Bryant 619C User Manual

installdt^n, start-up and service instructions
UNDER CEILING FAN COIL UNITS
619C
Sizes 024-048
2 to 4 Tons
CONTENTS
Page
SAFETY CONSIDERATIONS INSTALLATION
I. Complete Pre-Installation Checks ..............................2
II. Select Location
III. Mount Unit
IV. Connect Refrigerant Piping
V. Connect Condensate Drain Line
VI. Make Electrical Connections
VII. Install Control................................................................8
VIII. Connections to Outdoor Unit.......................................9
START-UP..............................................................................9-12
I. After Extended Shutdown
II. Seasonal Changeovers
III. Adjusting Airflow
IV. Operating Mode Memory............................................11
V. Automatic Operation (Auto.) Mode
VI. Operating Fault Diagnosis.........................................11
VII. Operation of Microprocessor Control
CLEANING AND MAINTENANCE.......................................12,13
SERVICE..................................................................................14
TROUBLESHOOTING
NOTE: Detailed controls, service, and troubleshooting
......................................................................
.....................................................................
....................................................
.............................................................
.........................................
................................
.......................................
...........................................
................................................
........................................................
.......................
.....................
........................................................
14-17
1
1-9
3 3 3 5
8
9 9
11 11 11
information is in a separate manual, available from your distributor.
Cancels: New
II 619C-24-1
INSTALLATION
The 619C under ceiling fan coil unit is installed with the 700C outdoor condensing unit, or the 705C heat pump (Fig. 1). Re fer to Table 1 to make sure the correct indoor unit is in stalled with the correct outdoor unit.
Fig. 1 — 619C Under Ceiling Fan Coil Unit
Table 1 — System Combinations for Indoor
and Outdoor Units
SAFETY CONSIDERATIONS
Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical compo nents. Only trained and qualified service personnel should install or service air conditioning equipment.
Untrained personnel can perform basic maintenance, such as
cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in literature, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extin guisher available. Read these instructions thoroughly. Con sult local building codes and National Electrical Code (NEC) for special installation requirements.
SPLIT
SYSTEM UNIT UNIT
Under Ceiling Cooling Only System
535BNC024 619CNX0240E0 700CNX024 535BNC036 535BNC048 619CNX0480E0
Under Ceiling Heat Pump System
635ANC024 635ANC036 635ANC048 619CNX0480W0 705CNX048000
INDOOR OUTDOOR
619CNX0360E0
619CNX0240W0 619CNX0360W0
700CNX036 700CNX048
705CNX024000 705CNX036000
Installation instructions for 619C fan coils are contained in this manual. Refer to this manual for proper installation of the complete system. Note that the 700C and 705C outdoor units are shipped with installation and service instructions for basic installation of the outdoor section.
Be sure the unit will be operated within the application guide lines shown in Table 2. When installing the 700C or 705C unit, it is important to note that for cooling operation when,, the outside air temperature is below 55 F, it is necessary to equip the outdoor unit with the low-ambient control accessory.
■À
To install this system you will need:
1 — 619C fan coil 1 — 700C or 705C outdoor unit 1 — Remote controller kit (included with 619C fan coil) —
note that kit normally includes 15-ft long wire cable; however, cable length up to 200 ft can be ordered.
1 — Low Ambient Kit (if required for your application) 1 — Check-Flo-Rater™ Metering Device Kit (included with
619C fan coil) 1 — Fresh-Air Intake Kit (if required for your application) 1 — Condensate Pump Kit (if required for your application)
NOTE: Refrigerant pipe, drain pipe, wire, etc., are also re
quired to install system. Be sure you have the required parts before beginning instal
lation. The 619C unit utilizes a microprocessor control sys tem to deliver optimal levels of comfort and efficiency. Be sure to follow these instructions carefully to obtain proper func tioning of the unit.
Table 2 - Application Range
COOLING
Maximum
Indoor
95 F DB
71 F WB
Maximum
Indoor
80 F DB
71 F WB
LEGEND
DB — Dry Bulb
WB - Wet Bulb
'Unit may be equipped with a iow-ambient control that will allow
operation down to ~20 F
I. COMPLETE PRE-INSTALLATION CHECKS
A. Unpack Unit
Outdoor Indoor
125 F DB
HEATING
Outdoor Indoor
75 F DB 65 F WB
57 F WB
Minimum
Outdoor
67 F DB
Minimum
55 F DB -20 F DB
55 F DB*
Outdoor
Store unit in the original packaging until it is moved to the
final site for installation. When removing unit from carton, lift unit by its 4 corners; DO NOT lift unit by its plastic parts.
B. Inspecf^hipmeiit
Upon receipt of shipment check unit for damage. Forward claim papers directly to the transportation company. Manufac turer is not responsible for damage incurred in transit.
Check all items; if any item is missing notify your distribu tor. To prevent loss or damage, leave all parts in original pack ages until installation.
