Bryant DURAPAC 579F Installation, Start-up And Service Instructions Manual

installation, start-up and service instructions
SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-22
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 3
III. Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . 8
IV. Step 4 — Make Unit Duct Connections . . . . . . . . . . 8
V. Step 5 — Install Flue Hood and Wind Baffle . . . . . . 8
VI. Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . . 8
VII. Step 7 — Orifice Change. . . . . . . . . . . . . . . . . . . . . . 9
VIII. Step 8 — Install Gas Piping . . . . . . . . . . . . . . . . . . 10
IX. Step 9 — Make Electrical Connections . . . . . . . . . 10
X. Step 10 — Make Outdoor-Air Inlet
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
XI. Step 11 — Install Outdoor-Air Hood. . . . . . . . . . . . 11
XII. Step 12 — Install All Accessories . . . . . . . . . . . . . 13
XIII. Step 13 — Adjust Factory-Installed Options. . . . . 14
XIV. Step 14 — Install Humidistat for Optional
Perfect Humidity™ Dehumidification Package . . . 21
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22-28
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28-37
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .38-42
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service a ir-conditioning equip ment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters . A ll other o per­ations should be performed by trained service per sonnel. When working on air-conditi oning equipme nt, obser v e precautions in the literature, tags and labels attached to the unit, and other safety prec au tions that may a pp ly.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing opera tions.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install lockout tag on disconnect switch. Electrical shock could cause personal injury.
579F
Dura
Cancels: II 579F-180-7 II 579F-180-8
WARNING:
1. Improper installation, adjustment, alteration, service, or maintena nce c an caus e pr ope rty dam ­age, personal injury, or loss of life. Refer t o the User’s Information Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable vapors and liquids in the vi cinity of this or any other appliance.
What to do if yo u sm ell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any elec trical switch, or use an y phone in your building.
3. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire department.
WARNING: Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure grea ter than 0.5 psig, it must be replaced before use. When pressure testing field­supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by clos­ing the manual gas valve(s).
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the units will automatically lock the com­pressor out of operation. Manual reset will be required to restart the compressor.
INSTALLATION
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb or horizontal adapter roof curb in accordance with instructions shipped with this accessory. See Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb or horizontal adapter roof curb before unit is set in place. Cur b or ada pt er roof curb shou ld b e le ve l. This is necessary to permit unit drain to function properly. Unit leveling tolera nce is ± tion. Refer to Accessory Roof Curb or Horizontal Adapter Roof Curb Installation Instructions for additi onal information as required. When accessory roof curb or horizontal adapter roof curb is used, unit may be installed on class A, B, or C roof cov­ering material.
1
/16 in. per linear ft in any direc-
Series
Sizes 180-300
15 to 25 Tons
3/15/06
DESCRIPTION
CURB
HEIGHT
PKG. NO. REF.
Fig. 1 — Roof Curb Details
CRRFCURB010A00 1′− 2 (305) Standard Curb 14 High
CRRFCURB011A00 2-0 (610) Standard Curb for Units Requiring High Installation
CRRFCURB012A00 2-0 (610) Side Supply and Return Curb for High Installation
2
3 1/2"
2" X 1/4 SUPPORT TYP. STITCH WELDED
FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible.
For horizontal return applications: The power exhaust and barometric
relief dampers must be installed in the return air duct.
Fig. 2 — Horizontal Supply/Return Adapter Installation (579F180-240)
IMPORTANT: The gasketing of the un it to the roof curb or
adapter roof curb is critical for a watertight seal. Install gas­ket with the roof curb or adapter as shown in Fig. 1. Improp­erly applied gasket can also result in air leaks and poor unit performance.
B. Alternate Unit Support
When the curb or ada pter cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency.
Do not drop unit; keep uprig ht. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame a s a refer­ence; leveling tolerance is ±
1
/16 in. per linear ft in a ny di re c­tion. See Fig. 3 for additional information. Unit operating weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging instructions on unit.
14 3/4"
6"
ACCESSORY
PACKAGE NO.
