• Virtually no glide. Unlike other alternative refrigerants, the
MERV 11 2” Pleated fi lter
All GT-PG units include a factory
installed 2” fi lter rack/duct collar
with a 2” pleated high effi ciency
MERV 11 air fi lter. The MERV
(minimum effi ciency reporting value
per ASHRAE Standard 52.2) design
features ultra low velocity (<300
fpm) for extended fi lter life, low pressure drop (0.13 – 0.18 in. wg.)
and high particulate effi ciency (size E1=41%, E2=69% and E3=87%).
The pleated design and low velocity combine to allow the fi lter to
store a large amount of dirt and result in a practical replacement life of
up to 6 months.
Tin-Coated Air Coil
All Bryant Geothermal GTPG Series models feature a
tin-coated air-coil. This coating
process will provide years of
protection against corrosion
from airborne chemicals
resulting from modern building
material out gassing and most
environmental chemicals found
in the air. Modern building
materials such as counter-tops,
fl oor coverings, paints and other materials can “outgas” chemicals into
the home’s air. Some of these chemicals are suspected of contributing
to corrosion in the air coils found in both traditional and geothermal
heating and cooling equipment. Corrosion often results in refrigerant
leaks and eventual failure of the air coil costing hundreds of dollars to
replace. Studies have also shown that these air coil coatings improve
moisture shedding and therefore improve a unit’s moisture removal
capability resulting in a more comfortable home. The GT-PG Series is
your assurance of both maximum air coil life and comfort.
Refrigerant
®
is a non-chlorine based (HFC-410A) refrigerant, that with
50% R-125.
Zero ozone depletion potential and low global warming potential.
two components in HFC-410A have virtually the same leak
rates. Therefore, refrigerant can be added if necessary without
recovering the charge.
MERV 11
Copeland – turned theory into practical
reality, using sophisticated, computer-assisted
design and manufacturing methods to achieve
the critical tolerances required. In the years
since, Copeland has become the leader in
scroll compressor applications, with nine scroll
manufacturing facilities on three continents and
millions of units installed worldwide.
Copeland Scroll compressors employ two
identical, concentric scrolls, one inserted
within the other. One scroll remains stationary as the other orbits
around it. This movement draws gas into the compression chamber
and moves it through successively smaller “pockets” formed by the
scroll’s rotation, until it reaches maximum pressure at the center
of the chamber. There, it’s released through a discharge port in the
fi xed scroll. During each orbit, several pockets are compressed
simultaneously, so operation is virtually continuous.
Recently, Copeland produced its 500,000th Scroll compressor with
the environmentally sound refrigerant HFC-410A. Field results have
shown that HFC-410A units with Copeland Scroll compressors offer
nearly 30% lower failure rates versus existing R-22 units. HFC-410A
units can reach the industry’s highest effi ciency levels. HFC-410A
scrolls also offer sound advantages to other compressor technologies,
typically operating several decibels quieter than comparable R-22
models. The result is unsurpassed reliability and virtually silent
operation.
Other New Features
• Powder coated cabinet, taupe metallic.
• Liftout handles for front access panels.
• Corrosion and stain resistant stainless steel drain pan with extra
slope designed in.
• Factory mounted fi lter drier for trouble free reliability.
• Easy access low profi le horizontal control box.
• Double isolated compressor for quiet and vibration
free operation.
Foil faced insulation in air handling compartment to allow easy
•
cleaning and prevent microfi ber introduction into the air stream.
• Open Service-Friendly Cabinet ( i.e, all components in
compressor section can be serviced from the front).
Copeland Scroll Compressor
There’s a reason 9 out of every 10 scroll compressors installed
are Copeland. With over 15 years of painstaking R & D and rigid
production controls, Copeland is able to build the most reliable,
effi cient and quiet scroll compressors in the world.
The concept of compressing a gas by turning one involute form – or
“scroll” – against another around a common axis is nearly a century
old. It wasn’t until the late 1980s, however that one company –
Residential Products Technical Guide
GT-PG
3
GT-PG (50YE) Series
GT-PG Design Features
The GT-PG Series has abundant features and industry leading
effi ciency.
• Oversized tin-coated, rifl ed tube/lanced aluminum fi n, air to
•
Service Advantages
• Removable panels - 3 for compressor, 2 for air
• Low profi le control box grants easy access to all
• Factory installed liquid line fi lter/drier.
• Brass swivel-type water connections for quick connection and
• Bi-directional thermal expansion valve.
• CXM control features status light with memory for
• Unit Performance Sentinel alerts homeowner of potential
®
HFC-410A zero ozone depletion refrigerant.
stage ratings for heating COPs, cooling EERs with low water
fl ow rates.
ultra high effi ciencies and unsurpassed comfort.
shorter loops.
water at considerable savings.
scroll compressors provide the extremely high effi ciencies
and capacities.
operate at low liquid pressure drop. Convoluted copper (and
optional cupro-nickel) water tube functions effi ciently at low-fl ow
rates and provides freeze-damage resistance.
refrigerant heat exchangers provide high effi ciency at low
face velocity.
Large low RPM blowers with optional variable speed fan motors
provide quiet, effi cient air movement with high static capability.
handling compartment.
internal components.
elimination of wrenches or sealants during installation.
easy diagnostics.
performance issues.
• Circuit breaker protected 75VA control transformer.
• Optional ECM motor includes control board with thermostat
signal diagnostic LEDs, airfl ow display LED (100 CFM per fl ash),
and simplifi ed CFM selection.
• Insulated divider and separate air handling/compressor
compartments permit service testing without air bypass.
• Fan motors have quick attach wiring harness for fast removal.
• Internal dropout blower for easy servicing.
• High and low pressure service ports on refrigerant circuit.
• Accurate refrigerant sensing low temperature protection.
Factory Quality
• All units are built on our Integrated Process Control
Assembly System (IPCS). The IPCS is a unique state of the art
manufacturing system that is designed to assure quality of the
highest standards of any manufacturer in the water-source
industry. Our IPCS system:
- Verifi es that the correct components are being assembled.
- Automatically performs special leak tests on all joints.
- Conducts pressure tests.
- Performs highly detailed run test unparalleled in the
HVAC industry.
- Automatically disables packaging for a “failed” unit.
- Creates computer database for future service analysis and
diagnostics from run test results.
• All units are water run-tested in all modes to insure effi ciency
and reliability.
• Heavy gauge galvanized steel cabinets are epoxy powder coated
for durable and long-lasting fi nish.
