• Electrical Operating Sequences and Troubleshooting
, i SAFETY CONSIDERATIONS
Ij^proper installation, adjustment, alteration, service, maintenance,
of use Can cause explosion, fire, electrical shock, or other
conditions which may cause personal injury or property damage.
CpnSult a qualiSed installer, service agency, or your distributor or
blknch for information or assistance. The qualified installer or
agency must use factory-authoriied kits or accessories when
modifying thiS;pfoduct. Refer to the individual installation instruc
tions packaged With the kits or accessories for detailed informa
tion..
Follow all Safety codes. Wear safety glasses and work gloves. Use
quenching cloth for bracing operations. Have fire extinguisher
avmlable. Read these instructions thoroughly and follow all
warnings or cautions attached to the unit. Consult local building
m'dës and National Eectricai Code (NEC) for special installation
requirements-
It is important to recognize safety information. This is the
safety-alert symbol^j^ , When you sec this symbol on the unit or in
instructions and manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, and CAU
TION. These words are used with the safety-alert symbol, DANGER identifies the most serious hazards which will result in severe
^I3anc0ls; SM03-1
Fig. 1—Typical Fan Coll
...............................
SM03-2
1-1-95
A9£071
24-29
-1-
V, ■../.
■:i^
.^.■■■' 'i.
■'r ' •i ' -;r*;'ii.M *■
: ■'■ —V r:^- ■: ~J
-■■;'■■: le :'- '- v -i:
i-'-
I • L ■ - . ■ --Ji- S..',
t-o
CTJ
CTJ
oo
■=:
C3
LjO
-c
s
o
•TrJ
>=-
X
2jitl- Position—Fan CoiF
A- RNC
B-Standard
C - Deluxe
D - Furred in, Cased
E - Furred in. Uncased'
F - Through Ihe Wall
G- Commercfal
H - Standard .Electric Fumaoe
personal injury or death. WARNING signifies hazards which
could result in personal ityury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
INTRODUCTION
The "F" Scries fan coil units arc designed for flexibility in a variety
of applications, meeting upflow, horizontal, or downflow require
ments. Units are available in 1-1/2 through 5 ton nominal cooling
capaddes. Factory-authorized, field-installed electric heater pack
ages are available in 3 through 30 kilowatts.
WARNING: Before installing or servicing fan coil,
always turn off all power to unit. There may be more than
A
1 disconnect switch. Turn off accessory heater power if
applicable. Electrical shock can cause personal injury or
death.
UNIT IDENTIFICATION
The 16 position numbering chart allows identification of all
available fan coil units, (See Fig. 2.)
FA4A, FB4A, FC4B, AND FR4A CIRCUIT BOARD
FUNCTION AND TROUBLESHOOTING
This section of the service manual describes the CES0130003
PCB by examining the functional operation of the PCB compo
nents.
I. PRINTED CIRCUIT BOARD (PCB) COMPONENT
LAYOUT AND DESCRIPTION
Layout of the actual PCB is depicted in Fig. 3.
L The low-voltagc ¡stripped leads are used to connect the 24-v
side of transformer
to indoor thermostat and outdoor
section.
-3-
F A X N o , 3 1 7 2 4 0 5 6 6 2
Multipolar
Multlpolne
50 Hz
MuitipoiSQ
50 Hz
Multipoise
HIGH
SPEED
Black
—
MEDIUM
SPEED
—
—
———
LOW
SPEED
'Blue
RedViolet
2. A 5-amp fuse is used to protect the low-voltagc transformer
secondary.
3. The fan relay is controlled by thermostat and turns fan on
and off,
4. A plug is used as the connection for PCB power and electric
heaters. Note the pin numbers on plug,
5. A time-delay relay circuit keeps fan motor running for 90
sec after G is dc-energiied.
