Unit Features ............................................................................................3
Model Key ..................................................................................................5
Rated Equipment Performance & Effi ciencies .......................6
Performance Data .................................................................................7
Physical Data ............................................................................................9
Dimensions.............................................................................................10
Electrical Data .......................................................................................11
Wiring Diagrams .................................................................................12
Engineering Guide Specifi cations ...............................................20
Accessories & Options ....................................................................21
Warranty Information ......................................................................21
Revision History ..................................................................................22
2
Bryant: Whatever It Takes.
Bryant Geothermal Heat Pump Systems
50YEW Water-To-Water Design Features
The 50YEW series is unlike any other water-to-water heat pump on the market today. The large operating map of the scroll compressor allows high temperature operation, up to 145°F [63°C] leaving load water temperature even at 32°F [0°C] entering source water temperature. The combination of a coaxial (tube-in-tube) heat exchanger for the source (ground loop) side and a brazed plate heat exchanger for the load (heating/hot water) side provides very high effi ciencies. Integral controls for hydronic heating and domestic water heating avoid the need for external microprocessor-based controls for outdoor temperature reset, warm weather shutdown, staging and other controls.
The 50YEW has an extended range refrigeration circuit, capable of ground loop (geothermal) applications as well as open loop (well water) applications. Standard features and factory-installed options are many. Unique application-specifi c controls make the 50YEW series ideal for hydronic heating and domestic hot water generation. The heating-only refrigeration circuit is optimized for high water temperatures, heating effi ciencies, and capacities.
The dual level compressor isolation mounting system, insulated compressor enclosure, and compressor discharge muffl er make the 50YEW series one of the quietest water-to-water heat pumps available. The attractive “Euro-style” cabinet allows the unit to fi t into any decor.
Application Flexibility
• Capacities 10kW [32,600 Btuh].
• High temperature scroll compressor, up to 145°F [63°C] leaving water temperature.
• Ultra high effi ciencies (4.2 COP at ground loop conditions; up to
5.5 COP at ground water conditions).
• Built-in programmable controller with Outdoor Temperature Reset and Warm W eather Shutdown.
• Large, back-lit digital user interface.
• Rugged coaxial (tube-in-tube) “Source” heat exchanger (copper or cupronickel).
• Close approach temperature brazed plate stainless steel “Load” heat exchanger.
• Dual level compressor isolation, compressor enclosure, and discharge muffl er for Ultra quiet operation.
• “Euro-style” cabinet for attractive look.
• Insulated cabinet with foil backed insulation for ease of cleaning.
• Flush-mount FPT fi ttings, secured to the cabinet (no backup wrench required).
• TXV metering device.
• 12-point low voltage terminal strip for ease of installation.
• ETL safety listing.
• Wide variety of options including internally factory installed Domestic Hot Water Mode, Load and Source side pumps with expansion tanks, VSFP (variable speed fl oor pump connection) Controls and Cupro-Nickel Source Heat Exchanger.
Service & Installation Advantages
• Hinged front access door and 3 removable panels for ease of installation and service.
• Galvanized steel construction with protective powder coat paint and hinged front access door.
• Bi-directional thermal expansion valve.
• Puron
• Circuit breaker protected 75VA control transformer.
• High and low pressure service ports on refrigerant circuit.
• Accurate refrigerant sensing freeze protection.
Factory Quality & Certifi cations
• All units are built on our Integrated Process Control Assembly System (IPCS). The IPCS is a unique state of the art manufacturing system that is designed to assure quality of the highest standards of any manufacturer in the water-source industry. Our IPCS system:
a. Verifi es that the correct components are being assembled. b. Automatically performs special leak tests on all joints. c. Conducts pressure tests. d. Performs highly detailed run test unparalleled in the HVAC industry. e. Automatically disables packaging for a “failed” unit. f. Creates computer database for future service analysis and
diagnostics from run test results.
• All units are water run-tested in all modes to insure effi ciency and reliability.
