986TA
EVOLUTIONR TWO--STAGE
4--WAY MULTIPOISE, VARIABLE SPEED
CONDENSING GAS FURNACE, SERIES A
Product Data
A11264
The 986TA Multipoise Variable--Speed Condensing Gas Furnace is
features the two--stage EvolutionR System. The Perfect HeatR
technology two--stage gas valve is at the heart of the comfort
provided by this furnace, along with the variable--speed ECM
blower motor, and two--speed inducer motor. With an Annual Fuel
Utilization Efficiency (AFUE) up to 96.5%, the Evolution
two--stage gas furnace provides exceptional savings as well when
compared to standard gas furnaces. This Evolution Gas Furnace
also features 4--way multipoise installation flexibility, and is
available in six model sizes. The 986TA can be vented for direct
vent/two--pipe,ventilatedcombustionair, or single--pipe
applications. A Bryant Evolution Control and Evolution Air
Conditioner or Heat Pump, can be used to form a complete
Evolution System. All units meet California Air Quality
Management District emission requirements. All sizes are design
certified in Canada.
STANDARD FEATURES
S EvolutionR System; compatible with single--zone Evolution
systems.
S Evolution Features—match with the Evolution Control for
Evolution System benefits.
S All sizes meet ENERGY STARR Version 4.0 criteria for gas
furnaces: 95+AFUE; AMACF electrical rating; 2% or less
cabinet airflow leakage.
S Quiet operation. Comparefor yourself at HVACpartners.com.
S Ideal height 35” (889 mm) cabinet: short enough for taller coils,
but still allows enough room for service.
S Silicon Nitride Perfect Light™ Hot Surface Igniter.
S SmartEvap™ technology helps control humidity levels in the
home when used with a compatible humidity control system.
S FanOn Plus™technology allows control of continuous fan speed
from a compatible thermostat.
S External Media Filter Cabinet included.
S 4--way multipoise design for upflow, downflow or horizontal
installations, with unique vent elbow and optional through-the--cabinet downflow venting capability.
S Full--featured variable--speed blower motor, two--speed inducer
motor, and two--stage gas valve.
S Self--diagnostics and extended diagnostic data through the
Advanced Product Monitor (APM) accessory or Evolution User
Interface.
S Adjustable blower speed for cooling, continuous fan, and
dehumidification.
S Aluminized--steel primary heat exchanger.
S Stainless--steel condensing secondary heat exchanger.
S Propane convertible (See Accessory list).
S Factory--configured ready for upflow applications.
S Fully--insulated casing including blower section.
S Convenient Air Purifier and Humidifier connections.
S Direct--vent/sealed combustion, single--pipe venting or
ventilated combustion air.
S Installation flexibility: sidewall or vertical vent.
S Residential installations may be eligible for consumer financing
through the Retail Credit Program.
S Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1--in. water column with all
present air inlets, air outlets, and condensate drain port(s) sealed.
LIMITED WARRANTY*
S 10 year partsand lifetime heat exchanger limited warranty to the
original purchaser upon timely registration.
S Limited warranty period is five years for parts and twenty years
for the heat exchanger if not registered within 90 daysof
installation.{
* For owner occupied, residential applications.
{Jurisdictions where warranty benefits cannot be conditioned on registra-
tion will receive registered limited warranty benefits.
CERTIFIED
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
{Capacity in accordance with DOE test procedures. Ratings are position dependent. See rating plate.
‡Minimum heat CFM when low ---heat rise adjustment switch (SW 1 ---3) and comfort/efficiency adju stment switch (SW1 - -- 4) on control center are OFF.
Perfect HeatR Technology — This feature with Adaptive Control
is a proprietary function that promotes homeowner comfort
through two stages of heating. This Bryant furnace offers a
986TA
patented algorithm that continually monitors and adjusts furnace
operation by looking at both current and past conditions to
determine the most effective stage of heating and the amount of
time to run each stage, every cycle.
Perfect HumidityR Technology — The Perfect Humidity system
actively controls both temperature and humidity in the home to
provide the best comfort all year long. Other systems depend on
heating or cooling demand to manage the moisture in the air. But,
Perfect Humidity gives the homeowner the right amount of
humidity day and night, even in mild weather. No other
manufacturer can do this! Perfect Humidity saves energy, too. By
keeping humidity under control, the homeowner can set their
thermostat lower to stay comfortable and save energy.
SmartEvapt Technology — When paired with a compatible
thermostat, this dehumidification feature overrides the cooling
blower off-delay when there is a call for dehumidification. By
deactivating the blower off-delay, SmartEvap technology prevents
condensate that remains on the coil after a dehumidification cycle
from re-humidifying throughout the home. This results in reduced
humidity and a more comfortable indoor environment for the
homeowner.
