Bryant DuraPac 558F, DuraPac Series Installation & Service Instructions Manual

Page 1
installation, start-up and
558F
service instructions
SINGLE PACKAGE ROOFTOP ELECTRIC HEAT/ELECTRIC COOLING UNITS
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-20
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 1
IV. Step 4 — Make Unit Duct Connections . . . . . . . . . . .9
V. Step 5 — Trap Condensate Drain . . . . . . . . . . . . . . . 9
VI. Step 6 — Make Electrical Connections. . . . . . . . . . . 10
VII. Step 7 — Make Outdoor-Air Inlet
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VIII. Step 8 — Install Outdoor-Air Hood. . . . . . . . . . . . . 14
IX. Step 9 — Install All Accessories . . . . . . . . . . . . . . 17
X. Step 10 — Install Humidity Control
Accessory for Optional Perfect Humidity™
Dehumidification Package . . . . . . . . . . . . . . . . . . . 18
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-26
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-32
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .33,34
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, rep air, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air -conditio ning equip ment, observ e precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasse s and work g love s. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install lockout tag on disconnect switch. Electrical shock could cause personal injury.
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the unit will automatically lock the com­pressor out of operation. Manual reset will be required to restart the compressor.
DuraPac Series
Sizes 180-300
15 to 25 Tons
Cancels: New II 558F-180-1
6/15/02
INSTALLATION
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb or horizontal adapter roof curb in accordance with instructions shipped with the curb or horizonta l adapter. Accessory roof curb and horizontal adapter roof curb and information required to field fabricate a roof curb or h orizo ntal ada pter roo f curb are shown in Fig. 1A, 1B and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be secured to roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof curb or adapter roof curb is critical for a leak-proof seal. Install gasket supplied with the roof c urb or adapter roof curb as shown in Fig. 1A and 1B. Improperly applied gasket can result in air leaks and poor unit performance.
Curb or adapter roof curb should be le vel. This is necessary to permit unit drain to function properly. Unit leveling toler­ance is ± sory Roof Curb or Horizontal Adapter Roof Curb Installation Instructions for additional information as required.
B. Alternate Unit Support
When the curb or adapter cannot be used, support unit with sleepers using unit curb or adapter s upport area. If sl eepers cannot be used, su ppor t l on g si des o f unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — RIG AND PLACE UNIT
Inspect unit for transportation da mage. File any claim with transportation agency. Keep unit upright, and do not drop. Use spreader bars over unit to prevent sling or cable dam­age. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tol erance is ± per linear ft in any direction. See Fig. 3 for additional infor­mation. Unit weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging instructions on unit.
A. Positioning
Provide clearance around and above unit for airflow, safety, and service access (Fig. 4-6).
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
1
/16 in. per linear ft in any direction. Refer to Acces -
1
/16 in.
Page 2
Fig. 1A — Roof Curb Details — 558F180-240
—2—
Page 3
Fig. 1B — Roof Curb Details — 558F300
—3—
Page 4
NOTE:
For preassembled horizontal adapter roof curb part no. CRRFCURB013A00, the accessory kit includes a factory-designed, high-static, transition duct. For horizontal curb part no. CRRFCURB012A00, a field-supplied transition duct is required.
Fig. 2 — Horizontal Adapter Roof Curb
and Roof Curb
UNIT 558F
180 210 240 300
NOTES
:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4-6 for unit operating weights.
MAXIMUM
SHIPPING WEIGHT
Lb Kg Ft-in. mm Ft-in. mm
1725 782 6-11 1785 810 6-11 1905 864 6-11 2255 1023 6-11
DIMENSIONS
AB
1
/22121 4- 0 1219
1
/22121 3-10 1168
1
/22121 3- 7 1092
1
/22121 3- 5 1041
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars.
5. Weights do not include optional EconoMi$er. See Fig. 4-6 for EconoMi$er weight. See Table 1 for Perfect Humidity™ Dehumidifi­cation Package weight.
6. Weights given are for aluminum evaporator and condenser coil plate fins.
CAUTION:
All panels must be in place when rigging.
Fig. 3 — Rigging Details
—4—
Page 5
Fig. 4 — Base Unit Dimensions — 558F180,210
—5—
Page 6
Fig. 5 — Base Unit Dimensions — 558F240
—6—
Page 7
(1219) if
-0
(8) on each side for top
16
/
5
-
(1219) for proper operation of damper and power exhaust if so
(1219) for proper condenser coil airflow.
-0
-0
(1219) for control box access.
(2134) for coil removal. This dimension can be reduced to 4
-0
Rear: 7
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of gravity.
NOTES:
4. Direction of airflow.
conditions permit coil removal from the top.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
(1829) to assure proper condenser fan operation.
-0
-0
Left Side: 4
Front: 4
Right Side: 4
equipped.
Top : 6
Local codes or jurisdiction may prevail.
exhaust as stated in Note #6, a removable fence or barricade requires no clearance.
cover drip edge.
for units equipped with electric heaters.
7. With the exception of clearance for the condenser coil and the damper/power
8. Dimensions are from outside of corner post. Allow 0
9. A 90 degree elbow must be installed on the supply ductwork below the unit discharge
10. The lower forklift braces must be removed prior to setting unit on roof curb.
Fig. 6 — Base Unit Dimensions — 558F300
—7—
Page 8
Table 1 — Physical Data
UNIT 558F 180 210 240 300 NOMINAL CAPACITY (tons) OPERATING WEIGHT COMPRESSOR/MANUFACTURER
Quantity...Model (Ckt 1/Ckt 2)
Stages of Capacity Control (%) Number of Refrigerant Circuits Oil (oz) (Ckt 1, Ckt 2)
REFRIGERANT TYPE
Expansion Device Operating Charge (lb-oz) Circuit 1† Circuit 2
CONDENSER COIL
Rows...Fins/in. Total Face Area (sq ft)
CONDENSER FAN
Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total)
EVAPORATOR COIL
Rows...Fins/in. Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.) Type Drive Nominal Cfm Motor Hp Motor Nominal Rpm Maximum Continuous Bhp
Motor Frame Size Nominal Rpm High/Low Fan Rpm Range Low-Medium Static
Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter
Min/Max (in.) Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Low-Medium Static
Nominal Fan Shaft Diameter (in.) Belt, Quantity...Type...Length (in.) Low-Medium Static
Pulley Center Line Distance (in.) Speed Change per Full Turn of
Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns
From Closed Position Factory Speed Factory Speed Setting (rpm) Low-Medium Static
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Cutout Reset (Auto)
High Static
Low-Medium Static
High Static
High Static
High Static
Low-Medium Static
High Static
High Static
LOW-PRESSURE SWITCH (psig)
Cutout Reset (Auto)
FREEZE PROTECTION THERMOSTAT (F)
Opens Closes
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
RETURN-AIR FILTERS
Quantity...Size (in.)
POWER EXHAUST
LEGEND
Bhp — TXV —
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and Circuit 2
**Pulley has 6 turns. Due to belt and pulley size, moveable pulley cannot be set to 0 to 1 ††Pulley has 6 turns. Due to belt and pulley size, moveable pulley cannot be set to 0 to 1/2 turns open. ***The 558F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min
NOTE:
Brake Horsepower Thermostatic Expansion Valve
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total capacity) and a
ZR68KC (24% total capacity).
uses the upper por tion of both coils.
(such as American Air Filter no. 5700 or equivalent).
The 558F180-300 units have a low-pressure switch (standard) located on the suction side.
15 18 20 25
For Operating Weights see Fig. 4-6.
1...ZR94KC,
1...ZR72KC 60/40 55/45 55/45 50/50
22 2 2
85,60 106,81 106,106 106, 106
1...ZR108KC,
1...ZR94KC
Scroll/Copeland
1...ZR125KC,
1...ZR108KC
1...ZRU140KC*,
1...ZR144KC
R-22
TXV
19-8 19-8 19-11 26-13 13-8 19-2 19-14 25-10
Cross-Hatched
4...15 4...15 4...15 3...15 (2 coils)
21.7 21.7 21.7 43.4
10,500 10,500 14,200 21,000
3...22 3...22 2...30 6...22
1
/2...1050
1100 1100 3400 2200
Aluminum Pre-Coated, or Copper Plate Fins
1
/2...1050 1...1075
Cross-Hatched
4...15 4...15 4...15 4...15
17.5 17.5 17.5 17.5
2...12x12 2...12 x 12 2...12 x 12 2...12 x 12 Belt Belt Belt Belt
6000 7200 8000 10,000
55 7.5 10
1745 1745 1745 1740
6.13 5.90
184T 184T 213T 215T
873-1021 910-1095 1002-1151 1066-1283
1025-1200 1069-1287 1193-1369 1332-1550
Ball Ball Ball Ball
1550 1550 1550 1550
4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9
4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9
1
/
1
8
9.4 9.4 9.4 8.0
8.0 8.0 7.9 6.4
7
/
1
16
1...BX...50 1...BX...50 1...BX...53 2...BX...50
1...BX...48 1...BX...48 1...BX...50 2...BX...47
13.3-14.8 13.3-14.8 14.6-15.4 14.6-15.4
37 37 37 36 44 34 44 45
——
11/
17/
3
/8-in. Copper Tubes, Aluminum Lanced,
Propeller Type
3
/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
Centrifugal Type
8.70 [208/230 v]
9.50 [460 v]
17/
13/
8
16
8
16
1
/2...1050
10.20 [208/230 v]
11.80 [460 v]
6** 6†† 6** 6††
3.5 3.5 3.5 3.5
965 1002 1120 1182
1134 1178 1328 1470
7
/
1
16
17/
16
17/
16
426 320
27 44
30 ± 5 45 ± 5
Cleanable
2...20 X 25 X 1
1...20 X 20 X 1 Throwaway***
4...20 x 20 x 2
1
/2 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
1
/2 turns open.
4...16 x 20 x 2
17/
17/
13/
8
16
16
—8—
Page 9
III. STEP 3 — FIELD FABRICATE DUCTWORK
3/4" FPT DRAIN CONNECTION
1-3/8" DRAIN HOLES
Secure all duct s to bu ilding struct ure. Use fl exible duct con ­nectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and m asti c i n acc ordance with applica­ble codes. Ducts passing through a n unc ondit i one d spa ce must be insu­lated and covered with a vapor barrier. The 558F units with electric heat require a 1-in. clearance for the first 24 in. of ductwork.
Outlet grilles must not lie directly below unit discharge. NOTE: A 90-degree elbow must be provided in the ductwork
to comply with UL (Underwriters’ Laboratories) codes for use with electric heat.
WARNING: For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90 degre e turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Due to electric heater, supply duct will require 90 degree elbow.
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS
Unit is shipped for through-the-bottom duct connections. Ductwork openings ar e show n in F i g. 7. Field-fabricated con­centric ductwork may be conne cted as shown in Fig. 8 and 9. Attach all ductwork to roof curb and roof curb basepans. Refer to installation instructions shipped with accessory roof curb for more information.
V. STEP 5 — TRAP CONDENSATE DRAIN
See Fig. 4-6, an d 10 for drain locat ion. Plug is provide d in drain hole and must be removed when unit is operating. One
3
/4-in. half-coupling is provided inside unit evaporator sec­tion for condensate drain connection. An 8 diameter nipple and a 2-in. x coupled to standard
3
3
/4-in. diameter pipe nipple are
/4-in. diameter elbows to provide a
1
/2 in. x 3/4-in.
straight path down through holes in unit base rails (see Fig. 11). A trap at least 4-in. deep must be used.
NOTE:
Do not drill in this area; damage to basepan may result in water
leak.
