Bryant DURAPAC PLUS SERIES 542J Installation, Start-up And Service Instructions Manual

Page 1
installation, start-up and service instructions
SINGLE PACKA GE ROOFT OP HEAT PUM P UNITS
Cancels: II 542J-150-3 II 542J-150-4
Dura
542J
Plus Series
Sizes 150,180
12 and 15 Tons
3/15/06
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 1
III. Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . 1
IV. Step 4 — Make Unit Duct Connections . . . . . . . . . . 3
V. Step 5 — Trap Condensate Drain. . . . . . . . . . . . . . . 3
VI. Step 6 — Make Electrical Connections . . . . . . . . . . 7
VII. Step 7 — Make Outdoor-Air Inlet Adjustments. . . 10
VIII. Step 8 — Install Outdoor-Air Hood. . . . . . . . . . . . . 10
IX. Step 9 — Install All Accessories . . . . . . . . . . . . . . 10
X. Step 10 — Adjust Factory-Installed Options. . . . . 11
XI. Step 11 — Defrost Cycle . . . . . . . . . . . . . . . . . . . . . 18
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-22
SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-29
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .30-35
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained se rvice per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety pre c au ti ons th at ma y a ppl y.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
INSTALLATION
IMPORTANT: Units have high ambient operating limits. If
limits are exceeded , the un it will au tomatica lly lock the com­pressor out of operation. Manual reset will be required to restart the compressor.
I. STEP 1 — PROVIDE UNIT SUPPORT A. Roof Curb
Assemble and install a ccessory roof curb in accordanc e with instructions shipped with the curb. Accessory roof curb and information required to field fabricate a roof curb are shown
in Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Du ctwork can be secured to roof curb before unit is set in pl ace. Horizontal adapter installa­tion is shown in Fig. 2.
IMPORTANT: Th e gasketing of the unit to the roof curb is crit­ical for watert ight seal. Install ga sket suppli ed with the ro of curb as shown in Fig. 1. Improp erly applied gasket can result in air leaks and poor unit performance.
Curb should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerances is ± ear ft in any dire ction . Refe r to Accessory Roof Curb Installa­tion Instructions for addition al information as required.
B. Alternate Unit Support
When the curb cannot be used, support unit with sleepers using unit curb support area. If sleepers cannot be used, sup­port long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright, and do not drop. Use spreader bars over unit to prevent sl ing or cabl e damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ± linear ft in any direction. See Fig. 1 for additional leveling tol­erance information. Unit weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging inst ructions on unit.
A. Positioning
Provide clearance around and above unit for airflow, safety, and service access (Fig. 4 and 5).
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air .
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
III. STEP 3 — FIELD FABRICATE DUCTWORK
Secure all ducts to buildi ng structure. Use flexible duct con­nectors between unit and ducts as required. Insulate and weatherproof all external ductwo rk, join ts, and roof openings with counter flashing and mastic in accordanc e with applica­ble codes.
Ducts passing through an unconditioned space must be insu­lated and covered with a vapor barrier.
The 542J units with electric heat requi r e a 1-in. clearance for the first 24 in. of ductwork.
1
/16 in. per lin-
1
/
in. per
16
Page 2
lb density.
2
/
1
AB
Deg. in. Deg. in.
DIMENSIONS (degrees and inches)*
ALL .28 .45 .28 .43
UNIT
below the unit discharge for units equipped with electric heaters.
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1thick neoprene coated 1
3. Dimensions in ( ) are in millimeters.
NOTES:
4. Direction of airflow.
the indoor section, unit can only be pitched as shown.
5. Roof curb: 16 ga. (VA03-56) stl.
6. A 90 degree elbow must be installed on the supply ductwork
7. To prevent the hazard of stagnant water build-up in the drain pan of
DESCRIPTION
CURB
HEIGHT
Fig. 1 — Roof Curb Details
Standard Curbfor Units
Requiring High Installation
Side Supply and Return
Curb for High Installation
PKG. NO. REF.
CRRFCURB010A00 1-2 (305) Standard Curb 14 High
CRRFCURB011A00 2-0 (610)
CRRFCURB012A00 2-0 (610)
2
Page 3
3 1/2"
2" X 1/4 SUPPORT TYP. STITCH WELDED
FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible.
For horizontal return applications: The power exhaust and barometric
relief dampers must be installed in the return air duct.
Fig. 2 — Horizontal Supply/Return Adapter Installation
MAXIMUM
UNIT 542J
150 1895 860 3-1 948 180 2205 1000 3-6 1059
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Table 1 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars.
5. Weights do not include optional EconoMi$erIV. See Table 1 for EconoMi$erIV weight.
6. Weights given are for aluminum indoor coil plate fins and copper outdoor coil plate fins. Weights of other metal combinations are listed in Table 1.
SHIPPING WEIGHT
lb kg ft-in. mm
DIMENSION A
CAUTION: All panels must be in place when rigging.
Fig. 3 — Rigging Details
14 3/4"
6"
ACCESSORY
PACKAGE NO.
CRRFCURB013A00
12" WIDE STANDING SEAM PANELS
CURB
HEIGHT
1-11
(584)
DESCRIPTION
Pre-Assembled, Horizontal
Adapter Roof Curb
23"
Outlet grilles must not lie directly below unit discharge. NOTE: A 90-degree elbo w must be provid ed in the du ctwork
to comply with UL (Underwriters Laboratori es ) co d e s f or use with electric heat.
WARNING: For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Insta ll a 90-de gree t urn in th e return ductwor k between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Due to electric heater, supply duct will require 90-degree elbow.
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS
Unit is shipped for thru-the-bottom duct connections. Duct­work openings are shown in Fig. 6. Field-fabricated concen­tric ductwork may be connected as shown in Fig. 7 and 8.
Attach all ductwork to roof curb and roof curb basepans. Refer to installation instructions shipped with accessory roof curb for more information.
V. STEP 5 — TRAP CONDENSATE DRAIN
See Fig. 4 or 5 and 9 for drain location. Plug is provided in drain hole and must be removed when unit is operating. One
3
/4-in. half coupling is provided inside unit indoor air section for condensate drain connection. An 81/2 in. x 3/4-in. diameter nipple and a 2-in. x
3
/4-in. diameter pipe nipple are coupled to standard 3/4-in. diameter elbows to provide a straight path down through holes in unit base rails (see Fig. 10). A trap at least 4-in. deep must be used.
3
Page 4
Table 1 — Physical Data
UNIT SIZE 542J 150 180 NOMINAL CAPACITY (tons) 12
1
/
2
15
OPERATING WT (lb)
Al/Al* 1615 1925 Al/Al Coated* 1615 1925 Unit Al/Cu* 1745 2075
Cu/Cu* 1815 2165 Electric Heat 65 65 EconoMi$erIV 90 90 Roof Curb† 200 200
COMPRESSOR Semi-Hermetic
Type (Number) 06D-328 (1) 06D-818 (2) Cylinders 64 Oil Change (oz.) (each circuit) 115 88
REFRIGERANT TYPE R-22
Charge (lb)
System 1 26.0 16.5 System 2 16.5
3
OUTDOOR COIL
Rows 33
/8 in., Internally Grooved Copper T ubes, Aluminum or Copper Lanced Fins
Fins/in. 15 15 Total Face Area (sq ft) 21.7 21.7
OUTDOOR FAN Propeller Type, Direct Drive
Nominal Cfm 9,000 9,000 Number...Diameter (in.) 3...22 3...22 Motor Hp (1075 rpm) Watts Input (Total) 1090 1090
INDOOR CO IL
Expansio n D ev i c e Fixed Orifice
3
/8 in., Internally Grooved Copper Tubes, Aluminum or Copper Lanced Fins, Face Split
1
/
2
1
/
2
Rows 33 Fins/in. 15 15 Total Face Area (sq ft) 17.5 17.5
INDOOR FAN Centrifugal, Adjustable Pitch Belt Drive
Quantity...Size (in.) Nominal Cfm 5000 6000
2...10 x 10 2...12 x 12
Maximum Continuous Bhp 4.25 5.90 Fan Rpm Range 862-1132 799-1010 Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Diameter (in.) 3.1/4.1 3.7/4.7 Fan Pulley Pitch Diameter (in.) Belt, Quantity...Type...Length (in.) 1...BX...42 1...BX...46 Pulley Center Line Distance (in.) 13.5-15.5 13.3-14.8 Speed Change Per Turn (rpm)
6.0 11.4
54 42
Pulley Maximum Full Turns 6** 6** Factory Pulley Turns Setting 33 Factory Speed Setting (rpm) 1024 926 Fan Shaft Diameter (in.) Motor Hp (Service Factor) 3.7 (1.15) 5.0 (1.15) Motor Frame Size 56H 184T Motor Efficiency 0.84 0.84
3
/
1
16
17/
16
HIGH-PRESSURE SWITCH
Cutout (psig) 426 Reset (psig) 320
LOW-PRESSURE/LOSS-OF-CHARGE SWITCH
Cutout (psig) 7 Reset (psig) 22
AIR INLET SCREENS Cleanable
Economi zer, Quantity...Size (in.)
RETURN-AIR FILTERS (TYPE) 10% Efficient — 2-in. Throwaway Fiberglass
Quantity...Size (in.)
DEFROST THERMOSTAT
Defrost Time 30 min (Adjustable to 50 or 90 min)
2...20 x 25 x 1
1...20 x 20 x 1
4...20 x 20 x 2
4...16 x 20 x 2
Closes (F) 28 Opens (F) 65
LEGEND
Al — Aluminum Cu — Copper
*Indoor coil fin material/outdoor coil fin material.
†Weight of 14 in. roof curb.
**Pulley cannot be run at 0 or
1
/2 turns open.
4
Page 5
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
•Rear: 7′-0″ (2 134) for coil removal. This dimension can be reduced to 4′-0″ (1219) if conditions per mit coil removal from the top.
• Left side: 4′-0″ (1219) for proper outdoor coil airflow.
• Front: 4′-0″ (1219) for control box access.
• Right side: 4′-0″ (1219) for proper operation of damper and power exhaust (if so equipped).
• Top: 6′-0″ (1829) to assure proper outdoor fan operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the outdoor coil and the damper/power exhaust as stated in note no. 6, a removable fence or barricade requires no clearance.
