Information in these installation instructions pertains only to GT
series units.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety--alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors.Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
1
!
!
2
3
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury
or equipment damage.
PuronR refrigerant systems operate at higher pressures than
standard R --22 systems. Do not use R-- 22 service equipment
or components on PuronR refrigerant equipment.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
WARNING
Fig. 1 -- Standard Package
A14032
1. GT Series Water-- To Air Heat Pump
2. Installation and Owner’s Manual
3. Hanging Bracket Kit (HZ unit only)
2
APPLICATION CONSIDERATIONS
Geothermal Systems
Closed loop and pond applications require specialized design
knowledge. No attempt at these installations should be made unless
the dealer has received specialized training. Anti-- freeze solutions
are utilized when low evaporating conditions are expected to occur.
Refer to the Flow Center installation manuals for more specific
instructions. (See Fig. 2)
(1) Line Voltage Disconnect (unit)(8) Ground Loop Connection Kit
(3) Low Voltage Control Connection(10) Polyethylene with Insulation
(4) Line Voltage Connection(11) Line Voltage Disconnect (electric heater)
(5) P/T Ports
(6) Vibration Pad
(7) Condensate Drain Connection
Fig. 2 -- Example Geothermal System Setup
Diagram shows typical
installation and is for
illustration purposes
only. Ensure access to
Heat Pump is not
restricted.
A14132
3
Well Water Systems
IMPORTANT: Table 1 must be consulted for water quality
requirements when using open loop systems. A water sample must
be obtained and tested, with the results compared to the table.
Scaling potential should be assessed using the pH/Calcium
hardness method. If the pH is <7.5 and the calcium hardness is
l<100 ppm, the potential for scaling is low. For numbers out of the
range listed, a monitoring plan must be implemented due to
probable scaling.
Other potential issues such as iron fouling, corrosion, erosion and
clogging must be considered. Careful attention to water conditions
must be exercised when considering a well water application.
Failure to perform water testing and/or applying a geothermal heat
pump to a water supply that does not fall within the accepted
quality parameters will be considered a mis--application of the unit
and resulting heat exchanger failures will not be covered under
warranty. Where a geothermal system will be used with adverse
water conditions, a suitable plate--frame heat exchanger MUST be
used to isolate the well water from the geothermal unit.
Proper testing is required to assure the well water quality is suitable
for use with water source equipment.
In conditions anticipating moderate scale formation or in brackish
water, a cupronickel heat exchanger is recommended. Copper is
adequate for ground water that is not high in mineral content.
In well water applications, water pressure must always be
maintained in the heat exchanger. This can be accomplished with
either a control valve or a bladder type expansion tank.
When using a single water well to supply both domestic water and
the heat pump, care must be taken to insure that the well can
provide sufficient flow for both.
In well water applications, a slow closing solenoid valve must be
used to prevent water hammer (hammering or stuttering sound in
the pipeline). Solenoid valves should be connected across Y1 and
C1 on the thermostat interface board for all. Make sure that the VA
draw of the valve does not exceed the contact rating of the
thermostat. (See Fig. 3)
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Discharge air configuration change is not possible on Heat
Pumps equipped with Electric Heat Option.
CAUTION
1
13
12
2
11
6
5
9
7
4
(1) Flex Duct Connection(8) Hose Kits (optional)
(2) Low Voltage Control Connection(9) Pressure Tank (optional)
(3) Vibration Pad(10) P/T Ports (optional)
(4) Ball Valves(11) Line Voltage Connection
(5) Solenoid Valve Slow Closing(12) Electric Heater Line Voltage Disconnect
(6) Condensate Drain Connection(13) Unit Line Voltage Disconnect
(7) Drain Valves
Fig. 3 -- Example Well Water System Setup
10
3
Typical Installation shown for
8
illustration purposes only.