C. Before Installation
Perform the following steps before installing indoor unit (Fig. 2). Place the unit upside down on the floor, then:
1. Remove side panels by sliding forward, then away from sides of unit.
2. Remove air filters from inlet grilles; then remove and retain screws securing inlet grilles to indoor unit.
3. Remove inlet grilles from indoor unit by sliding forward.
LOOSEN eOLTS AND SLIDE-
MOUNTING BRACKET THIS
DIRECTION—TO REMOVE
2 T/8
tSSJ
DISCHARGE AIR
SLIDE SIDE PANEL THIS
OIRECTION—TO REMOVE
PIPING JOINT
(LIQUID SIDE)
PIPING JOINT
(VAPOR SIDE)
REMOVABLE AIR FILTER
NOTE: Dimensions shown in brackets [ ] are in mm
Fig. 2 — Removal of Mounting Brackets
from Indoor Unit
'-DRAIN CONNECTION
[INLET AIR
PIPING KNOCKOUT (RIGHT SIDE)
UNIT 619C
OPERATING WT (lb)
REFRIGERANT FAN
Rpm
High Med Low
Nominal Cfm (High Speed)
COIL
Rows Face Area (sq ft) FIns/in. Number of Circuits
CONNECTIONS
Suction (in.) Flare Liquid (in.) Flare Condensate Drain (in.)
LINE SIZES
Suction (in.) Liquid (in.) Condensate Drain
Table 3 — Physical Data
NX0240E0 NX0360E0 NX0480E0 NX0240W0
108 117 140
R-22, Check-Flo-Rater Control
1035 1310 1345
990 1160 1307 940 1010 1270 635 935 1300
4 4 4
2.189 2.625 3 069 149 149 14.9
4
% % %
% % % % 3/e
3/4
4
3/4
3/a
3/4
3/4
3/4 3/4
-2-
8 4
3/4 3/a
3/a 3/a
3/4
%
110 119 142
1035
990 940 635
4
2 189 2.625
14.9 14.9
3/4 3/4
Va 3/4
3/4
NX0360W0 NX0480W0
1310 1345 1160 1307 1010
935
4 4
4
3/4
Ve 3/a
3/a 3/a
3/4
1270 1300
3.069
14.9 8
3/4
3/4
%
3/4
II. SELECT LOCATION
Consult local building codes and NEC for special installation requirements.
There are several ways the unit may be installed to different types of ceiling construction. These instructions do not cover all installation methods. As a typical installation, these in structions focus primarily on mounting the unit to metal in new construction. Plan your installation carefully before you begin. Listed below are some guidelines that should be fol lowed when determining location for the unit.
1. Place unit adjacent to an outside wall if fresh air is re quired, ensuring that location allows for complete air distribution.
2. Determine a convenient and accessible location to mount the wired remote controller. Note that because the con troller is not used to sense room conditions, it is not nec essary to consider this factor when determining the controller location.
The controller cable can be routed through walls and does not need to be surface mounted. For additional informa tion on remote controller, see separate controller kit in stallation instructions.
3. Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit (Fig. 3).
4. Make sure the unit is easily accessible to electrical power.
5. Run refrigerant piping as directly as possible, avoiding any unnecessary turns or bends.
6. Condensate piping can be directed through the inside wall to an approved drain, or directed straight outside.
NOTE: The piping hole for condensate line must slope at a
minimum pitch of 1 in. per 10 ft to ensure proper drainage. If proper pitch cannot be achieved, install accessory conden sate pump at this time.
NOTE; The accessory condensate pump should be installed
before hanging the unit.
2. Determine installation position, paying particular at tention to piping lengths and wiring connections, clear ances, etc. See Fig. 3 for connection locations. Fig. 6 for clearances, and Fig. 7 and 8 for bolt locations.
3. Open knockout if right-side piping connections are re quired (Fig. 9).
4. Cut the slit portion in rear of the side panel with a saw or cutter knife. (Fig. 9).
If indoor unit accessory louver guard is to be installed, in stall at this time and refer to installation instructions pack aged with this accessory.
5. Mount hanging brackets on ceiling (Fig. 10) for either concealed or exposed bolt hanging position.
6. Lift the unit into place, and fit the hex-head bolts on sides of indoor unit into slit grooves of mounting brack ets (Fig. 11). Ensure unit is mounted level to assure proper drainage.
7. Tighten bolts securely.
IV. CONNECT REFRIGERANT PIPING
Fan coil units may be connected to condensing units using field-supplied refrigerant grade piping. Refer to Table 3 for the correct size piping. The length of refrigerant pipe de pends on the unit placement and building structure; keep in mind to run pipes as directly as possible. For piping require ments over 50 ft of total run, or more than 25 ft of lift, con sult the long line application guidelines available from your distributor.
III. MOUNT UNIT
Refer to Fig. 6 for clearances and dimensions. Use mounting template included inside box to locate mounting bolt holes, piping holes, electrical connections, and accessory outdoor­air intake, if used.
Select proper type of hardware from the guidelines below. See Fig. 4.
Wooden Structure Install hanging bolts on a square wooden piece placed over
beams. Newly Built Concrete Slab Install hanging bolts with inserts, embedded bolts, etc. Metal Structure Install hanging bolts utilizing an existing angle or by install
ing a new support angle. Previously Built Concrete Slab
Install hanging bolts with expansion anchor.
A. To Mount Unit:
1. Remove mounting bracket and reinstall the 2 hex-head bolts (factory supplied) into each side of indoor unit as shown in Fig. 5. Allow approximately 3/8-in. space be tween bolt head and unit.
Use the following instructions to connect piping.
1. Install insulation. Insulate all refrigerant lines on heat pumps to prevent condensation. It is extremely impor tant that all refrigerant lines and the Check-Flo­Rater"' metering device be insulated on heat pumps. On cooling only units, the liquid line may be left uninsu lated. Use any acceptable heat resistant closed-cell foam insulation (minimum 3/8-in. wall thickness). When in sulating piping, cap ends and slide insulation over the piping. Insulation can also be cut and placed over piping.