CRRFCURB013A00
12" WIDE STANDING SEAM PANELS
CURB
HEIGHT
1-11
(584)
DESCRIPTION
Pre-Assembled, Roof Curb,
Horizontal Adapter
23"
A. Positioning
Maintain clearance, per Fig. 4 and 5, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor l ocation. Do not locate unit air inlets near exhaust vents or other sources of contami­nated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Sec­tion 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the buil ding, and at le ast 4 ft fr om any adj acen t buil d­ing. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
B. Roof Mount
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Instructions continued on page 8.
3
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4 and 5 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars on all units.
5. Weights do not include optional EconoMi$erIV. Add 90 lb (41 kg) for EconoMi$erIV weight.
6. Weights given are for aluminum evaporator and condenser coil plate fins.
CAUTION: All panels must be in place when rigging
UNIT 579F
MAXIMUM
SHIPPING WEIGHT
lb kg Ft-in. mm Ft-in. mm 180 1775 805 6-11 216 1875 850 6-11 240 1985 900 6-11 300 2135 968 6-11
Fig. 3 — Rigging Details
DIMENSIONS
AB
1
/22121 3-5 1041
1
/22121 3-3 991
1
/22121 3-2 965
1
/22121 3-2 965
4
DIM A DIM B DIM C
D
CORNER
C
CORNER
(8) on each side
16
/
5
B
CORNER
A
CORNER
WEIGHT
ECONOMI$ERIV
lb kg lb kg lb kg lb kg lb kg lb kg ft-in. mm ft-in. mm ft-in. mm
WEIGHT
STD UNIT
UNIT
•Top: 6′-0″ (1829) to assure proper condenser fan operation.
grounded surfaces.
• Local codes or jurisdiction may prevail.
power exhaust as stated in Note #6, a removable fence or barricade
• Bottom: 14 (356) to combustible surfaces (when not using curb).
• Control box side: 3′-0″ (914) to ungrounded surfaces, non-combustible.
• Control box side: 3′-6″ (1067) to block or concrete walls, or other
requires no clearance.
for top cover drip edge.
7. With the exception of clearance for the condenser coil and the damper/
8. Dimensions are from outside of corner post. Allow 0′-
4-0 (1219) if conditions permit coil removal from the top.
•Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to
•4′-0″ (1219) to combustible surfaces, all four sides (includes between
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
579F180 1650 748 90 41 423 192 386 175 403 183 438 199 3-5 1041 3-5 1041 1-10 559
579F216 1800 816 90 41 432 196 410 186 461 209 472 214 3-3 991 3-7 1092 1- 8 508
exhaust if so equipped.
units).
• Right side: 4′-0″ (1219) for proper operation of damper and power
• Front: 4-0 (1219) for control box access.
• Left side: 4′-0″ (1219) for proper condenser coil airflow.
Fig. 4 — Base Unit Dimensions; 579F180,216
5
DIM A DIM B DIM C
D
CORNER
C
CORNER
B
CORNER
A
CORNER
WEIGHT
ECONOMI$ERIV
(8) on each
16
/
5
4-0 (1219) if conditions permit coil removal from the top.
•4′-0″ (1219) to combustible surfaces, all four sides (includes between
• Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
exhaust if so equipped.
units).
• Right side: 4′-0″ (1219) for proper operation of damper and power
• Front: 4′-0″ (1219) for control box access.
• Left side: 4′-0″ (1219) for proper condenser coil airflow.
grounded surfaces.
• Bottom: 14 (356) to combustible surfaces (when not using curb).
• Control box side: 3′-0″ (914) to ungrounded surfaces, non-combustible.
• Control box side: 3′-6″ (1067) to block or concrete walls, or other
• Local codes or jurisdiction may prevail.
power exhaust as stated in Note #6, a removable fence or barricade
7. With the exception of clearance for the condenser coil and the damper/
requires no clearance.
side for top cover drip edge.
8. Dimensions are from outside of corner post. Allow 0′-
•Top: 6′-0″ (1829) to assure proper condenser fan operation.
