Bryant 113A, Legacy 113A Product Data

113A LegacytRNC Line 13 Air Conditioner with Puronr Refrigerant 1--1/2 to 5 Nominal Tons (Sizes 018--060)
Product Data
the environmentally sound refrigerant
Bryant’s Air Conditioners with Puronr refrigerant provide a collection of featu res unmatch ed by any other family of equipment. The 113A has been designed utilizing Bryant’s Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth’s ozone layer.
As an Energy Starr Partner, Bryant Heating and Cooling has determined that this product meets the Energy Starr guidelines for energy efficiency. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines.
NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up --to--date ratings information.
INDUSTRY LEADING FEATURES / BENEFITS
Efficiency
13 -- 14 SEER/10.55 -- 12 EER
S S Microtube Technologyt refrigeration system S Indoor air quality accessories available
Sound
Sound level as low as 75 dBA
S S Sound level as low as 74 dBA with accessory sound
blanket
Comfort
System supports Thermidistatt or standard thermostat
S
controls
Reliability
Puronr refrigerant -- environmentally sound, won’t
S
deplete the ozone layer and low lifetime servce cost.
S Scroll compressor S Internal pressure relief valve S Internal thermal overload S Filter drier S Balanced refrigeration system for maximum reliability
Durability
DuraGuardt protection package:
S Solid, durable sheet metal construction S Dense wire coil guard available S Baked--on, complete outer coverage, powder paint
Applications
Long-- line -- up to 250 feet (76.20 m) total equivalent
S
length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information.)
S Low ambient (down to --20_F/--28.9_C)) with
accessory kit
MODEL NUMBER NOMENCLATURE
12 3 4 5 6789 1011 1214 N N N A A/N N N N N A/N A/N N A
11 3 A N A036 0 0 0 0
Product
Famil y
1=AC
Tier SEER
1=
Legacy RNC
3=13 SEER A=Puron
Major
Series
Vol ta ge
N= 208---230 --- 1
or 208/230--- 1
Grille
Vari a ti on s
A=Dense
W=Standard
ISO 9001:2000
Cooling Capacity
Open Open Open Series
0=Not
Defined
0=Not
Defined
0=Not
Defined
the environmentally sound refrigerant
113A
REGISTERED
This product has been designed and manuf actured to meet Energy Star ® criteria f or energy efficiency when matched with appropriate coi l components. However, proper refri gerant charge and proper air fl ow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturing refrigerant charging and air flow instructions. Failure to confirm
proper ch arge and air flow may reduce energy efficiency and shorten equipment life.
STANDARD FEATURES
Feature 018 024 030 036 042 048 060
Puron Refrigerant X X X X X X X
Maximum SEER 14.5 14.5 14.5 14.0 14.0 14.5 13.5
Scroll Compressor X X X X X X X
FieldInstalledFilterDrier X X X X X X X
Front Seating Service Valves X X X X X X X
Internal Pressure Relief Valve X X X X X X X
Internal Thermal Overload X X X X X X X
Long Line capability X X X X X X X
Low Ambient capability with Kit X X X X X X X
X=Standard
2
PHYSICAL DATA
UNIT SIZE--- VOLTAGE, SERIES 018 --- D 024 --- D 030 --- E 036---E 042 --- C 048 --- E 060 --- G
Operating Weight lb (kg)
Shipping Weight lb (kg)
Compressor Type Scroll
REFRIGERANT Puron® (R --- 410A)
Control TXV (Puron® Hard Shutoff)
Charge lb (kg)
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM) 1792 2218 2218 2954 3167 3365 3129
Motor HP 1/12 1/10 1/10 1/4 1/5 1/4 1/4
Motor RPM 1100 1100 1100 1100 1100 1100 800
COND COIL
Face Area (Sq ft) 8.4 8.4 9.80 13.13 17.25 19.40 12.93
Fins per In. 20 25 25 25 25 25 20
Rows 1 1 1 1 1 1 2
Circuits 3 3 3 3 4 5 5
VALVECONNECT.(In.ID)
Vapor 3/4 3/4 3/4 7/8 7/8 7/8 7/8
Liquid 3/8
REFRIGERANT TUBES (In. OD)
Rated Vapor* 3/4 3/4 3/4 7/8 7/8 7/8 1 --- 1 / 8
Max Liquid Line{ 3/8
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
{ See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
107
(48.5)
130
(59.0)
3.50
(1.59)
110
(49.9)
134
(60.8)
3.80
(1.72)
111
(50.3)
136
(61.7)
4.10
(1.86)
141
(64.0)
170
(77.1)
5.34
(2.42)
189
(85.7)
217
(98.4)
5.84
(2.65)
186
(84.4)
224
(101.6)
7.00
(3.18)
190
(86.2)
226
(102.5)
8.19
(3.71)
113A
3
REFRIGERANT PIPING LENGTH L I M I TATIONS
Liquid Line Sizing and Maximum Total Equivalent Lengths
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units.