2. Run liquid and gas refrigerant piping. a. Run pipes as directly as possible, avoiding any un
necessary turns and bends.
b. Suspend refrigerant pipes so that the insulation is
not damaged and vibrations are not transmitted to the structure.
c. Leave slack in the refrigerant pipe between the struc
ture and the unit to absorb vibrations.
d. Install flare connection on tubing to liquid line at fan
coil (Fig. 12). The correct piston size is shipped in ths
Check-Flo-Rater body with 619C units. If you have
any questions, use Table 4 to determine required pis ton size for the system being installed. The arrow on the metering device body must face away from the indoor coil.
-3-
f8J
9 15/16
f253J I
6 9/16
[167J
-2 II/J6
f69J
UNIT 619C
024 036 048
UNIT 619C
024 036 048
NOTESI
I. OÍMENS/ONS IN [ J ARE MÍLL/METERS.
DIRECT/ON OF AIR FLOW.
DIMENSIONS (in.)
571/2
70/4
E
B
53% evs 665/s
F G
— —
201/4 371/2
A
5015/16 46 58'3/, 6
713/16
495/8
C
6V8 7%
7%
7%
6%
201/16 2315/16
FRONT VIEW
LOOSEN BOLTS AND SLIDE
MOUNTING BRACKET TH/S
D1RECT10N-»TO REMOVE
SIDE PANEL
D
DISCHARGE AIR
SLIDE SIDE PANEL THIS
DIRECT lON^o-TO REMOVE
PIPING JOINT
(LIQUID SIDE)
PIPING JOINT
REMOVABLE AIR FILTER
Fig. 3 — 619C Dimensional Drawing
-4-
(VAPOR SIDE)
DRAIN CONNECTION
INLET AIR
SIDE VIEW
PIPING KNOCKOUT
(RIGHT SIDE)
(SLIDE INSERT)
HANGING I BRACE BOLT
I WOODEN
WOODEN STRUCTURE
^HANGER BOLT
IL à
METAL STRUCTURE PREVIOUSLY
Fig. 5 - instaliing Hex-Head Mounting Boits
REAM (EDGE SHARP “ INSERT)
NEWLY BUILT CONCRETE SLAB
Fig. 4 - 619C Unit-Mounting Methods
(Hardware is Fieid Suppiied)
INDOOR UNIT
in 619C Unit
(EMBEDDED BOLT OF PIPING)
BUILT CONCRETE SLAB
REINFORCING
BAR«
"‘embedded
BOLT
^EXPANSION
ANCHOR
BOLT
e. On heat pump installations check for factory-installed
piston in service valve. If not already installed, in
stall piston in the metering device located in the ser
vice valve on the outdoor unit (Fig. 13). Make sure
Teflon seal on the piston faces toward the outdoor unit.
Use Table 4 to determine required piston size for the
system being installed.
f Refer to 700C and 705C installation, start-up and ser
vice instructions for additional information.
g. Install a liquid line filter drier near the outdoor unit.
On heat pump systems, a bi-flow filter drier must be used.
3. Insulate and caulk wall openings to reduce air infiltra tion and refrigerant pipe vibrations on structure.
4. Evacuate piping, if necessary. If either refrigerant pip ing or the indoor coil is exposed to atmospheric condi tions for longer than 5 minutes, it must be evacuated to
1000 microns to eliminate contamination and moisture
in the system.
V. CONNECT CONDENSATE DRAIN LINE
Observe all local sanitary codes when installing condensate drains. Refer to Fig. 3 and 14 for drain hose connection from indoor unit.
1. Use hard polyvinyl chloride (PVC) pipe material with nominal ID of 3/4 in. to connect at drain line. Use pipe insulation 1/4-in. thick, such as Armaflex insulation, on
exposed piping inside the conditioned space.
FRONT VIEW
-5-
CONCEALED MOUNTING HOLE FOR HANGING BOLT 4 -1/2" X 1" SLOTS
EXPOSED MOUNTING HOLE FOR HANGING BOLT
4 -1/2” X 1" SLOTS
SIDE VIEW OF RIGHT­SIDE PANEL
ri-|='C io
T
3 5/8"
IV" !
21
_____1______
i
1-
--------------
UNIT 619C
024 036 048
Fig. 7 — 619C Unit Hanging Dimensions
TOP
11 IN
REAR
NOTE: Dimensions are found in Fig. 7.
Fig. 8 — Mounting Template Included with 619C Unit
B
A
IQ
________
>1
DIMENSIONS (in.)
A
50'5/i6 46 58'3/i6 53%
718/16 66%
B CONCEALED MOUNT -
------
D EXPOSED MOUNT -
23 5/8”
oo
T
IT
r -................................1
1
1
---------------D-----------------
h
---------------A----------------
B C
D
6'/8 6'/8 7% 70V4
49Vb
57V2
POSITION OF HANGING BOLT (3/8 IN DIA. HOLE)
. FOLD
TEMPLATE ON DOTTED LINE
:«i' 1 u-fi
1
-
Fio. 9 — Removina Rear Knockout
If Right-Side Piping Connection is Used
1
rtrr 1
iliC - -------------
CUTTHESUT PORTION IN REAR OF PANEL WITH A SAW OR CUTTER KNIFE
2. To ensure regular flow of condensate water, the drain pipe should be pitched toward an open drain or sump at a downward slope of at least 1/4-in. per foot.
3. Secure drain pipe with nylon wire tie passing through the knockout, as shown in Fig. 15.
4. Attach plate with screws under piping hole.
5. Attach drain pipe with nylon wire tie passing through hole (Fig. 15).
NOTE: Do not fasten nylon wire ties tight enough to deform
the insulation, as this affects its performance.