• All refrigerant brazing is done in a nitrogen atmosphere.
• All units are deep evacuated to less than 100 microns prior to
refrigerant charging.
• All joints are both helium and halogen leak tested to insure
annual leak rate of less than 1/4 ounce.
• Coaxial heat exchanger, refrigerant suction lines and all water
lines are fully insulated to eliminate condensation problems in low
temperature applications.
• Noise Reduction features include: double isolation mounted
compressors; insulated compressor compartment; interior cabinet
insulation using 1/2” coated glass fi ber and optional variable
speed fan.
• Safety features include: high pressure and loss of charge to
protect the compressor; condensate overfl ow protection; low
temperature protection sensors to safeguard the coaxial heat
exchanger and air coil; hot water high-limit and low compressor
discharge temperature switch provided to shut down the hot
water generator when conditions dictate. Fault lockout enables
emergency heat and prevents compressor operation until
thermostat or circuit breaker has been reset.
Simplifi ed Controls
• CXM solid state control module.
• ‘CFM’ LED displays airfl ow (optional ECM motor).
Foil Faced Insulation In The Blower Section, Fully Insulated
4
Compressor Section
Two Inch Filter Frame With High Performance MERV 11
5
Pleated Air Filter*
Stainless Steel Drain Pan For Long Life
6
7
Unit Performance Sentinel: Automatic Alert System
Lets You Know If The System Is Not Running At Peak
Performance**
Exclusive Dual Level Compressor Vibration Isolation For
8
Ultra Quiet Operation
9
Five Easy, Lift-out Service Access Panels
With Powder Coated Cabinet, Taupe Metallic
* MERV= Minimum Effi ciency Reporting Value as specifi ed by ASHRAE (American
Society of Heating, Refrigerating and Air Conditioning Engineers) standard 52.2.
** When installed with a Bryant Geothermal Residential Thermostat.
2
3
6
1
8
4
7
9
87
Residential Products Technical Guide
Features Puron®
HFC-410A Zero Ozone
Depletion Refrigerant
GT-PG
5
GT-PG (50YE) Series
Unit Model Key
5 0J0 2 4BC311
Prefix
YEV = Puron Vertical Upflow Single-Stage
YEH = Puron Horizontal Single-Stage
YED = Puron Vertical Downflow Single-Stage
Option
JKLeft
L*R*Left
Option
JKLeft
L*R*Left
Option
N
P
W
Y
Z*
B*
S*
E*
* PSC motor not available on size 070
Series
018, 024, 030, 036, 042, 048, 060, 070
Air Flow Configuration
Vertical Upflow YEV
Discharge
Return
Right
Right
Vertical Downflow YED
Discharge
Return
Right
Right
Horizontal YEH
Discharge
Return
Right
Right
Left
Left
Right
Right
Left
Left
1 2 3
Y E V
Unit Size
Top
Top
Top
Top
Down
Down
Down
Down
Left
Back
Right
Back
Left
Back
Right
Back
Filter
2”
2”
2”
2”
Filter
2”
2”
2”
2”
Filter
2”
2”
2”
2”
2”
2”
2”
2”
4 5 67
Motor
ECM
ECM
PSC
PSC
Motor
ECM
ECM
PSC
PSC
Motor
ECM
ECM
ECM
ECM
PSC
PSC
PSC
PSC
9101112
8
Heat Exchanger Options
Without Hot Water Generator
Standard
Whole House Dehumidification
Whole House Dehumidification
w/Hot Water Generator
Controls
C = CXM
D = DXM
Revision Level
1 = 024-070
2 = 018
Voltage
3 = 280-230/60/1
Packaging
1 = Single Pack, Domestic
Coated Air Coil
Copper
Cupro-Nickel
A
B
RF
LM
J
K
GT-PG
6
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
About AHRI/ISO/ASHRAE 13256-1
About AHRI/ISO/ASHRAE 13256-1
AHRI/ASHRAE/ISO 13256-1 (Air-Conditioning and Refrigeration Institute/American Society of Heating, Refrigerating and Air Conditioning
Engineers/International Standards Organization) is a certifi cation standard for water-source heat pumps used in the following applications:
• WLHP (Water Loop Heat Pump – Boiler/Tower)
• GWHP (Ground Water Heat Pump – Open Loop)
• GLHP (Ground Loop Heat Pump – Geothermal)
The directory at http://www.ahrinet.org/ is constantly being updated and immediately available on the Internet. All ratings are submitted by the
manufacturer for certifi cation, and must be approved by AHRI. Therefore, there is a signifi cant difference between AHRI “certifi ed” and AHRI
“rated.” Thirty percent of a manufacturer’s basic models must be tested each year. AHRI selects models at random from stock for testing on
the basis of its evaluation of a participant’s certifi cation data.
Units that fail one or more certifi ed test (90% of declared performance or lower) may be declared defective. If the initial failure is a
performance test, the manufacturer must obsolete all units within the same basic model group or elect to have a second sample tested. If the
second unit fails a performance test, it must be obsoleted, together with all units within the same basic model group. Bryant Geothermal takes
certifi cation seriously. We were recently awarded a certifi cate for consecutive years of no AHRI failures.
Temperatures used in AHRI certifi cation standards are S.I. (Système International – metric) based. For example, typical catalog data for cooling
is shown at 80°F DB/67°F WB [26.7°C DB/19.4°C] entering air temperature, but the AHRI standard for cooling is 80.6°F DB/66.2°F WB
[27°C DB/19°C], since it is based upon whole numbers in degrees Celsius. Water and air temperatures for the standard are shown below.
Test Condition Comparison Table
WLHPGWHPGLHP
Cooling
Entering Air Temperature - DB/WB °F [°C]
Entering Water Temperature - °F [°C]
Fluid Flow Rate
Heating
Entering Air Temperature - DB/WB °F [°C]
Entering Water Temperature - °F [°C]
Fluid Flow Rate
*Flow rate is specifi ed by the manufacturer
80.6/66.2 [27/19]
86 [30]
*
68 [20]
68 [20]
*
80.6/66.2 [27/19]
59 [15]
*
68 [20]
50 [10]
*
80.6/66.2 [27/19]
77 [25]
*
68 [20]
32 [0]
*
Data certifi ed by AHRI include heating/cooling capacities, EER (Energy Effi ciency Ratio – Btuh per Watt) and COP (Btuh per Btuh) at the
various conditions shown above. Pump power correction is calculated to adjust effi ciencies for pumping Watts. Within each model, only one
water fl ow rate is specifi ed for all three groups, and pumping Watts are calculated using the formula below. This additional power is added
onto the existing power consumption.
