Bryant GAMA 331JAV Installation And Operating Instructions Manual

installation, start-up, and operating instructions
DOWNFLOW 2-SPEED, 2-STAGE, INDUCED-COMBUSTION GAS-FIRED FURNACE
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. Index Page
SAFETY CONSIDERATIONS .....................................................1
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE........................................................................1-2
INTRODUCTION.......................................................................2-3
Clearances to Combustibles......................................................3
LOCATION....................................................................................4
General ......................................................................................4
Location Relative to Cooling Equipment ................................4
Hazardous Locations.................................................................4
AIR FOR COMBUSTION AND VENTILATION...................4-5
Unconfined Space .....................................................................4
Confined Space......................................................................4-5
SUPPLY-AIR PLENUM INSTALLATION
(DOWNFLOW) .....................................................................5-6
Downflow Installation .............................................................5
Installation On Combustible Floor........................................5-6
FILTER ARRANGEMENT .......................................................6-7
GAS PIPING...............................................................................6-8
ELECTRICAL CONNECTIONS...............................................8-9
115-v Wiring.............................................................................8
24-v Wiring............................................................................8-9
Accessories .............................................................................. 9
VENTING ......................................................................................9
START-UP, ADJUSTMENT, AND SAFETY CHECK.......10-20
General ....................................................................................10
Sequence of Operation ......................................................10-14
Non-Adaptive Heating Mode .................................................12
Cooling Mode .........................................................................13
Continuous Blower Mode.......................................................13
Heat Pump Mode...............................................................13-14
Defrost Mode ..........................................................................14
Start-Up Procedures................................................................14
Adjustments .......................................................................14-20
Set Temperature Rise ........................................................19-20
Set Thermostat Heat Anticipator............................................20
Check Safety Controls.......................................................20-21
Checklist..................................................................................21
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
331JAV
Series B
Cancels: II 331J-60-1 II 331J-60-2
12-97
ama
CANADIAN GAS ASSOCIATION
®
REGISTERED QUALITY SYSTEM
Follow all safety codes. In the United States, refer to the National Fuel Gas Code (NFGC) NFPA No. 54-1996/ANSI Z223.1-1996. In Canada, refer to the current edition of the National Standard of Canada CAN/CGA-B149.1- and .2-M95 Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electro­static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
APPROVED
R
.
—1—
1
28
⁄2″
20
13
⁄16″
7
39
⁄8″
11
⁄16″
INLET
7
⁄8″ DIA
ACCESSORY
3
⁄4″ DIA HOLE
1
GAS ENTRY
OUTLET
19
ADDITIONAL
NOTE:
LOCATED IN THE TOP PLATE AND BOTTOM PLATE
7
⁄8″ DIA K.O. ARE
VENT CONNECTION
13
⁄16″
1
9
⁄8″
1
10
⁄4″
1
1
⁄16″
1
2
⁄8″
1
8
⁄4″
11
⁄16″
D
E
A
AIRFLOW
1
⁄2″ DIA
2
3
4
⁄16″
15
2
⁄16″
1
16
⁄16″
5
13
⁄16″
1
10
11
⁄16″
DIMPLES TO DRILL HOLES FOR HANGER BOLTS (4 PLACES) IN HORIZONTAL POSITION
⁄4″
THERMOSTAT  WIRE ENTRY
7
⁄8″ DIA
ACCESSORY
7
⁄8″ DIA HOLE
POWER ENTRY
1
1
⁄2″ DIA
R.H. GAS ENTRY
7
⁄8″ DIA
ACCESSORY
1
1
⁄16″
1
2
⁄8″
TYP
1
5
⁄8″ TYP
Fig. 1—Dimensional Drawing TABLE 1—DIMENSIONS (IN.)
UNIT SIZE A D E VENT CONN SHIP. WT
036060 14-3/16 12-9/16 12-11/16 4 145 048080 17-1/2 15-7/8 16 4 154 060100 21 19-3/8 19-1/2 4 181
A88324
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch­ing control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
INTRODUCTION
The model 331JAV Series B Furnace is available in sizes 60,000 through 100,000 Btuh input capacities.
The design of the downflow gas-fired furnace is A.G.A./C.G.A. certified for natural and propane gases and for installation on noncombustible flooring. The furnace is factory-shipped for use with natural gas. The manufacturer’s accessory gas conversion kit is required to convert furnace for use with propane gas.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, the manufacturer’s accessory floor base must be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used. This furnace is for installation in alcoves, attics, crawlspaces, basements, closets, or utility rooms. The design of this furnace line is not A.G.A./C.G.A. certified for installation in mobile homes, recreation vehicles, or outdoors.
