Bryant ERVBBLHU1150, ERVBBLHU1200 Installation, Start-up, And Operating Instructions Manual

Installation, Start-Up, and Operating Instructions
ERVBBLHU ENERGY RECOVERY VENTILATOR
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................1
INTRODUCTION ..........................................................................1
INSTALLATION CONSIDERATIONS .......................................1
Inspect Equipment ....................................................................1
COMPONENT DESCRIPTION ....................................................2
INSTALLATION ...........................................................................3
Mount Unit................................................................................3
Independent System Application..............................................3
Forced-Air Application.............................................................3
Connect Ducts to ERV .............................................................3
Locate and Install Exterior Hoods ...........................................3
Condensate Drain......................................................................4
Wall Control..............................................................................4
ELECTRICAL CONNECTIONS ..................................................4
115–vac Wiring.........................................................................4
12–vdc Wiring ..........................................................................4
ACCESSORIES..............................................................................4
Interlock Relay..........................................................................4
20 Minute Timer.......................................................................5
60 Minute Adjustable Timer ....................................................5
BALANCING ERV .......................................................................5
Balancing Dampers...................................................................6
Flow Collar ...............................................................................6
CONTROL BOARD OPERATION ..............................................8
Board Function..........................................................................8
Defrost.......................................................................................8
OFF and INTERMITTENT/OFF Mode...................................8
High-Speed Air Exchange ........................................................8
Low-Speed Air Exchange.........................................................9
CARE AND MAINTENANCE.....................................................9
Door.........................................................................................10
Filter ........................................................................................10
Blower Motor and Wheel.......................................................10
Cleaning Core .........................................................................10
TROUBLESHOOTING ...............................................................10
Wall Control............................................................................10
Control Board..........................................................................10
Blower Motor..........................................................................10
Blower Speed Selection..........................................................11
SAFETY CONSIDERATIONS
Installation and servicing of this heating equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Cancels: II ERV-64–2 II ERV-64–3
4–05
A00092
Fig. 1–ERVBBLHU Energy Recovery Ventilator
Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, or CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in personal injury or product or property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability or operation.
INTRODUCTION
The ERVBBLHU Energy Recovery Ventilator (ERV) is used to exchange indoor stale air with outside fresh air. The ERV unit is equipped with a special energy recovery core which transfers both sensible and latent heat with the fresh incoming air. The cross-flow design core allows entering and leaving air streams to transfer heat energy without mixing (See Fig. 14).
The model ERVBBLHU is available in 2 sizes with airflow ranges of 64–152 CFM, and 117–214 CFM. The design of this unit is horizontal. Special attention should be given to duct application, balancing the ERV, and locating unit for easy access and routine maintenance.
INSTALLATION CONSIDERATIONS
I. INSPECT EQUIPMENT
Move carton to final installation location. Remove ERVBBLHU from carton taking care not to damage unit. Remove all packaging and inspect unit for damage. Remove parts bag from inside unit. File claim with shipping company if shipment is damaged or incomplete. Check to make sure ERV unit matches Fig. 2.
.
—1—
3
2
16"
(56.2)
3
4
4"
(120.6)
4 PLCS
20"
(508.0)
4
1"
(25.4) 2 PLCS
1
D
2
3
5
2
16"
(58.7)
1
18
8"
(460.4)
16
(428.6)
C
G
7
5
8" DIA
(149.2) 4 PLCS
7
8"
15"
(381.0)
F
B
1
30
4"
(768.3)
E
A
NOTES:
1. FRESH AIR FROM OUTSIDE TO ERV
2. FRESH AIR FROM ERV TO HOUSE
3. STALE AIR FROM HOUSE TO ERV
4. STALE AIR FROM ERV TO OUTSIDE
MODEL NO. A B C D E F G
in. mm. in. mm. in. mm. in. mm. in. mm. in. mm. in. mm.
