Bryant DuraPac 580f User Manual

installation, start-up and service instructions
Dura
SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 580F-36-3 II 580F-36-4
580F
Pac
Series
Sizes 036-073
3 to 6 Tons
1/15/04
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation instructions before installing this unit (Fig. 1A and 1B).
2. Be sure the installation conforms to all applicable lo­cal and national codes.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-36
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 4
III. Step 3 — Install External Trap for
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
IV. Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 4
V. Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . 6
VI. Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . 6
VII. Step 7 — Make Electrical Connections . . . . . . . . . 10
VIII. Step 8 — Adjust Factory-Installed Options. . . . . . 14
IX. Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . 24
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37-47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47-52
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .53-57
APPENDIX A — ECONOMI$ER+ LABEL . . . . . . . . . . . 58, 59
APPENDIX B — JOB SPECIFIC ECONOMI$ER+
CONFIGURATION SETTINGS . . . . . . . . . . . . . . . . . . . . . 60
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations sh o uld be perfor me d by trai ne d se rvi ce per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing opera tions.
WARNING: Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres­sures greater tha n resulting in hazardous condition. If gas valve is sub­jected to pressure greater than replaced before use. When pressure testing field­supplied gas piping at pressures of unit connected to such piping must be isolated by man­ually closing the gas valve.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install a lockout tag. Electrical shock could cause personal injury.
CAUTION: Ensure voltage listed on unit data plate agrees with electrical supply p r ov ided fo r t he unit .
Unit is ship ped in t he ve rti cal d uc t con figu rat ion . To convert t o horizontal configuration, remove screws from side duct open­ing covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 3. Install insulation, cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. The accessory thru-the-bottom power and gas connection package must be installed before the unit is set on the roof curb. If field-
installed (thru-the-roof curb) gas connections are desired, use factory-supplied to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roo f curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-bottom service con­nections to the basepan in accordance with the accessory installation instructions.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 4. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
1
/2 psig will cause g as valve damage
1
/2 psig, it must be
1
/2 psig or less, a
INSTALLATION
3
/4-in. pipe coupling and gas plate assembly
2
Fig. 1A — Base Unit Dimensions — 580F036-072
3
Fig. 1B — Base Unit Dimensions — 580F073
Fig. 2 — Horizontal Conversion Panels
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab tha t extends a minimum of 6 in. beyond unit cabi ne t. I nsta ll a grav el apr on in f ron t of con dens er coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
C. Alternate Unit Support
A non-combustible sleepe r rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building s tructure on verti ­cal ducted units. Do not connect ductwork to unit. For h or i­zontal applications, fiel d-supplie d flanges sh ould b e attach ed to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all exter­nal ductwork, joints , and roo f openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through a n unc ondit i one d spa ce must be insu­lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli­cable fire codes.
A minimum clearance is not required around ductwork. Cab­inet return air static shall not exceed –.20 in. wg with economizer or –.45 in. wg without economizer.
These units are designed for a minimum continuous heating return-air temperature of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat.
To operate at lower return-air temperatures, a field-supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor comfort may be compromised when these lower air tempera­tures are used with insufficient heating temperature rise.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDEN­SATE DRAIN
The unit’s
3
/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; eit her drain con­nection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-i nstalle d plug (Re d) from t he bott om con­nection to the side connection. The center dr ain plug l ooks like a star connection, however it can be removed with a
1
/2-in. socket drive. See Fig. 5A. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the li ne away fr om th e unit a t 1 i n. per 10 ft of run . Do not use a pipe size smaller than the unit connection (
3
/4 in.).
See Fig. 5B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a ref erence. See Table 1 and Fi g. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 1A and 1B. Refer to rigging instructions on unit.
CAUTION: All panels must be in place when rigging.
A. Positioning
Maintain clearan ce around and above un it to provide mini­mum distance from combustible materials, proper airflow, and service access. See Fig. 1A a nd 1B. A properly positioned unit will have the follo wing c l ea ranc es betw een unit a nd r oof
1
curb:
/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4-in. clearance between roof curb and condenser coil end of unit. (S ee Fig. 3, section C-C.)
4
ROOF CURB ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
A UNIT SIZE
1-2 [356]
2-0 [610]
580F
036-073
1-4 [406]
DALT DRAIN
HOLE
13/4″
[44.5]
GAS POWER CONTROL
3
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT 11/4″ [31.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb, galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01 CRBTMPWR002A01 1 CRBTMPWR003A01
1-9
11
[551]
/16″
CRBTMPWR004A01
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for thru-the-curb type gas. Packages CRBTMPWR003A01 and 4A01 are for thru-the-bottom type gas connections.
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″
[12.7]
NPT
ACCESSORY
POWER
1
/2″
[12.7]
NPT
Fig. 3 — Roof Curb
5
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 4 — Unit Leveling Tolerances
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 5A — Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 5B — External Trap Condensate Drain
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contami­nated air.
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
Unit may be installed dire ctly on wood flooring or on Class A, B, or C roof-covering material when roo f curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
Minimum distance between unit and other electrically live parts is 48 inches.
Flue gas can deteriorate building materials . Orie nt unit suc h that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combus­tion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protectio n Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping materials.
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 7.
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipped for use wi th type of gas shown on name­plate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas con­nection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is oper atin g. On 580F04 8,0 60,072 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connec­tion. Support gas pipi ng as shown in the ta ble in Fig. 8. For example, a
3
/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 2 support beams, a 48-ft long pipe would have a minimum of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external manual main shutoff valve.
CAUTION: When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent valve damage.
6
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
CAUTION: All panels must be in place when rigging.
UNIT 580F
036 510 231 048 520 236 060 540 245 072 615 279 073 665 302
MAX WEIGHT “A” “B” “C” Lb Kg in. mm in. mm in. mm
Fig. 6 — Rigging Details
73.69 1872 37.50 953 33.35 845
7
Tabl e 1 — Physical Data
UNIT SIZE 580F 036 048 060 072 073 NOMINAL CAPACITY (tons) 34566 OPERATING WEIGHT (lb)
Unit
Al/Al* 460 470 490 565 615 Al/Cu* 465 476 497 576 Cu/Cu* 468 482 505 587
Economizer
EconoMi$er+ 50 50 50 50
Roof Curb† 115 115 115 115 115
COMPRESSOR Reciprocating Scroll
Quantity 11111 No. Cylinders (per Circuit) 22222 Oil (oz) 50 50 50 54 60
REFRIGERANT TYPE R-22
Expansion Device Fixed Orifice Metering Device Operating Charge (lb-oz)
Circuit 1 4-4 6-6 6-14 9-0 11-0 Circuit 2 —————
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 1...17 2...17 2...17 2...17 2...17 Tot al F ace Ar ea (sq ft) 8.36 8.36 10.42 10.42 16.5
CONDENSER FAN Propeller Type
Nominal Cfm 3500 4000 4000 4000 4100 Quantity...Diameter (in.) 1...22.0 1...22.0 1...22.0 1...22.0 1...22.0 Motor Hp...Rpm Watts Input (To ta l) 325 325 325 325 320
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Rows...Fins/in. 2...15 2...15 3...15 4...15 4...15 Tot al F ace Ar ea (sq ft) 4.17 5.5 5.5 5.5 5.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 1...10 x 10
Typ e Drive Std Direct Direct Direct Belt Belt
Nominal Cfm 1200 1600 2000 2100 2100 Maximum Continuous BhpStd.34 .75 1.20 2.40 2.40
Motor FrameSizeStd48 48 48 56 56
Nominal Rpm High/Low (Direct Drive) Std 860/800 1075/970 1075/970
Fan Rpm Range Std 1070-1460 1070-1460
Motor Bearing Type Ball Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.8/3.8 2.8/3.8
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std —— —4.54.5
Belt, Quantity...Type...Length(in.) Std 1...A...40 1...A...40
Pulley Center Line Distance (in.) Std 14.7-15.5 14.7-15.5
Speed Change per Full Turn of Std —— — 8080
Movable Pulley Flange (rpm) Alt 48 70 80
MovablePulleyMaximum Full Turns Std ——— 55
From Closed Position Alt 556——
Factory Setting Std ——— 33
Factory Speed Setting (rpm) Std 1226 1226
Fan Shaft Diameter at Pulley (in.)
Alt 1...10 x 10 1...10 x 10 1...10 x 10 High-Static 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 1...10 x 10
Alt Belt Belt Belt High-Static Belt Belt Belt Belt Belt
Alt 1.20 1.20 1.30/2.40** High-Static 2.40 2.40 2.90 2.90 2.90
Alt 48 48 56 High-Static 56 56 56 56 56
Alt ————— High-Static —————
Alt 685-1045 770-1175 8778-1192 High-Static 1075-1455 1075-1455 1300-1685 1300-1685 1300-1685
Alt 1.9/2.9 1.9/2.9 2.4/3.4 High-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/4.4 3.4/4.4
Alt High-Static
Alt 4.5 4.0 4.5 High-Static 4.5 4.5 4.5 4.5 4.5
Alt 1...A...34 1...A...34 1...A...39 High-Static 1...A...39 1...A...39 1...A...40 1...A...40 1...A...40
Alt 10.0-12.4 10.0-12.4 14.7-15.5 High-Static 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 14.7-15.5
High-Static 65 65 60 60 60
High-Static 66555
Alt 333—— High-Static 3
Alt 829 932 1035 High-Static 1233 1233 1416 1416 1416
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local rep-
resentative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
1
/4...1100
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating input values as follows: 580FJV036115 — 115,000 Btuh 580FJV048150 — 150,000 Btuh 580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/4...1100
1
/
1
/
5
/
31/
5
/
1
/4...1100
1
31/
/
2
5
/
8
5
/
8
2
5
/
8
2 2 8
2
8
1
/4...1100
5
/
8
——
5
/
8
31/
2
5
/
8
models have combustion products
x
50
1
/4...1100
5
/
8
7
/
8
31/
5
/
8
2
8
Table 1 — P hysical Data (cont)
UNIT SIZE 580F 036 048 060 072 AND 073 FURNACE SECTION
Rollout Switch Cutout Temp (F)†† 195 195 195 195 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std 074 .113...33 .113...33 .113...33 .113...33
Liquid Propane Alt 074 .089...43 .089...43 .089...43 .089...43
Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1 .14 .14 .14 .14
460 v Stage 1 .14 .14 .14 .14
Gas Input (Btuh) CA High Output 3-Phase Units
Stage 2 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
Standard Units 074 74,000/— 74,000/— 74,000/— 74,000/— (Stage 2/ Stage 1) 115*** 115,000/82,000 115,000/— 115,000/— 115,000/—
Low NOx Units 060N††† 60,000 60,000 60,000
Efficiency (Steady
State)(%) 80 80 80 80
Temperature Rise Range 074 25-55 25-55 25-55 25-55
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5 Gas Valve Quantity 1111 Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5 Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320
LOSS-OF-CHARGE (LOW-PRESSURE SWITCH)(psig)
Cutout 7±3 Reset (Auto.) 22 ± 7
FREEZEPROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable. Screen size and quantity varies with option selected. RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2
LEGEND
Al Aluminum Bhp— Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local rep-
resentative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
114/115 .113...33 .113...33 .113...33 .113...33 149/150 .129...30 .129...30 .129...30
060N .102...38 .102...38 .102...38 090N .102...38 .102...38 .102...38 120N .116...32 .116...32
114/115 .089...43 .089...43 .089...43 .089...43 149/150 .104...37 .104...37 .104...37
060N .082...45 .082...45 .082...45 090N .082...45 .082...45 .082...45 120N .094...42 .094...42
114|| 115,000 149|| 150,000 150,000
150*** 150,000/120,000 150,000/120,000 150,000/120,000
090N††† 90,000 90,000 90,000 120N††† 120,000 120,000
114/115 55-85 35-65 35-65 35-65 149/150 50-80 50-80 50-80 060N 20-50 20-50 20-50 090N 30-60 30-60 30-60 120N 40-70 40-70
1
/
2
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating input values as follows: 580FJV036115 — 115,000 Btuh 580FJV048150 — 150,000 Btuh 580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/
2
1
/
2
models have combustion products
x
1
/
2
9
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possi­bility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accor­dance with NEC (N a tio n al Electrical Code), ANSI/N FPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for p er­sonal injury of others.
BLOWER ACCESS PANEL
A. Field Power Supply
All units except 208/230-v units are factory wired for the voltage shown on the na meplate. If the 208/230-v u nit is to be connected to a 208-v power supply, the transformer must be rewired by m oving the blac k wire with th e
1
/4-in. female space connector from the 230-volt connection and moving to the 208-volt
1
/4-in. male terminal on the primary side of the
transformer. Refer to unit label diagram for additional information.
Pigtails are provided for fie ld wire connectio ns. Use factory­supplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.
When installing units, provide a disconnect per the NEC. All field wiring must comply with NEC and local require-
ments. Install field wiring as foll ows:
1. Install conduit through side panel openings. Install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 9.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Tables 2A and 2B). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Tables 2A and 2B, Note 2 to determine the percent of voltage imbalance. Operation on impr op er lin e volta ge or excess ive phase imbal­ance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accor­dance with thermostat installation instructions. Connect thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 10).
NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over
Fig. 7 — Flue Hood Details
LEGEND
NFGC — National Fuel Gas Code
*Field supplied. NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/4or 1 8
1
1
/4or larger 10
X
DIMENSION
(feet)
6
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than n o. 18 AWG cannot be dir ectly con nect ed to the thermos tat and wi ll req uire a j unction box and s plice a t the thermostat.
Pass the control wires thro ugh the hole provided i n the cor­ner post; then feed w ires throug h the raceway buil t into the corner post to the 24-v barri er located on the le ft side of the control box. See Fig. 11. The raceway provides the UL required clearance between high-voltage and low-voltage wiring.
C. Heat Anticipator Settings
Set heat anticipator settings at .14 amp fo r the first stage and .14 amp for second-stage heating, when available.
10
208/230-1-60
208/230-3-60
460-3-60
(SIZES 072 AND 073)
575-3-60
(SIZES 072 AND 073)
LEGEND
C—Contactor COMP — Compressor IFC Indoor-Fan Contactor NEC National Electrical Code TB Terminal Block
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
Fig. 9 — Power Wiring Connections
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
208/230-3-60
575-3-60, 460-3-60
(SIZES 036-060)
RACEWAY LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
THERMOSTAT DIPSWITCH SETTINGS
ON OFF
B
A
D
C
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when con­figured for A/C operation.
Fig. 10 — Low-Voltage Connections
HOLE IN END PANEL (HIDDEN)
Fig. 11 — Field Control Wiring Raceway
11
Table 2A — Electrical Data (Without Convenience Outlet)
UNIT 580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB)457–452= 5v (BC) 464 – 457 = 7v (AC)457–455= 2v
NOMINAL VO LTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
LEGEND
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
TYPE
High 5.2 19.4/19.4 25/25 19/19 109/109
High 2.6 8.9 15 9 57
High 2.6 6.3 15 7 56
High 5.2 25.9/25.9 30/30 25/25 124/124
High 2.6 13.8 20 13 62
High 2.6 9.7 15 10 49
High 7.5 28.9/28.9 35/35 29/29 174/174
High 3.4 13.5 20 13 93
High 3.4 9.9 15 11 76
High 7.5 34.7/34.7 40/40 34/34 205/205
High 3.4 16.2 20 16 103
High 3.4 11.9 15 13 86
High 7.5 34.7/34.7 40/40 34/34 205/205
High 3.4 16.2 20 16 103
High 3.4 11.9 15 13 86
average voltage
452 + 464 + 455
1371
=
= 457
VO LTAGE
IFM
Std
Alt 4.9 26.6/26.6 35/35 26/26 111/111
Std
Alt 4.9 19.1/19.1 25/25 19/19 90/ 90
Std
Alt 2.1 8.4 15 8 48
Std
Alt 2.1 6.0 15 7 37
Std
Alt 4.9 35.4/35.4 45/45 34/34 133/133
Std
Alt 4.9 25.6/25.6 30/30 25/25 105/105
Std
Alt 2.1 13.3 20 13 53
Std
Alt 2.1 9.3 15 10 42
Std
Alt 6.6 44.0/44.0 60/60 42/42 184/184
Std
Alt 5.2 26.6/26.6 35/35 26/26 148/148
Std
Alt 2.6 13.5 20 13 81
Std
Alt 2.6 9.9 15 11 65
Std
Std
Std
Std
Std
Std
3
RANGE
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
187 254 16.2 96.01/41.4
187 254 10.2 75.01/41.4
414 508 4.4 40.01/40.8
518 632 3.7 31.01/40.8
187 254 23.3 118.01/41.4
187 254 15.4 90.01/41.4
414 508 8.3 45.01/40.8
518 632 6.4 36.01/40.8
187 254 28.8 147.01/41.4
187 254 16.0 114.01/41.4
414 508 7.4 64.01/40.8
518 632 6.2 52.01/40.8
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.9
518 632 7.6 58.41/40.6
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.9
518 632 7.6 58.41/40.6
3
COMPR
(ea)
Use
OFM
(ea)
Maximum devia tion is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
COMBUSTION
IFM
3.5
3.5
1.3
1.3
3.5
3.5
1.8
1.8
5.9
5.9
3.1
3.1
5.2
2.6
2.6
5.2
2.6
2.6
FAN MO TOR
FLA
.6
.6
.3
.3
.6
.6
.3
.3
.6
.6
.3
.3
.6
.3
.3
.6
.3
.3
= 1.53%
POWER EXHAUST
PAR T N O.
CRPWREXH030A00 1.6 N/A 0.64 15 CRPWREXH021A00 N/A 0.9 N/A 15 CRPWREXH022A00 3.3 N/A 1.32 15 CRPWREXH023A00 N/A 1.8 N/A 15 CRPWREXH028A00 1.7 N/A 0.68 15 CRPWREXH029A00 N/A 1.0 N/A 15
POWER SUPPLY
25.2/25.2 30/30 24/24 106/106
17.7/17.7 25/25 17/17 85/ 85
7.6 15 7 44
5.5 15 6 35
34.0/34.0 40/40 32/32 129/129
24.2/24.2 30/30 23/23 101/101
13.0 20 13 51
9.2 15 10 41
43.3/43.3 60/60 42/42 161/161
27.3/27.3 35/35 27/27 128/128
13.2 20 13 71
9.7 15 11 58
32.4/32.4 40/40 31/31 180/180
15.4 20 15 90
11.4 15 12 75
32.4/32.4 40/40 31/31 180/180
15.4 20 15 90
11.4 15 12 79
7
457
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
DISCONNECT
SIZE*
(for separate
power source)
MOCP
12
Table 2B — Electrical Data (With Convenience Outlet)
UNIT 580F
036
(3Tons)
048
(4Tons)
060
(5Tons)
072
(6Tons)
073
(6Tons)
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB)457–452= 5v (BC) 464 – 457 = 7v (AC)457–455= 2v
NOMINAL VO LTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
LEGEND
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
IFM
TYPE
Std
Std
High 5.2 24.2/24.2 30/30 25/25 114/114
Std
High 2.6 11.1 15 11 59
Std
High 2.6 8.0 15 9 58
Std
Std
High 5.2 30.7/30.7 35/35 31/31 129/129
Std
High 2.6 16.0 20 16 64
Std
High 2.6 11.4 15 12 51
Std
Std
High 7.5 33.7/33.7 40/40 34/34 179/179
Std
High 3.4 15.6 20 16 96
Std
High 3.4 11.7 15 13 77
Std
High 7.5 39.5/39.5 45/45 39/39 210/210
Std
High 3.4 18.4 25 18 105
Std
High 3.4 13.7 20 15 90
Std
High 7.5 39.5/39.5 45/45 39/39 210/210
Std
High 3.4 18.4 25 18 105
Std
High 3.4 13.7 20 15 90
average voltage
452 + 464 + 455
1371
=
= 457
VO LTAGE
RANGE
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
187 254 16.2 96.01/41.4
Alt 4.9 32.6/32.6 40/40 31/31 116/116
187 254 10.2 75.01/41.4
Alt 4.9 23.9/23.9 30/30 25/25 95/ 95
414 508 4.4 40.01/40.8
Alt 2.1 10.6 15 11 50
518 632 3.7 31.01/40.8
Alt 2.1 7.7 15 9 39
187 254 23.3 118.01/41.4
Alt 4.9 41.4/41.4 50/50 40/40 138/138
187 254 15.4 90.01/41.4
Alt 4.9 30.4/30.4 35/35 30/30 110/110
414 508 8.3 45.01/40.8
Alt 2.1 15.5 20 15 55
518 632 6.4 36.01/40.8
Alt 2.1 11.1 15 12 44
187 254 28.8 147.01/41.4
Alt 6.6 50.0/50.0 60/60 48/48 188/188
187 254 16.0 114.01/41.4
Alt 5.2 31.4/31.4 40/40 32/32 153/153
414 508 7.4 64.01/40.8
Alt 2.6 15.6 20 15 83
518 632 6.2 52.01/40.8
Alt 2.6 11.7 15 12 67
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.6
518 632 7.6 58.41/40.6
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.6
518 632 7.6 58.41/40.6
3
3
COMPR
(ea)
Use
OFM
(ea)
Maximum devia tion is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
COMBUSTION
IFM
3.5
3.5
1.3
1.3
3.5
3.5
1.8
1.8
5.9
5.9
3.1
3.1
5.2
2.6
2.6
5.2
2.6
2.6
FAN MO TOR
FLA
.6
.6
.3
.3
.6
.6
.3
.3
.6
.6
.3
.3
.6
.3
.3
.6
.3
.3
= 1.53%
POWER EXHAUST
PAR T N O.
