Maximum Allowable Exposed Vent Lengths Insulation43......
Maximum Equivalent Vent Length44......................
Deductions from Maximum Equivalent Vent Length44........
Altitude Derate Multiplier for U.S.A.64....................
Blower Off Delay Setup Switch64........................
Gas Rate64..........................................
Orifice Size and Manifold Pressure65.....................
Always Ask For
CERTIFIED
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program. For verification
of certification for individual
products, go to
www.ahridirectory.org.
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1--2009E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the complete
and official position of the NFPA or ANSI on the referenced
subject, which is represented only by the standard in its entirety.
1
Page 2
987MA
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA--54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an
alarm and battery back--up is installed on the floor level where the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on
each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It
shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of
hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back--up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the timeof completion of installation, the owner shall
have a period of thirty (30) days to comply with the aboverequirements; provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print size no less than one--half (1/2) inch in size, ”GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled ”Equipment Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
c. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design
or venting system components with the equipment, the instructions provided by the manufacturer for installation of
the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
d. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the
parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be
satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation
instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.
e. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain
with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and
Gas Fitters, 239 Causeway Street, Boston, MA 02114. 617--727--9952.
2
Page 3
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous
operation, personal injury, death, or property damage.
Improper installation, adjustment, alteration, service,
maintenance, or use can cause carbon monoxide poisoning,
explosion, fire, electrical shock, or other conditions which
may cause personal injury or property damage. Consult a
qualified service agency, local gas supplier, or your
distributor or branch for information or assistance. The
qualified service agency must use only factory--authorized
and listed kits or accessories when modifying this product.
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component
damage.
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate,
air temperature rise, unit leveling, and unit sizing.
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on heating
equipment, observe precautions in literature, on tags, and on labels
attached to or shipped with furnace and other safety precautions
that may apply.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing
residential construction practices. We require these instructions as a
minimum for a safe installation.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
This is the safety--alert symbol. When you see this symbol on
the furnace and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING,and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify hazards which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
1. Use only with type of gas approved for this furnace. Refer
to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the
“Gas Piping” section.
6. Always install furnace to operate within the furnace’s intended temperature--rise range with a duct system which has an
external static pressure within the allowable range, as specified in the “Start--Up, Adjustments, and Safety Check”
section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by
duct(s) sealed to the furnace casing and terminating outside
the space containing the furnace. See “Air Ducts” section.
8. A gas--fired furnace for installation in a residential garage
must be installed as specified in the warning box in the
“Location” section.
9. The furnacemay be used for construction heat provided that
the furnace installation and operation complies with the first
CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas--Fired Furnaces are CSA design--certified for use with natural and propane gases (see furnace
rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The
furnace is factory--shipped for use with natural gas. A CSA
(A.G.A. and C.G.A.) listed accessory gas conversion kit is
required to convert furnace for use with propane gas.
11. See Table 2 for required clearances to combustible construction.
12. Maintain a 1--in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914
mm) horizontally from the furnace. See NFPA 90B or local
code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood
flooring. In downflow installations, factory accessory floor
base MUST be used when installed on combustible materials and wood flooring. Special base is not required when
this furnace is installed on manufacturer’s Coil Assembly
Part No. CNRV, CNPV, CAP, or CAR or when Coil Box
Part No. KCAKC is used. See Table 2 for clearance to combustible construction information.
987MA
3
Page 4
INTRODUCTION
This 4--way multipoise Category IV condensing furnace is CSA
design--certified as a direct (2-pipe) or non-direct vent (1-pipe)
furnace. (See Fig. 2.)The furnace is factory--shipped for use with
natural gas. The furnace can be converted in the field for use with
propane gas when a factory-supplied conversion kit is used. Refer
to the furnace rating plate for conversion kit information.
This furnace is not approved for installation in mobile homes,
recreational vehicles, or outdoors.
This furnace is designed for minimum continuous return--air
temperature of 60_F(15_C) db or intermittent operation down to
55_F(13_C) db such as when used with a night setback
thermostat. Return-air temperature must not exceed 80_F(27_C)
db. Failure to follow these return-air temperature limits may affect
reliability of heat exchangers, motors, and controls. (See Fig. 3).
The furnace should be sized to provide 100 percent of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. Heating load estimates can
be made using approved methods available from Air Conditioning
Contractors of America (Manual J); American Society of Heating,
987MA
Refrigerating, and Air--Conditioning Engineers; or other approved
engineering methods. Excessive oversizing of the furnace could
cause the furnace and/or vent to fail prematurely.
For accessory installation details, refer to the applicable instruction
literature.
NOTE: Remove all shipping materials, loose parts bag, and
literature before operating the furnace. (See Table 1).
CODES AND STANDARDS
Follow all national and local codes and standards in addition
to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating,
plumbing, and other codes. In absence of local codes, the
installation must comply with the national codes listed below and
all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for
the following:
Safety
S US: National Fuel Gas Code (NFGC) NFPA 54--2009/ANSI
Z223.1--2009 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: National Standard of Canada, Natural Gas and
S US: NFGC and the NFPA 90B. For copies, contact the National
Fire Protection Association Inc., Batterymarch Park, Quincy,
MA 02269; or for only the NFGC contact the American Gas
Association, 400 N. Capitol, N.W., Washington DC 20001
S CANADA: NSCNGPIC. For a copy, contact Standard Sales,
S US: Section 9.3 of the NFPA54/ANSI Z223.1--2009 Air for
Combustion and Ventilation
S CANADA: Part 8 of the CAN/CSA B149.1--2010, Venting
Systems and Air Supply for Appliances
Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors
National Association (SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005
Fundamentals Handbook Chapter 35
Acoustical Lining and Fibrous Glass Duct
S US and CANADA: current edition of SMACNA, NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
S US: NFPA 54/ANSI Z223.1--2009 NFGC; Chapters 5, 6, 7, and 8
and national plumbing codes.
CANADA: CAN/CSA--B149.1--2010, Parts 4, 5, 6, and 9.
In the state of Massachusetts:
S This product must be installed by a licensed plumber or gas fitter.
S When flexible connectors are used, the maximum length shall
not exceed 36 in. (914 mm).
S When lever type gas shutoffs are used they shall be T--handle type.
S The use of copper tubing for gas piping is not approved by the
state of Massachusetts.
Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2011
S CANADA: Canadian Electrical Code CSA C22.1
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component
damage.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing
to protect the furnace electronic control. Precautions will
prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These
precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control,
and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects
may be required. DO NOT TOUCH THE CONTROL
OR ANY WIRE CONNECTED TO THE CONTROL
PRIORTODISCHARGINGYOURBODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a
person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing to
recharge your body with static electricity (for example; DONOT move or shuffle your feet, do not touch ungrounded
objects, etc.).
4. If you touch ungrounded objects (and recharge your body
with static electricity), firmly touch a clean, unpainted metal
surface of the furnace again before touching control or
wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and
new controls into containers before touching ungrounded
objects.
4
Page 5
7. An ESD service kit (available from commercial sources)
mayalsobeusedtopreventESDdamage.
ACCESSORIES
See Product Data Sheet for a list of accessories for this product
LOCATION
!
CAUTION
PERSONAL INJURY AND/OR PROPERTY
DAMAGE HAZARD
Improper use or installation of this furnace may result in
premature furnace component failure. This gas furnace may
be used for heating buildings under construction provided
that:
--The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the
space containing the furnace. This prevents a negative
pressure condition as created by the circulating air blower,
causing a flame rollout and/or drawing combustion
products into the structure.
--The furnace is controlled by a thermostat. It may not be
“hot wired” to provide heat continuously to the structure
without thermostatic control.
--Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is
maintained between 55_F(13_C) and 80_F(27_C), with
no evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on
the furnace rating plate, and the gas input rate has been set
to the nameplate value.
--The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
--Verify proper furnace operating conditions including
ignition, gas input rate, air temperature rise, and venting
according to these installation instructions.
General
These furnaces are shipped with the following materials to assist in
proper furnace installation. These materials are shipped in the
main blower compartment.See Table 1 for loose parts bag
contents.
This furnace must:
S be installed so the electrical components are protected from
water.
S not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
S be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown in
Table 2 or on the furnace clearance to combustible construction
label.
Failure to follow this warning could result in personal injury
or death and unit component damage.
Corrosive or contaminated air may cause failure of parts
containing flue gas, which could leak into the living space.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products. Do not install
furnace in a corrosive or contaminated atmosphere. Make
sure all combustion and circulating air requirements are met,
in addition to all local codes and ordinances.
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings
S Buildings with indoor pools
S Laundry rooms
S Hobby or craft rooms
S Chemical storage areas
If air is exposed to the following substances, it should not be used
for combustion air, and outdoor air may be required for
combustion:
S Permanent wave solutions
S Chlorinated waxes and cleaners
S Chlorine based swimming pool chemicals
S Water softening chemicals
S De--icing salts or chemicals
S Carbon tetrachloride
S Halogen type refrigerants
S Cleaning solvents (such as perchloroethylene)
S Printing inks, paint removers, varnishes, etc.
S Hydrochloric acid
S Cements and glues
S Antistatic fabric softeners for clothes dryers
S Masonry acid washing materials
All fuel--burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal must be
made between the furnace cabinet and the return--air duct to
prevent pulling air from the burner area.
987MA
5
Page 6
!
WARNING
!
WARNING
987MA
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18 in.
(457 mm) above the floor. The furnace must be located or
protected to avoid damage by vehicles. When the furnace is
installed in a public garage, airplane hangar, or other
building having a hazardous atmosphere, the furnace must
be installed in accordance with the NFPA 54/ANSI
Z223.1--2009 or CAN/CSA B149.2--2010. (See Fig. 5.)
Table 1 – Loose Parts Bag Contents (Provided in blower compartment)
DESCRIPTIONQUANTITY
AirIntakePipeFlange1
Vent Pipe Flange1
Coupling Flange Gaskets2
Sharp Tip Screws (Vent and Inlet Flanges)10
Vent Pipe Coupling1
Vent Pipe Coupling Clamps2
Pressure Switch Tube1
Outlet Choke Plate (used with 40k BTUH furnaces, only)1
Drain Tube Elbow1
Drain Extension Tube1
Drain Tube Clamps2
Drain Line Grommet1
Gas Line Grommet1
Gas Line Knockout Plug1
Junction Box Cover1
Junction Box Base1
Green Ground Screw1
Blunt Tip Screws (Junction Box)3
Thermostat Wire Grommet1
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect
return--air ducts to the back of the furnace. (See Fig. 4.)
Location Relative to Cooling Equipment
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless the
damper is in the full--heat or full--cool position.
Table 2 – Minimum Clearances to Combustible Materials for All Units
POSITIONCLEARANCE
Rear0(0mm)
Front (Combustion air openings in furnace and in structure)1in.(25mm)
c. For 1600 CFM ---22 --- in. (559 mm) round or 14 1/2 x 22 1/16--- in. (368 x 560mm) rectangle.
a. For 800 CFM---16 ---in. (406 mm) round or 14 1/2 x 12---i n. (368 x 305 mm) rectangle.
b. For 1200 CFM--- 20--- in. (508 mm) round or 14 1/2 x 19 1/2---i n. (368 x 495 mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in these installation instructions for specific use of single side inlets. The use of both side inlets, a combination
NOTE: Doors may vary by model.
[668.8]
26 5/16
21
[534.0]
A11522
Fig. 1 -- Dimensional Drawing
7
Page 8
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
987MA
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
Fig. 2 -- Multipoise Orientations
SUPPLY AIR
Fig. 3 -- Freeze Protection and Return Air Temperature
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
80/ 27˚C
60
/ 16˚C
A10490
Fig. 4 -- Prohibited Installations
A10494
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
8
Page 9
AIR FOR COMBUSTION AND
VENTILATION
Introduction
Direct Vent (2--pipe) Applications
When the furnace is installed as a direct vent (2-pipe) furnace, no
special provisions for air for combustion are required. However,
other gas appliances installed in the space with the furnace may
require outside air for combustion. Follow the guidelines below to
insure that other gas appliances have sufficient air for combustion.
Ventilated Combustion Air Applications
When the furnace is installed using the ventilated combustion air
option, the attic or crawlspace must freely communicate with the
outdoor to provide sufficient air for combustion. The combustion
air pipe cannot be terminated in attics or crawlspaces that use
ventilation fans designed to operate during the heating season. If
ventilation fans are present in these areas, the combustion air pipe
must terminate outdoors as a Direct Vent/ 2-Pipe system.
All air for combustion is piped directly to the furnace from a space
that is well ventilated with outdoor air (such as an attic or crawl
space) and the space is well isolated from the living space or
garage. In addition, other gas appliances installed in the space with
the furnace may require outside air for combustion. Follow the
guidelines below to insure that the roof or crawlspace walls have
sufficient free area to provide sufficient air for combustion and
ventilation for the furnaces. The guidelines below can be used to
insure that other gas appliances have sufficient air for combustion.
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
S U.S.A. Installations: Section 9.3 of the NFPA 54/ANSI
Z223.1--2009 , Air for Combustion and Ventilation and
applicable provisions of the local building codes.
S Canada: Part 8 of the CAN/CSA--B149.1--2010, Venting
Systems and Air Supply for Appliances.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion,
ventilation, and dilution of flue gases using permanent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate
with the outdoors.
2. Fig. 6 illustrates how to provide TWO OUTDOOROPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300 mm)
of the ceiling and the second opening MUST commence
within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 6 and Table 3.
c. TWO HORIZONTAL DUCTS require 1 sq. in. (645 sq.
mm) of free areaper 2,000 Btuh (1,100mm
binedinput for allgasappliances in thespaceper Fig. 6and
Tab le 3 .
d. TWO OPENINGS OR VERTICAL DUCTS require 1
sq. in. (645 sq. mm) of free area per 4,000 Btuh (550
2
/kW) for combined input of all gas appliances in the
mm
space per Fig. 6 and Table 3.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (645 sq. mm) of free area per 3,000 Btuh (734
2
/kW) for combined input of all gas appliances in the
mm
space per Fig. 6 and Table 3.
b. Not less than thesum of the areas ofall vent connectors in
the space.
The opening shall commence within 12 in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at least 1
in. (25 mm) from the sides and back and 6 in. (150 mm) from the
front. The opening shall directly communicate with the outdoors or
shall communicate through a vertical or horizontal duct to the
outdoors or spaces (crawl or attic) that freely communicate with the
outdoors.
2
/kW) of com-
987MA
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make--up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to the
Carbon Monoxide Poisoning Hazard warning in the venting
section of these instructions to determine if an adequate
amount ofmake--up air isavailable.
9
Page 10
Table 3 – Minimum Free Area Required for Each Combustion AirOpening or Duct to Outdoors
100,000+30,000=(130,000 divided by 4,000)= 32.5 Sq. In. for each two Vertical Ducts or Openings
60,000+40,000=(100,000 divided by 3,000)= 33.3 Sq. In. for each Single Duct or Opening
80,000+30,000=(110,000 divided by 2,000)= 55.0 Sq. In. for each two Horizontal Ducts
Table 4 – Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
987MA
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
0.60
0.50
0.40
0.30
0.20
0.10
0.00
NP = Not Permitted
304050406080100120140
1,050
(29.7)
1,260
(35.6)
1,575
(44.5)
2,100
(59.4)
3,150
(89.1)
6,300
(178.0)
NPNPNPNPNPNPNPNPNP
1,400
(39.6)
1,680
(47.5)
2,100
(59.4)
2,800
(79.2)
4,200
(118.9)
8,400
(237.8)
1,750
(49.5)
2,100
(59.4)
2,625
(74.3)
3,500
(99.1)
5,250
(148.6)
10,500
(297.3)
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of
Opening and D uct
Sq. In (Sq. mm)
Round Duct
In. (mm) Dia
EXAMPLES: Determining Free Area
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
SpaceVolumeFt3(M3)
1,400
(39.6)
1,680
(47.5)
2,100
(59.4)
2,800
(79.2)
4,200
(118.9)
8,400
(237.8)
DUCTS
TO
OUTDOORS
1,500
(42.5)
1,800
(51.0)
2,250
(63.7)
3,000
(84.9)
4,500
(127.3)
9,000
(254.6)
1 SQ IN.
PER 4000
BTUH*
2,000
(56.6)
2,400
(67.9)
3,000
(84.9)
4,000
(113.2)
6,000
(169.8)
12,000
(339.5)
TWO OPENINGS OR
VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH)
Free Area of Open-
2,500
(70.8)
3,000
(84.9)
3,750
(106.1)
5,000
(141.5)
7,500
(212.2)
15,000
(424.4)
(550 SQ. MM/KW)
ing and Duct
Sq. In ( mm)
(101.9)
(127.3)
(169.8)
(254.6)
18,000
(509.2)
3,000
(84.9)
3,600
4,500
6,000
9,000
Round Duct
In. (mm) Dia.
3,500
(99.1)
4,200
(118.9)
5,250
(148.6)
7,000
(198.1)
10,500
(297.1)
21,000
(594.1)
(305mm)
12″ MAX
1 SQ IN.
PER 2000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 2000
BTUH*
(305mm)
12″ MAX
CIRCULATING AIR DUCTS
NOTE: Use any of the following combinations of openings:
B
AIR DUCTS
CIRCULATING
A
*Minimum dimensions of 3---in. (76 mm).
OF COMBUSTION AIR
CLEARANCE IN FRONT
A&BC&DD&EF&G
D
VENT
THROUGH
ROOF
(76mm)
AT LEAST 3 IN.
OPENINGS SHALL BE
OUTDOORS
C
DUCT
TO
E
12″ MAX
(305mm)
F
1 SQ IN.
1 SQ IN.
G
1 SQ IN.
PER 4000
BTUH*
12″
MAX
PER
4000
BTUH*
OUTDOORS
PER
4000
BTUH*
12″
MAX
(305mm)
(305mm)
Fig. 6 -- Air for Combustion, Ventilation, and Dilution for Outdoors
10
A03174
Page 11
CONDENSATE TRAP
Condensate Trap--Upflow Orientation
When the furnace is installed in the upflow position, it is not
necessary to relocate the condensate trap or associated tubing.
Refer to Fig. 7 for upflow condensate trap information. Refer to
Condensate Drain section for information how to install the
condensate drain.
Condensate Trap--Downflow Orientation.
When the furnace is installed in the downflow position, the
factory--installed trap will be located at the upper left corner of the
collector box. When the furnace is installed in the downflow
orientation, the factory--installed trap must be relocated for proper
condensate drainage.
To Relocate the Condensate Trap:
S Orient the furnace in the downflow position.
S Fig. 8 shows the condensate trap and tubing before and after
relocation.
S Refer to the appropriate figure to begin the trap conversion.
S Remove the relief tube from the condensate trap.
S Remove the screw that secures the condensate trap to the
collector box.
S Remove the trap.
S Remove the relief tube from of the port on the collector box. It is
not necessary to remove thehose from the inducer assembly.
S Remove the pressure switch tube from the port on the collector
box.
S Remove the pressure switch tube from the stand--offs on the
inducer assembly
S Loosen the clamp around the inlet of the vent elbow on the
inducer.
S Removethe middle and bottom plugs from the lower right side
of the collector box and set aside. Do Not Discard Plugs.
S Refer to the appropriate figure to begin the trap conversion.
S Install the 2 plugs previous removed from the collector box in
the ports where the condensate trap was removed.
S Install the trap over the ports on the lower right side of the
collector box.
S Secure the trap to the collector box with the screw.
S Connect the relief tube to the condensate trap to the relief port of
the condensate trap.
S If necessary, slide the relief tube in the inducer stand--offs to
adjust the position of the tube.
S Connect the relief tube to the relief port of the condensate trap.
S Route the pressure switch tube to the port on the collector box
next to the condensate trap. Trim off any excesstube to avoid
sags or kinks in the tube.
S Rotate the vent elbow to the desired position and tighten the
clamp 15 lb--in.
S Refer to Condensate Drain section for information how to install
the condensate drain.
Condensate Trap--Horizontal Orientation.
When the furnace is installed in the horizontal right position, the
factory--installed trap will be located at the bottom left corner of the
collector box. When the furnace is installed in the horizontal left
position, the factory--installed trap will be located at the top of the
collector box. The trap must be repositioned on the collector box
for proper condensate drainage.
When the furnace is installed as a direct--vent furnace, a field
supplied, accessory Horizontal Installation Kit is required for all
horizontal installations. The kit contains a rubber Casing Grommet
designed to seal between the furnace casing and the condensate
trap.
NOTE: The condensate trap extends below the side of the casing
in the horizontal position. A minimum of 2 in. (51 mm) of
clearance is required between the casing side and the furnace
platform for the trap to extend out of the casing in the horizontal
position. In areas where the ambient temperature will fall below
32_ F. ( 0_C), a field--supplied condensate freeze protection kit is
required. See Product Data for current kit offering. Follow the
instructions included in the kit.
To Relocate the Condensate Trap:
S Remove the knockout in the casing for the Casing Grommet.
S Install the grommet in the casing.
NOTE:This grommet is only required for Direct--Vent
applications.
S Orient the furnace in the desired position.
S Allow for 2 in. (51 mm) of clearance underneath the furnace for
the condensate trap and drain line.
S Fig. 9 shows the condensate trap and tubing before and after
relocation in the horizontal right position.
S Fig. 10 shows the condensate trap and tubing before and after
relocation in the horizontal left position.
S Refer to the appropriate figure to begin the trap conversion.
S Remove the relief tube from the condensate trap.
S Remove the screw that secures the condensate trap to the
collector box.
S Remove the trap.
Horizontal Left only:
S Remove the relief tube from the port on the collector box. It is
not necessary to remove thetube from the inducer assembly.
S Remove the pressure switch tube from the port on the collector
box.
S Remove the pressure switch tube from the stand--offs on the
inducer assembly.
For Horizontal Right only:
S The pressure switch tube location is not modified.
S Loosen the clamp around the inlet of the vent elbow on the
inducer.
S Remove the plugs from the collector box and set aside. Do Not
Discard Plugs.
For Horizontal Left only:
S Removethe middle and right plug from the ports at the bottom
of the collector box.
For Horizontal Right only:
S Remove the plug to the right of the condensate trap.
S Refer to the appropriate figure to begin the trap conversion.
S Install the plugs previous removed from the collector box in the
ports where the condensatetrap was removed.
S Install the trap over the ports on the lower side of the collector
box.
S Secure the trap to the collector box with the screw.
S Connect the relief tube to the condensate trap to the relief port of
the condensate trap.
S If necessary, slide the relief tube in the inducer stand--offs to
adjust the position of the tube.
987MA
11
Page 12
For Horizontal Left only:
S Connect the relief tube to the relief port of the condensate trap.
S Connect the pressure switch tube to the port on the collector box
next to the condensate trap. Trim off any excesstube to avoid
sags or kinks in the tube.
S Rotate the vent elbow to the desired position and tighten the
clamp 15 lb--in.
S Refer to Condensate Drain section for information how to install
the condensate drain.
Condensate Drain Protection
Freezing condensate left in condensate trap and drain line may
cause cracks, and possible water damage may occur. Freeze
protection of the condensate trap is required when the furnace is
installed in the horizontal position and the attic temperature is
below 32 deg. F (0 deg. C).
If freeze protection for the condensate trap is required, use
condensate freeze protection accessory.
See Product Data for current kit offering.
The remaining condensate drain line can be protected by using a 3
to 6 watt per ft. (.3M) at 120v and 40_F(4.4_C) self--regulating,
shielded, and waterproof heat tape. Wrap field drain pipe with heat
tape, approximately 1 wrap per ft. (.3M). Follow manufacturer’s
recommendations and installation instructions supplied with heat
tape.
987MA
Collector Box
Plugs
Condensate Trap
Relief Port
Fig. 7 -- Upflow Trap Configuration
Vent Pipe Clamp
Pressure Switch
(Appearance May Vary)
Vent Elbow Clamp
Vent Elbow
Collector Box
Plug
Condensate Trap
Relief Port
Condensate Trap
Outlet
Port
A11306
12
Page 13
Remove relief tube from relief
port on condensate trap.
Remove pressure switch tube from
pressure switch port.
Remove trap from
collector box.
Loosen clamp on inlet
to vent elbow.
Install plugs on
open ports on
collector box.
Connect relief tube to
port on collector box.
Route tube through
7
inducer stand-offs
Remove tube from
relief port.
Remove middle and bottom plugs.
DO NOT DISCARD.
Trim excess tube.
8
Connect pressure switch
tube to port on collector box.
Attach condensate trap
with screw to collector
box.
987MA
Rotate elbow to
desired position and
9
tighten clamp to
15 lb.-in.