8. Dimensions are from outside of cor ner post. Allow
5
/
(8) on each side for top cover drip edge.
0-
16
9. A 90 degree elbow must be installed on the supply ductwork below the unit discharge for units equipped with electric heat.
STANDARD UNIT
WEIGHT
ECONOMI$ERIV
WEIGHT
1615 lb (733 kg) 90 lb (41 kg)
Fig. 4 — Base Unit Dimensions — 542J150
5
Page 6
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direc tion of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
• Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to 4′-0″ (1219) if conditions per mit coil removal from the top.
• Left side: 4′-0″ (1219) for proper outdoor coil airflow.
•Front: 4′-0″ (1219) for control box access.
• Right side: 4′-0″ (1219) for proper operation of damper and power exhaust (if so equipped).
• Top: 6′-0″ (1829) to assure proper outdoor fan operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the outdoor coil and the damper/power exhaust as stated in note no. 6, a removable fence or barricade requires no clearance.
8. Dimensions are from outside of corner post. Allow
5
/
(8) on each side for top cover drip edge.
0-
16
9. A 90 degree elbow must be installed on the supply ductwork below the unit discharge for units equipped with electric heat.
STANDARD UNIT
WEIGHT
ECONOMI$ERIV
WEIGHT
1925 lb (874 kg) 90 lb (41 kg)
Fig. 5 — Base Unit Dimensions — 542J180
6
Page 7
NOTE: Do not drill in this area, as damage to basepan may result in water leak.
Fig. 6 — Air Distribution — Thru-the-Bottom
(542J180 Shown)
VI. STEP 6 — MAKE ELECTRIC CONNECTIONS A. Field Power S upply
Unit is factory wired for voltage shown on nameplate. When installing units, provide a disconnect of adequate size
per NEC (National Electrical Code) requirements (Table 2). All field wiring must comply with NEC and local
requirements. Route power lines through control box access panel or unit
basepan (Fig. 4 and 5) to connections as shown on unit wir­ing diagram and Fig. 11.
Transformers no. 1 and 2 are wired for 230-v unit. If 208/ 203-v unit is to be run with 208-v power supply, the trans­formers must be rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2% and the current must be balanced w ith in 10%.
Use the following formula to determine the percentage of voltage imbalance.
Perce nt ag e of Voltage Imbalance
NOTE: Do not drill in this area, as damage to basepan may result in water leak.
Fig. 7 — Concentric Duct Air Distribution
(542J180 Shown)
Shaded area indicates block-off panels.
NOTE: Dimensions A, A′ and B, B are obtained from field-supplied ceiling diffuser.
Fig. 8 — Concentric Duct Details
= 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
455 + 464 + 455
1371
=
3
3
= 457
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine the percent voltage imbal ance:
Percentage of Voltage Imbalance= 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
Unit failure as a res ult of ope ra tio n o n imp ro per line volt age or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
7
Page 8
INDOOR FAN MOTOR ACCESS
FILTER ACCESS
3/4" FPT DRAIN CONNECTION
1-3/8" DRAIN HOLE
Fig. 9 — Condensate Drain Details
Fig. 10 — Condensate Drain Piping Details
LEGEND
EQUIP GND — Equipment Ground kcmil Thousand Circular Mils NEC National Electrical TB Terminal Block
NOTE: The maximum wire size for TB1 is 350 kcmil f or all unit v olt ages.
Fig. 11 — Field Power Wiring Connections
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to th e installation instru ctions included with the accessory. Refer to unit Price Pages or contact your local Bryant representative for more information. Locate
thermostat assembly on a solid wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire from subbase te r­minals through conduit in unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 12.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insu­lated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wi re larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Set heat anticipator settings as indicated in T able 3. Settings may be changed sligh tly to pr ovide a great er degree of com­fort for a particular installation.
C. Optional Non-Fused Disconnect
On units with the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 13 for wiring for 100 and 200 amp disconnect switches. Units with an MOCP (maximum overcurrent protection) under 100 will use the 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Open the control box door and r e mo ve t he handle and shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect switch. The bolt is locat ed on the sq uare hole a nd is used to hold the shaft in place. The shaft cannot be inserted until the Allen bolt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is spe­cially cut and the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control bo x door.
6. Attach the handle to the external access door with the two screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in the OFF position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door. The handle should fit over th e end of the shaf t when the door is closed.
8. The handle must be in the OFF position to open the control box door.
D. Optional Convenience Outlet
On units with optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outl et rece ptacle is pr o­vided for field wiring. Field wiring should be run thro ugh th e
7
/8-in. knockout provided in the basepan near the return air
opening.
8
Page 9
Table 2 — Electrical Data
UNIT
542J
150
180
VOLTAGE
(3 Ph,
60 Hz)
208/230 187 253 39.7 228 3 1.7 3.7 10.5/10.5
208/230 187 253 28.2 160 28.2 160 3 1.7 5 15.8/15.8
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty
460 414 508 19.9 114 3 0.8 3.7 4.8
460 414 508 14.1 80 14.1 80 3 0.8 5 7.9
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — M aximum Overcurrent Protection NEC National Electrical Code RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, and
480 v. If po wer distribution voltage to unit varies from rated heater volt­age, heater kW will vary accordingly.
†Fuse or HACR circuit breaker. This is the maximum size permissible;
smaller fuse size may be used where conditions permit.
COMPRESSOR OUTDOOR
No. 1 No. 2
FAN
MOTOR
FLA
(ea)
INDOOR FAN
MOTOR
Hp FLA FLA LRA FLA kW MCA MOCP† RLA LRA
POWER
EXHAUST
——
4.6 18.8
——
2.3 6.0
——
4.6 18.8
——
2.3 6.0
ELECTRIC HEAT* POWER SUPPLY
—/— —/— 65/ 65 100/100 64/ 64 39/ 45 14/19 114/122 125/150 64/ 64 72/ 82 26/34 155/168 175/175 94/107
117/135 42/56 211/200 225/225 147/167
—/— —/— 70/ 70 100/100 69/ 69 39/ 45 14/19 119/126 125/150 69/ 69 72/ 82 26/34 159/173 175/175 100/112
117/135 42/56 216/205 225/225 152/173
32 50 31 18 15 54 60 31 39 32 81 90 50 66 55 98 110 82
34 50 34 18 15 57 70 34 39 32 83 90 53 66 55 100 110 84
—/— —/— 84/ 84 110/110 89/ 89
117/135 42/56 231/219 250/225 153/173
—/— —/— 89/ 89 110/110 94/ 94
117/135 42/56 235/224 250/225 158/179
42 50 44 66 55 108 110 85
44 50 47 66 55 110 125 88
DISCONNECT
SIZING
387/387
406/406
189
195
499/48572/ 82 26/34 174/187 175/200 101/112
518/50472/ 82 26/34 179/191 200/200 106/118
23839 32 91 100 54
24439 32 93 100 57
NOTES:
1. In compliance with NEC requirements for multimotor and combina­tion load equipment (refer to NEC Articles 430 and 440), the over­current protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
2. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA).
Fig. 12 — Field Control Thermostat Wiring
Table 3 — Heat Anticipator Settings
UNIT 542J
UNIT
VOLTAGE
208/230-3-60
150
460
208/230
180
460
HEATER
kW
14/19 .40 — 26/34 .40 .40 42/56 .66 .40
15 .40 — 32 .40 .40 55 .40 .66
26/34 .40 .66 42/56 .66 .40
32 .40 .40 55 .40 .66
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
STAGE 1 STAGE 2
NOTE: The disconnect takes the place of TB-1 as shown on the unit
wiring diagram label and the component arrangement label.
Fig. 13 — Optional Non-Fused Disconnect Wiring
9
Page 10
VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS A. Manual Outdoor-Air Damper
All units (except those equipped with a factory-installed EconoMi$erIV ) h ave a ma nual out door-air damper to provide ventilation air . Damper can be preset to admit up to 25% out­door air into return-air compartment. To adjust, loosen securing screws and move damper to desired setting. Then retighten screws to secure damper (Fig. 14).
VIII. STEP 8 — INSTALL OUTDOOR-AIR HOOD IMPORTANT: If the unit is equipped with the optional
EconoMi$erIV component, move the outdoor-air tempera­ture sensor prior to installing the outdoor-air hood. See the Optional EconoMi$erIV section for more information.
The same type of factory-installed hood is used on units with 25% air ventilation and units with an EconoMi$erIV.
NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, and filter support bracket are secured oppo­site the outdoor coil end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and all other hardware ar e in a package located inside t he return-air filter access panel (Fig. 15).
1. Attach seal strip to upper filter retainer. See Fig. 16.
2. Assemble hood top panel and side panels, upper filter retainer, and hood drain pan (Fig. 17).
3. Secure lower filter retainer and long section of filter support bracket to unit. See Fig. 17.
4. Loosen sheet metal screws for base unit top panel located above o utdoor-air inlet opening, and remove
screws for hood side panels located on the sides of the outdoor-air inlet opening.
5. Match notches in hood top panel to unit top panel screws. Insert hood flange between unit top panel flange and unit. Tighten screws.
6. Hold hood side panel flanges flat against unit, and install screws removed in Step 4.
7. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket.
8. Attach remaining short section of filter support bracket.
IX. STEP 9 — INSTALL ALL ACCESSORIES
After all the factory-installed options have been adjusted, install all field-instal led accessories. Refer to the accessory installation instructions included with each accessory.
Fig. 14 — 25% Outdoor-Air Section Details
HOOD TOP PANEL
Fig. 16 — Seal Strip Location
(Air Hood Cross-Sectional View)
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
FILTER SUPPORT BRACKET
HOOD SIDE PANELS (2)
LOWER FILTER RETAINER
Fig. 15 — Outdoor-Air Hood Component Location
HOOD DRAIN PAN
UPPER FILTER RETAINER
NOTE: The outdoor-air hood comes with a baffle which is not used on these units. Discard the baffle.
Fig. 17 — Outdoor-Air Hood Details
10
Page 11
A. Motormaster® I Control Installation
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures. See Fig. 18 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to at tach baffles t o unit. Screws shou ld
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster I Controls Only one Motormaster I control is required per unit. The
Motormaster I control must be used in c onjunction with the accessory 0° F low ambien t kit (purchased separately). The Motormaster I device controls outdoor fan no. 1 while ou t­door fans no. 2 and 3 are sequenced off by the accessory 0° F low ambient kit.
