704C
EVOLUTIONt 13 SEER SINGLE--PACKAGED AIR CONDITIONER
SYSTEM WITH PURON®(R--410A) REFRIGERANT
2 TO 5 NOMINAL TONS (024--060)
Product Data
room to room; and reduced indoor noise due to lower air velocity.
In addition, you’ll realize improved installation flexibility with 3
different airflow choices for best overall comfort.
Easy installation
Factory--assembled package is a compact, fully self--contained,
electric cooling unit that is pre--wired, pre--piped, and
pre--charged for minimum installation expense. 704C units are
available in a variety of standard capacity ranges with voltage
options to meet residential and light commercial requirements.
Units install easily on a rooftop or at ground level.
Durable, dependable components
Compressors are designed for high efficiency. Each compressor
is hermetically sealed against contamination to help promote
longer life and dependable operation. Vibration isolation provides
quiet operation. Compressors have internal high--pressure and
overcurrent protection.
Convertible duct configuration
Unit is designed for easy use in either downflow or horizontal
applications. Each unit is easily converted from horizontal to
A06047
Unit 704C
Single--Packaged Products with Energy--Saving Features and
®
refrigerant.
Puron
S
13 SEER
S
Low Sound Levels
S
Variable--Speed Blower (Standard)
S
Factory--Installed TXV
FEATURES/BENEFITS
One--piece cooling unit with optional electric heater, low
installation cost, dependable performance and easy maintenance.
Efficient operation
High--efficiency design with SEERs (Seasonal Energy Efficiency
Ratio) of 13.0.
®
Puron
unique refrigerant designed to help protect the environment.
Puron refrigerant is an HFC refrigerant which does not contain
chlorine that can harm the ozone layer. The most important
advantage of Puron refrigerant is that it has not been banned in
future air conditioning systems as the traditional refrigerant R--22
has been. Puron refrigerant is in service in over 100,000 systems
proving highly reliable, environmentally sound performance.
PerfectHumidityt Technology featuring Evolutiont control
and Variable--Speed Blower motor that provides greater
comfort, humidity control, and energy efficiency.
Variable--Speed Blower motors provide better comfort and
energy efficiency. You can expect up to 30 times better
dehumidification; economical constant fan which provides
improved indoor air quality and more even temperatures from
Environmentally--Sound Refrigerant is Bryant’s
downflow and includes horizontal duct covers.
Direct--drive, variable--speed blower motor is standard on all
704C models.
Direct--drive, PSC condenser fan motors are designed to help
reduce energy consumption and provide for cooling operation
downto55°Foutdoor temperature.Motormaster
low--ambient kit is available as a field --installed accessory.
Evolutiont User Interface designed to work as a system with
Bryant’s single--packaged product.
Refrigerant system is designed to provide dependability. Liquid
refrigerant filter driers are used to promote clean, unrestricted
operation. Each unit leaves the factory with a full Puron
refrigerant charge. Refrigerant service connections make checking
operating pressures easier.
Indoor and outdoor coils are computer designed for optimum
heat transfer and cooling efficiency. The indoor coil is fabricated
from copper tube and aluminum fins and is located inside the unit
for protection against damage. The outdoor coil is internally
mounted on the top tier of the unit. Copper fin coils and
pre--coated fin coils are available from the factory by special
order. These coils are recommended in applications where
aluminum fins are likely to be damaged due to corrosion. They
are ideal for seacoast applications.
Thermostatic Expansion Valve—A hard--shutoff, balance--port
TXV maintains a constant superheat at the evaporator exit
(cooling cycle) resulting in higher overall system efficiency.
High-- and Low--Pressure Switches give added safety and
reliability to the compressor.
Low sound ratings ensure a quiet indoor and outdoor
environment with sound ratings as low as 72 dB. (See page 3.)
Easy to service cabinets provide easy single--panel accessibility
to serviceable components during maintenance and installation.
The basepan, with integrated drain pan, provides easy ground
level installation with or without a mounting pad. Convenient
®
II
1
Page 2
handholds are provided to manipulate the unit on the job site. A
nesting feature ensures a positive basepan to roof curb seal when
the unit is roof mounted. A convenient 3/4--in. wide perimeter
flange makes frame mounting on a rooftop easy.
Louvered grille provides hail and vandalism protection for the
coil.
Downflow operation is easily provided in the field to allow
vertical ductwork connections. The basepan utilizes knockout
style seals on the bottom openings to ensure a positive seal in the
horizontal airflow mode.