Slide tube in stand-offs
to adjust length.
Connect relief tube to
relief port on condensate
trap.
Align condensate trap
over middle and bottom
ports of collector box.
A11277
Fig. 8 -- Downflow Trap Configuration
(Appearance May Vary)
13
Page 14
Remove plug from
collector box.
DO NOT DISCARD.
If alternate vent position
is required, loosen clamp
on inlet of vent elbow.
987MA
Remove trap from
collector box.
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Right Orientation
Slide relief tube in
stand-offs to adjust length.
Attach condensate trap
to collector box with
screw.
Install plug in open
port on collector box.
Horizontal Right Trap Configuration
Vent elbow shown in alternate
orientation. Tighten clamp on
inlet to vent elbow 15 lb.-in.
Align trap over middle and
right-hand port on collector box.
A11278
Fig. 9 -- Horizontal Right Trap Configuration
(Appearance May Vary)
14
Page 15
If alternate vent position
is required, loosen clamp
on vent elbow inlet.
Remove relief tube
from port on collector
box.
Remove trap from
collector box.
Remove relief tube
from relief port on
condensate trap.
Remove pressure switch tube
from port on collector box.
987MA
Remove middle and right
plug from collector box.
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Left Orientation
Rotate elbow to
desired position and
torque clamp on inlet
15 lb.-in.
Slide relief tube in
stand-offs to adjust
length.
Attach condensate
trap to collector box
with screw.
Align trap over middle
and right-hand port on
collector box.
Install plugs in open
ports on collector box.
Connect relief tube to
port on collector box.
Trim excess tube.
Route pressure switch tube
underneath relief tube and
connect to port on collector box.
Connect relief tube to
relief port on condensate
trap.
Horizontal Left Trap Configuration
A11279
Fig. 10 -- Horizontal Left Configuration
(Appearance May Vary)
15
Page 16
CONDENSATE DRAIN CONNECTION
Upflow/Downflow Orientation
In the Upflow or Downflow orientation, the condensate trap is
inside the furnace casing. The condensate drain must be routed
from the trap through the furnace casing. The condensate drain can
be routed through the left or right side of the casing. (The left or
right side is as you are viewing the furnace.) The furnace
condensate drain can be connected to the Air Conditioning
condensate drain as shown in Fig. 12.
NOTE: On narrower casings, it may be easier to remove the
condensate trap, connect the drain line components and re-install
the condensate trap. Read the steps thoroughly to familiarize
yourself with the required steps.
For Right Side Condensate Drain:
1. Remove the 7/8--in. knock--out from the right side of the
casing. (See Fig. 11 .)
2. Remove the pre--formed drain tube and two spring clamps
from the loose parts bag.
987MA
3. Slide a spring clamp 1 inch (25 mm) down the plain end of
the drain tube.
4. From inside the casing, insert the formed grommet end of
the tube through the 7/8--in. knockout in the casing.
5. Pull the tube through the casing from the outside until it is
seated in the knockout
6. Attach the plain end of the drain tube to the outlet stub on
the drain trap. Secure the drain tube to the trap with the
spring clamp.
7. Slide a spring clamp over the open end of the drain tube
outside the casing.
8. Open the spring clamp and connect a field--supplied 1/2--in.
CPVC street elbow to the open end of the drain tube. (See
Fig. 13.)
9. Connect additional 1/2--in. CPVC piping to a condensate
pump approved for use with acidic furnace condensate or to
a code--approved drain.
For Left Side Condensate Drain Connection:
1. For left side condensate drainage, the drain line is routed
from the condensate trap, behind the inducer and out
through the left side of the casing. A pre-formed “Z” pipe is
provided in the loose parts bag shipped with the furnace.
The “Z” pipe is long enough to extend out of the casing on
the 14 3/16-in. (360 mm) wide furnace. Larger casings will
require a field supplied CPVC pipe and to extend the drain
line out of the furnace.
2. The “Z” pipe is connected to the condensate trap by
modifying the formed rubber drain tube. Connect the drain
line as shown below:
3. Remove the knock-out from the left side of the casing. (See
Fig. 11.)
4. Install the grommet for the 1/2-in. CPVC drain line in the
7/8-in. knockout in the casing.
5. Remove the pre-formed drain tube, the offset 1/2-in. CPVC
pipe and two spring clamps from the loose parts bag.
6. Remove the formed grommet on the tube by cutting the
tube along the vertical line located about 1 inch (25 mm)
away from the formed grommet.(See Fig. 14.)
7. Slide a spring clamp 1 inch (25 mm) down the plain end of
the drain tube.
8. With the bend in the tube oriented horizontally and plain
end of the tube pointing away from you, insert the 1/2-in.
CPVC pipe into the other end of the drain tube. Rotate the
tube so the offset in the tube points away from you. Slide a
spring clamp over the open end of the 1/2-in. CPVC tube
and secure the cut end of drain tube to the pipe. (See Fig.
15)
9. Prime the bare end of the pipe with CPVC primer.
10. Route the offset pipe behind the inducer assembly and
through the grommet in the casing, if the “Z” pipe is long
enough. If the “Z” pipe is not long enough, continue with
installation.
11. Attach the plain end of the drain tube to the outlet stub on
the drain trap. Secure the drain tube to the trap with the
spring clamp.
12. If the “Z” pipe does not extend through the casing, slide a
piece of field supplied CPVC through the grommet in the
casing, otherwise, go to Step 17.
13. Cement a 1/2-in. CPVC coupling to the end of the CPVC
pipe.
14. Apply cement to the end of the “Z” pipe connected to the
condensate trap.
15. Connect the field-supplied CPVC pipe to the CPVC pipe
connected to the condensate trap.
16. Cut off excess CPVC pipe outside the casing.
17. Connect additional 1/2-in. CPVC piping to a condensate
pump approved for use with acidic furnace condensate or to
a code-approved drain.
18. When a condensate pump is not used, slope the pipe away
from the furnace to allow for proper drainage.
Horizontal Orientation
1. In the Horizontal orientation, a field supplied accessory
drain trap grommet is required to seal the gap between the
casing and the condensate trap for direct vent applications,
only. The condensate trap outlet extends 2 in. (51 mm)
below the furnace casing. To allow for servicing the trap,
the condensate drain tube in the loose parts bag can be
modified to make a coupler to allow for future service of the
condensate trap and drain line.
2. Remove the knock-out for the condensate trap in the side of
the casing.
3. Install the drain trap grommet in the casing. (For direct vent
applications.) If necessary, remove the trap, install the
grommet and re-install the trap.
4. Remove the pre-formed drain tube, the offset 1/2-in. CPVC
pipe and two spring clamps from the loose parts bag.
5. Remove the formed grommet on the tube to create an elbow
or straight connector. (See Fig. 14.)
6. Connect the cut tube to the outlet of the condensate trap
with 1 spring clamp.
7. Slide the other spring clamp down the plain end of the drain
tube.
8. Connect additional 1/2-in. CPVC piping to the open end of
the tube.
9. Slide the spring clamp down over the 1/2-in. CPVC pipe
10. Connect additional 1/2-in. CPVC piping to a condensate
pump approved for use with acidic furnace condensate or to
a code-approved drain.
11. When a condensate pump is not used, slope the pipe away
from the furnace to allow for proper drainage.
16
Page 17
!
CAUTION
Cut and remove formed end of
drain tube for left side and horizontal
drain connection
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
Fig. 11 -- Knockout Removal
OPEN STAND
PIPE FOR
A/C OR
HUMIDIFIER
DRAIN
TEE
TO OPEN
DRAIN
Fig. 12 -- Example of Field Drain Attachment
A11305
A11276
RIGHT SIDE DRAIN ELBOW
Fig. 14 -- Modify Drain Tube
Attach tube to condensate trap
Cut formed end o
condensate drain tube
Field supplied 1/2” CPVC
coupling & drain extension
17 1/2“, 21” and 24 1/2” casing
Field supplied 1/2”
CPVC to drain
Casing grommet from
loose parts bag
Connect short end
of “Z” pipe to modied
drain tube
TRAP, DRAIN ELBOW WITH DISCHARGE PIPE
Modied drain tube connect to
condensate trap and “Z” pipe
INSTALL CLAMPS ON DRAIN TUBE
ATTACH DRAIN TUBE TO CONDENSATE
DRAIN TRAP
PULL DRAIN STUB
THROUGH CASING
Fig. 13 -- Formed Tube Grommet
A11342
Remove knockout.
Install grommet before
relocating condensate
trap.
A11348
Fig. 16 -- Horizontal Drain Trap Grommet
17
Page 18
INSTALLATION
Upflow Installation
NOTE: The furnace must be pitched forward as shown in Fig. 22
for proper condensate drainage.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.
Connect supply--air duct to flanges on furnace supply--air outlet.
Bend flange upward to 90_ with wide duct pliers. (See Fig. 19.)
The supply--air duct must be connected to ONLY the furnace
supply--outlet--air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach
supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.
Return Air Connections
987MA
!
WARNING
FIRE HAZARD
A failure to follow this warning could cause personal injury,
death and/or property damage.
Never connect return--air ducts to the back of the furnace.
Follow instructions below.
The return--air duct must be connected to bottom, sides (left or
right), or a combination of bottom and side(s) of main furnace
casing. Bypass humidifier may be attached into unused return air
side of the furnace casing. (See Fig. 23, 24, 25.)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove this panel when bottom return
air is used. This panel may be used as the bottom closure of an
accessory bottom return air box, or discarded. To remove bottom
closure panel, perform the following:
1. Tilt or raise furnace and remove 4 screws holding bottom
plate. (See Fig. 21.)
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. This panel MUST be in place when
only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and
some HORIZONTAL configurations. Do not use side return--air
openings in DOWNFLOW configuration. (See Fig. 23, 24, 25.)
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 20.) Install field--supplied, 5/16 x 1--1/2 in. (8 x 38
mm) (max) corrosion--resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used.
It may be necessary to remove and reinstall bottom closure panel to
install leveling legs. To remove bottom closure panel, see Item 1 in
Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each
bottom corner of furnace.
2. For each leg, install nut on bolt and then install bolt with
nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
Downflow Installation
NOTE: The furnace must be pitched forward as shown in Fig. 22
for proper condensate drainage.
Supply Air Connections
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3
accessories are used:
S Special Base, KGASB
S Cased Coil Assembly Part No. CNPV, CNRV, CAP, or CAR
S Coil Box Part No. KCAKC
1. Determine application being installed from Table 6.
2. Construct hole in floor per Table 6 and Fig. 18.
3. Construct plenum to dimensions specified in Table 6 and
Fig. 18.
4. Install special base coil assembly or coil box as shown in in
Fig. 18.
NOTE: It is recommended that the perforated supply--air duct
flanges be completely removed from furnace when installing the
furnace on a factory--supplied cased coil or coil box. To remove the
supply--air duct flange, use wide duct pliers or hand seamers to
bend flange back and forth until it breaks off. Be careful of sharp
edges. (See Fig. 19.)
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
Connect supply--air duct to supply--air outlet on furnace. Bend
flange inward past 90_ with wide duct pliers (See Fig. 19.) The
supply--air duct must be connected to ONLY the furnace supply
outlet or air conditioning coil casing (when used). When installed
on combustible material, supply--air duct must be connected to
ONLYthefactory--approvedaccessorysubbase, ora
factory--approved air conditioning coil casing. DO NOT cut main
furnace casing to attach supply side air duct, humidifier, or other
accessories. All accessories MUST be connected to duct external to
furnace casing.
Return Air Connections
!
WARNING
FIRE HAZARD
A failure to follow this warning could cause personal injury,
death and/or property damage.
Never connect return--air ducts to the back of the furnace.
Follow instructions below.
The return--air duct must be connected to return--air opening
(bottom inlet). DO NOT cut into casing sides (left or right).
Bypass humidifier connections should be made at ductwork or coil
casing sides exterior to furnace. (See Fig. 24.)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove and discard this panel when
18
Page 19
bottom return air is used in downflow applications. To remove
bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 4 screws holding bottom
plate. (See Fig. 21.)
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Horizontal Installation
NOTE: The furnace must be pitched forward as shown in Fig. 22
for proper condensate drainage.
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect
return--air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawlspace
on either the left--hand (LH) or right--hand (RH) side. The furnace
can be hung from floor joists, rafters or trusses or installed on a
non--combustible platform, blocks, bricks or pad.
Platform Furnace Support
Construct working platform at location where all required furnace
clearances are met. (See Table 2 and Fig. 26.) For furnaces with
1--in. (25 mm) clearance requirement on side, set furnace on
non--combustible blocks, bricks or angle iron. For crawlspace
installations, if the furnace is not suspended from the floor joists,
the ground underneath furnace must be level and the furnace set on
blocks or bricks.
Suspended Furnace Support
The furnace must be supported under the entire length of the
furnace with threaded rod and angle iron. (See Fig. 27.) Secure
angle iron to bottom of furnace as shown.
Roll--Out Protection
Provide a minimum 12--in. x 22--in. (305 x 559 mm) piece of sheet
metal for flame roll--out protection in front of burner area for
furnaces closer than 12--in. (305 mm) above the combustible deck
or suspended furnaces closer than 12--in. (305 mm) to joists. The
sheet metal MUST extend underneath the furnace casing by 1--in.
(25 mm) with the door removed.
The bottom closure panel on furnaces of widths 17--1/2--in. (445
mm) and larger may be used for flame roll--out protection when
bottom of furnace is used for return air connection. See Fig. 26 for
proper orientation of roll--out shield.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.
Connect supply--air duct to flanges on furnace supply--air outlet.
Bend flange upward to 90_ with wide duct pliers. (See Fig. 19.)
The supply--air duct must be connected to ONLY the furnace
supply--outlet--air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach
supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.
Return Air Connections
The return--air duct must be connected to bottom of the furnace.
The side of casing that faces downward may also be used for return
air connection. A combination of the bottom and downward
facing side may also be used. Bypass humidifier may be attached
into unused return air side of the furnace casing. (See Fig. 25.)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. Remove this panel when bottom return
air is used. This panel may be used as a roll--out shield or discard.
To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 4 screws holding bottom
plate. (See Fig. 21.)
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. This panel MUST be in place when
side return air inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air
connections (See Fig. 25.)
Filter Arrangement
!
WARNING
FIRE, CARBON MONOXIDE AND POISONING
HAZARD
Failure to follow this warning could result in fire, personal
injury or death.
Never operate a furnace without a filter or filtration device
installed. Never operate a furnace with filter or filtration
device access doors removed.
There are no provisions for an internal filter rack in these furnaces.
An external filter is required.
The furnace is shipped with a factory-supplied Media Filter
Cabinet. The Media Filter Cabinet uses either a standard 1-inch (25
mm) filter or 4-inch (102 mm) wide Media Filter which can be
purchased separately. A field supplied accessory air cleaner may
also be used in place of the media cabinet.
The Media Cabinet is sized for bottom return applications for use
in upflow, downflow and horizontal applications. A 16--inch (406
mm) Media Cabinet is shipped with the 14--3/16-in. (360 mm)
furnace and includes block-off plates
For upflow side return applications, the Media Cabinet (or field
supplied accessory air cleaner) can be installed on the side of the
furnace or side and bottom when a bottom plenum is used. (See
Fig. 17 and 23.)
For downflow applications, the Media Cabinet (or field supplied
accessory air cleaner) must only be connected to the bottom
opening on the furnace. See Fig. 17 and 24.
For horizontal applications, the Media Cabinet (or field supplied
accessory air cleaner) for all models can be connected to the
bottom opening on the furnace. For side return use in the
horizontal position, refer to Fig. 25. If both side and bottom
openings are used in Fig. 25, each opening used will require a
filter.
The media cabinet (or field supplied accessory air cleaner) can also
be installed in the common return duct prior to entering the return
air opening in any orientation.
Refer to the instructions supplied with Media Cabinet or accessory
air filter for assembly and other details. See Table 5 for filter size
details.
987MA
19
Page 20
Table 5 – Filter Size Information -- In. (mm)
FURNACE CASING WIDTH
17 --- 1/2 (445)
21 (533)
24 --- 1/2 (622)
* Recommended to maintain air filter face vel ocity. See Product Data for part number.
SIDE RETURNBOTTOM RETURN
16 x 25 x 3/4
(406 x 635 x 19)
16 x 25 x 3/4
(406 x 635 x 19)
16 x 25 x 3/4
(406 x 635 x 19)
FILTER SIZE
Air Filter Located in Filter Cabinet
FILTER CABINET HEIGHT --- IN (MM)F I L T E R S I Z E --- I N ( M M )FILTER TYPE
(1) 16 x 25 x 3/4*
16 (406)
987MA
* Filters with a side return ---air may have a different filter size. Measure the filter to obtain the correct size.
* Recommended to maintain air filter face vel ocity. See Product Data for part number.
20 (508)
24 (610)
(406 x 635 x 19) or
(1) 16 x 25 x 4---5/16
(406 x 635 x 110)
(1) 20 x 25 x 3/4*
(508 x 635 x 19) or
(1) 20 x 25 x 4---5/16
(508 x 635 x 110)
(1) 24 x 25 x 3/4*or
(610 x 635 x 19) or
(1) 24 x 25 x 4---5/16
(610 x 635 x 110)
16 x 25 x 3/4
(406 x 635 x 19)
20 x 25 x 3/4
(508 x 635 x 19)
24 x 25 x 3/4
(610 x 635 x 19)
FILTER TYPE
Washable*
Washable*
Washable*
Washable or Media*
Washable or Media*
Washable or Media*
20
Page 21
14-3/16 and 17-1/2-in.
Furnace
21-in. Furnace
4-Ton or less, AC
capacity airflow
4-in.
Block Off
Plate
Screws
1/2-in.
16-in. Media Cabinet
Media Cabinet Installation
Side Return
21- or 24-1/2-in.
Furnace
Up to 5-Ton AC
capacity airflow
20- or 24-in. Media
Cabinet
Bottom Return Plenum
20- or -24-in. Media Cabinet Installation
for Combination Side and Bottom Return
20-in. Media Cabinet
Media Cabinet Installation Option for
4-Ton or Less A/C Capacity
21-in. Furnace
up to 5-Ton AC
Capacity
24-1/2-in. Furnace
up to 4-Ton AC
Capacity
45°
Transition
20- or 24-in. Media Cabinet
20- or -24-in. Media Cabinet Installation
with Angled Transition
987MA
14-3/16-in. Furnace
Screw
Filler plates
14--3/16-in. Furnace with Filler Plates, Centered
14-3/16-in. Furnace
Screws
Screw
Filler plate
14--3/16-in. Furnace with Filler Plates, Off--Set to Right
A11437
Fig. 17 -- Media Filter
21
Page 22
FURNACE
(OR COIL CASING
WHEN USED)
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
987MA
FURNACE
CASING
WIDTH
IN. (mm)
17–1/2
(445)
21
(533)
24 --- 1/2
(622)
A
PLENUM
OPENING
B
C
FLOOR
OPENING
D
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 18 -- Installation on Combustible Flooring
Table 6 – Opening Dimensions -- In. (mm)
APPLICATION
Upflow Applications on Combustible or Noncombustible Floor-
Downflow Applications on Noncombustible Flooring (KGASB
Downflow applications on combustible flooring (KGASB sub-
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB
Upflow Applications on Combustible or Noncombustible Floor-
Downflow Applications on Noncombustible Flooring (KGASB
Downflow applications on combustible flooring (KGASB sub-
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB
Upflow Applications on Combustible or Noncombustible Floor-
Downflow Applications on Noncombustible Flooring (KGASB
Downflow applications on Combustible flooring (KGASB sub-
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB
ing (KGASB subbase not required)
subbase not required)
base required)
subbase not required)
ing (KGASB subbase not required)
subbase not required)
base required)
subbase not required)
ing (KGASB subbase not required)
subbase not required)
base required)
subbase not required)
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
PLENUM OPENINGFLOOR OPENING
ABCD
16
(406)
15--- 7/8
(403)
15--- 1/8
(384)
15--- 1/2
(394)
19--- 1/2
(495)
19--- 3/8
(492)
18--- 5/8
(473)
19
(483)
23
(584)
22--- 7/8
(581)
22--- 1/8
(562)
22--- 1/2
(572)
21--- 5/8
(549)
19
(483)
19
(483)
19
(483)
21--- 5/8
(549)
19
(483)
19
(483)
19
(483)
21--- 1/8
(537)
19
(483)
19
(483)
19
(483)
16--- 5/8
(422)
16--- 1/2
(419)
16--- 3/4
(425)
16--- 1/2
(419)
20--- 1/8
(511)
20
(508)
20--- 1/4
(514)
20
(508)
23--- 5/8
(600)
23--- 1/2
(597)
23--- 3/4
(603)
23--- 1/2
(597)
22--- 1/4
(565)
19--- 5/8
(498)
20--- 5/8
(600)
(508)
22--- 1/4
(565)
19--- 5/8
(498)
20--- 5/8
(600)
(508)
22--- 1/4
(565)
19--- 5/8
(498)
20--- 5/8
(600)
(508)
A10491
20
20
20
22
Page 23
PERFORATED
DISCHARGE DUCT
FLANGE
UPFLOWDOWNFLOWHORIZONTAL
90°
90°
5/
(8mm)
(44mm)
16
1 3 / 4 ″
120°
MIN
YES
YES
NO
120°
MIN
YES
YES
NO
120°
MIN
YES
YES
NO
987MA
A10493
Fig. 19 -- Duct Flanges
″
(8mm)
5/
16
″
3
/ 4 ″
1
(44mm)
(8mm)
5
/
16
″
1
(44mm)
3/
4 ″
3/
1
4 ″
(44mm)
Fig. 20 -- Leveling Legs
LEVEL 0-IN. (0 MM) TO
1/2-IN. (13 MM) MAX
(8mm)
5/
16
″
UPFLOW OR
DOWNFLOW
A89014
Fig. 21 -- Removing Bottom Closure Panel
MIN 1/4-IN. (6 MM) TO
1/2-IN. (13 MM) MAX
HORIZONTAL
Fig. 22 -- Furnace Pitch Requirements
BOTTOM
CLOSURE
PAN EL
BOTTOM PLA TE
A11092
A11237
23
Page 24
ANY COMBINATION OF 1, 2, OR 3 PERMITTED.
987MA
Fig. 23 -- Upflow Return Air Configurations and Restrictions
Fig. 25 -- Horizontal Return Air Configurations
A11036
HORIZONTAL TOP
RETURN NOT
PERMITTED FOR
ANY MODEL
and Restrictions
A11037
Fig. 24 -- Downflow Return Air Configurations
and Restrictions
A11038
24
Page 25
COMBUSTION - AIR PIPE
(SEE VENTING SECTION)
2-IN.
(51 mm)
30 IN. (762 mm)
MIN. WORK AREA
987MA
ROLLOUT PROTECTION REQUIRED
Install 12” x 22” (305 x 559 mm) sheet
metal in front of burner compartment
area.
Fig. 26 -- Working Platform for Attic Installation
COMBUSTION-AIR PIPE
(SEE VENTING SECTION)
2-IN.
(51 mm)
A11154
A11155
Fig. 27 -- Suspended Furnace Installation
25
Page 26
AIR DUCTS
General Requirements
The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems DesignGuidelines reference tables available from your local distributor.
The duct system should be sized to handle the required system
design CFM at the design external static pressure. The furnace
airflow rates are provided in Table 7--Air Delivery--CFM (With
Filter). When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to the
furnace casing and terminating outside the space containing the
furnace.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply-- and return--duct connections to furnace with code
approved tape or duct sealer.
987MA
NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be
insulated to enhance system performance. When air conditioning is
used, a vapor barrier is recommended.
Maintain a 1--in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36--in. (914 mm) horizontally
from the furnace. See NFPA 90B or local code for further
requirements.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow
and 10 ft. (3 M) of main duct to the first branch take--off may
require internal acoustical lining. As an alternative, fibrous
ductwork may be used if constructed and installed in accordance
with the latest edition of SMACNA construction standard on
fibrous glass ducts. Both acoustical lining and fibrous ductwork
shall comply with NFPA 90B as tested by UL Standard 181 for
Class 1 Rigid air ducts.
NOTE: For horizontal applications, the top most flange may be
bent past 90_to allow the evaporator coil to hang on the flange
temporarily while the remaining attachment and sealing of the coil
are performed.
26
Page 27
INPUT
BTUH
Table 7 – Air Delivery -- CFM (With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See Notes 1 and 2.)
1. Nominal 350 CFM/ton cooling airflow is delivered with SW1-5 and SW4-2 set to OFF.
Set SW1-5 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW4-3 to ON for nominal 325 CFM/ton (-7% airflow).
