Bryant DuraPac 580f User Manual

installation, start-up and service instructions
Dura
SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 580F-36-3 II 580F-36-4
580F
Pac
Series
Sizes 036-073
3 to 6 Tons
1/15/04
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation instructions before installing this unit (Fig. 1A and 1B).
2. Be sure the installation conforms to all applicable lo­cal and national codes.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-36
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 4
III. Step 3 — Install External Trap for
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
IV. Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 4
V. Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . 6
VI. Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . 6
VII. Step 7 — Make Electrical Connections . . . . . . . . . 10
VIII. Step 8 — Adjust Factory-Installed Options. . . . . . 14
IX. Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . 24
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37-47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47-52
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .53-57
APPENDIX A — ECONOMI$ER+ LABEL . . . . . . . . . . . 58, 59
APPENDIX B — JOB SPECIFIC ECONOMI$ER+
CONFIGURATION SETTINGS . . . . . . . . . . . . . . . . . . . . . 60
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations sh o uld be perfor me d by trai ne d se rvi ce per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing opera tions.
WARNING: Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres­sures greater tha n resulting in hazardous condition. If gas valve is sub­jected to pressure greater than replaced before use. When pressure testing field­supplied gas piping at pressures of unit connected to such piping must be isolated by man­ually closing the gas valve.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install a lockout tag. Electrical shock could cause personal injury.
CAUTION: Ensure voltage listed on unit data plate agrees with electrical supply p r ov ided fo r t he unit .
Unit is ship ped in t he ve rti cal d uc t con figu rat ion . To convert t o horizontal configuration, remove screws from side duct open­ing covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 3. Install insulation, cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. The accessory thru-the-bottom power and gas connection package must be installed before the unit is set on the roof curb. If field-
installed (thru-the-roof curb) gas connections are desired, use factory-supplied to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roo f curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-bottom service con­nections to the basepan in accordance with the accessory installation instructions.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 4. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
1
/2 psig will cause g as valve damage
1
/2 psig, it must be
1
/2 psig or less, a
INSTALLATION
3
/4-in. pipe coupling and gas plate assembly
2
Fig. 1A — Base Unit Dimensions — 580F036-072
3
Fig. 1B — Base Unit Dimensions — 580F073
Fig. 2 — Horizontal Conversion Panels
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab tha t extends a minimum of 6 in. beyond unit cabi ne t. I nsta ll a grav el apr on in f ron t of con dens er coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
C. Alternate Unit Support
A non-combustible sleepe r rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building s tructure on verti ­cal ducted units. Do not connect ductwork to unit. For h or i­zontal applications, fiel d-supplie d flanges sh ould b e attach ed to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all exter­nal ductwork, joints , and roo f openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through a n unc ondit i one d spa ce must be insu­lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli­cable fire codes.
A minimum clearance is not required around ductwork. Cab­inet return air static shall not exceed –.20 in. wg with economizer or –.45 in. wg without economizer.
These units are designed for a minimum continuous heating return-air temperature of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat.
To operate at lower return-air temperatures, a field-supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor comfort may be compromised when these lower air tempera­tures are used with insufficient heating temperature rise.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDEN­SATE DRAIN
The unit’s
3
/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; eit her drain con­nection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-i nstalle d plug (Re d) from t he bott om con­nection to the side connection. The center dr ain plug l ooks like a star connection, however it can be removed with a
1
/2-in. socket drive. See Fig. 5A. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the li ne away fr om th e unit a t 1 i n. per 10 ft of run . Do not use a pipe size smaller than the unit connection (
3
/4 in.).
See Fig. 5B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a ref erence. See Table 1 and Fi g. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 1A and 1B. Refer to rigging instructions on unit.
CAUTION: All panels must be in place when rigging.
A. Positioning
Maintain clearan ce around and above un it to provide mini­mum distance from combustible materials, proper airflow, and service access. See Fig. 1A a nd 1B. A properly positioned unit will have the follo wing c l ea ranc es betw een unit a nd r oof
1
curb:
/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4-in. clearance between roof curb and condenser coil end of unit. (S ee Fig. 3, section C-C.)
4
ROOF CURB ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
A UNIT SIZE
1-2 [356]
2-0 [610]
580F
036-073
1-4 [406]
DALT DRAIN
HOLE
13/4″
[44.5]
GAS POWER CONTROL
3
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT 11/4″ [31.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb, galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01 CRBTMPWR002A01 1 CRBTMPWR003A01
1-9
11
[551]
/16″
CRBTMPWR004A01
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for thru-the-curb type gas. Packages CRBTMPWR003A01 and 4A01 are for thru-the-bottom type gas connections.
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″
[12.7]
NPT
ACCESSORY
POWER
1
/2″
[12.7]
NPT
Fig. 3 — Roof Curb
5
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 4 — Unit Leveling Tolerances
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 5A — Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 5B — External Trap Condensate Drain
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contami­nated air.
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
Unit may be installed dire ctly on wood flooring or on Class A, B, or C roof-covering material when roo f curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
Minimum distance between unit and other electrically live parts is 48 inches.
Flue gas can deteriorate building materials . Orie nt unit suc h that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combus­tion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protectio n Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping materials.
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 7.
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipped for use wi th type of gas shown on name­plate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas con­nection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is oper atin g. On 580F04 8,0 60,072 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connec­tion. Support gas pipi ng as shown in the ta ble in Fig. 8. For example, a
3
/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 2 support beams, a 48-ft long pipe would have a minimum of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external manual main shutoff valve.
CAUTION: When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent valve damage.
6
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
CAUTION: All panels must be in place when rigging.