Cabinetsareconstructedofheavy--duty,phosphated,
zinc--coated, pre--painted steel capable of withstanding 500 hrs of
salt spray. Interior surfaces of the evaporator and electric heater
compartments are insulated with cleanable semi--rigid insulation
board, which keeps the conditioned air from being affected by the
outdoor ambient temperature and provides improved indoor air
quality. (Conforms to American Society of Heating, Refrigeration
and Air Conditioning Engineers No. 62P.) The sloped drain pan
minimizes standing water in the drain, which is provided with an
external drain.
Standard metal duct covers with insulation come with the unit
and cover the horizontal duct openings. These can be left in place
if the units are converted to downflow.
Limited Warranty—Standard 5--year limited warranty on all
parts, 10--year limited warranty on compressor.
Electrical Supply
N – 208/230-1-60
P – 208/230-3-60
AA
000 BT
Options
BT - AL evap, vinyl condenser
CC - AL evap, CU condenser
CU - CU evap & condenser
TP - Base unit with tin plated indoor coil hairpins
TV - TP with vinyl coating on outdoor coil
TC - TP with AL indoor coil & CU/CU outdoor coil
Only used if ordering an option
N/A
Series
A – Original
Nominal Cooling Capacity
024 – 2.0 Tons
030 – 2.5 Tons
Brand Name
A – Common Unit
036 – 3.0 Tons
042 – 3.5 Tons
048 – 4.0 Tons
060 – 5.0 Tons
N/A
LEGEND
AL— Aluminum
CU — Copper
ARI* CAPACITIES
Cooling Capacities, Efficiencies and Sound Ratings
** ”A” conditions--- 80°F indoor db/67°F indoor wb & 95°F outdoor db.{ Rated in accordance with U.S. Government DOE (Department of Energy) test
procedures and/or ARI Standards 210/240 ---94.
} Tested in accordance with ARI Standard 270---95 (not listed in ARI).
NOTES
1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:
Cooling Standard: 80°F db, 67°Fwb indoor entering --- air temperature and 95°F db outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
LEGEND
dBA—Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
ORIFICE OD (in.)0.035 (2)0.035 (2)0.038 (2)0.038 (2)
OUTDOOR COIL
Rows…Fins/in.2…212…212…212…212…212…21
Face Area (sq. ft.)12.312.313.615.417.219.4
OUTDOOR FAN
Nominal Cfm270027002800280033003300
Diameter222222222222
Motor HP (RPM)1/8 (825)1/8 (825)1/8 (825)1/8 (825)1/4 (1100)1/4 (1100)
INDOOR COIL
Rows…Fins/in.3…153…154…153…154…154…17
Face Area (sq. ft.)3.73.73.74.74.75.7
INDOOR BLOWER
Nominal Airflow (Cfm)
704C
Size (in.)10x1010x1011x1 011x1 011x 1 011x 1 0
Motor HP (RPM)1/21/23/43/43/41
HIGH-- PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
LOSS-- OF--CHARGE SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto)
RETURN-- AIR FILTERS (IN.)*
Throwaway
*Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity
of 300 ft/minute for throwaway type or 450 f t/minute for high---capacity type. Air filter pressure drop for n on ---standard filters must not exceed 0.08 in. wg.
ISO 9001:2000
ComfortVariable based on Comfort Rollback (see User Interface instructions for more information).
Coil options include tin--plated* indoor hairpins, copper/copper
and vinyl--coated construction for refrigerant coils. Units are
shipped standard with copper tube/aluminum fin construction.
See model number nomenclature for coil options.
*Tin--plated indoor coils are built with special hairpins that are
designed to resist both general pitting corrosion and excessive
indoor corrosion (Formicary Corrosion).
Field-- installed accessories
Manual Air Damper (25% open)
Electric Heaters
Filter Rack
Flat Roof Curbs (8--in. and 14--in.)
Square--to--Round Duct Transition Kit
Evolutiont User Interface
Crankcase Heater
Low--Ambient Kit (Motormaster II Control)
Lifting Kit
Compressor Hard Start Kit
Manual outside air damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Electric heatersprovide additional heat in the unit when
required. Each package has a heater module that slides into the
controls compartment. Heater sizes range from 5.0 to 20.0 kW.
The electric heater design allows the use of a single--point power
supply for the entire unit, resulting in lower installed costs.