II. UNIT FUNCTIONS
A- Transformer
1. Proper Wiring of Transformer Primary or High Side
Yellow wire from Molex plug is wired to C terminal on
transformer and black wire from PCB relay (normallyopeij) terminal is wired to 2Q5V or 230V terminal on
transformer. Units are factory wired at 230V terminal
2. Proper wiring of Transformer Secondary or 24-v Side
Red wire of transformer is wired to T terminal on PCB and
brown wire of transformer is wired to C terminal on PCB.
NOTE: T terminal on PCB is used to protect transformer. T
terminal is connected through the fuse to R terminal on PCB.
B. Indoor Fan
1. Wiring
Indoor fan motor yellow lead is wired to C terminal on
transformer. The red, blue, or black speed lead is wired to
5PT terminal On fan relay part of PCB. Units are factory
wired on medium speed (blue lead connected),
NOTE: Unused fan speed leads must be capped or taped off to
prevent direct short to cabinet surface.
Single Piece
Modular
Single Piece
Single Piece
Single Piece
Single Piece
COMMON
Yellow
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 5
UTC TECH PUB
FIg. 3—Fan Còli
2. Functional Control
a. Thermostat and Relay Control
When thermostat calls for the fan in cooling, heat pomp,
heating, or fan-only mode, a 24-vdc signal is sent to
relay. This causes the relay to close its nonnally-opcn
contacts, turning On fan. When thermostat no longer calls
for the fan, the signal sent to relay is turned off and relay
opens causing fan to turn off after a 90-sec fan-off delay,
b. Sequencer Interlock
The fan will also Operate whenever there is a call for
electric heat, even if fan relay is nOt energized. This
happens because fan is interlocked with first stage of
electric heat through the normally-dosed contact of fan
relay.
NOTE: The fan interlock is only connected to first stage electric
heat W2, W3 and E do not contain an interlock with fan. See
outdoor thermostat Installation Instructions when electric heat
Staging is desired;
C. Electric Heat
When thermostat calls for electric heat, a 24-vac signal is sent to
PCB through WZ, causing first stage to turn on. W3 and E also
receive signal if wired in with WZ. The signal sent to WZ causes
J5r$t stage to turn on. If W3 and E arc not wired to W2, the
sequencers can be controlled individually to stage additional
electric heat. The sequence control is described in the following
Section;
1. W2
When thermostat sends a signal to WZ, a Z4-vac signal is
applied across sequencer number f, causing it to close after
a short delay. When sequencer number 1 closes, first stage
of electric heal is energized. In straight electric heat, fan is
also energized through the nonnally-doscd contacts of fan
relay. In cooling, heat pump, or manual fan mode, fan will
already be running since fan relay would have been
energized. When thermostat stops calling for electric heat,
the 24-'Vac signal to sequencer number 1 turns off and
sequencer opens after a delay of 60 to 90 sec. When
sequencer opens, first stage of heat turns off along with fan,
providing thermostat is not calling for the fan.
2. W3
When a signal is sent to W3, a 24-vaO Signal to sequencer
number 2 causes sequencer to dose, with Second stage of
electric heat turning on after a short delay. The 24-vac
F A X N o , 3 1 7 2 4 0 5 6 6 2
PCB BLOCK WIRINS
LOW
VOLTAGE
FUSE
Printed-Circuit Boafd , 2
-4-
signal applied to sequencer number iJ chuses fan -tb;opkate.
Timing is Such that'sequchc'or liuinB'if FWiIf'iiirn:tii.h:'before
sequencer number 2. Whem, sigriifl to'WS' is turned off,
sequencer number 2 op,ens;;^^aiter a short 'delay. tf^.W^Z is also
satisfied, first stage of.,dectriC'heat and^-fimwiy ais^o tum
off, providing thermostat is not calling for the fan.
3, E ■'
When thermostat ..sends, a signal :iDrB^ ' a' 24-v~ac signalris sent
to sequencer number 3, The 24^Wc; sighhl' applied to
sequencer number 3 turns" on third'stagcof'clcctric heat.