• Pump power correction = (gpm x 0.0631) x (Press Drop x 2990)/300
Fan power is corrected to zero external static pressure using the equation below. The nominal airfl ow is rated at a specifi c external static
pressure. This effectively reduces the power consumption of the unit and increases cooling capacity but decreases heating capacity.
• Fan Power Correction = (cfm x 0.472) x (esp x 249)/300
Capacities and effi ciencies are calculated using the following equations:
• ISO Cooling Capacity = Cooling Capacity (Btuh) + [Fan Power Correction (Watts) x 3.412]
• ISO EER Effi ciency (Btuh/W) =
ISO Cooling Capacity (Btuh)/[Power Input (Watts) – Fan Power Correction (Watts) + Pump Power Correction (Watts)]
• ISO Heating Capacity = Heating Capacity (Btuh) – [Fan Power Correction (Watts) x 3.412]
• ISO COP Effi ciency (Btuh/Btuh) =
ISO Heating Capacity (Btuh) x 3.412/[Power Input (Watts) - Fan Power Correction (Watts) + Pump Power Correction (Watts)]
Residential Products Technical Guide
GT-PG
7
GT-PG (50YE) Series
AHRI/ISO/ASHRAE/ANSI 13256-1 Performance
ASHRAE/AHRI/ISO 13256-1. English (I-P) Units
Water Loop Heat PumpGround Water Heat PumpGround Loop Heat Pump
Model
018
TS018
TS024
024
030
TS030
TS036
036
042
TS042
TS048
048
060
TS060
TS070
070
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All ratings based upon operation at lower voltage of dual voltage rated models
Water Loop Heat PumpGround Water Heat PumpGround Loop Heat Pump
Model
018
TS018
024
TS024
TS030
036
030
TS036
042
TS042
TS048
048
060
TS060
070
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature
Heating capacities based upon 20°C DB, 15°C WB entering air temperature
All ratings based upon operation at lower voltage of dual voltage rated models
Hot Water Generator capacities (HWC) are based on potable water fl ow rate of 0.4 gpm per nominal equipment ton and 90°F
entering potable water temperature.
CFM = airfl ow, cubic feet/minute
EWT = entering water temperature, ˚F
GPM = water fl ow in US gallons/minute
EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)
HC = air heating capacity, Mbtuh
TC = total cooling capacity, Mbtuh
SC = sensible cooling capacity, Mbtuh
KW = total power unit input, KiloWatts
HR = total heat of rejection, Mbtuh
UPFLOW
HE = total heat of extraction, Mbtuh
HWC = Hot Water Generator (desuperheater) capacity, Mbtuh
WPD = Water coil pressure drop (psi & ft hd)
EER = Energy Effi ciency Ratio = BTU output/Watt input
COP = Coeffi cient of Performance = BTU output/BTU input
LWT = leaving water temperature, °F
LAT = leaving air temperature, °F
LC = latent cooling capacity, Mbtuh
S/T = sensible to total cooling ratio
LEFT RETURN AIR
Piping End
Piping End
Left Return Air
Back Discharge
Piping End
Left Return Air
Side Discharge
Left Return AirRight Return Air
Piping End
Residential Products Technical Guide
RIGHT RETURN AIR
Piping End
Right Return Air
Back Discharge
Piping End
Right Return Air
Side Discharge
Piping End
GT-PG
9
GT-PG (50YE) Series
Air Flow Correction Factors
PSC Fan Motor
Airfl owCoolingHeating
% of
Rated
68.75%
75%
81.25%
87.50%
93.75%
100%
106.25%
112.50%
118.75%
125%
130%
Black area denotes where operation is not recommended.
Total
Capacity
0.94650.80190.84720.96140.9496
0.96020.83500.86960.96750.96170.97401.09360.9425
0.97240.87330.89810.97440.97280.98101.06350.9592
0.98310.91490.93060.98210.98290.98761.03790.9744
0.99230.95780.96530.99060.99200.99401.01670.9880
1.00001.00001.00001.00001.00001.00001.00001.0000
1.00621.03921.03281.01021.00701.00570.98781.0105
1.01091.07331.06171.02111.01301.01120.98001.0194
1.01411.10011.08481.03291.01801.01630.97051.0284
1.01591.11741.09991.04551.02201.02110.96141.0368
1.01611.12291.10501.05621.02441.02470.95541.0430
Sensible
Capacity
S/TPower
Heat of
Rejection
Heating
Capacity
Power
Heat of
Extraction
ECM Fan Motor
Airfl owCoolingHeating
% of
Rated
68.75%
75%
81.25%
87.50%
93.75%
100%
106.25%
112.50%
118.75%
125%
130%
Black area denotes where operation is not recommended.
Total
Capacity
0.94700.82650.87270.93630.9449
0.96190.85930.89330.94550.95870.97001.08220.9410
0.97470.89430.91750.95640.97110.97751.05360.9579
0.98530.93020.94410.96910.98210.98511.03040.9733
0.99380.96590.97190.98370.99180.99251.01250.9874
1.00001.00001.00001.00001.00001.00001.00001.0000
1.00411.03131.02711.01811.00691.00740.99281.0112
1.00601.05841.05221.03811.01231.01480.99091.0210
1.00701.08151.07401.05981.01741.02220.96221.0377
1.00761.09981.09161.08341.02251.02950.86811.0712
1.00831.11101.10181.10351.02711.03540.84561.0844
Sensible
Capacity
S/TPower
Heat of
Rejection
Heating
Capacity
Power
Heat of
Extraction
GT-PG
10
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
Entering Air Correction Factors
Heating
Entering
Air DB°F
45
50
55
60
65
68
70
75
80
Entering
Air WB°F
50
55
60
65
66.2
67
70
75
* = Sensible capacity equals total capacity
AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/66.2°F WB, 1
and Heating - 68°F DB/59°F WB entering air temperature
Performance capacities shown in thousands of Btuhting
Heating - EAT 70°F
Airfl ow
CFM
HCkWHELATCOPHW
Performance Data Selection Notes
For operation in the shaded area when water is used in
lieu of an anti-freeze solution, the LWT (Leaving Water
Temperature) must be calculated. Flow must be maintained
to a level such that the LWT is maintained above 40°F
[4.4°C] when the JW3 jumper is not clipped (see example
below). Otherwise, appropriate levels of a proper anti-freeze
should be used in systems with leaving water temperatures
of 40°F or below and the JW3 jumper should be clipped.