See Table below for liquid line sizing and maximum lengths :
Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit
Liquid
Size
18000
AC with
Puron
24000
AC with
Puron
30000
AC with
Puron
36000
AC with
113A
Puron 42000
AC with
Puron 48000
AC with
Puron 60000
AC with
Puron
* Maximum actual length not to exceed 200 ft (61 m) { Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
Liquid Line
Connection
3/8
3/8
3/8
3/8
3/8
3/8 3/8 250* 250* 250* 250* 250* 250* 230 160 --- ---
3/8 3/8 250* 250* 250* 225* 190 150 110 --- --- --- ---
Line
Diam.
w/ TXV
5/16 250* 250* 250* 250* 250* 250* 250* 225* 150
5/16 250* 250* 250* 250* 250* 225* 175 125 100
1/4 30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --­5/16 175 225* 200 175 125 100 75 --- --- --- ---
5/16 175 150 150 100 100 100 75 --- --- --- ---
3//8 250* 250* 250* 250* 250* 250* 250* 250* 250*
5/16 125 100 100 75 75 50 --- --- --- --- --- ---
(0---1.5)
1/4 150 150 125 100 100 75 --- --- --- --- --- ---
3/8 250* 250* 250* 250* 250* 250* 250* 250* 250* 1/4 75 75 75 50 50 --- --- --- --- --- --- --- ---
3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250* 150
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor
0 --- 5
6 --- 1 0
(1.8---3.0)
11---20
(3.4---6.1)
{
for Cooling Only Systems with Puronr Refrigerant:
Vertical Separation ft (m)
21---30
(6.4---9.1)
31---40
(9.4---12.2)
41---50
(12.5---15.2)
51---60
(15.5---18.3)
(18.6---21.3)
61---70
71---80
(21.6---24.4)
Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
Liquid
Size
18000
AC with
Puron
24000
AC with
Puron
30000
AC with
Puron
36000
AC with
Puron 42000
AC with
Puron 48000
AC with
Puron 60000
AC with
Puron
* Maximum actual length not to exceed 200 ft (61 m) { Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
Liquid Line
Connection
3/8
3/8
3/8
3/8
3/8
3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
Line
Diam.
w/ TXV
1/4 175 250* 250* 250* 250* 250* 250* 250*
5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250* 1/4 100 125 175 200 225* 250* 250* 250*
5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250* 1/4 30 --- --- --- --- --- --- --- --- --- --- --- --- --- --­5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
5/16 225* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
5/16 175 200 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor
25
(7.6)
26---50
(7.9---15.2)
51---75
(15.5---22.9)
Vertical Separation ft (m)
76---100
(23.2---30.5)
101---125
(30.8---38.1)
126---150
(38.4---45.7)
151---175
(46.0---53.3)
176---200
(53.6---61.0)
4
REFRIGERANT CHARGE ADJUSTMENTS
Liquid Line Size Puron Charge oz/ft
3/8
5/16 0.40
1/4 0.27
(Factory charge for lineset = 9 oz)
0.60
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length o r diameter liquid lines, charge adjustments are required per the chart above.
Charging
Formula:
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment
Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?
Formula: (.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.
Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?
Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
LONG LINE APPLICATIONS
An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor
1/4
5/16 120 (36.6) 50 (15.2) 120 (36.6)
3/8 80 (24.4) 35 (10.7) 80 (24.4)
Note: SeeLongLineGuidelinefordetails
No accessories needed within allowed lengths
No accessories needed within allowed lengths
175 (53.3)
113A
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
Unit
Nominal
Size (Btuh)
18000 1Stage AC with
Puron
24000 1Stage AC with
Puron
30000 1Stage AC with
Puron
36000 1Stage AC with
Puron
42000 1Stage AC with
Puron
48000 1Stage AC with
Puron
60000 1Stage AC with
Puron
Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.
