Bryant fe4anf005, FE4A Installation Instructions Manual

COMMUNICATING VARIABLE SPEED FAN COIL PURON® REFRIGERANT
PREMIUM ENVIRONMENTALLY SOUND
The FE4A is the premium air handler combining the proven technology of Bryant fan coils with the environmentally sound refrigerant, Puron®. The FE4A achieves an operation advantage because the ECM (Electronically Commutated Motor) combined with a Quantum Plus heat pump with Puron is highly efcient at all possible operating speeds, and delivers the precise amount of airow desired over a wide range of duct static pressure conditions.
The FE4A comes with state of the art smart diagnostics capability. This enables faster troubleshooting providing ease of service and repair. The FE4A also provides a 4-wire hook up with matching outdoor unit and the Evolution Control. This makes installation simpler and a lot quicker than with conventional fan coils. The FE4As advanced technology allows the fan coil to self-congure with a matching outdoor unit and the Evolution Control, cutting down on installation time.
Other features homeowners appreciate are quiet operation of the FE4A, including the soft ramp up at the beginning of a heating or cooling cycle, and its soft ramp down when the duty cycle is complete. Annoying sounds from sudden changes in airow are reduced for worry free comfort. When used in continuous fan mode, the FE4A can operate quietly at very low levels of airow for gentle reduction of temperature differences between areas of the home and within each individual room from oor to ceiling. In addition, when used in conjunction with Bryant air cleaners, the FE4A provides continual cleansing of the air while quietly operating in continuous fan duty, for the best in indoor air quality.
The FE4A is loaded with other popular features. The Thermostatic Expansion Valve (TXV) reliably meters refrigerant at all operating conditions during cooling mode providing excellent compressor protection. Grooved copper tubing, louvered aluminum ns, and the large face areas of the FE4A refrigerant coils provide superior efciency, for high SEER and HSPF performance. Robust, corrosion resistant and highly draining condensate pans provide for excellent condensate control. All components are protected within a rugged, prepainted metal cabinet lined with super thick, high density insulation and vapor barrier. The unit exterior features sweat
A02332
refrigerant connections for simple leak free performance, multiple electrical entry for both high and low voltage service to simplify installation. Field-installed heaters are also available, ranging from 5-kw to 30-kw.
For the best in efciency and Environmentally Sound operation, comfort, ease of installation and reliable performance, the FE4A cant be beat.
MODEL FE4A
FE4A
FAN COIL
Form No. PDS FE4A.18.1
FEATURES
Smart Diagnostics
Self conguring (ease of installation)
Easier troubleshooting, providing faster service and repair.
Puron®, Environmentally Sound Refrigerant
Puron-ready TXV
Efcient ECM makes the most of the outdoor units performance capabilities
Static pressure-adapting ECM for dependable airow
Large, grooved tube, louvered n coils
Unique cabinet design that meets new stringent regulations for air leakage. Meets requirements of a 2% cabinet leakage rate when tested at 1.0 inches of static pressure
Dedicated refrigerant circuits
Efcient, quiet, time tested blower housings and diffusers
Sturdy, drainable condensate pans
Brass drain connections
Tested for condensate disposal in conditions more rigorous than Air Conditioning and Refrigeration Institute requirements
Super thick insulation with vapor barrier
Galvanized, pre-painted cabinet
Installation-exible, multipoise units
Horizontal hanging provisions on cabinet
Factory-supplied, cleanable and reusable lter
Newly improved lter rack-lter insulation added for an improved air seal.