Fig. 7 — Air Distribution — Thru-the-Bottom
NOTE:
Do not drill in this area; damage to basepan may result in water
leak.
Fig. 8 — Concentric Duct Air Distribution
Shaded area indicates block-off panels.
NOTE:
Dimensions A, A′, and B, B′ are obtained from field-supplied
ceiling diffuser.
Fig. 9 — Concentric Duct Details
Fig. 10 — Condensate Drain Details
(558F180,210 Shown)
—9—
Page 10
Fig. 11 — Make Electrical Connections
VI. STEP 6 — MAKE ELECTRICAL CONNECTIONS
A. Field Power Supply
Unit is factory wired for voltage sh own on nameplate. When installing units, provide a disconnect, per NEC
(National Electrical Code) requirements, of adequate size (Table 2).
All field wiring must comply with NEC and local requirements.
Route power lines through control box access panel or unit basepan (Fig. 4-6) to connections as shown on unit wiring diagram and Fig. 12.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2% and the current must be balanced within 10%.
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
Unit failure as a res ult of ope ra tio n o n imp ro per line volt age or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly or light commercial therm idistat for units equipped with Per­fect Humidity™ Dehumidification option, according to the installation inst ructions included with th e accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire from subbase ter­minals through conduit in unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 13.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wi re larger than no. 18 AWG cannot be directly connected to the thermost at and will require a junction box and splice at the thermostat.
Set heat anticipator settings as indicated in Table 3. Settings may be changed slightly to pr ovide a greater degree of com­fort for a particular installation.
CAUTION: The correct power phasing is critical in the operation of the scroll compressors. An incorrect phasing will cause the compressor to rotate in the wrong direction. This m ay lead to premature compres ­sor failure.
Use the following formula to determine the percentage of voltage imbalance.
Percentage of Voltage Imbalance = 100 x
max voltage deviation from average voltage average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
=
455 + 464 + 455 3
1371 3
= 457
Determine ma ximum deviation from average voltage:
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance:
Percentage of Voltage Imbalance = 100 x
7 457
= 1.53%
UNIT
558F
All
EQUIP — GND — kcmil — NEC — TB
LEGEND
Equipment Ground Thousand Circular Mils National Electrical Code Terminal Block
Fig. 12 — Field Power Wiring Connections
REMOVABLE JUMPER
RC
RH
R
RED
Fig. 13 — Field Control Thermostat Wiring
TB1 MAXIMUM WIRE SIZE
VOLTAGE
208/230 460
350 kcmil 2/0
THERMOSTAT ASSEMBLY
PNK
W1
W1Y2
ORN
W2
W2
VIO
GC
G
BLK
Y1 Y2
Y1
BLU
UNIT LOW-VOLTAGE CONNECTIONS
C
BRN
L
X
X
WHT
—10—
Page 11
Table 2 — Electrical Data
UNIT 558F
180
210
240
NOMINAL VOLTAGE
(3 Ph, 60 Hz)
208/230 187 253 32.1 195 ——20.7 156 3 0.5 1.7 5.0 15.8/15.8
460 414 508 16.4 95 ——10 70 3 0.5 0.8 5.0 7.9
208/230 187 253 30.1 225 ——28.8 195 3 0.5 1.7 5.0 15.8/15.8
460 414 508 15.5 114 ——14.7 95 3 0.5 0.8 5.0 7.9
208/230 187 253 42 239 ——33.6 225 2 1 6.6 7.5 25.0/25.0
460 414 508 19.2 125 ——17.3 114 2 1 3.3 7.5 13.0
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
COMPRESSOR
No. 1 No. 1A No. 2
OFM IFM
FLA
Hp FLA FLA LRA kW FLA MCA MOCP†
(ea)
POWER
EXHAUST
—— — 82/ 82 110/110
4.6 18.8 ——86/ 86 110/110 ——26/34 71/ 82 109/122 110/125
4.6 18.8 26/34 71/ 82 114/128 125/150 ——42/56 117/135 166/155 175/175
4.6 18.8 42/56 117/135 172/161 175/175 ——56/75** 156/180 176/200 200/225
4.6 18.8 56/75** 156/180 182/206 200/225 —— — 41 50
2.3 6.0 —— 43 50 —— 32
2.3 6.0 32 39 62 70 —— 55 66 76 90
2.3 6.0 55 66 79 90 —— 80** 96 106 125
2.3 6.0 80** 96 109 125 —— — 87/ 87 110/110
4.6 18.8 ——92/ 92 110/110 ——26/34 71/ 82 109/122 110/125
4.6 18.8 26/34 71/ 82 114/128 125/150 ——42/56 117/135 166/155 175/175
4.6 18.8 42/56 117/135 172/161 175/175 ——56/75 156/180 176/200 200/225
4.6 18.8 56/75 156/180 182/206 200/225 —— — 44 50
2.3 6.0 —— 47 60 —— 32 39 59 60
2.3 6.0 32 39 61 70 —— 55 66 76 90
2.3 6.0 55 66 79 90 —— 80 96 106 125
2.3 6.0 80 96 109 125 —— — 124/124 150/150
4.6 18.8 ——129/129 150/150 ——26/34 71/ 82 124/134 150/150
4.6 18.8 26/34 71/ 82 129/140 150/150 ——42/56 117/135 178/166 200/175
4.6 18.8 42/56 117/135 183/172 200/175 ——56/75 156/180 187/211 200/225
4.6 18.8 56/75 156/180 193/217 200/225 —— — 61 80
2.3 6 —— 63 80 —— 32 39 65 80
2.3 6 32 39 68 80 —— 55 66 82 90
2.3 6 55 66 85 90 —— 80 96 112 125
2.3 6 80 96 115 125
ELECTRIC
HEAT*
39
POWER SUPPLY
59 60
Table continued on next page.
—11—
Page 12
Table 2 — Electrical Data (cont)
UNIT 558F
FLA — HACR — IFM — LRA — MCA — MOCP — NEC — OFM — RLA
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v.
Fuse or HACR circuit breaker.
**Electric heaters are field installed.
NOTES:
EXAMPLE: Supply voltage is 460-3-60.
NOMINAL VOLTAGE
(3 Ph, 60 Hz)
208/230 187 253 20.7 156 20.7 156 47.1 245 6 0.5 1.7 10.0 28.0/28.0
300
460 414 508 10.0 75 10.0 75 19.6 125 6 0.5 0.8 10.0 14.6
Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps
Heaters are rated at 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. To determine heater capacity at actual unit voltage, multiply 240 v or 480 v capacity by multipliers found in table in Note 4.
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
2.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
imbalance. % Voltage Imbalance
Use the following formula to determine the percent of voltage
= 100 x
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
LEGEND
max voltage deviation from average voltage
average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
COMPRESSOR
No. 1 No. 1A No. 2
452 + 464 + 455
3
1371
=
3
= 457
OFM IFM
FLA
Hp FLA FLA LRA kW FLA MCA MOCP†
(ea)
Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT:
your local electric utility company immediately.
3. MCA calculation for 558F units with electric heaters over 50 kW = (1.25 x
4. Use the following table to determine heater capacity at actual voltage.
If the supply voltage phase imbalance is more than 2%, contact
IFM amps) + (1.00 x heater FLA).
HEATER
RATING
VOLTAGE
240
0.694 0.751 0.918 1.000 ————
480
EXAMPLE: 34 kW (at 230 v) heater on 208 v
= 34.0 (.751 mult factor) = 25.5 kW capacity at 208 v.
POWER
EXHAUST
—— — — 138/138 175/175
4.6 18.8 ——143/143 175/175 ——26/34 71/ 82 138/138 175/175
4.6 18.8 26/34 71/ 82 143/143 175/175 ——42/56 117/135 181/170 200/175
4.6 18.8 42/56 117/135 187/176 200/200 ——56/75 156/180 191/215 200/225
4.6 18.8 56/75 156/180 197/221 200/225 —— — — 64 80
2.3 6 —— 66 80 —— 32 39 67 80
2.3 6 32 39 70 80 —— 55 66 84 90
2.3 6 55 66 87 100 —— 80 96 114 125
2.3 6 80 96 117 125
= 1.53%
200 208 230 240 380 440 460 480
————0.626 0.840 0.918 1.000
ELECTRIC
HEAT*
7
457
ACTUAL HEATER VOLTAGE
POWER SUPPLY
—12—
Page 13
C. Optional Non-Fused Disconnect
CONTROL MODULE
ACTUATOR
ECONOMI$ER
On units with the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 14 for wiring for 100 and 200 amp disconnect switches. Units with an MOCP (maximum overcurrent protection) under 100 will use the 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during s hipping, the disconne ct han dle and shaft are shipped and packaged inside the unit control box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Open the c o ntr ol b ox do or an d re mo ve th e handle and shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect switch. The bo lt is locate d on the square hole and is used to hold the shaft in place. The shaft cannot be inserted until the Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is spe­cially cut and the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with the two screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in the OFF position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door. The handle should fit over the end of the shaft when the door is closed.
8. The handle must be in the OFF position to open the control box door.
D. Optional Convenience Outlet
On units with optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outlet re ce ptacle is pro­vided for field wiring . F ield wir ing s ho uld be run th roug h th e
7
/8-in. knockout pr ovided in th e basepan near the retu rn air
opening.
VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS
A. Manual Outdoor-Air Damper
All units (except those equipped with a factory-installed EconoMi$er) have a manual outdoor-air damper to provide ventilation air. Damper can be preset to admit up to 25% out­door air into return-air compartment. To adjust, loosen securing screws and move dampe r to desired setting. Then retighten screws to secure damper (Fig. 15).
B. Optional EconoMi$er
EconoMi$er Motor Control Module (Fig. 16-18) Set the ECONSP dial to the ‘‘D’’ setting (Fig. 17). The control
module is located on the EconoMi$er motor. See Fig. 16 and 18.
Damper Vent Position Setting
1. Set fan switch at ON position (continuous fan opera­tion) and close night switch if used.
2. Set system selector switch to OFF position.
3. Turn Min Pos (%) dial slowly until dampers assume desired vent position. Do not manually operate
EconoMi$er motor since damage to motor will result.
Fig. 15 — 25% Outdoor-Air Section Details
NOTE:
The disconnect takes the place of TB-1 as shown on the unit
wiring diagram label and the component arrangement label.
Fig. 14 — Optional Non-Fused Disconnect Wiring
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
Fig. 16 — EconoMi$er Damper Assembly
— End View
—13—
Page 14
Table 3 — Heat Anticipator Settings
UNIT 558F
180-300
*Heater kW is based on heater voltage of 208 v, 240 v, and 480 v.
UNIT
VO LTAG ES
208/230-3-60
460-3-60
kW* STAGE 1 STAGE 2
26/34 .40 .66 42/56 .66 .40 56/75 .66 .66
32 .40 .40 55 .40 .66 80 .66 .66
Fig. 17 — EconoMi$er Control Module
Adjustment Potentiometers
CONTROL MODULE ACTUATOR
Fig. 18 — EconoMi$er Control Module Location
VIII. STEP 8 — INSTALL OUTDOOR-AIR HOOD
The same type of factory-installed hood is used on unit s with 25% air ventilation and units with an EconoMi$er.
NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baffle (300), and filter support bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and all other hardware are in a package located inside the return-air filter access panel (Fig. 19).
1. Attach seal strip to upper filter retainer. See Fig. 20.
2. Assemble hood top panel and side panels, upper filter retainer, and hood drain pan (Fig. 21).
3. Secure lower filter retainer and long section of filter support bracket to unit. See Fig. 21. Leave screws loose on size 300 units.