6. Insulate condensate drain line(s). Insulate the conden sate drain lines that are located in or above an occupied area with a condensate proof material such as polyure thane or neoprene.
7. Install an external trap at the end of the condensate line.
NOTE: Should your particular installation require one, a con
densate pump may be ordered as an accessory option.
Fig. 10 — Mounting Ceiling Brackets
NOTE: Arrow on Check-Flo-Rater body points in free flow direction away
from the indoor coil
Fig. 12
Check-Flo-Rater™Metering Device in Liquid
Line (Bypass-Type Components)
UNDER CEILING INDOOR UNIT
Fig. 13 - Check-Flo-Rater Metering Device at Service
Valve (Bypass-Type Components)
Air Delivery Louvers Air Filters
Remote Controller Not Used Drain Pipe Interconnecting Tubing and Wire Outdoor Condensing Unit Outdoor Unit Disconnect Switch Indoor Unit Disconnect Switch
Fig. 14 - Component Location (Typical Under Ceiling System)
OUTDOOR UNIT
-7-
RIGHT-HAND EXIT
Fig. 15 — Routing Drain Piping
VI. MAKE ELECTRICAL CONNECTIONS
Be sure field wiring complies with local building codes and NEC, and unit voltage is within limits shown in Table 5.
Contact local power company for correction of improper line voltage.
NOTE: Use copper wire only between disconnect switch and
unit.
NOTE; Install branch circuit disconnect of adequate size to
handle unit starting current per NEC. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC. Some codes allow indoor unit to share disconnect with outdoor unit if disconnect can be locked; check local code be fore installing in this manner.
1. Route ground and power wires.
2. Route line power leads (see Fig. 16) from indoor discon nect to the fan coil unit. Place wire through hole on the control box (Fig. 17). Connect wire to high voltage ter minal board (TB-1) and ground screw. When routing the wire in the unit, use care to keep the wire away from refrigerant and condensate piping and any sharp edges. Units are factory wired for 230 V to 24-V transformer operation. For 208 V to 24-V operation, interchange blue
(208 V) and red (230 V) wires. Cap unused wires with
wire nuts.
VII. INSTALL CONTROL
The 619C unit is equipped with a microprocessor control which operates the system. This control is located in the control box of the fan coil, with thermistors located in the fan coil inlet and discharge, on the indoor coil, on the outdoor coil, and in the outdoor-air inlet (heat pump systems only). The ther mistors monitor system operation and control the operating mode. To change settings or modes of operation, a wired re mote controller is supplied.
The factory-preset DIP switches on the 619C control board set the operation of the unit cooling only or for heat pump operation. Be sure the switches are set correctly. See wiring diagram on page 16 or 17, and also the control, service, and troubleshooting guide (available from your distributor) for more information.
A. Wired Remote Controller
The wired controller is directly connected to the unit by the plug connection provided. Standard cable length is 15 ft, but the cable can be any length up to 200 ft.
Determine where the best location is to mount the controller. Since the controller is not used to sense the temperature of the room, locate the controller in a convenient place that is easily accessible to the user.
The cable can be surface mounted or may be run over ceil ings and through walls. Follow local codes when installing low voltage wires.
To install remote controller, see separate remote controller installation instructions.
OUTDOOR UNIT
700CNX024 700CNX036 700CNX048 705CNX024 705CNX036 705CNX048
LEGEND
B - Chatleff
Table 4 — Required Piston Size for Check-Flo-Rater™ Metering Device
INDOOR UNIT
619CNX0240E0 55 619CNX0360E0
619CNX0480E0 619CNX0240WO ­619CNX0360W0 619CNX0480W0
INDOOR PISTON
INDOOR PISTON TYPE
B 65 84
-
-
B
B
B
B
B
'Charge amount is determined with 25 ft. of iine
-8-
OUTDOOR
PISTON
- A
-
-
~ A -
-
-
OUTDOOR PISTON
TYPE
A A
A - A
REQUIRED SYSTEM
CHARGE * (lb)
68
6.8
too
-
Table 5 — Electrical Data
OPERATIONAL
INDOOR UNIT
619CNX0240E0 619CNX0360E0 20 1.3 160 -
619CNX0480E0 3.7 1.0 396 619CNX0240W0 07 0.5 2092 619CNX0360W0 20 1.3 619CNX0480W0
FLA — Full Load Amps HACR — Heating, Air Conditioning, Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps per NEC Section 430-24 NEC — National Electrical Code
208/230 VOLT 1-PHASE CONNECTION TO INDOOR DISCONNECT
<
V-PH
208/230-1-60
LEGEND
VOLTAGE*
Max
187
Min
253
FAN
LRA FLA
07 0.5 92
37
WATTS
3160 3
1.0
‘Permissible limits of the voltage range at which unit will operate
satisfactorily.
4396 4
The following checks should be made before system start-up. Refer to 700C or 705C installation, start-up and service in structions for system start-up instructions and refrigerant charging methods.
EQUIPMENT GROUND
Fig. 16 — Line Power Connections
VIII. CONNECTIONS TO OUTDOOR UNIT A. Cooling Only Systems
The following connections must be made to the 700C unit for it to operate as a system with the indoor unit:
1. A thermistor connection cord with a lead length of 35 ft is shipped with the 619C unit. Run the connection cord from the condensing unit to the low-voltage terminal strip on the control board of the fan coil unit. The stripped end of the connection cord goes to the fan coil end. Use
1. Check condensate drainage system. a. Remove grille and frame from the unit. b. On the opposite side of the drain connection, insert a
water bottle up into the fan coil unit and fill drain pan. Refer to Fig. 18. Water must flow regularly; if not, check the pipe slope or inspect for any pipe restrictions.