Unlike competitive systems, SmartEvap technology only overrides
the cooling blower off delay when humidity control is needed.
Once humidity is back in control, SmartEvap re-enables the
energy-saving cooling blower off-delay.
FanOnPlust Technology — Sometimes the constant fan setting
on a standard furnace system can actually reduce homeowner
comfort by providing too much or too little air! Fan On Plus
technology improves comfort all year long by allowing the
homeowner to select the continuous fan speed of their choice using
a compatible thermostat.
HYBRID HEATR Dual Fuel system — This system can provide
more control over your monthly energy bills by automatically
selecting the most economical method of heating. With HYBRID
HEAT, our system automatically switches between the gas furnace
and the electric heat pump as outside temperatures change to
maintain greater efficiency and comfort than with any traditional
single-source heating system. The heat pump also delivers
high-efficiency cooling in the summer.
Power Heatt Igniter — Bryant’s unique SiN igniter is not only
physically robust but it is also electrically robust. It is capable of
running at line voltage and does not require complex voltage
regulators as do other brands. This unique feature further enhances
the gas furnace reliability and continues Bryant’s tradition of
technology leadership and innovation in providing a reliable and
durable product.
(Electronically Commutated Motor) provides variable-speed
operation to optimize comfort levels in the home year round;
features such as passive/active dehumidification, ramping profiles,
and quiet operation. They can provide cooling match
enhancements to increase the effective SEER of select Bryant air
conditioner or heat pump system. This motor does not report back
RPM and static pressure to enable static pressure reporting to the
UI or zoning system, which is required for zoning, active filter
monitoring and system static pressure reporting.
Reliable Heat Exchanger Design — The aluminized steel,
clamshell primary heat exchanger was reengineered to achieve
greater efficiency out of a smaller size. The first two passes of the
heat exchanger are based on the current 80% product, a design
with more than ten years of field-proven performance and success.
These innovations, paired with the continuation of a crimped,
no-weld seam create an efficient, robust design for this essential
component.
The condensing heat exchanger, a stainless steel fin and tube
design, is positioned in the furnace to extract additional heat.
Stainless steel coupling box componentry between heat exchangers
has exceptional corrosion resistance in both natural gas and
propane applications.
Media Filter Cabinet — Enhanced indoor air quality in the home
is made easier with our media filter cabinet—a standard accessory
on all deluxe furnaces. When installed as a part of the system, this
cabinet allows for easy and convenient addition of a Bryant high
efficiency air filter.
4-Way Multipoise Design — One model for all applications –
there is no need to stock special downflow or horizontal models
when one unit will do it all. The new heat exchanger design allows
these units to achieve the certified AFUE in all positions.
Direct or Single-pipe Venting, or Optional Ventilated
Combustion Air
— This furnace can be installed as a 2-pipe
(Direct Vent) furnace, in an optional ventilated combustion air
application, or in single-pipe, non-direct vent applications. This
provides added flexibility to meet diverse installation needs.
Sealed Combustion System — This furnace brings in combustion
air from outside the furnace, which results in especially quiet
operation. By sealing the entire combustion vestibule, the entire
furnace can be made quieter, not just the burners.
Insulated Casing — Foil-faced insulation in heat exchanger
section of the casing minimizes heat loss. The acoustical insulation
in the blower compartment reduces air and motor noise for quiet
operation.
Monoport Burners — The burners are specially designed and
finely tuned for smooth, quiet combustion and economical
operation.
Bottom Closure — Factory--installed for side return; easily
removable for bottom return. The multi-use bottom closure can
also serve for roll-out protection in horizontal applications, and act
as the bottom closure for the optional return air base accessory.
APPROX.
SHIP WT.
(LB)
2
Page 3
Certifications — This furnace is CSA (AGA and CGA) design
certified for use with natural and propane gases. The furnace is
factory--shipped for use with natural gas. A CSA listed gas
gas. The efficiency is GAMA efficiency rating certified. This
furnace meets California Air Quality Management District
emission requirements.
