Bryant DuraPac 580F Series Installation, Start-up And Service Instructions Manual

Page 1
installation, start-up and service instructions
SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 580F-90-2 II 580F-90-3
580F
Dura
Pac
Series
Sizes 090-151
71/2to 121/2Tons
2/1/04
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation instructions b efore installing this unit. (See Fig. 1A and 1B.)
2. Be sure the installation conforms to all applicable local and national codes.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-49
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 4
III. Step 3 — Install External Trap for
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . 4
IV. Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 4
V. Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . 12
VI. Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . 12
VII. Step 7 — Make Electrical Connections . . . . . . . . . 12
VIII. Step 8 — Adjust Factory-Installed Options. . . . . . 17
IX. Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . 27
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50-61
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61-68
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .69-73
APPENDIX A — ECONOMI$ER+ LABEL . . . . . . . . . . . .74,75
APPENDIX B — JOB SPECIFIC ECONOMI$ER+
CONFIGURATION SETTINGS . . . . . . . . . . . . . . . . . . . . . 76
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or servic e air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply provided for the unit.
WARNING: Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres­sures greater tha n resulting in hazardous condition. If gas valve is ever subjected to pressure greater than replaced before use. When pressure testing field­supplied gas piping at pressures of unit connected to such piping must be isolated by man­ually closing the gas valve(s).
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install lockout tag. Electrical shock could cause personal injury.
Unit is shipped in the vertical discharge configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation side down. Seals around duct openings must be tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install access ory roof curb in accorda nce with instructions shipped with curb. See Fig. 3. Install insulation, cant strips, roofi ng fe lt, and counter flashing as shown. Duct- work must be attached to curb. If gas or electr ical co nnec tion s are to be routed through the curb, attach the access ory thru­the-curb service connectio n plate to the roof curb in accor­dance with the accessory installation instructions. Connec­tions must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can also result in air or water leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 4. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
If gas or electrical connections are to be routed through the bottom of the unit, attach accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions.
1
/2 psig will cause g as valve damage
1
/
psig, it must be
2
1
/2 psig or less, a
INSTALLATION
Page 2
Fig. 1A — Base Unit Dimensions — 580F090,102,120,150
2
Page 3
Fig. 1B — Base Unit Dimensions — 580F091,103,121,151
3
Page 4
B. Alternate Unit Support
When the curb or adapter cannot be used, su pport unit with sleepers using un it curb or adapter supp ort area. If sleeper s cannot be used, support long sides of unit with a minimum of three 4-in. x 4-in. pads, two at the corners and one at the unit’s center of gravity. If more than 3 pads are used, equally space them along the side.
C. Slab Mount (Horizontal Units Only)
Provide a level concrete slab tha t extends a min imum of 6 in. beyond unit cabinet. Ins tall a 6-in. g ravel apron in f ront of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building s tructure on verti ­cal units. Do not connect ductwork to unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork secured to the flanges. Insulate and weatherproof all external duct­work, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through a n unc ondit i one d spa ce must be insu­lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli­cable fire codes.
A minimum clearance is not required around ductwork. Cab­inet return-air static shall not exceed –.30 in. wg with EconoMi$er+ or .45 in. wg without economizer.
These units are designed for a minimum heating operation continuous return-air te mperature of 50 F (dry bulb), o r an intermittent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat.
To operate at lower return air temperatures, a field-supplied outdoor-air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor
comfort may be compromised wh en these lo wer ai r tempera­tures are used with insufficient heating temperature ri se.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDEN­SATE DRAIN
The unit’s
3
/4-in. condensate drain connections ar e located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installa­tion, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 5A. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap a minimum of 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
3
/4 in.). See Fig. 5B .
The center drain plug looks lik e a star conne ctio n, however it can be removed with a
1
/2 in. socket drive extension.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Tables 1A and 1B and Fig. 6 for additional inf ormat ion. Op era ting we ight is s hown in Table 1 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 1 and 6. Refer to rigging instructions on unit.
CAUTION: Al l panels must be in place wh en rig-
ging and lifting.
Fig. 2 — Horizontal Conversion Panels
4
Page 5
CONNECTOR
PKG. ACCY.
CRBTMPWR001A01 CRBTMPWR002A01
CRBTMPWR003A01
CRBTMPWR004A01
BC
7
2-8
/16″
1-1015/16″
[827]
[583]
DALT
DRAIN
HOLE
13/4″
[44.5]
GAS POWER CONTROL
3
/4″
/2″
/4″
/4″ [19] NPT
1
1
/4″ [31.7]
3
/4″ [19] NPT
11/4″ [31.7]
[12.7] NPT
3
[19] NPT
1
[12.7] NPT
3
[19] NPT
1
/2″
ACCESSORY
POWER
1
/2″
[12.7] NPT
ROOF CURB
ACCESSORY CRRFCURB003A01 1-2[356] CRRFCURB004A01 2-0[610]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam, 13/4lb density.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
“A” UNIT SIZE
580F
090-151
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for thru-the-curb gas type. Packages CRBTMPWR003A01 and 4A01 are for thru-the-bottom type gas connections.
Fig. 3 — Roof Curb Details
5
Page 6
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 4 — Unit Leveling Tolerances
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 5A — Condensate Drain Pan (Side View)
3/4” FPT DRAIN CONNECTION (HALF COUPLING)
8 1/2-IN. (FIELD­SUPPLIED) NIPPLE
2-IN. (FIELD-SUPPLIED) NIPPLE
A. Positioning
Maintain clearan ce around and above un it to provide mini­mum distance from combustible materials, proper airflow, and service access. See Fig. 1A and 1B Notes.
Do not install unit in an indoor l ocation. Do not locate unit air inlets near exhaust vents or other sources of contami­nated air.
Be sure that unit is installed so that sn ow will not b lock the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Position unit on roof curb so that the following clearances are
1
maintained: rails on each side and duct end of unit; 3
/4-in. clearance between roof curb and base
5
/16-in. clearance between roof curb and condenser section end. (See Fig. 3, section C-C.)
Locate mechanical draft system flue assembly at least 48 in. from an adjacent building or combustible material. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
Flue vent discharge must have a minimum horizontal clear­ance of 48 in. from electric and gas meters, gas regulators, and gas relief equipment.
Flue gas can deteriorate building materials. Orient unit so that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation com­plies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI
3”
(American National Standards Institute) Z223.1-latest year and addendum Z223.1A-latest year. In Canada, installation must be in accordance with the CAN1. B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
4”
Fig. 5B — Condensate Drain Piping Details
6
Page 7
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of grav­ity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Weights include base unit without economizer. See Table 1 for economizer weights.
CAUTION: All panels must be in place when rigging.
Fig. 6 — Rigging Details
OPERATING
UNIT
580F090,091 870 395 87.38 2219 40.25 1022 41.31 1050 580F102,103 880 399 87.38 2219 40.25 1022 41.31 1050 580F120,121 1035 469 87.38 2219 40.25 1022 49.31 1253 580F150,151 1050 476 87.38 2219 40.25 1022 49.31 1253
WEIGHT
lb kg in. mm in. mm in. mm
DIMENSIONS
‘‘A’’ ‘‘B’’ ‘‘C’’
7
Page 8
Tab le 1A — Physical Data (580F090, 102, 120, 150 Units)
UNIT SIZE 580F 090 102 120 150 NOMINAL CAPACITY (tons) 7
OPERATING WEIGHT (lb)
Unit
Al/Al* 870 880 1035 1050 Al/Cu* 881 896 1057 1077 Cu/Cu* 893 907 1080 1100
Economizer
EconoMi$er+ 75 75 75 75
Roof Curb† 143 143 143 143
COMPRESSOR Reciprocating Reciprocating Reciprocating Scroll
Quantity 2222 No. Cylinders (per Circuit) 222— Oil (oz) 42 ea 65 ea 54 ea 54 ea
REFRIGERANT TYPE R-22
Expansion Device Fixed Orifice Metering Device Operating Charge (lb-oz)
Circuit 1 4-13 6-14 7- 3 8-10 Circuit 2 4-14 9- 2 7-13 8- 6
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 1...17 2...17 2...17 2...17 Tot al F ace Ar ea (sq ft) 20.50 18.00 20.47 25.00
CONDENSER FAN Propeller Type
Nominal Cfm 6400 6400 7000 7000 Quantity...Diameter (in.) 2...22 2...22 2...22 2...22 Motor Hp...Rpm Watts Input (To ta l) 600 600 600 600
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split
Rows...Fins/in. 3...15 3...15 3...15 4...15 Tot al F ace Ar ea (sq ft) 8.0 8.0 10.0 11.1
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...15 x 15 1...15 x 15 1...15 x 15 1...15 x 15
Typ e Drive Std Belt Belt Belt Belt
Nominal Cfm 3000 3100 4000 5000 Maximum Continuous BhpStd 2.40 2.40 2.40 3.70
Motor FrameSizeStd56 56 56 56
Fan Rpm Range Std 590-840 685-935 685-935 860-1080
Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.4/3.4 2.8/3.8 2.8/3.8 4.0/5.0
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 7.0 8.0
Belt, Quantity...Type...Length(in.) Std 1...A...49 1...A...49 1...A...49 1...A...52
Pulley Center Line Distance (in.) Std 16.75-19.25 16.75-19.25 15.85-17.50 15.85-17.50
Speed Change per Full Turn of Std 50 50 50 44
Movable Pulley Flange (rpm) Alt 50 50 50
MovablePulleyMaximum Full Turns Std 5555
From Closed Position Alt 5—5 6
Factory Setting Std 5555
Factory Speed Setting (rpm) Std 590 685 685 860
Fan Shaft Diameter at Pulley (in.) 1111
Alt 1...15 x 15 1...15 x 15 1...15 x 15 High-Static 1...15 x 15 1...15 x 15 1...15 x 15
Alt Belt Belt Belt High-Static Belt Belt Belt
Alt 2.40 2.90 5.25 High-Static 3.70 3.70 5.25
Alt 56 56 56 High-Static 56 56 56
Alt 685-935 835-1085 830-1130 High-Static 860-1080 860-1080 830-1130
Alt 2.8/3.8 3.4/4.4 3.1/4.1 High-Static 4.0/5.0 4.0/5.0 2.8/3.8
Alt High-Static
Alt 7.0 7.0 5.9 High-Static 8.0 8.0 5.8
Alt 1...A...49 1...A...49 1...BX...46 High-Static 1...A...55 1...A...55 1...BX...46
Alt 16.75-19.25 15.85-17.50 15.85-17.50 High-Static 16.75-19.25 16.75-19.25 15.85-17.50
High-Static 60 60 60
High-Static 556—
Alt 5—5 5 High-Static 555—
Alt 685 835 887 High-Static 860 860 887
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre-
sentative for details about coated fins.
1
/
2
1
/4...1100
5
/
8
1
/
2
7
/
8
†Weight of 14-in. roof curb. **Rollout switch lockout is manually reset by interrupting power to unit or resetting
thermostat.
81/
1
/4...1100
5
/
8
7
/
8
2
10 121/
1
/4...1100
5
/
8
7
/
8
7
/
8
NOTE: High-static motor not available on size 150 and 151 units.
1
/4...1100
7
/
7
/
2
8 8
8
Page 9
Table 1 A — P hysical Data (580F090, 102, 120, 150 Units)(cont)
UNIT SIZE 580F 090 102 120 150 FURNACE SECTION
Rollout Switch Cutout Temp (F)** 195 195 195 195 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std LOW .120...31 .120...31 .120...31 .120...31
Liquid Propane Alt LOW .096...41 .096...41 .096...41 .096...41
Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1 .14.14.14.14
460v Stage1 .14.14.14.14
Gas Input (Btuh) Stage 1 LOW 125,000 125,000 120,000 180,000
Stage 2 .20.20.20.20
Stage 2 .20.20.20.20
Stage 2 LOW 180,000 220,000
Efficiency (Steady
State)(%) 80 80 80 80
Temperature Rise Range LOW 20-50 20-50 35-65 35-65
Manifold Pressure (in. wg)
Natural Gas Std 3.53.53.53.5
Liquid Propane Alt 3.53.53.53.5 Gas Valve Quantity 1111 Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5 Field Gas Connection Size (in.) LOW
HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320
LOSS-OF-CHARGE (LOW-PRESSURE)
SWITCH (psig) Cutout 7±3 Reset (Auto.) 22 ± 7
FREEZEPROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable. Screen size and quantity varies by option selected. RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 4...16 x 20 x 2 4...16 x 20 x 2 4...20 x 20 x 2 4...20 x 20 x 2
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre-
sentative for details about coated fins.
MED .120...31 .120...31 .120...31 .129...30 HIGH .120...31 .120...31 .129...30
MED .096...41 .096...41 .096...41 .102...38 HIGH .096...41 .096...41 .102...38
MED 120,000 120,000 180,000 200,000 HIGH 180,000 180,000 200,000
MED 180,000 180,000 220,000 250,000 HIGH 220,000 220,000 250,000
MED 35-65 35-65 35-65 40-70 HIGH 45-75 45-75 40-70
MED HIGH
1
/
2
3
/
4
3
/
4
†Weight of 14-in. roof curb.
**Rollout switch lockout is manually reset by interrupting power to unit or resetting
thermostat.
1
/
2
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
NOTE: High-static motor not available on size 150 and 151 units.
9
Page 10
Tab le 1B — Physical Data (580F091, 103, 121, 151 [ASHRAE 90.1-1999 Compliant Units])
UNIT SIZE 580F 091 103 121 151 NOMINAL CAPACITY (tons) 7
OPERATING WEIGHT (lb)
Unit
Al/Al* 870 880 1035 1050 Al/Cu* 881 896 1057 1077 Cu/Cu* 893 907 1080 1100
Economizer
EconoMi$er+ 75 75 75 75
Roof Curb† 143 143 143 143
COMPRESSOR Reciprocating Scroll Scroll Scroll
Quantity 2222 No. Cylinders (per Circuit) 2222 Oil (oz) (each compressor) 42 53 50 60
REFRIGERANT TYPE R-22
Expansion Device Fixed Orifice Metering Device Operating Charge (lb-oz)
Circuit 1 7-10 7-14 8-10 9-8 Circuit 2 8-2 8-5 8-8 9-5
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 2...17 2...17 2...17 2...17 Tot al F ace Ar ea (sq ft) 20.50 20.50 25.00 25.00
CONDENSER FAN Propeller Type
Nominal Cfm 6500 6500 7000 7000 Quantity...Diameter (in.) 2...22 2...22 2...22 2...22 Motor Hp...Rpm Watts Input (To ta l) 650 650 650 650
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split
Rows...Fins/in. 3...15 3...15 3...15 4...15 Tot al F ace Ar ea (sq ft) 8.9 8.9 10.0 11.1
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...15 x 15 1...15 x 15 1...15 x 15 1...15 x 15
Typ e Drive Std Belt Belt Belt Belt
Nominal Cfm 2900 3000 3200 5000 Maximum Continuous BhpStd2.40 2.40 2.40 3.70
Motor FrameSizeStd56 56 56 56
Fan Rpm Range Std 590-840 685-935 685-935 860-1080
Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.4/3.4 2.8/3.8 2.8/3.8 4.0/5.0
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std 7.0 7.0 7.0 8.0
Belt, Quantity...Type...Length(in.) Std 1...A...49 1...A...49 1...A...49 1...A...52
Pulley Center Line Distance (in.) Std 16.75-19.25 16.75-19.25 15.85-17.50 15.85-17.50
Speed Change per Full Turn of Std 50 50 50 44
Movable Pulley Flange (rpm) Alt 50 50 50
MovablePulleyMaximum Full Turns Std 5555
From Closed Position Alt 5—56
Factory Setting Std 5555
Factory Speed Setting (rpm) Std 590 685 685 860
Fan Shaft Diameter at Pulley (in.) 1111
Alt 1...15 x 15 1...15 x 15 1...15 x 15 High-Static 1...15 x 15 1...15 x 15 1...15 x 15
Alt Belt Belt Belt High-Static Belt Belt Belt
Alt 2.40 2.90 5.25 High-Static 3.70 3.70 5.25
Alt 56 56 56 High-Static 56 56 56
Alt 685-935 835-1085 830-1130 High-Static 860-1080 860-1080 830-1130
Alt 2.8/3.8 3.4/4.4 3.1/4.1 High-Static 4.0/5.0 4.0/5.0 2.8/3.8
Alt High-Static
Alt 7.0 7.0 5.9 High-Static 8.0 8.0 5.8
Alt 1...A...49 1...A...49 1...BX...46 High-Static 1...A...55 1...A...55 1...BX...46
Alt 16.75-19.25 15.85-17.50 15.85-17.50 High-Static 16.75-19.25 16.75-19.25 15.85-17.50
High-Static 60 60 60
High-Static 556
Alt 5—55 High-Static 555
Alt 685 835 887 High-Static 860 860 887
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre-
sentative for details about coated fins.
1
/
2
1
/4...1100
5
/
8
5
/
8
7
/
8
†Weight of 14-in. roof curb.
**Rollout switch lockout is manually reset by interrupting power to unit or resetting
thermostat.
81/
1
/4...1100
5
/
8
7
/
8
2
10 121/
1
/4...1100
5
/
8
7
/
8
7
/
8
NOTE: High-static motor not available on size 150 and 151 units.
1
/4...1100
7
/
7
/
2
8 8
10
Page 11
Table 1 B — P hysical Data (580F091, 103, 121, 151 [ASHRAE 90.1-1999 Compliant Units]) (cont)
UNIT SIZE 580F 091 103 121 151 FURNACE SECTION
Rollout Switch Cutout Temp (F)** 195 195 195 195 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std LOW .120...31 .120...31 .120...31 .120...31
Liquid Propane Alt LOW .096...41 .096...41 .096...41 .096...41
Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1 .14 .14 .14 .14
460v Stage1 .14 .14 .14 .14
Gas Input (Btuh) Stage 1 LOW 125,000 125,000 120,000 180,000
Stage 2 .20 .20 .20 .20
Stage 2 .20 .20 .20 .20
Stage 2 LOW 180,000 220,000
Efficiency (Steady
State)(%) 80 80 80 80 Temperature Rise Range LOW 20-50 20-50 35-65 35-65
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5 Gas Valve Quantity 1111 Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5 Field Gas Connection Size (in.) LOW
HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320
LOW-PRESSURE SWITCH (psig)
Cutout Reset (Auto.) 22 ± 7
FREEZEPROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable. Screen size and quantity varies by option selected. RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 4...16 x 20 x 2 4...16 x 20 x 2 4...20 x 20 x 2 4...20 x 20 x 2
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local repre-
sentative for details about coated fins.
MED .120...31 .120...31 .120...31 .129...30 HIGH .120...31 .120...31 .129...30
MED .096...41 .096...41 .096...41 .102...38 HIGH .096...41 .096...41 .102...38
MED 120,000 120,000 180,000 200,000 HIGH 180,000 180,000 200,000
MED 180,000 180,000 220,000 250,000 HIGH 220,000 220,000 250,000
MED 35-65 35-65 35-65 40-70 HIGH 45-75 45-75 40-70
MED HIGH
1
/
2
3
/
4
3
/
4
1
/
2
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
7±3
†Weight of 14-in. roof curb.
**Rollout switch lockout is manually reset by interrupting power to unit or resetting
thermostat.
NOTE: High-static motor not available on size 150 and 151 units.
11
Page 12
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood and screen in location shown in Fig. 7.
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipp ed for use with type of gas shown on name­plate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-latest year and addendum Z223.1A­latest year entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appli­ances when installing gas piping.
For natural gas applications, gas pressure at unit gas con­nection must not be less than 4.0 in. wg (5.0 in. wg in high heat units) or greater than 13.0 in. wg while unit is operat­ing. For liquid propane applications, the pressure must not be less than 5.0 in. wg or greater than 13.0 in. wg at the unit connection.
Size gas supply piping for 0.5 i n. wg ma ximum pre ssure drop . Do not use supply pip e smaller than unit gas connection.
CAUTION: When installing gas piping to gas valve inlet, use properly sized back-up wrench on inlet flange flats to prevent valve damage.
Support gas piping as shown in the table in Fig. 8. For exam-
3
ple, a
/4-in. gas pipe must have one field-fabricated support
beam every 8 ft. See Fig. 8 for typical pipe guide and locations of external
manual gas shutoff valve. NOTE: If field-installed thru-the-bottom connections are
used, refer to the accessory installation instructions for power wiring and gas connections. Refer to Fig. 1A and 1B for drilling holes in basepan.
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electric al wir e connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Associa­tion), latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of other s.
A. Field Power Supply
All units except 208/230-v units are factory wired for the voltage shown on the na meplate. If the 208/230-v u nit is to be connected to a 208-v power supply, the transformer must
1
be rewired by moving the black wire from the 230- v
/4-in. male spade terminal on the transformer and connecting it to the 208-v
1
/4-in. male spade terminal from the transformer.
Refer to unit label diagram for additional information. Pig­tails are provided for field service.
When installing units, provide a disconnect per NEC. Use copper conductors only when splice connectors are used.
All field wiring must comply with NEC and local require­ments. In Canada, electrical connections must be in accor­dance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.
Fig. 7 — Flue Hood Details
SPACING OF SUPPORTS
LEGEND
NFGC —
*Field supplied. NOTE: Follow all local codes.
National Fuel Gas Code
STEEL PIPE
NOMINAL
DIAMETER (in.)
1
/
2
3
/
or 1
4
1
1
/
or larger
4
X
DISTANCE
(feet)
6 8
10
Fig.8—GasPipingGuide(With Accessory
Thru-the-Curb Service Connections)
Install conduit through side panel openings indicated in Fig. 1A and 1B. Route power lines through connector to ter­minal connections as shown in Fig. 9.
On 3-phase units, voltages between ph ase s must be balanced within 2% and the current within 10%. Use the formula shown in Tables 2A and 2B, Note 2 to determine the percent­age of voltage im balance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
NOTE: If field-installed thru-the-bottom connections are used, refer to the accessory installation instructions for power wiring and gas connectio ns. Refer to Fig. 1A and 1B for drilling holes in basepan.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accor­dance with thermostat installation instructions.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than n o. 18 AWG cannot be dir ectly con nect ed to the thermos tat and wi ll req uire a j unction box and s plice a t the thermostat.
12
Page 13
Route thermostat cable or equivalent single leads of colored wire from thermostat subbase terminals to low-voltage con­nections on unit (shown in Fig. 10) as described in Steps 1-4 below.
If unit is mounted on roof curb and accessory thru-the-curb service plate connection is used, route wire through connec­tion plate.
Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 1A and 1 B).
Feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box.
Table 2A — Electrical Data (Without Convenience Outlet)
UNIT
580F
090
(71/2Ton s)
091
(71/2Ton s)
102
(81/2Ton s)
103
(81/2Ton s)
120
(10 Tons)
121
(10 Tons)
150
1
(12
/2Ton s)
151
1
(12
/2Ton s)
NOMINAL VO LTAGE
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
VO LTAGE
IFM
TYPE
RANGE
Min Max Qty RLA LRA Qty Hp FLA F LA MCA MOCP** FLA LRA
Std
187 254 2 14.0 91.0 21/41.4
Alt 5.8 40.1/40.1 45/45 42/42 229/229
High 10.6 44.9/44.9 50/50 48/48 273/273
Std
414 508 2 6.4 42.0 21/40.7
Alt 2.6 18.4 20 19 108
High 4.8 20.6 25 22 130
Std
518 632 2 5.2 39.0 21/40.7
Alt 2.6 14.9 20 16 97
High 4.8 16.7 20 18 114
Std
187 254 2 14.0 91.0 21/41.4
Alt 5.8 40.1/40.1 45/45 42/42 229/229
High 10.6 44.9/44.9 50/50 48/48 273/273
Std
414 508 2 6.4 42.0 21/40.7
Alt 2.6 18.4 20 19 108
High 4.8 20.6 25 22 130
Std
518 632 2 5.2 39.0 21/40.7
Alt 2.6 14.9 20 16 97
High 4.8 16.7 20 18 114
Std
187 254 2 16.0 137.0 21/41.4
High 10.6 49.4/49.4 60/60 52/52 365/365
Std
414 508 2 8.3 69.0 21/40.7
High 4.8 24.9 30 26 184
Std
518 632 2 6.4 58.0 21/40.7
High 4.8 19.4 25 20 152
Std
187 254 2 17.3*** 120.0*** 21/41.4
High 10.6 49.1/49.1 60/60 52/52 316/316
Std
414 508 2 7 .9*** 70.0*** 21/40.7
High 4.8 23.2 30 24 171
Std
518 632 2 5 .5*** 50.0*** 21/40.7
High 4.8 18.5 25 19 126
Std
187 254 2 15.8 130.0 21/41.4
Alt 7.5 45.9/45.9 50/50 48/48 326/326
High 15.0 53.4/53.4 60/60 57/57 374/374
Std
414 508 2 7.9 64.0 21/40.7
Alt 3.4 22.6 25 24 191
High 7.4 26.6 30 28 185
Std
Alt 3.4 18.7 25 20 155
518 632 2 6.6 52.0 2
High 7.4 21.9 30 23 150
Std
187 254 2 16.0 125.0 21/41.4
Alt 7.5 46.3/46.3 60/60 49/49 316/316
High 15.0 53.4/53.4 60/60 57/57 374/374
Std
414 508 2 8.0 62.5 21/40.7
Alt 3.4 22.8 25 24 191
High 7.4 26.8 30 29 182
Std
518 632 2 6.3 50.0 21/40.7
Alt 3.4 18.0 20 19 151
High 7.4 21.2 25 23 146
Std
187 254 2 23.0 146.0 21/41.4
Alt 15.0 69.6/69.6 80/80†† 73/73 406/406
Std
414 508 2 10.4 73.0 21/40.7
Alt 7.4 32.2 45 34 203
Std
518 632 2 8.3 58.4 2
Alt 7.4 25.7 30 27 162
Std
187 254 2 19.0 156.0 2
Alt 15.0 60.6/60.6 70/70†† 64/64 378/378
Std
414 508 2 9.0 75.0 2
Alt 7.4 29.1 35 31 213
Std
518 632 2 7.4 54.0 21/40.7
Alt 7.4 23.7 30 25 159
COMPR
(ea)
See Fig. 11. The raceway provides the UL-required (Under­writers’ Laboratories) clearance between high- and low­voltage wiring.