A14130
4
Table 1 – Water Quality Requirements for Open--Loop Geothermal Heat Pump System
Water Quality ParameterHX MaterialClosed RecirculatingOpen Loop and Recirculating Well
Scaling Potential - Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below:
pH/Calcium Hardness
Method
Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)
Scaling indexes should be calculated at 150°F for direct use and HWG applications, and at 90°F for indirect HX use.
A monitoring plan should be implemented.
Ryznar Stability IndexAll--
Langelier Saturation IndexAll--
Iron Fouling
Iron Fe² (Ferrous)
(Bacterial Iron Potential)
Iron FoulingAll--
Corrosion Prevention
pHAll
Hydrogen Sulfide (H2S)All--
Ammonia ion as hydroxide,
chloride, nitrate and sulfate
compounds
Maximum Chloride Levels
Erosion and Clogging
Particulate Size and
Erosion
NOTES:
SClosed recirculating system is identified by a closed pressurized piping system.
SRecirculating open wells should observe the open recirculating design considerations.
SNR - application not recommended
S"—" No design Maximum
All--pH <7.5 and Ca Hardness <100ppm
6.0 - 7.5
If > 7.5 minimize steel pipe use
-0.5 to +0.5
If <-0.5 minimize steel pipe use.
Based upon 150°F HWG and Direct well,
84°F Indirect Well HX
<0.2 ppm (Ferrous)
All--
If Fe²* (ferrous) >0.2 ppm with pH 6-8, O2<5 ppm check
for iron bacteria
<0.5 ppm of Oxygen
Above this level deposition will occur
6-8.5
Monitor/treat as needed
Minimize steel pipe below 7 and no open tanks with pH <8
6-8.5
At H S>0.2 ppm, avoid use of copper and copper nickel
piping or HXs. Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components are OK
to <0.5 ppm
All--<0.5 ppm
Maximum Allowable at Maximum Water Temperature
50°F75°F100°F
Copper--<20 ppmNRNR
cupronickel--<150 ppmNRNR
304 SS--<400 ppm<250 ppm<150 ppm
316 SS--<1000 ppm<550 ppm<375 ppm
Titanium-->1000 ppm>550 ppm>375 ppm
All
<10 ppm of particles and a
maximum velocity of 1.8 m/s.
Filtered for maximum 841 micron [0.84 mm 20 mesh] size
<10 ppm (<1 ppm "sandfree" for reinjection) of particles
and a maximum velocity of 1.8 m/s. Filtered for maximum
841 micron [0.84 mm. 20 mesh] size. Any particulate that
is not removed can potentially clog components
5
INSTALLATION RECOMMENDATIONS
The Water--to-- Air Heat Pumps are designed to operate with
entering fluid temperature between 20_Fto90_F in the heating
mode and between 30_F to 120_F in the cooling mode.
NOTE:50_ minimum Entering Water Temperature (EWT) is
recommended for well water applications with sufficient water
flow to prevent freezing. Antifreeze solution is required for all
closed loop applications or EWT less than 45_. Cooling
Tower/Boiler and Geothermal applications should have sufficient
antifreeze solution to protect against extreme conditions and
equipment failure. Frozen water coils are not covered under
warranty. Other equivalent methods of temperature control are
acceptable.
Check Equipment and Job Site
Moving and Storage
If the equipment is not needed for immediate installation upon its
arrival at the job site, it should be left in its shipping carton and
stored in a clean, dry area. Units must only be stored or moved in
the normal upright position as indicated by the “UP” arrows on
each carton at all times.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
If unit stacking is required for storage, stack units as follows:
Do not stack units larger than 6 tons!
Vertical units: less than 6 tons, no more than two high.
Horizontals units: less than 6 tons, no more than three high.
Inspect Equipment
Be certain to inspect all cartons or crates on each unit as received at
the job site before signing the freight bill. Verify that all items have
been received and that there are no visible damages; note any
shortages or damages on all copies of the freight bill. In the event
of damage or shortage, remember that the purchaser is responsible
for filing the necessary claims with the carrier. Concealed damages
not discovered until after removing the units from the packaging
must be reported to the carrier within 24 hours of receipt.
