Liquid Line Strainers20...............................
High Flow Valves20.................................
TROUBLESHOOTING20..............................
START--UP CHECKLIST20............................
A05194
Fig. 1 -- Unit 664B
1
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due
to mechanical and electrical components. Only trained and
qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on this
equipment, observe precautions in the literature, on tags, and on
labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. Installation must be in compliance with
local and national building codes. Wear safety glasses, protective
clothing, and work gloves. Have fire extinguisher available. Read
these instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit.
Recognize safety information. This is the safety --alert symbol
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these
signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety --alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
664B
or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main
power to system and tag. There may be more than one
disconnect switch. Turn off accessory heater power switch if
applicable.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate clothing.
CAUTION
INTRODUCTION
The 664B packaged heat pump is fully self--contained and
designed for outdoor installation (See Fig. 1). Standard units are
shipped in a horizontal--discharge configuration for installation on
a ground--level slab or directly on the ground if local codes permit.
Standard units can be converted to downflow (vertical) discharge
configurations for rooftop applications with a field supplied
plenum.
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY UNIT
The unit model number and serial number are printed on the unit
informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If
unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.
Forward claim papers directly to transportation company.
Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest equipment distribution office if any item is missing. To
prevent loss or damage, leave all parts in original packages until
installation.
Step 2 — Provide Unit Support
For hurricane tie downs, contact distributor for details and PE
(Professional Engineering) Certificate, if required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4
in. (102 mm) thick with 2 in. (51 mm) above grade. The slab
should extend approximately 2 in. (51 mm) beyond the casing on
all 4 sides of the unit. Do not secure the unit to the slab except
when required by local codes.
A 6--in. (152 mm) wide gravel apron should be used around the
flat surface to prevent airflow blockage by grass or shrubs. The
unit should be level within 1/4 in. (6 mm). This is necessary for the
.
unit drain to function properly.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground
prepared with gravel for condensate discharge.
Step 3 — Provide Clearances
The required minimum service clearances are shown in Fig. 5.
Adequate ventilation and outdoor air must be provided.
The outdoor fan draws air through the outdoor coil and discharges
it through the top fan grille. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48
in. (1219 mm) above the unit top. The maximum horizontal
extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab--mounted units
should be at least 4 in. (102 mm) above the highest expected water
and runoff levels. Do not use unit if it has been under water.
Step 4 — Place Unit
Unit can be moved with the rigging holds provided in the unit
base. Refer to Table 1 for operating weights. Use extreme caution
to prevent damage when moving the unit. Unit must remain in an
upright position during all moving operations. The unit must be
level with in 1/4 in. (6 mm) for proper condensate drainage; the
ground--level pad must be level before setting the unit in place.
When a field--fabricated support is used, be sure that the support is
level and that it properly supports the unit.
Step 5 — Select and Install Ductwork
The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
non--residence type air conditioning and ventilating systems,
NFPA 90A or residence type, NFPA 90B and/or local codes and
ordinances.
Select and size ductwork, supply--air registers, and return air grilles
accordingtoASHRAE(AmericanSocietyof Heating,
Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply-- and return--air
openings on the side of the unit. See Fig. 5 for connection sizes
and locations. The 14 --in. (356 mm) round duct collars are shipped
inside the unit attached to the base pan in the indoor blower
compartment. They are field--installed and must be removed from
the indoor blower compartment prior to start--up, even if they are
not used for installation.
2
When designing and installing ductwork, consider the following:
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit
components.
When connecting ductwork to units, do not drill deeper
than 3/4 in. (19 mm) in shaded area shown in Fig. 2 or coil
may be damaged.
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL)
DISCHARGE
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations on the
system, turn off main power to unit and install lockout tag.
19.17 in. (487 mm)
3.92 in.
(100 mm)
A08003
Fig. 2 -- Area Not to be Drilled More Than 3/4 --in. (19 mm)
Deep
1. All units should have field--supplied filters or accessory
filter rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.
2. Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24--in.
(610 mm) from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum
air quantity for proper electric heater operation is listed in
Table 2. Heater limit switches may trip at air quantities
below those recommended.
4. Seal, insulate, and weatherproof all external ductwork. Seal,
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and
Air Conditioning ContractorsNationalAssociation
(SMACNA) and Air Conditioning Contractors Association
(ACCA) minimum installation standards for residential
heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof,
and vibration--isolate duct openings in wall or roof
according to good construction practices.
