Liquid Line Strainers20...............................
High Flow Valves20.................................
TROUBLESHOOTING20..............................
START--UP CHECKLIST20............................
A05194
Fig. 1 -- Unit 664B
1
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due
to mechanical and electrical components. Only trained and
qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on this
equipment, observe precautions in the literature, on tags, and on
labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. Installation must be in compliance with
local and national building codes. Wear safety glasses, protective
clothing, and work gloves. Have fire extinguisher available. Read
these instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit.
Recognize safety information. This is the safety --alert symbol
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these
signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety --alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
664B
or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main
power to system and tag. There may be more than one
disconnect switch. Turn off accessory heater power switch if
applicable.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate clothing.
CAUTION
INTRODUCTION
The 664B packaged heat pump is fully self--contained and
designed for outdoor installation (See Fig. 1). Standard units are
shipped in a horizontal--discharge configuration for installation on
a ground--level slab or directly on the ground if local codes permit.
Standard units can be converted to downflow (vertical) discharge
configurations for rooftop applications with a field supplied
plenum.
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY UNIT
The unit model number and serial number are printed on the unit
informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If
unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.
Forward claim papers directly to transportation company.
Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest equipment distribution office if any item is missing. To
prevent loss or damage, leave all parts in original packages until
installation.
Step 2 — Provide Unit Support
For hurricane tie downs, contact distributor for details and PE
(Professional Engineering) Certificate, if required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4
in. (102 mm) thick with 2 in. (51 mm) above grade. The slab
should extend approximately 2 in. (51 mm) beyond the casing on
all 4 sides of the unit. Do not secure the unit to the slab except
when required by local codes.
A 6--in. (152 mm) wide gravel apron should be used around the
flat surface to prevent airflow blockage by grass or shrubs. The
unit should be level within 1/4 in. (6 mm). This is necessary for the
.
unit drain to function properly.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground
prepared with gravel for condensate discharge.
Step 3 — Provide Clearances
The required minimum service clearances are shown in Fig. 5.
Adequate ventilation and outdoor air must be provided.
The outdoor fan draws air through the outdoor coil and discharges
it through the top fan grille. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48
in. (1219 mm) above the unit top. The maximum horizontal
extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab--mounted units
should be at least 4 in. (102 mm) above the highest expected water
and runoff levels. Do not use unit if it has been under water.
Step 4 — Place Unit
Unit can be moved with the rigging holds provided in the unit
base. Refer to Table 1 for operating weights. Use extreme caution
to prevent damage when moving the unit. Unit must remain in an
upright position during all moving operations. The unit must be
level with in 1/4 in. (6 mm) for proper condensate drainage; the
ground--level pad must be level before setting the unit in place.
When a field--fabricated support is used, be sure that the support is
level and that it properly supports the unit.
Step 5 — Select and Install Ductwork
The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
non--residence type air conditioning and ventilating systems,
NFPA 90A or residence type, NFPA 90B and/or local codes and
ordinances.
Select and size ductwork, supply--air registers, and return air grilles
accordingtoASHRAE(AmericanSocietyof Heating,
Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply-- and return--air
openings on the side of the unit. See Fig. 5 for connection sizes
and locations. The 14 --in. (356 mm) round duct collars are shipped
inside the unit attached to the base pan in the indoor blower
compartment. They are field--installed and must be removed from
the indoor blower compartment prior to start--up, even if they are
not used for installation.
2
When designing and installing ductwork, consider the following:
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit
components.
When connecting ductwork to units, do not drill deeper
than 3/4 in. (19 mm) in shaded area shown in Fig. 2 or coil
may be damaged.
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL)
DISCHARGE
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations on the
system, turn off main power to unit and install lockout tag.
19.17 in. (487 mm)
3.92 in.
(100 mm)
A08003
Fig. 2 -- Area Not to be Drilled More Than 3/4 --in. (19 mm)
Deep
1. All units should have field--supplied filters or accessory
filter rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.
2. Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24--in.
(610 mm) from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum
air quantity for proper electric heater operation is listed in
Table 2. Heater limit switches may trip at air quantities
below those recommended.
4. Seal, insulate, and weatherproof all external ductwork. Seal,
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and
Air Conditioning ContractorsNationalAssociation
(SMACNA) and Air Conditioning Contractors Association
(ACCA) minimum installation standards for residential
heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof,
and vibration--isolate duct openings in wall or roof
according to good construction practices.
Fig. 6 shows a typical duct system with 664B unit installed.
Units are dedicated side supply products. They are not convertible
to vertical air supply. A field--supplied plenum must be used to
convert to vertical air discharge.