2. Make sure that all wiring connections are correct and that they are tight.
3. Check that all barriers, covers, and panels are in place. Ensure that the filters and return-air grilles have been installed and that the discharge louvers are positioned correctly.
care to route the wires so that they will not be dam aged, and do not run them near power wires. Connect the orange wires to terminals D1 and D2 on the control board.
2. Route 2 wires of 18-gage thermostat cable between the low-voltage terminal block of the fan coil and the 700C
I. AFTER EXTENDED SHUTDOWN
If the system has been turned off for more than 12 hours, turn on the indoor and outdoor unit disconnect switches to supply power to the system for 12 hours BEFORE starting
the system. unit. Connect the wires Y to blue wire going to high­pressure switch, and R to R on the low-voltage transformer.
B. Heat Pump Systems
The following connections must be made to the 705C unit for it to operate as a system with the indoor unit:
1. A thermistor cord with a lead length of 35 ft is shipped with the 619C unit. Run this cable from the heat pump to the low-voltage terminal strip on the control board on the fan coil unit. Use care to route the wires so that they will not be damaged, and do not run them near power wires. Connect the orange wires to terminals D1 and D2 on the terminal strip, and the blue wires to terminals A1 and A2 on the terminal strip.
2. Route 4 wires of 18-gage thermostat cable between the
II. SEASONAL CHANGEOVERS
When changing heat pump system from cooling to heating or heating to cooling, or before starting cooling only system af ter it has been out of use for the winter season, the following steps must be performed.
BEFORE starting the system:
1. Inspect and clean the outdoor unit, particularly the coil.
2. Clean or replace the air filters in the indoor unit.
3. Clean the indoor unit drain pan and drain pipe, and re move any obstructions.
4. Turn on indoor and outdoor unit disconnect switches to supply power to the system 12 hours before starting the system.
low-voltage terminal block of the fan coil and the 705C unit low-voltage terminal block. Connect Y to Y, O to O,
G to G, and C to C with the wires.
ELECTRIC
HEATER
kW AT 240 V
-
2
START-UP
20
MAX FUSE OR
HACR TYPE
CKT BKR AMPS
MCA
1 0
1.8
11.5
17.9 35
22.9
15 15 15 20
40
-9-
FRONT VIEW
<3>®<Z>(D(B)<3>
I IFM
®®<3> ®®CD
gMHiM5
¿b
QD<S><B>
Itili
i?iat
"T
'B
SIDE VIEW
ll
-POWER LEADS
CONNECTION
ASM — Air Sweep Motor ASR — Air Sweep Reiay
CB — Circuit Breaker DAT — Discharge Air Temperature Thermistor EQUIP GND — Equipment Ground IDC — Indoor Coil Temperature Thermistor IFM — Indoor Fan Motor NEC — National Electrical Code PCB — Printed Circuit Board PL - Plug
RA — Return Air Temperature Thermistor TB — Terminal Board TRAN — Transformer
NOTES:
1 If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2 Wire in accordance with NEC and local codes
Fig. 17 — Control Circuit Connections
<Z>
Circuit Board Run Terminal (Marked)
Terminal Block
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring
-10-
III. ADJUSTING AIRFLOW A. Automatic Air Sweep
All units are equipped with an automatic air sweep feature which automatically directs the airflow louvers up and down to provide optimum room air circulation. If the auto sweep feature is not desired, temporarily start the auto sweep us ing the remote controller. When the louvers are in the de sired position, turn the auto sweep off to hold them in that position.
IV. OPERATING MODE MEMORY
After the system is turned off or after a power failure, the system remains in the last operating mode selected. When the system is turned back on, or when power is automati cally restored, operation continues in the same operating mode as when it shut down.
V. AUTOMATIC OPERATION (AUTO.) MODE
If Auto, mode is selected, the system automatically switches over the Operating mode from heating to cooling, or from cool ing to heating (heat pump system only) depending on the se lected temperature.
NOTE: Betvieen the cooling cycle and the heating cycle there
is a neutral zone of approximately 2° F above and 2° F below the selected temperature when only the fan is operating. This neutral zone lasts for a minimum of 10 minutes.
VI. OPERATING FAULT DIAGNOSIS
The system includes an automatic diagnosis feature which is activated under difficult or unacceptable operating condi tions. If such conditions occur, the system stops automati cally, the operating fault signal appears on the liquid crystal display (LCD) of the remote controller, and an analysis of the system operating conditions is initiated. The system will then be restarted automatically, as soon as normal conditions have been restored, or it will remain off. If the system does not start again, the temperature indicator on the LCD display alternates between the selected temperature value and an er ror code. See separate controls, service, and troubleshooting guide to troubleshoot the problem.
VII. OPERATION OF MICROPROCESSOR CONTROL
This system is controlled by a microprocessor control de signed to give optimum levels of comfort and operating effi ciency. The control is located in the 619C unit. To operate the unit, a remote controller is required. This control may be wired directly to the unit and mounted on the wall up to 200 ft away from the unit.
See separate owner’s manual for remote controller operation instructions. More detailed operating sequence and timing are located in the controls, service, and troubleshooting guide. Both manuals are available from your distributor.