• Heavy gauge galvanized steel cabinets are epoxy powder coated for durable and long-lasting fi nish.
• All refrigerant brazing is done in a nitrogen atmosphere.
• All units are deep evacuated to less than 100 microns prior to refrigerant charging.
• All joints are both helium and halogen leak tested to insure annual leak rate of less than 1/4 ounce.
• Coaxial heat exchanger, refrigerant suction lines and all water lines are fully insulated to eliminate condensation problems in low temperature applications.
• Noise Reduction features include: dual level compressor isolation, insulated compressor compartment, interior cabinet insulation using 1/2” coated glass fi ber, and variable speed fan.
• Safety features include: high pressure and loss of charge to protect the compressor, condensate overfl ow protection, freeze protection sensors to safeguard the coaxial heat exchanger and air coil, hot water high-limit and low compressor discharge temperature switch provided to shut down the hot water generator when conditions dictate. Fault lockout enables emergency heat and prevents compressor operation until thermostat or circuit breaker has been reset.
• 10-year limited warranty on major refrigerant circuit components, Optional extended warranties available.
• AHRI/ASHRAE/ANSI/ISO 13256-2 certifi ed.
• NRTL & CSA listed.
• US EPA “Energy Star” compliant.
• ISO 9001:2000 Certifi ed.
Options & Accessories
• Full Condensing Hot Water Generation With Internal Secondary Heat Exchanger and Potable Water Circulating Pump.
• Factory Installed “Load” and “Source” Pumps.
• Factory Installed Expansion Tanks.
• Cupro-Nickel Source Water Coil.
• Extended Labor Allowance and Service Warranty.
®
HFC-410A zero ozone depletion refrigerant.
Residential Products Technical Guide
3
50YEW W ater -To-W ater Series
50YEW Water-To-Water Series Features
1
Euro-Style Cabinet For Attractive Look
2
High Temperature Scroll Compressor
3
Rugged Coaxial “Source” Heat Exchanger
Close Approach Temperature Brazed Plate
4
Stainless Steel “Load” Heat Exchanger Optional Full Condensing Hot Water
5
Generation With Internal Secondary Heat Exchanger and Potable Water Circulating Pump
Optional Factory Installed “Load” and
6
“Source” Pumps with expansion tanks Fully Insulated Water and
7
Refrigerant Lines
5
6
7
14
11
4
1
8
Fully Insulated Compressor Section
Powder Coated Galvanized Steel Cabinet
9
and Front Access Panel For Long Life, Taupe Metallic
Large Backlight User Interface
10
Built-In Programmable Controller With
11
Outdoor Temperature Reset and Warm Weather Shutdown
Dual level compressor isolation and discharge
12
muffl er for ultra quiet operation Hinged Front Access Door and Three
13
Removable Panels For Ease of Installation and Service
12-Point Terminal Strip For Ease of Low
14
V oltage Wiring
3
2
12
9
13
10
4
8
Bryant: Whatever It Takes.
Bryant Geothermal Heat Pump Systems
Model Key
5 0 A0 1 0 CW 3 1 1
Y E W
Prefix
Residential Series
YEW = Puron High Temperature
Heating Only Water-to-Water
1 2 3
4 5 6 7
Unit Size
010 (10kW)
Hydronic Options
A = No Pump B = Load Pump w/Expansion Tank C = Load Pump & Source Pump(s) w/Expansion Tanks
8
9101112
Water Coil & DHW Options
C = Copper Source & Braze Plate Load, No DHW D = Copper Source & Braze Plate Load, DHW w/Sec. hx & pump N = Cupro-Nickel Source & Braze Plate Load, No DHW P = Cupro-Nickel Source & Braze Plate Load, DHW w/Sec. hx & pump
Controls
W = CXM Y = CXM w/VSFP
Packaging
1 = Single Pack, Domestic
Revision Level
1 = Current
Voltage
3 = 208-230/60/1
*When digit 9 = “D” or “P,” digit 7 cannot be “A.”