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Unit removes condensate through a 1--3/64 in. (27 mm) ID hole
(using 3/4--in. (19 mm) OD piping or tubing) which is located at
the end of the unit. See Fig. 5 for location of condensate
connection.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground
level installations. Install a field--supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. (25 mm) lower than the drain
pan condensate connection to prevent the pan from overflowing
(See Fig. 3 and 4). When using a gravel apron, make sure it slopes
away from the unit.
If the installation requires draining the condensate water away from
the unit, install a 2--in. (51 mm) trap using a 3/4--in. (19 mm) OD
tubing or pipe. (See Fig. 3 and 4.) Make sure that the outlet of the
trap is at least 1 in. (25 mm) lower than the unit drain--pan
condensate connection to prevent the pan from overflowing. Prime
the trap with water. Connect a drain tube using a minimum of
3/4--in. (19 mm) PVC, 3/4 --in. (19 mm) CPVC, or 3/4--in. copper
pipe (all field supplied). Do not undersize the tube. Pitch the drain
tube downward at a slope of at least 1 in. (25 mm) for every 10 ft
(3 m) of horizontal run. Be sure to check the drain tube for leaks.
Prime trap at the beginning of the cooling season start--up.
Allowable glues for condensate trap connection are: Standard
ABS, CPVC, or PVC cement..
1” (25 mm) MIN
1" (25 mm) MIN
.
TRAP
OUTLET
Fig. 3 -- Condensate Trap
TRAP
OUTLET
.
Fig. 4 -- PVC Condensate Trap
2” (51 mm) MIN.
2" (51 mm) MIN
A08001
.
664B
3
664B
Fig. 5 -- Unit Base Dimensions, 664B024 --060
4
A08414
RETURN
AIR
INDOOR
THERMOSTAT
TOP COVER
Power Wirin g
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND
LOW-VOLTAGE
ENTRY
COMPOSITE
RUST-PROOF
BASEPAN
CONDENSATE
DRAIN
CONNECTION
FROM
POWER
SOURCE
DISCONNECT
PER NEC
(UNIT AND
ELECTRIC
HEATER)
A08207
Fig. 6 -- Typical Installation
Table 1 – Physical Data
UNIT SIZE024030036042048060
NOMINAL CAPACITY (ton)22--1/233--1/245
OPERATING WEIGHT (lb)
(kg)
COMPRESSORScrollUltra Tech Scroll
REFRIGERANT (R-- 22)
Quantity (lb)
(kg)
REFRIGERANT METERING DEVICEAccuRater
Orifice ID (in.)0.0670.0670.0820.086––
Orifice OD (in.)0.0490.0570.0590.0630.0700.073
CONDENSER COILCopper Tubes, Aluminum Plate Fins
Rows…Fins/in.2…212…212…212…212…212…21
Face Area (sq. ft.)11. 112.715.815.813.315.8
CONDENSER FANPropeller
Nominal Cfm260026003200320032003300
Diameter (in.)
(mm)
Motor HP (RPM)1/8 (825)1/8 (825)1/4 (1100)1/4 (1100)1/4 (1100)1/2 (1100)
EVAPORATOR COILCopper Tubes, Aluminum Plate Fins
Rows…Fins/in.3…173…174…174…174…174…17
Face Area (sq. ft.)4.34.94.96.14.96.1
Evaporator blowerDirect Drive
Nominal Airflow (Cfm)80010001200140016001875
Size (in.)
(mm)
Motor HP (RPM)1/2 (1050)1/2 (1050)3/4 (1050)3/4 (1050)1 (1050)1 (1050)
CONNECTING DUCT SIZESRound
Supply Air (in.)
(mm)
Return Air (in.)
(mm)
Return--Air Filters* Throwaway (in.)
(mm)
*Required filter sizes shown are based on the ARI (Air conditioning & Refrigeration Institute) rated airflow at a velocity of 300 ft/min (91 m) for throwaway type or
450 ft/min (137 m) for high capacity type. Recommended filter s are 1 - --in. (25 mm) thick.
293
133
7.5
3.4
20
508
10x8
254 x 203
324
147
10.3
4.7
20
508
24 x 24
610 x 610
377
171
10.3
4.7
®
20
508
11x 9
279 x 229
389
176
11. 9
5.4
20
508
384
174
11. 4
5.2
20
508
433
196
13.3
6.0
TXV
20
508
11x 10
279 x 254
14
356
14
356
24 x 30
610 x 762
30 x 30
762 x 762
664B
5
Table 2 – Minimum Airflow for Safe Electric Heater Operation
Failure to follow this warning could result in personal
injury or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
664B
consist of an electrical wire connected to the unit ground
screw in the control compartment, or conduit approved for
electrical ground when installed in accordance with NEC,
ANSI/NFPA 70 American National Standards Institute/
National Fire Protection Association (latest edition) (in
Canada, Canadian Electrical Code CSA C22.1) and local
electrical codes.