This is due to the potential of the refrigerant temperature
being as low as 32°F [0°C] with 40°F [4.4°C] LWT, which may
lead to a nuisance cutout due to the activation of the Low
Temperature Protection. JW3 should never be clipped for
standard range equipment or systems without antifreeze.
Example:
At 50°F EWT (Entering Water Temperature) and 1.5 gpm/
ton, a 3 ton unit has a HE of 22,500 Btuh. To calculate LWT,
rearrange the formula for HE as follows:
HE = TD x GPM x 500, where HE = Heat of Extraction (Btuh);
TD = temperature difference (EWT - LWT) and GPM = U.S.
Gallons per Minute.
TD = HE/(GPM x 500)
TD = 22,500/(4.5 x 500)
TD = 10°F
LWT = EWT - TD
LWT = 50 - 10 = 40°F
In this example, as long as the EWT does not fall below 50°F, the system will operate as designed. For EWTs below 50°F,
higher fl ow rates will be required (open loop systems, for example, require at least 2 gpm/ton when EWT is below 50°F).
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
All units have compressor mountings, TXV expansion devices, and 1/2” [12.7mm] & 3/4” [19.1mm] electrical knockouts.
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
Dimensions — Vertical Upfl ow GT-PG (50YE) Series
Vertical
Upfl ow
Model
018
024 -
030incm
036
042 -
048incm
060 -
070incm
Vertical
Upfl ow
Model
018
024 -
030
036
042 -
048
060 -
070
Overall Cabinet
A
WidthBDepthCHeight
in
22.4
cm
56.8
22.4
56.8
in
25.4
cm
64.5
25.4
64.5
25.4
64.5
12345
D
In
in
cm
in
cm
in
cm
in
cm
in
cm
2.1
5.2
2.1
5.2
3.4
8.6
3.4
8.6
3.4
8.6
25.6
65.1
25.6
65.1
30.6
77.8
30.6
77.8
30.6
77.8
E
Out
10.0
25.4
10.0
25.4
10.8
27.5
10.8
27.5
10.8
27.5
44.6
123.2
48.5
123.2
50.5
128.3
54.5
138.4
58.5
148.6
Water Connections
F
HWG
IN
13.9
35.2
13.9
35.2
15.6
39.7
15.6
39.7
15.6
39.7
G
HWG
Out
16.9
42.9
16.9
42.9
18.9
47.9
18.9
47.9
18.9
47.9
H
Condensate
7.8
19.8
7.8
19.7
7.8
19.7
7.8
19.7
7.8
19.7
Loop
Water
FPT
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
HWG
FPT
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
Electrical Knockouts
018
024 -
030
036
042 -
048
060 -
070
Vertical
Upfl ow
Model
in
cm
in
cm
in
cm
in
cm
in
cm
J
1/2”
Low
Voltage
3.6
9.2
3.6
9.2
3.6
9.2
3.6
9.2
3.6
9.2
K
1/2”
External
Pump
6.1
15.6
6.1
15.6
6.1
15.6
6.1
15.6
6.1
15.6
L
3/4”
Power
Supply
8.6
21.9
8.6
21.9
8.6
21.9
8.6
21.9
8.6
21.9
Condensate is 3/4” PVC female glue socket and is switchable from front to side.
Unit shipped with deluxe duct collar/fi lter rack extending from unit 3” [7.6cm] and is suitable for duct connection.
Discharge fl ange is fi eld installed.
Residential Products Technical Guide
GT-PG
29
GT-PG (50YE) Series
Dimensions — Vertical Upfl ow GT-PG (50YE) Series
Vertical
Upfl ow
Model
Return
018
024 -
030
036
042 -
048
060 -
070
in
cm
in
cm
in
cm
in
cm
in
cm
CAP=Control Access Panel
CSP=Compressor Service Panel
BSP=Blower Service Panel
ASP=Alternate Service Panel
Legend
P
Duct Flange Installed (+/- 0.20 in, +/- 5.1mm)
Discharge Connection
M
Left
7.2
18.3
7.2
18.3
6.4
16.1
6.4
16.1
6.4
16.1
N
5.8
14.8
5.8
14.8
6.3
16.0
6.3
16.0
6.3
16.0
N
O
Supply
Width
14.0
35.6
14.0
35.6
18.0
45.7
18.0
45.7
18.0
45.7
N
P
Supply
Depth
14.0
35.6
14.0
35.6
18.0
45.7
18.0
45.7
18.0
45.7
B
P
Q
Right
Return
4.9
12.4
4.9
12.4
5.3
13.5
5.3
13.5
5.3
13.5
Return Connection
Standard Deluxe Filter Rack
(+/- 0.20 in, +/- 5.1mm)
S
R
1.7
4.3
1.7
4.3
1.7
4.3
1.7
4.3
1.7
4.3
Deluxe Filter Bracket
Air Coil
Return
Depth
22.2
56.4
22.2
56.4
27.2
69.1
27.2
69.1
27.2
69.1
Return
Height
22.2
66.5
26.2
66.5
26.2
66.5
30.2
76.7
34.2
86.9
Field Installed
Discharge Flange
BSP
T
U
1.7
4.3
1.7
4.3
1.7
4.3
1.7
4.3
1.7
4.3
Access Panels
ASP
GT-PG
30
Front
Front
O
Q
Top View-Right Return
U
T
C
Right Return Right View
- Filter Rack Knife Edge
Air Coil Side
S
Frame Depth
2 & 1 / 8" [54.0mm]
Flange Depth
3 / 8" [9.5mm]
R
Air Coil
Back
Back
Air Coil Side
Top View-Left Return
R
U
T
C
Left Return Left View
- Filter Rack Knife Edge
Bryant: Whatever it Takes.