The 24-vac signal applied to sequencer number 1 turns on
first stage of electric heat'arid fan. ’^hen 'thermostat stops
calling for electric heat,' the signartO'Sequ£d£efs I, 2, and 3
are turned off/^ahd sequdhfcefs b'|fieh;'''Th'il5''caii&es''dw^
heat to turn off with fan providihg'lheriniti^Iat'i^'hdt calling
for the fan, ^ ^ .
NOTE: Electric heaters are factory wired with alj stages tied
together. If independent staging is desired, cpnsul|, outdoor ther^
mostat Installation Instructions. ./
III. TROUBLESHOOTING PCB . ■ > 2
Use wiring schematic shown in Fig, 4 as a guide in troubleshooting
PCB unless otherwise notedv ■ ■ —
A. If Fan Will Not tum On ffom TherWost^i: ' ^
IF THERE IS NO HIGH VOLTAGE TO PCB:
1. Check plug/receptacle connection. This supplies power
from heaters to PCB. Be sure plug is connected properly.
, 2-, Check sequencer number X and plug wiring. Yellow, wire
should be connected to pin number 9 of plug and to limit
switch. Black wire should be Connected to pin number 7 of
plug and to sequencer number 1.
3. Check power leads Cl and L2. tf these are not receiving
power, system cannot function.
IF PCB HAS HIGH VOLTAGE APPLIED TO IT;
1, Check low-voltagc transformer leads R (red) and C
(brown). Be sure they are wired to correct locations,
2. Check output voltage of transformer secondary side R (red)
and C (brown). Be sure transformer output is between IS
and 30 vac. If transfbmicr output is incorrect and transfonner is reqeiving correct input voltage (208v or 230v),
then transformer needs to be replaced with recommended
transformer. If no problem exists with transformer secondary, proceed to items 3 and 4.
A9434S
A Ï Ï G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 6
UTC TECH PUB
) . 3 1 7 2 4 0 5 6 6 2
P ,
f THIS COMPARTMENT MUST BE CLOSEP EXCEPT TOR SERVICING
1 BLOWER MOTOR |
.„.J ROTATION
CboKW 1PH SCHEMATIC DIAGRAM)
NOT SUITABLE FOR Ü5É ON SYSTElilS EXCEEOINS
leovTO GROUND
USE COPPER WIRE (/S'C MIN) ONLY BETWEEN D[SCCNNECT 3WIT01 AND UNFT,
TO BE WIRED IN ACCORDANCE WITH NEC AND UDCALOODES,
i, TRANSPORMER PRIMARY LEADS, BLUE 20aV, RED 230V.
A IF ANY OFTHE ORIGINAL WIRE, AS 5UPPUED. MUST BE REPLACED,
USE THE SAME OR RQUIVACPJTTYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
20KW HEATER USES ONE DOUSLg POLE LS ON MIDDLE TOP ELEMENT.
10, Й4 AND 30KW HEATERS USE СЮиВ1^ POLE UHIT SWITCHES.
LARGEST HEATERS ARE SHOWN, SMALLER HEATSR5 Will HAVE FEWER ELEMENTS AND
COMPONENTS.
1 PHASE HEATERS ARE SHOWN WIRED FOR 8INSL£ SUPPLY CIRCUIT.
10. USE SO AMP CLA38 К FUSSS ONLY. FOR REPLACEMENT.
11, (3) SPEED MOTOR SHOWN. OPTIONAL (2) SPEED MOTOR иЗЕЗШ(ВЦ^ AND LOW
(BLU OR RED).
13, CONNECT fi TO R, S TO G, ETC.. SEE OLnDOQR INSTRUCTION FOR DETAILS,
la. IF WIRE CRIMP IS REMOVED AN EMEHOENCV HgATftgUY 16 REQUIRED.