CRPWREXH030A00 1.6 N/A 0.64 15 CRPWREXH021A00 N/A 0.9 N/A 15 CRPWREXH022A00 3.3 N/A 1.32 15 CRPWREXH023A00 N/A 1.8 N/A 15 CRPWREXH028A00 1.7 N/A 0.68 15 CRPWREXH029A00 N/A 1.0 N/A 15
POWER SUPPLY
31.2/31.2 35/35 30/30 111/111
22.5/22.5 25/25 23/23 90/ 90
9.8 15 10 47
7.2 15 8 36
40.0/40.0 45/45 38/38 134/134
29.0/29.0 35/35 29/29 106/106
15.2 20 15 53
10.9 15 12 42
49.3/49.3 60/60 47/47 166/166
32.1/32.1 40/40 32/32 133/133
15.3 20 15 74
11.5 15 13 60
37.2/37.2 45/45 37/37 184/184
17.6 20 17 92
13.1 20 14 77
37.2/37.2 45/45 37/37 184/184
17.6 20 17 92
13.1 20 14 77
7
457
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
DISCONNECT
SIZE*
(for separate
power source)
MOCP
13
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS
A. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for build­ing. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws. See Fig. 12.
3. Separate hood and screen from basepan by removing the 4 screws securing them. Save al l screws.
4. Replace evaporator coil access panel.
5. Place hood o n front of outdo or air open ing panel. See Fig. 13 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 14.
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air da mper. See Fig. 13 and 14. Se­cure hood with 6 screws from Step 6.
8. Adjust minimum positio n setti ng of the dampe r bla d e by adjusting the manual outdoor-air adjustment screws on the front of th e damper bla de. See Fig. 12. Slide blade vertically until it is in the appropriate po­sition determined by Fig. 15. Tighten screws.
9. Remove and save scr ews currently on sides of hood. Insert screen. Secure screen to hood using the screws. See Fig. 14.
Fig. 12 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 14 — Outdoor-Air Damper with
Hood Attached
Fig. 13 — Outdoor-Air Hood Details
Fig. 15 — Outdoor-Air Damper Position Setting
14
B. Optional EconoMi$er+
See Fig. 16 for EconoMi$er+ component locations. NOTE: These instructions are for the factory-installed
optional EconoMi$er+ only. Refer to the accessory EconoMi$er+ installation instructions when field installing an EconoMi$er+ accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 17.
2. The box with the EconoMi$er+ hood components is shipped in the compartment behind the EconoMi$er+. The EconoMi$er+ does not have to be removed to retrieve the hood box. Remove the scre w holding the hood box bracket to the top of the EconoMi$er+. Slid e the hood box out of the un it. See Fig. 18.
IMPORTANT: If a power exhaust accessory will b e installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust.
3. The indoor coil access panel will be used as the top of the hood. Remove the screws along t he bottom of the indoor coil access panel. See Fig. 19.
4. Swing out the indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use the screws provided to attach the hoo d sides to the unit. See Fig. 20.
5. Remove the shipping tape holding the EconoMi$er+ barometric relief damper in place.
6. Insert the hood divider between the hood side s. See Fig. 20. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bot­tom filter rack (hood divid er). Push the filter into po­sition past the o pen filter clips. Close the filter clips to lock the filter into place. See Fig. 21.
8. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 19.
9. Replace the filter access panel.
10. Install all EconoMi$er+ accessories. EconoMi$er+ wiring is shown in Fig. 22.
Barometric flow capacity is shown in Fig. 23. Outdoor air leakage is shown in Fig. 24. Return air pressure drop is shown in Fig. 25.
FILTER ACCESS PANEL
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
Fig. 17 — Typical Access Panel Locations
x
o
B
H
d
o
o
HOOD BOX BRACKET
Fig. 18 — Hood Box Removal
ECONOMI$ER+ PLUG
OUTDOOR AIR TEMPERATURE SENSOR
ECONOMI$ER+ CONTROLLER (UNDER COVER)
OUTDOOR AIR HOOD
Fig. 16 — EconoMi$er+ Component Locations
HOOD SHIPPING BRACKET
ECONOMI$ER+ CONTROLLER LABELS
GEAR DRIVEN DAMPER
BAROMETRIC RELIEF DAMPER
15
SIDE PANEL
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
INDOOR COIL ACCESS PANEL
CAULK HERE
Fig. 19 — Indoor Coil Access Panel Relocation
TOP PANEL
INDOOR COIL ACCESS PANEL
17 1/4
LEFT HOOD SIDE
B
19 1/16
HOOD DIVIDER
SCREW
Fig. 20 — Outdoor-Air Hood Construction
33 3/8
BAROMETRIC RELIEF
DIVIDER
OUTSIDE AIR
CLEANABLE ALUMINUM FILTER
FILTER
Fig. 21 — Filter Installation
HOOD
FILTER CLIP
(FIELD-SUPPLIED)
ECON — Economizer OAR H — Outdoor-Air Relative Humidity (Signal) POT — Potentiometer IAQ Indoor-Air Quality (4 to 20 mA) OAT Outdoor-Air Temperature RAT — Return-Air Temperature IARH — Indoor-Air Relative Humidity (Signal) ORH Outdoor-Air Relative Humidity (Sensor) SAT — Supply-Air Temperature IRH Indoor-Air Relative Humidity (Sensor) PL Plug
NOTES:
1. Terminals 13-17 are wired to 5-pin plug assembly (P/N CRE+PLUG001A00).
2. Pin numbers are not printed on the controller. They are provided in this book as a reference.
LEGEND
Fig. 22 — EconoMi$er+ Wiring
16
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
0.05
STATIC PRESSURE (in. wg)
0.15
0.25
Fig. 23 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.2 0 0.22 0.25 0. 30 0.35 0.40 0 .45 0.5 0
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 24 — Outdoor-Air Damper Leakage
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0.20 0.25 0.30 0.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 25 — Return-Air Pressure Drop
C. EconoMi$er+ Control Mode
Determine the EconoMi$er+ control mode before installing sensors and accessories. Different sensors are required for different control modes, and a number of accessories are available. R efer to Tables 3 and 4.
Outdoor Dry Bulb Changeover The standard control mode for the EconoMi$er+ is Outdoor
Dry Bulb Changeover. The outdoor air an d supply air tem­perature sensors are also included as standard. EconoMi$er+ control is based on the outdoor temperature relative to a set point in the software. If the outdoor air
temperature is above the set point then the EconoMi$er should be in minim um position. If the outdoor air tem pera­ture is below the set point, the position should be controlled to maintain the leaving air temperature set point. The set point range is 45 to 70 F.
Differential D r y Bulb Changeover The control supports differential dry bulb changeover con-
trol. This requires an accessory return air temperature sensor CRTEMPSN001A00 installed in the return air­stream. Refer to the Start-up section for details on how to configure and enable the control mode. The user can check the operation of the s ensor using the Read function.
Outdoor Air Enthalpy Changeover The control supports outside air enthalpy changeover con-
trol. This mode requires a factory-supplied outdoor air tem­perature sensor (OAT) and an accessory outdoor air humidity sensor (ORH) (part no. CRHUMDSN001B00). Refer to the Start-Up section for details on how to configure and enable the contro l mode. The user can check the o pera­tion of the sensors using the Read function.
Differential Ent halpy Changeover The control supports differential enthalpy changeover con-
trol. This requir es the factory -supplied ou tside air tempera ­ture sensor, an accessory outdoor air humidity sensor, an accessory return air temperature sensor, and an accessory indoor air humidi ty sensor. Refer to the Start-Up section fo r details on how to configure and enable the control mode. The user can check the o peration of the sens ors using the Read function.
D. Damper Movement
When the EconoMi$e r+ board receives initia l power, it will take the damper up to 2
1
/2 minutes before it begins to posi­tion itself. After the initial positioning, subsequent changes to damper position will take up to 30 seconds to initiate. Damper movement from full open to full closed (or vice versa) takes 2
1
/2 minutes.
If the damper is in the process of changing positions (for example it is trying to open to 100%) and the fan signal is turned off, the damper will con tinue to its 100% open posi­tion before closing.
NOTE: Occupied minimum position can not be set lower than +1% higher than the value of IAQ minimum economizer position. Refer to the setup examples on page 42.
E. EconoMi$er+ Controller Wiring
The EconoMi$er+ is sup plied fr om the factory with a supply air temperature sensor and an outside air temperature sen­sor. This allows for op eration of the EconoMi$e r+ with out­side air dry bulb changeover control. Additional accessories can be added to allow for different types of change over con­trol and operation of the EconoMi$er+ and unit.
F. T hermostats
The EconoMi$er+ co ntrol works with conventional t hermo­stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er+ control does not support sensor thermostats like the T56 and T57. Connections are made at the thermo­stat terminal connection board located in the main control box.
17
Table 3 — EconoMi$er+ Sensor Usage
APPLICATION
Standard Unit Included — HH79NZ039
Differential
Dry Bulb
Outdoor Air
Enthalpy
Differential Enthalpy Included — HH79NZ039
NOTES:
Sensors (Optional, 5-Pin sensor wiring plug CRE+PLUG001A00 required for installation.).
1. CO
2
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 — Aspirator box used for duct-mounted CO 33ZCT55CO2 — Space temperature and CO 33ZCT56CO2 — Space temperature and CO2room sensor with override and set point. CRCBDIOX002A00 — Return air CO
2. All units include the following Standard Sensors: Outdoor-Air Sensor — set point adjustable from 45 F to 70 F, factory set at 65 F. Supply-Air Sensor — set point adjustable from 40 F to 65 F. Factory set at 55 F. All temperature adjustments are made at the EconoMi$er+ controller.
STANDARD OUTDOOR AIR
TEMPERATURE SENSOR
Included — HH79NZ039
Included — HH79NZ039
room sensor with override.
2
sensor.
2
Table 4 — EconoMi$er+ Field-Installed Accessories
DESCRIPTION PART NUMBER 3-6 Ton Power Exhaust 208-230 v 1 Ph CRPWREXH030A00 3-6 Ton Power Exhaust 460 v 3 Ph CRPWREXH021A00 Return Air Temperature Sensor with
Harness Outdoor Air Humidity Sensor with Harness CRHUMDSN001B00 Indoor Air Humidity Sensor with Harness CRHUMDSN001B00 Return Air CO
Room Sensor 33ZCSENCO2*
CO
2
Aspirator Box for Duct Mount
Sensor
CO
2
Space Temperature and CO Room Sensor with Override
Space Temperature and CO Room Sensor with Override and Set Point
5-Pin Sensor Wiring Plug CRE+PLUG001A00*
*5-pin sensor wiring plug accessory (P/N CRE+PLUG001A00) is
required to install IAQ sensor.
Sensor CRCBDIOX002A00*
2
2
2
CRTEMPSN001A00
33ZCASPCO2
33ZCT55CO2*
33ZCT56CO2*
ACCESSORY RETURN AIR
TEMPERATURE SENSOR
Required —
CRTEMPSN001A00
Required —
CRTEMPSN001A00
room sensor.
2
I. Indoor Air Quality (IAQ) Sensor
Any indoor air quality or CO 20 mA output can be used as the IAQ sensor. The controller will modulate the o utdoor-air damper to pr ovide ventilati on based on the sensor output and the IAQ setting of the con­troller . The CO from the minimum po sition ( IAQ minimum damper po sition set point) to the maximum position (occupied minimum damper positi on). When th ere i s no CO go to the unoccupied minimum position. When there is a CO call, the damper will be between the IAQ minimum econo­mizer set point position and the occupied minimum damper position.
Mount the sensor according to manufacturer specifications. In order to wire this sensor, an accessory 5-pin plug (part number CRE+PLUG001A00) is required. See Fig. 22.
The IAQ sensor is wired to the g round a nd IAQ w ires in the harness. The a ccesso r y 5-pin wi ring plug is c onnec ted to pi ns 13-17 of J3 on the EconoMi$er+ controller. Push the plug
ACCESSORY
OUTDOOR AIR
HUMIDITY SENSOR
——
Required —
CRHUMDSN001B00
Required —
CRHUMDSN001B00
sensor that provides a 4 to
2
sensor will mo dul ate th e ou tdoo r -a ir d amper
2
down onto the pin s of the Ec onoMi$er+ con troller to install.
G. Outdoor Air Temperature (OAT) Sensor (Provided)
The outdoor air tem peratur e sens or is a 10K therm isto r used to measure the o ut door-air temp erat ure. T he se nso r c on tro ls EconoMi$er+ changeover and compressor lockout. The sen­sor is factory-installed on the EconoMi$er+ in the outdoor airstream. The operating range of temperature measure­ment is 0° to 158 F. See Tables 5 and 6 for thermistor resis­tance and resolution values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
The user can read the value of the sensor using the Read mode, described in the Start-Up section.
H. Supply Air Temperature (SAT) Sensor (Provided)
The supply air temperature sensor is a 10K thermistor located at the inlet to the indoor fan. This sensor must be field installed . Th e o per ating range of temperature me as ur e­ment is 0° to 158 F. See Tables 5 and 6 for thermistor resis­tance and resolution values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
Pins 13 and 14 are used for the IAQ sensor. Pins 15-17 are used for the field-installed remote potentiometer. Connect the IAQ sensor to the BRN and WHT wires o f the accessor y 5-pin plug.
NOTE: Pin numbers are not shown on the controller. They are provided only as reference for the installer. On the EconoMi$er+ board, they numbered 1-17 from left to right, but only the 1 and the 17 are printed on the board.
Sensor wiring should be extended with wire and wire nuts and routed to the IAQ sensor location. Adjust the IAQ set­ting at the controller to correspond to the IAQ voltage output of the sensor at the user-determined set point. See Fig. 26. Power the sensor with a field-supplied transformer.
J. Return Air Temperature (RAT) Sensor
The EconoMi$er+ controller will accept input from the accessory 10K return air temperature sensor (CRTEMPSN001A00) in addition to the outdoor air tempera­ture sensor shipped with the EconoMi$er+. By using both sensors, the outdoor air and the return air temp eratures are compared (differential dry bulb) for optimal energy savings. See Tables 5 and 6 for thermistor resistance and resolution values.
The temperature sensor looks like an eye let terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
ACCESSORY INDOOR
RETURN AIR
HUMIDITY SENSOR
Required —
CRHUMDSN001B00
call, the damper will
2
2
18
The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
Mount the return air temperature sensor on the EconoMi$er+, through pre-punched holes. See Fig. 27.
The return air temperature (RAT) sensor is provided with a 2-wire, 42-in. long wiring harness with a 2-pin connector. The plug is installed on pins 5 and 6 on J3 of the EconoMi$er+ controller. The pins are labeled with a ground symbol and RAT on the EconoMi$er+ controller . See Fig. 22. The red wire of the harness is connected to pin 5 (ground). The black wire of the harness is connected to pin 6 (RAT). The wiring har­ness should be routed from the EconoMi$er+ controller to the sensor. The controller compares the temperatures of the two airstreams, chooses the best one, and modulates the EconoMi$er+ actuator accordingly.
This 10K thermistor is used to measure the return air temperature vs. resistance cu rve, per Table 5. The range of temperature measurement is between 0° and 158 F. See Table 6 for resolution.
K. Outdoor Air Humidity Sensor
The EconoMi $er+ con tro ller accep ts inpu t fro m the acc ess ory outdoor air humidity sensor in addition to the outdoor air temperature s en sor s hip pe d w ith th e Eco no M i$ er + . By us ing both sensors, the total enthalpy of the outside air is calculated.
Mount the outdoor-air humidity sensor in to the EconoMi$er+, through the pre-punched holes. See Fig. 28. The outdoor-air humidity senso r is provided with a 2-wire, 42-in. wiring harness with a 2-pin connector. The plug is installed on pins 11 and 12 on J3 of the EconoMi$er+ con­troller. The pins are labeled ORH and VREF on the EconoMi$er+ controller. See Fig. 22. The orange wire of the harness is connected to pin 11 (ORH). The blue wire of the harness is connected to pin 12 (VREF). The wiring harness should be rout ed fr om the Eco no Mi$er + con tro ller to t he sen­sor location.
The outdoor enthalpy changeover curve is set at the EconoMi$er+ controller. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
CO SENSOR MAX RANGE SETTING
2
6000
ECONOMI$ER+ CONTROLLER
ACTUATOR
RETURN AIR
TEMP SENSOR
(HIDDEN)
VERTICAL ECONOMI$ER+
(3 TO 12 1/2 TON UNITS)
(SIDE VIEW)
Fig. 27 — Return Air Temperature Sensor
ECONOMI$ER+
ECONOMI$ER+ CONTROLLER
WIRING GROMMET
OUTDOOR AIR HUMIDITY SENSOR
OUTDOOR AIR TEMPERATURE SENSOR
HOOD
GROMMET
CURB
INDOOR AIR HUMIDITY SENSOR
RELIEF BLADE
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 26 — Indoor Air Quality Voltage Setting
800 ppm 900 ppm 1000 ppm 1100 ppm
Fig. 28 — Outdoor-Air Humidity Sensor
19
Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors
(CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve
TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE
CF ohmsCF ohmsCF ohms 120 248.0 390.0 66 150.8 2,011.0 12 53.6 18,090.0 119 246.2 401.2 65 149.0 2,083.0 11 51.8 18,972.0 118 244.4 412.8 64 147.2 2,157.0 10 50.0 19,903.0 117 242.6 424.8 63 145.4 2,235.0 9 48.2 20,883.0 116 240.8 437.2 62 143.6 2,315.0 8 46.4 21,918.0 115 239.0 450.0 61 141.8 2,400.0 7 44.6 23,013.0 114 237.2 462.5 60 140.0 2,488.0 6 42.8 24,117.0 113 235.4 475.5 59 138.2 2,579.0 5 41.0 25,396.0 112 233.6 488.9 58 136.4 2,675.0 4 39.2 26,686.0 111 231.8 502.7 57 134.6 2,774.0 3 37.4 28,052.0 110 230.0 517.0 56 132.8 2,878.0 2 35.6 29,498.0 109 228.2 531.0 55 131.0 2,986.0 1 33.8 31,030.0 108 226.4 545.6 54 129.2 3,099.0 0 32.0 32,654.0 107 224.6 560.5 53 127.4 3,217.0 –1 30.2 34,367.0 106 222.8 576.0 52 125.6 3,340.0 –2 28.4 36,182.0 105 221.0 592.0 51 123.8 3,469.0 –3 26.6 38,109.0 104 219.2 608.5 50 122.0 3,603.0 –4 24.8 40,153.0 103 217.4 625.5 49 120.2 3,743.0 –5 23.0 42,324.0 102 215.6 643.0 48 118.4 3,889.0 –6 21.2 44,617.0 101 213.8 661.2 47 116.6 4,042.0 –7 19.4 47,052.0 100 212.0 680.0 46 114.8 4,203.0 –8 17.6 49,640.0
99 210.2 700.0 45 113.0 4,370.0 –9 15.8 52,392.0 98 208.4 720.6 44 111.2 4,544.0 –10 14.0 55,319.0 97 206.6 742.0 43 109.4 4,727.0 –11 12.2 58,415.0 96 204.8 764.1 42 107.6 4,918.0 –12 10.4 61,711.0 95 203.0 787.0 41 105.8 5,117.0 –13 8.6 65,219.0 94 201.2 810.8 40 104.0 5,327.0 –14 6.8 68,957.0 93 199.4 835.5 39 102.2 5,546.0 –15 5.0 72,940.0 92 197.6 861.0 38 100.4 5,774.0 –16 3.2 77,162.0 91 195.8 888.5 37 98.6 6,014.0 –17 1.4 81,662.0 90 194.0 915.0 36 96.8 6,266.0 –18 –0.4 86,463.0 89 192.2 944.0 35 95.0 6,530.0 –19 –2.2 91,588.0 88 190.4 974.0 34 93.2 6,806.0 –20 –4.0 97,060.0 87 188.6 1005.0 33 91.4 7,096.0 –21 –5.8 102,868.0 86 186.8 1037.0 32 89.6 7,401.0 –22 –7.6 109,075.0 85 185.0 1070.0 31 87.8 7,720.0 –23 –9.4 115,710.0 84 183.2 1104.0 30 86.0 8,056.0 –24 –11.2 122,807.0 83 181.4 1140.0 29 84.2 8,407.0 –25 –13.0 130,402.0 82 179.6 1177.0 28 82.4 8,776.0 –26 –14.8 138,482.0 81 177.8 1215.0 27 80.6 9,164.0 –27 –16.6 147,134.0 80 176.0 1255.0 26 78.8 9,571.0 –28 –18.4 156,404.0 79 174.2 1297.0 25 77.0 10,000.0 –29 –20.2 166,342.0 78 172.4 1340.0 24 75.2 10,449.0 –30 –22.0 177,000.0 77 170.6 1385.0 23 73.4 10,921.0 –31 –23.8 188,340.0 76 168.8 1431.0 22 71.6 11,418.0 –32 –25.6 200,510.0 75 167.0 1480.0 21 69.8 11,942.0 –33 –27.4 213,570.0 74 165.2 1530.0 20 68.0 12,493.0 –34 –29.2 227,610.0 73 163.4 1582.0 19 66.2 13,071.0 –35 –31.0 242,700.0 72 161.6 1637.0 18 64.4 13,681.0 –36 –32.8 258,730.0 71 159.8 1693.0 17 62.6 14,323.0 –37 –34.6 275,970.0 70 158.0 1752.0 16 60.8 15,000.0 –38 –36.4 294,520.0 69 156.2 1813.0 15 59.0 15,714.0 –39 –38.2 314,490.0 68 154.4 1876.0 14 57.2 16,464.0 –40 –40.0 336,000.0 67 152.6 1943.0 13 55.4 17,255.0
Temperature Sensors (CRTEMPSN001A00 or HH79NZ039) —Thermistor Resolution
Table 6 — Outdoor Air, Return Air, and Supply Air
RANGE
Low High
FF F
–41 –18 4.0 –17 14 2.0
15 28 1.0 29 47 0.8 48 86 0.7
87 108 0.8 109 126 1.0 127 171 2.0 127 195 4.0
RESOLUTION
20
Fig. 29 — Enthalpy Changeover Settings
20
18
16
14
12
10
CURRENT IN mA
8
6
4
0102030
RH — Relative Humidity
50
40
HUMIDITY IN % RH
60 70
80
90
Fig. 30 — Humidity Sensor Current vs. Humidity
21
100
RH (%)
10 20 30 40 50 60 70 80 90
CURRENT
(mA)
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
L. Indoor Air Humidity Sensor
For differential enthalpy sensing, the EconoMi$er+ control­ler uses the standard outdoor air temperature sensor, the outdoor air humidity sensor, and the optional indoor air humidity sensor, an optional return air t emperature sensor (RAT). The indoor-air humidity sensor is provided with a 2-wire, 42-in. wiring harness with a 2-pin connector. The plug is installed on pins 8 and 9 on J3 of the EconoMi$er+ controller. The pins are labeled IRH and VREF on the EconoMi$er+ controller. See Fig. 22. The orange wire of the harness is connected to pin 8 (IRH). The blue wire of th e har­ness is connected to pin 9 (VREF). The wiring harness should be extended with wires and wire nuts and routed from the EconoMi$er+ controller to the sensor location. The EconoMi$er+ controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er+ use. The controller selects the lower enthalpy ai r (return or out­door) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er+ control­ler opens the damper to bring in outdoor air for free cooling.