4. Slide baffle (size 300 unit) behind lower filter retainer and tighten screws.
5. Loosen sheet metal screws for base unit top panel located above outdoo r-air inlet opening, and rem ove screws for hood side panels located on the sides of the outdoor-air inlet opening.
6. Match notches in hood top panel to unit top panel screws. Insert hood flange between unit top panel flange and unit. Tighten screws.
7. Hold hood side panel flanges flat against unit, and install screws removed in Step 5.
8. Insert ou tdo o r-air inlet screens and spacer in c ha nne l created by lower filter retainer and filter support bracket.
9. Attach remaining short section of filter support bracket.
A. Outdoor Air Enthalpy Sensor Installation
Perform the following procedure to install the outdoor air enthalpy sensor (part no. CROUTENT001A00).
1. Remove the outdoor air temperature sensor cover. See Fig. 22. Save cover and screws.
2. Disconnect the wiring from the installed outdoor air temperature sensor. See Fig. 23.
3. Use a
1
/4-in. nut driver to remove the 2 screws secur­ing the outdoor air temperature sensor to the sheet metal.
4. Mount the outdoor air enthalpy sensor in the outdoor air temperature sensor location using the screws removed in Step 3.
5. Connect the outdoor air enthalpy sensor wiring har­ness to the EconoMi$er control module and sensor.
6. Re-install sensor cover saved f rom Step 1.
B. Return Air Temperature Sensor or Return Air Enthalpy Sensor Installation
Perform the following procedure to install the return air temperature sensor (part no. CRRETTMP001A00) or return air enthalpy sensor (part no. CRRETENT001A00).
1. Attach the sensor to the mounting bracket using 2 self-tapping
1
/2-in. screws provided.
2. Mount the bracket to the inside of the return air
1
opening flange using a
/4-in. nut driver and 2 no. 6
sheet metal screws.
NOTE: The sensor must be mounted in an upright position.
3. Feed the sensor wiring through the bushing in EconoMi$er t o sec ur e wires.
4. Route sensor wiring harness from sensor to EconoMi$er control module. Secure wiring harness to the original har ness using tie wraps.
5. Wire the sensor to the EconoMi$er control module. See Fig. 24 and 25.
Fig. 19 — Outdoor-Air Hood Component Location
—14—
Page 15
Fig. 20 — Seal Strip Location
SENSOR COVER
OUTSIDE AIR SENSOR
MOUNTING SCREW
MOUNTING SCREW
WIRING HARNESS
SENSOR WIRING CONNECTIONS
(Air Hood Cross-Sectional View)
BAFFLE (300 ONLY)
HOOD TOP PANEL
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
HOOD SIDE PANELS (2)
BAFFLE (300 ONLY)
Fig. 22 — Outdoor-Air Sensor Location
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
HOOD DRAIN PAN
UPPER FILTER RETAINER
NOTE:
The outdoor-air hood comes with a baffle which is used on
size 300 units only; discard baffle for 180-240 units.
Fig. 21 — Outdoor-Air Hood Details
C. Commissioning
The EconoMi$er saves energy when it uses outdoor air to provide free cooling instead of mechanical air conditioning. The EconoMi$er switchov er strategy determines if the out­door air is suitable for free cooling. The EconoMi$er chooses the switchover strategy with the most energy savings, pro­vided that the required sensors are connected and function­ing normally.
IMPORTANT: If a sensor stops functioning normally (becomes unreliable), the EconoMi$er switches to the next best strategy.
Refer to Table 4 to determine the sensors required for each strategy.
Fig. 23 — Outdoor-Air Sensor Details
Differential Enthalpy Switchover Strategy The differential enthalpy switchover strategy must be
selected manually, if required. To enable, press and hold the CONFIG button for 30 seconds, then release. The LED will flash twice to indicate the change of configuration.
To return to single enthalpy mode, press and hold the CON­FIG button for 30 seconds. The LED will flash once to indi­cate the change of configuration.
D. Discharge Air Thermistor (DAT)
The discharge air thermistor is factory-mounted on the supply-fan housing in the fan section of the unit. The DAT is factory-wired to the EconoMi$er Control Module.
E. CO
Control Setup
2
The CO
sensor monitors carbon dioxide levels. This infor-
2
mation is used to modify the position of the outdoor-air dampers to admit more or less air.
1. Determine the value at which the minimum positi on of the dampers will be gin opening to allow a greater amount of outdoor air to enter. The range is 800 to 1,400 ppm.
2. Locate the CO
SP (PPM) potentiometer and adjust
2
to the desired set point. See Fig. 17.
—15—
Page 16
F. Mechanical Cooling Lockout
Determine the outdoor-air temperature at which the mechanical cool ing (co mpressor s) wi ll be disabl ed. Locat e the mechanical cooling lockout (MECH CLG LOCKOUT) poten­tiometer. To disable this feature, turn the potentiometer counterclockwise (CCW) to th e OFF position. Otherwise, set the value between 10 and 60 F. Mechanical cooling will not operate when the outdoor air temperature is below this value. See Fig. 17.
G. Dry Bulb Changeover Set Up
Determine the dry bulb changeove r set point from Table 5. The settings are A, B, C and D . Locate the ECON SP potenti­ometer and set the dry bulb changeover set point. See
Table 4 — EconoMi$er Switchover Control Strategy
ECONOMI$ER SWITCHOVER STRATEGY
Dry Bulb
Single Enthalpy
Differential Temperature
Differential Enthalpy*
*Must be selected manually.
Outdoor Air Temperature Outdoor Air Enthalpy Return Air Temperature Return Air Enthalpy
X
XX
Fig. 17. When the OAT is above this set point, the damper is limited to minimum position setting.
If a potentiometer fails, its setting will default to the values in Table 6.
H. Ventilation Air (Minimum Position Set Up)
If ventilatio n ai r is n ot r eq ui re d, skip th is s ec tio n . If vent ila ­tion air is required, perform the following:
1. The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G te rminals at the ro oftop unit connecti on board.
SENSORS REQUIRED
X
XX
Table 5 — Changeover Set Points
Dry Bulb (°F) Single Enthalpy* (Btu/lb) Differential Temperature*
(°F, Not Adjustable) Differential Enthalpy*
(Btu/lb, Not Adjustable)
*Field-installed accessory.
SETTINGS A B C D
73 69 66 63 27 25 24 22
2222
1111
Table 6 — Default Potentiometer Settings
POTENTIOMETER DEFAULT SETTING
CO2 SP (PPM) MECH CLG LOCKOUT
ECON SP MIN POS (%)
1,000
50 F
D
20
CLG — COM — DAT — DM — GND — LED —
Cooling Common Discharge Air Thermistor Damper Motor Ground Light-Emitting Diode
*OAT sensor shipped with economizer option. OAH, RAT, RAH and CO
LEGEND
OAH — OAT — POT — RAH — RAT — REM —
Outdoor-Air Enthalpy Sensor Outdoor-Air Temperature Sensor Potentiometer Return-Air Enthalpy Sensor Return-Air Temperature Sensor Remote
are field-installed accessories.
2
Fig. 24 — Typical EconoMi$er Sensor Wiring
—16—
Page 17
2. Locate the minimum position (MIN POS) potentiome­ter. Turn the potentiome ter full CCW to ful ly close the outdoor air dampers. Turn the potentiometer gradu­ally clockwise (CW) to the desired position. See Fig. 17.
3. Replace the filter ac cess panel. See Fig. 19. Ensure the filter access panel is securely engaged.
4. Calculate the minimum airflow across the EconoMi$er.
a. Calculate % of outside air using the following
formula. % Outdoor air through EconoMi$er % Outdoor
air
Mixture Temp – Return Air Temp
=
Outdoor Temp – Return Air Temp
b. Multiply total CFM by percentage outdoor air,
this gives outdoor air vol um e in CFM.
WARNING: Personal Injury Hazard. Avoid possi-
ble injury by keeping finger s a way from damper blades.
IX. STEP 9 — INSTALL ALL ACCESSORIES
After all the factory-installed options have been adjusted, install all field-instal led accessories. Refer to the accessory installation instructions included with each accessory.
A. Motormaster® I Control (–20 F) Installation (558F180 and 210 Only)
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures.
See Fig. 26 for baffle de tails. Use 20-gage, galvani zed sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drill in g holes.
Install Motormaster I Controls One Motormaster I control is required on size 180 and 210
units. The Motormaster I control must be used in conjunction with the Accessory Fan Motor Sequencing Kit and Winter Start Kit (purchased separately). The Motormaster I device controls outdoor fan no. 1 whi le outdoor fans no. 2 and 3 are sequenced off by the Accessory Fan Motor Sequencing Kit.
Accessory Fan Motor Sequencing Kit — Inst all th e Acce ss or y Fan Motor Sequencing Kit per instruction supplied with accessory (purchased separately).
Winter Start Time Delay Relay Kit — Install the kit per the in­structions supplied with the accessory (purchased separately).
Sensor Assembly — Install the sensor assembly in the loca­tion shown in Fig. 27.
Motor Mount — To ensure proper fan height, replace the existing motor mount with the new motor m ount provided with accessory.
Outdoor Air Enthalpy
CROUTENT001A00
OAT COM OAH +15V RAT COM RAH +15V
CO
(+)
2
CO
2
COM DAT COM REM POT COM LED COM
Tan Violet White Red
Tan Violet White Red
T
Violet
O
C
U
O
T
T
M
PW
C O
M
Remote
Minimum Position
1k ohm Potentiometer
T
PW
O U TT
Unoccupied Control
(Part number on the control
must be AD-DME1701-1
or AD-DME1711-1.)
Unoccupied
Contact
24 VAC must be present
on BI for the system to be
Violet
470 ohm
5watt
Resistor
unoccupied.
Return Air Enthalpy
CRRETENT001A00
CO2 Sensors:
CRCDXSEN004A00
NOT
USED
2
1
2to10VDCat 0 to 2000 ppm
Line
20 VA
24 VAC
Voltage
20 mA LED
Remote
LED
-
Field-supplied Wiring W iring Included
Fig. 25 — Typical EconoMi$er Sensor Wiring
—17—
Page 18
Transf ormer (460-V Unit s Only) — On 460-volt units a trans­former is required. The transformer is provided with the accessory and must be field-installed.
Motormaster® I Control — Recommended mounting location is on the inside of the panel to the left of the con t rol box. The control should be mounted on the inside of the panel, verti­cally, with leads prot ruding from bot tom of extrusion.
B. Motormaster III Control (–20 F) Installation (558F240 Only)
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures. See Fig. 26 for ba ffle detai ls. Use 20-gage, g alvanized s heet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster III Controls Only one Motormaster III control is required per unit. The Motormaster III control must be used in conjunction
with the accessory Fan Motor Sequencing Kit and the acces­sory Winter Start Kit (purchased separately). The device controls outdoor fan no. 1 (motor change out required) while outdoor fan is sequenced off by fan motor sequencing kit.
Sensor — Install the sensor for thermistor input control in the location shown in Fig. 28. Connect sensor leads to the purple and grey control signal leads on the Motormaster III control.
Winter Start Time Delay Relay Kit — Install the kit per the instructions supplied with the accessory (2 required, pur­chased separately).
Accessory Fan Motor Sequencing Kit — Inst all t he Acce ssor y Fan Motor Sequencing Kit (purchased separately) per instructions supplied with the accessory.
Signal Selection Switch — Remove the cover of the Mot or­master III control. Set t he switch to accept the thermistor sensor input signal. Set the frequency to match the unit power supply (60 Hz).
Motormaster III Control — Recommended mounting location is beneath the control box, mounted to the partition that sep­arates the control box section from the indoor section.
