Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as
cleaning and replacing filters. All other operations should be
performed by trained service personnel. When working on air
conditioning equipment, observe safety precautions in literature, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly. Consult local building codes and the National Electrical Code
(NEC) for special installation requirements.
619ENQ
Sizes 018-036
Cancels: NewII 619E-18-4
4/1/06
GENERAL
CAUTION: This system uses R-410A, which has
higher pressures than R-22 and other refrigerants. No
other refrigerant may be used in this system. All
equipment must be designed to handle R-410A refrigerant. If unsure about equipment, consult the equipment manufacturer.
These instructions cover the installation, start-up and service
of cooling only and heat pump duct-free systems.
INSTALLATION
I. STEP 1 — COMPLETE PRE-INSTALLATION CHECKS
A. Unpack Units (See Fig. 1)
Move the unit to final location. Remove unit from carton,
being careful not to damage service valves and grilles. See
Table 1A for installation materials included in shipment and
see Table 1B for field supplied materials needed to complete
the installation.
B. Inspect Shipment
File a claim with the shipping company if shipment is damaged or incomplete. Check the unit nameplate to ensure unit
matches the job requirements.
C. Consider System Requirements
Consult local building codes and NEC for special installation
requirements. Use only designated indoor units with outdoor
units. See Tables 2 and 3.
WAR NING : Before installing or servicing system,
always turn off main power to system. There may be
more than one disconnect switch. Turn off accessory
heater power if applicable. Electrical shock can cause
serious personal injury.
Fig. 1 — 619ENF,ENQ Units
Page 2
Table 1A — Installation Materials — Included In Shipment
DESCRIPTIONQTYUSAGE
Wall Hanging Bracket1For indoor unit installation.
Screws, 4xL102For affixing unit and hanging bracket.
TypeR-410A
Control Device (Cooling)Accurator Piston at Outdoor Unit
Control Device (Heating)Accurator Piston at Outdoor Unit
System Charge Required (lb)*6.06.37.410.5
INDOOR FAN
Rpm/Cfm (High)1335/6451335/6451030/7301200/900
Rpm/Cfm (Med)1120/5251120/525930/6301050/750
Rpm/Cfm (Low)1000/4601000/460830/530900/600
Motor Watts64647474
Blowers Quantity...Size1...4.0 x 33.71...4.0 x 33.72...4.2 x 23.52...4.2 x 23.5
INDOOR COIL
Face Area (sq ft)3.03.04.94.9
No. Rows2222
FPI (619ENF/ENQ)16/1616/2018/1818/18
Circuits5599
FILTERS
Quantity...Size (in.)2...12.5 x 16.1 2...12.5 x 16.1 3...17.3 x 16.1 3...17.3 x 16.1
AIR SWEEP
Cooling (Min/Max)59 F wb, 70 F db/74 F wb, 90 F db
CONTROLSIntegrated Microprocessor
Remote Controller OptionsWireless, CRC
DiagnosticsYe s
Defrost MethodDemand Defrost
Timer ModeYe s
Warm Start FeatureYe s
Test ModeYe s
Freeze ProtectionYe s
Dehumidification ModeYe s
Fan ModeYes
Auto ChangeoverYe s
Auto RestartYe s
Control Voltage24v
System Voltage208/230
REFRIGERANT LINES
Connection TypeFlare
Mixed Phase Line (in.) OD
Vapor Line (in.) OD
Max Length (ft)200
Max Lift (Fan coil above) (ft)60
Max Drop (Fan coil below) (ft)60
CONDENSATE DRAIN
Size (in.)
LEGEND
CRC — Carrier Room Controller
db— dry bulb
FPI — Fins Per Inch
wb— wet bulb
*Factory charge is based on 25 ft of interconnecting line.
5.4/5.27.9/7.98.8/9.213.0/12.8
3
/
8
5
/
8
5
/8 OD, 7/16 ID
3
/
8
5
/
8
5
/8 OD, 7/16 ID3/4 OD, 5/9 ID3/4 OD, 5/9 ID
3
/
8
3
/
4
3
/
8
3
/
4
—3—
Page 4
619ENF,ENQ
Fig. 2 — Unit Dimensions
619ENF01824
619ENQ018,024
DIMENSIONS
(in.)
619ENF,ENQ
030, 036
DIMENSIONS
(in.)
A42.557.5
B11.613.4
C7.99.5
4 in.
min.
4 in.
min.
80 in.
min.
8 in.
min.