WEIGHT
STD UNIT
UNIT
lb kg lb kg lb kg lb kg lb kg lb kg ft-in. mm ft-in. mm ft-in. mm
579F240 1850 839 90 41 443 201 406 184 476 216 525 238 3-2 965 3-5 1041 1-8 508
579F300 2000 907 90 41 471 214 428 194 526 239 574 260 3-2 965 3-5 1041 1-8 508
Fig. 5 — Base Unit Dimensions; 579F240,300
6
Table 1 — Physical Data
NOMINAL CAPACITY (tons) 15 18 20 25 OPERATING WEIGHT (lb) 1650 1800 1850 2000
EconoMi$erIV 90 90 90 90 Roof Curb 200 200 200 200
COMPRESSOR/MANUFACTURER Scroll, Copeland
Quantity...Model (Ckt 1, Ckt 2) 2...SR*942AE Number of Refrigerant Circuits 2222
Stages of Capacity Control (%) 50/50 60/40 52/48 56/44 Oil (oz) (Ckt 1, Ckt 2) 90, 90 110, 72 110, 110 112, 110
REFRIGERANT TYPE R-22
Expansion Device TXV Operating Charge (lb-oz) Circuit 1* 10-13 15-2 16-3 21-0 Circuit 2 10- 5 11-5 14-8 15-4
CONDENSER COIL Cross-Hatched
Rows...Fins/in. 2...17 3...15 3...15 4...15 Total Face Area (sq ft) 21.7 21.7 21.7 21.7
CONDENSER FAN Propeller Type
Nominal Cfm 10,500 9250 13,650 12,500 Quantity...Diameter (in.) 3...22 3...22 2...30 2...30 Motor Hp...Rpm Watts Input (Total) 1100 1100 3400 3400
EVAPORATOR COIL Cross-Hatched
Rows...Fins/in. 2...17 3...15 3...15 4...15 Total Face Area (sq ft) 17.5 17.5 17.5 17.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...10 x 10 2...12 x 12 2...12 x 12 2...12 x 12 Type Drive Belt Belt Belt Belt Nominal Cfm 6000 7200 8000 10,000 Motor Hp 3.7 5 7.5 10 Motor Nominal Rpm 1725 1745 1745 1740
Maximum Continuous Bhp 4.25 5.90 Motor Frame Size 56H 184T 213T 215T
Fan Rpm Range Low-Medium Static 891-1179 910-1095 1002-1225 1066-1283
Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1550 1550 1550 1550 Motor Pulley Pitch Diameter Low-Medium Static 3.1/4.1 4.9/5.9 5.4/6.6 4.9/5.9
Min/Max (in.) High Static 3.7/4.7 4.9/5.9 5.4/6.6 4.9/5.9 Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Low-Medium Static 6.0 9.4 9.4 8.0
Nominal Fan Shaft Diameter (in.) 1 Belt, Quantity...Type...Length (in.) Low-Medium Static 1...BX...42 1...BX...50 1...BX...54 2...BX...50
Pulley Center Line Distance (in.) 13.5-15.5 13.3-14.8 14.6-15.4 14.6-15.4 Speed Change per Full Turn of
Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns
From Closed Position 6666 Factory Speed Pulley Setting 3.5 3.5 3.5 3.5 Factory Speed Setting (rpm) Low-Medium Static 1035 1002 1120 1182
FURNACE SECTION (Low Heat/High Heat)
Rollout Switch Cutout Temp (F)† 190 190 190 190
Burner Orifice Diameter (in. ...drill size)
Natural Gas Thermostat Heat Anticipator Setting (amps)
208/230 v Stage 1 0.98 0.98 0.98 0.98
460 v Stage 1 0.80 0.80 0.80 0.80
Gas Input Stage 1 206,000/270,000 206,000/270,000 206,000/270,000 206,000/270,000
Efficiency (Steady State) (%) 81 81 81 81 Temperature Rise Range 15-45/20-50 15-45/20-50 15-45/20-50 15-45/20-50 Manifold Pressure (in. wg)
Natural Gas 3.3 3.3 3.3 3.3 Gas Valve Quantity 1111 Field Gas Connection Size (in.-FPT)
HIGH-PRESSURE SWITCH (psig)
Cutout 426 Reset (Auto) 320
LOW-PRESSURE SWITCH (psig)
Cutout 27 Reset (Auto) 44
FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 2...20 x 25 x 1
RETURN-AIR FILTERS Throwaway**
Quantity...Size (in.) 4...20 x 20 x 2
POWER EXHAUST
LEGEND
Bhp Brake Horsepower TXV Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of condenser coil and lower portion of evaporator coils;
and Circuit 2 uses the upper portion of both coils.