NOTE: If unit power is supplied through the roof curb and basepan of the unit, mount the Motormaster III control on the corner post adjacent to the conduit running from the basepan to the bottom of the control box.
C. Low Ambient Control (10 F) Installation (558F180, 210,
300)
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures. See Fig. 29 for ba ffle detai ls. Use 20-gage, g alvanized s heet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
Install Low Ambient Controls Install the Low Ambient Control per instructions supplied
with the accessory . Fan Motor Sequencing Kit — Only one access ory Fan Motor
Sequencing Kit is require d per unit (purchased separately). Install the Fan Motor Sequencing Kit per instructi ons sup­plied with the accessory.
Winter Start Time Delay Relay Kit — Two accessory Winter Start Time Delay Relay kits are required per unit (pur­chased separately). Install the kits per the i nstructions sup­plied with the accessory.
X. STEP 10 — INSTALL HUMIDITY CONTROL ACCESSORY FOR OPTIONAL PERFECT HUMIDITY™ DEHUMIDIFICA­TION PACKAGE
Perfect Humidity dehumidification package operation can be controlled by field installation of a Bryant-approved humidistat or light commercial thermidistat. To install the control, perfor m the following procedure:
1. Locate the control on a solid interior wall in the con­ditioned space. Location should be a well ventilated area to sense average humidity.
2. For humidistat, route thermostat cable or equivalent single leads of colored wire from humidistat termi­nals through conduit in unit to the low voltage con­nection on the 2-pole terminal strip (TB3) as shown in Fig. 29 and 30. Remove jumper.
3. For light commercial thermidistat, install field­supplied relay (R1, part number HN61KK324) in con­trol box and wire the contact terminal s of relay (R1) to the low-voltag e te r min als 1 a nd 2 o n t he 2-po le ter ­minal strip (TB3). See Fig. 31. Route thermostat cable from thermidistat through conduit in unit into control box. Connect the lead from the DEHUM ter­minal of the thermidis tat to one of the coil terminals of relay R1. Wire the other coil terminal to common (C) of the rooftop unit terminal board (TB2).
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
—18—
NOTE:
Dimensions in ( ) are in mm.
Fig. 26 — Wind Baffle Details
Page 19
SENSOR
SENSOR LOCATION
HAIRPIN END
LOCATION
SENSOR LOCATION
HAIRPIN END
HAIRPIN END
558F180 558F210
NOTE:
All sensors are located on the eighth hairpin up from the
bottom.
Fig. 27 — Motormaster® I Sensor Locations
558F240
NOTE:
All sensors are located on the eighth hairpin up from the
bottom.
Fig. 28 — Motormaster III Sensor Locations
LEGEND
Circuit Breaker Liquid Line Solenoid Valve Low Pressure Switch Terminal Block Transformer
CB — LLSV — LPS — TB — TRAN —
Fig. 29 — Typical Perfect Humidify™ Dehumidification Package
Humidistat Wiring Schematic (460V Unit Shown)
—19—
Page 20
Fig. 30 — Typical Perfect Humidity™
Dehumidification Package Control Box
START-UP
Use the following information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up.
I. UNIT PREPARATION
Check that unit has been installed in accordance with these installation instructions and all applicable codes.
II. INTERNAL WIRING
Check all electrical connections in unit control boxes; tighten as required.
III. CRANKCASE HEATER
Heater is energized as long as there is power to unit and compressor is not operating.
IMPORTANT: Unit power must be on for 24 hours prior to start-up. Otherwise, damage to compressor may result.
IV. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
V. REFRIGERANT SERVICE PORTS
Each refrigerant system has a total of 3 Schrader-type ser­vice gage ports. One port is located on th e suction line, one on the compressor discharge line, and one on the liquid line. In addition Schrader-type valves ar e located u ndernea th the low-pressure switches. Be sure that caps on the ports are tight.
VI. COMPRESSOR ROTATION
It is important to be c ertain the c ompressors are rotating in the proper direction. To determine whether or n ot compres­sors are rotating in the proper direction:
1. Connect serv ice gages t o suctio n and disch arge pres ­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres­sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in the wrong direction.
2. Turn off power to the unit.
3. Reverse any two of the incoming power leads.
4. Turn on power to the compressor.
The suction and discharge pressure levels should now move to their normal start-up levels.
NOTE: When compr essors are rotating in the wrong direc­tion, the unit will have increased noise levels and will not provide heating and cooling.
After a few minutes of r eve rse o p erati on , t he s cro ll com pres ­sor internal overload protection will open, which will acti­vate the unit’s lockout and requires a manual reset. Reset is accomplished by turning the thermostat on and off.
VII. EVAPORATOR FAN
Fan belt and variable pulleys are factory installed. Remove tape from the fan pulley. See T able 7 for Air Quantity Limits. See Tables 8-11 for Fan Performance data. Be sure that fans rotate in the proper directi on. See Table 12 for Static Pres­sure information for accessories and options. See Table 13 for fan rpm at various fan motor pulley settin gs. For evaporator fan motor pe rformance, see Tables 14 and 15. To alter fan performance, see Evaporator-Fan Performance Adjustment section, page 26.
NOTE: A 3
1
/2-in. bolt and threaded plate ar e included in the installer’s packet. The bolt and plate can be added to the motor support channel below the motor mounting plate to aid in raising the fan motor.
Table 7 — Air Quantity Limits
UNIT 558F MINIMUM CFM MAXIMUM CFM
180 210 240 300
4500 7,500 5400 9,000 6000 10,000 7000 11,250
VIII. CONDENSER FANS AND MOTORS
Fans and motors are factory set. Refer to Condenser-Fan Adjustment section ( page 27) as required.
IX. RETURN-AIR FILTERS
Check that correct filters are installed in filter tracks. See Table 1. Do not operate unit without return-air filters.
X. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screen s must be in place bef ore operating unit.
XI. ACCESSORY ECONOMI$ER ADJUSTMENT
Remove filter access panel. Check that outdoor-air damper blades are closed and return-air da mper blades are open.
EconoMi$er operation and adjustment is described in Base Unit Operation and EconoMi$er Adjustment sections (pages 24 and 28), respectively.
—20—
Page 21
LCT
R
C Y1 Y2
G W1 W2
DEHUM
OC
AIRFLOW
(Cfm)
4500
4800
5100
5700
6000
6300
6600
6900
7200
7500
TB2
ROOFTOP UNIT
R
TSTAT WIRES
R1
R1
FIELD-SUPPLIED RELAY
HN61KK324
TB3
C
Y1
Y2
W1
W2
1
2
LCT — LLSV —
G
LPS — TB
LEGEND
Light Commercial Thermidistat Liquid Line Solenoid Valve Low-Pressure Switch Terminal Block
24 V
FROM PERFECT HUMIDITY LLSV
FROM PERFECT HUMIDITY LLSV
Fig. 31 — Typical Perfect Humidity™ Dehumidification Package Thermidistat Wiring Schematic
Table 8 — Fan Performance — 558F180*
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
753 1.53 1307 753 1.53 1307 784 1.64 1397 859 1.92 1635 928 2.20 1880 993 2.50 2133 747 1.62 1384 747 1.62 1384 806 1.83 1563 878 2.12 1808 946 2.42 2060 1009 2.72 2319 741 1.72 1465 752 1.76 1500 828 2.05 1745 898 2.34 1996 964 2.65 2255 1026 2.96 2521 735 1.95 1659 805 2.22 1895 876 2.53 2156 942 2.84 2423 1004 3.16 2696 1064 3.49 2975 759 2.18 1854 832 2.48 2118 901 2.80 2388 965 3.12 2663 1026 3.45 2943 1083 3.79 3228 790 2.45 2088 860 2.77 2360 926 3.09 2638 988 3.43 2920 1048 3.76 3208 1104 4.11 3501 821 2.74 2340 888 3.07 2621 952 3.41 2906 1013 3.75 3196 1070 4.10 3491 1125 4.45 3791 852 3.06 2611 917 3.40 2900 979 3.75 3194 1038 4.10 3492 1094 4.45 3794 1147 4.81 4101 883 3.40 2903 946 3.75 3200 1006 4.11 3501 1063 4.47 3807 1118 4.83 4117 1170 5.20 4431 914 3.77 3215 975 4.13 3521 1033 4.49 3830 1089 4.86 4143 1142 5.23 4461 1193 5.61 4781
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
4500
4800
5100
5700
6000
6300
6600
6900
7200
7500
AIRFLOW
(Cfm)
4500
4800
5100
5700
6000
6300
6600
6900
7200
7500
LEGEND
Bhp — Watts —
*Standard low-medium static drive range is 873 to 1021 rpm. Alternate high-static
drive range is 1025 to 1200. Other rpms require a field-supplied drive.
Brake Horsepower Input Watts to Motor
1.4 1.6 1.8 2.0 2.2 2.4
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1055 2.81 2394 1114 3.12 2662 1170 3.45 2938 1224 3.78 3220 1276 4.12 3509 1326 4.46 3805 1070 3.03 2585 1127 3.35 2859 1183 3.68 3139 1236 4.02 3427 1287 4.36 3721 1336 4.72 4020 1086 3.28 2794 1142 3.60 3073 1196 3.94 3359 1248 4.28 3650 1299 4.63 3949 1347 4.99 4253 1120 3.82 3260 1174 4.17 3551 1226 4.51 3848 1277 4.87 4151 1325 5.23 4458 1373 5.60 4772 1139 4.13 3520 1192 4.48 3817 1243 4.83 4119 1292 5.19 4427 1340 5.56 4741 1387 5.93 5060 1158 4.46 3799 1210 4.81 4102 1260 5.17 4410 1309 5.54 4724 1356 5.91 5043 —— — 1178 4.80 4095 1229 5.17 4405 1278 5.54 4720 1326 5.91 5039 —— — —— — 1199 5.18 4412 1249 5.55 4728 1297 5.92 5050 —— — —— — —— — 1221 5.57 4749 1270 5.95 5072 ———————————— 1243 5.99 5107 ———————————————
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.6 2.8 3.0 3.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1375 4.82 4107 1421 5.18 4414 1467 5.55 4728 1511 5.92 5047 1384 5.07 4326 1430 5.44 4638 1475 5.81 4955 ——— 1395 5.35 4563 1440 5.72 4879 —————— 1418 5.97 5091 —————————
———————————— ———————————— ———————————— ———————————— ———————————— ————————————
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Maximum continuous bhp for the standard motor is 6.13. The maximum con­tinuous watts is 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
2. See page 23 for general fan performance notes.
—21—
Page 22
AIRFLOW
(Cfm)
5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500
10,000
Table 9 — Fan Performance — 558F210*
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
682 1.99 1675 760 2.29 1922 832 2.59 2177 901 2.90 2441 965 3.22 2712 1027 3.56 2990 730 2.38 2005 802 2.68 2257 871 2.99 2516 935 3.31 2783 997 3.63 3057 1056 3.97 3337 778 2.82 2373 846 3.13 2630 911 3.44 2893 972 3.76 3164 1031 4.09 3440 1087 4.43 3722 828 3.31 2780 892 3.62 3042 953 3.94 3310 1011 4.26 3583 1067 4.59 3863 1121 4.93 4148 878 3.84 3227 938 4.15 3494 996 4.48 3766 1051 4.81 4043 1105 5.14 4326 1156 5.49 4613 928 4.42 3715 985 4.74 3986 1040 5.07 4263 1093 5.40 4544 1144 5.74 4830 1194 6.09 5120
979 5.05 4245 1033 5.38 4521 1085 5.71 4801 1136 6.05 5086 1185 6.39 5375 1232 6.74 5669 1030 5.73 4817 1082 6.06 5098 1131 6.40 5382 1180 6.74 5671 1227 7.09 5964 1272 7.44 6260 1082 6.46 5433 1131 6.80 5718 1178 7.14 6007 1225 7.49 6299 1270 7.84 6595 1313 8.20 6895 1134 7.25 6093 1180 7.59 6382 1226 7.94 6675 1270 8.29 6971 1313 8.65 7271 1356 9.01 7574
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500
10,000
LEGEND
Bhp — Watts —
*Standard low-medium static drive range is 910 to 1095 rpm. Alternate high-static
drive range is 1069 to 1287 rpm. Other rpms require a field-supplied drive.
