SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 580F-36-3II 580F-36-4
580F
Pac
Series
Sizes 036-073
3 to 6 Tons
1/15/04
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation
instructions before installing this unit (Fig. 1A and
1B).
2. Be sure the installation conforms to all applicable local and national codes.
3. These instructions contai n importa nt inform ation for
the proper maintenance and repair of this equipment.
Retain these instructions for futu re use.
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations sh o uld be perfor me d by trai ne d se rvi ce personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing opera tions.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than 1/2 psig. Pressures greater tha n
resulting in hazardous condition. If gas valve is subjected to pressure greater than
replaced before use. When pressure testing fieldsupplied gas piping at pressures of
unit connected to such piping must be isolated by manually closing the gas valve.
WARNING: Before performing service or maintenance operations on unit, turn off main power switch
to unit and install a lockout tag. Electrical shock could
cause personal injury.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply p r ov ided fo r t he unit .
Unit is ship ped in t he ve rti cal d uc t con figu rat ion . To convert t o
horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation-side down.
Seals around duct openings must be tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 3. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. The accessory
thru-the-bottom power and gas connection package must be
installed before the unit is set on the roof curb. If field-
installed (thru-the-roof curb) gas connections are desired, use
factory-supplied
to mount the thru-the-roof curb connection to the roof curb.
Gas connections and power connections to the unit must be
field installed after the unit is installed on the roo f curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory
installation instructions.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 3. Improperly applied gasket can
result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 4. This is necessary for unit drain to function properly.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
1
/2 psig will cause g as valve damage
1
/2 psig, it must be
1
/2 psig or less, a
INSTALLATION
3
/4-in. pipe coupling and gas plate assembly
—2—
Fig. 1A — Base Unit Dimensions — 580F036-072
—3—
Fig. 1B — Base Unit Dimensions — 580F073
Fig. 2 — Horizontal Conversion Panels
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab tha t extends a minimum of 6 in.
beyond unit cabi ne t. I nsta ll a grav el apr on in f ron t of con dens er
coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
C. Alternate Unit Support
A non-combustible sleepe r rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building s tructure on verti cal ducted units. Do not connect ductwork to unit. For h or izontal applications, fiel d-supplie d flanges sh ould b e attach ed
to horizontal duct openings and all ductwork should be
secured to the flanges. Insulate and weatherproof all external ductwork, joints , and roo f openings with counter flashing
and mastic in accordance with applicable codes.
Ducts passing through a n unc ondit i one d spa ce must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return air static shall not exceed –.20 in. wg with
economizer or –.45 in. wg without economizer.
These units are designed for a minimum continuous heating
return-air temperature of 50 F (dry bulb), or an intermittent
operation down to 45 F (dry bulb), such as when used with a
night set-back thermostat.
To operate at lower return-air temperatures, a field-supplied
outdoor air temperature control must be used to initiate both
stages of heat when the temperature is below 45 F. Indoor
comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDENSATE DRAIN
The unit’s
3
/4-in. condensate drain connections are located on
the bottom and side of the unit. Unit discharge connections do
not determine the use of drain connections; eit her drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure
the plug (Red) in the alternate bottom connection is tight
before installing the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory-i nstalle d plug (Re d) from t he bott om connection to the side connection. The center dr ain plug l ooks like
a star connection, however it can be removed with a
1
/2-in.
socket drive. See Fig. 5A. The piping for the condensate drain
and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage.
Install a trap at least 4-in. deep and protect against freeze-up.
If drain line is installed downstream from the external trap,
pitch the li ne away fr om th e unit a t 1 i n. per 10 ft of run . Do
not use a pipe size smaller than the unit connection (
3
/4 in.).
See Fig. 5B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit.
Rollers may be used to move unit across a roof. Level by
using unit frame as a ref erence. See Table 1 and Fi g. 6 for
additional information.