Mount the return-air humidity sensor in the return-air duct. See Fig. 31.
The outdoor enthalpy changeover curve is set with at the EconoMi$er+ controller. The selectable curves are A, B, C, and D. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
M. Occupied/Unoccupied Switch
The EconoMi$er+ supports the use of a field-supplied occupied/unoccupied switch. When the switch is closed it pro­vides a 24-vac signal to the unit for occupied mode and when open, there is no signal to indicate unoccupied mode. The control can be configured to allow different minimum econo­mizer damper positio ns and to control how mechanic al cool­ing will and will not be used in the occupied mode.
NOTE: The remote potentiometer (see below) will override the occupied minimum position if the potentiometer s etting is greater than the occupied minimum position.
A wire from J1-OCC (pin 4) and a wire from J1-24V (pin 5) are wire-nutted together to jumper the terminals.
An occupied/unoccupied switch can be field-installed in place of the jumper to allow the user to force the control into occupied or unoccup ied mode of operation for EconoMi$ er+ damper position. The occupied/unoccupied switch is required if the user wants to use unoccupied free cooling or different EconoMi$er+ d a mp e r vent positions in th e u noc c up ie d m od e.
N. Power Exhaust
Refer to the Accessor y Power Exhaust i nstallation instruc­tions for information on installing the power exhaust accessory.
O. Remote EconoMi$er+ Enable Control
When the control is used with energy ma nagement syst ems that enable and disable the EconoMi$er+, the user can install a field-supplied enable/disable switch. The switch must be wired in series with a 3K ohm, 1 watt or greater resistor. The switch is wired to terminals ORH (pin 11) and VREF (pin 12) on J3. Refer to the Start-Up section for details on how to configure th e control.
P. R e mote Potentiometer Occupied Minimum Position
The occupied minimum position set point remote potentiom­eter (field-sup plied) is used when requ iring additional tem­porary ventilation. The remote potentiometer (10K ohm ­closed damper, 100K ohm - open damper) will only control the occupied minimum position.
ECONOMI$ER+ CONTROLLER
ECONOMI$ER+
GROMMET
RETURN AIR HUMIDITY SENSOR
RETURN DUCT (FIELD-PROVIDED)
Fig. 31 — Return Air Humidity Sensor
The accessory 5-in wiring plug, CRE+PLUG001A00 is required to connect the potentiometer.
The plug is installed on pins 15, 16 and 17 on J3 of the EconoMi$er+ controller. The pins are labeled with the ground symbol, MIN and VREF on the EconoMi$er+ control­ler. See Fig. 22. The pink wire from the harness is connected to pin 15 (ground symbol). The gray wire from the harness is connected to pin 16 (MIN). The yellow wire from the harness is connected to pin 16 (VREF). The wiring harness should be extended with wires and wire nuts and routed from the EconoMi$er+ controller to the remote potentiometer location.
NOTE: Pins 13 (ground symbol) and 14 (IAQ), which are wired to the accessory 5-pin plug, are not used for the remote potentiometer installation. They are used for an accessory IAQ sensor (if required).
The unoccupied minimum position can only be set at the controller. The occupied minimum position set point config­ured at the EconoMi$er+ controller shou ld be set to 0 when using a remote potentiometer. The occupied minimum posi­tion will also be used as part of the IAQ routing; it will be the maximum position the damper moves to when there is an IAQ call.
If the remote potentiometer (occupied) position is greater than the EconoMi$er+ control ler unoccupie d minimum posi­tion, then the remote potentiometer setting will be used. The remote potentiometer is field supplied and must be a 3-wire, linear potentiometer with a resistance between 10K ohm and 100K ohm (such as the Honeywell S963B1128).
Q.Demand Ventilation Control
Demand ventilation control uses an IAQ sensor (CRE+PLUG001A00 required) to control the amount of out­side air admitted into the system. Normally, the minimum position of the EconoMi$er+ damper is established based on the demand occupancy of the space. The IAQ sensor will be used to modulate the EconoMi$er + minimum damper position below the normal minimum position based on full occupancy. The lower limit is called the base ventilat ion r ate . S ee Fig. 32.
If there is no IAQ signal the damper will be in the unoccu­pied minimum position (configuration item number 3). If there is an IAQ signal the damper will be in the occupied
22
minimum position (configuration item number 15), unless the remote potentiometer is used to override it.
For the demand ventilation control logic, the user configures the lower and upper actuator position to esta blish the base ventilation rate (IAQMIN_SP) and the design ventilation rate (ECONOMIN_SP) for full occupancy. When the EconoMi$er+ damper is being modulated for demand venti­lation control, the damper position will be between IAQMIN_SP and ECONOMIN_SP. The upper IAQ differen­tial set point is DAQHI. The lo wer I AQ differ ential set point is DAQLO.
The differential set points represent the differential CO level (in ppm) above the outdoor reference IAQ levels. Normally, the outdoor reference IAQ levels are around 400 ppm, bu t the value should be configured bas ed on the reference levels taken at the job site.
The following equation is used to determine EconoMi$er+ damper position (ECONOMIN_POS):
IAQMIN_SP +=
R. CO
2
The CO
(ECONOMIN_SP – IAQMIN_SP) * (IAQ – OAQ – DAQLO)
(DAQHI – DAQLO)
Sensor Configuration
sensor has preset standard voltage settings that
2
can be selected anytime afte r the sensor is powere d up. See Table 7.
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode 2 times. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See Table 7.
4. Press Enter to lock in the selection.
Press Mode to exi t and resume normal ope ration. The cus­tom settings of the CO
sensor can be changed any time
2
after the sensor is energized. Follow the steps below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode 2 times. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the s election, then press Mode to continue to the next variable.
S. Dehumidification of Fresh Air with Demand Control Ven­tilation (DCV)
Information from ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) indi cates that the largest humidity load on any zone is the fresh air intro­duced. For some applications, a device such as a energy recovery unit is added to reduce the moist ure content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling pro­cesses are more than adequate to remove the humidity loads for most commercial applications.
This makes the control of the dehumidification device simple
2
when using the enthalpy or differential enthalpy sens or. The enthalpy sensor or diffe rential enthalpy sensor is installed on the equipment to determine economizer operation. The high enthalpy signal from the temperature and humidity sensors or differential temperature and humidity sensors can be used to turn on the outdoor air moisture removal device any time fresh air is required for the space.
The energy recovery device should be sized for maximum latent and sensible conditioning at maximum ventilation on a design day.
A calculation for leaving-air temperature on a low ambient, low ventilation day should also be done to determine the supply-air temperature of the return and pre-conditioned outside air. The design should produce air temperature somewhat near room conditions to prevent reheat of the air mixture. The energy recovery device should be interlocked with the heat to turn off the device when in the heat mode.
DAMPER POSTION
FULL OCCUPANCY
ECONOMIZER MINIMUM OCCUPIED DAMPER POSITION (ECONOMIN_SP)
IAQ MINIMUM ECONOMIZER POSITION SET POINT (IAQMIN_SP)
OUTDOOR REFERENCE LEVEL (OAQ)= 400
VENTILATION RATE
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
100 500
AQ DIFFERENTIAL LOW (DAQLO)
AQ DIFFERENTIAL HIGH (DAQHI)
INSIDE/OUTSIDE CO
700
1100
INSIDE CO
CONCENTRATION
2
Fig. 32 — Demand Ventilation Control
CO LEVEL
2
DIFFERENTIAL
2
Tab le 7 — CO
SETTING EQUIPMENT OUTPUT
1
Interface with Standard
2 Proportional Any 7-20 mA 0-2000 1000 50
Building Control System
3 Exponential Any 4-20 mA 0-2000 1100 50 4 5 Proportional 20 4-20 mA 0- 900 900 50
Economizer
6 Exponential 15 4-20 mA 0-1100 1100 50 7 Exponential 20 4-20 mA 0- 900 900 50 8 Health & Safety Proportional 4-20 mA 0-9999 5000 500 9 Parking/Air Intakes/ Loading Docks Proportional 4-20 mA 0-2000 700 50
LEGEND
ppm — Parts Per Million
*Available sensor part numbers are listed in Table 4.
Proportional Any 4-20 mA 0-2000 1000 50
Proportional 15 4-20 mA 0-1100 1100 50
Sensor* Standard Settings
2
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO
CONTROL
2
RANGE (ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
23
RELAY
HYSTERESIS
(ppm)
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
Adjust evaporator-fan rpm to meet jobsite conditions. Table 8 shows fan rpm at motor pulley set tings. T abl e 9 sho ws motor performance. Refer to Tables 10-33 to determine fan speed settings.
A. Direct-Drive Motors
The evaporator-fan motor factory speed setting is shown on label diagram affixed to base unit. If other than factory set­ting is desired, refer to label diagram for motor reconnection. See Fig. 33 for direct drive motor location.
B. Belt-Drive Motors
Fan motor pulleys are factory set for speed shown in Table 1. See Fig. 34 for belt drive motor location.
NOTE: Before adjusting fan speed, make sure the new fan speed will provi de an air temperature rise range as show n in Table 1.
To change fan speed:
1. Shut off unit power supply and tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts. See Fig. 34.
3. Loosen movable pulley flange setscrew (see Fig. 35).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed incr eases lo ad on motor. Do not exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide m otor mounti ng plate away fr om fan scroll for proper belt tension (
1
/2-in. deflection with 8 to 10 lb of
force).
3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed position.
Fig. 33 — Direct-Drive Motor Mounting
MOTOR MOUNTING PLATE NUTS
Fig. 34 — Belt Drive Motor Mounting
24
Fig. 35 — Evaporator-Fan Pulley Adjustment
Tabl e 8 — Fan Rpm at Motor Pulley Settings*
UNIT 580F
0
036† 1045 1009 973 937 901 865 829 793 757 721 685
1
/
2
11
1
/
2
036** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 048† 1175 1135 1094 1054 1013 973 932 892 851 811 770 048** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 060† 1192 1166 1140 1114 1087 1061 1035 1009 983 957 930 904 878 060** 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300 072, 073†† 1460 1421 1382 1343 1304 1265 1226 1187 1148 1109 1070 072, 073** 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300
*Approximate fan rpm shown.
†Indicates alternate motor and drive package.
MOTOR PULLEY TURNS OPEN
22
1
/
33
2
**Indicates high-static motor and drive package.
††Indicates standard motor and drive package.
1
/
2
44
1
/
2
55
Table 9 — Motor Data
UNIT
580F
036
048
060
072, 073
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horse-
power range of the motors can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in nui­sance tripping or premature motor failure. Unit warranty will not be affected.
†Single phase/three-phase.
EVAPORATOR-FAN
MOTOR
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
High Static
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
208/230
460 1.3
0.34 440
575 1.3
208/230
460 2.1
1.20 1000
575 2.1
208/230
460 3.0
2.40 2120
575 3.0
208/230
460 1.8
0.75 850
575 1.8
208/230
460 2.1
1.20 1000
575 2.1
208/230
460 3.0
2.40 2120
575 3.0
208/230
460 3.2
1.20 1340
575 3.2
208/230
460 3.0
1.30/2.40† 2120
575 3.0
208/230
460 3.9
2.90 2562
575 3.9
208/230
460 3.0
2.40 2120
575 3.0
208/230
460 3.9
2.90 2562
575 3.9
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require­ments as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
2. High-static motor not available on single-phase units.
1
/
2
MAXIMUM
AMP DRAW
2.8
4.9
6.0
3.5
4.9
6.0
5.9
10.1/6.7†
8.6
6.7
8.6
6
Table10—FanPerformance 580F036 — Vertical Discharge Units, Standard Motor
Airflow
(Cfm)
900 0.49 0.21 253 0.50 0.23 277 0.51 0.26 307 0.55 0.31 363 1000 0.42 0.23 270 0.43 0.25 292 0.43 0.27 321 0.51 0.32 374 1100 0.37 0.24 287 0.38 0.26 307 0.39 0.28 335 0.46 0.33 385 1200 0.33 0.26 304 0.33 0.27 323 0.34 0.29 349 0.40 0.34 397 1300 0.27 0.27 321 0.28 0.29 338 0.28 0.31 364 0.34 0.34 408 1400 0.20 0.29 338 0.23 0.30 354 0.25 0.32 378 1500 0.16 0.30 355 0.18 0.31 369 0.20 0.33 392
ESP Bhp Watts ESP BhpWattsESP Bhp Watts ESP BhpWatts
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
LEGEND See page 36 for general fan performance notes.
Bhp—Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
STANDARD MOTOR (DIRECT DRIVE)
25
Table11—FanPerformance 580F036 — Vertical Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 643 0.15 152 768 0.22 222 870 0.30 296 958 0.37 373 1037 0.46 454 1000 683 0.19 191 804 0.27 268 904 0.35 348 991 0.43 430 1069 0.52 517 1100 725 0.24 237 842 0.32 321 939 0.41 407 1025 0.50 496 1102 0.59 588 1200 767 0.29 291 880 0.38 382 976 0.48 474 1060 0.57 570 1136 0.67 668 1300 811 0.35 352 920 0.45 451 1013 0.55 550 1095 0.66 652 1170 0.76 756 1400 855 0.43 423 960 0.53 529 1051 0.64 636 1132 0.75 744 1205 0.86 855 1500 900 0.51 504 1002 0.62 617 1090 0.74 731 1169 0.85 846 1242 0.97 963
AIRFLOW
(Cfm)
900 1110 0.54 538 1177 0.63 627 1239 0.72 718 1298 0.82 813 1355 0.92 911 1000 1141 0.61 607 1207 0.70 700 1269 0.80 796 1328 0.90 895 1384 1.00 998 1100 1173 0.69 683 1238 0.79 781 1300 0.89 883 1358 0.99 987 1414 1.10 1094 1200 1205 0.77 768 1270 0.88 872 1332 0.98 979 1389 1.09 1088 —— — 1300 1239 0.87 863 1303 0.98 972 1364 1.09 1084 —— — —— — 1400 1273 0.97 967 1337 1.09 1082 —— — —— — —— — 1500 1309 1.09 1082 —— — —— — —— — —— —
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 1045 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWatts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm BhpWatts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 36 for general fan performance notes.
Table12—FanPerformance 580F036 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 643 0.15 152 768 0.22 222 870 0.30 296 958 0.37 373 1037 0.46 454 1000 683 0.19 191 804 0.27 268 904 0.35 348 991 0.43 430 1069 0.52 517 1100 725 0.24 237 842 0.32 321 939 0.41 407 1025 0.50 496 1102 0.59 588 1200 767 0.29 291 880 0.38 382 976 0.48 474 1060 0.57 570 1136 0.67 668 1300 811 0.35 352 920 0.45 451 1013 0.55 550 1095 0.66 652 1170 0.76 756 1400 855 0.43 423 960 0.53 529 1051 0.64 636 1132 0.75 744 1205 0.86 855 1500 900 0.51 504 1002 0.62 617 1090 0.74 731 1169 0.85 846 1242 0.97 963
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
900 1110 0.54 538 1177 0.63 627 1239 0.72 718 1298 0.82 813 1355 0.92 911 1000 1141 0.61 607 1207 0.70 700 1269 0.80 796 1328 0.90 895 1384 1.00 998 1100 1173 0.69 683 1238 0.79 781 1300 0.89 883 1358 0.99 987 1414 1.10 1094 1200 1205 0.77 768 1270 0.88 872 1332 0.98 979 1389 1.09 1088 1444 1.21 1200 1300 1239 0.87 863 1303 0.98 972 1364 1.09 1084 1421 1.21 1199 1475 1.32 1316 1400 1273 0.97 967 1337 1.09 1082 1397 1.21 1200 1453 1.33 1320 1507 1.45 1443 1500 1309 1.09 1082 1371 1.21 1204 1430 1.33 1327 1486 1.46 1453 1540 1.59 1581
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. Seee page 36 for general fan performance notes.
Table13—FanPerformance 580F048 — Vertical Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1200 0.68 0.41 458 0.74 0.45 506 0.74 0.51 572 0.85 0.56 632 1300 0.61 0.42 471 0.67 0.46 521 0.66 0.52 589 0.78 0.58 651 1400 0.53 0.45 503 0.59 0.49 556 0.59 0.54 616 0.70 0.60 681 1500 0.45 0.47 536 0.51 0.52 593 0.52 0.56 631 0.63 0.62 698 1600 0.36 0.49 557 0.42 0.54 616 0.45 0.58 654 0.56 0.64 723 1700 0.26 0.52 584 0.32 0.57 646 0.37 0.60 678 0.48 0.66 750 1800 0.15 0.54 610 0.22 0.60 674 0.30 0.62 698 0.41 0.68 772 1900 0.04 0.56 629 0.11 0.62 696 0.23 0.64 720 0.34 0.70 796 2000 0.16 0.66 744 0.26 0.73 823
Bhp—Brake Horsepower Input to Fan ESP External Static Pressure (in. wg)
ESP BhpWattsESP Bhp Watts ESP Bhp Watts ESP BhpWatts
LEGEND See page 36 for general fan performance notes.
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
26
Table14—FanPerformance 580F048 — Vertical Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 2000 962 0.85 847 1049 1.05 1043
AIRFLOW
(Cfm)
1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 —— — 1400 1147 0.98 972 1208 1.09 1086 —— — —— — —— — 1500 1175 1.09 1086 1600 ——— ——— ——— ——— ——— 1700 ——— ——— ——— ——— ——— 1800 ——— ——— ——— ——— ——— 1900 ——— ——— ——— ——— ——— 2000 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 770 to 1175 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 36 for general fan performance notes.
Table15—FanPerformance 580F048 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 1200 1.32 1316 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 1165 1.29 1283 1231 1.46 1453 2000 962 0.85 847 1049 1.05 1043 1127 1.24 1233 1198 1.42 1417 1263 1.61 1598
AIRFLOW
(Cfm)
1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 1346 1.28 1275 1400 1147 0.98 972 1208 1.09 1086 1265 1.21 1199 1320 1.32 1310 1371 1.43 1419 1500 1175 1.09 1086 1235 1.22 1209 1292 1.34 1332 1346 1.46 1452 1397 1.58 1572 1600 1204 1.21 1207 1263 1.35 1340 1320 1.48 1472 1373 1.61 1603 1424 1.74 1732 1700 1233 1.34 1336 1292 1.49 1480 1348 1.63 1622 1401 1.77 1762 1451 1.91 1901 1800 1262 1.48 1473 1321 1.64 1627 1376 1.79 1779 1428 1.94 1930 1479 2.09 2078 1900 1293 1.63 1620 1350 1.79 1784 1405 1.96 1946 1457 2.12 2106 1506 2.28 2265 2000 1323 1.79 1776 1380 1.96 1950 1434 2.13 2123 1486 2.31 2293 —— —
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.
