Bryant FA4A User Manual

A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 5
UTC TECH PUB
Service Manual
FAN COIL UNITS
F A X N o , 3 1 7 2 4 0 5 6 6 2
P . 0 0 1
o
; - IM'
■■■'-- ■ ■
f ABLE OF CONTENTS
... ■ -i'
SAFETY considerations.................................................................
iNTROPucTioi^ ....................................................^
UNIT irtENTIUCATiON
PRODUCT OFEERMG..........................................................................3
FAN MOTOR STEBfi TATS.........................
FA4A, FB4A, FC4B, AKD FH4A CIRCUIT BOARD
FUNCTIONJ^TROORLE^^ 3^6
■ Printed GirciiitBoifd jfPCB) CqmpijSntjjt ^Layout and Description
• Unit Functions ■_. ■ , fj I
• Troubleshooting PCB 'i; ''
ELECTRIC HEATER FUNCTION
AND TROUBLESHOOTiNG^„„„„;„,,........................................6-7
*-Description of Electric Heater Components
- Troubleshooting KFA and KFB Scries Electric Heaters FK4B FAN COIL DESCRIPTION
I ^'J'f AND TROUBLESHOOTING
• Integrated Controls and Motor (ICM2)
■ • PCB Layout and Description
• ,St(5iience of Operation
• Easy Select Configuration Taps ' : "
• Troubleshooting PCB " >
• Troubleshooting ICM2 ' ■ it'
■ Condensed Version of Troubleshooting Motor
. and Controls
• Accessories . , THERMOSTATIC EXPANSION VALVEis (TXV) ' Problems Affecting "DCV PISTON BODY CLEANING OR REPl^'CEMENT LIQUID TUBE STRAINER
coil/condensate fan removal
AND replacement....................................L.............................16-17
- A-Coil Units ‘ Slope Coil Units CARE AND MAINTENANCE
■ Filter Assembly.
Cooling Coil, Drain Tan, and Condensate Drain
• Blower Motor and Wheel ■■iC ;
FFIA/FFIB SERVICE AND TROUBLESHOOTING
• Fan Motor
• Electric Heater Service
• Cleaning or Replafcmg Refrigerant Flow^Control Device
• Liquid Tube Strainer .■ iyi:.,.
' Sequence of Operation if 2
• Care and Maintenance
FD3A SERVICE AND TROUBLESHOOTING...........................21-23
• Fan Motor - ;
• Electric Heater Service
- Cleaning or Replacing Refrigerant Flow-Control Device
• Liquid Tube Strainer
Care and Maintenance
FG3A SERVICE AND TROUBLESHOOTING...........................23-24
- Service
• Maintenance
........
..............
...................T.
.....................................................
...........................
.................
.................................... 17-lS
.................................
.......................
.......................................
.......................
....................
.................................
.................
18-21
7-lS
15
15-16
1-3
2-^
i ;
.iïixi-
3
3
FA^A, FB4A, AND FC4B SMART HEAT CIRCUIT BOARD
IhJNCTION AND TROUBLESHOOTING
• PCB Component Layout, Description, and Function
■ Unit Functions
• Smart Heat Operation
• Electrical Operating Sequences and Troubleshooting

, i SAFETY CONSIDERATIONS

Ij^proper installation, adjustment, alteration, service, maintenance, of use Can cause explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. CpnSult a qualiSed installer, service agency, or your distributor or blknch for information or assistance. The qualified installer or agency must use factory-authoriied kits or accessories when modifying thiS;pfoduct. Refer to the individual installation instruc tions packaged With the kits or accessories for detailed informa tion..
Follow all Safety codes. Wear safety glasses and work gloves. Use quenching cloth for bracing operations. Have fire extinguisher avmlable. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building m'dës and National Eectricai Code (NEC) for special installation requirements-
It is important to recognize safety information. This is the safety-alert symbol^j^ , When you sec this symbol on the unit or in instructions and manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU TION. These words are used with the safety-alert symbol, DAN­GER identifies the most serious hazards which will result in severe

^I3anc0ls; SM03-1

Fig. 1—Typical Fan Coll
...............................
SM03-2
1-1-95
A9£071
24-29
-1-
V, ■../.
■:i^
.^.■■■' 'i.
■'r ' •i ' -;r*;'ii.M *■
: ■'■ —V r:^- ■: ~ J
-■■;'■■: le :'- '- v -i:
i-'-
I • L ■ - . ■ --Ji- S..',
t-o CTJ CTJ oo
■=:
C3
LjO
-c
s
o
•TrJ
>=-
X
2jitl- Position—Fan CoiF
A- RNC B-Standard C - Deluxe D - Furred in, Cased E - Furred in. Uncased'
F - Through Ihe Wall G- Commercfal H - Standard .Electric Fumaoe
J - Standard Hot Water .
K- ICM Motor, High EffTciericy
V - VariabJe Speed ^
o
I ■A;f''.i №.."-'«;■■
. Vri^
t . 'i ■':■=. ■■ =■ ¿i' i': ;
. ■■ F x;-- -=-■ \
■■' -. i
:^... ■.. ■■■ ■■
* \>rL^% U .-- ^ Jl, C
on C?7>
t-O
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 5
MObÈL UNIT SIZE DESCRIPTION CABINET
FA4ANF 01S-060 FB4ANB 042-070 Multtpoise Modular FB4ANF 016-060 Multipoise Single Piece
FB4ASB 042-060
FB4ASF 010-060
FC4BNB 042-070 Multipoise Modular FC4BNF 024-060 FD3ANA 018-030 Horizontal Single Piece
FF1A/FF1BNA 010-030 Vortical
FG3ANA 024, 036, 048, 060 Horizontal/Small Commercial Single Piece FH4ANB FH4ANF 001-004 Multipoles Single Piece FK4BNri 005, 006 Multipoise Modular FK4BNF 001-004 Multipolee
NOTE: Multipoise units are approved for upflow, doivnflow, and horizontal left and right applications.
UTC TECH PUB
table 1product offering
003, 004 Multi poiss Modular
TABLE 2—FAN MOTOR SPEED TAPS
MODEL
FA4A 018-036 2 Black FA4A 042-060 3 Black Blue Red Yellow
FB4A 018-070 FC4B 024-070 3 Black Slue Red Yellow FD3A 016-030 2 Black Red Yellow
FF1A/FF1B 018-030
FG3A 024, 036, 048, 060 1* FH4A G01-0D4 3 Black Blue Red Yellow
*Belt drive,
UNIT SIZE
NUMBER OF
SPEEDS
3 Black Blue Red Yellow
2
personal injury or death. WARNING signifies hazards which could result in personal ityury or death. CAUTION is used to identify unsafe practices which would result in minor personal
injury or product and property damage.

INTRODUCTION

The "F" Scries fan coil units arc designed for flexibility in a variety of applications, meeting upflow, horizontal, or downflow require ments. Units are available in 1-1/2 through 5 ton nominal cooling capaddes. Factory-authorized, field-installed electric heater pack ages are available in 3 through 30 kilowatts.
WARNING: Before installing or servicing fan coil,
always turn off all power to unit. There may be more than
A
1 disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury or death.

UNIT IDENTIFICATION

The 16 position numbering chart allows identification of all available fan coil units, (See Fig. 2.)
FA4A, FB4A, FC4B, AND FR4A CIRCUIT BOARD
FUNCTION AND TROUBLESHOOTING
This section of the service manual describes the CES0130003 PCB by examining the functional operation of the PCB compo nents.

I. PRINTED CIRCUIT BOARD (PCB) COMPONENT LAYOUT AND DESCRIPTION

Layout of the actual PCB is depicted in Fig. 3.
L The low-voltagc ¡stripped leads are used to connect the 24-v
side of transformer
to indoor thermostat and outdoor
section.
-3-
F A X N o , 3 1 7 2 4 0 5 6 6 2
Multipolar
Multlpolne
50 Hz
MuitipoiSQ
50 Hz
Multipoise
HIGH
SPEED
Black
MEDIUM
SPEED
LOW
SPEED
'Blue
Red Violet
2. A 5-amp fuse is used to protect the low-voltagc transformer secondary.
3. The fan relay is controlled by thermostat and turns fan on and off,
4. A plug is used as the connection for PCB power and electric heaters. Note the pin numbers on plug,
5. A time-delay relay circuit keeps fan motor running for 90
sec after G is dc-energiied.

II. UNIT FUNCTIONS

A- Transformer

1. Proper Wiring of Transformer Primary or High Side
Yellow wire from Molex plug is wired to C terminal on transformer and black wire from PCB relay (normally­opeij) terminal is wired to 2Q5V or 230V terminal on transformer. Units are factory wired at 230V terminal
2. Proper wiring of Transformer Secondary or 24-v Side Red wire of transformer is wired to T terminal on PCB and
brown wire of transformer is wired to C terminal on PCB.
NOTE: T terminal on PCB is used to protect transformer. T
terminal is connected through the fuse to R terminal on PCB.

B. Indoor Fan

1. Wiring
Indoor fan motor yellow lead is wired to C terminal on transformer. The red, blue, or black speed lead is wired to 5PT terminal On fan relay part of PCB. Units are factory wired on medium speed (blue lead connected),
NOTE: Unused fan speed leads must be capped or taped off to
prevent direct short to cabinet surface.
Single Piece
Modular
Single Piece
Single Piece
Single Piece
Single Piece
COMMON
Yellow
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 5
UTC TECH PUB
FIg. 3—Fan Còli
2. Functional Control a. Thermostat and Relay Control
When thermostat calls for the fan in cooling, heat pomp, heating, or fan-only mode, a 24-vdc signal is sent to relay. This causes the relay to close its nonnally-opcn contacts, turning On fan. When thermostat no longer calls for the fan, the signal sent to relay is turned off and relay opens causing fan to turn off after a 90-sec fan-off delay,
b. Sequencer Interlock
The fan will also Operate whenever there is a call for electric heat, even if fan relay is nOt energized. This happens because fan is interlocked with first stage of electric heat through the normally-dosed contact of fan relay.
NOTE: The fan interlock is only connected to first stage electric
heat W2, W3 and E do not contain an interlock with fan. See outdoor thermostat Installation Instructions when electric heat Staging is desired;
C. Electric Heat
When thermostat calls for electric heat, a 24-vac signal is sent to PCB through WZ, causing first stage to turn on. W3 and E also receive signal if wired in with WZ. The signal sent to WZ causes J5r$t stage to turn on. If W3 and E arc not wired to W2, the sequencers can be controlled individually to stage additional electric heat. The sequence control is described in the following Section;
1. W2 When thermostat sends a signal to WZ, a Z4-vac signal is
applied across sequencer number f, causing it to close after a short delay. When sequencer number 1 closes, first stage of electric heal is energized. In straight electric heat, fan is
also energized through the nonnally-doscd contacts of fan relay. In cooling, heat pump, or manual fan mode, fan will already be running since fan relay would have been energized. When thermostat stops calling for electric heat, the 24-'Vac signal to sequencer number 1 turns off and
sequencer opens after a delay of 60 to 90 sec. When sequencer opens, first stage of heat turns off along with fan, providing thermostat is not calling for the fan.
2. W3 When a signal is sent to W3, a 24-vaO Signal to sequencer
number 2 causes sequencer to dose, with Second stage of electric heat turning on after a short delay. The 24-vac
F A X N o , 3 1 7 2 4 0 5 6 6 2
PCB BLOCK WIRINS
LOW
VOLTAGE FUSE
Printed-Circuit Boafd , 2
-4-
signal applied to sequencer number iJ chuses fan -tb;opkate. Timing is Such that'sequchc'or liuinB'if FWiIf'iiirn:tii.h:'before sequencer number 2. Whem, sigriifl to'WS' is turned off,
sequencer number 2 op,ens;;^^aiter a short 'delay. tf^.W^Z is also satisfied, first stage of.,dectriC'heat and^-fimwiy ais^o tum off, providing thermostat is not calling for the fan.
3, E ■'
When thermostat ..sends, a signal :iDrB^ ' a' 24-v~ac signalris sent to sequencer number 3, The 24^Wc; sighhl' applied to
sequencer number 3 turns" on third'stagcof'clcctric heat. The 24-vac signal applied to sequencer number 1 turns on first stage of electric heat'arid fan. ’^hen 'thermostat stops calling for electric heat,' the signartO'Sequ£d£efs I, 2, and 3
are turned off/^ahd sequdhfcefs b'|fieh;'''Th'il5''caii&es''dw^ heat to turn off with fan providihg'lheriniti^Iat'i^'hdt calling for the fan, ^ ^ .
NOTE: Electric heaters are factory wired with alj stages tied
together. If independent staging is desired, cpnsul|, outdoor ther^ mostat Installation Instructions. ./
III. TROUBLESHOOTING PCB . ■ > 2
Use wiring schematic shown in Fig, 4 as a guide in troubleshooting PCB unless otherwise notedv ■ ■
A. If Fan Will Not tum On ffom TherWost^i: ' ^
IF THERE IS NO HIGH VOLTAGE TO PCB:
1. Check plug/receptacle connection. This supplies power from heaters to PCB. Be sure plug is connected properly.
, 2-, Check sequencer number X and plug wiring. Yellow, wire
should be connected to pin number 9 of plug and to limit switch. Black wire should be Connected to pin number 7 of plug and to sequencer number 1.
3. Check power leads Cl and L2. tf these are not receiving power, system cannot function.
IF PCB HAS HIGH VOLTAGE APPLIED TO IT;
1, Check low-voltagc transformer leads R (red) and C
(brown). Be sure they are wired to correct locations,
2. Check output voltage of transformer secondary side R (red) and C (brown). Be sure transformer output is between IS and 30 vac. If transfbmicr output is incorrect and trans­fonner is reqeiving correct input voltage (208v or 230v), then transformer needs to be replaced with recommended transformer. If no problem exists with transformer second­ary, proceed to items 3 and 4.
A9434S
A Ï Ï G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 6
UTC TECH PUB
) . 3 1 7 2 4 0 5 6 6 2
P ,
f THIS COMPARTMENT MUST BE CLOSEP EXCEPT TOR SERVICING
1 BLOWER MOTOR |
.„.J ROTATION
CboKW 1PH SCHEMATIC DIAGRAM)
NOT SUITABLE FOR Ü5É ON SYSTElilS EXCEEOINS leovTO GROUND
в 117
£0B/240VAC 24VAC 24VAC
3 11 7 U
LEGEND
U 3 2 8 1 4
ATTENTION:
MARKED TERMINAL PLUS AND RECEPTACLE
PflINTSD CIRCUIT BOARP
SEQUENCER TRANSFORMER UNMARKED TERMINAL RECEPTACLE
CIRCUIT BREAKER
Я p e 1 i
CAUTION: ^
USE COPPER WIRE (/S'C MIN) ONLY BETWEEN D[SCCNNECT 3WIT01 AND UNFT,
TO BE WIRED IN ACCORDANCE WITH NEC AND UDCALOODES, i, TRANSPORMER PRIMARY LEADS, BLUE 20aV, RED 230V. A IF ANY OFTHE ORIGINAL WIRE, AS 5UPPUED. MUST BE REPLACED,
USE THE SAME OR RQUIVACPJTTYPE WIRE.
REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
20KW HEATER USES ONE DOUSLg POLE LS ON MIDDLE TOP ELEMENT. 10, Й4 AND 30KW HEATERS USE СЮиВ1^ POLE UHIT SWITCHES. LARGEST HEATERS ARE SHOWN, SMALLER HEATSR5 Will HAVE FEWER ELEMENTS AND COMPONENTS. 1 PHASE HEATERS ARE SHOWN WIRED FOR 8INSL£ SUPPLY CIRCUIT.
10. USE SO AMP CLA38 К FUSSS ONLY. FOR REPLACEMENT.
11, (3) SPEED MOTOR SHOWN. OPTIONAL (2) SPEED MOTOR иЗЕЗШ(ВЦ^ AND LOW
(BLU OR RED). 13, CONNECT fi TO R, S TO G, ETC.. SEE OLnDOQR INSTRUCTION FOR DETAILS, la. IF WIRE CRIMP IS REMOVED AN EMEHOENCV HgATftgUY 16 REQUIRED.
(SEE OUTDOOR-THERMOSTAT (NSTRUCTIOMS)
3, Check low-voltage fuse shown in Fig. 3. Jf fuse is blown,
replace it. The transformer cannot supply power to board with fuse bjowfl or loose. If fuse blows when unit has pow‘er applied to it, the systejs most likely has 1 of the following problems:
a. Check all 24-v wiring for an electrical short. b. The maximum load on transfonner is 40 va. If load ott
transformer is excessive, the low-voltage 5-anjp fuse
will blow to protect transformer. If load exceeds va rating of transformer, a larger va rated transformer needs to be installed. Check sequencers for excessive current draw.
32121A-101 REV. C