Lifting holes are provided in base rails as shown in Fig. 1A
and 1B. Refer to rigging instructions on unit.
CAUTION: All panels must be in place when rigging.
A. Positioning
Maintain clearan ce around and above un it to provide minimum distance from combustible materials, proper airflow,
and service access. See Fig. 1A a nd 1B. A properly positioned
unit will have the follo wing c l ea ranc es betw een unit a nd r oof
1
curb:
/4-in. clearance between roof curb and base rails on
each side and duct end of unit; 1/4-in. clearance between roof
curb and condenser coil end of unit. (S ee Fig. 3, section C-C.)
—4—
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
AUNIT SIZE
1′-2″
[356]
2′-0″
[610]
580F
036-073
1′-4″
[406]
DALT
DRAIN
HOLE
13/4″
[44.5]
GASPOWERCONTROL
3
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT11/4″ [31.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb, galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01
CRBTMPWR002A011
CRBTMPWR003A01
1′-9
11
[551]
/16″
CRBTMPWR004A01
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for
thru-the-curb type gas. Packages CRBTMPWR003A01 and
4A01 are for thru-the-bottom type gas connections.
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″
[12.7]
NPT
ACCESSORY
POWER
1
/2″
[12.7]
NPT
Fig. 3 — Roof Curb
—5—
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 4 — Unit Leveling Tolerances
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 5A — Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 5B — External Trap Condensate Drain
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contaminated air.
Be sure that unit is installed such that snow will not block
the combustion intake or flue outlet.
Unit may be installed dire ctly on wood flooring or on Class
A, B, or C roof-covering material when roo f curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
Minimum distance between unit and other electrically live
parts is 48 inches.
Flue gas can deteriorate building materials . Orie nt unit suc h
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for
proper operation of this equipment. Be sure that installation
complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), and
ANSI (American National Standards Institute) Z223.1, and
NFPA (National Fire Protectio n Association) 54 TIA-54-84-1.
In Canada, installation must be in accordance with the
CAN1-B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping
materials.
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the basepan beside the
burner compartment access panel. Remove from shipping
location and using screws provided, install flue hood and
screen in location shown in Fig. 7.
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipped for use wi th type of gas shown on nameplate. Refer to local building codes, or in the absence of local
codes, to ANSI Z223.1 entitled National Fuel Gas Code. In
Canada, installation must be in accordance with the
CAN1.B149.1 and CAN1.B149.2 installation codes for gas
burning appliances.
For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is oper atin g. On 580F04 8,0 60,072 high
heat units, the gas pressure at unit gas connection must not
be less than 5 in. wg or greater than 13 in. wg while the unit
is operating. For propane applications, the gas pressure
must not be less than 5 in. wg or greater than 13 in. wg at
the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection. Support gas pipi ng as shown in the ta ble in Fig. 8. For
example, a
3
/4-in. gas pipe must have one field-fabricated
support beam every 8 ft. Therefore, an 18-ft long gas pipe
would have a minimum of 2 support beams, a 48-ft long pipe
would have a minimum of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external
manual main shutoff valve.
CAUTION: When connecting the gas line to the
unit gas valve, the installer MUST use a backup
wrench to prevent valve damage.
—6—
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.”
Holes in base rails are centered around the unit center of gravity. Use
wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
CAUTION: All panels must be in place when rigging.