Accessory 0° F Low Ambient K it — Install the accessory 0° F low ambient kit per instruction supplied with accessory.
Sensor Assembl y — Install the sensor assembly in the loca­tion shown in Fig. 19.
Motor Mount — To ensure proper fan height, replace the existing motor mount with the new motor m ount provided with accessory .
Transfor mer (460-V Units On ly) — On 460-volt units a trans­former is required. The transformer is provided with the accessory and must be field-installed.
Motormaster I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti­cally, with leads protruding from bottom of extrusion.
MOTORMASTER SENSOR LOCATION
NOTES:
1. All sensors are located on the eighth hairpin up from the bottom.
2. Field-installed tubing insulation is required to be installed over the TXV bulb and capillary tube for proper operation at low ambients. Tubing insulation is only required on the por­tion of suction line located between indoor and outdoor section.
HAIRPIN END
Fig. 19 — Motormaster I Sensor Locations
X. STEP 10 — ADJUST FACTORY-INSTALLED OPTIONS A. Optional EconoMi$erIV
See Fig. 20 and 21 for EconoMi$erIV component locati ons. NOTE: These instructions are for installing the optional
EconoMi$erIV only. Refer to the accessory EconoMi$erIV or EconoMi$er2 installation instructions when field in stalling an EconoMi$erIV or EconoMi$er2 accessory.
To complete installation of t he optional EconoMi$erIV, per­form the following procedure.
1. Remove the EconoMi$er IV hood. Refer to Step 8 — Install Outdoor-Air Hood on page 10 for info rmation on removing and in stalling the outdoor-air hood.
2. Relocate outdoor air temperature sensor from ship­ping position to operation pos ition on EconoMi $erIV. See Fig. 20.
IMPORTANT: Failure to relocate the sensor w ill res ult in the EconoMi$erIV not operating properly.
3. Re-install economizer hood.
4. Install all EconoMi$erIV accessories. EconoMi$erIV wiring is shown in Fig. 22.
Outdoor air leakage is shown in Table 4. Return air pressure drop is shown in Tabl e 5.
Table 4 — Out door Air Damper Leakage
NOTE: Dimensions in ( ) are in mm.
Fig. 18 — Wind Baffle Details
DAMPER STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
LEAKAGE (cfm) 35 53 65 75 90 102
Table 5 — Return Air Pressure Drop (in. wg)
CFM
4500 5000 5400 6000 7200 7500
0.040 0.050 0.060 0.070 0.090 0.100
11
Page 12
SCREWS
ECONOMI$ERIV
FRAME
TOP
SCREWS
OUTDOOR AIR TEMPERATURE SENSOR (INSTALLED OPERATION POSITION)
LOW TEMPERATURE COMPRESSOR LOCKOUT SWITCH
ECONOMI$ERIV
SUPPLY AIR TEMPERATURE SENSOR LOCATION
Fig. 20 — EconoMi$erIV Component Locations —
End View
ACTUATOR
CONTROLLER FLANGE
AND SCREWS (HIDDEN)
1 R T
R T
c a V 4
2
M O C
4 2
_
c a V
T
O
H
H X E
+
t e
S
V 0
2
1
V 2
1
1
N
5
N
n
H
i
X
M
E
s o
P
4
n
P1
e p
P
O
3
V C
1
D
x a
EF
T1
M
T
V 0
1
EF
V 2
V C
D
V
t
C
e
D
S
V
1
0
Q
1
A
Q A
V 2
+
e
O
e r
S
C
F
l o
O
o
S
C
B
D
+ R S
A
R
S
Fig. 21 — EconoMi$erIV Component Locations —
Side View
DCV — Demand Controlled Ventilation
LEGEND
IAQ — Indoor Air Quality LALS— Low Temperature Compressor
Lockout Switch
OAT — Outdoor-Air Temperature POT — Potentiometer
Potentiometer Default Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
NOTES:
1. 620 ohm, 1 watt 5% resistor should be rem oved only when using differential enthalpy or dry bulb.
2. If a separate field -supplied 24 v transform er is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position.
Fig. 22 — EconoMi$erIV Wiring
12
Page 13
B. EconoMi$erIV Standard Sensors
Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoo r-air temperature. The outdoor-air temperature is used to determine when the EconoMi$erIV can be used for free cooling. The sen sor must be field-relocat ed. See Fig. 20. The operat ing range of tem­perature measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 21. This sensor is factory installed. The operating range of temperature measurement is 0° to 158 F. See Table 6 for sensor tempera­ture/resistance values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Low Temperature Compressor Lockout Switch The EconoMi$erIV is equipped with an ambient tempera-
ture lockout switch located in the outdoor air stream which is used to lockout the compressors below a 42 F ambient tem­perature. See Fig. 20.
Table 6 — Supply Air Sensor Temperature/
Resistance Values
TEMPERATURE (F) RESIST ANCE (ohms)
–58 200,250 –40 100,680 –22 53,010
–4 29,091 14 16,590 32 9,795 50 5,970 68 3,747 77 3,000
86 2,416 104 1,597 122 1,080 140 746 158 525 176 376 185 321 194 274 212 203 230 153 248 116 257 102 266 89 284 70 302 55
C. EconoMi$erIV Control Modes
Determine the EconoMi$erIV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 7. The EconoMi$erIV is supplied from the factory with a supply air temp erat ure sen sor, a low temperature com­pressor lockout switch, and an outdoor air temperature sensor. This allows for operation of the EconoMi$erIV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$erIV and unit.
Outdoor Dry Bulb Changeover The standard controller is shippe d from the factory config-
ured for outdoor dry bulb changeover control. The outdoor air and su pply air temperature sensors are included as stan­dard. For this control mode, the outdoor temperature is com­pared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$erIV will adjust the outdoor-air dampers to mini­mum position. If the outdoor-air temperature is below the set point, the position of the outdoor-air dampers will be con­trolled to provid e fr ee co o lin g us ing out do or ai r. When in this mode, the LED next to the free cooling set point potentiome­ter will be on. The changeover temp erature set poi nt is con­trolled by the free cooling set poi nt potentiomete r located on the control. See Fig. 23. The scal e on the p otentio meter i s A, B, C, and D. See Fig. 24 for the corresponding temp erature changeover values.
Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional acces­sory return air sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. See Fig. 25.
In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower tem­perature airstream is used for cooling. When using this mode of changeover control, turn the free cooling/enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 23.
APPLICATION
Outdoor Air Dry Bulb None. The outdoor air dry bulb sensor is factory installed. CRTEMPSN002A00*
Differential Dry Bulb CRTEMPSN002A00* ( 2) CRTEMP S N002 A 00*
Single Enthalpy HH57AC078 None. The single enthalpy sensor is factory installed.
Differential Enthalpy
for DCV Control using a
CO
2
Wall-Mounted CO
for DCV Control using a
CO
2
Duct-Mounted CO
*CRENTDIF004A00 an d CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may conta in parts that will not be need ed for
installation.
†CGCDXSEN004A00 is an accessory CO
**CGCDXASP001A00 is an accessory aspirator box required for duct-mounted applicatio ns.
Sensor
2
Sensor
2
sensor.
2
Table 7 — EconoMi$er IV Sensor Usage
ECONOMI$ERIV WITH OUTDOOR AIR
DRY BULB SENSOR
Accessories Required Accessories Required
HH57AC078
and
CRENTDIF004A00*
CGCDXSEN004A00
CGCDXSEN004A00†
and
CGCDXASP001A00**
ECONOMI$ERIV WITH SINGLE
ENTHALPY SENSOR
CRENTDIF004A00*
13
Page 14
Fig. 23 — EconoMi$erIV Controller Potentiometer
and LED Locations
19
LED ON
mA
18 17
16 15 14 13 12 11 10
9
40
45
LED OFF
50
D
LED ON
C
LED OFF
60
55
LED ON
B
LED OFF
70
75
65
LED ON
A
LED OFF
90
95
85
80
DEGREES FAHRENHEIT
Fig. 24 — Outside Air Temperature
Changeover Set Points
1 R T
R T
c Va 4
2
OM C
4
2
_
c Va
T
H
O
X
H
E
t
+
e S
V
10
2
V
2
1 N
1
N
5
n i
XH
M
E
s o P
IAQ
SENSOR
1 P
4
en
P
p
O
V
3
C
D
x
1 T
1
a
F
M
E
T
V 0 1
F E
V 2
V C D
V
C
et
D
S
V
0
Q1
1
A
Q A
V 2
+
O
e e
S
r
C
F
l
O
o
o
S
C
B
D + R
S
A
R
S
RETURN AIR
TEMPERATURE
OR ENTHALPY
SENSOR
Fig. 25 — Return Air Temperature or Enthalpy
Sensor Mounting Location
100
Outdoor Enthalpy Changeover For enthalpy control, accessory enthalpy sensor (part num-
ber HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 20. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the ou tdoor enthalpy set poi nt potentiome­ter on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 26. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$erIV controller. See Fig. 23 and 27.
Differential Ent halpy Control For differential enthalpy control, the EconoMi$er IV cont rolle r
uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return airstream on the EconoMi$erIV frame. The EconoMi$erIV controller compares t he outdoor air enthalp y to the return air entha lpy to dete rmine Econo Mi$erIV use. The controller s elects the lower enthal py air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air and is below the set point, the EconoMi$erIV opens to bring in outdoor air for free c ooling.
Replace the standard outside air dry bulb temperature sen­sor with the acc essor y enth alpy senso r in th e same mou nting location. See Fig. 20. Mount th e return air enthalpy sen sor in the return airstream . See Fig. 25. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on th e EconoMi$erIV controller. When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting.
NOTE: Remove 620-ohm resistor if differential enthalpy sen­sor is installed.
Indoor Air Quality (IAQ) Sensor Input The IAQ input can be used for demand control ventilation
control based on the level of CO2 measured in the sp ace or return air duct.
Mount the accessory IAQ sensor according to manufacturer specifica t io n s. The IAQ se n so r sh ould be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiome­ters to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. See Fig. 28.
If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$erIV control board will be damaged.