Flat roof curbs in both 8 in. and 14 in. sizes are available for
roof mounted applications.
Square--to--round duct transition kit enables 024-- 048 size
units to be fitted to 14 in. round ductwork.
EvolutionUserInterfacecoupled withthesystem’s
variable--speed indoor blower delivers Bryant’s patented
PerfectHumidity technology that allows for even greater humidity
control. Along with more precisely controlling temperature and
humidity, the Evolution User Interface offers full seven--day
programmability allowing you to further customize your comfort
and energy savings.
Lifting kit includes 4 metal brackets that are available to assist in
lifting this product onto a roof application.
Crankcase heaterprovides anti--floodback protection for
low--load cooling applications.
®
Low--ambient kit (Motormaster
II control) allows the use of
mechanical cooling down to outdoor temperatures as low as 0°F.
Filter rackfeatures easy installation, serviceability, and
high--filtering performance for vertical or horizontal applications.
Compressor hard start kitassists compressor start--up by
providing additional starting torque on single--phase units and
prolongs compressor motor life.
704C
Electric Heaters
ODS Catalog
Ordering No.(kW)FusedStages243036424860
CPHEATER080A003.8 / 5.0NO1XXXXXX
CPHEATER082A005.4 / 7.2NO1XXXXXX
CPHEATER084A007.5 / 10.0NO1XXXXXX
CPHEATER086A0011.3 / 15.0YES2XXXXX
CPHEATER088A0015.0 / 20.0YES2XXXX
CPHEATER090A003.8 / 5.0NO1XXXX
CPHEATER091A007.5 / 10.0NO1XXXX
CPHEATER093A0011.3 / 15.0NO2XXXX
CPHEATER095A0015.0 / 20.0YES2XXX
NOTE
Electric heaters are r ated at 240v. Refer to Multiplication Factors table for other voltages.
LEGEND
ODS—Order D istribution System
Nominal
Capacity
Used With Sizes
208/230 —SINGLE PHASE —60 Hz
208/230 -- THREE PHASE -- 60 Hz
5
Page 6
FILTER RACK
MANUAL OUTSIDE AIR DAMPER
704C
EVAPORATOR
COIL
BEND FLANGE AT 90°-SCREW TO
DIVIDER WITH 1-IN. SCREW
9. When u nit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when req uired by code for hurricaneorseismic
conditions. This bracket is available through Micrometl.
Determine cooling and heating requirements at design
conditions:
Given:
REQUIRED COOLING CAPACITY (TC)34,500 BTUH.....
SENSIBLE HEAT CAPACITY (SHC)26,000 BTUH........
REQUIRED HEATING CAPACITY (SHC)15,000 BTUH....
CONDENSER ENTERING AIR TEMPERATURE95°F.....
INDOOR-- AIR TEMPERATURE80°FEDB,67°FEWB.....
EVAPORATOR AIR QUANTITY1200 CFM..............
ELECTRICAL CHARACTERISTICS230--1--60............
Select unit based on required cooling capacity
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F. The 036 unit at 1200 cfm and 67°Fewb
(entering wet bulb) will provide a total capacity of 36,000 Btuh
and a SHC of 27,200 Btuh. Calculate SHC correction, if required,
using Note 4 under Cooling Capacities tables.
Corner Weights (Lbs.)
704C
Model
Select electric heat
The required heating capacity is 15,000 Btuh.
Determine additional electric heat capacity in kW.
Enter the Electric Heater table on page 5 for 208/230v,
single--phase unit. The 5--kW heater at 240v most closely satisfies
the heating required. To calculate kW at 230v, multiply the heater
kW by multiplication factor 0.92 found in the Multiplication
Factors table on page 14.
5 kW x 0.92 = 4.6 kW
4.6 kW x 3414 Btuh/kW = 15,704 Btuh
Total unit heating capacity is 35,904 Btuh
(20,200 + 15,704).
Select unit that corresponds to power source available
The Electrical Data table shows that the unit is designed to
operate at 208/230--1--60.
