SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 580F-90-2II 580F-90-3
580F
Dura
Pac
Series
Sizes 090-151
71/2to 121/2Tons
2/1/04
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation
instructions b efore installing this unit. (See Fig. 1A
and 1B.)
2. Be sure the installation conforms to all applicable
local and national codes.
3. These instructions contai n importa nt inform ation for
the proper maintenance and repair of this equipment.
Retain these instructions for futu re use.
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or servic e air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply provided for the unit.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than 1/2 psig. Pressures greater tha n
resulting in hazardous condition. If gas valve is ever
subjected to pressure greater than
replaced before use. When pressure testing fieldsupplied gas piping at pressures of
unit connected to such piping must be isolated by manually closing the gas valve(s).
WARNING: Before performing service or maintenance operations on unit, turn off main power switch
to unit and install lockout tag. Electrical shock could
cause personal injury.
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the
insulation side down. Seals around duct openings must be
tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install access ory roof curb in accorda nce with
instructions shipped with curb. See Fig. 3. Install insulation,
cant strips, roofi ng fe lt, and counter flashing as shown. Duct-work must be attached to curb. If gas or electr ical co nnec tion s
are to be routed through the curb, attach the access ory thruthe-curb service connectio n plate to the roof curb in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 3. Improperly applied gasket can
also result in air or water leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 4. This is necessary for unit drain to function properly.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
If gas or electrical connections are to be routed through the
bottom of the unit, attach accessory thru-the-bottom service
connections to the basepan in accordance with the accessory
installation instructions.
1
/2 psig will cause g as valve damage
1
/
psig, it must be
2
1
/2 psig or less, a
INSTALLATION
Page 2
Fig. 1A — Base Unit Dimensions — 580F090,102,120,150
—2—
Page 3
Fig. 1B — Base Unit Dimensions — 580F091,103,121,151
—3—
Page 4
B. Alternate Unit Support
When the curb or adapter cannot be used, su pport unit with
sleepers using un it curb or adapter supp ort area. If sleeper s
cannot be used, support long sides of unit with a minimum of
three 4-in. x 4-in. pads, two at the corners and one at the
unit’s center of gravity. If more than 3 pads are used, equally
space them along the side.
C. Slab Mount (Horizontal Units Only)
Provide a level concrete slab tha t extends a min imum of 6 in.
beyond unit cabinet. Ins tall a 6-in. g ravel apron in f ront of
condenser coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building s tructure on verti cal units. Do not connect ductwork to unit. For horizontal
applications, field-supplied flanges should be attached to
horizontal discharge openings and all ductwork secured to
the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and
mastic in accordance with applicable codes.
Ducts passing through a n unc ondit i one d spa ce must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed –.30 in. wg with
EconoMi$er+ or .45 in. wg without economizer.
These units are designed for a minimum heating operation
continuous return-air te mperature of 50 F (dry bulb), o r an
intermittent operation down to 45 F (dry bulb), such as when
used with a night set-back thermostat.
To operate at lower return air temperatures, a field-supplied
outdoor-air temperature control must be used to initiate both
stages of heat when the temperature is below 45 F. Indoor
comfort may be compromised wh en these lo wer ai r temperatures are used with insufficient heating temperature ri se.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDENSATE DRAIN
The unit’s
3
/4-in. condensate drain connections ar e located on
the bottom and side of the unit. Unit discharge connections
do not determine the use of drain connections; either
drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, make sure
the plug (Red) in the alternate bottom connection is tight
before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the
bottom connection to the side connection. See Fig. 5A. The
piping for the condensate drain and external trap can be
completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap a minimum of 4-in. deep and protect
against freeze-up. If drain line is installed downstream from
the external trap, pitch the line away from the unit at 1 in.
per 10 ft of run. Do not use a pipe size smaller than the unit
connection (
3
/4 in.). See Fig. 5B .
The center drain plug looks lik e a star conne ctio n, however it
can be removed with a
1
/2 in. socket drive extension.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit.
Rollers may be used to move unit across a roof. Level by
using unit frame as a reference. See Tables 1A and 1B and
Fig. 6 for additional inf ormat ion. Op era ting we ight is s hown
in Table 1 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 1
and 6. Refer to rigging instructions on unit.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
“A”UNIT SIZE
580F
090-151
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01
areforthru-the-curbgastype.Packages
CRBTMPWR003A01 and 4A01 are for thru-the-bottom
type gas connections.
Fig. 3 — Roof Curb Details
—5—
Page 6
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 4 — Unit Leveling Tolerances
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 5A — Condensate Drain Pan (Side View)
3/4” FPT
DRAIN CONNECTION
(HALF COUPLING)
8 1/2-IN. (FIELDSUPPLIED) NIPPLE
2-IN. (FIELD-SUPPLIED) NIPPLE
A. Positioning
Maintain clearan ce around and above un it to provide minimum distance from combustible materials, proper airflow,
and service access. See Fig. 1A and 1B Notes.
Do not install unit in an indoor l ocation. Do not locate unit
air inlets near exhaust vents or other sources of contaminated air.
Be sure that unit is installed so that sn ow will not b lock the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Position unit on roof curb so that the following clearances are
1
maintained:
rails on each side and duct end of unit; 3
/4-in. clearance between roof curb and base
5
/16-in. clearance
between roof curb and condenser section end. (See Fig. 3,
section C-C.)
Locate mechanical draft system flue assembly at least 48 in.
from an adjacent building or combustible material. When
unit is located adjacent to public walkways, flue assembly
must be at least 7 ft above grade.
Flue vent discharge must have a minimum horizontal clearance of 48 in. from electric and gas meters, gas regulators,
and gas relief equipment.
Flue gas can deteriorate building materials. Orient unit so
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion
and Ventilation, NFGC (National Fuel Gas Code), ANSI
3”
(American National Standards Institute) Z223.1-latest year
and addendum Z223.1A-latest year. In Canada, installation
must be in accordance with the CAN1. B149.1 and
CAN1.B149.2 installation codes for gas burning appliances.
4”
Fig. 5B — Condensate Drain Piping Details
—6—
Page 7
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail as shown in detail
‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps
from damaging unit.
3. Weights include base unit without economizer. See Table 1 for
economizer weights.
CAUTION: All panels must be in place when rigging.
**Rollout switch lockout is manually reset by interrupting power to unit or resetting
thermostat.
NOTE: High-static motor not available on size 150 and 151 units.
—11—
Page 12
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the burner compartment
access panel. Remove from shipping location and, using
screws provided, install flue hood and screen in location
shown in Fig. 7.
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipp ed for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local
codes, to ANSI Z223.1-latest year and addendum Z223.1Alatest year entitled National Fuel Gas Code. In Canada,
installation must be in accordance with the CAN1.B149.1
and CAN1.B149.2 installation codes for gas burning appliances when installing gas piping.
For natural gas applications, gas pressure at unit gas connection must not be less than 4.0 in. wg (5.0 in. wg in high
heat units) or greater than 13.0 in. wg while unit is operating. For liquid propane applications, the pressure must not
be less than 5.0 in. wg or greater than 13.0 in. wg at the unit
connection.
Size gas supply piping for 0.5 i n. wg ma ximum pre ssure drop .
Do not use supply pip e smaller than unit gas connection.
CAUTION: When installing gas piping to gas valve
inlet, use properly sized back-up wrench on inlet flange
flats to prevent valve damage.
Support gas piping as shown in the table in Fig. 8. For exam-
3
ple, a
/4-in. gas pipe must have one field-fabricated support
beam every 8 ft.
See Fig. 8 for typical pipe guide and locations of external
manual gas shutoff valve.
NOTE: If field-installed thru-the-bottom connections are
used, refer to the accessory installation instructions for
power wiring and gas connections. Refer to Fig. 1A and 1B
for drilling holes in basepan.
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the
possibility of personal injury if an electrical fault
should occur. This ground may consist of electric al wir e
connected to unit ground lug in control compartment,
or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do notuse gas piping as an electrical ground. Failure to follow
this warning could result in the installer being liable
for personal injury of other s.
A. Field Power Supply
All units except 208/230-v units are factory wired for the
voltage shown on the na meplate. If the 208/230-v u nit is to
be connected to a 208-v power supply, the transformer must
1
be rewired by moving the black wire from the 230- v
/4-in.
male spade terminal on the transformer and connecting it to
the 208-v
1
/4-in. male spade terminal from the transformer.
Refer to unit label diagram for additional information. Pigtails are provided for field service.
When installing units, provide a disconnect per NEC. Use
copper conductors only when splice connectors are used.
All field wiring must comply with NEC and local requirements. In Canada, electrical connections must be in accordance with CSA (Canadian Standards Association) C22.1
Canadian Electrical Code Part One.
Fig. 7 — Flue Hood Details
SPACING OF SUPPORTS
LEGEND
NFGC —
*Field supplied.
NOTE: Follow all local codes.
National Fuel
Gas Code
STEEL PIPE
NOMINAL
DIAMETER (in.)
1
/
2
3
/
or 1
4
1
1
/
or larger
4
X
DISTANCE
(feet)
6
8
10
Fig.8—GasPipingGuide(With Accessory
Thru-the-Curb Service Connections)
Install conduit through side panel openings indicated in
Fig. 1A and 1B. Route power lines through connector to terminal connections as shown in Fig. 9.
On 3-phase units, voltages between ph ase s must be balanced
within 2% and the current within 10%. Use the formula
shown in Tables 2A and 2B, Note 2 to determine the percentage of voltage im balance. Operation on improper line voltage
or excessive phase imbalance constitutes abuse and may
cause damage to electrical components. Such operation
would invalidate any applicable Bryant warranty.
NOTE: If field-installed thru-the-bottom connections are
used, refer to the accessory installation instructions for
power wiring and gas connectio ns. Refer to Fig. 1A and 1B
for drilling holes in basepan.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the
accessory. Locate thermostat assembly on a solid wall in the
conditioned space to sense average temperature in accordance with thermostat installation instructions.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than n o. 18 AWG cannot be dir ectly con nect ed to
the thermos tat and wi ll req uire a j unction box and s plice a t
the thermostat.
—12—
Page 13
Route thermostat cable or equivalent single leads of colored
wire from thermostat subbase terminals to low-voltage connections on unit (shown in Fig. 10) as described in Steps 1-4
below.
If unit is mounted on roof curb and accessory thru-the-curb
service plate connection is used, route wire through connection plate.
Pass control wires through the hole provided on unit (see
connection D in Connection Sizes table in Fig. 1A and 1 B).
Feed wires through the raceway built into the corner post to
the 24-v barrier located on the left side of the control box.
Table 2A — Electrical Data (Without Convenience Outlet)
UNIT
580F
090
(71/2Ton s)
091
(71/2Ton s)
102
(81/2Ton s)
103
(81/2Ton s)
120
(10 Tons)
121
(10 Tons)
150
1
(12
/2Ton s)
151
1
(12
/2Ton s)
NOMINAL
VO LTAGE
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
VO LTAGE
IFM
TYPE
RANGE
Min Max QtyRLALRAQty Hp FLA F LAMCAMOCP**FLALRA
Std
187254214.091.021/41.4
Alt5.840.1/40.145/4542/42229/229
High10.644.9/44.950/5048/48273/273
Std
41450826.442.021/40.7
Alt2.618.42019108
High4.820.62522130
Std
51863225.239.021/40.7
Alt2.614.9201697
High4.816.72018114
Std
187254214.091.021/41.4
Alt5.840.1/40.145/4542/42229/229
High10.644.9/44.950/5048/48273/273
Std
41450826.442.021/40.7
Alt2.618.42019108
High4.820.62522130
Std
51863225.239.021/40.7
Alt2.614.9201697
High4.816.72018114
Std
187254216.0137.021/41.4
High10.649.4/49.460/6052/52365/365
Std
41450828.369.021/40.7
High4.824.93026184
Std
51863226.458.021/40.7
High4.819.42520152
Std
187254217.3***120.0***21/41.4
High10.649.1/49.160/6052/52316/316
Std
41450827 .9***70.0***21/40.7
High4.823.23024171
Std
51863225 .5***50.0***21/40.7
High4.818.52519126
Std
187254215.8130.021/41.4
Alt7.545.9/45.950/5048/48326/326
High15.053.4/53.460/6057/57374/374
Std
41450827.964.021/40.7
Alt3.422.62524191
High7.426.63028185
Std
Alt3.418.72520155
51863226.652.02
High7.421.93023150
Std
187254216.0125.021/41.4
Alt7.546.3/46.360/6049/49316/316
High15.053.4/53.460/6057/57374/374
Std
41450828.062.521/40.7
Alt3.422.82524191
High7.426.83029182
Std
51863226.350.021/40.7
Alt3.418.02019151
High7.421.22523146
Std
187254223.0146.021/41.4
Alt15.069.6/69.680/80††73/73406/406
Std
414508210.473.021/40.7
Alt7.432.24534203
Std
51863228.358.42
Alt7.425.73027162
Std
187254219.0156.02
Alt15.060.6/60.670/70††64/64378/378
Std
41450829.075.02
Alt7.429.13531213
Std
51863227.454.021/40.7
Alt7.423.73025159
COMPR
(ea)
See Fig. 11. The raceway provides the UL-required (Underwriters’ Laboratories) clearance between high- and lowvoltage wiring.
Connect thermostat wires to sc rew terminal s on low-voltage
connecti on board.
C. Heat Anticipator Settings
Set heat anticipator settings at .14 amp for the first stage
and .20 amp for second-stage heating.
OFM
(ea)
1
/40.7
1
/40.7
1
/41.4
1
/40.7
IFM
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
10.6
4.8
4.8
10.6
4.8
4.8
COMBUSTION
FAN M OTO R
FLA
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
POWER SUPPLY*
40.1/40.145/4542/42229/229
18.42019108
14.9201697
40.1/40.145/4542/42229/229
18.42019108
14.9201697
44.6/44.650/5047/47321/321
22.72524162
17.62018135
44.3/44.350/5046/46272/272
21.02522149
16.72017109
44.2/44.250/5046/46307/307
21.82523152
18.12519123
44.6/44.650/5047/47297/297
22.02524188
17.42018119
65.2/65.280/80††68/68383/383
29.64031192
23.63025154
56.2/56.270/70††59/59359/359
26.53028174
21.62523127
DISCONNECT
SIZE†
—13—
Page 14
LEGEND AND NOTES FOR TABLES 2A AND 2B
LEGEND
FLA — Full Load Amps
HACR— Heating, Air Conditioning and Refrigeration
IFM — Indoor (Evaporator) Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*The values listed in this table do not include power exhaust. See table
below for power exhaust requirements.
†Used to determine minimum disconnect per NEC.
**Fuse or HACR circuit breaker.
††Fuse only.
***Compressor no. 1 data indicated in table.
208/230-3-60: Compressor no. 2 RLA is 14.1 amps and LRA is
105 amps.
460-3-60: Compressor no. 2 RLA is 7.1 amps and LRA is 55 amps.
575-3-60: Compressor no. 2 RLA is 6.4 amps and LRA is 40 amps.
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
of voltage imbalance.
% Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
Use the following formula to determine the percent
max voltage deviation from average voltage
AB = 452 v
BC = 464 v
AC = 455 v
average voltage
Average Voltage =
457
=1.53%
452 + 464 + 455
3
1371
=
3
= 457
7
NOTE: If a single power source is to be used, size wire to include power
exhaust MCA and MOCP. Must be in accordance with NEC or local
codes.
Check MCA and MOCP when power exhaust is powered through the
unit. Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580FPV090 unit with MCA = 40.1 and MOCP
= 45, with CRPWREXH030A00 power exhaust.