pig. 4—^Wiring Diagram

4. Check connections on primary side of transfonner. If they
■ 9 ■■ '■■ ■ 1
C, Check wiring of heaters. If a heater is miswired, fuse
arc not connected properly, the low-voltage terminal board cannot supply the 24-v signal to energize fan relay. If transfonner is receiving correct primary voltage hut is not
putting out correct secondary voltage, transformer needs to
be replaced.
1
2DB;S4aVAC J 24VAC 24VAC
may blow. If a heater is miswired, correct miswiring by comparing it to heater wiring label.
3^ 6
1 4
A9434G
-5-
AÏÏG/14/2008/THÜ 03:46 PM UTC TECH PUB
FAX No. 317 240 5662
P. 006
fe. If Electric Hegt Stages Will Not Turn On But Fan Will
Turn On:
IF THERE IS NO HIGH VOLTAGE TO PCB:
1. Check plug connection between heaters and board. This supplies power to transformer and fan. Be sure plug is connected properly.
2. Check sequencer number 1 and plug wiring. Yellow wire should be connected to pin number 9 of plug and to limit switch. Black wire should be connected to pin number 7 of
plug and to sequencer number 1-
3- Check incoming high-voltage power leads, tf these arc not
receiving power, system c&undt function.
IF PCB HAS HIGH VOLTAGE APPLIED TO IT;
1, Check low-voltage transformer leads R (red) and C
(brown). Make sure they are wired to correct location. The
unit will not function without proper connections.
2. Check output voltage of transformer secondary side R (red) and C (brown). If transformer output is low (less than 18 vac), reifer to items 3 and 4 of previous If PCB Has High Voltage Applied To It section.
IF TRACES ARE OVERHEATED ON BACK OF PCB:
Usually whenever a trace is blown on PCB, it means cither there has been a high-voltage short or high voltage has been applied to low-voltage circuit. This can be prevented by making sure PCB is wired correctly before PCB has power applied to it,
C, If PCB Fuse Keeps Blowing:
When loW“Voltage fuse blows, it means transformer would have blown if fuse had riot been in circuit to protect it. The fuse usually blows when there is a high Current draw on transformer, high voltage applied to low-voltagc circuit, Or a direct secondary short. When there is a high current draw on transformer, it is most likely because transformer has been shorted or system is trying to draw more va than transformer rating allows. When fuse blows because of high voltage, the system has mixed high- and low-voltage signals.
1. Check wiring of sequencers as shown in Fig. 4, Be sure transformer is not shorting out because thermostat wires arc miswired.
2. Check wiring of sequencers as shown in Fig. 4. Be sure low-voJtagc and high-voltage wiring is connected to proper sequencers.
3. Check va draw on transformer. If va draw is more than va rating of transformer, fuse will blow. If this is the case, replace transformer with one that has a higher va rating and meets system spccifícationS-
D. If F^n Runs Continuously:
1. If PCB has no low-vohage power, check blue and black fan leads. These may be switched at sequencer,
2. If PCB has lowwoltage power, check fan relay to see if it is , opening and closing. It may be stuck in the normally-closed position due to debris in relay.
E- Transformer Failure:
1. Check 208-v and 230-v transformer connections. They may
be miswired.
ELECTRIC HEATER FUNCTION AND
TROUBLESHOOTING
This section describes KFA and KFB series electric heaters by examining the functional operation of these heaters,

I. DESCRIPTION OF ELECTRIC HEATER COMPONENTS

A. Limit Switch

The limit switch is a temperature-sensitive control whose function is to prevent System from, overheating in abnormal conditions. The temperature settings often vary from heater to heater due to
variations in airflow patterns and clement radiant heat conditions. The devices arc sized to remain on-line under heat pump condi tions (11 ST air off coil) and minimum CFM;, but trip to prevent outlet air conditions above 200T or excessive component or duct temperatures.
The device itself consists of a bimetallic disc, which when overheated "snaps through" to open a normaliy-closed high­voltage, high-current switch. When system temperatures cool sufficiently, the switch will automatically reset to its closed position. Normal failure mode for this switch is open.
If a limit switch has been determined to be défective, NEVER BYPASS THE LIMIT SWITCH. When replacing limit Switch, ensure that it is replaced with a limit switch of identical opening température and closing differential. Limits switches are typically
color coded to identify their range.
B. Sequencer
The sequencer is essentially a thermally activated time-delay relay normally activated by low-voltage control signals from thermostat. The typical sequencer is a 1- Or 2-pole normally-open device which energizes within 10 to 30 sec after application of control signal and de-energizes 60 to 90 sec after control signal is removed. In simplistic terms, the sequencers which we use are nothing more than normally-open limit switches which sit on top of a small
resistive heater. When voltage is applied to this heater, a positive temperature coefficient resistor (BTC), heat is supplied to a bimetallic disc which "snaps through" and closes switch­Tbe time required for PTC to heat to a suffiejeut point controls ON timing of device. The time required for disc to cool down when
power is removed controls OFF time of device. The PTC can be varied to provide varied timing. Typically a short ON equates to a long OFF,
Because this is a thermally-activated device, ambient conditions affect the ON/OFF cycle. Higher ambient temperature means shorter ON times and longer OFF times.
These sequencers may be "ganged up" to 3 On a common mounting plate to control up to 6 heater elements. In this situation, PTCs arc different in each sequencer to provide a staged QN of a minimum of 10 sec between each sequencer — 3 stages of 2 elements since
the KFA and KFB Series .Деа1ег8 use , sequencers in which both switches of the 2-polc sequencer close simultaneously. Older models used sequencers which had a minimum delay of fO sec between each switch.
Application of these devices is such that the first switch ON not only turns on first heater element, but also ensures that indoor fan is energized, because first ON is last OFF. This ensures fan remains ON until the last heater de-energizes-
с. Positive Temperature Coefficient (PTC)
The PTC heater is essentially a resistor. It will operate on either AC or DC voltages. It should be noted that because resistance of PTC increases as, it, heats, initial current inrush is higher than its steady state condition.

II. TROUBLESHOOTING KFA AND KFB SERIES

electric heaters

A. Discolored Wire Insulation at Tormincl

Check quick-coimect terminal at discoloration. Connection may be loose, creating a high resistance through connection point.
B. Fuse Failure
1, Check for shorted wire. Replace wire. Never try to fix wire
using electrical tape,
2. Check shorted element. If element is shorted, replace heater.

C. No Heat

1, Check fuse for failure. If fuse has failed, refer to Fuse
Failure section.
-b-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 6
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 6 6 6 2
2. Check for faulty transformer. Check output voltage of transformer secondary side R (red) and C (brown). Make sure output is between IS and 30 vac. If output voltage is
low pud input voltage teçtç normaJ, replace transformer.
3. Check for miswired heater plug harness,
4. Check limit switch or sequencer failure. These switches
should have failed in open position. If output voltage is zero
V, replace Switch,

D. Heater Will Not Turn Off

1. Check low-voltage wiring for miswire.
2. Check for shorted elements to ground.
3. Replace sequencer contacts. They may be stuck closed.
E. Nuisance Trips
1. Check for low airflow due to dirty filters» blocked registers, Of Undersized duct.
2. Check blower motor and wheel for proper operation. Excessive current draw of motor will cause internal over load to trip.
3. The fan Speed may be low.
FK4B FAN COIL DESCRIPTION
AND TROUBLESHOOTING
The FK4B is similar to the discontinued FK4A only in that they both have integrated controls and motor (ICM) and their own
Special circuit board. The greatest difference between the 2 models
is the way each goes about delivering air. Setting up desired airflow on the FK4B is obtained by the
selections made on Easy Select circuit board. The motor delivers requested airflow as defined by signals received from Easy Select Board and its internal programming. The major difference is that the FK4B motor reacts to changes in system static pressures to
mainiain constant airflow. Unlike conventional fan coils where static pressure affects airflow,
the FK4B is a constant airflow unit. The blower delivers requested
airflow up to about 0.7 in. of static pressure. The ÏCM2 is pre-programmed and contains airflows for al) modes of operation. Blower characteristics (airflow, torque, and spccd-vs-static pres sure) are known from laboratory testing. If any 3 characteristics are known, the fourth iS defined.
Requested airflow is known because of Easy Select board con
figuration and thermostat signals. Torque is known because it is
directly related to armature current which is measured by motor
control. Speed is measured from its generated back EMF. This information is entered into an expression which calculates tOrque from speed and airflow numbers. If calculation does not match stored blower characteristics, torque is adjusted every 0.6 sec until agreement is reached. The unit does not directly measure static pressure, but does react to a^ change in static to maintain constant ■ airflow.

I. INTEGRATED CONTROLS AND MOTOR (ICM2)

The ICM2 is similar to the ICMI used in FK4A series units, but cannot be used as ,a replacement without some modification to FK4A unit. Consult SMB 93-0052 for motor conversion kit. The electronics of motor are built into rear of motor, deriving the name ICM, (Sec Fig, 5.)
An ICM is first fed high voltage AC power through the 5-pin connector. The AC power is then rectiEcd to DC by a diode module. After rectification, DC signal is electronically communi
cated and fed in sequential order to 3 stator windings. The frequency of.communication pulses dctemiines motor speed. The rotor is permanently magnetized.
An ICM is powered with high voltage at all times. The motor will not run with high voltage alone. Low voltage must be applied to control plug to run motor-
II. PCB LAYOUT AND DESCRIPTION NOTE: Layout of actual PCB is depicted in Fig, 6 and 7,
The control is a single PCB which interfaces a variable-speed
ICM2 with Other System components. Power for system is supplied from a 230-vac^ 60-Hz line. Class 2 voltage (24 vac nom.), used for thermostat connections, is derived from a transformer located in close proximity to control. The primary and Secondary of transformer are connected to control board. The 24-vac secondary circuit includes a socket, soldered into circuit at SEC2, to receive a 5-amp automotive-type fuse. Connection to heater panel is made through 12-circuit connector
PI. Connections to thermostat are made at screw terminals. Line voltage for ICM2 is made through 7-circuit connector P2. Eighteen quick-connect terminals comprise field select taps for motor. Fuse Data; 5 amp automotive-type ATC/ATO (tan)
32v 200 percent current Opening time of 5 sec maximum
A. Electrical ConnectiDna
Eighteen 0,lS7-in quick-connect terminals arc used to provide programming selections for operating modes of ICM2. The 5 selection modes № listed belOw, For additional information, refer to Easy Select Configuration Taps section.
AUX Heat Range ^(Violet Wire) AC/HP Size-(Blue Wire)
Type—(Orange Wire) AC/HP CFM Adjust-(Black Wire) AC/HP Time Delay-(Grey Wire)
III, SEQUENCE OF OPERATION A. Continuous Fan Mode
The thermostat closes circuit R to G, The G signal is sent directly to ICM2.
B. Cooling Mode—Single Speed or 2-Speed High
Thermostat closes circuits R to Y/Y2 and R to O (heat pump only) for single speed. A circuit from R to Y1 is also required for 2-spced high. The Y/Y2 signal is sent directly to 1CM2.
C. Cooling Mode—Two-Speed Low
Thermostat closes circuits R to Y1 and R to O (heat pump only). The Yl signal is sent directly to ICM2.
D. Electric Heat Heating Mode
Thermostat doses circuit R to W2, W3, or E,
The terminal block positions W2, W3, and E arc tied together by jumpers JWl and JW2, These jumpers are provided for field staging of electric heater banks through use of thermostats. When staging is a requirement, installer cuts jumpers and wires in thermostats as is the common practice with other fan coils. To ensure motor operation if any 1 of the inputs is energized^ the 3 electric heater inputs arc also interlocked through diodes Dl, D2^ and D3 to motor W input.
E. Heat Pump Heating Mode—Single Speed or 2-Speed High ■
Thcmiostai doses circuit R to Y/Y2 for single speed. A dreuit
from R to Yl is also required for 2-speed high. The Y/Y2 signal is sent directly to ICM2,
F. Heat Pump Heating Mode—Two-Speed Low
Thermostat doses R to Yl. The Yl signal is sent directly to ICM2.
G. Heat Pump Heating With Auxiliary Electric Heat
Thermostat doses circuits R to Y/Y2 and/or R to Yl with R to W2,
W3, Or E (and R to 0 in the case of defrost).
See previously described modes for circuit paths. In the event that electric heating is called for by thermostat while heat pump is also operating in either heating or defrost mode, electric heating signal will appear at motor connector pin 1 as described previously. If necessary» the motor will modify its airflow output to provide an airflow which is deEned as safe for operation of electric heater.
-7-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 7
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
OPTIONAL SAFETY GROUND
Ш®®®Qp
POWER CONNECTOR
CONTROL CONNECTOR

