SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 580F-36-3II 580F-36-4
580F
Pac
Series
Sizes 036-073
3 to 6 Tons
1/15/04
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation
instructions before installing this unit (Fig. 1A and
1B).
2. Be sure the installation conforms to all applicable local and national codes.
3. These instructions contai n importa nt inform ation for
the proper maintenance and repair of this equipment.
Retain these instructions for futu re use.
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations sh o uld be perfor me d by trai ne d se rvi ce personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing opera tions.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than 1/2 psig. Pressures greater tha n
resulting in hazardous condition. If gas valve is subjected to pressure greater than
replaced before use. When pressure testing fieldsupplied gas piping at pressures of
unit connected to such piping must be isolated by manually closing the gas valve.
WARNING: Before performing service or maintenance operations on unit, turn off main power switch
to unit and install a lockout tag. Electrical shock could
cause personal injury.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply p r ov ided fo r t he unit .
Unit is ship ped in t he ve rti cal d uc t con figu rat ion . To convert t o
horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation-side down.
Seals around duct openings must be tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 3. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. The accessory
thru-the-bottom power and gas connection package must be
installed before the unit is set on the roof curb. If field-
installed (thru-the-roof curb) gas connections are desired, use
factory-supplied
to mount the thru-the-roof curb connection to the roof curb.
Gas connections and power connections to the unit must be
field installed after the unit is installed on the roo f curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory
installation instructions.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 3. Improperly applied gasket can
result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 4. This is necessary for unit drain to function properly.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
1
/2 psig will cause g as valve damage
1
/2 psig, it must be
1
/2 psig or less, a
INSTALLATION
3
/4-in. pipe coupling and gas plate assembly
—2—
Fig. 1A — Base Unit Dimensions — 580F036-072
—3—
Fig. 1B — Base Unit Dimensions — 580F073
Fig. 2 — Horizontal Conversion Panels
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab tha t extends a minimum of 6 in.
beyond unit cabi ne t. I nsta ll a grav el apr on in f ron t of con dens er
coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
C. Alternate Unit Support
A non-combustible sleepe r rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building s tructure on verti cal ducted units. Do not connect ductwork to unit. For h or izontal applications, fiel d-supplie d flanges sh ould b e attach ed
to horizontal duct openings and all ductwork should be
secured to the flanges. Insulate and weatherproof all external ductwork, joints , and roo f openings with counter flashing
and mastic in accordance with applicable codes.
Ducts passing through a n unc ondit i one d spa ce must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return air static shall not exceed –.20 in. wg with
economizer or –.45 in. wg without economizer.
These units are designed for a minimum continuous heating
return-air temperature of 50 F (dry bulb), or an intermittent
operation down to 45 F (dry bulb), such as when used with a
night set-back thermostat.
To operate at lower return-air temperatures, a field-supplied
outdoor air temperature control must be used to initiate both
stages of heat when the temperature is below 45 F. Indoor
comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDENSATE DRAIN
The unit’s
3
/4-in. condensate drain connections are located on
the bottom and side of the unit. Unit discharge connections do
not determine the use of drain connections; eit her drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure
the plug (Red) in the alternate bottom connection is tight
before installing the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory-i nstalle d plug (Re d) from t he bott om connection to the side connection. The center dr ain plug l ooks like
a star connection, however it can be removed with a
1
/2-in.
socket drive. See Fig. 5A. The piping for the condensate drain
and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage.
Install a trap at least 4-in. deep and protect against freeze-up.
If drain line is installed downstream from the external trap,
pitch the li ne away fr om th e unit a t 1 i n. per 10 ft of run . Do
not use a pipe size smaller than the unit connection (
3
/4 in.).
See Fig. 5B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit.
Rollers may be used to move unit across a roof. Level by
using unit frame as a ref erence. See Table 1 and Fi g. 6 for
additional information.
Lifting holes are provided in base rails as shown in Fig. 1A
and 1B. Refer to rigging instructions on unit.
CAUTION: All panels must be in place when rigging.
A. Positioning
Maintain clearan ce around and above un it to provide minimum distance from combustible materials, proper airflow,
and service access. See Fig. 1A a nd 1B. A properly positioned
unit will have the follo wing c l ea ranc es betw een unit a nd r oof
1
curb:
/4-in. clearance between roof curb and base rails on
each side and duct end of unit; 1/4-in. clearance between roof
curb and condenser coil end of unit. (S ee Fig. 3, section C-C.)
—4—
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
AUNIT SIZE
1′-2″
[356]
2′-0″
[610]
580F
036-073
1′-4″
[406]
DALT
DRAIN
HOLE
13/4″
[44.5]
GASPOWERCONTROL
3
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT11/4″ [31.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb, galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01
CRBTMPWR002A011
CRBTMPWR003A01
1′-9
11
[551]
/16″
CRBTMPWR004A01
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for
thru-the-curb type gas. Packages CRBTMPWR003A01 and
4A01 are for thru-the-bottom type gas connections.
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″
[12.7]
NPT
ACCESSORY
POWER
1
/2″
[12.7]
NPT
Fig. 3 — Roof Curb
—5—
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 4 — Unit Leveling Tolerances
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 5A — Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 5B — External Trap Condensate Drain
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contaminated air.
Be sure that unit is installed such that snow will not block
the combustion intake or flue outlet.
Unit may be installed dire ctly on wood flooring or on Class
A, B, or C roof-covering material when roo f curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
Minimum distance between unit and other electrically live
parts is 48 inches.
Flue gas can deteriorate building materials . Orie nt unit suc h
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for
proper operation of this equipment. Be sure that installation
complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), and
ANSI (American National Standards Institute) Z223.1, and
NFPA (National Fire Protectio n Association) 54 TIA-54-84-1.
In Canada, installation must be in accordance with the
CAN1-B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping
materials.
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the basepan beside the
burner compartment access panel. Remove from shipping
location and using screws provided, install flue hood and
screen in location shown in Fig. 7.
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipped for use wi th type of gas shown on nameplate. Refer to local building codes, or in the absence of local
codes, to ANSI Z223.1 entitled National Fuel Gas Code. In
Canada, installation must be in accordance with the
CAN1.B149.1 and CAN1.B149.2 installation codes for gas
burning appliances.
For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is oper atin g. On 580F04 8,0 60,072 high
heat units, the gas pressure at unit gas connection must not
be less than 5 in. wg or greater than 13 in. wg while the unit
is operating. For propane applications, the gas pressure
must not be less than 5 in. wg or greater than 13 in. wg at
the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection. Support gas pipi ng as shown in the ta ble in Fig. 8. For
example, a
3
/4-in. gas pipe must have one field-fabricated
support beam every 8 ft. Therefore, an 18-ft long gas pipe
would have a minimum of 2 support beams, a 48-ft long pipe
would have a minimum of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external
manual main shutoff valve.
CAUTION: When connecting the gas line to the
unit gas valve, the installer MUST use a backup
wrench to prevent valve damage.
—6—
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.”
Holes in base rails are centered around the unit center of gravity. Use
wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
CAUTION: All panels must be in place when rigging.
UNIT 580F
036510231
048520236
060540245
072615279
073665302
MAX WEIGHT“A”“B”“C”
LbKgin.mmin.mmin.mm
Fig. 6 — Rigging Details
73.69187237.5095333.35845
—7—
Tabl e 1 — Physical Data
UNIT SIZE 580F036048060072073
NOMINAL CAPACITY (tons)34566
OPERATING WEIGHT (lb)
*Evaporator coil fin material/condenser coil fin material. Contact your local rep-
resentative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
1
/4...1100
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating
input values as follows:
580FJV036115 — 115,000 Btuh
580FJV048150 — 150,000 Btuh
580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/4...1100
1
/
1
/
5
/
31/
5
/
1
/4...1100
1
31/
/
2
5
/
8
5
/
8
2
5
/
8
2
2
8
2
8
1
/4...1100
5
/
8
——
5
/
8
31/
2
5
/
8
models have combustion products
x
50
1
/4...1100
5
/
8
7
/
8
31/
5
/
8
2
—8—
Table 1 — P hysical Data (cont)
UNIT SIZE 580F036048060072 AND 073
FURNACE SECTION
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating
input values as follows:
580FJV036115 — 115,000 Btuh
580FJV048150 — 150,000 Btuh
580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/
2
1
/
2
models have combustion products
x
1
/
2
—9—
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur.
This ground may consist of electrical wire connected to
unit ground lug in control compartment, or conduit
approved for electrical ground when installed in accordance with NEC (N a tio n al Electrical Code), ANSI/N FPA,
latest edition, and local electrical codes. Do not use gaspiping as an electrical ground. Failure to follow this
warning could result in the installer being liable for p ersonal injury of others.
BLOWER
ACCESS
PANEL
A. Field Power Supply
All units except 208/230-v units are factory wired for the
voltage shown on the na meplate. If the 208/230-v u nit is to
be connected to a 208-v power supply, the transformer must
be rewired by m oving the blac k wire with th e
1
/4-in. female
space connector from the 230-volt connection and moving to
the 208-volt
1
/4-in. male terminal on the primary side of the
transformer.
Refer to unit label diagram for additional information.
Pigtails are provided for fie ld wire connectio ns. Use factorysupplied splices or UL (Underwriters’ Laboratories)
approved copper/aluminum connector.
When installing units, provide a disconnect per the NEC.
All field wiring must comply with NEC and local require-
ments.
Install field wiring as foll ows:
1. Install conduit through side panel openings. Install
conduit between disconnect and control box.
2. Install power lines to terminal connections as shown
in Fig. 9.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate (see
Tables 2A and 2B). On 3-phase units, voltages between
phases must be balanced within 2% and the current within
10%. Use the formula shown in the legend for Tables 2A and
2B, Note 2 to determine the percent of voltage imbalance.
Operation on impr op er lin e volta ge or excess ive phase imbalance constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any applicable
Bryant warranty.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the
accessory. Locate thermostat assembly on a solid wall in the
conditioned space to sense average temperature in accordance with thermostat installation instructions. Connect
thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through connector on unit to
low-voltage connections (shown in Fig. 10).
NOTE: For wire runs up 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
Fig. 7 — Flue Hood Details
LEGEND
NFGC — National Fuel Gas Code
*Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/4or 18
1
1
/4or larger10
X
DIMENSION
(feet)
6
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than n o. 18 AWG cannot be dir ectly con nect ed to
the thermos tat and wi ll req uire a j unction box and s plice a t
the thermostat.
Pass the control wires thro ugh the hole provided i n the corner post; then feed w ires throug h the raceway buil t into the
corner post to the 24-v barri er located on the le ft side of the
control box. See Fig. 11. The raceway provides the UL
required clearance between high-voltage and low-voltage
wiring.
C. Heat Anticipator Settings
Set heat anticipator settings at .14 amp fo r the first stage
and .14 amp for second-stage heating, when available.
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
(CONNECTION
BOARD)
208/230-3-60
575-3-60, 460-3-60
(SIZES 036-060)
RACEWAYLOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
B
A
D
C
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.
Fig. 10 — Low-Voltage Connections
HOLE IN END PANEL (HIDDEN)
Fig. 11 — Field Control Wiring Raceway
—11—
Table 2A — Electrical Data (Without Convenience Outlet)
UNIT
580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
Maximum devia tion is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include
power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
Table 2B — Electrical Data (With Convenience Outlet)
UNIT
580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
Maximum devia tion is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include
power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and
screws. See Fig. 12.
3. Separate hood and screen from basepan by removing
the 4 screws securing them. Save al l screws.
4. Replace evaporator coil access panel.
5. Place hood o n front of outdo or air open ing panel. See
Fig. 13 for hood details. Secure top of hood with the
4 screws removed in Step 3. See Fig. 14.
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
6. Remove and save 6 screws (3 on each side) from sides
of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air da mper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6.
8. Adjust minimum positio n setti ng of the dampe r bla d e
by adjusting the manual outdoor-air adjustment
screws on the front of th e damper bla de. See Fig. 12.
Slide blade vertically until it is in the appropriate position determined by Fig. 15. Tighten screws.
9. Remove and save scr ews currently on sides of hood.
Insert screen. Secure screen to hood using the screws.
See Fig. 14.
Fig. 12 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 14 — Outdoor-Air Damper with
Hood Attached
Fig. 13 — Outdoor-Air Hood Details
Fig. 15 — Outdoor-Air Damper Position Setting
—14—
B. Optional EconoMi$er+
See Fig. 16 for EconoMi$er+ component locations.
NOTE: These instructions are for the factory-installed
optional EconoMi$er+ only. Refer to the accessory
EconoMi$er+ installation instructions when field installing
an EconoMi$er+ accessory.
1. To remove the existing unit filter access panel, raise
the panel and swing the bottom outward. The panel is
now disengaged from the track and can be removed.
See Fig. 17.
2. The box with the EconoMi$er+ hood components is
shipped in the compartment behind the
EconoMi$er+. The EconoMi$er+ does not have to be
removed to retrieve the hood box. Remove the scre w
holding the hood box bracket to the top of the
EconoMi$er+. Slid e the hood box out of the un it. See
Fig. 18.
IMPORTANT: If a power exhaust accessory will b e installed
on the unit, the hood shipped with the unit will not be used
and must be discarded. Save the aluminum filter for use in
the power exhaust.
3. The indoor coil access panel will be used as the top of
the hood. Remove the screws along t he bottom of the
indoor coil access panel. See Fig. 19.
4. Swing out the indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
the screws provided to attach the hoo d sides to the
unit. See Fig. 20.
5. Remove the shipping tape holding the EconoMi$er+
barometric relief damper in place.
6. Insert the hood divider between the hood side s. See
Fig. 20. Secure hood divider with 2 screws on each
hood side. The hood divider is also used as the bottom
filter rack for the aluminum filter.
7. Open the filter clips which are located underneath
the hood top. Insert the aluminum filter into the bottom filter rack (hood divid er). Push the filter into position past the o pen filter clips. Close the filter clips
to lock the filter into place. See Fig. 21.
8. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 19.
9. Replace the filter access panel.
10. Install all EconoMi$er+ accessories. EconoMi$er+
wiring is shown in Fig. 22.
Barometric flow capacity is shown in Fig. 23. Outdoor air
leakage is shown in Fig. 24. Return air pressure drop is
shown in Fig. 25.
1. Terminals 13-17 are wired to 5-pin plug assembly (P/N CRE+PLUG001A00).
2. Pin numbers are not printed on the controller. They are provided in this book as a reference.
LEGEND
Fig. 22 — EconoMi$er+ Wiring
—16—
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
0.05
STATIC PRESSURE (in. wg)
0.15
0.25
Fig. 23 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.2 0 0.22 0.25 0. 30 0.35 0.40 0 .45 0.5 0
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 24 — Outdoor-Air Damper Leakage
6000
5000
4000
3000
2000
1000
0
0.050.100.150.200.250.300.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 25 — Return-Air Pressure Drop
C. EconoMi$er+ Control Mode
Determine the EconoMi$er+ control mode before installing
sensors and accessories. Different sensors are required for
different control modes, and a number of accessories are
available. R efer to Tables 3 and 4.