No tools required to service lter
5- through 30-kw accessory heaters
Easy plug in heater installation
Ready for humidier
Entry options for high and low voltage wiring hook-up
Simple, 5-amp blade fuse (and a spare) to protect 40 VA transformer
Easy coil inspection (removable, snap-in plug on A-coil models)
Leak-preventing sweat connections
Cabinet construction features innovations designed to prevent cabinet sweating
2 through 5 ton coverage
MODEL NUMBER NOMENCLATURE
F E 4 A N F 002 000 A A A A
Fan Coil Variations
Premium Puron Variations
Multipoise Series
Series Variations
Electrical 208/230/1 Heating Size (kw)
FSingle Piece Cabinet with 1-in. Thick Insulation BBoth Modular and 1-in. Thick Insulation
REGISTERED
QUALITY SYSTEM
2
Size Designation 002 005 003 006
T
O
D
E
A
I
R
F
I
I
T
A
R
S
E
C
R
E
R
U
T
C
A
F
U
N
A
M
A
R
C
O
A
M
I
R
C
P
O
Y
R
A
T
I
N
U
I
S
L
N
D
Y
I
T
I
N
I
O
G
N
I
N
W
G
I
T
E
T
H
T
Q
N
U
E
I
P
M
0
1
2
D
A
R
N
A
D
T
O
D
E
A
I
R
F
I
I
T
A
R
S
E
C
R
E
R
U
T
C
A
F
U
N
A
M
A
R
C
O
M
H
P
E
A
Y
R
A
T
I
N
U
I
S
L
T
Y
P
I
U
N
M
G
P
W
I
T
H
®
E
T
Q
N
U
E
I
P
M
0
4
2
D
T
A
R
N
A
D
CERTIFICATION APPLIES ONLY WHEN THE
COMPLETE SYSTEM IS LISTED WITH ARI.
SPECIFICATIONS
MODEL FE4A
SIZE 002 003 005 006*
SHIPPING WEIGHT (Lb) 135 150 172 207 REFRIGERANT Puron (R-410A)
Refr. Metering Device TXV Size 2 Ton3 Ton4 Ton4 Ton
COIL
Type A Slope A A Rows - Fins/In. 3 - 14.5 Face Area (sq-ft) 3.46 3.46 5.93 7.42
MATCHES OUTDOOR UNIT SIZES Nominal Cooling Tons 1.5, 2, 2.5, 3 2, 2.5, 3, 3.5 2.5, 3, 3.5, 4 3, 3.5, 4, 5
FAN
Upow, Downow, HorizontalAir Discharge
CFM/TON (Nominal) 350+ MOTOR HP (ECM) 1/2 1/2 1/2 3/4 FILTER 21-1/2 x 16-3/8 21-1/2 x 18-7/8 21-1/2 x 18-7/8 21-1/2 x 23-5/16
* Modular Unit + Nominal airow = outdoor unit size (tons) x 350 cfm. Airow may be modied by system operating mode.
3
A02321
DIMENSIONS
ABCDEH J
In. In. In. In. In. In. In.
002 42-11/16 17-5/8 15-3/4 15-5/8 10-3/4 ——
003 53-7/16 21-1/8 19-1/4 19-1/8 19-3/16 19
005 53-7/16 21-1/8 19-1/4 19-1/8 19-1/2 ——
006 59-3/16 24-11/16 22-3/4 22-11/16 25-1/4 34-1/16
UNIT SIZE
FE4A
4
A02322
WEIGHT
SHIPPING
DIMENSIONS Continued
F G COIL CONFIGURATION
In. In. SLOPE “A” Lb
UNIT SIZE
002 18-9/16 18-1/4 Yes 135
003 26-15/16 27-1/2 Yes 150
005 27-1/4 26-15/16 Yes 172
FE4A
006 32-15/16 32-5/8 Yes 207
5
PERFORMANCE DATA
AIRFLOW DELIVERY — COOLING, HEATING, ELECTRIC HEATING MODES
The FE4 fan coil will provide airow at a rate that is requested by the Integrated System User Interface during Air Conditioning or Heat Pump Heating (without electric heat) modes. The nominal airow for both heating and cooling modes is 350 cfm/ton nominal refrigeration size of the outdoor unit installed. The airow actually requested by the User Interface is modied by its internal algorithms for zoning, comfort or efciency concerns.