И. CFM Select Configuration Taps

The CTM Select taps are used by installer to configure system. The
ICM2 is capable of discerning wave shapes on some of its input?
and uses this capability to modify its operation to a pre
programmed table of airflows and can be modified in response to other inputs Such as the need for de-humidification.
I. 1CM2 Control Power
The ICM2 control power is supplied from R circuit through printed-circuit runs to motor control connector pin 6|, through rnotor control harness to motor. The C side of low-vpltagc control power circuit is connected by printed-circuit runs to motor connector pins 4 and 5, then through motor control harness to motor,
J. Low-Voltage Circuit Fusing and Reference
The low-voltage circuit is fused by a board-mounted 5-amp automotive-type fuse placed in series with transformer SEC2 and R circuit. The C circuit of transformer is referenced to chassis ground through a printed-circuit run at SECl connected to metal standoff marked GROUND SCREW REQUIRED,
NOTE: A ground screw must be in place or erratic motor
operation can result.
K. Transformer, Motor, and Electric Heater Power
Connections
The high-voltage (230-vac) power input to board is provided through electric heater connector pins 7 and 9. The high voltage is then connected through printed-circuit runs to motor power con-
A94079
ICM2 Motor
nections Ml and M2 and transforníer power connections T1 and T3. Transformer connection T2 is a dummy terminal used for unused primary power lead. The transformer Secondary conriec­tions are made at SECl and SEC2 connectors.

IV, EASY SELECT CONFIGURATION TAPS

The Easy Select taps are used by installer to configuire system. The ICM2 uses selected taps to modify its operation to a pre
programmed table of airflows. Airflows are based on system size
or mode of operatibh and thosd airflows arc modified in response to other inpüts stich as the need for de-humidifícation. (Sec Fig. 6.)
The FK4B Ran Coil must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board located next to select pins), move the 5 select wires to pins which match components used,

A. Auxiliary Heat Range

The installer must select the auxiliary heat airflow approved for application with kw size heater installed. If no heater is installed,
skip this step. Each select pin is marked with a range of heaters for which airflow (also marked) is approved. The heater installed must fall within range selected for safe and continuous operation. It is appropriate to mention that airflow marked is the airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is primary heating source. To ensure safe heater operation in heat pump heating mode when
-8-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 7
UTC TECH PUB
MOLEX 7-PIN-
CONNECTOR (1)
LOW VOLTAGE
TERMINAL BLOCK
EASY SELECT
AUX HÈAT HANQE
СГН 'ÎÏÔT
Ac/Ht> SIZE
(H2 [ DIS [ D3D I OM
TYPE
№<ШГйКГ NPOT
AC
QHNI GiQ
, ......
0=0 0=0
AC/HP. ÛFM ADJUST
Ifl UCD HI
\ &€> \ &e>
AC/HP TIME DELAY
1 MUHI
Sift tfCl □ JIM C —] [■=
C-=-3 C-=-] m“ I ШШ HUU
F A X N o , 3 1 7 2 4 0 5 6 6 2 P . 0 0 9
W2-E JUMPER 3RD STAGE
W2-W3 JUMPER 2ND STAGE
XPOfiM
^6-IN, MALE
EASTON
AMP-TYP
(£1) PLCS
«ОГОЯ
VAC •
t#-I
24D
VAC
T|
240 1
TÎ ^
71
.
-OOOC­OOOO]
-OOOC-
Irr-n--□--П-d
©
electric heaters are energized, the ICM3 will run the higher or heat pump efficiency airflow and electric heater airflow. The factory selection is largest heater range approved. (See Fig- 6-)

Fig, 6—Easy

B. AC/HP Size
The fectory setting for air conditioner or heat pump size is largest unit meant for application with model of fan coil purchased. The installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for size of unit
installed in all operational modes. (See Fig. 6.)
C. System Type
The type of system must be selected.
1. AC—air conditioner
2. HP-COMFORT—provides same airflow as air conditioner selection (approximately 375 CFM/ton)
3. HP-EFF—provides most efficient airflow for heating and cooling modes (approximately 410 CFM/ton heating and
375 CFM/ton cooling)
The factory Setting is AC, (Sec Fig, 6.)
D. AC/HP CFM Adjust
Select low, medium, or high airflow. To provide any of these airflows, AC/HP ADJUST select must be moved to MED position. The factory selection is LO. The adjust selections HI/TO will regulate airflow supplied for all operational modes, except non­heat pump heating modes, +10 percent and -10 percent respec tively. The adjust selection options are provided to adjust airflow Supplied to meet individual installation needs for such things as noise, comfort, and humidity removal. (Sec Fig, ti,)
E. AC/HP Time Delay
Select desired time delay profile. Four motor operation delay profiles are provided to customize and enhance system operation, (See Fig. 6.) The selection options arc:
JEA1S1
П П П П T-1
i '''
\ To,
CES0130007-QI1
AMP 12-PIN MATE-N-LOCK CONNECTOR (1)

Select Board

V. TROUBLESHOOTING PCB

Use Fig. 7 and S and Tables 3,4, and 5 as guides in troubleshoot ing PCB unless otherwise noted.

A. If Fan Wilt Not Turn On Ftom Thermostat:

IF THERE IS NO HIGH VOLTAGE TO PCB:
IF PCB HAS HIGH voltage APPLIED TO IT:
.9-
1/4-in. male
FASTON AMP-TYP (9) PLCS
ASdOT6
1. The standard 90 sec off delay (factory setting).
2. No delay option used for servicing unit or when a thermo stat is utilized to perform delay functions.
3. A 30 sec on/90 see off delay profile used when it is desirable to allow system coils time to heat up/cool down
prior to airflow. This profile will minimize cold blow in heat pump operation and could enhance system efficiency.
4. ENH, enhanced selection provides a 30 sec on/lfiO sec off delay at half airflow, adding comfort‘and efficiency.
1. Check connection of 12-pin plug from heaters to receptacle
On Easy Select board. This supplies power to PCB- Be Smre
plug is connected properly,
2. Check sequencer number 1 and plug wiring. Yellow wire should be connected to pin number 9 of plug and to limit switch. Black wire should be connected to pin number 7 of
plug and to sequencer number 1.
3. Check power leads LI and L2, If these arc not receiving
power. System cannot function.
1, Check low-voltage transformer leads (red and brown). Be
sure they are wired to correct locations, (Sec Fig. 6 and 8,)
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 7 P M
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
P . 0 1 0
2, Check output voltage of transformer secondary side SEC2
and SECl. Be sure transformer output is around 24 vac. If tráíisfoTOjef output is zero vac and transformer is! receiving correct input voltage (208v or 240v), then transformer needs to be replaced with recommended transformer. If transfoirtier output is 24 vaCj proceed to items 3 and 4,
3. Check Jow-voltage fuse shown in Fig. 6. If fuse is blown, replace it. The transfortner cannot supply power to board with fuse blown or loose. If fuse blows when unit has power applied to it, the system most likely has 1 of the following problems:
a. Check control circuit for a short or miswiring problem, b. The maximui» load on transformer is 40 va. If load on
transformer is excessive, the low-voltage 5-amp firse will blow to protect transfomicr. If load exceeds va rating of transformer, a larger va rated transformer needs to be installed. Check sequencers for excessive current draw.
c. Check wiring of heaters. If a heater is miswirsd, fuse
may blow, if a heater is mis wired, correct miswiring.
4. Check Tl, T2, and T3 connections on primary side of transformer. If they are not connected properly, low-voltage terminal board cannot supply 24-v signal to energize fan motor. If transformer is receiving correct primary voltage but is not putting Out correct secondary voltage, transformer
needs to be replaced,
B, If Electric Heat Stages Will Not Turn On But Fan WIN
Turn On:
1. Check wiring of sequencers. Pay particular attention to high- and low-voltagB wiring of sequencers.
2. Check plug wiring to make sure that it is wired correctly,
3. Check voltage to sequencer. Sequencer number 1 receives a
24-vac signal. If it is receiving correct voltage, cheek to see if sequencer is closing. If sequencer is not dosing but is
10-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 7
SIZE FEMALE
0.250 X 0.032
0.187 X 0.032
TABLE 4™C0NNECTI0NS ON SINGLE BARRIER StrIR MOUNTED, CROSS SLOTTED, CAPTIVE BINDING HEAD
SCREW
TERMINAL
W2
W3
E
Y/Y2 Connection for Y signal from thermostat
G 0
L
Y1
R C
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
0 1
TABLE 3—MALE/FEMALE QUICK-CONNECT TERMINALS
SIZE MALE
M2 Motor line voltage connection (230 vac 60 Hz) T3
T2 SEC1 SEC2
HUM1 HUM2 AUX1
AUX2
Ml
T1
REd I
Connection fbr W2 signal from thermostat Connection for W3 signal from outdoor thermostat Connection for E signal from thermostat
Connection for G signal from thermostat Connection for 0 signal from thermostat
This connection Is a field termination for use in connecting L lines of thermostat and outdoor unit together. Thare is no connection of this terminal with control circuity.
Connaction for low-speed compressor operation Connection for R signal to tharmostat (24 vac) Connection for C terminal to thermostat (24 vac common)
Transformer line voltage connection (230 vac go Hz) Transfomior tap storage terminal for 208-vac lead Secondary connection from transformer (24 vac)
This connection is common to chassis ground through sydet marked GROUND SCREW REQUIRED, Secondary connection from transformer (24 vac) Low voltage ground for humidifier option (24 vdc) Low voltage output for humidifier option (24 vdc) Low voltage ground for auxiliary option (24 vdc)
Low voltage output for auxiliary option (24 vdc) Common connection to blower motor Common connection for transformer Common to R screw terminal and SEC2
DESCRIPTION
DESCRIPTION
TABLE 5—CONNECTIONS AND CONNECTOR
TYPE
CONNECTION
Heater
Connection
ICM2 Motor
1
TYPE
CONNECTOR
12-Pln
7-Pin Header
PIN NO.
Pin 1 Common to E screw terminal Pin 2
Pin 3
Pin 4 Common to C screw terminal, SEC1 terminal, and chassis ground
Pins
Pin 6
Pin? Plh'B Pin 9
Pin 10
Pin 11
Pin 12
Pin 1 Pin 2
Pin3
Pin 4
Pins
Pin 6 Pin?
receiving correct voltage, replace sequencer. If sequencer is dosing, check high-voltage wiring as discussed in items 1 and 2.
IF THERE ARE BLOWN DIODES:
If diodes are blown, it is probable electric heater plug is miswired. Correct miswiring.
NOTE: Board will need to be replaced if diode is bad.
DESCRIPTION
Common to W2 screw terminal Common to C screw terminal, SEC1 terminal, and chassis ground
No connection Common to W3 scraw terminal
Common to M2 and T3 quick-connects, 230 vac input No connection
Common to Mi and T1 quick-connects, 230 vac input
No connection No connection No connection Diode OR output of E or W3 or W2 thermostat signals Thermostat G signal Common to C, SECI, and chassis ground Common to C, SEC1, and chassis ground Common to R and SEC2 (via 5-amp fuse)
Thermostat Yrir2 signal Thermostat Y1 signal
IF TRACES ARE OVERHEATED ON BACK OF PQB;
Usually whenever there js a trace blown on PCB, it means cither there has been a high-voltage short or high voltage has been applied to low-voltage circuit. This can be prevented by making
sure PCB is wired correctly before PCB has power applied to it.
-11-
AÏÏG/14/2008/THÏÏ 03:47 PM UTC TECH PUB
FAX No. 317 240 5662
P. 012
-H !
■mis COMPARTMENT must be closed except for servicing
&DKW IPH SCHEMATIC PI AG RA^O
FIELi] WIFtlrJÜ
PH ■ Л __j_ Lam
PLUE 1 ПЁЬ
DISCONNECT PER NEC
3
____
_____
üSâ rtAïiNiï plate
_ j.
PLUlj Я
CAUTION:
exceeding 150V to ground
ATTENTION:
DE PLUS DE 150 V A LA TERRE
QlfiCONHECT PER NEC
|oND I
?=
FIELD POWER WIRING
c
1
SEE RATIHQ PLATE
pgn VÛLT3 t HERTZ
hfOT SUITABLE FOR USE OW SYSTEMS
NE CONVIENT FAS AUX INSTALLATIONS
fjliHEMATia OlAflftAM
[5E5 NPT41)
( cot^jjHceoNTBQL wifliHa 1
COQLINa CONTROL ONLY
-----------
VIÜ
AUX HEAT RANGE
4-0 о ,o О
ACЛ^P SIÎR
-----------
-----------
BLU
ПА 1И
—О © © ©“
QRY
red
RED
BLK
—®
/
/
/
/
О О ofâ
туре ^
AJ HP-COMFORT HP-CFF g]—
О о
... . HCIHP CFM TRIM
АС/HP DELAY OW/OFF
Oran ЗПРГ1г 30Î3D □/□
О О О О
о
йЁса^Х^
_______
5ЯС1 *=* AUX1 HUM1
ЯЭйгтТтГ
-BLU^ RECP1
оо
О-
©­(|Н - -
©т
оо
AUKÏ ниш
щ.
----------
INDOOR THERMOBTAT
.я,о^ РСВ
NOTEfi:
11 U80 copper Wire only between dleconnect ewHoh unit.
2. Connect (Y) to fV), (C) to (C), fito. In pattern etiown.
a. Tmnaformer primary leads; BLUE MflV, RED 230V.
4. To be wired in Bccordendo^ with NEC and Id cal cOdea. 5, It any of the ortalnal wire, ав supplied, must b? roplaned, use the same Or“
G. Replace low voltage fuse with no greater than 5 emp tose,
7, Fuse is wired In series between transformer' SEC2 end lOW VOllsge 'Ft' circuit,
8. BOKW heator ubbb one double pole LS on middle top elertient.
9.16,24 and 30Kvy heaters use double pole limit swibhes.
ID. Largest heatera are shown, smaller heaters will have tawar elamanta and
□□mporients.
11,1 phase heaters are shown wired for single supply circuit. Multiple
supply clrculte may be wired directly to fuse/C.B.'S.
Fig. 8—FK4B Wiring Diagram
\
equivalent type wire.
-12^
Oy^L I Y". .
ЮфффффШф
blkT вшТоенТа^
HARKED TERMINAL
о
UNMARKED TERMINAL
9
FIELD POWER WIRING
----Й----
PLUG AND RECEPTACLE PCB BREAKOFF JUMPER
AUX
auxiliary
PRINTED CIRCUIT BOARD
PCB НРТВ
HEAT PUMP TERM BRD LOW VOLT TERM BRD
LVTB
SEQUENCER
8ЕС1 HTR
HEATER
HIGH VOLTAGE TERMINAL BOX
HVTB ним
HUMIDIFIER
- LEGEND
LIMIT SWITCH
LS ICM FAN MOTOR TRAN TRANSFORMER GND
EQUIPMENT GROUND
FU FUSE
RECEPTACLE
RECP CB CIRCUIT BREAKER F
LOW VOLTAGE FUSS