Outdoor Dry Bulb Changeover
The standard control mode for the EconoMi$er+ is Outdoor
Dry Bulb Changeover. The outdoor air an d supply air temperature sensors are also included as standard.
EconoMi$er+ control is based on the outdoor temperature
relative to a set point in the software. If the outdoor air
temperature is above the set point then the EconoMi$er
should be in minim um position. If the outdoor air tem perature is below the set point, the position should be controlled
to maintain the leaving air temperature set point. The set
point range is 45 to 70 F.
Differential D r y Bulb Changeover
The control supports differential dry bulb changeover con-
trol. This requires an accessory return air temperature
sensor CRTEMPSN001A00 installed in the return airstream. Refer to the Start-up section for details on how to
configure and enable the control mode. The user can check
the operation of the s ensor using the Read function.
Outdoor Air Enthalpy Changeover
The control supports outside air enthalpy changeover con-
trol. This mode requires a factory-supplied outdoor air temperature sensor (OAT) and an accessory outdoor air
humidity sensor (ORH) (part no. CRHUMDSN001B00).
Refer to the Start-Up section for details on how to configure
and enable the contro l mode. The user can check the o peration of the sensors using the Read function.
Differential Ent halpy Changeover
The control supports differential enthalpy changeover con-
trol. This requir es the factory -supplied ou tside air tempera ture sensor, an accessory outdoor air humidity sensor, an
accessory return air temperature sensor, and an accessory
indoor air humidi ty sensor. Refer to the Start-Up section fo r
details on how to configure and enable the control mode. The
user can check the o peration of the sens ors using the Read
function.
D. Damper Movement
When the EconoMi$e r+ board receives initia l power, it will
take the damper up to 2
1
/2 minutes before it begins to position itself. After the initial positioning, subsequent changes
to damper position will take up to 30 seconds to initiate.
Damper movement from full open to full closed (or vice
versa) takes 2
1
/2 minutes.
If the damper is in the process of changing positions (for
example it is trying to open to 100%) and the fan signal is
turned off, the damper will con tinue to its 100% open position before closing.
NOTE: Occupied minimum position can not be set lower than
+1% higher than the value of IAQ minimum economizer
position. Refer to the setup examples on page 42.
E. EconoMi$er+ Controller Wiring
The EconoMi$er+ is sup plied fr om the factory with a supply
air temperature sensor and an outside air temperature sensor. This allows for op eration of the EconoMi$e r+ with outside air dry bulb changeover control. Additional accessories
can be added to allow for different types of change over control and operation of the EconoMi$er+ and unit.
F. T hermostats
The EconoMi$er+ co ntrol works with conventional t hermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1
(heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er+ control does not support sensor thermostats
like the T56 and T57. Connections are made at the thermostat terminal connection board located in the main control
box.
—17—
Table 3 — EconoMi$er+ Sensor Usage
APPLICATION
Standard UnitIncluded — HH79NZ039———
Differential
Dry Bulb
Outdoor Air
Enthalpy
Differential EnthalpyIncluded — HH79NZ039
NOTES:
Sensors (Optional, 5-Pin sensor wiring plug CRE+PLUG001A00 required for installation.).
1. CO
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 — Aspirator box used for duct-mounted CO
33ZCT55CO2 — Space temperature and CO
33ZCT56CO2 — Space temperature and CO2room sensor with override and set point.
CRCBDIOX002A00 — Return air CO
2. All units include the following Standard Sensors:
Outdoor-Air Sensor — set point adjustable from 45 F to 70 F, factory set at 65 F.
Supply-Air Sensor — set point adjustable from 40 F to 65 F. Factory set at 55 F.
All temperature adjustments are made at the EconoMi$er+ controller.
STANDARD OUTDOOR AIR
TEMPERATURE SENSOR
Included — HH79NZ039
Included — HH79NZ039—
room sensor with override.
2
sensor.
2
Table 4 — EconoMi$er+ Field-Installed Accessories
DESCRIPTIONPART NUMBER
3-6 Ton Power Exhaust 208-230 v 1 PhCRPWREXH030A00
3-6 Ton Power Exhaust 460 v 3 PhCRPWREXH021A00
Return Air Temperature Sensor with
Harness
Outdoor Air Humidity Sensor with Harness CRHUMDSN001B00
Indoor Air Humidity Sensor with HarnessCRHUMDSN001B00
Return Air CO
Room Sensor33ZCSENCO2*
CO
2
Aspirator Box for Duct Mount
Sensor
CO
2
Space Temperature and CO
Room Sensor with Override
Space Temperature and CO
Room Sensor with Override
and Set Point
5-Pin Sensor Wiring PlugCRE+PLUG001A00*
*5-pin sensor wiring plug accessory (P/N CRE+PLUG001A00) is
required to install IAQ sensor.
SensorCRCBDIOX002A00*
2
2
2
CRTEMPSN001A00
33ZCASPCO2
33ZCT55CO2*
33ZCT56CO2*
ACCESSORY RETURN AIR
TEMPERATURE SENSOR
Required —
CRTEMPSN001A00
Required —
CRTEMPSN001A00
room sensor.
2
I. Indoor Air Quality (IAQ) Sensor
Any indoor air quality or CO
20 mA output can be used as the IAQ sensor. The controller
will modulate the o utdoor-air damper to pr ovide ventilati on
based on the sensor output and the IAQ setting of the controller . The CO
from the minimum po sition ( IAQ minimum damper po sition
set point) to the maximum position (occupied minimum
damper positi on). When th ere i s no CO
go to the unoccupied minimum position. When there is a CO
call, the damper will be between the IAQ minimum economizer set point position and the occupied minimum damper
position.
Mount the sensor according to manufacturer specifications.
In order to wire this sensor, an accessory 5-pin plug (part
number CRE+PLUG001A00) is required. See Fig. 22.
The IAQ sensor is wired to the g round a nd IAQ w ires in the
harness. The a ccesso r y 5-pin wi ring plug is c onnec ted to pi ns
13-17 of J3 on the EconoMi$er+ controller. Push the plug
ACCESSORY
OUTDOOR AIR
HUMIDITY SENSOR
——
Required —
CRHUMDSN001B00
Required —
CRHUMDSN001B00
sensor that provides a 4 to
2
sensor will mo dul ate th e ou tdoo r -a ir d amper
2
down onto the pin s of the Ec onoMi$er+ con troller to install.
G. Outdoor Air Temperature (OAT) Sensor (Provided)
The outdoor air tem peratur e sens or is a 10K therm isto r used
to measure the o ut door-air temp erat ure. T he se nso r c on tro ls
EconoMi$er+ changeover and compressor lockout. The sensor is factory-installed on the EconoMi$er+ in the outdoor
airstream. The operating range of temperature measurement is 0° to 158 F. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor l ooks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
The user can read the value of the sensor using the Read
mode, described in the Start-Up section.
H. Supply Air Temperature (SAT) Sensor (Provided)
The supply air temperature sensor is a 10K thermistor
located at the inlet to the indoor fan. This sensor must be
field installed . Th e o per ating range of temperature me as ur ement is 0° to 158 F. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor l ooks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
The user can read the value of the sensor using the Read
mode, described in the EconoMi$er+ Controller section.
Pins 13 and 14 are used for the IAQ sensor. Pins 15-17 are
used for the field-installed remote potentiometer. Connect
the IAQ sensor to the BRN and WHT wires o f the accessor y
5-pin plug.
NOTE: Pin numbers are not shown on the controller. They
are provided only as reference for the installer. On the
EconoMi$er+ board, they numbered 1-17 from left to right,
but only the 1 and the 17 are printed on the board.
Sensor wiring should be extended with wire and wire nuts
and routed to the IAQ sensor location. Adjust the IAQ setting at the controller to correspond to the IAQ voltage output
of the sensor at the user-determined set point. See Fig. 26.
Power the sensor with a field-supplied transformer.
J. Return Air Temperature (RAT) Sensor
The EconoMi$er+ controller will accept input from the
accessory 10K return air temperature sensor
(CRTEMPSN001A00) in addition to the outdoor air temperature sensor shipped with the EconoMi$er+. By using both
sensors, the outdoor air and the return air temp eratures are
compared (differential dry bulb) for optimal energy savings.
See Tables 5 and 6 for thermistor resistance and resolution
values.
The temperature sensor looks like an eye let terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
ACCESSORY INDOOR
RETURN AIR
HUMIDITY SENSOR
—
Required —
CRHUMDSN001B00
call, the damper will
2
2
—18—
The user can read the value of the sensor using the Read
mode, described in the EconoMi$er+ Controller section.
Mount the return air temperature sensor on the
EconoMi$er+, through pre-punched holes. See Fig. 27.
The return air temperature (RAT) sensor is provided with a
2-wire, 42-in. long wiring harness with a 2-pin connector. The
plug is installed on pins 5 and 6 on J3 of the EconoMi$er+
controller. The pins are labeled with a ground symbol and
RAT on the EconoMi$er+ controller . See Fig. 22. The red wire
of the harness is connected to pin 5 (ground). The black wire
of the harness is connected to pin 6 (RAT). The wiring harness should be routed from the EconoMi$er+ controller to the
sensor. The controller compares the temperatures of the two
airstreams, chooses the best one, and modulates the
EconoMi$er+ actuator accordingly.
This 10K thermistor is used to measure the return air
temperature vs. resistance cu rve, per Table 5. The range of
temperature measurement is between 0° and 158 F. See
Table 6 for resolution.
K. Outdoor Air Humidity Sensor
The EconoMi $er+ con tro ller accep ts inpu t fro m the acc ess ory
outdoor air humidity sensor in addition to the outdoor air
temperature s en sor s hip pe d w ith th e Eco no M i$ er + . By us ing
both sensors, the total enthalpy of the outside air is
calculated.
Mount the outdoor-air humidity sensor in to the
EconoMi$er+, through the pre-punched holes. See Fig. 28.
The outdoor-air humidity senso r is provided with a 2-wire,
42-in. wiring harness with a 2-pin connector. The plug is
installed on pins 11 and 12 on J3 of the EconoMi$er+ controller. The pins are labeled ORH and VREF on the
EconoMi$er+ controller. See Fig. 22. The orange wire of the
harness is connected to pin 11 (ORH). The blue wire of the
harness is connected to pin 12 (VREF). The wiring harness
should be rout ed fr om the Eco no Mi$er + con tro ller to t he sensor location.
The outdoor enthalpy changeover curve is set at the
EconoMi$er+ controller. The factory default is curve “A.” See
Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
CO SENSOR MAX RANGE SETTING
2
6000
ECONOMI$ER+ CONTROLLER
ACTUATOR
RETURN AIR
TEMP SENSOR
(HIDDEN)
VERTICAL ECONOMI$ER+
(3 TO 12 1/2 TON UNITS)
(SIDE VIEW)
Fig. 27 — Return Air Temperature Sensor
ECONOMI$ER+
ECONOMI$ER+
CONTROLLER
WIRING
GROMMET
OUTDOOR AIR
HUMIDITY
SENSOR
OUTDOOR AIR
TEMPERATURE
SENSOR
HOOD
GROMMET
CURB
INDOOR AIR
HUMIDITY SENSOR
RELIEF
BLADE
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 26 — Indoor Air Quality Voltage Setting
800 ppm
900 ppm
1000 ppm
1100 ppm
Fig. 28 — Outdoor-Air Humidity Sensor
—19—
Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors
(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve
Temperature Sensors (CRTEMPSN001A00 or HH79NZ039) —Thermistor Resolution
Table 6 — Outdoor Air, Return Air, and Supply Air
RANGE
LowHigh
FFF
–41–184.0
–17142.0
15281.0
29470.8
48860.7
871080.8
1091261.0
1271712.0
1271954.0
RESOLUTION
—20—
Fig. 29 — Enthalpy Changeover Settings
20
18
16
14
12
10
CURRENT IN mA
8
6
4
0102030
RH — Relative Humidity
50
40
HUMIDITY IN % RH
6070
80
90
Fig. 30 — Humidity Sensor Current vs. Humidity
—21—
100
RH (%)
10
20
30
40
50
60
70
80
90
CURRENT
(mA)
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
L. Indoor Air Humidity Sensor
For differential enthalpy sensing, the EconoMi$er+ controller uses the standard outdoor air temperature sensor, the
outdoor air humidity sensor, and the optional indoor air
humidity sensor, an optional return air t emperature sensor
(RAT). The indoor-air humidity sensor is provided with a
2-wire, 42-in. wiring harness with a 2-pin connector. The
plug is installed on pins 8 and 9 on J3 of the EconoMi$er+
controller. The pins are labeled IRH and VREF on the
EconoMi$er+ controller. See Fig. 22. The orange wire of the
harness is connected to pin 8 (IRH). The blue wire of th e harness is connected to pin 9 (VREF). The wiring harness
should be extended with wires and wire nuts and routed
from the EconoMi$er+ controller to the sensor location. The
EconoMi$er+ controller compares the outdoor air enthalpy
to the return air enthalpy to determine EconoMi$er+ use.
The controller selects the lower enthalpy ai r (return or outdoor) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air, the EconoMi$er+ controller opens the damper to bring in outdoor air for free cooling.
Mount the return-air humidity sensor in the return-air duct.
See Fig. 31.
The outdoor enthalpy changeover curve is set with at the
EconoMi$er+ controller. The selectable curves are A, B, C,
and D. The factory default is curve “A.” See Fig. 29. See
Fig. 30 for Sensor Curve vs. Humidity.
M. Occupied/Unoccupied Switch
The EconoMi$er+ supports the use of a field-supplied
occupied/unoccupied switch. When the switch is closed it provides a 24-vac signal to the unit for occupied mode and when
open, there is no signal to indicate unoccupied mode. The
control can be configured to allow different minimum economizer damper positio ns and to control how mechanic al cooling will and will not be used in the occupied mode.
NOTE: The remote potentiometer (see below) will override
the occupied minimum position if the potentiometer s etting
is greater than the occupied minimum position.
A wire from J1-OCC (pin 4) and a wire from J1-24V (pin 5)
are wire-nutted together to jumper the terminals.
An occupied/unoccupied switch can be field-installed in place
of the jumper to allow the user to force the control into
occupied or unoccup ied mode of operation for EconoMi$ er+
damper position. The occupied/unoccupied switch is required
if the user wants to use unoccupied free cooling or different
EconoMi$er+ d a mp e r vent positions in th e u noc c up ie d m od e.
N. Power Exhaust
Refer to the Accessor y Power Exhaust i nstallation instructions for information on installing the power exhaust
accessory.
O. Remote EconoMi$er+ Enable Control
When the control is used with energy ma nagement syst ems
that enable and disable the EconoMi$er+, the user can
install a field-supplied enable/disable switch. The switch
must be wired in series with a 3K ohm, 1 watt or greater
resistor. The switch is wired to terminals ORH (pin 11) and
VREF (pin 12) on J3. Refer to the Start-Up section for details
on how to configure th e control.
P. R e mote Potentiometer Occupied Minimum Position
The occupied minimum position set point remote potentiometer (field-sup plied) is used when requ iring additional temporary ventilation. The remote potentiometer (10K ohm closed damper, 100K ohm - open damper) will only control
the occupied minimum position.