Set both SW1-5 and SW4-3 to ON for nominal 370 CFM/ton (+7% airflow).
2. Maximum cooling airflow is achieved when switches SW3-1, SW3-2, SW3-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
3. All heating CFM's are when minimum/intermediate heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) are both set to OFF.
4. Ductwork must be sized for maximum-heating CFM within the operational range of E.S.P. Operation within the blank areas of the chart is not recommended
because maximum-heat operation will be above 1.0 E.S.P.
5. All airflows on 21" (533 mm) casing size furnaces are 5% less on side return only installations.
6. Side returns for 24.5" (622 mm) casing sizes require two sides, or side and bottom, to allow sufficient airflow at the return of the furnace.
28
Page 29
GAS PIPING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of
life.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control
manifold and gas valve.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until
gas supply line is permanently installed to protect the valve
from moisture and debris. Also, install a sediment trap in the
gas supply piping at the inlet to the gas valve.
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S.A. Refer to
current edition of CAN/CSA B149.1 in Canada.
Installations must be made in accordance with all authorities
having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.
NOTE: Use a back--up wrench on the inlet of the gas valve when
connecting the gas line to the gas valve.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed
plumber or gas fitter.
2. When flexible connectors are used, the maximum length
shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves
are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
Refer to Table 8 for recommended gas pipe sizing. Risers must be
used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft. (1.8 M). Joint compound (pipe dope) should be applied
sparingly and only to male threads of joints. Pipe dope must be
resistant to the action of propane gas.
!
WARNING
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal
injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a
connector which has previously served another gas
appliance. Black iron pipe shall be installed at the furnace
gas control valve and extend a minimum of 2--in. (51 mm)
outside the furnace.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to
avoid damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed
external to furnace casing and within 6 ft. (1.8 M) of furnace.
Install a sediment trap in riser leading to furnace as shown in Fig.
29. Connect a capped nipple into lower end of tee. Capped nipple
should extend below level of furnace gas controls. Place a ground
joint union between furnace gas control valve and exterior manual
equipment gas shutoff valve.
A 1/8--in. (3 mm) NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas
supply connection to furnace and downstream of manual
equipment shutoff valve.
Piping should be pressure and leak tested in accordance with the
current addition of the NFGC in the United States, local, and
national plumbing and gas codes before the furnace has been
connected. Refer to current edition of NSCNGPIC in Canada.
After all connections have been made, purge lines and check for
leakage at furnace prior to operating furnace.
NOTE:The furnace gas control valve inlet pressure tap
connection is suitable to use as test gauge connection providing
test pressure DOES NOT exceed maximum 0.5 psig (14--In. W.C.)
stated on gas control valve. (See Fig. 50.)
If pressure exceeds 0.5 psig (14--In. W.C.), gas supply pipe must be
disconnected from furnace and capped before and during supply
pipe pressure test. If test pressure is equal to or less than 0.5 psig
(14--In. W.C.), turn off electric shutoff switch located on furnace
gas control valve and accessible manual equipment shutoff valve
before and during supply pipe pressure test. After all connections
have been made, purge lines and check for leakage at furnace prior
to operating furnace.
The gas supply pressure shall be within the maximum and
minimum inlet supply pressures marked on the rating plate with
the furnace burners ON and OFF.
Some installations require gas entry on right side of furnace (as
viewed in upflow). (See Fig. 28.)
Gas Pipe Grommet
For direct vent (2-pipe) applications, the knockout for the gas pipe
must be sealed to prevent air leakage. Remove the knockout, install
the grommet in the knockout, then insert the gas pipe. The
grommet is included in the loose parts bag. See Fig. 28.
* Cubic ft of gas per hr for gas pressures o f 0.5 psig (14---In. W.C.) or less and
a pressure drop of 0.5 --- In. W.C. (based on a 0.60 specific gravit y gas). Ref:
Table 8 above and 6.2 of NFPA54/ANSI Z223.1--- 2009.
Left Side Gas Entry. Gas Pipe
Grommet Required For Direct
Vent Applications.
(3.0)20(6.0)30(9.1)40(12.1)50(15.2)
LENGTH OF PIPE --- FT (M)
10
Gas Pipe Grommet Required
For Direct Vent Applications
987MA
Fig. 28 -- Gas Entry
GAS
SUPPLY
FRONT
MANUAL
SHUT OFF
VALV E
(REQUIRED)
SEDIMENT
TRAP
UNION
Fig. 29 -- Typical Gas Pipe Arrangement
NOTE: Union may be inside the
vestibule where permitted by
local codes.
ELECTRICAL CONNECTIONS
A11338
A11035
Field--supplied wiring shall conform with the limitations of 63_F
(33_C) rise.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken
ground according to NEC ANSI/NFPA 70--2011 or local
codes to minimize personal injury if an electrical fault
should occur. In Canada, refer to Canadian Electrical Code
CSA C22.1. This may consist of electrical wire, conduit
approved for electrical ground or a listed, grounded power
cord (where permitted by local code) when installed in
accordance with existing electrical codes. Refer to the
power cord manufacturer’s ratings for proper wire gauge.
Do not use gas piping as an electrical ground.
!
CAUTION
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent
furnace operation.
Furnace control must be grounded for proper operation or
else control will lock out. Control must remain grounded
through green/yellow wire routed to gasvalve and manifold
bracket screw.
115-- V Wiring
Furnace must have a 115-v power supply properly connected and
grounded.
NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control LED status indicator light will flash
rapidly and furnace will NOT operate.
Verify that the voltage, frequency, and phase correspond to that
specified on unit rating plate. Also, check to be sure that service
provided by utility is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 9 for equipment electrical
specifications.
U.S.A. Installations: Make all electrical connections in accordance
with the current edition of the National Electrical Code (NEC)
ANSI/NFPA 70 and any local codes or ordinances that might
apply.
Canada Installations: Make all electrical connections in
accordance with the current edition of the Canadian Electrical
Code CSA C22.1 and any local codes or ordinances that might
apply.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower door switch opens 115--v power to control. No
component operation can occur. Do not bypass or close
switch with blower door removed.
See Fig. 33 for field wiring diagram showing typical field 115--v
wiring. Check all factory and field electrical connections for
tightness.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not connect aluminum wire between disconnect
switch and furnace. Use only copper wire. See Fig. 31.
Use a separate, fused branch electrical circuit with a properly sized
fuse or circuit breaker for this furnace. See Table 9 for wire size
and fuse specifications. A readily accessible means of electrical
disconnect must be located within sight of the furnace.
30
Page 31
J--Box Installation
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
If field--supplied manual disconnect switch is to be mounted
on furnace casing side, select a location where a drill or
fastener cannot damage electrical or gas components.
The J-Box is used when field line voltage electrical connections are
made to the furnace wiring harness inside the furnace casing. The
J-Box is not required if a field-supplied electrical box is attached to
the outside of the furnace casing and the box is grounded to the
green ground wire of the main wiring harness and the earth ground
of the field electrical supply.
The J--Box cover, mounting bracket and screws are shipped in the
loose parts bag included with the furnace. The J--Box can be
mounted on the left or right side of the casing, as viewed from the
upflow position.
Remove the J--Box cover and mounting bracket from the loose
parts bag. Select a 7/8--in. (22 mm) knock-out on the desired side
of the casing. Remove the knock-out from the casing. Drill two (2)
1/8--in. (3 mm) pilot holes in the casing dimples by the desired
7/8--in. (22 mm) knock-out.
Align the J--box mounting bracket against the inside of the casing
and secure the mounting bracket with the screws. (See Fig. 30.)
Electrical Box on Furnace Casing Side
NOTE: Check that duct on side of furnace will not interfere with
installed electrical box.
1. Fasten a field-supplied external electrical box to the outside
of the casing by driving two field-supplied screws from inside electrical box into casing. (See Fig. 31.)
2. Route field power wiring into external electrical box.
3. Pull furnace power wires through 1/2-in. (12 mm) diameter
hole in J-Box. If necessary, loosen power wires from strain-relief wire-tie on furnace wiring harness.
4. Connect any code required external disconnect(s) to field
power wiring.
5. Route external field power wires through holes in electrical
box and casing.
6. Connect field ground wire and factory ground wire to green
ground screw on J--Box mounting bracket as shown in Fig.
30.
7. Connect field power and neutral leads to furnace power
leads as shown in Fig. 33.
8. Attach furnace J-Box cover to mounting bracket with
screws supplied in loose parts bag. Do not pinch wires
between cover and bracket.
9. Complete external disconnect wiring and installation. Connect line voltage leads as shown in Fig. 31. Use best practices (NEC in U.S.A. for wire bushings, strain relief, etc.,
CANADA: Canadian Electrical Code CSA C22.1)
Power Cord Installation in Furnace J--Box
NOTE:Power cords must be able to handle the electrical
requirements listed in Table 9. Refer to power cord manufacturer’s
listings.
1. Install J--Box mounting bracket to inside of furnace casing.
(See Fig. 30.)
2. Route listed power cord through 7/8--in. (22 mm) diameter
hole in casing and J--Box bracket.
3. Secure power cord to J--Box bracket with a strain relief
bushing or a connector approved for the type of cord used.
4. Pull furnace power wires through 1/2--in. (12 mm) diameter
hole in J--Box. If necessary, loosen power wires from
strain—relief wire--tie on furnace wiring harness.
5. Connect field ground wire and factory ground wire to green
ground screw on J--Box mounting bracket as shown in Fig.
30.
6. Connect power cord power and neutral leads to furnace
power leads as shown in Fig. 33.
7. Attach furnace J--Box cover to mounting bracket with
screws supplied in loose parts bag. Do not pinch wires
between cover and bracket. (See Fig. 30).
BX Cable Installation in Furnace J--Box
1. Install J--Box mounting bracket to inside of furnace casing.
See Fig. 30.
2. Route BX connector through 7/8--in. (22 mm) diameter
hole in casing and J--Box bracket.
3. Secure BX cable to J--Box bracket with connectors approved for the type of cable used.
4. Connect field ground wire and factory ground wire to green
ground screw on J--Box mounting bracket as shown in Fig.
30.
5. Connect field power and neutral leads to furnace power
leads. as shown in Fig. 33.
6. Attach furnace J--Box cover to mounting bracket with
screws supplied in loose parts bag. Do not pinch wires
between cover and bracket.
24--V Wiring
Make field 24--v connections at the 24--v terminal strip. (See Fig.
34.) Connect terminal Y/Y2 as shown in Fig. 33 for proper
cooling operation. Use only AWG No. 18, color--coded, copper
thermostat wire.
NOTE: Use AWG No. 18 color-coded copper thermostat wire for
lengths up to 100 ft. (30.5 M). For wire lengths over 100 ft., use
AWG No. 16 wire.
The 24--v circuit contains an automotive--type, 3--amp. fuse located
on the control. Any direct shorts during installation, service, or
maintenance could cause this fuse to blow. If fuse replacement is
required, use ONLY a 3--amp. fuse of identical size. See Fig. 34.
Thermostats
For best results, use a communicating wall control to control this
modulating furnace. A single stage or two--stage heating and
cooling thermostat can be used with the furnace. The furnace
control board CPU will control the furnace and outdoor unit
staging. A two stage heating and cooling thermostat can also be
used to control the staging. However, full modulating capability
will not be available when the furnace staging is controlled by the
thermostat. Furnace staging will be limited to Minimum and
Maximum inputs or Intermediate and Maximum inputs depending
on the configuration of set-up switches SW1-2 and SW4-2. For
two stage thermostat control of a 2-stage outdoor unit, remove the
ACRDJ jumper from the furnace control board. Refer to typical
thermostat wiring diagrams and the Sequence of Operation section
for additional details. Consult the thermostat installation
instructions for specific information about configuring the
thermostat. See Fig. 34 and 35.
Accessories (See Fig. 32 and 34.)
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used) using
1/4--in. female quick connect terminals to the two male
1/4--in. quick--connect terminals on the control board
marked EAC--1 and EAC--2. The terminals are rated for
115VAC, 1.0 amps maximum and are energized during
blower motor operation.
31
987MA
Page 32
2. Humidifier (HUM)
The HUM terminal is a 24 VAC output, energized when the blower
is operating during a call for heat.
Connect an accessory 24 VAC, 0.5 amp. maximum humidifier (if
used) to the ¼--in. male quick--connect HUM terminal and
COM--24V screw terminal on the control board thermostat strip.
NOTE: If the humidifier has its own 24 VAC power supply, an
isolation relay may be required. Connect the 24 VAC coil of the
isolation relay to the HUM and COM/24V screw terminal on the
control board thermostat strip. (See Fig. 32.)
3. Communication Connector (ABCD connection)
This connection is used when the furnace is controlled by
Alternate Power Supplies
This furnace is designed to operate on utility generated power
which has a smooth sinusoidal waveform. If the furnace is to be
operated on a generator or other alternate power supply, the
alternate power supply must produce a smooth sinusoidal
waveform for compatibility with the furnace electronics. The
alternate power supply must generate the same voltage, phase, and
frequency (Hz) as shown in Table 9 or the furnace rating plate.
Power from an alternate power supply that is non-sinusoidal may
damage the furnace electronics or cause erratic operation.
Contact the alternate power supply manufacturer for specifications
and details.
an optional communicating User Interface instead of a
standard thermostat. The ABCD plug is supplied with the
User Interface. Refer to the instructions supplied with the
User Interface for complete details. See Fig. 34.
4. Outside Air Thermistor (OAT)
The OAT connection is used in conjunction with communicating User Interface. It is not required when the furnace
987MA
is controlled by a standard type thermostat. Refer to the instructions supplied with the User Interface for complete details.
* Permissible limits of the voltage range at which th e unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,
etc.) full load amps.
{Time---delay type is recommended.
}Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE*
Maximum* Minimum*
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)}
FUSE OR CKT
MAXIMUM
BKR
AMPS{
32
Page 33
J BOX LOCATIONS
J−BO X
MOUNTING
SCREWS
J−BO X
MOUNTING
BRACKET
GROUND
SCREW
J−BOX COVER
NEUTRAL
LINE VOLTAGE
DISCONNECT
GROUND
987MA
ELECTRIC
SWITCH
COPPER
WIRE ONLY
Fig. 30 -- Installing J--Box (When Used)
(Appearance May Vary)
A11156
ALUMINUM
WIRE
A11146
Fig. 31 -- Field--Supplied Electrical Box on Furnace Casing
33
Page 34
To Humidifier Leads
To HUM Terminal On
Furnace Control Board
24 V
Coil
987MA
To Humidifier Leads
BLOWER
DOOR
SWITCH
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
To Com/24V Screw Terminal
on Thermostat Strip
Fig. 32 -- Field--supplied Isolation Relay for Humidifiers with Internal Power Supply
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
BLK
WHT
JUNCTION
BOX
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
FURNACE
W2
C
COM
O
N
W/W1
T
Y/Y2
R
O
R
L
G
24-VOLT
TERMINAL
BLOCK
NOTE 2
WCYRG
NOTE 1
NOTES: 1.
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
2.
If any of the original wire, as supplied, must be replaced, use
3.
same type or equivalent wire.
1-STAGE
THERMOSTAT
TERMINALS
CONDENSING
UNIT
FIELD-SUPPLIED
FUSED DISCONNECT
GND
A11157
208/230- OR
460-VOLT
THREE
PHASE
208/230VOLT
SINGLE
PHASE
A11401
Fig. 33 -- Typical Two--Stage Field Wiring Diagram
34
Page 35
24-V THERMOSTAT
TERMINALS
PL2 – HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115-VAC (L2) NEUTRAL
CONNECTIONS
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
PL3 – ECM BLOWER
HARNESS
CONNECTOR
TRANSFORMER 24-VAC
CONNECTIONS
3-AMP FUSE
STATUS AND COMM
LED LIGHTS
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
MODEL PLUG
CONNECTOR
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
COMMUNICATION
CONNECTOR
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
OUTDOOR
AIR TEMP
CONNECTOR
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
ACRDJ – AIR
CONDITIONING
RELAY DISABLE
JUMPER
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
SW4 SETUP
SWITCHES
SOFTWARE
VERSION
PART NUMBER AND
DATE CODE WWYY
PL8 - MODULATING
GAS VALVE
CONNECTOR
987MA
A11425
Fig. 34 -- Modulating Furnace Control
35
Page 36
987MA
THERMOSTAT
THERMOSTAT
D
D
11, and 16
Modulating and 2-Stage Furnace with Single-Speed Air Conditioner
THERMOSTAT
D
15, and 16
Modulating and 2-Stage Furnace with Single-Speed Heat Pump
THERMOSTAT
D
Modulating and 2-Stage Furnace with Two-Speed Air Conditioner
12 and 16
Modulating and 2-Stage Furnace with Two-Speed Heat Pump
Fig. 35 -- Thermostat Wiring Diagrams
36
15, and 16
A11274
Page 37
NOTES FOR THERMOSTAT WIRING DIAGRAMS
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. If the heat pump date code is 1501E or earlier, select the “ZONE” position on the two speed heat pump control. Heat pumps with date
code 1601E and later do not have or require a “ZONE” selection.
4. Outdoor Air Temperature - sensor must be attached in all dual fuel applications.
5. Configure the thermostat for air conditioner installations. Refer to thermostat instructions.
6. Configure thermostat for heat pump installations. Refer to thermostat instructions.
7. Configure thermostat for single-stage compressor operation. Refer to thermostat instructions.
8. Configure thermostat for two-stage compressor operation. Refer to thermostat instructions.
9. Configure thermostat for Dual Fuel Operation. Refer to thermostat instructions.
10. NO connection should be made to the furnace HUM terminal when using a thermostat with a 24 volt humidifier output.
11. Optional connection - If wire is connected to W2 on furnace control board, either dip switch SW1-2 or SW4-2 on furnace control
should be set in ON position to allow thermostat to control furnace at 2 stages Min/Max or Intermediate/Max.
12. Optional connection - If wire is connected, ACRDJ jumper on furnace control should be removed to allow thermostat to control
outdoor unit staging.
13. Furnace must control its own staging operation via furnace control algorithm. This is factory default.
14. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
15. If thermostat has internal control of heat pump balance point, DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE
POINT” option on the two-speed heat pump control board. Refer to thermostat instructions
16. Configure Dehumidify function to remove 24 VAC from Dehum terminal on a demand to dehumidify.
987MA
37
Page 38
VENTING
Furnace is set in place in the required orientation.
Special Venting Requirements for Installations in
Canada
Installation in Canada must conform to the requirements of
CAN/CSA B149 code. Vent systems must be composed of pipe,
fittings, cements, and primers listed to ULC S636. The special
vent fittings and accessory concentric vent termination kits and
accessory external drain trap have been certified to ULC S636 for
use with those Royal Pipe and IPEX PVC vent components which
have been certified to this standard. In Canada, the primer and
cement must be of the same manufacturer as the vent system –
GVS-65 Primer (Purple) for Royal Pipe or IPEX System 636,
PVC/CPVC Primer, Purple Violet for Flue Gas Venting and
GVS-65 PVC Solvent Cement for Royal Pipe or IPEX System
t, PVC Cement for Flue Gas Venting, rated Class IIA, 65 deg
636
(1)
C. must be used with this venting system - do not mix primers and
cements from one manufacturer with a vent system from a different
manufacturer. Follow the manufacturer’s instructions in the use of
primer and cement and never use primer or cement beyond its
987MA
expiration date.
The safe operation, as defined by ULC S636, of the vent system is
based on following these installation instructions, the vent system
manufacturer’s installation instructions, and proper use of primer
and cement. All fire stop and roof flashing used with this system
must be UL listed material. Acceptability under Canadian standard
CAN/CSA B149 is dependent upon full compliance with all
installation instructions. Under this standard, it is recommended
that the vent system be checked once a year by qualified service
personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a
permit.
*IPEX System 636™ is a trademark of IPEX Inc.
Consignes spéciales pour l’installation de
ventilation au Canada
L’installation faite au Canada doit se conformer aux exigences du
code CAN/CSA B149--2010. Ce systême de ventillation doit se
composer de tuyaux, raccords, ciments et apprêts conformes au
ULC S636. La tuyauterie de ventillation des gaz, ses accessoires,
le terminal concentrique mural ainsi que l’ensemble du drain de
condensat extérieur ont été certifiés ULCS 636 pour l’application
des composantes Royal Pipe, IPEX PVC qui sont certifiées à ce
standard. Au Canada, l’apprêt et le ciment doivent être du même
fabricant quele système d’évacuation. L’apprêt GVS-65 (Purple) et
le ciment-solvant GVS-65 doivent être utilisé avec les Royal Pipe.
Système IPEX 636, apprêt PVC/CPVC, Purple pour évacuation
des gaz de combustion et système IPEX 636(1)t, ciment PVC pour
évacuation des gaz de combustion, coté classe IIA, 65 deg C.
doivent être utilisés avec le système d’évacuation IPEX 636 – Ne
pas combiner l ’apprêt et le ciment d’un manufacturier avec un
système d’évacuation d’un manufacturier différent.
Bien suivre les indications du manufacturier lors de l’utilisation de
l’apprêt et du ciment et ne pas utiliser ceux-ci si la date d’expiration
est atteinte.
L’opération sécuritaire, tel que définit par ULC S636, du système
de ventilation est basé sur les instructions d’installation suivantes,
ainsi que l’usage approprié de l’apprêt et ciment. Tout arrêt feu et
solin de toit utilisés avec ce système doivent être des matériaux
listés UL. L’acceptation du standard Canadien CAN/CSA B149
est directement relié à l’installation conforme aux instructions cihaut mentionnées. Le standard Canadien recommande l’ inspection
par un personnel qualifié et ce, une fois par année.
Les autorité es ayant juridiction (inspecteurs de gas, inspecteurs en
bâtiments, département des incendies, etc) devraient être consultées
avant l’installation afin de déterminer si un permis est requis.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, NFPA 54/ANSI Z223.1--2009 and these
instructions. In Canada, refer to CAN/CSA-B149.1--2010. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies,
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of
main burner operation. Use the flame of a match or
candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with the National Fuel Gas Code, NFPA
54/ANSI Z223.1--2009. In Canada, refer to CAN/
CSA--B149.1--2010.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other
gas--fired burning appliance to their previous
conditions of use.
General
If this furnace replaces a furnace that was connected to a vent
system or chimney, the vent or vent connectors of other remaining
appliances may need to be re--sized. Vent systems or vent
connectors of other appliances must be sized to the minimum size
as determined using appropriate table found in the current edition
of National Fuel Gas Code NFPA 54/ANSI Z--223.1. In Canada,
refer to CAN/CSA--B149.1.
An abandoned masonry chimney may be used as a raceway for
properly insulated and supported combustion--air (when
applicable) and vent pipes. Each furnace must have its own set of
combustion--air and vent pipes and be terminated individually, as
shown in Fig. 46 for Direct Vent (2--Pipe) system or Fig. 47 for
ventilated combustion air option.
38
Page 39
A furnace shall not be connected to a chimney flue serving a
separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use
the abandoned chimney as a raceway providing it is permitted by
local code, the current edition of the National Fuel Gas Code and
the vent or liner manufacturer’s installation instructions. Care must
be taken to prevent the exhaust gases from one appliance from
contaminating the combustion air of other gas appliances.
Do not take combustion air from inside the chimney when using
ventilated combustion air or single pipe vent option.
These furnaces can be vented as either direct vent furnace or as
ventilated combustion air system. Each type of venting system is
described below. Common venting between furnaces or other
appliances prohibited.
Materials
U.S.A.
Combustion air and vent pipe, fittings, primers, and solvents must
conform to American National Standards Institute (ANSI)
standards and American Society for Testing and Materials (ASTM)
standards. See Table 11 for approved materials for use in the
U.S.A.
Canada
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of
CAN/CSA B149 code. Vent systems must be composed of pipe,
fittings, cements, and primers listed to ULC S636.
Ven ti ng Systems
A factory accessory KGAVT vent termination kit must be used for
all direct vent terminations. Termination kits are available for 2--in.
or 3--in. pipe. See Table 10 for available options.
Table 10 – Vent Termination Kit for Direct Vent (2--pipe)
Systems
DIRECT VENT
(2 --- PIPE)
TERMINATION KIT
2 --- i n . (5 1 m m )
Concentric Vent Kit
3 --- i n . (7 6 m m )
Concentric Vent Kit
2 --- i n . (5 1 m m )
Termination Bracket
Kit
3 --- i n . (7 6 m m )
Termination Bracket
Kit
TERMINATION
SYSTEM
Single Penetration of
Wall or Roof
Single Penetration of
wall or Roof
2 -- -Pipe Termin ation
System
2 -- -Pipe Termin ation
System
Direct Vent / 2-Pipe System
In a direct-vent (2-pipe) system, all air for combustion is taken
directly from outdoor atmosphere, and all flue products are
discharged to outdoor atmosphere. Combustion-air and vent pipes
must terminate together in the same atmospheric pressure zone,
either through the roof or a sidewall (roof termination preferred). A
factory accessory vent termination kit MUST be used in a direct
vent (2-pipe) system. See Fig. 44 for required clearances.
