• Virtually no glide. Unlike other alternative refrigerants, the
MERV 11 2” Pleated fi lter
All GT-PG units include a factory
installed 2” fi lter rack/duct collar
with a 2” pleated high effi ciency
MERV 11 air fi lter. The MERV
(minimum effi ciency reporting value
per ASHRAE Standard 52.2) design
features ultra low velocity (<300
fpm) for extended fi lter life, low pressure drop (0.13 – 0.18 in. wg.)
and high particulate effi ciency (size E1=41%, E2=69% and E3=87%).
The pleated design and low velocity combine to allow the fi lter to
store a large amount of dirt and result in a practical replacement life of
up to 6 months.
Tin-Coated Air Coil
All Bryant Geothermal GTPG Series models feature a
tin-coated air-coil. This coating
process will provide years of
protection against corrosion
from airborne chemicals
resulting from modern building
material out gassing and most
environmental chemicals found
in the air. Modern building
materials such as counter-tops,
fl oor coverings, paints and other materials can “outgas” chemicals into
the home’s air. Some of these chemicals are suspected of contributing
to corrosion in the air coils found in both traditional and geothermal
heating and cooling equipment. Corrosion often results in refrigerant
leaks and eventual failure of the air coil costing hundreds of dollars to
replace. Studies have also shown that these air coil coatings improve
moisture shedding and therefore improve a unit’s moisture removal
capability resulting in a more comfortable home. The GT-PG Series is
your assurance of both maximum air coil life and comfort.
Refrigerant
®
is a non-chlorine based (HFC-410A) refrigerant, that with
50% R-125.
Zero ozone depletion potential and low global warming potential.
two components in HFC-410A have virtually the same leak
rates. Therefore, refrigerant can be added if necessary without
recovering the charge.
MERV 11
Copeland – turned theory into practical
reality, using sophisticated, computer-assisted
design and manufacturing methods to achieve
the critical tolerances required. In the years
since, Copeland has become the leader in
scroll compressor applications, with nine scroll
manufacturing facilities on three continents and
millions of units installed worldwide.
Copeland Scroll compressors employ two
identical, concentric scrolls, one inserted
within the other. One scroll remains stationary as the other orbits
around it. This movement draws gas into the compression chamber
and moves it through successively smaller “pockets” formed by the
scroll’s rotation, until it reaches maximum pressure at the center
of the chamber. There, it’s released through a discharge port in the
fi xed scroll. During each orbit, several pockets are compressed
simultaneously, so operation is virtually continuous.
Recently, Copeland produced its 500,000th Scroll compressor with
the environmentally sound refrigerant HFC-410A. Field results have
shown that HFC-410A units with Copeland Scroll compressors offer
nearly 30% lower failure rates versus existing R-22 units. HFC-410A
units can reach the industry’s highest effi ciency levels. HFC-410A
scrolls also offer sound advantages to other compressor technologies,
typically operating several decibels quieter than comparable R-22
models. The result is unsurpassed reliability and virtually silent
operation.
Other New Features
• Powder coated cabinet, taupe metallic.
• Liftout handles for front access panels.
• Corrosion and stain resistant stainless steel drain pan with extra
slope designed in.
• Factory mounted fi lter drier for trouble free reliability.
• Easy access low profi le horizontal control box.
• Double isolated compressor for quiet and vibration
free operation.
Foil faced insulation in air handling compartment to allow easy
•
cleaning and prevent microfi ber introduction into the air stream.
• Open Service-Friendly Cabinet ( i.e, all components in
compressor section can be serviced from the front).
Copeland Scroll Compressor
There’s a reason 9 out of every 10 scroll compressors installed
are Copeland. With over 15 years of painstaking R & D and rigid
production controls, Copeland is able to build the most reliable,
effi cient and quiet scroll compressors in the world.
The concept of compressing a gas by turning one involute form – or
“scroll” – against another around a common axis is nearly a century
old. It wasn’t until the late 1980s, however that one company –
Residential Products Technical Guide
GT-PG
3
GT-PG (50YE) Series
GT-PG Design Features
The GT-PG Series has abundant features and industry leading
effi ciency.