Location / Clearance
Locate the unit in an indoor area that allows easy removal of the
filter and access panels, and has enough room for service personnel
to perform maintenance or repair. Provide sufficient room to make
fluid, electrical, and duct connection(s). If the unit is located in a
confined space such as a closet, provisions must be made for return
air to freely enter the face of unit’s air coil. On horizontal units,
allow adequate room below the unit for a condensate drain trap and
do not locate the unit above supply piping.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
These units are not approved for outdoor installation;
therefore, they must be installed inside the structure being
conditioned. Do not locate in areas that are subject to
freezing.
!
UNIT DAMAGE AND/OR OPERATION HAZARD
Failure to follow this caution may result in equipment
damage and/or improper equipment operation.
It is extremely important to take the proper precautions to
insure that the heat pump unit is installed in the proper
location and that measures have been taken to prevent
rupturing the water coil due to freezing conditions.
Frozen water coils are not covered under the limited
product warranty.
CAUTION
CAUTION
6
CONTROL
J15
GY
RD
TO ECM MOTOR
CFMADJUST
WHBLORBR YL
NO
HGRH
TEST
YES
NORM
(+)
(-)
A
BCD
THERMOSTAT
CFM
R C G O Y1 Y2 W1 W2 H C
J14
J17
GN/
GY
PU
BK
YL
WH
BL
ORGN/
BR
BK
J1J2J13
P1
GN/
YL
OR
BR
BK
GY
GYPU
RD
L1
P2
BL
WH
P13
GY
GY
RD
PU
L2
BK
WH
BK WH
GN/
LOW VOLTHIGH VOLT
YL
Fig. 4 -- Constant Airflow Motor
J19
P19
A150437
7
MOUNTING VERTICAL UNITS
Vertical units should be mounted level on a vibration absorbing
pad slightly larger than the base to minimize vibration transmission
to the building structure. It is not necessary to anchor the unit to the
floor. See Fig. 5.
NOTE:On VT and CF units, the condensate drain pan is
internally sloped. There is no internal P--Trap.
CONDENSATE DRAIN
VIBRATION PAD
FULL SIZE
A14117
Fig. 5 -- Vibration Absorbing Pad
MOUNTING HORIZONTAL UNITS
While horizontal units may be installed on any level surface strong
enough to hold their weight, they are typically suspended above a
ceiling by threaded rods. The manufacturer recommends these be
attached to the unit corners by hanger bracket kits. The rods must
be securely anchored to the ceiling. Refer to the hanging bracket
assembly and installation instructions for details.
IMPORTANT: Horizontal units installed above the ceiling
must conform to all local codes. An auxiliary drain pan, if
required by code, should be at least four inches larger than the
bottom of the heat pump.
Plumbing connected to the heat pump must not come in direct
contact with joists, trusses, walls, etc. Some applications require an
attic floor installation of the horizontal unit. In this case, the unit
should be set in a full size secondary drain pan on top of a
vibration absorbing mesh.
The Secondary drain pan prevents possible condensate overflow or
water leakage damage to the ceiling.
The secondary drain pan is usually placed on a plywood base
isolated from the ceiling joists by additional layers of vibration
absorbing mesh.
In both cases, a 3/4”drain connected to this secondary pan should
be run to an eave at a location that will be noticeable. If the unit is
located in a crawl space, the bottom of the unit must be at least 4”
above grade to prevent flooding of the electrical parts due to heavy
rains.
NOTE: HZ unit condensate drain pan is NOT internally sloped.
IMPORTANT: Horizontal (HZ) units must be installed pitched
toward the Condensate Drain Connection 1/8” per foot.