Before installing the furnace, refer to the current edition of the NFGC and the NFPA 90B. Canadian installations must be installed in accordance NSCNGPIC and all authorities having jurisdiction. For a copy of the NFGC NFPA54/Z223.1, contact International Approval Services U.S. Inc., 8501 E. Pleasant Valley Road, Cleveland, OH 44131 or National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269. For a copy of NFPA 90B, contact National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269.
Before installing the furnace in Canada, refer to the current edition of the NSCNGPIC. Contact Standards Department of Canadian Gas Association, 55 Scarsdale Road, Don Mills, Ontario, Canada M3B 2R3.
The duct system should be designed and sized according to accepted national standards published by: Air Conditioning Con­tractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA). Or consult the Residential Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the maximum CFM capabilities of the equipment at the optimum design static pressure.
—2—
INSTALLATION
This unit is certified for downflow installation only. See Installation Manual for
important installation instructions.
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
This forced air furnace is equipped for use with natural gas at altitudes 0 ­10,000 ft (0-3,050m).
An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications.
This furnace is for indoor installation in a building constructed on site.
This furnace may be installed on combustible flooring in alcove or closet at minimum clearance from combustible material.
This furnace may be used with a Type B-1 Vent and may be vented in common with other gas-fired appliances.
For installation on non-combustible
floors only. For installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL, Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
For furnaces wider than 14.25
#
inches (362mm) may be 0 inches.
Ø
18 inches front clearance required
for alcove.
For single wall vent type 6 inches.
##
This furnace is approved for DOWNFLOW installations only.
1"
0"
B
A
C
K
E
D
I
S
1" #
Clearance in inches.
TOP / PLENUM
E
C
A
N
R
U
F
T
N
O
R
F
F
R
O
N
T
##
BOTTOM
"
1
Vent Clearance to combustibles:
For Single Wall vents 6 inches (6 po). For Type B-1 vent type 1 inch (1 po).
#
1"
E
D
I
S
S
E
R
V
I
C
E
30"
MIN
Ø
322567-101 REV. E (LIT)
Fig. 2—Clearances to Combustibles
CAUTION: Application of this furnace should be in-
doors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause prema­ture component failure.
Installation must conform to regulations of serving gas supplier and local building, heating, and plumbing codes in effect in the area in which installation is made, or in absence of local codes with requirements of the NFGC.
This furnace is designed for a minimum continuous return-air temperature of 60°F db or intermittent operation down to 55°F such as when used with a night setback thermostat. Return-air temperature must not exceed 85°F db.
To aid in installation, troubleshooting, and service, a status code label is located on blower component door. This label explains how to use the LED status indicated on furnace control which is viewed through the sight glass on door.
A97620
WARNING: Improper installation, adjustment, alter­ation, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury, loss of life, or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified in­staller or agency must use only factory-authorized and listed kits or accessories when modifying this product. A failure to follow this warning could result in electrical shock, fire, personal injury, or death.
For high-altitude installation, the high-altitude conversion kit must be installed at or above 5500 ft above sea level.
For accessory installation details, refer to applicable installation literature.
NOTE: Remove all shipping brackets and materials before oper­ating furnace.
—3—
I. LOCATION
A. General
CAUTION: DO NOT install furnace in a corrosive or
contaminated atmosphere. Make sure all combustion and circulating air requirements are followed. DO NOT use this furnace during construction when adhesives, sealers, and/or new carpets are being installed and curing. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned in combustion air form acids which will cause corrosion of the heat exchangers and metal vent systems. Some of these compounds are released from paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construc­tion process. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
This furnace must be installed so electrical components are protected from water.
Locate furnace as near to center of air distribution system and chimney or vent as possible. The furnace should be installed as level as possible.
When furnace is installed so that supply ducts carry air to areas outside space containing furnace, the return air must also be handled by a duct(s) sealed to furnace casing and terminating outside space containing furnace.
Provide ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown on unit clearance label. This furnace shall not be installed directly on carpeting, tile, or any combustible material other than wood flooring. The furnace may be installed on combustible flooring when installed with accessory downflow subbase, which is available from your dis­tributor or branch when required.
B. Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchangers. When installed parallel with furnace, dampers or other means used to control the flow of air must prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with means to prevent operation of either unit unless damper is in full-heat or full-cooling position.
C. Hazardous Locations
When furnace is installed in a residential garage, it must be installed so that burners and ignition source are at least 18 in. above floor. The furnace should be protected from physical damage by vehicles.