ECONOMI$ER+
CONTROLLER
ECONOMI$ER+
GROMMET
RETURN AIR
HUMIDITY SENSOR
RETURN DUCT
(FIELD-PROVIDED)
Fig. 31 — Return Air Humidity Sensor
The accessory 5-in wiring plug, CRE+PLUG001A00 is
required to connect the potentiometer.
The plug is installed on pins 15, 16 and 17 on J3 of the
EconoMi$er+ controller. The pins are labeled with the
ground symbol, MIN and VREF on the EconoMi$er+ controller. See Fig. 22. The pink wire from the harness is connected
to pin 15 (ground symbol). The gray wire from the harness is
connected to pin 16 (MIN). The yellow wire from the harness
is connected to pin 16 (VREF). The wiring harness should
be extended with wires and wire nuts and routed from the
EconoMi$er+ controller to the remote potentiometer
location.
NOTE: Pins 13 (ground symbol) and 14 (IAQ), which are
wired to the accessory 5-pin plug, are not used for the remote
potentiometer installation. They are used for an accessory
IAQ sensor (if required).
The unoccupied minimum position can only be set at the
controller. The occupied minimum position set point configured at the EconoMi$er+ controller shou ld be set to 0 when
using a remote potentiometer. The occupied minimum position will also be used as part of the IAQ routing; it will be the
maximum position the damper moves to when there is an
IAQ call.
If the remote potentiometer (occupied) position is greater
than the EconoMi$er+ control ler unoccupie d minimum position, then the remote potentiometer setting will be used. The
remote potentiometer is field supplied and must be a 3-wire,
linear potentiometer with a resistance between 10K ohm
and 100K ohm (such as the Honeywell S963B1128).
Q.Demand Ventilation Control
Demand ventilation control uses an IAQ sensor
(CRE+PLUG001A00 required) to control the amount of outside air admitted into the system. Normally, the minimum
position of the EconoMi$er+ damper is established based on
the demand occupancy of the space. The IAQ sensor will be
used to modulate the EconoMi$er + minimum damper position
below the normal minimum position based on full occupancy.
The lower limit is called the base ventilat ion r ate . S ee Fig. 32.
If there is no IAQ signal the damper will be in the unoccupied minimum position (configuration item number 3). If
there is an IAQ signal the damper will be in the occupied
—22—
minimum position (configuration item number 15), unless
the remote potentiometer is used to override it.
For the demand ventilation control logic, the user configures
the lower and upper actuator position to esta blish the base
ventilation rate (IAQMIN_SP) and the design ventilation
rate (ECONOMIN_SP) for full occupancy. When the
EconoMi$er+ damper is being modulated for demand ventilation control, the damper position will be between
IAQMIN_SP and ECONOMIN_SP. The upper IAQ differential set point is DAQHI. The lo wer I AQ differ ential set point
is DAQLO.
The differential set points represent the differential CO
level (in ppm) above the outdoor reference IAQ levels.
Normally, the outdoor reference IAQ levels are around
400 ppm, bu t the value should be configured bas ed on the
reference levels taken at the job site.
The following equation is used to determine EconoMi$er+
damper position (ECONOMIN_POS):
IAQMIN_SP +=
R. CO
2
The CO
(ECONOMIN_SP – IAQMIN_SP) * (IAQ – OAQ – DAQLO)
(DAQHI – DAQLO)
Sensor Configuration
sensor has preset standard voltage settings that
2
can be selected anytime afte r the sensor is powere d up. See
Table 7.
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode 2 times. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
See Table 7.
4. Press Enter to lock in the selection.
Press Mode to exi t and resume normal ope ration. The custom settings of the CO
sensor can be changed any time
2
after the sensor is energized. Follow the steps below to
change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode 2 times. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the s election, then press Mode
to continue to the next variable.
S. Dehumidification of Fresh Air with Demand Control Ventilation (DCV)
Information from ASHRAE (American Society of Heating,
Refrigeration and Air Conditioning Engineers) indi cates that
the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a energy
recovery unit is added to reduce the moist ure content of the
fresh air being brought into the building when the enthalpy
is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads
for most commercial applications.
This makes the control of the dehumidification device simple
2
when using the enthalpy or differential enthalpy sens or. The
enthalpy sensor or diffe rential enthalpy sensor is installed
on the equipment to determine economizer operation. The
high enthalpy signal from the temperature and humidity
sensors or differential temperature and humidity sensors
can be used to turn on the outdoor air moisture removal
device any time fresh air is required for the space.
The energy recovery device should be sized for maximum
latent and sensible conditioning at maximum ventilation on
a design day.
A calculation for leaving-air temperature on a low ambient,
low ventilation day should also be done to determine the
supply-air temperature of the return and pre-conditioned
outside air. The design should produce air temperature
somewhat near room conditions to prevent reheat of the air
mixture. The energy recovery device should be interlocked
with the heat to turn off the device when in the heat mode.
DAMPER
POSTION
FULL OCCUPANCY
ECONOMIZER
MINIMUM
OCCUPIED
DAMPER
POSITION
(ECONOMIN_SP)
IAQ
MINIMUM
ECONOMIZER
POSITION
SET POINT
(IAQMIN_SP)
*Available sensor part numbers are listed in Table 4.
ProportionalAny4-20 mA0-2000100050
Proportional154-20 mA0-1100110050
Sensor* Standard Settings
2
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO
CONTROL
2
RANGE (ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
—23—
RELAY
HYSTERESIS
(ppm)
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
Adjust evaporator-fan rpm to meet jobsite conditions. Table 8
shows fan rpm at motor pulley set tings. T abl e 9 sho ws motor
performance. Refer to Tables 10-33 to determine fan speed
settings.
A. Direct-Drive Motors
The evaporator-fan motor factory speed setting is shown on
label diagram affixed to base unit. If other than factory setting is desired, refer to label diagram for motor reconnection.
See Fig. 33 for direct drive motor location.
B. Belt-Drive Motors
Fan motor pulleys are factory set for speed shown in Table 1.
See Fig. 34 for belt drive motor location.
NOTE: Before adjusting fan speed, make sure the new fan
speed will provi de an air temperature rise range as show n in
Table 1.
To change fan speed:
1. Shut off unit power supply and tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts.
See Fig. 34.
3. Loosen movable pulley flange setscrew (see Fig. 35).
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed incr eases lo ad on motor. Do not
exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub
and tighten setscrew. (See Table 1 for speed change
for each full turn of pulley flange.)
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide m otor mounti ng plate away fr om fan scroll for
proper belt tension (
1
/2-in. deflection with 8 to 10 lb of
force).
3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed
position.
*Extensive motor and electrical testing on these units ensures that the full horse-
power range of the motors can be utilized with confidence. Using your fan
motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
†Single phase/three-phase.
EVAPORATOR-FAN
MOTOR
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
High Static
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
208/230
4601.3
0.34440
5751.3
208/230
4602.1
1.201000
5752.1
208/230
4603.0
2.402120
5753.0
208/230
4601.8
0.75850
5751.8
208/230
4602.1
1.201000
5752.1
208/230
4603.0
2.402120
5753.0
208/230
4603.2
1.201340
5753.2
208/230
4603.0
1.30/2.40†2120
5753.0
208/230
4603.9
2.902562
5753.9
208/230
4603.0
2.402120
5753.0
208/230
4603.9
2.902562
5753.9
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
2. High-static motor not available on single-phase units.
1
/
2
MAXIMUM
AMP DRAW
2.8
4.9
6.0
3.5
4.9
6.0
5.9
10.1/6.7†
8.6
6.7
8.6
6
Table10—FanPerformance 580F036 — Vertical Discharge Units, Standard Motor
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See below for general fan performance notes.
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 9 — Motor Data for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
—36—
PRE-START-UP
WARNING: Failure to observe the following warnings
could result in serious personal injury .
1. Follow recognized safety practices and wear protective
goggles when checking or the servicing refrigerant
system.
2. Do not opera te the compres sor or provide an y electric
power to the unit unless the compres sor termina l cover is in place and secured.
3. Do not remove the com pre ssor termi nal cover unti l all
electrical sources are disconn ected.
4. Relieve all pressure from the system before touching
or disturbing anything in side the c omp ress or term ina l
box if refrigerant leak is suspected around the compressor terminals.
5. Never attempt to repai r a soldered connection while
the refrigerant system is under pressure.
6. Do not use torch to remove any component. The system contains oil and refrigerant under pressure. To remove a component, wear protective goggles and
proceed as follows:
a. Shut off gas and then electrical power to the unit.
Install lockout tag.
b. Relieve all pressure from the system using both
high-pressure and low-pressure ports.
c. Cut the component connection tubing with a tubing
cutter, and remove the component from the unit.
d. Carefully unsweat the remaining tubing stubs when
necessary. Oil can ignite when exposed to torch
flame.
Proceed as follows to ins pect and prep are the unit f or initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to,
or shipped with, the unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose p arts, or discon nec ted wires,
etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates
a refrigerant leak. Leak-test all refrigerant tubing
connections using an electronic leak detector,
halide torch, or liquid-soap solution.
c. Inspect all field- and factory-wiring connections.
Be sure that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten the fins with a fin
comb.
4. Verify the following conditions:
a. Make sure that condenser fan blade is correctly
positioned in the fan orifice. See Condenser-Fan
Adjustment section on page 48 for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
I. UNIT PREPARATION
Make sure that unit has bee n installed in accordance with
these installation instructions and applicable codes. Make
sure Start-Up Checklist on back page is filled out and
completed.
II. RETURN-AIR FILTERS
Make sure correct filters are installed in filter tracks. See
Table 1. Do not operate unit without return-air filters.
III. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or
remove compressor holddown bolts.
IV INTERNAL WIRING
Check all electrical connections in unit control boxes.
Tighten as required. Ensure wiring does not come in contact
with refrigerant tubing.
V. GAS PIPING
Check gas piping for leaks.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than
1
sures greater tha n
/2 psig will cause g as valve damage
1
/2 psig. Pres-
resulting in hazardous condition. If gas valve is subjected to pressure greater than
1
/2 psig, it must be
replaced before use. When pressure testing fieldsupplied gas piping at pressures of
1
/2 psig or less, a
unit connected to such piping must be isolated by manually closing the gas valve.
VI. REFRIGERANT SERVICE PORTS
To service refrigerant service ports, remove compressor
access panel. Each unit system has 4 Schrader-type service
gage ports: one on the suction line, one on the liquid line, and
two on the compressor discharge line. Be sure that caps on
the ports are tight. One of the Schrader-type valves on the
compressor discharge line is located under the low-pressure
switch.
The Schrader valve on the compr essor di scharge li ne that is
located under the high pressure switch does not contain a
Schrader core in the valve.
VII. HIGH FLOW VALVES
Located on the compressor hot gas and suction tubes are
High Flow Valves. Large black plastic caps distinguish these
valves with o- r in gs located inside the c aps. These valv es cannot be accessed for service in the field. Ensure the plastic
caps are in place and tight or the possibility of refrigerant
leakage could occur.
VIII. COMPRESSOR ROTATION
On 3-phase units with scroll compressors, it is important to
be certain compressor is rotating i n the proper direc tion. To
determine whether or not compressor is rotating in the
proper direction:
1. Connect service gage s to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating
in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the unit.
—37—
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compres sor is rotating in the wrong direction, the unit makes an elevated level of noise and does not
provide cooling.
IX. COOLING
Set space thermostat to OFF position. To start unit, turn on
main power supply. Set system selector switch at COO L position and fan switch at AUTO. position. Adjust thermostat to
a setting below room temperature. Compressor, outdoor fan
and evaporator motor start on closure of contactor.
Check unit charge. Refer to Service, Refrigerant Charge section, page 48.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off after
30-second delay.
To Shut Off Unit
Set system selector switch at OFF position. Resetting thermostat at a position ab ove room temperature shu ts unit off
temporarily until space temperature exceeds thermostat
setting.
X. MAIN BURNERS
Main burners are factory set and should require no
adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set p oint abov e room tem perature a nd verify that the burners light and evaporator fan is energized.
After ensuring that the unit continues to heat the building,
lower the thermostat setting below room temperature and
verify that the burners and evaporator fan turn off. (Fan will
turn off only if fan selector switch is in the AUTO. position.)
Refer to Table 34A and 34B for the correct orifice to use at
high altitudes.
XI. HEATING
1. Purge gas supply line of air by opening union ahead
of gas valve. If gas odor is detected, tighten union and
wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas val ve .
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then
there is a 22-second delay before another 5-second
try. If the burner still does not light, the time delay is
repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the
24-v power to W1.
6. The evaporator-fan motor wil l turn on 45 seconds after the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds after thermo st a t te m p e r at u r e i s sa t isfied.
8. Adjust airflow to obtain a temperature rise within
the range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor ON/
OFF delay is 45 seconds. The Integrated Gas Unit Controller
(IGC) modifies this value when abnormal limit switch cycles
occur . Based upon unit operating conditions, the ON delay can
be reduced to 0 seconds and the OFF delay can be extended
to 180 seconds. When one flash of the LED is observed, t he
evaporator-fan ON/OFF delay has been modified.
If the limit switch trips at the start of the heating cycle during the evap or ator ON delay, t he time period of the ON delay
for the next cycle will be 5 seconds less than the time at
which the swit ch trip ped. (Exa mple: If th e l imit switch trip s
at 30 seconds, t he ev aporator-fan ON delay for the next cycle
will occur at 25 seconds.) To prevent short-cycling, a 5-second
reduction will only occur if a minimum of 10 minutes has
elapsed since the last call for heating.
The evaporator-fan OFF delay can also be modified. Once the
call for heating has ended, there is a 10-minute period during which the modification can occur. If the limit switch trips
during this period, the evaporator-fan OFF delay will
increase by 15 seconds. A maximum of 9 trips can occur,
extending the evaporator-fan OFF delay to 180 seconds.
To restore the original default value, reset the power to the
unit.
To Shut Off Unit
Set system selector switch at OFF position. Resetting heating selector lever bel ow room temperature will temporar ily
shut unit off until space temperature falls below thermostat
setting.
Table 34A — Altitude Compensation* — Standard Units
*As the height above sea level increases, there is less oxygen per cubic foot of
air. Therefore, the input rate should be reduced at higher altitudes.
†Orifices are available through your local Bryant distributor.
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
120,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size
Liquid
Propane
Orifice
Size†
—38—
XII. SAFETY RELIEF
A soft solder joint at the suction service Schrader port provides pressure relief under abnormal temperature and pressure conditions (i.e., fire in building).
XIII. VENTILATION (CONTINUOUS FAN)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuous ly to
provide constant air circulation. When the evaporator-fan
selector switch is turned to the OFF position, there is a
30-second del a y be f or e th e f an tur ns off.
XIV. ECONOMI$ER+ CONTROLLER
The EconoMi$er+ controller is mounted to the top of the
EconoMi$er+ d amp er and is acce ssibl e by remo ving the fi lter
access door of the unit.