ERVBBLHU1150 15-1/8 384.2 4-1/16 104 5-5/8 143.3 14-1/2 368.9 10-3/8 288.9 4-3/8 111.3 7-3/4 196.9 ERVBBLHU1200 19 483 5-13/16 147.7 5-1/16 128.6 14-1/2 368.9 11-3/16 283.9 4-3/8 111.3 10-1/16 255.6
Fig. 2–Dimensional Drawing ERVBBLHU
II. SELECT LOCATION
The ERV should be located in a conditioned space and in close proximity to a fused power source. It should be easily accessible for routine maintenance.
3
6
5
11
2
If ERV is installed independent of a forced-air system, unit should be located near the center of the air distribution system. If ERV is installed in conjunction with a forced-air system, unit should be located next (or close to) the indoor equipment.
1
10
COMPONENT DESCRIPTION
The following lists components of the ERVBBLHU (See Fig. 3).
8
4
7
9
1. Stale air return from building connected to return-air duct system.
2. Fresh-air intake connected to outdoor-air inlet hood.
Fig. 3–ERVBBLHU Cross-Flow
3. Exhaust-air connected to outdoor-air exhaust hood.
4. Mechanical filters trap dust contained in the air.
5. Energy recovery core is a cross-flow type. It transfers sensible and latent energy between the 2 airstreams.
6. Blowers bring in fresh-air from outside and exhaust stale-air to outside.
9. Terminal connector block for wiring wall and timer con­trols.
10. Electrical cord connects to standard 115–v outlet.
11. Damper motor.
7. Electronic control circuit board ensures proper operation of unit.
8. Fresh-air supply connected to return-air duct system.
A00093
A00113
—2—
Maximum length of duct for the system should be designed according to the highest speed of the unit. Refer to specifications listed in unit Product Data Sheet for ventilation capacities.
III. FORCED-AIR APPLICATION
Most ERV applications will be installed in conjunction with new or existing forced-air systems. To operate properly, the fresh-air supply and stale-air return from ERV connect directly to return-air duct system. This is how the ERV distributes fresh air and removes stale air from inside of the building (See Fig. 7). For these installations, furnace or fan coil blower must be interlocked and operate continuously whenever ERV is energized.
Interlock relay kit Part No. KVAAC0101VIR is available and designed to interlock ERV with indoor equipment blower. When ERV is energized, R and G circuit inside of furnace or fan coil will energize. See Fig. 10 and interlock relay kit for additional information and Installation Instructions.
NOTE: The fresh air from ERV is introduced into return-air duct at a point no less than 6 ft upstream of furnace or fan coil. This connection should be direct (See Fig. 7). This is to allow incoming fresh-air to mix before entering indoor equipment.
IV. CONNECT DUCTS TO ERV
A92269
Fig. 4–Chain Spring Installation
INSTALLATION
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced life of this unit. Do not install ERV in a corrosive or contaminated atmosphere.
I. MOUNT UNIT
The ERV can be suspended from floor joists or rafters using chains and 4 springs. Attach a metal hanging bracket to all 4 sides of the cabinet (See Fig. 4). The unit may be installed on a shelf, if an isolation pad is provided to dampen vibration. Unit should always be installed as level as possible.
II. INDEPENDENT SYSTEM APPLICATION
In the absence of a forced-air system and a typical duct system layout, the ERV can be applied as an independent stand alone unit. To ensure comfort, this type of application involves running both fresh-air, and return-air registers (or stale-air pick-up registers) throughout the home.
CAUTION: CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. Do not install return-air registers (or stale-air pickup registers) in same room as gas furnace or water heater
Fresh-air registers are normally located in bedrooms, dining rooms, living rooms, and basements. It is recommended that registers be placed 6 to 12 in. from the ceiling on an interior wall and airflow directed towards ceiling. If registers are floor installed, airflow should be directed toward the wall.
Return air (or stale-air pickup registers) are normally located to draw from kitchen, bathroom, basement, or other rooms where stale-air can exist.
Proper size and type of registers must be used to minimize pressure drop. The velocity of airflow through register should not be above 400 feet per minute.