Brake Horsepower Input Watts to Motor
1.4 1.6 1.8 1.9 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1086 3.89 3275 1142 4.24 3567 1197 4.59 3864 1223 4.77 4015 1249 4.96 4167 1112 4.31 3623 1167 4.66 3915 1219 5.01 4213 1245 5.19 4364 1270 5.37 4516 1142 4.77 4010 1194 5.12 4304 1245 5.47 4602 1270 5.65 4754 1294 5.83 4906 1173 5.28 4438 1224 5.63 4733 1273 5.98 5033 1296 6.17 5184 1320 6.35 5337 1207 5.83 4906 1255 6.19 5203 1302 6.55 5504 1326 6.73 5657 1348 6.91 5810 1242 6.44 5415 1289 6.80 5714 1334 7.16 6018 1357 7.34 6171 1379 7.52 6325 1279 7.10 5966 1324 7.45 6268 1368 7.82 6573 1389 8.00 6728 1411 8.18 6883 1317 7.80 6561 1360 8.16 6865 1403 8.53 7173 1424 8.71 7328 1445 8.90 7484 1356 8.56 7198 1398 8.93 7505 1440 9.29 7815 1460 9.48 7972 1480 9.67 8129 1397 9.37 7881 1438 9.74 8190 1477 10.11 8503 ——————
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
Table 10 — Fan Performance — 558F240*
AIRFLOW
(Cfm)
6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500
10,000
AIRFLOW
(Cfm)
6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500
10,000
0.20.40.60.81.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
753 2.83 2385 816 3.06 2579 884 3.33 2807 949 3.61 3040 1010 3.89 3277 793 3.25 2738 861 3.51 2959 925 3.78 3186 987 4.05 3418 1045 4.33 3653 844 3.74 3151 908 4.00 3372 968 4.27 3598 1026 4.54 3828 1082 4.82 4062 895 4.27 3596 955 4.53 3817 1013 4.80 4042 1068 5.07 4271 1121 5.34 4504 947 4.83 4073 1004 5.09 4294 1058 5.36 4518 1111 5.63 4747 1162 5.91 4978
999 5.44 4583 1053 5.70 4803 1105 5.96 5027 1155 6.23 5255 1204 6.51 5485 1052 6.08 5125 1103 6.34 5345 1152 6.61 5569 1200 6.88 5796 1247 7.15 6025 1105 6.76 5699 1153 7.02 5919 1200 7.29 6142 1246 7.56 6369 1291 7.83 6598 1158 7.48 6306 1204 7.74 6526 1249 8.01 6750 1293 8.27 6975 1336 8.55 7203
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1069 4.17 3517 1125 4.46 3761 1180 4.75 4006 1232 5.05 4255 1283 5.35 4506 1102 4.62 3891 1156 4.90 4132 1208 5.19 4377 1259 5.48 4623 1308 5.78 4871 1136 5.10 4299 1188 5.38 4538 1239 5.67 4780 1288 5.96 5025 1335 6.25 5271 1173 5.62 4739 1223 5.90 4977 1272 6.19 5217 1319 6.48 5460 1365 6.77 5705 1211 6.18 5212 1259 6.46 5449 1306 6.75 5688 1352 7.03 5929 1396 7.32 6172 1251 6.78 5718 1297 7.06 5954 1342 7.35 6192 1386 7.63 6431 1429 7.92 6673 1292 7.42 6257 1337 7.70 6492 1380 7.98 6729 1423 8.27 6967 1464 8.55 7207 1335 8.10 6830 1377 8.38 7063 1419 8.66 7299 1460 8.94 7536 1501 9.22 7776 1378 8.82 7434 1419 9.10 7667 1460 9.37 7902 1499 9.65 8138 1538 9.94 8377
1.21.41.61.82.0
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Maximum continuous bhp is 5.90. The maximum continuous watts is 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
2. See page 23 for general fan performance notes.
AIRFLOW
(Cfm)
6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500
10,000
Bhp — Watts —
*Standard low-medium static drive range is 1002 to 1151 rpm. Alternate high-
LEGEND
static drive range is 1193 to 1369. Other rpms require a field-supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1332 5.65 4750 1380 5.95 5015 1427 6.25 5272 1472 6.56 5531 1517 6.87 5793 1356 6.08 5122 1402 6.38 5375 1447 6.68 5630 1492 6.98 5886 1535 7.29 6144 1381 6.55 5519 1427 6.84 5770 1471 7.14 6022 1514 7.45 6276 —— — 1409 7.06 5951 1453 7.35 6199 1496 7.65 6449 1538 7.95 6701 —— — 1440 7.61 6417 1482 7.90 6663 1523 8.20 6911 —— — —— — 1471 8.20 6916 1513 8.49 7161 —— — —— — —— — 1505 8.84 7449 1545 9.13 7693 —— — —— — —— — 1540 9.51 8016 —— — —— — —— — —— —
—— — —— — —— — —— — —— —
Brake Horsepower Input Watts to Motor
2.22.42.62.83.0
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Maximum continuous bhp for the standard motor is 8.70 (for 208/230-v units) and 9.50 (for 460-v units). The maximum continuous watts is 7915 (for 208/230-v units) and 8640 (for 460-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operat­ing cfm.
2. See page 23 for general fan performance notes.
—22—
Page 23
Table 11 — Fan Performance — 558F300*
AIRFLOW
(Cfm)
7,000 7,500 8,000 8,500 9,000
9,500 10,000 10,500 11,000 11,250
AIRFLOW
(Cfm)
7,000
7,500
8,000
8,500
9,000
9,500
10,000 10,500 11,000 11,250
Bhp — Watts —
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-
LEGEND
Brake Horsepower Input Watts to Motor
static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
845 3.26 2693 909 3.60 2979 969 3.96 3272 1028 4.32 3574 1083 4.70 3883 1137 5.08 4,200 896 3.82 3156 956 4.17 3450 1014 4.54 3752 1069 4.91 4060 1123 5.29 4375 1174 5.68 4,698
948 4.43 3667 1005 4.80 3969 1060 5.17 4278 1112 5.56 4593 1163 5.94 4915 1213 6.34 5,243 1001 5.11 4226 1054 5.49 4537 1106 5.87 4853 1156 6.26 5175 1205 6.66 5504 1253 7.06 5,838 1053 5.85 4836 1104 6.23 5155 1154 6.63 5478 1202 7.02 5808 1248 7.43 6142 1294 7.84 6,483 1106 6.65 5498 1155 7.04 5824 1202 7.44 6155 1248 7.85 6492 1293 8.26 6833 1336 8.68 7,179 1159 7.52 6214 1206 7.92 6547 1251 8.33 6886 1295 8.74 7229 1338 9.16 7577 1380 9.59 7,929 1213 8.45 6984 1257 8.86 7325 1300 9.28 7671 1342 9.70 8020 1384 10.13 8375 1424 10.56 8,733 1266 9.45 7810 1309 9.87 8159 1350 10.29 8511 1391 10.73 8868 1431 11.16 9229 1470 11.60 9,594 1293 9.97 8245 1334 10.40 8597 1375 10.83 8953 1415 11.26 9313 1454 11.70 9677 1493 12.15 10,045
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1189 5.47 4,524 1239 5.87 4,854 1288 4.91 5191 1224 6.08 5,026 1272 6.48 5,362 1320 5.56 5703 1261 6.75 5,577 1307 7.16 5,917 1353 6.26 6263 1299 7.47 6,177 1344 7.89 6,523 1388 7.02 6873 1338 8.26 6,828 1382 8.68 7,179 1424 7.85 7534 1379 9.11 7,530 1421 9.54 7,887 1462 8.74 8247 1421 10.02 8,286 1461 10.46 8,648 1501 9.70 9014 1464 11.00 9,096 1503 11.45 9,464 1541 10.73 9835 1508 12.05 9,963 1546 12.50 10,336 ——— 1530 12.60 10,417 ——————
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Maximum continuous bhp is 10.20 (208/230 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.
2. See below for general fan performance notes.
GENERAL FAN PERFORMANCE NOTES
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See Table 12 below for accessory/factory-installed option static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature
Table 12 — Accessory/FIOP Static Pressure (in. wg)* — 558F180-300
COMPONENT
EconoMi$er Glycol Coil Electric Heat (kW)
26/34 32 42/56 55 56/75 80
Perfect Humidity™ Dehumidification Package
LEGEND
FIOP —
Factory-Installed Option
5400 6000 7200 9000 10,000 11,250
0.06 0.07 0.09 0.11 0.12 0.14
0.30 0.35 0.44 0.58 0.66 0.77
0.08 0.09 0.11 0.15 0.17 0.20
0.08 0.09 0.11 0.15 0.17 0.20
0.11 0.12 0.15 0.19 0.21 0.24
0.11 0.12 0.15 0.19 0.21 0.24
0.14 0.15 0.20 0.24 0.26 0.29
0.14 0.15 0.20 0.24 0.26 0.29
0.06 0.07 0.10 0.16 0.20 0.25
motor failure. Unit warranty will not be affected. See Table 14 for Evaporator­Fan Motor Performance on page 24 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
CFM
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in con­junction with the Fan Performance tables to determine blower rpm and watts.
—23—
Page 24
Table 13 — Fan Rpm at Motor Pulley Settings*
UNIT 558F
180† 180** 210† 210** 240† 240** 300† 300**
*Approximate fan rpm shown.
Indicates standard drive package.
†† †† †† †† 1021 1002 984 965 947 928 910 891 873 †† †† †† †† 1200 1178 1156 1134 1112 1091 1069 1047 1025 †† †† 1095 1077 1058 1040 1021 1002 984 965 947 928 910 †† †† 1287 1265 1243 1222 1200 1178 1156 1134 1112 1091 1069 †† †† †† †† 1151 1132 1114 1095 1077 1058 1040 1021 1002 †† †† †† †† 1369 1347 1325 1303 1281 1259 1237 1215 1193 †† †† 1283 1269 1247 1225 1203 1182 1160 1138 1116 1095 1066 †† †† †† †† 1551 1524 1497 1470 1443 1415 1388 1361 1332
1
0
/
2
1
11
Table 14 — Evaporator-Fan Motor Performance
UNIT 558F
180
210
240
300
BHP — BkW —
*Extensive motor and electrical testing on these units ensures that the full horse-
LEGEND
Brake Horsepower Brake Kilowatts
power (brake kilowatt) range of the motors can be utilized with confidence. Using
UNIT
VOLTAGE
208/230 6.13 4.57 5,180 15.8
460 6.13 4.57 5,180 7.9
208/230 5.90 4.40 5,180 15.8
460 5.90 4.40 5,180 7.9
208/230 8.70 6.49 7,915 22.0
460 9.50 7.08 8,640 13.0
208/230 10.20 7.61 9,510 28.0
460 11.80 8.80 11,000 14.6
MAXIMUM ACCEPTABLE CONTINUOUS
BHP*
/
2
MOTOR PULLEY TURNS OPEN
1
22
MAXIMUM ACCEPTABLE CONTINUOUS
/
331/
2
**Indicates alternate drive package.
††Due to belt and pulley size, pulley cannot be set to this number of turns open.