UNIT 580F
036 510 231 048 520 236 060 540 245 072 615 279 073 665 302
MAX WEIGHT “A” “B” “C” Lb Kg in. mm in. mm in. mm
Fig. 6 — Rigging Details
73.69 1872 37.50 953 33.35 845
7
Tabl e 1 — Physical Data
UNIT SIZE 580F 036 048 060 072 073 NOMINAL CAPACITY (tons) 34566 OPERATING WEIGHT (lb)
Unit
Al/Al* 460 470 490 565 615 Al/Cu* 465 476 497 576 Cu/Cu* 468 482 505 587
Economizer
EconoMi$er+ 50 50 50 50
Roof Curb† 115 115 115 115 115
COMPRESSOR Reciprocating Scroll
Quantity 11111 No. Cylinders (per Circuit) 22222 Oil (oz) 50 50 50 54 60
REFRIGERANT TYPE R-22
Expansion Device Fixed Orifice Metering Device Operating Charge (lb-oz)
Circuit 1 4-4 6-6 6-14 9-0 11-0 Circuit 2 —————
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 1...17 2...17 2...17 2...17 2...17 Tot al F ace Ar ea (sq ft) 8.36 8.36 10.42 10.42 16.5
CONDENSER FAN Propeller Type
Nominal Cfm 3500 4000 4000 4000 4100 Quantity...Diameter (in.) 1...22.0 1...22.0 1...22.0 1...22.0 1...22.0 Motor Hp...Rpm Watts Input (To ta l) 325 325 325 325 320
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Rows...Fins/in. 2...15 2...15 3...15 4...15 4...15 Tot al F ace Ar ea (sq ft) 4.17 5.5 5.5 5.5 5.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 1...10 x 10
Typ e Drive Std Direct Direct Direct Belt Belt
Nominal Cfm 1200 1600 2000 2100 2100 Maximum Continuous BhpStd.34 .75 1.20 2.40 2.40
Motor FrameSizeStd48 48 48 56 56
Nominal Rpm High/Low (Direct Drive) Std 860/800 1075/970 1075/970
Fan Rpm Range Std 1070-1460 1070-1460
Motor Bearing Type Ball Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.8/3.8 2.8/3.8
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std —— —4.54.5
Belt, Quantity...Type...Length(in.) Std 1...A...40 1...A...40
Pulley Center Line Distance (in.) Std 14.7-15.5 14.7-15.5
Speed Change per Full Turn of Std —— — 8080
Movable Pulley Flange (rpm) Alt 48 70 80
MovablePulleyMaximum Full Turns Std ——— 55
From Closed Position Alt 556——
Factory Setting Std ——— 33
Factory Speed Setting (rpm) Std 1226 1226
Fan Shaft Diameter at Pulley (in.)
Alt 1...10 x 10 1...10 x 10 1...10 x 10 High-Static 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 1...10 x 10
Alt Belt Belt Belt High-Static Belt Belt Belt Belt Belt
Alt 1.20 1.20 1.30/2.40** High-Static 2.40 2.40 2.90 2.90 2.90
Alt 48 48 56 High-Static 56 56 56 56 56
Alt ————— High-Static —————
Alt 685-1045 770-1175 8778-1192 High-Static 1075-1455 1075-1455 1300-1685 1300-1685 1300-1685
Alt 1.9/2.9 1.9/2.9 2.4/3.4 High-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/4.4 3.4/4.4
Alt High-Static
Alt 4.5 4.0 4.5 High-Static 4.5 4.5 4.5 4.5 4.5
Alt 1...A...34 1...A...34 1...A...39 High-Static 1...A...39 1...A...39 1...A...40 1...A...40 1...A...40
Alt 10.0-12.4 10.0-12.4 14.7-15.5 High-Static 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 14.7-15.5
High-Static 65 65 60 60 60
High-Static 66555
Alt 333—— High-Static 3
Alt 829 932 1035 High-Static 1233 1233 1416 1416 1416
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local rep-
resentative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
1
/4...1100
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating input values as follows: 580FJV036115 — 115,000 Btuh 580FJV048150 — 150,000 Btuh 580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/4...1100
1
/
1
/
5
/
31/
5
/
1
/4...1100
1
31/
/
2
5
/
8
5
/
8
2
5
/
8
2 2 8
2
8
1
/4...1100
5
/
8
——
5
/
8
31/
2
5
/
8
models have combustion products
x
50
1
/4...1100
5
/
8
7
/
8
31/
5
/
8
2
8
Table 1 — P hysical Data (cont)
UNIT SIZE 580F 036 048 060 072 AND 073 FURNACE SECTION
Rollout Switch Cutout Temp (F)†† 195 195 195 195 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std 074 .113...33 .113...33 .113...33 .113...33
Liquid Propane Alt 074 .089...43 .089...43 .089...43 .089...43
Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1 .14 .14 .14 .14
460 v Stage 1 .14 .14 .14 .14
Gas Input (Btuh) CA High Output 3-Phase Units
Stage 2 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
Standard Units 074 74,000/— 74,000/— 74,000/— 74,000/— (Stage 2/ Stage 1) 115*** 115,000/82,000 115,000/— 115,000/— 115,000/—
Low NOx Units 060N††† 60,000 60,000 60,000
Efficiency (Steady
State)(%) 80 80 80 80
Temperature Rise Range 074 25-55 25-55 25-55 25-55
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5 Gas Valve Quantity 1111 Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5 Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320
LOSS-OF-CHARGE (LOW-PRESSURE SWITCH)(psig)
Cutout 7±3 Reset (Auto.) 22 ± 7
FREEZEPROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable. Screen size and quantity varies with option selected. RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local rep-
resentative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
114/115 .113...33 .113...33 .113...33 .113...33 149/150 .129...30 .129...30 .129...30
060N .102...38 .102...38 .102...38 090N .102...38 .102...38 .102...38 120N .116...32 .116...32
114/115 .089...43 .089...43 .089...43 .089...43 149/150 .104...37 .104...37 .104...37
060N .082...45 .082...45 .082...45 090N .082...45 .082...45 .082...45 120N .094...42 .094...42
114|| 115,000 149|| 150,000 150,000
150*** 150,000/120,000 150,000/120,000 150,000/120,000
090N††† 90,000 90,000 90,000 120N††† 120,000 120,000
114/115 55-85 35-65 35-65 35-65 149/150 50-80 50-80 50-80 060N 20-50 20-50 20-50 090N 30-60 30-60 30-60 120N 40-70 40-70
1
/
2
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating input values as follows: 580FJV036115 — 115,000 Btuh 580FJV048150 — 150,000 Btuh 580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/
2
1
/
2
models have combustion products
x
1
/
2
9
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possi­bility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accor­dance with NEC (N a tio n al Electrical Code), ANSI/N FPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for p er­sonal injury of others.