There are 7 operating modes (including the OFF mode) for cooling only systems and 11 operating modes (including the OFF mode) for heat pump systems. The following operation should be expected in each mode.
• OFF Mode — When the unit is in the OFF mode, all func tions (compressor, outdoor fan, indoor fan, electric heat, and air sweep) are off, except the reversing valve, which will stay energized if the unit was last operated in the COOL ING mode.
• AIR CIRCULATION Mode (Fan Operation Only) - When AIR CIRCULATION mode is selected, the indoor fan will operate continuously in the selected speed (high, medium, low, or auto). If the AUTO, mode is selected, the indoor fan will operate at high speed. The compressor, outdoor fan, and electric heat are off The reversing valve will remain in the last operating mode. The air sweep motor will oper ate if selected.
• COOLING Mode — When the COOLING mode is selected, the indoor fan will operate continuously at the selected speed if the speed is high, medium, or low. If the indoor fan is in auto., the fan will change operating speeds depending on the room temperature. The electric heat will be off and re versing valve will be on. The compressor cannot run for 3 minutes from the time the system starts up or for 3 min utes from the time it last operated. When the temperature of the room is 2° F above the selected temperature, the com pressor and outdoor fan will operate until the room tem perature is equal to the selected temperature. If the room temperature is 4° F or more above the selected tempera ture, the indoor fan will run at high speed. When the room temperature is between
F and 4° F above the selected temperature, the indoor fan will operate at medium speed. When the room temperature is 2° F below the selected tem perature, the indoor fan will operate at low speed.
When the room temperature is equal to the selected tem perature, the compressor and outdoor fan shut off. The in door fan, if in auto, operation, operates for one minute af ter the compressor shuts off. The fan remains off for 3 minutes, then operates for one minute at low speed. The indoor fan repeats this process until cooling is again required.
• MAXIMUM DEHUMIDIFICATION Mode - When the DE HUMIDIFICATION mode is selected, the indoor fan will operate continuously at the selected speed if the speed is high, medium, or low. If the indoor fan is in auto, opera tion, the fan will change operating speeds depending on the room temperature. The electric heat will be off and revers ing valve will be on. The compressor cannot run for 3 min utes from the time the system starts up or for 3 minutes from the time it last operated.
Initial Operation — When the mode is first selected, or if the indoor fan has been off for more than one minute, the fan will operate at low speed for 30 seconds. Then, if the room temperature is above the selected temperature, the unit will operate for 16 minutes, and the compressor and outdoor fan will operate. The indoor fan will operate as in the cooling mode. After 16 minutes of operation, the unit switches to normal operation.
If the room temperature is below the selected tempera ture, the unit will operate for 8 minutes, and the compres sor and outdoor fan will operate for 3 minutes. The indoor fan will operate in low speed, and one minute after the com pressor stops the indoor fan stops. After remaining off for 3 minutes, the indoor fan starts in low speed for one minute, then switches to normal operation.
-11-
Normal Operation — When the temperature of the room is
6° P above the selected temperature, the compressor and outdoor fan will operate for 8 minutes. The indoor fan will operate in low speed. If the room temperature is above the selected temperature, but not by more than 6° F, the com pressor and outdoor fan operate for 4 minutes. The indoor fan will run at low speed and will stop 30 seconds after the compressor stops. After 3 minutes, the indoor fan runs at low speed for 30 seconds. The normal dehumidification op eration is repeated for the new room temperature.
When the room temperature is within 4° F below the se
lected temperature, the system operates for 8 minutes. The compressor and outdoor fan operate for 3V2 minutes. The indoor fan will operate at low speed and will stop 30 sec onds after the compressor stops. After 3 minutes, the in door fan starts in low speed for one minute. The normal dehumidification operation is repeated for the new room temperature.
If the room temperature is 4° F below the selected temper ature, the compressor, outdoor fan, and indoor fan remain off. After 3 minutes, the indoor fan operates at low speed for one minute. This is repeated until 8 minutes have elapsed. The normal dehumidification operation is repeated for the new room temperature.
HEAT PUMP Heating Mode (Heat Pump Systems Only)
— When the HEAT PUMP mode is selected, the indoor fan will operate continuously at the selected speed if the speed is high, medium, or low. If the indoor fan is in auto oper ation, the fan will change operating speeds depending on the room temperature. The electric heat is off and the re versing valve will be on. The compressor cannot run for 3 minutes from the time the system starts up or for 3 min utes from the time it last operated. When the temperature of the room is 8° F below the selected temperature, the unit will operate in HEAT PUMP mode until the temperature is F above the selected temperature. If the temperature
of the room is between 2° F and 8° F below the selected
temperature, the unit operates in HEAT PUMP mode un
til the selected temperature is reached.
In the HEAT PUMP mode, the compressor and outdoor fan
will operate until the room temperature has reached the
temperature indicated above. The indoor fan will remain
off until the discharge temperature of the fan coil is 86 F.
The fan will then operate in low speed until the discharge
temperature is 98 F. Then the fan will operate at high speed
if the room temperature is 4° F or more below the selected
temperature. The indoor fan will run at medium speed when
the room temperature is between 2° F and
F below the selected temperature. The indoor fan will operate at low speed if the room temperature is within 2° F of the se lected temperature. When the heating demand is satisfied, the compressor and outdoor fan will stop and the indoor fan will operate until the discharge air temperature is 77 F. The fan will turn off for 3 minutes, then turn on for one minute — this will be repeated until heating is again required.