Connect thermostat wires to sc rew terminal s on low-voltage connecti on board.
C. Heat Anticipator Settings
Set heat anticipator settings at .14 amp for the first stage and .20 amp for second-stage heating.
OFM
(ea)
1
/40.7
1
/40.7
1
/41.4
1
/40.7
IFM
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
10.6
4.8
4.8
10.6
4.8
4.8
COMBUSTION
FAN M OTO R
FLA
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
POWER SUPPLY*
40.1/40.1 45/45 42/42 229/229
18.4 20 19 108
14.9 20 16 97
40.1/40.1 45/45 42/42 229/229
18.4 20 19 108
14.9 20 16 97
44.6/44.6 50/50 47/47 321/321
22.7 25 24 162
17.6 20 18 135
44.3/44.3 50/50 46/46 272/272
21.0 25 22 149
16.7 20 17 109
44.2/44.2 50/50 46/46 307/307
21.8 25 23 152
18.1 25 19 123
44.6/44.6 50/50 47/47 297/297
22.0 25 24 188
17.4 20 18 119
65.2/65.2 80/80†† 68/68 383/383
29.6 40 31 192
23.6 30 25 154
56.2/56.2 70/70†† 59/59 359/359
26.5 30 28 174
21.6 25 23 127
DISCONNECT
SIZE†
13
Page 14
LEGEND AND NOTES FOR TABLES 2A AND 2B
LEGEND
FLA — Full Load Amps HACR— Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP— Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*The values listed in this table do not include power exhaust. See table
below for power exhaust requirements.
†Used to determine minimum disconnect per NEC.
**Fuse or HACR circuit breaker. ††Fuse only. ***Compressor no. 1 data indicated in table.
208/230-3-60: Compressor no. 2 RLA is 14.1 amps and LRA is 105 amps. 460-3-60: Compressor no. 2 RLA is 7.1 amps and LRA is 55 amps. 575-3-60: Compressor no. 2 RLA is 6.4 amps and LRA is 40 amps.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PA RT N O.
CRPWREXH021A00 N/A 0.9 N/A 15 CRPWREXH022A00 3.3 N/A 1.32 15 CRPWREXH023A00 N/A 1.8 N/A 15 CRPWREXH024A00 1.6 N/A 0.64 15 CRPWREXH025A00 N/A 0.9 N/A 15 CRPWREXH026A00 3.3 N/A 1.32 15 CRPWREXH027A00 N/A 1.8 N/A 15 CRPWREXH028A00 1.7 N/A 0.68 15 CRPWREXH029A00 N/A 1.0 N/A 15 CRPWREXH030A00 1.6 N/A 0.64 15
N/A—Not available
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
MOCP
(for separate
power source)
NOTES:
1. In compliance with NEC requirements for multimotor and combina­tion load equipment (refer to NEC Articles 430 and 440), the overcur­rent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
of voltage imbalance. % Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
Use the following formula to determine the percent
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
average voltage
Average Voltage =
457
=1.53%
452 + 464 + 455
3
1371
=
3
= 457
7
NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Must be in accordance with NEC or local codes.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the fol­lowing formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580FPV090 unit with MCA = 40.1 and MOCP
= 45, with CRPWREXH030A00 power exhaust. MCA New = 40.1 amps + 1.6 amps = 41.7 amps If the new MCA does not exceed the published MOCP, then MOCP
would not change. The MOCP in this example is 45 amps and the MCA New is below 45; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
14
Page 15
Table 2B — Electrical Data (With Convenience Outlet)
UNIT 580F
NOMINAL VOLTAGE
IFM
TYPE
Std
208/230-3-60
Alt 5.8 46.1/46.1 50/50 48/48 233/233
High 10.6 50.9/50.9 60/60 53/53 273/273
Std
Alt 2.6 24.1 25 22 110
High 4.8 23.3 30 24 132
1
(7
090
/2Tons)
460-3-60
Std
575-3-60
Alt 2.6 20.9 25 18 99
High 4.8 19.4 25 20 117
Std
208/230-3-60
Alt 5.8 44.9/44.9 50/50 48/48 234/234
High 10.6 49.7/49.7 60/60 53/53 277/277
Std
Alt 2.6 20.6 25 22 110
High 4.8 22.8 30 24 132
1
(7
091
/2Tons)
460-3-60
Std
575-3-60
Alt 2.6 16.6 20 18 99
High 4.8 18.4 20 20 116
Std
High 10.6 55.4/55.4 60/60 58/58 369/369
Std
High 4.8 27.6 35 29 138
Std
High 4.8 22.1 30 22 155
Std
High 10.6 53.9/53.9 60/60 57/57 320/320
Std
High 4.8 25.4 30 27 173
Std
High 4.8 20.2 25 21 128
1
(8
1
(8
102
/2Tons)
103
/2Tons)
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
Std
208/230-3-60
Alt 7.5 51.9/51.9 60/60 54/54 330/330
High 15.0 59.4/59.4 70/70†† 62/62 378/378
120
(10 Tons)
460-3-60
Std
Alt 3.4 25.3 30 26 193
High 7.4 29.3 35 31 187
Std
575-3-60
Alt 3.4 24.7 25 22 141
High 7.4 24.6 30 25 136
Std
208/230-3-60
Alt 7.5 51.9/51.9 60/60 54/54 321/321
High 15.0 58.6/58.6 70/70†† 63/63 369/369
121
(10 Tons)
460-3-60
Std
Alt 3.4 25.0 30 26 190
High 7.4 29.0 35 31 184
Std
575-3-60
Alt 3.4 19.7 25 21 152
High 7.4 22.9 25 25 148
Std
Alt 15.0 75.6/75.6 80/80†† 79/79 410/410
Std
Alt 7.4 34.9 40 37 205
Std
Alt 7.4 31.7 35 29 165
Std
Alt 15.0 65.4/65.4 80/80†† 70/70 383/383
Std
Alt 7.4 31.3 35 33 215
Std
Alt 7.4 25.4 30 27 160
150
1
(12
Tons)
151
1
(12
Tons)
/
2
/
2
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
See Legend and Notes on page 14.
VOLTAG E
RANGE
Min Max Qty RLA LRA Qty Hp FLA FLA MCA MOCP** FLA LRA
187 254 2 14.0 91.0 2
414 508 2 6.4 42.0 2
518 632 2 5.2 39.0 2
187 254 2 14.0 91.0 2
414 508 2 6.4 42.0 2
518 632 2 5.2 39.0 2
187 254 2 16.0 137.0 2
414 508 2 8.3 69.0 2
518 632 2 6.4 58.0 2
187 254 2 17.3*** 120.0*** 2
414 508 2 7.9*** 70.0*** 2
518 632 2 5.5*** 50.0*** 2
187 254 2 15.8 130.0 2
414 508 2 7.9 64.0 2
518 632 2 6.6 52.0 2
187 254 2 16.0 125.0 2
414 508 2 8.0 62.5 2
518 632 2 6.3 50.0 2
187 254 2 23.0 146.0 2
414 508 2 10.4 73.0 2
518 632 2 8.3 58.4 2
187 254 2 19.0 156.0 2
414 508 2 9.0 75.0 2
518 632 2 8.3 58.4 2
COMPR
(ea)
OFM
(ea)
1
/41.4
1
/40.7
1
/40.7
1
/41.4
1
/40.7
1
/40.7
1
/41.4
1
/40.7
1
/40.7
1
/41.4
1
/40.7
1
/40.7
1
/41.4
1
/40.7
1
/40.7
1
/41.4
1
/40.7
1
/40.7
1
/41.4
1
/40.7
1
/40.7
1
/41.4
1
/40.7
1
/40.7
IFM
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
5.8
2.6
2.6
10.6
4.8
4.8
10.6
4.8
4.8
COMBUSTIO
N
FAN M OTO R
FLA
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
.6
.3
.3
POWER SUPPLY*
DISCONNECT
SIZE†
46.1/46.1 50/50 48/48 233/233
24.1 25 22 110
20.9 25 18 99
44.9/44.9 50/50 48/48 234/234
20.6 25 22 110
16.6 20 18 99
50.6/50.6 60/60 52/52 325/325
25.4 30 26 164
20.3 25 20 137
49.1/49.1 60/60 52/52 277/277
23.2 30 24 151
18.4 25 19 111
50.2/50.2 60/60 52/52 311/311
27.8 30 25 154
24.1 25 21 109
49.4/49.4 60/60 52/52 302/302
24.2 30 26 151
19.1 25 20 121
71.2/71.2 80/80†† 74/74 387/387
35.6 40 34 194
29.6 35 27 156
61.0/61.0 70/70†† 65/65 364/364
28.7 35 30 176
23.3 30 25 129
15
Page 16
Fig. 9 — Power Wiring Connections
LEGEND
C—Contactor COMPS — Compressors IFC Indoor (Evaporator)
Fan Contactor
NEC National Electrical Code TB Terminal Block
Terminal Block Connection
Splice Connection (Factory Supplied) Field Wiring Factory Wiring
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON OFF
B
A
C
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
D
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.
Fig. 10 — Low-Voltage Connections
UNIT LOW VOLTAGE CONNECTION BOARD
RACEWAY
COMPRESSOR NO. 2
Fig. 11 — Field Control Wiring Raceway
and Compressor Location
INTEGRATED GAS UNIT CONTROLLER (IGC)
COMPRESSOR NO.1
16
Page 17
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS
A. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for build­ing. Record amount for use in Step 8.
2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track an d can be re moved. No to ols are required to remove the filt er ac cess pa nel. Remove outdoo r-air opening panel. Save panels and screws. See Fig. 12.
3. Separate hood and screen from basepan by removing the screws and brackets securing them. Save all screws and discard brackets.
4. Replace outdoor air o pening panel wi th screws saved from Step 2.
5. Place hood on front of outdoor-air opening panel. See Fig. 13 for hood details. Secure top of hood with the 6 screws removed in Step 3. See Fig. 14.
6. Remove and save 6 screws (3 on each side) from sides of the manual outdo or-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6.
8. Adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 12. Slide blade vertically until it is in the appropriate position determined by Fig. 15. Tighten screws.
9. Remove and save screws currently on sides of hood. Insert screens. Secure screens to hood using the screws. See Fig. 14.
10. Replace filter access panel. Ensure filter acces s panel slides along the tracks and is securely engaged.
Fig. 13 — Outdoor-Air Hood Details
HOOD
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
Fig. 12 — Damper Panel with Manual
Outdoor-Air Damper Installed
NOT SHOWN)
Fig. 14 — Optional Manual Outdoor-Air Damper
with Hood Attached
Fig. 15 — Outdoor-Air Damper Position Setting
17
Page 18
B. Optional EconoMi$er+
See Fig. 16 for EconoMi$er+ component locations. NOTE: These instructions are for the factory-installed optional
EconoMi$er+ only. Refer to the accessory EconoMi$er+ installation instr uc t ion s w hen f iel d ins t all ing an Ec o noMi$er+ accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 17.
2. The box with the EconoMi$er+ hood components is shipped in the compartment behind the EconoMi$er+. The EconoMi$er+ does not have to be removed to retrieve the hood box. Remove the screw holding the hood box bracket to the top of the EconoMi$er+. Slide the hood box out of the unit. See Fig. 18.
IMPORTANT: If a power exhaust accessory will be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust.
3. The indoor coil access panel will be used as the top of the hood. Remove the screws a long t he bottom of the indoor coil access panel. See Fig. 19.
4. Swing out the indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use the screws provided to attach the hoo d sides to the unit. See Fig. 20.
5. Remove the shipping tape holding the EconoMi$er+ barometric relief damper in place.
6. Insert the hood divider between the hood side s. See Fig. 20. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider) . Push the filter into position pa st th e op en fi lter c lip s . Cl ose the f ilt er c lip s to lock the filter into place. See Fig. 21.
8. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 19.
9. Replace the filter access panel.
10. Install all Eco noMi$ er+ acc essori es . Econ oMi$er + wir ing is shown in Fig. 22.
Barometric flow capacity is shown in Fig. 23. Outdoor air leakage is shown in Fig. 24. Return air pressure drop is shown in Fig. 25.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
Fig. 17 — Typical Access Panel Locations
x
o
B
H
d
o
o
HOOD BOX BRACKET
Fig. 18 — Hood Box Removal
ECONOMI$ER+ PLUG
OUTDOOR AIR TEMPERATURE SENSOR
ECONOMI$ER+ CONTROLLER (UNDER COVER)
OUTDOOR AIR HOOD
Fig. 16 — EconoMi$er+ Component Locations
HOOD SHIPPING BRACKET
ECONOMI$ER+ CONTROLLER LABELS
GEAR DRIVEN DAMPER
BAROMETRIC RELIEF DAMPER
18
SIDE PANEL
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
INDOOR COIL ACCESS PANEL
CAULK HERE
Fig. 19 — Indoor Coil Access Panel Relocation
Page 19
TOP PANEL
INDOOR COIL ACCESS PANEL
22 1/4
LEFT HOOD SIDE
B
24 9/16
HOOD DIVIDER
SCREW
Fig. 20 — Outdoor-Air Hood Construction
40 3/8
BAROMETRIC RELIEF
DIVIDER
OUTSIDE AIR
CLEANABLE ALUMINUM FILTER
FILTER
Fig. 21 — Filter Installation
HOOD
FILTER CLIP
(FIELD-SUPPLIED)
LEGEND
ECON — Economizer OAT — Outdoor-Air Temperature IAQ Indoor-Air Quality (4 to 20 mA) ORH — Outdoor-Air Relative Humidity (Sensor) IARH — Indoor-Air Relative Humidity (Signal) POT — Potentiometer IRH Indoor-Air Relative Humidity (Sensor) RAT — Return-Air Temperature OARH — Outdoor-Air Relative Humidity (Signal) SAT — Supply-Air Temperature
NOTES:
1. Terminals 13-17 are wired to 5-pin plug assembly (P/N CRE+PLUG001A00).
2. Pin numbers are not printed on the controller. They are provided in this book as a reference.
Fig. 22 — EconoMi$er+ Wiring
19
Page 20
2500
2000
FLOW IN CUBIC FEET PER MINUTE (cfm)
1500
1000
500
0
0.05
0.15
STATIC PRESSURE (in. wg)
0.25
71/2-121/2Ton
Fig. 23 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.2 0 0. 22 0.25 0.30 0.35 0.40 0 .45 0.5 0
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
7 1/2-12 1/2 Ton
Fig. 24 — Outdoor-Air Damper Leakage
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0.20 0.25 0.30 0. 35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
7 1/2-12 1/2 Ton
Fig. 25 — Return-Air Pressure Drop
C. EconoMi$er+ Control Mode
Determine the EconoMi$er+ control mode before installing sensors and accessories. Different sensors are required for different control modes, and a number of accessories are available. Refer to Tables 3 and 4.
Outdoor Dry Bulb Changeover The standard control mode for the EconoMi$er+ is Outdoor
Dry Bulb Changeover. The outdoor air an d supply air tem­perature sensors are also included as standard. EconoMi$er+ control is based on the outdoor temperature relative to a set point in the software. If the outdoor-air tem­perature is above the set point then the EconoMi$er should be in minimum position. If the outdoor-air temperature is below the set point, the position should be controlled to maintain the l eav ing a ir t emper ature set po in t. The s et po int range is 45 to 70 F.
Differential D r y Bulb Changeover The control supports differential dry bulb changeover con-
trol. This requires an accessory return air temperature sensor CRTEMPSN001A00 installed in the return air­stream. Refer to the Start-up section for details on how to configure and enable the control mode. The user can check the operation of the s ensor using the Read function.
Outdoor Air Enthalpy Changeover The control support s ou tdoor air e nthal py cha ngeo ver con trol.
This mode requires a factory-supplied outdoor air temperature sensor (OAT) and an accessory outdoor air humidity sensor (ORH) (part no. CRHUMDSN001B00). Refer to the Start-Up section fo r details on how to con figure and enable th e control mode. The user ca n check the operation of the sensors using the Read function.
Differential Ent halpy Changeover The control supports differential enthalpy changeover con-
trol. This requires the factory-supplied outdoor air tempera­ture sensor, an accessory outdoor air humidity sensor, an accessory return air temperature sensor, and an accessory indoor air humidit y sensor. Refer to the Start-Up section fo r details on how to configure and enable the control mode. The user can check the o peration of the sens ors using the Read function.
D. Damper Movement
When the EconoMi$e r+ board receives initia l power, it will take the damper up to 2
1
/2 minutes before it begins to posi­tion itself. After the initial positioning, subsequent changes to damper position will take up to 30 seconds to initiate. Damper movement from full open to full closed (or vice versa) takes 2
1
/2 minutes.
If the damper is in the process of changing positions (for example it is trying to open to 100%) and the fan signal is turned off, the damper will con tinue to its 100% open posi­tion before closing.
NOTE: Occupied minimum position can not be set lower than +1% higher than the value of IAQ minimum ec onomizer posi­tion. Refer to the setup examples on page 56.
E. EconoMi$er+ Controller Wiring
The EconoMi$er+ is sup plied fr om the factor y with a suppl y air temperature sensor and an outside air temperature sensor. This allows for operation of the EconoMi$er+ with outdoor air dry bulb changeover control. Additional accesso­ries can be added to allow for different types of change over control and operation of the EconoMi$er+ and unit.
F. T hermostats
The EconoMi$er+ control works with conventional thermo­stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2) , and G (fan). The EconoMi$er+ control does not support sensor thermostats l ike the T56 and T57. Connections are made at the thermos tat terminal con­nection board located in the main control box.
20
Page 21
Table 3 — EconoMi$er+ Sensor Usage
APPLICATION
Standard Unit Included — HH79NZ039
Differential
Dry Bulb
Outdoor Air
Enthalpy
Differential Enthalpy Included — HH79NZ039
NOTES:
Sensors (Optional, 5-Pin sensor wiring plug CRE+PLUG001A00 required for installation.).
1. CO
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO 33ZCT55CO2 — Space temperature and CO 33ZCT56CO2 — Space temperature and CO2room sensor with override and set point. CRCBDIOX002A00 — Return air CO
2. All units include the following Standard Sensors: Outdoor-Air Sensor — set point adjustable from 45 F to 70 F, factory set at 65 F. Supply-Air Sensor — set point adjustable from 40 F to 65 F. Factory set at 55 F. All temperature adjustments are made at the EconoMi$er+ controller.
STANDARD OUTDOOR AIR
TEMPERATURE SENSOR
Included — HH79NZ039
Included — HH79NZ039
room sensor with override.
2
sensor.
2
Table 4 — EconoMi$er+ Field-Installed Accessories
1
7
/2-121/2Ton Powe r E xhaust
208-230 v 1 Ph
1
7
/2-121/2Ton Powe r E xhaust
460 v 3 Ph Return Air Temperature Sensor with
Harness Outdoor Air Humidity Sensor with
Harness Indoor Air Humidity Sensor w/Harness CRHUMDSN001B00 Return Air CO
Room Sensor 33ZCSENCO2*
CO
2
Aspirator Box for Duct Mount
Sensor
CO
2
Space Temperature and CO Room Sensor with Override
Space Temperature and CO Room Sensor with Override and Set Point
5-Pin Sensor Wiring Plug CRE+PLUG001A00*
*5-pin sensor wiring plug accessory (P/N CRE+PLUG001A00) is
required to install IAQ sensor.
DESCRIPTION PART NUMBER
CRPWREXH022A00
CRPWREXH023A00
CRTEMPSN001A00
CRHUMDSN001B00
Sensor CRCBDIOX002A00*
2
33ZCASPCO2
2
2
33ZCT55CO2*
33ZCT56CO2*
ACCESSORY RETURN AIR
TEMPERATURE SENSOR
Required —
CRTEMPSN001A00
Required —
CRTEMPSN001A00
room sensor.
2
The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
I. Indoor Air Quality (IAQ) Sensor
Any indoor air quality or CO 20 mA output can be used as the IAQ sensor. The controller will modulate the outdoor-air damper to provide ventilation based on the sensor output and the IAQ se tting of the con trol­ler. The CO the minimum position (IAQ minimum damper position set point) to the maximum position (occupied minimum damper position). When there is no CO unoccupied minimum pos ition. When there is a CO damper will be between the IAQ minimum economizer set point position and the occup ied min imum da mper pos ition.
Mount the sensor according to manufacturer specifications. In order to wire this sensor, an accessory 5-pin plug (part number CRE+PLUG001A00) is required. See Fig. 22.
The IAQ sensor is wired to the g round an d IAQ w ires in the harness. The accessory 5-pin wiring plug is connected to pins 13-17 of J3 on the EconoMi$er+ controller. Push the plug down onto the pins of the EconoMi$e r+ controller to instal l.
sensor will modulate the outdoor-air damper from
2
ACCESSORY
OUTDOOR AIR
HUMIDITY SENSOR
——
Required —
CRHUMDSN001B00
Required —
CRHUMDSN001B00
sensor that provides a 4 to
2
call, the damper will go to the
2
Pins 13 and 14 are used for the IAQ sensor. Pins 15-17 are
G. Outdoor Air Temperature (OAT) Sensor (Provided)
The outdoor air temperature sensor is a 10K thermistor used to measure the outdoor-air temperature. The sensor controls EconoMi$er+ changeover and compressor lockout. The sensor is factory-installed on the EconoMi$er+ in the outdoor air­stream. The operating range of temperature measurement is 0° to158 F. See Tables 5 and 6 for thermistor resistan ce and resolution values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
The user can read the value of the sensor using the Read mode, described in the Start-Up section.
H. Supply Air Temperature (SAT) Sensor (Provided)
The supply air temperature sensor is a 10K thermistor located at the inlet to the indoor fan. This sensor must be field installed . Th e o per ating range of temperature me as ur e­ment is 0° to158 F. See Tables 5 and 6 for thermistor resis­tance and resolution values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
used for the field-installed remote potentiometer. Connect the IAQ sensor to the BRN and WHT wires o f the accessor y 5-pin plug.
NOTE: Pin numbers are not sh own on th e cont roller. They are provided only as reference for the installer. On the EconoMi$er+ board, they numbered 1-17 from left to right, but only the 1 and the 17 are printed on the board.
Sensor wiring should be extended with wire and wire nuts and routed to the IAQ sensor location. Adjust the IAQ set­ting at the controller to correspond to the IAQ voltage output of the sensor at the user-determined set point. See Fig. 26. Power the sensor with a field-supplied transformer.
J. Return Air Temperature (RAT) Sensor
The EconoMi$er+ controller will accept input from the acces­sory 10K return air temperature sensor (CRTEMPSN001A00) in addition to the outdoor air temperature sensor shipped with the EconoMi$er+. By using both sensors, the outdoor air and the return air temperatures are compared (differential dry bulb) for optimal energy savings. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor looks like an eye let terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
ACCESSORY INDOOR
RETURN AIR
HUMIDITY SENSOR
Required —
CRHUMDSN001B00
call, the
2
21
Page 22
The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
Mount the return air temp erature sens or on the Eco noMi$er+, through pre-punched holes. See F ig . 2 7.
The return air temperature (RAT) sensor is provided with a 2-wire, 42-in. long wiring harness with a 2-pin connector. The plug is installed on pins 5 and 6 on J3 of the EconoMi$er+ controller. The pins are labeled with a ground symbol and RAT on the EconoMi$er+ controller. See Fig. 22. The red wire of the harness is connected to pin 5 (ground). The black wire of the harness is connected to pin 6 (RAT). The wiring harness should be routed from the EconoMi$er+ controller to the sensor. The controller compares the temper­atures of the two ai rstream s, chooses the be st one, and mod ­ulates the EconoMi$er+ actuator accordingly.
This 10K thermistor is used to measure the return air temperature vs. resistance curve, per Table 5. The range of temperature measurement is between 0° and 158 F. See Table 6 for resolution.
K. Outdoor Air Humidity Sensor
The EconoMi$er+ controller accepts input from the accessory outdoor air humidity sensor in ad dition to the out door air tem­perature sensor shipped with the EconoMi$er+. By using both sensors, the total ent halpy of the out sid e air is ca lcula ted.
Mount the outdoor-air humidity sensor in to the EconoMi$er+, through the pre-punched holes. See Fig. 28. The outdoor-air humidity senso r is provided with a 2-wire, 42-in. wiring harness with a 2-pin connector. The plug is installed on pins 11 and 12 on J3 of the EconoMi$er+ con­troller. The pins are labeled ORH and VREF on the EconoMi$er+ controller. See Fig. 22. The orange wire of the harness is connected to pin 11 (ORH). The blue wire of the harness is connected to pin 12 (VREF). The wiring harness should be rout ed from the Eco noMi$ er+ cont roll er to the se n­sor location.