The EconoMi$er+ controller is protected by a sheet metal
enclosure mounted over the controller. Remove the single
screw on the front of the enclosure and lift off the top for
access to the controller . The primary purpose of the controller
is to provide control of the EconoMi$er+ dampers and the
cooling compression stages. The status of the indoor fan is
monitored through the G input but is not directly controlled
by the controller. The heating function is completely independent of the controller.
IMPORTANT: The controller can only be used with conventional thermostats with Y1, Y2 and G input to the controller;
it can NOT be used with electron ic thermostats wi th a proportional room temperature input, or with Variable Air Volume systems.
There are 4 LEDs on the con troller, which are used to rea d
values and display status and configuration information.
There are 2 buttons (READ/ADJUST and ADVANCE/ MANUAL), which change modes and configure the controller. See
Fig. 36.
The EconoMi$er+ microprocessor based control system provides the following control functions:
• EconoMi$er+ damper control for free cooling
• Minimum position control for ventilation
• Demand Ventilation Control using a CO
sensor
2
• Compressor Cooling Stage Control
• Occupied/Unoccupied Control
• Diagnostics Display and History
• Manual test co ntrol
See Table 35 for Inputs and Outputs.
A. Integrated Display
The control board includes an integrated display, which is
used for the following functions:
•Configuration and setup
• Set point and control adjustment
• Error status and alarm monitoring
• Manual control
• Reading sensor values
There are 5 modes of display operation:
•Startup Mode
•Run Mode
• Read Mode
•Setup Mode
• Manual Mode
External devices are not required to operate and con figure
the control.
B. Startup Mode
During the first 3 seconds after power is applied to the control, the four LEDs flash as shown in Table 36, indicating
that the control is being initialized. The buttons are not
operational during Startup mode.
C. Run Mode
Run mode indicates status of control ler and unit. The mode
can be changed to the Read, Setup, or Manual modes by
pushing va ri ous buttons.
While the control is in Run mode, the DS1 heartbeat indicator LED (red) will flas h to indi cat e the cont rolle r is ope rat ing
properly. The DS2 Econo indicator LED (yellow) will flash
whenever economiz e r is b ein g us ed f or f re e cool i ng. The DS3
first stage cooling indicator LED (green) will be on steady
indicate demand for sta ge 1 cooling. The DS4 second stage
cooling indicator LED (green) will be on steady to indicate
demand for stage 2 cooling.
If the controller is in a different mode, the controller will
return to Run mode after 10 minutes of user inactivity or if
the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are held for at least 3 seconds until all LEDs flash.
D. Read Mode
Read mode is used to check set points (Table 37) and I/O
channel status (Table 38). Enter the Read mode by pushing
and releasing the READ/ADJUST (#1) button. A user can
only enter Read mode from the Run mode (to get to Run
mode, press both the #1 and #2 buttons for at least 3 seconds
until all LEDs flash). In Read mode, LEDs are not lit until
the READ/ADJUST button (#1) is pushed.
NOTE: If the user pushes and holds the READ/ADJUST button (#1) for more than 3 seconds, then the control will go into
the Setup mode, indicated by the yellow LED (on steady).
While in Read mode, push button #1 then the DS1 LED
(Red) flashes to indicate setup point number as defined in
the setup table. The two green LEDs will then show the
value of the display item. The DS3 LED will first display the
tens digit and the DS4 LED will the n display the ones digit.
For example to display 54, the DS3 LED will flash 1 group of
5 at a high flash rate to indicate 50, and then follow with
4 flashes (DS4) at 1-second intervals to complete the display
of the number 54.
NOTE: Do not try to count the “5 Fast Flashes” individually,
but instead count how many groups of 5 flashes were displayed. In this case, 1 group of 5 flashes, plus the 4 flashes at
1 second results in the value of 54.
To read the display again, push the READ/ADJUST (#1) button and the sequence will repeat as many times as needed.
To advance to the next setup point, push the ADVANCE/
MANUAL (#2) button. The controller will cycl e through all
the setup channels (Table 37) and then the I/O channels
(Table 38) and then back to the first setup channel.
NOTE: The user can only advance forward, not reset to #1 or
go backwards. Cycling the EconoMi$er + po we r will r eset the
item number (but not the item value) to item #1.
In the Read mode for setup variables, the LEDs will not turn
on steady; the LEDs will always flash. Steady-on indicators
are reserved for the configuration modes. No data is modified
in the Read mode. The con troller will always remain at the
last read number even if reset back to normal operat ion.
NOTE: To enter another mode, the user first must exit the
Read mode.
If no button is pushed in 10 minutes, Read mode will automatically be exited. Also, if the READ/ADJUST (#1) and
ADVANCE/MANUAL (#2) buttons are pushed and held for
more than 3 seconds, then Read mode will be exited to Run
mode. While i n the Read mod e , the c ontro ller will conti nue to
operate with normal unit control.
—39—
READ/
ADJUST
ADVANCE
MANUAL
DS1DS2
DS3
DS4
Y1
Y2
G
OCC
24V
date or serial no
#1
PUSH BUTTONS
#2
SETPOINT DISPLAY
RED
YELLOW
GREEN
J4
24 VAC
24 VAC
24 VAC
EX2/CP3
OUTPUT RELAYS
EX1/CP4
CP1
CP2
Relays rated at 24 VAC 3A
and traces for 8A.
J1
1
Y1 (cool 1)
Y2 (cool 2)
G (fan)
OCC
Occupied/unoccupied
I/O support dry circuit
contact (min 24 mA I)
NOTE: For 1 and 2 stage
cooling, 2 stages of power
exhaust will be used.
For 3 cooling stages, only 1
stage of power exhaust will be
used, and for 4 stages no power
exhaust will be controlled
directly by the control.
C1
C2
24V
24V
24V
C3
C4
24 VAC
5
THERMOSTAT INPUTS
4-20 mA external powered between signal and ground
4-20 mA loop powered between 24 VDC and signal
ANALOG INPUTS
2-10 VDC
ECONOMIZER
CONTROL
24 VAC
24 VAC
Control
24V
24V
CNT
OAT (10k thermistor)
SAT (10k thermistor)
IRH (4-20 ma)
RAT (10k thermistor)
ORH (4-20 ma)
Vref
IAQ (4-20ma)
min (10K pot)
Vref
Vref
J3
5
1
SAT
OAT
IRH
RAT
VRF
ORH
VRF
IAQ
MIN
VRF
17
J2
1
POWER
SUPPLY
Fig. 36 — EconoMi$er+ Controller Board
Table 35 — EconoMi$er+ Inputs and Outputs
INPUTNAMETYPEUSE
INPUT/OUTPUT
RANGE
THERMOSTAT INPUTS
Y1 (Cool/Low Cool)Y1SwitchStandard 18-30 vac 50/60 Hz w/min 24 mA LoadNAOn/OffJ11
Y2 (Cool 2/High Cool)Y2SwitchOption18-30 vac 50/60 Hz w/min 24 mA LoadNAOn/OffJ12
G (fan)GSwitchStandard 18-30 vac 50/60 Hz w/min 24 mA LoadNAOn/OffJ13
Occupied/UnoccupiedOCCSwitchOption18-30 vac 50/60 Hz w/min 24 mA LoadNAOn/OffJ14,5
POWER
Powe r24VInputStandard18-30 VAC 50/60 HzNANAJ21,2
ECONOMIZER MOTOR
ControlCNT2-10 vdcStandard2-10 vdc0-100%1%J23,4,5
ANALOG INPUTS
Supply Air Temperature SAT 10 K Thermistor Standard1816 to 86407 Ohms30 to 125 F0.8 FJ31,2
Outside Air
Temperature
OAT 10 K Thermistor Standard1816 to 86407 Ohms30 to 125 F0.8 FJ33,4
Return Air Temperature RAT10 K ThermistorOption1816 to 86407 Ohms30 to 125 F0.8 FJ35,6
Indoor HumidityIRH
Outdoor HumidityORH
Indoor CO
Remote Minimum
Position Po t
2
IAQ
MIN10KOption10K to 100K Ohms0 to 100%1%J3
4-20 mA,
Loop Powered
4-20 mA,
Loop Powered
4-20 mA,
Ext Sourced
Option4-20 mA, 24 vdc0-100%.08 mAJ37,8,9
Option4-20 mA, 24 vdc0-100%.08 mAJ3
Option4-20 mA, 24 vdc0-200 PPM/1010 PPMJ313,14
RELAY OUTPUTS
Cooling Stage 1CP1RelayStandard24 vac, 2.5 Amps at 24 vacNAOn/OffJ41,3,4
Cooling Stage 2CP2RelayOption24 vac, 2.5 Amps at 24 vacNAOn/OffJ42,3,4
Powe r Exhaust 2/
Cooling Stage 3*
Powe r Exhaust 1/
Cooling Stage 4†
CP3/
EX2
CP4/
EX1
RelayOption24 vac, 2.5 Amps at 24 vacNAOn/OffJ45,6
RelayOption24 vac, 2.5 Amps at 24 vacNAOn/OffJ45,7
DISPLAY
Setpoint Switch 1SP1DigitalStandardOpen/ClosedLogicOpen/ClosedOn BoardNA
Setpoint Switch 2SP2DigitalStandardOpen/ClosedLogicOpen/ClosedOn BoardNA
LED 1DS1LED OutputStandardRedLogicOn/OffOn BoardNA
LED 2DS2LED OutputStandardYellowLogicOn/OffOn BoardNA
LED 3DS3LED OutputStandardGreenLogicOn/OffOn BoardNA
LED 4DS4LED OutputStandardGreenLogicOn/OffOn BoardNA
*If there are 3 stages then there can only be 1 stage of power exhaust.
†If there are 4 stages then no power exhaust stages are directly controlled.
CONVERSION
RANGE
CONVERSION
RESOLUTION
CONNECTION
10,11,1
15,16,1
PIN
NO.
2
7
—40—
Table36—Start-UpModeSequence
TIME
0-1.0 SEC
1-1.5 SEC
1.5-2.0 SEC
2.0-2.5 SEC
2.5-3.0 SEC
LED — Light-Emitting Diode
LED 1/DS1 (RED)LED 2/DS2 (YELLOW)LED 3/DS3 (GREEN)LED 4/DS4 (GREEN)
OFFOFFOFFOFF
FLASH ½ SECOFFOFFOFF
OFFFLASH ½ SECOFFOFF
OFFOFFFLASH ½ SECOFF
OFFOFFOFFFLASH ½ SEC
Table 37 — Configuration Variables (Read and Setup Modes)
NO.
1 Supply Air Temperature SetpointF40 F65 F55 F1 FLeaving Air Temperature Control Point
Occupied Minimum Economizer
2
Posi tion
Unoccupied Minimum Economizer
3
Posi tion
4 Economizer Maximum Position%1%100%100%1%Maximum Econo Position
5 Economizer Type—1321
6 Economizer Changeover Type—15211 = Switch, 2 = Outdoor Dr y Bulb,
Economizer Changeover Setpoint
7
(mode 2)
8 Economizer Changeover Setpoint
(mode 3)
9 No.ofcompressors—14211,2,3,or4
10 Compressor Sequencing—1411
11 Power Exhaust Stage 1 Activation%1%Item 12 -5%25%1%Economizer Position
12 Power Exhaust Stage 2 Activation%Item 11 +1%100%50%1%Economizer Position (> stage 1)
13 Unoccupied Configuration—13311 = No Unoccupied Cooling,
14 Compressor Lockout Temperature—1 F65 F45 F1 FCompressor Operation
20 1st Most Recent Error/Reset—18——Used in Setup Mode to Reset Alarms
21 2nd Most Recent Error (read only)—18——Not Displayed in Setup Mode
22 3rd Most Recent Error (read only)—18——Not Displayed in Setup Mode
23 4th Most Recent Error (read only)—18——Not Displayed in Setup Mode
24 5th Most Recent Error (read only)—18——Not Displayed in Setup Mode
DC — Direct Control
IAQ — Indoor Air Quality
LAT — Leaving Air Temperature Compensated Control
VOC — Volatile Organic Compounds
SETUP POINTS
(viewable and adjustable)
LEGENDNOTE: The accessibility of these channels will be as follows:
UNITS
%Item 15 +1%100%15%1%Min Econo Position (occupied mode)
%1%100%5%1%Min Econo Position (unoccupied mode)
F45 F70 F65 F1 FFor Outdoor Changeover
—1411Outdoor Enthalpy Changeover Setpoint
%1%Item 2 +1%5%1%Min IAQ Position for VOC Emissions
PPM/101 PPM/10
PPM/10
MINIMUM
VAL UE
Item 18 +1
PPM/10
MAXIMUM
VAL UE
Item 19 -1
PPM/10
200 PPM/10140 PPM/10 1 PPM/10
READ MODE — All channels will be accessible.
SETUP MODE — Only channels 1-20 will be accessible and 20 will be used to
reset alarms.
1C1 Output—OffOn—Compressor 1
2C2 Output—OffOn—Compressor 2
3C3 Output—OffOn—Compressor 3/Power Exhaust 2
4C4 Output—OffOn—Compressor 4/Power Exhaust 1
5Economizer Damper Output%1 F100 F1%Damper Commanded Position
6Supply Air TemperatureF1 F150 F1 FSupply Air Temperature
7Outdoor Air TemperatureF1 F150 F1 FOutdoor Air Temperature
8Return Air TemperatureF1 F150 F1 FReturn Air Temperature
9Indoor Relative Humidity%1%100%1%Return Air Relative Humidity
10Outdoor Relative Humidity%1%100%1%Outdoor Air Relative Humidity
11Indoor Air QualityPPM1 PPM/10200 PPM/1010 PPM Indoor Air Quality (/10)
12Remote Minimum Position%1%100%1%Remote Minimum Pot Position
13Y1 Status—OpenClose—Thermostat Y1 Status
14Y2 Status—OpenClose—Thermostat Y2 Status
15G Status—OpenClose—Indoor Fan Status
16Occ Status—OpenClose—Remote Occupied Status
NOTE: The accessibility of these channels will be as follows:
READ MODE — All channels will be accessible for reading.
ADJUST MODE — Only channels 1-5 will be accessible.
MANUAL MODE — Only channels 1-5 will be accessible.
—41—
After advancing through all the configuration variables in
the Read mode, the controller will then advance through t he
status of the I/O channels. As in the Read mode, there will be
no LEDs on. Push the READ/ADJUST (#1) button and the
yellow LED will flash the “I/O Point” numbe r and the green
LEDs will flash the “I/O Values” in the same manner
described in the Read mode section. See Ta ble 38. At the first
I/O point (Compressor 1 Ou tput), the DS2 LED (Yellow) will
flash with the number of the I/O channel and the DS1 LED
(red) will stop fla shi ng. This will be followed b y the I/O c h annel status. To read the value ag ain, pus h the R EAD/ADJU ST
(#1) button.
To advance to the next channel, push the ADVANCE/MANUAL (#2) button. If the number of the channel or the status
value is greater than 4 the controller will count out the
increments of 5 a t a high fl ash rate foll owed by the remaining digits. The channel number will be counted out through
the DS2 LED (yellow). Th e status value wil l be counted out
through the DS3 and DS4 LEDs (green).