!
CAUTION
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The
high--voltage leads should be in a conduit until they enter the unit;
conduit termination at the unit must be watertight. Run the
high--voltage leads through the hole on the control box side of the
unit (See Fig. 7). When the leads are inside the unit, run leads to
the control box (See Fig. 8). For single--phase units, connect leads
to the black and yellow wires (See Fig. 9).
CONNECTING GROUND LEAD TO UNIT GROUND
Connect the ground lead to the chassis using the unit ground in the
control box (See Fig. 8 and 9).
ROUTING CONTROL POWER WIRES (24--V)
Form a drip--loop with the thermostat leads before routing them
into the unit. Route the thermostat leads through grommeted hole
provided in unit into unit control box (See Fig. 7). Connect
thermostat leads and unit power leads as shown in Fig. 9, 10 and
11.
Route thermostat wires through grommet providing a drip--loop at
the panel. Connect low--voltage leads to the thermostat as shown in
Fig. 10 & 11.
The unit transformer supplies 24--v power for complete system
including accessory electrical heater. Transformer is factory wired
for 230-- v operation.
ACCESSORY ELECTRIC HEAT WIRING
Refer to accessory electric heat installation instructions for
information on installing accessory electric heat. Accessory electric
heat wiring is shown in Fig. 17 and 18.
HIGH-VOLTAGEPOWER
WIRINGENTRYHOLE
LOW-VOLTAGEWIRING
ENTRYHOLE
(grommethole)
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit being installed.
1. Make all electrical connections in accordance with NEC
ANSI/NFPA 70 (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field--supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-- voltage power to unit is within
operating voltage range indicated on unit rating plate. On
3--phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of
improper voltage and/or phase imbalance.
4. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit,
etc.
HIGH--VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a
field--supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field--supplied disconnect may be mounted on the unit over
the high--voltage inlet hole when the standard power and
low--voltage entry points are used. See Fig. 6 and 7 for acceptable
location.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.
A08407
Fig. 7 -- Unit Electrical Connection
6
3-PHASE
Thermostat
Unit Control
G
Y
W2
W3
R
RED
GRN
YEL
O
ORN
C
BRN
WHT
VIO
Thermostat
Unit Control
G
Y
Y1
O
R
RED
GRN
YEL
W2
PNK
W3
ORN
WHT
VIO
C
BRN
CONNECTIONS
TO DISCONNECT
PER NEC
and subbase
Fig. 8 -- Control Box Wiring
UNIT GROUND
LEAD
SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
GROUND
L
L
L
Fig. 9 -- Line Power Connections
HEATER LOW
VOLTAGE PLUG
A05388
BLK
YEL
BLU
C00012
and subbase
Power
Fig. 11 -- Control Connections (Sizes 048--060)
PRE--START--UP
!
WARNING
FIRE,EXPLOSION,ELECTRICALSHOCK
HAZARD
Failure to follow this warning could result in personal
injury or death and/or property damage.
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Relieve and recover all refrigerant from system before
touching or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor
terminals.
3. Never attempt to repair soldered connection while
refrigerant system is under pressure.
4. Do not use torch to remove any component. System
contains oil and refrigerant under pressure.
5. To remove a component, wear protective goggles and
proceed as follows:
a. Shut off electrical power to unit and install
lockout tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to flame.
A05208
664B
Power
Fig. 10 -- Control Connections (Sizes 024-- 042)
A05207
Proceed as follows to inspect and prepare the unit for initial
start-- up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a
refrigerant leak. Leak test all refrigerant tubing
connections using electronic leak detector, or
liquid-- soap solution. If a refrigerant leak is detected, see
Check for Refrigerant Leaks section.
7
c. Inspect all field-- and factory--wiring connections. Be
sure that connections are completed and tight.
d. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
e. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that outdoor--fan blade is correctly positioned
in fan orifice. Top edge of blade should be 3.125 in.(79
mm) down from outdoor coil outlet grille (size
024--048, See Fig. 19) or hub should be 0.708--in. (18
mm) away from motor end bell (size 060, See Fig. 19).
See Outdoor Fan Adjustment section.
b. Make sure that air filter is in place.
c. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
START--UP
Step 1 — Check for Refrigerant Leaks
664B
Proceed as follows to locate and repair a refrigerant leak and to
charge the unit:
1. Locate leak and make sure that refrigerant system pressure
has been relieved and reclaimed from both high-- and
low--pressure ports.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened
for repair.
Step 2 — Start--Up Cooling and Make Adjustments
Complete the required procedures given in the Pre--Start--Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in cooling mode
when the outdoor temperature is below 40°F(4.4°C) (unless
accessory low--ambient kit is installed). Do not rapid cycle the
compressor. Allow 5 min. between “on” cycles to prevent
compressor damage.