MCA New = 40.1 amps + 1.6 amps = 41.7 amps
If the new MCA does not exceed the published MOCP, then MOCP
would not change. The MOCP in this example is 45 amps and the MCA
New is below 45; therefore the MOCP is acceptable. If “MCA New” is
larger than the published MOCP, raise the MOCP to the next larger size.
For separate power, the MOCP for the power exhaust will be 15 amps
per NEC.
—14—
Page 15
Table 2B — Electrical Data (With Convenience Outlet)
Splice Connection
(Factory Supplied)
Field Wiring
Factory Wiring
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
B
A
C
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
D
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
(CONNECTION
BOARD)
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when
configured for A/C operation.
Fig. 10 — Low-Voltage Connections
UNIT LOW VOLTAGE
CONNECTION
BOARD
RACEWAY
COMPRESSOR
NO. 2
Fig. 11 — Field Control Wiring Raceway
and Compressor Location
INTEGRATED
GAS UNIT
CONTROLLER
(IGC)
COMPRESSOR
NO.1
—16—
Page 17
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS
A. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove filter access panel by raising panel and
swinging panel outward. Panel is now disengaged
from track an d can be re moved. No to ols are required
to remove the filt er ac cess pa nel. Remove outdoo r-air
opening panel. Save panels and screws. See Fig. 12.
3. Separate hood and screen from basepan by removing
the screws and brackets securing them. Save all
screws and discard brackets.
4. Replace outdoor air o pening panel wi th screws saved
from Step 2.
5. Place hood on front of outdoor-air opening panel. See
Fig. 13 for hood details. Secure top of hood with the 6
screws removed in Step 3. See Fig. 14.
6. Remove and save 6 screws (3 on each side) from sides
of the manual outdo or-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fig. 13 and 14.
Secure hood with 6 screws from Step 6.
8. Adjusting the manual outdoor-air adjustment screws
on the front of the damper blade. See Fig. 12. Slide
blade vertically until it is in the appropriate position
determined by Fig. 15. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screens. Secure screens to hood using the
screws. See Fig. 14.
10. Replace filter access panel. Ensure filter acces s panel
slides along the tracks and is securely engaged.
Fig. 13 — Outdoor-Air Hood Details
HOOD
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
Fig. 12 — Damper Panel with Manual
Outdoor-Air Damper Installed
NOT
SHOWN)
Fig. 14 — Optional Manual Outdoor-Air Damper
with Hood Attached
Fig. 15 — Outdoor-Air Damper Position Setting
—17—
Page 18
B. Optional EconoMi$er+
See Fig. 16 for EconoMi$er+ component locations.
NOTE: These instructions are for the factory-installed optional
EconoMi$er+ only. Refer to the accessory EconoMi$er+
installation instr uc t ion s w hen f iel d ins t all ing an Ec o noMi$er+
accessory.
1. To remove the existing unit filter access panel, raise
the panel and swing the bottom outward. The panel is
now disengaged from the track and can be removed.
See Fig. 17.
2. The box with the EconoMi$er+ hood components is
shipped in the compartment behind the EconoMi$er+.
The EconoMi$er+ does not have to be removed to
retrieve the hood box. Remove the screw holding the
hood box bracket to the top of the EconoMi$er+. Slide
the hood box out of the unit. See Fig. 18.
IMPORTANT: If a power exhaust accessory will be installed
on the unit, the hood shipped with the unit will not be used
and must be discarded. Save the aluminum filter for use in
the power exhaust.
3. The indoor coil access panel will be used as the top of
the hood. Remove the screws a long t he bottom of the
indoor coil access panel. See Fig. 19.
4. Swing out the indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
the screws provided to attach the hoo d sides to the
unit. See Fig. 20.
5. Remove the shipping tape holding the EconoMi$er+
barometric relief damper in place.
6. Insert the hood divider between the hood side s. See
Fig. 20. Secure hood divider with 2 screws on each
hood side. The hood divider is also used as the bottom
filter rack for the aluminum filter.
7. Open the filter clips which are located underneath
the hood top. Insert the aluminum filter into the
bottom filter rack (hood divider) . Push the filter into
position pa st th e op en fi lter c lip s . Cl ose the f ilt er c lip s
to lock the filter into place. See Fig. 21.
8. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 19.
9. Replace the filter access panel.
10. Install all Eco noMi$ er+ acc essori es . Econ oMi$er + wir ing
is shown in Fig. 22.
Barometric flow capacity is shown in Fig. 23. Outdoor air
leakage is shown in Fig. 24. Return air pressure drop is
shown in Fig. 25.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
Fig. 17 — Typical Access Panel Locations
x
o
B
H
d
o
o
HOOD BOX
BRACKET
Fig. 18 — Hood Box Removal
ECONOMI$ER+
PLUG
OUTDOOR AIR
TEMPERATURE
SENSOR
ECONOMI$ER+
CONTROLLER
(UNDER COVER)
OUTDOOR
AIR HOOD
Fig. 16 — EconoMi$er+ Component Locations
HOOD
SHIPPING
BRACKET
ECONOMI$ER+
CONTROLLER
LABELS
GEAR
DRIVEN
DAMPER
BAROMETRIC
RELIEF
DAMPER
—18—
SIDE
PANEL
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
CAULK
HERE
Fig. 19 — Indoor Coil Access Panel Relocation
Page 19
TOP
PANEL
INDOOR COIL
ACCESS PANEL
22 1/4”
LEFT
HOOD
SIDE
B
24 9/16”
HOOD DIVIDER
SCREW
Fig. 20 — Outdoor-Air Hood Construction
40 3/8”
BAROMETRIC
RELIEF
DIVIDER
OUTSIDE
AIR
CLEANABLE
ALUMINUM
FILTER
FILTER
Fig. 21 — Filter Installation
HOOD
FILTER
CLIP
(FIELD-SUPPLIED)
LEGEND
ECON — EconomizerOAT — Outdoor-Air Temperature
IAQ— Indoor-Air Quality (4 to 20 mA)ORH — Outdoor-Air Relative Humidity (Sensor)
IARH — Indoor-Air Relative Humidity (Signal) POT — Potentiometer
IRH— Indoor-Air Relative Humidity (Sensor) RAT — Return-Air Temperature
OARH — Outdoor-Air Relative Humidity (Signal) SAT — Supply-Air Temperature
NOTES:
1. Terminals 13-17 are wired to 5-pin plug assembly (P/N CRE+PLUG001A00).
2. Pin numbers are not printed on the controller. They are provided in this book as a reference.
Fig. 22 — EconoMi$er+ Wiring
—19—
Page 20
2500
2000
FLOW IN CUBIC FEET PER MINUTE (cfm)
1500
1000
500
0
0.05
0.15
STATIC PRESSURE (in. wg)
0.25
71/2-121/2Ton
Fig. 23 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.2 0 0. 22 0.25 0.30 0.35 0.40 0 .45 0.5 0
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
7 1/2-12 1/2 Ton
Fig. 24 — Outdoor-Air Damper Leakage
6000
5000
4000
3000
2000
1000
0
0.050.100.15 0.200.250.300. 35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
7 1/2-12 1/2 Ton
Fig. 25 — Return-Air Pressure Drop
C. EconoMi$er+ Control Mode
Determine the EconoMi$er+ control mode before installing
sensors and accessories. Different sensors are required for
different control modes, and a number of accessories are
available. Refer to Tables 3 and 4.
Outdoor Dry Bulb Changeover
The standard control mode for the EconoMi$er+ is Outdoor
Dry Bulb Changeover. The outdoor air an d supply air temperature sensors are also included as standard.
EconoMi$er+ control is based on the outdoor temperature
relative to a set point in the software. If the outdoor-air temperature is above the set point then the EconoMi$er should
be in minimum position. If the outdoor-air temperature is
below the set point, the position should be controlled to
maintain the l eav ing a ir t emper ature set po in t. The s et po int
range is 45 to 70 F.
Differential D r y Bulb Changeover
The control supports differential dry bulb changeover con-
trol. This requires an accessory return air temperature
sensor CRTEMPSN001A00 installed in the return airstream. Refer to the Start-up section for details on how to
configure and enable the control mode. The user can check
the operation of the s ensor using the Read function.
Outdoor Air Enthalpy Changeover
The control support s ou tdoor air e nthal py cha ngeo ver con trol.
This mode requires a factory-supplied outdoor air temperature
sensor (OAT) and an accessory outdoor air humidity sensor
(ORH) (part no. CRHUMDSN001B00). Refer to the Start-Up
section fo r details on how to con figure and enable th e control
mode. The user ca n check the operation of the sensors using
the Read function.
Differential Ent halpy Changeover
The control supports differential enthalpy changeover con-
trol. This requires the factory-supplied outdoor air temperature sensor, an accessory outdoor air humidity sensor, an
accessory return air temperature sensor, and an accessory
indoor air humidit y sensor. Refer to the Start-Up section fo r
details on how to configure and enable the control mode. The
user can check the o peration of the sens ors using the Read
function.
D. Damper Movement
When the EconoMi$e r+ board receives initia l power, it will
take the damper up to 2
1
/2 minutes before it begins to position itself. After the initial positioning, subsequent changes
to damper position will take up to 30 seconds to initiate.
Damper movement from full open to full closed (or vice
versa) takes 2
1
/2 minutes.
If the damper is in the process of changing positions (for
example it is trying to open to 100%) and the fan signal is
turned off, the damper will con tinue to its 100% open position before closing.
NOTE: Occupied minimum position can not be set lower than
+1% higher than the value of IAQ minimum ec onomizer position. Refer to the setup examples on page 56.
E. EconoMi$er+ Controller Wiring
The EconoMi$er+ is sup plied fr om the factor y with a suppl y
air temperature sensor and an outside air temperature
sensor. This allows for operation of the EconoMi$er+ with
outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of change over
control and operation of the EconoMi$er+ and unit.
F. T hermostats
The EconoMi$er+ control works with conventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat
stage 1), W2 (heat stage 2) , and G (fan). The EconoMi$er+
control does not support sensor thermostats l ike the T56 and
T57. Connections are made at the thermos tat terminal connection board located in the main control box.
—20—
Page 21
Table 3 — EconoMi$er+ Sensor Usage
APPLICATION
Standard UnitIncluded — HH79NZ039———
Differential
Dry Bulb
Outdoor Air
Enthalpy
Differential EnthalpyIncluded — HH79NZ039
NOTES:
Sensors (Optional, 5-Pin sensor wiring plug CRE+PLUG001A00 required for installation.).
1. CO
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 — Aspirator box used for duct-mounted CO
33ZCT55CO2 — Space temperature and CO
33ZCT56CO2 — Space temperature and CO2room sensor with override and set point.
CRCBDIOX002A00 — Return air CO
2. All units include the following Standard Sensors:
Outdoor-Air Sensor — set point adjustable from 45 F to 70 F, factory set at 65 F.
Supply-Air Sensor — set point adjustable from 40 F to 65 F. Factory set at 55 F.
All temperature adjustments are made at the EconoMi$er+ controller.
STANDARD OUTDOOR AIR
TEMPERATURE SENSOR
Included — HH79NZ039
Included — HH79NZ039—
room sensor with override.
2
sensor.
2
Table 4 — EconoMi$er+ Field-Installed Accessories
1
7
/2-121/2Ton Powe r E xhaust
208-230 v 1 Ph
1
7
/2-121/2Ton Powe r E xhaust
460 v 3 Ph
Return Air Temperature Sensor with
Harness
Outdoor Air Humidity Sensor with
Harness
Indoor Air Humidity Sensor w/HarnessCRHUMDSN001B00
Return Air CO
Room Sensor33ZCSENCO2*
CO
2
Aspirator Box for Duct Mount
Sensor
CO
2
Space Temperature and CO
Room Sensor with Override
Space Temperature and CO
Room Sensor with Override
and Set Point
5-Pin Sensor Wiring PlugCRE+PLUG001A00*
*5-pin sensor wiring plug accessory (P/N CRE+PLUG001A00) is
required to install IAQ sensor.
DESCRIPTIONPART NUMBER
CRPWREXH022A00
CRPWREXH023A00
CRTEMPSN001A00
CRHUMDSN001B00
SensorCRCBDIOX002A00*
2
33ZCASPCO2
2
2
33ZCT55CO2*
33ZCT56CO2*
ACCESSORY RETURN AIR
TEMPERATURE SENSOR
Required —
CRTEMPSN001A00
Required —
CRTEMPSN001A00
room sensor.
2
The user can read the value of the sensor using the Read
mode, described in the EconoMi$er+ Controller section.
I. Indoor Air Quality (IAQ) Sensor
Any indoor air quality or CO
20 mA output can be used as the IAQ sensor. The controller
will modulate the outdoor-air damper to provide ventilation
based on the sensor output and the IAQ se tting of the con troller. The CO
the minimum position (IAQ minimum damper position set
point) to the maximum position (occupied minimum damper
position). When there is no CO
unoccupied minimum pos ition. When there is a CO
damper will be between the IAQ minimum economizer set
point position and the occup ied min imum da mper pos ition.
Mount the sensor according to manufacturer specifications.
In order to wire this sensor, an accessory 5-pin plug (part
number CRE+PLUG001A00) is required. See Fig. 22.
The IAQ sensor is wired to the g round an d IAQ w ires in the
harness. The accessory 5-pin wiring plug is connected to pins
13-17 of J3 on the EconoMi$er+ controller. Push the plug
down onto the pins of the EconoMi$e r+ controller to instal l.
sensor will modulate the outdoor-air damper from
2
ACCESSORY
OUTDOOR AIR
HUMIDITY SENSOR
——
Required —
CRHUMDSN001B00
Required —
CRHUMDSN001B00
sensor that provides a 4 to
2
call, the damper will go to the
2
Pins 13 and 14 are used for the IAQ sensor. Pins 15-17 are
G. Outdoor Air Temperature (OAT) Sensor (Provided)
The outdoor air temperature sensor is a 10K thermistor used
to measure the outdoor-air temperature. The sensor controls
EconoMi$er+ changeover and compressor lockout. The sensor
is factory-installed on the EconoMi$er+ in the outdoor airstream. The operating range of temperature measurement is
0° to158 F. See Tables 5 and 6 for thermistor resistan ce and
resolution values.
The temperature sensor l ooks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
The user can read the value of the sensor using the Read
mode, described in the Start-Up section.
H. Supply Air Temperature (SAT) Sensor (Provided)
The supply air temperature sensor is a 10K thermistor
located at the inlet to the indoor fan. This sensor must be
field installed . Th e o per ating range of temperature me as ur ement is 0° to158 F. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor l ooks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
used for the field-installed remote potentiometer. Connect
the IAQ sensor to the BRN and WHT wires o f the accessor y
5-pin plug.
NOTE: Pin numbers are not sh own on th e cont roller. They are
provided only as reference for the installer. On the
EconoMi$er+ board, they numbered 1-17 from left to right, but
only the 1 and the 17 are printed on the board.
Sensor wiring should be extended with wire and wire nuts
and routed to the IAQ sensor location. Adjust the IAQ setting at the controller to correspond to the IAQ voltage output
of the sensor at the user-determined set point. See Fig. 26.
Power the sensor with a field-supplied transformer.
J. Return Air Temperature (RAT) Sensor
The EconoMi$er+ controller will accept input from the accessory 10K return air temperature sensor (CRTEMPSN001A00)
in addition to the outdoor air temperature sensor shipped
with the EconoMi$er+. By using both sensors, the outdoor air
and the return air temperatures are compared (differential
dry bulb) for optimal energy savings. See Tables 5 and 6 for
thermistor resistance and resolution values.