UNIT 580F
036510231
048520236
060540245
072615279
073665302
MAX WEIGHT“A”“B”“C”
LbKgin.mmin.mmin.mm
Fig. 6 — Rigging Details
73.69187237.5095333.35845
—7—
Tabl e 1 — Physical Data
UNIT SIZE 580F036048060072073
NOMINAL CAPACITY (tons)34566
OPERATING WEIGHT (lb)
*Evaporator coil fin material/condenser coil fin material. Contact your local rep-
resentative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
1
/4...1100
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating
input values as follows:
580FJV036115 — 115,000 Btuh
580FJV048150 — 150,000 Btuh
580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/4...1100
1
/
1
/
5
/
31/
5
/
1
/4...1100
1
31/
/
2
5
/
8
5
/
8
2
5
/
8
2
2
8
2
8
1
/4...1100
5
/
8
——
5
/
8
31/
2
5
/
8
models have combustion products
x
50
1
/4...1100
5
/
8
7
/
8
31/
5
/
8
2
—8—
Table 1 — P hysical Data (cont)
UNIT SIZE 580F036048060072 AND 073
FURNACE SECTION
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating
input values as follows:
580FJV036115 — 115,000 Btuh
580FJV048150 — 150,000 Btuh
580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/
2
1
/
2
models have combustion products
x
1
/
2
—9—
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur.
This ground may consist of electrical wire connected to
unit ground lug in control compartment, or conduit
approved for electrical ground when installed in accordance with NEC (N a tio n al Electrical Code), ANSI/N FPA,
latest edition, and local electrical codes. Do not use gaspiping as an electrical ground. Failure to follow this
warning could result in the installer being liable for p ersonal injury of others.
BLOWER
ACCESS
PANEL
A. Field Power Supply
All units except 208/230-v units are factory wired for the
voltage shown on the na meplate. If the 208/230-v u nit is to
be connected to a 208-v power supply, the transformer must
be rewired by m oving the blac k wire with th e
1
/4-in. female
space connector from the 230-volt connection and moving to
the 208-volt
1
/4-in. male terminal on the primary side of the
transformer.
Refer to unit label diagram for additional information.
Pigtails are provided for fie ld wire connectio ns. Use factorysupplied splices or UL (Underwriters’ Laboratories)
approved copper/aluminum connector.
When installing units, provide a disconnect per the NEC.
All field wiring must comply with NEC and local require-
ments.
Install field wiring as foll ows:
1. Install conduit through side panel openings. Install
conduit between disconnect and control box.
2. Install power lines to terminal connections as shown
in Fig. 9.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate (see
Tables 2A and 2B). On 3-phase units, voltages between
phases must be balanced within 2% and the current within
10%. Use the formula shown in the legend for Tables 2A and
2B, Note 2 to determine the percent of voltage imbalance.
Operation on impr op er lin e volta ge or excess ive phase imbalance constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any applicable
Bryant warranty.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the
accessory. Locate thermostat assembly on a solid wall in the
conditioned space to sense average temperature in accordance with thermostat installation instructions. Connect
thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through connector on unit to
low-voltage connections (shown in Fig. 10).
NOTE: For wire runs up 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
Fig. 7 — Flue Hood Details
LEGEND
NFGC — National Fuel Gas Code
*Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/4or 18
1
1
/4or larger10
X
DIMENSION
(feet)
6
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than n o. 18 AWG cannot be dir ectly con nect ed to
the thermos tat and wi ll req uire a j unction box and s plice a t
the thermostat.
Pass the control wires thro ugh the hole provided i n the corner post; then feed w ires throug h the raceway buil t into the
corner post to the 24-v barri er located on the le ft side of the
control box. See Fig. 11. The raceway provides the UL
required clearance between high-voltage and low-voltage
wiring.
C. Heat Anticipator Settings
Set heat anticipator settings at .14 amp fo r the first stage
and .14 amp for second-stage heating, when available.
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
(CONNECTION
BOARD)
208/230-3-60
575-3-60, 460-3-60
(SIZES 036-060)
RACEWAYLOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
B
A
D
C
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.
Fig. 10 — Low-Voltage Connections
HOLE IN END PANEL (HIDDEN)
Fig. 11 — Field Control Wiring Raceway
—11—
Table 2A — Electrical Data (Without Convenience Outlet)
UNIT
580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
Maximum devia tion is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include
power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
Table 2B — Electrical Data (With Convenience Outlet)
UNIT
580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
Maximum devia tion is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include
power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and
screws. See Fig. 12.