CHECKINGCOOLINGANDHEATINGCONTROL
OPERATION
Start and check the unit for proper cooling control operation as
follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is
placed in ON position and shuts down within 60 sec. (for
024--042) or 90 seconds (for 048 and 060) when FAN
switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch
in AUTO position. Set control below room temperature.
Observe that compressor, outdoor fan, and indoor blower
motors start and that reversing valve shifts. Observe that
cooling cycle shuts down when control setting is satisfied.
Reversing valve (RV) remains energized.
3. Place system switch in HEAT position. Observe that
compressor, indoor fan and outdoor fan energize (Reversing
Valve is deenergized in heat pump heating mode). Set
control above room temperature. Observe that heating cycle
shuts down when control setting is satisfied.
4. When using an automatic changeover room thermostat,
place both SYSTEM and FAN switches in AUTO positions.
Observe that unit operates in Cooling mode when
temperature control is set to call for Cooling (below room
temperature), and unit operates in Heating mode when
temperature control is set to call for Heating (above room
temperature).
Step 3 — Refrigerant Charge
Refrigerant Charge — Amount of refrigerant charge is listed on
unit nameplate and in Table 1. Refer to Bryant Refrigerant Service
Techniques Manual, Refrigerants section. Unit panels must be in
place when unit is operating during charging procedure. Unit must
operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer to Bryant Refrigerant Service Techniques. Use standard
evacuating techniques. After evacuating system, weigh in the
specified amount of refrigerant (refer to Table 1).
LOW CHARGE COOLING
024--042 units:
1. Measure suction line pressure by attaching a gauge to the
service port.
2. Measure the suction line temperature by attaching a
temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor
ambient doesn’t affect the reading.
4. Locate the measured suction line pressure in the top row of
Table 5 and the measured outdoor ambient temperature in
the left column of the table. Based on the two values,
determine the required suction line temperature.
5. If the measured suction line temperature is greater than the
tabulated temperature, add charge in the system.
048 and 060 units:
1. Measure discharge line pressure by attaching a gauge to the
service port.
2. Measure the liquid line temperature by attaching a
temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor
ambient doesn’t affect the reading.
4. Refer to the required subcooling in Tables 3 to find the
required subcooling based on the model size and the
outdoor ambient temperature.
5. Interpolate if the outdoor temperature lies in between the
table values. Extrapolate if the temperature lies beyond the
table range.
6. Find the pressure value corresponding to the measured
pressure on the compressor discharge line.
7. Read across from the pressure reading to obtain the Liquid
line temperature for a required subcooling.
8. Add charge if the measured temperature is higher than the
liquid line temperature value in the table.
9. Add charge using the service connection on the suction line
of the compressor.
HEATING MODE CHARGE
Do not attempt to adjust charge by cooling methods while in heat
pump heating mode. Recover refrigerant and weigh in according to
unit data plate refrigerant data.
8
Table 3 – Required Subcooling
664B
Step 4 — Indoor Airflow and Airflow Adjustments
NOTE: For cooling operation, the recommended airflow is 350
to 450 cfm for each 12,000 Btuh of rated cooling capacity.
Table 4 shows dry coil air delivery for horizontal discharge units.
Tables 6-- 8 show pressure drops.
NOTE: Be sure that all supply-- and return --air grilles are open,
free from obstructions, and adjusted properly.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect electrical power to the unit and install lockout
tag before changing blower speed.
Airflow can be changed by changing the lead connections at the
blower motor. To change motor speeds, reposition wire at fan
motor speed terminals labeled 1--2 --3--4 (refer to Fig. 12).
Remove the speed tap connector labeled 1 through 5 on the motor.
While looking at the connector end that is inserted into the motor,
gently pry the locking tab outward and remove the wire from the
connector. Insert the wire into the desired tap until it locks into
place. Be sure new airflow meets the range noted above and
minimum electric heat CFM, if equipped. Refer to Table 2 and 4.
All model sizes are factory wired or rated airflow operation.
Fig. 12 -- Motor Speed Selection
FOR 208/230V BLOWER MOTORS
The motor lead speed connections are as follows:
SIZERATED AIRFLOWHIGH AIRFLOW
024Ta p 1Ta p 3
030Ta p 2Ta p 4
036Ta p 1Ta p 3
042Ta p 2Ta p 4
RATED AIRFLOWHIGH AIRFLOW
SIZE
048Ta p 1Ta p 3Ta p 2Ta p 4
060Ta p 1Ta p 3Ta p 2Ta p 4
Low
Stage
High
Stage
Low
Stage
A08406
A08412
High
Stage
9
Step 5 — Unit Controls
All compressors have the following internal--protection controls.