(SEE OUTDOOR-THERMOSTAT (NSTRUCTIOMS)
3, Check low-voltage fuse shown in Fig. 3. Jf fuse is blown,
replace it. The transformer cannot supply power to board
with fuse bjowfl or loose. If fuse blows when unit has pow‘er
applied to it, the systejs most likely has 1 of the following
problems:
a. Check all 24-v wiring for an electrical short.
b. The maximum load on transfonner is 40 va. If load ott
transformer is excessive, the low-voltage 5-anjp fuse
will blow to protect transformer. If load exceeds va
rating of transformer, a larger va rated transformer needs
to be installed. Check sequencers for excessive current
draw.
32121A-101 REV. C
pig. 4—^Wiring Diagram
4. Check connections on primary side of transfonner. If they
■ 9 ■■ '■■ ■ 1
C, Check wiring of heaters. If a heater is miswired, fuse
arc not connected properly, the low-voltage terminal board
cannot supply the 24-v signal to energize fan relay. If
transfonner is receiving correct primary voltage hut is not
putting out correct secondary voltage, transformer needs to
be replaced.
1
2DB;S4aVACJ 24VAC 24VAC
may blow. If a heater is miswired, correct miswiring by
comparing it to heater wiring label.
3^ 6
1 4
A9434G
-5-
AÏÏG/14/2008/THÜ 03:46 PM UTC TECH PUB
FAX No. 317 240 5662
P. 006
fe. If Electric Hegt Stages Will Not Turn On But Fan Will
Turn On:
IF THERE IS NO HIGH VOLTAGE TO PCB:
1. Check plug connection between heaters and board. This
supplies power to transformer and fan. Be sure plug is
connected properly.
2. Check sequencer number 1 and plug wiring. Yellow wire
should be connected to pin number 9 of plug and to limit
switch. Black wire should be connected to pin number 7 of
plug and to sequencer number 1-
3- Check incoming high-voltage power leads, tf these arc not
receiving power, system c&undt function.
IF PCB HAS HIGH VOLTAGE APPLIED TO IT;
1, Check low-voltage transformer leads R (red) and C
(brown). Make sure they are wired to correct location. The
unit will not function without proper connections.
2. Check output voltage of transformer secondary side R (red)
and C (brown). If transformer output is low (less than 18
vac), reifer to items 3 and 4 of previous If PCB Has High
Voltage Applied To It section.
IF TRACES ARE OVERHEATED ON BACK OF PCB:
Usually whenever a trace is blown on PCB, it means cither there
has been a high-voltage short or high voltage has been applied to
low-voltage circuit. This can be prevented by making sure PCB is
wired correctly before PCB has power applied to it,
C, If PCB Fuse Keeps Blowing:
When loW“Voltage fuse blows, it means transformer would have
blown if fuse had riot been in circuit to protect it. The fuse usually
blows when there is a high Current draw on transformer, high
voltage applied to low-voltagc circuit, Or a direct secondary short.
When there is a high current draw on transformer, it is most likely
because transformer has been shorted or system is trying to draw
more va than transformer rating allows. When fuse blows because
of high voltage, the system has mixed high- and low-voltage
signals.
1. Check wiring of sequencers as shown in Fig. 4, Be sure
transformer is not shorting out because thermostat wires arc
miswired.
2. Check wiring of sequencers as shown in Fig. 4. Be sure
low-voJtagc and high-voltage wiring is connected to proper
sequencers.
3. Check va draw on transformer. If va draw is more than va
rating of transformer, fuse will blow. If this is the case,
replace transformer with one that has a higher va rating and
meets system spccifícationS-
D. If F^n Runs Continuously:
1. If PCB has no low-vohage power, check blue and black fan
leads. These may be switched at sequencer,
2. If PCB has lowwoltage power, check fan relay to see if it is ,
opening and closing. It may be stuck in the normally-closed
position due to debris in relay.
E- Transformer Failure:
1. Check 208-v and 230-v transformer connections. They may
be miswired.