The outdoor enthalpy changeover curve is set at the EconoMi$er+ controller. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
L. Indoor Air Humidity Sensor
For differential enthalpy sensing, the EconoMi$er+ control­ler uses the standard outdoor air temperature sensor, the outdoor air humidity sensor, and the optional indoor air humidity sensor, an optional return air t emperature sensor (RAT). The indoor-air humidity sensor is provided with a 2-wire, 42-in. wiring harness with a 2-pin connector. The plug is installed on pins 8 and 9 on J3 of the EconoMi$er+ controller. The pins are labeled IRH and VREF on the EconoMi$er+ controller. See Fig. 22. The orange wire of the harness is connected to pin 8 (IRH). The blue wire of th e har­ness is connected to pin 9 (VREF). The wiring harness should be extended with wires and wire nuts and routed from the EconoMi$er+ controller to the sensor location. The EconoMi$er+ controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er+ use.
The controller select s the lower enthalpy air (return or out­door) for cooling. For example, when the outdoor air has a lower enthalpy than the return air , the EconoMi$er+ control­ler opens the damp er to bring in outdoor air for free cooling.
Mount the return-air humidity sensor in the return-air duct. See Fig. 31.
The outdoor enthalpy changeover curve is set with at the EconoMi$er+ controller. The selectable curves are A, B, C, and D. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
CO SENSOR MAX RANGE SETTING
2
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
800 ppm 900 ppm 1000 ppm 1100 ppm
Fig. 26 — Indoor Air Quality Voltage Setting
ECONOMI$ER+ CONTROLLER
ACTUATOR
RETURN AIR
TEMP SENSOR
(HIDDEN)
CURB
VERTICAL ECONOMI$ER+
(3 TO 12 1/2 TON UNITS)
(SIDE VIEW)
HOOD
GROMMET
INDOOR AIR HUMIDITY SENSOR
Fig. 27 — Return Air Temperature Sensor
22
Page 23
Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors
(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve
TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE
CF ohmsCF ohmsCF ohms 120 248.0 390.0 66 150.8 2,011.0 12 53.6 18,090.0 119 246.2 401.2 65 149.0 2,083.0 11 51.8 18,972.0 118 244.4 412.8 64 147.2 2,157.0 10 50.0 19,903.0 117 242.6 424.8 63 145.4 2,235.0 9 48.2 20,883.0 116 240.8 437.2 62 143.6 2,315.0 8 46.4 21,918.0 115 239.0 450.0 61 141.8 2,400.0 7 44.6 23,013.0 114 237.2 462.5 60 140.0 2,488.0 6 42.8 24,117.0 113 235.4 475.5 59 138.2 2,579.0 5 41.0 25,396.0 112 233.6 488.9 58 136.4 2,675.0 4 39.2 26,686.0 111 231.8 502.7 57 134.6 2,774.0 3 37.4 28,052.0 110 230.0 517.0 56 132.8 2,878.0 2 35.6 29,498.0 109 228.2 531.0 55 131.0 2,986.0 1 33.8 31,030.0 108 226.4 545.6 54 129.2 3,099.0 0 32.0 32,654.0 107 224.6 560.5 53 127.4 3,217.0 –1 30.2 34,367.0 106 222.8 576.0 52 125.6 3,340.0 –2 28.4 36,182.0 105 221.0 592.0 51 123.8 3,469.0 –3 26.6 38,109.0 104 219.2 608.5 50 122.0 3,603.0 –4 24.8 40,153.0 103 217.4 625.5 49 120.2 3,743.0 –5 23.0 42,324.0 102 215.6 643.0 48 118.4 3,889.0 –6 21.2 44,617.0 101 213.8 661.2 47 116.6 4,042.0 –7 19.4 47,052.0 100 212.0 680.0 46 114.8 4,203.0 –8 17.6 49,640.0
99 210.2 700.0 45 113.0 4,370.0 –9 15.8 52,392.0 98 208.4 720.6 44 111.2 4,544.0 –10 14.0 55,319.0 97 206.6 742.0 43 109.4 4,727.0 –11 12.2 58,415.0 96 204.8 764.1 42 107.6 4,918.0 –12 10.4 61,711.0 95 203.0 787.0 41 105.8 5,117.0 –13 8.6 65,219.0 94 201.2 810.8 40 104.0 5,327.0 –14 6.8 68,957.0 93 199.4 835.5 39 102.2 5,546.0 –15 5.0 72,940.0 92 197.6 861.0 38 100.4 5,774.0 –16 3.2 77,162.0 91 195.8 888.5 37 98.6 6,014.0 –17 1.4 81,662.0 90 194.0 915.0 36 96.8 6,266.0 –18 –0.4 86,463.0 89 192.2 944.0 35 95.0 6,530.0 –19 –2.2 91,588.0 88 190.4 974.0 34 93.2 6,806.0 –20 –4.0 97,060.0 87 188.6 1005.0 33 91.4 7,096.0 –21 –5.8 102,868.0 86 186.8 1037.0 32 89.6 7,401.0 –22 –7.6 109,075.0 85 185.0 1070.0 31 87.8 7,720.0 –23 –9.4 115,710.0 84 183.2 1104.0 30 86.0 8,056.0 –24 –11.2 122,807.0 83 181.4 1140.0 29 84.2 8,407.0 –25 –13.0 130,402.0 82 179.6 1177.0 28 82.4 8,776.0 –26 –14.8 138,482.0 81 177.8 1215.0 27 80.6 9,164.0 –27 –16.6 147,134.0 80 176.0 1255.0 26 78.8 9,571.0 –28 –18.4 156,404.0 79 174.2 1297.0 25 77.0 10,000.0 –29 –20.2 166,342.0 78 172.4 1340.0 24 75.2 10,449.0 –30 –22.0 177,000.0 77 170.6 1385.0 23 73.4 10,921.0 –31 –23.8 188,340.0 76 168.8 1431.0 22 71.6 11,418.0 –32 –25.6 200,510.0 75 167.0 1480.0 21 69.8 11,942.0 –33 –27.4 213,570.0 74 165.2 1530.0 20 68.0 12,493.0 –34 –29.2 227,610.0 73 163.4 1582.0 19 66.2 13,071.0 –35 –31.0 242,700.0 72 161.6 1637.0 18 64.4 13,681.0 –36 –32.8 258,730.0 71 159.8 1693.0 17 62.6 14,323.0 –37 –34.6 275,970.0 70 158.0 1752.0 16 60.8 15,000.0 –38 –36.4 294,520.0 69 156.2 1813.0 15 59.0 15,714.0 –39 –38.2 314,490.0 68 154.4 1876.0 14 57.2 16,464.0 –40 –40.0 336,000.0 67 152.6 1943.0 13 55.4 17,255.0
23
Page 24
Table 6 — Outdoor Air, Return Air, and Supply Air
Temperature Sensors (CRTEMPSN001A00 or HH79NZ039)
—Thermistor Resolution
RANGE
Low High
FF F
–41 –18 4.0 –17 14 2.0
15 28 1.0 29 47 0.8 48 86 0.7
87 108 0.8 109 126 1.0 127 171 2.0 127 195 4.0
RESOLUTION
ECONOMI$ER+
ECONOMI$ER+ CONTROLLER
WIRING GROMMET
OUTDOOR AIR HUMIDITY SENSOR
OUTDOOR AIR TEMPERATURE SENSOR
Fig. 28 — Outdoor-Air Humidity Sensor
RELIEF BLADE
Fig. 29 — Enthalpy Changeover Settings
24
Page 25
20
18
16
14
12
10
CURRENT IN mA
8
6
4
0102030
RH — Relative Humidity
50
40
HUMIDITY IN % RH
Fig. 30 — Humidity Sensor Current vs. Humidity
ECONOMI$ER+ CONTROLLER
ECONOMI$ER+
GROMMET
RETURN AIR HUMIDITY SENSOR
RETURN DUCT (FIELD-PROVIDED)
Fig. 31 — Return Air Humidity Sensor
M. Occupied/Unoccupied Switch
The EconoMi$er+ supports the use of a field-supplied occupied/
unoccupied switch. When the switch is closed it provides a
24-vac signal to the unit for occu pied mode and when open,
there is no signal to indicate unoccupied mode. The control can
be configured to allow di fferent m inimum e conomizer damper
positions and t o control how mechanical cool ing will and wi ll
not be used in the occupied mode.
NOTE: The remote potentiometer (see below) will overri de th e
occupied minimum position if the potentiometer setting is
greater than the occupied minimum position.
For 3 to 12
1
/2 ton units, a wire from J1-OCC (pin 4) and a wire from J1-24V (pin 5) a re wire -nutted together to jumper the terminals.
CURRENT
(mA)
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
60 70
RH (%)
10 20 30 40 50 60 70 80 90
80
90
100
An occupied/unoccupied switch can be field-installed in place of the jumper to allo w the use r to forc e t he co ntrol i nto o ccu­pied or unoccupied mode of operation for EconoMi$er+ damper position. The occupied/unoccupied switch is required if the user wants to use unoccupied free cooling or different EconoMi$er+ damper vent positions in the unoccupied mode.
N. Power Exhaust
Refer to the Accessory Power Exhaust installation instructions for information o n i n stal ling the power exhaust acc es so ry.
O. Remote EconoMi$er+ Enable Control
When the control is used with energy management systems that enable and disable the EconoMi$er+, the user can install a field­supplied enable/disable switch. The switch must be wired in series with a 3K ohm, 1 watt or greater resistor. The switch is wired to terminals ORH (pin 11) and VREF (pin 12) on J3. Refer to the Start-Up section for details on how to configure the control.
P. R e mote Potentiometer Occupied Minimum Position
The occupied minimum position set point remote potentiom­eter (field-supplied) is used when requiring additional tem­porary ventilation. The remote potentiometer (10K ohm ­closed damper, 100K ohm - open damper) will only control the occupied minimum position.
The accessory 5-in wiring plug, CRE+PLUG001A00 is required to connect the potentiometer.
The plug is installed on pins 15, 16 and 17 on J3 of the EconoMi$er+ controller. The pins are labeled with the ground symbol, MIN and VREF on the EconoMi$er+ controller. See Fig. 22. The pink wire from the harness is connected to pin 15 (ground symbol). The gray wire fr om the harness is con­nected to pin 16 (MIN). The yello w wire from the harn ess is connected to pin 16 (VREF). The wiring harness should be extended with wires and wire nuts and routed from the EconoMi$er+ controller to the remote potentiometer location.
NOTE: Pins 13 (ground symbol) and 14 (IAQ), which are wired to the accessory 5-pin plug, are not used for the remote potentiometer installation. They are used for an accessory IAQ sensor (if required).
25
Page 26
The unoccupied m ini mum posi tio n ca n onl y b e se t a t the co n­troller. The occupied minimum position set point configured at the EconoMi$er+ controller should be set to 0 when using a remote potentiometer. The occupied minimum position will also be used as part of the IAQ routing; it will be the maximum position the damper moves to when there is an IAQ call.
If the remote potentiometer (occupied) position is greater than the EconoMi$er+ controller unoccupied minimum posi­tion, then the remote potentiometer setting will be used. The remote potentiometer is field supplied and must be a 3-wire, linear potentiometer with a resistance between 10K ohm and 100K ohm (such as the Honeywell S963B1128).
Q.Demand Ventilation Control
Demand ventilation control uses an IAQ sensor (CRE+PLUG001A00 required) to control the amount of out­side air admitted into the system. Normally, the minimum position of the EconoMi$ er+ damper is est ablished based on the demand occ upancy of the space. The IAQ s ensor wil l be used to modulate the EconoMi$er+ minimum damper posi­tion below the normal minimum position based on full occu­pancy. The lowe r li mit is called the base ventilation r at e. See Fig. 32.
If there is no IAQ signal the damper will be in the unoccu­pied minimum position (configuration item number 3). If there is an IAQ signal the damper will be in the occupied minimum position (configuration item number 15), unless the remote potentiometer is used to override it.
For the demand ventilation control logic, the user configures the lower and upper actuator position to establish the base ventilation rate (IAQMIN_SP) and the de sign ventilation rate (ECONOMIN_SP) for full occupancy. When the EconoMi$er+ damper is being modulated for demand ventilation control, the damper position will be between IAQMIN_SP and ECONOMIN_SP. The upper IAQ differential set point is DAQHI. The lower IAQ differential set point is DAQLO.
The differential set points represent the differential CO level (in ppm) above the outdoor reference IAQ le vels. Nor­mally, the outdoor ref er ence IAQ le vel s ar e a ro und 4 0 0 ppm , but the value should be configured based on the reference levels taken at the job site.
DAMPER
POSTION
FULL OCCUPANCY
ECONOMIZER MINIMUM OCCUPIED DAMPER POSITION (ECONOMIN_SP)
IAQ MINIMUM ECONOMIZER POSITION SET POINT (IAQMIN_SP)
OUTDOOR REFERENCE LEVEL (OAQ)= 400
VENTILATION RATE
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
100 500
AQ DIFFERENTIAL LOW (DAQLO)
1100
AQ DIFFERENTIAL HIGH (DAQHI)
INSIDE/OUTSIDE CO
700
INSIDE CO
CO LEVEL
2
DIFFERENTIAL
2
CONCENTRATION
2
Fig. 32 — Demand Ventilation Control
The following equation is used to determine EconoMi$er+ damper position (ECONOMIN_POS):
IAQMIN_SP + =
(ECONOMIN_SP – IAQMIN_SP) * (IAQ –OAQ –DAQLO)
(DAQHI – DAQLO)
R. CO2Sensor Configuration
The CO
sensor has preset standard voltage settings that
2
can be selected anytime afte r the sensor is pow ered up. See Table 7.
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode 2 times. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See Table 7.
4. Press Enter to lock in the selection.
Press Mode to exit and resume normal operation. The cus­tom settings of the CO
sensor can be changed any time after
2
the sensor is energized. Follow the steps below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
S. Dehumidification of Fresh Air with Demand Control Ventilation (DCV)
Information from ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) indi cates that
2
the largest humidity load on any zone is the fresh air intro­duced. For some applications, a device such as a energy recovery unit is added to reduce the moist ure content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling pro­cesses are more than adequate to remove the humidity loads for most commercial applications.
This makes the control of the dehumidification device simple when using the enthalpy or differential enthalpy sensor. The enthalpy sensor or diffe rential enthalpy sensor is installed on the equipment to determine economizer operation. The high enthalpy signal from the temperature and humidity sensors or differential temperature and humidity sensors can be used to turn on the outdoor air moisture removal device any time fresh air is required for the space.
The energy recovery device should be sized for maximum latent and sensible conditioning at maximum ventilation on a design day.
A calculation for leaving-air temperature on a low ambient, low ventilation day should also be done to determine the supply-air temperature of the return and pre-conditioned outside air. The design should produce air temperature somewhat near room conditions to prevent reheat of the air mixture. The energy recovery device should be interlocked with the heat to turn off the device when in the heat mode.
26
Page 27
Tab le 7 — CO2Sensor* Standard Settings
SETTING EQUIPMENT OUTPUT
1
Interface with Standard
2 Proportional Any 7-20 mA 0-2000 1000 50
Building Control System
3 Exponential Any 4-20 mA 0-2000 1100 50 4 5 Proportional 20 4-20 mA 0- 900 900 50
Economizer
6 Exponential 15 4-20 mA 0-1100 1100 50 7 Exponential 20 4-20 mA 0- 900 900 50 8 Health & Safety Proportional 4-20 mA 0-9999 5000 500 9 Parking/Air Intakes/ Loading Docks Proportional 4-20 mA 0-2000 700 50
LEGEND
ppm — Parts Per Million
*Available sensor part numbers are listed in Table 4.
Proportional Any 4-20 mA 0-2000 1000 50
Proportional 15 4-20 mA 0-1100 1100 50
VENTILATION
RATE
(cfm/Person)
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
Adjust evaporator-fan speed to meet jobsite requirement. Table 8 shows fan rpm at motor pulley settings and Table 9
shows motor efficiencies. Table 10 shows motor performance. Refer to Fan Performance Tables 11-30 to determine fan speed settings. Fan motor pulleys are factory set for speed shown in Tables 1A and 1B.
To change fan speed:
1. Shut off unit power supply and install lockout tag.
2. Loosen belt by loosening fan motor mounting plate nuts (see Fig. 33 and 34).
3. Loosen movable pulley flange setscrew (see Fig. 35).
4. Screw movable flange toward fixed flange to increase
ANALOG
OUTPUT
deflection with 5 to 10 lb of force) and tighten mount­ing nuts (see Fig. 33).
Units 120-151 — Slide motor mounting plate down­ward to tighten belt tension. ( 5 to 10 lb of force.) Secure motor mounting plate nuts. See Fig. 34.
3. Adjust bolt and nut on mounting plate to secure motor in fixed position.
Realign fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting plate.
CONTROL
CO
2
RANGE (ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
1
/2-in. deflection with
fan speed and away from fixed flange to decrease fan speed. Incre asing fan speed in creases load on mo tor. Do not exceed maximum speed specified in Tables 1A and 1B.
5. Set movable flange at nearest flat of pulley hub and tighten setscrew (see Tables 1A and 1B for speed change for each full turn of pulley flange).
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting plate.
MOTOR MOUNTING PLATE NUTS
To adjust belt tension (see Fig. 33 and 34):
1. Loosen fan motor mounting plate nuts.
2. Units 090-103 — Slide motor mounting plate away from fan scroll for proper belt tension (
1
/2-in.
Fig. 33 — Typical Belt-Drive Motor Mounting
for Sizes 090-103
RELAY
HYSTERESIS
(ppm)
27
Page 28
Fig. 34 — Typical Belt-Drive Motor Mounting
for Sizes 120-151
Tabl e 8 — Fan Rpm at Motor Pulley Settings*
Fig. 35 — Evaporator-Fan Pulley Adjustment
UNIT 580F
0
1
/
2
11
1
/
2
MOTOR PULLEY TURNS OPEN
22
1
/
2
33
1
/
2
44
1
/
2
55 090,091† 840 815 790 765 740 715 690 665 635 615 590 090,091** 935 910 885 860 835 810 785 760 735 710 685 090,091†† 1080 1025 1007 988 970 952 933 915 897 878 860 102,103† 935 910 885 860 835 810 785 760 735 710 685 102,103†† 1080 1025 1007 988 970 952 933 915 897 878 860 120,121† 935 910 885 860 835 810 785 760 735 710 685 120,121** 1085 1060 1035 1010 985 960 935 910 885 860 835 120,121†† 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830 150,151† 1080 1060 1035 1015 990 970 950 925 905 880 860 150,151** 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
*Approximate fan rpm shown.
†Indicates standard motor and drive package.
**Indicates alternate motor and drive package.
††Indicates high-static motor and drive package.
Table 9 — Evaporator-Fan Motor Efficiency
UNIT
580F 090-121 80 150,151 87
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
MOTOR EFFICIENCY
(%)
1
/
6
2
28
Page 29
Table 10 — Evaporator-Fan Motor Performance
UNIT 580F
090,091
102,103
120,121
150,151
EVAPORATOR-FAN
MOTOR
Standard,
Alternate
High Static
Standard
High Static
Standard
Alternate
High Static
Standard
Alternate
UNIT
VO LTAGE
208/230
460 3.0 575 3.0
208/230
460 5.5 575 5.5
208/230
460 3.0 575 3.0
208/230
460 5.5 575 5.5
208/230
460 3.0 575 3.0
208/230
460 3.9 575 3.9
208/230
460 8.5 575 8.5
208/230
460 5.5 575 5.5
208/230
460 8.5 575 8.5
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
2.40 2120
3.70 3313
2.40 2120
3.70 3313
2.40 2120
2.90 2615
5.25 4400
3.70 3313
5.25 4400
MAXIMUM ACCEPTABLE
OPERAT ING WATTS
MAXIMUM
AMP DRAW
6.7
12.2
6.7
12.2
6.7
8.6
17.3
12.2
17.3
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit war­ranty will not be affected.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
2. High-static motor not available on size 150 and 151 units.
be affected. See Evaporator-Fan Motor Performance data in Tables 10 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
29
Page 30
Table 11 — Fan Performance 580F090,091 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
AIRFLOW
(Cfm)
521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823
597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 —— — 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 —— — 694 1.47 1374 758 1.78 1660 816 2.10 1961 — 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 727 1.71 1596 789 2.03 1896 845 2.37 2210 —— — —— — 744 1.84 1716 804 2.17 2023 — 752 1.91 1778 812 2.24 2089
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2250 839 1.86 1735 889 2.18 2032 —— — —— — —— — 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
844 1.90 1773 893 2.22 2073 —— — —— — —— — 854 1.99 1855 903 2.32 2159 —— — —— — —— — 865 2.08 1940 —— — —— — —— — —— — 870 2.13 1985 —— — —— — —— — —— — 875 2.18 2031 —— — —— — —— — —— — 886 2.28 2126 —— — —— — —— — —— — 897 2.39 2227 —— — —— — —— — —— —
—— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— —
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 590 to 840 rpm. All other rpms require field-
supplied drive.
30
Page 31
Table12—FanPerformance 580F090,091 — Vertical Discharge Units; Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
AIRFLOW
(Cfm)
521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152
694 1.47 1374 758 1.78 1660 816 2.10 1961 — 711 1.59 1482 773 1.90 1775 831 2.23 2082 — 727 1.71 1596 789 2.03 1896 845 2.37 2210 — 744 1.84 1716 804 2.17 2023 — 752 1.91 1778 812 2.24 2089
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2250 839 1.86 1735 889 2.18 2032 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
844 1.90 1773 893 2.22 2073 — 854 1.99 1855 903 2.32 2159 — 865 2.08 1940 — 870 2.13 1985 — 875 2.18 2031 — 886 2.28 2126 — 897 2.39 2227
—— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— —
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
31
Page 32
Table13—FanPerformance 580F090,091 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2250 513 0.54 505 595 0.76 713 665 1.01 940 728 1.27 1187 786 1.56 1453 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
AIRFLOW
(Cfm)
521 0.57 531 601 0.79 741 671 1.04 972 734 1.31 1222 791 1.60 1489 535 0.63 584 615 0.86 802 684 1.11 1038 745 1.39 1293 802 1.68 1566 551 0.69 642 628 0.93 866 696 1.19 1109 757 1.47 1369 813 1.77 1647 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 933 2.93 2737 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 946 3.09 2877 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 959 3.24 3023 752 1.91 1778 812 2.24 2089 867 2.59 2413 918 2.95 2750 966 3.32 3100
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2250 839 1.86 1735 889 2.18 2032 935 2.52 2345 980 2.87 2673 1022 3.23 3015 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
844 1.90 1773 893 2.22 2073 940 2.56 2389 984 2.91 2718 1027 3.28 3062 854 1.99 1855 903 2.32 2159 950 2.66 2478 993 3.02 2812 1035 3.39 3159
865 2.08 1940 913 2.41 2249 959 2.76 2573 1003 3.12 2911 1044 3.50 3261 870 2.13 1985 918 2.46 2296 964 2.81 2622 1008 3.18 2962 1049 3.55 3315 875 2.18 2031 923 2.51 2344 969 2.87 2673 1012 3.23 3014 1054 3.61 3370 886 2.28 2126 934 2.62 2445 979 2.98 2777 1022 3.35 3123 — 897 2.39 2227 944 2.73 2550 989 3.10 2888 1032 3.47 3238 — 908 2.50 2333 955 2.85 2661 1000 3.22 3003 1042 3.60 3358 — 920 2.62 2443 966 2.98 2777 1010 3.35 3123 — 931 2.75 2560 977 3.11 2899 1021 3.49 3250 — 943 2.88 2682 989 3.25 3026 1032 3.63 3383 — 955 3.01 2810 1000 3.39 3159 — 967 3.16 2945 1012 3.54 3299 — 980 3.31 3084 1024 3.69 3445 — 992 3.46 3230
1005 3.63 3383
—— — —— — —— — —— — —— —
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
32
Page 33
Table 14 — Fan Performance 580F102,103 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 3700 744 1.84 1716 804 2.17 2023 3750 752 1.91 1778 812 2.24 2089 3800 761 1.98 1842 820 2.31 2156 3900 777 2.12 1974 4000 794 2.27 2113 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4250 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 870 2.13 1985 2600 875 2.18 2031 2700 886 2.28 2126 2800 897 2.39 2227 2900 —— — —— — —— — —— — —— — 3000 —— — —— — —— — —— — —— — 3100 —— — —— — —— — —— — —— — 3200 —— — —— — —— — —— — —— — 3300 —— — —— — —— — —— — —— — 3400 —— — —— — —— — —— — —— — 3500 —— — —— — —— — —— — —— — 3600 —— — —— — —— — —— — —— — 3700 —— — —— — —— — —— — —— — 3750 —— — —— — —— — —— — —— — 3800 —— — —— — —— — —— — —— — 3900 —— — —— — —— — —— — —— — 4000 —— — —— — —— — —— — —— — 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4250 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
33
Page 34
Table15—FanPerformance 580F102,103 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 558 0.72 673 635 0.97 900 702 1.23 1146 763 1.51 1409 818 1.81 1689 2600 566 0.76 705 642 1.00 935 709 1.27 1183 769 1.55 1450 824 1.86 1732 2700 582 0.83 771 656 1.08 1008 721 1.35 1263 781 1.65 1535 835 1.95 1823 2800 597 0.90 842 670 1.16 1086 734 1.44 1347 793 1.74 1625 847 2.06 1917 2900 613 0.98 918 684 1.25 1169 748 1.54 1436 805 1.84 1720 859 2.16 2019 3000 629 1.07 999 699 1.35 1256 761 1.64 1530 818 1.95 1820 871 2.28 2125 3100 645 1.16 1085 713 1.45 1349 775 1.75 1630 831 2.06 1925 883 2.40 2235 3200 662 1.26 1176 728 1.55 1448 788 1.86 1734 844 2.18 2036 895 2.52 2352 3300 678 1.36 1272 743 1.66 1551 802 1.98 1845 857 2.31 2152 908 2.65 2475 3400 694 1.47 1374 758 1.78 1660 816 2.10 1961 870 2.44 2275 920 2.79 2603 3500 711 1.59 1482 773 1.90 1775 831 2.23 2082 884 2.58 2402 933 2.93 2737 3600 727 1.71 1596 789 2.03 1896 845 2.37 2210 897 2.72 2537 946 3.09 2877 3700 744 1.84 1716 804 2.17 2023 860 2.51 2343 911 2.87 2677 959 3.24 3023 3750 752 1.91 1778 812 2.24 2089 867 2.59 2413 918 2.95 2750 966 3.32 3100 3800 761 1.98 1842 820 2.31 2156 874 2.66 2484 925 3.03 2824 973 3.41 3177 3900 777 2.12 1974 835 2.46 2296 889 2.82 2630 939 3.19 2977 986 3.58 3336 4000 794 2.27 2113 851 2.62 2442 904 2.99 2784 953 3.36 3137 4100 811 2.42 2259 867 2.78 2595 919 3.16 2944 968 3.54 3304 4200 828 2.59 2412 883 2.95 2755 934 3.34 3110 4250 837 2.67 2490 891 3.04 2838 942 3.43 3197
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 870 2.13 1985 918 2.46 2296 964 2.81 2622 1008 3.18 2962 1049 3.55 3315 2600 875 2.18 2031 923 2.51 2344 969 2.87 2673 1012 3.23 3014 1054 3.61 3370 2700 886 2.28 2126 934 2.62 2445 979 2.98 2777 1022 3.35 3123 2800 897 2.39 2227 944 2.73 2550 989 3.10 2888 1032 3.47 3238 2900 908 2.50 2333 955 2.85 2661 1000 3.22 3003 1042 3.60 3358 3000 920 2.62 2443 966 2.98 2777 1010 3.35 3123 3100 931 2.75 2560 977 3.11 2899 1021 3.49 3250 3200 943 2.88 2682 989 3.25 3026 1032 3.63 3383 3300 955 3.01 2810 1000 3.39 3159 3400 967 3.16 2945 1012 3.54 3299 3500 980 3.31 3084 1024 3.69 3445 3600 992 3.46 3230 3700 1005 3.63 3383 3750 —— — —— — —— — —— — —— — 3800 —— — —— — —— — —— — —— — 3900 —— — —— — —— — —— — —— — 4000 —— — —— — —— — —— — —— — 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4250 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 29 for General Fan Performance Notes.