UNIT 579F 180 216 240 300
1
/2...1050
1...SM120
1...SR*782*AE
3
Aluminum Pre-Coated, or Copper Plate Fins
3
/8-in. Copper Tubes, Aluminum Lanced or Copper Plate Fins, Face Split
/8-in. Copper Tubes, Aluminum Lanced,
1
/2...1050 1...1075 1...1075
1...SM120
1...SM110
8.7 [208/230 v]
9.5 [460 v]
1...SM161
1...SM120
10.2 [208/230 v]
11.8 [460 v]
High Static 1227-1550 1069-1287 1193-1458 1332-1550
7
/
8
High Static 5.2 8.0 7.9 6.4
3
/
16
11/
8
17/
16
13/
8
17/
16
13/
17/
High Static 1...BX...42 1...BX...48 1...BX...50 2...BX...47
Low-Medium Static 48 37 37 36 High Static 55 34 44 45
High Static 1389 1178 1328 1470
0.1285...30/
0.136...29
0.1285...30/
0.136...29
0.1285...30/
0.136...29
0.1285...30/
0.136...29
Stage 2 0.44 0.44 0.44 0.44
Stage 2 0.44 0.44 0.44 0.44
Stage 2 275,000/360,000 275,000/360,000 275,000/360,000 275,000/360,000
3
/
4
3
/
4
3
/
4
3
1...20 x 20 x 1
1
/2 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
†Rollout switch is manual reset.
**The 579F300 units requires 2-in. industrial-grade filters capable of handling face veloc-
ities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 579F180-300 units have a low-pressure switch (standard) located on the suction side.
4...16 x 20 x 2
8
16
/
4
7
III. STEP 3 — FIELD FABRICATE DUCTWORK
Secure all ducts to building structure. Use flexible duct con­nectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and m asti c i n acc ordance with applica­ble codes.
Ducts passing through a n unc ondit i one d spa ce must be insu­lated and covered with a vapor barrier.
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS
Unit is shipped for thru-the-bottom duct connections. Duct­work openings are shown in Fig. 1, 4, and 5. Duct connec­tions are shown in Fig. 6. Field-fabricated concentric ductwork may be connected as shown in Fig. 7 and 8. Attach all ductwork to roof curb and roof curb basepans.
V. STEP 5 — INSTALL FLUE HOOD AND WIND BAFFLE
Flue hood and wind baffle are shipped secured under main control box. To install, secure flue hood to access panel. See Fig. 9. The wind baffle is then installed over the flue hood.
NOTE: Whe n properly insta lled, flue hoo d will line up with combustion fan housing. See Fig. 10.
VI. STEP 6 — TRAP CONDENSATE DRAIN
See Fig. 11 for drain location. One
3
/4-in. half coupling is pro­vided inside unit evaporator section for condensate drain connection. An 8 diameter pipe nipple, coupled to standard
1
/2-in. x 3/4-in. diameter and 2-in. x 3/4-in.
3
/4-in. diameter elbows, provide a straight path down through hole in unit base rails (see Fig. 12). A trap at leas t 4-in. deep must be used.
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 6 — Air Distribution — Thru-the-Bottom
NOTE: Dimensions A, A′, and B are obtained from field-supplied ceil-
ing diffuser.
Shaded area indicates block-off panels.
Fig. 8 — Concentric Duct Details
WIND BAFFLE
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 7 — Concentric Duct Air Distribution
Fig. 9 — Flue Hood Location
8
INDUCED DRAFT MOTOR
VII. STEP 7 — ORIFICE CHANGE
This unit is factory assembled for heating operation using natural gas at an elevation from sea level to 2000 ft. This unit uses orifice type LH32RFn nn, wher e “nnn” i ndicates th e orifice size based on drill size diameter in thousands of an inch.
A. High Elevation (Above 2000 ft)
Use accessory high altitude kit when installing this unit at an elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer to Table 2 to identify the correct orifice size for the elevation. See Table 3 for the nu mber of orifi ces re quired for each unit size. Purc hase the se orifi ces f rom your lo cal Bryant dealer. Fo llow in structions in ac cessory I nstallati on Ins truc­tions to install the correct orif ices.