ELECTRIC HEATER FUNCTION AND
TROUBLESHOOTING
This section describes KFA and KFB series electric heaters by
examining the functional operation of these heaters,
I. DESCRIPTION OF ELECTRIC HEATER
COMPONENTS
A. Limit Switch
The limit switch is a temperature-sensitive control whose function
is to prevent System from, overheating in abnormal conditions. The
temperature settings often vary from heater to heater due to
variations in airflow patterns and clement radiant heat conditions.
The devices arc sized to remain on-line under heat pump condi
tions (11 ST air off coil) and minimum CFM;, but trip to prevent
outlet air conditions above 200T or excessive component or duct
temperatures.
The device itself consists of a bimetallic disc, which when
overheated "snaps through" to open a normaliy-closed highvoltage, high-current switch. When system temperatures cool
sufficiently, the switch will automatically reset to its closed
position. Normal failure mode for this switch is open.
If a limit switch has been determined to be défective, NEVER
BYPASS THE LIMIT SWITCH. When replacing limit Switch,
ensure that it is replaced with a limit switch of identical opening
température and closing differential. Limits switches are typically
color coded to identify their range.
B. Sequencer
The sequencer is essentially a thermally activated time-delay relay
normally activated by low-voltage control signals from thermostat.
The typical sequencer is a 1- Or 2-pole normally-open device
which energizes within 10 to 30 sec after application of control
signal and de-energizes 60 to 90 sec after control signal is
removed.
In simplistic terms, the sequencers which we use are nothing more
than normally-open limit switches which sit on top of a small
resistive heater. When voltage is applied to this heater, a positive
temperature coefficient resistor (BTC), heat is supplied to a
bimetallic disc which "snaps through" and closes switchTbe time required for PTC to heat to a suffiejeut point controls ON
timing of device. The time required for disc to cool down when
power is removed controls OFF time of device. The PTC can be
varied to provide varied timing. Typically a short ON equates to a
long OFF,
Because this is a thermally-activated device, ambient conditions
affect the ON/OFF cycle. Higher ambient temperature means
shorter ON times and longer OFF times.
These sequencers may be "ganged up" to 3 On a common mounting
plate to control up to 6 heater elements. In this situation, PTCs arc
different in each sequencer to provide a staged QN of a minimum
of 10 sec between each sequencer — 3 stages of 2 elements since
the KFA and KFB Series .Деа1ег8 use , sequencers in which both
switches of the 2-polc sequencer close simultaneously. Older
models used sequencers which had a minimum delay of fO sec
between each switch.
Application of these devices is such that the first switch ON not
only turns on first heater element, but also ensures that indoor fan
is energized, because first ON is last OFF. This ensures fan
remains ON until the last heater de-energizes-
с. Positive Temperature Coefficient (PTC)
The PTC heater is essentially a resistor. It will operate on either
AC or DC voltages. It should be noted that because resistance of
PTC increases as, it, heats, initial current inrush is higher than its
steady state condition.
II. TROUBLESHOOTING KFA AND KFB SERIES
electricheaters
A. Discolored Wire Insulation at Tormincl
Check quick-coimect terminal at discoloration. Connection may be
loose, creating a high resistance through connection point.
B. Fuse Failure
1, Check for shorted wire. Replace wire. Never try to fix wire
using electrical tape,
2. Check shorted element. If element is shorted, replace
heater.
C. No Heat
1, Check fuse for failure. If fuse has failed, refer to Fuse
Failure section.
-b-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 6
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 6 6 6 2
2. Check for faulty transformer. Check output voltage of
transformer secondary side R (red) and C (brown). Make
sure output is between IS and 30 vac. If output voltage is
low pud input voltage teçtç normaJ, replace transformer.
3. Check for miswired heater plug harness,
4. Check limit switch or sequencer failure. These switches
should have failed in open position. If output voltage is zero
V, replace Switch,
D. Heater Will Not Turn Off
1. Check low-voltage wiring for miswire.
2. Check for shorted elements to ground.
3. Replace sequencer contacts. They may be stuck closed.
E. Nuisance Trips
1. Check for low airflow due to dirty filters» blocked registers,
Of Undersized duct.
