Bryant ERVBBSVA1100 User Manual

ERVBBSVA1100, ERVBBSHA1100 HRVBBSVA1100, HRVBBSHA1100 ENERGY/HEAT RECOVERY VENTILATOR
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
PAGE
INTRODUCTION 1...................................
UNIT INSTALLATION 2...............................
WALL CONTROL 4...................................
OPERATING THE ERV/HRV WITH
ACCESSORIES 6.....................................
BALANCIN G E RV /HRV 7..............................
TROUBLESHOOTING 9...............................
1. Fresh air to building port
2. Exhaust air from building port
3. Fresh air from outside port
4. Exhaust air to outside port
A08103
Fig. 1 -- ERV/HRV Unit (Top Port)
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses, protective clothing, and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand these signal wo rds; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
The Energy/Heat Recovery Ventilator (ERV/HRV) is used to exchange indoor stale air with outside fresh air. The unit is equipped with a special energy/heat recovery core which transfers both sensible and/or latent heat between the fresh incoming air and stale exhaust air. The cross--flow design core allows entering and leaving air streams to transfer heat and/or latent energy without mixing (See Fig. 3).
FRESH AIR STALE AIR FROM BUILDING
FROM OUTSIDE
.
Fig. 2 -- ERV/HRV Unit (Side Port)
A05330
FRESH AIR TO BUILDING
Fig. 3 -- ERV/HRV Airflow During Air Exchange
(Bottom view with access door removed)
STALE AIR TO OUTSIDE
A07460
The model operates at 2 airflows, 50 CFM in low speed and 100 CFM in high speed. This unit comes in two configurations, vertical or horizontal. Special attention should be given to duct application, balancing the ERV/HRV, and locating unit for easy access and routine maintenance.
INSTALLATION CONSIDERATIONS
Inspect Equipment
Move carton to final installation location. Remove ERV/HRV from carton taking care not to damage unit. Remove all packaging and inspect unit for damage. Remove parts bag from inside unit. File claim with shipping company if shipment is damaged or incomplete. Check to make sure ERV/HRV unit matches Fig. 1 or Fig. 2.
Select Location
The ERV/HRV should be located in a conditioned space and in close proximity to a fused power source. It should be easily accessible for routine maintenance.
If ERV/HRV is installed independent of a forced--air system, unit should be located near the center of the air distribution system. If ERV/HRV is installed in conjunction with a forced--air system, unit
ERV / HRV
should be located next to (or close to) the indoor equipment.
COMPONENT DESCRIPTION
The following listed items are components o f ERVBBSHA (See Fig. 4).
1. Exhaust--air connected to outdoor air exhaust hood.
2. Fresh--air intake connected to outdoor air inlet hood.
3. Fresh--air supply from ERV connected to return--air duct of forced--air system.
4. Mechanical filters trap dust contained in the air.
5. Energy recovery core is a cross--flow type. The core trans­fers heat between the 2 air streams.
6. Blowers bring in fresh--air from outside and exhaust stale-­air to outside.
7. Electronic control circuit ensures proper unit operation.
8. Stale air return from building connected to return--air duct system.
WALL CONTROL
ERV ports on side (bottom view)
4 5
3
2
7
4
8
1
6
A05263
Fig. 4 -- Conventional Horizontal Unit
See Fig. 5 for terminal connector block for wiring wall and timer controls.
UNIT INSTALLATION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not install ERV/HRV in a corrosive or contaminated atmosphere.
Mount Unit
The ERV/HRV can be suspended from floor joists using chains and 4 springs. Attach metal hanging bracket to all 4 sides of cabinet. (See Fig. 6.) The unit may be installed on a shelf if an isolation pad is provided to dampen vibration. Unit should always be installed as level as possible.
CAUTION
Ris k of electric s hoc k. Be fore per formin g
any maintenance or s ervici n g, al way s
disconnect the unit fr om it s p ower s our ce .
Unscr ew both screws to open the electrical
compar tment . To com plete ly remo ve , detac h
No light OFF or remote controled Amber light LOW speed Green ligh HIGH speed Blinking light See User Manual Sans lumière Arrêté ou contrôlé par contrôle mura l Lumière ambre Basse vitesse Lumière verte Haute vitesse Clignotant Voir guide d’utilisation
WARNING
CAUTIO N
from it s retention wire in s ide.
AVER TISS EMENT
Danger d’électr ocution. Dé branchez toujour s l’a ppareil avant d’entre p rendr e des tra vaux d’entretien ou de ré paration.
AT TENTION
Dévi ss er le s deux vi sp our ouvrir le com par timent
électrique . Pour retirer com plètement , le détacher de son fil de rétention intérieur .
Terminal Connector
BLACK
GREEN
RED
YELLOW
Fig. 5 -- Control Connector
2
CONTROL
CONNECTOR
A
B
A07418
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not install return--air registers (or stale--air pickup registers) in same room as gas furnace or water heater.
A05331
Fig. 6 -- Chain Spring Installation
Independent System Application
In the absence of a forced--air system and a typical duct system layout, the ERV/HRV can be applied as an independent or stand alone unit. To ensure comfort, this type of application involves running both fresh--air and return--air registers (or stale--air pickup registers) throughout the home.
Fresh--air registers are normally located in bedrooms, dining room, living room, and basement. It is recommended that registers be placed 6 to 12” (152 to 305mm) from the ceiling on an interior wall and airflow directed toward ceiling. If registers are floor installed, airflow should be directed toward the wall.
Return--air (or stale--air pickup registers) are normally located to draw from kitchen, bathroom, basement, or other rooms where stale--air can exist.
