677C----A
PREFERREDt 14 SEER SINGLE--PACKAGED HYBRID HEATr
DUAL FUEL SYSTEM WITH PURONr (R--410A) REFRIGERANT
SINGLE AND THREE PHASE
2--5 NOMINAL TONS (SIZES 24--60)
Installation Instructions
NOTE:Read the entire instruction manual before starting the
installation.
NOTE:Installer: Make sure the Owner’s Manual and Service
Instructions are left with the unit after installation.
Improper installation, adjustment, alteration, service maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. consult local
building codes, the current editions of the National Fuel Gas Code
(NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code
(NEC) NFPA 70.
In Canada refer to the current editions of the National Standards of
Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane
Installation codes, and Canadian Electrical Code CSA C22.1
Recognize safety information. This is the safety--alert symbol
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these
signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
A09042
Fig. 1 -- Unit 677C-- --A
SAFETY CONSIDERATIONS
.
1
or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch. Turn off accessory heater power switch if
applicable. TAG THE DISCONNECT SWITCH WITH A
SUITABLE WARNING LABEL.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND
CARBON MONOXIDE POISONING HAZARD
677C-- --A
Failure to follow this warning could result in personal
injury, death or property damage.
A qualified installer or agency must use only
factory--authorized kits or accessories when modifying this
product.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 19) or performing
maintenance functions inside your unit, be aware of sharp
sheet metal parts and screws. Although special care is taken
to reduce sharp edges to a minimum, be extremely careful
when handling parts or reaching into the unit.
INTRODUCTION
The 677C----A unit (see Fig. 1) is a fully self--contained,
combination Category I gas heating/electric heating and cooling
unit designed for outdoor installation (See Fig. 2 and 3 for unit
dimensions). All unit sizes have return and discharge openings for
both horizontal and downflow configurations, and are factory
shipped with all downflow duct openings covered. Units may be
installed either on a rooftop, a cement slab, or directly on the
ground, if local codes permit (See Fig. 4 for roof curb dimensions).
Models with an N in the thirteenth position of the model number
are dedicated Low NOx units designed for California installations.
These models meet the California maximum oxides of nitrogen
(NOx) emissions requirements of 40 nanograms/joule or less as
shipped from the factory and must be installed in California Air
Quality Management Districts or any other regions in North
America where a Low NOx rule exists.
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY UNIT
The unit model number and serial number are stamped on the unit
information plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage before removing packaging materials.
If unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.
Forward claim papers directly to transportation company.
Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest equipment distribution office if any item is missing. To
prevent loss or damage, leave all parts in original packages until
installation.
Step 2 — Provide Unit Support
For hurricane tie downs, contact distributor for details and PE
(Professional Engineering) Certificate if required.
ROOF CURB
Install accessory roof curb in accordance with instructions shipped
with curb (See Fig. 4). Install insulation, cant strips, roofing, and
flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a water tight seal. Install gasketing material supplied
with the roof curb. Improperly applied gasketing also can result in
air leaks and poor unit performance.
Curb should be level to within 1/4 in. (6 mm). This is necessary for
unit drain to function properly. Refer to accessory roof curb
installation instructions for additional information as required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4
in. (102 mm) thick with 2 in. (51 mm) above grade. The slab
should be flush on the compressor end of the unit (to allow
condensate drain installation) and should extend 2 in. (51 mm) on
the three remaining sides of the unit. Do not secure the unit to the
slab except when required by local codes.
Step 3 — Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal
applications, unit is provided with flanges on the horizontal
openings. All ductwork should be secured to the flanges. Insulate
and weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire codes.
Read unit rating plate for any required clearances around ductwork.
Cabinet return--air static shall not exceed --.25 IN. W.C.
Step 4 — Provide Clearances
The required minimum operating and service clearances are shown
in Fig. 2 and 3.