Fig. 6 -- Condensate Drain
A drain line must be connected to the heat pump and pitched away
from the unit a minimum of 1/8” per foot to allow the condensate
to flow away from the unit.
IMPORTANT: This connection must be in conformance with
local plumbing codes. A trap must be installed in the
condensate line to insure free condensate flow.
NOTE: HZ heat pump drain pan is not internally sloped.
A vertical air vent is sometimes required to avoid air pockets. The
length of the trap depends on the amount of positive or negative
pressure on the drain pan. A second trap must not be included.
A14118
DUCT SYSTEM
A supply air outlet collar and return air duct flange are provided on
all units to facilitate duct connections.
NOTE: Supply air duct and return air duct flanges are shipped
unfolded with unit.
Fold the duct flange outwards along the perforated line. Refer to
unit Dimensional Drawings for physical dimensions of the collar
and flange.
A flexible connector is recommended for supply and return air duct
connections on metal duct systems. All metal ducting should be
insulated with a minimum of one inch duct insulation to avoid heat
loss or gain and prevent condensate from forming during the
cooling operation.
Application of the unit to uninsulated duct work is not
recommended as the unit’s performance will be adversely affected.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper
equipment operation.
Do not connect discharge ducts directly to the blower
outlet.
The factory provided air filter must be removed when using a filter
back return air grill. The factory filter should be left in place on a
free return system.
If the unit will be installed in a new installation which includes new
duct work, the installation should be designed using current
ASHRAE procedures for duct sizing.
If the unit is to be connected to existing duct work, a check should
be made to assure that the duct system has the capacity to handle
the air required for the unit application.
If the duct system is too small, larger duct work should be installed.
Check for existing leaks and repair.
The duct system and all diffusers should be sized to handle the
designed air flow quietly. To maximize sound attenuation of the
unit blower, the supply and return air plenums should be insulated.
8
CAUTION
There should be no direct straight air path through the return air
grille into the heat pump. The return air inlet to the heat pump must
have at least one 90 degree turn away from the space return air
grille. If air noise or excessive air flow are a problem, the blower
speed can be changed to a lower speed to reduce air flow.
PIPING
Supply and return piping must be as large as the unit connections
on the heat pump (larger on long runs).
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper
equipment operation.
Never use flexible hoses of a smaller inside diameter than
that of the fluid connections on the unit.
GT units are supplied with either a copper or optional cupronickel
condenser. Copper is adequate for ground water that is not high in
mineral content.
NOTE: Proper testing is recommended to assure the well water
quality is suitable for use with water source equipment. When in
doubt, use cupronickel. See Application Considerations notes on
page 4.
In conditions anticipating moderate scale formation or in brackish
water, a cupronickel heat exchanger is recommended.
Both the supply and discharge water lines will sweat if subjected to
low water temperature. These lines should be insulated to prevent
damage from condensation. All manual flow valves used in the
system must be ball valves. Globe and gate valves must not be
used due to high pressure drop and poor throttling characteristics.
!
EQUIPMENTDAMAGEAND/ORUNIT
OPERATION HAZARD
Failure to follow this caution may result in equipment
damage and/or improper operation.
Never exceed the recommended water flow rates as serious
damage or erosion of the water--to--refrigerant heat
exchanger could occur.
Always check carefully for water leaks and repair appropriately.
Units are equipped with female pipe thread fittings. Consult Unit
Dimensional Drawings.
NOTE: Teflon tape sealer should be used when connecting water
piping connections to the units to insure against leaks and possible
heat exchanger fouling.
NOTE: The unit is shipped with water connection O--rings. A 10
pack of O--rings (part #4026) can be ordered through Replacement
Components Division (RCD).
IMPORTANT: Do not over-- tighten connections.
Flexible hoses should be used between the unit and the rigid
system to avoid possible vibration. Ball valves should be installed
in the supply and return lines for unit isolation and unit water flow
balancing (on open--loop systems).
