Bryant FNCCAB series, FNCCAB-0014, FNCCAB-0017, FNCCAB-0021, FNCCAB-0024 Installation Instructions Manual

Sizes: 014, 017, 021, 024
Installation Instructions
C04032
Fig. 1 -- FNCCAB High Efficiency Air Filtration System
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA
70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION and NOTE. The words DANGER, WARNING,andCAUTION are used with the safety alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices
FNCCAB
High Efficiency Filtration System
For Fan Coils
which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
These instructions cover the installation, operation and maintenance of FNCCAB High Efficiency Air Filtration System. Become familiar with the components listed in Table 1. See Fig. 2.
Table 1 – FNCCAB Major Components
COMPONENT DESCRIPTION
1 Cabinet 2 Filter 3 Access Handle 4 Access Door 5 Door Latch Hardware 6 Door Alignment Table
DESCRIPTION AND USAGE
!
CAUTION
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury and/or damage to the equipment.
Prior to installing this product, you should read these entire instructions and follow all directions.
APPLICATION
This High Efficiency Air Filtration System must be used in a forced air heating, cooling or ventilation system. This High Efficiency Air Filtration System cleaner should be installed in the system so that all the system air is circulated through this air cleaner. The High Efficiency Air Filtration System will only remove the airborne contaminants delivered to it. Maximum performance is obtained when the system blower is set for continuous operation.
.
INSTALLATION REQUIREMENTS
The location for the High Efficiency Air Filtration System is on the return side of the fan coil next to the blower compartment. In this location, both the blower motor and cooling coils will be kept clean. Do not install the air cleaner in the discharge (supply) air duct. The front of this unit must be readily accessible for periodic inspection and replacement of filter to maintain maximum efficiency and trouble--free operation.
2
3
5
1
6
AIR FLOW
4
C04033
Fig. 2 -- FNCCAB Major Components
A
B
7 "8-7/8 "
19-1/2"
22-1/4"
Fig. 3 -- FNCCAB Dimensions
Table 2 – Dimensions and Airflow
MODELS FNCCAB---0014 FNCCAB---0017 FNCCAB---0021 FNCCAB---0024
Airflow (CFM) Range 600---900 600 --- 1350 600---2000 600--- 2200
A 14---5/16 --- in (36 cm) 1 7 --- 5 / 8 --- i n (4 5 cm ) 2 1 --- 1 / 8 --- i n (5 4 cm ) 2 4 --- 5 / 8 --- i n (6 3 cm ) B 1 1 --- i n ( 2 8 c m ) 14---11/32 --- in (36 cm) 1 7 --- 7 / 8 --- i n (4 5 cm ) 21--- 11/32- --in (54 cm)
Table 3 – Typical Pressure Drop
TYPICAL PRESSURE DROP
Airflow Range
(CFM)
600 .044 .125 .060 .040 .015
800 .075 .150 .090 .060 .030 1000 .072 .250 .125 .070 .040 1200 .100 --- .180 .090 .060 1400 .092 --- .250 .140 .090 1600 .120 --- --- .187 .125 1800 .152 --- --- .230 .150 2000 .187 --- --- .280 .190 2200 --- --- --- --- .250
Typical Factory--- supplied
Filter in Fan Coil Unit
FNCCAB --- 0014 FNCCAB --- 0017 FNCCAB --- 021 FNCCAB --- 0024
Resistance (in. w.c.)
Model Number
C04031
2