320486-301 REV. C

A94078
AUG/14/2008/THU 03:48 PM UTC TECH PUB
FAX No. 317 240 5662
TABLE e—МОТОВ CONTROL TEST VALUES
OPERATING MODE
Electric
1-Speed A/C
2-Speed A/C, Low Speed
S-Speed A/C, High Speed
1-Speed HP
1-Speed HP 2-Speed HP, Lew Speed Cooling R 2-5peed HP, Low Speed
2-Speed HP, High Speed
2-Speed HP, High Speed
ContinuDue Fan
Pin 1 @ 24 vdc with or without jumpers when ever any Individual heeter input or any combination of heater inputs are energized.
Heating R Cooling R
Cooling R
Cooling R
Cooling R
Heating R
Heating Cooling R
Heating R
SCREW TERMINALS
HAVING 24 VAC
W2 W3* E*
Y/Y2
Y1 Q Y/Y2 G Y/Y2 G 0
Y/Y2 G
Y1 G 0
Yi G
R
Y/Y2 Y/Y2 YI Q
R
G
Y1 G
0
W
Pin 1
24 vde
0
0 £4 vac 0 □ 0 0 0 24 vac 0
0 0
VOLTAGES—7-PIN PLUG P2
Q
Pin 2CPln3
0
£4 vac , 0
24 vac 0 £4 vac 24 vac £4 vac 0
24 vac 0 24 vac 24 vac 0
c
Pin 4RPin 5
0
0
0 £4 vac 0
0
0 24 vac
0 £4 vac
24 vec
0
0 24 vac
24 vac
0
24 vac
0 0 24 vac
£4 vac
0
24 vac 24 vac 24 vac
0
24 vac
0
P. 013
Y/Y2 Pin 6
24 vac 0
0 24 vac 0 24 vac 24 vac 0
0 0
24 vac
Q 0
Pin 7
24 vac
24 vac 24 vac
24 vac
Y
0
d

C. If PCB Fuse Keeps Blowing:

When low-voltage fuse blows, it means transformer would have blown if fuse had not been in circuit to protect it. The fuse usually blows when there is a high current drawn on transformer, high
voltage applied to low-voltage circuit, or a direct secondary short. When there is a high current drawn on fransforaier, it is most likely because transformer has been shorted or system is trying to draw more va than transformer rating allows. When fuse blows because of high voltage, the system has mixed high- and levy-voltage signals,
1. Check transformer and thermostat wiring. (See Fig. 6 and 8,) Be Sure transformer is not shorting out because thermo stat wires are miswired,
2. Check wiring of sequencers. (See Fig. 6 and 8,) Be sure low-voltage and high-voltage wiring are connected to proper sequencers.
3. Check va draw o.n transformer. If va draw is more than va
rating of transformer, fuse will blow. If this is the case, replace transformer with one that has a higher va rating and meets system specifications,
VI. TROUBLESHOOTING ICM2 FAN MOTOR A. If Motor Does Not Run:
1. With power turned off, check all plugs and receptacles on circuit board and at motor for any defonnation that may cause a bad connection. Be sure all plugs are placed fully seated.
%. Verify that there are approximately 230v at terminals Ml
apd Iyf2.,lf not, determine if high voltage is entering board. It enters through black and yellow wires at pins 7 and ? in 12-pin plug.
3, Verify that there is a low-voltage control signal to motor.
The motor receives its contml signals through the 7-pin mQ,tor plug P2. The voltage output of each pin in plug will be different for each mode of operation. Table 6 lists circuit board screw terminals that have 24 vac present (powered by thermostat) and lists voltage that is present at each pin of 7-pin plug for each operating mode. Tests should be taken between points listed and common (C screw terminal). If all values of any 1 of operating modes checks OK and motor
fails to run, then motor is defective and should be replaced,

B. If Motor Does Not Run Smoothly;

First verify that the cause is not an out-of-balapce or damaged blower wheel. If it is not blower wheel, motor is defective and should be replaced.

C. If Motor Shaft Does Not Rotate Smoothly:

When manually turning Shaft Of ICM, the shaft does not rotate
smoothly. The shaft has steps during rotation and is referred to as
motor cogging. The cogging is caused, by permanent magnets passing each pole of motor. However, shaft should not require excessive force to turn. If shaft is VERY difficult to turn, motor control or bearings have failed and motor must be replaced.
D. If Motor Does Not Stop Running
1. Check for good ground between motor ground lead and transformer common lead.
2. If motor continues to nin, remove all thermostat wires. If motor stops, replace circuit board.
3. If motor continues to run, remove the 7-pin plug. If motor continues to run, replace motor.

VII. CONDENSED VERSION OF TROUBLESHOOTING FK4B MOTOR AND CONTROLS

This section provides a quick summary of how to troubleshoot the FK4B. If more information is needed, refer to appropriate sections
of this service manual.
+ MOTOR
- If motor is hard to turn manually, replace motor.
- If motor docs not. run, check the components listed below according to their instructions.
■- If motor runs in some operation modes and not in others, check for a good ground connection between motor ground lead and circuit board screw marked "ground screw" and check the room thermostat and wiring harness according to instructions listed below.
- If motor does not stop running, remove the 7-pin plug from circuit board. If motor continues to run, replace motor. If motor stops running,''it is either the circuit board or thermo stat causing the problem. Test whether thermostat is at fault
by disconnecting it from the board.
+ CIRCUIT BOARD
- Check 5-amp fuse,
- Check for 230v between terminals Ml and M2. If m voltage is present, check power to'board. 230-v power enters the board through the black and yellow lead in the 12-pin plug,
- Check for 24v between SECl and'SEC2, If no voltage is present, check the transformer.
- Check for burn traces or burnt components. If bum spots arc present, replace board.
'13-
A Ï Ï G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 8

+ ROOM THERMOSTAT

- Remove thetrtiOStst 'wires from the circuit board,
- Jumper screw terminais (J at & time) R-G, R-Y/Y2, R-YJ^ and R-W2, If motor runs in all cases, thermostat is bad. Replace thermostat. If motor does not run, or runs in some cases but not in others, continue by checking the wiring
harness.
+ WIRING HARNESS
- Shut off power to unit.
- Remove 5-pin plug from motor.
CAUTION: Never remove 5-pin high voltage plug from
A
the motor with the power on.
Remove 16-pin plug from motor. , Replace 5-pin plug and turn on power. Check for 24v between pin-1 and pin-12 on the l6-pin plug.
If rm voltage is present, replace wiring'harness. (See Fig, 9.) If voltage is present, jumper screw terminal R-Y/Y2 on
circuit board and check for 24v between pjh-1-2 and pin-14 on 16-pin plug. (See Fig. 9 ) If no voltage is present, replace harness.
H 24v is present, the motor is bad. Replace motor.
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
0 1 4
16 15 14 13 12 11 10 9
8 7
ЗИШИ1
Fig. Э—Wiring Harness 16-Ptn Plug VIII. ACCESSORIES A. Electronic Air Cleaner (EAC)
Familiar 230-vac EAC control/power signal EACl and БАС2 is not available, because the ICM2 blower motor used in the FK4B Fan Coil is controlled by low-voUsgc signals. This signal is replaced by a 24“Vdc signal which is provided at circuit board terminals AUXl and AUX2, (See Fig 6.)
This signal is present when either G or W is present and' is active in all heating and cooling modes. Because 24-vdc relays may not be readily available to installer, a kit exists, KFAJROIOIACR, containing a 24-vdc relay which mounts directly inside EAC cabinet. User-supplied 110 vac is switched by relay to power air cleaner when G or W arc present. (See Fig. 10 and 11.)
In heat pump applications, the G signal is present in both cooling and heating modes, permitting НАС to be controlled from G signal only. For this application, a user-supplied 24-vac relay can be driven by G terminal eliminating need for relay kit.
B. FK4B De-Hufflidify Mode NOTE: Humidistat must open cm humidity rise.
Latent capacities for systems using the FK4B Fan Coil are better
than average systems. If increased latent capacity is an application requirenjeut, the FK4B can be wired to provide this requirement by adjusting its airflow in response to standard humidistat input. Fig. 12 illustrates the wiring connections to activate de-huraidify mode. Carefully consult product airflow data for cooling and dehumidi­iying mode,

THERMOSTATIC EXPANSION VALVES (TXV)

The FC4B and FK4B Fan Coils are factory equipped with a hard shutoff (HSO) TXV,
5 4 3 2 1
16-PIN PLUG
A94375
A9321S
Fig. 10—Mounting KFAIRO101ACR Relay Kit
FK4B
AUXl AUX2
Fig. 11—KFAlROlOIACR Relay Kit Wiring
RED WIRE ГЛ
FROM ЮМ2 -f-i-
MOTÛR
Fig. l3“HumIdIstat Wiring for De-Humidify Mode
The hard shutoff TXV has no bleed port and allows no bleed-
through after system is shutdown. No pressure equalization occurs. A start capacitor and relay must be installed on single-phaSc reciprocating compressors to boost torque to compressor motor so it may overcome the unequalized system pressures.
110 VAC BRANCH CKT
GND HOTNËUT
Schematic
HUMIDISTAT
HUMIDISTAT wiring FOR DE-HUMlDiFY MODE
TO PCB TERMINAL
MARKED 'RED'
A93215
-14-
A D G / 1 4 / 2 0 0 8 / T H U 0 3 :
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
P , 0 1 5
The standard TXV is a bi-flow meterijig device that is used in
condensing and heat pump systems to adjust to changing load conditions by maintaining a preset superheat temperature at outlet of evaporator coil. The volume of refrigerant metered through valve scat is dependent upon the following:
1. Superheat temperature sensed by sensing bulb on suction tube at Outlet of evaporator coil. As long as this bulb contains some liquid refrigerantj this temperature is con verted into pressure pushing downward on the diaphragm, which opens the valve via push rods,
2. The Suction pressure at outlet of evaporator coil is trans ferred via the external equalizer tube to underside of diaphragm.
3. The needle valve On pin carrier is spring-loaded, which also exerts pressure on underside of diaphragm via push rods,
which doses valve. Therefore, bulb pressure equals evapo rator pressure at outlet of coil plus spring pressure. If load increases, temperature increases at bulb, which increases pressure on topside of diaphragm, which pushes pin carrier
away from seal, opening valve and increasing flow of re:frigerant. The increased refrigerant flow causes increased leaving evaporator pressure which is transferred via the
equalizer tube to underside of diaphragm, with which the pin carrier spring pressure closes valve. The refrigerant flow is effectively stabilised to load demand with negligible change in superheat.
The bi-flow TXV is used on split system heat pumps. In cooling mode, TXV operates the same as a standard TXV previously explained. However, when system is switched to heating mode of operation, refrigerant ,flow is reversed. The bi"flow TXV has an
additional internal cheeje valve and external tubing. These addi tions allow refrigerant to bypass TXV when refrigerant flow is reversed with only a 1- to 2-psig pressure drop through device. When heat pump switches to defiost mode, refrigerant flows through a completely open (not throttled) TXV, The bulb Senses the residual heat of outlet tube of coil that had been operating in heating mode (about S5“F and 155 psig). This temporary, not throttled valve, decreases indoor pressure drop, which in turn .
increases refrigerant flow rate, decreases overall defrost time, and enhances defrost efficiency.

I. PROBLEMS AFFECTING TXV

A. Low Suction Pressure

1. Restriction in TXV
2. Low refrigerant charge
3. Low indoor load
4. Low evaporator airflow

B. High Suction Pressure

1. Overcharging 2, Sensing bulb not secure to vapor tube 3, High indoor load
4. Large evaporator face area
When installing or removing TXV, wrap TXV with a wet cloth. When reattaching TXV, make sure sensing bulb is in good thermal contact with suction tube.