If the status value is an analog value then the numeric value
will be displayed by using the D S3 Green LED to display the
tens digit and the DS4 will be used to display the ones digit.
If the channel is a digital output (relay), the DS3 LED (flashing green) will in dicate ON stat us and the DS4 LED (flashing green) will indicate OFF status. If the output is the
economizer control signal then the DS3 LED will be used to
indicate the motor is being driven open, and the DS4 LED
will be used to indicate it is being closed. If the motor i s not
being commanded in either direction then both the DS3 and
DS4 LEDs will be on. The controller will first go through the
output relays, then the economizer motor, and will then fol low with the values currently being read for the analog input
channels as defined in the configuration table. All values are
maintained in memory even during a power loss. To exit
Setup mode, push and hold the READ/ADJUST (#1) and
ADVANCE/MANUAL (#2) buttons for more than 3 seconds.
Setup mode wil l automati cally be exited aft er 10 minu tes of
no activity.
E. Setup Mode
The Setup mode is used to change set points and configuration values.
Enter the Setup mode by pushing and holding the READ/
ADJUST (#1) button 1 for at least 3 seconds until all LEDs
flash once. Then, the yellow LED will come on steady. A user
can only enter the Setup mode from the Run m ode (to get to
Run mode, press buttons both buttons #1 and #2 for at least
3 seconds).
In Setup mode, all configurations can be modifi ed e ven w hil e
the unit is running, but the use r will not be able to adjus t the
I/O channels . O nly c ha nne ls 1 th roug h 20 on Table 37 will b e
accessible in the Setup mode. Channel 20 will be used to
reset any alarms that may have occurred. As an option,
alarms can also be reset by cycling power to the cont roller.
NOTE: During the Setup mode, all routines including safety
routines will continue to run and control the unit.
While in this mode, the DS1 LED (red) will flash to indicate
the number of the configuration item. The DS2 LED (yellow)
will be on continuousl y to i ndi cate tha t the uni t is i n c on figuration mode. Use the ADVANCE/MANUAL button to
sequence through the setup channels. If the value of the
channel is less than 5 it will count out the value of the channel on the DS1 LED at 1-second intervals. If the channel
value is 5 or great er, the DS1 LED will first c ount out the
groups of 5 and then following with the remaining digit.
Verify what Setup Point is being read by pushing the READ/
ADJUST button (#1). First the Red LED will flash the set
point number, then the Green LEDs will flash the value.
Then, the green DS3 and DS4 LEDs will each come on
steady for about 2 seconds. While DS3 is on steady, its new
value can be entered by pushing READ/ADJUST (#1), and
entering the value for the ten’s digit. When the DS4 comes
on steady, enter the value for th e one's d igit. Afte r the green
LEDs are off, push the READ/ADJUST button (#1) again to
verify that the correct value has been entered. If the configuration is a discrete On/off setting, push the READ/ADJUST
button (#1) to toggle LED 3 or 4 on or off.
Setup Example 1: Change “Occupied Minimum Position”
(configuration item 2) to 53%.
1. Read the General Notes about reading and entering
values found on the label on the top of the
EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at
least 3 seconds until all LEDs flash. The yellow LED
will go on steady.
3. Read the current configuration point by pushing button #1. The red LED flashes the configuration point
number and the green LEDs flash the current setting
for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2
and Note 1 for Setup mode operation.
5. Use button #2 (ADVANCE/MANUAL) to advance to
configuration point number 2, Occupied Min.
NOTE: Before performing Step 6, be ready to push button
#1; there is a limited time window that can easily be missed
when the DS3 green LED c omes on, and agai n when th e DS4
green LED comes on.
6. Verify the configuration point by pushing button #1.
The red LED should flash twice to indic ate point 2,
and then the green LEDs will flash the current
setting.
7. Next, the green DS3 LED wil l turn on steady for 2
seconds. During this time, push button #1 five times.
8. The DS3 LED wi ll turn off and the gree n DS4 LED
will go on steady for 2 seconds. During this time,
push button #1 three times.
9. The 5 button #1 pushes, followed by the 3 button #1
pushes is the sequ ence that sets the occupied mini mum position to 53%.
10. Wait until the green LEDs turn off then verify the
setting by pushing button #1 to read the value. There
should be 5 fast blinks of DS3 and 3 slow blinks of
DS4.
Setup Example 2: Change the Occupied Minimum Position
(item 2) to 2% (lowest value).
1. Read the General Notes about reading and entering
values found on the label on the top of the
EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at
least 3 seconds until all LEDs flash. The yellow LED
will go on steady.
3. Read the current configuration point by pushing button #1. The red LED flashes the configuration point
number and the green LEDs flash the current setting
for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2
and Note 1 for Setup mode operation.
5. Use button #2 (ADVANCE/MANUAL) to advance to
configuration point number 2, Occupied Min.
—42—
6. Verify the configuration point by pushing button #1.
The red LED should flash twice to indicate point 2,
and then the green LEDs will flash the current
setting.
NOTE: Since the occupied minimum position MUST
be 1 greater than the IAQ minimum position (item
15), the IAQ minimum position must be changed
first. (IAQ min has a default value of 5%, which is
higher than the 2% value in this example.)
7. Use button #2 (ADV ANCE/MANUAL) to get to configuration point 15 (IAQ Minimum Position).
NOTE: Before performing Step 8, be ready to push button
#1; there is a limited time window that can ea sily be missed
when the DS3 green LED com es on, and ag ain wh en the DS 4
green LED comes on.
8. Verify the configuration point by pushing button #1.
The red LED should flash 15 times to indicate point
15, then the green LEDs will flash the current
setting.
9. Next, the green DS3 LED will turn on steady for 2
seconds. During this time, do NOT do anything so
that the position defaults to 0.
10. The DS3 LED will turn off and the green DS4 LED
will go on steady for 2 seconds. During this time,
push button #1 once to set the point to 1%.
11. Wait until the green LEDs turn off then verify the
setting by pushing button #1 to read the value. DS3
should not blink, and DS4 should blink once.
12. Now configure the Occupied Minimum Position to
2%. Use button #2 (ADVANCE/MANUAL) to get to
configuration point 2.
NOTE: Before performing S tep 13, be ready to push button
#1; there is a limited time window that can ea sily be missed
when the DS3 green LED com es on, and ag ain wh en the DS 4
green LED comes on.
13. Verify the configuration point by pushing button #1.
The red LED should flash twice to indicate point 2,
then the green LEDs will flash the current setting.
14. Next, the green DS3 LED will turn on steady for 2
seconds. During this time, do NOT do anything so
that the position goes to 0.
15. The DS3 LED will turn off and the green DS4 LED
will go on steady for 2 seconds. During this time,
push button #1 twice to set the point to 2%.
16. Wait until the green LEDs turn off then verify the
setting by pushing button #1 to read the value. DS3
should not blink, and DS4 should blink twice.
NOTE: Configuration items 2, 15, 11, 12, 18 and 19 (in
Table 37) are dependent upo n other items. Befo re attempting to change one of these items, be sure to check the value of
the item it depends upon (as described in Example 2 above).
IMPORTANT: During SETUP MODE, changes are allowed
when the DS3 LED and DS4 LED are lit for 2 seconds (as
described in Example 1 and 2 above). During this time, if
button #1 is pushed to change one position and not the other,
the value for that one position will change and the oth er will
default to zero (unless a dependency prevents the zero). However, if button #1 is not pushed at all during the 2 seconds
that the green LEDs are lit, the configuration item will not
change.
F. Manual Mode
Manual mode is used to contr ol the status of I/O channels for
use in troubleshooting. See Table 38.
Enter the Manual mode by holding down the ADVANCE/
MANUAL (#2) button for at least 3 seconds until all LEDs
flash and then the red LED comes on steady.
NOTE: A user can only enter the Manual mode from the
RUN mode, which is entered by pushing buttons #1 and #2
for at least 3 seconds.
All EconoMi$er+ control outputs are turned off. “I/O
Inputs” 1-5 can be adjusted even if the unit is in operation.
In manual mode, the yellow DS2 LED flashes once to indicate the I/O c han nel . Se e Table 38. If th e val u e is le ss th an 5,
the yellow DS2 LED will count out the valu e using 1-secon d
flashes. If the value is greater than 4, the yellow DS2 LED
will count out groups of 5 at a high flash rate and then follow
with the additional value at a flash rate of once per
second. For example a flash of 1 indicates Compressor Relay
Output 1.
Push READ/ADJUST button (#1) to read the value. The yellow LED will flash the I/O Ch annel number being viewed.
Once the channel number is displayed it will then turn on
the appropriate green LED (DS3 or DS4) to i ndicate the status of the output. For relay outputs i f the DS3 LED is on,
then the output is on. If DS4 is on, then the output is off. The
green DS3 and DS4 LEDs will remain on for about 2 seconds
and if during this time the READ/ADJUST (#1) button is
pushed, then the output will toggle to the alternate state. To
change again, push the READ/ADJUST button and re peat
the test or change the status of the output. As an example,
for channel 5 (EconoMi$er+ control damper motor) use the
READ/ADJUST button to toggle the motor from open to
close in %.
At any time, the ADVANCE/MANUAL (#2) button can be
used to advance to the next SET I/ O. To exit the mode, push
and hold the READ/ADJUST and ADVANCE/MANUAL buttons (#1 and #2) for more than 3 seconds.
NOTE: After exiting the Manual mode, the controller will
re-initialize and start with all outputs off.
G. Error Mode
The error mode is used to indicate that an error has occurred
The error is indicated by LED #1 red and #2 yellow are on
steady.
Enter the RUN mode by pushing the READ/ADJUST and
ADVANCE/MANUAL buttons (#1 and #2) for at least
3 seconds until all LEDs flash. Next, push and release button #1 to enter the Read mode. Then push button #2 to
advance to item 20 (“first most recen t err or”). De termi ne the
error by reading the value in items 20 to 24 and referring to
the Troubleshooting section.
One the error has been fixed, press buttons #1 and 2 for at
least 3 second s to exit Read mode. All LEDs will flash.
Enter Setup mode by pressing the READ/ADJUST button
(#1) for at least 3 seconds. All LEDs will flash. Push the
ADVANCE/MANUAL button (#2) to advance to item 20.
Push READ/ADJUST to read item 20.
To reset the error code while the green DS4 LED is on, press
the READ/ADJUST button (#1) once. In addition to resetting
the error mode, this will er ase all error codes. Cycling the
power will also erase the error code.
XV. ECONOMI$ER+ CONFIGURATION
For most applications, the factory setting will be used to control the EconoMi$er+. However, there are 19 diff erent variables that can be used to co nfig ure the contr ol for wide r an g e
of applications. The factory settings and variable s are shown
in Table 37.
—43—
IMPORTANT: There is no way to reset/restore the factory
default c onfig urati ons; us e ca utio n when makin g chang es to
any set point or operational variabl e.
The EconoMi$er+ control accepts an occupied/unoccupied
switch input. This input is used to control the occupied
and unoccupied minimum ventilation damper position as
shown in Table 37 items 2 (ECONOMIN_SP) and 3
(U_ECONOMIN_SP). These va lues represent the minimu m
damper position. In addition, the controls allows for different
modes of compressor operation in the unoccupied mode.
Using item 13 in Table 37 (OCC_MODE), the user can select
one of the following unoccupied modes:
• No unoccupied cooling
• Unoccupied free cooling (Econ oMi$er+)
• Unoccupied free cooling and mechanical cooling
The EconoMi$er+ will control the cooling operation of the
unit based on the demand from the thermostat outpu ts Y1
and Y2. The EconoMi$er+ will monitor the fan output G, but
will not control the fan directly. Note that G must be energized for any cooling to take place. Gas or electric heating
will be controlled dire ctly from the thermostat.
When a demand for coo ling occurs, the control will check to
see if it is in the occupied or unoccupied mode. Depen ding on
the configuration, the control will move the outside air
damper to the ventilati on position. If the outside air co nditions are acceptable, then the control will use the
EconoMi$er+ for free cool ing. If the supply air temperature
does not meet the configurable set point, then the control
will turn on additional stages of mechanical cooling. Several
compressor sequences can be used depending on the application requiremen ts; these will be covered in t he mechanical
compressor staging section.
A. Compressor Configuration and Control
The EconoMi$er+ control can support from 1 to 4 compressor
stages. For the 3 to 12
1
/2 ton units, there will only be 1 or
2 stages of compressor cooling, so the control is factory
configured for 2 stages. There is no difference between 1 and
2 stages. The control also provides the option to configure for
high sensible o r hi gh latent loads , but for units with o nl y t wo
compressors this option does not apply.
Compressors are co nfigured using item 10 (STAGE_TYPE)
in Table 37. The control also has the capability of controlling
directly to Y1 and Y2 inputs. The contr ol can be configured
to control to the leaving air te mperatur e using Y1 and Y2 as
a low cool and high cool demand based on the supply air set
point and the rate of ch ange of supply air tem perature. For
low cool the leaving air temperature set point will be
SAT_SP+2° F. For high cool the leaving air temperature set
point will be the supply air temperature set point (SAT_SP).
To use this option, configure the compressor sequencing variable (STAGE_ TYPE ) to a valu e of 3. Con figur e the supply air
temperature set point (SAT_SP) to the desired leaving-air
temperature.
NOTE: The supply air temperature set point is also the temperature used for EconoMi$er+ control.
The logic will control the operation of the compressors
depending on the configuration selected. If free cooling can
be used, then the compressors will be integrated with the
EconoMi$er+ to provide the lowest cost cooling control. The
logic includes time guards on the compressors to provide a
minimum of 3 minutes on and 3 minutes off time. The control will also prevent two compressors from starting at the
same time. The lo gic use s the EconoMi $er+ to prev ent r apid
cycling of the compressors and l ow air temperatures.
B. Ventilation Air and Free Cooling
In order for the EconoMi $er+ to control ventilation air and
free cooling, several items must be configured.
EconoMi$er+ Type
First, select the EconoMi$e r+ control type that will be used.
This is the EconoMi$er+ Type function (ECONO_TYPE)
defined by item 5 in Table 37. The choices are:
1. Vent only — This is used to have just ventilation control. The EconoMi$er+ will not provide free cooling,
but the occupied and unoccupied minimum positions
can be used.
2. Proportional — In this configuration, full proportional EconoMi$er+ control will be used. When
EconoMi$er+ free cooling cannot be used, the dampers will be set t o the approp riate occupied and unoccupied minimum positions.
3. Three-Position — This mode of EconoMi$er+ is used
to provide a mini mum venti lation Ec onoMi$e r+ position and a fixed free cooling or high ventil ation position. The high ventilation position is controlled by the
optional Remote EconoMi$er+ Enable Switch Input
connected to terminals 11 and 12 on T3.
Supply Air Temperature Set Point
Once the type of Econ oMi$e r+ cont rol ha s been selecte d, the
user will need to set the Supply Air Temperature set point
(SAT_SP). The SAT_SP has a range of 40 to 65 F.
NOTE: This will be the set point when both Y1 and Y2 are
closed. When just Y1 is closed, the set point will be 2 F
higher.