AIRFLOW PERFORMANCE - AVAILABLE EXTERNAL STATIC PRESSURE
FAN COIL
MODEL AIRFLOW DELIVERY
525 CFM
FE4ANF002
FE4ANF003
FE4ANF005
FE4ANB006
700 CFM 875 CFM
1050 CFM
700 CFM
875 CFM 1050 CFM 1225 CFM
875 CFM 1050 CFM 1225 CFM 1400 CFM
1050 CFM 1225 CFM 1400 CFM 1750 CFM
Refer to the documentation for the User Interface for more information on how the User Interface controls the fan coil. Safe operation of electric heaters requires airow delivery at or above the minimum CFM for electric heater application listed in the chart below. The fan coil will adjust its airow delivery to maintain safe airow as operating mode and staging conditions require.
AVAILABLE STATIC
PRESSURE
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
0.80 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
1.00 IN. H2O
6
PERFORMANCE DATA Continued
MINIMUM CFM FOR ELECTRIC HEATER APPLICATION
HEAT PUMP
UNIT SIZE
002
003
005
006
NOTE: Heater OnlyAir conditioner with electric heater application.
These airows are the minimum acceptable air ows as U.L. listed.
UNIT SIZE
Heater Only
018 024 030 036
Heater Only
024 030 036 042
Heater Only
030 036 042 048
Heater Only
036 042 048 060
5 9, 10 15 20 24, 30
625 650 675 850
1000
675 675
850 1025 1150
675
850 1025 1150 1325
1050 1150 1150 1325 1650
650 650 775 950
1050
725 875
950 1075 1200
725
950 1075 1200 1325
1050 1150 1150 1325 1650
CFM
Heater Size KW
825
900 1050 1125
850
1100 1150 1300
850 1100 1150 1300 1400
1050 1350 1350 1400 1650
1025
— —
1125 1225
1100
1150 1275 1400
1100 1150 1275 1400 1500
1100 1350 1575 1600 1750
— — — — —
— — — — —
1400
— — —
1600
1750
— —
1750 1750
7
0.7
0.6
0.5
0.4
ACCEPTABLE RANGE
0.3
0.2
SUPPLY STATIC PRESSURE, IN.W.C.
TOO HIGH RETURN STATIC PRESSURE (DIFFICULT TO MAKE TRAP)
0.1
0
0
0.1 0.2 0.3 0.4 0.5 0.6
RETURN STATIC PRESSURE, IN.W.C.
A96052
Acceptable Duct Conditions
For satisfactory operation (specically making dry secondary trap), subject fan coils must be installed with duct systems which fall within the Acceptable Range” illustrated above.
8
EVAPORATOR
UNIT SIZE
002
003
005
006
See notes on page 10.
AIR Cfm
500 40 32 26 36 28 22 32 24 18 27 19 14 21 13 11
0.04
650 50 40 32 45 36 27 39 30 22 33 24 18 26 17 14
0.07
875 58 49 38 53 42 32 46 35 27 39 28 22 31 20 18
0.10
1000 62 51 41 56 45 35 50 38 29 42 30 24 33 22 20
0.11
1250 67 55 45 61 49 39 54 42 33 46 34 28 37 25 24
0.13
800 59 48 38 53 42 32 46 35 24 39 27 20 30 18 16
0.20
1000 68 56 45 61 49 37 54 41 29 45 32 25 35 22 20
0.22