• Oversized tin-coated, rifl ed tube/lanced aluminum fi n, air to
•
Service Advantages
• Removable panels - 3 for compressor, 2 for air
• Low profi le control box grants easy access to all
• Factory installed liquid line fi lter/drier.
• Brass swivel-type water connections for quick connection and
• Bi-directional thermal expansion valve.
• CXM control features status light with memory for
• Unit Performance Sentinel alerts homeowner of potential
®
HFC-410A zero ozone depletion refrigerant.
stage ratings for heating COPs, cooling EERs with low water
fl ow rates.
ultra high effi ciencies and unsurpassed comfort.
shorter loops.
water at considerable savings.
scroll compressors provide the extremely high effi ciencies
and capacities.
operate at low liquid pressure drop. Convoluted copper (and
optional cupro-nickel) water tube functions effi ciently at low-fl ow
rates and provides freeze-damage resistance.
refrigerant heat exchangers provide high effi ciency at low
face velocity.
Large low RPM blowers with optional variable speed fan motors
provide quiet, effi cient air movement with high static capability.
handling compartment.
internal components.
elimination of wrenches or sealants during installation.
easy diagnostics.
performance issues.
• Circuit breaker protected 75VA control transformer.
• Optional ECM motor includes control board with thermostat
signal diagnostic LEDs, airfl ow display LED (100 CFM per fl ash),
and simplifi ed CFM selection.
• Insulated divider and separate air handling/compressor
compartments permit service testing without air bypass.
• Fan motors have quick attach wiring harness for fast removal.
• Internal dropout blower for easy servicing.
• High and low pressure service ports on refrigerant circuit.
• Accurate refrigerant sensing low temperature protection.
Factory Quality
• All units are built on our Integrated Process Control
Assembly System (IPCS). The IPCS is a unique state of the art
manufacturing system that is designed to assure quality of the
highest standards of any manufacturer in the water-source
industry. Our IPCS system:
- Verifi es that the correct components are being assembled.
- Automatically performs special leak tests on all joints.
- Conducts pressure tests.
- Performs highly detailed run test unparalleled in the
HVAC industry.
- Automatically disables packaging for a “failed” unit.
- Creates computer database for future service analysis and
diagnostics from run test results.
• All units are water run-tested in all modes to insure effi ciency
and reliability.
• Heavy gauge galvanized steel cabinets are epoxy powder coated
for durable and long-lasting fi nish.
• All refrigerant brazing is done in a nitrogen atmosphere.
• All units are deep evacuated to less than 100 microns prior to
refrigerant charging.
• All joints are both helium and halogen leak tested to insure
annual leak rate of less than 1/4 ounce.
• Coaxial heat exchanger, refrigerant suction lines and all water
lines are fully insulated to eliminate condensation problems in low
temperature applications.
• Noise Reduction features include: double isolation mounted
compressors; insulated compressor compartment; interior cabinet
insulation using 1/2” coated glass fi ber and optional variable
speed fan.
• Safety features include: high pressure and loss of charge to
protect the compressor; condensate overfl ow protection; low
temperature protection sensors to safeguard the coaxial heat
exchanger and air coil; hot water high-limit and low compressor
discharge temperature switch provided to shut down the hot
water generator when conditions dictate. Fault lockout enables
emergency heat and prevents compressor operation until
thermostat or circuit breaker has been reset.
Simplifi ed Controls
• CXM solid state control module.
• ‘CFM’ LED displays airfl ow (optional ECM motor).
Foil Faced Insulation In The Blower Section, Fully Insulated
4
Compressor Section
Two Inch Filter Frame With High Performance MERV 11
5
Pleated Air Filter*
Stainless Steel Drain Pan For Long Life
6
7
Unit Performance Sentinel: Automatic Alert System
Lets You Know If The System Is Not Running At Peak
Performance**
Exclusive Dual Level Compressor Vibration Isolation For
8
Ultra Quiet Operation
9
Five Easy, Lift-out Service Access Panels
With Powder Coated Cabinet, Taupe Metallic
* MERV= Minimum Effi ciency Reporting Value as specifi ed by ASHRAE (American
Society of Heating, Refrigerating and Air Conditioning Engineers) standard 52.2.