Table 2 — Altitude Compensation*
COMBUSTION FAN HOUSING
MAIN BURNER SECTION
HEAT EXCHANGER SECTION
Fig. 10 — Combustion Fan Housing Location
3/4" FPT DRAIN CONNECTION
1-3/8" DRAIN HOLE
Fig. 11 — Condensate Drain Details (579F180 Shown)
ELEVATION (ft)
0-1,999 30 29
2,000 30 29 3,000 31 30 4,000 31 30 5,000 31 30 6,000 31 30 7,000 32 31 8,000 32 31 9,000 33 31
10,000 35 32
*As the height above sea level increases, there is less oxygen per cubic
foot of air. Therefore, heat input rate should be reduced at higher alti­tudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Bryant dealer.
NATURAL GAS ORIFICE†
Low Heat High Heat
Table 3 — Orifice Quantity
UNIT ORIFICE QUANTITY 579F180 Low Heat 5 579F210 Low Heat,
579F240 Low Heat, 579F300 Low Heat, 579F180 High Heat
579F210 High Heat, 579F240 High Heat, 579F300 High Heat
6
7
B. Conversion To LP (Liquid Propane) Gas
Use accessory LP gas conversion kit when converting this unit for use with LP fuel usage for elevations up to 7000 ft. For elevations above 7000 ft, refer to Table 4 to identify the correct orifice size for the elevation. See Table 3 for the number of orifices required for each unit size. Purchase these orifices from your local Bryant deale r. Follow instructions in acce ssory Installation Instructions to install the correc t orific es.
Table 4 — LP Gas Conversion*
Fig. 12 — Condensate Drain Piping Details
ELEVATION (ft) LP GAS ORIFICE†
0-1,999 36
2,000 37 3,000 38 4,000 38 5,000 39 6,000 40 7,000 41 8,000 41 9,000 42
10,000 43
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Bryant dealer.
9
VIII. STEP 8 — INSTALL GAS PIPING
Unit is equipped for use with natural gas. Installation must conform with local bu ilding codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.
Install field-supplied manual gas shutoff valve with a
1
/8-in. NPT pressure tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 13.
WARNING: Do not pressure test gas supply while connected to unit. Always disconnect union before servicing.
IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5.5 in. wg or greater than 13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.
Fig. 13 — Field Gas Piping
IX. STEP 9 — MAKE ELECTRICAL CONNECTIONS
A. Field Power Supply
Unit is factory wired for voltage sh own on nameplate. When installing units, provide a disconnect per NEC
(National Electrical Code) of adequate size (see Table 5). All field wiring must comply with NEC and local
requirements. Route power ground lines through control box end panel or
unit basepan (see Fig. 4 and 5) to connections as shown on unit wiring diagram and Fig. 14.
CAUTION: The correct power phasing is critical in the operation of the scroll compressors. An incorrect phasing will cause the compressor to rotate in the wrong direction. This m ay lead to prematu re comp res­sor failure.
WARNING: The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association).
Field wiring must confirm to temperature limitations for type “T” wire. All field wiring must comply with NEC and local require ments.
Transformer no. 1 is wi r ed for 230 -v uni t. If 2 08/ 230-v unit is to be run with 208-v power supply, the tran sformer must be rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damag e the transformers.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2%.
Unit failure as a res ult of ope ra tio n o n imp ro per line volt age or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with acces­sory. Locate thermostat assembly on a solid interior wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of colored wire from sub bas e t ermin als through conduit in unit to low-voltage connection s as sho wn on unit la be l wi ring dia­gram and in Fig. 15.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected a t the thermos tat and wi ll req uire a j unction box and s plice a t the thermostat.
Set heat anticipator settings as follows:
VOLTAGE W1 W2
208/230
460
0.98
0.80
0.44
0.44
Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
C. Optional Non-Fused Disconnect
On units with the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 16 for wiring for 100 and 200 amp disconnect switches. Units with an MOCP (maximum overcurrent protection) under 100 will use the 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Open the co ntro l box door and remov e th e han d le a nd shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect switch. The bolt is locat ed on the sq uare hole a nd is used to hold the shaft in place. The shaft cannot be inserted until the Allen bo lt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is spe­cially cut and the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with the two screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in the OFF position, the handle will be horizontal.