Proper size and type of registers must be used to minimize pressure drop. The velocity of airflow through register should not be above 400 ft (122m) per minute.
Maximum length of duct for the system should be designed according to the highest speed of the unit. Refer to specifications listed in unit Product Data Digest for ventilation capacities.
Forced--Air Application
Most ERV/HRV applications will be installed in conjunction with new or existing forced--air system. To operate properly, the fresh--air supply and stale--air return from ERV/HRV connect directly to return--air duct system. This is how the ERV/HRV distributes fresh air and removes stale air from inside of building (See Fig. 7). For these installations, furnace or fan coil blower must be interlocked and operate continuously whenever ERV/HRV is energized. See Fig. 17 for interlock wiring detail.
NOTE: The fresh air from ERV/HRV is introduced into return--air duct at a point no less than 6 ft (1.8m) upstream of furnace or fan coil. This connection should be direct (See Fig. 7). This is to allow incoming fresh --air to mix before entering indoor equipment.
NOTE: A + B = Not less than 10 ft / 3 m
A
ERV / HRV
FURNACE
B
INLET HOOD
ERV
REAR
6 ft / 1.8 m
EXHAUST HOOD
GROUND LEVEL
Fig. 7 -- Exhaust Ventilation
3 ft / .9 m MIN
INSULATED DUCT CONNECTING FRESH AIR & EXHAUST TO OUTSIDE
NOTE: Supply & exhaust ducts have
internal balancing dampers that must be adjusted.
18" / 457 mm
A07282
3
Connect Ducts to ERV/HRV
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in minor property damage from sweating duct or loss of unit efficiency and capacity.
If ERV/HRV duct work is installed in an unconditioned space, insulated flexible duct is required.
Insulated flexible duct is required on both fresh--air inlet and exhaust-- air outlet ducts connecting to exterior wall. When
using insulated flexible duct, the vapor barrier of the flexible ducts must be taped very tight to prevent condensation problems. To reduce pressure drop, stretch the flex duct and support it in a proper manner to avoid reduced airflow.
When connecting the ERV/HRV to a return--air duct system, insulated flexible duct can be used. However, when metal or rigid ducts are applied use approximately 18” (457mm) of flexible duct at ERV/HRV ports for fresh--air supply, and stale--air return. When
ERV / HRV
using metal duct from fresh--air supply to system duct work, the metal duct should be insulated. (See Fig. 8.) This can act as a silencer when connecting ducts to return--air duct system. This should eliminate transmission of noise or vibration from unit to main duct system.
CAUTION
1. Punch out holes in foam insulation and door, then insert sleeved grommets into bottom of unit using the gasket washer and nut. (See Fig. 9.)
2. Cut two sections of plastic tubing, about 12” / 305mm long and attach them to each drain.
3. Join the two short sections of plastic tubing to the “T” con­nector and the main tube as shown.
4. Make a loop in the tubing below the “T” connector to create a trap to prevent sewer gases from entering the ventilation system. (See Fig. 9.)
5. Connect unit drain to building’s main drain. Provide slight slope from unit for run --off.
STALE-AIR RETURN
FRESH-AIR SUPPLY
FLEXIBLE DUCTS CONNECTING TO
RETURN-AIR DUCT SYSTEM
A08102
Fig. 8 -- Flexible Duct Fit--Up
Locate and Install Exterior Hoods
IMPORTANT: To prevent condensation problems, insulated
flexible ducts are required on both fresh--air inlet and exhaust--air outlet ducts connecting between ERV/HRV and exterior wall.
Fresh--air intake and stale--air exhaust must be separated by at least 6 ft (1.8m). Fresh--air intake must be positioned at least 10 ft (3m) from nearest dryer vent, furnace exhaust, driveway, gas meter, or oil fill pipe. Fresh--air intake must be positioned as far as possible from garbage containers and potential chemical fumes. When possible, it is advised to locate the intake and exhaust hoods on same side of house or building. The intake and exhaust hoods should never be located on interior corners or in dead air pockets (See Fig. 7). Both intake and exhaust hoods must be 18” (457mm) from ground and at least 12” (305mm) above anticipated snow level.
After selecting proper hood locations, make appropriate size hole through exterior wall, pass flexible duct through hole and insert hood tube into duct. Tape duct vapor barrier tightly around hood tube and insert assembly back into wall and fasten securely.
Condensate Drain
(For ERV, skip this step and continue to the next step.) To connect condensate drain, proceed as follows:
A99268
Fig. 9 -- Condensate Drain With Loop Trap (HRV Only)
WALL CONTROL
Typ es
Four remote wall control options are available:
1. Basic Control (see Table 1).
2. OneTouch Control
3. Standard Control (includes dehumidistat)
4. Latent Control (includes humidistat for use with ERV’s only)
Ta ble 1 – Basic Control
MODE OPERATION
Off Off Closed to outside Off
Low
Intermittent
High
Air exchange with
outside
Air exchange with
outside
Air exchange with
outside
DAMPER
POSITION
Open to outside Low
Open to outside Low
Open to outside High
Table 2 – Recommended Humidity Levels
OUTSIDE
TEMPERATURE
50°F/10°C 55% 65%
32°F/0°C 45% 55%
14°F / --- 1 0 °C 35% 45%
--- 4 °F / --- 2 0 °C 30% 45%
--- 2 2 °F / --- 3 0°C 25% 35%
D O U B L E --- P A N E
WINDOWS
T R I P L E --- P A N E
WINDOWS
Location
The Standard Control and the Latent Control sense humidity and not temperature. They must be located in an area where they will continually monitor fresh air circulating within the home. Install ERV/HRV wall controls as close as possible to main system
FAN
SPEED
4
Loading...
+ 9 hidden pages