When furnace is installed in public garages, airplane hangars, or other buildings having hazardous atmospheres, unit must be installed in accordance with recommended good practice require­ments of the National Fire Protection Association, Inc.
II. AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3, Air for Combustion and Ventilation, of the NFGC or applicable provisions of local building codes.
Canadian installations must be in accordance with NSCNGPIC and all authorities having jurisdiction.
CAUTION: Air for combustion must not be contami­nated by halogen compounds which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
CAUTION: The operation of exhaust fans, kitchen ven­tilation fans, clothes dryers, or fireplaces could create a negative air pressure condition at the furnace. Make-up air must be provided for these devices, in addition to that required by the furnace.
All fuel-burning equipment must be supplied with air for combus­tion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in equipment room or space. In addition, a positive seal MUST be made between furnace cabinet and return-air duct to avoid pulling air from the burner area and draft safeguard opening into circulating air. The requirements for combustion and ventilation air depend upon whether furnace is located in a CONFINED or UNCONFINED space.
A. Unconfined Space
An unconfined space must have at least 50 cu ft for each 1000 Btuh of input for all appliances (such as furnaces, clothes dryer, water heaters, etc.) in the space. For Example:
331JAV FURNACE
HIGH-FIRE INPUT
BTUH 63,000 420 84,000 560
105,000 700
MINIMUM SQ FT
WITH
7-1/2 FT CEILING
If the unconfined space is constructed unusually tight, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with outdoors. Combustion and ventilation openings must be sized the same as for a confined space as defined below. Return air must not be taken from the room unless equal or greater amount of air is supplied to the room.
B. Confined Space
A confined space is defined as a space whose volume is less than 50 cu ft per 1000 Btuh of total input ratings of all appliances installed in that space. A confined space MUST have provisions for supplying air for combustion, ventilation, and dilution of flue gases using 1 of the following methods. NOTE: In determining free area of an opening, the blocking effect of louvers, grilles, and screens must be considered. If free area of louver or grille design is unknown, assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed. The size of the openings depends upon whether air comes from outside of the structure or an unconfined space inside the structure.
1. All air from an unconfined space inside the structure requires 2 openings (for structures not usually tight): a. Each opening MUST have at least 1 sq in. of free area
per 1000 Btuh of total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 3 and Table 2.) The minimum dimension of air openings shall not be less than 3 in.
b. If the building is constructed unusually tight, a perma-
nent opening directly communicating with the outdoors shall be provided. (See item 2 below.)
—4—
VENT THROUGH ROOF (CATEGORY I)
DUCTS TO
OUTDOORS
1 SQ IN. PER 4000 BTUH
*
RETURN
AIR
INTERIOR
HEATED
SPACE
SUPPLY AIR
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in.
Minimum of 3 in. when type B-1 vent is used.
12 MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
6 MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
12 MAX
A93387
Fig. 3—Confined Space: Air for Combustion and Ventilation
from an Unconfined Space
c. If furnace is installed to obtain return air is taken directly
from hallway or space adjacent to furnace, all air for combustion must come from outdoors.
2. Air from outside the structure requires 1 of the following methods:
a. If combustion air is taken from outdoors through 2
vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table 2.)
b. If combustion air is taken from outdoors through 2
horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table 2.)
c. If combustion air is taken from outdoors through a single
opening or duct (horizontal or vertical) commencing within 12 in. of the top of the confined space, opening and duct MUST have at least 1 sq in. of free area per 3000 Btuh of the total input for all equipment within the confined space and not less than the sum of the areas of all vent connectors in the confined space. (See Fig. 4 and Table 2.) Equipment clearances to the structure shall be at least 1 in. from the sides and back and 6 in. from the front of the appliances.
When ducts are used, they must be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of ducts must not be less than 3 in. (See Fig.
4.)
12 MAX
1 SQ IN. PER 2000 BTUH
*
DUCTS
TO
OUTSIDE
1 SQ IN. PER 2000 BTUH
*
12 MAX
SUPPLY AIR
Minimum dimensions of 3 in.