HIGH--PRESSURE RELIEF VALVE
This valve opens when the pressure differential between the low
and high side becomes excessive.
LOSS OF CHARGE SWITCH
Located on the outdoor liquid line is a low--pressure switch which
functions as a loss--of-- charge switch. This switch contains a
Schrader core depressor. This switch opens at 7 psig and closes at
22 psig. No adjustment is necessary.
COMPRESSOR OVERLOAD
This overload interrupts power to the compressor when either the
currentorinternaltemperaturebecomeexcessive,and
automatically resets when the internal temperature drops to a safe
level.
This overload may require up to 60 minutes (or longer) to reset;
therefore, if the internal overload is suspected of being open,
disconnect the electrical power to the unit and check the circuit
through the overload with an ohmmeter or continuity tester.
Step 6 — Compressor Rotation
664B
On 3--Phase units it is important to be certain compressor is
rotating in the proper direction. To determine whether or not
compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure
should rise, as is normal on any start--up.
If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:
1. Turn off power to the unit and tag disconnect.
2. Reverse any two of the unit power leads.
3. Turn on power to the unit.
The suction and discharge pressure levels should now move to
their normal start--up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes an elevated level of noise and does not provide
cooling.
Step 7 — Sequence of Operation
FAN O PERATI ON
The FAN switch on the thermostat controls indoor fan operation.
When the FAN switch is placed in the ON position, the IFR
(indoor--fan relay) is energized through the G terminal on the
thermostat. The normally-- open contacts close, which then provide
power to the indoor (evaporator) fan motor (IFM). The IFM will
run continuously when the FAN switch is set to ON.
When the FAN switch is set to AUTO, the thermostat deenergizes
the IFR (provided there is not a call for cooling). The contacts open
and the IFM is deenergized. The IFM will be energized only when
there is a call for cooling, in heat pump heating mode or if the unit
is equipped with accessory electric heat, the indoor--fan motor will
also run while the accessory electric heat is energized.
NOTE:Some units are equipped with a time--delay relay. On
these units, the indoor fan remains on for 30 seconds after G or Y
is deenergized.
COOLING OPERATION (SIZES 024--042)
With a call for cooling (Y/Y2), the indoor fan energizes
immediately whereas the contactor energizes after a 5 minute time
delay (in case of initial start--up) starting the compressor and the
outdoor fan motor. When the cooling demand is met, Y/Y2
de-- energizes, shutting the compressor, indoor fan and the outdoor
fan.
COOLING OPERATION (SIZES 048 AND 060)
These units utilize a 2 stage indoor thermostat. With a first stage
call for cooling (Y1), the indoor fan (low stage) energizes
immediately whereas the contactor energizes after a 5 minute time
delay (in case of an initial start--up) starting the compressor (low
stage) and the outdoor fan motor. If the low stage operation cannot
satisfy the cooling demand, the second stage cooling (Y2)
energizes switching the compressor into high stage cooling through
energizing an internal solenoid valve inside the scroll compressor
and switching the indoor fan into high stage. When second stage
cooling is satisfied, Y2 de--energizes switching the compressor and
the indoor fan into low stage cooling. When the low stage cooling
demand is met, Y1 de--energizes shutting the compressor, indoor
fan and the outdoor fan.
HEATING OPERATION (SIZES 024--042)
With a call for heating (Y1), the indoor fan (low stage) energizes
immediately whereas the contactor energizes after a 5 minute time
delay (in case of initial start--up) starting the compressor and the
outdoor fan motor. If Y/Y2 cannot satisfy the heating demand, the
auxiliary or backup heat (W2) energizes. In case of staged heating,
W3 is energized if the demand is not met. The highest airflow
selected is run while the electric heat is in operation. When heating
demand is met, W3, W2 and Y/Y2 sequentially de-- energize
shutting the compressor, indoor fan and the outdoor fan.
HEATING OPERATION (SIZES 048 AND 060)
With a first stage call for heating (Y1), the indoor fan (low stage)
energizes immediately whereas the contactor energizes after a 5
minute time delay (in case of initial start--up) starting the
compressor (low stage) and the outdoor fan motor. If the low stage
oepration cannot satisfy the heating demand, the second stage
heating (Y2) energizes switching the compressor into high stage
heating through energizing an internal solenoid valve inside the
scroll compressor and switching the indoor fan into high stage. The
auxiliary or backup heat is controlled by a third stage (W2). If the
demand is not met, W3 is energized in case of staged heating.
When heating demand is satisfied, W3, W2 and Y2 sequentially
de--energize switching the compressor and the indoor fan into low
stage heating. When the low stage heating demand is met, Y1
de-- energizes shutting the compressor, indoor fan and the outdoor
fan.