BLOWER ACCESS PANEL
A. Field Power Supply
All units except 208/230-v units are factory wired for the voltage shown on the na meplate. If the 208/230-v u nit is to be connected to a 208-v power supply, the transformer must be rewired by m oving the blac k wire with th e
1
/4-in. female space connector from the 230-volt connection and moving to the 208-volt
1
/4-in. male terminal on the primary side of the
transformer. Refer to unit label diagram for additional information.
Pigtails are provided for fie ld wire connectio ns. Use factory­supplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.
When installing units, provide a disconnect per the NEC. All field wiring must comply with NEC and local require-
ments. Install field wiring as foll ows:
1. Install conduit through side panel openings. Install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 9.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Tables 2A and 2B). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Tables 2A and 2B, Note 2 to determine the percent of voltage imbalance. Operation on impr op er lin e volta ge or excess ive phase imbal­ance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accor­dance with thermostat installation instructions. Connect thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 10).
NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over
Fig. 7 — Flue Hood Details
LEGEND
NFGC — National Fuel Gas Code
*Field supplied. NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/4or 1 8
1
1
/4or larger 10
X
DIMENSION
(feet)
6
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than n o. 18 AWG cannot be dir ectly con nect ed to the thermos tat and wi ll req uire a j unction box and s plice a t the thermostat.
Pass the control wires thro ugh the hole provided i n the cor­ner post; then feed w ires throug h the raceway buil t into the corner post to the 24-v barri er located on the le ft side of the control box. See Fig. 11. The raceway provides the UL required clearance between high-voltage and low-voltage wiring.
C. Heat Anticipator Settings
Set heat anticipator settings at .14 amp fo r the first stage and .14 amp for second-stage heating, when available.
10
208/230-1-60
208/230-3-60
460-3-60
(SIZES 072 AND 073)
575-3-60
(SIZES 072 AND 073)
LEGEND
C—Contactor COMP — Compressor IFC Indoor-Fan Contactor NEC National Electrical Code TB Terminal Block
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
Fig. 9 — Power Wiring Connections
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
208/230-3-60
575-3-60, 460-3-60
(SIZES 036-060)
RACEWAY LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
THERMOSTAT DIPSWITCH SETTINGS
ON OFF
B
A
D
C
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when con­figured for A/C operation.
Fig. 10 — Low-Voltage Connections
HOLE IN END PANEL (HIDDEN)
Fig. 11 — Field Control Wiring Raceway
11
Table 2A — Electrical Data (Without Convenience Outlet)
UNIT 580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB)457–452= 5v (BC) 464 – 457 = 7v (AC)457–455= 2v
NOMINAL VO LTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
LEGEND
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
TYPE
High 5.2 19.4/19.4 25/25 19/19 109/109
High 2.6 8.9 15 9 57
High 2.6 6.3 15 7 56
High 5.2 25.9/25.9 30/30 25/25 124/124
High 2.6 13.8 20 13 62
High 2.6 9.7 15 10 49
High 7.5 28.9/28.9 35/35 29/29 174/174
High 3.4 13.5 20 13 93
High 3.4 9.9 15 11 76
High 7.5 34.7/34.7 40/40 34/34 205/205
High 3.4 16.2 20 16 103
High 3.4 11.9 15 13 86
High 7.5 34.7/34.7 40/40 34/34 205/205
High 3.4 16.2 20 16 103
High 3.4 11.9 15 13 86
average voltage
452 + 464 + 455
1371
=
= 457
VO LTAGE
IFM
Std
Alt 4.9 26.6/26.6 35/35 26/26 111/111
Std
Alt 4.9 19.1/19.1 25/25 19/19 90/ 90
Std
Alt 2.1 8.4 15 8 48
Std
Alt 2.1 6.0 15 7 37
Std
Alt 4.9 35.4/35.4 45/45 34/34 133/133
Std
Alt 4.9 25.6/25.6 30/30 25/25 105/105
Std
Alt 2.1 13.3 20 13 53
Std
Alt 2.1 9.3 15 10 42
Std
Alt 6.6 44.0/44.0 60/60 42/42 184/184
Std
Alt 5.2 26.6/26.6 35/35 26/26 148/148
Std
Alt 2.6 13.5 20 13 81
Std
Alt 2.6 9.9 15 11 65
Std
Std
Std
Std
Std
Std
3
RANGE
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
187 254 16.2 96.01/41.4
187 254 10.2 75.01/41.4
414 508 4.4 40.01/40.8
518 632 3.7 31.01/40.8
187 254 23.3 118.01/41.4
187 254 15.4 90.01/41.4
414 508 8.3 45.01/40.8
518 632 6.4 36.01/40.8
187 254 28.8 147.01/41.4
187 254 16.0 114.01/41.4
414 508 7.4 64.01/40.8
518 632 6.2 52.01/40.8
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.9
518 632 7.6 58.41/40.6
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.9
518 632 7.6 58.41/40.6
3
COMPR
(ea)
Use
OFM
(ea)
Maximum devia tion is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
COMBUSTION
IFM
3.5
3.5
1.3
1.3
3.5
3.5
1.8
1.8
5.9
5.9
3.1
3.1
5.2
2.6
2.6
5.2
2.6
2.6
FAN MO TOR
FLA
.6
.6
.3
.3
.6
.6
.3
.3
.6
.6
.3
.3
.6
.3
.3
.6
.3
.3
= 1.53%
POWER EXHAUST
PAR T N O.