Fig. 6 shows a typical duct system with 664B unit installed.
Units are dedicated side supply products. They are not convertible
to vertical air supply. A field--supplied plenum must be used to
convert to vertical air discharge.
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Unit removes condensate through a 1--3/64 in. (27 mm) ID hole
(using 3/4--in. (19 mm) OD piping or tubing) which is located at
the end of the unit. See Fig. 5 for location of condensate
connection.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground
level installations. Install a field--supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. (25 mm) lower than the drain
pan condensate connection to prevent the pan from overflowing
(See Fig. 3 and 4). When using a gravel apron, make sure it slopes
away from the unit.
If the installation requires draining the condensate water away from
the unit, install a 2--in. (51 mm) trap using a 3/4--in. (19 mm) OD
tubing or pipe. (See Fig. 3 and 4.) Make sure that the outlet of the
trap is at least 1 in. (25 mm) lower than the unit drain--pan
condensate connection to prevent the pan from overflowing. Prime
the trap with water. Connect a drain tube using a minimum of
3/4--in. (19 mm) PVC, 3/4 --in. (19 mm) CPVC, or 3/4--in. copper
pipe (all field supplied). Do not undersize the tube. Pitch the drain
tube downward at a slope of at least 1 in. (25 mm) for every 10 ft
(3 m) of horizontal run. Be sure to check the drain tube for leaks.
Prime trap at the beginning of the cooling season start--up.
Allowable glues for condensate trap connection are: Standard
ABS, CPVC, or PVC cement..
1” (25 mm) MIN
1" (25 mm) MIN
.
TRAP
OUTLET
Fig. 3 -- Condensate Trap
TRAP
OUTLET
.
Fig. 4 -- PVC Condensate Trap
2” (51 mm) MIN.
2" (51 mm) MIN
A08001
.
664B
3
664B
Fig. 5 -- Unit Base Dimensions, 664B024 --060
4
A08414
RETURN
AIR
INDOOR
THERMOSTAT
TOP COVER
Power Wirin g
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND
LOW-VOLTAGE
ENTRY
COMPOSITE
RUST-PROOF
BASEPAN
CONDENSATE
DRAIN
CONNECTION
FROM
POWER
SOURCE
DISCONNECT
PER NEC
(UNIT AND
ELECTRIC
HEATER)
A08207
Fig. 6 -- Typical Installation
Table 1 – Physical Data
UNIT SIZE024030036042048060
NOMINAL CAPACITY (ton)22--1/233--1/245
OPERATING WEIGHT (lb)
(kg)
COMPRESSORScrollUltra Tech Scroll
REFRIGERANT (R-- 22)
Quantity (lb)
(kg)
REFRIGERANT METERING DEVICEAccuRater
Orifice ID (in.)0.0670.0670.0820.086––
Orifice OD (in.)0.0490.0570.0590.0630.0700.073
CONDENSER COILCopper Tubes, Aluminum Plate Fins
Rows…Fins/in.2…212…212…212…212…212…21
Face Area (sq. ft.)11. 112.715.815.813.315.8
CONDENSER FANPropeller
Nominal Cfm260026003200320032003300
Diameter (in.)
(mm)
Motor HP (RPM)1/8 (825)1/8 (825)1/4 (1100)1/4 (1100)1/4 (1100)1/2 (1100)
EVAPORATOR COILCopper Tubes, Aluminum Plate Fins
Rows…Fins/in.3…173…174…174…174…174…17
Face Area (sq. ft.)4.34.94.96.14.96.1
Evaporator blowerDirect Drive
Nominal Airflow (Cfm)80010001200140016001875
Size (in.)
(mm)
Motor HP (RPM)1/2 (1050)1/2 (1050)3/4 (1050)3/4 (1050)1 (1050)1 (1050)
CONNECTING DUCT SIZESRound
Supply Air (in.)
(mm)
Return Air (in.)
(mm)
Return--Air Filters* Throwaway (in.)
(mm)
*Required filter sizes shown are based on the ARI (Air conditioning & Refrigeration Institute) rated airflow at a velocity of 300 ft/min (91 m) for throwaway type or
450 ft/min (137 m) for high capacity type. Recommended filter s are 1 - --in. (25 mm) thick.