Ventilated Combustion Air Systems
In a ventilated combustion air option, the vent terminates and
discharges the flue products directly to the outdoors similar to a
direct vent system. See Fig. 45 for required clearances.
All air for combustion is piped directly to the furnace from a space
that is well ventilated with outdoor air (such as an attic or crawl
space) and the space is well isolated from the living space or
garage. Combustion air requirements for this option are the same as
the requirements for providing outside air for combustion for a
single pipe vent system. Refer to the “Air For Combustion and
Ventilation Section.
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
DIAM. OF COMBUSTION AIR AND VENT
PIPES --- IN. (mm)
1, 1 --- 1/2, 2, or 2 ---1/2
(24, 36, 51, 64 mm)
2---1/2, 3 or 4
(64, 76, 102 mm)
1, 1 --- 1/2 or 2
(25, 36, 51 mm)
2---1/2, 3 or 4
(64, 76, 102 mm)
U.S.A. Installations: Section 9.3 NFPA 54/ANSI Z223.1-2009,
Air for Combustion and Ventilation and applicable provisions of
the local building codes.
Canadian Installations: Part 8 of CAN/CSA-B149.1-10. Venting
Systems and Air Supply for Appliances and all authorities having
jurisdiction.
Locating the Vent Termination
General
NOTE:Termination Requirements for the Provinces of
Alberta and Saskatchewan are located at the end of this
section.
Combustion--air (direct vent/2--pipe system only) and vent pipe
must terminate outside structure, either through sidewall or roof.
For vent termination clearance, refer to Fig. 44 for Direct
Vent/2--Pipe system and Fig. 45 for Non--direct Vent/1--Pipe
system. For exterior termination arrangements, refer to Fig. 46 for
Direct Vent/2--Pipe system and Fig. 47 for Non-- Direct/1--Pipe
system.
Roof termination is preferred since it is less susceptible to damage
or contamination, and it has less visible vent vapors. Sidewall
terminations require sealing or shielding of building surfaces with a
corrosive resistance material due to corrosive combustion products
of vent system.
NOTE: (Direct Vent/2--Pipe system ONLY) A factory accessory
termination kit MUST be used. See Table 10 for availableoptions.
When determining appropriate location for termination, consider
the following guidelines:
1. Comply with all clearance requirements stated in Fig. 44 or
Fig. 45 per application.
2. Termination or termination kit should be positioned where
vent vapors will not damage plants/shrubs or air conditioning equipment.
3. Termination or termination kit should be positioned so that
it will not be affected by wind eddy, such as inside building
corners, nor by recirculation of flue gases, airborne leaves,
or light snow.
4. Termination ortermination kit should be positioned where it
will not be damaged by or subjected to foreign objects such
as stones, balls, etc.
5. Termination or termination kit should be positioned where
vent vapors are not objectionable.
Direct Vent / 2-Pipe System
Direct vent (2--pipe) vent and combustion air pipes must terminate
outside the structure. Follow all clearances as shown Fig. 44.
Allowable vent and combustion air terminations are shown in Fig.
46.
Ventilated Combustion Air
The vent pipe for a Ventilated Combustion Air System must
terminate outdoors. Follow all vent termination clearances shown
in Fig. 45. Allowable vent terminations are shown in Fig. 47. The
combustion air pipe terminates in a well--ventilated attic or crawl
space. Follow the clearances as shown in Fig. 49. When the
furnace is installed in a well ventilated attic or crawlspace, install
the combustion air pipe as shown in Fig. .43
The combustion air pipe cannot terminate in attics or crawl spaces
that use ventilation fans designed to operate in the heating season.
If ventilation fans are present in these areas, the combustion air
pipe must terminate outdoors as a Direct Vent System.
Termination Requirements for the Provinces of Alberta and
Saskatchewan
The Provinces of Alberta and Saskatchewan require a minimum
unobstructed distance of 4 ft. (1.2 M) from the foundation to the
property line of the adjacent lot for vent termination of any
appliance with an input over 35,000 btuh. If there is less than 4 ft.
987MA
39
Page 40
(1.2 M) of unobstructed distance to the property line of the
adjacent lot, no type of vent termination is permitted for appliances
with inputs greater than 35,000 btuh.
There are no additional restrictions on unobstructed distances
greater than 8 ft. (2.4 M). All single, two-pipe and concentric vents
may be used, providing all other Code and manufacturer’s
requirements in these instructions are adhered to. Refer to the
appropriate Vent Termination section above for locating the vent
termination
If the unobstructed distance from the foundation to the property
line of the adjacent lot is no less than 4 ft. (1.2 M) and no greater
than 8 ft. (2.4 M), it will be necessary to re-direct the flue gas
plume. In this situation, a concentric vent kit cannot be used. A
2-pipe termination (or single pipe termination when permitted) that
re-directs the flue gas away by use of an elbow or tee, certified to
ULC S636 from the adjacent property line must be used. See Fig.
48.
The concentric vent kit currently cannot be modified to attach an
elbow to the vent portion of the rain cap. A tee attached to the rain
cap could potentially direct the flue gas plume toward the intake air
987MA
stream and contaminate the incoming combustion air for the
furnace.
Refer to Fig. 48 for terminations approved for use in Alberta and
Saskatchewan.
Size the Vent and Combustion Air Pipes
General
Furnace combustion air and vent pipe connections are sized for
2-in. (51 mm) pipe. Any pipe diameter change should be made
outside furnace casing in vertical pipe. Any change is diameter to
the pipe must be made as close to the furnace as reasonably
possible.
The Maximum Vent Length for the vent and combustion air pipe
(when used) is determined from the Maximum Equivalent Vent
Length in Table 13 or 15, minus the number of fittings multiplied
by the deduction for each type of fitting used from Table 14.
The measured length of pipe used in a single or 2--pipe termination
is included in the total vent length. Include a deduction for a Tee
when used for Alberta and Saskatchewan terminations. Concentric
vent terminations, pipe lengths or elbows do not require a
deduction from the Maximum Equivalent Vent Length.
1. Measure the individual distance from the furnace to the termination for each pipe.
2. Select a Maximum Equivalent Vent Length (MEVL) longer
than the measured distance of the individual vent and combustion air connections to the vent termination.
3. Count the number of elbows for each pipe.
4. For each pipe, multiply the number of elbows by the equivalent length for the type of elbow used. Record the equivalent length of all the elbows for each pipe.
5. If a Tee is used on the termination, record the equivalent
length of the Tee used.
6. Record the equivalent length of the termination to be used.
7. Subtract the equivalent lengths of the fittings and terminations from the Maximum Equivalent Vent Length.
8. If the Maximum Vent Length calculated is longer than the
individual measured length of the vent pipe and combustion
air pipe, then the diameter of pipe selected may be used.
9. If the Maximum Vent Length calculated is shorter than the
individual measured length of either the vent pipe or the
combustion air pipe, recalculate the Maximum Vent Length
using the next larger diameter pipe.
NOTE: The vent pipe and combustion air pipe must be the same
diameter.
NOTE: If the Maximum Vent Length for diameter of the pipe
selected is longer than the measured length and the equivalent
length of all the fitting and terminations, recalculate using the next
smaller diameter. If the recalculated Maximum Vent Length is
longer than the measured length of the vent pipe and combustion
air pipe, then that diameter of pipe selected may be used.
When installing vent systems of short pipe lengths, use the smallest
allowable pipe diameter. Do not use pipe size greater than required
or incomplete combustion, flame disturbance, or flame sense
lockout may occur.
Combustion Air and Vent Piping Insulation
Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent.
The vent pipe may pass through unconditioned areas. The amount
of exposed pipe allowed is shown in Table 12.
1. Using winter design temperature (used in load calculations),
find appropriate temperature for your application and furnace model.
2. Determine the amount of total and exposed vent pipe.
3. Determine required insulation thickness for exposed pipe
length(s).
4. When combustion air inlet piping is installed above a suspended ceiling, the pipe MUST be insulated with moisture
resistant insulation such as Armaflex or other equivalent
type of insulation.
5. Insulate combustion air inlet piping when run in warm, humid spaces.
6. Install the insulation per the insulation manufacturer’s installation instructions.
NOTE: Pipe length (ft. / M) specified for maximum pipe lengths
located in unconditioned spaces cannot exceed total allowable pipe
length as calculated from Table 13 or 15.
Configure the Furnace
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
To route the vent pipe and combustion air pipe through the
furnace, the manufacturer supplied kit must be used. Failure
to properly seal the blower compartment from the furnace
vestibule could result in the circulation of carbon monoxide
throughout the structure. The vent pipe and combustion air
pipe must be a continuous pipe while passing through the
blower compartment. Seals supplied in this kit must be
installed per the instructions provided. Follow all
procedures outlined in these instructions.
Install the Vent and Combustion Air Pipe
With the furnace installed in the required position, remove the
desired knockouts from the casing. It will be necessary to remove
one knockout for the vent pipe and the other knockout for the
combustion air connection. (See Fig. 11.)
Use a flat blade screwdriver and tap on the knockout on opposite
sides, where the knockout meets the casing. Fold the knockout
down with duct pliers and work the knockout back and forth until
it is removed. Trim any excess metal from the knockout with tin
snips.
The vent elbow can be rotated to the required location on the
casing if necessary. See Fig. 37. To rotate the vent elbow:
1. Loosen the clamp on the inlet of the vent elbow attached to
the inducer.
40
Page 41
2. Rotate the vent elbow to the required position. There are
rounded notches in the vent elbow to align it with the
inducer housing for each orientation.
3. Tighten the clamp around the vent elbow. Torque the clamp
to 15 lb--in. See Fig. 38--41.
Installing the Vent Pipe Adapter and Combustion Air
Pipe Adapter
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
To route the vent pipe and combustion air pipe through the
furnace, the manufacturer supplied kit must be used. Failure
to properly seal the blower compartment from the furnace
vestibule could result in the circulation of carbon monoxide
throughout the structure. The vent pipe and combustion air
pipe must be a continuous pipe while passing through the
blower compartment. Seals supplied in this kit must be
installed per the instructions provided. Follow all
procedures outlined in these instructions.
NOTE: The rubber coupling that attaches to the vent pipe adapter
must be used. The adapter seals the vent pipe to the casing and
reduces the strain on the vent elbow attached to the inducer.
1. Apply the gaskets to the vent pipe and combustion air pipe
adapters. See Fig. 36.
NOTE: The vent pipe adapter and the combustion air pipe adapter
have the same ID however, the combustion air pipe adapter has a
pipe stop at the end.
2. Align the screw holes in the plastic vent pipe adapter with
the dimples in the casing.
3. Pilot drill the screw holes for the adapter in the casing and
attach the vent pipe adapter to the furnace with sheet metal
screws
4. Slide the end of the rubber vent coupling with notches in it
over the standoffs on the vent pipe adapter.
5. Insert a length of vent pipe through the coupling into the
outlet of the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow.
Torque the clamp to 15 lb--in.
Install the remaining vent and combustion air pipes as shown
below. It is recommended that all pipes be cut, prepared, and
preassembled before permanently cementing any joint.
1. Working from furnace to outside, cut pipe to required
length(s).
2. Deburr inside and outside of pipe.
3. Chamfer outside edge of pipe for better distribution of
primer and cement.
4. Clean and dry all surfaces to be joined.
5. Check dry fit of pipe and mark insertion depth on pipe.
6. Insert the vent pipe into the vent elbow.
7. Torque clamp on vent elbow 15 lb--in.
8. Torque clamp on vent coupling 15 lb--in.
9. Insert the combustion air pipe into the adapter.
10. Pilot drill a screw hole through the adapter into the combustion air pipe and secure the pipe to the adapter with sheet
metal screws.
11. Seal around the combustion air pipe with silicone or foil
tape.
12. After pipes have been cut and preassembled, apply generous
layer of cement primer to pipe fitting socket and end of pipe
to insertion mark. Quickly apply approved cement to end of
pipe and fitting socket (over primer). Apply cement in a
light, uniform coat on inside of socket to prevent buildup of
excess cement. Apply second coat.
13. While cement is still wet, twist pipe into socket with 1/4--in.
turn. Be sure pipe is fully inserted into fitting socket.
14. Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made
joint.
15. Handle pipe joints carefully until cement sets.
16. Horizontal portions of the venting system shall be supported to prevent sagging. Support combustion air piping and
vent piping a minimum of every 5 ft. (1.5M)[3 ft. (.91M)
for SDR--21 or --26 PVC] using perforated metal hanging
strap or commercially available hangars designed to support
plastic pipe.
17. Prevent condensate from accumulating in the pipes by sloping the combustion air piping and vent piping downward
towards furnace a minimum of 1/4-in. per linear ft. with no
sags between hangers.
18. Complete the vent and combustion air pipe installation by
connecting the concentric vent or by installing the required
termination elbows as shown in Fig. 46, 47 and 48.
For Ventilated Combustion Air Termination, See Fig. 49
19. Use appropriate methods to seal openings where combustion air pipe and vent pipe pass through roof or sidewall.
Optional Installation of the Vent Pipe
This option provides a disconnect point for the vent pipe. The vent
pipe must be cemented to the plastic vent pipe adapter to maintain
a sealed vestibule. See Fig. 42.
1. Insert a length of vent pipe through the casing into the
outlet of the vent elbow.
2. Slide the plastic vent pipe adapter over the length of the
vent pipe down to the furnace casing. Mark the pipe where
it is flush with the outlet of the adapter.
3. Remove the pipe from the furnace and the adapter and cut
off any excess pipe.
4. Clean and prime the end of the pipe that is flush with the
vent adapter with a primer that is appropriate for the type of
pipe being used.
5. Re--insert the pipe through the casing into the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow.
Torque the clamp to 15 lb--in.
7. Apply cement to the end of the pipe and to the inside of the
plastic vent adapter.
8. Slide the adapter over the vent pipe and align the screw
holes in the adapter with the dimples in the furnace casing.
9. Pilot drill 1/8--in. screw holes for the adapter in the casing
and secure the adapter to the furnace with sheet metal
screws.
10. Loosen the clamps on the rubber vent coupling.
11. Slide the end of the coupling with notches in it over the
standoffs in the vent pipe adapter.
12. Tighten the clamp of the coupling over the vent pipe
adapter. Torque the lower clamp around the vent pipe
adapter to 15 lb--in.
13. Pilot drill a 1/8--in. hole in the combustion air pipe adapter.
14. Complete the vent and combustion air pipe as shown in
“Install the Vent and Combustion Air Pipe”
Installing the Vent Termination
Roof Terminations
A roof termination of any type will require a 4-in. (102 mm)
flashing for a 2 inch (51 mm) concentric vent or a 5--in. diameter
(127 mm) flashing for a 3-inch (76 mm) concentric vent kit. For
41
987MA
Page 42
two-pipe or single pipe vent systems, a flashing for each pipe of the
required diameter will be necessary.
It is recommended that the flashing be installed by a roofer or
competent professional prior to installing the concentric vent. The
terminations can be installed on a flat or pitched roof.
Concentric Vent
Single or multiple concentric vent must be installed as shown in
Fig. 46. Maintain the required separation distance between vents
or pairs of vents as shown in Fig. 46 and all clearance shown in
Fig. 44.
Cut one 4--in. (102 mm) diameter hole for 2--in. (51 mm) kit, or
one 5--in. (127 mm) diameter hole for 3--in. (76 mm) kit in the
desired location.
Loosely assemble concentric vent/combustion air termination
components together using instructions in kit.
Slide assembled kit with rain shield REMOVED through hole in
wall or roof flashing.
NOTE: Do not allow insulation or other materials to accumulate
inside of pipe assembly when installing it through hole.
987MA
Disassemble loose pipe fittings. Clean and cement using same
procedures as used for system piping.
Two--Pipe and Single--Pipe Terminations
Single and two pipe vent must be installed as shown in Fig. 46 and
47. Maintain the required separation distance between vents or
pairs of vents as shown in Fig. 46 and 47. and all clearance shown
in Fig. 44 and 45.
Cut the required number of holes in the roof or sidewall for vent
and (when used) combustion air pipes. Sidewall holes for two-pipe
vent terminations should be side-by-side, allowing space between
the pipes for the elbows to fit on the pipes.
Holes in the roof for two pipe terminations should be spaced no
more than 18 in. (457 mm) apart.
Termination elbows will be installed after the vent and (if used)
combustion air pipe is installed.
Sidewall Terminations
Concentric Vent Termination
Determine an appropriate location for termination kit using the
guidelines provided in section “Locating The Vent Termination” in
this instruction.
1. Cut one 4--in. diameter hole for 2--in. kit, or one 5--in. diameter hole for 3--in. kit.
2. Loosely assemble concentric vent/combustion air termination components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through
hole.
NOTE: Do not allow insulation or other materials to accumulate
inside of pipe assembly when installing it through hole.
4. Locate assembly through sidewall with rain shield positioned no more than 1--in. (25 mm) from wall as shown in
Fig. 46.
5. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
Direct Vent (2--pipe) Termination
Determine an appropriate location for termination kit using the
guidelines provided in section “Locating The Vent Termination” in
this instruction.
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size
being used.
2. Loosely install elbow in bracket and place assembly on
combustion--air pipe.
3. Install bracket as shown in Fig. 46 and 48.
NOTE: For applications using vent pipe option indicated by
dashed lines in Fig. 46 and 47, rotate vent elbow 90_ from
position.
4. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
For ventilated Combustion Air Terminations, terminate as
shown in Fig. 47.
(Direct Vent / 2-Pipe System ONLY)
When 2 or more furnaces are vented near each other, 2 vent
terminations may be installed as shown in Fig. 46, but next vent
termination must be at least 36 in. (914 mm) away from first 2
terminations. It is important that vent terminations be made as
showninFig.46toavoidrecirculationoffluegases.
Inducer Outlet Restrictor
The loose parts bag may contain an inducer outlet restrictor. The
outlet restrictor is NOT used on these furnaces. Discard restrictor.
Table 11 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installations)
ASTM SPECIFICATION
(MARKED ON MATERIAL)
D1527ABSPipe——S c h e d u l e --- 4 0
D1785PVCPipe——S c h e d u l e --- 4 0
D2235For ABS——Solvent CementFor ABS
D2241PVCPipe——S D R --- 2 1 & S D R --- 2 6
D2466PVC—Fittings—Sc h e d u l e --- 4 0
D2468ABS—Fittings—S c h e d u l e --- 4 0
D2564For PVC——Solvent CementFor PVC
D2661ABSPipeFittings—DWV at Schedule---40 IPS sizes
D2665PVCPipeFittings—DWV
F438CPVC—Fittings—S c h e d u l e --- 4 0
F441CPVCPipe——Sc h e d u l e --- 4 0
F442CPVCPipe——SDR
F493For CP VC——Solvent CementFor C PVC
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe
length calculated from Table 13 or 15.
† Insulation thickness based on R value of 3.5 per in.
Table 13 – Maximum Equivalent Vent Length -- Ft. (M)
0 to 4500 Ft. (0 to 1370 M) Altitude
DIRECT VENT (2-PIPE) AND VENTILATED COMBUSTION AIR ONLY
Vent Pipe Diameter (in.)
1-1/222-1/234
Table 14 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)
Pipe Diameter (in):1-1/222-1/23*4*
Mitered 90º Elbow8(2.4)8(2.4)8(2.4)NANANANA
Medium Radius 90º Elbow5(1.5)5(1.5)5(1.5)NANANANA
Long Radius 90º Elbow3(0.9)3(0.9)3(0.9)3(0.9)3(0.9)
Mitered 45º Elbow4(1.2)4(1.2)4(1.2)NANANANA
Medium Radius 45º Elbow2.5(0.8)2.5(0.8)2.5(0.8)NANANANA
Long Radius 45º Elbow1.5(0.5)1.5(0.5)1.5(0.5)1.5(0.5)1.5(0.5)
Tee16(4.9)16(4.9)16(4.9)16(4.9)16(4.9)
* Note: 3 --- and 4 ---in. Vent pipe systems require long radiu s elbows.
Venting System Length Calculations
The maximum length for each vent pipe (inlet or exhaust) equals the Maximum Equivalent Vent Length (MEVL) from Table 13 or Table 15
minus the number of elbows multiplied by the deduction for each elbow in Table 14.
Standard vent terminations and concentric vent terminations count for zero deductions.
Example
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 m) with 2--in.(51 mm) Vent piping. Venting system includes, FOR EACH
PIPE, (3) 90_ long radius elbows, (2) 45_ long radius elbows and a concentric vent kit.
Maximum Equivalent Vent Length=127 ft.(From Table 13)
Deduct (3) 90 long radius3x3 ft.=- 9 ft.(From Table 14)
Deduct (2) 45 long radius2x1.5 ft.=- 3 ft.(From Table 14)
Maximum Vent Length=115 ft.For EACH vent or inlet pipe
44
Page 45
NOTE: Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations. Use Table 14 - Deductions from
Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 15 – Maximum Equivalent Vent Length -- Ft. (M)
4501 to 10,000 Ft. (0 to 1370 M) Altitude
Altitude
FT (M)
4501 to 5000
(1370 to
1524)
5001 to 6000
(1524 to
1829)
6001 to 7000
(1829 to
2134)
7001 to 8000
(2134 to
2438)
8001 to 9000
(2438 to
2743)
9001 to
10,000
(2743 to
3048)
Unit Size
1-1/222-1/234
60,00035(10.7)111(33.8)198(60.4)221(67.4)NA
80,00023(7.0)85(25.9)146(44.5)195(59.4)216(65.8)
100,000NA40(12.2)91(27.7)200(61.0)222(67.7)
120,000NANANA80(24.4)211(64.3)
60,00037(11.3)103(31.4)186(56.7)207(63.1)NA
80,00022(6.7)76(23.2)137(41.8)183(55.8)200(61.0)
100,000NA33(10.1)85(25.9)188(57.3)208(63.4)
120,000NANANA74(22.6)199(60.7)
60,00035(10.7)96(29.3)174(53.0)194(59.1)NA
80,00020(6.1)71(21.6)120(36.6)171(52.1)185(56.4)
100,000NA31(9.4)79(24.1)178(54.3)195(59.4)
120,000NANANA68(20.7)187(57.0)
60,00032(9.8)89(27.1)163(49.7)181(55.2)NA
80,00018(5.5)66(20.1)120(36.6)159(48.5)170(51.8)
100,000NA29(8.8)73(22.3)167(50.9)182(55.5)
120,000NANANA62(18.9)175(53.3)
60,00030(9.1)82(25.0)152(46.3)168(51.2)NA
80,00017(5.2)62(18.9)111(33.8)148(45.1)156(47.5)
100,000NA27(8.2)67(20.4)157(47.9)170(51.8)
120,000NANANA56(17.1)164(50.0)
60,00027(8.2)76(23.2)142(43.3)156(47.5)NA
80,00015(4.6)57(17.4)103(31.4)137(41.8)142(43.3)
100,000NA24(7.3)62(18.9)147(44.8)157(47.9)
120,000NANANA51(15.5)153(46.6)
DIRECT VENT (2-PIPE) AND VENTILATED COMBUSTION AIR ONLY
Vent Pipe Diameter
987MA
Notes:
1. 3-- - and 4 ---in. Vent pipe systems require lon g radius elbows.
2. Vent sizing for C anadian installa tions over 4500 ft. (1370 M) above sea level are subject to acceptance by the local authorities having jurisdiction.
3. NA -- - Not allowed; pressure switch will not close, or flame disturbance may result.
4. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
5. Size both the combustion --- air and vent pipe independently, then use the larger diameter for both pipes.
6. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.
7. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
8. The minimum pipe length is 5 ft. (1.5 M) for all application s.
9. Use 3 ---in. (76 mm) diameter vent termination kit for installations requiring 4 --- in. (102 mm) diameter pipe.
45
Page 46
987MA
Attach gaskets to vent pipe and
combustion air adapters.
Fig. 36 -- Vent Coupling and Adapter with Gaskets
Vent Coupling and Adapter
VENT ELBOW CLAMP
TORQUE 15 LB-IN.
A11314
MODULATING INDUCER ASSEMBLY
INDUCER OUTLET
Fig. 37 -- Inducer Vent Elbow
(Appearance May Vary)
VENT PIPE CLAMP
TORQUE 15 LB-IN.