10
7. Turn the handle to the OFF position and close the door. The handle should fit over th e end of the shaft when the door is closed.
8. The handle must be in the OFF position to open the control box door.
D. Optional Convenience Outlet
On units with optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outlet receptacle is provided for field wiring. Field wiring should be run through
7
the
/8-in. knockout provided i n the basepan ne ar the return
air opening.
LEGEND
EQUIP — Equipment GND Ground NEC National Electrical Code TB Terminal Block
NOTE: The maximum wire size for TB1 is 2/0.
Fig. 14 — Field Power Wiring Connections
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
RC
RH
R
RED
Y1 Y2
Y1
BLU
PNK
W1
W1Y2
ORN
W2
W2
VIO
GC
G
BLK
C
BRN
L
X
X
WHT
Fig. 15 — Field Control Thermostat Wiring
6T3 4T2 2T1 LOAD
X. STEP 10 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS
A. Manual Outdoor-Air Damper
All units (except those equipped with a factory-installed economizer) have a manual outdoor-air damper to provide ventilation air.
Damper can be preset to admit up to 25% outdoor air into return-air compartment. To adjust, loosen securing screws and move damper to desired setting, then retighten screws to secure damper (Fig. 17).
XI. STEP 11 — INSTALL OUTDOOR-AIR HOOD
The outdoor-air hood is common to 25% air ventilation and EconoMi$erIV. If EconoMi$erIV is used, all electrical connec­tions have been made an d adjusted at th e factory. Assemble and install hood in the field.
IMPORTANT: If the unit is equipped with the optional EconoMi$erIV component, move the outdoor-air tempera­ture sensor prior to installing the outdoor-air hood. See the Optional EconoMi$erIV section for more inform ation.
NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baffle (size 300), and filter support bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and hardware are in a package located inside the return-air filter access panel (Fig. 18).
1. Attach seal strip to upper filter retainer. See Fig. 19.
2. Assemble hood top panel, side panels, upper filter retainer, and drain pan (see Fig. 20).
3. Secure lower filter retainer and support bracket to unit. See Fig. 20. Leave screws loose on size 300 units.
4. Slide baffle (size 300) behind lower filter retainer and tighten screws.
5. Loosen sheet metal screws for top panel of base unit located above o utdoor-air inlet opening, and remove screws for hood side panels located on the sides of the outdoor-air inlet opening.
6. Match notches in hood top panel to unit top panel screws. Insert hood flange between top panel flange and unit. Tighten screws.
7. Hold hood side panel flanges flat against unit, and install screws removed in Step 5.
8. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket.
NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.
Fig. 16 — Optional Non-Fused Disconnect Wiring Fig. 17 — Standard 25% Outdoor-Air Section Details
5L3 3L2 1L1 LINE
11
Table 5 — Electrical Data
UNIT 579F
180
(15 Tons)
216
(18 Tons)
240
(20 Tons)
300
(25 Tons)
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code, U.S.A. OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combina­tion load equipment (refer to NEC Articles 430 and 440), the overcur­rent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
NOMINAL VOLTAGE
(3 Ph, 60 Hz)
208/230 187 253 25.6 190 25.6 190 3 0.5 1.7 3.7 10.5/11.0
460 414 508 13.5 95 13.5 95 3 0.5 0.8 3.7 4.8
208/230 187 253 33 237 23 184 3 0.5 1.7 5.0 15.8/15.8
460 414 508 16.2 130 10.2 90 3 0.5 0.8 5.0 7.9
208/230 187 253 33 237 29.5 237 2 1 6.6 7.5 25.0/25.0
460 414 508 16.2 130 14.1 130 2 1 3.3 7.5 13.0
208/230 187 253 47.5 265 33.0 237 2 1 6.6 10.0 28.0/28.0
460 414 508 22.9 145 16.2 130 2 1 3.3 10.0 14.6
greater than 2%.
of voltage imbalance. % Voltage Imbalance
= 100 x
max voltage deviation from average voltage
VO LTAGE
RANGE
Min Max RLA LRA RLA LRA Qty Hp
LEGEND
Use the following formula to determine the percent
average voltage
COMPRESSOR
No. 1 No. 2
OFM IFM
FLA
Hp FLA FLA LRA FLA MCA MOCP*
(ea)
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact the local electric utility company immediately.