S
CSPASP
1.18 [30.0 mm]
Front
O
M
Front
A
Air Coil
Power Supply
3 / 4" [19.1mm]
HV Knockout
1 / 2" [12.7mm]
Knockout
Low Voltage
1 / 2" [12.7mm]
LV Knockout
CSP
2' (61cm)
Service
CSP
2' (61cm)
Optional
Service
Access
Left Rtn
(right
Opposite)
1.00 [25.4 mm]
1.68 [42.7 mm]
Condensate - 3 / 4" Glue
(PVC Socket)
(Opposite side of air coil)
G
F
E
D
Rev.: 08/9/12B
Isometric
View
CAP
L
ASP
4
3
2
5
1
CAP
1.63
[41.4 mm]
K
JH
Front-View
Bryant Geother mal Heat Pump Systems
Dimensions — Vertical Downfl ow GT-PG (50YE) Series
Downfl ow
018
024 -
030
036
042 -
048
060 -
070
Downfl ow
018
024 -
030
036
042 -
048
060 -
070
Vertical
Model
Vertical
Model
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
Overall Cabinet
A
WidthBDepthCHeight
in
in
in
in
in
in
in
in
in
in
22.4
56.8
22.4
56.8
25.4
64.5
25.4
64.5
25.4
64.5
12345
D
In
17.2
43.7
17.2
43.7
17.9
45.5
17.9
45.5
17.9
45.5
25.6
65.1
25.6
65.1
30.6
77.8
30.6
77.8
30.6
77.8
E
Out
9.3
23.6
9.3
23.6
10.5
26.7
10.5
26.7
10.5
26.7
48.6
123.4
52.5
133.4
54.5
138.4
58.5
148.6
62.5
158.8
Water Connections
F
HWG
IN
5.4
13.7
5.4
13.7
5.7
14.5
5.7
14.5
5.7
14.5
G
HWG
Out
2.4
6.1
2.4
6.1
2.4
6.1
2.4
6.1
2.4
6.1
H
Condensate
3.6
9.2
3.6
9.2
3.6
9.2
3.6
9.2
3.6
9.2
Loop
Water
FPT
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
HWG
FPT
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
Electrical Knockouts
Downfl ow
018
024 -
030
036
042 -
048
060 -
070
Vertical
Model
in
cm
in
cm
in
cm
in
cm
in
cm
J
1/2”
Low
Voltage
15.7
39.9
15.7
39.9
17.7
45.0
17.7
45.0
17.7
45.0
K
1/2”
External
Pump
13.2
33.5
13.2
33.5
15.2
38.6
15.2
38.6
15.2
38.6
L
3/4”
Power
Supply
10.7
27.2
10.7
27.2
12.7
32.3
12.7
32.3
12.7
32.3
Condensate is 3/4” PVC female glue socket and is switchable from front to side.
Unit shipped with deluxe duct collar/fi lter rack extending from unit 3” [7.6cm] and is suitable for duct connection.
Downfl ow unit does not have discharge fl ange, and is rated for zero clearance installation.
Residential Products Technical Guide
GT-PG
31
GT-PG (50YE) Series
Dimensions — Vertical Downfl ow GT-PG (50YE) Series
Vertical
Downfl ow
Model
018
024 -
030
036
042 -
048
060 -
070
Front
in
cm
in
cm
in
cm
in
cm
in
cm
O
Opening
Q
Air Coil Side
Right Return Discharge
Floor Foot Print
U
P
Blower
B
Duct Flange Installed (+/- 0.20 in, +/- 5.1mm)
Discharge Connection
M
Left
Return
6.7
17.1
6.7
17.1
7.4
18.7
7.4
18.7
7.4
18.7
N
ASP
N
8.4
21.4
8.4
21.4
9.0
22.9
9.0
22.9
9.0
22.9
A
Frame Depth
2 & 1 / 8" [54.0mm]
Flange Depth
3 / 8" [9.5mm]
O
Supply
Width
9.9
25.3
9.9
25.3
13.1
33.3
13.1
33.3
13.1
33.3
P
Supply
Depth
9.1
23.0
9.1
23.0
12.9
32.7
12.9
32.7
12.9
32.7
CAP=Control Access Panel
CSP=Compressor Service Panel
BSP=Blower Service Panel
ASP=Alternate Service Panel
N
O
A
U
Opening
M
Air Coil Side
Left Return Discharge
Floor Foot Print
1.1 [27.9mm]
Return
Legend
P
Blower
B
CSP
Q
Right
1.5
3.9
1.5
3.9
1.6
4.1
1.6
4.1
1.6
4.1
Return Connection
Standard Deluxe Filter Rack
(+/- 0.20 in, +/- 5.1mm)
S
R
Return
Depth
1.7
4.3
1.7
4.3
1.7
4.3
1.7
4.3
1.7
4.3
2’ [61cm] Optional Service
Front
22.2
56.4
22.2
56.4
27.2
69.1
27.2
69.1
27.2
69.1
CSP
Access Right Rtn
(left opposite)
2’ [61cm] Service
Access
Power Supply
3 / 4” [19.1mm]
HV Knockout
1 / 2” [12.7mm]
Knockout
Low Voltage
1 / 2” [12.7mm]
LV Knockout
ASP
CSP
T
Return
Height
22.2
56.4
26.2
66.5
26.2
66.5
30.2
76.7
34.2
86.9
Condensate 3/4”
1.6 [40.6mm]
21.9
55.6
21.9
55.6
23.9
60.7
23.9
60.7
23.9
60.7
Deluxe Filter Bracket
CAP
BSP
Glue
Isometric View
L
K
J
CAP
U
ASP
1.6 [40.6mm]
G
4
3
2
1
F
E
D
GT-PG
32
T
Front
Right Return Right View
- Filter Rack Knife Edge
Air Coil
T
C
Back
S
R
Back
R
Left Return Left View
- Filter Rack Knife Edge
S
Air Coil
Front
Condensate
3 / 4” Glue
(Right Return)
H
BSP
Condensate
3 / 4” Glue
5
Front-View
(Left Return)
5
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
Dimensions — Horizontal GT-PG (50YE) Series
Horizontal
018
024 -
030
036
042 -
048
060 -
070
Horizontal
018
024 -
030
036
042 -
048
060 -
070
Model
Model
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
Overall Cabinet
A
WidthBDepthCHeight
in
in
in
in
in
in
in
in
in
in
22.4
56.8
22.4
56.8
25.4
64.5
25.4
64.5
25.4
64.5
12345
D
In
2.1
5.2
2.1
5.2
3.4
8.6
3.4
8.6
3.4
8.6
62.2
158.0
62.2
158.0
71.2
180.8
76.2
193.5
81.2
206.2
E
Out
10.0
25.4
10.0
25.4
10.8
27.5
10.8
27.5
10.8
27.5
19.3
48.9
19.3
48.9
21.3
54.0
21.3
54.0
21.3
54.0
Water Connections
F
HWG
IN
13.9
35.2
13.9
35.2
15.6
39.7
15.6
39.7
15.6
39.7
G
HWG
Out
16.9
42.9
16.9
42.9
18.9
47.9
18.9
47.9
18.9
47.9
H
Condensate
0.6
1.5
0.6
1.5
0.6
1.5
0.6
1.5
0.6
1.5
Loop
Water
FPT
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
HWG
FPT
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
1”
Swivel
Electrical Knockouts
Horizontal
018
024 -
030
036
042 -
048
060 -
070
Model
cm
cm
cm
cm
cm
J
1/2”
Low
Voltage
in
in
in
in
in
3.6
9.2
3.6
9.2
3.6
9.2
3.6
9.2
3.6
9.2
K
1/2”
External
Pump
6.1
15.6
6.1
15.6
6.1
15.6
6.1
15.6
6.1
15.6
L
3/4”
Power
Supply
8.6
21.9
8.6
21.9
8.6
21.9
8.6
21.9
8.6
21.9
Condensate is 3/4” FPT.
