v transformer. If the overload trips, allow 10 minutes for automatic reset.
Check the operation of the indoor (evaporator) fan motor. Ensure that the supply--air temperature rise is in accordance with the range on the unit nameplate. Clean or replace filters.
Check the operation of the indoor (evaporator) fan motor and that supply--air temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that fame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Verify wiring connections to pressure switch and inducer motor. Verify pressure switch hose is tightly connected to both inducer housing and pressure switch. Verify inducer wheel is properly attached to inducer motor shaft. Verify inducer motor shaft is turn­ing.
Rollout switch will automatically reset, but IGC* will continue to lockout unit. Check gas valve operation. Ensure that induced--draft blower wheel is properly secured to motor shaft. Inspect heat exchanger. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC*.
Reset 24--v. to control board or turn thermostat off, then on again. Fault will automatically reset itself in one (1) hour.
674D-- --A
37
Page 38
START--UP CHECKLIST
(Remove and Store in Job Files)
I. PRELIMINARY INFORMATION
MODEL NO.:
SERIAL NO.: DATE:
TECHNICIAN:
II. PRESTART-- UP (Insert check mark in box as each item is completed)
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS F OR TIGHTNESS ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE)
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE ( ) VERIFY THAT UNIT INSTALLATION IS LEVEL
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
III. START--UP
ELECTRICAL
674D-- --A
SUPPLY VOLTAGE
COMPRESSOR AMPS INDOOR (EVAPORATOR) FAN AMPS
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE DB RETURN--AIR TEMPERATURE DB WB
COOLING SUPPLY AIR DB WB HEAT PUMP SUPPLY AIR__________________
GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE IN. W.C.
GAS MANIFOLD PRESSURE IN. W.C. REFRIGERANT SUCTION PSIG, SUCTION LINE TEMP* REFRIGERANT DISCHARGE PSIG, LIQUID TEMP{ ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS GAS HEAT TEMPERATURE RISE
TEMPERATURE RISE (See Literature) RANGE MEASURED TEMPERATURE RISE
* Measured at suction inlet to compressor { Measured at liquid line leaving condenser.
38
Page 39
VERTICAL ECONOMIZER
(FACTORY INSTALLED OPTION)
GENERAL
Economizers are recommended for only commercial packaged products that have X13 motors. The Economizer system utilizes the latest technology available for integrating the use of free cooling with mechanical cooling for rooftop units. The solid state control system optimizes energy consumption, zone comfort, and equipment cycling by operating the compressors when the outdoor air temperature is too warm, integrating the compressor with outdoor air when free cooling is available, and locking out the compressor when outdoor air temperature is too cold. Demand ventilation is supported.
The Economizer system utilizes gear--drive technology with a direct--mount spring return actuator that will close upon loss of power. The Economizer system comes standard with an outdoor air temperature sensor, a supply air temperature sensor, and low temperature compressor lockout switch. Indoor enthalpy, outdoor enthalpy, and CO
Barometric relief dampers provide natural building pressurization control. Barometric relief dampers are built into the design and are standard. See Table 14 for Hood Package contents. See Table 15 forsensorusage.
SMALL CHASSIS
(sizes 30 and 36)
Qty Content Description Qty Content Description
1 Hood Side, Right 1 Hood Side, Right
1 Hood Side, Left 1 Hood Side, Left
2 Angle, Filter 2 Angle, Filter
1
(20--- 1/2” x 16--- 1/2 x 1”)
(521 x 419 x 25 mm)
18
(#10 --- 14 x 5/8” w/Seal
2
( # 8 --- 1 8 x 3 / 4 ” T y pe B P a n
APPLICATION
Outdoor A ir Dry Bulb
Single Enthalpy HH57AC078
Differential Enthalpy HH57AC078 and CRENTDIF004A00*
CO2for DCV Control
U s i n g a W a l l --- M o u n t e d
CO
Sensor
2
CO2for DCV Control
U s i n g a D u c t ---
Mounted CO
*CRENTDIF004A00 accessory is used on many different base units. As such, these kits may contain parts that will not be needed for installation.
{33ZCSENCO2 and CGCDXSEN004A00 are accessory CO **33ZCASPC02 AND CGCDXASP00100 are accessory aspirator boxes
required for duct --- mounted applications. {{CRCBDIOX005A00 is a n accessory that contains both 33ZCSENCO2
AND 33ZVASPC02 accessories.
sensors are available for field installation.
2
Table 14 – Package Contents
LARGE CHASSIS
(sizes 42, 48, and 60)
Aluminum Filter
1
Screws
18
Washer)
Screws
2
Head)
1 Bracket, Sensor
Aluminum Filter
(20--- 1/2” x 16--- 1/2 x 1”)
(521 x 419 x 25 mm)
(#10 --- 14 x 5/8” w/Seal
( # 8 --- 1 8 x 3 / 4 ” T y pe B P a n
Table 15 – Economizer Sensor Usage
Sensor
2
ECONOMIZER WITH OUTDOOR AIR DRY BULB
None, The outdoor air dry bulb sensor is factory
33ZCSENC02 or CGCDXSEN004A00
33ZCSENC02 or
CGCDXSEN004A00{ and 33ZCASPCO2 or CGCDXASP00100**
SENSOR
Accessories Required
installed.
or CRCBDIOX005A00{{
Screws
Washer)
Screws
Head)
sensors.
2
ACCESSORIES
The economizer has several field--installed accessories available to optimize performance. Refer to Table 16 for authorized parts.