2. Check blower motor and wheel for proper operation.
Excessive current draw of motor will cause internal over
load to trip.
3. The fan Speed may be low.
FK4B FAN COIL DESCRIPTION
AND TROUBLESHOOTING
The FK4B is similar to the discontinued FK4A only in that they
both have integrated controls and motor (ICM) and their own
Special circuit board. The greatest difference between the 2 models
is the way each goes about delivering air.
Setting up desired airflow on the FK4B is obtained by the
selections made on Easy Select circuit board. The motor delivers
requested airflow as defined by signals received from Easy Select
Board and its internal programming. The major difference is that
the FK4B motor reacts to changes in system static pressures to
mainiain constant airflow.
Unlike conventional fan coils where static pressure affects airflow,
the FK4B is a constant airflow unit. The blower delivers requested
airflow up to about 0.7 in. of static pressure. The ÏCM2 is
pre-programmed and contains airflows for al) modes of operation.
Blower characteristics (airflow, torque, and spccd-vs-static pres
sure) are known from laboratory testing. If any 3 characteristics are
known, the fourth iS defined.
Requested airflow is known because of Easy Select board con
figuration and thermostat signals. Torque is known because it is
directly related to armature current which is measured by motor
control. Speed is measured from its generated back EMF. This
information is entered into an expression which calculates tOrque
from speed and airflow numbers. If calculation does not match
stored blower characteristics, torque is adjusted every 0.6 sec until
agreement is reached. The unit does not directly measure static
pressure, but does react to a^ change in static to maintain constant ■
airflow.
I. INTEGRATED CONTROLS AND MOTOR (ICM2)
The ICM2 is similar to the ICMI used in FK4A series units, but
cannot be used as ,a replacement without some modification to
FK4A unit. Consult SMB 93-0052 for motor conversion kit. The
electronics of motor are built into rear of motor, deriving the name
ICM, (Sec Fig, 5.)
An ICM is first fed high voltage AC power through the 5-pin
connector. The AC power is then rectiEcd to DC by a diode
module. After rectification, DC signal is electronically communi
cated and fed in sequential order to 3 stator windings. The
frequency of.communication pulses dctemiines motor speed. The
rotor is permanently magnetized.
An ICM is powered with high voltage at all times. The motor will
not run with high voltage alone. Low voltage must be applied to
control plug to run motor-
II. PCB LAYOUT AND DESCRIPTION
NOTE: Layout of actual PCB is depicted in Fig, 6 and 7,
The control is a single PCB which interfaces a variable-speed
ICM2 with Other System components.
Power for system is supplied from a 230-vac^ 60-Hz line. Class 2
voltage (24 vac nom.), used for thermostat connections, is derived
from a transformer located in close proximity to control. The
primary and Secondary of transformer are connected to control
board. The 24-vac secondary circuit includes a socket, soldered
into circuit at SEC2, to receive a 5-amp automotive-type fuse.
Connection to heater panel is made through 12-circuit connector
PI. Connections to thermostat are made at screw terminals. Line
voltage for ICM2 is made through 7-circuit connector P2. Eighteen
quick-connect terminals comprise field select taps for motor.
Fuse Data; 5 amp automotive-type ATC/ATO (tan)
32v
200 percent current Opening time of 5 sec maximum
A. Electrical ConnectiDna
Eighteen 0,lS7-in quick-connect terminals arc used to provide
programming selections for operating modes of ICM2. The 5
selection modes № listed belOw, For additional information, refer
to Easy Select Configuration Taps section.
AUX Heat Range ^(Violet Wire)
AC/HP Size-(Blue Wire)
Type—(Orange Wire)
AC/HP CFM Adjust-(Black Wire)
AC/HP Time Delay-(Grey Wire)
III, SEQUENCE OF OPERATION
A. Continuous Fan Mode
The thermostat closes circuit R to G, The G signal is sent directly
to ICM2.
