1. Check all local or other applicable codes for informa
tion concerning proximity to property lines, height
above roof, obstructions, etc.
2. Be sure the power supply available (voltage, fre
quency, and phase) corresponds to that specified on
the unit (230-60-1).
3. Check the electrical service provided by the utility
for the building to be sure that the service capacity
is sufficient to handle the load imposed by this unit.
4. Refer to the regulations of the service gas supplier
and the local building, heating, plumbing or other codes
in effect in the area in which installation is to be made.
5. Refer to the dimensional drawing on page 2 for
location of electrical, gas and chilled water connections
prior to setting the unit in place.
6. Model 453 chillers are not designed for operation
at outdoor ambients below 40°F.
7. When this chiller is used in conjunction with a
boiler, a 4-pipe system must be used. A common piping
system cannot be used. Use separate coils and piping.
GENERAL
Model 48-453 is a gas-fired air-cooled absorption
system which supplies chilled water to the cooling coil
and is suitable for residential and small commercial
air conditioning systems.
This unit is used for cooling only with indoor or outdoor
coil assemblies. The 48-453, can also be used in con
junction with a Bryant gas-fired furnace to provide
“all-seasons” air conditioning for warm air or cool
air as outside temperature dictates.
Multiple Chillers and Cooling Coiis
When it is planned to connect two or more chillers or
coils, additional piping and electrical information is
required and should be obtained from your Bryant
distributor.
Operation at Atmospheric Pressure
The chilled water tank on this unit is vented to the
atmosphere; consequently, the chilled water circuit
operates at atmospheric pressure. Therefore, conven
tional piping practices for a closed, pressurized system
do not apply for this unit.
briiant
Cancels; 39453D67
I
39453D86
8/15/71
F i L & s
I
■
¡DO NOTi
^REMOVE
w
B71285
Figure 1 - Model 453 Gas Air Conditioner
NOTE: When the water chiller is piped to a boiler as
described below, the indoor coil operates at or near
atmospheric pressure when used for cooling; it may be
pressurized when it is used with the boiler for heating.
When the chiller is piped with a boiler to form a com
bination heating and cooling system, provisions must
be made for a positive shutoff between the chiller tank
and the boiler.
When the boiler is in operation, the chiller tank must
be by-passed. A sediment strainer must be installed at
the chiller tank inlet when a common pipe connects
the chiller tank and boiler.
When the chiller is in operation, the boiler, of course,
should be by-passed.
Installation
Installation of Model 48-453, Series D Gas Chiller
consists of the following steps:
I. Locating and Mounting the Unit
II. Connecting Chilled Water Line
III. Making Electrical Connections
IV. .Making Gas Connections
V. Charging System with Water
VI. Checking the Unit Operation
VII. Adjusting Gas Input
VIII. Balancing the System
Each of the above steps is discussed in detail in this
instruction. Read the entire Installation Instructions
before starting the installation.
-1-
note; panelonfrontside
PROVIDES additional SERVICE
ACCESS.
-GAS CONNECTION
r 1"
l^HOLE-^PIPE 3!
Figure 2 - Unit Dimensional Drawing
A7C
RATINGS, CAPACITIES and COMPONENT INFORMATION
Gas InputBTUH112,000
Power Supply (Voltage - Frequency - Phase)230-60-1
Electrical Input
Condenser Air Flow
Refrigerant
AmountLbs1 1.0
Total SolutionLbs30
Factory Test Pressure (Refrigerant Cycle)
Relief Valve Set (Refrigerant Cycle)
Operating Chiller Water VolumeGal.3.8
Operating Chiller Water Level Above BaseInches
Internal Chilled Water Pressure Loss
Pressure in Chilled Water Tank
Nominal Chilled Water Flow Rate
Water-Solution Pump Motor
HP & Service Factor
Speed
Frame
Pulley Pitch Dia & Bore
Water Pump Pulley Pitch Dia & BoreInches
Solution Pump Pulley Pitch Dia & BoreInches
Belt Length & Width
Fan Motor
HP1/3
Speed
Frame
Fan Diameter
Unit Weight
* Atmospheric
-2-
KW1.45
CFM4,200
TypeR-717
PSIG
PSIG
Ft Water
PSIG*0
GPM
RPM
Inches
Inches
RPM
Inches
Lbs740
450
450
9-5/8
2.5
10
1/2-1.6
3450
48
3.09-0.50
2.74-0.628
7.03-0.626
36.5x5/16
825
48
26
LIQUID SUCTION
HEAT EXCHANGER
CONTROL BO.