*
*
Residential Products Technical Guide
5
50YEW W ater -To-W ater Series
Rated Equipment Performance & Effi ciencies
60 Hz (IP) Units
Ground Loop Heat Pump Ground Water Heat Pump
Heating Heating
Model
50YEW010
THW010 32.6 4.2 30.8 3.3 42.6 5.2 39.9 4.1
Indoor temperature is also called “Load;” outdoor temperature is also called “Source.” Numbers shown with “/” indicate entering/leaving water temperatures. Bold outline indicates typical radiant fl oor application temperatures. Ratings at 40°C [104°F] are based upon AHRI/ISO Standard 13256-2; all other ratings are based upon Standard EN 14511-2.
Indoor 86/95°F
Outdoor 32/27°F
Capacity
Mbtuh
COP
60 Hz (SI) Units
Ground Loop Heat Pump Ground Water Heat Pump
Heating Heating
Model
50YEW010
THW010 9.57 4.2 9.03 3.3 12.50 5.2 11.69 4.1
Indoor temperature is also called “Load;” outdoor temperature is also called “Source.” Numbers shown with “/” indicate entering/leaving water temperatures. Bold outline indicates typical radiant fl oor application temperatures. Ratings at 40°C [104°F] are based upon AHRI/ISO Standard 13256-2; all other ratings are based upon Standard EN 14511-2.
Indoor 30/35°C Outdoor 0/-3°C
Capacity
kW
COP
Indoor 104/113°F
Outdoor 32/27°F
Capacity
Mbtuh
Indoor 40/45°C Outdoor 0/-3°C
Capacity
kW
COP
COP
Indoor 86/95°F
Outdoor 50/45°F
Capacity
Mbtuh
Indoor 30/35°C
Outdoor 10/7°C
Capacity
kW
COP
COP
Indoor 104/113°F
Outdoor 50/45°F
Capacity
Mbtuh
Indoor 40/45°C
Outdoor 10/7°C
Capacity
kW
COP
COP
6
Bryant: Whatever It Takes.
Bryant Geothermal Heat Pump Systems
Performance Data - 50YEW010
Source Load
EWT
GPM
°F
20 8.3 1.3 3.1
4.2 0.3 0.8
30
8.3 0.9 2.0
4.2 0.3 0.7
50
8.3 0.7 1.7
4.2 0.3 0.7
70
8.3 0.7 1.7
THW operating parameters are as follows: Min Source EWT = 20°F; Max Load LWT = 145°F (see application section for design guidelines).
50YEW
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT (source) is based upon 15% methanol antifreeze solution. All performance data is based upon the lower voltage of dual voltage units. Antifreeze for source water is required for operation in the shaded area and all source EWTs below 40°F.
WPD
PSI FT PSI FT PSI FT
EWT
HC
°F
MBtuh
50 32.3 1.10 28.6 61.9 8.6 0.8 1.7 32.7 1.10 32.7 59.4 8.7 1.8 4.0 70 30.0 1.74 27.7 81.1 5.1 0.6 1.4 30.3 1.68 30.3 78.7 5.3 1.1 2.6 90 27.8 2.41 22.9 100.2 3.4 0.5 1.2 28.0 2.35 28.0 98.0 3.5 1.0 2.2