The temperature sensor looks like an eye let terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
ACCESSORY INDOOR
RETURN AIR
HUMIDITY SENSOR
—
Required —
CRHUMDSN001B00
call, the
2
—21—
Page 22
The user can read the value of the sensor using the Read
mode, described in the EconoMi$er+ Controller section.
Mount the return air temp erature sens or on the Eco noMi$er+,
through pre-punched holes. See F ig . 2 7.
The return air temperature (RAT) sensor is provided with a
2-wire, 42-in. long wiring harness with a 2-pin connector.
The plug is installed on pins 5 and 6 on J3 of the
EconoMi$er+ controller. The pins are labeled with a ground
symbol and RAT on the EconoMi$er+ controller. See Fig. 22.
The red wire of the harness is connected to pin 5 (ground).
The black wire of the harness is connected to pin 6 (RAT).
The wiring harness should be routed from the EconoMi$er+
controller to the sensor. The controller compares the temperatures of the two ai rstream s, chooses the be st one, and mod ulates the EconoMi$er+ actuator accordingly.
This 10K thermistor is used to measure the return air
temperature vs. resistance curve, per Table 5. The range of
temperature measurement is between 0° and 158 F. See
Table 6 for resolution.
K. Outdoor Air Humidity Sensor
The EconoMi$er+ controller accepts input from the accessory
outdoor air humidity sensor in ad dition to the out door air temperature sensor shipped with the EconoMi$er+. By using both
sensors, the total ent halpy of the out sid e air is ca lcula ted.
Mount the outdoor-air humidity sensor in to the
EconoMi$er+, through the pre-punched holes. See Fig. 28.
The outdoor-air humidity senso r is provided with a 2-wire,
42-in. wiring harness with a 2-pin connector. The plug is
installed on pins 11 and 12 on J3 of the EconoMi$er+ controller. The pins are labeled ORH and VREF on the
EconoMi$er+ controller. See Fig. 22. The orange wire of the
harness is connected to pin 11 (ORH). The blue wire of the
harness is connected to pin 12 (VREF). The wiring harness
should be rout ed from the Eco noMi$ er+ cont roll er to the se nsor location.
The outdoor enthalpy changeover curve is set at the
EconoMi$er+ controller. The factory default is curve “A.” See
Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
L. Indoor Air Humidity Sensor
For differential enthalpy sensing, the EconoMi$er+ controller uses the standard outdoor air temperature sensor, the
outdoor air humidity sensor, and the optional indoor air
humidity sensor, an optional return air t emperature sensor
(RAT). The indoor-air humidity sensor is provided with a
2-wire, 42-in. wiring harness with a 2-pin connector. The
plug is installed on pins 8 and 9 on J3 of the EconoMi$er+
controller. The pins are labeled IRH and VREF on the
EconoMi$er+ controller. See Fig. 22. The orange wire of the
harness is connected to pin 8 (IRH). The blue wire of th e harness is connected to pin 9 (VREF). The wiring harness
should be extended with wires and wire nuts and routed
from the EconoMi$er+ controller to the sensor location. The
EconoMi$er+ controller compares the outdoor air enthalpy
to the return air enthalpy to determine EconoMi$er+ use.
The controller select s the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air , the EconoMi$er+ controller opens the damp er to bring in outdoor air for free cooling.
Mount the return-air humidity sensor in the return-air duct.
See Fig. 31.
The outdoor enthalpy changeover curve is set with at the
EconoMi$er+ controller. The selectable curves are A, B, C,
and D. The factory default is curve “A.” See Fig. 29. See
Fig. 30 for Sensor Curve vs. Humidity.
CO SENSOR MAX RANGE SETTING
2
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
800 ppm
900 ppm
1000 ppm
1100 ppm
Fig. 26 — Indoor Air Quality Voltage Setting
ECONOMI$ER+ CONTROLLER
ACTUATOR
RETURN AIR
TEMP SENSOR
(HIDDEN)
CURB
VERTICAL ECONOMI$ER+
(3 TO 12 1/2 TON UNITS)
(SIDE VIEW)
HOOD
GROMMET
INDOOR AIR
HUMIDITY SENSOR
Fig. 27 — Return Air Temperature Sensor
—22—
Page 23
Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors
(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve
The EconoMi$er+ supports the use of a field-supplied occupied/
unoccupied switch. When the switch is closed it provides a
24-vac signal to the unit for occu pied mode and when open,
there is no signal to indicate unoccupied mode. The control can
be configured to allow di fferent m inimum e conomizer damper
positions and t o control how mechanical cool ing will and wi ll
not be used in the occupied mode.
NOTE: The remote potentiometer (see below) will overri de th e
occupied minimum position if the potentiometer setting is
greater than the occupied minimum position.
For 3 to 12
1
/2 ton units, a wire from J1-OCC (pin 4) and a
wire from J1-24V (pin 5) a re wire -nutted together to jumper
the terminals.
CURRENT
(mA)
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
6070
RH (%)
10
20
30
40
50
60
70
80
90
80
90
100
An occupied/unoccupied switch can be field-installed in place
of the jumper to allo w the use r to forc e t he co ntrol i nto o ccupied or unoccupied mode of operation for EconoMi$er+
damper position. The occupied/unoccupied switch is required
if the user wants to use unoccupied free cooling or different
EconoMi$er+ damper vent positions in the unoccupied mode.
N. Power Exhaust
Refer to the Accessory Power Exhaust installation instructions
for information o n i n stal ling the power exhaust acc es so ry.
O. Remote EconoMi$er+ Enable Control
When the control is used with energy management systems that
enable and disable the EconoMi$er+, the user can install a fieldsupplied enable/disable switch. The switch must be wired in
series with a 3K ohm, 1 watt or greater resistor. The switch is
wired to terminals ORH (pin 11) and VREF (pin 12) on J3. Refer
to the Start-Up section for details on how to configure the control.
P. R e mote Potentiometer Occupied Minimum Position
The occupied minimum position set point remote potentiometer (field-supplied) is used when requiring additional temporary ventilation. The remote potentiometer (10K ohm closed damper, 100K ohm - open damper) will only control
the occupied minimum position.
The accessory 5-in wiring plug, CRE+PLUG001A00 is
required to connect the potentiometer.
The plug is installed on pins 15, 16 and 17 on J3 of the
EconoMi$er+ controller. The pins are labeled with the ground
symbol, MIN and VREF on the EconoMi$er+ controller. See
Fig. 22. The pink wire from the harness is connected to pin
15 (ground symbol). The gray wire fr om the harness is connected to pin 16 (MIN). The yello w wire from the harn ess is
connected to pin 16 (VREF). The wiring harness should be
extended with wires and wire nuts and routed from the
EconoMi$er+ controller to the remote potentiometer location.
NOTE: Pins 13 (ground symbol) and 14 (IAQ), which are
wired to the accessory 5-pin plug, are not used for the remote
potentiometer installation. They are used for an accessory
IAQ sensor (if required).
—25—
Page 26
The unoccupied m ini mum posi tio n ca n onl y b e se t a t the co ntroller. The occupied minimum position set point configured
at the EconoMi$er+ controller should be set to 0 when using
a remote potentiometer. The occupied minimum position will
also be used as part of the IAQ routing; it will be the
maximum position the damper moves to when there is an
IAQ call.
If the remote potentiometer (occupied) position is greater
than the EconoMi$er+ controller unoccupied minimum position, then the remote potentiometer setting will be used. The
remote potentiometer is field supplied and must be a 3-wire,
linear potentiometer with a resistance between 10K ohm
and 100K ohm (such as the Honeywell S963B1128).
Q.Demand Ventilation Control
Demand ventilation control uses an IAQ sensor
(CRE+PLUG001A00 required) to control the amount of outside air admitted into the system. Normally, the minimum
position of the EconoMi$ er+ damper is est ablished based on
the demand occ upancy of the space. The IAQ s ensor wil l be
used to modulate the EconoMi$er+ minimum damper position below the normal minimum position based on full occupancy. The lowe r li mit is called the base ventilation r at e. See
Fig. 32.
If there is no IAQ signal the damper will be in the unoccupied minimum position (configuration item number 3). If
there is an IAQ signal the damper will be in the occupied
minimum position (configuration item number 15), unless
the remote potentiometer is used to override it.
For the demand ventilation control logic, the user configures
the lower and upper actuator position to establish the base
ventilation rate (IAQMIN_SP) and the de sign ventilation rate
(ECONOMIN_SP) for full occupancy. When the EconoMi$er+
damper is being modulated for demand ventilation control,
the damper position will be between IAQMIN_SP and
ECONOMIN_SP. The upper IAQ differential set point is
DAQHI. The lower IAQ differential set point is DAQLO.
The differential set points represent the differential CO
level (in ppm) above the outdoor reference IAQ le vels. Normally, the outdoor ref er ence IAQ le vel s ar e a ro und 4 0 0 ppm ,
but the value should be configured based on the reference
levels taken at the job site.
DAMPER
POSTION
FULL OCCUPANCY
ECONOMIZER
MINIMUM
OCCUPIED
DAMPER
POSITION
(ECONOMIN_SP)
IAQ
MINIMUM
ECONOMIZER
POSITION
SET POINT
(IAQMIN_SP)
OUTDOOR REFERENCE
LEVEL (OAQ)= 400
VENTILATION RATE
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
100
500
AQ
DIFFERENTIAL
LOW (DAQLO)
1100
AQ
DIFFERENTIAL
HIGH (DAQHI)
INSIDE/OUTSIDE CO
700
INSIDE CO
CO LEVEL
2
DIFFERENTIAL
2
CONCENTRATION
2
Fig. 32 — Demand Ventilation Control
The following equation is used to determine EconoMi$er+
damper position (ECONOMIN_POS):
IAQMIN_SP + =
(ECONOMIN_SP – IAQMIN_SP) * (IAQ –OAQ –DAQLO)
(DAQHI – DAQLO)
R. CO2Sensor Configuration
The CO
sensor has preset standard voltage settings that
2
can be selected anytime afte r the sensor is pow ered up. See
Table 7.
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode 2 times. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
See Table 7.
4. Press Enter to lock in the selection.
Press Mode to exit and resume normal operation. The custom settings of the CO
sensor can be changed any time after
2
the sensor is energized. Follow the steps below to change the
non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
S. Dehumidification of Fresh Air with Demand Control
Ventilation (DCV)
Information from ASHRAE (American Society of Heating,
Refrigeration and Air Conditioning Engineers) indi cates that
2
the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a energy
recovery unit is added to reduce the moist ure content of the
fresh air being brought into the building when the enthalpy
is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads
for most commercial applications.
This makes the control of the dehumidification device simple
when using the enthalpy or differential enthalpy sensor. The
enthalpy sensor or diffe rential enthalpy sensor is installed
on the equipment to determine economizer operation. The
high enthalpy signal from the temperature and humidity
sensors or differential temperature and humidity sensors
can be used to turn on the outdoor air moisture removal
device any time fresh air is required for the space.
The energy recovery device should be sized for maximum
latent and sensible conditioning at maximum ventilation on
a design day.
A calculation for leaving-air temperature on a low ambient,
low ventilation day should also be done to determine the
supply-air temperature of the return and pre-conditioned
outside air. The design should produce air temperature
somewhat near room conditions to prevent reheat of the air
mixture. The energy recovery device should be interlocked
with the heat to turn off the device when in the heat mode.
*Available sensor part numbers are listed in Table 4.
ProportionalAny4-20 mA0-2000100050
Proportional154-20 mA0-1100110050
VENTILATION
RATE
(cfm/Person)
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
Adjust evaporator-fan speed to meet jobsite requirement.
Table 8 shows fan rpm at motor pulley settings and Table 9
shows motor efficiencies. Table 10 shows motor performance.
Refer to Fan Performance Tables 11-30 to determine fan
speed settings. Fan motor pulleys are factory set for speed
shown in Tables 1A and 1B.
To change fan speed:
1. Shut off unit power supply and install lockout tag.
2. Loosen belt by loosening fan motor mounting plate
nuts (see Fig. 33 and 34).
3. Loosen movable pulley flange setscrew (see Fig. 35).
4. Screw movable flange toward fixed flange to increase
ANALOG
OUTPUT
deflection with 5 to 10 lb of force) and tighten mounting nuts (see Fig. 33).
Units 120-151 — Slide motor mounting plate downward to tighten belt tension. (
5 to 10 lb of force.) Secure motor mounting plate nuts.
See Fig. 34.
3. Adjust bolt and nut on mounting plate to secure
motor in fixed position.
Realign fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
CONTROL
CO
2
RANGE (ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
1
/2-in. deflection with
fan speed and away from fixed flange to decrease fan
speed. Incre asing fan speed in creases load on mo tor.
Do not exceed maximum speed specified in Tables 1A
and 1B.
5. Set movable flange at nearest flat of pulley hub and
tighten setscrew (see Tables 1A and 1B for speed
change for each full turn of pulley flange).
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
MOTOR MOUNTING
PLATE NUTS
To adjust belt tension (see Fig. 33 and 34):
1. Loosen fan motor mounting plate nuts.
2. Units 090-103 — Slide motor mounting plate away
from fan scroll for proper belt tension (
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
MOTOR EFFICIENCY
(%)
1
/
6
2
—28—
Page 29
Table 10 — Evaporator-Fan Motor Performance
UNIT
580F
090,091
102,103
120,121
150,151
EVAPORATOR-FAN
MOTOR
Standard,
Alternate
High Static
Standard
High Static
Standard
Alternate
High Static
Standard
Alternate
UNIT
VO LTAGE
208/230
4603.0
5753.0
208/230
4605.5
5755.5
208/230
4603.0
5753.0
208/230
4605.5
5755.5
208/230
4603.0
5753.0
208/230
4603.9
5753.9
208/230
4608.5
5758.5
208/230
4605.5
5755.5
208/230
4608.5
5758.5
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
2.402120
3.703313
2.402120
3.703313
2.402120
2.902615
5.254400
3.703313
5.254400
MAXIMUM ACCEPTABLE
OPERAT ING WATTS
MAXIMUM
AMP DRAW
6.7
12.2
6.7
12.2
6.7
8.6
17.3
12.2
17.3
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
2. High-static motor not available on size 150 and 151 units.
be affected. See Evaporator-Fan Motor Performance data in
Tables 10 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
—29—
Page 30
Table 11 — Fan Performance 580F090,091 — Vertical Discharge Units; Standard Motor (Belt Drive)*
Bhp—Brake Horsepower Input to Fan
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
—49—
Page 50
PRE-START-UP
WARNING: Failure to observe the following warn-
ings could result in serious personal injury.
1. Follow recognized safety practices and wear
protective goggles when checking or servicing
refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal
cover is in place and secured.
3. Do not remove comp ressor terminal cover until
all electrical sou rc e s are disco nnected.
4. Relieve all pressure from system before touching or disturbing anything inside terminal box
if refrigerant leak is su spe cte d arou nd c ompre ssor terminals.
5. Never attempt to repair soldered connection
while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective
goggles and proceed as follows:
a. Shut off electrical power and then gas to
unit.
b. Reclai m refrigerant to relie ve all pressure
from system using both high- and lo w-pre ssure ports.
c. Cut component connection tubing with tub-
ing cutter and remove component from
unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when
exposed to torch flame.
Proceed as follows to ins pect and prep are the unit f or initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected
wires, etc.
b. Inspect for oil at all refrigerant tubing connec-
tions and on unit base. Detecting oil generally
indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak
detector, halide torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring con-
nections. Be sure that connections are completed
and tight. Be sure that wires are not in contact
with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin
comb.