VENT ELBOW
A11286
46
Page 47
7
6
7
Any other unused
6
knockout may be used
for combustion air
connection.
Any other unused
knockout may be used
5
Rotate vent elbow to
1
3
2
&
5
4
required position.
A11309
for combustion air
connection.
Rotate vent elbow to
required position.
4
5
2
5
1
3
A11308
3
2
5
1
4
5
Any other unused
knockout may be used
7
6
for combustion air
connection.
A11310
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
6
Attach combustion air pipe adapter with gasket to furnace.
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
Fig. 38 -- Upflow Configurations
(Appearance May Vary)
987MA
A11399
47
Page 48
987MA
Rotate vent elbow to
required position.
3
2
5
1
6
7
4
5
Rotate vent elbow to
required position.
4
5
2
5
1
3
Any other unused
knockout may be used
for combustion air
connection.
A11311
6
7
A11312
A11313
Downflow Vertical
Requires Accessory Internal Vent Kit.
See Product Data for current kit number.
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
6
Attach combustion air pipe adapter with gasket to furnace.
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
Fig. 39 -- Downflow Configurations
(Appearance May Vary)
A11400
48
Page 49
HORIZONTAL LEFT VERTICAL VENT CONFIGURATION
HORIZONTAL LEFT RIGHT VENT CONFIGURATION*
*Requires Accessory Internal Vent Kit
See Product Data for Current Kit Number
HORIZONTAL LEFT LEFT VENT CONFIGURATION
987MA
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
Attach combustion air pipe adapter with gasket to furnace.
6
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
A11340
Fig. 40 -- Horizontal Left
(Appearance May Vary)
49
Page 50
HORIZONTAL RIGHT -
987MA
VERTICAL VENT CONFIGURATION
HORIZONTAL RIGHT LEFT VENT CONFIGURATION*
*Requires Internal Vent Kit
See Product Data for Current Kit Number
HORIZONTAL RIGHT RIGHT VENT CONFIGURATION
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
Attach combustion air pipe adapter with gasket to furnace.
6
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
A11341
Fig. 41 -- Horizontal Right
(Appearance May Vary)
50
Page 51
VENT PIPE ADAPTER WITH GASKET
INSTALLED ON FURNACE VENT
PIPE IS CUT FLUSH WITH TOP OF
ADAPTER.
ALIGN NOTCHES IN VENT PIPE
COUPLING OVER STAND-OFF
ON ADAPTER. TORQUE LOWER
CLAMP 15 LB-IN. WHEN REMAINING
VENT PIPE IS INSTALLED, TORQUE
UPPER CLAMP TO 15 LB-IN.
987MA
VENT PIPE FLUSH WITH ADAPTER
Fig. 42 -- Vent Pipe Flush with Adaptor
Point elbow down towards
back of furnace
VENT PIPE FLUSH SHOWING COUPLING
A11339
12” MINIMUM
256.0 mm
CASING SIDE ATTACHMENT
COMBUSTION AIR PIPE
(ATTIC OR CRAWLSPACE ONLY)
TOP PLATE ATTACHMENT
COMBUSTION AIR PIPE
(ATTIC OR CRAWLSPACE ONLY)
Vertical clearance to a ventilated soffit located above
the terminal within a horizontal di stance of 2 feet (61
D
cm) from the centerline o f the terminal
EClearance to an unventilated soff it
FClearance to a n outside corner
GClearancetoaninsidecorner
Clearance to each side o f the cente rline extended
above electrical meter or gas service regulator as-
H
sembly
IClearance to service regulator vent outlet3ft.(.9M)
Clearance to non--- mechanical air supply inlet to
building or the combustion air inlet to any other appli-
J
ance
KClearance to a mechanical air supply inlet6ft.(1.8M)3ft.(.9M)
LClearance under a veranda, porch, deck, or balcony
Clearance to each side o f the cente rline extended
above or below vent terminal of the furnace to a dryer
M
or water heater vent, or other appliance’s direct vent
intake or exhaust
Clearance to the vent termi nal of a dryer vent, wa ter
heater vent, or other applia nces direct ve nt intake or
N
exhaust
OClearance from a plumbing vent stack3ft.(.9M)3ft.(.9M)
Clearance above paved sidewalk or paved driveway
P
located on public property
(1) In accordance with the current C A N / CSA B
(2) In accordance with the current ANSI Z22 3.1.NFPA 54, National Fuel Gas Code
Notes:
1. The vent forthis appliance shall not terminate:
a. Over public walkways; or
b. Near soffit vents of crawl space vents or oth er areas where condensate or vap or could create a nuisance o r hazard or property damage; o r
c. Where condensate vapor could cause damage orcould be detrimental to the operation of regulators,relief valves,or otherequipment.
2. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combustion products of adjacent vents.
Recirculation can cause poor combustio n, inlet condensate problems, and accelerated corrosion of the heat exchan gers.
3. Avoid v enting under a deck or large overhang. Recirculation could o ccur and cause performance or system problems.
149.1, Natural Gas and Propane Installation Code.
V
12 in. (305 mm). 18 in. (457 mm) above roof surface.12 in. (305 mm)
12 in. (305 mm) for appliances > 10,000 Btuh (3kW)
and </--- 100,000 Btuh (30 kW), 36 in. (914 mm) for
appliances > 100,000 Btuh (30 kW)
For clearances not specified in ANSI Z223.1/NFPA 54 or
C A N / CSA B149.1, clearances shall be in accordance
with local installation codes and the requirements of
the gas supplier and the manufacturer’s installation
instructions.
3ft.(.9M)within15ft. (4.6 M) abovethemeter/
regulator assembly
12 in. (305 mm) for appliances > 10,000 Btuh(3kW)
and </--- 100,000 Btuh (30 kW), 36 in. (914 mm) for
appliances > 100,000 Btuh (30 kW)
12 in. (305 mm). Permitted only if veranda, porch,
deck, or balcony is fully open on a minimum of two
sides b eneath the f loor.
12 in. (305 mm)12 in. (305 mm)
3ft.(.9M)3ft.(.9M)
7 ft. (2.1 M). A vent shall not terminate above a sidewalk or paved driveway that is locate d betwee n two
single family dwellings and serves both dwellings.
Fig. 44 -- Direct Vent Termination Clearance
V
9 in. (229 mm) for appliances > 10,000 Btuh (3kW)
and </--- 50,000 Btuh (15 kW), 12 in. (305 mm) for
appliances > 500,000 Btuh (15 kW)
For clearances not specified in ANSI Z223.1/NFPA 54 or
C A N / CSA B149.1, clearances shall be in accordance
with loca l installation codes and the requi rements of
the gas supplier and the manufacturer’s installation
instructions.
3ft.(.9M)within15ft. (4.6 M) abovethemeter/
regulator assembly
*3 ft. (.9 M) *For cl eara nces not specified in ANSI Z223 .1
/NFPA 54or C A N / CSA B149.1, clearances shall be in
accordance wi th local i nstallati on codes and the
requirements of the gas supplier and the manufa cturer’s
installation instructions.
9 in. (229 mm) for appliances > 10,000 Btuh (3kW)
and </--- 50,000 Btuh (15 kW), 12 in. (305 mm) for
appliances > 500,000 Btuh (15 kW)
For clearances not specified in ANSI Z223.1/NFPA 54 or
C A N / CSA B149.1, clearances shall be in accordance
with loca l installation codes and the requi rements of
the gas supplier and the manufacturer’s installation
instructions.
For clearances not specified in ANSI Z223.1/NFPA 54 or
CAN/CSA B149.1, clearances shall be in accordance
with loca l installation codes and the requi rements of
the gas supplier and the manufacturer’s installation
instructions.
Vertical clearance to a ventilated soffit located above
the terminal within a horizontal di stance of 2 feet (61
D
cm) from the centerline of the te rminal
ECl earance to an unventila ted soffit
FCleara nce to an outside corner
GClea rance to an inside corner
Clearance to each side o f the cente rline extended
above electrical meter or gas service regulator as-
H
sembly
IClearance to service regulator vent outlet3ft.(.9M)
Clearance to non--- mechanical air supply inlet to
building or the combustion air inlet to any other appli-
J
ance
KClearance to a mechanical air supply inlet6ft.(1.8M)3ft.(.9M)
LClearance under a veranda, porch, deck, or balcony
Clearance to each side o f the cente rline extended
above or below vent terminal of the furnace to a dryer
M
or water heater vent, or other appliance’s direct vent
intake or exhaust
Clearance to the vent termi nal of a dryer vent, wa ter
heater vent, or other applia nces direct ve nt intake or
N
exhaust
OClea rance from a plumbing vent sta ck3ft.(.9M)3ft.(.9M)
Clearance above paved sidewalk or paved driveway
P
locate d on publ ic property
(1) In accordance with the current C A N / CSA B
(2) In accordance with the current ANSI Z22 3.1.NFPA 54, National Fuel Gas Code
Notes:
1. The vent forthis appliance shall not terminate:
a. Over public walkways; or
b. Near soffit vents of crawl space vents or oth er areas where condensate or vap or could create a nuisance o r hazard or property damage; o r
c. Where condensate vapor could cause damage orcould be detrimental to the operation of regulators,relief valves,or otherequipment.
2. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combustion products of adjacent vents.
Recirculation can cause poor combustion, inlet conden sate problems, and accelerated co rrosion of the heat exch angers.
3. Avoid v enting und er a deck or large overhang. R ecirculation could o ccur and cause performance or system problems.
149.1, Natural Gas and Propane Installation Code.
12 in. (305 mm). 18 in. (457 mm) above roof surface.12 in. (305 mm)
6 in. (152 mm) for appliances </--- 10,000 Btuh (3kW)
12 in. (305 mm) for appliances > 10,000 Btuh (3kW),
and </--- 100,000 Btuh (30kW), 36 in. (914 mm) for
appliances > 100,000 Btuh (30 kW)
For clearances not specified in ANSI Z223.1/NFPA 54 or
CAN/CSA B149.1, clearances shall be in accordance
with local installation codes and the requirements of
the gas supplier and the manufacturer’s installation
instructions.
3ft.(.9M)within15ft. (4.6 M) abovethemeter/
regulator assembly
6 in. (152 mm) for appliances </--- 10,000 Btuh (3kW)
12 in. (305 mm) for appliances > 10,000 Btuh (3kW),
and </--- 100,000 Btuh (30kW), 36 in. (914 mm) for
appliances > 100,000 Btuh (30 kW)
12 in. (305 mm). Permitted only if veranda, porch,
deck, or balcony is fully open on a minimum of two
sides b eneath the floo r.
12 in. (305 mm)12 in. (305 mm)
3ft.(.9M)3ft.(.9M)
7 ft. (2.1 M). A vent shall not terminate above a sidewalk or paved driveway that is locate d betwee n two
single family dwellings and serves both dwellings.
4 ft. (1.2 M) belo w or to the side of the openi ng. 1 ft.
(.3 M) above the opening.
For clearances not specified in ANSI Z223.1/NFPA 54 or
CAN/CSA B149.1, clearances shall be in accordance
with loca l installation codes and the requi rements of
the gas supplier and the manufacturer’s installation
instructions.
* 3 ft. (.9 M) * For clea rances not specified in ANSI
Z223.1/NFPA54 orCAN/CSAB149.1,clearancesshall
be in accordance with loca l install ation co des and the
requirements of the gas supplier and the manufacturer’s
installation instructions.
4 ft. (1.2 M) belo w or to the side of the openi ng. 1 ft.
(.3 M) above the opening.
For clearances not specified in ANSI Z223.1/NFPA 54 or
C A N / CSA B149.1, clearances shall be in accordance
with loca l installation codes and the requi rements of
the gas supplier and the manufacturer’s installation
instructions.
7ft.(2.1M).
Fig. 45 -- Ventilated Combustion Air and Non--Direct Vent Termination Clearance
987MA
A11047
53
Page 54
987MA
V e r tical separation
between comb ustion
air and v ent
8 3/4 in. (222mm)f or 3 in. (76mm)ki t
6 3/4 in. (172mm)f or 2 in. (51mm) ki t
Maintain 12 in. (305mm)min.
clearance abo ve
highest anticipated
sno w le ve l
Maximum of 24 in.(614mm)
abo v e roof
Note: "A" denotes 0 to < 2 in.
Between the first 2 vents
Third vent must be > 36 in. away
Roof T e rm ination (Pref erred)
18 in. maximu m
90 °
At least 36 in.
(914mm)
(457mm)
A t least 36 in
(914mm)
(51mm)
Concent ri c V ent and Comb ustion Ai r
A
Abandoned masonr y
used as race wa y
(per code)
(914mm)
12
in.
min fro m
ov erhang or roof
(typ)
in.
(305mm)
At least 36 in.
(914mm)
12
in. (305mm)
separation between
A
.
bottom ofcomb ustion air and
bottom of v ent (typ)
Maintain 12
min. clearance abo ve
highest anticipated
sno w le ve l or grade
whiche ve r is greater (typ)
Roof T er mination (pre fe rred)
A
Side wa ll te rm inatio n
in. (305mm)
of less than 12
At least
36 in.
(914mm)
above highest snow level
A
Maintain 12
in.
min. clearance abo ve
highest anticipated
sno w le ve l, maximum of
24 in . abo v e roof
1
in. (25mm)
A
t le
a
3
s t
6
in
.
Concent ri c V ent
and Comb ustion - Air
Side T e rm inatio n
(305mm)
maximum (typ) from wall to inlet
12
in. (305mm)
ov erhang or roof
A
Maintain 12
min. clearance ab ov e
highest anticipated
sno w le v el or grade
which eve r is greate r
minimum fro m
(305mm)
in.
Fig. 46 -- Combustion Air and Vent Pipe Termination for Direct Vent (2--Pipe) System
Roof Termination (Preferred)
Ven t
(305mm)
Maintain 12 in .
minimum clearance
above highest anticipated
snow level maximum of
24 in. (610mm) above roof.
Abandoned masonry
used as raceway
(per code)
12 in. min. (305 mm)from
overhang or roof
Sidewall Termination
with Straight Pipe (preferred)
90°
Side wall termination
with 2 elbows (preferred)
12 in. (305 mm) min. from
overhang or roof
Maintain 12 in. (305mm)
minimum clearance
above highest anticipated
snow level or grade
whichever is greater.
6 in. (152mm) minimum clearance
between wall and end of vent pipe.
10 in. (254mm) maximum pipe length
Maintain 12 in. (305mm)
minimum clearance
above highest anticipated
snow level or grade
whichever is greater
A05090
Fig. 47 -- Vent Pipe Termination for Non--Direct Vent and Ventilated Combustion Air System
A05091
54
Page 55
NOTE: This illustration is for
reference only. Your unit may
differ in appearance or may not
include all components shown.
VENT
Angle
o
22.5
to
o
45
off wall
BRACKET
COUPLING
COMBUSTION-AIR
(ELBOW PARALLEL
TO WALL)
OVERHANG OR ROOF
MAINTAIN 12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
12 IN. SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR AND
BOTTOM OF VENT
L10F022
987MA
EXHAUST
OVERHANG
Clearance to overhang per code
12 in. (304.8mm) MIN. Ground
Level OR Snow Level
Fig. 48 -- Alberta and Saskatchewan Vent Termination
A11346
55
Page 56
Ventilated Combustion
Air intake pipe
Pipe hangar
3” (76 mm)
987MA
Ventilated Combustion Air
intake termination in crawl
space
12” (305 mm)
CRAWL SPACE
highest level of insulation
Fig. 49 -- Vent Terminations for Ventilated Combustion Air
ATTIC
A10497
56
Page 57
START--UP, ADJUSTMENT, AND SAFETY
CHECK
General
1. Furnace must have a 115-v power supply properly connected and grounded.
NOTE: Proper polarity must be maintained for 115-v wiring.
Control status indicator light flashes rapidly and furnace does not
operate if polarity is incorrect.
2. Thermostat wire connections at terminals R, W/W1, G,
Y/Y2, etc. must be made at 24-v terminal block on furnace
control. See communicating wall control instructions for
proper wiring of communicating controls.
3. Natural gas service pressure must not exceed 0.5 psig (14in. w.c.), but must be no less than 0.16 psig (4.5-in. w.c.).
4. Blower door must be in place to complete 115-v electrical
circuit to furnace.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
These furnaces are equipped with a manual reset limit
switch in burner assembly. This switch opens and shuts off
power to the gas valve is an overheat condition (flame
rollout) occurs in burner assembly. Correct inadequate
combustion--air supply or improper venting condition
before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch
for continuity. If necessary, press button to reset switch.
EAC-1 terminal is energized whenever blower operates. HUM
terminal is only energized when blower is energized in heating.
Select Setup Switch Positions
There are 4 sets of setup switches on the furnace control board.
These switches configure the furnace for correct application
requirement. They also select the airflow settings for Air
Conditioning and Continuous Fan CFMs.
The Setup Switch locations are shown and described on Fig. 54.
The set up switches are also shown on the unit wiring label.
Setup Switches (SW1)
The furnace control has 8 setup switches that may be set to meet
the application requirements. To set these setup switches for the
appropriate requirement:
S Remove blower door.
S Locate setup switches on furnace control.
S Configure the set-up switches as necessary for the application.
S Replace blower door.
NOTE: If a bypass humidifier is used, setup switch SW1-3
(Min/Int Rise Adjust) should be in ON position. This compensates
for the increased temperature in return air resulting from bypass.
NOTE:If modulating dampers are used, blower motor
automatically compensates for modulating dampers.
Air Conditioning (A/C) Setup Switches (SW2)
The air conditioning setup switches are used to match furnace
airflow to cooling unit used.
To set the desired cooling airflow:
1. Remove blower door.
2. Locate A/C setup switches on furnace control.
3. Determine air conditioning tonnage used.
4. Configure the switches for the required cooling airflow.
NOTE: Excessive airflow caused by improper A/C switch setup
may cause condensate blow-off in cooling mode.
5. Replace blower door.
Continuous Fan (CF) Setup Switches (SW3)
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode or to select low-cooling
airflow for two-speed cooling units. This setup feature allows
continuous fan airflow or low-cooling airflow to be adjusted. To
set desired continuous fan airflow or low-cooling airflow:
1. Remove blower door.
2. Locate CF setup switches on furnace control.
3. Determine desired continuous fan airflow or low-cooling
airflow.
4. Configure the switches for the required continuous fan or
low--cooling airflow.
5. Replace blower door.
Additional Setup Switches (SW4)
The furnace control has 3 additional setup switches labeled SW4.
Setup switch SW4-2 can be used to lock the furnace into
intermediate heat. When setup switch SW4-2 is ON it will over
ride setup switch SW1-2 if it is ON SW4--3 is used to adjust
airflow. See communicating control instructions for use of SW4--1.
To activate setup switch SW4-2 and SW4--3:
1. Remove blower door.
2. Locate setup switch SW4 on furnace control.
3. Configure the switches for the required heat stages and
airflow if necessary.
4. Replace blower door.
Prime Condensate Trap with Water
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may
not occur. The condensate trap has two internal chambers
which can ONLY be primed by pouring water into the
inducer drain side of condensate trap.
1. Remove upper and middle collector box drain plugs opposite of the condensate trap. (See Fig. 57.)
2. Connect field-supplied 1/2-in. (13 mm) OD tube to upper
collector box drain connection.
3. Insert field-supplied funnel into tube.
4. Pour one quart of water into funnel/tube. Water should run
through collector box, overfill condensate trap, and flow into open field drain.
6. Connect field-supplied 1/2-in. (13 mm) OD tube to middle
collector box drain port.
7. Pour one quart of water into funnel/tube. Water should run
through collector box, overfill condensate trap, and flow into open field drain.
8. Remove funnel and tube from collector box and replace collector box drain plug.
987MA
57
Page 58
Purge Gas Lines
If not previously done, purge the lines after all connections have
been made and check for leaks.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of
life.
Adjustments
987MA
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
DO NOT redrill orifices. Improper drilling (burrs,
out--of--round holes, etc.) can cause excessive burner noise
and misdirection of burner flames. This can result in flame
impingement of heat exchangers, causing failures. (See Fig.
51.)
For proper operation and long term reliability, the Furnace input
rate must be within +2 percent of input rate on furnace rating plate.
The gas input rate on rating plate is for installations at altitudes up
to 2000 ft. (609.6M).
In the USA., the input rating for altitudes above 2000 ft. (609.6M)
must be reduced by 2 percent for each 1000 ft. (304.8M) above sea
level. Refer to Table 16.
In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 ft. (609.6M) to 4500 ft. (1371.6M) above sea
level.
To adjust manifold pressure to obtain the proper input rate, first,
determine if the furnace has the correct orifice installed. At higher
altitudes or different gas heat contents, it may be necessary to
change the factory orifice to a different orifice. Tables have been
provided in the furnace installation instructions to match the
required orifice to the manifold pressure to the heat content and
specific gravity of the gas. To do this:
a. Obtain average heat value (at installed altitude) from local
b. Obtain average specific gravity from local gas supplier.
c. Find installation altitude range for your installation in the
d. Find closest natural gas heat value and specific gravity in
e. Follow heat value and specific gravity lines to point of
f. Check and verify burner orifice size in furnace. Never
NOTE: For Canadian altitudes of 2000 to 4500 ft. (609.6 to
1371.6M), use USA altitudes of 2001 to 3000 ft. (609.6 to
914.4M).
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of
!
CAUTION
gas supplier.
manifold pressure tables. See Table 19.
Table 19.
intersection to find orifice size and maximum and minimum
manifold pressure settings for proper operation.
assume orifice size. Always check and verify.
correct size. Never redrill an orifice. A burr--free and squarely
aligned orifice hole is essential for proper flame characteristics.
See Example 1.
g. Replace original orifice with correct size, if required by
Table 19.Use only factory--supplied orifices.See
EXAMPLE 1.
EXAMPLE 1
EXAMPLE: 0 -- 2000 ft. (0 -- 609.6M) altitude
Heating value = 1050 Btu/cu ft.
Specific gravity = 0.62
Therefore: Orifice No. 44
Manifold pressure: 3.4--in. w.c. for maximum heat, 0.55--in. w.c.
for minimum heat.
* Furnace is shipped with No. 44 orifices. In this example, all main
burner orifices are the correct size and do not need to be changed to
obtain proper input rate.
The inlet gas pressure must be checked with the furnace operating
in maximum heat. This is necessary to make sure the inlet gas
pressure does not fall below the minimum pressure of 4.5 in. w.c.
for natural gas. The maximum inlet gas pressure is 13.6 in. of water
column. If the inlet pressure is too low, you will not be able to
adjust the manifold pressure to obtain the proper input rate. To
check the inlet gas pressure:
1. Make sure the gas supply is turned off to the furnace and at
the electric switch on the gas valve.
2. Remove the 1/8 in. NPT plug from the inlet pressure tap on
the gas valve.
3. Connect a manometer to the inlet pressure tap on gas valve.
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Jumper the R to W/W1 and W2 thermostat connections at
the furnace control board.
8. When main burners ignite, confirm inlet gas pressure is
Between 4.5 in. w.c. and 13.6 in. w.c.
9. Remove jumper across thermostat connections to terminate
call for heat. Wait until the blower off delay is completed.
10. Turn furnace gas valve electric switch to OFF position.
11. Turn gas supply manual shutoff valve to OFF position.
12. Turn off furnace power supply.
13. Remove manometer from the inlet pressure tap of the gas
valve.
14. Apply pipe dope sparingly to end of inlet gas pipe plug and
re--install in the gas valve.
For proper operation and long term reliability, the manifold
pressure must be adjusted within +2 percent of input rate on
furnace rating plate.
The modulating furnace manifold pressure is set at two points. The
first point is Maximum Heat. The second point is Minimum Heat.
Do not adjust Intermediate Heat manifold pressure. Intermediate
Heat manifold pressure is checked as part of the temperature rise,
but is not adjustable. Always adjust Maximum Heat first, then
Minimum Heat.
NOTE: DO NOT set Maximum Heat manifold pressure less than
3.2--in. w.c. or more than 3.8 in. w.c. for natural gas.
To adjust manifold pressure to obtain input rate for Maximum
Heat:
1. Make sure the gas supply is turned off to the furnace and at
the electric switch on the gas valve.
2. Remove the 1/8 inch NPT plug from the outlet pressure tap
on the gas valve.
3. Connect a manometer to the outlet pressure tap on gas
valve.
58
Page 59
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Jumper the R to W/W1 and W2 thermostat connections at
the furnace control board.
8. After the main burners ignite and the blower starts, confirm
Maximum Heat manifold pressure is correct, based on the
manifold pressure tables in the installation instructions.