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
The condenser fan pulls air through the condenser coil and
discharges it through the top grille. Be sure that the fan discharge
does not recirculate to the condenser coil. Do not locate the unit in
either a corner or under an overhead obstruction. The minimum
clearance under a partial overhang (such as a normal house
overhang) is 48--in. (1219 mm) above the unit top. The maximum
horizontal extension of a partial overhang must not exceed 48-- in.
(1219 mm).
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. The unit may be installed
on wood flooring or on Class A, B, or C roof covering materials.
2
677C-- --A
Fig. 2 -- 677C----A24 --30 Unit Dimensions
3
A09146
677C-- --A
Fig. 3 -- 677C----A36 --60 Unit Dimensions
4
A09147
HVAC unit
base rails
HVAC unit
basepan
B
C
Anchor screw
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
*Provided with roofcurb
ROOF CURB DETAIL
Sealing
Gasket
Roofcurb
Wood nailer*
Roofcurb*
Insulation
(field supplied)
A09090
F
A
D
SMALL CURB
E
A09110
677C-- --A
B
C
F
A
D
LARGE CURB
UNIT SIZE
Small
Large
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
IMPORTANT: Do not install large base pan HYBRID HEAT
units onto the small base pan (common curb). The center of gravity
on a large base pan HYBRID HEAT unit could overhang the curb
causing an unsafe condition. Before installing any large base pan
unit onto the common curb, check the “Y” distance in the product
A
IN. (mm)
Fig. 4 -- Roof Curb Dimensions
E
A09095
B
IN. (mm)*
10 (254)
C
IN. (mm)
D
IN. (mm)
E
IN. (mm)
32.4 (822)
16 (406)47.8 (1214)
14 (356)43.9 (1116)
literature dimensional drawing to ensure that “Y” is greater than 14
in. (356 mm). Do not install any large base pan unit onto the
common curb with a “Y” dimension (center of gravity) less than 14
in. (356 mm).
F
IN. (mm)
2.7 (69)
A09111
5
CAUTION - NOTICE TO RIGGERS
PRUDENCE - AVIS AUX MANIPULATEUR
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
DUCTS
MINIMUM HEIGHT: 36" (914.4 mm)
HAUTEUR MINIMUM
SEAL STRIP MUST BE IN
UNIT HEIGHT
HAUTEUR D'UNITÉ
677C-- --A
SEE DETAIL A
VOIR DÉTAIL A
Unit
Rigging
Weight
NOTE: See dimensional drawing for corner weight distribution.
2430
lbkglbkglbkglbkglbkglbkg
368167378171
Unit
Rigging
Weight
450204491223513233543246
DETAIL A
VOIR DÉTAIL A
36424860
PLACE BEFORE PLACING
UNIT ON ROOF CURB
BANDE SCELLANT DOIT ÊTRE
EN PLACE AVANT DE PLACER
L'UNITÉ SUR LA BASE DE TOIT
50CY502286 2.0
A09051
Fig. 5 -- 677C----A Suggested Rigging
Step 5 — Rig and Place Unit
Inspection
Prior to initial use, and at monthly intervals, all rigging shackles,
!
WARNING
PERSONAL INJURY OR PROPERTY DAMAGE
HAZARD
Failure to follow this warning could result in personal
clevis pins, and straps should be visually inspected for any
damage, evidence of wear, structural deformation, or cracks.
Particular attention should be paid to excessive wear at hoist
hooking points and load support areas. Materials showing any kind
of wear in these areas must not be used and should be discarded.
injury, death or property damage.
!
When installing the unit on a rooftop, be sure the roof will
support the additional weight.
Rigging and handling of this equipment can be hazardous for
many reasons due to the installation location (roofs, elevated
structures, etc.).
Only trained, qualified crane operators and ground support staff
UNIT FALLING HAZARD
Failure to follow this warning could result in personal
injury or death.
Never stand beneath rigged units or lift over people.
WARNING
should handle and install this equipment.
When working with this equipment, observe precautions in the
!
WARNING
literature, on tags, stickers, and labels attached to the equipment,
and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but
not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the
lifts to adapt to various sizes or kinds of loads.