Table 16 – Accessory List
DESCRIPTION PA RT N UM BE R
Outdoor Air Enthalpy Sensor HH57AC078
Indoor Air Enthalpy Sensor CRENTDIF004A00
Return Air CO2Sensor (4--- 20 mA) CRCBDIOX005A00
CO2Room Sensor (4 ---20 mA)
Aspirator Box for duct Mount CO2Sensor
( 4 --- 2 0 m A )
Space Temperature and CO2Room
Sensor with Override (4 ---20mA)
Space Temperature and CO2Room
Sensor with Override and Set Point
( 4 --- 2 0 m A )
Heat Pump Relay Package CPRLYKIT001A00
33ZCSENX02 Or
CGCDXSEN004A00
33ZCASPC02 Or
CGCDXASP001A00
33ZCT55C02
33ZCT56C02
INSTALLATION
Small Chassis
To install the Vertical Economizer on the small chassis perform the following procedure:
1. Turn off unit power supply and install lockout tag.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
2. Remove economizer hood top panel from the return side of the unit. See Fig. 27. Keep screws and panel next to the unit.
3. Open economizer hood package found on the top skid.
4. Remove red shipping tape that attaches the outside air temperature (OAT) sensor to the economizer assembly. Using two #8 fasteners, found in the hood package, attach the OAT sensor to the economizer according to Fig. 28.
NOTE: See label attached to economizer for OAT installing details.
5. Remove horizontal return duct cover panel and cut the wire ties that hold the hood divider to the economizer assembly. Slide hood divider off from the two slots holding it in place and place next to the unit. See Fig. 29.
NOTE: Gas units have a flue hood attached to the hood divider. Unscrew the fastener holding the flue hood in place and dispose the screw. Follow unit’s literature for flue hood installations.
674D-- --A
39
Page 40
6. Replace horizontal return duct cover panel. Screw in place ensuring all seams are air and watertight.
7. Install the 2 angle filter brackets to the right and left hood side panels respectively with the #10 screws provided. See Fig. 30.
8. Assemble hood according to Fig. 31 screwing together with provided #10 sheet metal screws.
9. Install assembled hood over the economizer opening in the replacement return chamber panel. See Fig. 32. Screw in place through pre-punched holes. Make sure all seams are air watertight.
NOTE: The two wires that connect to the outside air temperature sensor (OAT) should remain accessible.
10. Connect the outside air temperature sensor (OAT) to the economizer per wiring diagram.
11. Open the filter clips on the inside of the hood top. Insert the aluminum filter into the hood and close the clips to hold in place. See Fig. 33.
12. Toreplace12x20x1(304.8mm x 508mm x 25.4mm) air filters, open the filter access door (horizontal return duct cover panel), remove old filters and install new disposable filters in filter rack. See Table 17 for filter part number.
674D-- --A
OAT Sensor
Fig. 27 -- Economizer Hood Top Panel Removal
Hood Top Panel
A09689
Table 17 – Filter Part Number
DESCRIPTION PART NUMBER
Indoor Coil Air Filter
12 x 20 x 1
(304.8 x 508 x 25.4 mm)
KH01AA312
OAT Sensor
Fig. 28 -- Oat Sensor Installed
A09690
NOTE: The economizer control settings and the filters are accessible through the filter access door.
13. Economizer controls are set to a standard factory setting. Nevertheless, you can adjust these settings through the filter access door. Review the settings in the Operation section:
(1.) The standard economizer controller has a factory
setting of “C” for the outdoor air temperature changeover and 63_F(17_C) for the supply air (mixed air) temperature sensor. The outdoor air temperature changeover setting is adjusted on the sensor by setting the dip switches on the sensor. The ABCD potentiometer on the economizer controller should be set to the “D” position.
(2.) The low ambient compressor lockout switch setting
is fixed at 42_F(5.6_C).
(3.) The minimum position for the outdoor air damper
can be configured at the controller. When not using
2
sensor, the DCV Max potentiometer must be
aCO completely closed (CCW) for the Minimum Posi­tion potentiometer to function correctly.
(4.) Settings for the optional outdoor enthalpy sensor,
indoor enthalpy sensor, and CO
sensor can also be
2
configured at the controller.
14. Replace the filter access panel. Screw in place ensuring all seams are air and watertight.
15. Install all economizer accessories then power HVAC unit and test cycle economizer.
40
Page 41
Horizontal Return Duct Cover Panel
Hood Divider (Removed)
Hood Divider
674D-- --A
A09691
Fig. 29 -- Horizontal Return Duct Cover Panel Removal
Left Hood Side Panel
Filter Angle Bracket
Fig. 30 -- Filter Angle Bracket Installation
Right Hood Side Panel
Filter Angle Bracket
A09692
41
Page 42
Hood Top Panel
Right Hood Side Panel
Hood Divider
Left Hood Side Panel
A09693
Fig. 31 -- Economizer Hood Assembly
674D-- --A
Fig. 32 -- Economizer Hood Installation
Filter Clips
Aluminum Filter
A09694
A09695
Fig. 33 -- Filter Installation (See Through View)
42
Page 43
Large Chassis
To install the Vertical Economizer on the large chassis perform the following procedure:
1. Turn off unit power supply and install lockout tag.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
2. Remove economizer hood top panel from the return side of the unit. See Fig. 34. Keep screws and panel next to the unit.
3. Remove red shipping tape that attaches the outside air temperature (OAT) sensor to the economizer assembly and place sensor next to the unit.
4. Remove horizontal return duct cover panel and cut the wire ties that hold the hood divider to the economizer assembly. Slide hood divider off from the two slots holding it in place and place next to the unit. See Fig. 35.
NOTE: Gas units have a flue hood attached to the hood divider. Unscrew the fastener holding the flue hood in place and dispose the screw. Follow unit’s literature for flue hood installations.
5. Replace horizontal return duct cover panel. Screw in place ensuring all seams are air and watertight.
6. Open economizer hood package found on the top skid. Mount OAT sensor to its assigned bracket by screwing together with provided two #8 fasteners. Afterwards install OAT sensor to the right side hood panel with the provided #10 screws. See Fig. 36.
7. Install the 2 angle filter brackets to the right and left hood side panels respectively with the #10 screws provided. See Fig. 37.
