Bryant E 348 User Manual

S E P / 1 0 / 2 0 0 8 / W E D 1 1 : 3 2
UTC TECH PUB
F A X N o , 3 1 7 2 4 0 5 6 6 2
348
Installation Instructions
G AS-FIRED HORIZONTAL FURN ACE
Series E
39348D6 Rev 1 7/15/68 ^
The Bjjant Model 348 gas “fired forced air
horizontal furnace is certified by the Ameri
can Gas Association for attic installation .
Install in accordance with the requirements of the local utility or authority having juris diction.
The installer is referred to the American Standard "Installation of Gas Appliances and Gas'Piping, ASA Z21,30-1964, as a sound and practical guide. ' . _ __
INSPECTION
—ühe .furnace ..is- ■ shippeiLwith -GOnt-rol-s -fully-
assembled. Note that natural gas units are equipped with a combination regulator and main manual shut-Off. As assembled, the
valve handle is on the underneath side. When
,1 handle is parallel with direction of gas floWj
the valve is open; when handle is at right angles to direction of gas flow, the valve is closed.
GAS CONTROL OPTIONS
D4 - Natural Gas
Bryant Gas Control Valve Bryant Automatic Pilot Combination Regulator, Main and
“ ■
.......
Pii ot ' Ga s S upplyV'àlvé s
D5 - Natural Gas - 10G% Shut-off
.....
-^'BryanrGas Control“Wiye^^''^—--------------------------
Thermocouple Automatic ^Piìot
-
-----
Pilot Gas Valve . \
Gas Regulator Main Gas Shut-off Valve -
D2 - Propane Gas - 100% Shut-off
Bryant Gas Control Valve Thermocouple Automatic Pilot / Pilot Gas Valve
Main Gas Shut-off Valve
..- -
----------
S E P / 1 0 / 2 0 0 8 / W E D 1 1 : 3 3
UTC TECH PUB
DIMENSIONS
3 1 7 2 4 0 5 6 6 2
..
w '-ilii. 'ii.' i:i
i-
REAR
■■ All-siK;es have the same dimensions. :! ’iiOTvEii' Flue is 5" for sizes SO & ilDO; ■ ^
;. v - Flue is 6" for size 125 & 145. ^ ■
R A TIN OS AN D CAPACIT | E 5
-l-f-l
-1-
pW,-, ,
AGA RATINGS* BTU/HR
MODEL
NO;
”8Ti:a^ “^^647000^
. 100-348 I0i);000 ' j
42S-348- _..435_000^-^
145^348
*Pot elevations Up to 20Q0 ft; fori higher altitudes, reduce mtingh 4% ier:e&ch;;.lGQD^ft. above sea level. tOn size l45 permanent type filter is supplied as standard equipment. :‘See note cotidaming ait flow under
Table II, this iristfucUon. . /'■
INPUT OUTPUT' ,
. :80;000 ■ 1/2 1/2
■—iOOjDOO,-:-
145,000 , 116; 000 1/2
GAS CONNECTION SIZE :
NAT. PROP.
"■ 172 . -
------
iy_2—. .
■—^/2'
- ¡1/2 ¡.
BUilT-lN ^
FILTER
^2tT^':25jt;T^"
20 X 25 X 1
-20 3t 1-^ .i‘ . ^20 X 25 -x^il T:
FLUE
SIZE
■^■'5 5 175
.:■■■ 6
SHIPPING
---
.......
APPROX.
WT.
rers”
185 .—
185
■ 34S
- 2 -
SE P / 10 /2 0 08 / WE D 11 : 33 AM UT C T E CH PU B
F AX N o . 3 1 7 2 40 56 6 2
P . 0 03 / 00 8
SPECIAL LOCATING INFORMATION
Also see the following section on mounting the unit.
For special cases, refer to paragraphs 3 .4.2 and 3.4.3, American Standard "Installation of
Gas Appliances and Gas Piping, " ASA Z21,30
-1964.
1. Do not install unit in closet or alcove,
2. A,G.A, certified clearances from com
bustible material:
Attic Furnace From Draft Diverter 6" * From Casing Surface Line Contact Allowed From Base > Ú"
*When the furnace is mstalled in ^space large in comparison to the furnace, reduced clear
ances are permissible when combustibles in question are adequately protected.. ^
3" clearance permitted when 28 gauge sheet
damper is in the full heat or full cool position
5 . The unit should be located centrally with
respect to the air distribution system .Choose a location that will be as near the chimney as possible.
6 . For flexibility in selecting location of unit, the draft hood may be rotated 180 degrees. The manifold may also be rotated 180 de grees . The controls may then be on either
side of the furnace. They may also be in the vertical plane “ leading up or down from the manifold.
7. The wiring box is mounted externally alongside the draft hood. The wiring box is designed for field mounting on either side of the unit without breaking wiring connections .
MOUNTING THE UNIT
The unit may be placed directly on a combus-
.■tible;.;^ clearance requirements listed
should be observed.
O
to '.'the cpihbusLible "^materialxíánd ; coyjsrsíiail cómbus tibie;, .Wi'thih-;J5
Lë''''îhatéri^D' '■■is''"'àpplied' ■tb'’"the
material::and:;;covers all surfaces within 6". Other methods of protecting the combustible
,materiail'.a37e!:.':,ide ,in-.,T®ë''!^Ô,''Îlme
'èÿnl;Stanfe of Gas Appliances
and Gras P.i;ping, " AsA Z2i .30-1964* 3 . Service Access; Leave as much clearance
ad^posd'ible for service. The following is considered mihimum:' ■
■■ '25 ■’':'at filter ■ end 'to replace.;filtdr !' 6" at top for cleaning heat exchanger
4. Location with respect to codling equipment:
pf ,th,e cooling .unit to; avoid condensation in
d'^e; furnace, beating lelement.. -When ..installed
■^arallel.^yitb'.a poping,unit,^da.mpcrs or,other meani^ used to control the flow of air mast be adequate ^ tp. prevenf chilled air from entering the. furnace . If the, dampers are manually operated, they must be equipped with means
to prevent operation of either unit unless the
............... ■
...
.................
rsf'oteG'-'fhb^^^'^^^ 348'Hs A ;G.A. certified for
,painf,;d2r';iii:ie A^fth C'ombustible mater ial' abdye : ei^pept "drait hood must
, ,be ;at .least anyvcombusti^^^ material.
.Mpreifha^ dr ; line contact is not ap
proved.- ;If >an installation Gonflicts with
A*.G.A< ^PP^^'oval, consult .local codes for protective insulation requirements. See Ameri,cap Ap“ plianc.ea ;and Gas Fiping, ASA^Z2^
The draft hood may be reversed, The mani
fold may be reversed . The control's may be horizontal or vertical. See page 4.
If the unit is mounted so as to require shims
^(uneven, floor ox-craWl .space.).it must be .S;tip-_
porfed as shown in Figtire A. "When unit Is
suspended, the same kind of supjiort is re -
_quire.d.,_Riy^nt,.s.upplles..asj0pfipnaiivd.quipb\bnt_.
a suspension kit hs picturedthTi^rd B. The
_two __ chahhels, should' be plhce d 'Under the :iur_-
nace as ■ shown in The .¡Support for the blower comparftheht "Is fastened the channel and theh bent abound htid fastened to
the other end of the ciiaiiiiel shoWii in Fig ure C . This in effect mabes a support erfend­ing out under the blower, compartihenb. Note: the hanging rods for ttie suspension bars musi
be supplied by the installer. See page 5.
- 3 ^
348
Loading...
+ 5 hidden pages