Unit shipped with deluxe duct collar/fi lter rack extending from unit 3” [7.6cm] and is suitable for duct connection.
Discharge fl ange and hanger brackets are factory installed.
Residential Products Technical Guide
GT-PG
33
GT-PG (50YE) Series
g
Dimensions — Horizontal GT-PG (50YE) Series
Return Connection
Standard Deluxe Filter Rack
(+/- 0.20 in, +/- 5.1mm)
T
Return
Height
16.2
41.0
16.2
41.0
18.2
46.1
18.2
46.1
18.2
46.1
Horizontal
018
024 -
030
036
042 -
048
060 -
070
Model
cm
cm
cm
cm
cm
Duct Flange Installed (+/- 0.20 in, +/- 5.1mm)
1Discharge Connection
P
MNOSupply
Height
in
in
in
in
in
5.0
12.7
3.6
9.3
*3.1
7.9
3.1
7.9
3.1
7.9
6.8
17.3
2.0
5.1
1.2
3.1
1.2
3.1
1.2
3.1
12.5
31.8
12.5
31.8
19.0
48.3
19.0
48.3
19.0
48.3
Supply
Width
15.5
39.4
15.5
39.4
17.5
44.5
17.5
44.5
17.5
44.5
QRSReturn
Width
5.0
12.7
3.6
9.2
*3.1
7.9
3.1
7.9
3.1
7.9
2.1
5.3
2.0
5.2
1.0
2.6
1.0
2.6
1.0
2.6
33.8
85.8
33.8
85.8
34.8
88.3
39.8
101.0
44.8
113.7
*For units with modulating reheat option this dimension is 2.9” (7.4 cm).
1Discharge connection will change when using the accessory auxiliary electric heat package. Refer to the heater IOM for details.
Legend
L
K
J
Front-View
CAP
A
D
F
E
Right Return
[82.6mm]
G
H
Condensate
3 / 4” FPT
5
Back
Discharge
1.6 [40.6mm]1.6 [40.6mm]
4
3
2
1
2’ [61cm] Service
Access
LEFT RETURNRIGHT RETURN
CSP
Front
ASP
Straight
Discharge
2’ [61cm] optional
service access
Left Return
Back
Discharge
3.25
[82.6mm]3.25
H
5
Condensate
3 / 4” FPT
CAP=Control Access Panel
CSP=Compressor Service Panel
BSP=Blower Service Panel
ASP=Alternate Service Panel
The ECM fan is c o n t r o lled by an interface board that
converts thermostat inputs and fi eld selectable CFM
settings to signal s u s ed by the ECM motor co nt r o l l er.
Units manu f a c tured before J u l y 2005 have vers i o n I ( P/N
69243707). Units manufa ctured between July 2005 and
May 11, 2009 have versi o n II ( P/N 17B0019N01). Fan
speeds are selec te d w i t h ju m pers for version I or vi a a
nine positi on DIP switch for ver s ion II and III. To take
full advanta g e of t h e EC M m oto r fe a tures, a multi-stage
thermostat should be u s e d (2-st a g e h e a t/2-stage co ol or
3-stage h e a t/2-stage co o l ).
HFC-410A packaged unit s bu ilt a fter May 11, 2009 have
a ECM controll e r s ver s i on III ( P/N 17B0034N01). This
controlle r i nc lu de s l og i c an d a re l ay to con tro l th e HWG
functions.
Note: Power must be off to the unit for at least three
seconds before the ECM motor will recognize a speed
change. The motor will recognize a change in the CFM
Adjust or dehumidifi cation mode settings while the unit
is powered.
There are four different airfl ow settings from lowest airfl ow
rate (speed tap 1) to the highest airfl ow rate (speed tap 4).
The charts below indicate settings for both versions of the
ECM interface board, followed by detailed information for
each setting.
Cooling Settings: The cooling setting determines the
cooling (normal) CFM for all units with ECM motor.
Cooling (normal) setting is used when the unit is not in
dehumidifi cation mode. This setting also determines the
heating CFM for GT-G (50YC) units. Tap 1 is the lowest CFM
setting, while tap 4 is the highest CFM setting. To avoid air
coil freeze-up, tap 1 may not be used if the dehumidifi cation
mode is selected. Consult submittal data or specifi cations
catalog for the specifi c unit series and model to correlate
speed tap setting to airfl ow in CFM.
H
eating Settings
heating CFM for GT-PX (50YD) and GT-PG
This setting is not used for
the lowest CFM setting, while tap 4 is the highest CFM
setting. Consult submittal data or specifi cations catalog for
the specifi c unit series and model to correlate speed tap
setting to airfl ow in CFM.
: The heating setting determines the
(50YE) units.
GT-G (50YC)
units. Tap 1 is
or heating setting will be used. A “G” (fan) signal must be
present from the thermostat for electric heat to operate.
Consult the submittal data or specifi cations catalog for the
specifi c unit series and model to correlate speed tap setting
to airfl ow in CFM.
CFM Adjust Settings: The CFM adjust setting allows
four selections. The NORM setting is the factory default
position. The + or – settings adjust the airfl ow by +/- 15%.
The +/- settings are used to “fi ne tune” airfl ow adjustments.
The TEST setting runs the ECM motor at 70% torque, which
causes the motor to operate like a standard PSC motor, and
disables the CFM counter.
Dehumidifi cation Mode Settings: The dehumidifi cation
mode setting provides fi eld selection of humidity control.
When operating in the normal mode, the cooling airfl ow
settings are determined by the cooling tap setting above.
When dehumidifi cation is enabled there is a reduction in
airfl ow in cooling to increase the moisture removal of the
heat pump. Consult submittal data or specifi cations catalog
for the specifi c unit series and model to correlate speed
tap to airfl ow in CFM. The dehumidifi cation mode can be
enabled in two ways.