B. Cooling Mode—Single Speed or 2-Speed High
Thermostat closes circuits R to Y/Y2 and R to O (heat pump only)
for single speed. A circuit from R to Y1 is also required for
2-spced high. The Y/Y2 signal is sent directly to 1CM2.
C. Cooling Mode—Two-Speed Low
Thermostat closes circuits R to Y1 and R to O (heat pump only).
The Yl signal is sent directly to ICM2.
D. Electric Heat Heating Mode
Thermostat doses circuit R to W2, W3, or E,
The terminal block positions W2, W3, and E arc tied together by
jumpers JWl and JW2, These jumpers are provided for field
staging of electric heater banks through use of thermostats. When
staging is a requirement, installer cuts jumpers and wires in
thermostats as is the common practice with other fan coils. To
ensure motor operation if any 1 of the inputs is energized^ the 3
electric heater inputs arc also interlocked through diodes Dl, D2^
and D3 to motor W input.
E. Heat Pump Heating Mode—Single Speed or 2-Speed
High ■
Thcmiostai doses circuit R to Y/Y2 for single speed. A dreuit
from R to Yl is also required for 2-speed high. The Y/Y2 signal
is sent directly to ICM2,
F. Heat Pump Heating Mode—Two-Speed Low
Thermostat doses R to Yl. The Yl signal is sent directly to ICM2.
G. Heat Pump Heating With Auxiliary Electric Heat
Thermostat doses circuits R to Y/Y2 and/or R to Yl with R to W2,
W3, Or E (and R to 0 in the case of defrost).
See previously described modes for circuit paths.
In the event that electric heating is called for by thermostat while
heat pump is also operating in either heating or defrost mode,
electric heating signal will appear at motor connector pin 1 as
described previously. If necessary» the motor will modify its
airflow output to provide an airflow which is deEned as safe for
operation of electric heater.
-7-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 7
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
OPTIONAL SAFETY GROUND
Ш®®®Qp
POWER CONNECTOR
CONTROL CONNECTOR
И. CFM Select Configuration Taps
The CTM Select taps are used by installer to configure system. The
ICM2 is capable of discerning wave shapes on some of its input?
and uses this capability to modify its operation to a pre
programmed table of airflows and can be modified in response to
other inputs Such as the need for de-humidification.
I. 1CM2 Control Power
The ICM2 control power is supplied from R circuit through
printed-circuit runs to motor control connector pin 6|, through
rnotor control harness to motor. The C side of low-vpltagc control
power circuit is connected by printed-circuit runs to motor
connector pins 4 and 5, then through motor control harness to
motor,
J. Low-Voltage Circuit Fusing and Reference
The low-voltage circuit is fused by a board-mounted 5-amp
automotive-type fuse placed in series with transformer SEC2 and
R circuit. The C circuit of transformer is referenced to chassis
ground through a printed-circuit run at SECl connected to metal
standoff marked GROUND SCREW REQUIRED,
NOTE: A ground screw must be in place or erratic motor
operation can result.
K. Transformer, Motor, and Electric Heater Power
Connections
The high-voltage (230-vac) power input to board is provided
through electric heater connector pins 7 and 9. The high voltage is
then connected through printed-circuit runs to motor power con-
A94079
ICM2 Motor
nections Ml and M2 and transforníer power connections T1 and
T3. Transformer connection T2 is a dummy terminal used for
unused primary power lead. The transformer Secondary conriections are made at SECl and SEC2 connectors.
IV, EASY SELECT CONFIGURATION TAPS
The Easy Select taps are used by installer to configuire system. The
ICM2 uses selected taps to modify its operation to a pre
programmed table of airflows. Airflows are based on system size
or mode of operatibh and thosd airflows arc modified in response
to other inpüts stich as the need for de-humidifícation. (Sec Fig. 6.)