CONTINUOUS FAN
With the continuous Indoor fan option selected on the thermostat,
G is continuously energized. In case of 024--042 units, the selected
airflow setting is provided. In case of 048 and 060 units, the
system runs low stage (Y1) airflow for continuous fan operation.
DEFROST
Defrost board (DB) is a time and temperature control, which
includes a field--selectable time period between checks for defrost
(30, 60, 90 and 120 minutes). The time period is factory-- set at 60
minutes and should only be adjusted by a trained service person.
Electronic timer and defrost cycle start only when contactor is
energized and defrost thermostat (DFT) is closed.
Defrost mode is identical to Cooling mode. The outdoor fan motor
stops because of “OF1” and “OF2” contacts opening on the defrost
board, a bank of optional electric heat turns on to warm air
supplying the conditioned space.
ELECTRIC RESISTANCE HEATING
If accessory electric heaters are installed, on a call for “Emergency
Heat” the thermostat energizes W which energizes the heater relay
and in turn energizes the electric heaters. The IFR is energized
which starts the indoor--fan motor. If the heaters are staged, W2 is
energized when the second stage of heating is required. When the
need for heating is satisfied, the heater and IFM are de--energized.
Fig. 15 -- Typical Three--Phase Unit Electrical Diagram (Sizes 030--042)
13
A06325
664B
Fig. 16 -- Typical Three--Phase Unit Electrical Diagram (Sizes 048--060)
14
A06326
Fig. 17 -- Single--Phase Accessory Electric Heater Wiring
664B
A05209
Fig. 18 -- Three--Phase Accessory Electric Heater Wiring
15
A06327
Table 4 – Dry Coil Air Delivery* Horizontal Discharge
(Deduct 10 percent for 208 Volt Operation)
230 VOLT HORIZONTAL DISCHARGE
UNIT
SIZE
024
030
036
042
664B
048
060
*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occuratairflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This unit should be
inspected at least once each year by a qualified service person. To
troubleshoot unit, refer to Troubleshooting Chart in back of book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
!
WARNING
PERSONALINJURYANDUNITDAMAGE
HAZARD
Failure to follow this warning could result in personal
injury or death and possible unit component damage.
The ability to properly perform maintenance on this
equipment requires certain expertise, mechanical skills,
tools and equipment. If you do not possess these, do not
attempt to perform any maintenance on this equipment,
other than those procedures recommended in the Owner’s
Manual.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each
cooling season. Clean when necessary.
4. Check electrical connections for tightness and controls for
proper operation each cooling season. Service when
necessary.
5. Ensure electric wires are not in contact with refrigerant
tubing or sharp metal edges.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow these warnings could result in personal
injury or death:
1. Turn off electrical power to the unit before performing
any maintenance or service on this unit.
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact
with the unit.
Step 1 — Air Filter
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the
same dimensional size and type as originally installed. See Table 1
for recommended filter sizes.
Inspect air filter(s) at least once each month and replace
(throwaway-- type) or clean (cleanable-- type) at least twice during
each cooling season and twice during the heating season, or
whenever the filter becomes clogged with dust and lint.
Step 2 — Unit Top Removal
NOTE: When performing maintenance or service procedures that
require removal of the unit top, be sure to perform all of the routine
maintenance procedures that require top removal, including coil
inspection and cleaning, and condensate drain pan inspection and
cleaning.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect and tag electrical power to the unit before
removing top.
17
Only qualified service personnel should perform maintenance and
service procedures that require unit top removal.
Refer to the following top removal procedures:
1. Remove screws on unit top cover surface. (Save all screws.)
2. Remove screws on unit top cover flange. (Save all screws.)
3. Lift top from unit carefully. Set top on edge and make sure
that top is supported by unit side that is opposite duct (or
plenum) side.
4. Carefully replace and secure unit top to unit, using screws
removed in Steps 1 and 2, when maintenance and/or service
procedures are completed.
Step 3 — Indoor Blower and Motor
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.
!
WARNING
ELECTRICAL SHOCK HAZARD
664B
Failure to follow this warning could result in personal
injury or death.
Disconnect and tag electrical power to the unit before
cleaning and lubricating the blower motor and wheel.
To clean the blower wheel:
1. Remove the blower housing:
a. Remove the screws on the external side of the duct
panel that fasten the housing to the duct panel assembly.
b. Remove the side access panel and unscrew the
mounting bracket that fastens the blower housing to the
internal partition panel fo the control box assembly.
c. Make sure that the blower housing is supported by hand
before completely removing the mounting bracket.
d. Slide the blower housing from the rails of the duct panel
and place it outside the unit.