9. To adjust the Maximum Heat manifold pressure, slowly turn
adjusting screw counterclockwise to decrease manifold
pressure or clockwise to increase manifold pressure. Turn
adjustment no more than one click per second until you
obtain the required manifold pressure.
10. Main burner flame should be clear blue, almost transparent.
11. After adjusting the Maximum Heat manifold pressure,
remove jumpers across thermostat connections to terminate
the call for heat.
12. Wait for blower off-delay to finish then reset 115-v power to
furnace.
To adjust manifold pressure to obtain input rate for Minimum Heat:
1.TurnSW1--2ONandSW4--2mustbeOFF.
2. Jumper R and W/W1 thermostat connections on control to
start furnace.
3. After the main burners ignite and the blower starts, confirm
Minimum Heat manifold pressure is correct, based on the
manifold pressure tables in the installation instructions.
4. To adjust the Minimum Heat manifold pressure, slowly turn
adjusting screw counterclockwise to decrease manifold
pressure or clockwise to increase manifold pressure. Turn
adjustment no more than one click per second until you
obtain the required manifold pressure.
5. After adjusting the manifold pressure, remove jumpers
across thermostat connections to terminate the call for heat.
Wait until the blower off delay is completed.
6. Move setup switch SW1-2 to the OFF position.
7. Turn gas supply manual shutoff valve to OFF position.
8. Turn off furnace power supply.
9. Remove manometer from the inlet pressure tap of the gas
valve.
10. Apply pipe dope sparingly to end of inlet gas pipe plug and
re-install in the gas valve.
11. Re-install cap over adjustment screw on the top of the gas
valve.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in shortened
furnace life.
Set air temperature rise within limits specified on the rating
plate to prevent reduced life of furnace components.
Operation is within a few degrees of the mid--point of rise
rangewhensetupswitchSW1--4isOFF.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in overheating the
heat exchangers or condensing flue gases in heat exchanger
areas not designed for condensate.
Temperature rise must be within limits specified on unit
rating plate. Operation is within a few degrees of midpoint
ofriserangewhensetupswitchSW1--4isOFF.
Adjust Temperature Rise
When setup switch SW1-4 is ON, operation will be near the high
end of the rise range for improved comfort.
Furnace must operate within ranges of temperature rise specified
on the furnace rating plate. Determine air temperature rise as
follows:
1. Place thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
NOTE: Temperature rise can be determined for Minimum Heat,
Intermediate Heat and Maximum Heat operation by locking the
furnace in each mode of operation. The mode of operation is based
on the position of Set-up switch SW1-2 and SW4-2 on the furnace
control board.
The furnace is capable of automatically providing proper airflow to
maintain the temperature rise within the range specified on furnace
rating plate. If temperature rise is outside this range, proceed as
follows:
a. Check gas input for minimum, intermediate and maximum
heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive restrictions
causing static pressure greater than 0.5-in. w.c.
d. Ensure Min/Int Rise Adjust switch SW1--3 on furnace
control is in ON position when a bypass humidifier is used.
(See Fig. 54 for switch location.)
e. Check Troubleshooting Guide for Variable--Speed Step
Modulating Condensing Furnaces.
To lock the furnace in Minimum Heat:
1. Turn SW1--2 ON at the furnace control. Set up switch
SW4--2 must be OFF.
2. Connect a jumper across R and W/W1 at the thermostat
terminals at the furnace control.
3. Allow the burners to ignite and the blower to turn on.
4. Allow the supply temperature to stabilize and verify the
proper rise range.
If the temperature rise is too high or too low in Minimum Heat:
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Set up switch SW1--3. When set to
ON, airflow is raised 18% for Minimum Heat and for
Intermediate Heat. Factory default position is OFF.
5. Turn 115 VAC power on.
6. Re--check Minimum Heat Temperature Rise
987MA
59
Page 60
To lock the furnace in Intermediate Heat:
1. Turn SW1--2 OFF and SW4--2 ON at the furnace control.
2. Connect a jumper across R and W/W1 at the thermostat
terminals at the furnace control.
3. Allow the burners to ignite and the blower to turn on.
4. Allow the supply temperature to stabilize and verify the
proper rise range.
If the temperature rise is too high or too low in Intermediate Heat:
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Set up switch SW1--3. When set to
ON, airflow is raised 18% for Minimum Heat and for
Intermediate Heat. Factory default position is OFF.
5. Turn 115 VAC power on.
6. Re--check Minimum Heat Temperature Rise .
To lock the furnace in Maximum Heat:
987MA
1. Connect a jumper across R and W/W1 and W2 at the
thermostat terminals at the furnace control.
2. Allow the burners to ignite and the blower to turn on.
3. Allow the supply temperature to stabilize and verify the
proper rise range.
If the temperature rise is too high or too low in Maximum Heat:
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Set up switch SW1--4. When set to
OFF, airflow is raised 9% for Minimum Heat, 7% for
Intermediate Heat and 15% for Maximum Heat. Factory
default position is ON.
5. Turn 115 VAC power on.
6. Re--check Minimum Heat Temperature Rise.
After the temperature rise has been verified:
1. Remove jumpers from thermostat terminals.
2. Allow the blower off delay to complete.
3. Turn Set up switches SW1--2 and SW4--2 to the OFF position.
4. Install blower door.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Reinstall manifold pressure tap plug in gas valve to prevent
gas leak.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace
life.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
mid--point of rise range or slightly above.
f. Proceed to “Set Blower Off Delay” before installing
blower door.
Adjust Blower Off Delay (Heat Mode)
a. Remove blower door if installed.
b.TurnDipswitchSW--7orSW--8ONorOFFfordesired
blower off delay. (See Table 17 and Fig. 34 , 54 and 63.)
Adjust Cooling Airflow -- Single Stage and High
Stage
Cooling
The ECM blower can be adjusted for a range of airflow for Low
Speed or High Speed cooling. See Table 7--Air Delivery -- CFM
(With Filter ). Depending on the model size, the cooling airflow
can be adjusted from 1.5 to 6 tons based on 350 CFM ton.
The cooling airflow is adjusted by turning Setup switches SW2--1,
SW2--2 and SW2--3 either ON or OFF. Select the required airflow
from Table 7. Table 7 is based on 350 CFM per ton. For other
CFM per ton setup switch selections. See Fig. 34 and Fig. 54 and
Fig.63.
NOTE: 6 ton airflow will truncate at 2200 CFM on applicable
models. For a complete explanation of cooling airflow, refer to the
section titled “Sequence of Operation.”
Adjust Continuous Fan Airflow/Low Speed
Cooling
The ECM blower motor can be adjusted for continuous fan speeds
different than heating or cooling fan speed. See Table 7 -- Air
Delivery -- CFM (With Filter). Select the required continuous fan
airflow from Fig. 54 and Table 7. Other airflow options are
available via SW4--3. See Table 7.
The continuous fan speed is also the fan speed for low speed
cooling when furnace is used with a 2--speed cooling unit. Adjust
the Continuous Fan CFM to match the airflow required for low
speed cooling. Select the required airflow from Fig. 54. For other
CFM per ton setup switch selections. (See Fig. 34 and Fig. 54.)
The airflow selected for low speed cooling will also be the airflow
used for continuous fan.
The continuous fan speed can be further adjusted at the thermostat
using the “Comfort Fan” select function. Changing the continuous
fan speed at the thermostat DOES NOT change the low speed
cooling airflow selected at the control board.
Airflow
Adjust Thermostat Heat Anticipator.
a. Mechanical thermostat. Set thermostat heat anticipator to
match the amp. draw of the electrical components in the
R--W/W1 circuit. Accurate amp. draw readings can be obtained at the wires normally connected to thermostat subbaseterminals,R and W.The thermostatanticipator should
NOT be in the circuit while measuring current.
(1.) Set SW1--2 switch on furnace control board to ON.
(2.) Remove thermostat from subbase or from wall.
(3.) Connect an amp. meter as shown in Fig. 52 across
the R and W subbase terminals or R and W wires
at wall.
(4.) Record amp. draw across terminals when furnace is
in minimum heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat
instructions and install on subbase or wall.
(6.) Turn SW1--2 switch OFF.
(7.) Install blower door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked
in the Start--up procedure section as part of normal operation.
1. Check Main Limit Switch
This control shuts off combustion system and energizes air-circulating blower motor, if furnace overheats. By using this
method to check limit control, it can be established that limit is functioning properly and will operate if there is a re-
60
Page 61
stricted return--air supply or motor failure. If limit control
does not function during this test, cause must be determined
and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block offreturn air with a pieceof cardboard or
sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re--light when furnace cools down.
2. Check Pressure Switch(es)
This control proves operation of the draft inducer blower.
a. Turn off 115--v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115--v power to furnace.
d. Set thermostat to “call for heat” and wait 1 minute. When
pressure switch is functioning properly, hot surfaceigniter
should NOT glow and control diagnostic light flashes a
status code 32. If hot surface igniter glows when inducer
motor is disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function prop-
erly and correct condition.
f. Turn off 115--v power to furnace.
g. Reconnect inducer motor wires, replace blower door, and
turn on 115--v power.
h. Blower will run for 90 seconds before beginning the call
for heat again.
i. Furnace should ignite normally.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that switches SW1--1 and SW1--6 are OFF and other
setup switches are set as desired. Verify that switches
SW1--7 and SW1--8 for the blower OFF DELAY are set as
desired per Table 17.
3. Verify that blower and control doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review Owner’s Manual with owner.
7. Attach literature packet to furnace.
ON/OFF Switch
MODULATING
Fig. 50 -- Gas Valve
BURNER
Fig. 51 -- Orifice Hole
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
R Y W G
A10496
ORIFICE
987MA
A93059
Turn screw 1 click per
second to adjust rate.
Clockwise to increase
rate, counter clockwise
to decrease rate.
Inlet
Pressure Tap
GAS FLOW
Manifold
Pressure Tap
Min/Max Heat Adust
(Under Cap)
1/2” NPT Outlet
61
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
Fig. 52 -- Amp. Draw Check with Ammeter
A96316
Page 62
987MA
A11542
Fig. 53 -- Service Label Information
62
Page 63
Furnace Setup Switch Description
T
Bl
Off Del
Allows additional CFM per ton selections when used with SW
Turn ON to retrieve up to 7 stored status codes for
troubleshooting assistance when R thermostat lead is
disconnected.
When SW1-2 and SW4-2 are OFF allows Modulating operation
with a single stage thermostat. Turn ON SW1-2 when using
two-stage thermostat to allow Minimum Heat operation when
R to W/W1 closed and a Maximum heat operation when R to
W/W1 and R to W2 close.
urn ON to increase Minimum Heat and Intermediate Heat
airflow by 18 percent. This compensates for increased return
air temperature caused with bypass humidifier. This also
increases the Intermediate Heat inducer speed 15 percent.
Turn ON to decrease Minimum heat airflow by 9 percent,
Intermediate Heat airflow 7 percent and Maximum Heat airflow
15 percent for maximum comfort.
Turn ON for 400 CFM per ton, Turn OFF for 350 CFM per ton.
See also SW4.
Turn ON to initiate Component Self Test for troubleshooting
assistance when R thermostat lead is disconnected. Turn
OFF when Self Test is completed.
ower
seconds. See table in Adjustments section or refer to unit
wiring diagram.
When SW1-2 and SW4-2 are OFF allows Modulating operation
with a single stage thermostat. Turn ON SW4-2 when using
two-stage thermostat to allow Intermediate Heat operation
when R to W/W1 closed and a Maximum heat operation when
R to W/W1 and R to W2 close.
ay time – adjustable 90 seconds to 180
987MA
1
SW2
1
SW3
1-5
325 CFM per ton (nominal) when SW 4-3 ON and SW 1-5 OFF
350 CFM per ton (nominal) when SW 4-3 OFF and SW 1-5 OFF
SW4-3
O
N
1
2
3
AC
O
N
1
2
3
CF
SW 2, AC (Cooling Airflow) SETUP SWITCHES
The AC setup switch selects desired cooling or high stage cooling (two stage units) airflow.
See Air Delivery Tables for specific switch settings
SW 3, CF (Continuous Fan) SETUP SWITCHES
The CF setup switch selects desired Continuous Fan Airflow
The CF switch position is the low cooling airflow selection for two stage cooling units.
The CFM values in the Air Delivery Tables for SW 3 settings are the same as SW 2 settings.
SW 3 cannot be set for airflow higher than SW 2
See Air Delivery Tables for specific switch settings
CFM per ton Adjust
AIR CONDITIONING (A/C) SETUP SWITCHES
CONTINUOUS FAN (CF) SETUP SWITCHES
OFF
370 CFM per ton (nominal) when SW4-3 ON and SW 1-5 ON
400 CFM per ton (nominal) when SW 1-5 ON and SW 4-3 OFF
See Air Delivery Tables for model specific CFM vs. static
Failure to follow this warning could result in personal
injury, death and/or property damage.
The ability to properly perform maintenance on this
equipment requires certain knowledge, mechanical skills,
tools, and equipment. If you do not possess these, do not
attempt to perform any service and maintenance on this
equipment other than those procedures recommended in the
Owner’s Manual.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
pollution.
Remove and recycle all components or materials (i.e. oil,
refrigerant, control board, etc.) before unit final disposal.
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death, or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
install a lockout tag.There may be more than one
disconnect switch. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
!
CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper
furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation.
General
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 2,
you must revise your orientation to component location
accordingly.
Electrical Controls and Wiring
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
There may be more than one electrical supply to the furnace.
Check accessories and cooling unit for additional electrical
supplies that must be shut off during furnace servicing. Lock
out and tag switch with a suitable warning label.
The electrical ground and polarity for 115--v wiring must be
properly maintained. Refer to Fig. 33 for field wiring information
and to Fig. 63 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from heating. The
control system also requires an earth ground for proper operation
of the control and flame--sensing electrode.
The 24--v circuit contains an automotive--type, 3--amp. fuse located
on the control. (See Fig. 34.) Any shorts of the 24--v wiring during
installation, service, or maintenance will cause this fuse to blow. If
fuse replacement is required, use ONLY a 3--amp. fuse. The control
LED will display status code 24 when fuse needs to be replaced.
Troubleshooting
Refer to the service label. (See Fig. 53—Service Label.)
The Troubleshooting Guide (See Fig. 62) can be a useful tool in
isolating furnace operation problems. Beginning with the word
“Start,” answer each question and follow the appropriate arrow to
the next item.
The Guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light--Emitting Diode) to aid in installation, servicing, and
troubleshooting. Status codes can be viewed at the indicator in
blower door. The amber furnace control LED is either ON
continuously, rapid flashing, or a code composed of 2 digits. The
first digit is the number of short flashes, the second digit is the
number of long flashes.
For an explanation of status codes, refer to service label located on
control door or Fig. 53, and the troubleshooting guide which can
be obtained from your distributor.
Retrieving Stored Fault Codes
The stored status codes will NOT be erased from the control
memory, when 115-- or 24--v power is interrupted. The control will
store up to the last 7 Status Codes in order of occurrence.
1. To retrieve status codes, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all
blower--OFF delays must be completed.
a. Leave 115--v power to furnace turned on.
b. Look into blower door indicator for current LED status.
c. Remove blower door.
NOTE: The Status Codes cannot be retrieved by disconnecting
the limit switch. To retrieve Status Codes, follow the procedure
below.
987MA
67
Page 68
2. Turn Setup Switch, SW1--1 “ON.”
3. Manually close blower door switch.
4. Control will flash up to 7 Status Codes.
5. The last Status Code, or 8th Code, will be Code 11.
6. Turn SW1--1 “OFF.”
7. A continuously--lit Amber LED will appear and indicates
proper operation.
8. Release blower door switch, install blower door and refer
to the SERVICE label on the control door for more information.
Component Self--Test
Component Test can ONLY be initiated by performing the
following:
1. Remove blower door.
2. Remove the wire from the “R” terminal of the control
board.
3. Turn Setup Switch, SW--1--6 “ON.”
987MA
4. Manually close blower door switch.
Blower door switch opens 115--v power to control. No component
operation can occur unless switch is closed. Caution must be taken
when manually closing this switch for service purposes.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury,
or death.
Blower door switch opens 115--v power to furnace control.
No component operation can occur unless switch is closed.
Exercise caution to avoid electrical shock from exposed
electrical components when manually closing this switch for
service purposes.
Care and Maintenance
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Never store flammable or combustible materials on, near, or
in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning
compounds, plastic or plastic containers, gasoline,
kerosene, cigarette lighter fluid, dry cleaning fluids,
or other volatile fluids.
3. Paint thinners and other painting compounds, paper
bags, or other paper products. Exposure to these
materials could lead to corrosion of the heat
exchangers.
For continuing high performance and to minimize possible furnace
failure, periodic maintenance must be performed on this furnace.
Consult your local dealer about proper frequency of maintenance
and the availability of a maintenance contract.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and
install lockout tag before performing any maintenance or
service. Follow the operating instructions on the label
attached to the furnace.
5. Component Test sequence will function as follows:
a. The furnace control CPU turns the inducer motor IDM ON
at medium speed and keeps it ON through Step 4.
b. The furnace control CPU will test communication with the
modulating gas valve GV.
c. After waiting 15 seconds the furnace control CPU turns the
hot surface igniter ON for 15 seconds, then OFF.
d. The furnace control CPU then turns the blower motor
BLWM ON at mid-range airflow for 15 seconds, then OFF.
e. After shutting the blower motor BLWM OFF the furnace
control CPU shuts the inducer motor IDM OFF.
NOTE: The EAC terminals are energized when the blower is
operating.
After the component test is completed, 1 or more status codes (11,
25, 35, 41, or 42) will flash. See Service Label on control door or
Service/Status Code Instructions for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 to
OFF and then back ON.
f.TurnsetupswitchSW1--6OFF.
6. RELEASE BLOWER DOOR SWITCH, reattach wire to
“R” terminal on furnace control board and replace blower
door.
!
WARNING
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Never operate furnace without a filter or filtration device
installed. Never operate a furnace with filter or filtration
device access doors removed.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if
required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating
and cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as necessary.
68
Page 69
4. Inspect burner compartment before each heating season for
rust, corrosion, soot or excessive dust. If necessary, have
furnace and burner serviced by a qualified service agency.
5. Inspect the vent pipe/vent system before each heating season for water leakage, sagging pipes or broken fittings.
Have vent pipes/vent system serviced by a qualified service
agency.
6. Inspect any accessories attached to the furnace such as a humidifier or electronic air cleaner. Perform any service or
maintenance to the accessories as recommended in the accessory instructions.
Cleaning and/or Replacing Air Filter
The air filter type may vary depending on the application or
orientation. The filter is external to the furnace casing. There are no
provisions for an internal filter with this furnace. See “Filter
Arrangement” under the “Installation” section of this manual.
!
WARNING
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Never operate furnace without a filter or filtration device
installed. Never operate a furnace with filter or filtration
device access doors removed.
NOTE: If the filter has an airflow direction arrow, the arrow must
point toward the blower.
To clean or replace filters, proceed as follows:
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death, or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
install a lockout tag.There may be more than one
disconnect switch. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by
spraying cold tap water through filter in opposite direction
of airflow. Rinse filter and let dry. Oiling or coating of the
filter is not recommended.
5. If equipped with factory specified disposable media filter,
replace only with a factory specified media filter of the same
size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean
accumulated dirt and grease from blower wheel and motor
annually.
The inducer and blower motors are pre--lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
The following items should be performed by a qualified service
technician. Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove blower door.
3. All factory wires can be left connected, but field thermostat
and accessory wiring may need to be disconnected depending on their length and routing.
4. If the vent and combustion air pipe passes through the
blower compartment, it will be necessary to remove the
pipes from the blower compartment.
Disconnect the vent and combustion air pipe by:
a. Loosen theclamps on the vent couplingsand combustion
air pipe external to the furnace.
b. Separate the pipes from the couplings and move them
aside.
c. Loosen the clamps on the vent couplings andcombustion
air pipe located on the blower shelf.
d. Separate the pipes from the blower compartment and set
aside.
e. Removethecouplingsfromthepipeadaptersand set aside.
f. After servicing the blower, reverse steps a through e.
g. Tighten all clamps 15 lb --in.
See Fig. 60 For Steps 5 through 14.
5. Remove screws securing blower assembly to blower shelf
and slide blower assembly out of furnace. Detach ground
wire and disconnect blower motor harness plugs from
blower motor.
NOTE: Blower wheel is fragile. Use care.
6. Clean blower wheel and motor by using a vacuum with soft
brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades
as balance will be affected.
7. If greasy residue is present on blower wheel, remove wheel
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each
arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner. Do not
get degreaser in motor.
8. Reassemble motor and blower wheel by reversing items 7b
through 7f. Ensure wheel is positioned for proper rotation.
9. Torque motor mounting bolts to 40 +/-- 10 lb--in. when reassembling.
10. Torque blower wheel set screw to 160 +/-- 20 lb--in. when
reassembling.
11. Verify that blower wheel is centered in blower housing and
set screw contacts the flat portion of the motor shaft. Loosen
set screw on blower wheel and reposition if necessary.
12. Spin the blower wheel by hand to verify that the wheel does
not rub on the housing.
13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to blower
deck.
69
987MA
Page 70
15. Reconnect blower leads to furnace control. Refer to furnace
wiring diagram, and connect thermostat leads if previously
disconnected.
NOTE: Be sure to attach ground wire and reconnect blower
harness plugs to blower motor.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Blower door switch opens 115--v power to control. No
component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for
service purposes.
16. Downflow or horizontal furnaces with vent pipe through
furnace only:
987MA
a. Install and connect short piece of vent pipe inside furnace
to existing vent.
b. Connect vent connector to vent elbow.
17. Turn on electrical supply. If outdoor temperature is below
70_F, turn off circuit breaker to outdoor unit before running
furnace in the cooling cycle. Turn outdoor circuit breaker
on after completing cooling cycle. (See Fig. 34.) Manually
close blower door switch. Use a piece of tape to hold switch
closed. Check for proper rotation and speed changes
between heating and cooling by jumpering R to G and R to
Y/Y2 on furnace control thermostat terminals.
NOTE: If R--W/W1 thermostat terminals are jumpered at the time
blower door switch is closed, blower will run for 90 sec before
beginning a heating cycle.
a. Performcomponent self--testas shownat the bottom ofthe
SERVICE label, located on the control door.
b. Verify blower is rotating in the correct direction
18. If furnace is operating properly, RELEASE BLOWER
DOOR SWITCH. Remove any jumpers or reconnect any
disconnected thermostat leads. Replace blower door.
19. Turn on gas supply and cycle furnace through one complete
heating cycle. Verify the furnace temperature rise as shown
in Adjustments Section. Adjust temperature rise as shown in
Adjustments Section.
Cleaning Burners and Flame Sensor
The following items must be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:
NOTE: Use a back-up wrench on the gas valve to prevent the
valve from rotating on the manifold or damaging the mounting to
the burner assembly.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and
install lockout tag before performing any maintenance or
service. Follow the operating instructions on the label
attached to the furnace.
Refer to Fig. 61.
1. Disconnect power at external disconnect, fuse or circuit
breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect the gas pipe from gas valve and remove pipe
from the furnace casing.
6. Disconnect the connector harness from gas valve (Modulating only) or remove individual wires from terminals on gas
valve (All other models).
7. Disconnect Hot Surface Igniter (HSI) wires from HSI.
8. Disconnect Flame Sensor wire from Flame Sensor.
9. Support the manifold and remove the 4 screws that secure
the manifold assembly to the burner assembly and set aside.
Note the location of the green/yellow wire and ground terminal.
10. Inspect the orifices in the manifold assembly for blockages
or obstructions. Remove orifice and clean or replace orifice.
11. Remove the four screws that attach the top plate of the casing to the furnace.
12. Raise top plate up slightly and prop it up with a small piece
of wood or folded cardboard.
13. Support the burner assembly and remove the screws that attach the burner assembly to the heat exchanger cell panel.
14. Remove wires from both rollout switches.
15. Slide one--piece burner out of slots on sides of burner assembly.
16. Remove the flame sensor from the burner assembly.
17. (Optional) Remove the Hot Surface Igniter (HSI) and
bracket from the burner assembly.
18. Check igniter resistance. Nominal resistance is 40 to 70
ohms at room temperature and is stable over the life of the
igniter.
19. Clean burner with a brush and a vacuum.
20. Clean the flame sensor with fine steel wool (0000 grade).
Do not use sand paper or emery cloth.
To reinstall burner assembly:
1. Install the Hot Surface Igniter (HSI) and bracket in burner
assembly.