619ENF,ENQ UNITS
Fig. 3 — Unit Clearances
—4—
Page 5
II. STEP 2 — MOUNT UNIT
Before mounting the 619ENF,ENQ unit on the wall with a
wall hanging bracket, consider how the unit will be
connected to the refrigerant piping. The indoor unit can be
connected in four ways. Refer to Fig. 4 for connection options.
When the piping is connected to points 1, 2 or 4, remove the
knockout either at the side or at the bottom of the unit.
The indoor units are mounted on the wall with a wall hanging bracket. Position the wall hanging bracket so that it is
flush with the wall. See Fig. 5 for service clearances. See
Fig. 6 for wall bracket dimensions.
Complete the following when installing the wall hanging
bracket:
1. Before installing the wall hanging bracket to the wall
remove it from the indoor unit by pushing at the indicated pressure points at the bottom of the unit.
2. Install the wall hanging bracket in a location that is
strong enough to withstand the weight of the unit.
3. Install the wall hanging bracket so that it is level.
Use a plumb line if necessary.
NOTE: Be sure that the wall hanging bracket is level. If the
wall hanging bracket is not level water will leak from the
indoor unit.
4. Fasten the wall hanging bracket to the wall with 4 or
more screw anchors through the holes near the outer
edge of the bracket.
5. Install the wall hanging bracket flush to the wall,
and ensure the bracket does not move.
6. If the unit is removed from the wall hanging bracket
after installing it on to the wall, remove it by pushing up
on the indicated marks at the bottom of the unit body.
III. STEP 3 — COMPLETE REFRIGERANT PIPING
CONNECTIONS
When running the piping for indoor units the piping can be connected as rear piping or side or bottom piping. Refer to Fig. 4.
A. Rear Piping
Route the piping behind the indoor unit so that the piping is
concealed by the unit. For rear piping installation drill a
1
/2 in. diameter hole in the wall at point A or B in Fig. 6. Drill
2
the hole at a slope so that the outside end is lower (
1
/2 in.) than the inside end to ensure optimal drainage. Refer
1
/4 in. to
to Fig. 7. Pass the pipe through the hole.
Fig. 4 — Indoor Unit Piping Configurations
5 in. min.
12 in.
min.
Plumb line
Remove Screw
Fig. 5 — Installing the Wall Bracket
2.1"
1"
2"
A
A
2"
35.4"
2.8"
619ENF01824, 619ENQ018,024
619ENF, ENQ030,036
14.9"
2.8"
13.8
18 in.
min.
3.5"
7.7"
2.1"
B
5.1
"
"
B
5.1"
Fig. 6 — Wall Bracket Dimensions
B. Side or Bottom Piping
Remove the knockout in the unit and pass the piping
through the wall. The pipe should slope downward and away
from the unit to ensure optimal drainage.
C. Routing the Drain Hose and Refrigerant Piping
The drain hose and drain cap are assembled as shown in
Fig. 8 in the factory. To do right-side (1), right-bottom (2) or
right-back (3) piping in Fig. 4 draw the drain hose to rightside piping direction. (It is not always necessary to exchange
the location of drain hose and drain cap.)
1. Tie together the refrigerant piping, the drain hose,
and the electrical connection wire.
2. Route the refrigerant piping in the required direction, and bend carefully avoiding pipe deformation.
3. Bind the drain hose and the electrical connection
wire together with fastening tape.
4. The drain hose should be at the bottom. See Fig. 9
and 10.
5. For left-hand piping, fit the pipes and the wiring into
the recess at the back of the unit.
—5—
Page 6
Drill at Slope
Outdoor side
1/4 to 1/2 in. lower
Indoor side
Fig. 7 — Placement of Connection Piping
Drain Hose
Fig. 8 — Location of Drain Hose and Cap
Drain Cap
2
3
2
3
Fig. 10 — Location of Piping, Hose and Wiring
3. Fix the bottom part of the unit to the wall hanging
bracket by pushing it carefully until the two bracket
hooks fit into the marked places at the base of the
unit until it snaps into place. Refer to Fig. 11.
NOTE:
• Do not crush or kink the indoor piping. Avoid sharp bends
with a bend radius of less than 4 inches.
• Do not over bend the same part of the pipe frequently.
• Do not remove the flare nut from the indoor unit pipe
until the piping is connected.
E. Outdoor Units
Outdoor units may be connected to indoor units using fieldsupplied tubing of refrigerant grade and condition. See
Table 3 for correct line sizes. Do not use less than 10 ft of
interconnecting tubing.
Fig. 9 — Location of Piping
D. Installing the Indoor Unit Body to the Wall Hanging
Bracket
1. Pass the pipes through the wall sleeve and then hook
the indoor unit body on top of the wall hanging
bracket.