8. Assemble hood according to Fig. 38 screwing together with provided #10 sheet metal screws.
9. Install assembled hood over the economizer opening in the replacement return chamber panel. See Fig. 39. Screw in place through pre-punched holes. Make sure all seams are watertight.
NOTE: The two wires that connect to the outside air temperature sensor (OAT) should remain accessible.
10. Connect the outside air temperature sensor (OAT) to the economizer per wiring diagram.
Filter Access Panel
Hoop Top Panel
OAT Sensor
A09696
Fig. 34 -- Economizer Hood Top Panel Removal
674D-- --A
Horizontal Return Duct Cover Panel
Hood Divider
Fig. 35 -- Horizontal Return Duct Cover Panel and Hood Divider Removal
Hood Divider (Removed)
A09697
43
Page 44
A09698
Fig. 36 -- OAT Bracket Installation
674D-- --A
Left Hood Side Panel
Filter Angle Bracket
Filter Angle Bracket
Right Hood Side Panel
Left Hood Side
Right Hood Side
A09699
Fig. 37 -- Filter Angle Bracket Installation
44
Page 45
Left Hood Side Panel
Hood Top Panel
Hood Divider
Right Hood Side Panel
Fig. 38 -- Hood Assembly
NOTE: The economizer control settings and the filters are
accessible through the filter access door.
A09700
674D-- --A
A09701
Fig. 39 -- Economizer Hood Installation
11. Open the filter clips on the inside of the hood top. Insert the aluminum filter into the hood and close the clips to hold in place. See Fig. 40.
12. T o replace air filters, open filter access door remove old filters and install new disposable filters in filter rack. See Table 18 for filter part numbers.
IMPORTANT: On the the bent coil (See Fig. 41 to determine coil type) filter rack, the 18 x 24x1(257.2mm x 609.6mm x25.4mm) filter must be installed through the filter access door first then installthe16x24x1(406.4mm x 609.6mm x 25.4mm) filter.
Table 18 – Filter Part Number
DESCRIPTION PA RT N UM BE R
Straight Indoor
Coil Air Filter
Bent Indoor
Coil Air Filter
14 x 24 x 1
(355.6 x 609.6 x 25.4 mm)
16 x 24 x 1
(406.4 x 609.6 x 25.4 mm)
16 x 24 x 1
(406.4 x 609.6 x 25.4 mm)
18 x 24 x 1
(457.2 x 609.5 x 25.4 mm)
KH01AA314
KH01AA316
KH01AA316
KH01AA318
13. Economizer controls are set to a standard factory setting. Nevertheless, you can adjust these settings through the filter access door. Review the settings in the Operation section:
(1.) The standard economizer controller has a factory
setting of “C” for the outdoor air temperature changeover and 63_F(17_C) for the supply air (mixed air) temperature sensor. The outdoor air temperature changeover setting is adjusted on the sensor by setting the dip switches on the sensor. The ABCD potentiometer on the economizer controller should be set to the “D” position.
(2.) The low ambient compressor lockout switch setting
is fixed at 42_F(5.6_C).
(3.) The minimum position for the outdoor air damper
can be configured at the controller. When not using
2
sensor, the DCV Max potentiometer must be
aCO completely closed (CCW) for the Minimum Posi­tion potentiometer to function correctly.
(4.) Settings for the optional outdoor enthalpy sensor,
indoor enthalpy sensor, and CO
sensor can also be
2
configured at the controller.
14. Replace the filter access panel. Screw in place ensuring all seams are air and watertight.
15. Install all economizer accessories then power HVAC unit and test cycle economizer.
45
Page 46
CONFIGURATION
Economizer Standard Sensors
OUTDOOR AIR TEMPERATURE (OAT) S ENSOR— The
outdoorair temperaturesensor(HH57AC080) is a 10 to 20mAdevice used to measure the outdoor--air temperature. The outdoor--air temperature is used to determine when the Economizer can be used for free cooling. The operating range of temperature measurement is 40 to 100_F (4.4 to 37.8_C).The sensorhas 8 selectable temperature changeover setpoints. The temperature changeover is set using 3 dip
Filter Clips
Aluminum Filter
674D-- --A
A09704
Fig. 40 -- Filter Installation (See through view)
Top filter
Bottom filter rack
Screw
(Note 4 and 5)
rack
Evaporator Coil
RIGHT SIDE
switches on the sensor. The ABCD potentiometer on the controller should be set to the “D” position. See Fig. 44.
SUPPLY AIR TEMPERATURE (SAT) SENSOR—The supply air temperature sensor is a 3 KΩ thermistor located at the inlet of the indoor fan. See Fig. 42. The operating range of temperature measurement is 0_ to 158_F (-- 17.8_ to 70_C). See Table 19 for sensor temperature/resistance values. The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Table 19 – Supply Air Sensor Temperature/Resistance Values
TEMPERATURE
(_F)
--- 2 2 --- 3 0 53,010
--- 4 --- 2 0 29,091
14 --- 1 0 16,590
32 0 9,795
50 10 5,970
68 20 3,747
77 25 3,000
86 30 2,416
104 40 1,597
122 50 1,080
140 60 746
158 70 525
CELSIUS (_C) RESISTANCE (OHMS)
Supply Air Temperature Sensor (SAT)
BENT COIL
To p f il t er rack
Bottom filter rack
STRAIGHT COIL
Fig. 41 -- Indoor Coil with Filter Rack
Evaporator Coil
A09714
Indoor Blower
A09707
Fig. 42 -- SAT Location
LOW TEMPERATURE COMPRESSOR LOCKOUT SWITCH—The Economizer is equipped with a low ambient
temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42_F(5.6_C) ambient temperature.
46
Page 47
Economizer Control Modes
Determine the Economizer control
mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 15. The Economizer is supplied from the factory with a supply air temperature sensor, a low temperature compressor lockout switch, and an outdoor air temper­ature sensor. This allows for operation of the Economizer with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the Economizer and unit.
