Bryant 619FNQ, 619FNF User Manual

installation, start-up and
619FNF
service instructions
IN-CEILING CASSETTE FAN COIL UNITS
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
I. Step 1 — Complete Pre-Installation Checks . . . . . . 2
II. Step 2 — Locating and Mounting the Unit. . . . . . . . 6
III. Step 3 — Locating and Mounting the Room
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
IV. Step 4 — Complete Refrigerant Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
V. Step 5 — Make Electrical Connections . . . . . . . . . 11
INSTALLATION OPTIONS . . . . . . . . . . . . . . . . . . . . . . . .19-22
I. Fresh Air Intake . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
II. Conditioned Air Supply to Adjacent Room. . . . . . 19
III. Room Controller Configuration Setup . . . . . . . . . . 21
IV. Louver Mode Selection . . . . . . . . . . . . . . . . . . . . . . 21
V. Main Board Configuration. . . . . . . . . . . . . . . . . . . . 21
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22,23
SERVICE AND MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . 23
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .23,24
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install or service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe safety precautions in litera­ture, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extin­guisher available. Read these instructions thoroughly. Con­sult local building codes and the National Electrical Code (NEC) for special installation requirements.
619FNQ
Cancels: New II 619F-18-1
4/1/06
GENERAL
CAUTION: This system uses Puron® refrigerant
(R-410A), which has higher pressures than R-22 and other refrigerants. No other refrigerant may be used in this system. All equipment must be designed to handle R-410A refrigerant. If unsure about equipment, consult the equipment manufacturer.
CAUTION: Do not operate the unit without a filter or with the grille removed. Damage to the unit or per­sonal injury may result.
These instructions cover the installation, start-up and service of in-ceiling cassette fan coil units. See Fig. 1.
The following accessories can be used with 619FNF, FNQ units. See the price pages for part numbers and additional information for the following accessories:
• photocatalytic and electrostatic filter with mount
• air supply outlet obstruction kit
• wired room controller
• room controller wiring kit for multiple units
• zone manager kit for multiple units
• zone manager
• infrared remote kit
WAR NING : Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause serious personal injury.
Fig. 1 — 619FNF, FNQ Unit
INSTALLATION
I. STEP 1 — COMPLETE PRE-INSTALLATION CHECKS
A. Unpack Unit (See Fig. 1)
Move the unit to final location. The grille panel and the remote control are packed separately for maximum protec­tion. Remove unit from carton, being careful not to lift the unit by the condensate drain discharge pipe or by the refrig­erant connections. Handle by the four corners of the unit. See Table 1 for field-supplied installation materials required for installation.
B. Inspect Shipment
File a claim with the shipping company if shipment is dam-
C. Consider System Requirements
Consult local building codes and NEC for special installation requirements. Use only designated indoor units with outdoor units. See Tables 2-4B.
See Fig. 2 for unit dimensions. Allow sufficient space for air­flow clearance, wiring, refrigerant piping, and servicing units.
Avoid mounting the unit in areas that are:
• exposed to direct sunlight
• too close to heat sources
• damp or in areas exposed to water
• located in areas that could obstruct air circulation, such as near curtains or furniture
aged or incomplete. Check the unit nameplates to ensure units match job requirements.
Table 1 — Field-Supplied Installation Materials
NAME SPECIFICATIONS
Connection Pipe
Wall Sleeve Wall Cap Finishing Tape PVC Film Fastening Tape Tube Insulation Drain Hose 1 in. ID Sealer Putty
Outdoor Power Supply Cable
Control Wire Electrical Connecting Cable Between Indoor and Outdoor Unit
Wire Nuts Conduit
LEGEND
AWG — American Wire Gage NEC — National Electrical Code
619FNF018,024/FNQ01824: 619FNF, FNQ03036: 3/4 in. (Mixed Phase)/3/8 in. (Liquid)
619FNF018-03036: AWG 14 619FNQ01824-03036: AWG 12
Cable Type: AWG 22 synthetic rubber insulation with Neoprene coating, according to NEC codes.