27
Table16—FanPerformance 580F060 — Vertical Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1500 0.69 0.67 750 1.01 0.71 791 1.00 0.70 782 1.20 0.76 845 1.22 0.79 875 1.28 0.85 949 1600 0.49 0.70 780 0.85 0.74 824 0.85 0.74 821 1.06 0.79 883 1.09 0.82 913 1.17 0.89 988 1700 0.29 0.73 810 0.70 0.77 857 0.70 0.77 861 0.93 0.83 921 0.97 0.85 950 1.06 0.92 1027 1800 0.09 0.75 839 0.54 0.80 891 0.55 0.81 900 0.80 0.86 959 0.84 0.89 988 0.95 0.96 1066 1900 0.39 0.83 924 0.40 0.84 940 0.67 0.90 997 0.72 0.92 1025 0.84 0.99 1105 2000 0.23 0.86 957 0.25 0.88 979 0.54 0.93 1035 0.59 0.95 1063 0.73 1.03 1144 2100 0.08 0.89 990 0.10 0.91 1018 0.41 0.96 1073 0.46 0.99 1101 0.62 1.06 1183 2200 0.28 1.00 1111 0.34 1.02 1138 0.51 1.10 1222 2300 0.15 1.03 1149 0.21 1.06 1176 0.40 1.13 1261 2400 0.02 1.07 1187 0.09 1.09 1213 0.29 1.17 1300 2500 0.18 1.20 1340
Bhp—Brake Horsepower Input to Fan ESP External Static Pressure (in. wg)
208 V 230,460,575 V 208 V 230,460,575 V 208 V 230,460,575 V
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP BhpWattsESP Bhp Watts
LEGEND See page 36 for general fan performance notes.
Low Speed Medium Speed High Speed
Tabl e 1 7 — Fan Performance 580F060 — Single-Phase, Vertical Discharge Unit,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 —— — 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 2100 1035 0.98 869 1127 1.15 1021 2200 1075 1.11 984 1164 1.29 1141 2300 1115 1.25 1110 2400 ——— ——— ——— ——— ——— 2500 ——— ——— ——— ——— ———
AIRFLOW
(Cfm)
1500 1232 1.25 1109 —— — —— — —— — —— — 1600 ——— ——— ——— ——— ——— 1700 ——— ——— ——— ——— ——— 1800 ——— ——— ——— ——— ——— 1900 ——— ——— ——— ——— ——— 2000 ——— ——— ——— ——— ——— 2100 ——— ——— ——— ——— ——— 2200 ——— ——— ——— ——— ——— 2300 ——— ——— ——— ——— ——— 2400 ——— ——— ——— ——— ——— 2500 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See page 36 for general fan performance notes.
28
Table18—FanPerformance 580F060 — Three-Phase, Vertical Discharge Units,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1255 1.35 1197 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 1287 1.47 1302 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 1249 1.39 1236 1319 1.59 1416 2100 1035 0.98 869 1127 1.15 1021 1209 1.33 1183 1283 1.53 1357 1351 1.74 1541 2200 1075 1.11 984 1164 1.29 1141 1244 1.47 1309 1317 1.68 1488 1385 1.89 1676 2300 1115 1.25 1110 1202 1.43 1273 1280 1.63 1446 1352 1.83 1629 1418 2.05 1822 2400 1155 1.40 1246 1240 1.59 1415 1316 1.79 1594 1387 2.01 1782 1452 2.23 1980 2500 1196 1.57 1394 1278 1.77 1569 1353 1.97 1753 1422 2.19 1946 —— —
AIRFLOW
(Cfm)
1500 1232 1.25 1109 1297 1.46 1295 1357 1.68 1492 1415 1.91 1700 1469 2.16 1917 1600 1262 1.34 1190 1325 1.55 1379 1385 1.78 1579 1442 2.01 1788 1496 2.26 2009 1700 1291 1.44 1281 1354 1.66 1472 1414 1.89 1674 1470 2.12 1887 1524 2.37 2109 1800 1322 1.55 1380 1384 1.77 1575 1443 2.00 1779 1499 2.25 1994 —— — 1900 1352 1.68 1489 1414 1.90 1687 1472 2.13 1894 1528 2.38 2112 —— — 2000 1384 1.81 1607 1445 2.04 1808 1502 2.27 2019 —— — —— — 2100 1415 1.95 1736 1476 2.18 1940 —— — —— — —— — 2200 1448 2.11 1875 1507 2.35 2083 —— — —— — —— — 2300 1480 2.28 2025 —— — —— — —— — —— — 2400 ——— ——— ——— ——— ——— 2500 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.
Table19—FanPerformance 580F060 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1255 1.35 1197 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 1287 1.47 1302 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 1249 1.39 1236 1319 1.59 1416 2100 1035 0.98 869 1127 1.15 1021 1209 1.33 1183 1283 1.53 1357 1351 1.74 1541 2200 1075 1.11 984 1164 1.29 1141 1244 1.47 1309 1317 1.68 1488 1385 1.89 1676 2300 1115 1.25 1110 1202 1.43 1273 1280 1.63 1446 1352 1.83 1629 1418 2.05 1822 2400 1155 1.40 1246 1240 1.59 1415 1316 1.79 1594 1387 2.01 1782 1452 2.23 1980 2500 1196 1.57 1394 1278 1.77 1569 1353 1.97 1753 1422 2.19 1946 1486 2.42 2149
AIRFLOW
(Cfm)
1500 1232 1.25 1109 1297 1.46 1295 1357 1.68 1492 1415 1.91 1700 1469 2.16 1917 1600 1262 1.34 1190 1325 1.55 1379 1385 1.78 1579 1442 2.01 1788 1496 2.26 2009 1700 1291 1.44 1281 1354 1.66 1472 1414 1.89 1674 1470 2.12 1887 1524 2.37 2109 1800 1322 1.55 1380 1384 1.77 1575 1443 2.00 1779 1499 2.25 1994 1552 2.50 2219 1900 1352 1.68 1489 1414 1.90 1687 1472 2.13 1894 1528 2.38 2112 1580 2.63 2339 2000 1384 1.81 1607 1445 2.04 1808 1502 2.27 2019 1557 2.52 2240 1609 2.78 2470 2100 1415 1.95 1736 1476 2.18 1940 1533 2.43 2155 1587 2.68 2378 2200 1448 2.11 1875 1507 2.35 2083 1563 2.59 2301 1617 2.85 2528 2300 1480 2.28 2025 1539 2.52 2237 1595 2.77 2459 2400 1513 2.46 2187 1571 2.71 2403 2500 1547 2.66 2360
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 36 for general fan performance notes.
29
Table 20 — Fan Performance 580F072,073 — Vertical Discharge Units, Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 —— — 2600 1300 1.71 1518 1389 1.94 1726 1470 2.17 1929 1544 2.40 2130 —— — 2700 1343 1.90 1683 1430 2.14 1899 1509 2.38 2111 —— — —— — 2800 1386 2.09 1860 1471 2.35 2085 —— — —— — —— — 2900 1429 2.31 2050 3000 ——— ——— ——— ——— ———
AIRFLOW
(Cfm)
1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 —— — 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 —— — —— — 2200 1538 2.04 1816 1602 2.23 1984 —— — —— — —— — 2300 1572 2.23 1978 —— — —— — —— — —— — 2400 ——— ——— ——— ——— ——— 2500 ——— ——— ——— ——— ——— 2600 ——— ——— ——— ——— ——— 2700 ——— ——— ——— ——— ——— 2800 ——— ——— ——— ——— ——— 2900 ——— ——— ——— ——— ——— 3000 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.
Table21—FanPerformance 580F072,073 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 1576 2.41 2142 2600 1300 1.71 1518 1389 1.94 1726 1470 2.17 1929 1544 2.40 2130 1613 2.62 2329 2700 1343 1.90 1683 1430 2.14 1899 1509 2.38 2111 1581 2.61 2320 1649 2.85 2527 2800 1386 2.09 1860 1471 2.35 2085 1548 2.60 2305 1619 2.84 2522 2900 1429 2.31 2050 1512 2.57 2283 1588 2.83 2512 3000 1473 2.54 2252 1553 2.81 2494
AIRFLOW
(Cfm)
1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 1713 2.41 2142 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 1688 2.42 2149 1744 2.60 2312 2200 1538 2.04 1816 1602 2.23 1984 1663 2.42 2152 1720 2.61 2321 1775 2.81 2491 2300 1572 2.23 1978 1635 2.42 2153 1695 2.62 2328 1753 2.82 2504 —— — 2400 1607 2.42 2150 1669 2.63 2332 1729 2.83 2515 —— — —— — 2500 1642 2.63 2333 1704 2.84 2523 —— — —— — —— — 2600 1677 2.85 2527 2700 ——— ——— ——— ——— ——— 2800 ——— ——— ——— ——— ——— 2900 ——— ——— ——— ——— ——— 3000 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 36 for general fan performance notes.
30
Table22—FanPerformance 580F036 — Horizontal Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
900 0.54 0.21 253 0.57 0.23 277 0.55 0.26 307 0.60 0.31 363 1000 0.49 0.23 270 0.51 0.25 292 0.52 0.27 321 0.53 0.32 374 1100 0.43 0.24 287 0.45 0.26 307 0.46 0.28 335 0.49 0.33 385 1200 0.39 0.26 304 0.40 0.27 323 0.38 0.29 349 0.43 0.34 397 1300 0.33 0.27 321 0.35 0.29 338 0.35 0.31 364 0.36 0.34 408 1400 0.26 0.29 338 0.28 0.30 354 0.29 0.32 378 1500 0.21 0.30 355 0.23 0.31 369 0.24 0.33 392
Bhp—Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
ESP BhpWattsESP Bhp Watts ESP Bhp Watts ESP BhpWatts
LEGEND See page 36 for general fan performance notes.
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
Table23—FanPerformance 580F036 — Horizontal Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 607 0.14 142 745 0.22 221 856 0.31 304 952 0.39 393 1037 0.49 485 1000 640 0.18 174 775 0.26 261 884 0.35 351 978 0.45 446 1062 0.55 545 1100 674 0.21 212 805 0.31 307 912 0.41 404 1005 0.51 506 1089 0.61 611 1200 708 0.26 256 836 0.36 359 941 0.47 464 1033 0.57 572 1116 0.69 683 1300 743 0.31 307 868 0.42 417 971 0.53 530 1062 0.65 645 1143 0.77 764 1400 780 0.37 364 900 0.49 483 1002 0.61 603 1091 0.73 726 1172 0.86 851 1500 816 0.43 428 934 0.56 556 1033 0.69 685 1121 0.82 815 1201 0.95 947
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
900 1114 0.59 582 1186 0.69 684 1253 0.79 789 1316 0.90 898 1375 1.02 1010 1000 1139 0.65 648 1210 0.76 754 1277 0.87 865 1340 0.98 979 1399 1.10 1097 1100 1165 0.72 720 1236 0.84 832 1302 0.95 948 1364 1.07 1068 1423 1.20 1191 1200 1191 0.80 799 1261 0.92 917 1327 1.04 1039 1389 1.17 1165 —— — 1300 1218 0.89 885 1288 1.02 1010 1353 1.14 1138 —— — —— — 1400 1246 0.99 980 1315 1.12 1111 —— — —— — —— — 1500 1274 1.09 1083 —— — —— — —— — —— —
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 685 to 1045 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 36 for general fan performance notes.
Table24—FanPerformance 580F036 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 607 0.14 142 745 0.22 221 856 0.31 304 952 0.39 393 1037 0.49 485 1000 640 0.18 174 775 0.26 261 884 0.35 351 978 0.45 446 1062 0.55 545 1100 674 0.21 212 805 0.31 307 912 0.41 404 1005 0.51 506 1089 0.61 611 1200 708 0.26 256 836 0.36 359 941 0.47 464 1033 0.57 572 1116 0.69 683 1300 743 0.31 307 868 0.42 417 971 0.53 530 1062 0.65 645 1143 0.77 764 1400 780 0.37 364 900 0.49 483 1002 0.61 603 1091 0.73 726 1172 0.86 851 1500 816 0.43 428 934 0.56 556 1033 0.69 685 1121 0.82 815 1201 0.95 947
AIRFLOW
(Cfm)
900 1114 0.59 582 1186 0.69 684 1253 0.79 789 1316 0.90 898 1375 1.02 1010 1000 1139 0.65 648 1210 0.76 754 1277 0.87 865 1340 0.98 979 1399 1.10 1097 1100 1165 0.72 720 1236 0.84 832 1302 0.95 948 1364 1.07 1068 1423 1.20 1191 1200 1191 0.80 799 1261 0.92 917 1327 1.04 1039 1389 1.17 1165 1448 1.30 1293 1300 1218 0.89 885 1288 1.02 1010 1353 1.14 1138 1414 1.28 1270 1473 1.41 1404 1400 1246 0.99 980 1315 1.12 1111 1379 1.25 1246 1440 1.39 1383 1499 1.53 1523 1500 1274 1.09 1083 1342 1.23 1221 1406 1.37 1362 1467 1.51 1505 1525 1.66 1652
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.
31
Table25—FanPerformance 580F048 — Horizontal Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1200 0.75 0.41 458 0.81 0.45 506 0.87 0.51 572 0.92 0.56 632 1300 0.68 0.42 471 0.74 0.46 521 0.79 0.52 589 0.85 0.58 651 1400 0.60 0.45 503 0.66 0.49 556 0.71 0.54 616 0.77 0.60 681 1500 0.51 0.47 536 0.58 0.52 593 0.64 0.56 631 0.70 0.62 698 1600 0.42 0.49 557 0.49 0.54 616 0.56 0.58 654 0.63 0.64 723 1700 0.32 0.52 584 0.39 0.57 646 0.48 0.60 678 0.55 0.66 750 1800 0.21 0.54 610 0.29 0.60 674 0.41 0.62 698 0.48 0.68 772 1900 0.09 0.56 629 0.18 0.62 696 0.33 0.64 720 0.41 0.70 796 2000 0.06 0.65 731 0.26 0.66 744 0.33 0.73 823
Bhp—Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
ESP Bhp Watts ESP Bhp Watts ESP BhpWattsESP Bhp Watts
LEGEND See page 36 for general fan performance notes.
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
Table26—FanPerformance 580F048 — Horizontal Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122
AIRFLOW
(Cfm)
1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 —— — —— — 1300 1113 0.92 915 1177 1.06 1058 —— — —— — —— — 1400 1138 1.01 1000 1201 1.15 1149 —— — —— — —— — 1500 1163 1.10 1092 1600 1189 1.20 1191 —— — —— — —— — —— — 1700 ——— ——— ——— ——— ——— 1800 ——— ——— ——— ——— ——— 1900 ——— ——— ——— ——— ——— 2000 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 770 to 1175 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 36 for general fan performance notes.
32
Table27—FanPerformance 580F048 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 1177 1.25 1242 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 1205 1.37 1360 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 1165 1.31 1302 1234 1.49 1485
AIRFLOW
(Cfm)
1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 1270 1.27 1262 1324 1.42 1413 1300 1113 0.92 915 1177 1.06 1058 1237 1.21 1205 1293 1.36 1358 1347 1.52 1514 1400 1138 1.01 1000 1201 1.15 1149 1261 1.31 1303 1317 1.47 1461 1370 1.63 1623 1500 1163 1.10 1092 1226 1.25 1247 1285 1.41 1407 1341 1.58 1571 1394 1.75 1740 1600 1189 1.20 1191 1252 1.36 1353 1310 1.53 1520 1365 1.70 1690 1418 1.87 1865 1700 1216 1.31 1299 1277 1.48 1468 1335 1.65 1640 1390 1.83 1817 1442 2.01 1998 1800 1242 1.42 1414 1303 1.60 1590 1361 1.78 1770 1415 1.96 1953 1467 2.15 2140 1900 1270 1.55 1538 1330 1.73 1721 1387 1.92 1908 1441 2.11 2098 1493 2.30 2292 2000 1297 1.68 1672 1357 1.87 1862 1414 2.07 2055 1467 2.26 2252 —— —
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.
Table28—FanPerformance 580F060 — Horizontal Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1500 0.74 0.67 750 1.06 0.71 791 1.07 0.70 782 1.27 0.76 845 1.26 0.79 875 1.33 0.85 949 1600 0.54 0.70 780 0.90 0.74 824 0.92 0.74 821 1.13 0.79 883 1.14 0.82 913 1.22 0.89 988 1700 0.34 0.73 810 0.75 0.77 857 0.77 0.77 861 1.00 0.83 921 1.01 0.85 950 1.11 0.92 1027 1800 0.14 0.75 839 0.59 0.80 891 0.62 0.81 900 0.87 0.86 959 0.89 0.88 988 1.00 0.96 1066 1900 0.44 0.83 924 0.47 0.84 940 0.74 0.90 997 0.77 0.92 1025 0.89 0.99 1105 2000 0.28 0.86 957 0.32 0.88 979 0.61 0.93 1035 0.64 0.95 1063 0.78 1.03 1144 2100 0.13 0.89 990 0.17 0.91 1018 0.48 0.96 1073 0.51 0.99 1101 0.67 1.06 1183 2200 0.02 0.95 1058 0.35 1.00 1111 0.39 1.02 1138 0.56 1.10 1222 2300 0.22 1.03 1149 0.26 1.06 1176 0.45 1.13 1261 2400 0.09 1.07 1187 0.14 1.09 1213 0.34 1.17 1300 2500 ———————————————0.231.201340
Bhp—Brake Horsepower Input to Fan ESP — External Static Pressure (in. wg)
ESP Bhp Watts ESP BhpWattsESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
LEGEND See page 36 for general fan performance notes.
Low Speed Medium Speed High Speed
208V 230, 460, 575 V 208 V 230, 460, 575 V 208 V 230, 460, 575 V
33
Table29—FanPerformance 580F060 — Single-Phase, Horizontal Discharge Units,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 —— — 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 2200 1064 1.05 932 1147 1.23 1090 2300 1105 1.18 1050 2400 ——— ——— ——— ——— ——— 2500 ——— ——— ——— ——— ———
AIRFLOW
(Cfm)
1500 1223 1.18 1045 —— — —— — —— — —— — 1600 1249 1.27 1127 —— — —— — —— — —— — 1700 ——— ——— ——— ——— ——— 1800 ——— ——— ——— ——— ——— 1900 ——— ——— ——— ——— ——— 2000 ——— ——— ——— ——— ——— 2100 ——— ——— ——— ——— ——— 2200 ——— ——— ——— ——— ——— 2300 ——— ——— ——— ——— ——— 2400 ——— ——— ——— ——— ——— 2500 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 875 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See page 36 for general fan performance notes.
Table30—FanPerformance 580F060 — Three-Phase, Horizontal Discharge Units,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 1266 1.41 1248 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 1227 1.34 1189 1297 1.53 1360 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 1260 1.47 1305 1328 1.67 1481 2200 1064 1.05 932 1147 1.23 1090 1223 1.41 1256 1294 1.61 1430 1360 1.81 1612 2300 1105 1.18 1050 1185 1.37 1215 1259 1.56 1386 1328 1.76 1566 1393 1.97 1752 2400 1146 1.33 1179 1223 1.52 1349 1295 1.72 1527 1362 1.93 1711 1426 2.14 1903 2500 1187 1.48 1317 1262 1.68 1494 1332 1.89 1677 1398 2.10 1868 1460 2.33 2065
AIRFLOW
(Cfm)
1500 1223 1.18 1045 1291 1.36 1212 1355 1.56 1388 1415 1.77 1573 1473 1.99 1765 1600 1249 1.27 1127 1316 1.46 1298 1379 1.66 1478 1439 1.87 1665 1496 2.09 1860 1700 1277 1.37 1217 1342 1.57 1392 1404 1.77 1575 1463 1.99 1766 1520 2.21 1965 1800 1305 1.48 1316 1369 1.68 1495 1430 1.89 1681 1489 2.11 1876 1545 2.34 2078 1900 1333 1.60 1423 1397 1.81 1606 1457 2.02 1797 1514 2.25 1995 —— — 2000 1363 1.73 1540 1425 1.94 1727 1484 2.16 1922 1541 2.39 2124 —— — 2100 1393 1.87 1665 1454 2.09 1857 1512 2.31 2056 —— — —— — 2200 1424 2.03 1801 1484 2.25 1997 —— — —— — —— — 2300 1455 2.19 1946 —— — —— — —— — —— — 2400 1487 2.37 2103 —— — —— — —— — —— — 2500 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.
34
Table31—FanPerformance 580F060 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 1266 1.41 1248 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 1227 1.34 1189 1297 1.53 1360 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 1260 1.47 1305 1328 1.67 1481 2200 1064 1.05 932 1147 1.23 1090 1223 1.41 1256 1294 1.61 1430 1360 1.81 1612 2300 1105 1.18 1050 1185 1.37 1215 1259 1.56 1386 1328 1.76 1566 1393 1.97 1752 2400 1146 1.33 1179 1223 1.52 1349 1295 1.72 1527 1362 1.93 1711 1426 2.14 1903 2500 1187 1.48 1317 1262 1.68 1494 1332 1.89 1677 1398 2.10 1868 1460 2.33 2065
AIRFLOW
(Cfm)
1500 1223 1.18 1045 1291 1.36 1212 1355 1.56 1388 1415 1.77 1573 1473 1.99 1765 1600 1249 1.27 1127 1316 1.46 1298 1379 1.66 1478 1439 1.87 1665 1496 2.09 1860 1700 1277 1.37 1217 1342 1.57 1392 1404 1.77 1575 1463 1.99 1766 1520 2.21 1965 1800 1305 1.48 1316 1369 1.68 1495 1430 1.89 1681 1489 2.11 1876 1545 2.34 2078 1900 1333 1.60 1423 1397 1.81 1606 1457 2.02 1797 1514 2.25 1995 1570 2.48 2200 2000 1363 1.73 1540 1425 1.94 1727 1484 2.16 1922 1541 2.39 2124 1596 2.63 2333 2100 1393 1.87 1665 1454 2.09 1857 1512 2.31 2056 1568 2.55 2262 1622 2.79 2475 2200 1424 2.03 1801 1484 2.25 1997 1541 2.48 2200 1596 2.71 2411 2300 1455 2.19 1946 1514 2.42 2147 1571 2.65 2355 1625 2.89 2570 2400 1487 2.37 2103 1545 2.60 2308 1601 2.84 2521 2500 1520 2.56 2269 1577 2.79 2480
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 36 for general fan performance notes.