CAUTION
CAUTION
ELECTRICAL
Refer to electrical component box layout. See Fig. 7.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment
damage and/or improper operation.
S Field wiring must comply w ith local and national
electrical codes.
S Power to the unit must be within the operating voltage
range indicated on the unit nameplate or on the
performance data sheet.
S Operation of unit on improper line voltage or with
excessive phase imbalance will be hazardous to the unit,
constitutes abuse, and may void the warranty.
Properly sized fuses or HACR circuit breakers must be installed for
branch circuit protection. See unit nameplate for maximum fuse or
breaker size.
The unit is provided with a concentric knock--out for attaching
common trade sizes of conduit, route power supply wiring through
this opening.
Always connect the ground lead to the grounding lug provided in
the control box and power leads to the line side of compressor
contactor as indicated on the wiring diagrams.
IMPORTANT: Units supplied with internal electric heat
require two (2) separate power supplies:
1) Unit compressor
2) Electric Heat, blower motor and control circuit.
Refer to the ELECTRIC HEATER PACKAGE OPTION section.
See data plate for minimum circuit ampacities and maximum
fuse/breaker sizing.
S Water side freeze protection sensor, mounted close to condensing
water coil, monitors refrigerant temperature between condensing
11
1213
water coil and thermal expansion valve. If temperature drops
below or remains at freeze limit trip for 30 seconds, the controller
will shut down the compressor and enter into a soft lockout
condition.
The default freeze limit trip is 26_F, however this can be changed
to 15_F by cutting the R30 or Freeze1 resistor located on top of
DIP switch SW1 (Refer to Fig. 8, item (3) for resistor location),
RefertoFig.9forsensorlocation.
17
6
(1) Board Power Indicator(10) Compressor Contact Output
(2) UPM Status LED Indicator(11) High Pressure Switch Connection
(3) Water Coil Freeze Protection
Temperature Selection [R30]
(4) Air Coil Freeze Protection
Temperature Selection
(5) UPM Board Settings(14) 24VAC Power Common
(6) Water Coil Freeze Connection(15) Condensate Overflow Sensor
(7) Air Coil Freeze Connection(16) Dry Contact
(8) LCD Unit Display Connection(17) UPM Ground Standoff
(9) 24VAC Power Input
15
7
8
14
(12) Call for Compressor Y1
(13) Low Pressure Switch Connection
16
9
10
A14120
Fig. 8 -- Safety Device and UPM Controller
NOTES:
1. If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit malfunction output or relay. Refer to Fig. 8.
2. If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a
jumper between “R” and “COM” terminal of “ALR” contacts must be made.
3. If the thermostat is provided with a malfunction light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected
directly to the (ALR) contact on the unit’s UPM board.
Each unit is factory provided with a Unit Protection Module
(UPM) that controls the compressor operation and monitors the
safety controls that protect the unit.
Safety controls include the following:
S High pressure switch located in the refrigerant discharge line and
wired across the HPC terminals on the UPM.
S Low pressure switch located in the unit refrigerant suction line
and wired across terminals LPC1 and LPC2 on the UPM.
NOTE: UPM Board Dry Contacts are normally open (NO)
Fig. 9 -- Freeze Protection Sensor Location
A14121
!
CAUTION
UNIT DAMAGE AND/OR OPERATION HAZARD
Failure to follow this caution may result in unit damage
and/or improper equipment operation.
If unit is employing a fresh water system (no anti--freeze
protection), it is extremely important to have the Freeze1
R30 resistor set to 26_F in order to shut down the unit at
the appropriate leaving water temperature and protect your
heat pump from freezing if a freeze sensor is included.
S Evaporator freeze protection sensor, mounted after the thermal
expansion device and the evaporator, monitors refrigerant
temperature between the evaporator coil and thermal expansion
valve. If temperature drops below or remains at freeze limit trip
for 30 seconds, the controller will shut down the compressor and
enter into a soft lockout condition. The default freeze limit trip is
26_F. See Fig. 10.