Table 2 — Matching Indoor Units to Outdoor Units*
SYSTEM
TYPE
Cooling Only
Cooling with
Electric Heat
Heat Pump
*All units use R-410A refrigerant only.
SYSTEM SIZE
018 538ENF018000 619FNF018000 619FN9005 024 538ENF024000 619FNF024000 619FN9006 030 538ENF030000 619FNF030360 619FN9006 036 538ENF036000 619FNF030360 619FN9006 018 538ENF018000 619FNQ018240 619FN9006 024 538ENF024000 619FNQ018240 619FN9006 030 538ENF030000 619FNQ030360 619FN9006 036 538ENF036000 619FNQ030360 619FN9006 018 538QNF018000 619FNQ018240 619FN9006 024 538QNF024000 619FNQ018240 619FN9006 030 538QNF030000 619FNQ030360 619FN9006 036 538QNF036000 619FNQ030360 619FN9006
Table 3 — AccuRator* Control Sizes and Refrigerant Charge Requirements
SYSTEM
TYPE
Cooling Only
Cooling with
Electric Heat
Heat Pump
*AccuRator controls are for outdoor units. See the outdoor installation instructions for more information.
†The outdoor unit is either fully charged or under charged from the factory.
SYSTEM
SIZE
018 0.049 B 4.8 0.0 024 0.057 B 5.3 1.2 030 0.061 B 5.0 3.0 036 0.074 B 7.0 2.3 018 0.049 B 4.8 0.0 024 0.057 B 5.3 1.2 030 0.061 B 5.0 3.0 036 0.074 B 7.0 2.3 018 0.051 0.046 B 5.5 0.0 024 0.055 0.053 B 6.9 0.0 030 0.063 0.055 B 10.7 1.8 036 0.07 0.063 B 10.5 0.0
COOLING
ACCURATOR
OUTDOOR
UNIT
HEATING
ACCURATOR
ACCURATOR
TYPE
5
/8 in. (Mixed Phase)/3/8 in. (Liquid)
INDOOR UNIT
MODEL NUMBER
FAC TORY
CHARGE† (lb)
INDOOR UNIT
GRILLE ITEM NUMBER
ADDITIONAL FIELD
CHARGE REQUIRED† (lb)
—2—
)892("4/3-11
)522("46/55-8
)082("11
Supply air
1? 10-5/8??(575)
051( "23/92-5
Ø)
Return air
619FNF018
)021("4/3-4
Supply air
1
-
3/16
(30)
1' -10-5/8"(575)
3/8"(9)
2"(52)
)201("4
Ø 2-3/14" (70)
)351
( "6
)34("6
1
/11-1
)85
1
("23/7-7- '0
2'-4-11/32"(720)
1 -5/16"(49)
2-13/64"(56)
)342("61/9- 9
"
)
6
5
1/5
3 1
- 5 (
1'-9-21/32"(550)
)515("23/98-'1
"
Ø
2
(50)
"
2'-8-1/2"(825)
)5 0
3
(
'1
Supply air Supply air
)
05
1
("
23
/9
2-5
Ø
Return air
1"(25)
619FNF024, 03036 / 619FNQ01824, 03036
) 0 5 1
(
" 2 /3 9 2
­5
Ø3-15/16"
(100)
1-7/8"(47)
2'-8-1/2"(825)
) 0 21("4/3
­4
2
-
5
8/
"
7
("8/
)84
)8 2
1
(" 5
)351("6
) 42("6
1/ 51
(
6
6
)
)94("
6
1/51-1
)25
"6
1
11-57/64"
(
1'-11-7/16"(595)
(302)
1 -31/32"
(50)
) 31
8
(" 8
-'2
)732("23/11-9
) 8 6 1
(
" 8/
5
-6
)06
9
(" 4
6/15-1-'3
NOTE: Dimensions in ( ) are in mm.