POWER
EXHAUST
0.57 74/74 90/ 90
4.6 18.8 0.57 78/79 100/100 — 0.30 38 50
2.3 6.0 0.30 40 50 — 0.57 85/85 110/110
4.6 18.8 0.57 90/90 110/110 — 0.30 41 50
2.3 6.0 0.30 43 50 — 0.57 109/109 125/125
4.6 18.8 0.57 114/114 125/125 — 0.30 54 70
2.3 6.0 0.30 56 70 — 0.57 134/134 175/175
4.6 18.8 0.57 135/135 175/175 — 0.30 66 80
2.3 6.0 0.30 68 90
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
COMBUSTION
FAN MOTOR
452 + 464 + 455
3
1371
=
3
=
457
POWER SUPPLY
7
457
= 1.53%
12
Fig. 18 — Outdoor-Air Hood Component Location
Fig. 19 — Seal Strip Location
BAFFLE (300 ONLY)
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
HOOD SIDE
HOOD TOP PANEL
PANELS (2)
BAFFLE (300 ONLY)
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
XII. STEP 12 — INSTALL ALL ACCESSORIES
After all the factory-installed options have been adjusted, install all field-instal led accessories. Refer to the accessory installation instructions included with each accessory.
A. Motormaster® I Control Installation (579F180 and 216 Only)
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures. See Fig. 21 for baffle det ails. Use 20-gage, galva nized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster I Controls Only one Motormaster I control is required per unit. The
Motormaster I control must be used in conjunction wi th the Accessory 0° F Low Ambient Kit (purchased separately). The Motormaster I device controls ou tdoor fan no. 1 while out­door fans no. 2 and 3 are sequenced off by the Accessory 0° F Low Ambient Kit.
Accessory 0° F Low Ambient Kit
Install the Access ory 0° F Low Ambi ent Kit per instru ction supplied with accessory.
Sensor Assembly
Install the sensor assembly in the location shown in Fig. 22.
Motor Mount
To ensure proper fan height, replace the existing motor mount with the new motor mount provided with accessory.
Transformer (460-v Units Only)
On 460-v units, a transformer is required. The transformer is provided with the accessory and must be field-installed.
Motormaster I Control
Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on th e i nside of th e pan el, ver ticall y, with leads p ro­truding from bottom of extrusion.
B. Motormaster® V Control Installation
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures. See Fig. 21 for baffle det ails. Use 20-gage, galva nized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
UPPER FILTER RETAINER
Fig. 20 — Outdoor-Air Hood Details
HOOD DRAIN PAN
13
NOTE: Dimensions in ( ) are in mm.
Fig. 21 — Wind Baffle Details
Install Motormaster V Controls The Motormaster V control is a motor speed control device
which adjusts condenser fan motor speed in response to declining liquid refrigerant pressure. A properly applied Motormaster V control extends the operating range of air­condition ing systems and permits operation at lower outdoor ambient temperatures.
The minimum ambient temperatures at which the unit will operate are:
Standard Unit Unit with Low Ambient Kit Unit with MMV Control
40 25 –20
TEMPERATURE OPERATING LIMITS — F°
To operate down to the ambient temperatures listed, Motormaster V controls (Fig. 23) must be added. Field­fabricated and installed wind baffles are also r equired for all units (see Fig. 21). The Motormaster V control permits opera­tion of the unit to an ambient temperature of –20 F. The control regulates the speed of 3-phase fan motors that are compatible with the control. These motors are factory installed.
See Table 6 for the Motormaster V control accessory package usage. Table 7 shows applicable voltages and motors. Replacement of a motor IS NOT REQUIRED ON CUR- RENT PRODUCTION UNITS since the control is co mpati­ble with the factory-installed fan motors. Only field wiring control is required.
Install the Motormast er V control per instru ctions supplied with accessory .
Table 6 — Motormaster V Control Package Usage
UNIT VOLTAGE ITEM DESCRIPTION
579F180-300
208/230 CRLOWAMB015A00
460 CRLOWAMB016A00
SENSOR LOCATION
HAIRPIN END
NOTE: All sensors are located on the eighth hairpin up from the bottom.