Maximum
Liquid Line
Diameters
(In. OD)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapo r Line
Diameters
(In. OD)
1/2 1 2 3 5 6 7 8 9 11
5/8 0 1 1 1 2 2 2 3 3
3/4 0 0 0 0 1 1 1 1 1
5/8 0 1 2 2 3 3 4 5 5
3/4 0 0 1 1 1 1 1 2 2
7/8 0 0 0 0 0 1 1 1 1
5/8 1 2 3 3 4 5 6 7 8
3/4 0 0 1 1 1 2 2 2 3
7/8 0 0 0 0 1 1 1 1 1
5/8 1 2 4 5 6 8 9 10 12
3/4 0 1 1 2 2 3 3 4 4
7/8 0 0 0 1 1 1 1 2 2
3/4 0 1 2 2 3 4 4 5 6
7/8 0 0 1 1 1 2 2 2 3
11/8 0 0 0 0 0 0 0 0 0
3/4 0 1 2 3 4 5 5 6 7
7/8 0 0 1 1 2 2 2 3 3
11/8 0 0 0 0 0 0 0 1 1
3/4 1 2 4 5 6 7 9 10 11
7/8 0 1 2 2 3 4 4 5 5
11/8 0 0 0 1 1 1 1 1 1
26--- 50
(7.9---15.2)
51--- 80
(15.5---24.4)
81--- 100
(24.7---30.5)
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
101--- 125
(30.8---38.1)
126--- 150
(38.4---45.7)
151--- 175
(46.0---53.3)
176--- 200
(53.6---61.0)
201--- 225
(61.3---68.6)
226--- 250
(68.9---76.2)
5
ACCESSORY THERMOSTATS
THERMOSTAT / SUBBASE
PKG.
T 6 --- P R H 0 1 --- A Programmable Thermidistat
T 6 --- N R H 0 1 --- A Non ---programmable Thermidistat
T 6 --- P A C 0 1 Preferred Series Programmable AC Stat
T 6 --- N A C 0 1 Preferred Series Non --- programmable AC Stat
T 2 --- P A C 0 1 Legacy Series Programmable AC Stat
T 2 --- N A C 0 1 Legacy Series Non--- programmable AC Stat
T 1 --- P A C 0 1 Legacy RNC Series Programmable AC Stat
T 1 --- N A C 0 1 Legacy RNC Series Non --- programmable AC Stat
TSTATBBSEN01---B Outdoor Air T emperature Sensor
TSTATXXBBP01 Backplate for Builder’s Thermostat
TSTATXXNBP01 Backplate for Non --- Programmable Thermostat
TSTATXXPBP01 Backplate for Programmable Thermostat
TSTATXXCNV10 Thermostat Conversion Kit (4 to 5 wires) -- - 10 Pack
ACCESSORIES
113A
KIT NUMBER DESCRIPTION
KAAFT0101AAA FREEZE THERMOSTAT X X X X X X X
KAATD0101TDR TIME DELAY RELAY X X X X X X X
KSALA0301410 LOW AMBIENT PSW X X X X X X X
KSALA0601AAA{ MOTORMASTER 230V X X X X X X X
HC32GE234 MOTOR FAN BALL BEARING X
HC34GE239 MOTOR FAN BALL BEARING X X
HC40GE226 MOTOR FAN BALL BEARING X X
HC38GE219 MOTOR FAN BALL BEARING X
HC40GE225 MOTOR FAN BALL BEARING X
KSAHS1701AAA HARD START (CAP / RELAY) X X X X X X X
KSACY0101AAA CYCLE PROTECTOR X X X X X X X
KSASF0101AAA SUPPORT FEET X X X X X X X
KAACS0201PTC START ASSIST PTC X X X X X X X
KAALS0201LLS LIQUID LINE SOLENOID X X X X X X X
KAAWS0101AAA WINTER START X X X X X X X
KAACH1201AAA CRANKCASE HTR X X X
KAACH1401AAA CRANKCASE HTR X X X X
KSATX0201PUR TXV PURON HSO X X X
KSATX0301PUR TXV PURON HSO X X
KSATX0401PUR TXV PURON HSO X
KSATX0501PUR TXV PURON HSO X
KSASH0601COP SOUND HOOD X X X X X X
KSASH2101COP SOUND HOOD X
KAALP0401PUR LOW PRESSURE SWITCH X X X X X X X
KAAHI0501PUR HIGH PRESSURE SWITCH X X X X X X X
{ Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase h eater, evaporator freeze stat, hard shut ---off TXV. X = Accessory
018--- D 024--- D 030 - -- E 036- -- E 042 --- C 048--- E 060 - -- G
DESCRIPTION
Size --- Voltage & Series
6
ACCESSORY USAGE GUIDELINE
REQUIRED FOR LOW --- AMBI-
ACCESSORY
Ball Bearing Fan Motor Yes{ No No
Compressor Start Assist Capacitor and Relay Yes Ye s No
Crankcase Heater Yes Ye s No
Evaporator Freeze Thermostat Yes No No
H a r d S h u t --- O f f T X V Yes Ye s Yes
Liquid Line Solenoid Valve No No No
Motor Master®Control or
L o w --- a m b i e n t P r e s s u r e S w i t c h
Support Feet Recommended No Recommended
Winter Start Control Yes # No No
* Required for Low ---Ambient Controller (full modulation feature) MotorMasterr Control. { Required for Low ---Ambient Controller (full modulation feature) MotorMasterr Control.