S MALFUNCTION OUTPUT: Alarm output is Normally Open
(NO) dry contact. If pulse is selected the alarm output will be
pulsed. The fault output will depend on the dip switch setting for
”ALARM”. If it is set to ”CONT”, a continuous signal will be
produced to indicate a fault has occurred and the unit requires
inspection to determine the type of fault. If it is set to ”PULSE”, a
pulse signal is produced and a fault code is detected by a remote
device indicating the fault. See L.E.D Fault Indication below for
blink code explanation. The remote device must have a
malfunction detection capability when the UPM board is set to
”PULSE”.
NOTE:If 24 VAC output is needed, R must be wired to
ALR--COM terminal; 24 VAC will be available on the ALR--OUT
terminal when the unit is in the alarm condition.
S DISPLAY OUTPUT: The Display output is a pulse output
connected to the Unit Diagnostic Display (UDD) and it pulses
24VAC when the unit is in an lockout alarm condition.
S UPM TEST MODE: UPM test mode will allow all time--delay
settings to be reduced to 10 seconds for troubleshooting and
verification of unit operation. Reset unit to TEST mode: NO
when test is completed. During UPM test mode, the UPM LED
will flash a FREEZE SENSOR 6 flash code. Test mode will
automatically defeat after approximately 5 minutes with no LED
flash and normal delays.
TEMP
LOCKOUT
RESET
ALARM
TEST
UPM DIP SWITCH DEFAULT POSITION
lockout4
reset
alarm
test
The UPM Board includes the following features:
S ANTI-- S HORT CYCLE TIMER: 5 minute delay on break
timer to prevent compressor short cycling.
S RANDOM START: Each controller has an unique random start
delay ranging from 270 to 300 seconds on initial power up to
reduce the chance of multiple unit simultaneously starting at the
same time after power up or after a power interruption, thus
avoiding creating large electrical spike.
S LOW PRESSURE BYPASS TIMER:Ifthecompressoris
running and the low pressure switch opens, the controller will
keep the compressor ON for 120 seconds. After 2 minutes if the
low pressure switch remains open, the controllers will shut down
the compressor and enter a soft lockout. The compressor will not
be energized until the low pressure switch closes and the
anti--short cycle time delay expires. If the low pressure switch
opens 2--4 times in 1 hour, the unit will enter a hard lockout. In
order to exit hard lockoutpower to the unit would need to bereset.
S BROWNOUT / SURGE / POWER INTERRUPTION
PROTECTION: The brownout protection in the UPM board
will shut does the compressor if the incoming power falls below
18 VAC. The compressor will remain OFF until the voltage is
above 18 VAC and ANTI--SHORT CYCLE TIMER (300
seconds) times out. The unit will not go into a hard lockout.
30°F
2
Y
PULSE
NO
2
RY
Cont
yes
pulse
no
!
UNIT DAMAGE AND/OR OPERATION HAZARD
Failure to follow this caution may result in unit damage
and/or improper equipment operation.
Operation of unit in test mode can lead to accelerated wear
and premature failure of components. The ”TEST” switch
must be set back to ”NO” after troubleshooting/ servicing.
S FREEZE SENSOR: The default setting for the freeze limit trip is
26_F (sensor number 1); however this can be changed to 15_Fby
cutting the R30 resistor located on top of the DIP switch SW1.
Since freeze sensor 2 is dedicated to monitor the evaporator coil, it
is recommended to leave the factory default setting on the board.
The UPM controller will constantly monitor the refrigerant
temperature with the sensor mounted close to the condensing
water coil between the thermal expansion valve and water coil. If
temperature drops below or remains at the freeze limit trip for 30
seconds, the controller will shut the compressor down and enter
into a soft lockout condition. Both the status LED and the Alarm
contact will be active.