1200 75 62 49 68 54 42 60 45 34 50 36 29 40 25 23
0.25
1400 80 67 54 73 59 46 64 49 38 54 39 32 43 28 27
0.27
750 61 49 39 55 43 33 48 37 27 41 29 20 33 21 17
0.04
950 74 60 48 67 53 40 59 45 33 50 35 25 39 24 21
0.06
1150 89 72 57 79 63 48 69 52 38 58 41 31 44 29 25
0.07
1500 103 84 66 92 73 56 81 61 46 67 48 39 52 34 31
0.10
1700 110 89 71 99 78 60 86 65 49 72 51 42 56 37 35
0.11
1050 77 62 50 69 55 43 61 47 35 52 38 27 41 27 22
0.01
1300 100 82 65 90 71 55 79 60 45 66 47 37 49 32 27
0.02
1750 117 96 77 106 84 65 93 71 53 78 56 46 60 40 34
0.04
2050 126 103 83 114 91 71 99 76 59 84 60 50 65 44 39
0.05
2300 132 108 87 119 95 75 105 80 63 88 63 54 70 47 42
0.06
BF
PERFORMANCE DATA Continued
COOLING CAPACITIES (MBtuh)
COIL REFRIGERANT TEMPERATURE (°F)*
35 40 45 50 55
Evaporator Air — Entering Wet-Bulb Temperature (°F)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
18 18 19 16 16 17 14 14 15 12 12 13 10 10 11
21 22 23 19 20 21 16 17 18 14 15 16 12 13 14
24 26 28 22 24 25 19 21 22 17 19 19 15 16 18
26 28 31 23 26 28 21 23 25 18 20 21 16 18 20
29 33 36 27 30 33 24 27 30 22 24 26 19 21 24
28 29 31 25 27 28 22 23 24 19 20 20 16 16 16
32 34 37 29 31 33 26 28 28 23 24 25 19 20 20
35 39 42 32 36 38 29 32 33 26 28 29 22 23 23
38 43 47 35 39 43 32 36 37 28 32 32 24 26 27
27 27 28 24 25 25 21 22 22 18 18 18 15 15 15
32 34 35 29 30 31 25 26 27 22 23 23 18 18 19
37 39 41 33 35 36 29 31 32 25 26 27 20 22 22
43 46 49 38 41 44 34 37 39 29 32 33 25 27 27
45 50 53 41 45 48 36 39 42 31 34 36 27 29 30
34 36 37 31 32 33 27 28 29 23 25 24 20 20 20
42 45 47 37 40 42 33 35 37 29 31 32 23 25 24
48 53 57 44 48 52 39 43 46 34 38 39 29 31 31
52 58 63 48 53 57 43 47 51 37 42 43 33 35 35
55 62 68 50 57 61 45 51 54 40 45 46 35 39 38
9
* Saturated suction leaving evaporator coil.
Sensible Heat Capacity (1000 Btuh)
Gross Cooling Capacity (1000 Btuh)
BFBypass Factor
NOTES:
1. Net capacities shown include a deduction for evaporator fan motor heat.
2. Contact manufacturer for cooling capacities at conditions other than
shown in table.
3. Formulas:
Leaving db = entering db
Leaving wb = wb corresponding to enthalpy of air leaving coil (h
= h
h
lwb
ewb
where h
ewb
4. Direct interpolation is permissible. Do not extrapolate.
total capacity (Btuh)
= enthalpy of air entering coil.
4.5 x CFM
sensible heat cap.
1.09 x CFM
lwb
)
5. SHC is based on 80°F db temperature of air entering coil. Below 80°F subtract (corr factor x CFM) from SHC. Above 80°F db, add (corr factor x CFM) to SHC.