OUTDOOR DRY BULB CHANGEOVER—The standard controlleris shipped from the factory configuredforoutdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard.
For this control mode, the outdoor temperature is compared to a
selectable set point on the sensor See Fig. 44. If the outdoor--air
temperature is above the set point, the Economizer will adjust the outdoor air dampers to minimum position. If the outdoor--air temperature is below the set point, the position of the outdoor--air dampers will be controlled to provide free cooling using outdoor air. When in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover temperature set point is set using the switches on the sensor. See Fig. 44 for the corresponding temperature changeover values.
EXHAUST FAN
SETPOINT
LED LIGHTS WHEN
EXHAUST CONTACT
MINIMUM DAMPER
POSITION SETTING
MAXIMUM DAMPER DEMAND
CONTROL VENTILATION
LED LIGHTS WHEN DEMAND CONTROL
VENTILATION INPUT
IS ABOVE SETPOINT
DEMAND CONTROL
VENTILATION SETPOINT
LED LIGHTS WHEN
OUTDOOR AIR IS
SUITABLE FOR FREE
IS MADE
SETPOINT
COOLING
CHANGEOVER SETPOINT
ENTHALPY
A09708
Fig. 43 -- Economizer Controller Potentiometer and LED
Locations
OUTDOOR ENTHALPY CHANGEOVER—For enthalpy
control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location.
ECONOMIZER
RETURN AIR SENSOR
RETURN DUCT (FIELD-PROVIDED)
A09710
Fig. 45 -- Enthalpy Sensor Mounting Location
CONTROL
CURVE
A 73 (23)
B C D
16
14
12
CONTROL POINT
APPROX ˚F (˚C)
AT 50% RH
70 (21) 67 (19) 63 (17)
34
32
30
28
26
ENTHALPY – BTU PER POUND DRY AIR
24
22
20
18
40 (4)
35 (2)
55
(13)
50
C
(10)
45
D
(7)
85
(29)90(32)95(25)
46
44
80
42
40
38
36
65
(18)
60
(16)
A
B
(27)
75
(24)
70
(21)
100
90
80
70
60
50
RELATIVE HUMIDITY (%)
40
30
100
105
110
(38)
(41)
(43)
20
10
674D-- --A
Fig. 44 -- Outdoor Air Temperature Changeover Set Points
(8.9°C)
(11.7°C)
(12.8°C)
(14.4°C)
(17.2°C)
(20°C)
(22.8°C)
(25.6°C)
A10134
47
A
B
C
D
35 (2)40(4)45(7)50(10)55(13)60(16)65(18)70(21)75(24)80(27)85(29)90(32)95(36)
APPROXIMATE DRY BULB TEMPERATURE — ˚F (˚C)
Fig. 46 -- Enthalpy Changeover Setpoints
100
105
110
(38)
(41)
(43)
A09711
Page 48
6000
IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust theDCV potentiometersto correspondto theDCV
5000
voltage output of the indoor air quality sensor at the user determined set point. SeeFig. 47. If a separate field--supplied transformer is used
4000
3000
2000
1000
0
2 345678
Fig. 47 -- CO2Sensor Maximum Range Setting
800 ppm 900 ppm 1000 ppm 1100 ppm
A09713
to power the IAQ sensor, the sensor must not be grounded or the Economizer control board will be damaged.
EXHAUST SET POINT ADJUSTMENT—The exhaust setpoint will determine when the exhaust fan runs based on damper position (if power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 49 for Wiring Diagram. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, theEconomizer controllerprovidesa 45 ± 15 second delay beforeexhaust fan activation to allow thedampersto open. Thisdelay allows the damper to reach the appropriate position to avoid unnecessary fan overload.
MINIMUM POSITION CONTROL — There is a minimum
TR TR1
24 Vac
24
COM
Vac
HOT
12
5
43
EF1EF
A09712
EXH
DCV
Free Cool
EXH
Set
10V
2V
Min Pos
Open
DCV
Max
10V
2V
DCV
Set
10V
2V
C
B
DA
N1
N
P1
674D-- --A
P
T1
T
AQ+
AQ
SO+
SO
SR+
SR
Fig. 48 -- Economizer Controller
When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point,the outdoor--airdamper movesto its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the Economizer controller. The set points are A, B, C, and D. See Fig. 46. The factory--installed 620--ohm jumper must be in place across terminals SR and SR+ on the Economizer controller. See Fig. 48 and Fig. 49.
DIFFERENTIAL ENTHALPY CONTROL — For differential enthalpy control, the Economizer controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return airstream. The Economizer controller compares the outdoor air enthalpy to the return air enthalpy to determine Economizer use. The controller selects the lower enthalpy air(return or outdoor)for cooling. For example, whenthe outdoorair has a lower enthalpy than the return airand is below the set point, the Economizeropensto bring in outdoorair for freecooling.Replacethe standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. Mount the return air enthalpy sensor in the return air duct. See Fig. 45. When using this mode of changeover control, turn the enthalpy set point poten­tiometer fully clockwise to the D setting.
INDOOR AIR QUALITY (IAQ) SENSOR INPUT —The IAQ input can beused fordemand control ventilation control based on the level of CO
measured in the space or return air duct. Mount the
2
accessory IAQ sensor according to manufacturer specifications. The
damper position potentiometer on the Economizer controller. See Fig. 43 and Fig. 49. The minimum damper position maintains the minimumairflowinto the building during theoccupied period.When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The DCV Max potentiometer must be fully closed (CCW) to allow the minimum position potentiometer to function correctly.