Table32—FanPerformance 580F072,073 — Horizontal Discharge Units, Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945 2600 1255 1.73 1539 1322 1.89 1678 1386 2.05 1822 1448 2.22 1970 1508 2.39 2124 2700 1298 1.93 1713 1363 2.09 1857 1425 2.26 2005 2800 1341 2.14 1899 1404 2.31 2048 2900 1384 2.36 2099 3000 ——— ——— ——— ——— ———
AIRFLOW
(Cfm)
1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 —— — 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 —— — —— — 2400 1500 2.17 1928 1559 2.35 2083 —— — —— — —— — 2500 1533 2.36 2098 —— — —— — —— — —— — 2600 ——— ——— ——— ——— ——— 2700 ——— ——— ——— ——— ——— 2800 ——— ——— ——— ——— ——— 2900 ——— ——— ——— ——— ——— 3000 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.
35
Table 33 — Fan Performance 580F072,073 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945 2600 1255 1.73 1539 1322 1.89 1678 1386 2.05 1822 1448 2.22 1970 1508 2.39 2124 2700 1298 1.93 1713 1363 2.09 1857 1425 2.26 2005 1485 2.43 2158 1544 2.61 2315 2800 1341 2.14 1899 1404 2.31 2048 1464 2.48 2201 1523 2.66 2358 1580 2.84 2520 2900 1384 2.36 2099 1445 2.54 2253 1504 2.71 2410 1561 2.90 2572 3000 1428 2.60 2313 1487 2.78 2471
AIRFLOW
(Cfm)
1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 1673 2.53 2246 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 1644 2.52 2239 1699 2.71 2406 2400 1500 2.17 1928 1559 2.35 2083 1616 2.53 2243 1672 2.71 2408 1726 2.90 2579 2500 1533 2.36 2098 1591 2.54 2257 1647 2.73 2421 2600 1566 2.57 2281 1623 2.75 2444 2700 1600 2.79 2477 2800 ——— ——— ——— ——— ——— 2900 ——— ——— ——— ——— ——— 3000 ——— ——— ——— ——— ———
Bhp—Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm BhpWattsRpm BhpWattsRpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See below for general fan performance notes.
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 9 — Motor Data for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
36
PRE-START-UP
WARNING: Failure to observe the following warnings
could result in serious personal injury .
1. Follow recognized safety practices and wear protective goggles when checking or the servicing refrigerant system.
2. Do not opera te the compres sor or provide an y electric power to the unit unless the compres sor termina l cov­er is in place and secured.
3. Do not remove the com pre ssor termi nal cover unti l all electrical sources are disconn ected.
4. Relieve all pressure from the system before touching or disturbing anything in side the c omp ress or term ina l box if refrigerant leak is suspected around the com­pressor terminals.
5. Never attempt to repai r a soldered connection while the refrigerant system is under pressure.
6. Do not use torch to remove any component. The sys­tem contains oil and refrigerant under pressure. To re­move a component, wear protective goggles and proceed as follows: a. Shut off gas and then electrical power to the unit.
Install lockout tag.
b. Relieve all pressure from the system using both
high-pressure and low-pressure ports.
c. Cut the component connection tubing with a tubing
cutter, and remove the component from the unit.
d. Carefully unsweat the remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to ins pect and prep are the unit f or initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, the unit.
3. Make the following inspections: a. Inspect for shipping and handling damages such
as broken lines, loose p arts, or discon nec ted wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using an electronic leak detector, halide torch, or liquid-soap solution.
c. Inspect all field- and factory-wiring connections.
Be sure that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten the fins with a fin comb.
4. Verify the following conditions: a. Make sure that condenser fan blade is correctly
positioned in the fan orifice. See Condenser-Fan
Adjustment section on page 48 for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled
with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
I. UNIT PREPARATION
Make sure that unit has bee n installed in accordance with these installation instructions and applicable codes. Make
sure Start-Up Checklist on back page is filled out and completed.
II. RETURN-AIR FILTERS
Make sure correct filters are installed in filter tracks. See Table 1. Do not operate unit without return-air filters.
III. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
IV INTERNAL WIRING
Check all electrical connections in unit control boxes. Tighten as required. Ensure wiring does not come in contact with refrigerant tubing.
V. GAS PIPING
Check gas piping for leaks.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than
1
sures greater tha n
/2 psig will cause g as valve damage
1
/2 psig. Pres-
resulting in hazardous condition. If gas valve is sub­jected to pressure greater than
1
/2 psig, it must be replaced before use. When pressure testing field­supplied gas piping at pressures of
1
/2 psig or less, a unit connected to such piping must be isolated by man­ually closing the gas valve.
VI. REFRIGERANT SERVICE PORTS
To service refrigerant service ports, remove compressor access panel. Each unit system has 4 Schrader-type service gage ports: one on the suction line, one on the liquid line, and two on the compressor discharge line. Be sure that caps on the ports are tight. One of the Schrader-type valves on the compressor discharge line is located under the low-pressure switch.
The Schrader valve on the compr essor di scharge li ne that is located under the high pressure switch does not contain a Schrader core in the valve.
VII. HIGH FLOW VALVES
Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with o- r in gs located inside the c aps. These valv es can­not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.
VIII. COMPRESSOR ROTATION
On 3-phase units with scroll compressors, it is important to be certain compressor is rotating i n the proper direc tion. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gage s to suction and discharge pres­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres­sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the unit.
37
The suction and discharge pressure levels should now move to their normal start-up levels.
NOTE: When the compres sor is rotating in the wrong direc­tion, the unit makes an elevated level of noise and does not provide cooling.
IX. COOLING
Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COO L posi­tion and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor, outdoor fan and evaporator motor start on closure of contactor.
Check unit charge. Refer to Service, Refrigerant Charge sec­tion, page 48.
Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after 30-second delay.
To Shut Off Unit
Set system selector switch at OFF position. Resetting ther­mostat at a position ab ove room temperature shu ts unit off temporarily until space temperature exceeds thermostat setting.
X. MAIN BURNERS
Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move thermostat set p oint abov e room tem perature a nd ver­ify that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the thermostat setting below room temperature and verify that the burners and evaporator fan turn off. (Fan will turn off only if fan selector switch is in the AUTO. position.)
Refer to Table 34A and 34B for the correct orifice to use at high altitudes.
XI. HEATING
1. Purge gas supply line of air by opening union ahead of gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas val ve .
3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temper­ature lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 min­utes, there is a lockout. To reset the control, break the 24-v power to W1.
6. The evaporator-fan motor wil l turn on 45 seconds af­ter the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds af­ter thermo st a t te m p e r at u r e i s sa t isfied.
8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor ON/ OFF delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur . Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be extended
to 180 seconds. When one flash of the LED is observed, t he evaporator-fan ON/OFF delay has been modified.
If the limit switch trips at the start of the heating cycle dur­ing the evap or ator ON delay, t he time period of the ON delay for the next cycle will be 5 seconds less than the time at which the swit ch trip ped. (Exa mple: If th e l imit switch trip s at 30 seconds, t he ev aporator-fan ON delay for the next cycle will occur at 25 seconds.) To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating.
The evaporator-fan OFF delay can also be modified. Once the call for heating has ended, there is a 10-minute period dur­ing which the modification can occur. If the limit switch trips during this period, the evaporator-fan OFF delay will increase by 15 seconds. A maximum of 9 trips can occur, extending the evaporator-fan OFF delay to 180 seconds.
To restore the original default value, reset the power to the unit.
To Shut Off Unit
Set system selector switch at OFF position. Resetting heat­ing selector lever bel ow room temperature will temporar ily shut unit off until space temperature falls below thermostat setting.
Table 34A — Altitude Compensation* — Standard Units
74,000 AND 115,000 BTUH
ELEVATION
(ft)
0-2,000 33 43 30 37
2,000 36 44 31 39 3,000 36 45 31 40 4,000 37 45 32 41 5,000 38 46 32 42 6,000 40 47 34 43 7,000 41 48 35 43 8,000 42 49 36 44
9,000 43 50 37 45 10,000 44 50 39 46 11,000 45 51 41 47 12,000 46 52 42 48 13,000 47 52 43 49 14,000 48 53 44 50
*As the height above sea level increases, there is less oxygen per cubic foot of air.
Therefore, heat input rate should be reduced at higher altitudes.
†Orifices available through your Bryant distributor.
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
150,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
Table 34B — Altitude Compensation* — Low NOx Units
60,000 AND 90,000 BTUH
ELEVATION
(ft)
0-2,000 38 45 32 42
2,000 40 47 33 43 3,000 41 48 35 43 4,000 42 49 36 44 5,000 43 49 37 45 6,000 43 50 38 45 7,000 44 50 39 46 8,000 45 51 41 47
9,000 46 52 42 48 10,000 47 52 43 49 11,000 48 53 44 50 12,000 49 53 44 51 13,000 50 54 46 52 14,000 51 54 47 52
*As the height above sea level increases, there is less oxygen per cubic foot of
air. Therefore, the input rate should be reduced at higher altitudes.
†Orifices are available through your local Bryant distributor.
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
120,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size
Liquid
Propane
Orifice
Size†
38
XII. SAFETY RELIEF
A soft solder joint at the suction service Schrader port pro­vides pressure relief under abnormal temperature and pres­sure conditions (i.e., fire in building).
XIII. VENTILATION (CONTINUOUS FAN)
Set fan and system selector switches at ON and OFF posi­tions, respectively. Evaporator fan operates continuous ly to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second del a y be f or e th e f an tur ns off.
XIV. ECONOMI$ER+ CONTROLLER
The EconoMi$er+ controller is mounted to the top of the EconoMi$er+ d amp er and is acce ssibl e by remo ving the fi lter access door of the unit.
The EconoMi$er+ controller is protected by a sheet metal enclosure mounted over the controller. Remove the single screw on the front of the enclosure and lift off the top for access to the controller . The primary purpose of the controller is to provide control of the EconoMi$er+ dampers and the cooling compression stages. The status of the indoor fan is monitored through the G input but is not directly controlled by the controller. The heating function is completely indepen­dent of the controller.
IMPORTANT: The controller can only be used with conven­tional thermostats with Y1, Y2 and G input to the controller; it can NOT be used with electron ic thermostats wi th a pro­portional room temperature input, or with Variable Air Vol­ume systems.
There are 4 LEDs on the con troller, which are used to rea d values and display status and configuration information. There are 2 buttons (READ/ADJUST and ADVANCE/ MAN­UAL), which change modes and configure the controller. See Fig. 36.
The EconoMi$er+ microprocessor based control system pro­vides the following control functions:
• EconoMi$er+ damper control for free cooling
• Minimum position control for ventilation
• Demand Ventilation Control using a CO
sensor
2
• Compressor Cooling Stage Control
• Occupied/Unoccupied Control
• Diagnostics Display and History
• Manual test co ntrol See Table 35 for Inputs and Outputs.
A. Integrated Display
The control board includes an integrated display, which is used for the following functions:
•Configuration and setup
• Set point and control adjustment
• Error status and alarm monitoring
• Manual control
• Reading sensor values There are 5 modes of display operation:
•Startup Mode
•Run Mode
• Read Mode
•Setup Mode
• Manual Mode External devices are not required to operate and con figure
the control.
B. Startup Mode
During the first 3 seconds after power is applied to the con­trol, the four LEDs flash as shown in Table 36, indicating
that the control is being initialized. The buttons are not operational during Startup mode.
C. Run Mode
Run mode indicates status of control ler and unit. The mode can be changed to the Read, Setup, or Manual modes by pushing va ri ous buttons.
While the control is in Run mode, the DS1 heartbeat indica­tor LED (red) will flas h to indi cat e the cont rolle r is ope rat ing properly. The DS2 Econo indicator LED (yellow) will flash whenever economiz e r is b ein g us ed f or f re e cool i ng. The DS3 first stage cooling indicator LED (green) will be on steady indicate demand for sta ge 1 cooling. The DS4 second stage cooling indicator LED (green) will be on steady to indicate demand for stage 2 cooling.
If the controller is in a different mode, the controller will return to Run mode after 10 minutes of user inactivity or if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) but­tons are held for at least 3 seconds until all LEDs flash.
D. Read Mode
Read mode is used to check set points (Table 37) and I/O channel status (Table 38). Enter the Read mode by pushing and releasing the READ/ADJUST (#1) button. A user can only enter Read mode from the Run mode (to get to Run mode, press both the #1 and #2 buttons for at least 3 seconds until all LEDs flash). In Read mode, LEDs are not lit until the READ/ADJUST button (#1) is pushed.
NOTE: If the user pushes and holds the READ/ADJUST but­ton (#1) for more than 3 seconds, then the control will go into the Setup mode, indicated by the yellow LED (on steady).
While in Read mode, push button #1 then the DS1 LED (Red) flashes to indicate setup point number as defined in the setup table. The two green LEDs will then show the value of the display item. The DS3 LED will first display the tens digit and the DS4 LED will the n display the ones digit. For example to display 54, the DS3 LED will flash 1 group of 5 at a high flash rate to indicate 50, and then follow with 4 flashes (DS4) at 1-second intervals to complete the display of the number 54.
NOTE: Do not try to count the “5 Fast Flashes” individually, but instead count how many groups of 5 flashes were dis­played. In this case, 1 group of 5 flashes, plus the 4 flashes at 1 second results in the value of 54.
To read the display again, push the READ/ADJUST (#1) but­ton and the sequence will repeat as many times as needed.
To advance to the next setup point, push the ADVANCE/ MANUAL (#2) button. The controller will cycl e through all the setup channels (Table 37) and then the I/O channels (Table 38) and then back to the first setup channel.
NOTE: The user can only advance forward, not reset to #1 or go backwards. Cycling the EconoMi$er + po we r will r eset the item number (but not the item value) to item #1.
In the Read mode for setup variables, the LEDs will not turn on steady; the LEDs will always flash. Steady-on indicators are reserved for the configuration modes. No data is modified in the Read mode. The con troller will always remain at the last read number even if reset back to normal operat ion.
NOTE: To enter another mode, the user first must exit the Read mode.
If no button is pushed in 10 minutes, Read mode will auto­matically be exited. Also, if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are pushed and held for more than 3 seconds, then Read mode will be exited to Run mode. While i n the Read mod e , the c ontro ller will conti nue to operate with normal unit control.
39
READ/
ADJUST
ADVANCE
MANUAL
DS1 DS2
DS3
DS4
Y1 Y2
G
OCC
24V
date or serial no
#1
PUSH BUTTONS
#2
SETPOINT DISPLAY
RED
YELLOW
GREEN
J4
24 VAC
24 VAC
24 VAC
EX2/CP3
OUTPUT RELAYS
EX1/CP4
CP1
CP2
Relays rated at 24 VAC 3A and traces for 8A.
J1
1
Y1 (cool 1) Y2 (cool 2)
G (fan) OCC
Occupied/unoccupied I/O support dry circuit contact (min 24 mA I)
NOTE: For 1 and 2 stage cooling, 2 stages of power exhaust will be used. For 3 cooling stages, only 1 stage of power exhaust will be used, and for 4 stages no power exhaust will be controlled directly by the control.
C1
C2
24V 24V
24V
C3
C4
24 VAC
5
THERMOSTAT INPUTS
4-20 mA external powered between signal and ground 4-20 mA loop powered between 24 VDC and signal
ANALOG INPUTS
2-10 VDC
ECONOMIZER
CONTROL
24 VAC
24 VAC
Control
24V
24V
CNT
OAT (10k thermistor)
SAT (10k thermistor)
IRH (4-20 ma)
RAT (10k thermistor)
ORH (4-20 ma)
Vref
IAQ (4-20ma)
min (10K pot)
Vref
Vref
J3
5
1
SAT
OAT
IRH
RAT
VRF
ORH
VRF
IAQ
MIN
VRF
17
J2
1
POWER SUPPLY
Fig. 36 — EconoMi$er+ Controller Board
Table 35 — EconoMi$er+ Inputs and Outputs
INPUT NAME TYPE USE
INPUT/OUTPUT
RANGE THERMOSTAT INPUTS Y1 (Cool/Low Cool) Y1 Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 1 Y2 (Cool 2/High Cool) Y2 Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 2 G (fan) G Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 3 Occupied/Unoccupied OCC Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 4,5 POWER Powe r 24V Input Standard 18-30 VAC 50/60 Hz NA NA J2 1,2 ECONOMIZER MOTOR Control CNT 2-10 vdc Standard 2-10 vdc 0-100% 1% J2 3,4,5 ANALOG INPUTS Supply Air Temperature SAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 1,2 Outside Air
Temperature
OAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 3,4
Return Air Temperature RAT 10 K Thermistor Option 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 5,6
Indoor Humidity IRH
Outdoor Humidity ORH
Indoor CO
Remote Minimum Position Po t
2
IAQ
MIN 10K Option 10K to 100K Ohms 0 to 100% 1% J3
4-20 mA,
Loop Powered
4-20 mA,
Loop Powered
4-20 mA,
Ext Sourced
Option 4-20 mA, 24 vdc 0-100% .08 mA J3 7,8,9
Option 4-20 mA, 24 vdc 0-100% .08 mA J3
Option 4-20 mA, 24 vdc 0-200 PPM/10 10 PPM J3 13,14
RELAY OUTPUTS Cooling Stage 1 CP1 Relay Standard 24 vac, 2.5 Amps at 24 vac NA On/Off J4 1,3,4 Cooling Stage 2 CP2 Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 2,3,4 Powe r Exhaust 2/
Cooling Stage 3* Powe r Exhaust 1/
Cooling Stage 4†
CP3/
EX2
CP4/
EX1
Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 5,6
Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 5,7
DISPLAY Setpoint Switch 1 SP1 Digital Standard Open/Closed Logic Open/Closed On Board NA Setpoint Switch 2 SP2 Digital Standard Open/Closed Logic Open/Closed On Board NA LED 1 DS1 LED Output Standard Red Logic On/Off On Board NA LED 2 DS2 LED Output Standard Yellow Logic On/Off On Board NA LED 3 DS3 LED Output Standard Green Logic On/Off On Board NA LED 4 DS4 LED Output Standard Green Logic On/Off On Board NA
*If there are 3 stages then there can only be 1 stage of power exhaust. †If there are 4 stages then no power exhaust stages are directly controlled.
CONVERSION
RANGE
CONVERSION RESOLUTION
CONNECTION
10,11,1
15,16,1
PIN NO.
2
7
40
Table36—Start-UpModeSequence
TIME 0-1.0 SEC 1-1.5 SEC
1.5-2.0 SEC
2.0-2.5 SEC
2.5-3.0 SEC
LED — Light-Emitting Diode
LED 1/DS1 (RED) LED 2/DS2 (YELLOW) LED 3/DS3 (GREEN) LED 4/DS4 (GREEN)
OFF OFF OFF OFF
FLASH ½ SEC OFF OFF OFF
OFF FLASH ½ SEC OFF OFF OFF OFF FLASH ½ SEC OFF OFF OFF OFF FLASH ½ SEC
Table 37 — Configuration Variables (Read and Setup Modes)
NO.
1 Supply Air Temperature Setpoint F 40 F 65 F 55 F 1 F Leaving Air Temperature Control Point
Occupied Minimum Economizer
2
Posi tion Unoccupied Minimum Economizer
3
Posi tion
4 Economizer Maximum Position % 1% 100% 100% 1% Maximum Econo Position
5 Economizer Type 1 3 2 1
6 Economizer Changeover Type 1 5 2 1 1 = Switch, 2 = Outdoor Dr y Bulb,
Economizer Changeover Setpoint
7
(mode 2)
8 Economizer Changeover Setpoint
(mode 3)
9 No.ofcompressors 1 4 2 1 1,2,3,or4
10 Compressor Sequencing 1 4 1 1
11 Power Exhaust Stage 1 Activation % 1% Item 12 -5% 25% 1% Economizer Position 12 Power Exhaust Stage 2 Activation % Item 11 +1% 100% 50% 1% Economizer Position (> stage 1) 13 Unoccupied Configuration 1 3 3 1 1 = No Unoccupied Cooling,
14 Compressor Lockout Temperature 1 F 65 F 45 F 1 F Compressor Operation
IAQ Min Economizer Position
15
Setpoint
16 IAQ Enable 1 2 1 1 1 = Disabled, 2 = Enabled 17 Outdoor IAQ Reference PPM/10 1 PPM/10 100 PPM/10 40 PPM/10 1 PPM/10 Outdoor Reference IAQ Level
IAQ Lower Limit Control Point
18
Differential IAQ Upper Limit Control Point
19
Differential
20 1st Most Recent Error/Reset 1 8 Used in Setup Mode to Reset Alarms 21 2nd Most Recent Error (read only) 1 8 Not Displayed in Setup Mode 22 3rd Most Recent Error (read only) 1 8 Not Displayed in Setup Mode 23 4th Most Recent Error (read only) 1 8 Not Displayed in Setup Mode 24 5th Most Recent Error (read only) 1 8 Not Displayed in Setup Mode
DC — Direct Control IAQ — Indoor Air Quality LAT — Leaving Air Temperature Compensated Control VOC — Volatile Organic Compounds
SETUP POINTS
(viewable and adjustable)
LEGEND NOTE: The accessibility of these channels will be as follows:
UNITS
% Item 15 +1% 100% 15% 1% Min Econo Position (occupied mode)
% 1% 100% 5% 1% Min Econo Position (unoccupied mode)
F 45 F 70 F 65 F 1 F For Outdoor Changeover
1 4 1 1 Outdoor Enthalpy Changeover Setpoint
% 1% Item 2 +1% 5% 1% Min IAQ Position for VOC Emissions
PPM/10 1 PPM/10
PPM/10
MINIMUM
VAL UE
Item 18 +1
PPM/10
MAXIMUM
VAL UE
Item 19 -1
PPM/10
200 PPM/10 140 PPM/10 1 PPM/10
READ MODE — All channels will be accessible. SETUP MODE — Only channels 1-20 will be accessible and 20 will be used to reset alarms.