34
Page 35
Table 16 — Fan Performance 580F120,121 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 —— — 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 —— — 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 —— — —— — 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 —— — —— — 4300 989 1.93 1694 1039 2.19 1920 —— — —— — —— — 4400 1009 2.06 1804 1058 2.32 2034 —— — —— — —— — 4500 1030 2.19 1919 —— — —— — —— — —— — 4600 1051 2.32 2039 —— — —— — —— — —— — 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 —— — —— — 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 —— — —— — 3200 1041 1.97 1732 1088 2.22 1947 —— — —— — —— — 3300 1056 2.07 1817 1102 2.32 2036 —— — —— — —— — 3400 1071 2.17 1905 —— — —— — —— — —— — 3500 1087 2.28 1998 —— — —— — —— — —— — 3600 1102 2.39 2094 —— — —— — —— — —— — 3700 —— — —— — —— — —— — —— — 3800 —— — —— — —— — —— — —— — 3900 —— — —— — —— — —— — —— — 4000 —— — —— — —— — —— — —— — 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4300 —— — —— — —— — —— — —— — 4400 —— — —— — —— — —— — —— — 4500 —— — —— — —— — —— — —— — 4600 —— — —— — —— — —— — —— — 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
35
Page 36
Table17—FanPerformance 580120,121 — Vertical Discharge Units; Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 1106 2.48 2173 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 1123 2.60 2283 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 1095 2.46 2159 1140 2.73 2397 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 1113 2.59 2274 1157 2.87 2516 4300 989 1.93 1694 1039 2.19 1920 1086 2.45 2153 1131 2.73 2393 —— — 4400 1009 2.06 1804 1058 2.32 2034 1105 2.59 2272 1149 2.87 2517 —— — 4500 1030 2.19 1919 1078 2.45 2154 1124 2.73 2397 —— — —— — 4600 1051 2.32 2039 1098 2.60 2279 1143 2.88 2527 —— — —— — 4700 1071 2.47 2165 1118 2.75 2409 —— — —— — —— — 4800 1092 2.62 2295 1138 2.90 2545 —— — —— — —— — 4900 1113 2.77 2431 —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 1148 2.53 2219 1190 2.79 2449 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 1161 2.63 2308 1202 2.89 2540 3200 1041 1.97 1732 1088 2.22 1947 1132 2.47 2170 1174 2.73 2400 —— — 3300 1056 2.07 1817 1102 2.32 2036 1146 2.58 2262 1188 2.84 2496 —— — 3400 1071 2.17 1905 1116 2.43 2128 1160 2.69 2359 —— — —— — 3500 1087 2.28 1998 1131 2.53 2225 1174 2.80 2459 —— — —— — 3600 1102 2.39 2094 1146 2.65 2326 —— — —— — —— — 3700 1118 2.50 2195 1162 2.77 2430 —— — —— — —— — 3800 1134 2.62 2300 1177 2.89 2539 —— — —— — —— — 3900 1150 2.75 2410 —— — —— — —— — —— — 4000 1167 2.88 2524 —— — —— — —— — —— — 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4300 —— — —— — —— — —— — —— — 4400 —— — —— — —— — —— — —— — 4500 —— — —— — —— — —— — —— — 4600 —— — —— — —— — —— — —— — 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 835 to 1085 rpm. All other rpms require field-
supplied drive.
36
Page 37
Table18—FanPerformance 580F120,121 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 726 0.75 656 793 0.94 822 853 1.14 997 910 1.35 1181 962 1.56 1373 3100 746 0.81 713 811 1.01 883 870 1.21 1062 926 1.42 1250 978 1.65 1447 3200 766 0.88 773 829 1.08 947 887 1.29 1131 942 1.51 1323 993 1.74 1524 3300 786 0.95 836 847 1.16 1016 905 1.37 1204 958 1.60 1400 1008 1.83 1604 3400 806 1.03 904 866 1.24 1088 922 1.46 1280 975 1.69 1481 1024 1.92 1689 3500 826 1.11 975 885 1.33 1163 940 1.55 1360 991 1.78 1565 1040 2.03 1778 3600 846 1.20 1050 904 1.42 1243 958 1.65 1444 1008 1.88 1654 1056 2.13 1870 3700 866 1.29 1129 923 1.51 1327 975 1.75 1532 1025 1.99 1746 1073 2.24 1967 3800 886 1.38 1212 942 1.61 1415 994 1.85 1625 1043 2.10 1843 1089 2.36 2068 3900 907 1.48 1299 961 1.72 1507 1012 1.96 1722 1060 2.21 1944 1106 2.48 2173 4000 927 1.58 1391 980 1.83 1603 1030 2.08 1823 1078 2.33 2049 1123 2.60 2283 4100 948 1.69 1487 1000 1.94 1704 1049 2.20 1928 1095 2.46 2159 1140 2.73 2397 4200 968 1.81 1588 1019 2.06 1809 1067 2.32 2038 1113 2.59 2274 1157 2.87 2516 4300 989 1.93 1694 1039 2.19 1920 1086 2.45 2153 1131 2.73 2393 1175 3.01 2640 4400 1009 2.06 1804 1058 2.32 2034 1105 2.59 2272 1149 2.87 2517 1192 3.15 2768 4500 1030 2.19 1919 1078 2.45 2154 1124 2.73 2397 1168 3.01 2646 1210 3.31 2901 4600 1051 2.32 2039 1098 2.60 2279 1143 2.88 2527 1186 3.17 2780 1228 3.46 3040 4700 1071 2.47 2165 1118 2.75 2409 1162 3.03 2661 1205 3.33 2919 1245 3.63 3184 4800 1092 2.62 2295 1138 2.90 2545 1181 3.19 2801 1223 3.49 3064 1264 3.80 3333 4900 1113 2.77 2431 1158 3.06 2685 1201 3.36 2947 1242 3.66 3214 1282 3.97 3487 5000 1134 2.93 2572 1178 3.23 2832 1220 3.53 3097 1261 3.84 3369 1300 4.16 3647
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 1012 1.79 1574 1060 2.03 1781 1105 2.28 1997 1148 2.53 2219 1190 2.79 2449 3100 1027 1.88 1651 1073 2.12 1863 1118 2.37 2081 1161 2.63 2308 1202 2.89 2540 3200 1041 1.97 1732 1088 2.22 1947 1132 2.47 2170 1174 2.73 2400 1215 3.00 2636 3300 1056 2.07 1817 1102 2.32 2036 1146 2.58 2262 1188 2.84 2496 1228 3.12 2735 3400 1071 2.17 1905 1116 2.43 2128 1160 2.69 2359 1201 2.96 2595 1241 3.23 2839 3500 1087 2.28 1998 1131 2.53 2225 1174 2.80 2459 1215 3.08 2699 1255 3.36 2946 3600 1102 2.39 2094 1146 2.65 2326 1188 2.92 2563 1229 3.20 2808 1268 3.48 3058 3700 1118 2.50 2195 1162 2.77 2430 1203 3.04 2672 1243 3.33 2920 1282 3.62 3174 3800 1134 2.62 2300 1177 2.89 2539 1218 3.17 2785 1258 3.46 3036 1296 3.75 3295 3900 1150 2.75 2410 1193 3.02 2653 1233 3.31 2902 1273 3.60 3158 1311 3.90 3420 4000 1167 2.88 2524 1208 3.16 2770 1249 3.45 3024 1287 3.74 3284 1325 4.04 3549 4100 1183 3.01 2642 1224 3.30 2893 1264 3.59 3151 1302 3.89 3414 1340 4.20 3683 4200 1200 3.15 2765 1240 3.44 3020 1280 3.74 3282 1318 4.04 3549 1355 4.36 3823 4300 1216 3.30 2893 1257 3.59 3152 1295 3.89 3418 1333 4.20 3690 1370 4.52 3967 4400 1233 3.45 3025 1273 3.75 3289 1311 4.05 3559 1349 4.37 3834 1385 4.69 4116 4500 1250 3.60 3163 1290 3.91 3431 1328 4.22 3705 1364 4.54 3985 —— — 4600 1268 3.77 3306 1306 4.08 3578 1344 4.39 3856 1380 4.72 4140 —— — 4700 1285 3.94 3454 1323 4.25 3730 1360 4.57 4013 1396 4.90 4300 —— — 4800 1303 4.11 3608 1340 4.43 3888 1377 4.76 4175 —— — —— — 4900 1320 4.29 3766 1357 4.62 4051 1394 4.95 4342 —— — —— — 5000 1338 4.48 3930 1375 4.81 4219 —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
37
Page 38
Table 19 — Fan Performance 580F150,151 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 5100 961 3.29 3068 1007 3.59 3345 5200 978 3.48 3241 5300 995 3.67 3420 5400 —— — —— — —— — —— — —— — 5500 —— — —— — —— — —— — —— — 5600 —— — —— — —— — —— — —— — 5700 —— — —— — —— — —— — —— — 5800 —— — —— — —— — —— — —— — 5900 —— — —— — —— — —— — —— — 6000 —— — —— — —— — —— — —— — 6100 —— — —— — —— — —— — —— — 6200 —— — —— — —— — —— — —— — 6300 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 —— — 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 —— — 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 —— — —— — 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 —— — —— — 4200 1066 3.22 3004 1112 3.50 3264 —— — —— — —— — 4300 1078 3.38 3148 1123 3.66 3413 —— — —— — —— — 4400 1090 3.54 3297 —— — —— — —— — —— — 4500 1103 3.70 3451 —— — —— — —— — —— — 4600 —— — —— — —— — —— — —— — 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— — 5100 —— — —— — —— — —— — —— — 5200 —— — —— — —— — —— — —— — 5300 —— — —— — —— — —— — —— — 5400 —— — —— — —— — —— — —— — 5500 —— — —— — —— — —— — —— — 5600 —— — —— — —— — —— — —— — 5700 —— — —— — —— — —— — —— — 5800 —— — —— — —— — —— — —— — 5900 —— — —— — —— — —— — —— — 6000 —— — —— — —— — —— — —— — 6100 —— — —— — —— — —— — —— — 6200 —— — —— — —— — —— — —— — 6300 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
38
Page 39
Table20—FanPerformance 580F150,151 — Vertical Discharge Units; Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 728 1.36 1266 789 1.58 1473 848 1.81 1686 904 2.04 1906 957 2.29 2132 3800 744 1.46 1361 804 1.69 1572 861 1.92 1790 916 2.16 2015 969 2.41 2246 3900 760 1.57 1460 819 1.80 1676 875 2.04 1899 929 2.28 2128 981 2.53 2364 4000 777 1.68 1563 834 1.91 1785 889 2.16 2012 942 2.41 2247 993 2.67 2487 4100 793 1.79 1672 850 2.04 1899 904 2.29 2132 956 2.54 2371 1006 2.80 2615 4200 810 1.92 1786 865 2.16 2018 918 2.42 2255 969 2.68 2499 1018 2.95 2748 4300 826 2.04 1906 880 2.30 2142 932 2.56 2385 983 2.82 2633 1031 3.10 2888 4400 843 2.18 2031 896 2.44 2272 947 2.70 2520 996 2.97 2773 1044 3.25 3032 4500 860 2.32 2161 912 2.58 2408 962 2.85 2660 1010 3.13 2918 1057 3.41 3182 4600 876 2.46 2297 927 2.73 2549 977 3.01 2807 1024 3.29 3070 1070 3.58 3338 4700 893 2.62 2439 943 2.89 2696 992 3.17 2958 1038 3.46 3226 1084 3.75 3500 4800 910 2.77 2587 959 3.06 2849 1007 3.34 3116 1053 3.63 3390 1098 3.93 3668 4900 927 2.94 2741 975 3.23 3008 1022 3.52 3280 1067 3.82 3558 1111 4.12 3841 5000 944 3.11 2901 991 3.40 3173 1037 3.70 3451 1082 4.00 3733 1125 4.31 4021 5100 961 3.29 3068 1007 3.59 3345 1053 3.89 3627 1096 4.20 3915 1139 4.51 4208 5200 978 3.48 3241 1024 3.78 3523 1068 4.09 3811 1111 4.40 4103 1153 4.72 4400 5300 995 3.67 3420 1040 3.98 3707 1084 4.29 4000 1126 4.61 4298 1168 4.93 4600 5400 1012 3.87 3606 1056 4.18 3899 1099 4.50 4196 1141 4.82 4499 1182 5.15 4806 5500 1029 4.07 3799 1073 4.39 4097 1115 4.72 4400 1156 5.05 4707 —— — 5600 1046 4.29 3999 1089 4.61 4302 1131 4.94 4610 —— — —— — 5700 1063 4.51 4207 1105 4.84 4515 1146 5.18 4827 —— — —— — 5800 1080 4.74 4420 1122 5.08 4734 5900 1098 4.98 4642 6000 1115 5.22 4872 6100 —— — —— — —— — —— — —— — 6200 —— — —— — —— — —— — —— — 6300 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 1008 2.54 2364 1058 2.79 2602 1106 3.05 2846 1152 3.32 3094 1198 3.59 3348 3800 1019 2.66 2482 1068 2.92 2725 1116 3.19 2972 1162 3.46 3226 1206 3.74 3484 3900 1031 2.79 2605 1079 3.06 2852 1126 3.33 3104 1171 3.61 3362 1215 3.89 3624 4000 1042 2.93 2733 1090 3.20 2984 1136 3.48 3241 1180 3.76 3503 1224 4.04 3770 4100 1054 3.07 2866 1101 3.35 3122 1146 3.63 3383 1190 3.91 3649 1233 4.20 3921 4200 1066 3.22 3004 1112 3.50 3264 1157 3.79 3530 1200 4.08 3801 1243 4.37 4077 4300 1078 3.38 3148 1123 3.66 3413 1167 3.95 3683 1210 4.24 3958 1252 4.54 4238 4400 1090 3.54 3297 1135 3.82 3566 1179 4.12 3841 1221 4.42 4121 1262 4.72 4405 4500 1103 3.70 3451 1147 4.00 3726 1190 4.29 4005 1232 4.60 4289 1273 4.91 4578 4600 1115 3.87 3612 1159 4.17 3891 1201 4.48 4175 1243 4.79 4464 1283 5.10 4757 4700 1128 4.05 3778 1171 4.36 4062 1213 4.67 4350 1254 4.98 4644 —— — 4800 1141 4.24 3951 1183 4.55 4239 1225 4.86 4532 1265 5.18 4830 —— — 4900 1154 4.43 4130 1196 4.74 4422 1237 5.06 4720 —— — —— — 5000 1167 4.63 4314 1209 4.95 4611 —— — —— — —— — 5100 1181 4.83 4505 1221 5.16 4808 —— — —— — —— — 5200 1194 5.04 4703 —— — —— — —— — —— — 5300 —— — —— — —— — —— — —— — 5400 —— — —— — —— — —— — —— — 5500 —— — —— — —— — —— — —— — 5600 —— — —— — —— — —— — —— — 5700 —— — —— — —— — —— — —— — 5800 —— — —— — —— — —— — —— — 5900 —— — —— — —— — —— — —— — 6000 —— — —— — —— — —— — —— — 6100 —— — —— — —— — —— — —— — 6200 —— — —— — —— — —— — —— — 6300 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
39
Page 40
Table21—FanPerformance 580F090,091 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
AIRFLOW
(Cfm)
513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839
605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 — 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 —— — 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 —— — 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 736 1.78 1660 793 2.09 1944 — 745 1.85 1721 801 2.15 2008
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2250 838 1.81 1683 891 2.12 1981 —— — —— — —— — 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
842 1.84 1719 895 2.17 2019 —— — —— — —— — 851 1.92 1793 903 2.25 2097 —— — —— — —— — 860 2.01 1873 911 2.34 2180 —— — —— — —— — 865 2.05 1914 916 2.38 2223 —— — —— — —— — 869 2.10 1957 —— — —— — —— — —— — 879 2.19 2046 —— — —— — —— — —— — 889 2.29 2140 —— — —— — —— — —— — 899 2.40 2239 —— — —— — —— — —— —
—— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— —
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 590 to 840 rpm. All other rpms require field-
supplied drive.
40
Page 41
Table22—FanPerformance 580F090,091 — Horizontal Discharge Units; Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
AIRFLOW
(Cfm)
513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057
686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 — 703 1.54 1433 762 1.83 1705 817 2.14 1993 — 720 1.66 1543 777 1.95 1822 832 2.27 2116 — 736 1.78 1660 793 2.09 1944 — 745 1.85 1721 801 2.15 2008
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2250 838 1.81 1683 891 2.12 1981 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
842 1.84 1719 895 2.17 2019 — 851 1.92 1793 903 2.25 2097 — 860 2.01 1873 911 2.34 2180 — 865 2.05 1914 916 2.38 2223 — 869 2.10 1957 — 879 2.19 2046 — 889 2.29 2140 — 899 2.40 2239
—— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— — —— —
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
41
Page 42
Table 23 — Fan Performance 580F090,091 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2250 505 0.52 484 586 0.73 681 657 0.97 901 722 1.22 1142 782 1.50 1403 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
AIRFLOW
(Cfm)
513 0.55 509 592 0.76 708 663 1.00 931 727 1.26 1174 787 1.54 1437 527 0.60 561 605 0.82 766 674 1.07 993 738 1.33 1241 796 1.62 1508 543 0.66 617 618 0.89 828 686 1.14 1060 748 1.41 1312 806 1.70 1583 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 932 2.95 2750 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 944 3.10 2889 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 951 3.18 2962
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2250 838 1.81 1683 891 2.12 1981 941 2.46 2297 988 2.82 2629 1033 3.19 2976 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
842 1.84 1719 895 2.17 2019 944 2.51 2336 992 2.86 2669 1037 3.24 3018 851 1.92 1793 903 2.25 2097 952 2.59 2416 999 2.95 2752 1043 3.33 3104
860 2.01 1873 911 2.34 2180 960 2.68 2502 1006 3.05 2842 1051 3.43 3196 865 2.05 1914 916 2.38 2223 964 2.73 2547 1010 3.10 2888 1054 3.48 3243 869 2.10 1957 920 2.43 2267 968 2.78 2593 1014 3.15 2935 1058 3.53 3292 879 2.19 2046 929 2.53 2360 976 2.88 2689 1022 3.25 3035 1066 3.64 3395 889 2.29 2140 938 2.64 2458 985 2.99 2791 1030 3.37 3140 — 899 2.40 2239 948 2.75 2561 994 3.11 2898 1039 3.49 3250 — 910 2.51 2343 958 2.86 2670 1004 3.23 3011 1048 3.61 3366 — 921 2.63 2453 968 2.98 2783 1013 3.35 3128 — 932 2.75 2569 978 3.11 2903 1023 3.49 3252 — 943 2.88 2690 989 3.25 3029 1033 3.63 3382 — 954 3.02 2816 1000 3.39 3159 — 966 3.16 2950 1011 3.54 3297 — 978 3.31 3088 1022 3.69 3442 — 990 3.47 3233 — 996 3.55 3308
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
42
Page 43
Table24—FanPerformance 580F102,103 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 3700 736 1.78 1660 793 2.09 1944 3750 745 1.85 1721 801 2.15 2008 3800 753 1.91 1783 808 2.22 2074 3900 770 2.05 1912 824 2.37 2209 4000 787 2.20 2047 4100 804 2.35 2189 4200 —— — —— — —— — —— — —— — 4250 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 865 2.05 1914 916 2.38 2223 2600 869 2.10 1957 2700 879 2.19 2046 2800 889 2.29 2140 2900 899 2.40 2239 3000 —— — —— — —— — —— — —— — 3100 —— — —— — —— — —— — —— — 3200 —— — —— — —— — —— — —— — 3300 —— — —— — —— — —— — —— — 3400 —— — —— — —— — —— — —— — 3500 —— — —— — —— — —— — —— — 3600 —— — —— — —— — —— — —— — 3700 —— — —— — —— — —— — —— — 3750 —— — —— — —— — —— — —— — 3800 —— — —— — —— — —— — —— — 3900 —— — —— — —— — —— — —— — 4000 —— — —— — —— — —— — —— — 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4250 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
43
Page 44
Table 25 — Fan Performance 580F102,103 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 550 0.69 647 625 0.92 860 692 1.17 1095 754 1.45 1349 811 1.74 1623 2600 558 0.73 677 632 0.96 894 698 1.21 1131 759 1.49 1388 816 1.78 1664 2700 574 0.80 742 645 1.03 964 710 1.29 1207 770 1.58 1469 826 1.88 1749 2800 589 0.87 811 659 1.11 1039 723 1.38 1287 782 1.67 1554 837 1.97 1839 2900 605 0.95 885 673 1.20 1119 736 1.47 1372 794 1.76 1644 848 2.07 1933 3000 621 1.03 963 688 1.29 1204 749 1.57 1463 806 1.87 1740 859 2.18 2033 3100 637 1.12 1046 702 1.39 1293 762 1.67 1558 818 1.97 1840 871 2.29 2139 3200 654 1.22 1135 717 1.49 1388 776 1.78 1658 831 2.09 1946 882 2.41 2249 3300 670 1.32 1228 732 1.60 1488 789 1.89 1764 843 2.21 2057 894 2.54 2365 3400 686 1.42 1328 747 1.71 1593 803 2.01 1876 856 2.33 2174 907 2.67 2488 3500 703 1.54 1433 762 1.83 1705 817 2.14 1993 870 2.46 2297 919 2.81 2616 3600 720 1.66 1543 777 1.95 1822 832 2.27 2116 883 2.60 2425 932 2.95 2750 3700 736 1.78 1660 793 2.09 1944 846 2.41 2245 896 2.75 2560 944 3.10 2889 3750 745 1.85 1721 801 2.15 2008 853 2.48 2312 903 2.82 2630 951 3.18 2962 3800 753 1.91 1783 808 2.22 2074 861 2.55 2380 910 2.90 2701 957 3.26 3036 3900 770 2.05 1912 824 2.37 2209 875 2.70 2522 924 3.05 2848 970 3.42 3189 4000 787 2.20 2047 840 2.52 2351 890 2.86 2669 938 3.22 3002 984 3.59 3348 4100 804 2.35 2189 856 2.68 2499 905 3.03 2824 952 3.39 3162 4200 821 2.51 2338 872 2.85 2655 920 3.20 2986 967 3.57 3331 4250 829 2.59 2415 880 2.93 2735 928 3.29 3069 974 3.66 3417
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
2550 865 2.05 1914 916 2.38 2223 964 2.73 2547 1010 3.10 2888 1054 3.48 3243 2600 869 2.10 1957 920 2.43 2267 968 2.78 2593 1014 3.15 2935 1058 3.53 3292 2700 879 2.19 2046 929 2.53 2360 976 2.88 2689 1022 3.25 3035 1066 3.64 3395 2800 889 2.29 2140 938 2.64 2458 985 2.99 2791 1030 3.37 3140 2900 899 2.40 2239 948 2.75 2561 994 3.11 2898 1039 3.49 3250 3000 910 2.51 2343 958 2.86 2670 1004 3.23 3011 1048 3.61 3366 3100 921 2.63 2453 968 2.98 2783 1013 3.35 3128 3200 932 2.75 2569 978 3.11 2903 1023 3.49 3252 3300 943 2.88 2690 989 3.25 3029 1033 3.63 3382 3400 954 3.02 2816 1000 3.39 3159 3500 966 3.16 2950 1011 3.54 3297 3600 978 3.31 3088 1022 3.69 3442 3700 990 3.47 3233 3750 996 3.55 3308 3800 1002 3.63 3385 3900 —— — —— — —— — —— — —— — 4000 —— — —— — —— — —— — —— — 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4250 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 29 for General Fan Performance Notes.
