Bryant FF1DNE, FF1DNA User Manual

FF1DNA,
FAN COIL UNITS
FF1D
FF1DNE
Sizes 018, 024, 030
FEATURES
The FF1DNA and FF1DNE Fan Coil units are designed as upflow indoor air handlers for split-system heat pumps and air conditioners. They are available with factory- or field-installed electric heaters both of which include the disconnect. A field­installed cooling control with disconnect is also available. A TDR (Time Delay Relay) is included with either the electric heat or the cooling control packages. The FF1DNE models are avail­able with a factory installed TXV.
This fan coil may be installed free standing, wall hung or flush mounted in the wall. The 22-in. wide cabinet size in all models allows units to fit between standard stud spacings. No return air ductwork is required if the application provides for return air in the front of the cabinet through either a louvered closet door or an optional accessory decorative grille panel.
The cabinet exterior is made of pre-painted galvanized sheet metal. The cabinet is fully insulated to meet applications in con­ditioned space. Additional insulation is required if the unit is installed in an unconditioned space. Unit is supplied with replaceable filter.
Multispeed direct-drive PSC blower motors have been selected to provide the proper air handling for both heating and cooling. Motors are suspended at 3 points on rubber grommets for qui­eter operation.
All refrigerant lines, electrical power, and thermostat wiring enter from the top of the cabinet. Sweat-type refrigerant con­nections on both liquid and suction lines make for swift, low-cost installation. All service access to the unit is conveniently located in the front.
®
The CHECK-FLO-RATER dependable refrigerant metering, and eliminates potential ser­vice requirements of other metering devices. The CHECK-FLO-
®
RATER maintenance or changeout.
In addition, units can be factory ordered with a hard shut-off thermostatic expansion valve (TXV) metering device for perfor­mance improvement.
The drain pan is constructed of high-impact, sound-deadening, corrosion-proof polyester resin. Primary and secondary drain connections exit from the bottom or either side of the cabinet.
is located inside the unit, easily accessible for piston
piston ensures efficient and
Form No. PDS FF1D.18.2
MODEL NUMBER NOMENCLATURE
F F 1 D N A 018 075
Electric Heater (kw) 000 005 075 011
Nominal Capacity (Btu) 01818,000 02424,000 03030,000
AStandard ETXV
N208/230-1-60
DMajor Series
1Upow
FThrough-the-Wall
FFan Coil
T
O
D
E
A
I
R
F
I
I
T
A
R
S
E
C
R
E
R
U
T
C
A
F
U
N
A
M
A
R
C
O
A
M
I
R
C
P
O
Y
R
A
T
I
N
U
I
S
L
N
D
Y
I
T
I
N
I
O
G
N
I
N
W
G
I
T
E
T
H
T
Q
N
U
E
I
P
M
0
1
2
D
A
R
N
A
D
T
O
D
E
A
I
R
F
I
I
T
A
R
S
E
C
R
E
R
U
T
C
A
F
U
N
A
M
A
R
C
O
M
H
P
E
A
Y
R
A
T
I
N
U
I
S
L
T
Y
P
I
U
N
M
G
P
W
I
T
H
®
E
T
Q
N
U
E
I
P
M
0
4
2
D
T
A
R
N
A
D
CERTIFICATION LISTING
TESTING INSPECTION
CERTIFICATION APPLIES ONLY WHEN THE
COMPLETE SYSTEM IS LISTED WITH ARI.
PHYSICAL DATA
MODEL FF1DNA/FF1DNE 018 024 030
Fan
Rpm (2-Speed) Motor HP (PSC)
Wheel (In.) Filter (Permanent) (In.) 16 x 20 16 x 20 16 x 20 Connections (Sweat)
Suction OD
Liquid OD
Condensate (FPT) Operating Weight
(In.) (In.) (In.)
(Lb) 76 79 82
(With Electric Heat)
NOTE: Rough-in dimensions are 38-1/4 x 22-1/4 inches.
810/750
1/12
10 x 6
5/8 3/8 3/4
980/780
1/5
10 x 6
3/4 3/8 3/4
®
1110/950
1/3
10 x 6
3/4 3/8 3/4
CLEARANCES
A minimum clearance of 21 in. is required in front of the access panels for servicing. Please note that this clearance is recommended for servicing only. Installation clearances from combustible materials are: 0 in. from cabinet and supply-air duct (plenum included). Leave adequate room for the condensate pan and refrigerant line connection.
NOTE: 22-3/4 to 24-in. on-center between-studs and 38-1/8 to 36-3/4-in. top-to-bottom inside-studs spacing.