3. Separate hood and screen from basepan by removing
the 4 screws securing them. Save al l screws.
4. Replace evaporator coil access panel.
5. Place hood o n front of outdo or air open ing panel. See
Fig. 13 for hood details. Secure top of hood with the
4 screws removed in Step 3. See Fig. 14.
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
6. Remove and save 6 screws (3 on each side) from sides
of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air da mper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6.
8. Adjust minimum positio n setti ng of the dampe r bla d e
by adjusting the manual outdoor-air adjustment
screws on the front of th e damper bla de. See Fig. 12.
Slide blade vertically until it is in the appropriate position determined by Fig. 15. Tighten screws.
9. Remove and save scr ews currently on sides of hood.
Insert screen. Secure screen to hood using the screws.
See Fig. 14.
Fig. 12 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 14 — Outdoor-Air Damper with
Hood Attached
Fig. 13 — Outdoor-Air Hood Details
Fig. 15 — Outdoor-Air Damper Position Setting
—14—
B. Optional EconoMi$er+
See Fig. 16 for EconoMi$er+ component locations.
NOTE: These instructions are for the factory-installed
optional EconoMi$er+ only. Refer to the accessory
EconoMi$er+ installation instructions when field installing
an EconoMi$er+ accessory.
1. To remove the existing unit filter access panel, raise
the panel and swing the bottom outward. The panel is
now disengaged from the track and can be removed.
See Fig. 17.
2. The box with the EconoMi$er+ hood components is
shipped in the compartment behind the
EconoMi$er+. The EconoMi$er+ does not have to be
removed to retrieve the hood box. Remove the scre w
holding the hood box bracket to the top of the
EconoMi$er+. Slid e the hood box out of the un it. See
Fig. 18.
IMPORTANT: If a power exhaust accessory will b e installed
on the unit, the hood shipped with the unit will not be used
and must be discarded. Save the aluminum filter for use in
the power exhaust.
3. The indoor coil access panel will be used as the top of
the hood. Remove the screws along t he bottom of the
indoor coil access panel. See Fig. 19.
4. Swing out the indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
the screws provided to attach the hoo d sides to the
unit. See Fig. 20.
5. Remove the shipping tape holding the EconoMi$er+
barometric relief damper in place.
6. Insert the hood divider between the hood side s. See
Fig. 20. Secure hood divider with 2 screws on each
hood side. The hood divider is also used as the bottom
filter rack for the aluminum filter.
7. Open the filter clips which are located underneath
the hood top. Insert the aluminum filter into the bottom filter rack (hood divid er). Push the filter into position past the o pen filter clips. Close the filter clips
to lock the filter into place. See Fig. 21.
8. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 19.
9. Replace the filter access panel.
10. Install all EconoMi$er+ accessories. EconoMi$er+
wiring is shown in Fig. 22.
Barometric flow capacity is shown in Fig. 23. Outdoor air
leakage is shown in Fig. 24. Return air pressure drop is
shown in Fig. 25.
1. Terminals 13-17 are wired to 5-pin plug assembly (P/N CRE+PLUG001A00).
2. Pin numbers are not printed on the controller. They are provided in this book as a reference.
LEGEND
Fig. 22 — EconoMi$er+ Wiring
—16—
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
0.05
STATIC PRESSURE (in. wg)
0.15
0.25
Fig. 23 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.2 0 0.22 0.25 0. 30 0.35 0.40 0 .45 0.5 0
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 24 — Outdoor-Air Damper Leakage
6000
5000
4000
3000
2000
1000
0
0.050.100.150.200.250.300.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 25 — Return-Air Pressure Drop
C. EconoMi$er+ Control Mode
Determine the EconoMi$er+ control mode before installing
sensors and accessories. Different sensors are required for
different control modes, and a number of accessories are
available. R efer to Tables 3 and 4.