5
2
(
"1
Ø)
Fig. 2 — Unit Dimensions
—3—
Table 4A — 619FNF Physical Data
SYSTEM SIZE 018 024 030 036 NOMINAL CAPACITY (Btuh) 17,000 23,600 29,000 36,400 OPERATING WEIGHT (lb) 49 91 95 95 SEER 13 REFRIGERANT* R-410A
Control (Cooling) AccuRator Control
INDOOR FAN Direct Drive Centrifugal
Rpm/Cfm High 1000/470 440/690 660/910 660/910 Rpm/Cfm Medium 890/420 360/560 550/760 550/760 Rpm/Cfm Low 730/340 300/470 470/670 470/670 Motor Watts 120 110 210 210 Blowers Quantity...Size (in.) 1...11.1
INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 3.2 4.8 4.6 4.6 No. of Rows 2233 Fins/in. 22 18 18 18 Circuits 5 6 10 10
FILTERS Cleanable
Quantity...Size (in.) 1...17 x 16
AIRSWEEP
Horizontal Auto/Preset
OPERATING LIMITS
Cooling (Min/Max) 55 F/125 F
CONTROLS Integrated Microprocessor
Remote Controller Options Wireless, CRC Diagnostics Ye s Defrost Method Demand Defrost Timer Mode Ye s Warm Start Feature Ye s Tes t Mo de Ye s Freeze Protection Ye s Dehumidification Mode Ye s Fan Mode High/Medium/Low/Auto Auto Changeover Ye s Auto Restart Ye s Control Voltage 24 System Voltage 208/230
REFRIGERANT LINES
Connection Type Flare Flare Flare Flare Mixed-Phase Line (in.) OD Vapor Line (in.) OD Max Length (ft) 200 200 200 200 Max Lift (Fan Coil Above) (ft) 60 60 60 60
3
/
8
5
/
8
Max Lift (Fan Coil Below) (ft) 60 60 60 60
CONDENSATE DRAIN SIZE (in.) 1111
LEGEND
CRC — Carrier Room Controller SEER — Seasonal Energy Efficiency Ratio
*See Table 3 for factory charge and additional field charge requirements.
3
/
8
5
/
8
3
/
8
3
/
4
3
/
8
3
/
4
—4—
Table 4B — 619FNQ Physical Data
SYSTEM SIZE 018 024 030 036
NOMINAL CAPACITY (Btuh)
Heat Pump
Cooling 17,900 22,600 29,200 33,400 Heating 16,800 20,800 27,400 32,400
Cooling with Electric Heat 17,000 22,600 29,000 36,000 SEER 13 HSPF 7.7 OPERATING WEIGHT (lb) 91 91 95 95 REFRIGERANT* R-410A
Control (Cooling) AccuRator Control
Control (Heating) AccuRator Control INDOOR FAN Direct Drive Centrifugal
Rpm/Cfm High 440/690 440/690 660/910 660/910
Rpm/Cfm Medium 360/560 360/560 550/760 550/760
Rpm/Cfm Low 300/470 300/470 470/670 470/670
Motor Watts 110 110 210 210
Blowers Quantity...Size (in.) 1...18 INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 4.8 4.8 4.6 4.6
No. of Rows 2233
Fins/in. 18 18 18 18
Circuits 6 6 10 10 FILTERS Cleanable
Quantity...Size (in.) 1...24 x 23 AIRSWEEP
Horizontal Auto/Preset OPERATING LIMITS
Heating (Min/Max) 15 F/75 F
Cooling (Min/Max) 55 F/125 F CONTROLS Integrated Microprocessor
Remote Controller Options Wireless CRC
Diagnostics Ye s
Defrost Method Demand Defrost
Timer Mode Ye s
Warm Start Feature Ye s
Tes t Mo de Ye s
Freeze Protection Ye s
Dehumidification Mode Ye s
Fan Mode High/Medium/Low/Auto
Auto Changeover Ye s
Auto Restart Ye s
Control Voltage 24
System Voltage 208/230 REFRIGERANT LINES
Connection Type Flare Flare Flare Flare
Mixed-Phase Line (in.) OD
Vapor Line (in.) OD
Max Length (ft) 200 200 200 200
Max Lift (Fan Coil Above) (ft) 60 60 60 60
3
/
8
5
/
8
3
/
8
5
/
8
Max Lift (Fan Coil Below) (ft) 60 60 60 60 CONDENSATE DRAIN SIZE (in.) 1111
LEGEND
CRC Carrier Room Controller HSPF — Heating Seasonal Performance Factor SEER — Seasonal Energy Efficiency Ratio
*See Table 3 for factory charge and additional field charge requirements.