When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F (12.2_C) temperature difference between the outdoor and return--air temperatures. To determine the minimum position setting, perform the following procedure:
1. Calculate the appropriate mixed air temperature using the following formula: (T
x OA/100) + (TRx RA/100) = T
o
M
TO= Outdoor--Air Temperature OA = Percent of Outdoor Air
= Return--Air Temperature
T
R
RA = Percent of Return Air
= Mixed--Air Temperature
T
M
As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-- air temperature is 60_F (15.6_C), and return--air temperature is 75_F (23.9_C). (60 x .10) + (75 x .90) = 73.5_F (23.1_C)
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory--installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 49 and that the minimum position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer until the measured mixed-- air temperature matches the calculated value.
6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the Economizer damper is desirable when requiring additional temporary ventilation. If a field--supplied remote potentiometer (Honeywell part number S963B1128) is wired to the Economizer controller, the minimum position of the damper can be controlled from a remote location. To control the minimum damper position remotely, remove the factory installed jumper on the P and P1 terminals on the Economizer controller. Wire the field--supplied potentiometer to the P and P1 terminals on the Economizer controller. See Fig. 48 and Fig. 49.
48
Page 49
674D-- --A
A10059
Fig. 49 -- Economizer Wiring Diagram
49
Page 50
CONNECTION WIRING DIAGRAM
DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
NOTES:
1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED, THEY MUST BE REPLACED WITH THE SAME WIRE OR ITS EQUIVALENT.
2. SEE PRICE PAGES FOR THERMOSTATS.
3. USE 75 DEG. COPPER CONDUCTORS FOR FIELD INSTALLATION.
4. SEE INSTALLATION INSTRUCTIONS FOR PROPER HEATING AND COOLING CONNECTIONS FOR YOUR UNIT. INDOOR FAN MOTOR PLUGS
- "DO NOT DISCONNECT UNDER LOAD"
5. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257003.
6. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257005.
7. INDUCER CAPACITOR AND WIRING ON CERTAIN MODELS ONLY. IF CAP2 IS PRESENT, YELLOW WIRES FROM IGC AND IDM CONNECT ON SAME SIDE OF CAP2.
8. REMOVE YELLOW SPLICE WIRE WHEN ECONOMIZER AND ECONOMIZER RELAYS ARE USED AND CONNECT TO RELAY R1 AS SHOWN.
9. WHEN ECONOMIZER AND ECONOMIZER RELAYS ARE USED, CONNECT THE YELLOW AND BLACK WIRES TO RELAY R AS SHOWN. RELAY KIT REQUIRED WITH ECONOMIZER AND HEAT PUMP/DUAL FUEL UNITS.
10. WHEN ECONOMIZER AND ECONOMIZER RELAYS ARE USED, INSTALL WIRES AS SHOWN ONTO THE COILS OF RELAY R AND RELAY R1.
11. DEHUMIDIFICATION FEATURE CANNOT BE USED WHEN ECONOMIZER IS INSTALLED.
FIELD SPLICE TERMINAL (MARKED) TERMINAL (UNMARKED) SPLICE (IF USED) SPLICE (MARKED) FACTORY WIRING FIELD CONTROL WIRING FIELD POWER WIRING ACCESSORY OR OPTIONAL WIRING
C CONTACTOR CAP 1 CAPACITOR, COMP CAP 2 CAPACITOR, INDUCER CCH CRANK CASE HEATER COMP COMPRESSOR MOTOR CR COMBUSTION RELAY DB DEFROST BOARD DFT DEFROST TEMPERATURE SWITCH DH DEHUMIDIFICATION MODE DR DEFROST BOARD RELAY
ECONOMIZER PLUG
7
674D-- --A
SEE 50SD500625
7
6
6
11
11
10
10
8
8
2
2
3
3
4
4
ECONOMIZER LABEL DIAGRAM
1
1
5
5
9
9
12
12
ECON ECONOMIZER EQUIP EQUIPMENT FS FLAME SENSOR GND GROUND HPS HIGH PRESSURE SWITCH I IGNITOR IGC INTERGRATED GAS UNIT CONTROLLER IFB INDOOR FAN BOARD IDM INDUCED DRAFT MOTOR IFM INDOOR FAN MOTOR LGPS LOW GAS PRESSURE SWITCH (WHEN USED) LPS LOW PRESSURE SWITCH LS1 PRIMARY LIMIT SWITCH LS2 SECONDARY LIMIT SWITCH MGV MAIN GAS VALVE OFM OUTDOOR FAN MOTOR PRS PRESSURE SWITCH RS ROLLOUT SWITCH RVS REVERSING VALVE SAT SUPPLY AIR TEMPERATURE TRAN TRANSFORMER T-STAT THERMOSTAT
R ECON RELAY
R1 ECON RELAY
ECON
BL
P
P
SAT
BL
GY
Y
R
BR
BK
IGC
CR
L1
BL
L2
J2
IFO
GY
W
W
G
5AMP
R
R
FUSE
RS
RS
LS
LS
CS
CS
GV
GV
GROUNDED THRU STANDOFF
SEE NOTE 9
BK
Y
R
2
1
BK
3
Y
CM
BM
L2
L2
RT
V
V
GVR
FS
C
C
3
1
2
CAP 3
QT
SEE NOTE 6
BL
BL
LGPS (WHEN USED)
LS1
13
Y
O
BR
Y
I
O
R1
SEE NOTE 8
FIELD
SUPPLY
W
R
GY
BK
V
IDM
Y
BR
G/Y
R
RS
13
R
O
M
GY
FS
BR
G/Y
BR
EQUIP_GND
R
13
IF USED
BK
Y
BL
CCH
BK
C
11 21
13
BK
1
23
1
BK
G
COMPRESSOR PLUG
Y
BK
BK
PRIMARY
Y
COM
208/230V
DB
DR
OF1
BK
BK
OF2
BK
Y
CAP1
C
Y
BR
BR
F
BK
T1
T2
BL
Y
T3
BK
Y
BK
G/Y
230
Y
TRAN
SECONDARY
24 V
C
24V
R
BR
R
BR
W
SEE NOTE 5
IFB
GY
W
R
P2
R
R
Y
G
W
DEFROST BOARD (DB) DR
OF1
OF2
0
W2
R
P1 Y C
BR
CTD
T-STAT
GY
Y2
R
BR
Y
C
Y1
G
DH
BL
W
O
O
SEE NOTE 7
LS2
PRS
MGV
C
R
O
W
Y
1
24V
2
C
W
3
R
4
X
5
P1
R
1
2
C
3
Y1/Y
4
G
Y2/DH
5
6
W
Y
Y
SEE NOTE 10
BK
O
BL
T2
BR
C
P2
C
90
UP
6030120
SPEED
P
DFT
P
R
P3
BK
T1
BL
Y
BR
DIP SWITCH SETTINGS
DEFAULT
30 MINUTES
30
11 11133 33322 222
FIELD SELECTABLE OPTIONS FOR TIME PERIOD BETWEEN DEFROST CYCLES (MINUTES)
Y
Y
OR
60 MINUTES
60
90 MINUTES
120 MINUTES
OROR
90
Y
FUSE
RVS
DFT
ON
QUIET SHIFT
OFF
(DEFAULT)
SPEED
UP
1) MOMENTARILY SHORT PINS AND RELEASE TO BYPASS COMPRESSOR OFF DELAY.