** When installed with a Bryant Geothermal Residential Thermostat.
2
3
6
1
8
4
7
9
87
Residential Products Technical Guide
Features Puron®
HFC-410A Zero Ozone
Depletion Refrigerant
GT-PG
5
GT-PG (50YE) Series
Unit Model Key
5 0J0 2 4BC311
Prefix
YEV = Puron Vertical Upflow Single-Stage
YEH = Puron Horizontal Single-Stage
YED = Puron Vertical Downflow Single-Stage
Option
JKLeft
L*R*Left
Option
JKLeft
L*R*Left
Option
N
P
W
Y
Z*
B*
S*
E*
* PSC motor not available on size 070
Series
018, 024, 030, 036, 042, 048, 060, 070
Air Flow Configuration
Vertical Upflow YEV
Discharge
Return
Right
Right
Vertical Downflow YED
Discharge
Return
Right
Right
Horizontal YEH
Discharge
Return
Right
Right
Left
Left
Right
Right
Left
Left
1 2 3
Y E V
Unit Size
Top
Top
Top
Top
Down
Down
Down
Down
Left
Back
Right
Back
Left
Back
Right
Back
Filter
2”
2”
2”
2”
Filter
2”
2”
2”
2”
Filter
2”
2”
2”
2”
2”
2”
2”
2”
4 5 67
Motor
ECM
ECM
PSC
PSC
Motor
ECM
ECM
PSC
PSC
Motor
ECM
ECM
ECM
ECM
PSC
PSC
PSC
PSC
9101112
8
Heat Exchanger Options
Without Hot Water Generator
Standard
Whole House Dehumidification
Whole House Dehumidification
w/Hot Water Generator
Controls
C = CXM
D = DXM
Revision Level
1 = 024-070
2 = 018
Voltage
3 = 280-230/60/1
Packaging
1 = Single Pack, Domestic
Coated Air Coil
Copper
Cupro-Nickel
A
B
RF
LM
J
K
GT-PG
6
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
About AHRI/ISO/ASHRAE 13256-1
About AHRI/ISO/ASHRAE 13256-1
AHRI/ASHRAE/ISO 13256-1 (Air-Conditioning and Refrigeration Institute/American Society of Heating, Refrigerating and Air Conditioning
Engineers/International Standards Organization) is a certifi cation standard for water-source heat pumps used in the following applications:
• WLHP (Water Loop Heat Pump – Boiler/Tower)
• GWHP (Ground Water Heat Pump – Open Loop)
• GLHP (Ground Loop Heat Pump – Geothermal)
The directory at http://www.ahrinet.org/ is constantly being updated and immediately available on the Internet. All ratings are submitted by the
manufacturer for certifi cation, and must be approved by AHRI. Therefore, there is a signifi cant difference between AHRI “certifi ed” and AHRI
“rated.” Thirty percent of a manufacturer’s basic models must be tested each year. AHRI selects models at random from stock for testing on
the basis of its evaluation of a participant’s certifi cation data.
Units that fail one or more certifi ed test (90% of declared performance or lower) may be declared defective. If the initial failure is a
performance test, the manufacturer must obsolete all units within the same basic model group or elect to have a second sample tested. If the
second unit fails a performance test, it must be obsoleted, together with all units within the same basic model group. Bryant Geothermal takes
certifi cation seriously. We were recently awarded a certifi cate for consecutive years of no AHRI failures.
Temperatures used in AHRI certifi cation standards are S.I. (Système International – metric) based. For example, typical catalog data for cooling
is shown at 80°F DB/67°F WB [26.7°C DB/19.4°C] entering air temperature, but the AHRI standard for cooling is 80.6°F DB/66.2°F WB
[27°C DB/19°C], since it is based upon whole numbers in degrees Celsius. Water and air temperatures for the standard are shown below.