conversion kit is required to convert furnace for use with propane
SPECIFICATIONS
Heating Capacity and Efficiency300404206048080600806010066120
Direct-Drive Motor TypeElectronically Communicated Motor (ECM)
Direct-Drive Motor HP1/23/43/4111
Motor Full Load Amps6.88.48.410.910.910.9
RPM Range600 - 1200
Speed SelectionsVariable (PWM)
Blower Wheel Dia x Widthin.11 x 711 x 811 x 811 x 1011 x 1011 x 11
Air Filtration System
Filter Used for Certified Watt Data
High Heat
Low Heat
Heating0.100.120.150.150.200.20
Cooling0.50.50.50.50.50.5
Low Heat6608601160120014351675
Cooling90514751610200520052115
CFM/ton23.54555
CFM/ton2.544.55.55.56
40 - 70
(22 - 39)
30 - 60
(17 - 33)
KGAWF1606UFR
40 - 70
(22 - 39)
30 - 60
(17 - 33)
KGAWF1306UFRKGAWF1406UFR
40 - 70
(22 - 39)
30 - 60
(17 - 33)
Factory Supplied Media Cabinet
Field Supplied Filter
40 - 70
(22 - 39)
30 - 60
(17 - 33)
40 - 70
(22 - 39)
30 - 60
(17 - 33)
40 - 70
(22 - 39)
30 - 60
(17 - 33)
KGAWF1506UFR
986TA
Electrical Data300404206048080600806010066120
Input VoltageVolts-Hertz-Phase115-60-1
Operating Voltage RangeMin-Max104 - 127
Maximum Input AmpsAmps7.59.29.211.711.811.8
Unit AmpacityAmps10.312.412.415.515.615.6
Minimum Wire SizeAWG141414121212
Maximum Wire Length
@ Minimum Wire Size
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommended)
Transformer Capacity (24vac output)40 VA
External Control Power
Available
Controls300404206048080600806010066120
Gas Connection Size1/2" - NPT
Burners (Monoport)234456
Gas Valve (Redundant)ManufacturerWhite Rogers
Minimum Inlet Gas pressure (in. wc)4.5
Maximum Inlet Gas pressure (in. wc)13.6
Gas Conversion Kit - Natural to PropaneKGANP5201VSP
Gas Conversion Kit - Propane to NaturalKGAPN4401VSP
Manufactured (Mobile) Home Kitnot approved for MH use
Ignition DeviceSilicon Nitride
Limit Control165180170200180160
Heating Blower Control (Heating Off-Delay)Adjustable: 90, 120, 150, 180 seconds
Cooling Blower Control (Time Delay Relay)90 seconds
Communication SystemEvolution (non-zoning)
Thermostat ConnectionsR, W/W1, W2 Y/Y2, Y1, G, Com 24V, DHUM
Accessory ConnectionsEAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)
1. Nominal 350 CFM/ton cooling airflow is deliver ed with SW1-5 and SW4-3 set to OFF.
Set both SW1-5 and SW4-3 to ON for +7% airflow (nominal 370 CFM/ton).
Set SW1-5 to ON and SW4-3 to OFF for +15% airflow (nominal 400 CFM/ton).
Set SW4-3 to ON and SW1-5 to OFF for -7% airflow (nominal 325 CFM/ton).
The above adjustments in airflow are subject to motor horsepower range/capacity.
2. Maximum cooling airflow is achieved when switches SW2-1, SW2-2, S W2-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
3. All heating CFM's are when low heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) are both set to OFF.
4. Ductwork must be sized for high-heating CFM within the operational range of E.S.P. Operation within the blank areas of the chart is not recommended
because high-heat operation will be above 1.0 E.S.P.
5. All airflows of 1800 CFM or less on 21” and 24.5” casing size furnaces are 5% less on side return only installations.
6. Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return. A minimum filter size of 20” x 25” is required.
7. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
8. Airflow not stable at this E.S.P.
High Heat Airflow
Low Heat Airflow
2
3
3
note 8237523002205211520101890175016451550
note 8237523002205211520101890175016451550
1735167516251560150014551395134512851225
7
Page 8
NOTE: Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations. Use Table 2 - Deductions from
Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 1 – Maximum Equivalent Vent Length -- Ft. (M)
0 to 4500 Ft. (0 to 1370 M) Altitude
DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE)
Vent Pipe Diameter (in.)