PISTON BODY CLEANING OR REPLACEMENT

CAUTION; Do not vent refrigerant to atmosphere. Re^
A
cover during system repair or final unit disposal.
CAUTION: Damage may occur to the scroll compressor
A if operated at a negative suction pressure during a system
pumpdown.
1. Pump down outdoor unit. Close service valves at outdoor unit.
2. Recover remaining refrigerant from tubing and coil through gage port On vapor-tube service valve.
3. Disconnect refrigerant (liquid) tube from piston body, (See Fig. 13.)
4. Avoid damaging seal ring or machined surfaces on piston,
bore, and retainer.
5. Using small wire with a hook on end of it, remove piston from body.
A93530
Fig. 13—Refrigerant Flow-Control Device
(For FA, FB, and FF)
CAUTION: When cleaning the pi?ton orifice, be careful
not to scratch or enlarge the opening, as this will affect
A
operation.
6. Install new or cleaned piston into body.
7. Replace seal ring on retainer.
S. Reconnect refrigerant tube to piston body,
9. Pressurize tubing and coil, then leak check.
10. Evacuate tubing and, coil as necessary.
CAUTION: Use a backup wrench and do not over
tighten, as deformation of the piston body will occur,
A
Causing the piston to lodge in a partially open or closed
position.

LIQUID TUBE STRAINER

The TXV and refrigerant flow-control device is protected on the indoor coil by a wire mesh strainer. It is located inside the 3/S-in. liquid tube at field braze joint just outside unit casing. Access to
strainer is through field braze joint.
COIUCONDENSATE PAN REMOVAL

I. A-COIL UNITS

If it is determined that system does not have leaks and refiigerant
is not contaminated, proceed as follows:
1, Recover system refrigerant.
AND replacement
^15-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 8
Fig. l4"’A-Coil Component Lpç^tion
a. Attach jïiajiifüld/gage sfit to scrvict valves. b. Front seat (dose) liquid tube service valve. c. Start unit in cooling mode. d. Run unit until vapor pressure reaches 5 psig (35kPa). e. Turn off electrical supply to outdoor unit.
£ Front seat vapor service valve. g, Recover any remalning .refrigerant.
NOTE: All outdoor unit coils will hold only factory-supplied amount of refrigerant. Excess refrigerant;, such as in long-tube applications, may cause compressor internal pressure relief valve
to open (indicated by sudden rise in vapor pressure) before vapor pressure reaches 5 psig C35kPa), If this occurs, tiim riff electrical supply to outdoor unit immediately, front seat vapor service valve, and recover any remaining refrigerant,
2. Turn off electrical supply to indoor unit.
3. Disconnect condensate drain tube,
4. Disconnect liquid and vapor tubes from indoor coil. Use a tubing cutter to cut tubes.
NOTE; If a torch is used to unbrace tube set, protect fitting panel with a wet cloth or braze shield, as necessary.
5. Remove coil access panel,
6. Remove clip securing fitting panel to condensate drain pan. Remove fitting panel,
7. Remove any shipping dips, including horizontal pan clip, and slide coil/condcnsatc pan assembly out of unit.
8. Upflow or Horizontal Applications Only—Remove hori zontal condensate drain pan from coij/condensate pan assembly. (See Fig. 14.)
UTC TECH PUB
A902G8
F A X N o , 3 1 7 2 4 0 5 6 6 2
9- Remove 4 coil brackets. (See Fig. 14.)
10. Remove screws at delta plates and remove coil from vertical condensate drain pan, (Sec Fig, 14,)
11. Horizontal Applications Only—Remove coil top seal
(attached with, 4 screws) and J-shaped tube from original
coil and install it in same position on new coil. (See Fig,
14.)
12. Place coil assembly in plastic condensate pan and secure using 4 screws through delta plate, (See Fig- ,14.)
13. Horizontal andUpflow Applications Only—Attach 4 coil brackets to coil/pan assembly. (See Fig. 14.)
14. Horizontal Applications only—Place horizontal conden
sate pan into position on coil/pan assembly,
NOTE: Installation of horizontal cemdenfiate pan is not necessary for upflow or downflow applications,
15. Slide complete assembly into unit,
16. Reinstall fitting panel and reconnect clip securing fitting pane] to condensate drain pan.
17. Horizontal Applleotions Only — Reinstall horizontal pan clip. Secure with 1 screw. (See Fig. 14.)
18. Reinstall coil access panel.
19. Reconnect liquid and vapor refrigerant tubes, and conden sate drain tube. Install Elter-drjer(s), if necessary.
20. Eyhcu^ate tube set and indoor coil, back seat (open) liquid and vapor service valves.
21. Turn'bn electrical supplies to indoor and outdoor units.
22. Check system refrigerant charge and operation. See "Split-
System Residential Air Conditioners and Heat Pumps Service Manual" for further information,

II. SLOPE COIL UNITS .

If it is determined that system does not have leaks and refrigerant is not contaminated, proceed as follows:
1. Recover system refrigerant.
16-
AÏÏG/14/2008/THÏÏ 03:49 PM UTC TECH PUB
FAX No. 317 240 5662
P. 017
a. Attach manifold/gage set to service valves, b. Front scat (close) liquid tube service valve, c. Start yirit in cooling mode. d. Run unit until vapor pressure reaches 5 pSig (35kPa).
c. Turn off electrical supply to outdoor unit. f. Front seat vapor Service valve. g. Recover any remaining refrigerant.
NOTE: All outdoor unit coils will hold only factory-supplied amount of refrigerant. E?tcess refrigerant, such as in long-tube applications, may cause compressor internal pressure relief valve
to open (indicated by sudden rise in vapor pressure) before vapor pressure reaches 5 psig (35Ji:Pa). If this occurs, turn off electrical supply to outdoor unit immediately, front seat vapor service valve, and recover any remaining refrigerant.
2. Turn off electrical supply to indpor unit.
3. Disconnect condensate drain tube,
4. Disconnect liquid and vapor tubes from indoor coil. Use either a tubing cutter to cut tubes or a torch to unbrace tubes as required.
NOTE: If a torch Is used to unbraze line set, protect fitting panel
with a wet doth or br^e shield, as necessary. System contains oil
vapors which may ignite when ejeposed to a flame.
5. Remove coil access and fitting panels.
6. Remove 1 screw securing coil to unit casing.
7. Remove coil/pan assembly from unit.
8. Place assembly oti; a flat surface. Removc=2 screws securing coil support columns to pan. (See Fig. 15.)
9. Rotate columns 90“, pull away from coil, and remove columns from assembly.
10. Remove remaining 2 screws securing coil to condensate pan,
11. Remove coil from condensate pan.
12. Remove coil top seal, (See Fig. 15.)
.13. Install new coil into condensate pan using 2 original screws
and 2 support columns.
NOTE: Correct coil position in condensate pan is essential to
reliable operation.
14. Install new coil/pan assembly into unit. Secure with 2 Sci:c'vv5 previously removed from unit casing,
15. Reinstall coil access and fitting panels.
16. Reconnect liquid and vapor refrigerant tubes, and conden sate drain tiibe. Install fr]t6r-drier(s), if necessary.
17. Evacuate tube set and indoor coil, back scat (open) liquid and vapor service valves.
18. Turn on electrical supplies to indoor and outdoor units.
19- Check system refrigerant charge and operation. See ''Split-
System Residential Air^Gonditioners and Heat-Tumps Service Manual" for further information.
WARNING; Disconnect all power to the unit before
servicing the field wires Or removing the control package. The disconnect (when used) on the access panel does not
A
disconnect power to the line side of the disconnect, but does allow safe service to all other parts of the unit.
Electrical shock can cause personal injury or death.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect and clean or replace air filter each month or as required.
2. Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary. An inspection port is provided on all A-coil delta plates. Remove plastic plug to inspect. Replace plug after inspec tion.
3. Inspect blower motor and wheel for cleanliness each
heating and cooling season. Clean as necessary.
4. Inspect electrical connections for tightness and controls for proper operation each heating and cooling season. Service as necessary.
WARNING: As witja^any mechanical equipment, per
A
sonal injury can .result frpm sharp metal edges. Be careful
^vyhen, removing,parts.

I. FILTER ASSEMBLY

To clean Or replace air filter, push plastic connectors toward center
of unit and remove filter access panel outward. -Push filter up and back into unit. Then slide filter out. Clean filter by tising cold water and mild detergent. Rinse and allow filter to dry. No oiling or coating of filter is required. New filters are available from your local distributor. Place filter in slot with cross-mesh binding up or
facing cooling coil and replace filter access panel,

II. COOLING COIL, DRAIN RAN, AND CONDENSATE DRAIN

The cooling coil is easily cleaned when it is dry. Inspect the coil and clean (if necessary) before each cooling season. To check or clean cooling coil, rethov^ coil access paiidl. If coil is coated with dirt or lint, vacuurn it' with a soft brush attachment.
Be careful not to bend coil fins. If coil is coated with oil or grease,
clean it with a mild detergent and water solution. Rinse coil thoroughly with olpar water;^Be careful not,to splash water on insulation,
Inspect drain pan and condensate drain at the same time cooling coil is checked. Clean drain pan and condensate drain by removing any foreign matter fitom pan. Flush pan and drain tube with clear
water. If drain tube is restricted, it can generally be cleared by high-
pr'essure water. Cut plastic line and, work outside condensate pan and away from coil to clpan drain tube, ,,

CARE AND MAINTENANCE

To continue high performance, and minimize possible equipment failure, it is essential periodic maintenance be performed on this equipment,
11)6 ability to properly perform maiuteuauce on this equipment requires certain mechanical skills and tools- The only consumer service recommended or required is filter maintenance. (See Filter Assembly.)
-17-
CAUTION: Dp not use caustic household drain cleaners
A
in the condensate pan or near the coil. Drain cleaners can quickly destroy a coil,'

III. BLOWER MOTOR AND WHEEL

Clean blower motor and wheel when cooling coil is cleaned.
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 4 9
UTC TECH PUB
1 , 3 1 7 2 4 0 5 6 6 2
P , 0 1 8
CAUTION: Disconnect elfictdcd power before remov-
A
Щ any access panels.
To clean blower motor or blower wheel:
1. Remove blower access panel.
2. Remove motor leads from PCB. Note lead loofttion for case of reassembly.
3. Remove 2 outside screws holding blower/jiiotor assembly against blower-deck flange and slide assembly out of cabinet,
4. Remove screw in strap holding motor capacitor to blower
housing and slide capacitor Out from under strap. Remove screw with green wire from blower housing. Mafic blower wheelj motor, and motor support in relation to blower housing before disassembly to ensure proper reassembly.
Note position of blades on wheel,
5. Loosen setscrew holding blower wheel onto motor shaft,
6. Remove 3 bolts holding motor mount to blower housing and
slide motor and mount out of housing. Further disassembly should not be necessary as adequate clearance is available.
7. Remove blower wheel from housing by removing cutoff plate from blower housing outlet. Note wheel orientation and cutoff location for reassembly. The blower motor and wheel may be cleaned by using a vacuum With a soft-brush attachment.
S. Remove grease with a mild solvent such as hot water and
detergent. Be careful not to disturb balance weights (clips)
on blower-wheel vanes. Also, do not drop or bend wheel, as balance will be affected.
To reassemble blower:
f. Place blower wheel back into housing. Be sure to position
correctly for proper location.
2. Reassemble cutoff plate to housing using identified holes disassembly procedure.
3. Position motor and mount in same position as when blower
housing was in unit. Secure motor mount on housing, using removed bolts. Make sure mount or motor is grounded to. blower hoiising.
4. Locate blower wheel setscrew over flat on motor shaft.
Rotate wheel in housing. It should not mb housing and
should be centered in inlet opening. If notj loosen setscrew
and align as necessary.
5. Attach green wire to blower housing with screw.
6. Secure motor capacitor under strap and tighten strap screw.
7. Slide blower assembly to blower deck. Be sure (once blower is within the unit casing) to force blower assembly toward control box while sliding assembly into unit to ensure that blower assembly engages deck properly.
8. Fasten blower assembly to deck with screws previously removed.
9. Reconnect electrical leads to PCB.
10. Reconnect electrical power to unit and test fan for proper rotation.

FF1A/FF1B SERVICE AND TROUBLESHOOTING

WARNING: Before installation or servicing system, always turn off main power to system: There may be more than 1 disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury or death.

L FAN MOTOR

The motor is 2-spccd direct drive. High-speed lead is black, low-speed lead is red, and common lead is violet. Be sure proper blower speed has Ьeí^п selected. For units with electrical heat, low-speed tap can be used. For cooling, use high-speed tap.
The motor is turned on through 2 different routes. The first occurs when thermostat calls for the fan in cooling, heat pump, or fan-only mode, A 24-vac signal is sent to relay, causing relay to dose its normally-open contacts, turning fan on. The second occurs when there is a call for electric heat. A 24-vac signal is sent to heater sequencer, causing it to dose, directing 230v through the normally-closed contact of fan relay, turning fan on. The fan remains on until sequencer opens. Refer to FFIA/FFIB typical
wiring diagram Shown in Fig. 16. If motor docs ПШ, test motor for an open winding or a winding
shorted to motor case. If any 1 of the 2 is present, replace motor.

II. ELECTRIC HEATER SERVICE

Service can be completed with heater in place. Shut off power
before servicing,

A. Limit Switch

Malfunction prevenís heating element from coming on. Replace switch if malfunction occurs.
B. Sequencer
Malfunction causes heater not to come on or never shut off.
Replace sequencer. '

C. Transformer

A 40-va transformer supplies 24-v power for control circuit. Replace transformer if faulty,

NOTE: Transformer is fused. Do not short circuit. D. Fan Relay

Malfunction causes unit fan not to run Or run continuously. Replace relay.
III. CLEANING OR REPLACING REFRIGERANT FLOW­CONTROL DEVICE
Refer to Fig. 13 and instructions given in Piston Body Cleaning or
Replacement section above,

IV. LIQUID TUBE STRAINER

The refrigerant flow-control device is protected by a wire mesh strainer. It is located inside the З/8-Ín. liquid tube at field braze
joint next to flow-control device. Access to strainer is through field
braze joint.