Outdoor Dry Bulb Changeover
The standard control mode for the EconoMi$er+ is Outdoor
Dry Bulb Changeover. The outdoor air an d supply air temperature sensors are also included as standard.
EconoMi$er+ control is based on the outdoor temperature
relative to a set point in the software. If the outdoor air
temperature is above the set point then the EconoMi$er
should be in minim um position. If the outdoor air tem perature is below the set point, the position should be controlled
to maintain the leaving air temperature set point. The set
point range is 45 to 70 F.
Differential D r y Bulb Changeover
The control supports differential dry bulb changeover con-
trol. This requires an accessory return air temperature
sensor CRTEMPSN001A00 installed in the return airstream. Refer to the Start-up section for details on how to
configure and enable the control mode. The user can check
the operation of the s ensor using the Read function.
Outdoor Air Enthalpy Changeover
The control supports outside air enthalpy changeover con-
trol. This mode requires a factory-supplied outdoor air temperature sensor (OAT) and an accessory outdoor air
humidity sensor (ORH) (part no. CRHUMDSN001B00).
Refer to the Start-Up section for details on how to configure
and enable the contro l mode. The user can check the o peration of the sensors using the Read function.
Differential Ent halpy Changeover
The control supports differential enthalpy changeover con-
trol. This requir es the factory -supplied ou tside air tempera ture sensor, an accessory outdoor air humidity sensor, an
accessory return air temperature sensor, and an accessory
indoor air humidi ty sensor. Refer to the Start-Up section fo r
details on how to configure and enable the control mode. The
user can check the o peration of the sens ors using the Read
function.
D. Damper Movement
When the EconoMi$e r+ board receives initia l power, it will
take the damper up to 2
1
/2 minutes before it begins to position itself. After the initial positioning, subsequent changes
to damper position will take up to 30 seconds to initiate.
Damper movement from full open to full closed (or vice
versa) takes 2
1
/2 minutes.
If the damper is in the process of changing positions (for
example it is trying to open to 100%) and the fan signal is
turned off, the damper will con tinue to its 100% open position before closing.
NOTE: Occupied minimum position can not be set lower than
+1% higher than the value of IAQ minimum economizer
position. Refer to the setup examples on page 42.
E. EconoMi$er+ Controller Wiring
The EconoMi$er+ is sup plied fr om the factory with a supply
air temperature sensor and an outside air temperature sensor. This allows for op eration of the EconoMi$e r+ with outside air dry bulb changeover control. Additional accessories
can be added to allow for different types of change over control and operation of the EconoMi$er+ and unit.
F. T hermostats
The EconoMi$er+ co ntrol works with conventional t hermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1
(heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er+ control does not support sensor thermostats
like the T56 and T57. Connections are made at the thermostat terminal connection board located in the main control
box.
—17—
Table 3 — EconoMi$er+ Sensor Usage
APPLICATION
Standard UnitIncluded — HH79NZ039———
Differential
Dry Bulb
Outdoor Air
Enthalpy
Differential EnthalpyIncluded — HH79NZ039
NOTES:
Sensors (Optional, 5-Pin sensor wiring plug CRE+PLUG001A00 required for installation.).
1. CO
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 — Aspirator box used for duct-mounted CO
33ZCT55CO2 — Space temperature and CO
33ZCT56CO2 — Space temperature and CO2room sensor with override and set point.
CRCBDIOX002A00 — Return air CO
2. All units include the following Standard Sensors:
Outdoor-Air Sensor — set point adjustable from 45 F to 70 F, factory set at 65 F.
Supply-Air Sensor — set point adjustable from 40 F to 65 F. Factory set at 55 F.
All temperature adjustments are made at the EconoMi$er+ controller.
STANDARD OUTDOOR AIR
TEMPERATURE SENSOR
Included — HH79NZ039
Included — HH79NZ039—
room sensor with override.
2
sensor.