4. Verify the following conditions:
a. Make sure that condenser-fan blade are correctl y
positioned in fan orifice. See Condenser-Fan
Adjustment section on page 62 for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
I. UNIT PREPARATION
Make sure that unit has b een installed in accordance with
these installation instructions and applicable codes. Make
sure that Start-Up Checklist, located on back page of this
booklet, has been completed and filled out.
II. RETURN-AIR FILTERS
Make sure correct filters are inst alled in filter trac ks (see T ables
1A and 1B). Do not operate unit without return-air filters .
III. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screens must be in place before op erating
unit.
IV. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or
remove compressor holddown bolts. On 580F150 and 151
units, remove the tiedown bands that hold the compressors
together.
V. INTERNAL WIRING
Check all electrical connections in unit control boxes.
Tighten as required. Ensure wiring does not come into direct
contact with refrigerant tubing.
VI. GAS PIPING
Check gas piping for leaks.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than
1
/2 psig. Pressures greater tha n 1/2 psig will cause g as valve damage
resulting in hazardous condition. If gas valve is subjected to pressure greater than
1
/2 psig, it must be
replaced before use. When pressure testing fieldsupplied gas piping at pressures of
1
/2 psig or less, a
unit connected to such piping must be isolated by manually closing t he ga s valve.
VII. REFRIGERANT SERVICE PORTS
To service refrigerant service ports, remove compressor
access panel. Each unit system has 3 Schrader-type service
gage ports: one on the suction line, one on the liquid line, and
one on the compressor discharg e line. Be sure that caps on
the ports are tight. The Schrader-type valve on the discharge
line is located under th e low-pressu re switch. Anoth er valve
is located on the discharge line underneath the highpressure switch. It is screwed on a Schrader fitting but there
is no Schrader core.
VIII. HIGH FLOW VALVES
Located on the compressor hot gas and suction tubes are
High Flow Valves. Large black plastic caps distinguish these
valves with O-rings located in s i de th e ca p s. These valves can
not be accessed for service in the field. Ensure the plastic
caps are in place and tight or the possibility of refrigerant
leakage could occur.
IX. COMPRESSOR ROTATION
On 3-phase units with scroll compressors, it is important to
be certain compressor is rotating i n the proper direc tion. To
determine whether or not compressor is rotating in the
proper direction:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
—50—
Page 51
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating
in the wrong direction.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Reapply power to unit. Reen ergize compressor.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction, the unit will make an elevated level of noise and will
not provide cooling.
X. COOLING
To start unit, turn on m ain power supply. Set system selector
switch at CO OL positi on and fan switch at AUT O. position.
Adjust thermostat to a setting below room temperature.
Compressor, indoor and outdoor fans start on closure of
contactors.
Check unit charge. Refer to Checking and Adjusting
Refrigerant Charge section, page 62. Unit must operate a
minimum of 10 minutes before adjusting charge.
Reset thermostat at a position above room temperature.
Compressor and outdoo r fans will shut off. Evaporator fan
will shut off after 30-second delay.
A. To Shut Off Unit
Set system selector switch at OFF position. Resetting thermostat at a positio n above room temperature sh uts unit off
temporarily until space temperature exceeds thermostat
setting.
XI. MAIN BURNERS
Main burners are factory set and should require no
adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set p oint abo ve room t emperat ure and ve rify that the burne rs light and evaporator fan is energized.
After ensuring that the unit continues to heat the building,
lower the thermostat setting below the room temperature
and verify that the burne rs and evapor ator fan turn off ( fan
will turn off only if fan selector switch is in the AUTO. position). Refer to Table 31 for the correct orifice to use at high
altitudes.
NOTE: Upon a call for heat, the main burners will remain on
for a minimum of 60 seconds.
A. Adjust Gas Input
The gas input to the unit is determined by mea suring the
gas flow at the m eter o r by me asuri ng th e ma nifold pres sure .
Manifold pressure should be 3.5 in. wg. in high-fire
operation.
NOTE: Unit uses a 2-stage gas valve. There is no need to
adjust the “Low Fire” manifold pressure.
Measure Gas Flow (Natural Gas Units)
Minor adjustment to the gas flow can be made by changing
the manifold pressure. The manifold pressure must be
3.5 in. wg. Normal manifold pressure is 3.5 in. wg in high
fire (W1 and W2 inputs to gas valve).
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold then connect manometer at this point. Turn on gas to unit. Ensure gas
valve is in high fire operation.
Observe manifold pressure in high fire (W1 and W2 energized) and proceed as follows to adjust gas input:
1. Remove cover screw ove r regulator a djustment s crew
on gas valve. Ensure gas valve is operating in high
fire mode.
2. Turn regulator adjustment screw clockwise to
increase gas input, or turn regulator adjustment
screw counterclockwise to decrease input. High fire
manifold pressure must be 3.5 in. wg.
WARNING: Unsafe operation of the unit may
result if manifold pressure is outside 3.4 to 3.6 in. wg
range. Personal injury or unit damage may result.
3. Replace cover screw cap on gas valve.
4. Turn off gas supply to un it. Rem ove m anometer from
pressure tap and replace pipe plug on gas valve. Turn
on gas to unit and check for leaks.
*As the height above sea level increases, there is less oxygen per cubic foot
of air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local distributor.
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
250,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
XII. HEATING
1. Purge gas supply line of air by opening union ahead
of gas valve. When gas odor is detected, tighten union
and wait 5 minutes before proceeding.
2. Turn on electrical supply and open manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature lever above room temperature.
4. The induced-draft motor will start, purging heat
exchangers.
5. After a call for heating, the main burners should light
within 5 seconds. If the burners do not light, then
there is a 22-second delay before another 5-second
ignition try. If the burners still do not light, the time
delay is repeated. If the burners do not light within
15 minutes, there is a lockout. To reset the control,
break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds
after the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds
after the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within
the range specified on the unit nameplate and in
Tables 1A and 1B.
—51—
Page 52
XIII. INTEGRATED GAS CONTROLLER (IGC) OPERATION
NOTE: The default value for the evaporator-fan motor ON
and OFF delay is 45 sec ond s. The I ntegr ate d Gas Con trol ler
(IGC) modifies this valu e when a bnormal limi t switch cycl es
occur. Based up on unit operating conditions, the O N delay
can be reduced to 0 seconds and the OFF delay can be
extended to 180 seconds.
When one flash of the LED (light-emitting diode) is
observed, the evap orator-fan ON/OFF del ay has been modified. If the limit switch trips at the star t of t he he ating cycle
during the evaporator ON delay, the time period of the ON
delay for the next cycle will be 5 seco nds less than the time
at which the switch tripped. (Example: If the limit switch
trips at 30 seconds, the evaporator-fan ON delay for the next
cycle will occur at 25 seconds.) To prevent short-cycling, a
5-second reduction w ill only occur if a minimum of 10 minutes has elapsed since the last call for heating.
The evaporator -fan O FF dela y can also be m odified. O nce th e
call for heating has ended, there is a 10-min ute period during which the modification can occur. If the limit switch trips
during this period, the evaporator-fan OFF delay will
increase by 15 seco nds on the next cycle. A maximum of 9
trips can occur, extending the evaporator-fan OFF delay to
180 seconds. To restore the original default value, reset the
power to the unit.
A. To Shut Off Unit
Set system selector sw itch at OFF p osition. Re setting h eating selector lever below room temperature will shut unit off
temporarily until space temperature falls below thermostat
setting.
XIV. SAFETY RELIEF
A soft-solder joint at the suction l ine Schrader port provi des
pressure relief under abnormal temperature and pressure
conditions.
XV. VENTILATION (Continuous Fan)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuous ly to
provide constant air circulation. When the evaporator-fan
selector switch is turned to the OFF position, there is a
30-second del a y be f or e th e f an tur ns off.
XVI. ECONOMI$ER+ CONTROLLER
The EconoMi$er+ controller is mounted to the top of the
EconoMi$er+ d amp er and is acce ssibl e by remo ving the fi lter
access door of the unit.
The EconoMi$er+ controller is protected by a sheet metal
enclosure mounted over the controller. Remove the single
screw on the front of the enclosure and lift off the top for
access to the contro ller. The primary purpose of the control ler is to provide cont rol of the EconoMi$er+ da mpers and the
cooling compression stages. The status of the indoor fan is
monitored through the G input but is n ot directly cont rolled
by the controller. The heating function is completely independent of the controller.
IMPORTANT: The controller can only be used with conventional thermostats with Y1, Y2 and G input to the controller;
it can NOT be used with electroni c thermostats with a proportional room temperature input, or with Variable Air Volume systems.
There are 4 LEDs on the controller, which are used to read values and display status and configuration information. There
are 2 buttons (READ/ADJUST and ADVANCE/MANUAL),
which change modes and configure the controller . See Fig. 36.
The EconoMi$er+ microprocessor based control system provides the following control functions:
• EconoMi$er+ damper control for free cooling
• Minimum position control for ventilation
• Demand Ventilation Control using a CO
sensor
2
• Compressor Cooling Stage Control
• Occupied/Unoccupied Control
• Diagnostics Display and History
• Manual test control
See Table 32 for Inputs and Outputs.
A. Integrated Display
The control board includes an integrated display, which is
used for the following functions:
• Configuration and setup
• Set point and control adjustment
• Error status and alarm monitoring
• Manual control
• Reading sensor values
There are 5 modes of display operation:
•Startup Mode
•Run Mode
• Read Mode
•Setup Mode
• Manual Mode
External devices are not required to operate and configure
the control.
B. Startup Mode
During the first 3 secon ds after power is applied to the control, the four LEDs flash as shown in Table 33, indicating
that the control is being initialized. The buttons are not
operational during Startup mode.
C. Run Mode
Run mode indicates status of control ler and unit. The mode
can be changed to the Read, Setup, or Manual modes by
pushing va ri ous buttons.
While the control is in Run mode, the DS1 heartbeat indicator LED (red) will flas h to indi cat e the cont rolle r is ope rat ing
properly. The DS2 Econo indicator LED (yellow) will flash
whenever econom ize r is b ein g us ed f o r fre e co olin g. The DS3
first stage cooling indicator LED (green) will be on steady
indicate demand for sta ge 1 cooling. The DS4 second stage
cooling indicator LED (green) will be on steady to indicate
demand for stage 2 cooling.
If the controller is in a different mode, the controller will
return to Run mode after 10 minutes of user inactivity or if
the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are held for at least 3 seconds until all LEDs flash.
D. Read Mode
Read mode is used to check set points (Table 34) and I/O
channel status (Table 35). Enter the Read mode by pushing
and releasing the READ/ADJUST (#1) button. A user can
only enter Read mode from the Run mode (to get to Run
mode, press both the #1 and #2 buttons for at least 3 seconds
until all LEDs flash). In Read mode, LEDs are not lit until
the READ/ADJUST button (#1) is pushed.
NOTE: If the user pushes and holds the READ/ADJUST button (#1) for more than 3 seconds, then the control will go into
the Setup mode, indicated by the yellow LED (on steady).
While in Read mode, push button #1 then the DS1 LED
(Red) flashes to indicate setup point number as defined in
the setup table. The two green LEDs will then show the
value of the display item. The DS3 LED will first display the
—52—
Page 53
tens digit and the DS4 LED will then display the ones digit.
For example to display 54, the DS3 LED will flash 1 group of
5 at a high flash rate to indicate 50, and then follow with 4
flashes (DS4) at 1-second intervals to complete the display of
the number 54.
NOTE: Do not try to count the “5 Fast Flashes” individually,
but instead count how many groups of 5 flashes were
displayed. In this case, 1 group of 5 flashes, plus the 4 flashes
at 1 second results in the value of 54.
To re ad the di splay again, push the READ/AD JUST (# 1) button and the sequence will repeat as many times as needed.
To advance to the next setup point, push the ADVANCE/
MANUAL (#2) button. The controller will cycle throu gh all
the setup channels (Table 34) and then the I/O channels
(Table 35) and then back to the first setup channel.
NOTE: Th e user can only advance forw ard, no t reset to # 1 or go
backwards. Cycling the EconoMi$er+ power will reset the item
number (but not the item value) to item #1.
In the Read mode for setup variables, the LEDs will not turn
on steady; the LEDs will always flash. Steady-on indicators
are reserved for the configuration modes. No data is modified
in the Read mode. The con troller will always remain at the
last read number even if reset back to normal operat ion.
NOTE: To enter another mode, the user first must exit the
Read mode.
If no button is pushed in 10 minutes, Read mode will automatically be exited. Also, if the READ/ADJUST (#1) and
ADVANCE/MANUAL (#2) buttons are pushed and held for
more than 3 seconds, then Read mode will be exited to Run
mode. While i n the Read mod e , the c ontro ller will conti nue to
operate with normal unit control.
Y1
Y2
G
OCC
24V
READ/
ADJUST
date or serial no
J1
1
Y1 (cool 1)
Y2 (cool 2)
G (fan)
OCC
24 VAC
5
J2
Occupied/unoccupied
I/O support dry circuit
contact (min 24 mA I)
THERMOSTAT INPUTS
POWER
ECONOMIZER
SUPPLY
24 VAC
1
24V
2-10 VDC
CONTROL
24 VAC
Control
24V
CNT
5
#1
J3
ADVANCE
MANUAL
PUSH BUTTONS
1
#2
Relays rated at 24 VAC 3A
and traces for 8A.
NOTE: For 1 and 2 stage
cooling, 2 stages of power
exhaust will be used.
For 3 cooling stages, only 1
stage of power exhaust will be
used, and for 4 stages no power
exhaust will be controlled
directly by the control.
4-20 mA external powered between signal and ground
4-20 mA loop powered between 24 VDC and signal
G (fan)GSwitchStandard 18-30 vac 50/60 Hz w/min 24 mA LoadNAOn/OffJ13
Occupied/UnoccupiedOCCSwitchOption18-30 vac 50/60 Hz w/min 24 mA LoadNAOn/OffJ14,5
POWER
Power24VInputStandard18-30 VAC 50/60 HzNANAJ21,2
ECONOMIZER MOTOR
ControlCNT2-10 vdcStandard2-10 vdc0-100%1%J23,4,5
ANALOG INPUTS
Supply Air TemperatureSAT 10 K Thermistor Standard1816 to 86407 Ohms30 to 125 F0.8 FJ31,2
Outside Air TemperatureOAT 10 K Thermistor Standard1816 to 86407 Ohms30 to 125 F0.8 FJ33,4
Return Air TemperatureRAT 10 K ThermistorOption1816 to 86407 Ohms30 to 125 F0.8 FJ35,6
Indoor HumidityIRH
Outdoor HumidityORH
Indoor CO
Remote Minimum
Posi tion Pot
RELAY OUTPUTS
Cooling Stage 1CP1RelayStandard24 vac, 2.5 Amps at 24 vacNAOn/OffJ41,3,4
Cooling Stage 2CP2RelayOption24 vac, 2.5 Amps at 24 vacNAOn/OffJ42,3,4
Power Exhaust 2/
Cooling Stage 3*
Power Exhaust 1/
Cooling Stage 4†
DISPLAY
Setpoint Switch 1SP1DigitalStandardOpen/ClosedLogicOpen/ClosedOn BoardNA
Setpoint Switch 2SP2DigitalStandardOpen/ClosedLogicOpen/ClosedOn BoardNA
LED 1DS1LED OutputStandardRedLogicOn/OffOn BoardNA
LED 2DS2LED OutputStandardYellowLogicOn/OffOn BoardNA
LED 3DS3LED OutputStandardGreenLogicOn/OffOn BoardNA
LED 4DS4LED OutputStandardGreenLogicOn/OffOn BoardNA
*If there are 3 stages then there can only be 1 stage of power exhaust.