SHC CORRECTION FACTOR
ENTERING AIR DRY-BULB TEMP (°F)
79 78 77 76 75 Under 75
BYPASS FACTOR
0.10
0.20
0.30
Interpolation is permissible. Correction Factor = 1.09 x (1 – BF) x (db – 80)
81 82 83 84 85 Over 85
Correction Factor
0.98
1.96
2.94
3.92
4.91
0.87
0.76
1.74
1.53
2.62
2.29
3.49
3.05
4.36
3.82
Use formula
shown below
PERFORMANCE DATA Continued
ESTIMATED SOUND POWER LEVEL (dBA)*
UNIT SIZE
FE4-002
FE4-003
FE4-005
FE4-006
* Estimated sound power levels have been derived using the method described in the 1987 ASHRAE Systems & Applications Handbook, chapter 52, p. 52.7. CFM Cubic Ft per Minute ESP External Static Pressure RPM Revolutions per Minute
CONDITIONS OCTAVE BAND CENTER FREQUENCY
CFM ESP 63 125 250 500 1000 2000 4000
400 0.25 63.0 59.0 55.0 52.0 50.0 48.0 44.0 600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7 800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0 1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0 1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8 1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4
1400 0.25 63.0 59.0 55.0 52.0 50.0 48.0 44.0 1600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7 1800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0
1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0 1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8 1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4 636 0.25 65.0 61.0 57.0 54.0 52.0 50.0 46.0
400 0.25 63.0 59.0 55.0 52.0 50.0 48.0 44.0 600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7 800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0 1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0 1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8 1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4 1600 0.25 69.0 65.0 61.0 58.0 56.0 54.0 50.0
600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7 800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0 1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0 1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8 1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4 1600 0.25 69.0 65.0 61.0 58.0 56.0 54.0 50.0 1800 0.25 69.5 65.5 61.5 58.5 56.5 54.5 50.5 2000 0.25 70.0 66.0 62.0 59.0 57.0 55.0 51.0 2150 0.25 70.3 66.3 62.3 59.3 57.3 55.3 51.3
10
PERFORMANCE DATA Continued
AIRFLOW PERFORMANCE CORRECTION FACTORS
The FE4A Airow Performance table was developed using fan coils with 10-kw electric heaters (2 elements) in the units. For fan coils with heaters made up of a different number of elements, the external available static at a given CFM from the table may be corrected by adding or subtracting pressure. Use table for correction.
STATIC PRESSURE
CORRECTION (in. wc)
HEATER KW ELEMENTS
0 0 +.02 +.03
5 1 +.01 +.02
8, 10 2 0 0
9, 15 3 –.02 –.03
20 4 –.04 –.06
18, 24, 30 6 –.06 –.10
FACTORY-INSTALLED FILTER STATIC PRESSURE DROP (In. wc)
Sizes 002–005 Size 006
MODEL
FE4A
002 0.020 0.044 0.048 0.072 0.100 ————
003 0.020 0.035 0.051 0.070 0.092 ———
005 ——0.035 0.051 0.070 0.092 0.120 ——
006 ————0.070 0.092 0.120 0.152 0.187
400 600 800 1000 1200 1400 1600 1800 2000
CFM
AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (IN. WC)
AT INDICATED AIRFLOW (DRY TO WET COIL)
MODEL
FE4A
002 0.012 0.016 0.022 0.028 0.034 0.040 0.049 ———
003 0.026 0.034 0.042 0.052 0.063 0.075 0.083 0.091 0.098 0.110
005 0.006 0.008 0.010 0.012 0.015 0.017 0.020 0.023 0.027 0.030
006 0.013 0.016 0.018 0.020 0.023 0.027 0.030 0.034 0.039 0.044 0.048
NOTE: Subtract the above pressure drop corrections from unit airflow data when that component or condition is used. The remaining external static pressure
will be available for the duct system.
600 700 800 900 1000 1100 1200 1300 1400 1500 1600
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
CFM
CFM
11
1.
ACCESSORY LIST
ITEM ACCESSORY PART NO. FAN COIL SIZE USED WITH FE4A
Disconnect Kit KFADK0201DSC Cooling controls and heaters through 10-kW
Downow Conversion Kit (Slope) KFADC0201SLP 003
Downow Conversion Kit (A-coil) KFADC0401ACL 002, 005, 006
Downow Base Kit KFACB0201CFB 002
KFACB0301CFB 003, 005
KFACB0401CFB 006
Filter Kit (12 Pack) KFAFK0212MED 002
KFAFK0312LRG 003, 005
KFAFK0412XXL 006
Single-Point Wiring Kit KFASP0101SPK Only with 15- and 20-kW Fused Heaters
Airow Sensor Kit (Air Cleaner) KEAAC0101AAA All
Air Cleaner 240-Volt Conversion Kit KEAVC0201240 All
PVC Condensate Drain Trap Kit (50 Pack) KFAET0150ETK All
Downow/Horizontal Conversion Gasket Kit KFAHD0101SLP All
ACCESSORY KITS DESCRIPTION
SUGGESTED AND REQUIRED USE
Disconnect Kit
The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.