CRPWREXH030A00 1.6 N/A 0.64 15 CRPWREXH021A00 N/A 0.9 N/A 15 CRPWREXH022A00 3.3 N/A 1.32 15 CRPWREXH023A00 N/A 1.8 N/A 15 CRPWREXH028A00 1.7 N/A 0.68 15 CRPWREXH029A00 N/A 1.0 N/A 15
POWER SUPPLY
25.2/25.2 30/30 24/24 106/106
17.7/17.7 25/25 17/17 85/ 85
7.6 15 7 44
5.5 15 6 35
34.0/34.0 40/40 32/32 129/129
24.2/24.2 30/30 23/23 101/101
13.0 20 13 51
9.2 15 10 41
43.3/43.3 60/60 42/42 161/161
27.3/27.3 35/35 27/27 128/128
13.2 20 13 71
9.7 15 11 58
32.4/32.4 40/40 31/31 180/180
15.4 20 15 90
11.4 15 12 75
32.4/32.4 40/40 31/31 180/180
15.4 20 15 90
11.4 15 12 79
7
457
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
DISCONNECT
SIZE*
(for separate
power source)
MOCP
12
Table 2B — Electrical Data (With Convenience Outlet)
UNIT 580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB)457–452= 5v (BC) 464 – 457 = 7v (AC)457–455= 2v
NOMINAL VO LTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
LEGEND
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
IFM
TYPE
Std
Std
High 5.2 24.2/24.2 30/30 25/25 114/114
Std
High 2.6 11.1 15 11 59
Std
High 2.6 8.0 15 9 58
Std
Std
High 5.2 30.7/30.7 35/35 31/31 129/129
Std
High 2.6 16.0 20 16 64
Std
High 2.6 11.4 15 12 51
Std
Std
High 7.5 33.7/33.7 40/40 34/34 179/179
Std
High 3.4 15.6 20 16 96
Std
High 3.4 11.7 15 13 77
Std
High 7.5 39.5/39.5 45/45 39/39 210/210
Std
High 3.4 18.4 25 18 105
Std
High 3.4 13.7 20 15 90
Std
High 7.5 39.5/39.5 45/45 39/39 210/210
Std
High 3.4 18.4 25 18 105
Std
High 3.4 13.7 20 15 90
average voltage
452 + 464 + 455
1371
=
= 457
VO LTAGE
RANGE
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
187 254 16.2 96.01/41.4
Alt 4.9 32.6/32.6 40/40 31/31 116/116
187 254 10.2 75.01/41.4
Alt 4.9 23.9/23.9 30/30 25/25 95/ 95
414 508 4.4 40.01/40.8
Alt 2.1 10.6 15 11 50
518 632 3.7 31.01/40.8
Alt 2.1 7.7 15 9 39
187 254 23.3 118.01/41.4
Alt 4.9 41.4/41.4 50/50 40/40 138/138
187 254 15.4 90.01/41.4
Alt 4.9 30.4/30.4 35/35 30/30 110/110
414 508 8.3 45.01/40.8
Alt 2.1 15.5 20 15 55
518 632 6.4 36.01/40.8
Alt 2.1 11.1 15 12 44
187 254 28.8 147.01/41.4
Alt 6.6 50.0/50.0 60/60 48/48 188/188
187 254 16.0 114.01/41.4
Alt 5.2 31.4/31.4 40/40 32/32 153/153
414 508 7.4 64.01/40.8
Alt 2.6 15.6 20 15 83
518 632 6.2 52.01/40.8
Alt 2.6 11.7 15 12 67
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.6
518 632 7.6 58.41/40.6
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.6
518 632 7.6 58.41/40.6
3
3
COMPR
(ea)
Use
OFM
(ea)
Maximum devia tion is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
COMBUSTION
IFM
3.5
3.5
1.3
1.3
3.5
3.5
1.8
1.8
5.9
5.9
3.1
3.1
5.2
2.6
2.6
5.2
2.6
2.6
FAN MO TOR
FLA
.6
.6
.3
.3
.6
.6
.3
.3
.6
.6
.3
.3
.6
.3
.3
.6
.3
.3
= 1.53%
POWER EXHAUST
PAR T N O.