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36
in. (914 mm) above the unit top cover.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting
kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
Rigging/Lifting of Unit (See Fig. 5)
Lifting holes are provided in base rails as shown in Fig. 2 and 3.
1. Leave top shipping skid on the unit for use as a spreader bar
to prevent the rigging straps from damaging the unit. If the
skid is not available, use a spreader bar of sufficient length
to protect the unit from damage.
2. Attach shackles, clevis pins, and straps to the base rails of
the unit. Be sure materials are rated to hold the weight of the
unit (See Fig. 5).
6
3. Attach a clevis of sufficient strength in the middle of the
straps. Adjust the clevis location to ensure unit is lifted level
with the ground.
After the unit is placed on the roof curb or mounting pad, remove
the top skid.
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 677C ----A disposes of condensate water through a 3/4 in.
NPT fitting which exits through the compressor access panel (See
Fig. 2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground
level installations. Install a field--supplied condensate trap at end
of condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. (25 mm) lower than the
drain--pan condensate connection to prevent the pan from
overflowing (See Fig. 6). Prime the trap with water. When using a
gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away
from the unit, install a 2--in. (51 mm) trap at the condensate
connection to ensure proper drainage (See Fig. 6). Make sure that
the outlet of the trap is at least 1 in. (25 mm) lower than the
drain--pan condensate connection. This prevents the pan from
overflowing.
Prime the trap with water. Connect a drain tube -- using a minimum
of 3/4--in. PVC or 3/4--in. copper pipe (all field--supplied) -- at the
outlet end of the 2--in. (51 mm) trap. Do not undersize the tube.
Pitch the drain tube downward at a slope of at least 1--in. (25 mm)
for every 10 ft (3 m) of horizontal run. Be sure to check the drain
tube for leaks.
TRAP
OUTLET
1-in. (25 mm) min.
2-in. (51 mm) min.
A09052
Fig. 6 -- Condensate Trap
Step 7 — Install Flue Hood
The flue assembly is secured and shipped in the return air duct.
Remove duct cover to locate the assembly (See Fig. 8).
NOTE:Dedicated low NOx models MUST be installed in
California Air Quality Management Districts where a Low NOx
rule exists.
These models meet the California maximum oxides of nitrogen
(NOx) emissions requirements of 40 nanograms/joule or less as
shipped from the factory.
NOTE:Low NOx requirements apply only to natural gas
installations.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
The venting system is designed to ensure proper venting.
The flue hood assembly must be installed as indicted in this
section of the unit installation instructions.
Install the flue hood as follows:
1. This installation must conform with local building codes
and with the National Fuel Gas Code (NFGC) NFPA 54 /
ANSI Z223.1,(in Canada, CAN/CGA B149.1, and
B149.2) latest revision. Refer to Provincial and local
plumbing or wastewater codes and other applicable local
codes.
2. Remove flue hood from shipping location (inside the return
section of the blower compartment--see Fig. 8). Remove the
return duct cover to locate the flue hood. Place flue hood
assembly over flue panel. Orient screw holes in flue hood
with holes in the flue panel.
3. Secure flue hood to flue panel by inserting a single screw on
the top flange and the bottom flange of the hood.
Step 8 — Install Gas Piping
The gas supply pipe enters the unit through the access hole
provided. The gas connection to the unit is made to the 1/2--in.
(12.7 mm) FPT gas inlet on the gas valve.
Install a gas supply line that runs to the heating section. Refer to
Table 2 and the NFGC for gas pipe sizing. Do not use cast--iron
pipe. It is recommended that a black iron pipe is used. Check the
local utility for recommendations concerning existing lines. Size
gas supply piping for 0.5 IN. W.C. maximum pressure drop. Never
use pipe smaller than the 1/2-- in. (12.7 mm) FPT gas inlet on the
unit gas valve.