The LED will flash the code associated with this alarm condition
three (3) times. If this alarm occurs 2 times (or 4 if Dip switch is set
to 4) within an hour, the UPM controller will enter into a hard
lockout condition. It will constantly monitor the refrigerant
temperature with the sensor mounted close to the evaporator
between the thermal expansion valve and evaporator coil as
shown in Fig. 10.
If temperature drops below or remains at the freeze limit trip for
30 seconds, the controller will shut the compressor down and
enter into a soft lockout condition. Both the status LED and the
alarm cont act will be activ e. T he LE D will flash the cod e
associated with this alarm condition six (6) times. If this alarm
occurs 2 times (or 4 if Dip switch is set to 4) within an hour, the
controller will enter into a hard lockout condition.
!
UNIT DAMAGE AND/OR OPERATION HAZARD
Failure to follow this caution may result in unit damage
and/or improper equipment operation.
Freeze sensor will not guard against the loss of water. A
flow switch is recommended to prevent the unit from
running if water flow is lost or reduced.
S HIGH PRESSURE SWITCH: The high pressure switch safety
is designed to shut down the compressor if it exceeds limits. Cut
in 420 +/-- 15 psig and cut out 600 +/-- psig.
S LOW PRESSURE SWITCH: The low pressure switch safety is
designed to shut down thecompressor of loss of charge. Cut in 60
+/-- 15 psig and cut out 40 +/-- psig.
S INTELLIGENT RESET: If a fault condition is initiated, the 5
minute delay on break time period is initiated and the unit will
restart after these delays expire. During this period the fault LED
will indicate the cause of the fault. If the fault condition still exists
or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip
switch) before 60 minutes, the unit will go into a hard lockout and
requires a manual lockout reset.
A single condensateoverflow fault will cause the unit to go into a
hard lockout immediately,and willrequire a manual lockout reset.
S LOCKOUT RESET: A hard lockout can be reset by turning the
unit thermostat off and then back on when the “RESET” dip
switch is set to “Y” or by shutting off unit power at the circuit
breaker when the “RESET” dip switch is set to “R”.
NOTES: The blower motor will remain active during a lockout
condition.
S ECM TEST MODE: ECM test mode is to override the motor to
constant torque mode for motor troubleshooting. If the motor
runs in ECM test mode, the module and motor are good. To
engagein ECM test mode, only one switch canbe selected. Select
TEST ON and all others OFF. Reset the board to NORM ON and
TEST OFF when test is complete.
If the unit remains in test mode for normal operation, the system
will not run different CFMs based on thermostat call such as Y1,
Y2 or dehumidify. It may also experience problems with
nuisance strip during electric heat operation.
There is no way to check CFM based on number of blinks if the
board is set to test mode.
12
START
Y1 = ON
NO
RESET ON
Y
NO
RESET ON R
YES
R = 24VAC
YES
POWER/ SWITCHES/SENSOR
STATUS CHECK
V > 18VAC
NO
YES
HPC =
CLOSED
NO
YES
LPC
=CLOSED
NO
YES
START
TIMER
YES
CLEAR FAULTS
TIME > 120
NO
BLINK CODE ON STATUS LED
SOFT LOCKOUT
RECORD ALARM
START COUNTER (IF APPLICABLE)
LOCKOUT CAN BE SET
TO 4 VIA DIP SWITCH
BLINK CODE
ON STATUS LED
SEC
YES
NO
NO
NO
COUNTER
NEEDED?
YES
COUNT = 2
OR
COUNT = 4
YES
HARD
LOCKOUT?