†If there are 4 stages then there will not be power exhaust stages that will be directly controlled.
2
IAQ
MIN10KOption10K to 100K Ohms0 to 100%1%J315,16,17
CP3/
EX2
CP4/
EX1
4-20 mA,
Loop Powered
4-20 mA,
Loop Powered
4-20 mA,
Ext Sourced
RelayOption24 vac, 2.5 Amps at 24 vacNAOn/OffJ45,6
RelayOption24 vac, 2.5 Amps at 24 vacNAOn/OffJ45,7
20 1st Most Recent Error/Reset—18——Used in Setup Mode to Reset Alarms
21 2nd Most Recent Error (read only)—18——Not Displayed in Setup Mode
22 3rd Most Recent Error (read only)—18——Not Displayed in Setup Mode
23 4th Most Recent Error (read only)—18——Not Displayed in Setup Mode
24 5th Most Recent Error (read only)—18——Not Displayed in Setup Mode
DC — Direct Control
IAQ — Indoor Air Quality
LAT — Leaving Air Temperature Compensated Control
VOC — Volatile Organic Compounds
SETUP POINTS
(viewable and adjustable)
LEGENDNOTE: The accessibility of these channels will be as follows:
UNITS
%Item 15 +1%100%15%1%Min Econo Position (occupied mode)
%1%100%5%1%Min Econo Position (unoccupied mode)
F45 F70 F65 F1 FFor Outdoor Changeover
—1411Outdoor Enthalpy Changeover Setpoint
%1%Item 2 +1%5%1%Min IAQ Position for VOC Emissions
PPM/101 PPM/10
PPM/10
MINIMUM
VAL UE
Item 18 +1
PPM/10
MAXIMUM
VAL UE
Item 19 -1
PPM/10
200 PPM/10140 PPM/10 1 PPM/10
READ MODE — All channels will be accessible.
SETUP MODE — Only channels 1-20 will be accessible and 20 will be used to
reset alarms.
1C1 Output—OffOn—Compressor 1
2C2 Output—OffOn—Compressor 2
3C3 Output—OffOn—Compressor 3/Power Exhaust 2
4C4 Output—OffOn—Compressor 4/Power Exhaust 1
5Economizer Damper Output%1 F100 F1%Damper Commanded Position
6Supply Air TemperatureF1 F150 F1 FSupply Air Temperature
7Outdoor Air TemperatureF1 F150 F1 FOutdoor Air Temperature
8Return Air TemperatureF1 F150 F1 FReturn Air Temperature
9Indoor Relative Humidity%1%100%1%Return Air Relative Humidity
10Outdoor Relative Humidity%1%100%1%Outdoor Air Relative Humidity
11Indoor Air QualityPPM1 PPM/10200 PPM/1010 PPM Indoor Air Quality (/10)
12Remote Minimum Position%1%100%1%Remote Minimum Pot Position
13Y1 Status—OpenClose—Thermostat Y1 Status
14Y2 Status—OpenClose—Thermostat Y2 Status
15G Status—OpenClose—Indoor Fan Status
16Occ Status—OpenClose—Remote Occupied Status
NOTE: The accessibility of these channels will be as follows:
READ MODE — All channels will be accessible for reading.
ADJUST MODE — Only channels 1-5 will be accessible.
MANUAL MODE — Only channels 1-5 will be accessible.
—55—
Page 56
After advancing through all the configuration variables in
the Read mode, the controller will then advance through t he
status of the I/O channels. As in the Read mode, there will be
no LEDs on. Push the READ/ADJUST (#1) button and the
yellow LED will flash the “I/O Point” numbe r and the green
LEDs will flash the “I/O Values” in the same manner
described in the Read mode section. See Ta ble 35. At the first
I/O point (Compressor 1 Ou tput), the DS2 LED (Yellow) will
flash with the number of the I/O channel and the DS1 LED
(red) will stop fla shi ng. This will be followed b y the I/O c h annel status. To read the value ag ain, pus h the R EAD/ADJU ST
(#1) button.
To advance to the next channel, push the ADVANCE/
MANUAL (#2) button. If the number of the channel or the
status value is greate r than 4 the controller will co unt out
the increments of 5 at a high flash rate followed by the
remaining digits. The channel number will be counted out
through the DS2 LED (yellow). The status value will be
counted out through the DS3 and DS4 LEDs (green).
If the status value is an analog value then the numeric value
will be displayed by using the DS3 Green LED to display the
tens digit and the DS4 will be used to display the ones digit.
If the channel is a digital output (relay), the DS3 LED (flashing green) will in dicate ON stat us and the DS4 LED (flashing green) will indicate OFF status. If the output is the
economizer control signal then the DS3 LED will be used to
indicate the motor is being driven open, and the DS4 LED
will be used to indicate it is being closed. If the motor i s not
being commanded in either direction then both the DS3 and
DS4 LEDs will be on. The controller will first go through the
output relays, then the economizer motor, and will then fol low with the values currently being read for the analog input
channels as defined in the configuration table. All values are
maintained in memory even during a power loss. To exit
Setup mode, push and hold the READ/ADJUST (#1) and
ADVANCE/MANUAL (#2) buttons for more than 3 seconds.
Setup mode wil l automati cally be exited aft er 10 minu tes of
no activity.
E. Setup Mode
The Setup mode is used to change set points and configuration values.
Enter the Setup mode by pushing and holding the READ/
ADJUST (#1) button 1 for at least 3 seconds until all LEDs
flash once. Then, the yellow LED will come on steady. A user
can only enter the Setup mode from the Run m ode (to get to
Run mode, press buttons both buttons #1 and #2 for at least
3 seconds).
In Setup mode, all configurations can be modifi ed e ven w hil e
the unit is running, but the use r will not be able to adjus t the
I/O channels . O nly c ha nne ls 1 th roug h 20 on Table 34 will b e
accessible in the Setup mode. Channel 20 will be used to
reset any alarms that may have occurred. As an option,
alarms can also be reset by cycling power to the cont roller.
NOTE: During the Se tup mode, all routines including safety
routines will co ntinu e to ru n a nd c ontr ol the uni t.
While in this mode, the DS1 LED (red) will flash to indicate
the number of the configuration item. The DS2 LED (yellow)
will be on continuousl y to i ndi cate tha t the uni t is i n c on figuration mode. Use the ADVANCE/MANUAL button to
sequence through the setup channels. If the value of the
channel is less than 5 it will count out the value of the channel on the DS1 LED at 1-second intervals. If the channel
value is 5 or great er, the DS1 LED will first c ount out the
groups of 5 and then following with the remaining digit.
Verify what Setup Point is being read by pushing the READ/
ADJUST button (#1). First the Red LED will flash the set
point number, then the Green LEDs will flash the value.
Then, the green DS3 and DS4 LEDs will each come on
steady for about 2 seconds. While DS3 is on steady, its new
value can be entered by pushing READ/ADJUST (#1), and
entering the value for the ten’s digit. When the DS4 comes
on steady, enter the value for th e one's d igit. Afte r the green
LEDs are off, push the READ/ADJUST button (#1) again to
verify that the correct value has been entered. If the configuration is a discrete On/off setting, push the READ/ADJUST
button (#1) to toggle LED 3 or 4 on or off.
Setup Example 1: Change “Occupied Minimum Position”
(configuration item 2) to 53%.
1. Read the General Notes about reading and entering
values found on the label on the top of the
EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at
least 3 seconds until all LEDs flash. The yellow LED
will go on steady.
3. Read the current configuration point by pushing button #1. The red LED flashes the configuration point
number and the green LEDs flash the current setting
for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2
and Note 1 for Setup mode operation.
5. Use button #2 (ADVANCE/MANUAL) to advance to
configuration point number 2, Occupied Min.
NOTE: Before performing Step 6, be ready to push button #1;
there is a limited time window that can easily be missed when
the DS3 green LED comes on, and agai n when the DS4 green
LED comes on.
6. Verify the configuration point by pushing button #1.
The red LED should flash twice to indic ate point 2,
and then the green LEDs will flash the current setting.
7. Next, the green DS3 LED wil l turn on steady for 2
seconds. During this time, push button #1 five times.
8. The DS3 LED wi ll turn off and the gree n DS4 LED
will go on steady for 2 seconds. During this time,
push button #1 three times.
9. The 5 button #1 pushes, followed by the 3 button #1
pushes is the sequ ence that sets the occupied mini mum position to 53%.
10. Wait until the green LEDs turn off then verify the
setting by pushing button #1 to read the value. There
should be 5 fast blinks of DS3 and 3 slow blinks of
DS4.
Setup Example 2: Change the Occupied Minimum Position
(item 2) to 2% (lowest value).
1. Read the General Notes about reading and entering
values found on the label on the top of the
EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at
least 3 seconds until all LEDs flash. The yellow LED
will go on steady.
3. Read the current configuration point by pushing button #1. The red LED flashes the configuration point
number and the green LEDs flash the current setting
for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2
and Note 1 for Setup mode operation.
—56—
Page 57
5. Use button #2 (ADVANCE/MANUAL) to advance to
configuration point number 2, Occupied Min.
6. Verify the configuration point by pushing button #1.
The red LED should flash twice to indicate point 2,
and then the green LEDs will flash the current setting.
NOTE: Since the occupied minimum position MUST be 1
greater than the IAQ minimum position (item 15), the IAQ
minimum position must be changed first. (IAQ min has a
default value of 5%, whi ch is higher tha n the 2% value i n this
example.)
7. Use button #2 (ADV ANCE/MANUAL) to get to configuration point 15 (IAQ Minimum Position).
NOTE: Before performing Step 8, be read y to pus h button #1;
there is a limited time window that can easily be missed when
the DS3 green LED comes on, and again wh en the DS4 green
LED comes on.
8. Verify the configuration point by pushing button #1.
The red LED should flash 15 times to indicate point
15, then the green LEDs will flash the current
setting.
9. Next, the green DS3 LED will turn on steady for
2 seconds. During this time, do NOT do anything so
that the position defaults to 0.
10. The DS3 LED will turn off an d the green DS4 LED
will go on steady for 2 seconds. During this time,
push button #1 once to set the point to 1%.
11. Wait until the green LEDs turn off then verify the
setting by pushing button #1 to read the value. DS3
should not blink, and DS4 should blink once.
12. Now configure the Occupied Minimum Position to
2%. Use button #2 (ADVANCE/MANUAL) to get to
configuration point 2.
NOTE: Before performing Step 13, be ready to push button #1;
there is a limited time window that can easily be missed when
the DS3 green LED comes on, and again wh en the DS4 green
LED comes on.
13. Verify the configuration point by pushing button #1.
The red LED should flash twice to indicate point 2,
then the green LEDs will flash the current setting.
14. Next, the green DS3 LED will turn on steady for
2 seconds. During this time, do NOT do anything so
that the position goes to 0.
15. The DS3 LED will turn off an d the green DS4 LED
will go on steady for 2 seconds. During this time,
push button #1 twice to set the point to 2%.
16. Wait until the green LEDs turn off then verify the
setting by pushing button #1 to read the value. DS3
should not blink, and DS4 should blink twice.
NOTE: Configuration items 2, 15, 11, 12, 18 and 19 (in
Tabl e 34) are dependent upon other items . Before attempting
to change one of these items, be sure to check the value of the
item it depends upon (as described in Example 2 above).
IMPORTANT: During SETUP MODE, changes are allowed
when the DS3 LED and DS4 LED are lit for 2 seconds (as
described in Example 1 and 2 above). During this time, if
button #1 is pushed to change one position and not the other,
the value for that one position will change and the oth er will
default to zero (unless a dependency prevents the zero). However, if button #1 is not pushed at all during the 2 seconds
that the green LEDs are lit, the configuration item will not
change.
F. Manual Mode
Manual mode is used to contr ol the status of I/O channels for
use in troubleshooting. See Table 35.
Enter the Manual mode by holding down the ADVANCE/
MANUAL (#2) button for at least 3 seconds until all LEDs
flash and then the red LED comes on steady.
NOTE: A user can only enter the M anual mode from the Run
mode, which is entered by pushing buttons #1 and #2 for at
least 3 seconds.
All EconoMi$er+ c ontrol output s are tu rned off. “I/O Inputs”
1-5 can be adjusted even if the unit is in operation.
In manual mode, the yellow DS2 LED flashes once to indicate
the I/O channel. See Table 35. If the value is less than 5, the
yellow DS2 LED will count out the value using 1-second
flashes. If the value is greater than 4, the yellow DS2 LED
will count out groups of 5 at a high flash rate and then follow
with the additional value at a flash rate of once per second.
For example a flash of 1 indicates Compressor Relay Output 1.
Push READ/ADJUST button (#1) to read the value. The yellow LED will flash the I/O Ch annel number being viewed.
Once the channel number is displayed it will then turn on
the appropriate green LED (DS3 or DS4) to i ndicate the status of the output. For relay outputs i f the DS3 LED is on,
then the output is on. If DS4 is on, then the output is off. The
green DS3 and DS4 LEDs will remain on for about 2 seconds
and if during this time the READ/ADJUST (#1) button is
pushed, then the output will toggle to the alternate state. To
change again, push the READ/ADJUST button and re peat
the test or change the status of the output. As an example,
for channel 5 (EconoMi$er+ control damper motor) use the
READ/ADJUST button to toggle the motor from open to
close in %.
At any time, the ADVANCE/MANUAL (#2) button can be
used to advance to the next SET I/ O. To exit the mode, push
and hold the READ/ADJUST and ADVANCE/MANUAL buttons (#1 and #2) for more than 3 seconds.
NOTE: After exiti ng the Manual mode, the controller will reinitialize and start with all outputs off.
G. Error Mode
The error mode is used to indicate that an error has occurred
The error is indicated by LED #1 red and #2 yellow are on
steady.
Enter the RUN mode by pushing the READ/ADJUST and
ADVANCE/MANUAL buttons (#1 and #2) for at least 3 seconds until all LEDs flash. Next, push and release button #1
to enter the Read mode. Then push button #2 to advance to
item 20 (“first most recent error”). Determine the e rror by
reading the value in items 20 to 24 and referring to the Troubleshooting sect io n.
Once the error has b een fixed, pres s buttons #1 and 2 for at
least 3 second s to exit Read mode. All LEDs will flash.
Enter Setup mode by pressing the READ/ADJUST button
(#1) for at least 3 seconds. All LEDs will flash. Push the
ADVANCE/MANUAL button (#2) to advance to item 20.
Push READ/ADJUST to read item 20.
To reset the error code while the green DS4 LED is on, press
the READ/ADJUST button (#1) once. In addition to resetting
the error mode, this will er ase all error codes. Cycling the
power will also erase the error code.
—57—
Page 58
XVII. ECONOMI$ER+ CONFIGURATION
For most applications, the factory setting will be used to control the EconoMi$er+. How ever, there are 19 differe nt variables that can be used to co nfig ure the control for wide r a nge
of applications. The factory settings and variables are shown
in Table 34.
IMPORTANT:
There is no way to reset/restore the factory
default configurations; use caution when making changes to
any set point or operational variable.
The EconoMi$er+ control accepts an occupied/unoccupied
switch input. This input is used to control the occupied and
unoccupied minimum ventilation damper position as shown in
Table 34 items 2 (ECONOMIN_SP) and 3 (U_ECONOMIN_SP).