Exhaust Set Point Adjustment The exhaust set point will determine when the exhaust fan
runs based on d am p er po sit i on ( if accessory powe r ex ha ust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 23. The set point represents the damper position above which the exhaust fan will be turned on. When there is a call for exhaust, the E con o Mi $er I V co ntro ller provides a 45 ± 15 sec ­ond delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropri­ate position to avoid unnecessary fan overload.
14
Page 15
CONTROL
CURVE
4
1
2
1
A B C D
1
6
1
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
HA
NT
E
4
2
2
2
0
2
8
35
(2)
LPY
40 (4)
85
(29)90(32)95(35)
46
4
4
42
40
IR
8
3
Y A
6
DR
3
D
N
U
4
3
PO
R
32
E
P
TU
30
B
28
26
(16)
55
(13)
B
50
C
(10)
45
D
(7)
70
(21)
0
1
65
(18)
60
A
80
(27)
75
(24)
0
0
9
80
70
0
6
50
40
RELA
3
100
105
(38)
110
(41)
(43)
)
%
(
IDITY
IVE HUM
T
0
20
0
1
N1
P1
T1
AQ1
SO+
SR+
A
B
C
D
35
40
45
50
55
60
65
70
75
80
(2)
(4)
(7)
(10)
(13)
(16)
(18)
(21)
(24)
85
(27)
(29)90(32)95(35)
100 (38)
105 (41)
110 (43)
HIGH LIMIT CURVE
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 26 — Enthalpy Changeover Settings
CO SENSOR MAX RANGE SETTING
EXH
2V 10V
EXH
Open
2V 10V
DCV
2V 10V
Free Cool
B
A
Min Pos
DCV
Max
DCV
C
D
Set
Set
N
P
T
AQ
SO
SR
TR1
TR
24
24 Vac
Vac
COM
HOT
_
+
12
5
4
3
EF1
EF
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
Fig. 28 — CO2 Sensor Maximum Range Setting
2
800 ppm 900 ppm 1000 ppm 1100 ppm
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 27 — EconoMi$erIV Controller
15
Page 16
Minimum Position Control There is a minimum damper p osition potent iometer on the
EconoMi$erIV controller. See Fig. 23. The minimum damper position maintains the minimum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper posi­tion represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occu­pied ventilation.
When demand ventilation control is not being used, the min­imum position potentiometer should be used to set the occu­pied ventilation position. The maximum demand ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10° F temperature difference between the out­door and return-air temperatures.
To determine the minimum position setting, perform the following proced ur e :
1. Calculate the appropriate mixed-air temperature using the following formula:
OA
(T
x
O
T
= Outdoor-Air Temperature
O
)+ (TR xRA ) = T
100 100
M
OA = Percent of Outdoor Air T
= Return-Air Temperature
R
RA = Percent of Return Air T
= Mixed-Air Temperature
M
As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F.
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the supply-air sensor from terminals T and T1.
3. Ensure that the f actory-installed jumper is i n place across terminals P and P1. If remote damper posi­tioning is being used, make sure that the terminals are wired accor din g to Fig. 22 and that t he mi nimu m position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potent iomet er until the measured mixed-air temperature matches the calculated va lue.
6. Reconnect the supply-air sensor to terminals T and T1.
Remote control of the EconoMi$erIV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part num­ber S963B1128) is wired to the Ec onoMi $erIV con tr oller, the minimum position of the damper can be controlled from a remote location.
To control the minimum damper position remotely, remove the factory-insta lled jumper on the P and P1 terminals on the EconoMi$erIV controller. Wire the field-supplied potenti­ometer to the P and P1 terminal s on the EconoMi $erIV con­troller. See Fig. 27.
Damper Movement Damper movement from full open to full closed (or vice
versa) takes 2
1
/2 minutes. Thermostats The EconoMi$erIV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$erIV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
Occupancy Control The factory defaul t configuration for EconoMi$er IV control
is occupied mode. This is implemented by the RED jumper at TB2-9 to TB2-10. When unoccupied mode is desired, remove the RED jumper and install a field-supplied timeclock function between TB2-9 and TB2-10. When the timeclock contacts are open, the unit control will be in unoccupied mode; when the contacts ar e closed, the u nit control w ill be in occupied mode.
Demand Controlled V enti lation (DCV) When using the EconoMi$erIV for demand controlled venti-
lation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditio ns. The maximum damper position must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be ab out 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.
A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the requ ired ventilation rate at design con dition s. Exceeding th e requ ired ventilation rate means the equipment can co ndition air a t a maximum ventilation rate that is gre ater than the requ ired ventilation rate for maximum occupancy. A proportional­anticipatory strategy will cause the fresh air supplied to increase as the room CO
level increases even though the
2
CO2 set point has not been reached. By the time the CO level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.
In order to have the CO
sensor control the economizer damper
2
in this manner, first determine the damper voltage output for minimum or ba se ventilatio n. Base ventila tion is the ven tila­tion required to remove contaminants during unoccu pied peri­ods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.
(TO x
T
OA
)+ (TR x
100 100
= Outdoor-Air Temperature
O
RA
) = T
M
OA = Percent of Outdoor Air T
= Return-Air Temperature
R
RA = Percent of Return Air T
= Mixed-Air Temperature
M
2
16
Page 17
Once base ventilation has been determined, set the mini­mum damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts t o the ac tuat o r pro vide s a ba se ve ntil at io n rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or bas e plu s 15 cfm pe r pers on). Use Fig. 28 to determine the maximum setting of the CO
sensor.
2
For example, a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 28 to find the point when the CO
sensor output will be 6.7 volts. Line up
2
the point on the graph with the left side of the chart to deter­mine that the range configuration for the CO
sensor sho uld
2
be 1800 ppm. T he EconoMi$erIV control ler will output the
6.7 volts fro m the CO
sensor to the actuator when the CO
2
concentration in the spac e is a t 1100 ppm . The D CV set point may be left at 2 volts since the CO
sensor voltage wi ll be
2
ignored by the Econo Mi$erIV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.
Once the fully occupied damper position has been deter­mined, set the maximu m da mpe r de ma nd con t ro l ve nt il atio n potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels.
CO
Sensor Configuration
2
The CO2 sensor has preset standard voltage settings that can be selected anytime afte r the sensor is powere d up. See Table 8.
Use setting 1 or 2 f or Bryant equipment. See Table 8.
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See Table 8.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed any-
2
time after the s ensor is energiz ed. Follow the s teps belo w to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of
2
the nine variables, starting with Altitude, until the desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
Dehumidification of Fresh Air with DCV Control Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some applications, a field-supplied energy recovery unit can be added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most com­mercial applications.
If normal roof top heating and cooling operation is not ade­quate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.
Table 8 — CO
SETTING EQUIPMENT OUTPUT
1
Interface with Standard
2 Proportional Any
Building Control System
3 Exponential Any
4 5 Proportional 20
Economizer
6 Exponential 15 7 Exponential 20 8 Health & Safety Proportional
Parking/Air Intakes/
9
Loading Docks
LEGEND
ppm — Parts Per Million
Proportional Any
Proportional 15
Proportional
Sensor Standard Settings
2
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
CO
CONTROL RANGE
2
(ppm)
0-2000 1000 50 0-2000 1000 50 0-2000 1100 50 0-1100 1100 50 0- 900 900 50 0-1100 1100 50 0- 900 900 50 0-9999 5000 500 0-2000 700 50
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
17
Page 18
XI. STEP 11 — DEFROST CYCLE
The defrost timer is factory set at 30 minutes. The timer may be field-adjusted to 50 or 90 minutes by moving the wire from the 30 minute contact to the 50 to 90 minute contact. At the end of the time period, the defro st cycle will begin. See Fig. 29.
START-UP
Use the following information and complete Start-Up Check­list on page CL-1 to check out unit PRIOR to start-up.
I. UNIT PREPARATION
Check that unit has been installed in accordance with these installation instructions and all applicable codes.
II. COMPRESSOR MOUNTING
Loosen compressor holddown bolts until sideways movement of the washer under each holddown bolt head can be obtained. Do not loosen completely, as bolts are self -locking and will maintain adjustment.
III. INTERNAL WIRING
Check all electrical co nnec t ions i n uni t contr ol boxe s; tig h ten as required.
IV. REFRIGERANT SERVICE PORTS AND VALVES
Each 542J unit has 2 Schrader-type service ports per circuit; one on the suction line and one on the liquid line. Be sure that caps on the ports are tight. The units also have 2 service valves per circuit; one on the suction line and one on the dis­charge line. Be sure all valves are open.
V. CRANKCASE HEATERS
Heaters are energized as long as there is power to un it. IMPORTANT: Unit power must be on for 24 hours prior to
start-up. Otherwise, damage to compressor may result.
VI. INDOOR FAN
Fan belt and pulleys are factory installed. Remove tape from the fan pulley and adjust pulleys on 542J150 units as required. See Service section on page 23 for inst ructions on adjusting indoor fan performance. See Table 9 for air quan­tity limits. See Tables 10 and 11 for fan performance data.
DEFROST BOARD
90
50
30
DFT
T2
T1
O
R
Y
C
C
OF1
OF2
W2
DEFROST CYCLE TIME
DR
O
R
Y
C
ADJUSTMENT WIRE
LOGIC
CTD
TEST
Fig. 29 — Defrost Board Timer Wiring
Be sure that fa ns r otate in the proper di re c t ion . Se e Table 12 for static pressure drops for accessories and options. See Fig. 30 and 31 for fan performance using horizontal adapter and power exhaust. See Table 14 for fan rpm pulley settings. See Table 16 for indoor-fan moto r performance. To alter fan performance, see Indo or-F an, 542 J150 Un its and In door -Fan, 542J180 Units sections, pages 23 and 24.
Table 9 — Air Quantity Limits
UNIT 542J
150 3750 6250 180 4500* 7500
*Minimum cfm is 5600 when electric heater is used.