2. Remove the blower wheel from the housing:
a. Loosen the set screw which secures the wheel to the
motor shaft.
b. Loosen the three mounting legs of the motor by
removing the bolts that fasten themounting legs to the
housing.
c. Slide out the motor assembly (motor, belly band and the
3 mounting legs) from the hub of the wheel.
d. Remove the filler panel at the discharge end of the
blower housing by removing the two screws that fasten
it to the housing.
e. Remove the wheel form the housing.
3. Remove the caked on dirt from the wheel and the motor
using a brush.
4. Remove lint and dirt accumulations from the wheel and
housing with a vacuum cleaner, using a soft brush
attachment.
5. Remove grease and oil with a mild solvent.
6. Reassemble
a. Slip the wheel back in the housing with the hub set
screw parented in the correct direction.
b. Install the filler panel.
c. Reinsert the motor assembly in the wheel hub and align
the mounting legs with the housing mounting hold
locations.
d. Tighten the mounting bolts to fasten the motor assembly
with the housing.
e. Center the wheel in the housing by sliding it, align the
flat end of the shaft with the set screw and tighten the
set screw.
f. Slide back the blower housing into the mounting rails in
the duct panel and install the mounting bracket back in
its position.
g. Install the screws on the external side of the duct panel
Table 8 – Accessory Electric Heat Pressure Drop (in. wc)
HEATER
kW
5--200.060.080.100.130.150.180.200.230.25
6008001000120014001600180020002200
CFM
18
Step 4 — Outdoor Coil, Indoor Coil, and
Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent and water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit. On
units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain trough is restricted, clear it with a
“plumbers snake” or similar probe device.
Step 5 — Outdoor Fan
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of
unit.
1. Shut off unit power supply and install lockout tag.
2. Remove outdoor--fan assembly (grille, motor, motor cover,
and fan) by removing screws and flipping assembly onto
unit top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 19.
5. Tighten setscrews.
6. Replace outdoor-- fan assembly.
15/32-in. (12 mm)
A08004
Fig. 19 -- Outdoor Fan Adjustment
Step 6 — Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring.
Check all electrical connections for tightness. Tighten all screw
connections. If any smoky or burned connections are noticed,
disassemble the connection, clean all the parts, re--strip the wire
end and reassemble the connection properly and securely.
Check to ensure no wires are touching refrigerant tubing or sharp
sheet metal edges. Move and secure wires to isolate from tubing
and sheet metal edges.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
eachelectricalcomponentwiththeproperelectrical
instrumentation. Refer to the unit wiring label when making these
checks.
Step 7 — Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil
accumulation annually. Detecting oil generally indicates a
refrigerant leak.
If oil is detected or if low performance is suspected, leak test all
refrigerant tubing using an electronic leak detector, or liquid--soap
solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.
Step 8 — Indoor Airflow
The heating and/or cooling airflow does not require checking
unless improper performance is suspected. If a problem exists, be
sure that all supply-- and return--air grilles are open and free from
obstructions, and that the air filter is clean.
Step 9 — Metering Devices
Refrigerant cooling metering device is an AccuRater (024--042) or
TXV (048 and 060) located upstream of the indoor coil distributor
assembly. Refrigerant heating mode metering device is an
AccuRater located upstrem of the outdoor coil distributor
assembly.
Step 10 — Liquid Line Strainers
The liquid line strainers (to protect metering devices) are made of
wire mesh and are located in the liquid lines on the inlet side of the
metering devices.
Step 11 — High Flow Valves
High flow valves are located on the compressor hot gas and suction
tubes. Large black plastic caps distinguish these valves with
O-- rings located inside the caps. These valves can not be accessed
for service in the field. Ensure the plastic caps are in place and tight
or the possibility of refrigerant leakage could occur.
TROUBLESHOOTING
Refer to the Troubleshooting Chart (Table 9) for troubleshooting
information.
START--UP CHECKLIST
Use the Start--Up Checklist at the back of this manual.
664B
19
OUTDOOR COIL
INDOOR COIL
B
664B
A
ACCUMULATOR
COMPRESSOR
Check Valves
A
Open
B
Closed
C
Open
D
Closed
LCSLoss of Charge Switch
LEGEND
Acutrol Metering Device
Check Valve (Arrow indicates direction of flow)
HEATING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is
directed to the cooling liquid line check valve. It is then condensed
and directed through subcooling circuits and out to the strainer
and the check valve in the heating liquid line.
2. The refrigerant then feeds the outdoor coil through the Acutrol
metering device on each circuit.
3. Each circuit evaporates the refrigerant and the circuits are combined in the outdoor header with someof the circuits flowing through
the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator,
and back to the compressor.