These values represent the minimum damper position. In addition, the controls allows for different modes of compressor operation in the unoccupied mode. Using item 13 in Table 34
(OCC_MODE), the user can select one of the following unoccupied modes:
• No unoccupied cooling
• Unoccupied free cooling (EconoM i$er+)
• Unoccupied free cooling and mechanical cooling
The EconoMi$er+ will control the cooling operation of the
unit based on the demand from the thermostat outpu ts Y1
and Y2. The EconoMi$er+ will monitor the fan output G, but
will not control the fan directly. Note that G must be energized for any cooling to take place. Gas or electric heating
will be controlled dire ctly from the thermostat.
When a demand for coo ling occurs, the control will check to
see if it is in the occupied or un occupied mode. Depen ding on
the configuration, the control will move the outdoor air
damper to the vent ilation position . If the outdoor a ir conditions are acceptable, then the control will use the
EconoMi$er+ for free c ooling. If the supply-air temper ature
does not meet the configurable set point, then the control
will turn on additional stages of mechanical cooling. Several
compressor sequences can be used depending on the application requiremen ts; these will be covered in t he mechanical
compressor staging section.
A. Compressor Configuration And Control
The EconoMi$er+ control can support fro m 1 to 4 compressor stages. For the 3 to 12
2 stages of compressor cooling, so the control is factory
configured for 2 stages. There is no difference between 1 and
2 stages. The control also provides the option to configure for
high sensible o r hi gh latent loads , but for units with o nl y t wo
compressors this option does not apply.
Compressors are co nfigured using item 10 (STAGE_TYPE)
in Table 34. The control also has the capability of controlling
directly to Y1 and Y2 inputs. The contr ol can be configured
to control to the leaving-air temperature using Y1 and Y2 as
a low cool and high cool demand based on the supply air set
point and the rate of change of supply-air temperature. For
low cool the leaving air temperature set point will be
SAT_SP +2° F. For high cool the leaving air temperatur e set
point will be the supply-air temperature set point (SAT_SP).
To use this option, configure the compressor sequencing variable (STAGE_ TYPE ) to a valu e of 3. Con figur e the supply air
temperature set point (SAT_SP) to the desired leaving air
temperature.
NOTE: The supply air temperature s et point is also the temperature used for EconoMi$er+ control.
The logic will control the operation of the compressors
depending on the configuration selected. If free cooling can
be used, then the compressors will be integrated with the
EconoMi$er+ to provide the lowest cost cooling control. The
1
/2 ton units, there will only be 1 or
logic includes time guards on the compr essors to provide a
minimum of 3 minutes on and 3 minut es off time. T he control will also prevent two compress ors from starting at the
same time. The logic uses th e Econo Mi$er+ to pre vent r apid
cycling of the compressors and l ow air temperatures.
B. Ventilation Air And Free Cooling
In order for the EconoMi $er+ to control ventilation air and
free cooling, several items must be configured.
EconoMi$er+ Type
First, select the EconoMi$e r+ control type that will be used.
This is the EconoMi$er+ Type function (ECONO_TYPE)
defined by item 5 in Table 34. The choices are:
1. Vent only — This is used to have just ventilation control. The EconoMi$er+ will not provide free cooling,
but the occupied and unoccupied minimum positions
can be used.
2. Proportional — In this configuration, full proportional EconoMi$er+ control will be used. When
EconoMi$er+ free cooling cannot be used, the dampers will be set to the appropr iat e occ upie d and unoc cupied minimum positions.
3. Three-Position — This mode of EconoMi$er+ is used
to provide a mini mum venti lation Ec onoMi$e r+ position and a fixed free cooling or high ventil ation position. The high ventilation position is controlled by the
optional Remote EconoMi$er+ Enable Switch Input
connected to terminals 11 and 12 on T3.
Supply Air Temperature Set Point
Once the type of Econ oMi$e r+ cont rol ha s been selecte d, the
user will need to set the Supply Air Temperature set point
(SAT_SP). The SAT_SP has a range of 40 to 65 F.
NOTE: This will be the set point when both Y1 and Y2 are
closed. When just Y1 is closed, the set point will be ° F higher.
Minimum Damp er Position
Set the occupied mi nimum damper position (E CONOMIN _SP)
and unoccupied minimum position (U_ECONOMIN_SP).
These should be set t o pr ov ide the ventilation requirements at
full occupancy as defined by the building specifications. When
demand ventilation is used, the control will close the dampers
below this position based on measur ed CO
to provide additional operation savings.
The control wil l also a llow for the use o f a remo te mini mum
position potentiometer. This will only adjust the Occupied
Minimum position. If used, the software set point
ECONOMIN_SP sho uld be se t to 0 as the contr ol wi ll use the
largest set point.
The damper position is not linear with the amount of outside
air, so the user will need to set the position of the
EconoMi$er + acco rdi ngly. It is best to use the fo llow ing equ ation and measured data to set the position:
SAT – RAT
OA =
OAT – RAT
OA = % outdoor air
SAT = supply air temperature
RAT = return air temperature
OAT = outdoor air temperature
The SAT and OAT val ues can be read from the control and, if
the unit is equipped with an RAT sensor, then all three
values can be read. For the calculation to work properly,
there should be at least a 10° F difference between the OAT
and RAT temperatures.
*100
levels in the space
2
—58—
Page 59
Maximum Damper Position
Set the maximum EconoMi$er+ position. Normally this is
set at 100%. If using 3-position control or there is a reason
not to use 100% outside air, this can be set using the
EconoMi$er+ Maximum Position (MAX_POS_SP).
Compressor Lockout Temperature
Set the Compressor Lockout Temperature. The Compressor
Lockout Temperature (CMP_LOCK) is used to prevent compressor from running at low ambient conditions when an
EconoMi$er+ can easily satisfy the load.
EconoMi$er+ Changeover Control
Determine the type of EconoMi$er+ changeover control
which will be used to enable and disable free cooling. This is
done using the EconoMi$er+ Changeover Type.
1. Switch — This changeover setting is used when a
remote signal from an energy management system
will enable and disable the EconoMi$er+. This is
done through a remote EconoMi$er+ enable switch.
2. Outdoor Dry Bulb — For this changeover setting, the
EconoMi$er+ w ill be en abled b ase d on the ou tdo or-air
temperature. The EconoMi$er+ is shipped with an
outdoor air temperature sensor. The outdoor air temperature set point can be configured by th e user. The
EconoMi$er+ will be disabled when the outdoor-air
temperature rises above the set po int. The co nfiguration variable is the EconoMi$er+ Changeover set
point (OAT_SP).
3. Differentia l Dry Bulb — For this changeover setting,
the EconoMi$er+ will be en abled whenever the outside-air temperature is lower than the return-air
temperature. No configuration of set points is
required other than to sel ect the differe nt ial dry bu lb
function.
4. Outdoor Enthalpy — For this changeover setting, the
control will enable the EconoMi$er+ based on the
outdoor-air enthalpy curves as shown in Fig. 29.
Using the EconoMi$er+ Changeover set point
(ENTHALPY_SP), select curves A, B, C or D. The
control will then use the EconoMi$er+ at conditions
below the curve. The control uses the OAT and
optional humidity sensor to calculate the enthalpy
and also has the A, B, C, and D curves stored in
memory.
5. Differential Enthalpy — For this changeover setting,
the EconoMi$er+ will be enabled based o n the comparison of the enthalp y of the return air and outs ide
air. If the outside air enthalpy is lower than the
return air, then the EconoMi$er+ will be enabled. To
use this option, an accessory outside air humidity
sensor, a return air dry bulb sensor and a return air
humidity sensor must be ordered and installed. No
configuratio n of set points is required other th an to
select the function.
C. Demand Ventilation Configuration
The EconoMi$er+ control has demand ventilation control
capability when using an IAQ sen sor. The indoor air qualit y
(IAQ) is measured using a CO
sensor. The IAQ sensor can
2
be field-installed in the return duct or the occupied space.
The EconoMi$er+ control algorithm modulates the po sition
of the EconoMi$er+ damper between two user configurations
depending upon the relationship between the IAQ and the
Outdoor Air Quality (OAQ). The lower of these two positions
is referred to as the Min imum IAQ Min imum EconoM i$er+
Position (IAQMIN_SP).
The higher position is referred to as the Occupied EconoMi$er+
Minimum Position (ECONOMIN_SP). The IAQMIN_SP should
be set to an EconoMi$er+ position that brings in enough fresh
air to remove contaminants and CO
generated by sources
2
other than people. The ECONOMIN_SP should be set to an
EconoMi$er+ position that brings in enough fresh air to remove
contaminants and CO
generated by all sources including peo-
2
ple at the design value for maximum occupancy.
A reference differential CO
level above the outside CO
2
level is used as the starting point for IAQ control and
another reference differential level for maximum ventilation
at design occupancy is used for the end of IAQ control.
Between these points the control wi ll modulate the da mpers
open from the IAQMIN_SP and the ECONOMIN_SP setpoints. The damper position will never go above
ECONOMIN_SP or below IAQMIN_SP.
The control does not measure the outdoor IAQ reference
level as these levels are relatively constant. The installer
should take a measurement at start-up of the unit and enter
this value into the control using the Outdoor Air IAQ reference level configuration.
The control is configured for air quality sensors which provide 4 mA at 0 ppm and 20 mA at 2000 ppm. If a sensor has
a different range, these bounds must be reconfigured.
To configure the control for an IAQ sensor perform the following steps:
1. Determine the Occupied EconoMi$er+ Minimum position (ECONOMIN_SP) and enter it into the control.
2. Determine the IAQ minimum EconoMi$er+ position
(IAQMIN_SP) and enter it into the control.
3. Enable IAQ control using IAQ Enable (IAQ_FL G ).
4. Determine the Outdoor Air IAQ Reference (OAQ) and
enter it into the control.
NOTE: The value entered into the control will be the CO
ppm level divided by 10. For example, 400 ppm would be
entered as 40.
5. Determine the lower control point differential level
(DAQLO) and enter it i nto the control. This is a differential level so if the desired level to start IAQ control is 500 ppm and the OAQ reference level is 400
then a value of 100 would be used.
NOTE: The value entered into the control will be the CO
ppm level divided by 10. For example 100 ppm would be
entered as 10.
6. Determine the upper control point differential level
(DAQHI) and enter it into the control. This is a differential level so if the desired leve l to star t IAQ co ntrol
is 1100 ppm and the OAQ reference level is 400 then
a value of 700 would be used.
NOTE: The value entered into the control will be the CO
ppm level divided by 10. For example 700 ppm would be
entered as 70.
D. Power Exhaust Configuration
The EconoMi$er+ can control up to 2 stages of power
exhaust. Power exhaust activation is done through configurable damper pos ition set points. The first stage of power is
controlled by relay C4 on the EconoMi$er+ board. The activation point for the first stage is set using the Power
Exhaust Stage 1 Activation set point (PE_SP1 ). The second
stage of powe r exhaust mus t be set at a v alue greater than
the first stage. It is configured using the Power Exhaust
Stage 2 Activation set point (PE_SP2).
2
2
2
2
—59—
Page 60
XVIII. OPERATING SEQUENCE
A. Cooling, Units Without EconoMi$er+
When thermostat calls for cooling, terminals G and Y1 and
the compressor contactor (C) are energized. The indoor (evaporator) fan motor (IFM), compressor, and outdoor (condenser)
fan motor (OFM) start. The OFM runs continuously while the
unit is in cooling. When the thermostat is satisfied, C is deenergized and the compressor and OFM shut off. After a
30-second delay, the (IFM) shuts off. If the thermostat fan
selector switch is in the ON position, the evaporator motor
will run continuously.
B. Heating, Units Without EconoMi$er+
When the thermostat call s for heatin g, terminal W1 is energized. The induced-draft motor is energized and the burner
ignition seque nce begins. The indoor (evaporator) fan m otor
(IFM) is energized 45 seconds after a flame is ignited. When
additional he at is n eeded, W 2 is en ergized and t he high- fire
solenoid on the main gas valve (MGV) is energized. When
the thermostat is sati sfied and W1 is deenergiz ed, the IFM
stops after a 45-second time-off delay.
C. Cooling, Units With EconoMi$er+
For EconoMi$er+ operation, there must be a thermostat call
for the fan (G). This will move the damper to its minimum
position.
When the EconoMi$er+ control is the occupied m ode and a
call for cooling exists (Y1 on the thermostat), the control will
first check for indoor fan operat ion. If the fan is not on, th en
cooling will not be activated. If the fan is on, then the control
will open the EconoMi$er+ damper to the minimum position.
On the initial p ower to the EconoMi$er+ board, it will ta ke
the damper up to 2
1
/2 minutes before it begins to position
itself. With subsequent fan signal (G) to the board, the
change in damper position will take up to 30 seconds to initiate. Damper movement from full closed to full open (or vice
versa) will take 2
1
/2 minutes.
If the damper is in the process of a change (for example going
to 100% open) and the signal (G) is turn ed off, the damper
will continue to open to 100% before it closes (due to no fan
signal [G]).
If free cooling c an be used as determin ed from the appr opriate changeover command (switch, dry b ulb, enthalpy curv e,
differential dry bulb, or differential enthalpy), then the control will modulate the dampers open to main the supply air
temperature set point plus 2° F.
If there is a further demand for cooli ng (coo li ng secon d st age
— Y2 is energized), then the control set point for the l eaving
air will be set at the supply air set point to increase the cooling capacity. If this cannot satisfy the load then the control
will bring on comp ressor stages as needed to maintain the
supply air temperatu re set point. The EconoM i$er+ damper
will be locked o pen at 100% or the maximu m damper position set point.
To ensure that there is oil return, the compressors will operate for at least 3 minutes. If, during this period, the leaving
temperature drops below the set point by 5° F, then the
EconoMi$er+ dampers will be closed to 60% until the compressor is turned off to avoid cold leaving air temperatures.
If the conditions are not suitable for free cooling then the
EconoMi$er+ dampers will be closed to the minimum ventilation posit ion.
Compressor stage s will be used to co ol the air. If the control
is configured for direct control by Y1 and Y2, then the stages
will sequence based on the demand of Y1 and Y2. If the
control is configured for leaving air temperature control,
then Y1 will maintain the leaving air temperature at the
supply air set point plus 2° F. If Y1 and Y2 are closed, then
the leaving air will be c ontrolled t o the supp ly air se t point.
If Y2 is closed and Y1 is open, then control will shut down
and indicate an error due to a thermostat failure or improper
wiring of the thermostat.
If the unit is in the unoccupied m ode, then the control of the
temperature will depend on the unoccupied free cooling configuration: no unoccupied cooling, unoccupied free cooling
with any mechanical cooling, or unoccupied free and
mechanical cooling. If free cooling is enabled, then the control will check if free cooling can be used. The EconoMi$er+
will then control to the leaving air temperature set point
plus 2° F for a Y1 command, or the leaving air temperature
set point for a Y1 and Y2 command. If me chanical coo ling is
allowed to be used, then the control will then bring on additional stages o f me chani cal coo lin g i f f ree co ol in g c annot sa tisfy the load.
If the EconoMi$er+ control:
• is in the occupied mo de
• is configured to use demand ventilation
• cannot use free cooling
• has return air or space CO
levels below the DAQLO
2
limit,
then the EconoMi$er+ damper position will be set to the
IAQMIN_SP set point. If the CO2 level rises above the
DAQLO limit, then the dampers will modulate open in a linear relationship un til the return air o r space CO
levels are
2
at or above th e D AQHI l imit . The da mpe r p o siti on w il l be at
the ECONOMIN_SP set point.
When the EconoMi$er+ is being used for free cooling and the
position exceeds the power ex haust set point, then the control will turn on the appropriate power exhaust fans. Refer to
Fig. 23 for barometric relief capacit y, Fig. 24 for outdoor air
leakage, and Fig. 25 for pressure drop.