110 25.5 2.99 18.4 119.4 2.5 0.4 0.9 25.7 2.93 25.7 117.4 2.6 0.8 1.9
50 31.9 1.10 28.1 61.8 8.5 0.8 1.7 32.1 1.11 32.1 58.8 8.5 1.8 4.0 70 29.6 1.74 23.7 80.9 5.6 0.6 1.4 29.7 1.68 29.7 78.1 5.2 1.1 2.6
90 27.4 2.40 19.2 100.1 3.8 0.5 1.2 27.2 2.34 27.2 97.5 3.4 1.0 2.2 110 25.2 2.97 15.1 119.3 2.8 0.4 0.9 24.8 2.91 24.8 116.8 2.5 0.8 1.9 130 22.8 3.68 10.3 138.4 2.1 0.3 0.7 22.4 3.62 22.4 136.2 1.8 0.7 1.6
50 36.3 1.12 32.5 63.4 9.5 0.8 1.7 36.7 1.12 36.7 60.1 9.6 1.8 4.0
70 33.7 1.76 27.7 82.4 5.6 0.6 1.4 34.1 1.7 34.1 79.3 5.9 1.1 2.6
90 31.2 2.43 22.9 101.5 3.8 0.5 1.2 31.5 2.37 31.5 98.6 3.9 1.0 2.2 110 28.7 3 18.4 120.6 2.8 0.4 0.9 28.9 2.94 28.9 117.9 2.9 0.8 1.9 130 26.0 3.72 13.3 139.6 2.1 0.3 0.7 26.3 3.66 26.3 137.2 2.1 0.7 1.6
50 44.2 1.12 40.4 66.3 11.6 0.8 1.7 43.9 1.11 43.9 62.0 11.6 1.8 4.0
70 41.1 1.81 34.9 85.2 7.3 0.6 1.4 40.6 1.71 34.8 81.1 6.9 1.1 2.6
90 38.2 2.53 29.6 104.1 4.8 0.5 1.2 37.5 2.43 29.2 100.3 4.5 1.0 2.2 110 35.1 3.15 24.4 123.0 3.8 0.4 0.9 34.2 3.06 23.8 119.4 3.3 0.8 1.9 130 32.1 3.92 18.7 141.8 2.6 0.3 0.7 31.0 3.82 18.0 138.5 2.4 0.7 1.6
50 48.9 1.13 45.0 68.1 12.7 0.8 1.7 49.3 1.12 49.3 63.5 12.9 1.8 4.0
70 45.5 1.83 39.2 86.8 7.3 0.6 1.4 45.9 1.73 40.0 82.6 7.8 1.1 2.6
90 42.3 2.56 33.5 105.6 4.8 0.5 1.2 42.7 2.46 34.3 101.7 5.1 1.0 2.2 110 38.9 3.18 28.1 124.4 3.8 0.4 0.9 39.3 3.09 28.8 120.8 3.7 0.8 1.9 130 35.5 3.96 22.0 143.1 2.6 0.3 0.7 35.9 3.86 22.7 139.8 2.7 0.7 1.6
50 57.0 1.13 53.1 71.1 14.8 0.8 1.7 56.3 1.12 56.3 65.4 14.8 1.8 4.0
70 53.1 1.87 46.7 89.6 8.3 0.6 1.4 52.0 1.73 46.1 84.2 8.8 1.1 2.6
90 49.6 2.63 40.6 108.3 5.5 0.5 1.2 48.1 2.49 39.5 103.2 5.6 1.0 2.2 110 45.8 3.30 34.5 126.9 4.1 0.4 0.9 44.0 3.17 33.2 122.1 4.1 0.8 1.9 130 41.9 4.11 27.9 145.5 3.0 0.3 0.7 39.8 3.98 26.3 140.9 2.9 0.7 1.6
50 61.4 1.14 57.5 72.7 15.8 0.8 1.7 62.0 1.13 62.0 67.0 16.1 1.8 4.0
70 57.2 1.89 50.8 91.1 8.9 0.6 1.4 57.8 1.75 51.8 85.8 9.7 1.1 2.6
90 53.4 2.66 44.3 109.7 5.9 0.5 1.2 53.9 2.52 45.3 104.8 6.3 1.0 2.2 110 49.3 3.34 37.9 128.2 4.3 0.4 0.9 49.8 3.2 38.9 123.6 4.6 0.8 1.9 130 45.1 4.16 30.9 146.7 3.2 0.3 0.7 45.5 4.02 31.8 142.5 3.3 0.7 1.6
5.4 GPM
PowerkWHE
MBtuh
LWT
°F
COP
WPD
HC
MBtuh
7.3 GPM
PowerkWHE
MBtuh
LWT
°F
WPD
COP
Residential Products Technical Guide