C95045
OUTDOOR COIL
A
ACCUMULATOR
COMPRESSOR
Check Valves
A
Closed
B
Open
C
Closed
D
Open
LCSLoss of Charge Switch
LEGEND
Acutrol Metering Device
Check Valve (Arrow indicates direction of flow)
COOLING CYCLE
1. Hot gas from compressor flows through the 4-way valve and is
directed to the heating liquid line check valve. It is then condensed and subcooled throughconverging circuits.Refrigerant leaves
the outdoor coil by way of the strainer and the check valve in the
cooling liquid line.
2. The refrigerant then feeds the indoor coil through the Acutrol
metering device on each circuit.
3. Each circuit evaporates the refrigerant and the circuits are combined in the indoor coil header with some of the circuits flowing
through the check valve.
4. The refrigerant then flows through the 4-way valve, accumulator,
and back to the compressor.
C95044
20
Table 9 – Troubleshooting Chart
SYMPTOMCAUSEREMEDY
Power failureCall power company
Fuse blown or circuit breaker trippedReplace fuse or reset circuit breaker
Defective contactor, transformer, control relay, or
high--pressure, loss--
Compressor and outdoor fan
will not start
Compressor will not start but condenser fan
runs
Three--phase scroll compressor (size 030--
060 unit) has a low pressure differential3--phase power leads to the unit
Compressor cycles (other than normally satisfying) cooling/heating calls
Compressor operates continuously
Excessive head pressure
Head pressure too low
Excessive suction pressure
Suction pressure too low
of--charge or low--pressure switch
Insufficient line voltageDetermine cause and correct
Incorrect or faulty wiringCheck wiring diagram and rewire correctly
Thermostat setting too low/too highReset Thermostat setting
Faulty wiring or circuit
Loose connections in compressor
Compressor motor burned out, seized, orDetermine cause
internal overload openReplace compressor
Defective run capacitor, overload, or PTC (positive
temperature coefficient) thermistor
One leg of 3--phase power dead
Low input voltageDetermine cause and correct
Scroll compressor is rotating in the wrong direction
Refrigerant overcharge or undercharge
Defective compressorReplace and determine cause
Insufficient line voltageDetermine cause and correct
Blocked outdoor coilDetermine cause and correct
Defective run/start capacitor, overload or start relayDetermine cause and replace
Faulty outdoor fan motor or capacitorReplace
Restriction in refrigerant systemLocate restriction and remove
Dirty air filterReplace filter
Unit undersized for loadDecrease load or increase unit size
Thermostat temperature set too lowReset Thermostat setting
Low refrigerant chargeLocate leak, repair, and recharge
Air in system
Outdoor coil dirty or restrictedClean coil or remove restriction
Dirty air filterReplace filter
Dirty indoor or outdoor coilClean coil
Refrigerant overchargedRecover excess refrigerant
Air in system
Indoor or outdoor air restricted or air short--cyclingDetermine cause and correct
Low refrigerant chargeCheck for leaks, repair and recharge
Restriction in liquid tubeRemove restriction
High Heat loadCheck for source and eliminate
Reversing valve hung up or leaking internallyReplace valve
Refrigerant overchargedRecover excess refrigerant
Dirty air filterReplace filter
Low refrigerant chargeCheck for leaks, repair and recharge
Metering device or low side restrictedRemove source of restriction
Insufficient coil air flowCheck filter–replace if necessary
Temperature too low in conditioned areaReset Thermostat setting
Outdoor ambient below 55°F(13°C)Install low--ambient kit
Filter drier restrictedReplace
Replace component
Check wiring and repair or replace
Determine cause and replace
Replace fuse or reset circuit breaker
Determine cause
Correct the direction of rotation by reversing the
Recover refrigerant, evacuate system, and recharge to capacities shown on rating plate
Recover refrigerant, evacuate system, and recharge
Recover refrigerant, evacuate system, and recharge
664B
21
START--UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No ............................................................................................................................................................
Serial No .............................................................................................................................................................
Date .....................................................................................................................................................................
____ Verify that all packing materials have been removed from unit.
____ Verify that condensate connection is installed per installation instructions.
____ Check all electrical connections and terminals for tightness.
____ Check wire proximity to refrigerant tubes and sheet metal edges.
____ Check that indoor (indoor) air filter is clean and in place.
____ Verify that unit installation is level.
____ Check fan wheel propeller for location in housing and setscrew tightness.
Indoor Fan Amps: __________ Outdoor Fan Amps: __________
TEMPERATURE--Cooling Mode
Outdoor Air Temperature: __________ DB ____________WB
Return-- Air Temperature: __________ DB __________ WB
Cooling Supply Air: __________DB___________WB
Outdoor Air Temperature: __________ DB ____________WB
Return-- Air Temperature: __________ DB __________ WB
Cooling Supply Air: __________DB___________WB