2
Table 4 — EconoMi$er+ Field-Installed Accessories
DESCRIPTIONPART NUMBER
3-6 Ton Power Exhaust 208-230 v 1 PhCRPWREXH030A00
3-6 Ton Power Exhaust 460 v 3 PhCRPWREXH021A00
Return Air Temperature Sensor with
Harness
Outdoor Air Humidity Sensor with Harness CRHUMDSN001B00
Indoor Air Humidity Sensor with HarnessCRHUMDSN001B00
Return Air CO
Room Sensor33ZCSENCO2*
CO
2
Aspirator Box for Duct Mount
Sensor
CO
2
Space Temperature and CO
Room Sensor with Override
Space Temperature and CO
Room Sensor with Override
and Set Point
5-Pin Sensor Wiring PlugCRE+PLUG001A00*
*5-pin sensor wiring plug accessory (P/N CRE+PLUG001A00) is
required to install IAQ sensor.
SensorCRCBDIOX002A00*
2
2
2
CRTEMPSN001A00
33ZCASPCO2
33ZCT55CO2*
33ZCT56CO2*
ACCESSORY RETURN AIR
TEMPERATURE SENSOR
Required —
CRTEMPSN001A00
Required —
CRTEMPSN001A00
room sensor.
2
I. Indoor Air Quality (IAQ) Sensor
Any indoor air quality or CO
20 mA output can be used as the IAQ sensor. The controller
will modulate the o utdoor-air damper to pr ovide ventilati on
based on the sensor output and the IAQ setting of the controller . The CO
from the minimum po sition ( IAQ minimum damper po sition
set point) to the maximum position (occupied minimum
damper positi on). When th ere i s no CO
go to the unoccupied minimum position. When there is a CO
call, the damper will be between the IAQ minimum economizer set point position and the occupied minimum damper
position.
Mount the sensor according to manufacturer specifications.
In order to wire this sensor, an accessory 5-pin plug (part
number CRE+PLUG001A00) is required. See Fig. 22.
The IAQ sensor is wired to the g round a nd IAQ w ires in the
harness. The a ccesso r y 5-pin wi ring plug is c onnec ted to pi ns
13-17 of J3 on the EconoMi$er+ controller. Push the plug
ACCESSORY
OUTDOOR AIR
HUMIDITY SENSOR
——
Required —
CRHUMDSN001B00
Required —
CRHUMDSN001B00
sensor that provides a 4 to
2
sensor will mo dul ate th e ou tdoo r -a ir d amper
2
down onto the pin s of the Ec onoMi$er+ con troller to install.
G. Outdoor Air Temperature (OAT) Sensor (Provided)
The outdoor air tem peratur e sens or is a 10K therm isto r used
to measure the o ut door-air temp erat ure. T he se nso r c on tro ls
EconoMi$er+ changeover and compressor lockout. The sensor is factory-installed on the EconoMi$er+ in the outdoor
airstream. The operating range of temperature measurement is 0° to 158 F. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor l ooks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
The user can read the value of the sensor using the Read
mode, described in the Start-Up section.
H. Supply Air Temperature (SAT) Sensor (Provided)
The supply air temperature sensor is a 10K thermistor
located at the inlet to the indoor fan. This sensor must be
field installed . Th e o per ating range of temperature me as ur ement is 0° to 158 F. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor l ooks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
The user can read the value of the sensor using the Read
mode, described in the EconoMi$er+ Controller section.
Pins 13 and 14 are used for the IAQ sensor. Pins 15-17 are
used for the field-installed remote potentiometer. Connect
the IAQ sensor to the BRN and WHT wires o f the accessor y
5-pin plug.
NOTE: Pin numbers are not shown on the controller. They
are provided only as reference for the installer. On the
EconoMi$er+ board, they numbered 1-17 from left to right,
but only the 1 and the 17 are printed on the board.