Unit042048060
15,000 Btuh
3414 Btuh/kW
= 4.4kW of heat required
A06124
10
Page 11
PERFORMANCE DATA--STANDARD ECM I NDOOR MOTOR
Cooling Extended Performance Table
704C024
Tem p ( °F)
Outdoor Air
Entering Condenser
TC23.423.925.928.424.024.526.529.1
75
85
95
105
115
125
SHC20.319.817.614.721.921.318.715.4
kW1.61.61.81.81.71.71.81.8
TC22.322.724.827.322.923.325.327.9
SHC19.919.217.014.221.420.718.114.9
kW1.81.82.02.01.91.92.02.0
TC21.321.823.526.021.822.224.026.5
SHC19.318.816.513.620.820.217.614.3
kW2.22.22.22.22.22.22.22.2
TC20.020.522.224.620.520.922.625.0
SHC18.818.115.813.120.219.516.913.7
kW2.42.42.32.32.42.42.42.4
TC18.619.120.722.919.219.521.123.3
SHC18.217.415.312.319.418.816.313.0
kW2.72.72.72.72.72.72.72.7
TC17.117.519.321.117.818.019.421.4
SHC17.817.014.511.718.518.115.512.3
kW2.82.83.03.02.92.93.03.0
700 / 0.02800 / 0.03
6263*67726263*6772
Evaporator Air --- CFM/BF
Evaporator Air Ewb (°F)
704C
704C030
Tem p ( °F)
Outdoor Air
Entering Condenser
TC27.928.630.733.628.829.431.634.5
75
85
95
105
115
125
See page 14 for cooling notes.
SHC24.120.020.616.826.021.222.117.8
kW2.12.12.12.12.12.12.12.2
TC26.927.529.532.327.628.130.233.1
SHC23.819.520.316.425.620.821.717.4
kW2.32.32.42.42.32.42.42.4
TC25.626.228.230.826.326.828.831.5
SHC23.119.119.916.024.720.521.316.9
kW2.62.62.62.62.62.62.62.6
TC24.324.726.629.225.125.327.229.7
SHC22.418.619.315.423.819.920.816.3
kW2.92.92.92.92.92.92.92.9
TC22.823.224.927.323.823.625.327.7
SHC21.718.018.814.822.319.320.215.7
kW3.23.23.23.23.23.23.23.2
TC21.421.424.927.323.823.625.327.7
SHC20.717.318.814.822.319.320.215.7
kW3.53.53.23.23.23.23.23.2
Cooling Extended Performance Table
Evaporator Air --- CFM/BF
875 / 0.061000 / 0.07
Evaporator Air Ewb (°F)
6263*67726263*6772
11
Page 12
PERFORMANCE DATA--STANDARD ECM INDOOR MOTOR (CONT)
Cooling Extended Performance Table
704C036
Evaporator Air --- CFM/BF
Evaporator Air Ewb (°F)
704C
Tem p ( °F)
Outdoor Air
Entering Condenser
TC34.835.538.442.436.436.939.843.8
75
85
95
105
115
125
SHC30.424.725.720.934.327.528.722.8
kW2.52.62.62.62.72.72.72.8
TC33.234.036.740.534.835.237.941.8
SHC29.624.125.020.233.526.828.022.1
kW2.82.92.92.93.03.03.03.0
TC31.532.334.838.533.333.436.039.7
SHC29.423.324.219.532.526.127.221.4
kW3.13.23.23.23.33.33.33.4
TC29.730.433.036.431.731.533.937.4
SHC28.822.523.518.831.125.326.520.6
kW3.53.53.53.53.63.63.73.7
TC28.128.530.834.030.029.431.734.9
SHC27.821.722.718.029.724.525.719.8
kW3.83.93.93.94.04.04.04.0
TC26.526.428.531.528.127.229.332.3
SHC26.220.921.917.127.823.524.718.9
kW4.24.34.34.34.44.44.44.4
1050/ 0.041200 / 0.05
6263*67726263*6772
704C042
Tem p ( °F)
Outdoor Air
Entering Condenser
TC40.541.244.248.441.542.145.159.4
75
85
95
105
115
125
See page 14 for cooling notes.