5
/
16
3
/
8
3
/
4
3
/
8
3
/
4
—5—
II. STEP 2 — LOCATING AND MOUNTING THE UNIT
A. Locating the Unit
Install the unit as centrally as possible in the room. The air-
direction can be controlled by the remote control (where
flow used) or automatically, according to the unit operating mode (cooling or heating). Controlling the airflow automatically will ensure optimum distribution of the air in the room.
In Cooling mode, the louvers should be positioned so that the air is directed towards the ceiling. Refer to Fig. 3. In Heating mode, the louvers should be positioned so that the air is directed toward the floor to prevent layers of hot air forming close to the ceiling. Refer to Fig. 3. The louvers will be auto­matically positioned when the louvers are set to Automatic mode. Alternatively, the louvers can be placed in intermedi­ate positions (with infrared remote accessory kit only) or allowed to move continuously (Swing mode).
In order to allow easy and rapid installation and mainte­nance, ensure that the unit is mounted in a location that is easily accessible.
Restricting Air Outlets
A maximum of two air outlets can be restricted at one time. See Fig. 3. The air supply outlet obstruction accessory kit can be used to obstruct air outlets. Contact your local dealer for more information.
B. Mounting the Unit
Use a stacker to lift the unit to the installation location. Refer to Fig. 4. If the mounting location is in a plaster board ceiling, the maximum dimensions of the unit housing cutout must not exceed 2 ft, 2 in. square for 619FNF018 units and 2 ft, 11 in. square for 619FNF024, 03036 and 619FNQ01824, 03036 units.
NOTE: In rooms with high humidity, brackets should be insulated using self-adhesive insulation.
Mark the position of the hangers, refrigerant lines and con­densate drain pipe, power supply cables and remote control
cable (see Fig. 2 for dimensions). The cardboard template (supplied with the unit) may be used as a guide. Depending on the type of ceiling, the hangers can be fixed as shown in Fig. 5.
Once the threaded hangers have been positioned, do not tighten the nuts. Insert the washers as shown in Fig. 5. First position the refrigerant lines, which will be connected in the Complete Refrigerant Piping Connections section. Remove the “T” bar in the ceiling to facilitate installation. See Fig. 6.
Carefully lift the unit (without the frame) using the four sus­pension brackets (or the four corners), and insert it into the false ceiling. If the “T” bar cannot be removed from the ceil­ing the unit may need to be tilted. See Fig. 7.
NOTE: Tilting the unit may only be carried out with false
13
ceilings with a minimum height of 11 ft-
/16 inches.
Align and level the unit by adjusting the nuts and locknuts on the threaded hangers, maintaining a distance of 1 in. to
3
/16 in. between the sheet metal body and the underside of
1 the false ceiling. See Fig. 8. Reposition the “T” bar and align the unit in relation to the bar by tightening the nuts and locknuts. After connection of the condensate drain line and the refrigerant lines, carry out a final check to make sure that the unit is level.
Drilling the Hole for Connection Pipes in the External Wall
After positioning the units and determining the connection
3
position, drill a 2
/4 in. hole in the wall. The same hole can be
used as a condensate drain pipe conduit. The hole should
3
have a
/16 in. to 3/8 in. slope toward the outside. Refer to Fig. 9. Insert the plastic conduit. Pass the power connection cables through the conduit. The power connection cables will be connected in the Make Electrical Connections section.
Running the Condensate Drain Piping
To ensure correct condensate water flow, the drain pipe should have a gradient of 2% without obstructions. Addition­ally, a trap of at least 2 in. depth should be made to prevent unpleasant odors from reaching the room.