V. SEQUENCE OF OPERATION

Refer to Fig, 16,
A. Condensing Unit

COOLING

When thermostat calls for cooling, the circuit between R and G is complete and single-pole single-throw relay FR is energized. The nomially-open contacts close causing blower to operate. The circuit between R and Y is also complete. This completed circuit causes contactor in outdoor unit to close which starts compressor and outdoor fan.
-18^
AÜG/14/2008/THD 03:49 PM UTC TECH PUB
FAX No. 317 240 5662
P.019
SCHEMATIC DIAGRAM FOR 2. 9. & 5 KW HEATERS
SEE RATING PLATE
POR VOLTS & HZ
FIELD
POWER
SUPPLY
chassis'''^ Rp
GROUND TRANS
^V!0—
-r^GPN <:(FyG^ BRN
----
I,-----
_____
.SCHEMATIC DIAGRAM FOR 7.5 & 11 KW HEATERS
SEE RATING PLATE
FOR VOLTS Bl HZ
chassis“'^
GROUND
-[^ORN
SCHEMATIC DIAGRAM FOR COOLING CONTROL
SEE RATING PLATE
FOR VOLTS Si HZ
FIELD
POWER
-ORN
----------------
----
BLK
IFR fTDR OPTIONAL MOTOR CAP
BLK™(^ f^{^BLK
^ ' (^RED-
BLK slkKAVcpíO-^
SEQ ^LS
I
—BLK
IFR (TDR OPTIONAL) MOTOR CAP
BLK-(3)-|
BLK~—I HTR2
BLK^(^ f(^BLK-<AAX>2p—
■ SEQ - HTR1
SEQ ^LSI
RED |— BLU
OPTIONAL IFR/TDP
-BLK IFR [TDR OPTIONAL) MOTOR CAP
BLK©H f©)“BLK
©-RED,
a FR
OPTIONAL IFR/TDR
------------
(¿y^RED
Kiy-eLK-oWo^p—I
YEL
-----
-----
I£1^YEL
^V)0-
-------------
-VlO
9^7^BRN2_
---------------
BLK-
BLK-
CHASSIS
GROUND
COMPONENT ARRANGEMENT
TRANS I ÈAV
BLK 208 230
COM BLU RED
HTR2
DISCONNECT
WHEN EQUIPPED
MOTOR SPEED SÉLECTION
HI = BLACK LOW = RED COMMON = VlO
FIEl4D,W|RE
HEAT PKG.
2KW
3KW 5 KW 7,5 KW 11 KW 0 (COOLING)
o
'
o
LS
FR IFR IFR/TD SEQ CAP HTR
TRANS
/7*7
UNIT WiRED-FQR 230V OPERATION USING BLACK AND RED TRANSFORMER PRIMARY
LEADS, FOR 2dSV OPERATION, USE BLACK
AND'BLUE TRANSFORMER-PRIMARY LEADS. UNUSED TRANSFORMER LEADS MUST BP TAPED
.AND1.QQPED,.
IF ANY OF THE ORIGINAL WIRE. AS SUPPLIED, MUST BE REPLACED, USE THE
SAME DR EQUIVALENT WIRE. FIELD WIRING. USE COPPER CONDUCTORS.
ONLY. FAN RELAY M IS A DEAD TERMINAL FOR
UNUSED MOTOR LEAD STORAGE. TO CHANGE MOTOR SPEEDS, EXCHANGE THE BLACK AND RED MOTOR LEADS ON THE FAN RELAY.
MARKED TERMINAL
UNMARKED TERMINAL LIMIT SWITCH FAN RELAY INDOOR FAN RELAY INDOOR FAN RELAY/TIME DELAY
SEQUENCER CAPACITOR HEATER TRANSFORMER ' FIELD POWER WIRING
OPTIONAL WIRING FUSE CHASSIS GROUND
SIZE
' ^4
12
. ID'
8
6
14
LEGEND
■ NOTES
TEMP.
RATING
90"C
90“C
go'C âü“c
30"C 90“C

316596-401 REV. B

FÎ0. 16—FF1A/FF1B Typical Unît Wiring Label
-19-
A9114Q
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 0
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
P .

HEATING

When thermostat calls for heating and FAN switch is set on AUTO, the circuit between R and W is complete. The heater sequence SEQ is enfirgjitd which closes contacts of relay. There will be a time delay. This completed circuit enejgijes all heating elements HTR and blower motor.
B, Heat Pump COOLING
On a call for cooling, the thermostat makes circuits R-0, R-Y, and
R“Q. Circuit R-0 energizes reversing valve, switching it to cooling position. Circuit R-Y energizes contactor starting outdoor fan motor and compressor. Circuit R-G energizes indoor unit blower relay starting indoor blower motor. When thermostat is satisfied, its contacts open de-energizing contactor reversing valve and blower relay. This stops compressor and fan nibtofs.
HEATING
On a call for heating, the thonnostat makes circuits R-Y and R-G, Circuit R-Y energizes contactor starting outdoor fan motor and compressor. Circuit R-G energizes indoor blower relay starting
blower motor. Should temperature continue to faIl„R-W circuit is made through second-stage room thermostat bulb. Circuit R-W energizes a sequencer bringing on supplemental electric heat.
When thermostat is satisfied, its contacts open de-enftrgiiing
contactor and sequencer. All heaters and motors should stop.
VI. CARE AND MAINTENANCE
The minimum maintenance requirements for this equipment are as follows:
1. Inspect and clean or replace air Eltor each month or as required.
2. Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary,
3. Inspect blower motor and wheel for cleanliness each heating and cooling season. Clean-as necessary,
4. Inspect electrical connections for tightness and controls for proper Operation each heating and cooling season. Service as necessary.
WARNING: As with any mechanical equipment, per
A
sonal injury can result fi:om sharp metal edges. Be careful when removing parts.
A. Air Filter
To clean or replace air filter, grasp it at bottom and lift it out of unit. Clean filter using cold water. Rinse clean and let dry. Oiling or coating of filter is not required. To replace, stand filter in rack with binding facing coil. Press top edge under access panel.
NOTE: Steel rods in filter prevent it from being pulled into coil.
Retain these rods and reinstall after cleaning or before replacement if new filter is used.
A CAUTION; Never operate unit without a filter.
B. Cooling Coil, Drain Pan, and Condensate Drain
The cooling coil is easily cleaned when it is dry. Inspect coil and clean (if necessary) before each cooling season. To check or clean
cooling coil, remove blowcr/hcatcr access panel to gain full access to cooling coil- If coil is coated with dirt or lint, vacuum with a soft brush attachment.
Be careful not to bend coil fins. If coil is coated with oil or grease, clean it with a mild detergent-and-water solution. Rinse coil with clear water. Be cajcfol not to splash water onto insulation.
Inspect drain pan and condensate drain at same time cooling coil is checked. Clean drain pan and condensate drain by removing any foreign matter from pan. Flush pan and drain tube with clear water.
If drain tube is restricted, it- can generally be cleared by high­pressure water. Cut plastic line and work outside condensate pan
and away from coil to clear drain tube.
NOTE: There MUST be a trap in condensate line. Trap must be
at least 3-in. deep, not higher than the bottom of unit condensate drain opening, and pitched downward to an open drain or sump.
CAUTION: Do not use caustic household drain cleaners
A
in condensate pan or near coil. Drain cleaners can quickly
destroy coils.
C. Blower Motor and Wheel
Clean blower motor and'wheel when cooling coil is-cleaned.
To clean or service wheel or motor, proceed as follows:
1. Pull unit disconnect (when used) and remove blower access panel.
2. Disconnect motor electrical leads from control box and capacitor. Mark location of wires for reassembly.
3. Remove 3 bolts holding motor mount to blow'er bousing
while supporting motor shell with hand.
4. Pull motor inlet ring and blower wheel assembly out of blower housing.
5. With blower wheel, inlet ring, and motor mount still attached to motor, place motor on flat, horizontal surface,
shaft up, Mark position of wheel on motor shaft for reassembly.
6. Loosen blower wheel setscrew and remove blower wheel
from motor shaft.
NOTE: Further disassembly of motor and mount is not necessary
■ as adequate clearance is available to clean motor.
7. Qean blower motor and wheel using a vacuum with a soft
brush attachment- Remove grease with a mild solvent such as hot water and detergent. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not drop or bend wheel as balance will be affected.
To reassemble unit, proceed as follows;
1. Place motor with mount attached on flat, horizontal surface with shaft up-
2. Sef inlet ring 6n fop of motor mount grommets/ Center inlet ring flush on all 3 grommets.
3. Slide blower wheel onto motor shaft with setscrew upward and aligned with shaft flat portion. Vertically position wheel along shaft to position marked during disassembly.
NOTE: If previous shaft was not marked or if replacing previous motor, set blower wheel position by sliding blower wheel along motor shaft to 1-1/8 in, above rubber grommets. (See Fig, 17,)
4. Hold blower wheel in place and carefully tighten setscrew,
5. Position motor and blower wheel assembly to blower housing as originally oriented.
6. Secure motor mount to blower housing using bolts previ ously removed.
7. Attach green wire to blower housing with screw.
8. Connect electrical and capacitor leads to original terminals.
9. Replace blower access door and tighten all 4 screws,
10. Reinsert disconnect pullout only after blower access door is secured. Test blower for proper operution.
-20-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 0
UTC TECH PUB
ni
N o , 3 1 7 2 4 0 5 6 6 2
P . 0 2 1
BLOWER WHEEL
INLET RING
AÔËÛOS

FD3A SERVICE AND TROUBLESHOOTING

WARNING: Btfom instaJlation or servicing system,
always turn off main powet to system. There may be more than 1 disconnect switch/Turn off accessory beater power if applicable. Electrical shock can cause personal injury or death.

1. FAN MOTOR

The motor is 2-spccd direct drjve. High-speed lead is black, low-speed lead is red, and common lead is yellow,
NOTE: Unused fan speed leads must be tapped off to prevent
direct short to cabinet surface. The motor is turned on through 2 different routes. The first occurs
when thermostat calls for the fan in cooling, heat pump, or fan-only mode. A 24’Vac signal is sent to relay, causing relay to close its normally-open contacts, turning fan on. The second
occurs when there is a call for electric heat. A 24-vac signal is sent to heater sequencer, causing it to close, directing 230v through the normally-closed contact of fan relay, turning fan on- The fan remains on until sequencer opens. Refer to FD3A typical wiring diagram shown in Fig. 18.

li. ELECTRIC HEATER SERVICE

Service can be completed with heater in place. Shut off power before servidng-

A. Limit Switch

Malfunction prevents heating element from coming on. Replace
switch if malfunction occurs,
B. Sequencer
Malfunction causes heater not to come on or never shut off. Replace sequencer.
C. Transformer
A 60-va transformer supplies 24-v power for control circuit. Replace transformer if faulty.
NOTE: Transformer is fused. Do not short circuit.

D. Fan Beley

Malfunction causes unit fan not to run or run continuously. Replace relay.

E, Heater Removal

Disconnect wiring, remove 2 sheet metal screws, and pull heater out through Open hinged access panel. When replacing heater, ensure orientation of he&ter element is same as when removed.
ML cleaning OB REPLACING REFRIGERANT FLOW-
CONTROL DEVICE
1. Pump down outdoor unit. Close service valves at outdoor unit.
CAUTION: Damage may occur to the scroll compressor
if operated at a negative suction pressure during a system pumpdown.
2. Bleed and (if possible) recover remaining refrigerant from tubing and coil through gage port on vapor-tube service
valve.
3. Disconnect liquid refrigerant tube from refrigerant flow-
control device. Refer to Fig, 19,
4. Remove refrígerapt flow-control device piston retainer. Avoid damaging 6-xing or machined surfaces on piston, bore, and retainer,
5. Using small wire with a hook on end of it, remove piston
from refrigerant flow-control device body.
CAUTION: When cleaning piston orifice, be careful not
A
to scratch or enlarge opening as this will affect operation.
-21-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 0
1-2
1-1
UTC TECH PUB
FIELD POWER SUPPLY
F A X N o , 3 1 7 2 4 0 5 6 6 2
SCHEMATIC DIAGRAM
P . 0 2 2
BLK—h5)-bLkAP[^
BLK^ SEQ ^
6LK—<2H
FH(3>—RED
N H
---------------
D E ! I
o M
---------------
R 0 I !
^
□RN
^
-----
L^h-
BRN
COMPONENT ARRANGEMENT
BED BRN
( IFM )- YEL r
------------
BLK -\ _ y—arm-?, 9 1^^ 9
/(OI=TIoWa1>,HTR-2 1 ft.3
SEQ /ipT'CJNAL>^HTB.1 ,g ,
_ r note #2
^
QT
—VlO^LS-2
— TRANS
^^E_NqTE^^-^
-------
REm£pWE^WtplNG [y
- LEGEND -
““ FIELD POWER WIRING " - FIELD GROUND WIRING
-----
FIELD CONTROL WIRING
FIELD SPLICE
-•- JUNCTION
O MARKED CONNECTION
o UNMARKED CONNECTION FC FAN CAPACITOR FR FAN RELAY
HTR HEATER
IFM indoor fan motor
LS LIMIT SWITCH
QT QUAD terminal
SEQ SEQUENCER
TB TERMINAL BLOCK
TRANS TRANSFORMER
NOTES:
(OPTIONAL)
(fl
___
FUS!BLE_L1N1^^
----
WIRE SLEEVE
1. TRANSFORMER PIGTAILS: BLUE 20$V; RED 2ggV; INSULATE UNUSED LEAD.
2. FAN MOTOR pIGTaIls: RED LOW; BLACK HIGH, INSULATE UNUSED LEAD.
3. FAN MOTOR THERMALLY PROTECTED.
4. SUITABLE FOR USE WITH COPPER
OR COPPER CLAD ALUMINUM CONDUCTORS RATED FOR TS'-C MINIMUM. FOR COPPER USE 6
AWG. FOR COPPER CLAD
ALUMINUM USE 4 AWG,

40DQ500784 REV. C

Fig. 18—FD3A Typical Wiring Diagram
-72^
u
A94376
A U G / 1 4 / 2 0 0 8 / T H D 0 3 : 5 0
n
Fig, 19—Refrigerant Flow-Control Device
CAUTION: Use a backup wrench and do not over
tighten as deformation of refrigerant flow-control device
A
body will occur, causing piston to lodge in a partially
Open Or closed position.
6. Install new or cleaned piston in refrigerant flow-control device body.
7. Install new retainer (because of probable damage which occurred in initial remov&J)-
8. Reconnect refrigerant tube to refrigerant flow-cOntroI de vice.
9. Pressurize tubing and coil, then leak-check.
10. Evacuate tubing and cojl as necessary.