3
4
4
4
4
1-1/222-1/234
50(15.2)210(64.0)250(76.2)NA
NANA10(3.0)90(27.4)210(64.0)
NANANA80(24.4)185(56.4)
NANANA79(24.1)158(48.2)
NANANA69(21.0)146(44.5)
1
2
NA
Long
ELBOW CONFIGURATIONSVENT TERMINAL CONFIGURATIONS
Concentric
Medium
Mitered
Standard
A11580
8
Page 9
MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M) (CONTINUED)
Table 2 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)
Pipe Diameter (in):1-1/222-1/234
Mitered 90º Elbow8(2.4)8(2.4)8(2.4)8(2.4)8(2.4)
Medium Radius 90º Elbow5(1.5)5(1.5)5(1.5)5(1.5)5(1.5)
Long Radius 90º Elbow3(0.9)3(0.9)3(0.9)3(0.9)3(0.9)
Mitered 45º Elbow4(1.2)4(1.2)4(1.2)4(1.2)4(1.2)
Medium Radius 45º Elbow2.5(0.8)2.5(0.8)2.5(0.8)2.5(0.8)2.5(0.8)
Long Radius 45º Elbow1.5(0.5)1.5(0.5)1.5(0.5)1.5(0.5)1.5(0.5)
Tee16(4.9)16(4.9)16(4.9)16(4.9)16(4.9)
Concentric Vent TerminationNA0(0.0)NA0(0.0)NA
Standard Vent Termination0(0.0)0(0.0)0(0.0)0(0.0)0(0.0)
Venting System Length Calculations
The maximum length for each vent pipe (inlet or exhaust) equals the Maximum Equivalent Vent Length (MEVL) from Table 1 or Table 3
minus the number of elbows multiplied by the deduction for each elbow in Table 2.
Standard vent terminations and concentric vent terminations count for zero deductions.
See Vent Manufacturers’ data for equivalent lengths of flexible vent piping.
DO NOT ASSUME that one foot of flexible vent pipe is equivalent to one foot of standard PVC vent pipe.
Example
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) with 2--in.(51 mm) vent piping. Venting system includes, FOR EACH
PIPE, (3) 90_ long radius elbows, (2) 45_ long radius elbows and a concentric vent kit.
Maximum Equivalent Vent Length=127 ft.(From Table 1)
Deduct (3) 90 long radius3x3 ft.=- 9 ft.(From Table 2)
Deduct (2) 45 long radius2x1.5 ft.=- 3 ft.(From Table 2)
No deduction for Concentric Vent Kit0 ft.=- 0 ft.(From Table 2)
Maximum Vent Length=115 ft.For EACH vent or inlet pipe
986TA
9
Page 10
MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M) (CONTINUED)
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 2 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 3 – Maximum Equivalent Vent Length -- Ft. (M)
1. Use only the vent pipe sizes shown for each furnace. It is NOT necessary to choose the smallest diameter pipe possible for venting.
2. NA --- Not allowed. Pressure switch will not cl ose, or flame disturbance may result.
3. Total equivalent vent lengths un der 10’ for 40,000 BTUH furn a ces from 0 to 2000 ft. (0 to 610 M) above sea level require use of an outlet choke plate .
Failure to use an outlet choke when required may result in flame disturbance or flame sense lockout.
4. Not all furnace families include 140,000 BTUH input models.
5. Vent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by local authorities having jurisdiction.
6. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
7. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.
8. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
9. The minimum pipe length is 5 ft. (1.5 M) lin ear feet (meters) for all applications.
10. Use 3 ---in. (76 mm) diameter vent termination kit for installation s requiring 4 --- in. (102 mm) diameter pipe.
* Not all families have these models.
* Pipe length (f t) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe
length calculated from Table 1 or 3.
† Insulation thickness based on R value of 3.5 per in.
This furnace is designed for continuous return--air minimum temperature of 60_F(15_C) db or intermittent operation down to 55_F(13_C)
db such as when used with a night setback thermometer. Return--air temperature must not exceed 80_F(27_C) db. Failure to follow these
return air limits may affect reliability of heat exchangers, motors and controls.
80/ 27˚C
SUPPLY AIR
60
/ 16˚C
986TA
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
POSITIONCLEARANCE
Rear0(0mm)
Front (Combustion air openings in furnace and in structure)1in.(25mm)
Required for service*24 in. (610 mm)
All Sides of Supply Plenum1in.(25mm)
Sides0(0mm)
Ve n t0(0mm)
* Recommended
Top of Furnace1in. (25mm)
A10490
COMBUSTION--AIR PIPE FOR NON--DIRECT (1--PIPE) VENT APPLICATION
*The plenum should be constructed 1/4--- in. (6 mm) smaller in width and depth than the plenum dimensions shown above.