Test Condition Comparison Table
WLHPGWHPGLHP
Cooling
Entering Air Temperature - DB/WB °F [°C]
Entering Water Temperature - °F [°C]
Fluid Flow Rate
Heating
Entering Air Temperature - DB/WB °F [°C]
Entering Water Temperature - °F [°C]
Fluid Flow Rate
*Flow rate is specifi ed by the manufacturer
80.6/66.2 [27/19]
86 [30]
*
68 [20]
68 [20]
*
80.6/66.2 [27/19]
59 [15]
*
68 [20]
50 [10]
*
80.6/66.2 [27/19]
77 [25]
*
68 [20]
32 [0]
*
Data certifi ed by AHRI include heating/cooling capacities, EER (Energy Effi ciency Ratio – Btuh per Watt) and COP (Btuh per Btuh) at the
various conditions shown above. Pump power correction is calculated to adjust effi ciencies for pumping Watts. Within each model, only one
water fl ow rate is specifi ed for all three groups, and pumping Watts are calculated using the formula below. This additional power is added
onto the existing power consumption.
• Pump power correction = (gpm x 0.0631) x (Press Drop x 2990)/300
Fan power is corrected to zero external static pressure using the equation below. The nominal airfl ow is rated at a specifi c external static
pressure. This effectively reduces the power consumption of the unit and increases cooling capacity but decreases heating capacity.
• Fan Power Correction = (cfm x 0.472) x (esp x 249)/300
Capacities and effi ciencies are calculated using the following equations:
• ISO Cooling Capacity = Cooling Capacity (Btuh) + [Fan Power Correction (Watts) x 3.412]
• ISO EER Effi ciency (Btuh/W) =
ISO Cooling Capacity (Btuh)/[Power Input (Watts) – Fan Power Correction (Watts) + Pump Power Correction (Watts)]
• ISO Heating Capacity = Heating Capacity (Btuh) – [Fan Power Correction (Watts) x 3.412]
• ISO COP Effi ciency (Btuh/Btuh) =
ISO Heating Capacity (Btuh) x 3.412/[Power Input (Watts) - Fan Power Correction (Watts) + Pump Power Correction (Watts)]
Residential Products Technical Guide
GT-PG
7
GT-PG (50YE) Series
AHRI/ISO/ASHRAE/ANSI 13256-1 Performance
ASHRAE/AHRI/ISO 13256-1. English (I-P) Units
Water Loop Heat PumpGround Water Heat PumpGround Loop Heat Pump
Model
018
TS018
TS024
024
030
TS030
TS036
036
042
TS042
TS048
048
060
TS060
TS070
070
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All ratings based upon operation at lower voltage of dual voltage rated models
Water Loop Heat PumpGround Water Heat PumpGround Loop Heat Pump
Model
018
TS018
024
TS024
TS030
036
030
TS036
042
TS042
TS048
048
060
TS060
070
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature
Heating capacities based upon 20°C DB, 15°C WB entering air temperature
All ratings based upon operation at lower voltage of dual voltage rated models
Hot Water Generator capacities (HWC) are based on potable water fl ow rate of 0.4 gpm per nominal equipment ton and 90°F
entering potable water temperature.
CFM = airfl ow, cubic feet/minute
EWT = entering water temperature, ˚F
GPM = water fl ow in US gallons/minute
EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)
HC = air heating capacity, Mbtuh
TC = total cooling capacity, Mbtuh
SC = sensible cooling capacity, Mbtuh
KW = total power unit input, KiloWatts
HR = total heat of rejection, Mbtuh
UPFLOW
HE = total heat of extraction, Mbtuh
HWC = Hot Water Generator (desuperheater) capacity, Mbtuh
WPD = Water coil pressure drop (psi & ft hd)
EER = Energy Effi ciency Ratio = BTU output/Watt input
COP = Coeffi cient of Performance = BTU output/BTU input
LWT = leaving water temperature, °F
LAT = leaving air temperature, °F
LC = latent cooling capacity, Mbtuh
S/T = sensible to total cooling ratio
LEFT RETURN AIR
Piping End
Piping End
Left Return Air
Back Discharge
Piping End
Left Return Air
Side Discharge
Left Return AirRight Return Air
Piping End
Residential Products Technical Guide
RIGHT RETURN AIR
Piping End
Right Return Air
Back Discharge
Piping End
Right Return Air
Side Discharge
Piping End
GT-PG
9
GT-PG (50YE) Series
Air Flow Correction Factors
PSC Fan Motor
Airfl owCoolingHeating
% of
Rated
68.75%
75%
81.25%
87.50%
93.75%
100%
106.25%
112.50%
118.75%
125%
130%
Black area denotes where operation is not recommended.