For natural gas applications, the gas pressure at unit gas connection
must not be less than 4.0 IN. W.C. or greater than 13 IN. W.C.
while the unit is operating. For propane applications, the gas
pressure must not be less than 11.0 IN. W.C. or greater than 13 IN.
W.C. at the unit connection.
A 1/8--in. (3.2 mm) NPT plugged tapping, accessible for test gauge
connection, must be installed immediately upstream of the gas
supply connection to the gas valve.
When installing the gas supply line, observe local codes pertaining
to gas pipe installations. Refer to the NFGC NFPA 54/ANSI
Z223.1 latest edition (in Canada, CAN/CGA B149.1).
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed
plumber or gas fitter.
2. When flexible connectors are used, the maximum length
shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves
are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
In the absence of local building codes, adhere to the following
pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.
(6.35 mm) for every 15 ft (4.6 m) of length to prevent traps.
Grade all horizontal runs downward to risers. Use risers to
connect to heating section and to meter.
2. Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft (1.8
m). For pipe sizes larger than 1/2 in., (12.7 mm) follow
recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.
Never use Teflon tape.
4. Install sediment trap in riser leading to heating section (See
Fig. 7). This drip leg functions as a trap for dirt and
condensate.
677C-- --A
7
IN
made specifically for the detection of leaks (or method
specified by local codes and/or regulations).
Step 9 — Install Duct Connections
The unit has duct flanges on the supply-- and return--air openings
on the side and bottom of the unit. For downshot applications, the
ductwork connects to the roof curb (See Fig. 2 and 3 for
connection sizes and locations).
Configuring Units for Downflow (V ertical) Discharge
TEE
OUT
NIPPLE
CAP
C99020
Fig. 7 -- Sediment Trap
5. Install an accessible, external, manual main shutoff valve in
gas supply pipe within 6 ft (1.8 m) of heating section.
677C-- --A
6. Install ground-- joint union close to heating section between
unit manual shutoff and external manual main shut--off
valve.
7. Pressure test all gas piping in accordance with local and
national plumbing and gas codes before connecting piping
to unit.
NOTE: Pressure test the gas supply system after the gas supply
piping is connected to the gas valve. The supply piping must be
disconnected from the gas valve during the testing of the piping
systems when test pressure is in excess of 0.5 psig. Pressure test the
gas supply piping system at pressures equal to or less than 0.5 psig.
The unit heating section must be isolated from the gas piping
system by closing the external main manual shutoff valve and
slightly opening the ground--joint union.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch. Tag the disconnect switch with a suitable warning
label.
1. Open all electrical disconnects before starting any service
2. Remove horizontal (metal) duct covers to access vertical
3. Starting in a corner as shown in Fig. 9, score the panel in
4. If unit ductwork is to be attached to vertical opening flanges
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Collect ALL screws that were removed. Do not leave screws
on rooftop as permanent damage to the roof may occur.
!
work.
(downflow) discharge duct knockouts in unit basepan. (See
Fig. 8.)
both directions from the corner. Tap the panel out from the
scored corner using a small hammer. Be careful and not
damage any other part of the unit.
on the unit base (jackstand applications only), do so at this
time.
WARNING
!
CAUTION
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage.
--Connect gas pipe to unit using a backup wrench to avoid
damaging gas controls.
--Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections.
--Use proper length of pipe to avoid stress on gas control
manifold.
--If a flexible connector is required or allowed by authority
having jurisdiction, black iron pipe shall be installed at
furnace gas valve and extend a minimum of 2 in. (51 mm)
outside furnace casing.
--If codes allow a flexible connector, always use a new
connector. do not use a connector which has previously
serviced another gas appliance.
8. Checkfor gas leaksat thefield--installedand
factory--installed gas lines after all piping connections have
been completed. Use a commercially available soap solution
5. It is recommended that the base insulation around the
perimeter of the vertical return--air opening be secured to
the base with aluminum tape. Applicable local codes may
require aluminum tape to prevent exposed fiberglass.
6. Reinstall both horizontal duct covers. Ensure opening is
air-- and watertight.