FAC TORY
SETTING
60 PPM/10 1 PPM/10
INC COMMENTS
1 = Ven t On ly, 2 = Proportional, 3 = 3 Position
3 = Diff Dry Bulb, 4 = Outdoor Enthalpy, 5 = Diff Enthalpy
1 = A, 2 = B, 3 = C, 4 = D
1 = DC-Sensible, 2 = DC-Latent, 3 = LAT-Sensible, 4 = LAT-Latent
2 = Unoccupied Free Cooling, 3 = Unoccupied Free & Mech Cooling
Differential Lower Limit Indoor IAQ Level
Differential Upper Limit Indoor IAQ Level
Table38—Input/Output Channels
NO. I/O POINTS UNITS MINIMUM VALUE MAXIMUM VALUE INC COMMENTS
1 C1 Output Off On Compressor 1 2 C2 Output Off On Compressor 2 3 C3 Output Off On Compressor 3/Power Exhaust 2 4 C4 Output Off On Compressor 4/Power Exhaust 1 5 Economizer Damper Output % 1 F 100 F 1% Damper Commanded Position 6 Supply Air Temperature F 1 F 150 F 1 F Supply Air Temperature 7 Outdoor Air Temperature F 1 F 150 F 1 F Outdoor Air Temperature 8 Return Air Temperature F 1 F 150 F 1 F Return Air Temperature
9 Indoor Relative Humidity % 1% 100% 1% Return Air Relative Humidity 10 Outdoor Relative Humidity % 1% 100% 1% Outdoor Air Relative Humidity 11 Indoor Air Quality PPM 1 PPM/10 200 PPM/10 10 PPM Indoor Air Quality (/10) 12 Remote Minimum Position % 1% 100% 1% Remote Minimum Pot Position 13 Y1 Status Open Close Thermostat Y1 Status 14 Y2 Status Open Close Thermostat Y2 Status 15 G Status Open Close Indoor Fan Status 16 Occ Status Open Close Remote Occupied Status
NOTE: The accessibility of these channels will be as follows:
READ MODE — All channels will be accessible for reading. ADJUST MODE — Only channels 1-5 will be accessible. MANUAL MODE — Only channels 1-5 will be accessible.
41
After advancing through all the configuration variables in the Read mode, the controller will then advance through t he status of the I/O channels. As in the Read mode, there will be no LEDs on. Push the READ/ADJUST (#1) button and the yellow LED will flash the “I/O Point” numbe r and the green LEDs will flash the “I/O Values” in the same manner described in the Read mode section. See Ta ble 38. At the first I/O point (Compressor 1 Ou tput), the DS2 LED (Yellow) will flash with the number of the I/O channel and the DS1 LED (red) will stop fla shi ng. This will be followed b y the I/O c h an­nel status. To read the value ag ain, pus h the R EAD/ADJU ST (#1) button.
To advance to the next channel, push the ADVANCE/MAN­UAL (#2) button. If the number of the channel or the status value is greater than 4 the controller will count out the increments of 5 a t a high fl ash rate foll owed by the remain­ing digits. The channel number will be counted out through the DS2 LED (yellow). Th e status value wil l be counted out through the DS3 and DS4 LEDs (green).
If the status value is an analog value then the numeric value will be displayed by using the D S3 Green LED to display the tens digit and the DS4 will be used to display the ones digit.
If the channel is a digital output (relay), the DS3 LED (flash­ing green) will in dicate ON stat us and the DS4 LED (flash­ing green) will indicate OFF status. If the output is the economizer control signal then the DS3 LED will be used to indicate the motor is being driven open, and the DS4 LED will be used to indicate it is being closed. If the motor i s not being commanded in either direction then both the DS3 and DS4 LEDs will be on. The controller will first go through the output relays, then the economizer motor, and will then fol ­low with the values currently being read for the analog input channels as defined in the configuration table. All values are maintained in memory even during a power loss. To exit Setup mode, push and hold the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons for more than 3 seconds. Setup mode wil l automati cally be exited aft er 10 minu tes of no activity.
E. Setup Mode
The Setup mode is used to change set points and configura­tion values.
Enter the Setup mode by pushing and holding the READ/ ADJUST (#1) button 1 for at least 3 seconds until all LEDs flash once. Then, the yellow LED will come on steady. A user can only enter the Setup mode from the Run m ode (to get to Run mode, press buttons both buttons #1 and #2 for at least 3 seconds).
In Setup mode, all configurations can be modifi ed e ven w hil e the unit is running, but the use r will not be able to adjus t the I/O channels . O nly c ha nne ls 1 th roug h 20 on Table 37 will b e accessible in the Setup mode. Channel 20 will be used to reset any alarms that may have occurred. As an option, alarms can also be reset by cycling power to the cont roller.
NOTE: During the Setup mode, all routines including safety routines will continue to run and control the unit.
While in this mode, the DS1 LED (red) will flash to indicate the number of the configuration item. The DS2 LED (yellow) will be on continuousl y to i ndi cate tha t the uni t is i n c on figu­ration mode. Use the ADVANCE/MANUAL button to sequence through the setup channels. If the value of the channel is less than 5 it will count out the value of the chan­nel on the DS1 LED at 1-second intervals. If the channel value is 5 or great er, the DS1 LED will first c ount out the groups of 5 and then following with the remaining digit.
Verify what Setup Point is being read by pushing the READ/ ADJUST button (#1). First the Red LED will flash the set point number, then the Green LEDs will flash the value. Then, the green DS3 and DS4 LEDs will each come on steady for about 2 seconds. While DS3 is on steady, its new value can be entered by pushing READ/ADJUST (#1), and entering the value for the ten’s digit. When the DS4 comes on steady, enter the value for th e one's d igit. Afte r the green LEDs are off, push the READ/ADJUST button (#1) again to verify that the correct value has been entered. If the configu­ration is a discrete On/off setting, push the READ/ADJUST button (#1) to toggle LED 3 or 4 on or off.
Setup Example 1: Change “Occupied Minimum Position” (configuration item 2) to 53%.
1. Read the General Notes about reading and entering values found on the label on the top of the EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at least 3 seconds until all LEDs flash. The yellow LED will go on steady.
3. Read the current configuration point by pushing but­ton #1. The red LED flashes the configuration point number and the green LEDs flash the current setting for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2 and Note 1 for Setup mode operation.
5. Use button #2 (ADVANCE/MANUAL) to advance to configuration point number 2, Occupied Min.
NOTE: Before performing Step 6, be ready to push button #1; there is a limited time window that can easily be missed when the DS3 green LED c omes on, and agai n when th e DS4 green LED comes on.
6. Verify the configuration point by pushing button #1. The red LED should flash twice to indic ate point 2, and then the green LEDs will flash the current setting.
7. Next, the green DS3 LED wil l turn on steady for 2 seconds. During this time, push button #1 five times.
8. The DS3 LED wi ll turn off and the gree n DS4 LED will go on steady for 2 seconds. During this time, push button #1 three times.
9. The 5 button #1 pushes, followed by the 3 button #1 pushes is the sequ ence that sets the occupied mini ­mum position to 53%.
10. Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. There should be 5 fast blinks of DS3 and 3 slow blinks of DS4.
Setup Example 2: Change the Occupied Minimum Position (item 2) to 2% (lowest value).
1. Read the General Notes about reading and entering values found on the label on the top of the EconoMi$er+.
2. Push and hold button #1 (READ/ADJUST) for at least 3 seconds until all LEDs flash. The yellow LED will go on steady.
3. Read the current configuration point by pushing but­ton #1. The red LED flashes the configuration point number and the green LEDs flash the current setting for that setup point number.
4. On the label (on top of the EconoMi$er+), read Step 2 and Note 1 for Setup mode operation.
5. Use button #2 (ADVANCE/MANUAL) to advance to configuration point number 2, Occupied Min.
42
6. Verify the configuration point by pushing button #1. The red LED should flash twice to indicate point 2, and then the green LEDs will flash the current setting.
NOTE: Since the occupied minimum position MUST be 1 greater than the IAQ minimum position (item
15), the IAQ minimum position must be changed first. (IAQ min has a default value of 5%, which is higher than the 2% value in this example.)
7. Use button #2 (ADV ANCE/MANUAL) to get to config­uration point 15 (IAQ Minimum Position).
NOTE: Before performing Step 8, be ready to push button #1; there is a limited time window that can ea sily be missed when the DS3 green LED com es on, and ag ain wh en the DS 4 green LED comes on.
8. Verify the configuration point by pushing button #1. The red LED should flash 15 times to indicate point 15, then the green LEDs will flash the current setting.
9. Next, the green DS3 LED will turn on steady for 2 seconds. During this time, do NOT do anything so that the position defaults to 0.
10. The DS3 LED will turn off and the green DS4 LED will go on steady for 2 seconds. During this time, push button #1 once to set the point to 1%.
11. Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. DS3 should not blink, and DS4 should blink once.
12. Now configure the Occupied Minimum Position to 2%. Use button #2 (ADVANCE/MANUAL) to get to configuration point 2.
NOTE: Before performing S tep 13, be ready to push button #1; there is a limited time window that can ea sily be missed when the DS3 green LED com es on, and ag ain wh en the DS 4 green LED comes on.
13. Verify the configuration point by pushing button #1. The red LED should flash twice to indicate point 2, then the green LEDs will flash the current setting.
14. Next, the green DS3 LED will turn on steady for 2 seconds. During this time, do NOT do anything so that the position goes to 0.
15. The DS3 LED will turn off and the green DS4 LED will go on steady for 2 seconds. During this time, push button #1 twice to set the point to 2%.
16. Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. DS3 should not blink, and DS4 should blink twice.
NOTE: Configuration items 2, 15, 11, 12, 18 and 19 (in Table 37) are dependent upo n other items. Befo re attempt­ing to change one of these items, be sure to check the value of the item it depends upon (as described in Example 2 above).
IMPORTANT: During SETUP MODE, changes are allowed when the DS3 LED and DS4 LED are lit for 2 seconds (as described in Example 1 and 2 above). During this time, if button #1 is pushed to change one position and not the other, the value for that one position will change and the oth er will default to zero (unless a dependency prevents the zero). How­ever, if button #1 is not pushed at all during the 2 seconds that the green LEDs are lit, the configuration item will not change.
F. Manual Mode
Manual mode is used to contr ol the status of I/O channels for use in troubleshooting. See Table 38.
Enter the Manual mode by holding down the ADVANCE/ MANUAL (#2) button for at least 3 seconds until all LEDs flash and then the red LED comes on steady.
NOTE: A user can only enter the Manual mode from the RUN mode, which is entered by pushing buttons #1 and #2 for at least 3 seconds.
All EconoMi$er+ control outputs are turned off. “I/O Inputs” 1-5 can be adjusted even if the unit is in operation.
In manual mode, the yellow DS2 LED flashes once to indi­cate the I/O c han nel . Se e Table 38. If th e val u e is le ss th an 5, the yellow DS2 LED will count out the valu e using 1-secon d flashes. If the value is greater than 4, the yellow DS2 LED will count out groups of 5 at a high flash rate and then follow with the additional value at a flash rate of once per second. For example a flash of 1 indicates Compressor Relay Output 1.
Push READ/ADJUST button (#1) to read the value. The yel­low LED will flash the I/O Ch annel number being viewed.
Once the channel number is displayed it will then turn on the appropriate green LED (DS3 or DS4) to i ndicate the sta­tus of the output. For relay outputs i f the DS3 LED is on, then the output is on. If DS4 is on, then the output is off. The green DS3 and DS4 LEDs will remain on for about 2 seconds and if during this time the READ/ADJUST (#1) button is pushed, then the output will toggle to the alternate state. To change again, push the READ/ADJUST button and re peat the test or change the status of the output. As an example, for channel 5 (EconoMi$er+ control damper motor) use the READ/ADJUST button to toggle the motor from open to close in %.
At any time, the ADVANCE/MANUAL (#2) button can be used to advance to the next SET I/ O. To exit the mode, push and hold the READ/ADJUST and ADVANCE/MANUAL but­tons (#1 and #2) for more than 3 seconds.
NOTE: After exiting the Manual mode, the controller will re-initialize and start with all outputs off.
G. Error Mode
The error mode is used to indicate that an error has occurred The error is indicated by LED #1 red and #2 yellow are on steady.
Enter the RUN mode by pushing the READ/ADJUST and ADVANCE/MANUAL buttons (#1 and #2) for at least 3 seconds until all LEDs flash. Next, push and release but­ton #1 to enter the Read mode. Then push button #2 to advance to item 20 (“first most recen t err or”). De termi ne the error by reading the value in items 20 to 24 and referring to the Troubleshooting section.
One the error has been fixed, press buttons #1 and 2 for at least 3 second s to exit Read mode. All LEDs will flash.
Enter Setup mode by pressing the READ/ADJUST button (#1) for at least 3 seconds. All LEDs will flash. Push the ADVANCE/MANUAL button (#2) to advance to item 20. Push READ/ADJUST to read item 20.
To reset the error code while the green DS4 LED is on, press the READ/ADJUST button (#1) once. In addition to resetting the error mode, this will er ase all error codes. Cycling the power will also erase the error code.
XV. ECONOMI$ER+ CONFIGURATION
For most applications, the factory setting will be used to con­trol the EconoMi$er+. However, there are 19 diff erent vari­ables that can be used to co nfig ure the contr ol for wide r an g e of applications. The factory settings and variable s are shown in Table 37.
43
IMPORTANT: There is no way to reset/restore the factory default c onfig urati ons; us e ca utio n when makin g chang es to any set point or operational variabl e.
The EconoMi$er+ control accepts an occupied/unoccupied switch input. This input is used to control the occupied and unoccupied minimum ventilation damper position as shown in Table 37 items 2 (ECONOMIN_SP) and 3 (U_ECONOMIN_SP). These va lues represent the minimu m damper position. In addition, the controls allows for different modes of compressor operation in the unoccupied mode. Using item 13 in Table 37 (OCC_MODE), the user can select one of the following unoccupied modes:
• No unoccupied cooling
• Unoccupied free cooling (Econ oMi$er+)
• Unoccupied free cooling and mechanical cooling The EconoMi$er+ will control the cooling operation of the
unit based on the demand from the thermostat outpu ts Y1 and Y2. The EconoMi$er+ will monitor the fan output G, but will not control the fan directly. Note that G must be ener­gized for any cooling to take place. Gas or electric heating will be controlled dire ctly from the thermostat.
When a demand for coo ling occurs, the control will check to see if it is in the occupied or unoccupied mode. Depen ding on the configuration, the control will move the outside air damper to the ventilati on position. If the outside air co ndi­tions are acceptable, then the control will use the EconoMi$er+ for free cool ing. If the supply air temperature does not meet the configurable set point, then the control will turn on additional stages of mechanical cooling. Several compressor sequences can be used depending on the applica­tion requiremen ts; these will be covered in t he mechanical compressor staging section.
A. Compressor Configuration and Control
The EconoMi$er+ control can support from 1 to 4 compressor stages. For the 3 to 12
1
/2 ton units, there will only be 1 or 2 stages of compressor cooling, so the control is factory configured for 2 stages. There is no difference between 1 and 2 stages. The control also provides the option to configure for high sensible o r hi gh latent loads , but for units with o nl y t wo compressors this option does not apply.
Compressors are co nfigured using item 10 (STAGE_TYPE) in Table 37. The control also has the capability of controlling directly to Y1 and Y2 inputs. The contr ol can be configured to control to the leaving air te mperatur e using Y1 and Y2 as a low cool and high cool demand based on the supply air set point and the rate of ch ange of supply air tem perature. For low cool the leaving air temperature set point will be SAT_SP+2° F. For high cool the leaving air temperature set point will be the supply air temperature set point (SAT_SP).
To use this option, configure the compressor sequencing vari­able (STAGE_ TYPE ) to a valu e of 3. Con figur e the supply air temperature set point (SAT_SP) to the desired leaving-air temperature.
NOTE: The supply air temperature set point is also the tem­perature used for EconoMi$er+ control.
The logic will control the operation of the compressors depending on the configuration selected. If free cooling can be used, then the compressors will be integrated with the EconoMi$er+ to provide the lowest cost cooling control. The logic includes time guards on the compressors to provide a minimum of 3 minutes on and 3 minutes off time. The con­trol will also prevent two compressors from starting at the same time. The lo gic use s the EconoMi $er+ to prev ent r apid cycling of the compressors and l ow air temperatures.
B. Ventilation Air and Free Cooling
In order for the EconoMi $er+ to control ventilation air and free cooling, several items must be configured.
EconoMi$er+ Type First, select the EconoMi$e r+ control type that will be used.
This is the EconoMi$er+ Type function (ECONO_TYPE) defined by item 5 in Table 37. The choices are:
1. Vent only — This is used to have just ventilation con­trol. The EconoMi$er+ will not provide free cooling, but the occupied and unoccupied minimum positions can be used.
2. Proportional — In this configuration, full proportion­al EconoMi$er+ control will be used. When EconoMi$er+ free cooling cannot be used, the damp­ers will be set t o the approp riate occupied and unoc­cupied minimum positions.
3. Three-Position — This mode of EconoMi$er+ is used to provide a mini mum venti lation Ec onoMi$e r+ posi­tion and a fixed free cooling or high ventil ation posi­tion. The high ventilation position is controlled by the optional Remote EconoMi$er+ Enable Switch Input connected to terminals 11 and 12 on T3.
Supply Air Temperature Set Point Once the type of Econ oMi$e r+ cont rol ha s been selecte d, the
user will need to set the Supply Air Temperature set point (SAT_SP). The SAT_SP has a range of 40 to 65 F.
NOTE: This will be the set point when both Y1 and Y2 are closed. When just Y1 is closed, the set point will be 2 F higher.
Minimum Damp er Position Set the occupied minimum damper position
(ECONOMIN_SP) and unoccupied minimum position (U_ECONOMIN_SP). These should be set to provide the ventilation requirements at full occupancy as defined by the building specifications. When demand ventilation is used, the control will close the dampers below this position based on measured CO
levels in the space to provide additional
2
operation savings . The control wil l also a llow for the use o f a remo te mini mum
position potentiometer. This will only adjust the Occupied Minimum position. If used, the software set point ECONOMIN_SP sho uld be se t to 0 as the contr ol wi ll use the largest set point.
The damper position is not linear with the amount of outside air, so the user will need to set the position of the EconoMi$er + acco rdi ngly. It is best to use the fo llow ing equ a­tion and measured data to set the position:
OA =
SAT – RAT OAT – RAT
*100
OA = % outdoor air SAT = supply air temperature RAT = return air temperature OAT = outdoor air temperature
The SAT and OAT val ues can be read from the control and, if the unit is equipped with an RAT sensor, then all three val­ues can be read. For the calculation to work properly, there should be at least a 10° F differen ce between the OAT and RAT temperatures.
Maximum Damper Position Set the maximum EconoMi$er+ position. Normally this is
set at 100%. If using 3-position control or there is a reason not to use 100% outside air, this can be set using the EconoMi$er+ Maximum Position (MAX_POS_SP).
44
Compressor Lockout Temperature Set the Compressor Lockout Temperature. The Compressor
Lockout Temperature (CMP_LOCK) is used to prevent com­pressor from running at low ambient conditions when an EconoMi$er+ can easily satisfy the load.
EconoMi$er+ Changeover Control Determine the type of EconoMi$er+ changeover control
which will be used to enable and disable free cooling. This is done using the EconoMi$er+ Changeover Type.
1. Switch — This changeover setting is used when a remote signal from an energy management system will enable and disable the EconoMi$er+. This is done through a remote EconoMi$er+ enable switch.
2. Outdoor Dry Bulb — For this changeover setting, the EconoMi$er+ w ill be enabled based on the outsid e -air temperature. The EconoMi$er+ is shipped with an outside air tempe rature sensor. The outside air tem­perature set point can be configured by th e user. The EconoMi$er+ will be disabled when the outdoor-air temperature rises above the set po int. The co nfigura­tion variable is the EconoMi$er+ Changeover set point (OAT_SP).
3. Differentia l Dry Bulb — For this changeover setting, the EconoMi$er+ will be en abled whenever the out­side-air temperature is lower than the return-air temperature. No configuration of set points is re­quired other than to select the differential dry b ulb function.