Unoccupied and Occupied Minimum Position Control
There is an unoccupied minimum damper position and an
occupied minimum damper position on the EconoMi$er+
controller. When the HVAC fan is off the outdoor air damper
will always be closed. W hen the f an is on an d in the unoccu pied mode, the outdoor air damper will be at the unoccupied
minimum position . When the fan is on (G call ) and in the
occupied mode, the outdoor air damper will be at the occupied minimum position.
A jumper wire is factory-installed to force the unit into o ccupied configurat io n wh ene ver G or Y1 are clos ed. Withou t the
jumper wire, the unit will always be in unoccupied mode.
The 2 minimum position settings are also used in the
IAQ sequence of operation. See Indoor Air Quality Sensor on
page 21.
NOTE: The minimum position signal takes priority over the
maximum position sign al. If th e maxi mum da mper positi on is
set below the minimum damper position, the EconoMi$er+
controller will maintain the actuator at minimum position.
—60—
Page 61
Adjust the unoccupied minimum position to allow the minimum amount of outdoor air, as required by local codes, to
enter the building. Make minimum position adjustments
with at least 10 F (6 C) temperature difference b etween the
outdoor and return air temperatur es.
To determine the unoccupied minimum position setting, perform the following procedure:
Calculate the appr opriate supply-ai r temperature using the
following formula: (TO x OA) + (TR x RA) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Supply-Air Temperature
As an example, if local codes requ ire 10% outdoor air duri ng
occupied conditions, outdoor-air temperature is 60 F, and
return-air temperature is 75 F:
(60 x 0.10) + (75 x 0.90) = 73.5 F
Carefully adjust the unoccupied minimum position until the
measured supply-air temperature matches the calculated
value. Then, carefully adjust the occupied minimum position
set point on the controller until the desired position is
reached.
D. Heating, Units With Economizer+
When the thermostat call s for heatin g, terminal W1 is energized. The induced-draft motor is energized and the burner
ignition seque nce begins. The indoor (evaporator) f an motor
(IFM) is energized 45 seconds after a flame is ignited. When
additional he at is n eeded, W 2 is en ergized and t he high- fire
solenoid on the main gas valve (MGV) is energized. When
the thermostat is satisfied and W1 is deenergized, the
IFM stops after a 45-second time-off delay. The economizer
damper moves to the minimum position. When the thermostat is satisfied, the damper moves to the fully closed
position.
SERVICE
CAUTION: When servicing unit, shut off all elec-
trical power to unit and tag disconnect to avoid shock
hazard or injury from rotating parts.
I. CLEANING
Inspect unit interior at the beginning of each heating and
cooling season or more frequently as operating conditions
require.
A. Evaporator Coil
Clean coil as re quired. Inspect coil at beginning of heating
and cooling seasons.
1. Turn unit power off and install lockout tag. Remove
evaporator coil access panel.
2. If economizer is installed, remove economizer by disconnecting Molex plug and removing economizer
mounting screws. Refer to Accessory Economizer
Installation Instructions or Optional EconoMi$er+
section on page 18 for more detail s.
3. Remove filters from unit.
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister.
Wash both sides of coil and flush with clean water.
For best results, back-flush toward return-air section
to remove foreign material . Caution should be taken
as to not overflow the evaporator drain condensate
pan.
5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
8. Replace access panels.
B. Condenser Coil
Inspect coil month ly. Clean condenser coil annually, and as
required by location an d outdoor-air conditions.
One-Row Coils
Wash coil with commercial cleaner. Clean outer surfaces
with a stiff brush in the no rmal manne r. It is not necessar y
to remove top panel.
2-Row Coils
Clean coil as follows:
1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 37. To
hold top panel open, place coil corner post between
top panel and center post. See Fig. 38.
4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at
return end of condenser coil. Carefu lly separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 39.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil s ections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
7. Secure inner and outer coil rows together with a fieldsupplied fastener.
8. Reposition the outer coil se ction and remove the coil
corner post from between the top panel and center
post.
9. Reinstall the coil corner post and replace all screws.
C. Condensate Drain
Check and clean each year at star t of coo lin g sea so n. I n win ter, keep drain dry or protect against freeze-up.
D. Filters
Clean or rep lace at s tar t of e ach h eati ng an d co oling seas on,
or more often if operating conditions require it. Replacement
filters must be same dimensions as original filters.
Fig. 37 — Cleaning Condenser Coil
—61—
Page 62
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at
the factory.
B. Fan-Motor Bearings
Fan-motor bearings are of the permanently lubricated type.
No further lubrication is required. No lubrication of
condenser-fan or evaporator-fan motors is required.
III. CONDENSER FAN ADJUSTMENT (Fig. 40)
1. Shut off unit power supply and tag disconnect.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 40.
4. Tighten setscrews and replace condenser-fan
assembly.
IV. BLOWER BELT ADJUSTMENT
Inspect blower b elt for we ar, proper belt tension, and pu lley
alignment as conditions require or at the beginning of each
heating and air conditioning season. Refer to Step 9 —
Adjust Evaporator Fan Speed on page 27 for adjustment and
alignment pro ced ures.
V. MANUAL OUTDOOR-AIR DAMPER
If outdoor-air damper blade is required, see Manual
Outdoor-Air Damper section on page 17.
VI. ECONOMIZER ADJUSTMENT
Refer to Optional EconoMi$er+ section on page 18.
VII. CONDENSER COIL GRILLE
Condenser coil grille is shipped factory-installed. No adjustments are required.
VIII. HIGH-PRESSURE SWITCH
Located on the compressor’s hot gas line is a high-pressure
switch. This switch opens at 428 psig and closes at 320 psig.
No adjustment is necessary. Refer to Tables 1A and 1B.
NOTE: Th ere is no Sch rader cor e in the valve be low the hig hpressure switch.
IX. LOSS-OF-CHARGE SWITCH
Located on the condenser’s liquid line is a low-pressure
switch which functions as a loss-of-charge switch. This
switch contains a Schrader core depr es sor. This switch opens
at 7 psig and closes at 22 psig. No adjustment is necessary.
Refer to Tables 1A and 1B.
X. FREEZESTAT
Located on the “hair pin” end of the evaporator coil is a
bimetal temperature sensing switch. This switch protects
the evaporator coil from f reeze-u p due to lack of ai rflow. The
switch opens at 30 F and closes at 45 F. No adjustment is
necessary. Refer to Tables 1A and 1B.
XI. CHECKING AND ADJUSTING REFRIGERANT CHARGE
The refrigerant system is fully charged with R-22 refrigerant, tested, and factory-sealed. Unit must operate in Cooling
mode a minimum of 10 minutes before checking charge.
NOTE: Adjustment of the refrigerant charge is not required
unless the unit is suspected of not having the proper R-22
charge.
A superheat charging chart is attached to the outside of the
service access panel. The chart incl udes the re qui red suction
Fig. 38 — Propping Up Top Panel
Fig. 39 — Separating Coil Sections
580F UNIT VOLTAGEFAN HEIGHT “A” (in.)
208/230 V2.75
460 V and 575 V3.50
Fig. 40 — Condenser-Fan Adjustment
line temperature at given suction line pressures and outdoor
ambient temperatures.
An accurate superheat, thermocouple-type or thermistortype thermometer, and a gage manifold are required when
using the superheat charging method for evaluating the unit
charge. Do not use mercury or small dial-type ther mometers
because they are not adequate for this type o f measu rement.
CAUTION: When evaluating the refrigerant
charge, an indicated adjustment to the specified factory charge mus t al w ays be very minimal. If a substantial adjustment is indicated, an abnormal condition
exists somewhere in the cool ing system , such as in sufficient airflow across either coil or both coils.
—62—
Page 63
Proceed as follows:
1. Remove caps from low-pressure and high-pressure
Schrader valve fit tings.
2. Using hoses with valve core depressors, attach
low- and high-pressure gage hoses to low-pressure
and high-pressure service fittings, respectively.
3. Start unit in Cooling mode and let unit run until system pressure stabilize.
4. Measure and record the following:
a. Outdoor ambient-air temperature (F db).
b. Evaporator inlet-air temperature (F wb).
c. Suction-tube temperature (F) at low-side service
fitting.
d. Suction (low-side) pressure (psig).
5. Using “Cooling Charging Charts” compare outdoorair temperature (F db) with the suction line pressure
(psig) to determine desired system operating suction
line temperature. See Fig. 41-48.
6. Compare measured suction-tube temperature with
desired suction-tube temperature. Using a tolerance
of ± 3° F, add refrigerant if me asured temp eratur e is
more than 3° F higher than proper suction-tube temperature, or remove refrigerant if actua l temper ature
is more than 3° F low er than required s uction-tube
temperature.
A. To Use Cooling Charging Chart
This method is to be use d in Co oling m ode only. Take the outdoor ambient temperature and read the suction pressure
gage. Refer to appropriate chart to determine what suction
temperature should be. If suction temperature is high, add
refrigerant. If suction temp erature is low, carefully recover
CIRCUITS 1 AND 2
Fig. 41 — Cooling Charging Chart; 580F090
some of the charge. Recheck the su ction pressure as charge
is adjusted. Example (Fig. 44, Circuit 2):
To inspect the flue collector box and upper areas of the heat
exchanger:
1. Remove the combustion blower wheel and motor
assembly according to directions in Combustion-Air
Blower section below.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
XIII. COMBUSTION-AIR BLOWER
Clean seasonally to assure proper airflow and heating efficiency. Inspect blower wheel eve ry fall and periodical ly during heating season. For the first heating season, inspect
blower wheel bimonthly to determine proper cleaning
frequency.
To inspect blower wheel, shine a flashlight into draft hood
opening. If cleaning is required, remove motor and wheel as
follows:
1. Slide burner access panel out.
2. Remove the 6 screws that attach induced-draft motor
housing to vestibule plate (Fig. 49).
3. The blower wheel can be cleaned at this point. If
additional cleaning is required, continue with Steps 4
and 5.
4. To remove blower from the motor shaft, remove
2 setscrews.
5. To remove motor, remove the 4 screws that hold
blower housing to mount ing pla te. Remove th e motor
cooling fan by removing one setscrew. Then remove
nuts that hold motor to mounting plate.
6. To reinstall, reverse the pro c edure outlined above.
XIV. LIMIT SWITCH
Remove blower acce ss panel (F i g. 1A an d 1B). Limi t swit ch is
located on the fan deck. Verify operation of limit by te mporarily blocking return air until limit trips.
XV. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in
the control box (Fig. 11). Module contains a self-diagnostic
LED. A single LED on the IGC provides a visual display of
operational or sequential problems when the power supply is
interrupted. When a brea k in power occurs, the modu le will
ROLLOUT
SWITCH
be reset (resulting in a loss of fault history) and the i ndoor
(evaporator) fan ON/OFF times will be reset. For additional
information, refer to the Start-Up, Heating section on
page 51. The LED er ror code can be observed through the
viewport. See Fig. 11. During servicin g refer to the l abel on
the control box cover or Table 36 for an explanation of LED
error code descriptions.
If lockout occurs, unit may be adjusted by interrupting
power supply to unit for at least 5 seconds.
XVI. MAIN BURNERS
At the beginning of each heating season, inspect for deterioration, blockage due to corrosion or other causes. Observe
the main burner flames and replace burners if necessary.
CAUTION: When working on gas train, do not hit
or plug orifice spuds.
A. Removal and Replacement of Gas Train (Fig. 49 and 50)
1. Shut off manual gas valve.
2. Shut off power to unit and install lockout tag.
3. Slide out burner section side panel (not shown).
4. Disconnect gas piping at unit gas valve using backup
wrench on the flats of the valve body where the gas
pipe enters the gas valve. See Fig. 49.
5. Remove wires connected to gas valve. Mark each
wire.
Table 36 — LED Error Code Description*
LED INDICATIONERROR CODE DESCRIPTION
ONNormal Operation
OFFHardware Failure
1Flash†Evaporator Fan On/Off Delay Modified
2FlashesLimit Switch Fault
3FlashesFlame Sense Fault
4Flashes4 Consecutive Limit Switch Faults
5FlashesIgnition Lockout Fault
6FlashesInduced-Draft Motor Fault
7FlashesRollout Switch Fault
8FlashesInternal Control Fault
9FlashesSoftware Lockout
LEGEND
LED — Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in
numerical sequence.
†Indicates a code that is not an error. The unit will continue to operate
when this code is displayed.
IMPORTANT: Refer to Troubleshooting Tables 38-40 for additional
information.
Fig. 49 — Burner Section Details
BURNER
SECTION
FLUE
FLUE
EXHAUST
EXHAUST
VESTIBULE
PLATE
INDUCED-DRAFT
MOTOR
MANIFOLD
PRESSURE TAP
GA S VA LVE
GA S VA LVE
FLATS
Fig. 50 — Burner Tray Details
—67—
Page 68
6. Remove wires from ignitor and sensor wires at the
Integrated Gas Unit Controller (IGC).
7. Remove the 2 screws that attach the burner rack to
the vestibule plate.
8. Slide the burner tray out of the unit (Fig. 50).
9. To reinstall, reverse the procedure outlined above.
B. Cleaning and Adjustment
1. Remove burner rack from unit as described in
Removal and Replacement of Gas Train section,
above.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cro ss-over port
as required.
4. Adjust spark gap. See Fig. 51.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and
Replacement of Gas Train section, this page.
XVII. REPLACEMENT PARTS
A complete list of repl acement parts may be obtained from
any Bryant distributor upon request.
580F090,091,102,103
125,000 BTUH INPUT
NOTE: Dimensions in ( ) are millimeters.
580F090,091,102,103,120,121
180,000 BTUH INPUT
580F090,091,102,103,120,121,150,151
220,000 BTUH INPUT AND 580F120,121,150,151
250,000 BTUH INPUT
Fig. 51 — Spark Gap Adjustment
—68—
Page 69
TROUBLESHOOTING
I. ECONOMI$ER+ TROUBLESHOOTING
The EconoMi$er+ control has built-in diagnostics. The control can detect and display 10 different diagnostic codes as
shown in Table 37. The us er ca n al so us e the integra ted display to check the status of all the inputs and outputs and run
the manual control mode to check the operation of the
EconoMi$er+ and compressors.
Table 37 — EconoMi$er+ Error Codes
NO.DESCRIPTIONCRITERIA
1 SAT Sensor FailureTemperature <–40 F or Greater Than 250 F
2 RAT Sensor FailureTemperature <–40 F or Greater Than 250 F
3 OAT Sensor FailureTemperature <–40 F or Greater Than 250 F
4 ORH Sensor FailureRead Less Than 2 mA or Greater Than 22 mA
5 IRH Sensor FailureRead Less Than 2 mA or Greater Than 22 mA
6 IAQ Sensor FailureRead Less Than 2 mA or Greater Than 22 mA
7 Y2OnY1 OffWiring Error
8 Micro Fails E2 TestsHardware/Software Check
* Micro Fails RAM TestHardware/Software Check
† Micro Fails ROM Tests Hardware/Software Check
IAQ — Indoor Air Quality
IRH — Indoor Relative Humidity
OAT — Outdoor Air Temperature
ORH — Outdoor Relative Humidity
RAT — Return Air Temperature
SAT — Supply Air Temperature
*If there is a RAM failure DS1+DS3/DS2+DS4 will alternately flash.
†If there is a ROM failure DS1+DS2/DS3+DS4 will alternately flash.