BkW*
your fan motors up to the horsepower (brake kilowatt) ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
NOTE:
All indoor-fan motors 5 hp and larger meet the minimum efficiency re­quirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
441/
2
MAXIMUM
ACCEPTABLE
OPERATING
WATT S
2
55
1
/
2
MAXIMUM
AMP DRAW
6
Table 15 — Evaporator-Fan Motor Efficiency
MOTOR
HORSEPOWER
5 Hp
7.5 Hp
10.0 Hp
NOTE:
All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
MOTOR EFFICIENCY
(%)
87.5
88.5
89.5
XII. BASE UNIT OPERATION
A. Cooling, Units without EconoMi$er
When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and evaporator­fan motor, compressor no. 1 and condenser fans start. The condenser-fan motors run continuously while unit is cooling . If the thermostat calls f or a se cond stag e of cooling by energ izing Y2, compressor contactor no. 2 (C2) is energized and compres­sor no. 2 starts.
B. Heating, Units without EconoMi$er (If Accessory or Optional Heater is Installed)
Upon a call for heating through terminal W1, IFC and heater contactor no. 1 (HC1) are energized. On units equipped for 2 stages of heat, when additional heat is needed, HC2 is energized through W2.
C. Cooling Units with EconoMi$er
When the OAT is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the indoor-fan motors (IFM) is energized and the EconoMi$er damper modu­lates to minimum position. The compressor contactor and OFC are energized to start the compressor and outdoor-fan motor (OFM). After the thermostat i s satisfied, the da mper modu lates to the fully closed position when the IFM is deenergized.
When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cooling by modulating the return and outdoor air dampers to main­tain a 55 F supply air set point. If the supply-air temperature (SAT) is greater than 57 F, the EconoMi$er modulates open, allowing a greater amount of outdoor air to enter the unit. If the SAT drops below 53 F, the outdoor air damper modulates closed to reduce the amount of outdoor air. When the SAT is between 53 and 57 F, the EconoMi$er maintains its position.
If outdoor air alon e cannot satisfy the c ooling requiremen ts of the conditioned space, and the OAT is above the MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below.
NOTE: Compressors have a two-minute Minimum On and Minimum Off, whic h are accomplished by the strat egies below.
1. If Y1 is energized, and the room thermostat calls for Y2 (2-stage thermostat), the compressor and OFC are energized. The position of the EconoMi$er damper is maintaine d at its current value.
2. If Y1 is energized for more than 20 minutes, and Y2 is not energized (wh ether or n ot a 2- sta ge th er mos tat i s used), the compressor and OFC are energized. The position of the Econ oMi$er damper is maintai ned at its current value.
3. If Y1 is energized, and compressor no. 1 is already energized (see Ste p 2) and the room thermostat call s for Y2, compressor no. 1 continues to ope rate. If Y2 remains energized for more than 20 minutes, com­pressor no. 2 is energized.
—24—
Page 25
NOTE: Compressor no. 2 cannot be energized unless there is a signal for Y2 from the space thermostat.
4. If compressor no. 2 is energized, and the Y2 signal from the thermostat is satisfied, compressors 1 and 2 are deenergized. Re-asserting Y2 will start compres­sor no. 1 and (after a 20-minute interstage delay) compressor no. 2.
5. If compresso r no. 1 is energized and the thermostat is satisfied, compressor no. 1, the OFM, and IFM are deenergized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set point, the compressors re main off.
D. Freeze Protection Thermostat(s)
A freeze protection thermostat (FPT) is located on the top and bottom of the evaporator coil. It detects frost build-up and turns off the compress or, allowi ng the coil to clear. Once frost has melted, the compressor can be reenergized by reset­ting the compressor lockout.
E. Heating, Units with EconoMi$er (If Accessory or Optional Heater is Installed)
When the room thermostat calls for heat, th e heating con trols are energized as described in the Heating, Units Without EconoMi$er section. The IFM is energized and the EconoMi$er damper modulates to the minimum position. When the ther­mostat is satisfied, the damper modu lates cl osed.
F. Units with Perfect Humidity™ Dehumidification Package
When thermostat calls for cooling, terminals G and Y1 and/ or Y2 and the compressor contactor C1 and/or C2 are ener­gized. The indoor (evaporator) fan motor (IFM), compressors, and outdoor (condenser) fan motors (OFM) start. The OFMs run continuously while the unit is in cooling. As shipped
from the factory, both Perfect Humidity dehumidification cir­cuits are always energized.
If Perfect Humidity circuit modulation is desired, a field­installed, w all-mounted humidistat or li ght c om me rci al th er­midistat is required. If the Perfect Humidity control is installed and calls for the Perfect Humidity subcool er coil to operate, the control energizes the 3-way liquid line solenoid valve coils (LLSV1 for circuit 1 and LLSV2 for circuit 2) of the Perfect Humidity circuits, forcing t he warm liquid refrig­erant of the liquid line to enter the subcooler coils. See Fig. 32.
As the warm liquid passes through the subcooler coils, it is exposed to the cold supply airf low comi ng off the e vaporato r coils and the liquid is further cooled to a temperature approaching the evaporator coil leaving-air temperature. The state of the refrigerant leaving the subcooler coils is a highly subcooled liquid refrigerant. The liquid then enters a thermostatic expansion valve (TXV) where the liquid is dropped to the evaporator pressure. The TXVs can throttle the pressure drop of the liquid refrigerant and maintain proper conditions at the compressor suction valves over a wide range of operating conditions. The liquid proceeds to the evaporator coils at a temperature lower than normal cooling operati on. This low er temperatu re is what i ncreases the latent and sensible capacity of the evaporator coils.
The 2-phase refrige rant pass es th roug h the e vapo rator s an d is changed into a vapor. The air passing over the evaporator coils will become col der than during normal operation as a result of the colde r refrigeran t temperatures. However, as it passes over the subcooler coils, the air will be warmed, decreasing the sensible capacity and reducing the sensible heat of the roof-top un it.
Fig. 32 — Perfect Humidity Operation Diagram (Single Circuit Shown)
—25—
Page 26
As the refrigerant leaves the evaporator, the refrigerant passes a subcooler control low-pressure switch (S-LPS1 for circuit 1 or S-LPS2 for circuit 2) in the suction line. This low­pressure switch will deactivate the Perfect Humidity™ pack­age when the suction pressure reaches 60 psig. The subcooler control low-pressure switch is an added safety device to protect against evapor ator coil freeze-up during low ambient operation. The subcooler control low-pressure switch will only deactivate the 3-way liquid line solenoid valve in the Perfect Humidity circuit. The compressors will continue to run as long as there is a call for cooling, regard­less of the position of the subcooler control low-pressure switch. The 3-way solenoid valve and the Perfect Humidity package will be reactivated only when the call for cooling has been satisfied, the subcoole r control l ow-pressure switch has closed above 80 psig, and a new ca ll for cooling exists. The crankcase heaters on the scroll compressors provide addi­tional protection for the compres sors due to the additional refrigerant charge in the subcooler.
When the humidistat or light commercial thermidistat con­trol is satisfied, the control cuts power to and deenergizes the LLSVs. The refrigerant is routed back through the evap­orators and the su bcooler coils a re removed from th e refrig­erant loops. When the thermostat is satisfied, C1 and C2 are deenergized and the compressors, IFM, and OFMs shut off. If the thermostat fan selector switch is in the ON positi on, the IFM will run continuously.
SERVICE
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch to unit and install lockout tag on disconnect switch. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury.
I. CLEANING
Inspect unit interior at beginning of each heating and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior.
A. Evaporator Coil
Clean as required with a commercial coil cleaner. NOTE: The 558F300 unit has a mist eliminator screen
attached to the evaporator c oil to preve nt condensate runoff at high wet-bulb conditions. Check periodically and clean as necessary.
B. Condenser Coil
Clean condenser coil annually and as required by location and outdoor-air conditions. Inspect coil monthly — clean as required.
C. Condensate Drain
Check and clean each year at s t art of cooling season .
D. Filters
Clean or replace at start of each heating and cooling season, or more often if opera ting c ondit ions re quire. Refer to T able 1 for type and size.
NOTE: The 558F300 unit requires industrial grade throw­away filters capable of withstanding face velocities up to 625 fpm. Ensure that replacement filters for the 558F300 units are rated for 625 fpm.
E. Outdoor-Air Inlet Screen
Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens.
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of o il at the factory. Conventional white oil (Sontext 200LT) is used. White oil is compatible with 3GS oil, and 3GS oil may be used if the addition of oil is required. See compressor name­plate for original oi l charge. A complete recharge should be four ounces less than the original oil charge. When a com­pressor is exchanged in the field it is possible that a major portion of the oil from the rep laced compress or may still be in the system. While this will not affect the reliability of the replacement compressor, the extra oil will add rotor drag and increase power usa ge. To remove this excess o il, an access valve may be added to the lower portion of the suction line at the inlet of the compressor. The compressor should then be run for 10 minutes, shut down, and the access valve opened until no oil flows . Thi s shou ld be rep eate d twice to make s ure the proper oil level has been achieved.
B. Fan Shaft Bearings
The bearings are of t he pi ll ow bl oc k t y pe a nd ha v e gre ase fit­tings. The bearing opposite the motor end has an extended tube line so it can be lubr icated fr om the motor s ide. Lubri­cate the bearings twice annua lly.
Typical lubricants are given below:
MANUFACTURER LUBRICANT
Texaco
Mobil
Sunoco
Texaco
*Preferred lubricant because it contains rust and oxidation inhibitors.
Regal AFB-2*
Mobilplex EP No. 1
Prestige 42
Multifak 2
C. Condenser and Evaporator-Fan Motor Bearings
The condenser and ev ap orat or-fan motor s have pe rman en tly sealed bearings, so no field lubrication is necessary.
III. EVAPORATOR FAN PERFORMANCE ADJUSTMENT (Fig. 33 and 34)
Fan motor pulleys are factory set for speed shown in Table 1. To change fan speeds:
1. Shut off unit power supply.
2. Loosen nuts on the 2 carriage bolts in the motor mounting ba se. Inst all jacking bolt and plate und er motor base (bolt and plate are shipped in installer’s packet). See Fig. 34. Using bolt and plate, raise mo t or to top of slide and rem ove belt. Secure motor in this position by tightening the nuts on the carriage bolts.
3. Loosen movable-pulley flange setscrew (see Fig. 33).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1.
See Table 7 for air quantity limits.
5. Set movable flange at nearest keyway of pulley hub and tighten setsc rew. (See Table 1 for speed change for each full turn of pulley flange.)
6. Replace and tighten belts. See Belt Tension Adjust­ment section on page 27.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting plate.
—26—
Page 27
Fig. 33 — Evaporator-Fan Pulley Alignment
and Adjustment
NOTE:
packet. They should be added to the motor support channel below the motor mounting plate to aid in raising the motor. The plate part number is 50DP503842. The adjustment bolt is
1
/2-in. bolt and threaded plate are included in the installer’s
A 3
3
/8-16 x 13/4 in.-LG.
Fig. 34 — Evaporator-Fan Motor Section
IV. EVAPORATOR FAN SERVICE AND REPLACEMENT
The 558F units use a fan motor mounting system that fea­tures a slide-out motor mounting plate. To replace or service the motor, slide out the bracket. See Fig. 34.
1. Remove the evaporator-fan access panel and the heating control access panel.
2. Remove the cen ter pos t (loc ated bet we en the ev apora­tor fan and heating control access panels) and all screws securing it.