2) SHORT FOR 5+ SEC. AND RELEASE FOR FORCED DEFROST.
3) PERMANENT SHORT WILL BE IGNORED.
DEFROST WILL TERMINATE IN 30 SEC. IF DFT OPEN. DEFROST WILL TERMINATE NORMALLY IF DFT IS CLOSED.
Fig. 50 -- Connection Wiring Diagram 230--3
SCHEMATIC
208/230-3-60
OFM
COMP
N
G
L
C
BR
3A
COM
HEAT
BR
HPS
JUMPERED TEST PINS (USE METAL OBJECT) FIELD SPEED-UP CYCLE
IFM
BR
R
C
BR
C
BR
COM
BR
LOW
R
HIGH
GAS
SEE NOTE 11
INDOOR BLOWER 24V CONNECTIONS SEE NOTE 4
O
C2
C1
R
C2
C1
R1
C2
C1
C
LPS
BL
BK
THE COMPRESSOR WILL SHUT OFF FOR 30 SEC. ON DEFROST INITIATION AND TERMINATION IN THE "QUIET SHIFT" ON POSITION.
COLOR CODE
BK BLACK BL BLUE BR BROWN GY GRAY G GREEN O ORANGE P PINK R RED V VIOLET W WHITE Y YELLOW
BK
W
BR
2435
1
BL
P
R
SEE NOTE 4
BR
BK
O
A10075C
50
Page 51
LADDER WIRING DIAGRAM
DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
3 UNIT COMPONENT ARRANGEMENT
OUTDOOR FAN SECTION
COMPRESSOR SECTION
LPS
HPS
COMP
T1
T3
OFM
INDOOR FAN SECTION
CAP 1
R
CF
IFM
T2
CONTROL BOX AREA
LS1
(LARGE)
LS2
(SMALL)
R1
LS1
(SMALL CABINET)
23
13
C
IGC
PRS
GAS SECTION
TRAN
11
21
DB
IFB
CAP 2
IDM
MGV
MC
RS
I
FS
L1
11
11
11
USE COPPER CONDUCTORS ONLY
BK
FIELD SUPPLY
208/230 VAC, 60 HZ, 3PH
21
C
BK
BK
G/Y
CCH
(IF USED)
BK
OF1
BK
DB
DR
BK
OF2
CAP
BK
OFM
BK
C
S
BR
BR
F
C
T2
T1
COMP
IFM
BK
G
Y
R
Y
T3
Y
G/Y
L3
L2
BL
Y
23
Y
BL
Y
C
13
23
T'STAT
R
O
G
W
DH
Y1
C
Y2
IGC
CR
CM
11
L1
BK
V
IDM
G/Y
TRAN
SEE NOTE 5
IFB
24VAC R
FUSE
3A
P2-1"R"
P2-2"C"
P2-5"X"
P2-3"W"
1
R
1
O
1
G
1
W
1
BL
1
Y
P2-4"R"
P1-1"R"
P1-4"G"
P1-6"W"
W
P1-5"Y2/DH"
P1-3"Y1/Y"
R
BR
GY
W
R
IGC
5AMP
RT
FUSE
C
FS
RS
R
Y
BL
SEE NOTE 6
RS
RS
V
LS
LS
CS
CS
GV
IFO
R
LS1 LS2
IF USED
Y
O
O
GY
BK
R
24V
FS
BL
V
PRS
MC
MGV
230
PRIMARY 208/230V
SECONDARY 24V
Y
BR
CAP2
COM
BR
C
DB
P3-1
P3-2
P1-7,R
P1-8,O
O
P1-5,Y
Y
P1-6,W2
W
P2-4
P2-1
P
P
BK
T1
BL
Y
T2
BL
O
BK
BR
W
2
R
SEE NOTE 4
2
Y
3
R
4
5
6
7
8
W
SEE NOTE 8
SEE NOTE 4
Y
R1
2
BR
BK
BL
SAT
BL
1
3
R
Y
3
1
2
BK
BR
SEE NOTE 11
Y
LOW
GY
HIGH
GAS HEAT
Y
BK
O
ECONOMIZER PLUG
3
4
5
6
7
SEE 50SD500625
ECONOMIZER LABEL DIAGRAM
8
48EZ500146
Y
DFT
HPS
BK
C
RVS
SEE NOTE 10
BL
P
R
O
BK
SEE NOTE 9
Y
1 2
35 4
IGC
L2
BL
SEE NOTE 7
LPS
BR
BR
BR
R
R1
IFM
Y
G/Y
BR
COM C
A
23
IFB
COM
IFB C
DB-C
DB-C
C
C
GV
IGC
IGC
IFB COM
IFB P1-2
674D-- --A
C
C
A10075L
Fig. 50 Cont. -- Ladder Wiring Diagram 230--3
51
Page 52
DAMPER MOVEMENT — Damper movement from full open to full closed (or vice versa) takes 2 1/2 minutes.