MINIMUM AIRFLOW
(Cfm)
MAXIMUM AIRF LOW
(Cfm)
18
Page 19
Table 10 — Fan Performance Data, 542J150 Units
AIRFLOW
(Cfm)
3750 724 481 0.55 838 685 0.78 937 889 1.01 1028 1097 1.25 1111 1309 1.49 4000 754 613 0.70 865 824 0.94 962 1034 1.18 1050 1247 1.42 1131 1463 1.67 4250 786 757 0.86 893 975 1.11 987 1191 1.36 1073 1408 1.60 1152 1629 1.86 4500 818 914 1.04 922 1138 1.30 1013 1360 1.55 1097 1583 1.80 1174 1808 2.06 4750 850 1084 1.23 951 1313 1.50 1040 1541 1.76 1122 1770 2.02 1197 2000 2.28 5000 883 1267 1.44 980 1501 1.71 1068 1736 1.98 1147 1969 2.24 1221 2204 2.51 5250 917 1464 1.67 1011 1703 1.94 1096 1943 2.21 1174 2183 2.49 1 246 2423 2.76 5500 950 1675 1.91 1041 1918 2.19 1124 2165 2.47 1201 2409 2.75 1 272 2655 3.02 5750 985 1901 2.17 1072 2147 2.45 1153 2400 2.73 1228 2650 3.02 1 298 2901 3.31 6000 1020 2142 2.44 1103 2391 2.72 1183 2649 3.02 1256 2905 3.31 1324 3160 3.60 6250 1055 2398 2.73 1135 2650 3.02 1213 2912 3.32 1284 3175 3.62 1352 3435 3.91
AIRFLOW
(Cfm)
3750 1190 1526 1.74 1265 1746 1.99 1337 1972 2.25 1405 2199 2.51 1471 2431 2.77 4000 1208 1684 1.92 1281 1908 2.17 1351 2136 2.43 1418 2368 2.70 1483 2603 2.97 4250 1227 1853 2.11 1299 2082 2.37 1367 2313 2.64 1433 2548 2.90 1496 2787 3.18 4500 1247 2036 2.32 1317 2268 2.58 1384 2503 2.85 1448 2742 3.12 1510 2983 3.40 4750 1269 2232 2.54 1337 2468 2.81 1403 2707 3.08 1465 2948 3.36 1526 3194 3.64 5000 1291 2441 2.78 1358 2680 3.05 1422 2923 3.33 1484 3168 3.61 1544 3418 3.89 5250 1315 2664 3.03 1380 2907 3.31 1443 3154 3.59 1503 3403 3.88 1562 3655 4.16 5500 1339 2900 3.30 1403 3148 3.59 1464 3398 3.87 1524 3651 4.16 —— — 5750 1364 3151 3.59 1426 3403 3.88 1486 3657 4.17 6000 1389 3416 3.89 1450 3672 4.18 6250 1415 3695 4.21
LEGEND Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option Watts — In p u t Watts to M o t o r
NOTES:
1. Boldface indicates field-supplied drive required.
2. indicates field-supplied motor and drive required.
3. Factory-shipped motor drive range is 862 to 1132 rpm. Other rpms may require a field-supplied drive.
4. Maximum continuous bhp is 4.25 maximum continuous watts are
3775. Do not adjust motor rpm such that motor maximum bhp and/ or watts is exceeded at the maximum operating cfm.
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bh p Rpm Watts Bhp Rpm Watts Bhp
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
1476 3957 4.51 1534 4219 4.81
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL ST ATIC PRESSURE (in. wg)
1510 3930 4.48
5. Static pressure losses (i.e., EconoMi$erIV) must be added to external static pressure before entering Fan Performance table.
6. Interpolation is per miss ible. Do not extrapolate.
7. Fan performance is based on wet coils, clean filters, and casing losses. See Table 12 for accessory/FIOP static pressure information.
8. Extensive motor and drive testing on these units ensures tha t the full horsepower and watts range of the motor can be utilized with confidence. Using fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
1545 3914 4.46
19
Page 20
Table 11 — Fan Performance Data, 542J180 Units
AIRFLOW
(Cfm)
4500 584 717 0.8 695 952 1.1 798 1205 1.3 893 1483 1.7 984 1786 2.0 4800 609 839 0.9 717 1085 1.2 815 1346 1.5 907 1630 1.8 994 1938 2.2 5100 634 971 1.1 738 1229 1.4 833 1500 1.7 921 1791 2.0 1006 2104 2.4 5400 660 1118 1.3 760 1389 1.6 852 1669 1.9 937 1968 2.2 1019 2286 2.6 5700 687 1284 1.4 783 1566 1.8 873 1858 2.1 956 2165 2.4 1034 2490 2.8 6000 712 1458 1.6 805 1752 2.0 892 2055 2.3 973 2371 2.7 1049 2703 3.0 6300 736 1644 1.8 826 1952 2.2 911 2265 2.5 990 2591 2.9 1064 2930 3.3 6600 763 1856 2.1 851 2176 2.4 933 2502 2.8 1010 2837 3. 2 1082 3186 3.6 6900 788 2078 2.3 873 2410 2.7 954 2747 3.1 1029 3093 3. 5 1099 3451 3.9 7200 813 2316 2.6 896 2662 3.0 975 3011 3.4 1048 3367 3. 8 1117 3734 4.2 7500 841 2584 2.9 921 2943 3.3 998 3304 3.7 1070 3672 4. 1 1137 4049 4.5
AIRFLOW
(Cfm)
4500 1070 2113 2.4 1151 2458 2.8 1229 2819 3.2 1302 3194 3.6 1371 3578 4.0 4800 1078 2269 2.5 1157 2620 2.9 1233 2990 3.3 1306 3374 3.8 1375 3769 4.2 5100 1086 2439 2.7 1164 2795 3.1 1238 3170 3.5 1310 3560 4.0 1378 3965 4.4 5400 1097 2626 2.9 1172 2986 3.3 1245 3366 3.8 1315 3763 4.2 1382 4174 4.7 5700 1110 2835 3.2 1183 3200 3.6 1253 3584 4.0 1322 3986 4.5 1388 4404 4.9 6000 1122 3053 3.4 1193 3422 3.8 1262 3810 4.3 1329 4216 4.7 1393 4638 5.2 6300 1135 3286 3.7 1204 3660 4.1 1271 4052 4.5 1336 4461 5.0 1399 4887 5.5 6600 1151 3549 4.0 1218 3928 4.4 1283 4325 4.8 1347 4739 5.3 1409 5169 5.8 6900 1167 3821 4.3 1232 4207 4.7 1295 4608 5.2 1357 5026 5.6 7200 1183 4113 4.6 1246 4505 5.0 1308 4912 5.5 7500 1202 4437 5.0 1264 4837 5.4
LEGEND Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option Watts — In p u t Watts to M o t o r
NOTES:
1. Boldface indicates field-supplied drive required.
2. indicates field-supplied motor and drive required.
3. Factory-shipped motor drive range is 799 to 1010 rpm. Other rpms may require a field-supplied drive.
4. Maximum continuous bhp is 5.90 maximum continuous watts are
5180. Do not adjust motor rpm such that motor maximum bhp and/ or watts is exceeded at the maximum operating cfm.
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bh p Rpm Watts Bhp Rpm Watts Bhp
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL ST ATIC PRESSURE (in. wg)
1324 5251 5.9 1383 5679 6.4 1440 6122 6.9
5. Static pressure losses (i.e., EconoMi$erIV) must be added to external static pressure before entering Fan Performance table.
6. Interpolation is per miss ible. Do not extrapolate.
7. Fan performance is based on wet coils, clean filters, and casing losses. See Table 12 for accessory/FIOP static pressure information.
8. Extensive motor and drive testing on these units ensures tha t the full horsepower and watts range of the motor can be utilized with confidence. Using fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
1368 5335 6.0 1437 5773 6.5
1417 5460 6.1
20
Page 21
Table 12 — Accessory/FIOP Static Pressure (in. wg)
ACCESSORY/FIOP
Electric Heaters
UNIT SIZE
542J
150
180
UNIT VOLTAGE kW
208/230-3-60
460-3-60
208/230-3-60
460-3-60
14,34 42,56
15,32550.05 26,34
42,56
32 55
3750 4000 4500 5000 5600 6000 6250 7200 7500
0.05
0.05
0.06
0.05
0.06
0.06
0.07
0.06
0.07
0.06
0.06 ****
****
AIRFLOW (Cfm)
0.07
0.08
0.08
0.10
0.07
0.08
0.08
0.10
0.08
0.10
0.08
0.10
0.09
0.12
0.09
0.12
0.09
0.12
0.09
0.12
0.09
0.13
0.09
0.13
0.09
0.13
0.09
0.13
†† ††
0.11
0.16
0.11
0.15
EconoMi$erIV All All — 0.030.030.040.050.060.070.070.090.10
Glycol Coil All All — 0.160.180.220.260.310.350.370.440.46
LEGEND
FIOP — Factory-Installed Option
*Do not operate unit with electric heat at this cfm. Operation at this cfm
is below electric heat required minimum cfm.
†Do not operate unit at this cfm. Operation at this cfm is above unit
maximum cfm limit.
NOTES:
1. Heaters are rated at 208 v, 240 v and 480 v.
2. The factory asse mbled horizontal adapter substantially improves fan performance. See Fig. 30.
3. The static pressure must be added to external static pressure. The sum and the indoor-air section entering-air cfm should then be used in conjunction with the Fan Performance table to deter mine blower rpm, bhp, and watts.
Table 13 — Fan Rpm at Motor Pulley Settings* (Factory-Supplied Drives)
UNIT 542J
0
1
/
2
11
1
/
2
150 1132 1105 1078 1051 1024 997 970 943 916 889 862 180 1010 989 968 947 926 905 883 862 841 820 799
*Approximate fan rpm shown.
†Due to belt and pulley size, pulley cannot be set to this number of turns
open.
MOTOR PULLEY TURNS OPEN
22
1
/
2
33
NOTE: To run units at speeds not listed, field-supplied drives are
required.
1
/
2
44
1
/
2
551/
0.12
0.17
0.12
0.17
6
2
Table 14 — Indoor-Fan Motor Performance
UNIT 542J
UNIT
VOLTAGE
ACCEPTABLE CONTINUOUS
BHP*
MAXIMUM
150
180
208/230
460 4.9 85.8
208/230
460 7.9 87.5
4.25 3775
5.90 5180
LEGEND *Extensive motor and electrical testing on these units ensures that the
Bhp — Brake Horsepower
MAXIMUM
ACCEPTABLE
OPERATING
MAXIMUM
AMP DRAW
MOTOR
EFFICIENCY
WATTS
10.5 85.8
15.8 87.5
full horsepower range of the motors can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
NOTE: The CRRFCURB013A00 horizontal supply and return adapter accessory improves 542J fan performance by increasing external static pressure by amount shown above.