' MAXIMUM HEATING Mode (Heat Pump Systems Only)
— This mode of operation is the same as the HEAT PUMP heating mode, except that electric heat is used to assist the heat pump.
• ELECTRIC HEATING Mode (Heat Pump Systems Only) — The indoor fan operation is the same as the HEAT PUMP mode, except that electric resistance heating only is used.
• AUTOMATIC OPERATION Mode - AUTOMATIC OPER
ATION mode runs the system in cooling or heating at 2° F above the selectéd temperature for cooling and 2° F below the selected temperature for heating. In the temperature range between heating and cooling, only the fan will oper ate. A minimum of 10 minutes is required between a change from heating to cooling or from cooling to heating.
• DEMAND DEFROST Mode (Heat Pump Systems only) —
This unit uses a demand defrost system to remove frost from the outdoor coil during heating operation. The indoor fan and outdoor fan are shut off during defrost. For com plete description of defrost operation, see the controls, ser vice and troubleshooting guide sections of the duct-free
systems manual, available from your distributor.
• SLEEP Mode — The SLEEP mode timer will turn the unit
off when the timer reaches zero minutes. During the first
IV2 hours from the time the SLEEP mode timer starts, the
room temperature is set back from the selected tempera ture a total of 4 F in cooling and 6 F in heating.
• AWAKE Mode — The awake timer will turn the unit on
when the timer reaches zero minutes. The unit will start in the same mode and at the same selected temperature as when the system shut off.
NOTE: The system can be programmed for the sleep mode
or the awake mode, but it cannot be programmed for both of these modes simultaneously.
CLEANING AND MAINTENANCE
For proper system operation we recommend that the clean ing and maintenance operations in Table 6 be performed.
I. LUBRICATION
The indoor-fan motor, automatic air sweep motor, and the outdoor fan motor are factory lubricated and require no oiling.
-12-
II. TO REMOVE AND CLEAN OR REPLACE AIR FILTERS (FIG. 21)
A. To Remove Air Filters
Remove filters by pulling them straight out.
B. To Clean or Replace Filters
Filters can be vacuumed, or washed in warm water. See Fig. 19. Shake filter to remove any excess water, and replace by sliding filter behind grille until filter snaps in place.
NOTE: After cleaning, be sure to press the Filter Reset but
ton on the mode selection panel of the remote controller. If the filter has begun to break down or is torn, it needs to be
replaced. Replacement filters are available through your distributor.
A. REMOVE FILTERS
III. TO CLEAN INDOOR UNIT BOTTOM PANEL
If the bottom panel of the unit becomes dirty or smudged, wipe the outside of the panel with a soft dry cloth. Use a mild liquid detergent and wipe off carefully with a dry cloth.
IV. TO CLEAN INDOOR COIL
To clean the coil, remove indoor unit bottom panel and con
densate pan, and then vacuum the coil fins, using care not to bend or damage fins.
V. TO CLEAN OUTDOOR COIL
To clean the outdoor coil:
1. Remove any dirt or obstruction from discharge opening.
2. Use a garden hose to spray water on the coil. Debris that collects between coil fins inhibits heat transfer — direct the water spray between coil fins to flush out debris.
VI. TO CLEAN CONDENSATE DRAIN PIPE AND PAN
Clean drain pipe quarterly and drain pan at the start of each cooling season. Check the flow by pouring water into the drain pipe.
A. To Clean or Replace Drain Pan
1. Place a plastic sheet on the floor to catch any water that may spill from drain pan.
INTAKE GRILLE B WASH FILTERS,
OR
2. Remove the air intake and distribution assembly.
3. Remove the condensate water in the drain pan by let ting water drain into a 3-gallon bucket.
4. Remove the 4 screws holding the drain pan.
5. Carefully hold the drain pan to remove it from the assembly.
C. VACUUM FILTERS
Fig. 19 — Cleaning Filters
Table 6 — Cleaning and Maintenance Schedule
TASK MONTHLY
INDOOR UNIT
Clean Air Filters Clean Drain Pipe X Clean Condensate Drain Pan Clean Indoor Unit Front Panel
OUTDOOR UNIT
Clean the Fins From Outside Open the Unit and Clean Fins Inside Remove Dust From Eiectricai Parts Check Eiectricai Connections are Tight Ciean Outdoor Fan X Check that Outdoor Fan Assembiy is Tight Clean Condensate Drain Pan
NOTE: Maintenance procedures for the outdoor unit are in the 700C and 705C instaiiation instructions
X
QUARTERLY YEARLY
X
X X
X X X
X
X
-13-
1
SERVICE
NOTE: Refer to the control, service and troubleshooting guide
sections of the duct-free systems manual for a complete de scription of the control system and for detailed service and troubleshooting procedures. This manual is available from your distributor.
TROUBLESHOOTING
I. DIAGNOSTIC CODES
This unit is equipped with a microprocessor control which con tinuously monitors the operation of the unit. If an opera tional fault is detected, a fault code appears on the LCD dis play of the remote controller. A red LED indicator light, located on the control board in the control box of the indoor unit, will emit a flash code which can be used to troubleshoot a system problem. The control will continue to monitor the unit and, if thè conditions which cause the fault are cleared, the unit will return to normal operation. If the fault code is present for 5 cycles of the unit, the unit will be locked out and the alarm code will be displayed alternately with the temperature on the remote controller LCD display.
If the LED indicator light continuously flashes on for one sec ond, then off for one second, the control is functioning prop erly and no fault is present. A fast flashing LED indicates that a fault has been detected. Table 7 lists the number of quick flashes and the associated fault. If the system does not operate, the remote controller does not display a fault code, and the LED indicator does not flash, either the power to the control board is off, or the control board has failed.