Minimum Damp er Position
Set the occupied minimum damper position
(ECONOMIN_SP) and unoccupied minimum position
(U_ECONOMIN_SP). These should be set to provide the
ventilation requirements at full occupancy as defined by the
building specifications. When demand ventilation is used,
the control will close the dampers below this position based
on measured CO
levels in the space to provide additional
2
operation savings .
The control wil l also a llow for the use o f a remo te mini mum
position potentiometer. This will only adjust the Occupied
Minimum position. If used, the software set point
ECONOMIN_SP sho uld be se t to 0 as the contr ol wi ll use the
largest set point.
The damper position is not linear with the amount of outside
air, so the user will need to set the position of the
EconoMi$er + acco rdi ngly. It is best to use the fo llow ing equ ation and measured data to set the position:
OA =
SAT – RAT
OAT – RAT
*100
OA = % outdoor air
SAT = supply air temperature
RAT = return air temperature
OAT = outdoor air temperature
The SAT and OAT val ues can be read from the control and, if
the unit is equipped with an RAT sensor, then all three values can be read. For the calculation to work properly, there
should be at least a 10° F differen ce between the OAT and
RAT temperatures.
Maximum Damper Position
Set the maximum EconoMi$er+ position. Normally this is
set at 100%. If using 3-position control or there is a reason
not to use 100% outside air, this can be set using the
EconoMi$er+ Maximum Position (MAX_POS_SP).
—44—
Compressor Lockout Temperature
Set the Compressor Lockout Temperature. The Compressor
Lockout Temperature (CMP_LOCK) is used to prevent compressor from running at low ambient conditions when an
EconoMi$er+ can easily satisfy the load.
EconoMi$er+ Changeover Control
Determine the type of EconoMi$er+ changeover control
which will be used to enable and disable free cooling. This is
done using the EconoMi$er+ Changeover Type.
1. Switch — This changeover setting is used when a
remote signal from an energy management system
will enable and disable the EconoMi$er+. This is
done through a remote EconoMi$er+ enable switch.
2. Outdoor Dry Bulb — For this changeover setting, the
EconoMi$er+ w ill be enabled based on the outsid e -air
temperature. The EconoMi$er+ is shipped with an
outside air tempe rature sensor. The outside air temperature set point can be configured by th e user. The
EconoMi$er+ will be disabled when the outdoor-air
temperature rises above the set po int. The co nfiguration variable is the EconoMi$er+ Changeover set
point (OAT_SP).
3. Differentia l Dry Bulb — For this changeover setting,
the EconoMi$er+ will be en abled whenever the outside-air temperature is lower than the return-air
temperature. No configuration of set points is required other than to select the differential dry b ulb
function.
4. Outdoor Enthalpy — For this changeover setting, the
control will enable the EconoMi$er+ based on the
outside-air enthalpy curves as shown in Fig. 29. Using the EconoMi$er+ Changeover set point
(ENTHALPY_SP), select curves A, B, C or D.
The control will then us e the EconoMi$er+ at conditions below the curve. The control uses the OAT and
optional humidity sensor to calculate the enthalpy
and also has the A, B, C, and D curves stored in
memory.
5. Differential Enthalpy — For this changeover setting,
the EconoMi$er+ will be enabled based o n the comparison of the enthalp y of the return air and outs ide
air. If the outside air enthalpy is lower than the return air, then the EconoMi$er+ will be enabled. To
use this option, an accessory outside air humidity
sensor, a return air dry bulb sensor and a return air
humidity sensor must be ordered and installed. No
configuratio n of set points is required other th an to
select the function.
C. Demand Ventilation Configuration
The EconoMi$er+ control has demand ventilation control
capability when using an IAQ sen sor. The indoor air qualit y
(IAQ) is measured using a CO
sensor. The IAQ sensor can
2
be field-installed in the return duct or the occupied space.
The EconoMi$er+ control algorithm modulates the po sition
of the EconoMi$er+ damper between two user configurations
depending upon the relationship between the IAQ and the
Outdoor Air Quality (OAQ). The lower of these two positions
is referred to as the Min imum IAQ Min imum EconoM i$er+
Position (IAQMIN_SP).
The higher position is referred to as the Occupied
EconoMi$er+ Minimum Position (ECONOMIN_SP). The
IAQMIN_SP should be set to an EconoMi$er+ p osition that
brings in enough fresh ai r to remove conta minants and CO
generated by sources other than people. The
ECONOMIN_SP should be set to an EconoMi$er+ positi on
that brings in enough fresh air to remove contaminants and
CO
generated by all sources including people a t the design
2
value for maximum occupancy.
A reference differential CO
level above the outside CO
2
level is used as the starting point for IAQ control and
another reference differential level for maximum ventilation
at design occupancy is used for the end of IAQ control.
Between these points the control wi ll modulate the da mpers
open from the IAQMIN_SP and the ECONOMIN_SP setpoints. The damper position will never go above
ECONOMIN_SP or below IAQMIN_SP.
The control does not measure the outdoor IAQ reference
level as these levels are relatively constant. The installer
should take a measurement at start-up of the unit and enter
this value into the control using the Outdoor Air IAQ reference level configuration.
The control is configured for air quality sensors which provide 4 mA at 0 ppm and 20 mA at 2000 ppm. If a sensor has
a different range, these bounds must be reconfigured.
To configure the control for an IAQ sensor perform the following steps:
1. Determine the Occupied EconoMi$er+ Minimum
position (ECONOMIN_SP) and enter it into the
control.
2. Determine the IAQ minimum EconoMi$er+ position
(IAQMIN_SP) and enter it into the control.
3. Enable IAQ control using IAQ Enable (IAQ_FLG).
4. Determine the Outdoor Air IAQ Reference (OAQ) and
enter it into the control.
NOTE: The value entered into the co ntrol will be the
CO
ppm level divided by 10. For example, 400 ppm
2
would be entered as 40.
5. Determine the lower control point differential level
(DAQLO) and enter it i nto the control. This is a differential level so if the desired level to start IAQ control is 500 ppm and the OAQ reference level is 400
then a value of 100 would be used.
NOTE: The value entered into the co ntrol will be the
CO
ppm level divided by 10. For example 100 ppm
2
would be entered as 10.
6. Determine the upper control point differential level
(DAQHI) and enter it into the control. This is a differential level so if the desired leve l to star t IAQ co ntrol
is 1100 ppm and the OAQ reference level is 400 then
a value of 700 would be used.
NOTE: The value entered into the co ntrol will be the
CO
ppm level divided by 10. For example 700 ppm
2
would be entered as 70.
D. Power Exhaust Configuration
The EconoMi$er+ can control up to 2 stages of power
exhaust. Power exhaust activation is done through configurable damper pos ition set points. The first s tage of power is
controlled by relay C4 on the EconoMi$er+ board. The activation point for the first stage is set using the Power
Exhaust Stage 1 Activation set point (PE_SP1 ). The second
stage of powe r exhaust mus t be set at a v alue greater than
the first stage. It is configured using the Power Exhaust
Stage 2 Activation set point (PE_SP2).
XVI. OPERATING SEQUENCE
A. Cooling, Units without EconoMi$er+
When thermostat calls for cooling, terminals G and Y1 and
2
the compressor contactor (C) are energized. The indoor
(evaporator) fan motor (IFM), compressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously
2
—45—
while the unit is in cooling. When the thermostat is satisfied,
C is deenergized and the compressor and OFM shut off. After
a 30-second delay, the (IFM) shuts off. If the thermostat fan
selector switch is in the ON position, the evaporator motor
will run continuously.
B. Heating, Units without EconoMi$er+
When the thermostat call s for heatin g, terminal W1 is energized. The induced-draft motor is energized and the burner
ignition seque nce begins. The indoor (evaporator) fan m otor
(IFM) is energized 45 seconds after a flame is ignited. When
additional he at is n eeded, W 2 is en ergized and t he high- fire
solenoid on the main gas valve (MGV) is energized. When
the thermostat is sati sfied and W1 is deenergiz ed, the IFM
stops after a 45-second time-off delay.
C. Cooling, Units with EconoMi$er+
For EconoMi$er+ operation, there must be a thermostat call
for the fan (G). This will move the damper to its minimum
position.
When the EconoMi$er+ control is the occupied m ode and a
call for cooling exists (Y1 on the thermostat), the control will
first check for indoor fan operat ion. If the fan is not on, th en
cooling will not be activated. If the fan is on, then the control
will open the EconoMi$er+ damper to the minimum position.
On the initial p ower to the EconoMi$er+ board, it will ta ke
the damper up to 2
1
/2 minutes before it begins to position
itself. With subsequent fan signal (G) to the board, the
changed in damper position will take up to 30 seconds to initiate. Damper movement from full closed to full open (or vice
versa) will take 2
1
/2 minutes.
If the damper is in the process of a change (for example going
to 100% open) and the signal (G) is turn ed off, the damper
will continue to open to 100% before it closes (due to no fan
signal [G]).
If free cooling c an be used as determin ed from the appr opriate changeover command (switch, dry b ulb, enthalpy curv e,
differential dry bulb, or differential enthalpy), then the control will modulate the dampers open to main the supply air
temperature set point plus 2° F.
If there is a further demand for cooli ng (coo li ng secon d st age
— Y2 is energized), then the control set point for the l eaving
air will be set at the supply air set point to increase the cooling capacity. If this cannot satisfy the load then the control
will bring on comp ressor stages as needed to maintain the
supply air temperatu re set point. The EconoM i$er+ damper
will be locked o pen at 100% or the maximu m damper position set point.
To ensure that there is oil return, the compressors will
operate for a t least 3 mi nutes. If, dur ing th is pe riod , th e lea ving temperature dr ops below the set point by 5 F, then the
EconoMi$er+ dampers will be closed to 60% until the compressor is turned off to avoid cold leaving air temperatures.
If the conditions are not suitable for free cooling then the
EconoMi$er+ dampers will be closed to the minimum ventilation posit ion.
Compressor stages will be used to co ol the air. If the control
is configured for direct control by Y1 and Y2, then the stages
will sequence based on the demand of Y1 and Y2. If the
control is configured for leaving air temperature control,
then Y1 will maintain the leaving air temperature at the
supply air set point plus 2° F. If Y1 and Y2 are closed, then
the leaving air will be controlled to the supply air set point.
If Y2 is closed and Y1 is open, then control will shut down
and indicate an error due to a thermostat failure or improper
wiring of the thermostat.
If the unit is in the unoccupied m ode, then the control of the
temperature will depend on the unoccupied free cooling
configuration: no unoccupie d cool ing, unoccupied free cooling
with any mechanical cooling, or unoccupied free and
mechanical cooling. If free cooling is enabled, then the control will check if free cooling can be used. The EconoMi$er+
will then control to the leaving air temperature set point
plus 2 F for a Y1 command, or the leaving air temperature
set point for a Y1 and Y2 command. If me chanical coo ling is
allowed to be used, then the control will then bring on additional stages o f me chani cal coo lin g i f f ree co ol in g c annot sa tisfy the load.
If the EconoMi$er+ control:
• is in the occupied mode
• is configured to use demand ventilation
• cannot use free cooling
• has return air or space CO
levels below the DAQLO
2
limit,
then the EconoMi$er+ damper position will be set to the
IAQMIN_SP set point. If the CO2 level rises above the
DAQLO limit, then the dampers will modulate open in a linear relationship un til the return air o r space CO
levels are
2
at or above the DAQ HIG H limi t. The dampe r posit ion wi ll be
at the ECONOMIN_SP set point.
When the EconoMi$er+ is being used for free cool ing and the
position exceeds the power exhaust set point, then the control will turn on the appropriate power exhaust fans. Refer to
Fig. 23 for barometric relief capacit y, Fig. 24 for outdoor air
leakage, and Fig. 25 for pressure drop.
Unoccupied and Occupied Minimum Position Control
There is an unoccupied minimum damper position and an
occupied minimum damper position on the EconoMi$er+
controller. When the HVAC fan is off the outdoor air damper
will always be closed. W hen the f an is on an d in the unoccu pied mode, the outdoor air damper will be at the unoccupied
minimum position . When the fan is on (G call ) and in the
occupied mode, the outdoor air damper will be at the occupied minimum position.
A jumper wire is factory-installed to force the unit into
occupied configuration whenever G or Y1 are closed. Without
the jumper wire, the unit will alw a ys be in unoccupi ed mode.
The 2 minimum position settings are also used in the IAQ
sequence of operation. See Indoor Air Quality Sensor on
page 18.
NOTE: The minimum pos ition signal tak es priority over the
maximum position signal. If the maximum damper position
is set below the min imu m damper position, the Econ oMi $e r+
controller will maintain the actuator at minimum position.
Adjust the unoccupied minimum position to allow the minimum amount of outdoor air, as required by local codes, to
enter the building. Make minimum position adjustments
with at least 10 F (6 C) temperature difference between the
outdoor and return air temperatu res.
To determine the unoccupied minimum position setting, perform the following procedure:
Calculate the app ropriate supply-ai r temperature usin g the
following formula: (T O x OA) + (T R x RA) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Supply-Air Temperature
—46—
As an example, if local codes requ ire 10% outdoor air duri ng
occupied conditions, outdoor-air temperature is 60 F, and
return-air temperature is 75 F:
(60 x 0.10) + (75 x 0.90) = 73.5 F
Carefully adjust the unoccupied minimum position until the
measured supply-air temperature matches the calculated
value. Then, carefully adjust the occupied minimum position
set point on the controller until the desired position is
reached.
D. Heating, Units with Economi$er+
When the room temperature calls for heat through terminal
W1, the indoor (evaporator) fan contactor (IFC) and heater
contactor no. 1 (HC1) are energized. On units equipped for
2 stages of heat, when additional heat is needed, W2 is energized and the hig h-fire sole noid o n the main gas v alve (MG V)
is energized. The economizer damper moves to the minimum
position. When the thermostat is satisfied, the damper
moves to the fully closed position.
SERVICE
CAUTION: When servicing unit, shut off all electri-
cal power to unit and install lockout tag to avoid shock
hazard or injury from rotating parts .
I. CLEANING
Inspect unit interior at the beginning of heating and cooling
season and as operating conditions require.
A. Evaporator Coil
1. Turn unit power off and install lockout tag. Remove
evaporator coil access panel.
2. If economizer or two-position damper is installed,
remove economizer by disconnecting Mole x plug and
removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister.
Wash both sides of coil and flush with clean water.
For best results, back-flush toward return-air section
to remove foreign material. Flush condensate pan
after completion.
5. Reinstall ec onomizer and filters.
6. Reconnect wiring.
7. Replace access panels.
B. Condenser Coil
Inspect coil mon thly. Clean condenser coil annua lly, and as
required by location and outdoor air conditions.
One-Row Coils (Size 036)
Wash coil with comme rcia l coi l clea ner. It is not necessary to
remove top panel.
2-Row Coils (Sizes 048-073)
Clean coil as follows:
1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 37. To
hold top panel open, place coil corner post between
top panel and center post. See Fig. 38.
4. Remove screws securing coil to compressor plate and
compressor access panel.