4. Outdoor Enthalpy — For this changeover setting, the control will enable the EconoMi$er+ based on the outside-air enthalpy curves as shown in Fig. 29. Us­ing the EconoMi$er+ Changeover set point (ENTHALPY_SP), select curves A, B, C or D. The control will then us e the EconoMi$er+ at condi­tions below the curve. The control uses the OAT and optional humidity sensor to calculate the enthalpy and also has the A, B, C, and D curves stored in memory.
5. Differential Enthalpy — For this changeover setting, the EconoMi$er+ will be enabled based o n the com­parison of the enthalp y of the return air and outs ide air. If the outside air enthalpy is lower than the re­turn air, then the EconoMi$er+ will be enabled. To use this option, an accessory outside air humidity sensor, a return air dry bulb sensor and a return air humidity sensor must be ordered and installed. No configuratio n of set points is required other th an to select the function.
C. Demand Ventilation Configuration
The EconoMi$er+ control has demand ventilation control capability when using an IAQ sen sor. The indoor air qualit y (IAQ) is measured using a CO
sensor. The IAQ sensor can
2
be field-installed in the return duct or the occupied space. The EconoMi$er+ control algorithm modulates the po sition
of the EconoMi$er+ damper between two user configurations depending upon the relationship between the IAQ and the Outdoor Air Quality (OAQ). The lower of these two positions is referred to as the Min imum IAQ Min imum EconoM i$er+ Position (IAQMIN_SP).
The higher position is referred to as the Occupied EconoMi$er+ Minimum Position (ECONOMIN_SP). The IAQMIN_SP should be set to an EconoMi$er+ p osition that brings in enough fresh ai r to remove conta minants and CO generated by sources other than people. The ECONOMIN_SP should be set to an EconoMi$er+ positi on that brings in enough fresh air to remove contaminants and
CO
generated by all sources including people a t the design
2
value for maximum occupancy. A reference differential CO
level above the outside CO
2
level is used as the starting point for IAQ control and another reference differential level for maximum ventilation at design occupancy is used for the end of IAQ control. Between these points the control wi ll modulate the da mpers open from the IAQMIN_SP and the ECONOMIN_SP set­points. The damper position will never go above ECONOMIN_SP or below IAQMIN_SP.
The control does not measure the outdoor IAQ reference level as these levels are relatively constant. The installer should take a measurement at start-up of the unit and enter this value into the control using the Outdoor Air IAQ refer­ence level configuration.
The control is configured for air quality sensors which pro­vide 4 mA at 0 ppm and 20 mA at 2000 ppm. If a sensor has a different range, these bounds must be reconfigured.
To configure the control for an IAQ sensor perform the fol­lowing steps:
1. Determine the Occupied EconoMi$er+ Minimum position (ECONOMIN_SP) and enter it into the control.
2. Determine the IAQ minimum EconoMi$er+ position (IAQMIN_SP) and enter it into the control.
3. Enable IAQ control using IAQ Enable (IAQ_FLG).
4. Determine the Outdoor Air IAQ Reference (OAQ) and enter it into the control.
NOTE: The value entered into the co ntrol will be the CO
ppm level divided by 10. For example, 400 ppm
2
would be entered as 40.
5. Determine the lower control point differential level (DAQLO) and enter it i nto the control. This is a dif­ferential level so if the desired level to start IAQ con­trol is 500 ppm and the OAQ reference level is 400 then a value of 100 would be used.
NOTE: The value entered into the co ntrol will be the CO
ppm level divided by 10. For example 100 ppm
2
would be entered as 10.
6. Determine the upper control point differential level (DAQHI) and enter it into the control. This is a differ­ential level so if the desired leve l to star t IAQ co ntrol is 1100 ppm and the OAQ reference level is 400 then a value of 700 would be used.
NOTE: The value entered into the co ntrol will be the CO
ppm level divided by 10. For example 700 ppm
2
would be entered as 70.
D. Power Exhaust Configuration
The EconoMi$er+ can control up to 2 stages of power exhaust. Power exhaust activation is done through config­urable damper pos ition set points. The first s tage of power is controlled by relay C4 on the EconoMi$er+ board. The acti­vation point for the first stage is set using the Power Exhaust Stage 1 Activation set point (PE_SP1 ). The second stage of powe r exhaust mus t be set at a v alue greater than the first stage. It is configured using the Power Exhaust Stage 2 Activation set point (PE_SP2).
XVI. OPERATING SEQUENCE
A. Cooling, Units without EconoMi$er+
When thermostat calls for cooling, terminals G and Y1 and
2
the compressor contactor (C) are energized. The indoor (evaporator) fan motor (IFM), compressor, and outdoor (con­denser) fan motor (OFM) start. The OFM runs continuously
2
45
while the unit is in cooling. When the thermostat is satisfied, C is deenergized and the compressor and OFM shut off. After a 30-second delay, the (IFM) shuts off. If the thermostat fan selector switch is in the ON position, the evaporator motor will run continuously.
B. Heating, Units without EconoMi$er+
When the thermostat call s for heatin g, terminal W1 is ener­gized. The induced-draft motor is energized and the burner ignition seque nce begins. The indoor (evaporator) fan m otor (IFM) is energized 45 seconds after a flame is ignited. When additional he at is n eeded, W 2 is en ergized and t he high- fire solenoid on the main gas valve (MGV) is energized. When the thermostat is sati sfied and W1 is deenergiz ed, the IFM stops after a 45-second time-off delay.
C. Cooling, Units with EconoMi$er+
For EconoMi$er+ operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position.
When the EconoMi$er+ control is the occupied m ode and a call for cooling exists (Y1 on the thermostat), the control will first check for indoor fan operat ion. If the fan is not on, th en cooling will not be activated. If the fan is on, then the control will open the EconoMi$er+ damper to the minimum position.
On the initial p ower to the EconoMi$er+ board, it will ta ke the damper up to 2
1
/2 minutes before it begins to position itself. With subsequent fan signal (G) to the board, the changed in damper position will take up to 30 seconds to ini­tiate. Damper movement from full closed to full open (or vice versa) will take 2
1
/2 minutes.
If the damper is in the process of a change (for example going to 100% open) and the signal (G) is turn ed off, the damper will continue to open to 100% before it closes (due to no fan signal [G]).
If free cooling c an be used as determin ed from the appr opri­ate changeover command (switch, dry b ulb, enthalpy curv e, differential dry bulb, or differential enthalpy), then the con­trol will modulate the dampers open to main the supply air temperature set point plus 2° F.
If there is a further demand for cooli ng (coo li ng secon d st age — Y2 is energized), then the control set point for the l eaving air will be set at the supply air set point to increase the cool­ing capacity. If this cannot satisfy the load then the control will bring on comp ressor stages as needed to maintain the supply air temperatu re set point. The EconoM i$er+ damper will be locked o pen at 100% or the maximu m damper posi­tion set point.
To ensure that there is oil return, the compressors will operate for a t least 3 mi nutes. If, dur ing th is pe riod , th e lea v­ing temperature dr ops below the set point by 5 F, then the EconoMi$er+ dampers will be closed to 60% until the com­pressor is turned off to avoid cold leaving air temperatures.
If the conditions are not suitable for free cooling then the EconoMi$er+ dampers will be closed to the minimum venti­lation posit ion.
Compressor stages will be used to co ol the air. If the control is configured for direct control by Y1 and Y2, then the stages will sequence based on the demand of Y1 and Y2. If the control is configured for leaving air temperature control, then Y1 will maintain the leaving air temperature at the supply air set point plus 2° F. If Y1 and Y2 are closed, then the leaving air will be controlled to the supply air set point. If Y2 is closed and Y1 is open, then control will shut down and indicate an error due to a thermostat failure or improper wiring of the thermostat.
If the unit is in the unoccupied m ode, then the control of the temperature will depend on the unoccupied free cooling configuration: no unoccupie d cool ing, unoccupied free cooling with any mechanical cooling, or unoccupied free and mechanical cooling. If free cooling is enabled, then the con­trol will check if free cooling can be used. The EconoMi$er+ will then control to the leaving air temperature set point plus 2 F for a Y1 command, or the leaving air temperature set point for a Y1 and Y2 command. If me chanical coo ling is allowed to be used, then the control will then bring on addi­tional stages o f me chani cal coo lin g i f f ree co ol in g c annot sa t­isfy the load.
If the EconoMi$er+ control:
• is in the occupied mode
• is configured to use demand ventilation
• cannot use free cooling
• has return air or space CO
levels below the DAQLO
2
limit,
then the EconoMi$er+ damper position will be set to the IAQMIN_SP set point. If the CO2 level rises above the DAQLO limit, then the dampers will modulate open in a lin­ear relationship un til the return air o r space CO
levels are
2
at or above the DAQ HIG H limi t. The dampe r posit ion wi ll be at the ECONOMIN_SP set point.
When the EconoMi$er+ is being used for free cool ing and the position exceeds the power exhaust set point, then the con­trol will turn on the appropriate power exhaust fans. Refer to Fig. 23 for barometric relief capacit y, Fig. 24 for outdoor air leakage, and Fig. 25 for pressure drop.
Unoccupied and Occupied Minimum Position Control There is an unoccupied minimum damper position and an
occupied minimum damper position on the EconoMi$er+ controller. When the HVAC fan is off the outdoor air damper will always be closed. W hen the f an is on an d in the unoccu ­pied mode, the outdoor air damper will be at the unoccupied minimum position . When the fan is on (G call ) and in the occupied mode, the outdoor air damper will be at the occu­pied minimum position.
A jumper wire is factory-installed to force the unit into occupied configuration whenever G or Y1 are closed. Without the jumper wire, the unit will alw a ys be in unoccupi ed mode.
The 2 minimum position settings are also used in the IAQ sequence of operation. See Indoor Air Quality Sensor on page 18.
NOTE: The minimum pos ition signal tak es priority over the maximum position signal. If the maximum damper position is set below the min imu m damper position, the Econ oMi $e r+ controller will maintain the actuator at minimum position.
Adjust the unoccupied minimum position to allow the mini­mum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F (6 C) temperature difference between the outdoor and return air temperatu res.
To determine the unoccupied minimum position setting, per­form the following procedure:
Calculate the app ropriate supply-ai r temperature usin g the following formula: (T O x OA) + (T R x RA) = TM
TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Supply-Air Temperature
46
As an example, if local codes requ ire 10% outdoor air duri ng occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F:
(60 x 0.10) + (75 x 0.90) = 73.5 F Carefully adjust the unoccupied minimum position until the
measured supply-air temperature matches the calculated value. Then, carefully adjust the occupied minimum position set point on the controller until the desired position is reached.
D. Heating, Units with Economi$er+
When the room temperature calls for heat through terminal W1, the indoor (evaporator) fan contactor (IFC) and heater contactor no. 1 (HC1) are energized. On units equipped for 2 stages of heat, when additional heat is needed, W2 is ener­gized and the hig h-fire sole noid o n the main gas v alve (MG V) is energized. The economizer damper moves to the minimum position. When the thermostat is satisfied, the damper moves to the fully closed position.
SERVICE
CAUTION: When servicing unit, shut off all electri-
cal power to unit and install lockout tag to avoid shock hazard or injury from rotating parts .
I. CLEANING
Inspect unit interior at the beginning of heating and cooling season and as operating conditions require.
A. Evaporator Coil
1. Turn unit power off and install lockout tag. Remove evaporator coil access panel.
2. If economizer or two-position damper is installed, remove economizer by disconnecting Mole x plug and removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish­washer detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-flush toward return-air section to remove foreign material. Flush condensate pan after completion.
5. Reinstall ec onomizer and filters.
6. Reconnect wiring.
7. Replace access panels.
B. Condenser Coil
Inspect coil mon thly. Clean condenser coil annua lly, and as required by location and outdoor air conditions.
One-Row Coils (Size 036) Wash coil with comme rcia l coi l clea ner. It is not necessary to
remove top panel. 2-Row Coils (Sizes 048-073) Clean coil as follows:
1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 37. To hold top panel open, place coil corner post between top panel and center post. See Fig. 38.
4. Remove screws securing coil to compressor plate and compressor access panel.
5. Remove fast ener holdi ng coil sect ions togethe r at re­turn end of condenser coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section. See Fig. 39.
6. Use a water hose or other suitable equipment to flush down between the 2 coil s ections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
7. Secure inner and outer coil rows together with a field­supplied fastener.
8. Reposition the outer coil se ction and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws.
C. Condensate Drain
Check and clean each year at star t of coo lin g sea so n. I n win ­ter, keep drain dry or protect against freeze-up.
D. Filters
Clean or rep lace at s tar t of e ach h eati ng an d co oling seas on, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
E. Outdoor-Air Inlet Screen
Clean screen with stea m or hot water and a mild deter gent. Do not use disposable filters in place of screen.
Fig. 37 — Cleaning Condenser Coil
Fig. 38 — Propping Up Top Panel
47
Fig. 39 — Separating Coil Sections
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at the factory.
B. Fan Motor Bearings
Fan motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of con­denser or evaporator fan motors is required.
III. BLOWER BELT ADJUSTMENT
Inspect blower b elt for we ar, proper belt tension, and pu lley alignment as conditions require or at the beginning of each heating and air conditioning season.
Refer to Step 9 — Adjust Evaporator-Fan Speed on page 24 for adjustment and alignment procedures.
Check belt tension at least once each heating or cooling sea­son or as conditions require. Adjust as required.
IV. MANUAL OUTDOOR-AIR DAMPER
If outdoor-air damper blade adjustment is required, see Manual Outdoor-Air Damper section on page 14.
V. ECONOMI$ER+ ADJUSTMENT
Refer to Optional EconoMi$er+ section on page 15.
VI. CONDENSER-FAN ADJUSTMENT (Fig. 40)
Shut off unit power supply. Remove condenser-fan assembly (grille, motor, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 40. Tighten setscrews and replace condenser-fan assembly.
VII. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Compressor must run a minimum of 10 minutes before adjus ting or checki ng charge.
Unit panels must be in place when unit is operating during charging procedure.
Fig. 40 — Condenser-Fan Adjustment
A. No Charge
Use standar d evacuating technique s. After ev acuating sys­tem, to 500 microns, weigh in the specified amount of refrig­erant. (Refer to Table 1.)
B. Low-Charge Cooling
Using Cooling Charging Charts, Fig. 41-44, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different fr om type normally used. Charts are based on charging the units to the co rrect super­heat for the various operating c onditio ns. Accurate pressure gage and temperature sensing device are required. Do not use pocket type thermometers for measuring surface temper­atures as they are not designed for this type of measure­ment. Connect the pressure gage to the service port on the suction line. Moun t the temperature sensing device on the suction line and insulate it so that outdoor ambient tempera­ture does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit.
C. To Use Cooling Charging Chart
Take the outdoor ambient tempera ture and re ad the sucti on pressure gage. Refer to chart to determine what suction tem­perature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the su ction pressure as charge is adjusted.
EXAMPLE: (Fig. 43)
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 psig
Suction Temperature should be . . . . . . . . . . . . . . . . . . . 76 F
(Suction Temperature may vary 5 F.)
VIII. FLUE GAS PASSAGEWAYS
To inspect the flue collector box and upper areas of the hea t exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section on pa ge 49.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
48
IX. COMBUSTION-AIR BLOWER
Clean periodically to assure proper airflow and heating effi­ciency. Inspect blow er whee l ev ery f all and peri od ical ly d uri ng heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To access burner section, slide the sliding burner partition out of the unit.
To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 7 screws that attach induced-draft motor housing to vestibule plate (Fig. 45).
3. The blower wheel can be cleaned at this point. If ad­ditional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, remove 2 setscrews.
5. To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate.
6. To reinstall, reverse the pro c edure outlined above.
X. LIMIT SWITCH
Remove blower access panel (Fig. 7). Limit switch is located on the fan deck.
XI. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is loc ate d in the control box (Fig. 11). The IGC contains a self-diagnostic LED (light-emitting diode). A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. When a break in p ower occ urs , the IGC will be reset (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. The LED error code can be observed through the viewport. During servicing refer to the label on the control box co ver or Table 39 for an explanation of LED error code descriptions.
If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds.
Table 39 — LED Error Code Description*
LED INDICATION ERROR CODE DESCRIPTION
ON Normal Operation
OFF Hardware Failure
1Flash† Evaporator Fan On/Off Delay Modified
2Flashes Limit Switch Fault 3Flashes Flame Sense Fault 4Flashes 4 Consecutive Limit Switch Faults 5Flashes Ignition Lockout Fault 6Flashes Induced-Draft Motor Fault 7Flashes Rollout Switch Fault 8Flashes Internal Control Fault 9Flashes Internal Software Processor Fault
LEGEND
LED — Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more than one error
code exists, all applicable codes will be displayed in numerical sequence.
†Indicates a code that is not an error. The unit will continue to operate when this
code is displayed.
IMPORTANT: Refer to Troubleshooting Tables 41-43 for additional information.
XII. MAIN BURNERS
To access burners, remove burner access pa nel a nd slide out burner partition. At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.
CAUTION: When working on gas train, do not hit or
plug orifice spuds.
A. Removal and Replacement of Gas Train (Fig. 45-47)
1. Shut off manual gas valve.
2. Shut off power to unit and tag disconnect.
3. Slide out burner partition.
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor wires and sensor wires at the Inte­grated Gas Unit Controller (IGC) (see Fig. 11).
7. Remove the 2 screws that attach the burner rack to the vestibule pl ate (Fig. 45).
8. Slide the burner tray out of the unit (Fig. 46).
9. To reinstall, reverse the procedure outlined above.
B. Cleaning and Adjustment
1. Remove burner rack from unit as described in Removal and Replacement of Gas Train section, abo ve.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush clean burners and cross-over port as required.
4. Adjust spark gap. See Fig. 47.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and Replacement of Gas Train section, above.
XIII. HIGH-PRESSURE SWITCH
Located on the compressor hot gas line is a high-pressure switch containing a Schrader core depressor. This switch opens at 428 psig and closes at 320 psig. No adjustment is necessary. Refer to Table 1.
XIV. LOSS OF CHARGE SWITCH
Located on the cond enser liquid line is a low-pressure switch which functions as a loss-of-charge switch. This switch con­tains a Schrader core depressor. This switch opens at 7 psig and closes at 22 psig. No adjustment is necessary. Refer to Table 1.
XV. FREEZESTAT
Located on the “hair pin” end of the evaporator coil is a bimetal temperature sensing switch. This switch protects the evaporator coi l from f reeze -up due to lack of ai rflow. The switch opens at 30 F and closes at 45 F. No adjustment is necessary. Refer to Table 1.
XVI. REPLACEMENT PARTS
A complete list of repl acement parts may be obtained from any Bryant distributor upon request.
49
3 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10162127
100
90
80
70
689
621
552
483
OUTDOOR
TEMP
FC
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
45 7
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
414
345
276
207
Fig. 41 — Cooling Charging Chart, 580F036
4 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10162127
100
90
689
621
SUCTION LINE PRESSURE (KILOPASCALS)
OUTDOOR
TEMP
FC 125 115
105 41
95 35
85 29
52 46
80
70
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 42 — Cooling Charging Chart, 580F048
50
552
483
414
345
276
207
75
65
55
45 7
SUCTION LINE PRESSURE (KILOPASCALS)
24
18
13
5 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10 16 21 27
100
90
80
70
689
621
552
483
OUTDOOR
TEMP
FC
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13 45 7
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 43 — Cooling Charging Chart, 580F060
6 TON UNIT (60 Hz) CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10 16 21 27
100
90
80
70
414
345
276
207
SUCTION LINE PRESSURE (KILOPASCALS)
689
621
552
483
OUTDOOR
TEMP
FC 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 44 — Cooling Charging Chart, 580F072, 073
51
414
345
SUCTION LINE PRESSURE (KILOPASCALS)
276
207
INDUCED­DRAFT MOTOR MOUNTING PLATE
BURNER SECTION
INDUCED­DRAFT MOTOR
MANIFOLD PRESSURE TAP
Fig. 45 — Burner Section Details
ROLLOUT SWITCH
FLUE EXHAUST
VESTIBULE PLATE
BLOWER HOUSING
GAS VALV E
Fig. 46 — Burner Tray Details
580F036-073 — 74,000 BTUH INPUT
LOW HEAT
580F036-060 (Low NO
) — 60,000 BTUH INPUT
x
MEDIUM AND HIGH HEAT 580F036-073 — 115,000 BTUH INPUT 580F048-073 — 150,000 BTUH INPUT
580F036-060 (Low NO
580F048-060 (Low NO
) — 90,000 BTUH INPUT
x
) — 120,000 BTUH INPUT
x
Fig. 47 — Spark Adjustment
52
TROUBLESHOOTING
I. ECONOMI$ER+ TROUBLESHOOTING
The EconoMi$er+ control has built-in diagnostics. The con­trol can detect and display 10 different diagnostic codes as shown in Table 40. The us er ca n al so us e the integra ted dis­play to check the status of all the inputs and outputs and run the manual control mode to check the operation of the EconoMi$er+ and compressors.
Table 40 — EconoMi$er+ Error Codes
NO. DESCRIPTION CRITERIA
1 SAT Sensor Failure Temperature <–40 F or Greater Than 250 F 2 RAT Sensor Failure Temperature <–40 F or Greater Than 250 F 3 OAT Sensor Failure Temperature <–40 F or Greater Than 250 F 4 ORH Sensor Failure Read Less Than 2 mA or Greater Than 22 mA 5 IRH Sensor Failure Read Less Than 2 mA or Greater Than 22 mA 6 IAQ Sensor Failure Read Less Than 2 mA or Greater Than 22 mA 7 Y2OnY1 Off Wiring Error 8 Micro Fails E2 Tests Hardware/Software Check
* Micro Fails RAM Test Hardware/Software Check
Micro Fails ROM Tests Hardware/Software Check
LEGEND
IAQ — Indoor Air Quality IRH — Indoor Relative Humidity OAT — Outdoor Air Temperature ORH — Outdoor Relative Humidity RAT — Return Air Temperature SAT — Supply Air Temperature
*If there is a RAM failure DS1+DS3/DS2+DS4 will alternately flash.