2. For left-hand piping, hang the unit on top of the wall
hanging bracket and incline the unit using a tool such
as a screwdriver set between the middle area of the
body and bottom right of the wall hanging bracket.
Connecting the pipe can be done more easily if the
unit is inclined.
CAUTION: DO NOT BURY MORE THAN 36 IN.
OF REFRIGERANT PIPE IN THE GROUND. If any
section of pipe is buried, there must be a 6-in. vertical
rise to the valve connections on the outdoor unit. If
more than the recommended length is buried, refrigerant may migrate to cooler, buried section during
extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start-up.
If either refrigerant tubing or indoor coil is exposed to the
atmosphere, the system must be evacuated following good
refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding
unnecessary turns and bends. Suspend refrigerant tubes so
they do not damage insulation on vapor tube and do not
transmit vibration to structure. Also, when passing refrigerant tubes through a wall, seal the opening so that vibration
is not transmitted to structure. Leave some slack in refrigerant tubes between structure and outdoor unit to absorb
vibration.
—6—
Page 7
Wall
Hanging
Bracket
Hook
Hole
UNIT SIZE
619ENF01824 13.410.6
619ENF03012.2 12.2
619ENF03612.2 12.2
619ENQ01813.4 10.6
619ENQ02413.4 10.6
619ENQ03012.2 12.2
619ENQ03612.2 12.2
DIMENSION
AB
Open the mixed phase valve for 3 seconds, then quickly shut
it to check for possible leaks.
Replace caps and check for leaks using a leak detector specific for R-410A refrigerant.
After the leak test, fully open the three-way valves.
Table 4 — Tightening Torque
VALVE SIZEFLARE NUT (in.-lb)
3
/8 in.372
5
/8 in.487
3
/4 in.885
Retainer
Clip
A
Retainer
Clip
B
Fig. 11 — Wall Hanging Details
F. Make Piping Sweat Connections
Remove plastic caps from liquid and suction service valves.
Use refrigerant grade tubing.
Position tube end downward and cut the tube to the
requested length. Remove the burrs with a reamer. See
Fig. 12.
NOTE: Oil in the compressor is extremely susceptible to
moisture absorption. Keep ends of tubing sealed during
installation.
Remove flare nuts from the unit connections and place them
on the tube end. Flare the tube with the flaring tool. The
flare end must not have any burrs or imperfections. The
length of the flared walls must be uniform. See Fig. 13.
Lubricate the tube end and thread of the flare fitting with
antifreeze oil. Tighten the fitting several turns, then tighten
it fully with two wrenches by applying the tightening torque
indicated in Table 4 and Fig. 14.
Fig. 12 — Removing Burrs
L
L
CAUTION: Insufficient tightening torque will
cause gas leaks. Overtightening the fittings will damage the tube flaring and cause gas leaks. Equipment
damage and personal injury may result.
G. Air Purging And Leak Test
Only use a vacuum pump to purge air from the piping. Refer
to Fig. 15.
IMPORTANT: Do not use the system compressor as a vacuum
pump.
IMPORTANT: Do not use the unit refrigerant gas to purge
the connecting pipes.
Remove the caps from the valves. Create a vacuum with a
vacuum pump connected to the service connection of the suction shut-off valves completely shut until a 50 Pa vacuum
has been reached.
—7—
Fig. 13 — Flared Walls are Equal
3
Adjustable wrench or torque wrench
Outdoor end
Indoor end
Fig. 14 — Tightening Connections
1
2
Page 8
Three-way valve (mixed-phase)
Needle valve
Valve cap
Valve needle
Allen (hex. head) wrench
Two-way valve (liquid)
Flare nut
Liquid line (small diameter)
Mixed-phase line (large diameter)
Indoor unit
Outdoor unit
Vacuum pump
Fig. 15 — Air Purging
IV. STEP 4 — MAKE ELECTRICAL CONNECTIONS A. Power Wiring (Fig. 16-19)
Unit is factory wired for voltage shown on nameplate. Pro-
WAR NING : Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the
possibility of personal injury if an electrical fault
should occur. This ground may consist of electrical
wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC, and local electrical
codes. Failure to follow this warning could result in the
installer being liable for the personal injury of others.
vide adequate, fused disconnect switch within sight from
unit, readily accessible, but out of reach of children. Provision for locking the switch open (off) is advisable to prevent
power from being turned on while unit is being serviced. Disconnect switch, fuses, and field wiring must comply with the
NEC and local code requirements. Use copper wire only
between the disconnect switch and unit. Use minimum 60 C
wire for the field power connection.