5. Remove fast ener holdi ng coil sect ions togethe r at return end of condenser coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 39.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil s ections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
7. Secure inner and outer coil rows together with a fieldsupplied fastener.
8. Reposition the outer coil se ction and remove the coil
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
C. Condensate Drain
Check and clean each year at star t of coo lin g sea so n. I n win ter, keep drain dry or protect against freeze-up.
D. Filters
Clean or rep lace at s tar t of e ach h eati ng an d co oling seas on,
or more often if operating conditions require it. Replacement
filters must be same dimensions as original filters.
E. Outdoor-Air Inlet Screen
Clean screen with stea m or hot water and a mild deter gent.
Do not use disposable filters in place of screen.
Fig. 37 — Cleaning Condenser Coil
Fig. 38 — Propping Up Top Panel
—47—
Fig. 39 — Separating Coil Sections
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at
the factory.
B. Fan Motor Bearings
Fan motor bearings are of the permanently lubricated type.
No further lubrication is required. No lubrication of condenser or evaporator fan motors is required.
III. BLOWER BELT ADJUSTMENT
Inspect blower b elt for we ar, proper belt tension, and pu lley
alignment as conditions require or at the beginning of each
heating and air conditioning season.
Refer to Step 9 — Adjust Evaporator-Fan Speed on page 24
for adjustment and alignment procedures.
Check belt tension at least once each heating or cooling season or as conditions require. Adjust as required.
IV. MANUAL OUTDOOR-AIR DAMPER
If outdoor-air damper blade adjustment is required, see
Manual Outdoor-Air Damper section on page 14.
V. ECONOMI$ER+ ADJUSTMENT
Refer to Optional EconoMi$er+ section on page 15.
VI. CONDENSER-FAN ADJUSTMENT (Fig. 40)
Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, and fan) and loosen fan hub setscrews. Adjust
fan height as shown in Fig. 40. Tighten setscrews and
replace condenser-fan assembly.
VII. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate
(also refer to Table 1). Compressor must run a minimum of
10 minutes before adjus ting or checki ng charge.
Unit panels must be in place when unit is operating during
charging procedure.
Fig. 40 — Condenser-Fan Adjustment
A. No Charge
Use standar d evacuating technique s. After ev acuating system, to 500 microns, weigh in the specified amount of refrigerant. (Refer to Table 1.)
B. Low-Charge Cooling
Using Cooling Charging Charts, Fig. 41-44, vary refrigerant
until the conditions of the appropriate chart are met. Note
the charging charts are different fr om type normally used.
Charts are based on charging the units to the co rrect superheat for the various operating c onditio ns. Accurate pressure
gage and temperature sensing device are required. Do not
use pocket type thermometers for measuring surface temperatures as they are not designed for this type of measurement. Connect the pressure gage to the service port on the
suction line. Moun t the temperature sensing device on the
suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be
within the normal operating range of the unit.
C. To Use Cooling Charging Chart
Take the outdoor ambient tempera ture and re ad the sucti on
pressure gage. Refer to chart to determine what suction temperature should be. If suction temperature is high, add
refrigerant. If suction temperature is low, carefully recover
some of the charge. Recheck the su ction pressure as charge
is adjusted.
Suction Temperature should be . . . . . . . . . . . . . . . . . . . 76 F
(Suction Temperature may vary 5 F.)
VIII. FLUE GAS PASSAGEWAYS
To inspect the flue collector box and upper areas of the hea t
exchanger:
1. Remove the combustion blower wheel and motor
assembly according to directions in Combustion-Air
Blower section on pa ge 49.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
—48—
IX. COMBUSTION-AIR BLOWER
Clean periodically to assure proper airflow and heating efficiency. Inspect blow er whee l ev ery f all and peri od ical ly d uri ng
heating season. For the first heating season, inspect blower
wheel bimonthly to determine proper cleaning frequency.
To access burner section, slide the sliding burner partition
out of the unit.
To inspect blower wheel, shine a flashlight into draft hood
opening. If cleaning is required, remove motor and wheel as
follows:
1. Slide burner access panel out.
2. Remove the 7 screws that attach induced-draft motor
housing to vestibule plate (Fig. 45).
3. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4
and 5.
4. To remove blower from the motor shaft, remove 2
setscrews.
5. To remove motor, remove the 4 screws that hold the
motor to mounting plate. Remove the motor cooling
fan by removing one setscrew. Then remove nuts that
hold motor to mounting plate.
6. To reinstall, reverse the pro c edure outlined above.
X. LIMIT SWITCH
Remove blower access panel (Fig. 7). Limit switch is located
on the fan deck.
XI. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is loc ate d in the
control box (Fig. 11). The IGC contains a self-diagnostic LED
(light-emitting diode). A single LED on the IGC provides a
visual display of operational or sequential problems when the
power supply is uninterrupted. When a break in p ower occ urs ,
the IGC will be reset (resulting in a loss of fault history) and
the indoor (evaporator) fan ON/OFF times will be reset. The
LED error code can be observed through the viewport. During
servicing refer to the label on the control box co ver or Table 39
for an explanation of LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
Table 39 — LED Error Code Description*
LED INDICATIONERROR CODE DESCRIPTION
ONNormal Operation
OFFHardware Failure
1Flash†Evaporator Fan On/Off Delay Modified
2FlashesLimit Switch Fault
3FlashesFlame Sense Fault
4Flashes4 Consecutive Limit Switch Faults
5FlashesIgnition Lockout Fault
6FlashesInduced-Draft Motor Fault
7FlashesRollout Switch Fault
8FlashesInternal Control Fault
9FlashesInternal Software Processor Fault
LEGEND
LED — Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more than one error
code exists, all applicable codes will be displayed in numerical sequence.
†Indicates a code that is not an error. The unit will continue to operate when this
code is displayed.
IMPORTANT: Refer to Troubleshooting Tables 41-43 for additional information.
XII. MAIN BURNERS
To access burners, remove burner access pa nel a nd slide out
burner partition. At the beginning of each heating season,
inspect for deterioration or blockage due to corrosion or other
causes. Observe the main burner flames and adjust, if
necessary.
CAUTION: When working on gas train, do not hit or
plug orifice spuds.
A. Removal and Replacement of Gas Train (Fig. 45-47)
1. Shut off manual gas valve.
2. Shut off power to unit and tag disconnect.
3. Slide out burner partition.
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each
wire.
6. Remove ignitor wires and sensor wires at the Integrated Gas Unit Controller (IGC) (see Fig. 11).
7. Remove the 2 screws that attach the burner rack to
the vestibule pl ate (Fig. 45).
8. Slide the burner tray out of the unit (Fig. 46).
9. To reinstall, reverse the procedure outlined above.
B. Cleaning and Adjustment
1. Remove burner rack from unit as described in
Removal and Replacement of Gas Train section, abo ve.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush clean burners and cross-over port
as required.
4. Adjust spark gap. See Fig. 47.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and
Replacement of Gas Train section, above.
XIII. HIGH-PRESSURE SWITCH
Located on the compressor hot gas line is a high-pressure
switch containing a Schrader core depressor. This switch
opens at 428 psig and closes at 320 psig. No adjustment is
necessary. Refer to Table 1.
XIV. LOSS OF CHARGE SWITCH
Located on the cond enser liquid line is a low-pressure switch
which functions as a loss-of-charge switch. This switch contains a Schrader core depressor. This switch opens at 7 psig
and closes at 22 psig. No adjustment is necessary. Refer to
Table 1.
XV. FREEZESTAT
Located on the “hair pin” end of the evaporator coil is a
bimetal temperature sensing switch. This switch protects
the evaporator coi l from f reeze -up due to lack of ai rflow. The
switch opens at 30 F and closes at 45 F. No adjustment is
necessary. Refer to Table 1.
XVI. REPLACEMENT PARTS
A complete list of repl acement parts may be obtained from
any Bryant distributor upon request.
—49—
3 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10162127
100
90
80
70
689
621
552
483
OUTDOOR
TEMP
FC
12552
11546
10541
9535
8529
7524
6518
5513
457
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20304050607080
SUCTION LINE TEMPERATURE (DEG. F)
414
345
276
207
Fig. 41 — Cooling Charging Chart, 580F036
4 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10162127
100
90
689
621
SUCTION LINE PRESSURE (KILOPASCALS)
OUTDOOR
TEMP
FC
125
115
10541
9535
8529
52
46
80
70
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20304050607080
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 42 — Cooling Charging Chart, 580F048
—50—
552
483
414
345
276
207
75
65
55
457
SUCTION LINE PRESSURE (KILOPASCALS)
24
18
13
5 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7-1410162127
100
90
80
70
689
621
552
483
OUTDOOR
TEMP
FC
12552
11546
10541
9535
8529
7524
6518
5513
457
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20304050607080
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 43 — Cooling Charging Chart, 580F060
6 TON UNIT (60 Hz) CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7-1410162127
100
90
80
70
414
345
276
207
SUCTION LINE PRESSURE (KILOPASCALS)
689
621
552
483
OUTDOOR
TEMP
FC
12552
11546
10541
9535
8529
7524
6518
5513
457
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20304050607080
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 44 — Cooling Charging Chart, 580F072, 073
—51—
414
345
SUCTION LINE PRESSURE (KILOPASCALS)
276
207
INDUCEDDRAFT
MOTOR
MOUNTING
PLATE
BURNER
SECTION
INDUCEDDRAFT
MOTOR
MANIFOLD
PRESSURE
TAP
Fig. 45 — Burner Section Details
ROLLOUT
SWITCH
FLUE
EXHAUST
VESTIBULE
PLATE
BLOWER
HOUSING
GAS
VALV E
Fig. 46 — Burner Tray Details
580F036-073 — 74,000 BTUH INPUT
LOW HEAT
580F036-060 (Low NO
) — 60,000 BTUH INPUT
x
MEDIUM AND HIGH HEAT
580F036-073 — 115,000 BTUH INPUT
580F048-073 — 150,000 BTUH INPUT
580F036-060 (Low NO
580F048-060 (Low NO
) — 90,000 BTUH INPUT
x
) — 120,000 BTUH INPUT
x
Fig. 47 — Spark Adjustment
—52—
TROUBLESHOOTING
I. ECONOMI$ER+ TROUBLESHOOTING
The EconoMi$er+ control has built-in diagnostics. The control can detect and display 10 different diagnostic codes as
shown in Table 40. The us er ca n al so us e the integra ted display to check the status of all the inputs and outputs and run
the manual control mode to check the operation of the
EconoMi$er+ and compressors.
Table 40 — EconoMi$er+ Error Codes
NO.DESCRIPTIONCRITERIA
1 SAT Sensor FailureTemperature <–40 F or Greater Than 250 F
2 RAT Sensor FailureTemperature <–40 F or Greater Than 250 F
3 OAT Sensor FailureTemperature <–40 F or Greater Than 250 F
4 ORH Sensor FailureRead Less Than 2 mA or Greater Than 22 mA
5 IRH Sensor FailureRead Less Than 2 mA or Greater Than 22 mA
6 IAQ Sensor FailureRead Less Than 2 mA or Greater Than 22 mA
7 Y2OnY1 OffWiring Error
8 Micro Fails E2 TestsHardware/Software Check
* Micro Fails RAM TestHardware/Software Check
† Micro Fails ROM Tests Hardware/Software Check
LEGEND
IAQ — Indoor Air Quality
IRH — Indoor Relative Humidity
OAT — Outdoor Air Temperature
ORH — Outdoor Relative Humidity
RAT — Return Air Temperature
SAT — Supply Air Temperature
*If there is a RAM failure DS1+DS3/DS2+DS4 will alternately flash.
†If there is a ROM failure DS1+DS2/DS3+DS4 will alternately flash.
A. Error Code 1 — SAT Sensor Failure
Error Criteria
An SAT Sensor Failure error will occur if the sensor is
shorted or faulty. If the measured temperature reads below
–40 F or above 250 F an error will occur.
Required Action
If an error occurs, then the control will default to Mode 2
compressor stage contro l where Y1 and Y2 have direct control of the compressors. Use of free cooling is disabled and
the EconoMi$er+ will be set to the minimum damper position for either the occupied or unoccupied mode of operation.
Replace sensor if faulty.
Reset Method
The error will automatically reset after the value has
returned to a normal level. The alarm has to be cleared from
the display in the Setup mode or a power reset.
B. Error Code 2 — RAT Sensor Failure
Error Criteria
The RAT Sensor failure error is only applicable the unit
has been configured for EconoMi$er+ changeover methods
3 (differential dry bulb) or 5 (differential humidity). For
other modes it shou ld be ignored . If the sensor is shorted o r
faulty, then the measured temperature will be below –40 F
or above 250 F and the error will occur.
Required Action
If this error occurs, then change the default EconoMi$er+
changeover control to method 2 (dry bulb changeover control) or replace sensor.
Reset Method
This error will automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Se tup mode.
C. Error Code 3 — OAT Sensor Failure
Error Criteria
An OAT Sensor Failure error occurs if the sensor is short ed
or faulty, then the measured temperature will be below
–40 F or above 250 F.
Required Action
If this error occurs disable the economizer and set the econo-
mizer to the minimum economizer position.
Reset Method
This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.
Error Criteria
This error occurs if th e unit is configured for EconoMi$er+
changeover type 5 and the input signal is less than 2 mA or
greater than 22 mA (faulty sensor).
Required Action
If this error occurs, switch the EconoMi$ er+ to differential
dry bulb changeover control.
Reset Method
This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.
F. E rr or C od e 6 — I AQ Sensor Failure
Error Criteria
This error occurs if th e unit is configured for IAQ demand
ventilation control and the input signal is less than 2 mA or
greater than 22 mA (faulty sensor).
Required Action
If this error occurs, disable the IAQ control routine and
default to the standard EconoMi$er+ minimum position.
Reset Method
This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared
from the display in the Setup mode or by a power reset.
G. ErrorCode7—Y2onWith Y1 Off
Error Criteria
This error occurs if Y 2 is turned on and Y1 is of f. This indi-
cates that there is a wiring error at the thermostat connections. This alarm sho uld be ignored fo r the first 20 sec onds of
operation so tha t it does no t co nfl ic t wit h th e sp ec ial pr odu ction test mode.
Required Action
Shut the unit off and check wiring.
—53—
Reset Method
This error must be manually reset and requires a power
reset.
H. Error Code 8 — E2 Test Failure
Error Criteria
This error occurs if internal hardware detects an E2 failure.
Required Action
Shut the un it off.
Reset Method
This error must be manually reset and requires a power
reset.
I. Error Mode
When an error occurs, the red and yellow LEDs both come on
steady. To determine the error, follow these steps:
1. Enter the Run mode by pushing buttons #1 and #2 for
at least 3 seconds until all LEDs flash.
2. Press and release the #1 button to enter the Read
mode.
3. Push the ADVANCE/MANUAL (#2) button to advance to item number 20, “1st Most Recent Error.”
Determine the error(s) by reading the values in
items 20-24 and referring to the error codes described
above.
4. Fix the error(s).
5. Press buttons 1 and 2 to exit read mode. Enter Setup
mode by pressing button #1 for at least 3 seconds until all the LEDs flash.