Fig. 30 — Horizontal Supply/Return Fan Performance
with CRRFCURB013A00 Horizontal Supply Adapter
Fig. 31 — Fan Performance Using Accessory
Power Exha ust
21
Page 22
VII. OUTDOOR FANS AND MOTORS
Fans and motors are factory set. Refer to Outdoor-Fan Adjustment section on page 24 as required.
VIII. RETURN-AIR FILTERS
Check that correc t filters are instal led in filter tracks. See Table 1. Do not operate unit without return-air filters.
IX. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screens mu st be in place before op erating unit.
X. OPERA TING SEQUENCE A. Cooling, Units Without Economizer
When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC), reversing valve solenoids (RVS1 and RVS2 [RVS2 on size 180 only]) and compressor contactor are energized and indoor-fan motor, compressor, and outdoor fan starts. The outdoor-fan motor runs continuously while unit is cooling.
B. Heating, Units Without Economizer
Upon a request for heating from the space thermostat, ter­minal W1 will be ener gized with 24 v. The IFC, outdoor-fan contactor (OFC), C1, and C2 (size 180 only) will be ener­gized. The indoor fan, outdoor fans, and compressor no. 1, and compressor no. 2 are energized and RVS1 and RVS2 (size 180 only) are deenergized and switch position.
If the space temperature continues to fall while W1 is energized, W2 will be energized with 24 v, and the heater contactor(s) (HC) will b e energized, which will energize the electric heater(s).
When the space thermo stat is satisfied, W2 will be deener­gized first, and the electric heater(s) will be deenergized.
Upon a further rise in space temperature, W1 will be deenergized.
C. Cooling, Units With EconoMi$erIV
When free cooling is not avail able, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is modulated by the EconoMi$erIV c on tr o l to p rov id e a 50 to 5 5 F supply-air tem­perature into the zone. As the supply-air temperature fluctu­ates above 55 o r below 50 F, the dampers will be modu lated (open or close) to bring the supply-air temperature back within set point limits.
For EconoMi$erIV operation, there must be a thermostat call for the fan (G). This will move the damper to its mini­mum position during the occupied mode.
Above 50 F supply-air temperature, the dampers will modu­late from 100% o pen to the minimum open po sition. From 50 F to 45 F supply-air temperature, the dampers will main­tain at the minimum open position. Below 45 F the dampers will be completely shut. As the supply-air temperature rises, the dampers will com e ba ck ope n to the m inim u m ope n po si ­tion once the supply-air temperature rises to 48 F.
If optional power exhaust is installed, as the outdoor-air damper opens and c loses, the power exhaust fan will be e ner­gized and deenergized.
If field-installed accessory CO
sensors are connecte d to the
2
EconoMi$erIV control, a demand controlled ventilation strategy will begin to operate. As the CO increases abov e the CO
set point, the minimum position of
2
level in the zone
2
the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air
damper will be propo rtionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode.
Damper movement from full closed to full open (or vice versa) will take between 1
1
/2 and 21/2 minutes.
If free cooling can be used as determined from the appropri­ate changeover command (switch, dr y bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cool­ing (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply a ir tem­perature set point at 50 to 55 F.
As the supply-air temperature drops below the set point range of 50 to 55 F, the control will modulate the outdoor-air damp­ers closed to maintain the proper supply-air temperature.
D. Heating, Units With EconoMi$erIV
When the room thermostat calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. When the indoor fan is energized, the economizer damper moves to the minimum position. When the indoor fan is off, the economizer damper is fully closed.
E. Defrost
When the tempera ture of the outdoo r coil drops bel ow 28 F as sensed by the defros t thermostat (DFT2) and the defr ost timer is at the end of a timed period (adjustable at 30, 50, or 90 minutes), reversing valve solenoids (RVS1 and RVS2) are energized and the OFC is deenergized. This switches the position of the reversing valves and shuts off the outdoor fan. The electric heaters (if installed) will be energized.
The unit continues to defrost until the coil temperature as measured by DFT2 (see Fi g. 32 ) reach es 65 F, or the duration of defrost cycle completes a 10-minute period.
During the Defrost mode, if circuit 1 defrosts first, RVS1 will oscillate between Heating and Cooling modes until the Defrost mode is complete.
At the end of the defrost cycle, the electric heaters (if installed) will be deenergized; the reversing valves switch and the outdoor-fan motor will be energized. The unit will now operate in the Heating mode.
If the space thermostat is satisfied during a defrost cycle, the unit will continue in the Defrost mode until the time or tem­perature constraints are satisfied.
DEFROST THERMOSTAT
NOTE: Defrost thermostat is located at the bottom tee of circuit no. 1 and the top tee of circuit no. 2.
Fig. 32 — Defrost Thermostat Location
22
Page 23
SERVICE
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch to unit. Turn off accessory heater power switch if applicab le. Electrical shock could cause personal injury.
I. CLEANING
Inspect unit i nterior at beginni ng of each heating and cool­ing season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior.
A. Indoor Coil
Clean as required with a commercial coil cleaner.
B. Outdoor Coil
Clean outdoor coil annually and as required by location and outdoor-air conditions. Inspect coil monthly — clean as required.
C. Condensate Drain
Check and clean each year at start of cooling season.
D. Filters
Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to Table 1 for type and size.
E. Outdoor-Air Inlet Screens
Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens.
II. LUBRICATION A. Compressors
Each compressor is charged with the correct amount of oil at the factory. Observe the level in the sight glass immediately after shutdown while the oil is still warm. If the oil level is observed when the oil is cold, the level observed may be a mixture of oil and refrigerant which is not a true indication of the oil level. If oil level observed is not between the low limit and high limit levels as indicated in Fig. 33, add oil until it is in the correct range.
B. Fan Shaft Bearings
For size 150 units, bearings are permanently lubricated. No field lubrication is required. For size 180 units, the bearings are of the pillow block type and have grease fittings. The bearing opposite the motor end has an extended tube line so it can be lubricated from the motor side. Lubricate the bear­ings twice annually.
Typical lubricants are given below:
MANUFACTURER LUBRICANT
Texaco Regal AFB-2*
Mobil Mobilplex EP No. 1
Sunoco Prestige 42
Texaco Multifak 2
*Preferred lubricant because it contains rust and oxidation inhibitors.
C. Outdoor and Indoor-Fan Motor Bearings
The outdoor and indoor-fan motors have permanently sealed bearings, so no field lubrication is necessary.
III. INDOOR FAN, 542J150 UNITS A. Performance Adjustment
Fan motor pulleys on the 542J150 units are factory set for speed shown in Table 1.
To change fan speeds :
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting plate nuts.
3. Loosen movable-pulley flange setscrew (see Fig. 34).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fa n speed i ncreases load on mo tor. Do not exceed maximum speed specifie d in Table 1.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting plate.
B. Service and Replacement (see Fig. 35) NOTE: To remove belts only, follow Steps 1-7.
1. Remove filter and supply-air section panels.
2. Remove unit top panel.
3. Remove coil guard.
4. Loosen screws A and B on both sides of motor mount assembly.
5. Loosen screw C.
6. Rotate motor mount assembly (with motor attached) as far as possible away from indoor coil.
7. Remove belt.
8. Rotate motor mount assembly back past original position toward indoor coil.
9. Remove motor mounting nuts D and E (both sides).
10. Lift motor up through top of unit.
11. Reverse Steps 1-10 to install new motor.
12. Check and adjust belt tension as necessary.
Fig. 33 — Compressor Sight Glass Oil Level
Fig. 34 — Indoor-Fan Pulley Alignment and Adjustment
23
Page 24
Fig. 35 — 542J150 Indoor-Fan Motor Section
IV. INDOOR FAN, 542J180 UNITS A. Performance Adjustment
Fan motor pulleys are factory set for speed shown in Table 1.
To change fan speeds :
1. Shut off unit power supply.
2. Loosen nuts on th e 2 carriage bolts in the mo unting base. Install jacking bolt and plate under motor base (bolt and plate are shipped in installer’s packet). Using bolt and plate, raise motor to top of slide and remove belt. Secure motor in this position by tighten­ing the nuts on the carriage bolts.
3. Loosen movable-pulley flange setscrew (See Fig. 34).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed incr eases lo ad on motor. Do not exceed maximum speed specified in Table 1. See Table 9 for air quantity limits.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)
6. Replace and tighten belts. See Belt Tension Adjust­ment section below.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting plate.
B. Service and Replacement (see Fig. 36)
The 542J180 units use a fan motor mounting system that features a slide-out motor mounting plat e. To replace or ser­vice the motor, slide out the bracket.
1. Remove the indoor-fan access panel and the heating control access panel.
2. Remove the center post (located between the indoor fan and heating control access panels) and all screws securing it.
3. Loosen nuts on the two carriage bolts in the motor mounting base.
4. Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts.
5. Remove the belt drive.
6. Remove jacking bolt and tapped jacking bolt plate.
7. Remove the 2 screws that secure the motor mounting plate to the motor support channel.
8. Remove the 3 screws from the end of the motor sup­port channel that interfere with the motor slide path.
9. Slide out the motor and motor mounting plate.
10. Disconnect wiring connections and remove the 4 mounting bolts.
11. Remov e the motor.
12. To install the new motor, reverse Steps 1-11.
13. Check and adjust belt tension as necessary.
V. BELT TENSION ADJUSTMENT
To adjust belt tension:
1. Loosen fan motor bolts.
2. a. Size 150 units: Move motor mounting plate up or down for proper
belt tension (
1
/2 in. deflection w ith one finger).
b. Size 180 units:
Turn motor jacking bolt to move motor mounting plate up or down for proper belt tension (3/8 in. deflection at midspan with one finger [9 lb force]).
3. Tighten nuts.
4. Adjust bolts and nut on mounting plate to secure
motor in fixed position.
VI. OUTDOOR-FAN ADJUSTMENT (Fig. 37)
1. Turn off unit power supply.
2. Remove access panel(s) closest to the fan to be
adjusted.
3. Loosen fan hub setscrews.
4. Adjust the fan height on the shaft using a straight-
edge placed across the fan orifice.
5. Tighten setscrews and replace panel(s).
6. Turn on unit power.
VII. POWER FAILURE
Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Do not manually operate damper motor.