44
Page 45
Table26—FanPerformance 580F120,121 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 4400 750 2.01 1764 806 2.23 1958 4500 764 2.14 1879 819 2.37 2077 4600 779 2.28 1998 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 —— — 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 —— — 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 —— — 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 —— — —— — 3500 911 2.01 1760 959 2.21 1937 —— — —— — —— — 3600 920 2.11 1854 967 2.32 2033 —— — —— — —— — 3700 929 2.22 1951 3800 939 2.34 2053 —— — —— — —— — —— — 3900 —— — —— — —— — —— — —— — 4000 —— — —— — —— — —— — —— — 4100 —— — —— — —— — —— — —— — 4200 —— — —— — —— — —— — —— — 4300 —— — —— — —— — —— — —— — 4400 —— — —— — —— — —— — —— — 4500 —— — —— — —— — —— — —— — 4600 —— — —— — —— — —— — —— — 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
45
Page 46
Table27—FanPerformance 580F120,121 — Horizontal Discharge Units; Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 922 2.50 2191 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 884 2.41 2114 933 2.63 2307 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 896 2.54 2231 944 2.77 2428 4400 750 2.01 1764 806 2.23 1958 858 2.45 2154 908 2.68 2352 4500 764 2.14 1879 819 2.37 2077 871 2.59 2276 920 2.82 2479 4600 779 2.28 1998 833 2.51 2200 883 2.74 2404 4700 793 2.42 2121 846 2.65 2328 896 2.89 2537 4800 808 2.56 2251 860 2.81 2462 4900 822 2.72 2385 —— — —— — —— — —— — 5000 837 2.88 2525
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 1062 2.41 2114 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 1069 2.51 2203 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 1076 2.62 2295 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 1041 2.51 2205 1083 2.73 2393 3500 911 2.01 1760 959 2.21 1937 1004 2.41 2118 1048 2.62 2303 1091 2.84 2494 3600 920 2.11 1854 967 2.32 2033 1013 2.53 2217 1056 2.74 2406 3700 929 2.22 1951 976 2.43 2134 1021 2.65 2322 1064 2.86 2513 3800 939 2.34 2053 985 2.55 2239 1030 2.77 2430 3900 949 2.46 2159 995 2.68 2349 1039 2.90 2543 4000 959 2.59 2269 1004 2.81 2462 4100 969 2.72 2384 4200 979 2.85 2504 4300 —— — —— — —— — —— — —— — 4400 —— — —— — —— — —— — —— — 4500 —— — —— — —— — —— — —— — 4600 —— — —— — —— — —— — —— — 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 835 to 1085 rpm. All other rpms require field-
supplied drive.
46
Page 47
Table 28 — Fan Performance 580F120,121 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 555 0.72 630 629 0.87 765 696 1.03 904 757 1.19 1048 814 1.36 1198 3100 568 0.78 686 641 0.94 825 706 1.10 968 766 1.27 1115 823 1.45 1269 3200 582 0.85 745 652 1.01 888 717 1.18 1035 776 1.35 1186 832 1.53 1343 3300 595 0.92 808 664 1.09 955 728 1.26 1106 786 1.44 1261 841 1.62 1421 3400 609 1.00 874 677 1.17 1026 739 1.35 1181 797 1.53 1340 851 1.71 1503 3500 623 1.08 945 689 1.25 1100 750 1.43 1259 807 1.62 1422 860 1.81 1589 3600 636 1.16 1019 702 1.34 1179 762 1.53 1341 817 1.72 1508 870 1.91 1679 3700 650 1.25 1097 714 1.44 1261 773 1.63 1428 828 1.82 1598 880 2.02 1772 3800 664 1.34 1179 727 1.54 1347 785 1.73 1518 839 1.93 1693 890 2.13 1870 3900 678 1.44 1266 740 1.64 1438 797 1.84 1613 850 2.04 1791 901 2.25 1973 4000 693 1.55 1356 753 1.75 1533 809 1.95 1712 861 2.16 1894 911 2.37 2080 4100 707 1.65 1451 766 1.86 1632 821 2.07 1816 873 2.28 2002 922 2.50 2191 4200 721 1.77 1551 779 1.98 1736 833 2.19 1924 884 2.41 2114 933 2.63 2307 4300 735 1.89 1656 792 2.10 1845 846 2.32 2037 896 2.54 2231 944 2.77 2428 4400 750 2.01 1764 806 2.23 1958 858 2.45 2154 908 2.68 2352 955 2.91 2553 4500 764 2.14 1879 819 2.37 2077 871 2.59 2276 920 2.82 2479 966 3.06 2684 4600 779 2.28 1998 833 2.51 2200 883 2.74 2404 932 2.97 2611 978 3.21 2820 4700 793 2.42 2121 846 2.65 2328 896 2.89 2537 944 3.13 2747 989 3.37 2960 4800 808 2.56 2251 860 2.81 2462 909 3.05 2674 956 3.29 2889 1001 3.54 3106 4900 822 2.72 2385 873 2.96 2601 922 3.21 2818 968 3.46 3037 1013 3.71 3258 5000 837 2.88 2525 887 3.13 2745 935 3.38 2966 981 3.63 3189 1024 3.89 3414
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3000 867 1.54 1353 918 1.72 1513 966 1.91 1680 1012 2.11 1852 1056 2.31 2029 3100 876 1.63 1427 926 1.81 1590 973 2.00 1760 1019 2.20 1934 1062 2.41 2114 3200 884 1.71 1504 934 1.90 1671 981 2.10 1843 1026 2.30 2020 1069 2.51 2203 3300 893 1.81 1586 942 2.00 1755 988 2.20 1931 1033 2.40 2111 1076 2.62 2295 3400 902 1.90 1671 950 2.10 1844 996 2.30 2022 1041 2.51 2205 1083 2.73 2393 3500 911 2.01 1760 959 2.21 1937 1004 2.41 2118 1048 2.62 2303 1091 2.84 2494 3600 920 2.11 1854 967 2.32 2033 1013 2.53 2217 1056 2.74 2406 1098 2.96 2600 3700 929 2.22 1951 976 2.43 2134 1021 2.65 2322 1064 2.86 2513 1106 3.09 2710 3800 939 2.34 2053 985 2.55 2239 1030 2.77 2430 1073 2.99 2625 1114 3.22 2824 3900 949 2.46 2159 995 2.68 2349 1039 2.90 2543 1081 3.12 2741 1122 3.35 2943 4000 959 2.59 2269 1004 2.81 2462 1048 3.03 2660 1090 3.26 2861 1130 3.49 3067 4100 969 2.72 2384 1014 2.94 2581 1057 3.17 2782 1098 3.40 2987 1139 3.64 3195 4200 979 2.85 2504 1024 3.08 2705 1066 3.31 2909 1107 3.55 3117 1147 3.79 3329 4300 990 3.00 2629 1034 3.23 2833 1076 3.46 3040 1117 3.71 3252 1156 3.95 3467 4400 1000 3.14 2758 1044 3.38 2966 1085 3.62 3177 1126 3.87 3392 1165 4.11 3611 4500 1011 3.30 2892 1054 3.54 3104 1095 3.78 3319 1135 4.03 3537 1174 4.28 3759 4600 1022 3.45 3032 1064 3.70 3247 1105 3.95 3466 1145 4.20 3688 1183 4.46 3913 4700 1033 3.62 3176 1075 3.87 3395 1115 4.12 3618 1155 4.38 3843 1193 4.64 4072 4800 1044 3.79 3326 1085 4.04 3549 1126 4.30 3775 1164 4.56 4004 1202 4.83 4237 4900 1055 3.97 3482 1096 4.22 3708 1136 4.49 3938 1174 4.75 4171 1212 5.02 4406 5000 1066 4.15 3642 1107 4.41 3873 1146 4.68 4106 1184 4.95 4342 1221 5.22 4582
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
47
Page 48
Table29—FanPerformance 580F150,151 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 5100 882 2.81 2622 937 3.14 2926 989 3.47 3232 5200 897 2.97 2766 951 3.30 3077 1003 3.63 3389 5300 912 3.13 2917 966 3.47 3233 5400 927 3.30 3073 980 3.64 3395 5500 943 3.47 3234 5600 958 3.65 3402 5700 —— — —— — —— — —— — —— — 5800 —— — —— — —— — —— — —— — 5900 —— — —— — —— — —— — —— — 6000 —— — —— — —— — —— — —— — 6100 —— — —— — —— — —— — —— — 6200 —— — —— — —— — —— — —— — 6300 —— — —— — —— — —— — —— —
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 —— — 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 —— — —— — 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 —— — —— — 4300 1042 3.16 2951 1089 3.45 3218 —— — —— — —— — 4400 1053 3.31 3085 1100 3.60 3357 —— — —— — —— — 4500 1064 3.46 3224 4600 1075 3.61 3367 4700 —— — —— — —— — —— — —— — 4800 —— — —— — —— — —— — —— — 4900 —— — —— — —— — —— — —— — 5000 —— — —— — —— — —— — —— — 5100 —— — —— — —— — —— — —— — 5200 —— — —— — —— — —— — —— — 5300 —— — —— — —— — —— — —— — 5400 —— — —— — —— — —— — —— — 5500 —— — —— — —— — —— — —— — 5600 —— — —— — —— — —— — —— — 5700 —— — —— — —— — —— — —— — 5800 —— — —— — —— — —— — —— — 5900 —— — —— — —— — —— — —— — 6000 —— — —— — —— — —— — —— — 6100 —— — —— — —— — —— — —— — 6200 —— — —— — —— — —— — —— — 6300 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
48
Page 49
Table30—FanPerformance 580F150,151 — Horizontal Discharge Units; Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 676 1.19 1106 747 1.42 1328 811 1.66 1552 871 1.91 1779 927 2.15 2008 3800 690 1.27 1185 760 1.52 1414 823 1.76 1644 882 2.01 1876 938 2.26 2111 3900 705 1.36 1269 773 1.61 1503 835 1.86 1739 894 2.12 1977 948 2.38 2217 4000 719 1.45 1357 786 1.71 1597 848 1.97 1838 905 2.23 2082 959 2.50 2328 4100 734 1.55 1449 799 1.82 1695 860 2.08 1942 917 2.35 2192 970 2.62 2443 4200 748 1.66 1545 813 1.93 1797 872 2.20 2050 928 2.47 2305 981 2.75 2562 4300 763 1.76 1646 826 2.04 1903 885 2.32 2162 940 2.60 2423 992 2.88 2686 4400 778 1.88 1751 840 2.16 2014 898 2.44 2279 952 2.73 2546 1004 3.02 2814 4500 792 1.99 1860 853 2.28 2130 910 2.57 2401 964 2.87 2673 1015 3.16 2947 4600 807 2.12 1975 867 2.41 2250 923 2.71 2527 976 3.01 2805 1027 3.31 3085 4700 822 2.25 2094 881 2.55 2375 936 2.85 2658 989 3.15 2942 1038 3.46 3227 4800 837 2.38 2218 895 2.69 2505 949 3.00 2794 1001 3.31 3083 1050 3.62 3375 4900 852 2.52 2347 909 2.83 2640 963 3.15 2935 1014 3.46 3230 1062 3.78 3528 5000 867 2.66 2482 923 2.98 2781 976 3.30 3081 1026 3.63 3383 1074 3.95 3685 5100 882 2.81 2622 937 3.14 2926 989 3.47 3232 1039 3.80 3540 1086 4.13 3849 5200 897 2.97 2766 951 3.30 3077 1003 3.63 3389 1052 3.97 3702 1099 4.31 4017 5300 912 3.13 2917 966 3.47 3233 1016 3.81 3551 1065 4.15 3870 1111 4.49 4191 5400 927 3.30 3073 980 3.64 3395 1030 3.99 3719 1078 4.34 4044 1123 4.69 4370 5500 943 3.47 3234 994 3.82 3563 1044 4.17 3892 1091 4.53 4223 1136 4.88 4555 5600 958 3.65 3402 1009 4.01 3736 1057 4.37 4071 1104 4.73 4408 1149 5.09 4746 5700 973 3.83 3575 1023 4.20 3915 1071 4.56 4256 1117 4.93 4599 5800 988 4.03 3754 1038 4.40 4100 1085 4.77 4447 1130 5.14 4796 5900 1004 4.22 3939 1052 4.60 4292 1099 4.98 4645 6000 1019 4.43 4131 1067 4.81 4489 1113 5.20 4848 6100 1034 4.64 4329 1082 5.03 4693 6200 1050 4.86 4533 6300 1065 5.09 4744
AIRFLOW
(Cfm)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
EXTERNAL STATIC PRESSURE (in. wg)
3700 981 2.40 2240 1031 2.65 2473 1079 2.91 2709 1125 3.16 2948 1169 3.42 3189 3800 990 2.52 2348 1040 2.77 2587 1088 3.03 2828 1133 3.30 3073 1177 3.56 3319 3900 1000 2.64 2459 1050 2.90 2705 1097 3.17 2951 1142 3.43 3201 1186 3.70 3452 4000 1011 2.76 2576 1059 3.03 2826 1106 3.30 3079 1151 3.58 3334 1194 3.85 3591 4100 1021 2.89 2697 1069 3.17 2953 1116 3.44 3210 1160 3.72 3471 1203 4.00 3733 4200 1031 3.03 2822 1079 3.31 3083 1125 3.59 3347 1169 3.87 3612 1212 4.16 3880 4300 1042 3.16 2951 1089 3.45 3218 1135 3.74 3487 1179 4.03 3758 1221 4.32 4031 4400 1053 3.31 3085 1100 3.60 3357 1145 3.90 3632 1188 4.19 3909 1230 4.49 4187 4500 1064 3.46 3224 1110 3.76 3502 1155 4.06 3782 1198 4.36 4064 1239 4.66 4348 4600 1075 3.61 3367 1121 3.91 3650 1165 4.22 3937 1208 4.53 4224 1249 4.84 4514 4700 1086 3.77 3515 1131 4.08 3805 1175 4.39 4096 1217 4.71 4389 1258 5.02 4684 4800 1097 3.93 3668 1142 4.25 3963 1186 4.57 4260 1228 4.89 4559 1268 5.21 4860 4900 1109 4.10 3826 1153 4.43 4128 1196 4.75 4430 1238 5.08 4734 —— — 5000 1120 4.28 3990 1164 4.61 4296 1207 4.94 4604 —— — —— — 5100 1132 4.46 4159 1175 4.79 4471 1218 5.13 4784 —— — —— — 5200 1144 4.65 4333 1187 4.99 4651 —— — —— — —— — 5300 1155 4.84 4512 1198 5.19 4836 —— — —— — —— — 5400 1167 5.04 4697 —— — —— — —— — —— — 5500 1179 5.24 4889 —— — —— — —— — —— — 5600 —— — —— — —— — —— — —— — 5700 —— — —— — —— — —— — —— — 5800 —— — —— — —— — —— — —— — 5900 —— — —— — —— — —— — —— — 6000 —— — —— — —— — —— — —— — 6100 —— — —— — —— — —— — —— — 6200 —— — —— — —— — —— — —— — 6300 —— — —— — —— — —— — —— —
LEGEND
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 29 for General Fan Performance Notes.
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
49
Page 50
PRE-START-UP
WARNING: Failure to observe the following warn-
ings could result in serious personal injury.
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any elec­tric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove comp ressor terminal cover until all electrical sou rc e s are disco nnected.
4. Relieve all pressure from system before touch­ing or disturbing anything inside terminal box if refrigerant leak is su spe cte d arou nd c ompre s­sor terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. Sys­tem contains oil and refrigerant under pres­sure. To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power and then gas to
unit.
b. Reclai m refrigerant to relie ve all pressure
from system using both high- and lo w-pre s­sure ports.
c. Cut component connection tubing with tub-
ing cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to ins pect and prep are the unit f or initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU­TION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connec-
tions and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrig­erant tubing connections using electronic leak detector, halide torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring con-
nections. Be sure that connections are completed and tight. Be sure that wires are not in contact with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that condenser-fan blade are correctl y
positioned in fan orifice. See Condenser-Fan Adjustment section on page 62 for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
I. UNIT PREPARATION
Make sure that unit has b een installed in accordance with these installation instructions and applicable codes. Make sure that Start-Up Checklist, located on back page of this booklet, has been completed and filled out.
II. RETURN-AIR FILTERS
Make sure correct filters are inst alled in filter trac ks (see T ables 1A and 1B). Do not operate unit without return-air filters .
III. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screens must be in place before op erating unit.
IV. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts. On 580F150 and 151 units, remove the tiedown bands that hold the compressors together.
V. INTERNAL WIRING
Check all electrical connections in unit control boxes. Tighten as required. Ensure wiring does not come into direct contact with refrigerant tubing.
VI. GAS PIPING
Check gas piping for leaks.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than
1
/2 psig. Pres­sures greater tha n 1/2 psig will cause g as valve damage resulting in hazardous condition. If gas valve is sub­jected to pressure greater than
1
/2 psig, it must be replaced before use. When pressure testing field­supplied gas piping at pressures of
1
/2 psig or less, a unit connected to such piping must be isolated by man­ually closing t he ga s valve.
VII. REFRIGERANT SERVICE PORTS
To service refrigerant service ports, remove compressor access panel. Each unit system has 3 Schrader-type service gage ports: one on the suction line, one on the liquid line, and one on the compressor discharg e line. Be sure that caps on the ports are tight. The Schrader-type valve on the discharge line is located under th e low-pressu re switch. Anoth er valve is located on the discharge line underneath the high­pressure switch. It is screwed on a Schrader fitting but there is no Schrader core.
VIII. HIGH FLOW VALVES
Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located in s i de th e ca p s. These valves can not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.
IX. COMPRESSOR ROTATION
On 3-phase units with scroll compressors, it is important to be certain compressor is rotating i n the proper direc tion. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pres­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
50
Page 51
If the suction pressure does not drop and the discharge pres­sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in the wrong direction.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Reapply power to unit. Reen ergize compressor.
The suction and discharge pressure levels should now move to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc­tion, the unit will make an elevated level of noise and will not provide cooling.
X. COOLING
To start unit, turn on m ain power supply. Set system selector switch at CO OL positi on and fan switch at AUT O. position. Adjust thermostat to a setting below room temperature. Compressor, indoor and outdoor fans start on closure of contactors.
Check unit charge. Refer to Checking and Adjusting Refrigerant Charge section, page 62. Unit must operate a minimum of 10 minutes before adjusting charge.
Reset thermostat at a position above room temperature. Compressor and outdoo r fans will shut off. Evaporator fan will shut off after 30-second delay.
A. To Shut Off Unit
Set system selector switch at OFF position. Resetting ther­mostat at a positio n above room temperature sh uts unit off temporarily until space temperature exceeds thermostat setting.
XI. MAIN BURNERS
Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move thermostat set p oint abo ve room t emperat ure and ve r­ify that the burne rs light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the thermostat setting below the room temperature and verify that the burne rs and evapor ator fan turn off ( fan will turn off only if fan selector switch is in the AUTO. posi­tion). Refer to Table 31 for the correct orifice to use at high altitudes.
NOTE: Upon a call for heat, the main burners will remain on for a minimum of 60 seconds.
A. Adjust Gas Input
The gas input to the unit is determined by mea suring the gas flow at the m eter o r by me asuri ng th e ma nifold pres sure . Manifold pressure should be 3.5 in. wg. in high-fire operation.
NOTE: Unit uses a 2-stage gas valve. There is no need to adjust the “Low Fire” manifold pressure.
Measure Gas Flow (Natural Gas Units) Minor adjustment to the gas flow can be made by changing
the manifold pressure. The manifold pressure must be
3.5 in. wg. Normal manifold pressure is 3.5 in. wg in high fire (W1 and W2 inputs to gas valve).
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold then connect manome­ter at this point. Turn on gas to unit. Ensure gas valve is in high fire operation.
Observe manifold pressure in high fire (W1 and W2 ener­gized) and proceed as follows to adjust gas input:
1. Remove cover screw ove r regulator a djustment s crew on gas valve. Ensure gas valve is operating in high fire mode.
2. Turn regulator adjustment screw clockwise to increase gas input, or turn regulator adjustment screw counterclockwise to decrease input. High fire manifold pressure must be 3.5 in. wg.
WARNING: Unsafe operation of the unit may result if manifold pressure is outside 3.4 to 3.6 in. wg range. Personal injury or unit damage may result.
3. Replace cover screw cap on gas valve.
4. Turn off gas supply to un it. Rem ove m anometer from pressure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks.
Table 31 — Altitude Compensation*
125,000, 180,000, AND
220,000 BTUH
ELEVATION
(Ft)
0-2,000 31 41 30 38
2,000 32 42 30 39 3,000 32 42 31 40 4,000 32 42 32 41 5,000 33 43 33 42 6,000 34 43 34 43 7,000 35 44 35 43 8,000 36 44 36 44
9,000 37 45 37 44 10,000 38 46 38 45 11,000 39 47 39 45 12,000 40 47 40 46 13,000 41 48 41 47 14,000 42 48 42 47
*As the height above sea level increases, there is less oxygen per cubic foot
of air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local distributor.
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
250,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
XII. HEATING
1. Purge gas supply line of air by opening union ahead of gas valve. When gas odor is detected, tighten union and wait 5 minutes before proceeding.
2. Turn on electrical supply and open manual gas valve.
3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temper­ature lever above room temperature.
4. The induced-draft motor will start, purging heat exchangers.
5. After a call for heating, the main burners should light within 5 seconds. If the burners do not light, then there is a 22-second delay before another 5-second ignition try. If the burners still do not light, the time delay is repeated. If the burners do not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds after the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds after the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate and in Tables 1A and 1B.
51
Page 52
XIII. INTEGRATED GAS CONTROLLER (IGC) OPERATION
NOTE: The default value for the evaporator-fan motor ON
and OFF delay is 45 sec ond s. The I ntegr ate d Gas Con trol ler (IGC) modifies this valu e when a bnormal limi t switch cycl es occur. Based up on unit operating conditions, the O N delay can be reduced to 0 seconds and the OFF delay can be extended to 180 seconds.
When one flash of the LED (light-emitting diode) is observed, the evap orator-fan ON/OFF del ay has been modi­fied. If the limit switch trips at the star t of t he he ating cycle during the evaporator ON delay, the time period of the ON delay for the next cycle will be 5 seco nds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator-fan ON delay for the next cycle will occur at 25 seconds.) To prevent short-cycling, a 5-second reduction w ill only occur if a minimum of 10 min­utes has elapsed since the last call for heating.
The evaporator -fan O FF dela y can also be m odified. O nce th e call for heating has ended, there is a 10-min ute period dur­ing which the modification can occur. If the limit switch trips during this period, the evaporator-fan OFF delay will increase by 15 seco nds on the next cycle. A maximum of 9 trips can occur, extending the evaporator-fan OFF delay to 180 seconds. To restore the original default value, reset the power to the unit.
A. To Shut Off Unit
Set system selector sw itch at OFF p osition. Re setting h eat­ing selector lever below room temperature will shut unit off temporarily until space temperature falls below thermostat setting.
XIV. SAFETY RELIEF
A soft-solder joint at the suction l ine Schrader port provi des pressure relief under abnormal temperature and pressure conditions.
XV. VENTILATION (Continuous Fan)
Set fan and system selector switches at ON and OFF posi­tions, respectively. Evaporator fan operates continuous ly to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second del a y be f or e th e f an tur ns off.
XVI. ECONOMI$ER+ CONTROLLER
The EconoMi$er+ controller is mounted to the top of the EconoMi$er+ d amp er and is acce ssibl e by remo ving the fi lter access door of the unit.
The EconoMi$er+ controller is protected by a sheet metal enclosure mounted over the controller. Remove the single screw on the front of the enclosure and lift off the top for access to the contro ller. The primary purpose of the control ­ler is to provide cont rol of the EconoMi$er+ da mpers and the cooling compression stages. The status of the indoor fan is monitored through the G input but is n ot directly cont rolled by the controller. The heating function is completely inde­pendent of the controller.