2. Install flame sensor on burner.
3. Align the edges of the one-piece burner with the slots in the
burner assembly and slide the burners forward until they are
fully seated in the burner assembly.
4. Align the orifices in the manifold assembly with the support
rings on the end of the burner.
5. Insert the orifices in the support rings of the burners.
NOTE: If manifold does not fit flush against the burner, do not
force the manifold on the burner assembly. The burners are not
fully seated forward in the burner assembly. Remove the manifold
and check burner positioning in the burner assembly assembly
before re-installing the manifold.
6. Attach the green/yellow wire and ground terminal to one of
the manifold mounting screws.
7. Install the remaining manifold mounting screws.
8. Check the igniter alignment. See Fig. 55, 56 and 61.
9. Attach the wires to the roll-out switches.
10. Align the burner assembly with the openings in the primary
cell inlet panel and attach the burner assembly to the cell
panel.
11. Connect the wire for the flame sensor.
12. Connect the wire for the Hot Surface Igniter.
NOTE: Use propane-resistant pipe dope to prevent leaks. Do not
use Teflon tape.
13. Install the gas pipe to the gas valve.
70
Page 71
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of
life.
14. Check for gas leaks with a commercially available soap
15. Turn gas on at electric switch on gas valve and at external
16. Turn power on at external disconnect, fuse or circuit break-
17. Run the furnace through two complete heating cycles to
18. Install control door when complete.
Servicing Hot Surface Igniter
The igniter does NOT require annual inspection. Check igniter
resistance before removal. Refer to Fig. 55, 56 and 61.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect igniter wire connection.
4. Check igniter resistance. Igniter resistance is affected by
5. Remove igniter assembly.
6. To replace igniter and bracket assembly, reverse items 5a
7. Reconnect igniter harness to the igniter, dressing the igniter
8. Turn on gas and electrical supplies to furnace.
9. Verify igniter operation by initiating control board self--test
10. Replace control door.
Flushing Collector Box and Drainage System
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and
install lockout tag before performing any maintenance or
service. Follow the operating instructions on the label
attached to the furnace.
!
solution made specifically for the detection of leaks.
shut-off or meter
er.
check for proper operation
temperature. Only check resistance when the igniter is at
room temperature.
a. Using an ohm meter, check resistance across both igniter
leads in connector.
b. Cold reading should be between 40 ohms and 70 ohms.
Resistance reading will increase as igniter temperature
increases.
a. Using a 1/4--in. driver, removethe two screws securing the
igniter mounting bracket to the burner assembly (See Fig.
61 .)
b. Carefully withdraw the igniter and bracket assembly
through the frontof the burner assembly without striking
the igniter on surrounding parts.
c. Inspect igniter for signs of damage or failure.
d. If replacement is required, remove the screw that secures
the igniter on igniter bracket and remove the igniter.
through 5d.
wires to ensure there is no tension on the igniter itself. (See
Fig. 61.)
feature or by cycling thermostat.
!
WARNING
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect pressure switch tube from pressure switch port.
NOTE: Ensure the pressure switch tube disconnected from the
pressure switch is higher than the collector box opening or water
will flow out of tube.
4. Remove the collector box plug from the top port on the upper corner of the collector box. (See Fig. 57)
5. Attach a funnel with a flexible tube to port on the collector
box.
6. Flush inside of collector box with water until discharge
water from condensate trap is clean and runs freely.
7. Repeat steps 4 thru 6 with middle plug on upper corner of
collector box.
8. Remove the pressure switch tube from the collector box.
NOTE:DoNOT blow into tube with tube connected to the
pressure switch.
9. Clean pressure switch port on collect box with a small wire.
Shake any water out of pressure switch tube.
10. Reconnect tube to pressure switch and pressure switch port.
11. Remove the relief tube from the port on the collector box
and the trap.
12. Clean the relief port on collect box and the trap with a small
wire. Shake any water out of the tube.
13. Reconnect relief tube to trap and collector box ports.
Cleaning Condensate Drain and Trap
NOTE: If the condensate trap is removed, a new gasket between
the trap and collector box is required. Verify a condensate trap
gasket is included in the service kit or obtain one from your local
distributor.
1. Disconnect power at external disconnect, fuse or circuit
breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect external drain from condensate drain elbow or
drain extension pipe inside the furnace and set aside.
6. Disconnect the condensate trap relief hose from collector
box port and condensate trap.
NOTE: If condensate has a heat pad attached to the trap, trace the
wires for the pad back to the connection point and disconnect the
wires for the heat pad.
7. Remove the screw that secures the condensate trap to the
collector box, remove the trap and set aside.
8. Remove the trap gasket from the collector box if it did not
come off when the trap was removed.
9. Discard the old trap gasket.
10. Rinse condensate trap in warm water until trap is clean.
11. Flush condensate drain lines with warm water. Remember
to check and clean the relief port on the collector box.
12. Shake trap dry.
13. Clean port on collector box with a small wire.
To re-install Condensate Drain and Trap:
1. Remove adhesive backing from condensate trap gasket
2. Install gasket on collector box
3. Align the condensate trap with the drain opening on the collector box and secure the trap with the screw
4. Attach the relief hose to the relief port on the condensate
trap and collector box.
5. Secure tubing to prevent any sags or traps in the tubing.
6. Connect condensate drain elbow or drain extension elbow
to the condensate trap
7. Connect the leads of the condensate heat pad (if used)
8. Connect external drain piping to the condensate drain elbow
or drain extension pipe.
9. Turn gas on at electric switch on gas valve and at external
shut-off or meter
987MA
71
Page 72
10. Turn power on at external disconnect, fuse or circuit breaker.
11. Run the furnace through two complete heating cycles to
check for proper operation
12. Install control door when complete.
Checking Heat Pad Operation (If Applicable)
In applications where the ambient temperature around the furnace
is 32_F or lower, freeze protection measures are required. If this
application is where heat tape has been applied, check to ensure it
will operate when low temperatures are present.
NOTE: The Heat Pad, when used, should be wrapped around the
condensate drain trap. There is no need to use heat tape within the
furnace casing. Most heat tapes are temperature activated, and it is
not practical to verify the actual heating of the tape. Check the
following:
1. Check for signs of physical damage to heat tape such as
nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or
987MA
discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
Cleaning Heat Exchangers
The following items must be performed by a qualified service
technician.
Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build--up of soot and carbon indicates
that a problem exists which needs to be corrected, such as improper
adjustment of manifold pressure, insufficient or poor quality
combustion air, improper vent termination, incorrect size or
damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.
1. Turn off gas and electrical supplies to furnace.
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death, or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
install a lockout tag.There may be more than one
disconnect switch. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
3. Disconnect wires or connectors to flame rollout switch, gas
valve, igniter, and flame sensor.
4. Using backup wrench, disconnect gas supply pipe from furnace gas control valve.
5. Remove two screws attaching top filler plate and rotate upwards to gain access to screws attaching burner assembly to
cell panel.
6. Remove screws attaching burner assembly to cell panel.
(See Fig. 61.)
NOTE: Burner cover, manifold, gas valve, and burner assembly
should be removed as one assembly.
7. Clean heat exchanger openings with a vacuum and a soft
brush. (See Fig. 58.)
NOTE: After cleaning, inspect the heat exchangers to ensure they
are free of all foreign objects that may restrict flow of combustion
products.
8. Reverse items 6 through 1 for reassembly.
9. Refer to furnace wiring diagram and reconnect wires to
flame rollout switch, gas valve, igniter, and flame sensor.
10. Turn on gas and electrical supplies to furnace.
11. Check furnace operation through 2 complete heat operating
cycles. Look at burners. Burner flames should be clear blue,
almost transparent. (See Fig. 59.)
12. Check for gas leaks.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of
life.
13. Replace main furnace door.
Secondary Heat Exchangers
The condensing side (inside) of the secondary heat exchanger
CANNOT be serviced or inspected without complete removal of
the heat exchanger assembly. Detailed information on heat
exchanger removal can be obtained from your Distributor.
Wiring Diagrams
See Fig. 63 for the Deluxe 4--Way Multipoise Furnace wiring
diagrams.
!
WINTERIZATION
!
CAUTION
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and
install lockout tag before performing any maintenance or
service. Follow the operating instructions on the label
attached to the furnace.
2. Remove control door.
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in unit component or
property damage.
If the furnace is installed in an unconditioned space where the
ambient temperatures may be 32_ F(0_ C) or lower, freeze
protection measures must be taken to prevent property or
product damage.
Since the furnace uses a condensing heat exchanger, some water
will accumulate in the unit as a result of the heat transfer process.
Therefore, once it has been operated, it cannot be turned off and
left off for an extended period of time when temperatures will
reach 32_F(0_C) or lower unless winterized. Follow these
procedures to winterize your furnace:
72
Page 73
!
CAUTION
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
furnace and other property damage.
Do not use ethylene glycol (automotive antifreeze coolant or
equivalent). Failure of plastic components may occur.
1. Obtain propylene glycol (RV/swimming pool antifreeze or
equivalent).
2. Turn off gas and electrical supplies to your furnace.
3. Remove furnace control door.
4. Remove the top unused rubber plug from the port on the
collector box opposite the condensate trap. See Fig. 57.
5. Connect a field supplied 3/8--in. (9.5--mm) ID tube to the
open port on the collector box
6. Insert a field supplied funnel into the tube.
7. Pour 1 quart of anti--freeze solution into the funnel/tube.
Antifreeze should run through the inducer housing, overfill
condensate trap and flow to an open drain.
8. Replace the rubber plug in the port on the collector box.
9. Remove the middle unused rubber plug from the port on the
collector box opposite the condensate trap. See Fig. 57
10. Repeat Steps 5 through 8.
11. If a condensate pump is used, check with pump
manufacturer to verify pump is safe for use with antifreeze
used. Allow pump to start and pump anti--freeze to open
drain.
12. Replace main door.
13. When furnace is re--started, flush condensate pump with
clear water to check for proper operation before re--starting
furnace.
14. Propylene glycol need not be removed before re--starting
furnace.
Fig. 57 -- Priming Condensate Trap
(Appearance May Vary)
A11392
987MA
1-1/4-in.
(31.8)
2-1/2-in.
(64.4)
Fig. 55 -- Igniter Position -- Top View
2-in.
3/8-in.
Fig. 56 -- Igniter Position -- Side View
3/16-in.
(2.5 mm +/- .75 mm)
A11405
.
A11272
A11273
Fig. 58 -- Cleaning Heat Exchanger Cell
Burner Flame
Burner
Manifold
A11461
Fig. 59 -- Burner Flame
73
Page 74
987MA
A11347
Fig. 60 -- Blower Assembly
74
Page 75
BURNER SUPT. ASSY
BURNER ASSY
IGNITER
BRACKET, IGNITER
987MA
FLAME ROLLOUT
SWITCH
FLAME SENSOR
(BELOW BURNER)
Fig. 61 -- Burner Assembly
A11403
75
Page 76
NO
g
SEYSEYSEY
NO
YES
NO
987MA
Close door switch.
NO
Guide
Is door switch closed?
Troubleshootin
Is circuit breaker closed?
NO
YES
Is there 115V going to switch?
NO
Check for continuity in wire from circuit
breaker to furnace.
Close circuit breaker and go back to
START.
Is 24V present at W /W1, W2, Y1, Y/Y2 or
G thermostat terminals on the furnace
Check room thermostat or
interconnecting cable.
control?
Disconnect all the thermostat wires from
the furnace control.
Does the problem repeat when using a
jumper wire?
The thermostat is not c ompatible with the
furnace control. Either install a ballast
resistor, connect the Com24V thermostat
terminal to the thermostat, or replace the
thermostat.
YES
YES
Replace door switch.
Replace transformer.
Does the control respond to W/W1, W2,
Y1, Y/Y2, and G (24V) thermostat
signals?
Run system through a minimum-heat,
maximum-heat, or cooling cycle to check
operation. Status codes are erased after
72 hours or can be m anually erased by
putting setup switch SW1-1 in the ON
position and jumpering R, W/W1, and
Y/Y2 simultaneously until status code
#11 is flashed.
Replace furnace control.
ONON
YES
Is the re 115 V at L1 and L2?
ONON
Is there 24V at SEC-1 and SEC-2?
YES
Replace furnace control.
Check for correct line volt age polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
YES
NO
To recall previous status codes disconnect the R
NO
thermostat connection, reset power, an d put setup
switch SW1-1 in the ON position. The AMBER LED
will flash the status codes in the order of occ urrence.
Record status codes until status code #11 flashes (1
short and 1 long flash). After status code #11
flashes the status codes will repeat. Status codes
are erased after 72 hours or can be manually erased
by putting setup switch SW1-1 in the ON position
and jumpering R, W/W1, and Y/Y2 simultaneously
until status code #11 is flashed. When done put
setup switch SW1-1 in the O FF position.
Was there a previous status code o ther
than #11?
YES
YES
START
Is AMBER LED status light on?
Is AMBER LED status light blinking
rapidly without a paus e?
Is AMBER LED status light blinking
ON/OFF slowly with a combination of
short and long flashes?
Determine status code. The status code
is a 2 digit number with the first digit
determined by the number of short
flashes and the second digit by the
number of long flashes?
Go to section below for the status code
that was flashed.
A11290A
Fig. 62 -- Troubleshooting Guide
76
Page 77
LOCKOUT Auto-reset
45 CONTROL CIRCUITRY
open.
after 1 hour lockout due
to:
- Gas valve relay stuck
- Flame ci rcuit failure.
- Soft ware check error.
Reset power to clear
lockout. Replace control
if code repeats.
Replace furnace control.
Check for continuity in the
harness and igniter. Replace
defective component.
Check that all gas valves are
Check connections. If OK,
turned on. Replace valve.
replace control.
or rough ignition.
Check for:
- Inadequate flame carryover
Allow unit to drop to min-heat,
- Low inlet gas pressure.
and check manifold pres sure.
- Proper firing rate.
Check connections and r etry.
If current is near typical value
(4.0-6.0 nominal) and burners
will not stay on, repeat check
in max-heat. If burners will
still not stay on replace
control. If burners operate in
max-heat then switch to
intermediate-heat, check
manifold pressure. If OK,
check burner carryover and
Repeat test to check for
intermittent operation.
flame sensor location.
43 LOW OR MEDIUM PRESSURE SWITCH
32 LOW PRESSURE SWITCH DID NOT
NO
YES
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
YES
YES
987MA
OPEN W HILE MEDIUM OR H IGH
CLOSE OR REOPENED – If opens during
tubing.
PRESSURE SW ITCH IS CLOS ED -
Check for:
- Low or Med press. switch stuck open.
- Disconnec ted or obstructed pressure
blower on-delay period, blower will come
on for the selected blower off-delay. If
opens within 5 minutes af ter ignition the
next heating cycle will be restricted to
maximum-heat. Check for:
pipe.
Unplug igniter harness from control and
repeat component test by turning setup
switch SW1-6 OFF and then back ON.
Check for 115V between pin 3 and
NEUTRAL-L2 on the control. Was 115V
present for the 15 second peri od?
Reconnect the R thermos tat lead and set
thermostat to call for heat. Connect
voltmeter across gas valve BLUE and
GREEN/YELLOW wires. Does gas valve
receive 24V?
Does gas valve open and allow gas to
flow?
Do the main burners ignite?
- Low inlet gas pressure (if LGPS used).
- Plugged c ondensate drain.
- W ater in vent piping, possible sagging
- Improper pressure switch wiring.
Do the main burners stay on?
Repeat call for heat and check flame
sensor current during trial for ignition
period. Is the DC microamps below 0.5?
NO
71% of maximum
compartment.
tubing.
setup switch SW1-3 ON to boost
inducer speed
- Proper v ent sizing.
- Air leak between vestibule and blower
- Low inlet gas pressure (if LGPS used).
-Restrictedvent.
- Disconnected or obstructed pressure
- Defective or miswired press ure switches
- Excessive wind. If problem persists turn
pipe.
- Plugged c ondensate drain.
- W ater in vent piping, possible saggin g
33 LIMIT CIRCUIT FAULT – Indicates the
limit or a flame rollout switch is open or the
rate. Blo wer will run for 4 min. or until
open switch remakes whichever is longer.
If open longer than 3 min., code changes
to lockout #13. If open less than 3 min.
status code #33 continues to flash until
furnace is operating in maximum-heat only
mode due to 2 successive limit trips while
operating at any rate <
blower shuts off. Flame rollout switch
gas input adjustment.
requires manual reset. Check for:
- Loose blo wer wheel.
- Defective switch or connections.
- Improper minimum- or maximum-heat
- Improper limit switch or no limit gasket.
- Dirty filter or restricted d uct system.
not sensed during the trial for ignition
period, the control will repeat the ignition
34 IGNITION PROVING FAILURE – If flame is
Clean flame sensor with fine steel wool
and recheck current. Nominal current is
4.0 to 6.0 microamps.
Is current near typical value?Replace electrode.
Will main burners ignite and stay on?Replace furnace control.
Fixed.
YES
sequence 3 more times before lockout #14
occurs. If flame signal is lost during the
blower on-delay period, blower will come on
for the selected blower off-delay. Check
the following items first before proceeding
connected to furnace s heet metal.
to the next step.
- Gas valve tu rned off.
- GREEN/YELLOW wire MUST be
- Flame sensor must not be grounded.
To determine whether the problem is in the
gas valve, igniter, or flame sensor the
system can be operated in component test
mode. To check the igniter remove the R
thermostat connection from the control,
reset power, and put setup switch SW1-6 in
the ON position to start the component test.
Does the igniter glow orange/white by the
- Manual shut-off valve.
end of the 15 second warm-up period?
erased after 72 hours or can be manuall y
erased by putting setup switch SW 1-1 in
the ON position and jumperi ng R, W/W1,
and Y/Y2 simultaneously until status code
#11 is flashed. Run system through a
minimum-heat, maximum-heat, or cooling
cycle to check system.
(115V OR 24V) – Normal operation.
Blower runs for 90 sec onds, if unit is
powered up during a c all for heat (R-
W/W1 closed) or when (R-W /W1 opens)
during the blower on- delay period.
11 NO PREV IOUS CODE – Status codes are
12 BLOWER ON AFTER POWER UP –
13 LIMIT CIRCUIT LOCKOUT – Lockout
wiring including thermostat leads.
Disconnect thermostat leads to isolate
occurs if the limit or flame rollout switch is
open longer than 3 minutes or 10
successive limit trips occurred during
maximum-heat. Control will auto-reset
after 3 hours. See code 33.
ignite gas and prove flame i n 4 attempts.
Control will auto-reset after 3 hours. See
status code 34.
the blower failed to reach 250 RPM or the
blower failed to communicate within 30
seconds after being tur ned ON in two
successive heating cycles. Control will
14 IGNITION LOCKOUT – System failed to
15 BLOWER MOTOR LOCKOUT – Indicates
power a nd wait 5 mi nutes to retry. Check
for:
- Stuck closed gas valve relay on control.
- Miswire or short to gas valve BLUE wire.
Flame is proved while gas valv e is de-
energized. Inducer will run until fault is
cleared. Check for:
- Stuck ope n or leaky gas valve.
auto-reset after 3 hours. See code 41.
21 GAS HEATING LOCKOUT – Turn off
22 ABNORMAL FLAME-PROVING SIGNAL
Check for:
- Obstructed pressure tube.
- Pressure switch stuck closed.
23 PRESSURE SW ITCH DID NOT OPEN –
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for:
- Short circuit in secondary voltage (24V)
A11290B
short circuit.
77
Page 78
NO
Youhaveanopenwireorbad
terminal on either the BLACK or
WHITE power leads between
the furnace control and the
blower motor. If you have a
power choke disconnect it and
check continuity.
Youhaveanopenwireorbad
terminal on either the RED or
GREEN wire between the
furnace control and the blower
motor.
YES
Is there 5-VDC at PL3-3
YELLOW (+) and PL3-2
GREEN (-)?
Youhaveanopenwireorbad
terminal on the YELLOW wire
between the furnace control and
the blower motor.
987MA
NO
YES
YES
YES
Turn power back on. Is there 115VAC at
PL14-5 and PL14-4?
NO
Is there 12-VDC at PL13-1 RED (+) and
PL13-4 GREEN (-)?
NO
Is there 12-VDC at P L3-1 RED (+) and
PL3-2 GREEN (-)?
YES
NO
YES
Replace the furnace control.
Is there 5-VDC at PL13-2 YELLOW (+)
and PL13-4 GREEN (-)?
The voltage just measured should be
very stable and should not fluctuate more
than .02-VDC. If the voltage fluctuates
more than this get a different voltmeter
before proceeding.
Turn power off, reconnect PL13 and
PL14 to the blower motor, then turn
power back on. Connect a DC voltmeter
across PL3-3 YELLOW (+) and PL3-2
NO
Turn power off, disconnect PL13 and
PL14 from the blower motor, then turn
power back on. Connect a DC voltmeter
across PL13-3 BLUE (+) and PL13-4
GREEN (-). The voltage should be near
0-VDC but it will fluctuate briefly several
times a second. If you have an analog
voltmeter the needle will briefly go high
several times a second. If you have a
digital voltmeter with a bar graph it will
show a large change in magnitude on the
bar graph several times a second. If you
have a standard digi tal voltmeter it will
show a brief fluctuation in voltage and the
magnitude may vary depending on the
GREEN (-). Does the voltage fluctuate
more than it did in the previous step?
voltmeter used.
YES
NO
NO
NO
YES
blower failed to reach 250 RPM or the
blower failed to communicate within the
prescribed time limits. Thirty seconds
after being turned ON or ten seconds
during steady-state operation. Turn power
off and check the following items first
before proceeding to the next step.
41 BLOWER MOTOR FAULT – Indicates the
- Rubbing blower wheel.
motor.
- Loose blower wheel.
- Wiring from furnace control to blower
Remove the R thermostat connection from
the furnace control, disconnec t both
connectors from the blower motor PL13
and PL14. Does the blower wheel turn
freely?
Replace the blower control module attached to
the blower motor. Follow the instructions with
the blower control module to make sure the
entire blower motor does not need to be
replaced.
You have an open wire or bad terminal on the
BLUE wire between the furnace control and the
blower motor.
Replace the furnace control.
Connect a DC voltmeter across PL3-4 BLUE
(+) and PL3-2 GREEN (-). Does the voltage
fluctuate as described two steps back?
Does the voltage fluctuate as described in the
previous step?
Replace the blower control module attached to
the blower motor. Follow the instructions with
the blower control module to make sure the
entire blower motor does not need to be
replaced.
YES
no valid model stored in permanent
memory. This will happen if you forget
to install the model plug PL4 on a
SETUP ERROR – If status code 25 only
flashes 4 times on power-up the control is
missing its model plug PL4 and is
defaulting to the model selection stored in
memory. If status code 25 flashes
continuously it could indicate any of the
following:
- Model plug PL4 is missing and there is
25 INVAL ID MODEL SE LECTION OR
service replacement control.
- Thermostat call with SW 1-1 ON.
- Thermostat call with SW 1-6 ON.
Need modulating board with software
-SW1-1andSW1-6bothON.
version V17 or later.
- Two different furnace models twinned.
- Service replacement control is incorrect.
PRESSURE SWITCH, OR PSR RELAY
DID NOT CLOSE OR REOPENED -
Check for:
- PSR relay may be defective.
- See status code 32.
modulating gas valve failed to respond to
a command from the furnace control or
31 MEDIUM PRESSURE SWITCH, HIGH
35 GAS VALVE FAULT – Indicates the
ORANGE wire at gas valve or PL8
connections.
inducer motor has not started within 20
seconds after a call for heat, the inducer
motor RPM is outside its valid range of
operation, or the inducer RPM signal was
lost for 5 seconds during operation.
Check for:
- Proper vent sizing.
-Failedinducermotor.
- Restricted combustion air supply.
power to the gas valve electronics was
interrupted. Check for:
- Intermittent RED, YELLOW , or
42 INDUCER MOTOR FAULT – Indicates the
- Improper motor wiring.
A11290C
78
Page 79
SEQUENCE OF OPERATION
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation.
Furnace control must be grounded for proper operation or
control will lock out.Control is grounded through
green/yellow wire routed to gas valve and burner box
screw.
Using the schematic diagram (See Fig. 63), follow the sequence of
operation through the different modes. Read and follow the wiring
diagram very carefully!!
NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/W1-and-W2), the control will start a 90-second
blower-only ON period two seconds after power is restored, if the
thermostat is still calling for gas heating. The amber LED light will
flash code 12 during the 90-second period, after which the LED
will be ON continuous, as long as no faults are detected. After the
90-second period, the furnace will respond to the thermostat
normally.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot surface igniter HSI, and gas valve GV.