1. Constant Dehumidifi cation Mode: When the
dehumidifi cation mode is selected (via DIP switch or
jumper setting), the ECM motor will operate with a
multiplier applied to the cooling CFM settings (approx.
20-25% lower airfl ow). Any time the unit is running in
the cooling mode, it will operate at the lower airfl ow
to improve latent capacity. The “DEHUM” LED will be
illuminated at all times. Heating airfl ow is not affected.
NOTE: Do not select dehumidifi cation mode if cooling
setting is tap 1.
2. Automatic (Humidistat-controlled) Dehumidifi cation
Mode: When the dehumidifi cation mode is selected
(via DIP switch or jumper setting) AND a humidistat is
connected to terminal DH (version II) or HUM (version
I), the cooling airfl ow will only be reduced when the
humidistat senses that additional dehumidifi cation is
required. The DH (or HUM) terminal is reverse logic.
Therefore, a humidistat (not dehumidistat) is required.
The “DEHUM” LED will be illuminated only when
the humidistat is calling for dehumidifi cation mode.
Heating airfl ow is not affected. NOTE: Do not select
dehumidifi cation mode if cooling setting is tap 1.
Auxiliary/Emergency Heat Settings: The auxiliary/
emergency heat setting determines the CFM when the unit
is in auxiliary heat or emergency heat mode. This setting
is used for residential units with internal electric heat.
When auxiliary electric heat is energized (i.e. compressor
and electric heat), the greater of the auxiliary/emergency
See ECM control section for details on setting taps.
Bold numbers indicate factory settings.
During Auxiliary operation the CFM will run at the higher of the Heating (Delay jumper) or AUX settings.
Airfl ow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidifi cation mode if HP CFM is on setting 1.
All units AHRI/ISO/ASHRAE 13256-1 rated HP CFM Setting 3.
Black areas denote ESP where operation is not recommended.
Units factory shipped on medium speed. Other speeds require fi eld selection.
All airfl ow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Airfl ow (cfm) at External Static Pressure (in. wg)
GT-PG
42
Bryant: Whatever it Takes.
Auxiliary Heat Ratings
Bryant Geother mal Heat Pump Systems
Auxiliary Electric Heat
Auxiliary
Electric
Heat Model
AGM4A
AGM5A
AGM8A
AGM10A
AGL4A
AGL10A
AGL15A
AGL20A
Dotted area denotes compatibility
Note: Horizontal units rated for zero clearance unit and 1” clearance for the fi rst three feet of duct,
Vertical units rated for zero clearance for both unit and duct.
The water source heating/cooling units shall be vertical upfl ow air
discharge. Units shall be AHRI/ISO/ASHRAE 13256-1 (groundsource closed-loop) per for mance cer ti fi ed and listed by a nationally
recognized safety-testing lab o ra to ry or agency. Each unit shall be
water run-tested at the factory. Each unit shall be pallet mounted and
shipped with appropriate protective packaging to help avoid damage
in transportation. The units shall be war rant ed by the man u fac tur er
against defects in materials and workmanship for a period of 10 years
on all parts, and 10 years on the compressor and refrigerant circuit
parts with a service labor allowance for fi ve years on refrigeration
components and two years on other parts. An optional extended
war ran ty is available for the GT-PG Series units, which increases the
labor allowances to 10 years on all parts. The water source units shall
be de signed to operate with entering fl uid tem per a ture between
20°F and 120°F.
Casing & Cabinet
The cabinet shall be fabricated from heavy-gauge galvanized steel and
painted with an epoxy powder coating. The interior shall be insulated
with 1/2" thick, multi-density, coated glass fi ber. Insulation in the air
handler section shall be foil backed for ease of cleaning. Two (vertical)
or one (horizontal) blower compartment and three compressor
compartment access panels shall be pro vid ed and shall be re mov able
with supply and return ductwork in place. The internal component
layout shall provide for major service with the unit in-place for
re strict ed access installations.
A duct collar (Field installed) shall be provided on the supply air
opening. 2" high effi ciency MERV11 pleated fi lters shall be provided
with each unit. Units shall have fi lter frames. The units shall have an
insulated divider panel between the air handling section and the
com pres sor section to minimize the transmission of compressor
noise, and to permit op er a tion al service testing without air bypass.
Units shall be supplied with left or right air inlet.
Refrigerant Circuit
All units shall contain Puron
employing a hermetic motor-com pres sor, bidirectional thermal
expansion valve, fi nned tube tin plated air-to-refrigerant heat
exchanger, reversing valve, coaxial tube water-to-refrigerant heat
exchanger and service ports. An optional Hot Water Generator
(desuperheater) coil shall be provided.
Compressors shall be Copeland scroll type designed for heat pump
duty and mounted on dual level compressor vibration isolation.
Compressor motors shall be single phase PSC with internal over load
protection. A factory installed bidirectional fi lter drier shall be provided
on all models. The fi nned tube coil shall be sized for low-face velocity
and constructed of lanced aluminum fi ns bonded to rifl ed copper tubes
in a staggered pattern not less than three rows deep. Entire air coil
surface shall be tin-coated for corrosion protection.
The coaxial water-to-refrigerant heat exchangers shall be designed
for close approach temperatures and be con struct ed of a convoluted
copper (optional cu pro-n ick el) inner tube and a steel outer tube. The
thermal expansion valves shall provide proper superheat over the
entire fl uid temperature range with minimal “hunting”. The valve shall
operate bi-directionally without the use of check valves.
®
(HFC-410A) sealed re frig er ant circuit
The water-to-re frig er ant heat exchanger and refrigerant
suction lines shall be insulated to prevent condensation at low liquid
tem per a tures.
Fan Motor and Blower
The fan shall be a direct drive centrifugal type with a dynamically
balanced wheel. The wheel and housing shall be designed for quiet,
low outlet velocity operation. The fan housing shall be of galvanized
steel construction and shall be re mov able from the unit without
dis con nect ing the supply air ductwork for servicing of the fan motor.
The fan motor shall be of 3-speed per ma nent ly split ca pac i tor
(PSC) type. The fan motor shall be high ef fi cien cy and provide high
static capability, and shall include three on-motor selectable air fl ow
options. An optional variable speed electronically commutated
(ECM) fan motor is available with permanently lubricated ball
bearing con struc tion, and it has no less than four op er a tion al speeds
online. The fan motor shall be isolated from the housing by rubber
grommets. The motor shall be permanently lu bri cat ed and have
thermal overload protection.