*
NOTE:
Use any of the following combinations of openings: A & B C & D D & E F & G
RETURN
A
B
AIR
D
VENT THROUGH ROOF (CATEGORY I)
CONFINED
C
DUCT
TO
OUTDOORS
F
SPACE
G
E
12 MAX
12
MAX
1 SQ IN. PER 4000 BTUH
OUTDOORS
1 SQ IN. PER 4000 BTUH
12
MAX
1 SQ IN. PER 4000 BTUH
*
*
A93388
Fig. 4—Confined Space: Air for Combustion and Ventilation
from Outdoors
III. SUPPLY-AIR PLENUM INSTALLATION (DOWN­FLOW)
A. Downflow Installation
NOTE: This furnace is approved for use on combustible flooring when manufacturer’s accessory floor base Part No. KGASB0201ALL is used. Manufacturer’s accessory floor base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or Coil Box Part No. KCAKC is used.
1. Determine application being installed from Table 3.
2. Construct hole in floor per dimensions specified in Table 3 and Fig. 5.
3. Construct plenum to dimensions specified in Table 3.
4. If downflow subbase (KGASB) is used, install as shown in Fig. 6.
If coil assembly CD5, CK5, or Coil Box KCAKC is used, install as shown in Fig. 7.
B. Installation On Combustible Floor
1. Cut and frame hole in floor per dimensions in Installation Instructions packaged with downflow subbase.
2. When completed, downflow subbase, plenum, and furnace (or coil casing when used) should be installed as shown in Fig. 6.
—5—
TABLE 2—FREE AREA OF COMBUSTION AIR OPENING
331JAV
FURNACE
HIGH-FIRE
INPUT
(BTUH)
63,000 100 15.8 5 31.5 7 21.0 6 84,000 100 21.0 6 42.0 8 28.0 6
105,000 105 26.3 6 52.5 9 35.0 7
AIR FROM
UNCONFINED
SPACE
Free Area
of Opening
(Sq In.)
OUTDOOR AIR THROUGH
VERTICAL DUCTS
Free Area of
Opening and Duct
(Sq In.)
(In. Dia)
Round
Pipe
OUTDOOR AIR THROUGH
HORIZONTAL DUCTS
Free Area of
Opening and Duct
(Sq In.)
(In. Dia)
Round
Pipe
OUTDOOR AIR THROUGH
SINGLE DUCT
Free Area of
Opening and Duct
(Sq In.)
A
PLENUM
OPENING
B
OPENING
D
FLOOR
C
Round
Pipe
(In. Dia)
Fig. 5—Floor and Plenum Opening Dimensions
TABLE 3—OPENING DIMENSIONS (IN.)
FURNACE
CASING
WIDTH
14-3/16
17-1/2
21
Combustible Flooring Using KGASB Subbase 11-13/16 19 13-7/16 20-3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
Combustible Flooring Using KGASB Subbase 15-1/8 19 16-3/4 20-3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
Combustible Flooring Using KGASB Subbase 18-5/8 19 20-1/4 20-3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
APPLICATION
Non-Combustible Flooring 12-11/16 19 13-3/8 19-5/8
KCAKC Coil Box
Non-Combustible Flooring 16 19 16-5/8 19-5/8
KCAKC Coil Box
Non-Combustible Flooring 19-1/2 19 20-1/8 19-5/8
KCAKC Coil Box
IV. FILTER ARRANGEMENT
WARNING: Never operate unit without a filter or with
filter access door removed. A failure to follow this warning could result in fire, personal injury, or death.
The 2 factory-supplied filters are shipped in the blower compart­ment. After return-air duct has been connected to furnace, install filters in a V-formation inside return-air plenum. (See Fig. 8.)
V. GAS PIPING
Gas piping must be installed in accordance with national and local codes. Refer to the NFGC NFPA 54-1996/ANSI Z223.1-1996. Canadian installations must be installed in accordance with NSC­NGPIC and all authorities having jurisdiction.
A96283
PLENUM OPENING FLOOR OPENING
ABCD
12-5/16 19 13-5/16 20
15-1/2 19 16-1/2 20
19 19 20 20
The gas supply line should be a separate line directly from the meter to the furnace, if possible. Refer to Table 4 for recom­mended gas pipe sizing. Risers should be used to connect to the furnace and to the meter.
CAUTION: If flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at gas valve and extend a minimum of 2 in. outside furnace casing.
—6—
FURNACE
(OR COIL CASING
WHEN USED)
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Fig. 6—Furnace, Plenum, and Subbase Installed on
a Combustible Floor
WARNING: Use the proper length of pipes to avoid
stress on gas control manifold. A failure to follow this warning could result in a gas leak causing fire, explosion, personal injury, or death.
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A96284
Fig. 7—Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
CAUTION: Use a backup wrench at furnace gas control
when connecting gas pipe to furnace to avoid damaging gas controls or manifold.