# Required if Low Pressure Switch is factory or field installed.
ENT COOLING APPLICATIONS
(Below 55°F/12.8_C)
Yes No No
REQUIRED FOR LONG
LINE APPLICATIONS*
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr is used.
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.
Usage Guideline: Required for reciprocating compressors in the
following applications:
Long line Low ambient cooling
Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the compressor at each start-- up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications. Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor short cycling. This control provides an approximate 5--minute delay after power to the compressor has been interrupted for any reason, including power outage, protector control trip, thermostat jiggling, or normal cycling.
6. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
7. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low--ambient temperatures down to 0_F (--18_C) when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low-- Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).
8. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to --20_F (--28.9_C), it maintains condensing temperature at 100_F ±10_F (37.8_C ±
5.5_C).
Usage Guideline:
A MotorMasterr Low Ambient Controller or Low-- Ambient Pressure Switch must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).
Suggested for all commercial applications.
9. Outdoor Air Temperature Sensor
Designed for use with Bryant Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary heat lock out.
Usage Guideline:
Suggested for all Bryant thermostats listed in this publication.
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within2miles/3.22km)
113A
7
Accessory Description and Usage (Listed Alphabetically) (Continued)
10. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.
Usage Guideline: Suggested when unit is installed closer than 15 ft (4.57 m) to
quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less than 10 ft (3.05 m) apart.
11. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications: Coastal installations. Windy areas or where debris is normally circulating.
Rooftop installations. For improved sound ratings.
113A
12. Thermostatic Expansion Valve (TXV)
A modulating flow-- control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist Capacitor and Relay is required.
Usage Guideline:
Required to achieve ARI ratings in certain equipment combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner long line applications.
Required for use on all zoning systems.
13. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off.
NOTE: Most indoor unit controls include this feature. For those that do not, use the guideline below.
14. Winter Start Control
This control is designed to alleviate nuisance opening of the low--pressure switch by bypassing it for the first 3 minutes of operation.
Usage Guideline:
For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
8
ELECTRICAL DATA
UNIT
S I Z E ---
VOLTAGE,
SERIES
018--- D
024--- D
030--- E
036--- E
042--- C
048--- E
060--- G
* Permissible limits of the voltage range at which the unit will operate satisfactoril y { If wire is applied at ambient greater th an 30_C , consult table 310 ---16 of the NEC (NFPA 70). The ampacity of non ---metallic ---sheathed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other th a n uncoated (no ---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%. * * T i m e --- D e l a y f u se .
FLA --- F u l l L o a d A m p s LRA --- L o c k ed R o to r A mp s MCA --- Minimum Circuit Amps RLA --- RatedLoadAmps NOTE: Control circuit is 24--- V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
Complies with 2007 requirements of ASHRAE Standards 90.1
V/PH
208/230/1 253 197
All motors/compressors contain internal overload protection.
OPER
VOLTS*
COMPR FAN
MCA
MIN WIRE
SIZE{
MIN WIRE
SIZE{
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
48.0 9.0 0.5 11.8 14 14 66 (20.1) 63 (21.0) 15
58.3 13.5 0.77 17.6 14 14 44 (13.4) 42 (12.8) 25
64.0 12.8 0.77 16.8 14 14 46 (14.0) 44 (13.4) 25
77.0 14.1 1.4 20.5 12 12 61 (18.6) 58 (17.7) 30
112.0 17.9 1.1 23.5 12 12 53 (16.2) 51 (15.5) 40
109.0 19.9 1.4 26.2 10 10 76 (23.2) 72 (22.2) 40
134.0 26.4 1.2 34.2 8 10 62 (18.9) 55 (16.8) 50
MAX
LENGTH
ft. (m)}
MAX
LENGTH
ft. (m)}
A--WEIGHTED SOUND POWER (dBA)
U N I T S I Z E ---
SERIES
018--- D 72 53.5 59.5 63.5 67.0 63.5 59.0 52.5 024--- D 76 55.0 61.5 67.0 71.5 69.0 61.0 55.0 030--- E 74 55.0 63.5 68.5 68.5 65.5 61.0 54.0 036--- E 75 59.5 63.0 68.5 70.0 65.5 61.5 53.5 042--- C 78 57.5 65.0 71.0 73.0 70.5 67.5 62.5 048--- E 80 58.5 67.5 73.5 75.0 70.5 67.5 64.5 060--- G 78 59.0 67.5 71.5 73.5 69.0 66.0 63.5
NOTE: Tested in accordance with ARI Standard 270 ---2008 (not listed in AHRI).