CRPWREXH030A00 1.6 N/A 0.64 15 CRPWREXH021A00 N/A 0.9 N/A 15 CRPWREXH022A00 3.3 N/A 1.32 15 CRPWREXH023A00 N/A 1.8 N/A 15 CRPWREXH028A00 1.7 N/A 0.68 15 CRPWREXH029A00 N/A 1.0 N/A 15
POWER SUPPLY
31.2/31.2 35/35 30/30 111/111
22.5/22.5 25/25 23/23 90/ 90
9.8 15 10 47
7.2 15 8 36
40.0/40.0 45/45 38/38 134/134
29.0/29.0 35/35 29/29 106/106
15.2 20 15 53
10.9 15 12 42
49.3/49.3 60/60 47/47 166/166
32.1/32.1 40/40 32/32 133/133
15.3 20 15 74
11.5 15 13 60
37.2/37.2 45/45 37/37 184/184
17.6 20 17 92
13.1 20 14 77
37.2/37.2 45/45 37/37 184/184
17.6 20 17 92
13.1 20 14 77
7
457
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
DISCONNECT
SIZE*
(for separate
power source)
MOCP
13
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS
A. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for build­ing. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws. See Fig. 12.
3. Separate hood and screen from basepan by removing the 4 screws securing them. Save al l screws.
4. Replace evaporator coil access panel.
5. Place hood o n front of outdo or air open ing panel. See Fig. 13 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 14.
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air da mper. See Fig. 13 and 14. Se­cure hood with 6 screws from Step 6.
8. Adjust minimum positio n setti ng of the dampe r bla d e by adjusting the manual outdoor-air adjustment screws on the front of th e damper bla de. See Fig. 12. Slide blade vertically until it is in the appropriate po­sition determined by Fig. 15. Tighten screws.
9. Remove and save scr ews currently on sides of hood. Insert screen. Secure screen to hood using the screws. See Fig. 14.
Fig. 12 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 14 — Outdoor-Air Damper with
Hood Attached
Fig. 13 — Outdoor-Air Hood Details
Fig. 15 — Outdoor-Air Damper Position Setting
14
B. Optional EconoMi$er+
See Fig. 16 for EconoMi$er+ component locations. NOTE: These instructions are for the factory-installed
optional EconoMi$er+ only. Refer to the accessory EconoMi$er+ installation instructions when field installing an EconoMi$er+ accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 17.
2. The box with the EconoMi$er+ hood components is shipped in the compartment behind the EconoMi$er+. The EconoMi$er+ does not have to be removed to retrieve the hood box. Remove the scre w holding the hood box bracket to the top of the EconoMi$er+. Slid e the hood box out of the un it. See Fig. 18.
IMPORTANT: If a power exhaust accessory will b e installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust.
3. The indoor coil access panel will be used as the top of the hood. Remove the screws along t he bottom of the indoor coil access panel. See Fig. 19.
4. Swing out the indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use the screws provided to attach the hoo d sides to the unit. See Fig. 20.
5. Remove the shipping tape holding the EconoMi$er+ barometric relief damper in place.
6. Insert the hood divider between the hood side s. See Fig. 20. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bot­tom filter rack (hood divid er). Push the filter into po­sition past the o pen filter clips. Close the filter clips to lock the filter into place. See Fig. 21.
8. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 19.
9. Replace the filter access panel.
10. Install all EconoMi$er+ accessories. EconoMi$er+ wiring is shown in Fig. 22.
Barometric flow capacity is shown in Fig. 23. Outdoor air leakage is shown in Fig. 24. Return air pressure drop is shown in Fig. 25.
FILTER ACCESS PANEL
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
Fig. 17 — Typical Access Panel Locations
x
o
B
H
d
o
o
HOOD BOX BRACKET
Fig. 18 — Hood Box Removal
ECONOMI$ER+ PLUG
OUTDOOR AIR TEMPERATURE SENSOR
ECONOMI$ER+ CONTROLLER (UNDER COVER)
OUTDOOR AIR HOOD
Fig. 16 — EconoMi$er+ Component Locations
HOOD SHIPPING BRACKET
ECONOMI$ER+ CONTROLLER LABELS
GEAR DRIVEN DAMPER
BAROMETRIC RELIEF DAMPER
15
SIDE PANEL
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
INDOOR COIL ACCESS PANEL
CAULK HERE
Fig. 19 — Indoor Coil Access Panel Relocation
TOP PANEL
INDOOR COIL ACCESS PANEL
17 1/4
LEFT HOOD SIDE
B
19 1/16
HOOD DIVIDER
SCREW
Fig. 20 — Outdoor-Air Hood Construction
33 3/8
BAROMETRIC RELIEF
DIVIDER
OUTSIDE AIR
CLEANABLE ALUMINUM FILTER
FILTER
Fig. 21 — Filter Installation
HOOD
FILTER CLIP
(FIELD-SUPPLIED)
ECON — Economizer OAR H — Outdoor-Air Relative Humidity (Signal) POT — Potentiometer IAQ Indoor-Air Quality (4 to 20 mA) OAT Outdoor-Air Temperature RAT — Return-Air Temperature IARH — Indoor-Air Relative Humidity (Signal) ORH Outdoor-Air Relative Humidity (Sensor) SAT — Supply-Air Temperature IRH Indoor-Air Relative Humidity (Sensor) PL Plug
NOTES:
1. Terminals 13-17 are wired to 5-pin plug assembly (P/N CRE+PLUG001A00).
2. Pin numbers are not printed on the controller. They are provided in this book as a reference.
LEGEND
Fig. 22 — EconoMi$er+ Wiring
16
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
0.05
STATIC PRESSURE (in. wg)
0.15
0.25
Fig. 23 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.2 0 0.22 0.25 0. 30 0.35 0.40 0 .45 0.5 0
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 24 — Outdoor-Air Damper Leakage
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0.20 0.25 0.30 0.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 25 — Return-Air Pressure Drop
C. EconoMi$er+ Control Mode
Determine the EconoMi$er+ control mode before installing sensors and accessories. Different sensors are required for different control modes, and a number of accessories are available. R efer to Tables 3 and 4.