2
NOTE:
1. SERIES DESIGNATION IS THE 14TH POSITION OF UNIT MODEL NUMBER.
15 3⁄16
1
8
2 3⁄4
3
4
4 4 3⁄16
OUTLET AIR
DIMENSIONS FF1DNA, FF1DNE
REFRIGERANT
LINES ENTRY
3
2
8
5
1
8
TOP VIEW
22 1⁄8
7
8
11
3
16
2 7⁄16
10
1
5
16
LOW VOLTAGE ENTRY ( 7⁄8″ DIA. HOLE)
POWER ENTRY
3
1
8″ DIA. KNOCKOUT
7
8″ DIA. HOLE
13
16
2
9
16
16
1
3
COIL
1
1
8″ DIA.
KNOCKOUT
3
4
1
4
3
SUCTION
TUBE
38 1⁄16
1
16
24
INLET AIR
11
5
16
5
PRIMARY DRAIN
SIDE VIEW FRONT VIEW
PATCH PLATE
FAN COIL BASE
7
16
9
11 1⁄16
11 1⁄16
BLOWER, CONTROL AND ELECTRIC HEATER ACCESS PANEL
LIQUID TUBE
UNIT CONNECTION SIZES
SUCTION, 018, 024, 030 ­LIQUID, CONDENSATE, 3⁄4″ NPT
3
8″ I.D. SWEAT
FILTER MEDIA
SECONDARY DRAIN
13
16
5
3
4″ I.D. SWEAT
BOTTOM VIEW
3
A98336
SPECIFICATIONS
UNITS WITHOUT ELECTRIC HEATERS OR CONTROLS UNIT SIZE 0180 0240 0300
RATINGS & PERFORMANCES
Nominal Capacity (Btuh)* 18,000 24,000 30,000 Nominal Airow (CFM) 650 870 1080
ELECTRICAL
Unit Volts-Phase (60 Hz) 208/2301 208/2301 208/2301 Operating Voltage Range 187—253 187—253 187—253 Internal Circuit Protection None Minimum Ampacity for Wire Sizing Minimum Wire Size 14 Maximum Fuse Size (Amps or Ckt Bkr) 15 Control Transformer 24V (Va)
INDOOR COIL
Rows & Fins Per In. 2 & 14 3 & 14 Height x Width (In.) 18 x 17.8 22 x 17.8 Face Area (Sq Ft) 2.23 2.72 R-22 Refrigerant Metering Device–FF1DNA Check-Flo-Rater R-22 Refrigerant Metering Device–FF1DNE TXV Piston Number‡ 55 63 70 Condensate Drain Connection (Pri-Sec) 3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.) 10 x 6 Filter SizeCleanable (In.) 16 x 20 x 1 Blower Motor HP 1/12 1/5 1/3 Blower Motor Speeds & Type 2 & PSC 2 & PSC 2 & PSC Full Load Amps 0.7 1.5 2.0
OPTIONAL EQUIPMENT
Cooling Control Relay-Transformer Package
(with TDR) Louvered Wall Panel with Frame (6 Pack) KFBLG0106LGL Electric Heat Package See ‘‘Optional Field-Installed Electric Heat Packages’’ Ta ble
KFDCC0101DCC
UNITS WITH FACTORY-INSTALLED ELECTRIC HEATERS OR CONTROLS SIZES 018005 018075 018011††
RATINGS & PERFORMANCES
Nominal Capacity (Btuh)* 18,000 18,000 18,000 Nominal Airow (CFM) 650 650 650 Electric Heating Output (kw @240v) 5.0 7.5 11.0 Electric Heating Capacity (MBH @208/230v) 13.5/16.3 19.9/24.2 28.9/35.1
ELECTRICAL
Unit Volts-Phase (60 Hz) 208/2301 208/2301 208/2301 Operating Voltage Range 187—253 187—253 187—253 Internal Circuit Protection None Full Load Amps 18.1/20.0 27.1/30.0 39.8/44.0 Minimum Ampacity for Wire Sizing 23.5/25.9 34.8/38.4 50.6/55.9 Minimum Wire Size 10/10 8/8 6/6 Maximum Wire Length (Ft) 112/112 118/118 125/125 Maximum Fuse Size (Amps or Ckt Bkr) 25/30 35/40 60/60 Control Transformer 24V (VA) 40
INDOOR COIL
Rows & Fins Per In. 2 & 14 Height x Width (In.) 18 x 17.8 Face Area (Sq Ft) 2.23 R-22 Refrigerant Metering Device–FF1DNA Check-Flo-Rater R-22 Refrigerant Metering Device–FF1DNE TXV Piston Number‡ 55 Condensate Drain Connection (Pri-Sec) 3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.) 10 x 6 Filter SizeCleanable (In.) 16 x 20 x 1 Blower Motor HP 1/12 Blower Motor Speeds & Type 2 (PSC) Full Load Amps 0.7
OPTIONAL EQUIPMENT
Louvered Wall Panel with Frame (6 Pack) KFBLG0106LGL Electric Heat Package See ‘‘Optional Field-Installed Electric Heat Packages’’ Ta ble
See notes on page 5.