)V. LIQUID TUBE STRAINER

The refrigerant flow-coittrol device .is. protected on indoor coil by a wire mesh strainer. If strainer becomes plugged:
1. Complete items 1 and 2 under Cleaning or Replacing Refrigerant Flow-Control Device section.
2. Loosen flare fitting joint connecting refrigerant flow­control device to coil liquid refrigerant tube.
3. Remove sheet metal screw holding bracket clip in place, Screw is located between coil and refrigerant flow-control
device,
4. Pull bracket clip out.
5. Remove refrigerant flow-control device assembly,
6. Pull strainer out of coil liquid refrigerant tube and replace with new strainer,

V. CARE AND MAINTENANCE

WARNING: Hinged access panel contains electrical
A
components and is heavy. Support panel when lowering to clean unit to avoid personal injury.
WARNING: Disconnect electrical power to all circuits
A
before servicing unit. Failure to do so may result in personal injury from electrical shock ox movingiparts.
WARNING: As with any mechanical equipment, per
A
sonal injuXy can result from sharp metal edges. Be careful
when removing parts.
The minimum maintenance requirements for this equipment arc as
follows:
UTC TECH PUB
(For FD3A and FG3A)
-23-
F A X N o . 3 1 7 2 4 0 5 6 6 2
1. Inspect and dean or replace field-supplied air filter each
month or as required.
2. Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary. (To be performed by trained personnel.)
3. Inspect blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary,
4. Inspect electrical connections for tightness and controls for proper operation each heating and cooling season. Service
as necessary,
NOTE: Never operate without a Alter or with hinged access door
Open, Damage to blower motor may result.
A. Cooling Coll, Drain Pan, and Condeneata Drain
Remember to disconnect electrical power before opening hinged access panel.
The cooling coil ig easily cleaned when dry. Inspect coil and clean (if necessary) before e&ch cooling season. If coil inlet face is coated with dirt or lint, vacuum with a soft brush attachment.
Be careful not to bend coil flns. If coil is coated with oil or grease,
clean it with a mild detergent-and-hot water solution. Rinse coil with olear water. Be careful not to splash water onto insulation.
Inspectidrain pan and condensate drain at same time cooling coil is checked. Clean drain pan and condensate drain by removing any foreign matter from pan. Fliish pan and drain tube with dear water. Clear drain line ifrresfricted.
NOTE: There MUST be a trap in condensate line. Trap must be
at least 3-in. deep, not higher than the bottom of unit condensate drain opening, and pitched downward to an open drain or sump.
B. Blower Motor and Wheel
Clean blower motor and wheel when cooling coil is deaned. Lubricate , motor every 5 years if motor is used on-intermittent opefafidn (thermostat FAN switch at AUTO position);, or every 2 years if motor is in continuous operation (thermostat FAN switch
at ON position). Remove motor to lubricate. Put approximately 8 drops of SÁE 10 nondetergent oil in each oil hole. Do not bveroil motor. Plug hole securely so that oil does not drip when hinged access panel is lowered'to 'open position.
Blower motor and wheel may be cleaned using a vacuum with a soft brush attachment. Remove grtaae with a mild solvent such as
hot water and detergent. Be careful not to disturb balance weights (dips) on blower wheel vanes. Do not drop or bend wheel as balance will be affeefed.
FG3A service and TROUBLESHOOTING
1. SERVICE

A. Motor ......................

Ball bearing oilers are provided on blower motor. Use electric motor oil 6r SAE lp or'20 nondetergent oil. Check motor mount
bracket and''Í3ás¿ bolte. Tighten as required.
B. Blower
Check ball bearings for wear. Ball bearings are self-aligning and
grease packed. Replace as required. Check thrust collars for end
play and alignment of wheel. Check blades for accumulation of.
dirt. Clean as required. Check mounting brackets, base bolts, and
isolation material. See Fig, 20 for diagram of internal wiring for blower coil
assembly. Control box (standard 4-in. junction box) is mounted on
refrigerant connection side of unit. All leads pass through strain relief where they enter Control box. Wiring inside cabinet is located so it does not come in contact with moving parts or sharp edges,
C. Pulley and Belts
Check beJt tension and pulley alignment. (See Fig, 21,) Belt tension is adjusted by motor tailpiece bolt, A deflection of about
3/4 in. to 1 in, per foot of span should be obtained by pressing belt
P . 0 2 3
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 1
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2

B. Coil, Drain Pan, and Condensate Drain

UNE
:}
GROUNO LEAD
A91151
Fig. 20—Wiring Schematic
firmly. Lock adjusting bolt in position after adjustment is made. Align pulley grooves by locating motpr pujley on motor shaft or by moving entire motor along motor mounting bracket. Adjust blower speed by loosening setscrew in outer (moveable) pulley face and turning this face (half or full turns) so that adjusting setscrew is
positioned precisely over the flat on pulley hub. Speed is reduced by adjusting pulley faces so they are further apart; speeds is increased with faces closer together. Cheek pulley setscrews and bolts.
A91150

Fig. 21—Checking Pulley Alignment and Tightness

D. Cleaning or Replacing Refrigerant Flow-Control
Device
Refer to Fig. 19 and instructions given in FD3A Service and Troubleshooting section above,

II, MAINTENANCE

WARNING: Disconnect electrical power to all circuits
A
before servicing unit. Failure to do SO may result in
personal injury from dcctrical shock or moving parts.
WARNING: As with any mechamcaj equipment, per
A
sonal injury can result fi'om sharp metal edges. Be careful when removing parts.

A, Return-Air Filter

To clean or replace sir filter, remove screws and filter access door. Slide out filter. For washable type filters, clean with hot soapy
water. Rinse clean and let dry. New filters are available from a local distributor. Place filter in slot
with filter arrow facing direction of airflow. Replace filter access doors with screws previously removed.
CAUTION: Never operate unit without a filter or with
A
filter access door removed. Damage to blower motor may result-
CAUTION: Discounect electrical power before remov
A
ing any access panels or electrical shock may result.
The coil is easily cleaned when dry. To check or clean coil, remove coil access panel. If coil is coated with dirt or lint, vacuum with a soft brush attachment.
Be careful not to bend fins. If coil is coated with oil or grease, it may be cleaned with mild detergent and water solution. Rinse coil with dean water. Be carciiil not to splash water on insulation or filter.
Check drain pan and condensate.drain at same time cooling, coil is checked. Clean drain pan and condensate drain by removing any foreign matter from pan. Check for rust and holes. Flush pan and drain tube- with clear water. If drain is restricted, clean with high-pressure water. If this does not work. Use a plumbery's snake or similar probe device. Rcpitch drain pan to promote proper drainage.
FA4A, FB4A. AND FC4B SMART HEAT CIRCUIT BOARD

I. PCB COMPONENT LAYOUT, DESCRIPTION, AND FUNCTION

NOTE: All voltages are AC unless otherwise specified.
2. Jumper wires (JWl and JW2). (See Fig. 22.)
FUNCTION AND TROUBLESHOOTING
1. The low-voltage terminal board is used to coimeot indoor thermostat to low, 24-v side of transformer and to serve as a junction between indoor thermostat and outdoor seefion.
a, R terminal is used to connect secondary side of trans
former to thermostat and outdoor unit. R is fused.
b. C terminal is used to connect transformer secondary
common for thermostat and outdoor unit.
c, Y terminal provides input signal from thermostat signal
ing heat pump operation,
d. G terminal provitJes input signal from thermostat signal
ing cdnUiiiiOus fan 'dperatidn,
c, O terminal provides input and junction terminal for
reversing vaive sign'd.
f, W2D terminal provides input from outdoor unit (heat
pump) signaling control board that heat pump is in
defrost.
g. W2T terminal provides input from thermostat signaling
for supplemental or emergency heat.
h. W3 terminal provides input from outdoor thermostat.
W3 and W2T are factory connected by JWl. Thl^ input is used only if an outdoor thermostat is required by local
codes.
i, Y(, rerinihar provides output from control board to
energize outdoor unit (heat pump) contactor.
a. JWl connects W2T to W3 to limit staging of electric
heat with use of an outdoor thermostat. See Table 7 for staging. Smart Heat PCB controls staging to the extent that this feature is unnecessary unless required by local
codes Or regulations.
b. Cutting JW2 sets Smart Heat PCB in efficiency mods.
With JW2 cut, there is no loss of performance due to reduced indoor blower speed when heat pump is oper
ating near balance point. This jumper may need to be cut if selected cooling fan speed is the same as required minimum motor LO speed tap selection. With JW2 cut, fan terminal LO becomes a dummy terminal.
-24-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 1
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
7 0 2 5
Fig. ;£2—Pi'inted-Cir'cuit Board (PCB)
3. A fuse is used to protect low-voltage transformer and PCB,
4. AUX+ and AUX- are connections for air.4 conditioning accessories (EAC, humidifier, etc.).
5- FI, F2, HI, and LO arc connections for indoor fan. 6, The 9-pin receptacle connects heater package wiring har
ness.
7, SECl and SEC2 are used to connect secondary side of
transformer to PCB. SECf is connected to equipment ground,
tl.

UNIT FUNCTIONS

A. Transformer NOTE: Terminals Tl, T2 (^if used), and T3 are wired to primary
or hi^h side of tr^nsfqmer.'The ^08-v tqrininal ‘(br blue wire'jf transformer Has‘ primary lfeads) is on 2D8^^^applica-’'" tjons, The 230-v tcoiimal (t;>r red witt) i$ iisAa^on'i’3'tpr 23Q-v
applications, T2 is a dummy terminal. 'i ■'■■i >

B. Electric Heat

NOTE: When troubleshooting dements, position thermostat to emergency heat. Wait approximately 12 minutes for all elements to
come On,
1. When thermostat calls for electric heat, a 24-v signal is sent to PCB through W2T, The PCE energizes first stage of electric heat.

TABLE 7—ELECTRIC

HEATER PART NO.
Heater Stage 1
KPAFH22Q1H1Q
KFAEH2301H15 15 kw Fused 3 8 11 15
KFAEH2401H20 ЙО kw Fused 6 10 15 20
10 kw Non-Fuaed 3
2. The first 2 stages come on if WZT and Y are energized at the same time. After each 10 minutes W2T iiS energized, another stage of electric heat is energized.
3. As W2T is de-energized, electric heat, stages down in S minute steps with the exception of first step. The first step will be on only half as long as -it was prior to W2T de-energizing. -y-.,
4. When W2T is energized by itself, JWl is cut, and an outdoor thermostat is used and is open, staging is limited as
in Table 7,
5. When bAlh. W3 and W2T are energized without JWl being
cut'or with outdoor thermostat closed, system operation
.! stagesdieat up to maximum level if signal is energized for
ргоры gpiouhi:_pf .time,
6/ If'órilyFW3 is energized, there is no effect on PCE, No heat
.iS'^nergiicid..

C. Acces^Órics

Terminals AU^-t- and AUX- áre energized with 24 vdc when fan is energizetl. The accessbry kit KFAIROIOIACR is used to connect'aii EAC or'humidifier. NO.TjE: "Loads cannot^be connected directly to AUX+ and AUX". Us,e the specified kit only.

D. Blower

1. Blower On Dclay—To optimize comfort, there is a 30-sec blower on delay in heat pump heating mode only.

HEATER STAGE LIMITING

STAGES (KW OPERATING)
W2T Only (JW1 cut)
2 3 4 6 9 9
A94127
W2T and W3
-25-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 1
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
2. Blower Off Delay—Smart Heat control uses a 60-scc off blower delayj as opposed to the standard 90-sec delay.

IIL SMART HEAT OPERATION

A. Cooling

The Smart Heat option controls cooling mode in same manner as conventional heat pumps are controlled. The fan has a 90-sec delay
off/oji cycle down,
B. Heat Pump Heating
The Smart Heat option docs not control heating in the conventional method. The PCB energizes compressor 30 sec before indoor fan is energized. This allows indoor coil to heat up eliminating cold-blow on start“Up,
The electric heat is staged-on to allow continuous operation of heat pump and electric,resistance heat below balance point (below point where heat pump cannot maintain dwelling temperature without supplemental heat) independent of outdoor thermostats.
Although PCB has provisions for an outdoor thermostat, it is not needed for staging. On cycle down, indoor fan remains on 60 sec to recover heat stored in indoor coil,

C- Defrost

The Smart Heat PCB stages the correct amount of supplemental
heat during defrost. If too much heat is added, system stays in
defrost for completion of defrost cycle even though thermostat is satisfied. On next cycle, 1 less element is energized during next defrost period.
NOTE: If 24-v power from thermostat is inteiiupted while unit is
in defrost mode, the default cycle will be completed before unit shuts down.

P. Troubleshooting PrInted-CIrcult Board (Diagnostic LED)

The PCB of Smart Heat option heater package contains a micro processor which controls fan operation, fan speed, outdoor unit, and heater elements. Bor troubleshooting, a service LED Indicates condition of PCB, Sec Tabic 8 for LED flash codes,
TABLE 8—LED CODES FOR SMART HEAT PCB
FLASH CONDITION INPUT SIGNALS SYSTEM OPERATION
No Light/Flash
Steady Light
Steady Flash
1 Flash
2 Flashes Y and/or W2T
3 Flashes Y and/or W2T
4 Flashes Y and/or W2T 5 Flashes
6 Flashes Y, W2D. and/or W2T Defrost Mode 7 Flashes W2T Emergency Heat Mode
IV. ELECTRICAL OPERATING SEQUENCES AND
TROUBLESHOOTING
NOTE: Refer to Table 9 for proper input and output voltages.
A. Ready-To-Start
In rcady-to-start (standby) mode, LED on board indicates a steady flash.
In this mode, 24-v power should be available at control's low
voltage terminal strip terminals R and C. If 24v is not present
across R and C, check the followiug:
Yonly
Y. 0
No Power or
Board Failure Board Fallura
Stand By Condition
or Fan Only
Heat Pump Only
Operating
Heat Pump Plus
1 Sequencer
Heat Pump Plus
2 Sequencers
Heat Pump Plus
3 Sequencers
Cool Mode
* Is low-voltage fuse on control board good? ' Are line voltage fuses FUl and FU2 good?
■ Is LED on control on steadily or not on at all? Both of these indications signal a possible board failure.
‘ Is 2ÜS/230-V power available to control across pins 7 and 9
of 9-pin connector? Is connection to board tight?