293
133
7.5
3.4
20
508
10x8
254 x 203
324
147
10.3
4.7
20
508
24 x 24
610 x 610
377
171
10.3
4.7
®
20
508
11x 9
279 x 229
389
176
11. 9
5.4
20
508
384
174
11. 4
5.2
20
508
433
196
13.3
6.0
TXV
20
508
11x 10
279 x 254
14
356
14
356
24 x 30
610 x 762
30 x 30
762 x 762
664B
5
Table 2 – Minimum Airflow for Safe Electric Heater Operation
Failure to follow this warning could result in personal
injury or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
664B
consist of an electrical wire connected to the unit ground
screw in the control compartment, or conduit approved for
electrical ground when installed in accordance with NEC,
ANSI/NFPA 70 American National Standards Institute/
National Fire Protection Association (latest edition) (in
Canada, Canadian Electrical Code CSA C22.1) and local
electrical codes.
!
CAUTION
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The
high--voltage leads should be in a conduit until they enter the unit;
conduit termination at the unit must be watertight. Run the
high--voltage leads through the hole on the control box side of the
unit (See Fig. 7). When the leads are inside the unit, run leads to
the control box (See Fig. 8). For single--phase units, connect leads
to the black and yellow wires (See Fig. 9).
CONNECTING GROUND LEAD TO UNIT GROUND
Connect the ground lead to the chassis using the unit ground in the
control box (See Fig. 8 and 9).
ROUTING CONTROL POWER WIRES (24--V)
Form a drip--loop with the thermostat leads before routing them
into the unit. Route the thermostat leads through grommeted hole
provided in unit into unit control box (See Fig. 7). Connect
thermostat leads and unit power leads as shown in Fig. 9, 10 and
11.
Route thermostat wires through grommet providing a drip--loop at
the panel. Connect low--voltage leads to the thermostat as shown in
Fig. 10 & 11.
The unit transformer supplies 24--v power for complete system
including accessory electrical heater. Transformer is factory wired
for 230-- v operation.
ACCESSORY ELECTRIC HEAT WIRING
Refer to accessory electric heat installation instructions for
information on installing accessory electric heat. Accessory electric
heat wiring is shown in Fig. 17 and 18.
HIGH-VOLTAGEPOWER
WIRINGENTRYHOLE
LOW-VOLTAGEWIRING
ENTRYHOLE
(grommethole)
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit being installed.
1. Make all electrical connections in accordance with NEC
ANSI/NFPA 70 (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field--supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-- voltage power to unit is within
operating voltage range indicated on unit rating plate. On
3--phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of
improper voltage and/or phase imbalance.
4. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit,
etc.
HIGH--VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a
field--supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field--supplied disconnect may be mounted on the unit over
the high--voltage inlet hole when the standard power and
low--voltage entry points are used. See Fig. 6 and 7 for acceptable
location.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.
A08407
Fig. 7 -- Unit Electrical Connection
6
3-PHASE
Thermostat
Unit Control
G
Y
W2
W3
R
RED
GRN
YEL
O
ORN
C
BRN
WHT
VIO
Thermostat
Unit Control
G
Y
Y1
O
R
RED
GRN
YEL
W2
PNK
W3
ORN
WHT
VIO
C
BRN
CONNECTIONS
TO DISCONNECT
PER NEC
and subbase
Fig. 8 -- Control Box Wiring
UNIT GROUND
LEAD
SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
GROUND
L
L
L
Fig. 9 -- Line Power Connections
HEATER LOW
VOLTAGE PLUG
A05388
BLK
YEL
BLU
C00012
and subbase
Power
Fig. 11 -- Control Connections (Sizes 048--060)
PRE--START--UP
!
WARNING
FIRE,EXPLOSION,ELECTRICALSHOCK
HAZARD
Failure to follow this warning could result in personal
injury or death and/or property damage.
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Relieve and recover all refrigerant from system before
touching or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor
terminals.
3. Never attempt to repair soldered connection while
refrigerant system is under pressure.
4. Do not use torch to remove any component. System
contains oil and refrigerant under pressure.
5. To remove a component, wear protective goggles and
proceed as follows:
a. Shut off electrical power to unit and install
lockout tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to flame.
A05208
664B
Power
Fig. 10 -- Control Connections (Sizes 024-- 042)
A05207
Proceed as follows to inspect and prepare the unit for initial
start-- up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a
refrigerant leak. Leak test all refrigerant tubing
connections using electronic leak detector, or
liquid-- soap solution. If a refrigerant leak is detected, see
Check for Refrigerant Leaks section.
7
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.