Communicating Control and Modulating Heating
(Adaptive Mode)
Best comfort will be attained when a communicating wall control
is used with this product. Wiring and set--up instructions are
provided with the communicating control. See the furnace data
sheet accessory section for help in selecting the appropriate
communicating control for this furnace.
When a communicating control is used, the furnace will modulate
through its full operation range, or can be limited via the minimum
and maximum cfm configurations.
Operation of the furnace at the beginning and end of each heating
cycle will be the same as detailed below in the Single--Stage
Thermostat section EXCEPT that the communicating control will
send modulating rate command signals through the communication
bus rather than energizing the 24--v thermostat terminals. Note that
the R to W/W1 circuit signal will be controlled by the COMMR
relay on the furnace control. See the wiring diagram in Fig. 63 .
Single-Stage Thermostat and Modulating Heating
(Adaptive Mode)
See Fig. 34 and 35 for thermostat connections.
NOTE:Minimum-heat only switch SW1-2 selects the
minimum-heatonly operation mode when ON. Intermediate-heat
only switch SW4-2 selects intermediate-heat only operation
mode when ON. If both switches are ON the furnace control will
default to intermediate-heat. If either or both switches are ON, the
furnace control will operate at two-stages only as referenced in
Two Stage Thermostat section below. If both switches are OFF the
furnace control will operate in the adaptive heating mode in
response to a call for heat. (See Fig. 54.) When the W2 thermostat
terminal is energized it will always cause maximum-heat operation
as long as the R to W circuit is closed, regardless of the setting of
the minimum-heat or intermediate-heat only switches.
This furnace can operate as a modulating furnace with a
single-stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled operation, which
selects a modulated rate between minimum- and maximum-heat.
This selection is based upon the stored history of the length of
previous gas-heating periods of the single-stage thermostat.
The furnace will start up in either intermediate-, or maximum-heat.
The furnace will transition and operate at minimum-heat or the
calculated modulating rate after starting and operating for 45
seconds at intermediate-heat. The furnace control CPU defaults to
minimum-heat on the first thermostat cycle and calculates the
modulating rate that the furnace should run at for 19 minutes on
subsequent heat cycles.
If the power is interrupted, the stored modulating rate is erased and
the furnace control will select intermediate-heat for 45 seconds,
minimum-heat for 19 minutes and then switch to maximum-heat,
as long as the thermostat continues to call for heat. The furnace
control CPU then uses this information to calculate the modulating
rate the furnace will operate at on the next heating cycle. If the
calculated modulating rate is between 40% - 99% then the furnace
control CPU will operate for 45 seconds at intermediate-heat, and
then operate at the calculated modulating rate for up to 19 minutes
and then switch to maximum-heat as long as the thermostat
continues to call for heat. If the calculated modulating rate is 100%
then the furnace control will only operate at maximum-heat until
the thermostat is satisfied.
The wall thermostat ”calls for heat”, closing the R to W circuit. The
furnace control CPU performs a self-check, verifies the low,
medium, and high pressure switch contacts LPS,MPS, and HPS are
open, then de-energizes the PSR relay to close the NC contact.
1. Inducer Prepurge Period - The furnace control CPU turns
on inducer motor IDM and slowly increases the inducer
motor speed. After the low pressure switch LPS closes the
furnace control CPU continues to increase the inducer motor speed until the medium pressure switch MPS closes.
When the medium pressure switch MPS closes, inducer motor RPM is noted by the furnace control CPU, and a
25-second prepurge period begins. The RPM is used to
evaluate vent system resistance.This evaluation is then
used to determine the required RPM necessary to operate
the inducer motor during pre-purge, the first 45 seconds of
intermediate-heat, or any modulating rate that the furnace
will transition to after the blower on-delay is completed.
NOTE:The heat cycle can start in either intermediate- or
maximum-heat. If a maximum-heat cycle is initiated, the furnace
control CPU will continue to increase the inducer motor speed
after the medium pressure switch MPS closes. When the medium
pressure switch closes, inducer motor RPM is noted by the furnace
control CPU, and a 25-second prepurge period begins. The RPM
is used to evaluate vent system restriction. This evaluation is then
used to determine the required RPM necessary to operate the
inducer motor in maximum-heat pre-purge, or maximum-heat.
The high pressure switch HPS should be closed before ignition but
the furnace control ignores this input until after ignition occurs.
2. Igniter Warm-Up - At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second igniter warm-up period
3. Trial-For-Ignition Sequence - When the igniter warm-up
period is completed the main gas valve relay contact GVR
closes to energize the gas valve solenoid GV (pin 5). The
gas valve solenoid GV (pin 5) permits gas flow to the burners where it is ignited. Five seconds after the GVR closes, a
2-second Flame-Proving period begins. The HSI igniter
will remain energized until flame is sensed or until the
2-second flame proving period begins.
4. Flame-Proving - When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control
CPU begins the blower-ON delay period and continues to
hold the gas valve GV (pin 5) open. If the burner flame is
not proved within two seconds, the furnace control CPU
will close the gas valve GV (pin 5), and the furnace control
987MA
79
Page 80
987MA
CPU will repeat the ignition sequence for up to three more
Trials-For-Ignition before going to Ignition-Lockout. Lock-out will be reset automatically after three hours, or by momentarily interrupting 115 vac power to the furnace, or by
interrupting 24 vac power at SEC1 or SEC2 to the furnace
control CPU (not at W/W1, G, R, etc.).
If flame is proved when flame should not be present, the
furnace control CPU will lock out of Gas-Heating mode and
operate the inducer motor IDM at full speed until flame is
no longer proved.
5. Inducer Speed Change - If the cycle starts in intermedi-
ate-heat, the furnace control CPU reduces the inducer speed
slightly after flame sense. If cycle starts in maximum-heat,
the furnace control CPU increases the inducer speed after
flame sense.
6. Blower-On delay — If the burner flame is proven, the
blower-ON delay for intermediate-heat and maximum-heat
are as follows:
Intermediate-heat - 45 seconds after the gas valve GV (pin
5) is opened the blower motor BLWM is turned ON at the
modulating heat airflow.
Maximum-heat - 25 seconds after thegas valve GV (pin 5)
is opened the BLWM is turned ON at maximum-heat airflow.
Simultaneously, the humidifier terminal HUM and electronic air cleaner terminal EAC-1 are energized and remain
energized throughout the heating cycle.
7. Switching from Intermediate-Heat to a Low Range In-put - If the furnace control CPU switches from intermediate-heat to a low range input (low range input is an input
rate less than or equal to 51% of full rate), the furnace
control CPU will turn the blower ON or switch to the modulating heat airflow, energize the PSR relay to open the NC
contact, and slowly decrease the inducer motor speed to the
desired inducer RPM.
Switching from a Intermediate-Heat to a Medium
Range Input - If the furnace control CPU switches from
intermediate-heat to a different medium range input (medium range input is an input rate between 52% and 71% of
full rate), the furnace control CPU will turn the blower ON
or switch to the modulating heat airflow, and continue to
maintain the inducer motor speed or change it further if required.
Switching from a Intermediate-Heat to a High Range
Input - If the furnace control CPU switches from intermedi-
ate-heat to a high range input (high range input is an input
rate greater than or equal to 72% of full rate), the furnace
control CPU will turn the blower ON or switch to the modulating heat airflow, and increase the inducer motor speed to
the desired inducer motor RPM.
Switching from Low Range Input to Maximum-Heat - If
the furnace control CPU switches from a low range input
to maximum-heat, the furnace control CPU will de-energize the PSR relay to close the NC contact and slowly increase the inducer motor speed until the medium pressure
switch MPS closes. When the medium pressure switch
MPS closes the inducer motor RPM is noted by the furnace
control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor at
maximum-heat. The blower motor BLWM will transition
to maximum-heat airflow five seconds after the furnace
control CPU switches from a low range input to maximum-heat. As the inducer RPM increases, the high pressure
switch HPS should close.
Switching from Medium Range Input to Maximum-Heat - If the furnace control CPU switches from medi-
um range input to maximum-heat, the furnace control CPU
will increase the inducer motor speed to the maximum-heat
inducer motor RPM. The blower motor BLWM will transition to the maximum-heat airflow five seconds after the
furnace control CPU switches from a medium range input
to maximum-heat. As the inducer RPM increases, the high
pressure switch HPS should close.
8. Blower-Off Delay — When the thermostat is satisfied, the
R to W circuit is opened, de-energizing the gas valve GV
(pin 5), stopping gas flow to the burners, and humidifier terminal HUM. The inducer motor IDM will remain energized
fora 15-second post-purge period. The blower motor BLWM and air cleaner terminal EAC-1 will remain energized
at minimum-heat airflow or transition to minimum-heat airflow for 90, 120, 150, or 180 seconds (depending on selection at blower-OFF delay switches). The furnace control
CPU is factory-set for a 120-second blower- OFF delay.
Two--Stage Thermostat and Modulating Heating
(Adaptive Mode)
Operation of Modulating Heating (Adaptive Mode; SW1--2 and
SW4--2 are both OFF) with a two--stage thermostat is the same as
with a single--stage thermostat, EXCEPT for the following:
If the two--stage thermostat R--W2 circuit closes along with the R
to W/W1 circuit, while the furnace is operating at any capacity less
than maximum, the furnace will switch to the maximum heating
capacity. At this point, the furnace control heating algorithm is
overridden and the two--stage thermostat takes control of staging
until BOTH R to W/W1 and R to W2 circuits are opened.
The furnace with transition back to the lower heating capacity if
the two--stage thermostat opens the R--W2 circuit, but leaves R to
W/W1 circuit closed. The furnace control will continue to follow
the commands from the two--stage thermostat for W/W1 and W2,
until the R to W/W1 circuit is opened.
After the two--stage thermostat opens both the R to W/W1 and R to
W2 circuits, the adaptive algorithm will set the beginning capacity
of the next heating cycle to the same value as the heating cycle that
most recently completed.
Two-Stage Thermostat and Two-Stage Minimum/Maximum Heating
See Fig. 34 and 35 for thermostat connections.
NOTE: In this mode, the minimum-heat only switch SW1-2 must
be ON to select the minimum-heat only operation mode in
response to closing the thermostat R to W1 circuit. Closing the
thermostat Rto W1-and-W2 circuitsalways causes
maximum-heat operation, regardless of the setting of the
minimum-heat only switch.
The furnace will start up in either intermediate-, or maximum-heat.
The furnace will operate in minimum-heat after starting and
operating for 1 minute at intermediate-heat before transitioning to
minimum-heat.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
minimum-heat or closing the R to W1-and-W2 circuits for
maximum-heat. The furnace control performs a self-check, and
verifies the low, medium and high pressure switch contacts LPS,
MPS and HPS are open, then de-energizesthe PSR relay to close
the NC contact.
The start up and shut down functions and delays described above
apply to the 2-stage minimum/maximum heating mode as well,
except for switching from maximum- to minimum-heat.
1. Switching from Maximum- to Minimum-Heat —Ifthe
thermostat R to W2 circuit opens, and the R to W1 circuit
remains closed, the furnace control CPU will gradually decrease the inducer motor speed to the required intermediate-heat RPM. When the inducer motor IDM reduces pressure sufficiently, the high pressure switch HPS will open
and the gas rate will be changed to intermediate-heat. The
gas valve solenoid GV (pin 5) will remain energized aslong
as the low pressure switch LPS remains closed. When the
80
Page 81
inducer motor speed gets within 15% of the required intermediate-heat RPM the furnace control CPU will start a 5
second blower airflow change delay. After the 5 second
blower airflow change delay is completed the blower airflow will transition to minimum-heat airflow. At this point
the furnace control CPU will energize the PSR relay to open
the NC contact and slowly decrease the inducer motor
speed to the required minimum-heat RPM. When the
PSR relay is energized and the NC contact opens the furnace control CPU will reduce the gas rate to minimum-heat
RPM.
Two-Stage Thermostat and Two-Stage Intermediate/
Maximum Heating
See Fig. 34 and 35 for thermostat connections
NOTE: In this mode the intermediate-heat only switch SW4-2
must be ON to select the intermediate-heat only operation mode in
response to closing the thermostat R to W1 circuit. Closing the
thermostat Rto W1-and-W2 circuitsalways causes
maximum-heat operation, regardless of the setting of the
intermediate-heat only switch.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
intermediate-heat or closing the R to W1-and-W2 circuits for
maximum-heat. The furnace control performs a self-check, and
verifies the low, medium and high pressure switch contacts LPS,
MPS and HPS are open , then de-energizes the PSR relay to close
the NC contact.
The start up and shut down functions and delays described above
apply to the 2-stage intermediate/maximum heating mode as well,
except for switching from maximum- to intermediate-heat.
1. Switching from Maximum- to Intermediate-Heat — If
the thermostat R to W2 circuit opens, and the R to W1 circuit remains closed, the furnace control CPU will gradually
decrease the inducer motor speed to the required intermediate-heat RPM. When the inducer motor IDM reduces
pressure sufficiently, the high pressure switch HPS will
open and the gas rate will be changed to intermediate-heat.
When the inducer motor speed gets within 15% of the required intermediate-heat RPM the furnace control CPU will
start a 5 second blower airflow change delay. After the 5
second blower airflow change delay is completed the
blower airflow will transition to intermediate-heat airflow.
Cooling Mode
The thermostat “calls for cooling.”
1. Single-Speed Cooling
See Fig. 34 and 35 for thermostat connections.
The thermostat closes the R to G-and-Y circuits. The R to Y circuit
starts the outdoor unit, and the R to G-and-Y/Y2 circuits start the
furnace blower motor BLWM on cooling airflow. Cooling airflow
isbasedontheA/CselectionshowninFig.54.
The electronic air cleaner terminal EAC-1 is energized with 115
vac when the blower motor BLWM is operating. When the
thermostat is satisfied, the R to G-and-Y circuits are opened. The
outdoor unit will stop, and the furnace blower motor BLWM will
continue operating at cooling airflow for an additional 90 seconds.
Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5
seconds. (See Fig. 34.)
2. Single-Stage Thermostat and Two-Speed Cooling (Ad-
aptive Mode)
See Fig. 34 and 35 for thermostat connections.
This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled operation, which
selects low-cooling or high-cooling operation. This selection is
based upon the stored history of the length of previous cooling
period of the single-stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be
connected to enable the adaptive cooling mode in response to a call
for cooling. (See Fig. 34.) When in place the furnace control CPU
can turn on the air conditioning relay ACR to energize the Y/Y2
terminal and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either
low- or high-cooling. If starting up in low-cooling, the furnace
control CPU determines the low-cooling on-time (from 0 to 20
minutes) which is permitted before switching to high-cooling.
If the power is interrupted, the stored history is erased and the
furnace control CPU will select low-cooling for up to 20 minutes
and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high-cooling, as long
as the thermostat continues to call for cooling. Subsequent
selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G and- Y
circuits. The R to Y1 circuit starts the outdoor unit on low-cooling
speed, and the R to G-and-Y1 circuits starts the furnace blower
motor BLWM at low-cooling airflow which is the true on-board
CFselectionasshowninFig.54.
If the furnace control CPU switches from low-cooling to high
cooling, the furnace control CPU will energize the air conditioning
relay ACR. When the air conditioning relay ACR is energized the
R to Y1-and-Y2 circuits switch the outdoor unit to high-cooling
speed, and the R to G-and-Y1- and-Y/Y2 circuits transition the
furnace blower motor BLWM to high-cooling airflow.
High-cooling airflow is based on the A/C selection shown in Fig.
54.
NOTE: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the
furnace blower motor BLWM transitions to run at high-cooling
airflow.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuit are
opened. The outdoor unit stops, and the furnace blower BLWM
and electronic air cleaner terminal EAC-1 will remain energized for
an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off-delay to 5 seconds. (See Fig. 34.)
3. Two Stage Thermostat and Two-Speed Cooling
See Fig. 34 and 35 for thermostat connections.
NOTE: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 34.)
The thermostat closes the R to G-and-Y1 circuits for low cooling
or closes the R to G-and-Y1-and-Y2 circuits for high cooling. The
R to Y1 circuit starts the outdoor unit on low cooling speed, and
the R to G-and-Y1 circuit starts the furnace blower motor BLWM
at low-cooling airflow which is the true on-board CF selection as
shown in Fig. 54. The R to Y1-and-Y2 circuits start the outdoor
unit on high-cooling speed, and the R to G-and-Y/Y2 circuits start
the furnace blower motor BLWM at high-cooling airflow.
High-cooling airflow is based on the A/C selection shown in Fig.
54.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y1 or R to
G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, and
the furnace blower BLWM and electronic air cleaner terminal
EAC-1 will remain energized for an additional 90 seconds. Jumper
Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See
Fig. 54.)
4. Dehumidification Mode
See Fig. 34 and 35 for thermostat connections.
The dehumidification output, D or DHUM on the Thermostat
should be connected to the furnace control thermostat terminal
987MA
81
Page 82
DHUM. When there is a dehumidify demand, the DHUM input is
activated, which means 24 vac signal is removed from the DHUM
input terminal. In other words, the DHUM input logic is reversed.
The DHUM input is turned ON when no dehumidify demand
exists. Once 24 vac is detected by the furnace control,
dehumidification capability is activated. If the DHUM input is
removed for more than 48 hours, the furnace control reverts back
to non-dehumidification mode.
The cooling operation described above in the Cooling Mode
section also applies to Dehumidification Mode. The exceptions are
listed below:
a. Low cooling – When the R to G-and-Y1 circuit is closed
and there is a demand for dehumidification, the furnace
blowermotor BLWM willdrop theblower airflow to 86%
of low cooling airflow which is the true on-board CF
selectionasshowninFig.54.
b. High cooling– WhentheR toG-and Y/Y2circuit is closed
and there is a demand for dehumidification, the furnace
blowermotor BLWM willdrop theblower airflow to 86%
987MA
of high-cooling airflow. High-cooling airflow is based on
the A/C selection shown in Fig. 54.
c. Cooling off-delay – When the “call for cooling” is
satisfied and there is a demand for dehumidification, the
cooling blower-off delay is decreased from 90 seconds
to 5 seconds.
Super Dehumidify Mode
Super-Dehumidify mode can only be entered if the furnace control
is in the Dehumidification mode and there is a demand for
dehumidification. The cooling operation described in Cooling
Mode section above also applies to Super Dehumidify Mode. The
exceptions are listed below:
1. Low cooling –WhentheRtoY1circuitisclosed,RtoG
circuit is open, and there is a demand for dehumidification,
the furnace blower motor BLWM will drop the blower airflow to 65% of low-cooling airflow for a maximum of 10
minutes each cooling cycle or until the R to G circuit closes
or the demand for dehumidification is satisfied. Low-cooling airflow is the true on-board CF selection as shown in
Fig. 54.
2. High cooling – When the R to Y/Y2 circuit is closed, R to
G circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower
airflow to 65% of high-cooling airflow for a maximum of
10 minutes each cooling cycle or until the R to G circuit
closes or the demand for dehumidification is satisfied.
High-cooling airflow is based on the A/C selection shown
in Fig. 54.
3. Cooling off-delay – When the “call for cooling” is satisfied
and there is a demand for dehumidification, the cooling
blower-off delay is decreased from 90 seconds to 5
seconds.
Continuous Blower Mode
When the R to G circuit is closed by the thermostat, the blower
motor BLWM will operate at continuous blower airflow.
Continuous blower airflow selection is initially based on the CF
selection shown in Fig. 54. Factory default is shown in Fig. 54.
Terminal EAC-1 is energized as long as the blower motor BLWM
is energized.
During a call for heat, the furnace control CPU will transition the
blower motor BLWM to continuous blower airflow, minimum-heat
airflow, or the mid-range airflow, whichever is lowest. The blower
motor BLWM will remain ON until the main burners ignite then
shut OFF and remain OFF for the blower-ON delay (45 seconds in
intermediate heat, and 25 seconds in maximum-heat), allowing the
furnace heat exchangers to heat up more quickly, then restarts at
the end of the blower-ON delay period at modulating or
maximum-heat airflow respectively.
The blower motor BLWM will revert to continuous-blower
airflow after the heating cycle is completed. When the thermostat
satisfies, the furnace control CPU will drop the blower motor
BLWM to minimum-heat airflow during the selected blower-OFF
delay period before transitioning to continuous-blower airflow.
When the thermostat “calls for low-cooling”, the blower motor
BLWM will operate at low-cooling airflow. When the thermostat is
satisfied, the blower motor BLWM will operate an additional 90
seconds at low-cooling airflow before transitioning back to
continuous-blower airflow.
When the thermostat “calls for high-cooling”, the blower motor
BLWM will operate at high cooling airflow. When the thermostat
is satisfied, the blower motor BLWM will operate an additional 90
seconds at high-cooling airflow before transitioning back to
continuous-blower airflow.
When the R to G circuit is opened, the blower motor BLWM will
continue operating for an additional 5 seconds, if no other function
requires blower motor BLWM operation.
Continuous Blower Speed Selection from Thermostat
To select different continuous-blower airflows from the room
thermostat, momentarily turn off the FAN switch or push button on
the room thermostat for 1-3 seconds after the blower motor
BLWM is operating.
The furnace control CPU will shift the continuous-blower airflow
from the factory setting to the next highest CF selection airflow as
shown in Fig. 54. Momentarily turning off the FAN switch again at
the thermostat will shift the continuous-blower airflow up one
more increment. If you repeat this procedure enough you will
eventually shift the continuous blower airflow to the lowest CF
selection as shown in Fig. 54. The selection can be changed as
many times as desired and is stored in the memory to be
automatically used following a power interruption.
Heat Pump
See Fig. 34 and 35 for thermostat connections. When installed with
a heat pump, the furnace control automatically changes the timing
sequence to avoid long blower off times during demand defrost
cycles. Whenever W/W1 is energized along with Y1 or Y/Y2, the
furnace control CPU will transition to or bring on the blower motor
BLWM at cooling airflow, minimum-heat airflow, or the mid-range
airflow, whichever is lowest. The blower motor BLWM will
remain on until the main burners ignite then shut OFF and remain
OFF for 25 seconds before coming back on at modulating heat
airflow. When the W/W1 input signal disappears, the furnace
control begins a normal inducer post-purge period while changing
the blower airflow. If Y/Y2 input is still energized the furnace
control CPU will transition the blower motor BLWM airflow to
cooling airflow. If Y/Y2 input signal disappears and the Y1 input is
still energized the furnace control CPU will transition the blower
motor BLWM to low-cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor BLWM will
remain on at minimum-heat airflow for the selected blower-OFF
delay period. At the end of the blower-OFF delay, the blower
motor BLWM will shut OFF unless G is still energized, in which
case the blower motor BLWM will operate at continuous blower
airflow.
Component Self Test
Refer to page 68 for instructions.
82
Page 83
987MA
338307-2 Rev. C
A11429
Fig. 63 -- Wiring Diagram
83
Page 84
Casing Group
Blower door
Bottom plate
Control door
Door knob assembly
Top filler plate
Electrical Group
3--Amp fuse
Circuit board
Control box
Door switch
Junction box
Limit switch(es)
Transformer
987MA
Blower Group
Blower housing
Blower motor
Blower wheel
Capacitor (when used)
Capacitor strap (when used)
Cut--off plate
Power choke (where used)
Filter Group
Filter(s)
Media Cabinet (when used)
PARTS REPLACEMENT INFORMATION GUIDE
Gas Control Group
Burner
Flame sensor
Gas valve
Hot surface igniter
Manifold
Orifice
Condensate trap elbow
Gaskets
Inducer
Inducer assembly
Inducer motor capacitor (when used)
Inducer motor module (when used)
Pressure switch(es)
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under
“Heating Equipment” or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name or contact:
BRYANT HEATING & COOLING SYSTEMS
Consumer Relations Department
P.O. Box 4952
Syracuse, New York 13221--4952
1--800--428--4326
Have available the model number, series number, and serial number located on the unit rating plate to ensure correct replacement part.
Model Nomenclature
MODEL
987MA42060V17A-- A
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death or property damage.
Improper installation, adjustment, alteration, service, or maintenance can cause personal injury, property damage, or death. Consult a
qualified installer, service agency, or your local gas supplier for information or assistance. The qualified installer or service agency
must use only factory--authorized replacement parts, kits, or accessories when modifying this product.
COOLING
CAPACITY
HEATING
CAPACITY
!
MOTORWIDTHV OLTA GE
WARNING
FEATURES/
MINOR
SERIES
E2011 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Da te: 09/11
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
84
Catalog No. II987MA--- 0 3
Replaces: II987MA---02