Heat pump: louver position for correct airflow. Cooling: louver position for correct airflow.
Fig. 3 — Louver Positioning
—6—
Max. 2 louvers closed
Fig. 4 — Positioning Unit
Nut Washers Threaded hangers Wooden frame Nut
Washer Threaded hangers Washer Nut Nut
Fig. 5 — Attaching Hangers to Ceiling
Threaded hangers
False Ceiling
1 to 1-3/16
Spirit Level
Fig. 8 — Align and Level the Unit
"3
m)
÷
m 08/0
"4/ 3-2
7(
Indoor
3/16"
÷
(5
10 m
÷
3/8"
)
m
Outdoor
Fig. 9 — Drilling for Connections
The condensate may be discharged at a maximum height of
7
/8 in. above the unit, as long as the ascending tube is verti-
7 cal and aligned with the drainage flange.
If it is necessary to discharge the condensate from a level
7
above 7
/8 in., install an auxiliary water discharge pump and float valve. A float valve is recommended to stop the com­pressor if there is a fault at the auxiliary pump.
The condensate pipe must be insulated with condensation proof material such as polyurethane, propylene or neoprene
3
/16 in. to 3/8 in. thickness. See Fig. 10.
of
Threaded Hangers
T-Bar
Supension Brackets
"T" bar (to be removed)
Fig. 6 — Threaded Hangers and T Bar
Threaded Hangers
T-Bar
Supension Brackets
Fig. 7 — Positioning Unit in Ceiling
T-Bar
CAUTION: The drain tube extension must be securely fastened to the condensate drain. Failure to do so could result in condensate water dripping on to the floor, which could cause personal injury.
NOTE: If more than one unit is installed in the room, the drain system can be designed as shown in Fig. 10.
Installing the Grille and Frame Assembly
Carefully unpack the assembly and check for damage sus­tained in transport. Attach the assembly to the unit by using the two hooks. See Fig. 11. Tighten the four screws, link the electrical connectors and insert the wires in the cable clamp. Use the screws supplied to fix the frame in to position. See Fig. 12.
Ensure that the frame is not distorted by excessive tighten­ing, that it is aligned with the false ceiling and that there is a seal between the air inlet and outlet. See Fig. 13. Gasket “A” prevents return air from mixing with the supply air and gasket “B” prevents the supply air from leaking into the ceil­ing void. Once the unit is mounted in the ceiling, the gap between the unit frame and the false ceiling must not be
3
more than
/16 in. wide.
—7—
2%
2” (50 mm)
x.
a
m
7-7/8”(200 mm)
Fig. 10 — Condensate Drain Pipe
Frame support brackets
A. Gasket "A" B. Gasket "B"
A AIR B
Fig. 13 — Gasket Location
III. STEP 3 — LOCATING AND MOUNTING THE ROOM CONTROLLER
WARNING: Electrical shock can cause personal
injury and death. Shut off all power to this equipment during installation. There may be more than one dis­connect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
Fig. 11 — Attach Frame Assembly
Safety cord Cable clamp Power connection cables from unit Power connection cables from frame
Frame support screws
Fig. 12 — Fix Frame in Position
A. Locating the Room Controller
See Fig. 14 for room controller dimensions. If the air sensor in the room controller is going to be used, the room controller should be located by considering the following:
• Position controller with a minimum clearance of 5 ft from the floor.
• Locate the unit in the same area as the fan coil unit; pref­erably on an inside partitioning wall.
• Locate on a section of the wall without pipes or ductwork.
Do not locate close to a window, on an outside wall, or next to a door leading to the outside.
Do not locate where the controller is exposed to direct light and heat from a lamp, sun, fireplace, or other tem­perature-radiating object that may cause a false reading.
Do not locate close to, or in direct airflow of, a heating or cooling supply.
Do not locate in areas with poor circulation, such as behind a door or in an alcove.
NOTE: Do not exceed 500 ft of network wiring when mount­ing the room controller.
—8—
Loading...
+ 16 hidden pages