STANDARD
RATING
(dBA)
125 250 500 1000 2000 4000 8000
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
MAX
FUSE**
or CKT
BRK
AMPS
113A
A--WEIGHTED SOUND POWER WITH SOUND BLANKET (dBA)
U N I T S I Z E ---
SERIES
018--- D 71 55.5 60.5 64.0 66.0 63.0 58.5 52.0 024--- D 74 55.5 60.5 68.5 70.0 67.0 61.0 53.6 030--- E 73 55.5 64.0 68.0 67.0 64.0 60.0 52.5 036--- E 74 59.5 63.0 68.0 69.5 65.0 60.5 50.5 042--- C 77 57.5 65.0 70.5 72.0 70.0 67.0 62.0 048--- E 79 60.5 67.5 73.5 74.5 71.0 68.0 63.5 060--- G 78 59.0 68.0 70.5 72.5 68.0 67.0 63.0
NOTE: Tested in accordance with ARI Standard 270 ---2008 (not listed in AHRI).
STANDARD
RATING
(dBA)
125 250 500 1000 2000 4000 8000
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- SERIES REQUIRED SUBCOOLING _F(_C)
018--- D 10 (5.6) 024--- D 10 (5.6) 030--- E 10 (5.6) 036--- E 14 (7.8) 042--- C 10 (5.6) 048--- E 15 (8.3) 060--- G 13 (7.2)
9
AIR IN
113A
SHIPPING
SHIPPING
OPERATING
F
N
DIMENSIONS (L x W x H)
WEIGHT (lbs)
NOTES:
WEIGHT (lbs)
F, MAX. 1 25
48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAIN ING SIDE,
AND 24" BETWEEN UN ITS FOR PROPER AIRFLO W.
1. ALLOW 30" CLEAR ANCE TO SERVICE SIDE OF UNIT,
MODE IS 5 5
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING UNIT MODEL NUMBER.
3. SERIES DESIGNATION IS THE 14TH PO SITION OF THE
AIR
DISCHARGE
4. CENTER OF GRAVITY .
5. ALL DIMENSIONS ARE IN "INC HES" UNLESS NOT ED. AIR IN
M
G
AIR IN
E
AIR IN
K
(2) PLACES
5/16"
L
3"
3/8" TIEDOWN KNOCKOUTS
ABCDEFGKLMNP
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
113A018 D X O O O 23 1/2" 25 5/16" 3 3/4" 3/4" 4 7/16" 18 1/16" 7 13/16" 2 13/16" 1/2" 16 1/2" 15" 12" 107 130 24 1/4" X 27 3/8" X 33 1/2"
P
17/8"
SQ.
A
AIR DISCHARGE
X = YES
O=NO
460-3-60
208/230-3-60
230-1-60
208-230-1-60
7/8" HOLE
SUPPLY CONN .