4
SPECIFICATIONS Continued
UNITS WITH FACTORY-INSTALLED ELECTRIC HEATERS OR CONTROLS UNIT SIZE 024005 024075 024011 030005 030075 030011
RATINGS & PERFORMANCES
Nominal Capacity (Btuh)* 24,000 24,000 24,000 30,000 30,000 30,000 Nominal Airow (CFM) 870 1080 Electric Heating Output (kw @240v) 5.0 7.5 11.0 5.0 7.5 11.0 Electric Heating Capacity (MBH @208/230v) 14.0/16.9 20.4/24.7 29.4/35.7 14.3/17.2 20.7/25.0 29.7/36.0
ELECTRICAL
Unit Volts-Phase (60 Hz) 208/2301 208/2301 208/2301 208/2301 208/2301 208/2301 Operating Voltage Range 187—253 187—253 187—253 187—253 187—253 187—253 Internal Circuit Protection None Full Load Amps 18.1/20.0 27.1/30.0 39.8/44.0 18.1/20.0 27.1/30.0 39.8/44.0 Minimum Ampacity for Wire Sizing 24.5/26.9 35.8/39.4 51.6/56.9 25.2/27.5 36.4/40.0 52.3/57.5 Minimum Wire Size 10/10 8/8 6/6 10/10 8/8 6/6 Maximum Wire Length (Ft) 112/112 117/117 122/122 112/112 117/117 125/125 Maximum Fuse Size (Amps or Ckt Bkr) 25/30 40/40 60/60 30/30 40/40 60/60 Control Transformer 24V (Va) 40
INDOOR COIL
Rows & Fins Per In. 3 & 14 Height x Width (In.) 18 x 17.8 22 x 17.8 Face Area (Sq Ft) 2.23 2.73 R-22 Refrigerant Metering Device-FF1DNA Check-Flo-Rater R-22 Refrigerant Metering Device-FF1DNE TXV Piston Number 63 70 Condensate Drain Connection (Pri-Sec) 3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.) 10 x 6 Filter SizeCleanable (In.) 16 x 20 x 1 Blower Motor HP 1/5 1/3 Blower Motor Speeds & Type 2 (PSC) Full Load Amps 1.5 2.0
OPTIONAL EQUIPMENT (P/Ns)
Louvered Wall Panel with Frame (6 Pack) KFBLG0106LGL Electric Heat Package See ‘‘Optional Field-Installed Electric Heat Packages’’ Ta ble
* Rated in accordance with U.S. Government DOE test procedures and/or ARI Standard 210/240-94.
Use copper wire only. Use 75°C in this application. When using non-metallic (NM) sheathed cable, wire size required should be based on that of 60°C con-
ductors, instead of wire sizes shown in table above per NEC 1996 Article 336-30. Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
Check outdoor unit for required piston size.
†† 018 Size with 11-kw heater not approved for use with heat pumps.
5
BF
COOLING CAPACITIES (MBtuh)
EVAPORATOR
UNIT SIZE
018
024
030
AIR
CFM and
BF
400 27 23 19 25 20 16 22 17 13 19 14 10 15 10 8
0.08 500
0.10 600 33 27 22 30 24 19 26 21 16 23 17 13 18 12 11
0.13 650 34 28 23 31 25 20 27 21 17 23 17 14 18 13 12
0.14 600 38 32 26 35 29 22 31 24 18 26 19 14 21 13 12
0.05 700 41 34 28 38 30 24 33 26 20 28 20 16 22 15 13
0.06 875 46 38 31 41 34 27 37 29 22 31 23 19 25 17 16
0.08 750 46 38 31 41 33 26 36 28 21 30 22 17 24 16 14
0.04 900 50 42 34 46 37 29 40 31 23 33 25 19 26 18 16
0.06
1075 54 45 37 49 40 32 43 34 26 37 27 22 29 19 18
0.07
* Saturated suction leaving evaporator coil.
Sensible Heat Capacity (1000 Btuh) Gross Cooling Capacity (1000 Btuh)
Bypass Factor
NOTES:
1. Net capacities shown include a deduction for evaporator fan motor heat.
2. Contact manufacturer for cooling capacities at conditions other than shown in table.
3. Formulas:
Leaving db = entering db
Leaving wb = wb corresponding to enthalpy of air leaving coil (h
h
= h
lwb
where h
total capacity (Btuh)
ewb
= enthalpy of air entering coil.
ewb
4.5 x CFM
35 40 45 50 55
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
13 14 15 12 13 13 10 11 12 9 10 10 8 8 8 30 25 21 28 22 18 24 19 15 21 15 12 16 11 10 14 16 17 13 14 16 12 13 14 10 11 12 9 10 10
15 17 19 14 16 18 13 14 16 11 13 13 10 11 11
16 18 20 14 17 18 13 15 16 12 13 14 10 11 12
18 20 21 16 18 19 15 16 17 13 14 14 11 11 12
19 21 23 18 19 21 16 18 19 14 15 16 12 13 13
21 24 27 20 22 24 18 20 22 16 18 19 14 15 16
21 23 25 19 21 22 17 19 20 15 16 17 12 13 14
23 26 28 21 23 25 19 21 22 17 18 19 14 15 16
25 28 31 23 26 28 21 23 25 18 21 22 16 17 18
sensible heat cap.