Outdoor Dry Bulb Changeover The standard control mode for the EconoMi$er+ is Outdoor
Dry Bulb Changeover. The outdoor air an d supply air tem­perature sensors are also included as standard. EconoMi$er+ control is based on the outdoor temperature relative to a set point in the software. If the outdoor air
temperature is above the set point then the EconoMi$er should be in minim um position. If the outdoor air tem pera­ture is below the set point, the position should be controlled to maintain the leaving air temperature set point. The set point range is 45 to 70 F.
Differential D r y Bulb Changeover The control supports differential dry bulb changeover con-
trol. This requires an accessory return air temperature sensor CRTEMPSN001A00 installed in the return air­stream. Refer to the Start-up section for details on how to configure and enable the control mode. The user can check the operation of the s ensor using the Read function.
Outdoor Air Enthalpy Changeover The control supports outside air enthalpy changeover con-
trol. This mode requires a factory-supplied outdoor air tem­perature sensor (OAT) and an accessory outdoor air humidity sensor (ORH) (part no. CRHUMDSN001B00). Refer to the Start-Up section for details on how to configure and enable the contro l mode. The user can check the o pera­tion of the sensors using the Read function.
Differential Ent halpy Changeover The control supports differential enthalpy changeover con-
trol. This requir es the factory -supplied ou tside air tempera ­ture sensor, an accessory outdoor air humidity sensor, an accessory return air temperature sensor, and an accessory indoor air humidi ty sensor. Refer to the Start-Up section fo r details on how to configure and enable the control mode. The user can check the o peration of the sens ors using the Read function.
D. Damper Movement
When the EconoMi$e r+ board receives initia l power, it will take the damper up to 2
1
/2 minutes before it begins to posi­tion itself. After the initial positioning, subsequent changes to damper position will take up to 30 seconds to initiate. Damper movement from full open to full closed (or vice versa) takes 2
1
/2 minutes.
If the damper is in the process of changing positions (for example it is trying to open to 100%) and the fan signal is turned off, the damper will con tinue to its 100% open posi­tion before closing.
NOTE: Occupied minimum position can not be set lower than +1% higher than the value of IAQ minimum economizer position. Refer to the setup examples on page 42.
E. EconoMi$er+ Controller Wiring
The EconoMi$er+ is sup plied fr om the factory with a supply air temperature sensor and an outside air temperature sen­sor. This allows for op eration of the EconoMi$e r+ with out­side air dry bulb changeover control. Additional accessories can be added to allow for different types of change over con­trol and operation of the EconoMi$er+ and unit.
F. T hermostats
The EconoMi$er+ co ntrol works with conventional t hermo­stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er+ control does not support sensor thermostats like the T56 and T57. Connections are made at the thermo­stat terminal connection board located in the main control box.
17
Table 3 — EconoMi$er+ Sensor Usage
APPLICATION
Standard Unit Included — HH79NZ039
Differential
Dry Bulb
Outdoor Air
Enthalpy
Differential Enthalpy Included — HH79NZ039
NOTES:
Sensors (Optional, 5-Pin sensor wiring plug CRE+PLUG001A00 required for installation.).
1. CO
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO 33ZCT55CO2 — Space temperature and CO 33ZCT56CO2 — Space temperature and CO2room sensor with override and set point. CRCBDIOX002A00 — Return air CO
2. All units include the following Standard Sensors: Outdoor-Air Sensor — set point adjustable from 45 F to 70 F, factory set at 65 F. Supply-Air Sensor — set point adjustable from 40 F to 65 F. Factory set at 55 F. All temperature adjustments are made at the EconoMi$er+ controller.
STANDARD OUTDOOR AIR
TEMPERATURE SENSOR
Included — HH79NZ039
Included — HH79NZ039
room sensor with override.
2
sensor.
2
Table 4 — EconoMi$er+ Field-Installed Accessories
DESCRIPTION PART NUMBER 3-6 Ton Power Exhaust 208-230 v 1 Ph CRPWREXH030A00 3-6 Ton Power Exhaust 460 v 3 Ph CRPWREXH021A00 Return Air Temperature Sensor with
Harness Outdoor Air Humidity Sensor with Harness CRHUMDSN001B00 Indoor Air Humidity Sensor with Harness CRHUMDSN001B00 Return Air CO
Room Sensor 33ZCSENCO2*
CO
2
Aspirator Box for Duct Mount
Sensor
CO
2
Space Temperature and CO Room Sensor with Override
Space Temperature and CO Room Sensor with Override and Set Point
5-Pin Sensor Wiring Plug CRE+PLUG001A00*
*5-pin sensor wiring plug accessory (P/N CRE+PLUG001A00) is
required to install IAQ sensor.
Sensor CRCBDIOX002A00*
2
2
2
CRTEMPSN001A00
33ZCASPCO2
33ZCT55CO2*
33ZCT56CO2*
ACCESSORY RETURN AIR
TEMPERATURE SENSOR
Required —
CRTEMPSN001A00
Required —
CRTEMPSN001A00
room sensor.
2
I. Indoor Air Quality (IAQ) Sensor
Any indoor air quality or CO 20 mA output can be used as the IAQ sensor. The controller will modulate the o utdoor-air damper to pr ovide ventilati on based on the sensor output and the IAQ setting of the con­troller . The CO from the minimum po sition ( IAQ minimum damper po sition set point) to the maximum position (occupied minimum damper positi on). When th ere i s no CO go to the unoccupied minimum position. When there is a CO call, the damper will be between the IAQ minimum econo­mizer set point position and the occupied minimum damper position.