3. Loosen nuts on the two carriage bolts in the motor mounting base.
4. Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts.
5. Remove the belt drive.
6. Remove jacking bolt and tapped jacking bolt plate.
7. Remove the 2 screws that secure the motor mounting plate to the motor support channel.
8. Remove the 3 screws from the end of the motor sup­port channel that interfere with the motor slide path.
9. Slide out the motor and motor mounting plate.
10. Disconnect wiring connections and remove the 4 mounting bolts.
11. Remove the motor.
12. To install the new motor, reverse Steps 1-11.
V. BELT TENSION ADJUSTMENT
To adjust belt tension:
1. Loosen fan motor bolts.
2. Adjust belt tension: Turn motor jacking bolt to move motor mounting
plate up or down for proper belt tension (
3
/8 in. deflec-
tion at midspan with one finger [9 lb force]).
3. Tighten nuts.
4. Adjust bolts and nut on mounting plate to secure motor in fixed position.
VI. CONDENSER-FAN ADJUSTMENT
A. 558F180,210,300 Units (Fig. 35)
1. Shut off unit power supply.
2. Remove access panel(s) closest to the fan to be adjusted.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge placed across the fan orifice.
5. Tighten setscrews and replace panel(s).
6. Turn on unit power.
B. 558F240 Units (Fig. 36)
1. Shut off unit power supply.
2. Remove fan top-grille assembly and loosen fan hub screws.
3. Adjust fan height on unit, using a straightedge placed across the fan orifice.
4. Tighten setscrews and replace rubber hu bcap to pre­vent hub from rusting to motor shaft.
5. Fill hub recess with permagum if rubber hubcap is missing.
—27—
Page 28
NOTE:
Dimensions are in inches.
Fig. 35 — Condenser-Fan Adjustment,
558F180,210,300
NOTE:
Dimensions are in inches.
Fig. 36 — Condenser-Fan Adjustment,
558F240
VII. ECONOMI$ER ADJUSTMENT
A. LED indication
The EconoMi$er controller features an onboard diagnostic LED (light-emitting diode) that flashes to indicate its status. See Table 16 for flash codes. The controller also has terminal connections (REM LED) for remotely mounting an LED, if desired. The flash code priorities are as follows:
1. On/Off or continuous flash
2. Critical fault
3. Non-critical fault
If any sensors are opened, shorted, or removed, the EconoMi$er determines whether the failure is critical or
non-critical and flashes the appropriate code. If a non-critical sensor fault occurs (i.e., outdoor air humidity), the EconoMi$er automatically reconfigures its control strategy to a more appropriate m ode. If a critical sensor fault occurs (i.e., supply air sensor), the EconoMi$er reverts to a safe mode of operation until the sensor problem is resolved.
B. Manual Configuration Pushbuttom
The EconoMi$er cont roller also featur es an onboard button (CONFIG) to help troub leshoot the sy stem. See Fig. 17. The button can perform 3 different functions.
Pressing the CONFIG button for more than three seconds, but less than ten seconds and then releasing will start the automatic test procedure. The damper will modulate fully open, wait, and modulate closed. This process takes three minutes to complete. Use this feature to determine if the actuator can be commanded.
If the CONFIG button is pressed and held for ten seconds and less than 30 seconds then released, the EconoMi$er controller reconfigures its mode of operation based on the sensors that are connected and functioning normally, and cancels the automatic test procedure.
If the EconoMi$er co ntrol ler reco gni zed a non- cr itica l se nso r fault, and flashed a code (i.e., FLASH 6, outdoor air humidity sensor fault) the FLASH CODE will be cleared, and normal operation begins. Ensure faulty sensor is removed before clearing faults.
If the EconoMi$er controller recognizes a critical sensor fault, and flashes a code (i.e., FLASH 4, discharge air ther­mistor fault) the FLASH code will not be cleared, and the EconoMi$er will remain in the safe operation mode. The sensor fault must be corrected to enable EconoMi$er to revert to normal operation.
If the CONFIG button is pressed and held for more than 30 seconds and released, the EconoMi$er controller will enable the enthalpy comparison strategy (with outdoor air enthalpy and return air enthalpy sensors installed).
VIII. POWER FAILURE
Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Do not manually operate damper actuator.
Table 16 — EconoMi$er Control Module Flash Code Identification
FLASH CODE CAUSE ACTION TAKEN BY ECONOMI$ER
Constant On Constant Off Continuous
Flash Flash One Flash Two Flash Three
Flash Four
Critical Fault
Flash Five
Flash Six
Flash Seven
Flash Eight
Flash Nine
Non-Critical Fault
Flash Ten
Normal operation Normal operation. No power No operation. CONFIG button pushed and held
between 3 and 9 seconds Control board fault System shutdown. Thermostat fault (i.e., Y2 without Y1) System shutdown until corrected. Actuator fault Revert to mechanical cooling only.
Discharge air thermistor fault
Outdoor air temperature sensor fault
Outdoor air humidity sensor fault Continue operation with dry bulb or dry bulb differential switchover.
Return air temperature sensor fault
Return air humidity sensor fault
Carbon Dioxide (CO
Onboard adjustment potentiometer fault Continue operation with default potentiometer settings.
) sensor fault Continue operation without ventilation control.
2
Outdoor air damper is stroked fully open, then closed (automatic test procedure takes 3 minutes to complete).
Continue operation with damper at minimum position. Revert to mechanical cooling only.
Continue operation with damper at minimum position. Disable mechanical cooling lockout.
Continue operation with single enthalpy EconoMi$er switchover or dry bulb EconoMi$er switchover (without humidity sensor).
Continue operation with single enthalpy, differential dry bulb, or dry bulb EconoMi$er switchover.
—28—
Page 29
IX. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during charging procedure.
NOTE: Do not use recycled refrigerant as it may contain contaminants.
A. No Charge
Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 1).
B. Low Charge Cooling
Using cooling charging chart (see Fig. 37), add or remove refrigerant until conditions of the chart are m et. Note that charging chart is different from those normally used. An accurate pressure gage and temperature-sensing device is required. Chargi ng is accomplished by ens uring the proper amount of liquid subcooling. Measure liquid line pressure at the liquid line service valve using pressure gage. Connect temperature sensing device to the liquid line near the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading.
C. To Use the Cooling Charging Chart
Use the above temperature and pressure readings, and find the intersection point on the cooling charging chart. If inter­section point on chart is a bove line, add refrige rant. If inter­section point on chart is below line, carefully recover some of the charge. Recheck suction pressure as charge is adjusted.
NOTE: Indoor-air CFM must be within normal operating range of unit. All outdoor fans must be operating.
The TXV (thermostatic expansion valve) is set to maintain between 15 and 20 degrees of superheat at the compressors. The valves are factory set and should not require re-adjustment.
D. Perfect Humidity™ System Charging
The system charge for units with the Perfect Humidity option is greater than tha t of the standard unit alone. The charge for units with this option is indicated on the unit nameplate drawing. To charge systems using the Perfect Humidity Dehumidification package, fully evacuate, recover, and re-charge the system to the nameplate sp ecified charge level. To check or adjust refrigerant charge on systems using
BOTH CIRCUITS
REDUCE CHARGE IF BELOW CURVE
150
200
250
300
350
400
140
120
100
80
60
LIQUID TEMPERATURE AT LIQUID VALVE (DEG F)
40
50
ALL OUTDOOR FANS MUST BE OPERATING
ADD CHARGE IF ABOVE CURVE
100
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
Fig. 37 Cooling Charging Chart
the Perfect Humidity Dehumidification package, charge per the standard subcooling charts. The subcooler MUST be deenergized to use the charging charts. The charts reference a liquid pressure (psig) and temperature at a point between the condenser coil and the s ubcooler coil. A tap is provided on the unit to measure liquid pressure entering the sub­cooler (leaving t he condenser).
X. FILTER DRIER
Replace whenever refrigerant system is exposed to atmosphere.
XI. PROTECTIVE DEVICES
A. Compressor Protection
Overcurrent Each compressor has internal line break motor protection. Crankcase Heater All units are equipped with a 70-watt crankcase hea ter to
prevent absorptio n of liquid refrigera nt by oil in the crank­case when the compressor is idle. The crankcase heater is energized whenev er there is a main power to the unit and the compressor is not energized.
IMPORTANT: After prolonged shutdown or servicing, ener­gize the crankcase heaters for 24 hours before starting the compressors.
Compressor Lockout If any of the safeties (high-pressure, low-pressure, freeze
protection thermostat, compressor internal thermostat) trip, or if there is loss of power to the compressors, the CLO (com­pressor lockout) will lock th e comp ressors o ff. To reset, man­ually move the thermostat setting.
B. Evaporator Fan Motor Protection
A manual reset, calibrated trip, magnetic circuit breaker protects against ov ercurrent. Do not bypass connections or increase the size of the breaker to correct troubl e. Determine the cause and correct it before r esetting the breaker.
C. Condenser-Fan Motor Protection
Each condenser-fan motor is internally protected against overtemperature.
D. High- and Low-Pressure Switches
If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automati­cally locked out by the CLO. To reset, manually move the thermostat setting.
E. Freeze Protection Thermostat (FPT)
An FPT is located on the top and bottom of the evaporator coil. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the com­pressor can be reenergized.
XII. RELIEF DEVICES
All units have relief devices to protec t against damage from excessive pressures (e.g., fire). These devices protect the high and low side.
XIII. CONTROL CIRCUIT, 24-V
This control circuit is protected against overcurrent by a
3.2-amp circuit breaker. Breaker can be reset. If it trips, deter­mine cause of trou ble before resetting . See Fig. 38 and 39 .
XIV. REPLACEMENT PARTS
A complete list of repl acement parts may be obtained from any Bryant distributor upon request.
—29—
Page 30
XV. ECONOMI$ER LEDs
The EconoMi$er control module has an LED for diagnostic purposes. The flash code identification is shown in Table 16.
XVI. OPTIONAL HINGED ACCESS DOORS
When the hinged access doors option is ordered, the unit will be provided with extern al and internal hinged ac cess doors to facilitate service.
Four external hinged access do ors are provide d on size 180­240 units. Two external hinged doors are provided on size 300 units. All external doors are provided with 2 large
1
/4 turn latches with folding bail-type handles. (Compressor
access doors have one latch.) A single door is provided for
LEGEND AND NOTES FOR FIG. 38 AND 39
AHA BRK W/AT C CB CC CLO COMP CR CT DAT DM DU EC EQUIP FL FLA FPT FU
Adjustable Heat Anticipator Breaks with Amp Turns Contactor, Compressor Circuit Breaker Cooling Compensator Compressor Lockout Compressor Motor Control Relay Current Transformer Discharge Air Thermistor Damper Motor Dummy Terminal Enthalpy Control Equipment Fuse Link Full Load Amps Freeze Protection Thermostat Fuse
GND HC HPS HTR IFC IFCB IFM IFR L LOR LPS LS NEC OAT OFC OFM OP PL PRI
Ground Heater Contactor High-Pressure Switch Heater Indoor-Fan Contactor Indoor-Fan Circuit Breaker Indoor-Fan Motor Indoor-Fan Relay Light Lockout Relay Low-Pressure Switch Limit Switch National Electrical Code Outdoor-Air Thermostat Outdoor-Fan Contactor Outdoor-Fan Motor Overcurrent Protection Plug Assembly Primary
filter and drive access. One door is provided for control box access. The control box access door is interlocked with the non-fused disconnect which must be in the OFF position to open the door. On size 180-240 units, two doors are provided for access to the compressor compartment.