SUGGESTED USE: FE4 units with 3- through 10-kW electric resistance heaters and cooling controls.
2. Downflow Conversion Kit Fan coils are shipped from the factory for upow or horizontal-left applications. Downow conversion kits provide proper condensate water drainage and support for the coil when used in downow applications. Separate kits are available for slope coils and A-coils.
REQUIRED USE: This kit must be used whenever FE4 fan coils are used in downow applications.
3. Downflow Base Kit This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap free seal with the oor.
REQUIRED USE: This kit must be used whenever FE4 fan coils are used in downow applications.
4. Single-Point Wiring Kit The single-point wiring kit acts as a jumper between L1 and L3 lugs, and between L2 and L4 lugs. This allows the installer to run 2 heavy-gage, high-voltage wires into the fan coil rather than 4 light-gage, high-voltage wires.
SUGGESTED USE: FE4 fan coils with 15- and 20-kW fused heaters only.
5. Air Cleaner 240-Volt Conversion Kit The AIRA electronic air cleaner comes ready for 115-v operation.
REQUIRED USE: This kit is required when running 240-volt circuit to air cleaner.
6. Airflow Sensor Kit (Air Cleaner) The airow sensor kit ensures the FE4 fan coil and electronic air cleaner work as a system.
REQUIRED USE: This kit is required whenever an electronic air cleaner is used with an FE4 fan coil.
7. Fan Coil Filter Kit shipped from factory with 12 fan coil framed lters. These lters collect large dust particles from the return air entering the fan coil and prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and in turn the efciency of the system.
SUGGESTED USE: For replacing factory-supplied lters (same lters).
8. Condensate Drain Trap Kit This kit consists of 50 PVC condensate traps. Each trap is pre-formed and ready for eld installation. This deep trap helps the system make and hold proper condensate ow even during blower initiation.
SUGGESTED USE: FE4 fan coils.
9. Downflow/Horizontal Conversion Gasket Kit This kit provides the proper gasketing of units when applied in either a Downow or Horizontal application.
REQUIRED USE:
FE4 fan coils.
12
ELECTRICAL DATA
UNITS WITHOUT ELECTRIC HEATER
UNIT SIZE VOLTS-PHASE FLA
002 208/230-1 4.3 5.4 14 15
003 208/230-1 4.3 5.4 14 15
005 208/230-1 4.3 5.4 14 15
006 208/230-1 6.8 8.5 14 15
* Use copper wire only to connect unit. If other than uncoated (nonplated) 75°F ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used consult applicable tables of the National Electric Code (ANSI/NFPA 70). NOTE: If branch circuit wire length exceeds 100 ft, consult NEC 210-19a to determine maximum wire length. Use 2% voltage drop. FLA Full Load Amps
MIN
CKT
AMPS
Min Wire
Size Awg*
BRANCH CIRCUIT
Fuse/Ckt Bkr
Amps
ACCESSORY ELECTRIC HEATERS
ELECTRIC HEATERS
HEATER
PART NO.