SHC35.429.030.024.337.930.831.925.6
kW3.03.03.03.13.03.03.03.1
TC38.739.442.346.339.740.243.247.2
SHC34.628.229.223.637.030.031.124.8
kW3.33.33.43.43.33.33.43.4
TC36.937.540.344.137.838.241.044.9
SHC33.827.428.422.835.929.130.324.0
kW3.73.73.73.83.73.73.73.8
TC34.935.438.041.636.036.038.742.3
SHC32.726.527.622.034.328.329.423.2
kW4.14.14.14.14.14.14.14.1
TC32.833.135.538.934.033.736.139.5
SHC31.425.626.621.032.827.328.522.2
kW4.54.54.54.64.54.54.54.6
TC30.630.532.735.731.731.033.236.2
SHC29.624.525.520.030.626.127.321.1
kW4.94.94.95.04.94.94.95.0
Cooling Extended Performance Table
Evaporator Air --- CFM/BF
1225/ 0.071400 / 0.08
Evaporator Air Ewb (°F)
6263*67726263*6772
12
Page 13
PERFORMANCE DATA--STANDARD ECM INDOOR MOTOR (CONT)
Cooling Extended Performance Table
704C048
Tem p ( °F)
Outdoor Air
Entering Condenser
TC44.745.349.053.946.046.650.355.3
75
85
95
105
115
125
SHC40.832.834.327.643.935.236.729.3
kW3.33.33.33.43.33.33.43.4
TC42.443.046.551.243.744.147.752.4
SHC39.631.733.226.542.434.035.728.2
kW3.73.73.73.83.73.73.73.8
TC40.040.644.048.542.341.845.049.5
SHC38.230.632.225.541.133.134.527.1
kW4.14.14.14.14.14.14.14.2
TC37.938.141.245.539.739.142.146.4
SHC36.629.430.924.438.331.833.325.8
kW4.54.54.54.64.54.54.54.6
TC36.635.538.342.337.136.239.143.0
SHC34.128.229.623.236.630.432.024.7
kW5.04.95.05.05.05.05.05.0
TC33.132.635.338.834.633.335.939.5
SHC32.427.028.421.934.128.930.623.3
kW5.55.45.55.55.55.55.55.5
1400/ 0.061600 / 0.08
6263*67726263*6772
Evaporator Air --- CFM/BF
Evaporator Air Ewb (°F)
704C
704C060
Tem p ( °F)
Outdoor Air
Entering Condenser
TC58.859.764.069.860.060.864.970.8
75
85
95
105
115
125
See page 14 for cooling notes.
SHC53.651.844.535.457.655.447.136.8
kW4.24.34.34.44.44.44.54.6
TC56.257.061.166.657.458.161.967.4
SHC52.450.543.234.256.354.245.835.6
kW4.74.74.84.94.84.95.05.0
TC53.554.358.063.255.055.358.764.1
SHC51.149.241.932.955.052.944.534.4
kW5.15.25.35.35.25.35.55.5
TC50.751.454.859.652.552.455.460.2
SHC49.847.940.631.652.551.643.233.0
kW5.75.75.85.95.85.86.06.1
TC48.148.351.356.849.749.751.857.0
SHC48.146.639.230.649.749.741.831.7
kW6.26.36.46.46.46.46.66.6
TC45.245.147.452.546.446.447.952.2
SHC45.245.137.628.946.446.440.229.7
kW6.86.97.07.07.07.07.27.2
Cooling Extended Performance Table
Evaporator Air --- CFM/BF
1750/ 0.0072000 / 0.01
Evaporator Air Ewb (°F)
6263*67726263*6772
13
Page 14
PERFORMANCE DATA (CONT)
Heater kW RatingVoltage Distribution V/3/60Multiplication Factor
*At 75°F entering dry bulb (Tennessee Valley Authority [TVA] rating conditions); all other at 80°Fenteringdrybulb.
COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator fan motor
power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
Multiplication Factors
200.69
208.75
230.92
2401.00
t
ldb =tedb
Wet--- bulb temperature corresponding to enthalpy
t
lwb =
air leaving evaporator coil (
h
lwb =he w b ---
h
ewb = Enthalpy of air entering evaporator coil
Where:
4. The SHC is based on 80° F edb temperature of air entering evaporatorcoil.
Below 80° F edb, subtract (corr factor x cfm) from SHC.
Above 80° F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 + BF) x (edb + 80) .
5. Integrated capacity is maximum (instantaneous) capacity less the effect of
frost on the outdoor coil and the heat required to defrost it.
Sensible capacity
---
(Btuh)
1.10 x cfm
h
lwb)
total capacity (Btuh)
4.5 x cfm
14
Page 15
TYPICAL PIPING AND WIRING
ROOF-MOUNTING
CURB
SUPPLY-AIR
FLEXIBLE DUCT
ROOF
RETURN-AIR
FLEXIBLE DUCT
704C
CONCENTRIC DIFFUSER BOX
(FIELD-SUPPLIED)
TOP COVER
RETURN
AIR
CEILING
FROM
GAS LINE
USER
INTERFACE
FROM
POWER
SOURCE
DISCONNECT
PER NEC
C00023
*NEC - NATIONAL ELECTRICAL CODE
A06122
15
Page 16
APPLICATION DATA
Condensatetrap — A2--in. condensatetrapmust be field supplied.