7. After completing unit conversion, perform all safety checks
and power up unit.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:
1. Units are shipped for horizontal duct installation (by
removing duct covers).
2. Select and size ductwork, supply-- air registers, and
return--air grilles according to American Society of Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE)
recommendations.
3. Use flexible transition between rigid ductwork and unit to
prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to
ensure weather tight and airtight seal.
Rows...Fins/in.
F a c e A r e a --- s q f t
OUTDOOR FAN
Nominal Cfm
Diameter --- in.
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in.
F a c e A r e a --- s q f t
INDOOR BLOWER
S i z e --- i n .
M o t o r --- h p
FURNACE SECTION*
Burner Orifice
Natural Gas Qty...Drill Size
Propane GasQty...Drill Size
( p s i g ) C u t --- o u t
Reset (Auto)
L O S S --- O F --- C H A R G E /
(Liquid Line) (psig)
C u t --- o u t
Reset (auto)
RETURN---AIR FILTERS † }
Throwaway (in.)
(kg)
(kg)
(mm)
(mm)
(mm)
*Based on altitude of 0 to 2000 ft (0 ---610 m).
{Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow vel o city of
300 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.
368
167
9.5
4.3
0.032 (2)
.81
2...21
13.6
2500
22
559
1/8 (825)
3...17
3.7
800
10x10
254x254
1/2
2...44
2...55
20x20x1
508x508x25
368
167
9.5
4.3
0.032 (2)
.81
2...21
13.6
2500
22
559
1/8 (825)
3...17
3.7
800
10x10
254x254
1/2
2...38
2...53
378
171
10.5
4.8
0.038 (2)
.97
2...21
15.4
2600
22
559
1/8 (825)
3...17
3.7
1000
10x10
254x254
1/2
2...44
2...55
20x24x1
508x610x25
378
171
10.5
4.8
Indoor---TXV, Outdoor---Accurater
0.038 (2)
.97
2...21
15.4
2600
22
559
1/8 (825)
3...17
3.7
1000
10x10
254x254
1/2
2...44
2...53
650 +/--- 15
420 +/--- 25
2 0 + / --- 5
45 +/--- 10
450
204
9.0
4.1
0.040 (2)
1.02
2...21
13.6
3000
22
559
1/4 (1100)
3...17
4.7
1200
11x10
279x254
3/4
2...38
2...53
450
204
9.0
4.1
0.040 (2)
1.02
2...21
13.6
3000
22
559
1/4 (1100)
3...17
4.7
1200
11x10
279x254
3/4
3...38
3...53
24x30x1
610x762x25
491
223
14.0
6.4
0.038 (Left OD Coil)
0.040 (Right OD Coil)
.97/1.02
2...21
19.4
3500
22
559
1/8 (825)
3...17
4.7
1400
11x10
279x254
3/4
2...38
2...53
1/8 (825)
279x254
491
223
14.0
6.4
2...21
19.4
3500
22
559
3...17
4.7
1400
11x10
3/4
3...38
3...53
677C-- --A
Basepan
Downflow
(Vertical)
Supply
Knockout
Horizontal Duct Covers
Fig. 8 -- Supply and Return Duct Opening
A09076
Basepan
Downflow
(Vertical)
Return
Knockout
A09077
3
2
4
1
3
2
INSTRUCTIONS FOR REMOVING DOWNSHOT PANELS
1. Score groove in corner 1 in both directions as far as you can reach.
2. Starting in corner 1, tap-out all sides with a small hammer. Be careful
not to damage any other part of unit.
3. If side from corner 3 to 4 is not accessible due to heat exchanger,
pivot panel up and down by hand until remaining side breaks off.
Table 1 -- Physical Data -- Unit 677C-- --A Cont’d)
NUMBER
OF
MANIFOLD
PRES
SURE
ORIFICES
UNIT SIZE480904811548130600906011560130
NOMINAL CAPACITY ---ton444555
SHIPPING WEIGHT --- lb
COMPRESSORSScroll
Quantity1
REFRIGERANT (R ---410A)
Quantity ---lb
REFRIGERANT METERING DEVICETXV
OUTDOOR ORIFICE ---in. (qty)
OUTDOOR COIL
Rows...Fins ---in.