YES
NO
FRZ >TEMP
LIMIT
YES
CON > 0
YES
INITIAL
POWER UP
YES
NO
NO
NO
BLINK CODE ON STATUS LED
START
TIMER
TIME > 30
SEC
YES
NO
START
ANTI SHORT CYCLE
START
RANDOM START UP
NO
T > ASC OR
RS SEC
YES
CC
Fig. 12 -- UPM Sequence of Operation (SOO) Flow Chart
DISPLAY OUTPUT = PULSE
ALR OUTPUT = ON/PULSE
CC OUTPUT = OFF
CC OUTPUT = ON
A14129
13
ECM INTERFACE BOARD
Refer to Fig. 7, item (12) for ECM interface board location. In
addition to providing a connecting point for thermostat wiring, the
interface board also translates thermostat inputs into control
commands for the Electronic Commutated Motor (ECM) DC fan
motor and provides thermostat signals to unit’s UPM board. The
thermostat connections and their functions are as follows:
10
1
3
Dehumidification Mode
Position the HGRH DIP switch in the “NO” (OFF) position.
When the switch is in this position, upon a dehumidification call,
the unit will operate at a lower speed to increase dehumidification
while cooling. See Fig. 14.
8
9
(1) Motor Harness Plug(7) Thermostat Input Status Indication
(2) Blower CFM Adjustment(8) Reheat Digital Outputs
(3) Motor Settings(9) Thermostat Outputs
(4) Dehumidification Indication(10) 24 VAC
(5) Thermostat Contact Inputs(11) Dehumidification Method Selector
(6) CFM Count Indicator
27
5
11
46
A14124
Fig. 13 -- ECM Interface Board
NOTE:CFM LED indication is an approximation. Utilize
conventional Test and Balance equipment for accurate airflow
measurement.
S CFM count indicator (see Fig. 13, item 6) blinks to indicate
approximate airflow in CFM and may flicker when the unit is off.
S Each blink of the LED represent approximately 100 CFM of air
delivery so if the LED blinks 12 times, pauses, blinks 12 times,
etc. the blower is delivering approximately 1200 CFM.
Fig. 14 -- Dehumidification Method Selector
A14126
Thermostat Outputs
Dry Contact Left side terminal strip in the stat, D1, D2
YIFirst Stage Compressor Cool
Y/Y2Second Stage Compressor Cool
W1Auxiliary Electric Heat
(runs in conjunction with compressor)
W2/EEmergency Heat (electric heat only)
OReversing Valve (energized in cooling)
GFan
RTransformer 24 VAC Hot
CTransformer 24 VAC Common
NOTE: When unit is used with Carrier and Bryant thermostats
with Relative Humidity Control (Carrier Edge TP--PRH or
TP--NRH / Bryant Preferred T6-- PRH or T6--NRH), the unit’s
dehumidification mode is in reverse logic and will not activate
dehum unless a relay, as shown in Fig. 15, is used. A simplified
explanation of the reverse logic follows.
RHECM
Stat Logic:Board Logic:
No Dehum Demand: Dh -- energizedDh--not energized
Dehum Demand:Dh -- de--energizedDh -- energized
THERMOSTAT
24V OUTPUTS
DE-H UMID IFICATION CA LL
COOLING STAGE 1
COOLING STAGE 2
HEATING STAGE 1
HEATING STAGE 2
SWITCH OVER VALVE
BLOWER
24VAC (HOT)
24VAC (COMMON)
Fig. 15 -- Cool to Dehumidify Application for Thermostats with Dehumidification
Dry
Contact
Y1
Y2
W1
W2/E
O/B
G
R
C
RELAY
C
H
HUMIDISTAT
Y1
COOLING STAGE 1
Y2
COOLING STAGE 2
W1
HEATING STAGE 1
W2
HEATING STAGE 2
O
REVERSING VALVE
G
BLOWER
R
C
DHR – DEHUMIDIFICATION RELAY
FIELD INST ALLE D
CAV42
(Not required for Cor / Housewise thermostats)
ECM CONTROLLER INTERFACE
24V INPUTS
YES N O
STLOV ENIL
EX: 230VAC
LOW VOLTAGE CLASS II WIRING – 18AWG
HGRH
A150487
14
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.