1.09 x CFM )
lwb
COIL REFRIGERANT TEMPERATURE* (°F)
Evap AirEntering Wet-Bulb Temp (°F)
4. Direct interpolation is permissible. Do not extrapolate.
5. SHC is based on 80°F db temperature of air entering coil. Below 80°F subtract (corr factor x CFM) from SHC.
Above 80°F db, add (corr factor x CFM) to SHC.
SHC CORRECTION FACTOR
ENTERING AIR DRY-BULB TEMP (°F)
79 78 77 76 75 Under 75
BYPASS FACTOR
0.10
0.20
0.30
Interpolation is permissible. Correction Factor = 1.09 x (1 – BF) x (db – 80)
81 82 83 84 85 Over 85
Correction Factor
0.98
1.96
2.94
3.92
0.87
0.76
1.74
1.53
2.62
2.29
3.49
3.05
4.91
4.36
3.82
Use formula
shown below
OPTIONAL FIELD-INSTALLED ELECTRIC HEAT PACKAGES FOR FF1DNA AND FF1DNE
HEATER PART NUMBER
WITH TDR
SIZE
USED
WITH
KFDEH0801D05 All 5 208/2301 14.3 17.2 7 KFDEH0901D75 All 7.5 208/2301 20.7 25.0 7 KFDEH1001D11 All 11 208/2301 29.7 36.0 7
* Heater capacities shown here are for the largest size fan coil unit, and they do include blower motor heat.
NOMINAL
KW @
240V
HEATER
VOLTS—PHASE
(60 Hz)
6
HEATER
CAPACITY
(MBH)*
APPROX
SHIP.
WEIGHT
(lbs)208V 230V
AIR DELIVERY (CFM) AT INDICATED EXTERNAL
STATIC PRESSURE AND VOLTAGE
EXTERNAL STATIC PRESSUREIN. WC
UNIT
SIZE
018
024
030
NOTE: Data reects a dry coil, lter, and 11-kw electric heater installed.
BLOWER MOTOR
SPEED
High 610 720 580 665 540 610 475 540 380 415
Low 480 580 450 545 415 500 375 430 320 340
High 895 985 860 955 825 915 785 865 730 805
Low 650 740 620 710 585 680 550 640 510 600
High 1160 1190 1105 1135 1050 1080 990 1020 935 960
Low 885 1025 870 985 835 940 810 890 770 840
0.1 0.2 0.3 0.4 0.5
208V 230V 208V 230V 208V 230V 208V 230V 208V 230V
AIR DELIVERY PERFORMANCE CORRECTION
COMPONENT PRESSURE DROP (IN. WC) AT INDICATED AIRFLOW
AIR DELIVERY (CFM) 400 500 600 700 800 900 1000 1100
1-Element Electric Heaters
Dry-to­Wet Coil
Subtract the above pressure drop corrections from unit airow data when that component or condition is used. The remaining external static pressure will be available for the duct system.
5 kw
2-Element
7.5 & 11 kw 018 0.019 0.029 0.036 0.043 ——— 024 ——0.030 0.039 0.051 0.062 0.076 030 ————0.058 0.070 0.082 0.091
0.007 0.010 0.015 0.025 0.035 0.055 0.070 0.080
0.010 0.012 0.018 0.028 0.050 0.075 0.100 0.130
ESTIMATED SOUND POWER LEVEL (dBA)
CONDITIONS OCTAVE BAND CENTER FREQUENCY*
UNIT SIZE
FF1-018 600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7 FF1-024 800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0 FF1-030 1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0
* Estimated sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook,
Chapter 52, p. 52.7.
CFM
Ext Static
Pressure 63 125 250 500 1000 2000 4000
OTHER ACCESSORIES
KIT NUMBER DESCRIPTION USED ON SIZES
KFDCC0101DCC Cooling Control Package All
KFBLG0106LGL* Louvered Wall Panel with Frame All
* 6 pack
7
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
Unit Familiarization Maintenance
Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Cancels: PDS FF1D.18.1
Form PDS FF1D.18.2
© 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 PRINTED IN U.S.A. Catalog No. 12FF-1D1 1-03
8
Loading...