\
SERVICE
VALVE D
SERVICE VALVE C
RECTIFIER
CHILLER TANK
FAN
PUMP
INLETTANK
SERVICE
VALVE E I
PUMP ^
DISCHARGE
TANK
SUCTION DISCHARGE HYDRAULIC PUMP/
VALVE VALVE WATER PUMP MOTOR
Figure 3 - Partially Disassembled Unit (Front View)
FAN MOTOR
NONCONDENS
ABLE CUSHION
HYDRAULIC
PUMP
B71299
SAIL SWITCH
/
SERVICE
VALVE A'
ABSORBER/
CONDENSERASSY.
SOLUTION
COOLED ABSORBER
GAS INLET
CONNECTION
A643
GAS VALVE/
REGULATOR
'A-'t-T....' . . RESISTOR
- ' I _ ■. PARJ load
i ■ • - 1>C0NT SW.
BURNER PILOT PRESSURE
CAPACITOR
821 RELAY
T -»f-TRANSFORMER
LOW-VOLTAGE
TERMINAL BLOCK
MANUAL
RESET
BUTTON
POWER SUPPLY
CONNECTIONS
GENERATOR
PILOT
ADJUSTING
SCREW
PILOT
ASSEMBLY SWITCH
Figure 4A - Partially Disassembled Unit (Left Side View)
■
GAS INLET^
CONNECTION
REGULATOR
639 GAS PILOT
VALVE ADJUSTING
SCREW
Figure 4B - Partial View of Unit Equipped
with the A639 Gas Valve (Left Side View)
PILOT
ASSY.
BURNER
A70026
-3-
I. LOCATING AND MOUNTING THE UNIT
The construction of Model 48-453 is such that the unit
can be mounted on any NONCOMBUSTIBLE base.
However, there are several conditions, or circum
stances, that result in the requirement of field supplied
supports. Some of these circumstances are:
1. When state and/or local building codes prohibit
mounting the unit directly on a base.
2. When the unit is to be placed in an area where there
is danger of standing water.
Mounting Base
The unit is supported on 3 rails attached to the bottom
of the base. These rails extend the full length of the
unit as shown in the dimensional drawing on page 2.
The recommended types of mounting bases for all
installations are:
a. Precast concrete lintels.
Use three lintels run the depth of the unit; one each
under the right and left end and one at the center of
the unit.
b. Concrete blocks.
Use a block under each corner plus a block under each
of the two long sides midway between the corner
blocks. Arrange the blocks so that the center rail as
well as the front and back rail is supported.
c. Concrete slab.
Minimum thickness 4 inches.
CAUTION: ALWAYS USE NONCOMBUSTIBLE
MATERIAL FOR THE BASE.
Rooftop Installations
1; Place the unit above a load-bearing wall whenever
possible.
2. Roof areas are susceptible to standing water; there
fore, field-supplied supports should be placed under
the unit. Allow a minimum of 6 inches clearance
between bottom of unit and roof.
Clearances
The condenser coil is located at the back of the unit
with the condenser air inlet through the rear of the unit
and the discharge through the louvered top panel.
The minimum clearance between the back of the unit
and a wall is 15 inches. If the overhang is less than 7
feet above the unit, the unit must be mounted outside
a plumb line from the eaves of the overhang. The clear
ance on the right and left ends should be a minimum of
2 feet to provide access for servicing. See Figure 5.
II. CONNECTING CHILLED WATER LINES
Refer to the following information: “Multiple Chillers
and Cooling Coils,” page 1; “Operation at Atmospheric
TABLE I
Allowable Distances between Coil Model 405, 406, 407, 414 and Chiller (Note 1)
Pipe SizeBryant Quick-ConnectPolyethylene
(Inches)Tubing (Note 2)
3/4"42'40'45'6Г
1"90'176'189'200'
Note 1: Values shown are for one direction only, and
using Bryant water coils. Total length of pipe (from
chiller to coil and return) would be double the values
shown. All distances shown are shown on the predica
tion that only long elbows are used. Galvanized well
head elbows are used with the polyethylene pipe. When
using Bryant Quick-Connect Tubing, avoid any sharp
bends that would tend to restrict or stop the flow
of water.
Note 2: If Quick-Connect Tubing is used and coil is
above chiller water level, refer to PAM 400.2.6.
Simplified Guidelines When
Using Quick-Connect Tubing
1. Do not exceed 12 feet elevation with 3/4" Quick-
Connect.
Pressure,” page 1; and “Freezing Weather Protection,”
page 8.
CopperGalvanized
PipePipePipe
2. Do not exceed 10 feet elevation with 1" QuickConnect.
3. Do not exceed 15 feet of horizontal tubing at those
elevations.
4. Exercise good practice to avoid kinking, sagging
and stretching.
5. Any excess lengths should be coiled up at the lowest
elevation.
6. Polyethylene or hard pipe should be used at higher
installation.
-4-
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.