AIRFLOW
INSTALLATION
POSITION
OF FILTERS
RETURN-AIR
PLENUM
ACCESS DOOR
Fig. 8—Downflow Filter Arrangement
A88486
WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution to check for gas leaks. A failure to follow this warning could result in fire, explosion, personal injury, or death.
Piping should be pressure tested in accordance with local and national plumbing and gas codes before furnace has been attached. If test pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on the gas valve before test. It is recommended that ground joint union be loosened before pressure testing.
Joint compounds (pipe dope) should be applied sparingly and only to male threads of joints. This pipe dope must be resistant to action of propane gas.
TABLE 4—MAXIMUM CAPACITY OF PIPE*
NOMINAL
IRON PIPE
SIZE (IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1-1/4 1.380 1400 950 770 660 580 1-1/2 1.610 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a supply line pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2, NFPA 54-1996.
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
—7—
TABLE 5—ELECTRICAL DATA
UNIT SIZE
VOLTS— HERTZ—
PHASE
036060 115—60—1 127 104 10.5 14 35 15 048080 115—60—1 127 104 14.2 14 26 15 060100 115—60—1 127 104 17.9 12 32 20
* Permissible limits of the voltage range at which the unit will operate satisfactorily. † Time-delay fuse is recommended. ‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
Install accessible manual shutoff valve upstream of furnace gas controls and within 72 in. of furnace. A 1/8-in. NPT plugged tapping is provided on gas value for test gage connection. Installation of additional 1/8-in. NPT plugged tapping, accessible for test gage connection, installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve is not required. Place ground joint union between gas control manifold and manual shutoff.
Install sediment trap in riser leading to furnace. The trap can be installed by connecting a tee to riser leading from furnace. Connect capped nipple into lower end of tee. The capped nipple should extend below level of gas controls. (See Fig. 9.)
OPERATING
VOLTAGE RANGE
Max* Min*
MAX
UNIT
AMPS
EAC - ELECTRONIC
(115-VAC 1 AMP MAX)
MIN
WIRE
GAGE
AIR CLEANER
MAX WIRE
LENGTH
78 9
456
123
FT‡
PR2
PR1
L2
L1
PARK
COM
EAC-1
EAC-2
-HEAT
-HEAT
HI-GAS
LO-GAS
HI-COOL
SEC-1
10 11 12
789
456
123
MASTER SLAVE
TWIN
TEST
1
After all connections have been made, purge lines and check for gas leakage with regulated gas supply pressure.
1234
OFF
ON
MAX FUSE OR
HACR-TYPE
CKT BKR AMPS†
3-AMP
3
FU1
FUSE
LED - DIAGNOSTIC
SEC-2
LIGHT
TWIN / TEST
LED
HUM GRY/Y2W/W1
TERMINAL
HUM - HUMIDIFIER (24-VAC 0.5 AMP MAX)
1
24-VOLT THERMOSTAT TERMINALS
24 V
COM
W2
GAS
SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT TRAP
UNION
Fig. 9—Typical Gas Pipe Arrangement
VI. ELECTRICAL CONNECTIONS
A. 115-v Wiring
Refer to unit rating plate or Table 5 for equipment electrical requirements. The control system requires an earth ground for proper operation.
CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
Make all electrical connections in accordance with the current
edition of the National Electrical Code (NEC) ANSI/NFPA 70-1996 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with CSA C22.1 Canadian Electrical Code or authori­ties having jurisdiction.
A89414
FURNACE AND BLOWER OFF DELAY SETUP SWITCHES
NOTE: Proper polarity must be maintained for 115-v wiring. If
Fig. 10—Control Center
polarity is incorrect, the furnace control status LED will flash rapidly and prevent heating operation.
WARNING: The cabinet must have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70­1996 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
B. 24-v Wiring
Refer to ESD Precautions Procedure before proceeding with 24-v connections. Make field 24-v connections at the 24-v terminal block. (See Fig.
10.) Connect terminal Y/Y2 as shown in Fig. 11 or 12 for proper operation in cooling mode. Use AWG No. 18 color-coded, copper thermostat wire only. When furnace is installed in horizontal position with RH discharge air, 24-v wire connections can be made easier by removing the 2 control box mounting screws and letting control box turn so that 24-v screw terminals are visible. Be sure to reinstall control box after connections are made. The 24-v circuit contains an automotive-type, 3-amp fuse located on main control. Any 24-v electrical shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse. The control will flash code 24 when fuse needs replacement.
C. Accessories
1. Electronic air cleaner (EAC)
A93348
—8—
Loading...
+ 16 hidden pages