IMPORTANT: The controller can only be used with conven­tional thermostats with Y1, Y2 and G input to the controller; it can NOT be used with electroni c thermostats with a pro­portional room temperature input, or with Variable Air Vol­ume systems.
There are 4 LEDs on the controller, which are used to read val­ues and display status and configuration information. There are 2 buttons (READ/ADJUST and ADVANCE/MANUAL), which change modes and configure the controller . See Fig. 36.
The EconoMi$er+ microprocessor based control system pro­vides the following control functions:
• EconoMi$er+ damper control for free cooling
• Minimum position control for ventilation
• Demand Ventilation Control using a CO
sensor
2
• Compressor Cooling Stage Control
• Occupied/Unoccupied Control
• Diagnostics Display and History
• Manual test control See Table 32 for Inputs and Outputs.
A. Integrated Display
The control board includes an integrated display, which is used for the following functions:
• Configuration and setup
• Set point and control adjustment
• Error status and alarm monitoring
• Manual control
• Reading sensor values There are 5 modes of display operation:
•Startup Mode
•Run Mode
• Read Mode
•Setup Mode
• Manual Mode External devices are not required to operate and configure
the control.
B. Startup Mode
During the first 3 secon ds after power is applied to the con­trol, the four LEDs flash as shown in Table 33, indicating that the control is being initialized. The buttons are not operational during Startup mode.
C. Run Mode
Run mode indicates status of control ler and unit. The mode can be changed to the Read, Setup, or Manual modes by pushing va ri ous buttons.
While the control is in Run mode, the DS1 heartbeat indica­tor LED (red) will flas h to indi cat e the cont rolle r is ope rat ing properly. The DS2 Econo indicator LED (yellow) will flash whenever econom ize r is b ein g us ed f o r fre e co olin g. The DS3 first stage cooling indicator LED (green) will be on steady indicate demand for sta ge 1 cooling. The DS4 second stage cooling indicator LED (green) will be on steady to indicate demand for stage 2 cooling.
If the controller is in a different mode, the controller will return to Run mode after 10 minutes of user inactivity or if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) but­tons are held for at least 3 seconds until all LEDs flash.
D. Read Mode
Read mode is used to check set points (Table 34) and I/O channel status (Table 35). Enter the Read mode by pushing and releasing the READ/ADJUST (#1) button. A user can only enter Read mode from the Run mode (to get to Run mode, press both the #1 and #2 buttons for at least 3 seconds until all LEDs flash). In Read mode, LEDs are not lit until the READ/ADJUST button (#1) is pushed.
NOTE: If the user pushes and holds the READ/ADJUST but­ton (#1) for more than 3 seconds, then the control will go into the Setup mode, indicated by the yellow LED (on steady).
While in Read mode, push button #1 then the DS1 LED (Red) flashes to indicate setup point number as defined in the setup table. The two green LEDs will then show the value of the display item. The DS3 LED will first display the
52
Page 53
tens digit and the DS4 LED will then display the ones digit. For example to display 54, the DS3 LED will flash 1 group of 5 at a high flash rate to indicate 50, and then follow with 4 flashes (DS4) at 1-second intervals to complete the display of the number 54.
NOTE: Do not try to count the “5 Fast Flashes” individually, but instead count how many groups of 5 flashes were displayed. In this case, 1 group of 5 flashes, plus the 4 flashes at 1 second results in the value of 54.
To re ad the di splay again, push the READ/AD JUST (# 1) but­ton and the sequence will repeat as many times as needed.
To advance to the next setup point, push the ADVANCE/ MANUAL (#2) button. The controller will cycle throu gh all the setup channels (Table 34) and then the I/O channels (Table 35) and then back to the first setup channel.
NOTE: Th e user can only advance forw ard, no t reset to # 1 or go backwards. Cycling the EconoMi$er+ power will reset the item number (but not the item value) to item #1.
In the Read mode for setup variables, the LEDs will not turn on steady; the LEDs will always flash. Steady-on indicators are reserved for the configuration modes. No data is modified in the Read mode. The con troller will always remain at the last read number even if reset back to normal operat ion.
NOTE: To enter another mode, the user first must exit the Read mode.
If no button is pushed in 10 minutes, Read mode will auto­matically be exited. Also, if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are pushed and held for more than 3 seconds, then Read mode will be exited to Run mode. While i n the Read mod e , the c ontro ller will conti nue to operate with normal unit control.
Y1
Y2
G
OCC
24V
READ/
ADJUST
date or serial no
J1
1
Y1 (cool 1) Y2 (cool 2) G (fan) OCC
24 VAC
5
J2
Occupied/unoccupied I/O support dry circuit contact (min 24 mA I)
THERMOSTAT INPUTS
POWER
ECONOMIZER
SUPPLY
24 VAC
1
24V
2-10 VDC
CONTROL
24 VAC
Control
24V
CNT
5
#1
J3
ADVANCE
MANUAL
PUSH BUTTONS
1
#2
Relays rated at 24 VAC 3A and traces for 8A. NOTE: For 1 and 2 stage cooling, 2 stages of power exhaust will be used. For 3 cooling stages, only 1 stage of power exhaust will be used, and for 4 stages no power exhaust will be controlled directly by the control.
4-20 mA external powered between signal and ground 4-20 mA loop powered between 24 VDC and signal
OAT (10k thermistor)
SAT (10k thermistor)
SAT
OAT
DS1 DS2
YELLOW
RED
SETPOINT DISPLAY
ANALOG INPUTS
Vref
IRH (4-20 ma)
IRH
ORH (4-20 ma)
VRF
RAT (10k thermistor)
RAT
ORH
DS3
Vref
VRF
GREEN
EX2/CP3
OUTPUT RELAYS
EX1/CP4
DS4
CP1
CP2
24 VAC
24 VAC
24 VAC
IAQ (4-20ma)
IAQ
min (10K pot)
MIN
Vref
VRF
J4
C1
C2
24V 24V
24V
C3
C4
17
Fig. 36 — EconoMi$er+ Controller Board
53
Page 54
Table 32 — EconoMi$er+ Inputs and Outputs
INPUT NAME TYPE USE
THERMOSTAT INPUTS
Y1 (Cool/Low Cool) Y1 Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J11 Y2 (Cool 2/High Cool) Y2 Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J12
G (fan) G Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J13 Occupied/Unoccupied OCC Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J14,5 POWER Power 24V Input Standard 18-30 VAC 50/60 Hz NA NA J21,2 ECONOMIZER MOTOR Control CNT 2-10 vdc Standard 2-10 vdc 0-100% 1%J2 3,4,5 ANALOG INPUTS Supply Air Temperature SAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J31,2 Outside Air Temperature OAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J33,4 Return Air Temperature RAT 10 K Thermistor Option 1816 to 86407 Ohms 30 to 125 F 0.8 F J35,6
Indoor Humidity IRH
Outdoor Humidity ORH
Indoor CO
Remote Minimum Posi tion Pot
RELAY OUTPUTS Cooling Stage 1 CP1 Relay Standard 24 vac, 2.5 Amps at 24 vac NA On/Off J4 1,3,4 Cooling Stage 2 CP2 Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 2,3,4 Power Exhaust 2/
Cooling Stage 3* Power Exhaust 1/
Cooling Stage 4† DISPLAY Setpoint Switch 1 SP1 Digital Standard Open/Closed Logic Open/Closed On Board NA Setpoint Switch 2 SP2 Digital Standard Open/Closed Logic Open/Closed On Board NA LED 1 DS1 LED Output Standard Red Logic On/Off On Board NA LED 2 DS2 LED Output Standard Yellow Logic On/Off On Board NA LED 3 DS3 LED Output Standard Green Logic On/Off On Board NA LED 4 DS4 LED Output Standard Green Logic On/Off On Board NA
*If there are 3 stages then there can only be 1 stage of power exhaust. †If there are 4 stages then there will not be power exhaust stages that will be directly controlled.
2
IAQ
MIN 10K Option 10K to 100K Ohms 0 to 100% 1%J315,16,17
CP3/
EX2
CP4/
EX1
4-20 mA,
Loop Powered
4-20 mA,
Loop Powered
4-20 mA,
Ext Sourced
Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J45,6
Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J45,7
Option 4-20 mA, 24 vdc 0-100% .08 mA J3 7,8,9
Option 4-20 mA, 24 vdc 0-100% .08 mA J310,11,12
Option 4-20 mA, 24 vdc 0-200 PPM/10 10 PPM J313,14
INPUT/OUTPUT
RANGE
CONVERSION
RANGE
CONVERSION RESOLUTION
CONNECTION PIN NO.
TIME LED 1/DS1 (RED) LED 2/DS2 (YELLOW) LED 3/DS3 (GREEN) LED 4/DS4 (GREEN) 0-1.0 SEC OFF OFF OFF OFF 1-1.5 SEC FLASH ½ SEC OFF OFF OFF
1.5-2.0 SEC OFF FLASH ½ SEC OFF OFF
2.0-2.5 SEC OFF OFF FLASH ½ SEC OFF
2.5-3.0 SEC OFF OFF OFF FLASH ½ SEC
LED — Light-Emitting Diode
Table33—Start-UpModeSequence
54
Page 55
Table 34 — Configuration Variables (Read and Setup Modes)
NO.
1 Supply Air Temperature Setpoint F 40 F 65 F 55 F 1 F Leaving Air Temperature Control Point
Occupied Minimum Economizer
2
Posi tion Unoccupied Minimum Economizer
3
Posi tion
4 Economizer Maximum Position % 1% 100% 100% 1% Maximum Econo Position
5 Economizer Type 1 3 2 1
6 Economizer Changeover Type 1 5 2 1 1 = Switch, 2 = Outdoor Dry Bulb,
Economizer Changeover Setpoint
7
(mode 2)
8 Economizer Changeover Setpoint
(mode 3)
9 No.ofcompressors 1 4 2 1 1,2,3,or4
10 Compressor Sequencing 1 4 1 1
11 Power Exhaust Stage 1 Activation % 1% Item 12 -5% 25% 1% Economizer Position 12 Power Exhaust Stage 2 Activation % Item 11 +1% 100% 50% 1% Economizer Position (> stage 1) 13 Unoccupied Configuration 1 3 3 1 1 = No Unoccupied Cooling,
14 Compressor Lockout Temperature 1 F 65 F 45 F 1 F Compressor Operation
IAQ Min Economizer Position
15
Setpoint
16 IAQ Enable 1 2 1 1 1 = Disabled, 2 = Enabled 17 Outdoor IAQ Reference PPM/10 1 PPM/10 100 PPM/10 40 PPM/10 1 PPM/10 Outdoor Reference IAQ Level
IAQ Lower Limit Control Point
18
Differential IAQ Upper Limit Control Point
19
Differential
20 1st Most Recent Error/Reset 1 8 Used in Setup Mode to Reset Alarms 21 2nd Most Recent Error (read only) 1 8 Not Displayed in Setup Mode 22 3rd Most Recent Error (read only) 1 8 Not Displayed in Setup Mode 23 4th Most Recent Error (read only) 1 8 Not Displayed in Setup Mode 24 5th Most Recent Error (read only) 1 8 Not Displayed in Setup Mode
DC — Direct Control IAQ — Indoor Air Quality LAT — Leaving Air Temperature Compensated Control VOC — Volatile Organic Compounds
SETUP POINTS
(viewable and adjustable)
LEGEND NOTE: The accessibility of these channels will be as follows:
UNITS
% Item 15 +1% 100% 15% 1% Min Econo Position (occupied mode)
% 1% 100% 5% 1% Min Econo Position (unoccupied mode)
F 45 F 70 F 65 F 1 F For Outdoor Changeover
1 4 1 1 Outdoor Enthalpy Changeover Setpoint
% 1% Item 2 +1% 5% 1% Min IAQ Position for VOC Emissions
PPM/10 1 PPM/10
PPM/10
MINIMUM
VAL UE
Item 18 +1
PPM/10
MAXIMUM
VAL UE
Item 19 -1
PPM/10
200 PPM/10 140 PPM/10 1 PPM/10
READ MODE — All channels will be accessible. SETUP MODE — Only channels 1-20 will be accessible and 20 will be used to reset alarms.
FAC TORY
SETTING
60 PPM/10 1 PPM/10
INC COMMENTS
1 = Vent Only, 2 = Proportional, 3 = 3 Position
3 = Diff Dry Bulb, 4 = Outdoor Enthalpy, 5 = Diff Enthalpy
1=A,2=B,3=C,4=D
1 = DC-Sensible, 2 = DC-Latent, 3 = LAT-Sensible, 4 = LAT-Latent
2 = Unoccupied Free Cooling, 3 = Unoccupied Free & Mech Cooling
Differential Lower Limit Indoor IAQ Level
Differential Upper Limit Indoor IAQ Level
Table 35 — Input/Output Channels
NO. I/O POINTS UNITS MINIMUM VALUE MAXIMUM VALUE INC COMMENTS
1 C1 Output Off On Compressor 1 2 C2 Output Off On Compressor 2 3 C3 Output Off On Compressor 3/Power Exhaust 2 4 C4 Output Off On Compressor 4/Power Exhaust 1 5 Economizer Damper Output % 1 F 100 F 1% Damper Commanded Position 6 Supply Air Temperature F 1 F 150 F 1 F Supply Air Temperature 7 Outdoor Air Temperature F 1 F 150 F 1 F Outdoor Air Temperature 8 Return Air Temperature F 1 F 150 F 1 F Return Air Temperature
9 Indoor Relative Humidity % 1% 100% 1% Return Air Relative Humidity 10 Outdoor Relative Humidity % 1% 100% 1% Outdoor Air Relative Humidity 11 Indoor Air Quality PPM 1 PPM/10 200 PPM/10 10 PPM Indoor Air Quality (/10) 12 Remote Minimum Position % 1% 100% 1% Remote Minimum Pot Position 13 Y1 Status Open Close Thermostat Y1 Status 14 Y2 Status Open Close Thermostat Y2 Status 15 G Status Open Close Indoor Fan Status 16 Occ Status Open Close Remote Occupied Status
NOTE: The accessibility of these channels will be as follows: READ MODE — All channels will be accessible for reading.
ADJUST MODE — Only channels 1-5 will be accessible. MANUAL MODE — Only channels 1-5 will be accessible.
55
Page 56
After advancing through all the configuration variables in the Read mode, the controller will then advance through t he status of the I/O channels. As in the Read mode, there will be no LEDs on. Push the READ/ADJUST (#1) button and the yellow LED will flash the “I/O Point” numbe r and the green LEDs will flash the “I/O Values” in the same manner described in the Read mode section. See Ta ble 35. At the first I/O point (Compressor 1 Ou tput), the DS2 LED (Yellow) will flash with the number of the I/O channel and the DS1 LED (red) will stop fla shi ng. This will be followed b y the I/O c h an­nel status. To read the value ag ain, pus h the R EAD/ADJU ST (#1) button.
To advance to the next channel, push the ADVANCE/ MANUAL (#2) button. If the number of the channel or the status value is greate r than 4 the controller will co unt out the increments of 5 at a high flash rate followed by the remaining digits. The channel number will be counted out through the DS2 LED (yellow). The status value will be counted out through the DS3 and DS4 LEDs (green).
If the status value is an analog value then the numeric value will be displayed by using the DS3 Green LED to display the tens digit and the DS4 will be used to display the ones digit.
If the channel is a digital output (relay), the DS3 LED (flash­ing green) will in dicate ON stat us and the DS4 LED (flash­ing green) will indicate OFF status. If the output is the economizer control signal then the DS3 LED will be used to indicate the motor is being driven open, and the DS4 LED will be used to indicate it is being closed. If the motor i s not being commanded in either direction then both the DS3 and DS4 LEDs will be on. The controller will first go through the output relays, then the economizer motor, and will then fol ­low with the values currently being read for the analog input channels as defined in the configuration table. All values are maintained in memory even during a power loss. To exit Setup mode, push and hold the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons for more than 3 seconds. Setup mode wil l automati cally be exited aft er 10 minu tes of no activity.
E. Setup Mode
The Setup mode is used to change set points and configura­tion values.
Enter the Setup mode by pushing and holding the READ/ ADJUST (#1) button 1 for at least 3 seconds until all LEDs flash once. Then, the yellow LED will come on steady. A user can only enter the Setup mode from the Run m ode (to get to Run mode, press buttons both buttons #1 and #2 for at least 3 seconds).
In Setup mode, all configurations can be modifi ed e ven w hil e the unit is running, but the use r will not be able to adjus t the I/O channels . O nly c ha nne ls 1 th roug h 20 on Table 34 will b e accessible in the Setup mode. Channel 20 will be used to reset any alarms that may have occurred. As an option, alarms can also be reset by cycling power to the cont roller.
NOTE: During the Se tup mode, all routines including safety routines will co ntinu e to ru n a nd c ontr ol the uni t.
While in this mode, the DS1 LED (red) will flash to indicate the number of the configuration item. The DS2 LED (yellow) will be on continuousl y to i ndi cate tha t the uni t is i n c on figu­ration mode. Use the ADVANCE/MANUAL button to sequence through the setup channels. If the value of the channel is less than 5 it will count out the value of the chan­nel on the DS1 LED at 1-second intervals. If the channel value is 5 or great er, the DS1 LED will first c ount out the groups of 5 and then following with the remaining digit.
Verify what Setup Point is being read by pushing the READ/ ADJUST button (#1). First the Red LED will flash the set point number, then the Green LEDs will flash the value. Then, the green DS3 and DS4 LEDs will each come on steady for about 2 seconds. While DS3 is on steady, its new value can be entered by pushing READ/ADJUST (#1), and entering the value for the ten’s digit. When the DS4 comes on steady, enter the value for th e one's d igit. Afte r the green LEDs are off, push the READ/ADJUST button (#1) again to verify that the correct value has been entered. If the configu­ration is a discrete On/off setting, push the READ/ADJUST button (#1) to toggle LED 3 or 4 on or off.
Setup Example 1: Change “Occupied Minimum Position” (configuration item 2) to 53%.
1. Read the General Notes about reading and entering values found on the label on the top of the EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at least 3 seconds until all LEDs flash. The yellow LED will go on steady.
3. Read the current configuration point by pushing but­ton #1. The red LED flashes the configuration point number and the green LEDs flash the current setting for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2 and Note 1 for Setup mode operation.
5. Use button #2 (ADVANCE/MANUAL) to advance to configuration point number 2, Occupied Min.
NOTE: Before performing Step 6, be ready to push button #1; there is a limited time window that can easily be missed when the DS3 green LED comes on, and agai n when the DS4 green LED comes on.
6. Verify the configuration point by pushing button #1. The red LED should flash twice to indic ate point 2, and then the green LEDs will flash the current set­ting.
7. Next, the green DS3 LED wil l turn on steady for 2 seconds. During this time, push button #1 five times.
8. The DS3 LED wi ll turn off and the gree n DS4 LED will go on steady for 2 seconds. During this time, push button #1 three times.
9. The 5 button #1 pushes, followed by the 3 button #1 pushes is the sequ ence that sets the occupied mini ­mum position to 53%.
10. Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. There should be 5 fast blinks of DS3 and 3 slow blinks of DS4.
Setup Example 2: Change the Occupied Minimum Position (item 2) to 2% (lowest value).
1. Read the General Notes about reading and entering values found on the label on the top of the EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at least 3 seconds until all LEDs flash. The yellow LED will go on steady.
3. Read the current configuration point by pushing but­ton #1. The red LED flashes the configuration point number and the green LEDs flash the current setting for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2 and Note 1 for Setup mode operation.
56
Page 57
5. Use button #2 (ADVANCE/MANUAL) to advance to configuration point number 2, Occupied Min.
6. Verify the configuration point by pushing button #1. The red LED should flash twice to indicate point 2, and then the green LEDs will flash the current setting.
NOTE: Since the occupied minimum position MUST be 1 greater than the IAQ minimum position (item 15), the IAQ minimum position must be changed first. (IAQ min has a default value of 5%, whi ch is higher tha n the 2% value i n this example.)
7. Use button #2 (ADV ANCE/MANUAL) to get to config­uration point 15 (IAQ Minimum Position).
NOTE: Before performing Step 8, be read y to pus h button #1; there is a limited time window that can easily be missed when the DS3 green LED comes on, and again wh en the DS4 green LED comes on.
8. Verify the configuration point by pushing button #1. The red LED should flash 15 times to indicate point 15, then the green LEDs will flash the current setting.
9. Next, the green DS3 LED will turn on steady for 2 seconds. During this time, do NOT do anything so that the position defaults to 0.
10. The DS3 LED will turn off an d the green DS4 LED will go on steady for 2 seconds. During this time, push button #1 once to set the point to 1%.
11. Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. DS3 should not blink, and DS4 should blink once.
12. Now configure the Occupied Minimum Position to 2%. Use button #2 (ADVANCE/MANUAL) to get to configuration point 2.
NOTE: Before performing Step 13, be ready to push button #1; there is a limited time window that can easily be missed when the DS3 green LED comes on, and again wh en the DS4 green LED comes on.
13. Verify the configuration point by pushing button #1. The red LED should flash twice to indicate point 2, then the green LEDs will flash the current setting.
14. Next, the green DS3 LED will turn on steady for 2 seconds. During this time, do NOT do anything so that the position goes to 0.
15. The DS3 LED will turn off an d the green DS4 LED will go on steady for 2 seconds. During this time, push button #1 twice to set the point to 2%.
16. Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. DS3 should not blink, and DS4 should blink twice.
NOTE: Configuration items 2, 15, 11, 12, 18 and 19 (in Tabl e 34) are dependent upon other items . Before attempting to change one of these items, be sure to check the value of the item it depends upon (as described in Example 2 above).
IMPORTANT: During SETUP MODE, changes are allowed when the DS3 LED and DS4 LED are lit for 2 seconds (as described in Example 1 and 2 above). During this time, if button #1 is pushed to change one position and not the other, the value for that one position will change and the oth er will default to zero (unless a dependency prevents the zero). How­ever, if button #1 is not pushed at all during the 2 seconds that the green LEDs are lit, the configuration item will not change.
F. Manual Mode
Manual mode is used to contr ol the status of I/O channels for use in troubleshooting. See Table 35.
Enter the Manual mode by holding down the ADVANCE/ MANUAL (#2) button for at least 3 seconds until all LEDs flash and then the red LED comes on steady.
NOTE: A user can only enter the M anual mode from the Run mode, which is entered by pushing buttons #1 and #2 for at least 3 seconds.
All EconoMi$er+ c ontrol output s are tu rned off. “I/O Inputs” 1-5 can be adjusted even if the unit is in operation.
In manual mode, the yellow DS2 LED flashes once to indicate the I/O channel. See Table 35. If the value is less than 5, the yellow DS2 LED will count out the value using 1-second flashes. If the value is greater than 4, the yellow DS2 LED will count out groups of 5 at a high flash rate and then follow with the additional value at a flash rate of once per second. For example a flash of 1 indicates Compressor Relay Output 1.
Push READ/ADJUST button (#1) to read the value. The yel­low LED will flash the I/O Ch annel number being viewed.
Once the channel number is displayed it will then turn on the appropriate green LED (DS3 or DS4) to i ndicate the sta­tus of the output. For relay outputs i f the DS3 LED is on, then the output is on. If DS4 is on, then the output is off. The green DS3 and DS4 LEDs will remain on for about 2 seconds and if during this time the READ/ADJUST (#1) button is pushed, then the output will toggle to the alternate state. To change again, push the READ/ADJUST button and re peat the test or change the status of the output. As an example, for channel 5 (EconoMi$er+ control damper motor) use the READ/ADJUST button to toggle the motor from open to close in %.
At any time, the ADVANCE/MANUAL (#2) button can be used to advance to the next SET I/ O. To exit the mode, push and hold the READ/ADJUST and ADVANCE/MANUAL but­tons (#1 and #2) for more than 3 seconds.
NOTE: After exiti ng the Manual mode, the controller will re­initialize and start with all outputs off.
G. Error Mode
The error mode is used to indicate that an error has occurred The error is indicated by LED #1 red and #2 yellow are on steady.
Enter the RUN mode by pushing the READ/ADJUST and ADVANCE/MANUAL buttons (#1 and #2) for at least 3 sec­onds until all LEDs flash. Next, push and release button #1 to enter the Read mode. Then push button #2 to advance to item 20 (“first most recent error”). Determine the e rror by reading the value in items 20 to 24 and referring to the Trou­bleshooting sect io n.
Once the error has b een fixed, pres s buttons #1 and 2 for at least 3 second s to exit Read mode. All LEDs will flash.
Enter Setup mode by pressing the READ/ADJUST button (#1) for at least 3 seconds. All LEDs will flash. Push the ADVANCE/MANUAL button (#2) to advance to item 20. Push READ/ADJUST to read item 20.
To reset the error code while the green DS4 LED is on, press the READ/ADJUST button (#1) once. In addition to resetting the error mode, this will er ase all error codes. Cycling the power will also erase the error code.
57
Page 58
XVII. ECONOMI$ER+ CONFIGURATION
For most applications, the factory setting will be used to con­trol the EconoMi$er+. How ever, there are 19 differe nt vari­ables that can be used to co nfig ure the control for wide r a nge of applications. The factory settings and variables are shown in Table 34.
IMPORTANT:
There is no way to reset/restore the factory default configurations; use caution when making changes to any set point or operational variable.