B. Continuous Fan

On a call for continuous fan, thermostat provides a 24-v input signal to G terminal on low-voltage terminal strip. Sensing this signal, the microprocessor euergizeiS a relay on control to provide
power to high-speed winding of fan motor, at 1. The fan continues
to run until fan switch on thermostat is turned off.
During continuous fan operation with no call for heating Or cooling, LED indicates a steady flash, the same indication seen when system is in standby.
The call for continuous fan operation signal can be checked by placing voltmeter leads across terminals G and C of control’s low-voltagc terminal strip. If 24v is not seen across these termi
nals, check for the following:
’ Is 24v ayailable across R and C? If not, refer to Ready-To-
Start section for items to check if 24v is not available,
■ Is thermostat function switch set for continuous operation?
Confirm fan operation. Voltage to operate fan can be confirmed by placing.voltmeter leads across terminals FI and Ш on control. The reading should be 20S/230vi If 20S/230v is not observed, check the following:
* Is 20S/23ÜV available at pins 7 and 9 of 9-pin connector? Is
connection to board tight?
' Arc line voltage fuses FUl and FU2 good?
If 20&/230V is available across terminals FI and HI and fan does not operate, check the following:
* Is fan motor capacitor good?
‘ Is blower wheel jammed or loose? Are there any other
mechanical problems preventing fan operation?

C. Cooling

On a call for cooling, room thennostat provides input signals to control board at terminals Y and O'.' Thc О signal is also available to heat pump to energize reversing valve.
When it receives both these signals, the microprocessor responds
by providing a 24-v output signal at the terminal. This output signal energizes contactor in heat pump and starts compressor. There is a 3 to 5 sec delay in output of signal.
At the same time, control energizes fan coil's fan motor on high Speed through terminals FI and HI, The LED indicator on control signals 5 flashes, indicating cooling operation.
The call for cooling signals can be confirmed by placing voltmeter leads across low-voltage terminals Yl 0, and' C, The reading should be 24v. If 24v is not available, check the following:
* Is 24v available across R and C? See Ready-To-Start section
for items to check if 24v is not available.
* Is thermostat function switch set in COOL position with
thermostat calling for cooling?
Assuming heat pump has power and is adequately charged, it should be running at this time in cooling mode. Indoor fan should also be running at this time. If indoor fan is not running, refer to Continuous Fan section for items to check.

D. Heating (Compressor Only)

On a call for heat, room thermostat provides an input signal to control board at terminal Y. This signal causes the microprocessor to provide a 24-v output signal at terminal to energize contactor in heat pump. There is a 3 to 5 sec delay in output of Y,, signal.
-26-
Á U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 1
UTC TECH PUB

TABLE 9--TROUBL1ESHOOTING VOLTAGE READINGS AND TEST POINTS

LOCATION

Li and L2

L3 and L4
9-pin connsctpr 7 and 9
T1 and T3
NORMAL READING
206/230 vac 205/230 vac
208/230 vac
206/230 vac Power to transformer

SEC1 and SEC2 24 vac

n and C 24 Vac •Power from transformer secondary
G and C 24 vac

Y and C

O and C 24 vac
W2TandC
W2D and C , .24 ,vac
LOCATION HI and F1 LO and.Fl
and C '
’9-pin connactor
1 and 4 9-pln connector
2 arid 4 9-pln connector
3 and 4
Vac—vetts AC
vdD-^/oltS DC
24 vac
24 vao
NORMAL READING
208/230 vac 208/230 vac
24'vac Power to energize contactor in heat pump (heat and cool modes)
24 vdC
24 vdc
24 vdc
Thirty Sec after Y is energized, control energizes fan motor. It may run on high or low speedy depending on its operation in previous cycle.
Compressor operation in current cycle is monitored by the smart control to determine whether a fan speed change is required for enhanced indoor comfort. The LED indicator on control signals 1
flash, indicating compressor operation only with no ejegtric heat.
The call for heat signals can be confirmed by placing voltmeter leads across dow-‘voltag6 terminals Y, and C; The readings should be 24v, -If 24v is not available, eheck the following:
■ Is 24v available across R and'C? See Rcady-To-Start section for items to chedk if 24v is not available.
* Is thermostat function switch set in HEAT position with
theimostat calling for heat?
Assuming heat pump has power and is adequately charged, it should be running at this time in heating mode. Indoor fan should also be running at this time. H indoor fan is not mnniog, refer to , Continuous Ran section for items to check- When room thermostat is satisfied, indoor fan continues to run an additional 60 sec to recover heat remaining in indoor coil.
E. Heating (Compressor end Electric Heat)
If heat pump alone cannot satisfy heat requirements of structure, room thermostat calls for additional heat by way of an input to W2
terminal of control. When this occurs, control begins sequencing on electric heaters by energizing the first sequencer. Indoor fan should be running at this time.
If room temperature requirements cannot be met, additional stages
of electric heat are energized through the other 2 sequencers, at 2.
The logic of control determines how much and bow soon these additional stages are brought on. By observing LED status light, the number of operating stages of electric heat can be determined.
The control also varies indoor fan speed depending on number of
energized stages of heat. In general, the more stages of electric
heat, the higher the fan speed.
ni
N o , 3 1 7 2 4 0 5 6 6 2
7 0 2 7

INPUT VOLTAGES

PURPOSE Main power supply Input to fen coil. Power to electric heaters
Power to smart control
Power from transformer secondary
Call for continuous fan signal from room thermostat Call for heat/cool signal from room thermostat Signal to energize reversing valve from room thermostat (cooling). Also present
during defrost, Call for eiectric heat from room thermostat Defrost initiation signal from heat pump
___
OUTPUT VOLTAGES
; ; PURPOSE Power to blower motor (high speed) Power to blower ,motor_(low speed)
Power to energize SEQ 1
NOTE: Sequencers use DC voltage
Power to energize SEQ 2
Power to energize SEQ 3
There is no hard and fast rule for detennining exactly when stages will be energized since microprocessor in the smart control constantly monitors duration of previous heating cycle, setting of room thermostat, and number of stages of heat needed in previous cycle to satisfy room thcmiostat. Rather than try to determine what should be operating when, service technicians should check LED status light to see how many stages of electric heat are energJKfid at a given time and confirm operation of sequencer using a voltmeter. If a quick check of all stages is desired, set room
thermostat as high as it will go. With a constant signal on W2T terminal, sequencers energize every 10 minutes until all heaters are on.
The previous paragraphs described how to' check for low-voltage inputs to control by placing voltmeter leads across low-voltage terminal strip and checking for 24v, The call for electric heat can
be confirmed by placing voltmeter leads across W2T and C. To check for operation of" sequencers, check' directly across
appropriate sequencer coil for 24 volts DC, NOTE: All sequencer coils are powered by 24 volts DC. This
voltage is generated internally by the smart control. In this example, sequencer 1 is being checked. The procedure is
the same for all other sequencers. If 24 volts DC is not observed,
check the following;
* Is room thermostat calling for electric heat? This can be
confirmed by checking for 24 volts AC between low-voltage terminal strip terminals W2T and C-
* Is LED flashing appropriate code for number of sequencers
energized? In this example, 2 flashes should be visible, indicating 1 sequencer is energized. Indicator tells how many sequencers are energized, but docs not tell which ones are.
' Is 9-pin connector for heater package tightly secured to
control board?
-27-
AUG/14/2008/THU 03:52 PM UTC TECH PUB
FAX No, 31 7 240 5662
P, 028

R Checking Sequencer Operation

To check for operation of power circuit of ¡sequencer, place voltmstsr leads across sequencer teroiinal 1 of sequencer 1 and terminal 4 of limit switch 3. The reading should be 208/230v, and heater should be energized.
If 20S/230v is not observed at teritiinals specified, check the

following:

• Are fuses FU3 and FU4 good? * Is limit switch LS3 Open? If so, check fan coil air filter or air
distribution system for blocking or restriction that might
reduce airflow pud cause limit switch to open.
Operation of heaters can be confirmed^fiiither by using a clamp-on ammeter in circuit shown to verify current is flowing through heaters. Amperage readings will depend, on size of heater. The procedure fOr checking other sequencers in system is identical to that just described,
G. Emergency Heat
Emergency heat mode requires that room thermostat be placed in EMERGENCY HEAT position. This locks, out and prevents operation of heat pump outdoor unit. In tlits mode, heat is provided exclusively by electrical heaters in fan qoil.
In this mode, room thermostat, at 1, provides'an enaergency heat input signal to smart cdntrol at teiminaj WZT, If jumper JWl, at 2, has not been cut and an outdoor .thermostat installed to control electric heat stages, that samc input signal is applied to tcmiinakJ> W3. For this example, assume that jumper JWl has not been cut-
Evcntually, the total number of heaters is cycled on. In emergency heat mode, LED iijdicator signals 7 flashes.
The amount of emergency heat available depends on whether jumper JWl is cut and the nupiber of heatiji^ elements. Table 10 ­illustrates results under various conditions. The heaters cycle on every 5 minutes until maximum level is reached.
TABLE 10—EFFECT OF JW1 ON EMERGENCY HEAT
jWi cut*
4 elements
50%
JW1 not cut
4 elements
100^
Outdoor thermostat opens
With cut, an-outdoor thermostat (if closc^) could cycle on additional heaters and system would perform as if JWl was not cut. In effect, closed Outdoor thermostat replaces cut jumper,
3 elements
66.7%
3 elements
100%

H. Defrost

In defrost mode, LED indicator signals 6 flashes. Defrost is initiated by heat pump and is signalled to smart control by an input to W2D terminal During defrost, outdoor unit switches to cooling mode, making it necessary to cycle on electric heaters to temper indoor air.
If electric heaters were not energized prior to defrost, smart control energizes ’sufficient elements to temper air. If heaters were energized prior‘to defrost, additional heaters may ОГ may not be
cycled on to provide additional heat-
Л defrost initiation signal can be confirmed by attaching voltmeter leads ac/oss low-vcjltage terminals W2D and C. If 24v is not
observed, check the following;
* Is 24v available across R and C? See Ready-To-Start section
for items to check if 24v is not available,
* Is there continuity in thermostat leads between heat pump
and smart control?
* Is defrost control in heat pump operating properly?
-25-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 2
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
P .
1. USE COPPER WIRE (75-C MIN) OMLVa^EEM DISCONNECT SWITCH AND UNIT. "v,
2. CONNECT LOW VOLTASE WIRINS AS SHOWN (24VAC).
3. CONNECTTHANSFOñMÉflPRIUAHYTO-mEPHOPER
VOLTAGE TERMINAL
4. TO BE WIRED IN ACCORCJANCE WITH NEC AMD LOCAL CODES
5. IP ANY OF THE ORIGINAL WIRE,AS 5UPPUED, MUST BE
REPLACED. USE THE SAME OH EQUIVALENT TYPE WIRE
e, REPLACE LOW VOLTAGE FUSE WITTi NO GREATER THAN
6 AMP FUSE.
7, REFERTOTHSHMOSTATINSTRUCnONS FOR'E'JUMPER
INSTAliATlON.
B, DOHOTCQNNECTTHERMOSTAT’E" to PCB ’W3".
MINIMUM MOTOR LO SPEED TAP SELECTION
FAN COIL SIZE
l^MGTOR speed AT 20 KW
030
MED
033 030
MED
035
LO
LO LÖ LO
042 043 030
CAP CAPACITOR COMM COMMON F LOW VOLT FUSE
FW FAN MOTOR
GND EQUIPMENT GROUND
hplV heat pump LOW volt
HTR HEATffl
ls umit switch
070
LO LO
Fig. 23—Sm^rt Heat Typical Wiring Diagram (Motor Speed at 20kw Shown)
322251-101
REV.B
DtAGNOSTIC LIGHT O
LED
LOW VOLT TERM BRD
LVTB
SEQUENCER
SEQ
TRANSFORMER
TRAN JiFQRM PCBTHANTERMINAL8
---------
REID LOW VOLTAGE
HPLV LEADS
1 PUSH
£ FLASHES
3 FLASHES
4 FLABHHS
A FLASHES
0 MARKED TERMINAL 6 FLASHES
I
------
1 PCB JUMPER (JW)
a UNMARKED TERMINAL
7 FIASHE6
HEAT PUMP H^T
ONLY OPERATING
HEAT PUMP PLUS
iSEQUENCER .
HEAT PUMP PLUS
a SEQUENCERS
HEAT PUMP PLUS
3 SEQUENCERS
COOLMODE
DEFROST MODE
EMERGENCY HEAT
MODE
A94132
-29-
A U G / 1 4 / 2 0 0 8 / T H U 0 3 : 5 2 P M
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
A large selection of product, theory, and skills p[ograrris is available, using popular video-based formats and materials. All include video and/or slides, plus companion
hook.
Classroom Service Training plus "hands-on" the productejn our.labs can mean increased cxjnfidencelhat.reaily pays.dividehdsjn faster .tjpubleshooiing, fewer callbacks. Course descriptions and schedules are in our catalog,
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
SERVICE TRAINING
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
CALL FOR FREE CATALOG
[] Packaged Service Training [ J -Classrddrn Service Training
Afl432S
® i33G BDP Co,' KO. 7d ‘ Indianapolte, ipJ 4^206 Print0{J In u,s,A, _30 —
14072 Calalng No. 92-33FA-416
Loading...