579F180 579F216
SENSOR LOCATION
HAIRPIN END
Fig. 22 — Motormaster® I Sensor Locations
Table 7 — Applicable Voltages and Motors
VOLTAGE C OM PATIBL E MOTOR
208/230-3-60 HD52AK654
460-3-60 HD52AK654
XIII. STEP 13 — ADJUST FACTORY-INSTALLED OPTIONS
A. Optional EconoMi$erIV
See Fig. 24 and 25 for EconoMi$erIV component locations. NOTE: These instructions are for installing the optional
EconoMi$erIV only. Refer to the accessory EconoMi$erIV installation instructions when field installing an EconoMi$erIV accessory.
To complete installation of t he optional EconoMi$erIV, per­form the following procedure.
1. Remove the EconoMi $erIV hood. Ref er to Step 11 — Install Outdoor-Air Hood on page 11 for info rmation on removing and in stalling the outdoor-air hood.
2. Relocate outdoor air temperature sensor from ship­ping position to operation pos ition on EconoMi $erIV. See Fig. 24.
IMPORTANT: Failure to relocate the sensor w ill res ult in the EconoMi$erIV not operating properly.
3. Re-install economizer hood.
4. Install all EconoMi$erIV accessories. EconoMi$erIV wiring is shown in Fig. 26.
Outdoor air leakage is shown in Table 8. Return air pressure drop is shown in Tabl e 9.
14
FROM FUSE BLOCK
Table 8 — Outdoor Air Damper Leakage
BLK
YEL
BLU
B
13B
13C
12 13A
2
256
TO PRESSURE TRANSDUCER
2
3
1
TO MOTOR(S)
Fig. 23 — Motormaster® V Control
OUTDOOR AIR TEMPERATURE SENSOR (INSTALLED OPERATION POSITION)
SCREWS
ECONOMI$ERIV
FRAME
TOP
SCREWS
LOW TEMPERATURE COMPRESSOR LOCKOUT SWITCH
Fig. 24 — EconoMi$erIV Component Locations —
End View
SUPPLY AIR TEMPERATURE SENSOR LOCATION
ECONOMI$ERIV
ACTUATOR
CONTROLLER
FLANGE AND SCREWS (HIDDEN)
1 R
T
R T
c
a V 4 2
M
O C
4
2
_
c a V
T
O
H
H
X E
+
t e
S
V 0
2
1 V 2
1
1
N
5
N
n
H
i
X
M
E
s o
P
4
1
n
P
e
p
P
O
3
V C
1
D
x
F
a
1
E
T
M
T
V 0
F
1
E
V 2
V C
D
V
t
C
e
D
S
V
1
0
Q
1
A
Q A
V
2
+
e
O
e r
S
C
F
l o
O
o
S
C
B
D
+ R S
A
R
S
DAMPER STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
LEAKAGE (cfm) 35 53 65 75 90 102
Table 9 — Return Air Pressure Drop (in. wg)
CFM
4500 5000 5400 6000 7200 7500 9000 10,000 11,250
0.040 0.050 0.060 0.070 0.090 0.100 0.110 0.120 0.140
B. EconoMi$erIV Standard Sensors
Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature. The outdoor-air temperat ure is used t o determine whe n the EconoMi$erIV can be used for free cooling. The sensor must be field-reloca ted. See Fig. 24. The operati ng range of tem­perature measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 25. This sensor is factory installed. The operating range of temperature measurement is 0° to 158 F. See Tabl e 10 for sensor temper a­ture/resistance values.
The temperature sensor looks like an eyele t terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Low Temperature Compressor Lockout Switch The EconoMi$erIV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42 F ambient tem­perature. See Fig. 24.
Table 10 — Supply Air Sensor Temperature/
Resistance Values
TEMPERATURE (F) RESISTANCE (ohms)
–58 200,250 –40 100,680 –22 53,010
–4 29,091 14 16,590 32 9,795 50 5,970 68 3,747 77 3,000
86 2,416 104 1,597 122 1,080 140 746 158 525 176 376 185 321 194 274 212 203 230 153 248 116 257 102 266 89 284 70 302 55
Fig. 25 — EconoMi$erIV Assembled in Unit —
Side View
15
Loading...
+ 33 hidden pages