6. Push button #2 to advance to item number 20.
7. To reset the error code while the green DS4 LEDS is
ON, press the READ/ADJUST (#1) button once. This
resets the error mode and erases all repaired error
codes.
NOTE: Cycling power to the board will al so erase the
repaired error codes.
J. RAM Test Failure
Error Criteria
If internal hardware detects a RAM failure, this alar m will
be displayed by alternately flashing DS1+DS3 and
DS2+DS4.
Required Action
Shut the unit off.
Reset Method
This error must be manually reset and requires a power
reset.
K. ROM Test Failure
Error Criteria
If internal hardware detects a ROM failure, the alarm is dis-
played by alternately flashing DS1+DS2 an d DS3+DS4.
Required Action
Shut the unit off.
Reset Method
This error must be manually reset and requires a power
reset.
L. Unit Always in Unoccupied Mode
A jumper wire is factory-installed to force the unit into o ccupied configurat io n wh ene ver G or Y1 are clos ed. Withou t the
jumper wire, the unit will always be in unoccupied mode.
Check the wire. An occupied/unoccupied switch may be
installed in pl ace of the j ump er. Ch eck the wi ring and se tting
of the switch.
II. UNIT TROUBLESHOOTING
Refer to Tables 41-43.
—54—
Table41—LEDErrorCodeServiceAnalysis
SYMPTOMCAUSEREMEDY
Hardware Failure.
(LED OFF)
Fan ON/OFF Delay Modified
(LED/FLASH)
Limit Switch Fault.
(LED 2 flashes)
Flame Sense Fault.
(LED 3 flashes)
4ConsecutiveLimit
Switch Faults.
(LED 4 flashes)
Ignition Lockout.
(LED 5 flashes)
Induced-Draft Motor Fault.
(LED 6 flashes)
Rollout Switch Fault.
(LED 7 flashes)
Internal Control Fault.
(LED 8 flashes)
Internal Software Fault.
(LED 9 flashes)
CAUTION: If the IGC must be replaced, be sure to ground
yourself to dissipate any electrical charge that may be present before
handling new control board. The IGC is sensitive to static electricity
and may be damaged if the necessary precautions are not taken.
Loss of power to control module (IGC).Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat exchanger
warm-up period before fan-on delay expires.
Limit switch opens within three minutes after
blower-off delay timing in Heating mode.
High temperature limit switch is open.Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be
present.
Inadequate airflow to unit.Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for
15 minutes.
IGC does not sense that induced-draft
motor is operating.
Rollout switch has opened.Rollout switch will automatically reset, but IGC will continue to lockout unit.
Microprocessor has sensed an error in the
software or hardware.
Internal Software Processor fault.Fault code will automatically reset after one hour. Can be immediately
transformer. Units without a 24-v circuit breaker have an internal overload
in the 24-v transformer. If the overload trips, allow 10 minutes for automatic
reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure unit’s external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with the range
on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly terminated. Verify
that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the speed sensor
plug/IGC Terminal J2 connection. Proper connection: PIN 1 — White, PIN
2 — Red, PIN 3 — Black.
Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft.
Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
reset by resetting unit power supply.
IMPORTANT:
troubleshooting analysis.
IGC— Integrated Gas Unit Controller
LED — Light-Emitting Diode
Refer to Table 42 — Heating Service Analysis for additional
LEGEND
Table 42 — Heating Service Analysis
PROBLEMCAUSEREMEDY
Burners Will Not Ignite.Misaligned spark electrodes.Check flame ignition and sensor electrode positioning. Adjust as needed.
No gas at main burners.Check gas line for air, purge as necessary. After purging gas line of air, allow
Water in gas line.Drain water and install drip leg to trap water.
No power to furnace.Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.Check transformer. Transformers with internal overcurrent protection require a
Miswired or loose connections.Check all wiring and wire nut connections.
Burned-out heat anticipator in thermostat.Replace thermostat.
Broken thermostat wires.Run continuity check. Replace wires, if necessary.
Inadequate Heating.Dirty air filter.Clean or replace filter as necessary.
Gas input to unit too low.Check gas pressure at manifold. Clock gas meter for input. If too low, increase
Unit undersized for application.Replace with proper unit or add additional unit.
Restricted airflow.Clean filter, replace filter, or remove any restrictions.
Blower speed too low.Use high speed tap, increase fan speed, or install optional blower, as suitable
Limit switch cycles main burners.Check rotation of blower, thermostat heat anticipator settings, and temperature
Too much outdoor air.Adjust minimum position.
Poor FlameCharacteristics. Incomplete combustion (lack of combustion
Burners Will Not Turn Off.Unit is locked into Heating mode for a one
gas to dissipate for at least 5 minutes before attempting to relight unit.
Check gas valve.
cool down period before resetting.
manifold pressure, or replace with correct orifices.
for individual units.
rise of unit. Adjust as needed.
Check economizer operation.
Check all screws around flue outlets and burner compartment. Tighten as nec-
essary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust gas line or manifold
pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Wait until mandatory one minute time period has elapsed or re-
set power to unit.
—55—
Table 43 — Cooling Service Analysis
PROBLEMCAUSEREMEDY
Compressor and Condenser Fan
Will Not Start.
Compressor Will Not Start But
Condenser Fan Runs.
Compressor Cycles (Other Than
Normally Satisfying Thermostat).
Compressor Operates
Continuously.
Excessive Head Pressure.Dirty air filter.Replace filter.
Head Pressure Too Low.Low refrigerant charge.Check for leaks; repair and recharge.
Excessive Suction Pressure.High head load.Check for source and eliminate.
Suction Pressure Too Low.Dir ty air filter.Replace filter.
Evaporator Fan Will Not Shut Off.Time off delay not finished.Wait for 30-second off delay.
Compressor Makes Excessive
Noise (580F072 and 073 Scroll
Only).
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or
control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room temperature.
Faulty wiring or loose connections in compressor
circuit.
Compressor motor burned out, seized, or internal
overload open.
Defective run/start capacitor, overload, start relay.Determine cause and replace.
One leg of three-phase power dead.Replace fuse or reset circuit breaker. Determine cause.
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and recharge to
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or start relay.Determine cause and replace.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak; repair and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Recover excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and recharge.
Condenser air restricted or air short-cycling.Determine cause and correct.
Compressor valves leaking.Replace compressor.
Restriction in liquid tube.Remove restriction.
Low refrigerant charge.Check for leaks; repair and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Outdoor ambient below 25 F.Install low-ambient kit.
Compressor rotating in wrong direction.Reverse the 3-phase power leads as described in the
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
nameplate.
necessary.
Start-Up section on page 37.
—56—
NOTES:
1. If any of the original wire furnished must be
replaced,itmustbereplacedwithtype90Cwireor
its equivalent.
2. Three phase motors are protected under primary
single phasing conditions.
4. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with
208 v power supply, disconnect BLK wire from
230 v tap (ORN) and connect to 208 v tap (RED).
Insulate end of 230 v tap.
C—Contactor, Compressor
CAP— Capacitor
COMP — Compressor Motor
EQUIP — Equipment
FPT— Freeze Up Protection Thermostat
FU— Fuse
GND— Ground
GVR— Gas Valve Relay
HPS— High-Pressure Switch
HS— Hall-Effect Sensor
I—Ignitor
IDM— Induced-Draft Motor
IFC— Indoor Fan Contactor
IFM— Indoor (Evaporator) Fan Motor
IGC— Integrated Gas Unit Controller
LPS— Low-Pressure Switch
LS— Limit Switch
MGV— Main Gas Valve
LEGEND
OFM— Outdoor (Condenser) Fan Motor
OLR— Overload Relay
P—Plug
PL— Plug AssemblyQT—Quadruple Terminal
RS— Rollout Switch
SAT— Supply Air Temperature Sensor
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Fig. 48 — Typical Unit Wiring Diagram
—57—
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
PUSHBUTTONSLED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
OFF
ONES OR
TEN'S
OR ON
NamesADJUSTADVSET NO SETUP
SETUP MODE
APPENDIX A — ECONOMI$ER+ LABEL
OFF
ONES OR
TEN'S
OR ON
Actions Hold/Push Push flash, no steady flash no flash no
Each time the ADV button is pushed, the SET NO flashes the point number and then displays
the current setting
on use the ADJUST button to enter the value. (i.e., push the button 4 times to enter 4)
Then wait for the ONES indicator to turn on and enter the ONES setting
Note 1 Push and hold the ADJUST button until the SETUP indicator turns on.
Note 2 Push and release ADV button repeatedly to advance to the desired setup point.
Note 3 Once the current value has been displayed the TENS indicator will turn on steady and while it
Wait for indicator to turn off and then push read/adjust to check the setting
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
NamesADJUSTMANMANI/O NO
MANUAL
ActionsPush Hold/Push steady flash no flash no flash no
Each time the MAN button is pushed, the I/O NO flashes the I/O point number.
and off or open and closed
1 SATsensor invalid
2 RAT Sensor Invalid (only with changeover type 3&5)
3 OAT Sensor Invalid
4 ORH Sensor invalid (only with changeover type 3&4)
5 IRH Sensor invalid (only with changeover type 5)
6 IAQ Sensor Invalid (only if IAQ=1)
7 Y2onY1off
Note 1 Push and hold the MAN button until the MAN indicator turns on.
Note 2 Push and release MAN button repeatedly to advance to the desired I/O point.
NO DESCRIPTION
Note 3 After the desired I/O No is reached push and release the ADJUST to toggle the output on
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
ALARM CODES
8 Micro Fails E2 test
note 1 Micro Fails RAM test
note 2 Micro Fails ROM test
Note 1 DS1+DS3/DS2+D4 will alternately flash
Note 2 DS1+DS2/DS3+D4 will alternately flash
PUSHBUTTONSLED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
Actionflashflashflashflash
Indicators flash in sequence at .5 sec intervals
STARTUP MODE
Note 1
NamesHBECONOY1Y2
RUN MODE
Actionsflashflash steadysteady
Note 1 Heartbeat Indicator flashes to indicate proper operation of the control
Note 2 Econo indicator flashes to indicate free cooling being used
Note 3 Y1 and Y2 are on steady when a call thermostat Y1 and Y2 are closed
Note 4 ERROR - HB and Econo are on steady to indicate the presence of an error
OFF
ONES OR
TEN'S
OR ON
NamesREADADVSET NO I/O NO
ActionsPushPush flash, no flash no flash no flash no
READ MODE
Note 1 Push and release the READ button to enter Read Mode. The SET NO Indicator flashes once
to indicate the setup point is selected for viewing
Note 2 Push and release ADV button repeatedly to advance to the desired setup point or I/O point
Each time the ADV button is pushed, the SET NO flashes the point number until the desired
I/O point is reached and then the I/O NO flashes the I/O point no.
button to display the value in the TEN's and ONE's indicator (i.e., 5 flashes for a value of 5)
Note 3 After the SET NO indicator identifies the desired point no, push and release the READ
or a steady TEN's indicator for an on and a steady ONE's for off.
To aid in counting, values of 5 are flashed in groups of 5 (i.e., 150 = 3 groups of fast 5 flashes)
and then follow by balance in slow flashes (i.e., 7 = 5 quick flashes + 2 slow flashes)
Red Set No LED displays Setup item numbers, and Yellow I/O LED displays I/O item no
Note 4 Setpoint values are displayed first followed by I/O values and then back to Setpoint values
Note 5 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
NO I/O PointsUNITS
I/O POINTS
1 C1 Output-
2 C2 Output-
3 C3 Output-
4 C4 Output-
5 Economizer Damper Output%
6 Supply Air temperatureF
7 Outside Air temperatureF
8 Return Air TemperatureF
9 Indoor Relative Humidity%
10 Outdoor Relative Humidity%
11 Indoor Air QualityPPM
12 Remote Minimum Position%
13 Y1 Status (next version)-
14 Y2 Status (next version)-
15 G Status (next version)-
16 Occ Status (next version)-
—58—
APPENDIX A — ECONOMI$ER+ LABEL (cont)
—59—
APPENDIX B — JOB SPECIFIC ECONOMI$ER+ CONFIGURATION SETTINGS
Enter the job specific settings in the “Job Setting” column below.
Low pressure switch9, 49
Main burners 38, 49
Manual outdoor air damper 14
Mounting
Compressor 37
Unit 4
Natural gas 9
Operating limits4
Operating sequence 45-47
Cooling 45, 46
EconoMi$er+ 46, 47
Heating 46, 47
Outdoor air hood 14, 16
Outdoor air inlet screens
Cleaning47
Dimensions 9
Outdoor air humidity sensor19
Outdoor air temperature sensor 18
Physical data 8, 9
Power supply 10
Wiring11
Pressure switches
High pressure 9, 49
Low pressure9, 49
Pre-Start-Up 37
Refrigerant
Charge 8, 48
Type 8
Refrigerant service ports 37
Replacement parts 49
Return air filter 9, 37
Return air temperature sensor 18, 19
Rigging unit 4, 7
Roof curb
Assembly 1
Dimensions 5
Connector package 5
Leveling tolerances 6
Weight8
Safety considerations 1
Safety relief 39
Service 47-52
Service ports 37
Slab mount 4
Start-up37-47
Start-up checklistCL-1
Thermostat8
Troubleshooting 53-57
Ventilation39
Weight
Corner2, 3
EconoMi$er+ 2, 3, 8
Maximum 6
Unit 2, 3, 7, 8
Wiring
EconoMi$er+ 16
Power connections 11
Thermostat 11
Unit 57
—61—
SERVICE TRAINING
Packaged Service Training programs are an excelle nt way to increase your knowledge of the
equipment discussed in this manual, including:
• Unit Familiarization• Maintenance
• Installation Overview• Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based
formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our labs
can mean increased confidence tha t real ly pays dividen ds in fas ter trou bles hoo ting a nd fewer call backs. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training[ ] Classroom Service Training
MODEL NO.: _______________________________________ SERIAL NO.:_______ _______________________________________
DATE: _____________________________________________ TECHNICIAN: ____________________________________________
BUILDING LOCATION: ___________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
VERIFY THAT FLUE HOOD IS INSTALLED
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHA RP EDGES
CHECK GAS PIPING FOR LEAKS
CHECK THAT RETURN-AIR FILTER IS CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
VERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT
CUT ALONG DOTTED LINE
III. START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2__________ __L2-L3 ____________L3-L1____________
COMPRESSOR AMPS L1____________L2____________L3____________
INDOOR-FAN AMPL1____________L2____________L3____________
TEMPERATURES
OUTDOOR-AIR TEMPERATURE _____________DB_____________WB____________
RETURN-AIR TEMPERATURE_____________DB_____________WB____________
COOLING SUPPLY AIR_____________DB_____________WB_ ___________
GAS HEAT SUPPLY AIR_____________DB
PRESSURES
GAS INLET PRESSURE____________IN. WG
GAS MANIFOLD PRESSURE____________IN. WG (LOW FIRE)____________IN. WG (HI FIRE)
REFRIGERANT SUCTION____________PSIG____________TEMP ° F
REFRIGERANT DISCHARGE___ _________PSIG____________TEMP ° F
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION
(580F072 AND 073 ONLY)