Total
Capacity
0.94650.80190.84720.96140.9496
0.96020.83500.86960.96750.96170.97401.09360.9425
0.97240.87330.89810.97440.97280.98101.06350.9592
0.98310.91490.93060.98210.98290.98761.03790.9744
0.99230.95780.96530.99060.99200.99401.01670.9880
1.00001.00001.00001.00001.00001.00001.00001.0000
1.00621.03921.03281.01021.00701.00570.98781.0105
1.01091.07331.06171.02111.01301.01120.98001.0194
1.01411.10011.08481.03291.01801.01630.97051.0284
1.01591.11741.09991.04551.02201.02110.96141.0368
1.01611.12291.10501.05621.02441.02470.95541.0430
Sensible
Capacity
S/TPower
Heat of
Rejection
Heating
Capacity
Power
Heat of
Extraction
ECM Fan Motor
Airfl owCoolingHeating
% of
Rated
68.75%
75%
81.25%
87.50%
93.75%
100%
106.25%
112.50%
118.75%
125%
130%
Black area denotes where operation is not recommended.
Total
Capacity
0.94700.82650.87270.93630.9449
0.96190.85930.89330.94550.95870.97001.08220.9410
0.97470.89430.91750.95640.97110.97751.05360.9579
0.98530.93020.94410.96910.98210.98511.03040.9733
0.99380.96590.97190.98370.99180.99251.01250.9874
1.00001.00001.00001.00001.00001.00001.00001.0000
1.00411.03131.02711.01811.00691.00740.99281.0112
1.00601.05841.05221.03811.01231.01480.99091.0210
1.00701.08151.07401.05981.01741.02220.96221.0377
1.00761.09981.09161.08341.02251.02950.86811.0712
1.00831.11101.10181.10351.02711.03540.84561.0844
Sensible
Capacity
S/TPower
Heat of
Rejection
Heating
Capacity
Power
Heat of
Extraction
GT-PG
10
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
Entering Air Correction Factors
Heating
Entering
Air DB°F
45
50
55
60
65
68
70
75
80
Entering
Air WB°F
50
55
60
65
66.2
67
70
75
* = Sensible capacity equals total capacity
AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/66.2°F WB, 1
and Heating - 68°F DB/59°F WB entering air temperature
Performance capacities shown in thousands of Btuhting
Heating - EAT 70°F
Airfl ow
CFM
HCkWHELATCOPHW
Performance Data Selection Notes
For operation in the shaded area when water is used in
lieu of an anti-freeze solution, the LWT (Leaving Water
Temperature) must be calculated. Flow must be maintained
to a level such that the LWT is maintained above 40°F
[4.4°C] when the JW3 jumper is not clipped (see example
below). Otherwise, appropriate levels of a proper anti-freeze
should be used in systems with leaving water temperatures
of 40°F or below and the JW3 jumper should be clipped.
This is due to the potential of the refrigerant temperature
being as low as 32°F [0°C] with 40°F [4.4°C] LWT, which may
lead to a nuisance cutout due to the activation of the Low
Temperature Protection. JW3 should never be clipped for
standard range equipment or systems without antifreeze.
Example:
At 50°F EWT (Entering Water Temperature) and 1.5 gpm/
ton, a 3 ton unit has a HE of 22,500 Btuh. To calculate LWT,
rearrange the formula for HE as follows:
HE = TD x GPM x 500, where HE = Heat of Extraction (Btuh);
TD = temperature difference (EWT - LWT) and GPM = U.S.
Gallons per Minute.
TD = HE/(GPM x 500)
TD = 22,500/(4.5 x 500)
TD = 10°F
LWT = EWT - TD
LWT = 50 - 10 = 40°F
In this example, as long as the EWT does not fall below 50°F, the system will operate as designed. For EWTs below 50°F,
higher fl ow rates will be required (open loop systems, for example, require at least 2 gpm/ton when EWT is below 50°F).
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.