THERMOSTATS — The Economizer control works with conven­tionalthermostats that have aY1 (cool stage 1), Y2 (coolstage2),W1 (heatstage 1), W2 (heatstage2), andG (fan).The Economizercontrol does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
OCCUPANCY CONTROL — The factory default configuration for the Economizer control is occupied mode. Occupied status is provided by the black jumperfrom terminalTR to terminal N. When unoccupied mode is desired, install a field supplied time clock function inplaceof the jumper between TR and N. SeeFig. 49. When the timeclock contacts are closed, the Economizer control will be in occupied mode. Whenthetimeclockcontacts areopen (removingthe 24--v signal from terminal N), the Economizer willbe in unoccupied mode.
DEMAND CONTROLLED VENTILATION (DCV)—When using the Economizer for demand controlled ventilation, there are someequipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions.
674D-- --A
The maximum damper position must be calculated to provide the desired fresh air. Typically the maximum ventilation rate will be about 5 to 10% more than the typical CFM required per person, using normal outside air design criteria. An exponential anticipatory strategy should be taken with the following conditions: a zone with a large area,varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. An exponential--anticipatory strategy will causethe freshair suppliedto increase as the roomCO even though the CO CO
level reaches the set point, the damper will be at maximum
2
set point has not been reached. By the time the
2
level increases
2
ventilation and should maintain the setpoint. In orderto havetheCO sensorcontrolthe economizerdamper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside--air entering the building for a given damper position. For best results there should be at least a 10_F (12.2_C) difference in outside and return--air temperatures.
(T
x OA/100) + (TRx RA/100) = T
o
M
The DCV set point may be left at 2 volts since the CO voltage will be ignored by the Economizer controller until it rises above the 3.6 volt setting of the minimum position potentiometer. Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over ventilation to the space and potential high--humidity levels.
SENSOR CONFIGURATION — The CO2sensor has preset
CO
2
standard voltage settings that can be selected anytime after the sensor is powered up. Use setting 1 or 2 for equipment. See Table 20.
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See Table 20.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed anytime
2
after the sensor is energized. Follow the steps below to change the nonstandard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
DEHUMIDIFICATION OF FRESH AIR WITH DCV CONTROL—Information from ASHRAE indicates that the largest
humidity load on any zone is the fresh air introduced. For some applications, an energy recovery unit can be added to reduce the
2
moisture contentof thefresh air being broughtintothe building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications.
If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.
sensor
2
TO= Outdoor--Air Temperature OA = Percent of Outdoor Air T
= Return-- Air Temperature
R
RA = Percent of Return Air T
= Mixed--Air Temperature
M
Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position. The same equation can be used to determine the occupied or maximum ventilation rate to the building.For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 CFM per person). Use Fig. 47 to determine the maximum setting of the CO
sensor. For
2
example, a 1100 ppm setpoint relates to a 15 CFM per person design. Use the 1100 ppm curve on Fig. 47 to find the point when the CO
2
sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO
sensorshould be 1800 ppm. The Economizercontroller will
2
output the 6.7 voltsfrom the CO
sensorto theactuatorwhen theCO
2
2
concentration in the space is at 1100 ppm.
52
Page 53
Table20–CO
SETTING EQUIPMENT OUTPUT
1 Proportional Any
2
3 Exponential Any
4 Proportional 15
5 Economizer Proportional 20
6 Exponential 15
7 Exponential 20
8 Health & Safety Proportional ---
9 Parking/Air Intakes/Loading Docks Proportional ---
Interface w /Standard Building
Control System
Proportional Any
Sensor Standard Settings
2
VENTILATION
RATE
(CFM/
PERSON)
ANALOG
OUTPUT
0 --- 1 0 V
4 --- 2 0 m A
2 --- 1 0 V
7 --- 2 0 m A
0 --- 1 0 V
4 --- 2 0 m A
0 --- 1 0 V
4 --- 2 0 m A
0 --- 1 0 V
4 --- 2 0 m A
0 --- 1 0 V
4 --- 2 0 m A
0 --- 1 0 V
4 --- 2 0 m A
0 --- 1 0 V
4 --- 2 0 m A
0 --- 1 0 V
4 --- 2 0 m A
CO
2
CONTROL
RANGE
(PPM)
0--- 2000 1000 50
0--- 2000 1000 50
0--- 2000 1100 50
0--- 1100 1100 50
0 --- 9 0 0 900 50
1--- 1100 1100 50
0 --- 9 0 0 900 50
0--- 9999 5000 500
0--- 2000 700 50
OPTIONAL
RELAY
SETPOINT
(PPM)
HYSTERESIS
RELAY
(PPM)
Table21–CO2Sensor Standard Settings Economizer Input/Output Logic
INPUTS OUTPUTS
DEMAND
CONTROL
VENTILATION
(DCV)
Below set (DCV
LED Off)
Above set (DCV
LED On)
* For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
{Power at N terminal dete rmines Occupied/Uno ccupied setting: 24 va c (Occupied), now power (Unoccupied).
**Modulating is based on the supply---air sensor signal.
{{Modulation is based on the DCV signal.
***Modulation is based on the greater of DCV and supply--- air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply--- ai r signal).
{{{Modulating is based on the greater of DCV and supply---air sensor signals, between closed and wither maximum position (DCV) or fully open (supply--- air signal).
Sequence of Operation—When free cooling is not available, the compressor will be controlled by the thermostat. When free cooling is available, the outdoor--air damper is modulated by the Economizer control to provide a 50_ to 55_F(10_ to 12.8_C) supply--air temperature into the zone. As the supply--air temperature fluctuates above 55_ (12.8_C) or below 50_F(10_C), the dampers will be modulated (open or close) to bring the supply--air temperature back within the set points. For Economizer operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.