Mount the sensor according to manufacturer specifications. In order to wire this sensor, an accessory 5-pin plug (part number CRE+PLUG001A00) is required. See Fig. 22.
The IAQ sensor is wired to the g round a nd IAQ w ires in the harness. The a ccesso r y 5-pin wi ring plug is c onnec ted to pi ns 13-17 of J3 on the EconoMi$er+ controller. Push the plug
ACCESSORY
OUTDOOR AIR
HUMIDITY SENSOR
——
Required —
CRHUMDSN001B00
Required —
CRHUMDSN001B00
sensor that provides a 4 to
2
sensor will mo dul ate th e ou tdoo r -a ir d amper
2
down onto the pin s of the Ec onoMi$er+ con troller to install.
G. Outdoor Air Temperature (OAT) Sensor (Provided)
The outdoor air tem peratur e sens or is a 10K therm isto r used to measure the o ut door-air temp erat ure. T he se nso r c on tro ls EconoMi$er+ changeover and compressor lockout. The sen­sor is factory-installed on the EconoMi$er+ in the outdoor airstream. The operating range of temperature measure­ment is 0° to 158 F. See Tables 5 and 6 for thermistor resis­tance and resolution values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
The user can read the value of the sensor using the Read mode, described in the Start-Up section.
H. Supply Air Temperature (SAT) Sensor (Provided)
The supply air temperature sensor is a 10K thermistor located at the inlet to the indoor fan. This sensor must be field installed . Th e o per ating range of temperature me as ur e­ment is 0° to 158 F. See Tables 5 and 6 for thermistor resis­tance and resolution values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
Pins 13 and 14 are used for the IAQ sensor. Pins 15-17 are used for the field-installed remote potentiometer. Connect the IAQ sensor to the BRN and WHT wires o f the accessor y 5-pin plug.
NOTE: Pin numbers are not shown on the controller. They are provided only as reference for the installer. On the EconoMi$er+ board, they numbered 1-17 from left to right, but only the 1 and the 17 are printed on the board.
Sensor wiring should be extended with wire and wire nuts and routed to the IAQ sensor location. Adjust the IAQ set­ting at the controller to correspond to the IAQ voltage output of the sensor at the user-determined set point. See Fig. 26. Power the sensor with a field-supplied transformer.
J. Return Air Temperature (RAT) Sensor
The EconoMi$er+ controller will accept input from the accessory 10K return air temperature sensor (CRTEMPSN001A00) in addition to the outdoor air tempera­ture sensor shipped with the EconoMi$er+. By using both sensors, the outdoor air and the return air temp eratures are compared (differential dry bulb) for optimal energy savings. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor looks like an eye let terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
ACCESSORY INDOOR
RETURN AIR
HUMIDITY SENSOR
Required —
CRHUMDSN001B00
call, the damper will
2
2
18
The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
Mount the return air temperature sensor on the EconoMi$er+, through pre-punched holes. See Fig. 27.
The return air temperature (RAT) sensor is provided with a 2-wire, 42-in. long wiring harness with a 2-pin connector. The plug is installed on pins 5 and 6 on J3 of the EconoMi$er+ controller. The pins are labeled with a ground symbol and RAT on the EconoMi$er+ controller . See Fig. 22. The red wire of the harness is connected to pin 5 (ground). The black wire of the harness is connected to pin 6 (RAT). The wiring har­ness should be routed from the EconoMi$er+ controller to the sensor. The controller compares the temperatures of the two airstreams, chooses the best one, and modulates the EconoMi$er+ actuator accordingly.
This 10K thermistor is used to measure the return air temperature vs. resistance cu rve, per Table 5. The range of temperature measurement is between 0° and 158 F. See Table 6 for resolution.
K. Outdoor Air Humidity Sensor
The EconoMi $er+ con tro ller accep ts inpu t fro m the acc ess ory outdoor air humidity sensor in addition to the outdoor air temperature s en sor s hip pe d w ith th e Eco no M i$ er + . By us ing both sensors, the total enthalpy of the outside air is calculated.
Mount the outdoor-air humidity sensor in to the EconoMi$er+, through the pre-punched holes. See Fig. 28. The outdoor-air humidity senso r is provided with a 2-wire, 42-in. wiring harness with a 2-pin connector. The plug is installed on pins 11 and 12 on J3 of the EconoMi$er+ con­troller. The pins are labeled ORH and VREF on the EconoMi$er+ controller. See Fig. 22. The orange wire of the harness is connected to pin 11 (ORH). The blue wire of the harness is connected to pin 12 (VREF). The wiring harness should be rout ed fr om the Eco no Mi$er + con tro ller to t he sen­sor location.