KFCEH0501N05 5 230/1 5 None All 15,700
KFCEH0901N10 10 230/1 10 None All 31,400
KFCEH3001F15 15 230/1 5, 15 Fuses** All 47,100 5, 10, 15
KFCEH3201F20 20 230/1 5, 20 Fuses** All 62,800 5, 10, 15, 20
KFCEH2901N09 9 230/1* 3, 9 None All 28,300 3, 6, 9
KFCEH1601315 15 230/3 5, 15 None All 47,100
KFCEH3401F24 24 230/3 8, 16, 24 Fuses 005, 006 78,500 8, 16, 24
KFCEH3501F30 30 230/3 10, 20, 30 Fuses 005, 006 94,200 10, 20, 30
KFCEH2401C05 5 230/1 5 Ckt Bkr All 15,700
KFCEH2601C10 10 230/1 10 Ckt Bkr All 31,400
KFCEH3101C15 15 230/1 5, 15 Ckt Bkr All 47,100 5, 10, 15
KFCEH3301C20 20 230/1 5, 20 Ckt Bkr All 62,800 5, 10, 15, 20
* Field convertable to 3 phase.
These heaters eld convertable to single phase. Blower motor heat not included.
** Single point wiring kit required for these heaters in Canada.
KW
@ 240V VOLTS/PHASE
STAGES (KW OPERATING)
INTERNAL
CIRCUIT
PROTECTION
FAN COIL SIZE
USED WITH
HEATING CAP.
@230V‡
INTELLIGENT
HEAT
CAPABLE (KW
OPERATING)
HEATER KW PHASE
51 1/60
81 1/60
9 1/3 ——
10 1 1/60
15 1 2/30, 2/60 2/60
15 3 ——
18 3 ——
20 1 4/60 2/60
24 3/1 6/60
30 3/1 6/60
* All circuit breakers are 2 pole.
ELECTRIC HEATER INTERNAL PROTECTION
FUSES
QTY/SIZE
13
CKT BKR *
QTY/SIZE
Dual Circuit
208/230V (FT)‡‡
MAX WIRE LENGTH
Single
Circuit
Dual Circuit
208/230V
MAX FUSE/CKT BKR AMPS
Single
Circuit
Dual Circuit
208/230V
BRANCH CIRCUIT
MIN GND WIRE SIZE
Single
Circuit
208/230V (FT)‡‡
MAX WIRE LENGTH
208/230V
MAX FUSE/CKT BKR AMPS
208/230V
MIN GND
WIRE SIZE
Dual Circuit
208/230V††
MIN WIRE SIZE (AWG)
Single
Circuit
Electric Heater Electrical Data
Dual Circuit
208/230V**
MIN AMPACITY
Single
Circuit
Dual Circuit
208/230V
HEATER AMPS
Single
Circuit
CIRCUIT
INTERNAL
PROTECTION
PHASE
208/230V††
MIN WIRE SIZE (AWG)
208/230V**
MIN AMPACITY
Field Multipoint Wiring of 24-and 30-kW Single Phase
208/230V
HEATER AMPS
PHASE
KW
HEATER
3 2.3 1 None 10.9/12.0 ——15.9/17.3 ——12/12 ——12/12 ——20/20 ——67/68 ——
240v 208v L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4
PART NO.