Open the fan coil control box panel and connect the indoor
and outdoor units. Connect the wires through the terminals
CAUTION: Unit failure as a result of operation on
improper line voltage or excessive phase imbalance
as shown on the unit label diagram and in Fig. 16-19 and
Table 5. Unit must be grounded.
constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any
applicable Bryant warranty.
WAR NING : Before performing service or mainte-
nance, be sure main power switch is turned OFF and
indoor blower and outdoor fan have stopped. Failure to
do so may result in electrical shock or injury from
rotating fan blades.
—8—
Page 9
Fig. 16 — 619ENF01824 Matched with 538ENF Typical Wiring Schematic
—9—
Page 10
Fig. 17 — 619ENQ018,024 Matched with 538QNF Typical Wiring Schematic
—10—
Page 11
Fig. 18 — 619ENF030,036 Matched with 538ENF Typical Wiring Schematic
—11—
Page 12
Fig. 19 — 619ENQ030,036 Matched with 538QNF Typical Wiring Schematic
FLA— Full Load Amps
MCA — Minimum Circuit Amps per NEC Section 430-24
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
RLA— Rated Load Amps (Compressor)
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
START-UP
I. PRELIMINARY CHECKS
1. Check that all internal wiring connections are tight
and that all barriers, covers, and panels are in place.
2. Field electrical power source must agree with unit
nameplate rating.
3. All service valves must be open.
4. Crankcase heater must be tight on compressor crankcase (if equipped).
II. LEAK TEST
Field piping and fan coil must be leak tested by pressure
method. Use R-410A at approximately 25 psig backed up
with an inert gas to a total pressure not to exceed 245 psig.
NOTE: Leak detectors should be designed to detect HFC
(hydrofluorocarbon) refrigerant.
III. EVACUATE AND DEHYDRATE
Field piping and fan coil must be evacuated and dehydrated
following good refrigeration practices.
IV. START UNIT WITH OPERATING TEST
Turn power on to the unit. Insert batteries in remote control.
Press the and the buttons on the remote control for
5 seconds. The remote control will be cleared and the time
segment will display the Src1=service test mode.
Press the button to transmit the service test signal to
the unit. After the test has completed press the button
to leave the test menu.
NOTE: When 30 seconds have elapsed and no buttons have
been pressed, the remote control will automatically exit the
test menu and resume its normal operation.
VOLTAGE RANGE*FANPOWER
MinMaxFLA
Motor Power
(Watts)
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or equipped with a
breaker.
2. Motor RLA values are established in accordance with UL (Underwriters Laboratories) Standard 465.
MCAMOCP
V. CONFIGURING TWO INDOOR UNIT REMOTE CONTROLS
If two indoor units are being installed in the same room,
working independently, two remote controls need to be configured for proper operation.
A. Unit Configuration
Turn the unit off by pressing the . Press and hold the
and buttons of the remote control for more than
5 seconds. The display will be cleared and the time segments
will display the first configuration item (rAdr=remote
address) and the temperature segments will display the
default value of this configuration item (Ab=control of both
indoor units). Press and to change the default value
to the new value of (a) or (b). Press the button to transmit the new configuration to the unit. Press the button
to leave the configuration menu.
B. Remote Control Configuration
Turn the unit off by pressing the button. Press and hold
the and buttons for more than 5 seconds. The display will be cleared and the time segments will display the
first configuration item (CH=remote address) and the temperature segments will display the default value of this configuration item (Ab=control of both indoor units). Press
and to change the default value to the new value of (a) or
(b). Press the button to transmit the new configuration
to the unit. Press the button to leave the configuration
menu.
NOTE: When 30 seconds have elapsed and no buttons have
been pressed, the remote control will automatically exit the
test menu and resume its normal operation.
MIN WIRE
SIZE
—13—
Page 14
SERVICE
WAR NING : Before performing recommended
maintenance, be sure unit main power switch is turned
off. Failure to do so may result in electrical shock or
injury form rotating fan blade.
I. PUMPDOWN PROCEDURE
The system may be pumped down in order to make repairs
on the low side without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve gage
port.
2. Frontseat the mixed phase line valve.
CAUTION: The unit coils hold only the factory-des-
ignated amount of refrigerant. Additional refrigerant
may cause units to relieve pressure through the compressor internal pressure relief valve (indicated by a
sudden rise of suction pressure) before suction pressure reaches 20 psig. If this occurs, shut off unit immediately then frontseat the suction valve and remove
and recover excess refrigerant following accepted practices. Equipment damage may result.