The outdoor enthalpy changeover curve is set at the EconoMi$er+ controller. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
CO SENSOR MAX RANGE SETTING
2
6000
ECONOMI$ER+ CONTROLLER
ACTUATOR
RETURN AIR
TEMP SENSOR
(HIDDEN)
VERTICAL ECONOMI$ER+
(3 TO 12 1/2 TON UNITS)
(SIDE VIEW)
Fig. 27 — Return Air Temperature Sensor
ECONOMI$ER+
ECONOMI$ER+ CONTROLLER
WIRING GROMMET
OUTDOOR AIR HUMIDITY SENSOR
OUTDOOR AIR TEMPERATURE SENSOR
HOOD
GROMMET
CURB
INDOOR AIR HUMIDITY SENSOR
RELIEF BLADE
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 26 — Indoor Air Quality Voltage Setting
800 ppm 900 ppm 1000 ppm 1100 ppm
Fig. 28 — Outdoor-Air Humidity Sensor
19
Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors
(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve
TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE
CF ohmsCF ohmsCF ohms 120 248.0 390.0 66 150.8 2,011.0 12 53.6 18,090.0 119 246.2 401.2 65 149.0 2,083.0 11 51.8 18,972.0 118 244.4 412.8 64 147.2 2,157.0 10 50.0 19,903.0 117 242.6 424.8 63 145.4 2,235.0 9 48.2 20,883.0 116 240.8 437.2 62 143.6 2,315.0 8 46.4 21,918.0 115 239.0 450.0 61 141.8 2,400.0 7 44.6 23,013.0 114 237.2 462.5 60 140.0 2,488.0 6 42.8 24,117.0 113 235.4 475.5 59 138.2 2,579.0 5 41.0 25,396.0 112 233.6 488.9 58 136.4 2,675.0 4 39.2 26,686.0 111 231.8 502.7 57 134.6 2,774.0 3 37.4 28,052.0 110 230.0 517.0 56 132.8 2,878.0 2 35.6 29,498.0 109 228.2 531.0 55 131.0 2,986.0 1 33.8 31,030.0 108 226.4 545.6 54 129.2 3,099.0 0 32.0 32,654.0 107 224.6 560.5 53 127.4 3,217.0 –1 30.2 34,367.0 106 222.8 576.0 52 125.6 3,340.0 –2 28.4 36,182.0 105 221.0 592.0 51 123.8 3,469.0 –3 26.6 38,109.0 104 219.2 608.5 50 122.0 3,603.0 –4 24.8 40,153.0 103 217.4 625.5 49 120.2 3,743.0 –5 23.0 42,324.0 102 215.6 643.0 48 118.4 3,889.0 –6 21.2 44,617.0 101 213.8 661.2 47 116.6 4,042.0 –7 19.4 47,052.0 100 212.0 680.0 46 114.8 4,203.0 –8 17.6 49,640.0
99 210.2 700.0 45 113.0 4,370.0 –9 15.8 52,392.0 98 208.4 720.6 44 111.2 4,544.0 –10 14.0 55,319.0 97 206.6 742.0 43 109.4 4,727.0 –11 12.2 58,415.0 96 204.8 764.1 42 107.6 4,918.0 –12 10.4 61,711.0 95 203.0 787.0 41 105.8 5,117.0 –13 8.6 65,219.0 94 201.2 810.8 40 104.0 5,327.0 –14 6.8 68,957.0 93 199.4 835.5 39 102.2 5,546.0 –15 5.0 72,940.0 92 197.6 861.0 38 100.4 5,774.0 –16 3.2 77,162.0 91 195.8 888.5 37 98.6 6,014.0 –17 1.4 81,662.0 90 194.0 915.0 36 96.8 6,266.0 –18 –0.4 86,463.0 89 192.2 944.0 35 95.0 6,530.0 –19 –2.2 91,588.0 88 190.4 974.0 34 93.2 6,806.0 –20 –4.0 97,060.0 87 188.6 1005.0 33 91.4 7,096.0 –21 –5.8 102,868.0 86 186.8 1037.0 32 89.6 7,401.0 –22 –7.6 109,075.0 85 185.0 1070.0 31 87.8 7,720.0 –23 –9.4 115,710.0 84 183.2 1104.0 30 86.0 8,056.0 –24 –11.2 122,807.0 83 181.4 1140.0 29 84.2 8,407.0 –25 –13.0 130,402.0 82 179.6 1177.0 28 82.4 8,776.0 –26 –14.8 138,482.0 81 177.8 1215.0 27 80.6 9,164.0 –27 –16.6 147,134.0 80 176.0 1255.0 26 78.8 9,571.0 –28 –18.4 156,404.0 79 174.2 1297.0 25 77.0 10,000.0 –29 –20.2 166,342.0 78 172.4 1340.0 24 75.2 10,449.0 –30 –22.0 177,000.0 77 170.6 1385.0 23 73.4 10,921.0 –31 –23.8 188,340.0 76 168.8 1431.0 22 71.6 11,418.0 –32 –25.6 200,510.0 75 167.0 1480.0 21 69.8 11,942.0 –33 –27.4 213,570.0 74 165.2 1530.0 20 68.0 12,493.0 –34 –29.2 227,610.0 73 163.4 1582.0 19 66.2 13,071.0 –35 –31.0 242,700.0 72 161.6 1637.0 18 64.4 13,681.0 –36 –32.8 258,730.0 71 159.8 1693.0 17 62.6 14,323.0 –37 –34.6 275,970.0 70 158.0 1752.0 16 60.8 15,000.0 –38 –36.4 294,520.0 69 156.2 1813.0 15 59.0 15,714.0 –39 –38.2 314,490.0 68 154.4 1876.0 14 57.2 16,464.0 –40 –40.0 336,000.0 67 152.6 1943.0 13 55.4 17,255.0
Temperature Sensors (CRTEMPSN001A00 or HH79NZ039) —Thermistor Resolution
Table 6 — Outdoor Air, Return Air, and Supply Air
RANGE
Low High
FF F
–41 –18 4.0 –17 14 2.0
15 28 1.0 29 47 0.8 48 86 0.7
87 108 0.8 109 126 1.0 127 171 2.0 127 195 4.0
RESOLUTION
20
Loading...
+ 44 hidden pages