NOTE: The DCV Max potentiometer must be colosed (CCW) when not using CO
Above 50_F(10_C) supply--air temperature, the d ampers will modulate from 100% open to the minimum open position. From 50_Fto45_F(10_ to 7.2_C) supply--air temperature, the dampers will maintain at the minimum open position. Below 45_F(7.2_C), the dampers will be completely shut. As the supply--air temperature
ENTHALPY
OUTDOOR RETURN
High (Free Cooling
LED off)
Low (Free Cooling
LED on)
High (Free Cooling
LED off)
Low (Free Cooling
LED on)
OPERATION
2
sensor.
Low
High
Low
High
COMPRESSOR NTERMINAL
Y1 Y2
On On On On
Off Off Off Off
On On On Off
On Off Off Off
Off Off Off Off Minimum position Closed
On On On On
On Off On Off
Off Off Off Off
On On On Off
Off Off Off Off
STAGE1STAGE
2
OCCUPIED UNOCCUPIED
DAMPER
Minimum position ClosedOn Off On Off
Modulating** (between min.
p o s i ti on a n d f u l l --- o p e n )
Modulating{{ (between
min. position and DCV
maximum)
Modulating*** Modulating{{{On Off Off Off
Modulating** (between closed
Modulating{{ (between closed
a n d f u l l --- o p e n)
and DCV maximum)
exhaust is installed, as the outdoor--air damper opens and closes, the power exhaust fans will be energized and deenergized. If field -­installed accessory CO
sensors are connected to the Economizer
2
control, a demand controlled ventilation strategy will begin to operate. As the CO
level in the zone increases above the CO2set
2
point, the minimum position of the damper will be increased proportionally. As the CO
level decreases because of the increase in
2
fresh air, the outdoor--air damper will be proportionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode. Damper movement from full closed to full open (or vice versa) will take between 1 1/2 and 2 1/2 minutes. If free cooling can be used as determined from the appropriate changeover command (dry bulb, enthalpy curve, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply air temperature set point at 50_ to 55_F(10_ to 12.8_C). As the supply air temperature drops below the set point range of 50_ to 55_F(10_ to 12.8_C), the control will modulatethe outdoor--air dampers closed to maintain the proper supply--air temperature.
rises, the dampers will come back open to the minimum open position once the supply--air temperature rises to 48_F(8.9_C). If power
674D-- --A
53
Page 54
TROUBLESHOOTING
See Table 21 for Economizer logic. An Economizer simulator program is available to help with Economizer training and troubleshooting.
Economizer Preparation —This procedure is used to prepare the Economizer for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a 9--v battery, 1.2 kilo--ohm resistor, and a 5.6 kilo--ohm resistor which are not supplied with the Economizer.
1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo--ohm resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S Connect 1.2 kilo--ohm 4074EJM checkout resistor across terminals S
674D-- --A
8. Put 620--ohm resistor across terminals SR and +.
and +.
o
9. Set minimum position, DCV set point, and exhaust poten­tiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW (clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential Enthalpy — To check differential enthalpy:
1. Make sure Economizer preparation procedure has been performed.
2. Place 620--ohm resistor across S
and +.
o
3. Place 1.2 kilo--ohm resistor across SR and +. The Free Cool LED should be lit.
4. Remove 620--ohm resistor across S
and +. The Free Cool
o
LED should turn off.
5. Return Economizer settings and wiring to normal after completing troubleshooting.
Single Enthalpy—To check single enthalpy:
1. Make sure Economizer preparation procedure has been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.
4. Return Economizer settings and wiring to normal after completing troubleshooting.
DCV (Demand Controlled Ventilation) and Power Exhaust—To check DCV and Power Exhaust:
1. Make sure Economizer IV preparation procedure has been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.
3. Connect a 9--v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer
and +.
o
5. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9--v. The actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on.
7. Return Economizer settings and wiring to normal after completing troubleshooting.
DCV Minimum and Maximum Position —To check the DCV minimum and maximum position:
1. Make sure Economizer preparation procedure has been performed.
2. Connect a 9--v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actu­ator should drive to between 90 and 95% open.
3. Turn the DCV maximum position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
4. Turn the DCV maximum position potentiometer to fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should drive fully closed.
8. Return Economizer settings and wiring to normal after completing troubleshooting.
Supply--Air Input—To check supply--air input:
1. Make sure Economizer preparation procedure has beenperformed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.
3. Remove the 5.6 kilo--ohm resistor and jumper T to T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should drive fully closed.
5. Return Economizer settings and wiring to normal after completing troubleshooting.
Economizer Troubleshooting Completion —This procedure is used to return the Economizer to operation. No troubleshooting or testing is done by performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previous setting. Set DVC max potentiometer to fully closed (CCW) when not using a CO
2
sensor.
4. Set minimum position, DCV set point, and exhaust poten­tiometers to previous settings.
5. Remove 620-- ohm resistor from terminals SR and +.
6. Remove 1.2 kilo--ohm checkout resistor from terminals SO and +. If used, reconnect sensor from terminals SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo--ohm resistor from T and T1. Reconnect wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and P1.
11. Apply power (24 vac) to terminals TR and TR1. is approximately 90%. The actuator should remain in position.
54
Page 55
REQUIRED CLEARANCES TO COMBUSTIBLE MATL.
NEC. REQUIRED CLEARANCES
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
674D-- --A
A10220
Fig. 51 -- 674D-- -- A 30 -- 36 3 Phase with Economizer
55
Page 56
REQUIRED CLEARANCES TO COMBUSTIBLE MATL.
NEC. REQUIRED CLEARANCES
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
674D-- --A
Fig. 52 -- 674D-- -- A 42 -- 60 3 Phase with Economizer
E2010 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 04/10
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurri ng obligations.
56
A10221
Catalog No. II674D---07
Replaces: II674D--- 06
Loading...