F a c e A r e a --- s q f t
OUTDOOR FAN
Nominal Cfm
Diameter ---in.
M o t o r H p --- R p m
INDOOR COIL
Rows...Fins ---in.
F a c e A r e a --- s q f t
INDOOR BLOWER
Nominal C ooling Airflow---(CFM)
677C-- --A
Propane GasQty...Drill Size
HIGH -- -PRESSURE SWITCH (psig)
LOW---PRES SURE SWITCH
*Based on altitude of 0 to 2000 ft (0 ---610 m).
{Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow vel o city of
300 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.
* Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5--IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2
and the NFGC NFPA 54/ANSI.
† This length includes an ordinary number of fittings.
*When a unit is converted to propan e, different size orifices must be used. See separate, natural ---to ---propane conversion kit instructions.
{Based on altitudes from sea level to 2000 ft (610 m) above sea level. In th e U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each
additional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.
MANIFOLD PRESSURE
(IN. W.C.)
10
4. All units must have field--supplied filters or accessory filter
rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.
5. Size all ductwork for maximum required airflow (either
heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be
affected.
6. Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned
space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) and Air Conditioning Contractors
of America (ACCA) minimum installation standards for
heating and air conditioning systems. Secure all ducts to
building structure.
7. Flash, weatherproof, and vibration--isolate all openings in
building structure in accordance with local codes and good
building practices.
Step 10 — Install Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground. This ground may consist of an electrical
wire connected to the unit ground screw in the control
compartment,or conduit approved forelectrical ground when
installed in accordance with NEC, NFPA 70 National Fire
Protection Association (latest edition) (in Canada, Canadian
Electrical Code CSA C22.1) and local electrical codes.
!
CAUTION
The unit must have a separate electrical service with a
field--supplied, waterproof disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field--supplied disconnect switch box may be mounted on the
unit over the high--voltage inlet hole when the standard power and
low--voltage entry points are used (See Fig. 2 and 3 for acceptable
location).
See unit wiring label (Fig. 15 and 16) and Fig. 10 for reference
when making high voltage connections. Proceed as follows to
complete the high--voltage connections to the unit.
Single phase units:
1. Run the high--voltage (L1, L2) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5.ConnectfieldwireL2toyellowwireonconnection23of
the compressor contactor.
Three--phase units:
1. Run the high-- voltage (L1, L2, L3) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5.ConnectfieldwireL3toyellowwireonconnection13of
the compressor contactor.
6. Connect field wire L2 to blue wire from compressor.
Special Procedures for 208--V Operation
677C-- --A
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit
being installed.
1. Make all electrical connections in accordance with NEC
NFPA 70 (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field--supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-- voltage power to unit is within
operating voltage range indicated on unit rating plate. On
3--phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of
improper voltage and/or phase imbalance.
4. Insulate low--voltage wires for highest voltage contained
within conduit when low--voltage control wires are in
same conduit as high-- voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit,
etc.
High--Voltage Connections
When routing power leads into unit, use only copper wire between
disconnect and unit. The high voltage leads should be in a conduit
until they enter the duct panel; conduit termination at the duct
panel must be watertight.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Make sure the power supply tothe unit isswitchedOFF before
making any wiring changes. Tag the disconnect switch with a
suitable warning label. With disconnect switch open, move
black wire from transformer (3/16 in.) terminal marked 230 to
terminal marked 200. This retaps transformer to primary
voltage of 208 vac.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Beforemaking any wiring changes,make surethe gas supply
is switched off first. Then switch off the power supply to the
unit and install lockout tag.
WARNING
WARNING
Control Voltage Connections
Do not use any type of power--stealing thermostat. Unit control
problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated
(35_C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.