Two internal access doors are provided inside the filter/drive access door. The filter access door (on the left) is secured by 2 small
1
/4 turn latches with folding bail-type handles. This door must be opened prior to opening the drive access door. The drive access door is shipped with 2 sheet metal screws holding the door closed. Upon initial opening of the door, these screws may be removed and discarded. The door is then held shut by the filter access door, which closes over it.
LEGEND
TB TC TH TRAN
Terminal Block Thermostat Cooling Thermostat Heating Transformer
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring Field Control Wiring Option/Accessory Wiring To indicate common potential
only; not to represent wiring.
NOTES:
1. Compressor and fan motor(s) thermally protected; 3-phase motors protected against primary single-phasing conditions.
2. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
3. TRAN1 is wired for 230 v operation. If unit is 208 v, disconnect the black wires from the ORN TRAN wire and reconnect to the RED TRAN wire, apply wirenuts to wires.
5. IFCB must trip amps is equal to or less than 140% FLA.
6. The CLO locks out the compressor to prevent short cycling on compressor over­load and safety devices. Before replacing CLO, check these devices.
7. Jumpers are omitted when unit is equipped with EconoMi$er.
8. Number(s) indicates the line location of used contacts. A bracket over (2) num­bers signifies a single-pole, double-throw contact. An underlined number sig­nifies a normally closed contact. Plain (no line) number signifies a normally open contact.
—30—
Page 31
ELECTRIC HEAT
208/240 v Amps 200/230 v kW A B C
71.3/82.3 25.7/34.2 117/135 42.2/56.1 156/180 56.2/74.8
Fig. 38 Typical Wiring Schematic (558F240, 208/230-3-60 Shown)
—31—
Page 32
Fig. 38 Typical Wiring Schematic (558F240, 208/230-3-60 Shown) (cont)
Fig. 39 Typical Component Arrangement (558F240 Shown)
—32—
Page 33
PROBLEM CAUSE REMEDY
Compressor and condenser fan will not start.
Compressor will not start but condenser fan runs.
Compressor cycles (other than normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
TXV
Thermostatic Expansion Valve
LEGEND
TROUBLESHOOTING
Refer to Tables 17-19 for troubleshooting details.
Table 17 Cooling Service Analysis
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or control
relay. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Faulty wiring or loose connections in compressor circuit. Check wiring and repair or replace. Compressor motor burned out, seized, or internal
overload open. Defective overload. Determine cause and replace. Compressor locked out Determine cause for safety trip and reset lockout. One leg of 3-phase power dead. Replace fuse or reset circuit breaker.
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective overload. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty condenser-fan motor. Replace. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser coil dirty or restricted. Clean coil or remove restriction. Dirty air filter. Replace filter. Dirty condenser coil. Clean coil. Refrigerant overcharged. Recover excess refrigerant. Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
Air in system. Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air shor t-cycling. Determine cause and correct. Low refrigerant charge. Check for leaks, repair, and recharge. Restriction in liquid tube. Remove restriction. High heat load. Check for source and eliminate. Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
Refrigerant overcharged. Recover excess refrigerant. Dirty air filter. Replace filter. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted. Remove source of restriction. Faulty TXV. 1. Check TXV bulb mounting and secure tightly to
Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
Temperature too low in conditioned area. Reset thermostat. Field-installed filter drier restricted. Replace.
Replace component.
Determine cause. Replace compressor.
Determine cause.
to nameplate.
suction line.
2. Replace TXV if stuck open or closed.
suction line.
2. Replace TXV if stuck open or closed.
suction line.
2. Replace TXV if stuck open or closed.
necessary.
—33—
Page 34
Table 18 EconoMi$er Troubleshooting
PROBLEM POTENTIAL CAUSE REMEDY
Damper Does Not Open
EconoMi$er Operation Limited to Minimum Position
Damper Position Less than Minimum Position Set Point
Damper Does Not Return to Minimum Position
Damper Does Not Close on Power Loss
LEGEND
IFM PL
Indoor-Fan Motor Plug
Indoor (Evaporator) Fan is Off
No Power to EconoMi$er Controller
No Power to G Terminal If IFM is on, check to ensure 24 vac is present on G Terminal of the
Controller Fault If STATUS light is flashing one flash, the EconoMi$er controller is
Thermostat Fault If STATUS light is flashing two flashes, the EconoMi$er controller senses that
Actuator Fault Check the wiring between the EconoMi$er controller and the actuator.
Minimum Position Set Incorrectly
EconoMi$er Changeover Set Point Set Too High or Too Low
Discharge Air Thermistor Faulty
Outdoor Air Temperature Sensor Faulty
Supply Air Low Limit Strategy Controlling
Ventilation Strategy
CO
2
Controlling
Damper Travel is Restricted
Check to ensure that 24 vac is present at Terminal C1 (Common Power) on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board. Check to ensure that 24 vac is present across Terminals 24 VAC and
24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring (see unit label diagram). If 24 vac is present, STATUS light should be on constantly.
EconoMi$er controller. If 24 vac is not present, check wiring (see unit label diagram).
experiencing a fault condition. Cycle power to the controller. If condition continues, replace the EconoMi$er controller.
the thermostat is wired incorrectly. Check wiring between the thermostat and the connection board in the electrical panel. The fault condition is caused by Y2 being energized before Y1.
Hold CONFIG button between 3 and 10 seconds to verify the actuators operation. (This process takes 3 minutes to complete.)
Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 5.
If STATUS light is flashing 4 flashes, Discharge Air Thermistor is faulty. Check wiring or replace sensor.
If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is faulty. Check wiring or replace sensor.
The supply-air temperature is less than 45 F, causing the minimum position to be decreased. Refer to the Start-Up instructions. Verify correct setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
If a CO2 sensor is being used, and the damper position is greater than minimum position, the ventilation control strategy is controlling. Refer to the Start-Up instructions. EconoMi$er is operating correctly.
Check to ensure the damper is not blocked.
Table 19 Perfect Humidity Dehumidification Subcooler Service Analysis
PROBLEM CAUSE REMEDY
Subcooler will not energize
Subcooler will not deenergize Low system capacity
No power to subcooler control transformer. Check power source. Ensure all wire connections
No power from subcooler control transformer to liquid line three way valve.
Liquid line three-way valve will not operate. 1. Solenoid coil defective; replace.
Liquid Line three-way valve will not close. Valve is stuck open; replace. Low refrigerant charge or frosted coil. 1. Check charge amount. See system charging
—34—
are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Subcooler control low pressure switch open. Cycle unit off and allow low-pressure switch to reset. Replace switch if it will not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck closed; replace.
section.
2. Evaporator coil frosted; check and replace subcooler control low pressure switch if necessary.
Page 35
Access panels
5-7
Air quantity limits 20 Changeover set poi nts 16 Charging chart, refrigerant Clearance 5-7 CO2 sensor Settings
15
Compressor Lockout 29 Lubrication 26 Mounting 20 Rotation 20 Concentric duct 9 Condensate drain Cleaning 26 Location 9, 10 Condenser coil Cleaning 26 Condenser fan Adjustment 27, 28 Control circuit 29 Wiring 10 Convenience outlet 13 Crankcase heater Dimensions
20, 29
2, 3, 5-7
Ductwork 9 EconoMi$er
13-17, 20, 28, 34
Adjustment 20, 28 Commissioning 15 Components 13 , 14 Control module 14 Discharge air thermistor 15 Dry bulb changeover 16 Enthalpy sensor 14, 16 Flash code 28 Temperature sensor 14, 16 Wiring 16, 17 Electrical connections 10 Electrical data 11, 12 Evaporator coil Cleaning 26 Evaporator fan motor Efficiency 24 Lubrication 26 Motor data 24 Performance 21-23 Pulley adjustment
26, 27
Pulley setting 8, 24 Replacement 27 Speed 8 Factory-installed options Convenience outlet 13 EconoMi$er 13-17 Hinged access doors 30 Perfect Humidity 18-20 Non-fused disconnec t 13 Filter Cleaning 26 Installation 14, 15
8
Size Filter drier
29
Freeze protection thermostat Heat anticipator settings High pressure switch
14
8, 29
Horizontal adapter roof curb Humidistat Low pressure switch
18-20
8, 29
Manual outdoor air damper Motormaster I control Motormaster III control
17-19
18, 19
29
13
8, 29
4
INDEX
Mounting Compressor 20 Unit 1 Operating sequence Cooling 24 EconoMi$er 24, 25 Heating
24, 25
Perfect Humidity 25, 26 Outdoor air hood 14, 15 Outdoor air inlet screens Cleaning 26 Dimensions 8 Outdoor air sensor 15 Perfect Humidity dehumidification device 18-20, 25, 26, 29, 34 Physical data 8 Power supply Wiring 10 Pressure drop EconoMi$er 23 Electric heat 23 Glycol coil 23 Pressure switches High pressure Low pressure
8, 29
8, 29
Refrigerant Charge
8, 29
Type 8 Refrigerant service ports 20 Replacement parts 29 Return air filter 8 Rigging unit 1, 4 Roof curb Assembly 1 Dimensions 2, 3 Leveling tolerances 1-3 Safety considerations 1 Service 26-32 Service ports 20 Start-up 20-26 Start-up checklist CL -1 Thermostat 10 Troubleshooting 33, 34 Ventilation 16 Weight Corner 5-7 EconoMi$er
5-7
Maximum 4 Unit 5-7 Wind baffle 17, 18 Wiring EconoMi$er 16, 17 Perfect Humidity 19, 21 Power connections 10 Thermostat 10 Unit 31, 32
—35—
Page 36
Page 37
Page 38
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowled ge of t he equip­ment discussed in this manual, including:
• Unit F amiliarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based for­mats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our la bs can mean increased confidence that really pays dividends in faster troubleshooting and fewer call­backs. Course descriptions and schedules are in our catalog.
CALL FOR FREE CAT A LOG 1 -800 -96 2-92 12
[ ] Pac kaged Service Training [ ] Classroom Service Training
Copyright 2002 Bryant Heating & Cooling Systems CATALOG NO. 5355-811
Page 39
Page 40
START-UP CHECKLIST
MODEL NO.:
SERIAL NO.:
DATE: _ TECHNICIAN:
I. PRE-START-UP:
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY INSTALLATION OF INDOOR FAN MOTOR ADJUSTMENT BOLT AND PLATE
VERIFY INSTALLATION OF OUTDOOR AIR HOOD
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
CHECK THAT FILTERS AND SCREENS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW IS TIGHT
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
VERIFY THAT SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
VERIFY THAT CRANKCASE HEATER HAS BEEN ENERGIZED FOR 24 HOURS
II. START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 COMPRESSOR AMPS — COMPRESSOR NO. 1 L1 L2 L3 — COMPRESSOR NO. 2 L1 L2 L3
SUPPLY F AN AMPS EXHAUST FAN AMPS
CUT ALONG DOTTED LINE
ELECTRIC HEAT AMPS (IF SO EQUIPPED) L1 L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE F DB (Dry-Bulb) RETURN-AIR TEMPERATURE COOLING SUPPLY AIR ELECTRIC HEAT SUPPLY AIR (IF SO EQUIPPED)
F DB F WB (Wet-Bulb) F
F
PRESSURES
REFRIGERANT SUCTION CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 PSIG REFRIGERANT DISCHARGE CIRCUIT NO. 1
VERIFY REFRIGERANT CHARGE USING CHARGING CHART ON PAGE 29.
PSIG CIRCUIT NO. 2 PSIG
GENERAL
ECONOMI$ER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS (IF SO EQUIPPED)
VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES
CUT ALONG DOTTED LINE
Copyright 2002 Bryant Heating & Cooling Systems
CL-1
CATALOG NO. 5355-811
Loading...