CAUTION: PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in minor property damage from sweating duct or loss of unit efficiency and capacity. ERV should be installed in a conditioned space with insulated flex duct for supply and exhaust air to the outdoor ambient.
Insulated flexible duct is required on both fresh-air inlet and exhaust-air outlet ducts connecting to exterior wall. When using insulated flexible duct, the vapor barrier of the flexible ducts must be taped very tight to prevent condensation problems. To reduce pressure drop, stretch the flex duct and support it in a proper manner to avoid reduced airflow.
When connecting the ERV to a return-air duct system, insulated flexible duct can be used. However, when metal or rigid ducts are applied use approximately 18–in. of flexible duct at ERV ports for fresh-air supply, and stale-air return (See Fig. 6). This can act as a silencer when connecting ducts to return-air duct system. This should eliminate transmission of noise or vibration from unit to main duct system. In addition, there are four 30–in. duct ties provided to help fasten flexible duct to port on ERV.
V. LOCATE AND INSTALL EXTERIOR HOODS
IMPORTANT: To prevent condensation problems, insulated
flexible ducts are required on both fresh-air inlet and exhaust-air outlet ducts connecting between ERV and exterior wall.
Fresh-air intake and stale-air exhaust must be separated by at least 6 ft. Fresh-air intake must be positioned at least 10ft. from nearest dryer vent, furnace exhaust, driveway, gas meter, or oil fill pipe. Fresh-air intake must be positioned as far as possible from garbage containers and potential chemical fumes. When possible, it is advised to locate the intake and exhaust hoods on same side of house or building. The intake and exhaust hoods should never be located on interior corners or in dead air pockets. (See Fig. 7) Both intake and exhaust hoods must be 18 in. from ground and at least 12 in. above anticipated snow level.
After selecting proper hood locations, make appropriate size hole through exterior wall, pass flexible duct through hole and insert hood tube into duct. Tape duct vapor barrier tightly around hood tube and insert assembly back into wall and fasten securely.
—3—
A99268
Fig. 5–Condensate Drain With Loop Trap
FLEXIBLE DUCT
FRESH-AIR SUPPLY
DUCTS CONNECTING TO
RETURN-AIR DUCT SYSTEM
STALE-AIR RETURN
A98382
Fig. 6–Flexible Duct Fit-Up
VI. CONDENSATE DRAIN
To connect condensate drain, proceed as follows:
1. Insert sleeved grommets into bottom of unit using the gasket washer and nut (See Fig. 5).
2. Cut two sections of plastic tubing, about 12” long and attach them to each drain.
3. Join the two short sections of tubing to the “T” connector and the main tube as shown.
4. Make a loop in the tubing below the “T” connector to create a trap to prevent sewer gases from entering the ventilation system (See Fig. 5).
5. Connect unit drain to building’s main drain. Provide slight slope from unit for run-off.
VII. WALL CONTROL
1. Location
The ERV wall control is unique to this unit. The ERV will not operate without it. This control senses humidity not temperature. It must be located in an area where it will continually monitor fresh
air circulating within the home. Install ERV wall control as close as possible to main system thermostat and follow same guidelines as installing a thermostat (locate approximately 5 ft. above floor, mount on an inside partitioning wall, etc.).
2. Wiring
Remove top cover assembly from wall control and pass thermostat wire through hole located on back of control before attaching to wall. Connect Y, R, G, and B (yellow, red, green, and black) between wall control and ERV circuit board following color code (See Fig. 8 and 9). Replace top cover assembly. NOTE: ERV wall control and circuit board operate on 12vdc.
3. Operation
The ERV wall control has 3 basic modes of operation, OFF, LOW, and INTERMITTENT. Be sure that all modes of operation are fully functional. See Table 1 indicating standard control operation. OFF — When wall control is OFF, ERV is de-energized and both LED’s are off. LOW — This mode ensures continuous air exchange with outside at all times. If relative humidity level inside of building is higher than setpoint, then air exchange will occur at low speed. If relative humidity level inside of building is lower than setpoint, then air exchange occurs at high speed. INTERMITTENT — If relative humidity level inside of building is higher than setpoint, then no air exchange will occur and ERV shuts off. If relative humidity level inside building is lower than setpoint, then air exchange occurs at high speed, and shuts down ERV when humidity level reaches set point. This mode is ideal for maintaining proper humidity level when continuous mode cannot. To ensure highest degree of humidity control in cooling season, intermittent mode should not be used.