The EconoMi$er+ control accepts an occupied/unoccupied switch input. This input is used to control the occupied and unoccupied minimum ventilation damper position as shown in Table 34 items 2 (ECONOMIN_SP) and 3 (U_ECONOMIN_SP). These values represent the minimum damper position. In addi­tion, the controls allows for different modes of compressor opera­tion in the unoccupied mode. Using item 13 in Table 34 (OCC_MODE), the user can select one of the following unoccu­pied modes:
• No unoccupied cooling
• Unoccupied free cooling (EconoM i$er+)
• Unoccupied free cooling and mechanical cooling The EconoMi$er+ will control the cooling operation of the
unit based on the demand from the thermostat outpu ts Y1 and Y2. The EconoMi$er+ will monitor the fan output G, but will not control the fan directly. Note that G must be ener­gized for any cooling to take place. Gas or electric heating will be controlled dire ctly from the thermostat.
When a demand for coo ling occurs, the control will check to see if it is in the occupied or un occupied mode. Depen ding on the configuration, the control will move the outdoor air damper to the vent ilation position . If the outdoor a ir condi­tions are acceptable, then the control will use the EconoMi$er+ for free c ooling. If the supply-air temper ature does not meet the configurable set point, then the control will turn on additional stages of mechanical cooling. Several compressor sequences can be used depending on the applica­tion requiremen ts; these will be covered in t he mechanical compressor staging section.
A. Compressor Configuration And Control
The EconoMi$er+ control can support fro m 1 to 4 compres­sor stages. For the 3 to 12 2 stages of compressor cooling, so the control is factory configured for 2 stages. There is no difference between 1 and 2 stages. The control also provides the option to configure for high sensible o r hi gh latent loads , but for units with o nl y t wo compressors this option does not apply.
Compressors are co nfigured using item 10 (STAGE_TYPE) in Table 34. The control also has the capability of controlling directly to Y1 and Y2 inputs. The contr ol can be configured to control to the leaving-air temperature using Y1 and Y2 as a low cool and high cool demand based on the supply air set point and the rate of change of supply-air temperature. For low cool the leaving air temperature set point will be SAT_SP +2° F. For high cool the leaving air temperatur e set point will be the supply-air temperature set point (SAT_SP).
To use this option, configure the compressor sequencing vari­able (STAGE_ TYPE ) to a valu e of 3. Con figur e the supply air temperature set point (SAT_SP) to the desired leaving air temperature.
NOTE: The supply air temperature s et point is also the tem­perature used for EconoMi$er+ control.
The logic will control the operation of the compressors depending on the configuration selected. If free cooling can be used, then the compressors will be integrated with the EconoMi$er+ to provide the lowest cost cooling control. The
1
/2 ton units, there will only be 1 or
logic includes time guards on the compr essors to provide a minimum of 3 minutes on and 3 minut es off time. T he con­trol will also prevent two compress ors from starting at the same time. The logic uses th e Econo Mi$er+ to pre vent r apid cycling of the compressors and l ow air temperatures.
B. Ventilation Air And Free Cooling
In order for the EconoMi $er+ to control ventilation air and free cooling, several items must be configured.
EconoMi$er+ Type First, select the EconoMi$e r+ control type that will be used.
This is the EconoMi$er+ Type function (ECONO_TYPE) defined by item 5 in Table 34. The choices are:
1. Vent only — This is used to have just ventilation con­trol. The EconoMi$er+ will not provide free cooling, but the occupied and unoccupied minimum positions can be used.
2. Proportional — In this configuration, full propor­tional EconoMi$er+ control will be used. When EconoMi$er+ free cooling cannot be used, the damp­ers will be set to the appropr iat e occ upie d and unoc ­cupied minimum positions.
3. Three-Position — This mode of EconoMi$er+ is used to provide a mini mum venti lation Ec onoMi$e r+ posi­tion and a fixed free cooling or high ventil ation posi­tion. The high ventilation position is controlled by the optional Remote EconoMi$er+ Enable Switch Input connected to terminals 11 and 12 on T3.
Supply Air Temperature Set Point Once the type of Econ oMi$e r+ cont rol ha s been selecte d, the
user will need to set the Supply Air Temperature set point (SAT_SP). The SAT_SP has a range of 40 to 65 F.
NOTE: This will be the set point when both Y1 and Y2 are closed. When just Y1 is closed, the set point will be ° F higher.
Minimum Damp er Position Set the occupied mi nimum damper position (E CONOMIN _SP)
and unoccupied minimum position (U_ECONOMIN_SP). These should be set t o pr ov ide the ventilation requirements at full occupancy as defined by the building specifications. When demand ventilation is used, the control will close the dampers below this position based on measur ed CO to provide additional operation savings.
The control wil l also a llow for the use o f a remo te mini mum position potentiometer. This will only adjust the Occupied Minimum position. If used, the software set point ECONOMIN_SP sho uld be se t to 0 as the contr ol wi ll use the largest set point.
The damper position is not linear with the amount of outside air, so the user will need to set the position of the EconoMi$er + acco rdi ngly. It is best to use the fo llow ing equ a­tion and measured data to set the position:
SAT – RAT
OA =
OAT – RAT
OA = % outdoor air SAT = supply air temperature RAT = return air temperature OAT = outdoor air temperature
The SAT and OAT val ues can be read from the control and, if the unit is equipped with an RAT sensor, then all three values can be read. For the calculation to work properly, there should be at least a 10° F difference between the OAT and RAT temperatures.
*100
levels in the space
2
58
Page 59
Maximum Damper Position Set the maximum EconoMi$er+ position. Normally this is
set at 100%. If using 3-position control or there is a reason not to use 100% outside air, this can be set using the EconoMi$er+ Maximum Position (MAX_POS_SP).
Compressor Lockout Temperature Set the Compressor Lockout Temperature. The Compressor
Lockout Temperature (CMP_LOCK) is used to prevent com­pressor from running at low ambient conditions when an EconoMi$er+ can easily satisfy the load.
EconoMi$er+ Changeover Control Determine the type of EconoMi$er+ changeover control
which will be used to enable and disable free cooling. This is done using the EconoMi$er+ Changeover Type.
1. Switch — This changeover setting is used when a remote signal from an energy management system will enable and disable the EconoMi$er+. This is done through a remote EconoMi$er+ enable switch.
2. Outdoor Dry Bulb — For this changeover setting, the EconoMi$er+ w ill be en abled b ase d on the ou tdo or-air temperature. The EconoMi$er+ is shipped with an outdoor air temperature sensor. The outdoor air tem­perature set point can be configured by th e user. The EconoMi$er+ will be disabled when the outdoor-air temperature rises above the set po int. The co nfigura­tion variable is the EconoMi$er+ Changeover set point (OAT_SP).
3. Differentia l Dry Bulb — For this changeover setting, the EconoMi$er+ will be en abled whenever the out­side-air temperature is lower than the return-air temperature. No configuration of set points is required other than to sel ect the differe nt ial dry bu lb function.
4. Outdoor Enthalpy — For this changeover setting, the control will enable the EconoMi$er+ based on the outdoor-air enthalpy curves as shown in Fig. 29. Using the EconoMi$er+ Changeover set point (ENTHALPY_SP), select curves A, B, C or D. The control will then use the EconoMi$er+ at conditions below the curve. The control uses the OAT and optional humidity sensor to calculate the enthalpy and also has the A, B, C, and D curves stored in memory.
5. Differential Enthalpy — For this changeover setting, the EconoMi$er+ will be enabled based o n the com­parison of the enthalp y of the return air and outs ide air. If the outside air enthalpy is lower than the return air, then the EconoMi$er+ will be enabled. To use this option, an accessory outside air humidity sensor, a return air dry bulb sensor and a return air humidity sensor must be ordered and installed. No configuratio n of set points is required other th an to select the function.
C. Demand Ventilation Configuration
The EconoMi$er+ control has demand ventilation control capability when using an IAQ sen sor. The indoor air qualit y (IAQ) is measured using a CO
sensor. The IAQ sensor can
2
be field-installed in the return duct or the occupied space. The EconoMi$er+ control algorithm modulates the po sition
of the EconoMi$er+ damper between two user configurations depending upon the relationship between the IAQ and the Outdoor Air Quality (OAQ). The lower of these two positions is referred to as the Min imum IAQ Min imum EconoM i$er+ Position (IAQMIN_SP).
The higher position is referred to as the Occupied EconoMi$er+ Minimum Position (ECONOMIN_SP). The IAQMIN_SP should be set to an EconoMi$er+ position that brings in enough fresh air to remove contaminants and CO
generated by sources
2
other than people. The ECONOMIN_SP should be set to an EconoMi$er+ position that brings in enough fresh air to remove contaminants and CO
generated by all sources including peo-
2
ple at the design value for maximum occupancy. A reference differential CO
level above the outside CO
2
level is used as the starting point for IAQ control and another reference differential level for maximum ventilation at design occupancy is used for the end of IAQ control. Between these points the control wi ll modulate the da mpers open from the IAQMIN_SP and the ECONOMIN_SP set­points. The damper position will never go above ECONOMIN_SP or below IAQMIN_SP.
The control does not measure the outdoor IAQ reference level as these levels are relatively constant. The installer should take a measurement at start-up of the unit and enter this value into the control using the Outdoor Air IAQ refer­ence level configuration.
The control is configured for air quality sensors which pro­vide 4 mA at 0 ppm and 20 mA at 2000 ppm. If a sensor has a different range, these bounds must be reconfigured.
To configure the control for an IAQ sensor perform the fol­lowing steps:
1. Determine the Occupied EconoMi$er+ Minimum posi­tion (ECONOMIN_SP) and enter it into the control.
2. Determine the IAQ minimum EconoMi$er+ position (IAQMIN_SP) and enter it into the control.
3. Enable IAQ control using IAQ Enable (IAQ_FL G ).
4. Determine the Outdoor Air IAQ Reference (OAQ) and enter it into the control.
NOTE: The value entered into the control will be the CO ppm level divided by 10. For example, 400 ppm would be entered as 40.
5. Determine the lower control point differential level (DAQLO) and enter it i nto the control. This is a dif­ferential level so if the desired level to start IAQ con­trol is 500 ppm and the OAQ reference level is 400 then a value of 100 would be used.
NOTE: The value entered into the control will be the CO ppm level divided by 10. For example 100 ppm would be entered as 10.
6. Determine the upper control point differential level (DAQHI) and enter it into the control. This is a differ­ential level so if the desired leve l to star t IAQ co ntrol is 1100 ppm and the OAQ reference level is 400 then a value of 700 would be used.
NOTE: The value entered into the control will be the CO ppm level divided by 10. For example 700 ppm would be entered as 70.
D. Power Exhaust Configuration
The EconoMi$er+ can control up to 2 stages of power exhaust. Power exhaust activation is done through config­urable damper pos ition set points. The first stage of power is controlled by relay C4 on the EconoMi$er+ board. The acti­vation point for the first stage is set using the Power Exhaust Stage 1 Activation set point (PE_SP1 ). The second stage of powe r exhaust mus t be set at a v alue greater than the first stage. It is configured using the Power Exhaust Stage 2 Activation set point (PE_SP2).
2
2
2
2
59
Page 60
XVIII. OPERATING SEQUENCE
A. Cooling, Units Without EconoMi$er+
When thermostat calls for cooling, terminals G and Y1 and the compressor contactor (C) are energized. The indoor (evap­orator) fan motor (IFM), compressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. When the thermostat is satisfied, C is deen­ergized and the compressor and OFM shut off. After a 30-second delay, the (IFM) shuts off. If the thermostat fan selector switch is in the ON position, the evaporator motor will run continuously.
B. Heating, Units Without EconoMi$er+
When the thermostat call s for heatin g, terminal W1 is ener­gized. The induced-draft motor is energized and the burner ignition seque nce begins. The indoor (evaporator) fan m otor (IFM) is energized 45 seconds after a flame is ignited. When additional he at is n eeded, W 2 is en ergized and t he high- fire solenoid on the main gas valve (MGV) is energized. When the thermostat is sati sfied and W1 is deenergiz ed, the IFM stops after a 45-second time-off delay.
C. Cooling, Units With EconoMi$er+
For EconoMi$er+ operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position.
When the EconoMi$er+ control is the occupied m ode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operat ion. If the fan is not on, th en cooling will not be activated. If the fan is on, then the control will open the EconoMi$er+ damper to the minimum position.
On the initial p ower to the EconoMi$er+ board, it will ta ke the damper up to 2
1
/2 minutes before it begins to position itself. With subsequent fan signal (G) to the board, the change in damper position will take up to 30 seconds to ini­tiate. Damper movement from full closed to full open (or vice versa) will take 2
1
/2 minutes.
If the damper is in the process of a change (for example going to 100% open) and the signal (G) is turn ed off, the damper will continue to open to 100% before it closes (due to no fan signal [G]).
If free cooling c an be used as determin ed from the appr opri­ate changeover command (switch, dry b ulb, enthalpy curv e, differential dry bulb, or differential enthalpy), then the con­trol will modulate the dampers open to main the supply air temperature set point plus 2° F.
If there is a further demand for cooli ng (coo li ng secon d st age — Y2 is energized), then the control set point for the l eaving air will be set at the supply air set point to increase the cool­ing capacity. If this cannot satisfy the load then the control will bring on comp ressor stages as needed to maintain the supply air temperatu re set point. The EconoM i$er+ damper will be locked o pen at 100% or the maximu m damper posi­tion set point.
To ensure that there is oil return, the compressors will oper­ate for at least 3 minutes. If, during this period, the leaving temperature drops below the set point by 5° F, then the EconoMi$er+ dampers will be closed to 60% until the com­pressor is turned off to avoid cold leaving air temperatures.
If the conditions are not suitable for free cooling then the EconoMi$er+ dampers will be closed to the minimum venti­lation posit ion.
Compressor stage s will be used to co ol the air. If the control is configured for direct control by Y1 and Y2, then the stages will sequence based on the demand of Y1 and Y2. If the control is configured for leaving air temperature control, then Y1 will maintain the leaving air temperature at the supply air set point plus 2° F. If Y1 and Y2 are closed, then the leaving air will be c ontrolled t o the supp ly air se t point. If Y2 is closed and Y1 is open, then control will shut down and indicate an error due to a thermostat failure or improper wiring of the thermostat.
If the unit is in the unoccupied m ode, then the control of the temperature will depend on the unoccupied free cooling con­figuration: no unoccupied cooling, unoccupied free cooling with any mechanical cooling, or unoccupied free and mechanical cooling. If free cooling is enabled, then the con­trol will check if free cooling can be used. The EconoMi$er+ will then control to the leaving air temperature set point plus 2° F for a Y1 command, or the leaving air temperature set point for a Y1 and Y2 command. If me chanical coo ling is allowed to be used, then the control will then bring on addi­tional stages o f me chani cal coo lin g i f f ree co ol in g c annot sa t­isfy the load.
If the EconoMi$er+ control:
• is in the occupied mo de
• is configured to use demand ventilation
• cannot use free cooling
• has return air or space CO
levels below the DAQLO
2
limit,
then the EconoMi$er+ damper position will be set to the IAQMIN_SP set point. If the CO2 level rises above the DAQLO limit, then the dampers will modulate open in a lin­ear relationship un til the return air o r space CO
levels are
2
at or above th e D AQHI l imit . The da mpe r p o siti on w il l be at the ECONOMIN_SP set point.
When the EconoMi$er+ is being used for free cooling and the position exceeds the power ex haust set point, then the con­trol will turn on the appropriate power exhaust fans. Refer to Fig. 23 for barometric relief capacit y, Fig. 24 for outdoor air leakage, and Fig. 25 for pressure drop.
Unoccupied and Occupied Minimum Position Control There is an unoccupied minimum damper position and an
occupied minimum damper position on the EconoMi$er+ controller. When the HVAC fan is off the outdoor air damper will always be closed. W hen the f an is on an d in the unoccu ­pied mode, the outdoor air damper will be at the unoccupied minimum position . When the fan is on (G call ) and in the occupied mode, the outdoor air damper will be at the occu­pied minimum position.
A jumper wire is factory-installed to force the unit into o ccu­pied configurat io n wh ene ver G or Y1 are clos ed. Withou t the jumper wire, the unit will always be in unoccupied mode.
The 2 minimum position settings are also used in the IAQ sequence of operation. See Indoor Air Quality Sensor on page 21.
NOTE: The minimum position signal takes priority over the maximum position sign al. If th e maxi mum da mper positi on is set below the minimum damper position, the EconoMi$er+ controller will maintain the actuator at minimum position.
60
Page 61
Adjust the unoccupied minimum position to allow the mini­mum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F (6 C) temperature difference b etween the outdoor and return air temperatur es.
To determine the unoccupied minimum position setting, per­form the following procedure:
Calculate the appr opriate supply-ai r temperature using the following formula: (TO x OA) + (TR x RA) = TM
TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Supply-Air Temperature
As an example, if local codes requ ire 10% outdoor air duri ng occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F:
(60 x 0.10) + (75 x 0.90) = 73.5 F
Carefully adjust the unoccupied minimum position until the measured supply-air temperature matches the calculated value. Then, carefully adjust the occupied minimum position set point on the controller until the desired position is reached.
D. Heating, Units With Economizer+
When the thermostat call s for heatin g, terminal W1 is ener­gized. The induced-draft motor is energized and the burner ignition seque nce begins. The indoor (evaporator) f an motor (IFM) is energized 45 seconds after a flame is ignited. When additional he at is n eeded, W 2 is en ergized and t he high- fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay. The economizer damper moves to the minimum position. When the thermo­stat is satisfied, the damper moves to the fully closed position.
SERVICE
CAUTION: When servicing unit, shut off all elec-
trical power to unit and tag disconnect to avoid shock hazard or injury from rotating parts.
I. CLEANING
Inspect unit interior at the beginning of each heating and cooling season or more frequently as operating conditions require.
A. Evaporator Coil
Clean coil as re quired. Inspect coil at beginning of heating and cooling seasons.
1. Turn unit power off and install lockout tag. Remove evaporator coil access panel.
2. If economizer is installed, remove economizer by dis­connecting Molex plug and removing economizer mounting screws. Refer to Accessory Economizer Installation Instructions or Optional EconoMi$er+ section on page 18 for more detail s.
3. Remove filters from unit.
4. Clean coil using a commercial coil cleaner or dish­washer detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-flush toward return-air section to remove foreign material . Caution should be taken
as to not overflow the evaporator drain condensate pan.
5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
8. Replace access panels.
B. Condenser Coil
Inspect coil month ly. Clean condenser coil annually, and as required by location an d outdoor-air conditions.
One-Row Coils Wash coil with commercial cleaner. Clean outer surfaces
with a stiff brush in the no rmal manne r. It is not necessar y to remove top panel.
2-Row Coils Clean coil as follows:
1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 37. To hold top panel open, place coil corner post between top panel and center post. See Fig. 38.
4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at return end of condenser coil. Carefu lly separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 39.
6. Use a water hose or other suitable equipment to flush down between the 2 coil s ections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
7. Secure inner and outer coil rows together with a field­supplied fastener.
8. Reposition the outer coil se ction and remove the coil corner post from between the top panel and center post.
9. Reinstall the coil corner post and replace all screws.
C. Condensate Drain
Check and clean each year at star t of coo lin g sea so n. I n win ­ter, keep drain dry or protect against freeze-up.
D. Filters
Clean or rep lace at s tar t of e ach h eati ng an d co oling seas on, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
Fig. 37 — Cleaning Condenser Coil
61
Page 62
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at the factory.
B. Fan-Motor Bearings
Fan-motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of
condenser-fan or evaporator-fan motors is required.
III. CONDENSER FAN ADJUSTMENT (Fig. 40)
1. Shut off unit power supply and tag disconnect.
2. Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 40.
4. Tighten setscrews and replace condenser-fan assembly.
IV. BLOWER BELT ADJUSTMENT
Inspect blower b elt for we ar, proper belt tension, and pu lley alignment as conditions require or at the beginning of each heating and air conditioning season. Refer to Step 9 — Adjust Evaporator Fan Speed on page 27 for adjustment and alignment pro ced ures.
V. MANUAL OUTDOOR-AIR DAMPER
If outdoor-air damper blade is required, see Manual Outdoor-Air Damper section on page 17.
VI. ECONOMIZER ADJUSTMENT
Refer to Optional EconoMi$er+ section on page 18.
VII. CONDENSER COIL GRILLE
Condenser coil grille is shipped factory-installed. No adjust­ments are required.
VIII. HIGH-PRESSURE SWITCH
Located on the compressor’s hot gas line is a high-pressure switch. This switch opens at 428 psig and closes at 320 psig. No adjustment is necessary. Refer to Tables 1A and 1B.
NOTE: Th ere is no Sch rader cor e in the valve be low the hig h­pressure switch.
IX. LOSS-OF-CHARGE SWITCH
Located on the condenser’s liquid line is a low-pressure switch which functions as a loss-of-charge switch. This switch contains a Schrader core depr es sor. This switch opens at 7 psig and closes at 22 psig. No adjustment is necessary. Refer to Tables 1A and 1B.
X. FREEZESTAT
Located on the “hair pin” end of the evaporator coil is a bimetal temperature sensing switch. This switch protects the evaporator coil from f reeze-u p due to lack of ai rflow. The switch opens at 30 F and closes at 45 F. No adjustment is necessary. Refer to Tables 1A and 1B.
XI. CHECKING AND ADJUSTING REFRIGERANT CHARGE
The refrigerant system is fully charged with R-22 refriger­ant, tested, and factory-sealed. Unit must operate in Cooling mode a minimum of 10 minutes before checking charge.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R-22 charge.
A superheat charging chart is attached to the outside of the service access panel. The chart incl udes the re qui red suction
Fig. 38 — Propping Up Top Panel
Fig. 39 — Separating Coil Sections
580F UNIT VOLTAGE FAN HEIGHT “A” (in.)
208/230 V 2.75
460 V and 575 V 3.50
Fig. 40 — Condenser-Fan Adjustment
line temperature at given suction line pressures and outdoor ambient temperatures.
An accurate superheat, thermocouple-type or thermistor­type thermometer, and a gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type ther mometers
because they are not adequate for this type o f measu rement.
CAUTION: When evaluating the refrigerant charge, an indicated adjustment to the specified fac­tory charge mus t al w ays be very minimal. If a substan­tial adjustment is indicated, an abnormal condition exists somewhere in the cool ing system , such as in suf­ficient airflow across either coil or both coils.
62
Page 63
Proceed as follows:
1. Remove caps from low-pressure and high-pressure Schrader valve fit tings.
2. Using hoses with valve core depressors, attach low- and high-pressure gage hoses to low-pressure and high-pressure service fittings, respectively.
3. Start unit in Cooling mode and let unit run until sys­tem pressure stabilize.
4. Measure and record the following: a. Outdoor ambient-air temperature (F db). b. Evaporator inlet-air temperature (F wb). c. Suction-tube temperature (F) at low-side service
fitting.
d. Suction (low-side) pressure (psig).
5. Using “Cooling Charging Charts” compare outdoor­air temperature (F db) with the suction line pressure (psig) to determine desired system operating suction line temperature. See Fig. 41-48.
6. Compare measured suction-tube temperature with desired suction-tube temperature. Using a tolerance of ± 3° F, add refrigerant if me asured temp eratur e is more than 3° F higher than proper suction-tube tem­perature, or remove refrigerant if actua l temper ature is more than 3° F low er than required s uction-tube temperature.
A. To Use Cooling Charging Chart
This method is to be use d in Co oling m ode only. Take the out­door ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temp erature is low, carefully recover
CIRCUITS 1 AND 2
Fig. 41 — Cooling Charging Chart; 580F090
some of the charge. Recheck the su ction pressure as charge is adjusted. Example (Fig. 44, Circuit 2):
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . .85 F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74 psig
Suction Temperature should be . . . . . . . . . . . . . . . . . . . .5 6 F
(Suction temperature may vary ± 3 F.)
CIRCUIT NO. 1
Fig. 42 — Cooling Charging Chart; 580F102
CIRCUIT NO. 2
63
Page 64
CIRCUIT NO. 1
Fig. 43 — Cooling Charging Chart; 580F120
CIRCUIT NO. 2
Fig. 44 — Cooling Charging Chart; 580F150
64
Page 65
Fig. 45 — Cooling Charging Chart; 580F091
Fig. 46 — Cooling Charging Chart; 580F103 (Circuits 1 and 2)
65
Page 66
Fig. 47 — Cooling Charging Chart; 580F121
Fig. 48 — Cooling Charging Chart; 580F151
66
Page 67
XII. FLUE GAS PASSAGEWAYS
To inspect the flue collector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section below.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
XIII. COMBUSTION-AIR BLOWER
Clean seasonally to assure proper airflow and heating effi­ciency. Inspect blower wheel eve ry fall and periodical ly dur­ing heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 6 screws that attach induced-draft motor housing to vestibule plate (Fig. 49).
3. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, remove 2 setscrews.
5. To remove motor, remove the 4 screws that hold blower housing to mount ing pla te. Remove th e motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate.
6. To reinstall, reverse the pro c edure outlined above.
XIV. LIMIT SWITCH
Remove blower acce ss panel (F i g. 1A an d 1B). Limi t swit ch is located on the fan deck. Verify operation of limit by te mpo­rarily blocking return air until limit trips.