LEGEND
A. Error Code 1 — SAT Sensor Failure
Error Criteria
An SAT Sensor Failure error will occur if the sensor is
shorted or faulty. If the measured temperature reads below
–40 F or above 250 F an error will occur.
Required Action
If an error occurs, then the control will default to Mode 2
compressor stage contro l where Y1 and Y2 have direct control of the compressors. Use of free cooling is disabled and
the EconoMi$er+ will be set to the minimum damper position for either the occupied or unoccupied mode of operation.
Replace sensor if faulty.
Reset Method
The error will automatically reset after the value has
returned to a normal level. The alarm h as to be cleared from
the display in the Setup mode or a power reset.
B. Error Code 2 — RAT Sensor Failure
Error Criteria
The RAT Sensor failure error is only applicable the unit has
been configured for EconoMi$er+ changeover methods 3 (differential dry bulb) or 5 (differential humidity). For other
modes it should be ignored. If the sensor is shorted or faulty,
then the measured tempe r atur e w ill be below –40 F or abo v e
250 F and the error will occur.
Required Action
If this error occurs, then change the default EconoMi$er+
changeover control to method 2 (dry bulb changeover control) or replace sensor.
Reset Method
This error will automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Se tup mode.
C. Error Code 3 — OAT Sensor Failure
Error Criteria
An OAT Sensor Failure error occurs if the sensor is short ed
or faulty, then the measured temperature will be below –40
F or above 250 F.
Required Action
— If this error occurs disable the economizer and set the
economizer to the minimum economizer position.
Reset Method
This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.
Error Criteria
This error occurs if th e unit is configured for EconoMi$er+
changeover type 5 and the input signal is less than 2 mA or
greater than 22 mA (faulty sensor).
Required Action
If this error occurs, switch the EconoMi$ er+ to differential
dry bulb changeover control.
Reset Method
This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.
F. Error Code 6 — IAQ Sensor Failure
Error Criteria
This error occurs if th e unit is configured for IAQ demand
ventilation control and the input signal is less than 2 mA or
greater than 22 mA (faulty sensor).
Required Action
If this error occurs, disable the IAQ control routine and
default to the standard EconoMi$er+ minimum position.
Reset Method
This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.
G. Error Code 7 — Y2 On with Y1 Off
Error Criteria
This error occurs if Y 2 is turned on and Y1 is of f. This indi-
cates that there is a wiring error at the thermostat connections. This alarm sho uld be ignored fo r the first 20 sec onds of
operation so tha t it does no t co nfl ic t wit h th e sp ec ial pr odu ction test mode.
—69—
Page 70
Required Action
Shut the unit off and chec k wiring.
Reset Method
This error must be manu ally reset and re quires a power reset .
H. Error Code 8 — E2 Test Failure
Error Criteria
This error occurs if internal hardware detects an E2 failure.
Required Action
Shut the un it off.
Reset Method
This error must be manually reset and requires a power reset.
I. Error Mode
When an error occurs, the red and yellow LEDs both come on
steady. To determine the error, follow these steps:
1. Enter the Run mode by pushing buttons #1 and #2 for
at least 3 seconds until all LEDs flash.
2. Press and release the #1 button to enter the Read
mode.
3. Push the ADVANCE/MANUAL (#2) button to
advance to item number 20, “1st Most Recent Error.”
Determine the error(s) by reading the values in items
20-24 and referring to the error codes described above.
4. Fix the error(s).
5. Press buttons 1 and 2 to exit read mode. Enter Setup
mode by pressing button #1 for at least 3 seconds
until all the LEDs flash.
6. Push button #2 to advance to item number 20.
7. To reset t he error cod e while the green D S4 LEDS is ON ,
press the READ/ADJUST ( #1) button once. This res ets
the error mode and erases all repaired error codes.
NOTE: Cycling power to the board will also erase the repaired
error codes.
J. RAM Test Failure
Error Criteria
If internal hardware detects a RAM failure, this alarm will be
displayed by alternately flashing DS1+DS3 and DS2+DS4.
Required Action
Shut the unit off.
Reset Method
This error must be manually reset and requires a power
reset.
K. ROM Test Failure
Error Criteria
If internal hardware detects a ROM failure, the alarm is dis-
played by alternately flashing DS1+DS2 and DS3+DS4.
Required Action
Shut the unit off.
Reset Method
This error must be manually reset and requires a power
reset.
L. Unit Always In Unoccupied Mode
A jumper wire is factory-installed to force the unit into o ccupied configurat io n wh ene ver G or Y1 are clos ed. Withou t the
jumper wire, the unit will always be in unoccupied mode.
Check the wire. An occupied/unoccupied switch may be
installed in pl ace of the j ump er. Ch eck the wi ring and se tting
of the switch.
self to dissipate any electrical charge that may be present before handling
new control board. The IGC is sensitive to static electricity and may be
damaged if the necessary precautions are not taken.
SYMPTOMCAUSEREMEDY
Loss of power to control module (IGC).Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat
exchanger warm-up period
before fan-on delay expires.
Limit switch opens within three
minutes after blower-off delay
timing in Heating mode.
High temperature limit switch is open.Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that
should not be present.
Inadequate airflow to unit.Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted
ignition for 15 minutes.
IGC does not sense that
induced-draft motor is operating.
Rollout switch has opened.Rollout switch will automatically reset, but IGC will continue to lock
Microprocessor has sensed an
error in the software or hardware.
Electrical interference is impeding the IGC
software
CAUTION: If the IGC must be replaced, be sure to ground your-
transformer. Units without a 24-v circuit breaker have an internal
overload in the 24-v transformer. If the overload trips, allow
10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure unit’s external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with the range on the
unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly terminated.
Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection. Proper
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
out unit. Check gas valve operation. Ensure that induced-draft blower
wheel is properly secured to motor shaft. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
Reset 24-v to control board or turn the thermostat off and on. Fault will automatically
reset itself in one hour.
IMPORTANT: Refer to Heating troubleshooting chart for additional troubleshoot-
ing analysis.
IGC — Integrated Gas Unit Controller
LED — Light-Emitting Diode
LEGEND
—70—
Page 71
Table 39 — Cooling Service Troubleshooting
PROBLEMCAUSEREMEDY
Compressor and
Condenser Fan
Will Not Start.
Compressor Will Not Start
But Condenser Fan Runs.
Compressor cCycles (Other than
Normally Satisfying Thermostat).
Compressor Makes Excessive Noise
(580F103,121,150, and 151 Scroll
Only).
Compressor Operates Continuously.Dirty air filter.Replace filter.
Excessive Head Pressure.Dirty air filter.Replace filter.
Head Pressure Too Low.Low refrigerant charge.Check for leaks, repair, and recharge.
Excessive Suction Pressure.High heat load.Check for source and eliminate.
Suction Pressure Too Low.Dirty air filter.Replace filter.
Compressor No. 2 Will Not Run.Unit in economizer mode.Proper operation; no remedy necessary.
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
Faulty wiring or loose connections in com-
pressor circuit.
Compressor motor burned out, seized, or
internal overload open.
Defective run/start capacitor, overload, or
start relay.
One leg of 3-phase power dead.Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and recharge
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or
start relay.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Compressor rotating in wrong direction.Reverse the 3-phase power leads as described on
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak, repair, and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Remove excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and
Condenser air restricted or air short-cycling.Determine cause and correct.
Compressor valves leaking.Replace compressor.
Restriction in liquid tube.Remove restriction.
Low refrigerant charge.Check for leaks, repair, and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if nec-
Temperature too low in conditioned area.Reset thermostat.
Field-installed filter drier restricted.Replace.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
to nameplate.
Determine cause and replace.
page 50.
recharge.
recharge.
essary.
—71—
Page 72
Table 40 — Heating Service Troubleshooting
PROBLEMCAUSEREMEDY
Burners Will Not
Ignite.
Inadequate Heating.Dirty air filter.Clean or replace filter as necessary.
Poor Flame
Characteristics.
Burners Will NotUnit is locked into Heating mode for aWait until mandatory one minute time period has
Turn Off.one minute minimum.elapsed or power to unit.
Misaligned spark electrodes.Check flame ignition and sensor electrode positioning.
No gas at main burners.Check gas line for air purge as necessary. After purging
Water in gas line.Drain water and install drip leg to trap water.
No power to furnace.Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.Check transformer. Transformers with internal overcurrent
Miswired or loose connections.Check all wiring and wirenut connections.
Burned-out heat anticipator in thermostat.Replace thermostat.
Broken thermostat wires.Run continuity check. Replace wires, if necessary.
Gas input to unit too low.Check gas pressure at manifold. Clock gas meter for input. If too
Unit undersized for application.Replace with proper unit or add additional unit.
Restricted airflow.Clean filter, replace filter, or remove any restrictions.
Blower speed too low.Use high speed tap, increase fan speed, or install
Limit switch cycles main burners.Check rotation of blower, thermostat heat anticipator settings,
Too much outdoor air.Adjust minimum position.
Incomplete combustion (lack ofCheck all screws around flue outlets and burner
combustion air) results in:compartment. Tighten as necessary.
Aldehyde odors, CO, sooting flame, or floating
flame.
Adjust as needed.
gas line of air, allow gas to dissipate for at least 5 minutes before attempting to relight unit.
Check gas valve.
protection require a cool down period before resetting.
low, increase manifold pressure, or replace with correct orifices.
optional blower, as suitable for individual units.
and temperature rise of unit. Adjust as needed.
Check economizer operation.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
—72—
Page 73
C—Contactor, Compressor
CB— Circuit Breaker
COMP — Compressor Motor
EQUIP — Equi pment
FPT— Freeze Up Protection Thermostat
GND — Ground
HPS— High-Pressure Switch
HS— Hall-Effect Sensor
I—Ignitor
IDM— Induced-Draft Motor
IFC— Indoor Fan Contactor
Fig. 52 — Typical Unit Wiring Schematic (208/230-3-60 Unit Shown)
LEGEND
IFM— Indoor Fan Motor
IFMOVL — Indoor Fan Motor Overload Switch
IGC— Integrated Gas Unit Controller
LPS— Low-Pressure Switch
LS— Limit Switch
MGV— Main Gas Valve
OFC— Outdoor Fan Contactor
OFM— Outdoor Fan Motor
P—Plug
PL— Plug AssemblyQT—Quadruple Terminal
—73—
RS— Rollout Switch
SAT— Supply Air Temperature Sensor
SEN— Sensor
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
Page 74
PUSHBUTTONSLED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
OFF
ONES OR
TEN'S
OR ON
NamesADJUSTADVSET NO SETUP
Actions Hold/Push Push flash, no steady flash no flash no
SETUP MODE
Note 1 Push and hold the ADJUST button until the SETUP indicator turns on.
Note 2 Push and release ADV button repeatedly to advance to the desired setup point.
Each time the ADV button is pushed, the SET NO flashes the point number and then displays
the current setting
APPENDIX A — ECONOMI$ER+ LABEL
OFF
ONES OR
TEN'S
OR ON
NamesADJUSTMANMANI/O NO
ActionsPush Hold/Push steady flash no flash no flash no
on use the ADJUST button to enter the value. (i.e., push the button 4 times to enter 4)
Then wait for the ONES indicator to turn on and enter the ONES setting
Wait for indicator to turn off and then push read/adjust to check the setting
Note 3 Once the current value has been displayed the TENS indicator will turn on steady and while it
MANUAL
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
Note 1 Push and hold the MAN button until the MAN indicator turns on.
Note 2 Push and release MAN button repeatedly to advance to the desired I/O point.
Each time the MAN button is pushed, the I/O NO flashes the I/O point number.
and off or open and closed
1 SAT sensor invalid
2 RAT Sensor Invalid (only with changeover type 3&5)
3 OAT Sensor Invalid
4 ORH Sensor invalid (only with changeover type 3&4)
5 IRH Sensor invalid (only with changeover type 5)
6 IAQ Sensor Invalid (only if IAQ=1)
7 Y2onY1off
NO DESCRIPTION
Note 3 After the desired I/O No is reached push and release the ADJUST to toggle the output on
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
ALARM CODES
8 Micro Fails E2 test
note 1 Micro Fails RAM test
note 2 Micro Fails ROM test
Note 1 DS1+DS3/DS2+D4 will alternately flash
Note 2 DS1+DS2/DS3+D4 will alternately flash
PUSHBUTTONSLED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
Actionflashflashflashflash
Indicators flash in sequence at .5 sec intervals
STARTUP MODE
Note 1
NamesHBECONOY1Y2
RUN MODE
Actionsflashflash steadysteady
Note 1 Heartbeat Indicator flashes to indicate proper operation of the control
Note 2 Econo indicator flashes to indicate free cooling being used
Note 3 Y1 and Y2 are on steady when a call thermostat Y1 and Y2 are closed
Note 4 ERROR - HB and Econo are on steady to indicate the presence of an error
OFF
ONES OR
TEN'S
OR ON
NamesREADADVSET NO I/O NO
ActionsPushPush flash, no flash no flash no flash no
READ MODE
Note 1 Push and release the READ button to enter Read Mode. The SET NO Indicator flashes once
to indicate the setup point is selected for viewing
Note 2 Push and release ADV button repeatedly to advance to the desired setup point or I/O point
Each time the ADV button is pushed, the SET NO flashes the point number until the desired
I/O point is reached and then the I/O NO flashes the I/O point no.
button to display the value in the TEN's and ONE's indicator (i.e., 5 flashes for a value of 5)
Note 3 After the SET NO indicator identifies the desired point no, push and release the READ
or a steady TEN's indicator for an on and a steady ONE's for off.
To aid in counting, values of 5 are flashed in groups of 5 (i.e., 150 = 3 groups of fast 5 flashes)
and then follow by balance in slow flashes (i.e., 7 = 5 quick flashes + 2 slow flashes)
Red Set No LED displays Setup item numbers, and Yellow I/O LED displays I/O item no
Note 4 Setpoint values are displayed first followed by I/O values and then back to Setpoint values
Note 5 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
NO I/O PointsUNITS
I/O POINTS
1 C1 Output-
2 C2 Output-
3 C3 Output-
4 C4 Output-
5 Economizer Damper Output%
6 Supply Air temperatureF
7 Outside Air temperatureF
8 Return Air TemperatureF
9 Indoor Relative Humidity%
10 Outdoor Relative Humidity%
11 Indoor Air QualityPPM
12 Remote Minimum Position%
13 Y1 Status (next version)-
14 Y2 Status (next version)-
15 G Status (next version)-
16 Occ Status (next version)-
—74—
Page 75
APPENDIX A — ECONOMI$ER+ LABEL (cont)
—75—
Page 76
APPENDIX B — JOB SPECIFIC ECONOMI$ER+ CONFIGURAITON SETTINGS
Enter the job specific settings in the “Job Setting” column below.
Packaged Service Training programs are an excellent way to increas e your knowledge of the
equipment discussed in this manual, including:
• Unit Familiarization• Maintenance
• Installation Overview• Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based
formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our labs
can mean increased confidence tha t real ly pays dividen ds in fas ter trou bles hoo ting a nd fewer call backs. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training[ ] Classroom Service Training
MODEL NO. _______________________________________
DATE: _____________________________________________
UNIT NO.: _________________________________________
SERIAL NO. ___________________________________________
TECHNICIAN: _________________________________________
JOB LOCTION:______________________________ ___________
JOB NAME:____________________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE SHIPPING TIE DOWN BANDS ON COMPRESSOR (SIZE 150 AND 151 ONLY) PER
INSTALLATION INSTRUCTIONS
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FOR LEAKS
CHECK THAT RETURN-AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
ENSURE BELT TENSION IS CORRECT AND BLOWER PULLEYS ARE PROPERLY ALIGNED.