7/8" HOLE WITH
FIELD CONTROL
113A042 C X O O O 31 3/16" 32 5/16" 3 7/8" 7/8" 6 9/16" 24 11/16" 9 1/8" 2 15/16" 5/8" 15 3/4" 16 1/4" 13 3/4" 189 217 32 3/8" X 35 1/2" X 35 15/16"
113A048 E X O O O 31 3/16" 35 3/4" 3 7/8" 7/8" 6 9/16" 24 11/16" 9 1/8" 2 15/16" 5/8" 16 3/8" 15 3/8" 15 1/4" 186 224 32 3/8" X 35 1/2" X 39 3/8"
113A036 E X O O O 25 3/4" 32 5/16" 3 7/8" 7/8" 4 7/16" 21 1/4" 9 1/8" 2 15/16" 5/8" 14 1/4" 10 1/2" 16" 141 170 26 7/8" X 30 1/16" X 35 15/16"
113A060 F, G X O O O 31 3/16" 25 1/2" 3 7/8" 7/8" 6 9/16" 24 11/16" 9 1/8" 2 15/16" 5/8" 14 1/8" 15 3/8" 11 3/4" 190 226 32 3/8" X 35 1/2" X 32 9/16"
113A024 D X O O O 23 1/2" 25 5/16" 3 3/4" 3/4" 4 7/16" 18 1/16" 7 13/16" 2 13/16" 1/2" 16 1/2" 15" 12" 110 134 24 1/4" X 27 3/8" X 33 1/2"
113A030 E X O O O 23 1/2" 28 11/16" 3 3/4" 3/4" 4 7/16" 18 1/16" 7 13/16" 2 13/16" 1/2" 16 1/2" 15" 14" 111 136 24 1/4" X 27 3/8" X 33 1/2"
1 1/8" KNOCKOUT
FIELD POWER SUPPLY CO NN.
B
31/2"
C
MINIMUM
DIMENSIONS
MOUNTING PAD
D
VAPOR LINE CONN .
UNIT SIZE
- 35" X 35"
36 26" X 26"
18,24,30 23 1/2" X 23 1/2"
42,48,60 31 1/2" X 31 1/2"
DIMENSIONS -- ENGLISH
10
SHIPPING
AIR IN
F
SHIPPING
OPERATING
DIMENSIONS (L x W x H)
N
E
WEIGHT (Kgs)
AIR
C, MAX. 52
WEIGHT (Kgs)
1219.2 ABOVE UNIT, 152.4 ON ONE SIDE, 304.8 ON REMAINING SIDE,
AND 609.6 BETWEEN UNITS FOR PROPER AIRFLOW.
NOTES:
1. ALLOW 762.0 CLEARANCE TO SERVICE SIDE OF UNIT,
MODE IS 1 3
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING UNIT MODEL NUMBER.
3. SERIES DESIGNATION IS THE 14TH PO SITION OF THE
4. CENTER OF GRAVITY .
DISCHARGE
AIR IN
AIR IN
5. ALL DIMENSIONS ARE IN "MM" UN LESS NOTED.
M
G
K
(2) PLACES
8.0
L
AIR IN
76.2
9.53 TIEDOWN KNOCKOUTS
113A
P
47.6
X = YES
ABCDEFGKLMNP
O=NO
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
113A018 D X O O O 596.9 643.0 95.2 19.0 112.7 458.8 198.4 71.4 12.7 419.1 381.0 304.8 48.5 59.0 616.0 X 695.3 X 850.9
113A024 D X O O O 596.9 643.0 95.2 19.0 112.7 458.8 198.4 71.4 12.7 419.1 381.0 304.8 49.9 60.8 616.0 X 695.3 X 850.9
113A030 E X O O O 596.9 728.7 95.2 19.0 112.7 458.8 198.4 71.4 12.7 419.1 381.0 355.6 50.3 61.7 616.0 X 695.3 X 850.9
113A036 E X O O O 654.0 820.8 98.4 22.2 112.7 539.8 231.8 74.6 15.9 362.0 266.7 406.4 64.0 77.1 682.6 X 763.6 X 912.8
113A042 C X O O O 792.2 820.8 98.4 22.2 166.7 627.1 231.8 74.6 15.9 400.0 412.8 349.2 85.7 98.4 822.3 X 901.7 X 912.8
113A048 E X O O O 792.2 908.0 98.4 22.2 166.7 627.1 231.8 74.6 15.9 415.9 390.5 387.4 84.4 101.6 822.3 X 901.7 X 1000.1
113A060 F, G X O O O 792.2 647.7 98.4 22.2 166.7 627.1 231.8 74.6 15.9 358.8 390.5 298.4 86.2 102.5 822.3 X 901.7 X 827.1
DIMENSIONS -- SI
SQ.
A
AIR DISCHARGE
460-3-60
208/230-3-60
230-1-60
208-230-1-60
22.23 HOLE
SUPPLY CONN .
FIELD CONTROL
28.58 KNOCKOUT
22.23 HOLE WITH
FIELD POWER SUPPLY CO NN.
B
88.9
C
MINIMUM
DIMENSIONS
MOUNTING PAD
D
VAPOR LINE CONN .
- 889.0 X 889.0
36 660.4 X 660.4
18,24,30 596.9 X 596.9
UNIT SIZE
42,48,60 800.1 X 800.1
11