†If there is a ROM failure DS1+DS2/DS3+DS4 will alternately flash.
A. Error Code 1 — SAT Sensor Failure
Error Criteria An SAT Sensor Failure error will occur if the sensor is
shorted or faulty. If the measured temperature reads below –40 F or above 250 F an error will occur.
Required Action If an error occurs, then the control will default to Mode 2
compressor stage contro l where Y1 and Y2 have direct con­trol of the compressors. Use of free cooling is disabled and the EconoMi$er+ will be set to the minimum damper posi­tion for either the occupied or unoccupied mode of operation. Replace sensor if faulty.
Reset Method The error will automatically reset after the value has
returned to a normal level. The alarm has to be cleared from the display in the Setup mode or a power reset.
B. Error Code 2 — RAT Sensor Failure
Error Criteria The RAT Sensor failure error is only applicable the unit
has been configured for EconoMi$er+ changeover methods 3 (differential dry bulb) or 5 (differential humidity). For other modes it shou ld be ignored . If the sensor is shorted o r faulty, then the measured temperature will be below –40 F or above 250 F and the error will occur.
Required Action If this error occurs, then change the default EconoMi$er+
changeover control to method 2 (dry bulb changeover con­trol) or replace sensor.
Reset Method This error will automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Se tup mode.
C. Error Code 3 — OAT Sensor Failure
Error Criteria An OAT Sensor Failure error occurs if the sensor is short ed
or faulty, then the measured temperature will be below –40 F or above 250 F.
Required Action If this error occurs disable the economizer and set the econo-
mizer to the minimum economizer position. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
D. Error Code 4 — ORH (Outdoor Relative Humidity) Sen­sor Failure
Error Criteria If the unit is configured for economizer changeover type 3 or
4, and the input signal is less than 2 mA or greater than 22 mA, then the sensor is faulty and an error will occur.
Required Action If this error occurs, switch the EconoMi$er+ to dry bulb
changeover control. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
E. Error Code 5 — IRH (Indoor Relative Humidity) Sensor Failure
Error Criteria This error occurs if th e unit is configured for EconoMi$er+
changeover type 5 and the input signal is less than 2 mA or greater than 22 mA (faulty sensor).
Required Action If this error occurs, switch the EconoMi$ er+ to differential
dry bulb changeover control. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
F. E rr or C od e 6 — I AQ Sensor Failure
Error Criteria This error occurs if th e unit is configured for IAQ demand
ventilation control and the input signal is less than 2 mA or greater than 22 mA (faulty sensor).
Required Action If this error occurs, disable the IAQ control routine and
default to the standard EconoMi$er+ minimum position. Reset Method This error should automatically reset after the value has
returned to a normal level. The alarm will have to be cleared from the display in the Setup mode or by a power reset.
G. ErrorCode7—Y2onWith Y1 Off
Error Criteria This error occurs if Y 2 is turned on and Y1 is of f. This indi-
cates that there is a wiring error at the thermostat connec­tions. This alarm sho uld be ignored fo r the first 20 sec onds of operation so tha t it does no t co nfl ic t wit h th e sp ec ial pr odu c­tion test mode.
Required Action Shut the unit off and check wiring.
53
Reset Method This error must be manually reset and requires a power
reset.
H. Error Code 8 — E2 Test Failure
Error Criteria This error occurs if internal hardware detects an E2 failure. Required Action Shut the un it off. Reset Method This error must be manually reset and requires a power
reset.
I. Error Mode
When an error occurs, the red and yellow LEDs both come on steady. To determine the error, follow these steps:
1. Enter the Run mode by pushing buttons #1 and #2 for at least 3 seconds until all LEDs flash.
2. Press and release the #1 button to enter the Read mode.
3. Push the ADVANCE/MANUAL (#2) button to ad­vance to item number 20, “1st Most Recent Error.” Determine the error(s) by reading the values in items 20-24 and referring to the error codes described above.
4. Fix the error(s).
5. Press buttons 1 and 2 to exit read mode. Enter Setup mode by pressing button #1 for at least 3 seconds un­til all the LEDs flash.
6. Push button #2 to advance to item number 20.
7. To reset the error code while the green DS4 LEDS is ON, press the READ/ADJUST (#1) button once. This resets the error mode and erases all repaired error codes.
NOTE: Cycling power to the board will al so erase the repaired error codes.
J. RAM Test Failure
Error Criteria If internal hardware detects a RAM failure, this alar m will
be displayed by alternately flashing DS1+DS3 and DS2+DS4.
Required Action Shut the unit off. Reset Method This error must be manually reset and requires a power
reset.
K. ROM Test Failure
Error Criteria If internal hardware detects a ROM failure, the alarm is dis-
played by alternately flashing DS1+DS2 an d DS3+DS4. Required Action Shut the unit off. Reset Method This error must be manually reset and requires a power
reset.
L. Unit Always in Unoccupied Mode
A jumper wire is factory-installed to force the unit into o ccu­pied configurat io n wh ene ver G or Y1 are clos ed. Withou t the jumper wire, the unit will always be in unoccupied mode. Check the wire. An occupied/unoccupied switch may be installed in pl ace of the j ump er. Ch eck the wi ring and se tting of the switch.
II. UNIT TROUBLESHOOTING
Refer to Tables 41-43.
54
Table41—LEDErrorCodeServiceAnalysis
SYMPTOM CAUSE REMEDY
Hardware Failure. (LED OFF)
Fan ON/OFF Delay Modified (LED/FLASH)
Limit Switch Fault. (LED 2 flashes)
Flame Sense Fault. (LED 3 flashes)
4ConsecutiveLimit Switch Faults. (LED 4 flashes)
Ignition Lockout. (LED 5 flashes)
Induced-Draft Motor Fault. (LED 6 flashes)
Rollout Switch Fault. (LED 7 flashes)
Internal Control Fault. (LED 8 flashes)
Internal Software Fault. (LED 9 flashes)
CAUTION: If the IGC must be replaced, be sure to ground
yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.
Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat exchanger warm-up period before fan-on delay expires. Limit switch opens within three minutes after blower-off delay timing in Heating mode.
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be present.
Inadequate airflow to unit. Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for 15 minutes.
IGC does not sense that induced-draft motor is operating.
Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue to lockout unit.
Microprocessor has sensed an error in the software or hardware.
Internal Software Processor fault. Fault code will automatically reset after one hour. Can be immediately
transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure unit’s external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1 — White, PIN 2 — Red, PIN 3 — Black.
Check gas valve operation. Ensure that induced-draft blower wheel is prop­erly secured to motor shaft. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
reset by resetting unit power supply.
IMPORTANT:
troubleshooting analysis.
IGC Integrated Gas Unit Controller LED — Light-Emitting Diode
Refer to Table 42 — Heating Service Analysis for additional
LEGEND
Table 42 — Heating Service Analysis
PROBLEM CAUSE REMEDY
Burners Will Not Ignite. Misaligned spark electrodes. Check flame ignition and sensor electrode positioning. Adjust as needed.
No gas at main burners. Check gas line for air, purge as necessary. After purging gas line of air, allow
Water in gas line. Drain water and install drip leg to trap water. No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control circuit. Check transformer. Transformers with internal overcurrent protection require a
Miswired or loose connections. Check all wiring and wire nut connections. Burned-out heat anticipator in thermostat. Replace thermostat. Broken thermostat wires. Run continuity check. Replace wires, if necessary.
Inadequate Heating. Dirty air filter. Clean or replace filter as necessary.
Gas input to unit too low. Check gas pressure at manifold. Clock gas meter for input. If too low, increase
Unit undersized for application. Replace with proper unit or add additional unit. Restricted airflow. Clean filter, replace filter, or remove any restrictions. Blower speed too low. Use high speed tap, increase fan speed, or install optional blower, as suitable
Limit switch cycles main burners. Check rotation of blower, thermostat heat anticipator settings, and temperature
Too much outdoor air. Adjust minimum position.
Poor FlameCharacteristics. Incomplete combustion (lack of combustion
Burners Will Not Turn Off. Unit is locked into Heating mode for a one
air) results in: Aldehyde odors, CO, sooting flame, or floating flame.
minute minimum.
gas to dissipate for at least 5 minutes before attempting to relight unit. Check gas valve.
cool down period before resetting.
manifold pressure, or replace with correct orifices.
for individual units.
rise of unit. Adjust as needed.
Check economizer operation. Check all screws around flue outlets and burner compartment. Tighten as nec-
essary. Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust gas line or manifold
pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Wait until mandatory one minute time period has elapsed or re-
set power to unit.
55
Table 43 — Cooling Service Analysis
PROBLEM CAUSE REMEDY
Compressor and Condenser Fan Will Not Start.
Compressor Will Not Start But Condenser Fan Runs.
Compressor Cycles (Other Than Normally Satisfying Thermostat).
Compressor Operates Continuously.
Excessive Head Pressure. Dirty air filter. Replace filter.
Head Pressure Too Low. Low refrigerant charge. Check for leaks; repair and recharge.
Excessive Suction Pressure. High head load. Check for source and eliminate.
Suction Pressure Too Low. Dir ty air filter. Replace filter.
Evaporator Fan Will Not Shut Off. Time off delay not finished. Wait for 30-second off delay. Compressor Makes Excessive
Noise (580F072 and 073 Scroll Only).
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or
control relay. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Faulty wiring or loose connections in compressor
circuit. Compressor motor burned out, seized, or internal
overload open. Defective run/start capacitor, overload, start relay. Determine cause and replace. One leg of three-phase power dead. Replace fuse or reset circuit breaker. Determine cause. Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge to
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or start relay. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty condenser-fan motor or capacitor. Replace. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak; repair and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser coil dirty or restricted. Clean coil or remove restriction.
Dirty condenser coil. Clean coil. Refrigerant overcharged. Recover excess refrigerant. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air short-cycling. Determine cause and correct.
Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction.
Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant.
Low refrigerant charge. Check for leaks; repair and recharge. Metering device or low side restricted. Remove source of restriction. Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
Temperature too low in conditioned area. Reset thermostat. Outdoor ambient below 25 F. Install low-ambient kit.
Compressor rotating in wrong direction. Reverse the 3-phase power leads as described in the
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
nameplate.
necessary.
Start-Up section on page 37.
56
NOTES:
1. If any of the original wire furnished must be replaced,itmustbereplacedwithtype90Cwireor its equivalent.
2. Three phase motors are protected under primary single phasing conditions.
4. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap (ORN) and connect to 208 v tap (RED). Insulate end of 230 v tap.
C—Contactor, Compressor CAP Capacitor COMP — Compressor Motor EQUIP — Equipment FPT Freeze Up Protection Thermostat FU Fuse GND Ground GVR Gas Valve Relay HPS High-Pressure Switch HS Hall-Effect Sensor I—Ignitor IDM Induced-Draft Motor IFC Indoor Fan Contactor IFM Indoor (Evaporator) Fan Motor IGC Integrated Gas Unit Controller LPS Low-Pressure Switch LS Limit Switch MGV Main Gas Valve
LEGEND
OFM Outdoor (Condenser) Fan Motor OLR Overload Relay P—Plug PL Plug Assembly QT—Quadruple Terminal RS Rollout Switch SAT Supply Air Temperature Sensor TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Fig. 48 — Typical Unit Wiring Diagram
57
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring To indicate common potential only;
not to represent wiring.
PUSHBUTTONS LED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
OFF
ONES OR
TEN'S
OR ON
Names ADJUST ADV SET NO SETUP
SETUP MODE
APPENDIX A — ECONOMI$ER+ LABEL
OFF
ONES OR
TEN'S
OR ON
Actions Hold/Push Push flash, no steady flash no flash no
Each time the ADV button is pushed, the SET NO flashes the point number and then displays
the current setting
on use the ADJUST button to enter the value. (i.e., push the button 4 times to enter 4)
Then wait for the ONES indicator to turn on and enter the ONES setting
Note 1 Push and hold the ADJUST button until the SETUP indicator turns on.
Note 2 Push and release ADV button repeatedly to advance to the desired setup point.
Note 3 Once the current value has been displayed the TENS indicator will turn on steady and while it
Wait for indicator to turn off and then push read/adjust to check the setting
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
Names ADJUST MAN MAN I/O NO
MANUAL
Actions Push Hold/Push steady flash no flash no flash no
Each time the MAN button is pushed, the I/O NO flashes the I/O point number.
and off or open and closed
1 SATsensor invalid
2 RAT Sensor Invalid (only with changeover type 3&5)
3 OAT Sensor Invalid
4 ORH Sensor invalid (only with changeover type 3&4)
5 IRH Sensor invalid (only with changeover type 5)
6 IAQ Sensor Invalid (only if IAQ=1)
7 Y2onY1off
Note 1 Push and hold the MAN button until the MAN indicator turns on.
Note 2 Push and release MAN button repeatedly to advance to the desired I/O point.
NO DESCRIPTION
Note 3 After the desired I/O No is reached push and release the ADJUST to toggle the output on
Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
ALARM CODES
8 Micro Fails E2 test
note 1 Micro Fails RAM test
note 2 Micro Fails ROM test
Note 1 DS1+DS3/DS2+D4 will alternately flash
Note 2 DS1+DS2/DS3+D4 will alternately flash
PUSHBUTTONS LED INDICATORS
MODE OF OPERATION
2
1
(Green)
DS4
(Green)
DS3
(Yellow)
DS2
(Red)
DS1
Button
Button
Action flash flash flash flash
Indicators flash in sequence at .5 sec intervals
STARTUP MODE
Note 1
Names HB ECONO Y1 Y2
RUN MODE
Actions flash flash steady steady
Note 1 Heartbeat Indicator flashes to indicate proper operation of the control
Note 2 Econo indicator flashes to indicate free cooling being used
Note 3 Y1 and Y2 are on steady when a call thermostat Y1 and Y2 are closed
Note 4 ERROR - HB and Econo are on steady to indicate the presence of an error
OFF
ONES OR
TEN'S
OR ON
Names READ ADV SET NO I/O NO
Actions Push Push flash, no flash no flash no flash no
READ MODE
Note 1 Push and release the READ button to enter Read Mode. The SET NO Indicator flashes once
to indicate the setup point is selected for viewing
Note 2 Push and release ADV button repeatedly to advance to the desired setup point or I/O point
Each time the ADV button is pushed, the SET NO flashes the point number until the desired
I/O point is reached and then the I/O NO flashes the I/O point no.
button to display the value in the TEN's and ONE's indicator (i.e., 5 flashes for a value of 5)
Note 3 After the SET NO indicator identifies the desired point no, push and release the READ
or a steady TEN's indicator for an on and a steady ONE's for off.
To aid in counting, values of 5 are flashed in groups of 5 (i.e., 150 = 3 groups of fast 5 flashes)
and then follow by balance in slow flashes (i.e., 7 = 5 quick flashes + 2 slow flashes)
Red Set No LED displays Setup item numbers, and Yellow I/O LED displays I/O item no
Note 4 Setpoint values are displayed first followed by I/O values and then back to Setpoint values
Note 5 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit
NO I/O Points UNITS
I/O POINTS
1 C1 Output -
2 C2 Output -
3 C3 Output -
4 C4 Output -
5 Economizer Damper Output %
6 Supply Air temperature F
7 Outside Air temperature F
8 Return Air Temperature F
9 Indoor Relative Humidity %
10 Outdoor Relative Humidity %
11 Indoor Air Quality PPM
12 Remote Minimum Position %
13 Y1 Status (next version) -
14 Y2 Status (next version) -
15 G Status (next version) -
16 Occ Status (next version) -
58
APPENDIX A — ECONOMI$ER+ LABEL (cont)
59
APPENDIX B — JOB SPECIFIC ECONOMI$ER+ CONFIGURATION SETTINGS
Enter the job specific settings in the “Job Setting” column below.
60
Access panels
15
Altitude compensation 38 Barometric flow capacity 17 Burner ignition 49 Burner rack 52 Burner section 52 Burner spark gap 52 Charging chart, refrigerant 50, 51 Clearance 2, 3 CO2sensor
Configuration
23
Settings 23 Combustion blower wheel 49 Compressor
Lubrication 48
Mounting 37
Rotation 37 Condensate drain
Cleaning 47
Location 4, 6 Condenser coil 8
Cleaning 47 Condenser fan 8
Adjustment 48 Control circuit
Wiring 10
Wiring raceway 11 Demand control ventilation 22 Dimensions 2, 3, 5 Ductwork 4 EconoMi$er+ 15-23, 39-47
Adjustment 48
Components 15
Configuration 43-45
Controller wiring 17
Damper movement 17
Inputs and Outputs 40
Troubleshooting 53, 54
Wiring 16, 17 Electrical connections 10 Electrical data 12, 13 Enthalpy changeover set points 21 Evaporator coil 8
Cleaning 47 Evaporator fan motor
Lubrication 48
Motor data 25
Mounting 24
Performance 25-36
Pulley adjustment 24
Pulley setting 8
Speed 8, 25 Factory-installed options 14-23
EconoMi$er+ 15-23
Manual outdoor air damper 14 Filter
Cleaning 47
Installation 16
Size 9 Flue gas passageways 48 Flue hood 6, 10 Freeze protection thermostat 9, 49 Gas connection 9 Gas input 9 Gas piping 6, 10, 37 Gas pressure 1, 6, 9 Heat anticipator settings 9, 10 Heat exchanger 9 High flow valves 37 High pressure switch 9, 49 Horizontal units 1, 4 Indoor air humidity sensor 22 Indoor air quality sensor 18 Integrated gas controller 49
Error codes 49, 55 Leak test 37 Limit switch 49 Liquid propane 9
INDEX
Low pressure switch 9, 49 Main burners 38, 49 Manual outdoor air damper 14 Mounting
Compressor 37
Unit 4 Natural gas 9 Operating limits 4 Operating sequence 45-47
Cooling 45, 46
EconoMi$er+ 46, 47
Heating 46, 47 Outdoor air hood 14, 16 Outdoor air inlet screens
Cleaning 47
Dimensions 9 Outdoor air humidity sensor 19 Outdoor air temperature sensor 18 Physical data 8, 9 Power supply 10
Wiring 11 Pressure switches
High pressure 9, 49
Low pressure 9, 49 Pre-Start-Up 37 Refrigerant
Charge 8, 48
Type 8 Refrigerant service ports 37 Replacement parts 49 Return air filter 9, 37 Return air temperature sensor 18, 19 Rigging unit 4, 7 Roof curb
Assembly 1
Dimensions 5
Connector package 5
Leveling tolerances 6
Weight 8 Safety considerations 1 Safety relief 39 Service 47-52 Service ports 37 Slab mount 4 Start-up 37-47 Start-up checklist CL-1 Thermostat 8 Troubleshooting 53-57 Ventilation 39 Weight
Corner 2, 3
EconoMi$er+ 2, 3, 8
Maximum 6
Unit 2, 3, 7, 8 Wiring
EconoMi$er+ 16
Power connections 11
Thermostat 11
Unit 57
61
SERVICE TRAINING
Packaged Service Training programs are an excelle nt way to increase your knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our labs can mean increased confidence tha t real ly pays dividen ds in fas ter trou bles hoo ting a nd fewer call ­backs. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] Classroom Service Training
Copyright 2004 Bryant Heating & Cooling Systems CATALOG NO. 5358-023
START-UP CHECKLIST
(Remove and Use in Job File)
I. PRELIMINARY INFORMATION:
MODEL NO.: _______________________________________ SERIAL NO.:_______ _______________________________________ DATE: _____________________________________________ TECHNICIAN: ____________________________________________
BUILDING LOCATION: ___________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
VERIFY THAT FLUE HOOD IS INSTALLED
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHA RP EDGES
CHECK GAS PIPING FOR LEAKS
CHECK THAT RETURN-AIR FILTER IS CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
VERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT
CUT ALONG DOTTED LINE
III. START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2 __________ __ L2-L3 ____________ L3-L1 ____________ COMPRESSOR AMPS L1 ____________ L2 ____________ L3 ____________ INDOOR-FAN AMP L1 ____________ L2 ____________ L3 ____________
TEMPERATURES
OUTDOOR-AIR TEMPERATURE _____________ DB _____________ WB ____________ RETURN-AIR TEMPERATURE _____________ DB _____________ WB ____________ COOLING SUPPLY AIR _____________ DB _____________ WB _ ___________ GAS HEAT SUPPLY AIR _____________ DB
PRESSURES
GAS INLET PRESSURE ____________ IN. WG GAS MANIFOLD PRESSURE ____________ IN. WG (LOW FIRE) ____________ IN. WG (HI FIRE) REFRIGERANT SUCTION ____________ PSIG ____________ TEMP ° F REFRIGERANT DISCHARGE ___ _________ PSIG ____________ TEMP ° F
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION (580F072 AND 073 ONLY)
CUT ALONG DOTTED LINE
Copyright 2004 Bryant Heating & Cooling Systems CL-1 CATALOG NO. 5358-023
Loading...