XV. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box (Fig. 11). Module contains a self-diagnostic LED. A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is interrupted. When a brea k in power occurs, the modu le will
ROLLOUT SWITCH
be reset (resulting in a loss of fault history) and the i ndoor (evaporator) fan ON/OFF times will be reset. For additional information, refer to the Start-Up, Heating section on page 51. The LED er ror code can be observed through the viewport. See Fig. 11. During servicin g refer to the l abel on the control box cover or Table 36 for an explanation of LED error code descriptions.
If lockout occurs, unit may be adjusted by interrupting power supply to unit for at least 5 seconds.
XVI. MAIN BURNERS
At the beginning of each heating season, inspect for deterio­ration, blockage due to corrosion or other causes. Observe the main burner flames and replace burners if necessary.
CAUTION: When working on gas train, do not hit
or plug orifice spuds.
A. Removal and Replacement of Gas Train (Fig. 49 and 50)
1. Shut off manual gas valve.
2. Shut off power to unit and install lockout tag.
3. Slide out burner section side panel (not shown).
4. Disconnect gas piping at unit gas valve using backup wrench on the flats of the valve body where the gas pipe enters the gas valve. See Fig. 49.
5. Remove wires connected to gas valve. Mark each wire.
Table 36 — LED Error Code Description*
LED INDICATION ERROR CODE DESCRIPTION
ON Normal Operation
OFF Hardware Failure
1Flash† Evaporator Fan On/Off Delay Modified 2Flashes Limit Switch Fault 3Flashes Flame Sense Fault 4Flashes 4 Consecutive Limit Switch Faults 5Flashes Ignition Lockout Fault 6Flashes Induced-Draft Motor Fault 7Flashes Rollout Switch Fault 8Flashes Internal Control Fault 9Flashes Software Lockout
LEGEND
LED — Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in numerical sequence.
†Indicates a code that is not an error. The unit will continue to operate
when this code is displayed.
IMPORTANT: Refer to Troubleshooting Tables 38-40 for additional information.
Fig. 49 — Burner Section Details
BURNER SECTION
FLUE
FLUE EXHAUST
EXHAUST
VESTIBULE PLATE
INDUCED-DRAFT MOTOR
MANIFOLD PRESSURE TAP
GA S VA LVE
GA S VA LVE FLATS
Fig. 50 — Burner Tray Details
67
Page 68
6. Remove wires from ignitor and sensor wires at the Integrated Gas Unit Controller (IGC).
7. Remove the 2 screws that attach the burner rack to the vestibule plate.
8. Slide the burner tray out of the unit (Fig. 50).
9. To reinstall, reverse the procedure outlined above.
B. Cleaning and Adjustment
1. Remove burner rack from unit as described in Removal and Replacement of Gas Train section, above.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cro ss-over port as required.
4. Adjust spark gap. See Fig. 51.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and Replacement of Gas Train section, this page.
XVII. REPLACEMENT PARTS
A complete list of repl acement parts may be obtained from any Bryant distributor upon request.
580F090,091,102,103 125,000 BTUH INPUT
NOTE: Dimensions in ( ) are millimeters.
580F090,091,102,103,120,121
180,000 BTUH INPUT
580F090,091,102,103,120,121,150,151
220,000 BTUH INPUT AND 580F120,121,150,151
250,000 BTUH INPUT
Fig. 51 — Spark Gap Adjustment
68
Page 69
TROUBLESHOOTING
I. ECONOMI$ER+ TROUBLESHOOTING
The EconoMi$er+ control has built-in diagnostics. The con­trol can detect and display 10 different diagnostic codes as shown in Table 37. The us er ca n al so us e the integra ted dis­play to check the status of all the inputs and outputs and run the manual control mode to check the operation of the EconoMi$er+ and compressors.
Table 37 — EconoMi$er+ Error Codes
NO. DESCRIPTION CRITERIA
1 SAT Sensor Failure Temperature <–40 F or Greater Than 250 F 2 RAT Sensor Failure Temperature <–40 F or Greater Than 250 F 3 OAT Sensor Failure Temperature <–40 F or Greater Than 250 F 4 ORH Sensor Failure Read Less Than 2 mA or Greater Than 22 mA 5 IRH Sensor Failure Read Less Than 2 mA or Greater Than 22 mA 6 IAQ Sensor Failure Read Less Than 2 mA or Greater Than 22 mA 7 Y2OnY1 Off Wiring Error 8 Micro Fails E2 Tests Hardware/Software Check
* Micro Fails RAM Test Hardware/Software Check
Micro Fails ROM Tests Hardware/Software Check
IAQ — Indoor Air Quality IRH — Indoor Relative Humidity OAT — Outdoor Air Temperature ORH — Outdoor Relative Humidity RAT — Return Air Temperature SAT — Supply Air Temperature
*If there is a RAM failure DS1+DS3/DS2+DS4 will alternately flash.
†If there is a ROM failure DS1+DS2/DS3+DS4 will alternately flash.
LEGEND
A. Error Code 1 — SAT Sensor Failure
Error Criteria An SAT Sensor Failure error will occur if the sensor is
shorted or faulty. If the measured temperature reads below –40 F or above 250 F an error will occur.
Required Action If an error occurs, then the control will default to Mode 2
compressor stage contro l where Y1 and Y2 have direct con­trol of the compressors. Use of free cooling is disabled and the EconoMi$er+ will be set to the minimum damper posi­tion for either the occupied or unoccupied mode of operation. Replace sensor if faulty.
Reset Method The error will automatically reset after the value has
returned to a normal level. The alarm h as to be cleared from the display in the Setup mode or a power reset.
B. Error Code 2 — RAT Sensor Failure
Error Criteria The RAT Sensor failure error is only applicable the unit has
been configured for EconoMi$er+ changeover methods 3 (dif­ferential dry bulb) or 5 (differential humidity). For other modes it should be ignored. If the sensor is shorted or faulty, then the measured tempe r atur e w ill be below –40 F or abo v e 250 F and the error will occur.
Required Action If this error occurs, then change the default EconoMi$er+
changeover control to method 2 (dry bulb changeover con­trol) or replace sensor.
Reset Method This error will automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Se tup mode.
C. Error Code 3 — OAT Sensor Failure
Error Criteria An OAT Sensor Failure error occurs if the sensor is short ed
or faulty, then the measured temperature will be below –40 F or above 250 F.
Required Action — If this error occurs disable the economizer and set the
economizer to the minimum economizer position. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
D. Error Code 4 — ORH (Outdoor Relative Humidity) Sensor Failure
Error Criteria If the unit is configured for economizer changeover type 3 or
4, and the input signal is less than 2 mA or greater than 22 mA, then the sensor is faulty and an error will occur.
Required Action If this error occurs, switch the EconoMi$er+ to dry bulb
changeover control. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
E. Error Code 5 — IRH (Indoor Relative Humidity) Sensor Failure
Error Criteria This error occurs if th e unit is configured for EconoMi$er+
changeover type 5 and the input signal is less than 2 mA or greater than 22 mA (faulty sensor).
Required Action If this error occurs, switch the EconoMi$ er+ to differential
dry bulb changeover control. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
F. Error Code 6 — IAQ Sensor Failure
Error Criteria This error occurs if th e unit is configured for IAQ demand
ventilation control and the input signal is less than 2 mA or greater than 22 mA (faulty sensor).
Required Action If this error occurs, disable the IAQ control routine and
default to the standard EconoMi$er+ minimum position. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
G. Error Code 7 — Y2 On with Y1 Off
Error Criteria This error occurs if Y 2 is turned on and Y1 is of f. This indi-
cates that there is a wiring error at the thermostat connec­tions. This alarm sho uld be ignored fo r the first 20 sec onds of operation so tha t it does no t co nfl ic t wit h th e sp ec ial pr odu c­tion test mode.
69
Page 70
Required Action Shut the unit off and chec k wiring. Reset Method This error must be manu ally reset and re quires a power reset .
H. Error Code 8 — E2 Test Failure
Error Criteria This error occurs if internal hardware detects an E2 failure. Required Action Shut the un it off. Reset Method This error must be manually reset and requires a power reset.
I. Error Mode
When an error occurs, the red and yellow LEDs both come on steady. To determine the error, follow these steps:
1. Enter the Run mode by pushing buttons #1 and #2 for at least 3 seconds until all LEDs flash.
2. Press and release the #1 button to enter the Read mode.
3. Push the ADVANCE/MANUAL (#2) button to advance to item number 20, “1st Most Recent Error.” Determine the error(s) by reading the values in items 20-24 and referring to the error codes described above.
4. Fix the error(s).
5. Press buttons 1 and 2 to exit read mode. Enter Setup mode by pressing button #1 for at least 3 seconds until all the LEDs flash.
6. Push button #2 to advance to item number 20.
7. To reset t he error cod e while the green D S4 LEDS is ON , press the READ/ADJUST ( #1) button once. This res ets the error mode and erases all repaired error codes.
NOTE: Cycling power to the board will also erase the repaired error codes.
J. RAM Test Failure
Error Criteria If internal hardware detects a RAM failure, this alarm will be
displayed by alternately flashing DS1+DS3 and DS2+DS4. Required Action Shut the unit off. Reset Method This error must be manually reset and requires a power
reset.
K. ROM Test Failure
Error Criteria If internal hardware detects a ROM failure, the alarm is dis-
played by alternately flashing DS1+DS2 and DS3+DS4. Required Action Shut the unit off. Reset Method This error must be manually reset and requires a power
reset.
L. Unit Always In Unoccupied Mode
A jumper wire is factory-installed to force the unit into o ccu­pied configurat io n wh ene ver G or Y1 are clos ed. Withou t the jumper wire, the unit will always be in unoccupied mode. Check the wire. An occupied/unoccupied switch may be installed in pl ace of the j ump er. Ch eck the wi ring and se tting of the switch.
II. UNIT TROUBLESHOOTING
Refer to Tables 38-40 and Fig. 52.
Table 38 — LED Troubleshooting — Error Code
Hardware Failure. (LED OFF)
Fan ON/OFF Delay Modified (LED/FLASH)
Limit Switch Fault. (LED 2 flashes)
Flame Sense Fault. (LED 3 flashes)
4 Consecutive Limit Switch Faults. (LED 4 flashes)
Ignition Lockout. (LED 5 flashes)
Induced-Draft Motor Fault. (LED 6 flashes)
Rollout Switch Fault . (LED 7 flashes)
Internal Control Fault. (LED 8 flashes)
Temporary Software Lockout (LED 9 flashes)
self to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.
SYMPTOM CAUSE REMEDY
Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat exchanger warm-up period before fan-on delay expires.
Limit switch opens within three minutes after blower-off delay timing in Heating mode.
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be present.
Inadequate airflow to unit. Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for 15 minutes.
IGC does not sense that induced-draft motor is operating.
Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue to lock
Microprocessor has sensed an error in the software or hardware.
Electrical interference is impeding the IGC software
CAUTION: If the IGC must be replaced, be sure to ground your-
transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure unit’s external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information. Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
out unit. Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
Reset 24-v to control board or turn the thermostat off and on. Fault will automatically reset itself in one hour.
IMPORTANT: Refer to Heating troubleshooting chart for additional troubleshoot-
ing analysis.
IGC — Integrated Gas Unit Controller LED — Light-Emitting Diode
LEGEND
70
Page 71
Table 39 — Cooling Service Troubleshooting
PROBLEM CAUSE REMEDY
Compressor and Condenser Fan Will Not Start.
Compressor Will Not Start But Condenser Fan Runs.
Compressor cCycles (Other than Normally Satisfying Thermostat).
Compressor Makes Excessive Noise (580F103,121,150, and 151 Scroll Only).
Compressor Operates Continuously. Dirty air filter. Replace filter.
Excessive Head Pressure. Dirty air filter. Replace filter.
Head Pressure Too Low. Low refrigerant charge. Check for leaks, repair, and recharge.
Excessive Suction Pressure. High heat load. Check for source and eliminate.
Suction Pressure Too Low. Dirty air filter. Replace filter.
Compressor No. 2 Will Not Run. Unit in economizer mode. Proper operation; no remedy necessary.
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer,
or control relay. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Faulty wiring or loose connections in com-
pressor circuit. Compressor motor burned out, seized, or
internal overload open. Defective run/start capacitor, overload, or
start relay. One leg of 3-phase power dead. Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or
start relay. Defective thermostat. Replace thermostat. Faulty condenser-fan motor or capacitor. Replace. Restriction in refrigerant system. Locate restriction and remove. Compressor rotating in wrong direction. Reverse the 3-phase power leads as described on
Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and
Condenser coil dirty or restricted. Clean coil or remove restriction.
Dirty condenser coil. Clean coil. Refrigerant overcharged. Remove excess refrigerant. Air in system. Recover refrigerant, evacuate system, and
Condenser air restricted or air short-cycling. Determine cause and correct.
Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction.
Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant.
Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted. Remove source of restriction. Insufficient evaporator airflow. Increase air quantity. Check filter and replace if nec-
Temperature too low in conditioned area. Reset thermostat. Field-installed filter drier restricted. Replace.
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
cause.
to nameplate.
Determine cause and replace.
page 50.
recharge.
recharge.
essary.
71
Page 72
Table 40 — Heating Service Troubleshooting
PROBLEM CAUSE REMEDY
Burners Will Not Ignite.
Inadequate Heating. Dirty air filter. Clean or replace filter as necessary.
Poor Flame Characteristics.
Burners Will Not Unit is locked into Heating mode for a Wait until mandatory one minute time period has Turn Off. one minute minimum. elapsed or power to unit.
Misaligned spark electrodes. Check flame ignition and sensor electrode positioning.
No gas at main burners. Check gas line for air purge as necessary. After purging
Water in gas line. Drain water and install drip leg to trap water. No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control circuit. Check transformer. Transformers with internal overcurrent
Miswired or loose connections. Check all wiring and wirenut connections. Burned-out heat anticipator in thermostat. Replace thermostat. Broken thermostat wires. Run continuity check. Replace wires, if necessary.
Gas input to unit too low. Check gas pressure at manifold. Clock gas meter for input. If too
Unit undersized for application. Replace with proper unit or add additional unit. Restricted airflow. Clean filter, replace filter, or remove any restrictions. Blower speed too low. Use high speed tap, increase fan speed, or install
Limit switch cycles main burners. Check rotation of blower, thermostat heat anticipator settings,
Too much outdoor air. Adjust minimum position.
Incomplete combustion (lack of Check all screws around flue outlets and burner combustion air) results in: compartment. Tighten as necessary.
Aldehyde odors, CO, sooting flame, or floating flame.
Adjust as needed.
gas line of air, allow gas to dissipate for at least 5 min­utes before attempting to relight unit.
Check gas valve.
protection require a cool down period before resetting.
low, increase manifold pressure, or replace with correct orifices.
optional blower, as suitable for individual units.
and temperature rise of unit. Adjust as needed.
Check economizer operation.
Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment.
72
Page 73
C—Contactor, Compressor CB Circuit Breaker COMP — Compressor Motor EQUIP — Equi pment FPT Freeze Up Protection Thermostat GND — Ground HPS High-Pressure Switch HS Hall-Effect Sensor I—Ignitor IDM Induced-Draft Motor IFC Indoor Fan Contactor
Fig. 52 — Typical Unit Wiring Schematic (208/230-3-60 Unit Shown)
LEGEND
IFM Indoor Fan Motor IFMOVL — Indoor Fan Motor Overload Switch IGC Integrated Gas Unit Controller LPS Low-Pressure Switch LS Limit Switch MGV Main Gas Valve OFC Outdoor Fan Contactor OFM Outdoor Fan Motor P—Plug PL Plug Assembly QT—Quadruple Terminal
73
RS Rollout Switch SAT Supply Air Temperature Sensor SEN Sensor TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring To indicate common potential only;
not to represent wiring.
Page 74
PUSHBUTTONS LED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
OFF
ONES OR
TEN'S
OR ON
Names ADJUST ADV SET NO SETUP
Actions Hold/Push Push flash, no steady flash no flash no
SETUP MODE
Note 1 Push and hold the ADJUST button until the SETUP indicator turns on.
Note 2 Push and release ADV button repeatedly to advance to the desired setup point.
Each time the ADV button is pushed, the SET NO flashes the point number and then displays
the current setting
APPENDIX A — ECONOMI$ER+ LABEL
OFF
ONES OR
TEN'S
OR ON
Names ADJUST MAN MAN I/O NO
Actions Push Hold/Push steady flash no flash no flash no
on use the ADJUST button to enter the value. (i.e., push the button 4 times to enter 4)
Then wait for the ONES indicator to turn on and enter the ONES setting
Wait for indicator to turn off and then push read/adjust to check the setting
Note 3 Once the current value has been displayed the TENS indicator will turn on steady and while it
MANUAL
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
Note 1 Push and hold the MAN button until the MAN indicator turns on.
Note 2 Push and release MAN button repeatedly to advance to the desired I/O point.
Each time the MAN button is pushed, the I/O NO flashes the I/O point number.
and off or open and closed
1 SAT sensor invalid
2 RAT Sensor Invalid (only with changeover type 3&5)
3 OAT Sensor Invalid
4 ORH Sensor invalid (only with changeover type 3&4)
5 IRH Sensor invalid (only with changeover type 5)
6 IAQ Sensor Invalid (only if IAQ=1)
7 Y2onY1off
NO DESCRIPTION
Note 3 After the desired I/O No is reached push and release the ADJUST to toggle the output on
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
ALARM CODES
8 Micro Fails E2 test
note 1 Micro Fails RAM test
note 2 Micro Fails ROM test
Note 1 DS1+DS3/DS2+D4 will alternately flash
Note 2 DS1+DS2/DS3+D4 will alternately flash
PUSHBUTTONS LED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
Action flash flash flash flash
Indicators flash in sequence at .5 sec intervals
STARTUP MODE
Note 1
Names HB ECONO Y1 Y2
RUN MODE
Actions flash flash steady steady
Note 1 Heartbeat Indicator flashes to indicate proper operation of the control
Note 2 Econo indicator flashes to indicate free cooling being used
Note 3 Y1 and Y2 are on steady when a call thermostat Y1 and Y2 are closed
Note 4 ERROR - HB and Econo are on steady to indicate the presence of an error
OFF
ONES OR
TEN'S
OR ON
Names READ ADV SET NO I/O NO
Actions Push Push flash, no flash no flash no flash no
READ MODE
Note 1 Push and release the READ button to enter Read Mode. The SET NO Indicator flashes once
to indicate the setup point is selected for viewing
Note 2 Push and release ADV button repeatedly to advance to the desired setup point or I/O point
Each time the ADV button is pushed, the SET NO flashes the point number until the desired
I/O point is reached and then the I/O NO flashes the I/O point no.
button to display the value in the TEN's and ONE's indicator (i.e., 5 flashes for a value of 5)
Note 3 After the SET NO indicator identifies the desired point no, push and release the READ
or a steady TEN's indicator for an on and a steady ONE's for off.
To aid in counting, values of 5 are flashed in groups of 5 (i.e., 150 = 3 groups of fast 5 flashes)
and then follow by balance in slow flashes (i.e., 7 = 5 quick flashes + 2 slow flashes)
Red Set No LED displays Setup item numbers, and Yellow I/O LED displays I/O item no
Note 4 Setpoint values are displayed first followed by I/O values and then back to Setpoint values
Note 5 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
NO I/O Points UNITS
I/O POINTS
1 C1 Output -
2 C2 Output -
3 C3 Output -
4 C4 Output -
5 Economizer Damper Output %
6 Supply Air temperature F
7 Outside Air temperature F
8 Return Air Temperature F
9 Indoor Relative Humidity %
10 Outdoor Relative Humidity %
11 Indoor Air Quality PPM
12 Remote Minimum Position %
13 Y1 Status (next version) -
14 Y2 Status (next version) -
15 G Status (next version) -
16 Occ Status (next version) -
74
Page 75
APPENDIX A — ECONOMI$ER+ LABEL (cont)
75
Page 76
APPENDIX B — JOB SPECIFIC ECONOMI$ER+ CONFIGURAITON SETTINGS
Enter the job specific settings in the “Job Setting” column below.
76
Page 77
Access panels
18
Altitude compensation 51 Barometric flow capacity 20 Burner ignition 67 Burner rack 67 Burner section 67 Burner spark gap 68 Charging chart, refrigerant 63-66 Clearance 2, 3, 6 CO2sensor
Configuration
26
Settings 27 Combustion blower wheel 67 Compressor
Lubrication 62
Mounting 50
Rotation 50 Condensate drain
Cleaning 61
Location 4, 6 Condenser coil 8, 10
Cleaning 61 Condenser fan 8, 10
Adjustment 62 Control circuit
Wiring 12
Wiring raceway 16 Demand control ventilation 26 Dimensions 2, 3, 5 Ductwork 4 EconoMi$er+ 18-26, 52-61
Adjustment 62
Components 18
Configuration 58, 59
Controller wiring 20
Damper movement 20
Inputs and outputs 54
Wiring 19 Electrical connections 12 Electrical data 13-15 Enthalpy changeover set points 24 Evaporator coil 8, 10
Cleaning 61 Evaporator fan motor 8, 10
Lubrication 62
Motor data 29
Performance 30-49
Pulley adjustment 27, 28
Pulley setting 8, 10, 28
Speed 28 Factory-installed options
EconoMi$er+ 18-26
Manual outdoor air damper 17 Filter
Cleaning
61
Installation 19
Size 9, 11 Flue gas passageways 67 Flue hood 12 Freeze protection thermostat 9, 11, 62 Gas connection 9, 11 Gas input 9, 11 Gas piping 12, 50 Gas pressure 1, 9, 11, 50 Heat anticipator settings 9, 11, 13 Heat exchanger 9, 11 High flow valves 50 High pressure switch 9, 11, 62 Horizontal units 1, 4 Indoor air humidity sensor 22 Indoor air quality sensor 21 Integrated gas controller 52, 67
Error codes 67, 70 Leak test 50 Limit switch 67 Liquid propane 9, 11 Low pressure switch 9, 11, 62 Main burners 51, 67
INDEX
Manual outdoor air damper 17, 62 Mounting
Compressor 50
Unit 6 Natural gas 9, 11 Operating limits 4 Operating sequence 60, 61
Cooling 60
EconoMi$er+ 60, 61
Heating 60 Outdoor air hood 17, 19 Outdoor air humidity sensor 22, 24 Outdoor air inlet screens
Dimensions 9, 11 Outdoor air temperature sensor 21 Physical data 8-11 Power supply
Wiring 12, 16 Pressure switches
High pressure 9, 11, 62
Low pressure 9, 11, 62 Pre-Start-Up 50 Refrigerant
Charge 8, 10, 62-66
Type 8, 10 Refrigerant service ports 50 Replacement parts 68 Return air filter 9, 11, 50 Return air temperature sensor 21, 22 Rigging unit 4, 7 Roof curb
Assembly 1
Dimensions 5
Connector package 5
Leveling tolerances 6
Wei gh t 8, 10 Safety considerations 1 Safety relief 52 Service 61-68 Service ports 50 Slab mount 4 Start-up 50-61 Start-up checklist CL-1 Thermostat 12, 16 Troubleshooting 69-73 Ventilation 52 Wei gh t
Corner 2, 3
EconoMi$er+ 2, 3, 8, 10
Unit 2, 3, 7, 8, 10 Wiring
EconoMi$er+ 19
Power connections 16
Thermostat 16
Unit 73
77
Page 78
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increas e your knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our labs can mean increased confidence tha t real ly pays dividen ds in fas ter trou bles hoo ting a nd fewer call ­backs. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] Classroom Service Training
Copyright 2004 Bryant Heating & Cooling Systems CATALOG NO. 5358-024
Page 79
Page 80
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO. _______________________________________ DATE: _____________________________________________ UNIT NO.: _________________________________________
SERIAL NO. ___________________________________________ TECHNICIAN: _________________________________________ JOB LOCTION:______________________________ ___________ JOB NAME:____________________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE SHIPPING TIE DOWN BANDS ON COMPRESSOR (SIZE 150 AND 151 ONLY) PER INSTALLATION INSTRUCTIONS
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FOR LEAKS
CHECK THAT RETURN-AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
ENSURE BELT TENSION IS CORRECT AND BLOWER PULLEYS ARE PROPERLY ALIGNED.
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 COMPRESSOR AMPS L1 L2 L3 COMPRESSOR AMPS L1 L2 L3 INDOOR-FAN AMPS L1 L2 L3
CUT ALONG DOTTED LINE
TEMPERATURES AND PRESSURES
OUTDOOR-AIR TEMPERATURE DB RETURN-AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR DB
GAS INLET PRESSURE IN. WG GAS MANIFOLD PRESSURE IN. WG (HI FIRE) IN. WG (LO FIRE) REFRIGERANT SUCTION PRESSURE PSIG — CIRCUIT NO. 1 PSIG — CIRCUIT NO. 2 REFRIGERANT TEMP. (SUCTION) PRESSURE CIRCUIT NO. 1 CIRCUIT NO. 2 REFRIGERANT DISCHARGE PSIG — CIRCUIT NO. 1 PSIG — CIRCUIT NO. 2 DISCHARGE TEMPERATURE °F/C — CIRCUIT NO. 1 °F/C — CIRCUIT NO. 2
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION (580F103,121,150,151 ONLY)
CUT ALONG DOTTED LINE
Copyright 2004 Bryant Heating & Cooling Systems CL-1 CATALOG NO. 5358-024
Loading...