NOTE: Do not install a suction-line filter drier in the mixed
phase line.
III. REFRIGERANT CHARGING
WARNING: To prevent personal injury, wear
safety glasses and gloves when handling refrigerant.
Do not overcharge system — this can cause compressor
flooding.
NOTE: Do not vent or depressurize unit refrigerant to atmosphere. Remove and recover refrigerant following accepted
practices.
TROUBLESHOOTING
See Tables 6 and 7 for troubleshooting information.
I. FAULT CODE
Once a failure occurs with the indoor unit in operation, the
green LED on the indoor unit flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the
green LED flashes, blocking unit operation. Between one
flash cycle and the next one, a pause of 3 seconds elapses.
Table 6 — Green LED (Indoor Unit Fault)
3. Start unit and run until suction pressure reaches
5 psig.
4. Shut unit off and frontseat suction valve.
5. Depressurize low side of unit and recover refrigerant
following accepted practices.
II. FILTER DRIER
Whenever the filter drier is exposed to the atmosphere it
must be replaced. Only use factory specified liquid-line filter
driers with rated working pressure of at least 600 psig or
more.
CODEDESCRIPTION
3Room Air Sensor Fault
4Indoor Unit Coil Sensor Fault
14Outdoor Unit Air Sensor Fault
—14—
Page 15
Table 7 — Troubleshooting
PROBLEMPOSSIBLE CAUSESOLUTION
Compressor and Fan of the Outdoor
Unit Will Not Start
Compressor Will Not Start, But
Outdoor Fan is Operating
Compressor Stops Due to
Overtemperature
Compressor Runs ContinuouslyUnit selected is too small for application
Frequent Ice-Build-Up on Outdoor
Coil
Discharge Pressure Too HighOutdoor coil dirty or obstructed Clean or remove obstructions.
Discharge Pressure Too LowIndoor temperature setting too high or too lowCheck temperature setting.
Suction Pressure Too HighIndoor temperature setting too high or too lowCheck temperature setting.
Suction Pressure Too LowIndoor temperature setting too high or too lowCheck temperature setting.
Outdoor Fan Cycling Due to
Over-Temperature Protection
Unit not energizedCheck the main power connection.
Main switch is set to OFFCheck and put it to ON position.
Main switch fuses are blownReplace fuses.
Compressor cycling protection is onWait for 3 minutes.
Main power voltage is too lowCheck and set to the correct voltage.
Electrical connections are too loose or are wrong Check and tighten or correct connections.
Electrical connections of compressor are loose
or wrong
Compressor burnt out; seized or protection
device on
Wrong refrigerant charge in unit (excessive or
low) or air or other noncondensable gasses in
the circuit
Main voltage is too high or too lowCheck voltage setting and adjust if necessary.
Condenser coil obstructedRemove obstruction.
Outdoor fan offCheck cause and resume operation or repair.
Wrong indoor unit thermistorsReplace thermistors.
Refrigerant circuit cloggedCheck and remove obstructions.
Reversing valve faulty on heat pump modelsReplace reversing valve.
Expansion device clogged or covered with iceDrain refrigerant, evacuate and recharge.
requirements
Indoor temperature setting too low or too highCheck temperature setting.
Outdoor unit fan faultyReplace outdoor fan.
Air or other noncondensable gasses in the
circuit
Obstructions at air intake or dirty indoor unit
filters
Outdoor fan is stoppedCheck cause and repair.
Condenser fan faultyReplace condenser fan.
Indoor temperature setting too low or too highCheck temperature setting.
Air or other noncondensable gasses in the
circuit
Outdoor coil dirty or obstructedClean or remove obstructions.
Indoor unit air filter dirtyClean filter.
Reversing valve faulty or internal leakReplace reversing valve.
Evaporator coil covered with iceAir circulation on the evaporator not sufficient; check
Expansion device or suction line cloggedCheck and repair.
Outdoor fan does not stop during defrost
periods
Electrical connection looseCheck connections.
Fan motor burn outReplace.
Fan bearing seized Check and repair.
Expansion device clogged or covered with iceDrain refrigerant, evacuate and replace.
Check and tighten or repair compressor.
Check for the cause and replace compressor if
necessary.
Drain refrigerant, evacuate and recharge.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
Contact a qualified service technician for a system
evaluation.
Drain refrigerant, evacuate and recharge.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
Remove obstruction and/or clean filter.
Drain refrigerant, evacuate and recharge.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.
and repair.
Check electrical parts.
CAUTION: Do not vent refrigerant to the atmosphere;
use refrigerant recovery equipment.