24
Page 25
NOTE: A 31/2-in. bolt and threaded plate are included in the installer’s packet. They can be added to the motor support channel below the motor mounting plate to aid in raising the motor.
Fig. 36 — 542J180 Indoor-Fan Motor Section
NOTE: Dimensions are in inches.
Fig. 37 — Outdoor Fan Adjustment
VIII. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate and in Table 1.
Unit panels must be in place when unit is operating during charging procedure.
A. No Charge
Use standard evacuating techniques. After evacuating sys­tem, weigh in the specified amount of re frigerant (refer to Table 1).
B. Low Charge, Cooling
Using appropriate cooling charging chart (see Fig. 38 and
39), add refrigerant until conditions of the chart are met. Note that charging charts are different from those normally used. Charts are based on ch arging units to correct super­heat for various operating co nditions. An accurate pressure gage and temperature sensin g device are required. Connec t temperature sensing device to service port on suction line and insulate it so that outdoor ambient temperature does not affect reading. Indoor-air cfm must be within normal operat­ing range of unit.
C. To Use Cooling Charging Chart
Take outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determ ine cor­rect suction temperature. If suction temperature is high, add refrigerant. If suction tem perature is low, careful ly recover some of the charge. Recheck suction pressure as charge is adjusted.
Example (Fig. 39)
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 5 F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 psig
Suction Temperature Should be . . . . . . . . . . . . . . . . . . . .60 F
(Suction Temperature may vary ± 5 F.)
D. Low Charge, Heating
If outdoor ambient temperature is above 40 F, operate unit on cooling and refer to Low Charge, Cooli ng se ction ab ove. If outdoor ambient is below 40 F, evacuate sys tem and weigh in specified amount of refrigerant. (Refer to Table 1.)
IX. FILTER DRIER
Replace whenever refrigerant system is exposed to atmosphere.
X. PROTECTIVE DEVICES A. Compressor Protection
Overcurrent Each compressor has one manu al reset, calibrated trip, mag-
netic circuit bre aker. Do not bypass c onnections or incr ease the size of the circuit break er to correct trouble. Determine the cause of the trouble and c orrect it before resetting the breaker.
Overtemperature Each compressor has internal protector to protect it against
excessively high discharge gas temperature. Crankcase Heater Each compres sor ha s 125-wa tt cran kcase heat ers to preven t
absorption of liq uid r efri ge rant by oi l in the cr ank case when the compressor is idle. Since power for the crankcase heaters is drawn from the unit incoming power, main unit power must be on for the heaters to be energized.
IMPORTANT: After a prolonged shutdown or service job, energize the crankcase heaters for 24 hours before starting the compressors.
Compressor Lockout If any of the saf eties (high-pressure or low-pressure, freeze
protection thermostat, compressor internal thermostat) trip, or if there is loss of power to the compressor s, the CLO (com­pressor lockout) will lock the compressor s off. To reset, man­ually move the thermostat setting.
B. Indoor-Fan Motor Protection
A manual reset, calibrated trip, magnetic circuit breaker protects against ov ercurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before r esetting the breaker.
C. Outdoor-Fan Motor Protection
Each outdoor-fan motor is internally protected against overtemperature.
25
Page 26
Fig. 38 — Cooling Charging Chart, 542J150 Units
D. High and Low-Pressure Switches
If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automati­cally locked out by the CLO. To reset, manually move the thermostat setting.
E. Freeze Protection Thermostat (FPT)
An FPT is located on the indoor coil. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized by resetting the CLO from the thermostat.
XI. RELIEF DEVICES
All units have relief devices to protect against damage from excessive pressu res (i.e., fire). These devices protect the high and low side.
XII. CONTROL CIRCUIT, 24-V
This control circuit is protected against overcurrent by a
3.2-amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. Typical wiring is shown in Fi g. 40 and 41.
XIII. OPTIONAL HINGED ACCESS DOORS
When the option al se rvic e pac ka ge is ord ered or i f the hin ged access doors option is ordered, the unit will be provided with external and internal hi nged access doors to facilitate service.
Four external hinged access doors are provided. All external doors are provid ed with 2 l arge
1
/4 turn latches with folding bail-type handles. (Compressor access doors have one latch.) A single door is provided for filter and drive access. One door is provided for control box access. The control box access door is interlocked with the non-fused disconnect which must be in the OFF position to open the door. Two doors are provided for access to the compressor compartment.
Two internal access doors are provided inside the filter/drive access door. The filter access d oo r (on t he left) is secured by 2
1
small
/4 turn latches with folding bail-type handles. This door must be opened prior to opening the drive access door. The drive access door is shipped with 2 sheet metal screws holding the door closed. Upon initial opening of the door, these screws may be removed and discarded. The door is then held shut by the filter access door, which closes over it.
XIV. REPLACEMENT PARTS
A complete list of repl acement parts may be obtained from any Bryant distributor upon request.
Fig. 39 — Cooling Charging Chart, 542J180 Units
26
Page 27
Fig. 40 — Typical Wiring Diagram (542J150, 208/230-3-60 V Shown)
27
Page 28
Fig. 41 — Typical Component Arrangement (542J150, 208/230-3-60 V Shown)
28
Page 29
LEGEND AND NOTES FOR FIG. 40 AND 41
LEGEND
AHA Adjustable, Heat Anticipator BRK W/AT — Breaks with Amp Turns C—Contactor, Compressor CAP Capacitor CB Circuit Breaker CC Cooling Compensator CH Crankcase Heater CLO Compressor Lockout COMP Compressor Motor CTD Compressor Time Delay DB Defrost Board DFT Defrost Thermostat DM Damper Motor DR Defrost Relay DU Dummy Terminal EQUIP Equipment FL Fuse Link FPT Freeze Protection Thermostat FU Fuse GND Ground HC Heater Contactor HPS High-Pressure Switch HR Heat Relay HTR Heater IAQ Indoor Air Quality Sensor IFC Indoor-Fan Contactor IFCB Indoor-Fan Circuit Breaker IFM Indoor-Fan Motor IP Internal Protector L—Light LALS Low Temperature Compressor
LPS Low-Pressure Switch LS Limit Switch NEC National Electric Code OAT Outdoor Air Temperature Sensor OCCUP Occupancy Sensor
Lockout Switch
OFC Outdoor Fan Contactor OFM Outdoor Fan Motor OP Overcurrent Protector PL Plug Assembly QT Quadruple Terminal RVR Reversing Valve Relay RVS Rev ersing Valve Solenoid TB Terminal Block TC Ther m osta t Cooling TH Ther m osta t Heating TRAN — Transformer
Terminal (Marked) Terminal (Unmarked) Terminal Block Splice
Factory Wiring Field Wiring Option/Accessory Wiring To indicate common potential only;
not to represent wiring. Economizer Motor
Remote POT Field Accessory OAT Sensor Disch Air Sensor RAT Accessory Sensor
Low Ambient Lockout Switch
NOTES:
1. Compressor and/or fan motor(s) thermally protected three-phase motors protected against primar y single phasing conditions.
2. If any of the original wire furnished must be replaced, it must be replaced with T y pe 90° C or its equiv alent.
3. TRAN1 is wired for 230-v operation. If unit is 208-v, disconnect the black wires from the ORN TRAN wire and reconnect to the RED TRAN wire, apply wirenuts to wires.
4. CB1,2 must trip amps are equal to or less than 156% FLA, IFCB 140%.
5. The CLO locks out the com pressor to p revent short cycling on com pressor overload and safety devices; before replacing CLO, check these devices.
6. Jumpers are omitted when unit is equipped with economizer.
7. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single pole, double throw contact. An underlined number signifies a norm ally closed contact. Plain (no line) number signifies a normally open contact.
8. Remove jumper between RC & RN.
9. 620 Ohm, 1 watt, 5% resistor should be removed only when using differential enthalpy or dry bulb.
10. If a separate field-supplied 24-v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
11. OAT sensor is shipped inside unit and must be relocated in the field for proper operation.
12. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position.
29
Page 30
TROUBLESHOOTING
I. UNIT TROUBLESHOOTING
Refer to Table 15 and Fig. 42-45, for assistance when trou­bleshooting the 542J units.
A. Cooling Cycle
1. Hot gas from compressor flows through the 4-way valve and is directed to the outdoor-coil header. At the header it is condensed and subcooled through converging circuits (7-2-1). Refrigerant leaves the outdoor-coil by way of the check valve to the liquid line.
2. The refrigerant then flows through the filter drier and feeds the indoor coil by way of fixed orifice tubes on each circuit.
3. Each circuit evaporates the refrigerant, and the cir­cuits are combined in the indoor-coil header with some of the circuits flowin g through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator and back to the compressor.
B. Heating Cycle
1. Hot gas from the compressor flows through the 4-way valve and is directed to the indoor-coil header. At the header it is condensed and directed through subcool­ing circuits and out the indoor-coil check valve to the liquid line.
2. The refrigerant then flows through a strainer and feeds the outdoor-coil by way of fixed orific e tubes on each circuit.
3. Each circuit evaporates the refrigerant, and the cir­cuits are combined in the outdoor-coil header with some of the circuits flowin g through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator and back to the compressor.
II. ECONOMI$ERIV TROUBLSHOOTING
See Table 16 for EconoMi$erIV logic. A functional view of the Econ oMi$erIV is shown in Fig. 46.
Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$erIV simulator program is avail­able from Bryant to help with EconoMi$erIV training and troubleshooting.
A. EconoMi$erIV Preparation
This procedure is used to prepare the EconoMi$erIV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoM i$ er IV.
IMPORTANT: Be sure to record the positions of all potenti­ometers before star ting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contac ts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S
and +.
O
Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals S
8. Put 620-ohm resistor across terminals S
and +.
O
and +.
R
9. Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW (clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
B. Differential Enthalpy
To check differential enthalpy:
1. Make sure EconoMi $erIV preparat ion procedure h as been performed.
2. Place 620-ohm resistor across S
3. Place 1.2 kilo-ohm resistor across S
and +.
O
and +. The Free
R
Cool LED should be lit.
4. Remove 620-ohm resistor across S
and +. The Free
O
Cool LED should tu rn off.
5. Return EconoMi$erIV settings and wiring to normal after completing troubleshooting.
C. Single Enthlapy
To check si ngle enthalpy:
1. Make sure EconoMi $erIV preparat ion procedure h as been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.
4. Return EconoMi$erIV settings and wiring to normal after completing troubleshooting.
D. DCV (Demand Controlled Ventilation) and Power Exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi $erIV preparat ion procedure h as been performed.