Electrical
CXM Control - A microprocessor-based compressor controller
shall be provided to monitor and control unit operation. The control
shall provide com pres sor and electric heater sequencing, high and
low pressure monitoring, fi eld selectable water and air coil low
temperature protection sensing, condensate overfl ow sensing, over/
under voltage monitoring, and unit performance sentinel (UPS). The
control shall also provide for water valve connection, a test mode,
short cycle protection, random start-up, as well as fault LED, fault
mem o ry, and intelligent fault retry.
The control shall employ quick attach harness as sem blies for low
voltage connections to the control board to aid in troubleshooting
or replacement. An integral terminal block with screw ter mi nals shall
be provided on the control for all fi eld low voltage connections. A
circuit breaker protected 75VA transformer shall be employed. Line
voltage box lugs shall be provided for unit wiring. Units shall have
knockouts for entrance of low and line voltage wiring. The fan motor
and control box shall be harness plug-connected for easy removal.
Residential models shall have a dual circut-breaker protected power
block for the connection of external fl ow controller pump module.
Piping
Supply and return water connections, as well as Hot Water
Generator (desuperheater) connections shall be 1" FPT brass swivel
fi ttings which provide a union and eliminate the need for pipe
wrenches and sealants when making fi eld con nec tions. A thread by
sweat fi tting shall be provided for connection to the water heating.
All water piping shall be in su lat ed to prevent condensation at low
liquid tem per a tures.
The condensate connection shall be a 3/4" PVC glue (socket) with
internal-trap (Vertical Models).
GT-PG
44
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
Accessories & Warranty
Accessories & Options
Whole House Dehumidifi cation
An optional internal whole house dehumidifi er shall be factory
installed, which allo ws the unit to operate in one of three
modes, heating, cooling, or dehumidifi cation. Operation must include
modulating controls to provide neutral air (72°F) regardless of entering
water temperature. Requires ATP32U04 thermostat or separate
humidistat. See the Whole House Dehumidifi cation Installation Guide/
Application Manual for more details and unit availability.
Variable Speed ECM Fan Motor
An optional soft-starting, high effi ciency, variable speed fan motor
shall be provided with multiple fan speeds and dehumidifi cation
mode to improve comfort and effi ciency .
Hot Water Generator
An optional insulated heat reclaiming desuperheater coil of vented
double-wall copper construction suitable for potable water shall be
pro vid ed. The coil and hot water circulating pump shall be factory
mounted inside the unit. A high limit and low compressor discharge
line temperature switch shall be pro vid ed to disable the pump when
these conditions occur.
Cupro-Nickel Heat Exchanger
An optional corrosion resistant CuNi coaxial heat exchanger shall be
factory in stalled in lieu of standard copper construction.
Warranty Information
The 2010 standard warranty applies to units ordered on or after
July 1, 2010. See Bryant’s 2010 Limited Express Residential Warranty
Certifi cate CA234 for specifi c coverage and limitation.
Bryant residential class heat pumps are backed by a ten-year limited
warranty on all unit parts, including the following accessories when
installed with Bryant units: Flow Controllers & Electric Heaters.
Bryant goes even further to back up its commitment to quality
by including a service labor allowance for the fi rst fi ve years on
refrigeration circuit components and two years on all other parts,
auxiliary heaters and geothermal pumping modules.
The Optional Extended Factory Service Labor Allowance Warranty
offers additional length of term protection to the consumer by
offsetting service labor costs for 10 years.
To order this warranty, contact your Bryant distributor. This coverage
must be purchased within 90 days of unit installation. See Limited
Express Extended Labor Warranty Certifi cate CA235 for details.
Thermostat (fi eld installed)
A multistage auto-changeover electronic digital thermostat shall be
provided. The thermostat shall offer 3 heating and 2 cooling stages
with precise temperature control. An OFF-HEAT-AUTO-COOLEMERG system switch, OFF-AUTO fan switch, and indicating LED’s
shall be provided. The thermostat shall read out in °F or °C. An
optional remote indoor sensor and outdoor sensor shall be available
on some models.
Flow Controller (fi eld installed)
A self-contained module shall provide all fl uid pumping, fi ll and
connection requirements for ground-source closed-loop systems up
to 20 GPM. The Flow Controller shall provide 1" pump isolation
valves and 3-way service valves. Pump heads shall be removable
from the volute for easy replacement. The Flow Controller shall
be enclosed in a polystyrene case and fully insulated with urethane
foam to prevent condensation. The Flow Controller shall have a
5-year warranty on all parts.
Auxiliary Heater (fi eld installed)
An internal, fi eld-installed electric heater shall provide supplemental
and/or emergency heating capability when used with the three
stage heating thermostat. (Heater is externally mounted on
horizontal units).
Hose Connection Kit (fi eld installed)
An accessory hose kit shall provide 150psi 1” rubber hose with
brass fi ttings equipped with service pressure/temperature ports for
connection between the unit and Flow Controller.
Residential Products Technical Guide
GT-PG
45
GT-PG (50YE) Series
Notes
GT-PG
46
Bryant: Whatever it Takes.
Bryant Geother mal Heat Pump Systems
Notes
Residential Products Technical Guide
GT-PG
47
GT-PG (50YE) Series
Revision History
DatePage #Description
10 June, 1338Updated Unit Wiring Diagram
8 May, 13AllPages Re-numbered
4 Jan., 12VariousDeleted references to 070 Model with PSC
28 Sept., 10154ECM Electrical Data Updated
28 Sept., 10153Note Added for Electric Heat
25 Aug., 10153Horizontal units supply air dimension M and Q updated
21 July, 10
14 July, 10VariousCompressor isolation upgrade from Springs to grommets
01 July, 10VariousWarranty, Paint, Nomenclature Updates
04 June, 10153Dim. M & Q Changed
01 June, 10VariousWarranty, Tin-Plated Coils, Paint, Nomenclature Updates
02 June, 09AllRemoved R22 Units and Related Data
01 Jan, 09AllReformatted Document Size
03 Mar, 08163Updated Specifi cations
03 Mar, 08150Updated Downfl ow Dimensional Data
03 Mar, 08VariousUpdated Size 018 Data
05 Mar, 07154Added New Notes to Electrical Data
05 Mar, 07163Removed Incorrect Model From Table
05 Mar, 07152Updated Horizontal Dimensional Data
01 Oct, 08AllFirst Published
Wiring Diagram
Pages
Wire Diagram revision: water-side high pressure switches
added
GT-PG
48
Bryant: Whatever it Takes.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.