1” (25mm) MIN.
TRAP
OUTLET
2” (50mm) MIN.
Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
704C
To convert a unit to downflow discharge — Units are equipped
with factory--installed inserts in the downflow openings. Remove
the insertssimilar to removing an electricalknockout.Leaveon duct
covers to seal the horizontal discharge openings in the unit. Units
installed in horizontal discharge orientation do notrequire duct covers.
Minimum cooling ambient operating temperature —Allstandard units havea minimum ambient operatingtemperatureof 55°F.
With accessory low--ambient temperature kit, units can operate at
temperatures down to 0°F.
Maximum operating outdoor air temperature —Maximum
outdoor operating air temperature for cooling is 125°F.
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NE C
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit break er.
2. Minimum wire size is based on 60 C copper wire. I f other than
60 C wire is used, or if length exceeds wire length in table,
determine siz e from NEC..
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
704C
age is greater than 2%.
the percentage of voltage imbalance.
% Voltage imbalance
= 100 x
Heater capacity (kW) based on heater voltage of 208v & 240v.
If power distibution voltage to unit varies from rated heater
*
volta
max voltage deviation from average voltage
e, heater kW will vary accordingly.
Use the following formula to determine
average voltage
EXAMPLE: Supply voltage is 230-3-60.
®
Determine maximum deviation from average voltage.
(AB) 229 (BC) 231 -
(AC) 229 Maximum deviation is 2 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
AB = 228 v
BC = 231 v
AC = 227 v
Average Voltage =
228 =1v
229 =2v
227 =2v
= 0.8%
229
=
= 229
2
228 + 231 + 227
3
686
3
C03014
18
Page 19
TYPICAL WIRING SCHEMATIC — 230--1--60
704C
7.0
A06126
19
Page 20
TYPICAL WIRING SCHEMATIC — 230--3--60
704C
5.0
A06127
20
Page 21
CONTROLS
Sequence of Operation
The packaged air conditioner is designed for installation with a
communicating User Interface. This unit will not respond to
commands provided by a common thermostat except undercertain
emergency situations.
The User Interface uses temperature, humidity and other data
supplied from indoor and outdoor system components to control
heating or cooling system for optimum comfort. The unit will be
commanded by User Interface to supply airflow. The unit will
operate the indoor blower at requested airflow for most modes.
The nominal requested airflow will be 350 cfm per ton of nominal
cooling capacity as defined by unit size. Actual airflow request will
be adjusted from nominal using indoor and outdoor temperature
and indoor humidity data to optimize the system operation for
occupant comfort and system efficiency. Refer to User Interface
literature for further system control details.
Airflow during electric heater operation must be greater than a
minimum level for safe operation. If User Interface instructs unit to
turn on electric heat and the requested airflow is less than the
minimum level the unit control will override requested value.
NOTE: Once the compressor has started and then has stopped, it
should not be started again until 4 minutes have elapsed. The
cooling cycle remains “on” until the room temperature drops to
point that is slightly below the cooling control setting of the user
interface.
704C
21
Page 22
GUIDE SPECIFICA TIONS
SINGLE--PACKAGED ELECTRIC COOLING UNITS
CONSTANT VOLUME APPLICATION
HVAC GUIDE SPECIFICATIONS
SIZE RANGE:2 TO 5 TONS, NOMINAL COOLING
MODEL NUMBER: 704C
PART I -- GENERAL
SYSTEM DESCRIPTION
Outdoorrooftop or groundmounted electriccooling unit utilizinga hermeticcompressorfor cooling duty and optionalelectric
heating. Unit shalldischargesupply air vertically or horizontallyas shown oncontractdrawings.Outdoorfan/coilsection shall
have a draw--thru design with vertical discharge for minimum
sound levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
704C
210/240, and 270.
B. Unit shall be designed in accordance with UL Standard 1995.
C. Unit shall be manufactured in a facility registered to ISO
9001 manufacturing quality standard
D. Unit shall be UL listed and c--UL certified as a total package
for safety requirements.