2. Ensure terminals AQ and AQ1 are open. The LE D for both DCV and Exhaust should be off. The actuator should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The a ctua tor s hou ld dri ve to be tween 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position.
5. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9 v. The actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust con­tacts will close 30 to 120 seconds afte r the Exhaust LED turns on.
7. Return EconoMi$erIV settings and wiring to normal after completing troubleshooting.
30
Page 31
E. DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
1. Make sure EconoM i$erIV prepara tion procedu re has been performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). Th e DCV LED should turn on. The actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to mid­point. The actu ator should drive to bet ween 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should drive fully closed.
8. Return EconoMi$erIV settings and wiring to normal after completing troubleshooting.
F. Supply-Air Input
To check supply-air input:
1. Make sure EconoM i$erIV prepara tion procedu re has been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should drive fully closed.
5. Return EconoMi$erIV settings and wiring to normal after completing troubleshooting.
G. EconoMi$erIV Troubleshooting Completion
This procedure is used to return the Eco no Mi$ er IV to op era­tion. No trouble shooting or testing is done by performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiomete r to previ­ous setting.
4. Set minimum position, DCV set point, and exhaust potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals S
and +.
R
6. Remove 1.2 kilo-ohm checkout resistor from terminals S
and +. If used, reconnect sensor from terminals S
O
and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon­nect wires at T and T1.
10. Remov e jumper from P to P1. Reconn ect device at P and P1.
11. Apply power (24 vac) to terminals TR and TR1.
O
CHECK VALVE
IDENTIFICATION
(See Fig. 42 and 43)
A
B
C
D
E
F
LOCATION
Outdoor coil; Header
Outdoor coil; Liquid line feeding fixed orifice
Outdoor coil; Liquid line leaving coil
Indoor coil; Liquid line feeding fixed orifice
Indoor coil; Liquid line leaving coil
Indoor coil; Header
Table 15 — Check Valve Functions
COOLING
CYCLE
Closed Open
Open Closed Normal
Closed Open
Open Closed Normal
Closed Open
Open Closed Normal
HEATING
CYCLE
Lose circuiting in outdoor coil. Acts like low charge.
Restricted liquid line
Bypasses coil and floods compressor
COOLING CYCLE
CHECK VALVE STUCK
Open Closed Open Closed
Normal Normal
Lose some capacity
Normal Normal Restricted
indoor fixed orifice
Normal Normal Bottom circuits
of indoor coil inactive
Restricted outdoor fixed orifice
Lose some capacity Normal
Lose indoor coil circuiting — symptom of low charge
HEATING CYCLE
CHECK VALVE STUCK
Bottom 3 circuits restricted
Normal
Flooding outdoor coil and compressor
Restricted liquid line
Normal
31
Page 32
LEGEND
Refrigerant Flow Direction Check Valve Flow Direction
X—Fixed Orifice
NOTE: Circuitry shown is for single system; 542J180 units have
2 individual and independent refrigeration systems that each operate in an identical manner.
Fig. 42 — Heat Pump Cooling Cycle
CHECK VALVE* COOLING
A B C D E F
*See Table 15 for check valve operation
details.
Closed Open Closed Open Closed Open
LEGEND
Refrigerant Flow Direction Check Valve Flow Direction
X—Fixed Orifice
NOTE: Circuitr y shown is for single system; 542J180 units have
2 individual and independent refrigeration systems that each operate in an identical manner.
Fig. 43 — Heat Pump Heating Cycle
32
CHECK VALVE* COOLING
A B C D E F
*See Table 15 for check valve operation
details.
Open Closed Open Closed Open Closed
Page 33
Fig. 44 — Troubleshooting Chart, Heating Cycle
ODT — Outdoor Temperature
33
Page 34
Fig. 45 — Troubleshooting Chart, Cooling Cycle
34
Page 35
Table 16 — EconoMi$erIV Input/Output Logic
INPUTS OUTPUTS
Demand Control
Ventil ation (DCV)
Below set (DCV LED Off)
Above set (DCV LED On)
*For single enthalpy control, the module compares outdoor enthalpy
to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply air sensor signal.
††Modulation is based on the DCV signal.
High (Free Cooling LED Off)
Low (Free Cooling LED On)
High (Free Cooling LED Off)
Low (Free Cooling LED On)
Enthalpy*
Outdoor Return
Low On On On On Minimum position Closed
High On On On Off Modulating** (between min.
Low On On On On M odulating†† (between min.
High On On On Off Modulating*** Modulating†††
Y1 Y2
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off Minimum position Closed
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off
Compressor N Terminal†
Stage1Stage
2
position and full-open)
position and DCV maximum)
***Modulation is based on the greater of DCV and supply air sensor
signals, between minimum position and either maximum position (DCV) or fully open (supply air signal).
†††Modulation is based on the greater of DCV and supply air sensor
signals, between closed and either maximum position (DCV) or fully open (supply air signal).
Occupied Unoccupied
Damper
Modulating** (between closed and full-open)
Modulating†† (between closed and DCV maximum)
Fig. 46 — EconoMi$erIV Functional View
35
Page 36
Air quantity limits
18
Changeover set points 14 Charging chart, refr igera nt 26 Clearance 5, 6 CO2 sensor Configuration 17 Settings 15, 17 Compressor Lockout 13, 25 Lubrication 23 Mounting 18 Concentric duct 7 Condensate drain Cleaning 23 Location 3, 8 Control circuit Wiring 8, 9 Convenience outlet 8 Crankcase heater 18, 25 Defrost thermostat 22 Demand control ventilation 16, 17 Dimensions 2, 3, 5, 6 Ductwork 1, 3, 7 EconoMi$erIV 11-17 Control mode 13 Controller wiring 12 Damper movement 16 Demand ventilation control 16 Dry bulb changeover 13 Troubleshooting 30, 31, 35 Usage 13 Wiring 12 Electrical connections 7 Electrical data 9 Enthalpy changeover set points 15 Filter Cleaning 23 Size 4 Filter drier 25 Freeze protection thermostat 26 Heat anticipator settings 9 High-pressure switch 4 Hinged access doors 26 Horizontal adapter roof curb 3, 21 Indoor air quality sensor 14 Indoor coil 4 Cleaning 23 Indoor fan motor Lubrication 23 Motor data 21 Performance 19, 20 Pulley adjustment 23 Pulley setting 4, 21 Speed 4 Low-pressure switch 4 Manual outdoor air damper 10 Motormaster I cont ro l 11 Mounting Compressor 18 Unit 1 Non-fused disconnect 8, 9 Operating limits 18 Operating sequence 22 Cooling 22 Defrost 22 EconoMi$erIV 22 Heating 22 Outdoor air hood 10 Outdoor air i nlet s cre ens Cleaning 23 Outdoor air temperature sensor 13 Outdoor coil 4 Cleaning 23 Outdoor fan 4 Adjustment 24, 25 Physical data 4 Power exhaust 21
INDEX
Power supply 7 Wiring 8 Pressure, drop Economizer 21 Electric heat 21 Glycol heat 21 Pressure switches High pressure 4 Low pressure 4 Refrigerant Charge 25 Type 4 Refrigerant service ports 18 Replacement parts 26 Return air filter 4, 22 Return air temperature sen sor 14 Rigging unit 1, 3 Roof curb Assembly 1 Dimensions 2, 3 Leveling tolerances 2 W eight 4 Safety considerations 1 Service 23-29 Start-up 18-22 Start-up checklist CL-1 Supply-air temperature sensor 13 Thermostat 9, 16 Troubleshooting 30-35 W eight Economizer 4-6 Maximum 3 Unit 4-6 Wind baffle 11 Wiring EconoMi$erIV 12 Power connections 8 Thermostat 9 Unit 27, 28
36
Page 37
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
• Unit Familiari zat ion • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] Classroom Service Training
37
Page 38
Copyright 2006 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 5354-203
Page 39
Page 40
START-UP CHECKLIST
(Remove and Store in Job File)
MODEL NO.: __________________________________ SERIAL NO.: _____________________________________ DATE: ________________________________________ TECHNICIAN: ____________________________________
I. PRE-START-UP
VERIFY THA T ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY PROPER ADJUSTMENT OF INDOOR FAN MOTOR ADJUSTMENT BOLT (150 UNITS) AND ADJUSTMENT BOL T AND PLATE (180 UNITS)
LOOSEN ALL SHIPPING HOLDDOWN BOLTS PER INSTRUCTIONS
OPEN ALL SERVICE VAL VES (SUCTION, DISCHARGE, AND LIQUID)
VERIFY INSTALLATION OF OUTDOOR-AIR HOOD
VERIFY THA T CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
VERIFY THA T ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
CHECK THAT AIR INLET FIL TERS ARE CLEAN AND IN PLACE
VERIFY THA T UNIT IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW IS TIGHT
VERIFY THA T FAN SHEAVES ARE ALIGNED AND BEL TS ARE PROPERLY TENSIONED
VERIFY THA T CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR AL LEAST 24 HOURS
II. START-UP
ELECTRICAL
CUT ALONG DOTTED LINE
SUPPLY VOL TAGE L1-L2 L2-L3 L3-L1 COMPRESSOR AMPS — COMPRESSOR NO. 1 L1 L2 L3
INDOOR-F AN AMPS — COMPRESSOR NO. 2 (180 ONL Y ) L1 L2 L3 SUPPL Y FAN AMPS EXHAUST FAN AMPS ELECTRIC HEAT AMPS L1 L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE F DB (Dry-Bulb) RETURN-AIR TEMPERATURE F DB F WB (Wet-Bulb) COOLING SUPPLY AIR F HEAT PUMP SUPPLY AIR F ELECTRIC HEAT SUPPL Y AIR F
PRESSURES (COOLING MODE)
REFRIGERANT SUCTION CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 (180 ONL Y) PSIG REFRIGERANT DISCHARGE CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 (180 ONLY ) PSIG
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 26
GENERAL
ECONOMI$ERIV MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS
CUT ALONG DOTTED LINE
Copyright 2006 Bryant Heating & Cooling Systems Printed in U.S.A. CL-1 CATALOG NO. 5354-203
Loading...