The FK4B Ran Coil must be configured to operate properly with
system components with which it is installed. To successfully
configure a basic system (see information printed on circuit board
located next to select pins), move the 5 select wires to pins which
match components used,
A. Auxiliary Heat Range
The installer must select the auxiliary heat airflow approved for
application with kw size heater installed. If no heater is installed,
skip this step. Each select pin is marked with a range of heaters for
which airflow (also marked) is approved. The heater installed must
fall within range selected for safe and continuous operation. It is
appropriate to mention that airflow marked is the airflow which
will be supplied in emergency heat mode and heating mode on air
conditioners when electric heat is primary heating source. To
ensure safe heater operation in heat pump heating mode when
electric heaters are energized, the ICM3 will run the higher or heat
pump efficiency airflow and electric heater airflow. The factory
selection is largest heater range approved. (See Fig- 6-)
Fig, 6—Easy
B. AC/HP Size
The fectory setting for air conditioner or heat pump size is largest
unit meant for application with model of fan coil purchased. The
installer needs to select air conditioner or heat pump size to ensure
that airflow delivered falls within proper range for size of unit
installed in all operational modes. (See Fig. 6.)
C. System Type
The type of system must be selected.
1. AC—air conditioner
2. HP-COMFORT—provides same airflow as air conditioner
selection (approximately 375 CFM/ton)
3. HP-EFF—provides most efficient airflow for heating and
cooling modes (approximately 410 CFM/ton heating and
375 CFM/ton cooling)
The factory Setting is AC, (Sec Fig, 6.)
D. AC/HP CFM Adjust
Select low, medium, or high airflow. To provide any of these
airflows, AC/HP ADJUST select must be moved to MED position.
The factory selection is LO. The adjust selections HI/TO will
regulate airflow supplied for all operational modes, except nonheat pump heating modes, +10 percent and -10 percent respec
tively. The adjust selection options are provided to adjust airflow
Supplied to meet individual installation needs for such things as
noise, comfort, and humidity removal. (Sec Fig, ti,)
E. AC/HP Time Delay
Select desired time delay profile. Four motor operation delay
profiles are provided to customize and enhance system operation,
(See Fig. 6.) The selection options arc:
JEA1S1
П П П П T-1
i '''
\ To,
CES0130007-QI1
AMP 12-PIN MATE-N-LOCK
CONNECTOR (1)
Select Board
V. TROUBLESHOOTING PCB
Use Fig. 7 and S and Tables 3,4, and 5 as guides in troubleshoot
ing PCB unless otherwise noted.
A. If Fan Wilt Not Turn On Ftom Thermostat:
IF THERE IS NO HIGH VOLTAGE TO PCB:
IF PCB HAS HIGH voltage APPLIED TO IT:
.9-
1/4-in. male
FASTON
AMP-TYP
(9) PLCS
ASdOT6
1. The standard 90 sec off delay (factory setting).
2. No delay option used for servicing unit or when a thermo
stat is utilized to perform delay functions.
3. A 30 sec on/90 see off delay profile used when it is
desirable to allow system coils time to heat up/cool down
prior to airflow. This profile will minimize cold blow in
heat pump operation and could enhance system efficiency.
4. ENH, enhanced selection provides a 30 sec on/lfiO sec off
delay at half airflow, adding comfort‘and efficiency.
1. Check connection of 12-pin plug from heaters to receptacle
On Easy Select board. This supplies power to PCB- Be Smre
plug is connected properly,
2. Check sequencer number 1 and plug wiring. Yellow wire
should be connected to pin number 9 of plug and to limit
switch. Black wire should be connected to pin number 7 of
plug and to sequencer number 1.
3. Check power leads LI and L2, If these arc not receiving
power. System cannot function.
1, Check low-voltage transformer leads (red and brown). Be
sure they are wired to correct locations, (Sec Fig. 6 and 8,)
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.