Table 7 — System Fault Codes
FAULT CODE*
E2 E3 E4 E5 E6 E7
E8 E11 E12
‘The fault code is alternately displayed with the temperature on the re
mote controller LCD display
tHeat pump systems only
II. TEST MODES
NO. OF
FLASHES
2 3 4 5 6 7 8
11
12
SYSTEM FAULT
Outdoor Coll Thermistor
Outdoor Air Thermistort Room Air Thermistor Indoor Coil Thermistor Discharge Air Thermistor
Compressor Malfunction
Reversing Valve Malfunctlonf Electric Heat Malfunction Outdoor Coil Temperature
The remote controller allows troubleshooting of the system by running a series of test modes. These tests may be man
ually initiated with the remote controller to test the system operation:
• Fan Only Test
• Cooling Mode Test
• Dehumidification Test
• Heat Pump Heating Test
• Emergency Heat Test
See separate controls, service, and troubleshooting guide for additional details on operating test modes.
III. SYSTEM TESTS
System tests listed below are performed continuously by the microprocessor. If a fault is indicated, then the system al lows only limited operation until the problem is resolved. If the problem resolves itself, then the code is cleared and op eration resumes.
A. Indoor Coil High-Temperature Protection (Heat Pump Sys tems Only)
If indoor coil temperature is greater than or equal to 145 F but less than 165 F for one minute or more, the system shuts down.
B. Outdoor Coil High-Temperature Protection (Cooling or Dehumidification Mode Only)
If outdoor coil temperature is greater than or equal to 145 F but less than 165 F for one minute or more, the system shuts down.
C. Indoor Coil Freeze Protection (Cooling or Dehumidifica tion Mode Only)
If indoor coil temperature is less than or equal to 28 F but more than —13 F for 4 minutes and the compressor has run for 24 continuous minutes, the system shuts down.
D. Thermistor Tests
Each thermistor is tested for high limit out of range (shorted condition) and low limit out of range (open condition). If the thermistor is out of range, the fault status indicator comes
on and the LED flashes the appropriate fault code.
E. Compressor Failure
If the System is in COOLING or DEHUMIDIFICATION Mode
After 2 minutes of operation, if the temperature of the in
door coil is not 2° F less than at the time the call for cool ing started, then a compressor failure is indicated on the re mote controller LCD display.
If the System is in HEAT PUMP HEATING Mode - After 2
minutes of operation, if the temperature indicated by the out door thermistor is not 2° F less than at the time the call for heating started, then a compressor failure is indicated.
F. Reversing Valve Failure
If the System is in COOLING or DEHUMIDIFICATION Mode
After 4 minutes of operation, if the temperature at the in
door coil is 2° F more than at the time the call for heating started, then a reversing valve failure is indicated.
If the System is in HEAT PUMP HEATING Mode — After 4
minutes of operation, if the temperature indicated by tbe in door coil is not 2° F less than at the time the call for heat ing started, then a reversing valve failure is indicated.
G. Electric Heater Failure
If, 4 minutes after the heater is energized, the discharge-air temperature is not 2° F above the return-air temperature, an electric heater failure is indicated.
H. Filter Dirty Indicator
Indicator (on remote controller LCD display) turns on after 250 hours of indoor fan operation.
-14-
NOTES FOR FIG. 20 AND 21
1. Compressor and fan motor are thermally protected.
2. Wire in accordance with National Electrical Code (NEC) and local codes. If any of the original wire must be re placed, it must be replaced with type 90 C wire or its equivalent.
LEGEND FOR FIG. 20 AND 21
ASM ASR C CAP CB CH COMP DATTH DTS EQUIP GND FL HPS HR HTR HTT
_
Air Sweep Motor
Air Sweep Reiay
_
Compressor Contactor LPS
Capacitor
Circuit Breaker
Crankcase Heater
Compressor
Discharge Air Thermistor
Discharge Temperature Sensor
Equipment Ground
Fuse Link
High-Pressure Switch
Heater Relay
Heater Heater Temperature Thermostat
IDC TH IFM
OATTH
OCTTH OFM OFR PCB PL RA TH RVS Reversing Valve Solenoid SC SR TB TDR TRAN
3. Use minimum of 60 C wiring for field power wiring.
4. Thermostat is internal to unit. Unit must be controlled with wired or infrared wireless remote controller.
5. Use copper conductors only.
_
Indoor-Coil Thermistor
Indoor-Fan Motor
Low-Pressure Switch
Outdoor Air Thermistor
Outdoor Coil Thermistor
Outdoor Fan Motor Outdoor Fan Relay
Printed Circuit Board
Plug
Return Air Thermistor
Start Capacitor Start Relay
Terminal Block
--
Time-Delay Relay Transformer
<Z>
o
1 >■ 1
Circuit Board Run Terminal Marked
Terminal Unmarked Splice
Terminal Block
Factory Wiring
Field Control Wiring Field Power Wiring Accessory or Optional Wiring
-15-
Oi
-OPN-
-ft£D-
-UHT-
-BLK-
WIREO
REMOTE
I
Fig. 20 — Typical System Wiring Schematic; Heat Pump Systems
I
J
K-0^0-BLK*-BH>^^
- - - - - - -- - - -- - -- - - -•- - - - - - - -
-O-
O j .
LPS
-C0O
Fig. 21 - Typical System Wiring Schematic; Cooling Only Systems
J
Loading...