4. Humidity Selection
The humidity selector is a built-in humidity controller designed to properly control humidity level in a house during summer months. This acts like a limit switch. See Table 2 to select maximum humidity level. If the house becomes too dry in winter months, put wall control in INTERMITTENT mode and turn down humidity selector to provide ventilation less frequently.
5. Latent Control
NOTE: To ensure highest degree of humidity control in cooling season, the INTERMITTENT mode should be used. See Table 1 and reference LOW and INTERMITTENT control operation listed above.
ELECTRICAL CONNECTIONS
I. 115–VAC WIRING
The ERV operates on 115vac. It comes with a power cord attached to unit and ready to plug into a fused outlet. Unit must be grounded for proper operation. All electrical connections must comply with National and Local Electrical Codes, or other ordinances that might apply.
CAUTION: ELECTRICAL / FIRE HAZARD
Failure to follow this warning could result in property or unit damage. Do not use an extension cord as a power source for operating the ERV.
II. 12–VDC WIRING
The ERV circuit board, wall control, and accessories operate on 12vdc. See section, Wall Control, item Wiring, and Fig. 8 and 9 for more information.
ACCESSORIES
I. INTERLOCK RELAY
The interlock relay kit, Part No. KVAAC0101VIR is required when installing ERV into a forced-air heating and cooling system (See Fig. 10). Mount interlock relay inside of unit below control box assembly. For additional information, refer to Installation Instructions supplied with the interlock relay kit.
—4—
The purpose of the interlock relay kit is to energize indoor system equipment (furnace or fan coil) blower whenever ERV is calling. If ERV is energized, and indoor system equipment is not, interlock relay will energize and make R and G at indoor equipment. This will insure fresh air distribution throughout the building via the central duct system.
II. 20 MINUTE TIMER
A push button timer can be used to override the wall control and put ERV into high speed for 20 minutes. Connect switches in parallel and connect leads to ERV terminals I, OC, and OL. (See Fig. 10) Push button locations are ideal in special activity areas, such as bathrooms, or kitchens, where high-speed exhaust opera­tion is needed for a short period of time.
NOTE: The 20 minute timer will not function properly unless ERV wall control is applied and working correctly. Timing function is internal to electronic circuit board. It is activated by a momentary contact between OC and OL. The I connection is to illuminate the push button. The maximum number of push button timers that can be applied is 5.
III. 60 MINUTE ADJUSTABLE TIMER
A 60 minute adjustable timer can also be used to override wall control and put ERV into high-speed operation for a select amount of time. Connect timer in parallel with push button timers, or to ERV terminals OC and OL (See Fig. 11).
The 60 minute timer will provide a minimum of 10 minutes, and a maximum of 60 minutes of ventilation at high speed.
BALANCING ERV
Balancing intake and exhaust airflow is very important for proper system operation and optimum performance when applying an ERV. Unit balancing prevents a positive and/or negative pressure within a home. Balancing the ERV is done by applying temporary flow collars and adjusting the balancing dampers to the fresh air intake and stale air exhaust ducts (See Fig. 12). Airflow is temporarily determined by connecting a magnehelic gage to the temporary flow collar (See Fig. 13). Both flow collars and magnehelic gage are included in the accessory start-up balancing kit.
6
FURNACE
INLET HOOD
REAR
18MIN
INSULATED DUCT CONNECTING
ERV
6
EXHAUST HOOD
FRESH AIR & EXHAUST TO OUTSIDE
NOTE: Supply & exhaust ducts have
internal balancing dampers that must be adjusted.
18
GROUND LEVEL
A00111
Fig. 7–Exhaust Ventilation
—5—
Loading...
+ 11 hidden pages