FURNACE IN DOWNFLOW
APPLICATION
Furnace with or without Cased Coil
Assembly or Coil Box
Furnace with or without Cased Coil
Assembly or Coil Box
Furnace with or without Cased Coil
Assembly or Coil Box
PLENUM OPENING*FLOOR OPENING
ABCD
15--- 1/8
(384.2)
18--- 5/8
(396.4)
22--- 1/8
(562.0)
19 (482.6)
19 (482.6)
19 (482.6)
16--- 3/4
(425.5)
20--- 1/4
(514.4)
23--- 3/4
(603.3)
Disassembled
20--- 3/8
(517.5)
20--- 3/8
(517.5)
20--- 3/8
(517.5)
1
2
3
4
A88207
HOLE NO. FOR
WIDTH
ADJUSTMENT
3
2
1
986TA
Concentric Vent Kit
A concentric vent kit allows vent and combustion--air pipes to
terminate through a single exit in a roof or side wall. One pipe
runs inside the other allowing venting through the inner pipe and
combustion air to be drawn in through the outer pipe.
A93086
Downflow Subbase
A88202
One base fits all furnace sizes. The base is designed to be installed
between the furnace and a combustible floor when no coil box is
used or when a coil box other than a Bryant cased coil is used. It is
CSA design certified for use with Bryant branded furnaces when
installed in downflow applications.
13
Page 14
23-5/8"
(600mm)
23-3/8”
(594mm)
MEDIA FILTER CABINET
A
25-5/8"
(651mm)
24-1/4”
(616mm)
Opening with Flanges Bent
23-1/8”
(588mm)
Opening
B Opening
986TA
Furnace Side
Duct Side
23-3/4”
(603mm)
Centerline Screw Slots
3
"
5
4
(146mm)
Media Filter
Cabinet
16" (406mm)
20" (508mm)
24" (610mm)
A
17" (432mm)
21" (533mm)
25" (635mm)
B
16" (406mm)
20" (508mm)
24" (610mm)
A11456
TYPICAL WIRING SCHEMATIC
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
FIVE WIRE
THREE-WIRE
HEATING-ONLY
BLOWER DOOR SWITCH
BLK
WHT
115-V FIELD-
SUPPLIED
BLK
WHT
GND
AUXILIARY
J-BOX
DISCONNECT
GND
FURNACE
NOTE 2
W
C
R
O
N
T
G
R
O
COM
L
Y
24-V
TERMINAL
BLOCK
WCRGY
NOTE 1
NOTES:Connect Y-terminal in furnace as shown for proper blower operation.
1.
Some thermostats require a "C" terminal connection as shown.
2.
If any of the original wire, as supplied, must be replaced, use
3.
same type or equivalent wire.
THERMOSTAT
TERMINALS
CONDENSING
UNIT
TWO
WIRE
FIELD-SUPPLIED
DISCONNECT
GND
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
A11387
14
Page 15
DIMENSIONAL DRAWING
986TA
A11608
15
Page 16
GUIDE SPECIFICATIONS
General
System Description
Furnish a ______________________ 4--way multipoise gas--fired
condensing furnace for use with natural gas or propane (factory-authorized conversion kit required for propane); furnish cold air
return plenum; furnish external media cabinet for use with
accessory media filter or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit
will carry the CSA Blue StarR and Blue FlameRlabels. Unit
efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
986TA
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed ball bearings, of _______hp,
and have infinitely variable speed from 600--1200 RPM operating
only when motor inputs are provided. Blower motor shall be direct
drive and soft mounted to the blower scroll to reduce vibration
transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media
Filter is available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted
galvanized steel.
Draft Inducer
Draft inducer motor shall be two--speed design.
Motor
Primary Heat
Primary heat exchangers shall be 3--Pass corrosion-- resistant
aluminized steel of fold--and--crimp sectional design and applied
operating under negative pressure.
Secondary Heat
Secondary heat exchangers shall be of a stainless steel
flow--through of fin--and--tube design and applied operating under
negative pressure.
Controls
Controls shall include a micro--processor--based integrated
electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control, a
self--test feature that checks all major functions of the furnace, and
a replaceable automotive--type circuit protection fuse. Multiple
operational settings available, including separate blower speeds for
low heat, high heat, low cooling, high cooling and continuous fan.
Continuous fan speed may be adjusted from the thermostat.
Cooling airflow will be selectable between 325 and 400 CFM per
ton of air conditioning. Features will also include temporary
reducedairflowinthecoolingmodeforimproved
dehumidification when an Evolution Control or T6--PRH is
selected as the thermostat.
__________in. (mm); height___________in. (mm) (casing only).
Height shall be _________in. (mm) with A/C coil and
_________________in. (mm) overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be ________AWG; maximum fuse size
of HACR--type designated circuit breaker shall be _________
amps.
Special Features
Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.
E2012 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 01/12
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
16
Catalog No. PDS986TA--- 0 3
Replaces: PDS986TA--- 02