KFCEH0401N03
5 3.8 1 None 18.1/20.0 ——26.0/28.4 ——10/10 ——10/10 ——30/30 ——66/66 ——
5 3.8 1 None 18.1/20.0 ——31.2/33.5 ——8/8 ——10/10 ——35/35 ——85/88 ——
1
2
1
KFCEH0501N05
KFCEH0501N05
9 6.8 3 None 18.8/20.8 ——32.0/34.5 ——8/8 ——10/10 ——35/35 ——83/85 ——
5 3.8 1 Ckt Bkr 18.1/20.0 ——26.0/28.4 ——10/10 ——10/10 ——30/30 ——66/66 ——
5 3.8 1 Ckt Bkr 18.1/20.0 ——31.2/33.5 ——8/8 ——10/10 ——35/35 ——85/88 ——
9 6.8 1 None 32.8/36.0 ——49.5/53.5 ——8/6 ——10/10 ——50/60 ——54/87 ——
2
KFCEH2401C05
KFCEH0901N10 10 7.5 1 None 36.2/40.0 ——53.8/58.5 ——6/6 ——10/10 ——60/60 ——78/80 ——
KFCEH2401C05
KFCEH2901N09***‡
KFCEH3001F15*** 15 11.3 1 Fuse 54.2/59.9 36.2/40.0 18.1/20.0 76.3/83.4 53.8/58.5 22.7/25.0 4/4 6/6 10/10 8/8 10/10 10/10 80/90 60/60 25/25 88/89 78/80 75/76
KFCEH3101C15*** 15 11.3 1 Ckt Bkr 36.2/40.0 18.1/20.0 53.8/58.5 22.7/25.0 6/6 10/10 10/10 10/10 60/60 25/25 78/80 75/76
KFCEH2701C15*** 15 11.3 1 Ckt Bkr 36.2/40.0 18.1/20.0 53.8/58.5 22.7/25.0 6/6 10/10 10/10 10/10 60/60 25/25 78/80 75/76
KFCEH1601315 15 11.3 3 None 31.3/34.6 ——47.7/51.8 ——8/6 ——10/10 ——50/60 ——56/90 ——
KFCEH3201F20*** 20 15.0 1 Fuse 72.3/79.9 36.2/40.0 36.2/40.0 98.9/108.4 53.8/58.5 45.3/50.0 3/2 6/6 8/8 8/6 10/10 10/10 100/110 60/60 50/50 85/109 78/80 59/59
KFCEH2601C10 10 7.5 1 Ckt Bkr 36.2/40.0 ——53.8/58.5 ——6/6 ——10/10 ——60/60 ——78/80 ——
24 18.0 1 Fuse 86.7/95.5 ——116.9/127.9 ——1/1 ——6/6 ——125/150 ——115/116 ——
24 18.0 3 Fuse 50.1/55.4 ——71.2/77.8 ——4/4 ——8/8 ——80/80 ——94/95 ——
KFCEH3301C20*** 20 15.0 1 Ckt Bkr 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 6/6 8/8 10/10 10/10 60/60 50/50 78/80 59/59
KFCEH2801C20*** 20 15.0 1 Ckt Bkr 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 6/6 8/8 10/10 10/10 60/60 50/50 78/80 59/59
KFCEH3401F24†***
14
30 22.5 3 Fuse 62.6/69.2 ——86.8/95.0 ——3/3 ——8/8 ——90/100 ——97/98 ——
30 22.5 1 Fuse 109.0/120.0 ——144.8/158.5 ——0/00 ——6/6 ——150/175 ——117/150 ——
KFCEH3501F30†***
KW
HEATER PART NO.
240V 208V L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6
Field convertible to 1 phase, single or multiple supply circuit.
KFCEH3501F30†*** 30 22.5 1 36.2/40.0 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 45.3/50.0 6/6 8/8 8/8 10/10 60/60 50/50 50/50 78/80 59/59 59/59
Field convertible to 3 phase.
KFCEH3401F24†*** 24 18.0 1 28.9/32.0 28.9/32.0 28.9/32.0 44.7/48.5 36.2/40.0 36.2/40.0 8/8 8/8 8/8 10/10 45/50 40/40 40/40 59/60 73/73 73/73
1. For fan coil sizes 018-036.
2. For fan coil sizes 042-060 and all FE4A sizes.
3. Single circuit application of F15 and F20 heaters requires single-point wiring kit accessory.
(ANSI/NFPA 70).
** Includes blower motor amps of largest fan coil used with heater.
†† Copper wire must be used. If other than uncoated (non-plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code
‡‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
*** Heaters are Intelligent Heat capable
NOTES:
15
HEAT PUMP
MATCHED SYSTEM
VENTILATOR PLUS
ZONE PERFECT
PLUS
EQUIPMENT CONTROLLER
HUMIDIFIER
FAN COIL
ELECTRONIC AIR CLEANER
A02295
© 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 12FE-4A0 12-03
16
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Cancels: New
Form PDS FE4A.18.1
Loading...