E. Roof curb shall be designed to conform to NRCA Standards.
F. Insulation and adhesives shall meet NFPA 90A requirements
for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
Factory--assembled, single--piece, cooling unit. Contained
within the unit enclosure shall be all factory wiring, piping,
controls, refrigerant charge (R--410A), and special features required prior to field start--up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated,
zinc--coated, prepainted steel capable of withstanding 500
hrs of salt spray.
2. Normal service shall be through a single removable cabinet
panel.
3. The unitshallbe constructedon arust proof unitbase that has
an externally trapped, integrated sloped drain pan.
4. Indoor fan compartment top surface shall be insulated with
a minimum 1/2-- in. thick, flexible fiberglass insulation,
coated on the air side and retained by adhesive and
mechanical means. The indoor wall sections will be
insulated with afoil-- faced insulation capable of being wiped
clean. Aluminum foil--faced fiberglass insulation shall be
used in the entire indoor air cavity seciton.
5. Unit shall have a field--supplied condensate trap.
C. Fans:
1. The indoor fan shallbe variable--speed motor and control, as
shown on equipment drawings.
2. Fan wheel shall be made from steel, be double--inlet type.
Itshallhaveforward--curvedbladeswitha
corrosion--resistant finish and shall be dynamically
balanced.
3. Outdoor fan shall be of the direct--drivenpropeller type with
aluminum blades, riveted to corrosion--resistant steel
spiders. It shall be dynamically balanced and discharge air
vertically.
2. Scroll compressors shall be standard on all units.
E. Coils:
1. Indoor and outdoor coils shall have aluminum plate fins
mechanicallybonded to seamlesscopper tubes with alljoints
brazed.
2. Tube sheet openings shall be bellied to prevent tube wear.
F. Refrigerant Metering Device:
Refrigerant metering device shall be of the TXV type.
G. Filters:
Filter section shall consist of field--installed, throw--away,
1--in. thick fiberglass filters of commercially available sizes.
H. Controls and Safeties:
1. Unit controls shall be complete with self--contained low
voltage control circuit.
2. Units shallincorporate an internal compressorprotector that
provides reset capability.
3. Unit shall provide high and low/loss--of--charge pressure
safety protection.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at 125°F
ambient outdoor temperature, exceeding maximum load
criteria of ARI Standard 240.
2. Compressor with standard controls shall be capable of
operation down to 55°F ambient outdoor temperature.
J. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
K. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings
and inherent automatic reset thermal overload protection.
3. Outdoor fan motor shall be totally enclosed.
L. Grille
1. Louvered Grille:
Louvered grille shall be standard on all units.
22
Page 23
GUIDE SPECIFICATIONS (CONT)
M. Special Features:
1. Coil Options:
Shall include factory--installed optional tin-- plated indoor
copper/copper and vinyl--coated refrigerant coils.
2. Flat Roof Curb:
Curbs shall have seal stripand awood nailerfor flashingand
shall be installed per manufacturer’s instructions.
3. Manual Outdoor Air Damper:
Packageshall consist of damper, bird screen,and rain hood
which can bepresetto admitoutdoorairfor year--round ventilation.
4. Evolutiont User Interface:
To provide for two-- stage heating and one--stage cooling in
addition to manual or automatic changeover and indoor fan
control.
5. Low--Ambient Package:
Shall consist of a solid--state control and outdoor coil temperature sensor for controlling outdoor fan motoroperation,
which shallallow unit to operate down to 0°F outdoor ambient temperature in cooling.
6. Filter Rack Kit:
Shall provide filter mounting for downflow and horizontal
applications.
7. Square--To--Round Duct Transitions:
Shall have the ability to convertthe supplyand return open-
ings from rectangular to round (024--048 sizes only).
8. Crankcase Heater:
Shall provide anti--floodback protection for low--load cool-
ing applications. (Standard on 042--060 sizes.)
®
9. Compressor Protection (Time Guard
Solid--state control shall protect compressor by preventing
“short cycling.”
10. Electric heaters:
a. Electric heater shall be available as a field--installed
option.
b. Heater elements shall be open-- wire type, adequately
supported and insulated with ceramic bushings.
c. Electric heater packages must provide single--point
power connection capability.
11. Compressor Hard Start Kit:
Shall be available to give a boost to the compressor motor
at each start--up.
II Kit)
704C
23
Page 24
E2006 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231Printed in U.S.
A
Manufacture r reserves the right to discontinue, or change at any time, specif icatio ns or designs without notice and without incurring obligati ons.
.Edition Date: 05/06
24
Catalog No. PDS 704C.24.1
Replaces: New