Sensor wiring should be extended with wire and wire nuts
and routed to the IAQ sensor location. Adjust the IAQ setting at the controller to correspond to the IAQ voltage output
of the sensor at the user-determined set point. See Fig. 26.
Power the sensor with a field-supplied transformer.
J. Return Air Temperature (RAT) Sensor
The EconoMi$er+ controller will accept input from the
accessory 10K return air temperature sensor
(CRTEMPSN001A00) in addition to the outdoor air temperature sensor shipped with the EconoMi$er+. By using both
sensors, the outdoor air and the return air temp eratures are
compared (differential dry bulb) for optimal energy savings.
See Tables 5 and 6 for thermistor resistance and resolution
values.
The temperature sensor looks like an eye let terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
ACCESSORY INDOOR
RETURN AIR
HUMIDITY SENSOR
—
Required —
CRHUMDSN001B00
call, the damper will
2
2
—18—
The user can read the value of the sensor using the Read
mode, described in the EconoMi$er+ Controller section.
Mount the return air temperature sensor on the
EconoMi$er+, through pre-punched holes. See Fig. 27.
The return air temperature (RAT) sensor is provided with a
2-wire, 42-in. long wiring harness with a 2-pin connector. The
plug is installed on pins 5 and 6 on J3 of the EconoMi$er+
controller. The pins are labeled with a ground symbol and
RAT on the EconoMi$er+ controller . See Fig. 22. The red wire
of the harness is connected to pin 5 (ground). The black wire
of the harness is connected to pin 6 (RAT). The wiring harness should be routed from the EconoMi$er+ controller to the
sensor. The controller compares the temperatures of the two
airstreams, chooses the best one, and modulates the
EconoMi$er+ actuator accordingly.
This 10K thermistor is used to measure the return air
temperature vs. resistance cu rve, per Table 5. The range of
temperature measurement is between 0° and 158 F. See
Table 6 for resolution.
K. Outdoor Air Humidity Sensor
The EconoMi $er+ con tro ller accep ts inpu t fro m the acc ess ory
outdoor air humidity sensor in addition to the outdoor air
temperature s en sor s hip pe d w ith th e Eco no M i$ er + . By us ing
both sensors, the total enthalpy of the outside air is
calculated.
Mount the outdoor-air humidity sensor in to the
EconoMi$er+, through the pre-punched holes. See Fig. 28.
The outdoor-air humidity senso r is provided with a 2-wire,
42-in. wiring harness with a 2-pin connector. The plug is
installed on pins 11 and 12 on J3 of the EconoMi$er+ controller. The pins are labeled ORH and VREF on the
EconoMi$er+ controller. See Fig. 22. The orange wire of the
harness is connected to pin 11 (ORH). The blue wire of the
harness is connected to pin 12 (VREF). The wiring harness
should be rout ed fr om the Eco no Mi$er + con tro ller to t he sensor location.
The outdoor enthalpy changeover curve is set at the
EconoMi$er+ controller. The factory default is curve “A.” See
Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
CO SENSOR MAX RANGE SETTING
2
6000
ECONOMI$ER+ CONTROLLER
ACTUATOR
RETURN AIR
TEMP SENSOR
(HIDDEN)
VERTICAL ECONOMI$ER+
(3 TO 12 1/2 TON UNITS)
(SIDE VIEW)
Fig. 27 — Return Air Temperature Sensor
ECONOMI$ER+
ECONOMI$ER+
CONTROLLER
WIRING
GROMMET
OUTDOOR AIR
HUMIDITY
SENSOR
OUTDOOR AIR
TEMPERATURE
SENSOR
HOOD
GROMMET
CURB
INDOOR AIR
HUMIDITY SENSOR
RELIEF
BLADE
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 26 — Indoor Air Quality Voltage Setting
800 ppm
900 ppm
1000 ppm
1100 ppm
Fig. 28 — Outdoor-Air Humidity Sensor
—19—
Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors
(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve