Bryant 619B, 619F, 538S, 619C Installation, Start-up And Service Instructions Manual

Page 1
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation instructions before installingthisunit (see Fig. 1 for typi­cal multi-split system components).
2. Be sure the installation conforms to all applicable local and national codes.
3. These instructions contain important information for the proper maintenance and repair of this equipment. Re­tain these instructions for future use.
CONTENTS
Page
SAFETY CONSIDERATIONS ........................2
GENERAL .......................................2
I. System Description .........................2
II. Planning the System ........................2
INSTALLATION .................................2-13
I. Complete Pre-Installation Checks .............2
II. Install Outdoor Unit .........................4
III. Install Fan Coil Units ........................4
IV. Complete Refrigerant Piping ..................7
V. Make Electrical Connections .................8
START-UP ....................................13,14
I. Leak Test .................................13
II. Evacuate and Dehydrate ....................13
III. Charge System ............................13
IV. Preliminary Checks ........................13
V. Operating Sequence .......................13
SERVICE .....................................15-17
I. Outdoor Fan ..............................15
II. Scroll Compressors ........................15
III. High-Pressure Relief Valve ..................15
IV. Internal Current and Temperature Sensitive
Overload .................................15
V. High-Pressure Switch ......................15
VI. Low-Pressure Switch .......................15
VII. Service Valves ............................15
VIII. Refrigerant Charging .......................16
IX. Compressor Lockout Switch (CLO) ...........16
X. Outdoor-Coil Temperature Thermistor
(OCH TH) .................................17
XI. Low-Ambient Control Thermistor (LAT) .......17
XII. Pressure Transducer .......................17
MAINTENANCE .................................17
I. Lubrication ...............................17
II. Cleaning Coils ............................17
TROUBLESHOOTING ...........................17,18
I. Checking Cooling Control Operation ..........17
START-UP CHECKLIST ...................CL-1 to CL-4
538S (048 Shown)
619C
619B
619F
Fig. 1 — Multi-Split System Components
installation, start-up and service instructions
MULTI-SPLIT, DUCT-FREE OUTDOOR COOLING UNITS
538S
Sizes 024,048
2 and 4 Tons
Cancels: New II 538S-24-1
2/15/96
Page 2
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be haz­ardous due to system pressure and electrical components. Only trained and qualified service personnel should install or serv­ice air-conditioning equipment.
Recognize safety information. This is the safety-alertsymbol ( ). When you see this symbol on the unit and in instruc­tions or manuals, be alert to the potential for personal injury.
Understand the signal words — DANGER, WARNING, and CAUTION. These words are used with the safety-alert sym­bol. Danger identifies the most serious hazards which will result in severe personal injury or death. Warning indicates a situation that could result in personal injury. Caution is used to identify unsafe practices which would result in minor personal injury or product and property damage.
Untrained personnel can perform basic maintenance, such as cleaning and replacing filters.All other operations should be performed by trained service personnel. When working on air­conditioning equipment, observe safety precautions in litera­ture, and tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extin­guisher available. Read these instructions thoroughly. Con­sult local building codes and National Electrical Code (NEC) Standard ANSI/NFPA 70 (American National Standards Institute/National Fire Protection Association) for special in­stallation requirements.
WARNING:
Before installing or servicing system, al­ways turn off main power to system. There may be more than one disconnect switch, since each fan coil unit will normally have its own disconnect. Turn off accessory heater power if applicable. Electrical shock can cause personal injury.
GENERAL
IMPORTANT: Before installing a multi-split system, care-
fully read the following information:
• The TXV (thermostatic expansion valve) is located in the outdoor unit, NOT the indoor fan coil units.
• The 538S outdoor unit has a factory-installed low-ambient control which permits unit operation down to 0°F outdoor ambient temperatures.
• BOTH refrigerant linesbetween the indoor and outdoor units MUST BE insulated, because the TXV is in the outdoor unit.
• If the installation includes a 619C ceiling-suspended fan coil unit, REMOVE the AccuRatert device.
• DO NOT install a filter drier in the line set to the fan coil units. A filter drier has already been factory-installed on the outdoor unit.
• DO NOT run thermistor wires and control wires in the same jacket.
• The 538S unit has been pre-charged at the factory with sufficient refrigerant forthe entire system (assuming 25ft of tubing and the use of one of the system combinations listed in Planning the System section on this page).
I. SYSTEM DESCRIPTION
The 538S multi-split air conditioning system requires 3 ma­jor components (see Fig. 1):
• A 538S outdoor condensing unit
• Either 2, 3, or 4 duct-free split fan coil units for distribu­tion of air to a maximum of 4 independent zones (see Plan­ning the System section on this page)
• A wired or wireless infrared remote controller to control each fan coil unit independently (one remote controller is necessary for each fan coil unit)
NOTE: The remote controller is not available for 619F in­ceiling cassette fan coil units.
IMPORTANT: The 538S outdoor units may only be usedwith the indoor fan coil unit sizes listed in Planning the System section below. DO NOT try to substitute oradd more fan
coils to these systems.
II. PLANNING THE SYSTEM
This is a complex system with up to 4 separate tubing sys­tems and 8 different control cable sets. Plan the installation carefully as instructed below.Read these installation instruc­tions (outdoor condensing unit) and the installation instruc­tions included with each fan coil unit carefully and completely PRIOR to system installation.
1. Maximum line length is 50 ft equivalent (any single line run), and maximum elevation differential is 30 ft (from highest to lowest system component).
2. Verify that components received form a legitimate multi­split system as follows:
a. Systems using one 538S_024 outdoor condensing unit
may use any combination (for a system total of 2 fan coil units) of nominal 1
1
⁄2ton fan coil units.
b. Systems using one 538S_048 outdoor condensing unit
may use any of the following combinations:
• any combination (for a total of 2 fan coil units) of nominal 2 ton fan coil units (1 fan coil unit per circuit).
• any one nominal 2-ton fan coil unit on one circuit, and any combination of 2 nominal 1
1
⁄2ton fan coil units (for a system total of 3 fan coil units) on the other circuit.
• any combination (for a system total of 4 fan coil units) of nominal 1
1
⁄2ton fan coil units (2 fan coil
units per circuit).
3. Identify and record each fan coil section as it will be con­nected to the 538S outdoor unit on the Multi-Split Installation Planning Worksheetincluded as part of the Start-Up Checklist on page CL-1.
4. Check all system components to ensure that all re­quired materials are on hand before starting installa­tion of this system.
5. Re-read Installation section Step III — Install Fan Coil Units, on page 4 before installing indoor fan coil units.
INSTALLATION
I. COMPLETE PRE-INSTALLATION CHECKS A. Unpack Outdoor Unit (see Fig. 1)
Move 538S unit to final location. Remove carton from unit, being careful not to damage service valves and grilles.
B. Inspect Shipment
File claim with shipping company if shipment is damaged or incomplete. Check unit nameplate to be sure unit matches job requirements.
C. Consider System Requirements
Consult local building codes and NEC for specialinstallation requirements.
Allow sufficient space for airflow, wiring, refrigerant piping, and servicing unit. See Fig. 2 and 3.
Locate unit so that condenser coil airflow is unrestricted on both sides. Refer to Fig. 2 and 3.
—2—
Page 3
UNIT
538S
_
ABCDEFGH
Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm
024 2-1
1
⁄8638 3-015⁄
16
938 1-29⁄16370 1-4 406 1-117⁄16595 1-53⁄16437 1-51⁄2445 1-81⁄8511
048 3-1
3
⁄16945 3-89⁄
16
1132 1-51⁄16433 1-67⁄16468 2-61⁄
2
775 1-75⁄8499 2-55⁄8753 2-83⁄16818
UNIT
538S
_
J K L M N R S OPERATING WEIGHT
Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Lb Kg
024 1-2
7
⁄16367 0-63⁄4171 1-0 305 0-05⁄816 0-03⁄810 — — — — 159 72.0
048 1-2
3
⁄4375 0-71⁄2191 1-6 457 0-05⁄816 0-03⁄810 0-65⁄16160 0-57⁄8149 292 132.3
UNIT
538S
_
MINIMUM MOUNTING PAD DIMENSIONS
SUPPORT FEET SNOW STAND ICE STAND
Ft-in. mm Ft-in. mm Ft-in. mm
024 1-11 x 3-6 584 x 1067 2-2 x 3-6 660 x 1067 2-2 x 3-6 660 x 1067 048 2- 0 x 4-2 610 x 1270 2-4 x 4-4 711 x 1270 2-2 x 4-2 660 x 1270
NOTES:
1. Required clearances: with coil facing wall; allow 6 in. minimum clear­ance on coil side and coil end, and 3 ft minimum clearance on com­pressor end and fan side. With fan facing wall; allow 8 in. minimum clearance on fan side and coil end, and 3 ft minimum clearance on compressor end and coil side. With multi-unit application: arrange units so discharge of one does not enter inlet of another.
2. Dimensions in [ ] are in millimeters.
3. Center of gravity .
4. Thermistors are used with 619B and 619C fan coils only.
Fig. 2 — Base Unit Dimensional Drawing
—3—
Page 4
Unit may be mounted on a level pad directly on base legs or mounted on raised pads at support points. See Fig. 2 and 4 for center of gravity.
II. INSTALL OUTDOOR UNIT A. Mounting on Ground
Mount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly onto unit. If con­ditions or local codes require unit be fastened to pad, 6 field­supplied tiedown bolts should be used and fastened through slots provided in unit mounting feet. See Fig. 2.
B. Mounting on Roof
Mount unit on a level platform or frame at least 6 in. (154 mm) above roof surface. Isolate unit and tubing from structure.
C. Surrounding Fences and Walls
Select and install surrounding fences and walls to allow for free entry of ambient air. Avoid pits and solid walls as unit surroundings, because recirculation of warm discharge air can occur.
D. Rigging
CAUTION:
Be sure unit panels are securely in place
prior to rigging.
Keep unit upright. Lift unit using sling. Use cardboard or pad­ding under sling, and use spreader bars to prevent sling dam­age to unit. See Fig. 4. See Fig. 2 and 4 for center of gravity reference. Install unit so that coil does not face into prevail­ing winds. If this is not possible and constant winds above 25 mph are expected, field fabricate and install wind baffles. In areas where outdoor ambient will be less than 40 F during cooling, wind baffles are also required. Contact your local rep­resentative for drawings and assembly details.
III. INSTALL FAN COIL UNITS
Refer to Installation, Start-Up and Service Instructions pro­vided with the fan coil units.
NOTE: If this system is mixing 2 or more types of fan coil units, be sure to follow instructions provided with each type of fan coil unit closely.
Mount fan coil units in locations which will be easily acces­sible when routing refrigerant tubing (see Fig. 5 and 6) and electrical wiring between the fan coil unitsand outdoor unit. Fan coil unit locations must also provide adequate drainage capabilities. If desired, condensate pumps may be used with any type of fan coil unit.
IMPORTANT: DO NOT install filter driers or AccuRatert re- frigerant metering device body or pistons into this system. TXVs are located in the outdoor condensing unit to control refrigerant flow.
Fig. 4 — Lifting Unit With Sling
NOTE: Dimensions in [ ] are in mm.
(A) Minimum operating clearance required when this side faces a wall. (B) Minimum operating clearance required when this side faces away from a wall.
Fig. 3 — Operating and Service Clearance
—4—
Page 5
LEGEND
M—Motor
TXV — Thermostatic Expansion Valve
Field-Supplied Tubing
NOTE: Insulate ALL lines between outdoor condensing unit and indoor fan coil units.
Fig. 5 — Refrigerant Tubing Schematic (538S
_
048 Shown)
—5—
Page 6
LEGEND
NEC — National Electrical Code NOTE: Maximum system lift is 30 ft between lowest system compo-
nent and highest system component (see Fig. 7).
*See Connect Control Circuit Wiring section on page 9 for control
connection details.
Fig.6—Typical Piped System*
—6—
Page 7
IV. COMPLETE REFRIGERANT PIPING NOTE: Complete all refrigerant tubing connections at the fan
coil units first. Then route the tubing sets back to the out­door unit. Mark each tubing set carefully to identify its re­spective fan coil unit.
Outdoor units may be connected to indoor units using field­supplied tubing of refrigerant grade and condition. See Table 1 for correct line sizes. Do not use less than 10 ft of interconnecting tubing.
NOTE: It is not necessary to make any changes to line sizes or any refrigerant system modifications when using recom­mended refrigerant line lengths.
When installing tubing, both the vapor return line and the vapor supply (smaller) line must be insulated between out­door unit and indoor unit to avoid condensation on the lines. Use closed-cell foam insulation and tape all seams and joints.
CAUTION:
DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT TUBING IN THE GROUND. If any sec­tion of tubing is buried, there must be a 6-in. vertical rise to the valve connections on the outdoor unit. If more than the recommended length is buried, refrigerant may migrate to cooler, buried section during extended peri­ods of system shutdown. This causes refrigerant slug­ging and could possibly damage compressor at start­up.
DO NOT USE MORE THAN 50 FT of EQUIVALENT interconnecting tubing or more than 30 ft of VERTI­CAL lift (see Fig. 7) between the lowest system compo­nent and the highest system component.
If either refrigerant tubing or indoor coil is opened to atmo­spheric conditions for longer than 5 minutes, it must be evacu­ated to 1000 microns to eliminate contamination and mois­ture in the system.
Run refrigerant tubes as directly as possible, avoiding un­necessary turns and bends. Suspend refrigerant tubes so they do not damage insulation on vapor return or supply tubes and do not transmit vibration to structure. Also, when pass­ing refrigerant tubes through wall, seal opening so that vi­bration is not transmitted to structure. Leave some slack in refrigerant tubes between structure and outdoor unit to ab­sorb vibration. See Fig. 5 for indoor to outdoor unit tubing connections, and refer to separate indoor fan coil unit instal­lation instructions for additional information.
NOTE: If only 2 fan coil units are used on 538S_048 sys- tems, be sure that one is used with each compressor refrig­erant circuit. If 2 or 3 fan coil units are used, cap any unused refrigerant lines at the service valves.
WARNING:
DO NOT INSTALLAFIELD-SUPPLIED FILTER DRIER in this system. Filter drier is factory installed inside the outdoor unit. Installing a filter drier in the liquid line between the indoor and outdoor units will cause a high-pressure drop, and will result in ab­normal system operation.
Table 1 — Specifications
UNIT 538S
_
024 048
NOMINAL CAPACITY (Tons) 24 OPERATING WEIGHT (lb) 159 292 REFRIGERANT TYPE R-22
Control (Cooling) TXV in Condensing Unit Factory Charge (lb)*
Circuit A 5.0 5.5 Circuit B — 5.5
COMPRESSOR TYPE Copeland Scroll
Quantity...Model 1...ZR23K1 2...ZR49K3 Oil (Recharge) (oz) 25 53
OUTDOOR FAN Propeller, Direct Drive
Rpm 850 850 Diameter (in.)...No. of Blades 18...3 24...3 Pitch (Degrees) 27 24 Motor Hp
1
⁄
8
1
⁄
4
Nominal Air Cfm 1720 3900
OUTDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft)...No. of Rows 6.1...2 12.3...2 Fins/in. 15 15
CONTROLS
High-Pressure (psig)
Cut-in 320±20 Cutout 426 ± 7
Low-Pressure (psig)
Cut-in 22 ± 5
Cutout 7± 3 Fusible Plug 210 F Control Voltage 24
REFRIGERANT LINES
Connection Type Sweat Vapor Supply Line Quantity...OD (in.) 2...
3
⁄
8
2†...3⁄
8
Vapor Return Line Quantity...OD (in.) 2...5⁄
8
2†...7⁄
8
Maximum Length (ft) 50 50 Maximum Lift (Fan Coil Above Outdoor) (ft) 30** 30** Maximum Lift (Fan Coil Below Outdoor) (ft) 30** 30**
EXTERNAL FINISH Alpine Mist (Beige)
LEGEND
TXV — Thermostatic Expansion Valve
*Charge is based on 25 ft of interconnecting line.
†Per circuit.
**Maximum system lift is 30 ft between lowest system component and
highest system component.
—7—
Page 8
A. Make Piping Sweat Connections
Check tubing set identification against Multi-Split Installa­tion Planning Worksheet on page CL-1 to ensure correct se­lection of service valve set on outdoor unit.
Remove plastic caps from vapor supply and vapor return serv­ice valves. Use refrigerant grade tubing. Service valves are closed from the factory and are ready for brazing. Passnitro­gen or other inert gas through piping while brazing to pre­vent formation of copper oxide.
After wrapping the service valve with a wetcloth, the tubing set can be brazed to the service valve using either silver bear­ing or non-silver bearing brazing material. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing.
NOTE: Unit is shipped from the factory with a full system charge of R-22 (exact amount is indicated on unit name­plate).
CAUTION:
To avoid damage while brazing, service
valves should be wrapped with a heat-sinking material such as a wet cloth.
CAUTION:
When brazing tubing sets to the service valves, a brazing shield MUST be used to prevent dam­age to the painted unit surface.
B. Provide Safety Relief
A fusible plug is located in unit vapor return line; do not cap this plug. If local code requires additional safety devices, in­stall as directed.
C. Leak Test, Evacuate, and Dehydrate System
Refer to Leak Test and Evacuate and Dehydrate sections on page 13 for details.
V. MAKE ELECTRICAL CONNECTIONS
WARNING:
Unit cabinet must have anuninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur.This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit ap­proved for electrical ground when installed in accor­dance with NEC, ANSI/NFPA 70, and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
*The maximum system elevation is 30 ft from lowest point in the
system to highest point in the system.
Fig. 7 — Maximum Elevation Differential
—8—
Page 9
CAUTION: Unit failure as a result of operation on improper line voltage or excessive phase imbalance con­stitutes abuse and may cause damage to electrical com­ponents. Do not install units in system where voltage may fluctuate above or below permissible limits. Such operation would invalidate any applicable warranty.
A. Outdoor Condensing Unit
Be sure field wiring complies with local and national fire, safety, and electrical codes, and that voltage to the system is within limits shown in Table 2. Contact local power company for cor­rection of improper line voltage.
See Table 2 for recommended fuse sizes. When making elec­trical connections, provide clearance at unit for refrigerant piping connections.
B. Install Branch Circuit Disconnect Per NEC
Install a disconnect of adequate size to handle unit starting current. Locate disconnect within sight from and readily ac­cessible from unit per Section 440-14 of NEC.
C. Route Line Power Leads
Extend leads from disconnect through power wiring hole pro­vided and into unit splice area. Remove outdoor unit control box cover to gain access to unit wiring.
NOTE: Power leads from disconnect into outdoor unit must be COPPER WIRE ONLY.
D. Connect Ground Lead and Power Wiring
Connect ground lead to equipment ground connection in out­door unit control box. Then connect power wiring to TB1 (terminal block no. 1). See Fig. 8. Splice the line power leads to yellow and black leads provided.
E. Indoor Unit
Refer to installation instructions included with the fan coil units for fan coil unit installation and power supply details.
F. Connect Control Circuit Wiring
WARNING:
To avoid personal injury, be sure system
main power switch is turned off before proceeding.
1. Refer to Multi-Split Installation Planning Worksheetcom­pleted prior to the start of this installation and verify the markings on each set of control wiring cable sets.
2. Route 24-v control wiring through wiring hole on the out­door unit. See Fig. 9 for typical connections for each type of fan coil. See. Fig. 10 and 11 for 538S component ar­rangement and unit wiring details. See Fig. 12 for 538S to fan coil unit control wiring connection details.
3. Connect wiring to screw connections labeled FC1, FC2, FC3, and FC4 on terminal board for each corresponding fan coil unit. See Fig. 9-12.
4. Route the other end of the control wiring back to the fan coil unit and connect to the fan coil terminal board according to the wiring schematic for the fan coil unit. See fan coil unit installation instructions for wiring schematic.
G. Connect Thermistor Wiring
1. Refer to fan coil unit installation instructions for loca­tion of thermistor harness assemblies (not used on 619F units). The installation instructions are shipped with each fan coil unit. Connect the outdoor unit thermistor har­ness plugs at the matching fan coil unit terminal blocks.
2. Label each thermistor harness per the previously com­pleted Multi-Split Installation Planning Worksheet.
3. Route the thermistor harness assemblies from the out­door unit to the indoor fan coil units.
IMPORTANT: DO NOT RUN THE THERMISTOR CABLES IN THE SAME CONDUIT AS THE CON­TROL CIRCUIT OR POWER WIRING.
4. Route harnesses into 538S unit junction box.
5. Connect each thermistor plug to its matching plug in the outdoor condensing unit.
Table 2 — Electrical Data
UNIT SIZE
538S
_
V-PH-Hz
OPERATING
VOLTAGE
MINIMUM*
OPERATING
VOLTAGE
MAXIMUM*
COMPRESSOR FAN POWER SUPPLY
Quantity
RLA
(Ea)
LRA
(Ea)
FLA MCA
Max Fuse
or HACR-Type
Circuit Breaker Amps
024
208/230-1-60 187 254
1
12.9 62.5
0.70 16.8 25
048 2 1.45 30.5 40
LEGEND
FLA — Full Load Amps HACR — Heating, Air Conditioning, Refrigeration LRA — Locked Rotor Amps MCA — Minimum CircuitAmps NEC — National Electrical Code RLA — Rated Load Amps (Compressor)
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
NOTES:
1. The 538S units contain a 24-v transformer; additional transformers are not required.
2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combina­tion load equipment (refer to NEC Articles 430 and 440), the over­current protective device for the unit shall be fuse or HACR breaker.
4. Motor RLAvalues are established in accordance with UL (Underwrit­ers’ Laboratories) Standard 1995.
LEGEND
NEC — National Electrical Code
Field Wiring
TB — Terminal Board
Factory Wiring
TB Connections
Fig. 8 — Line Power Connections
—9—
Page 10
LEGEND
FC — Fan Coil Unit OCT TH — Outdoor Coil Temperature Thermistor TB — Terminal Block
Fig. 9 — Control Line Connections (Typical Connections for Each Type of Fan Coil Illustrated)
—10—
Page 11
Fig. 10 — Component Arrangement, 538S_024
Fig. 11 — Component Arrangement, 538S_048
LEGEND FOR FIG. 10 AND 11
C—Contactor, Compressor CAP — Capacitor CLO — Compressor Lock Out COMP — Compressor Motor CT — Current Transformer DTS — Discharge Temperature
Switch
EQUIP — Equipment FC — Fan Coil Unit FCR — Fan Coil Relay FR — Fan Relay GND — Ground
HPS — High-Pressure Switch J—Connector LPS — Low-Pressure Switch LA — Low Ambient MCB — Multi-Split Control Board NEC — National Electrical Code OCT — Outdoor Coil Temperature OFM — Outdoor-Fan Motor P—Connector SV — Solenoid Valve TB — Terminal Block TH — Themistor
TR — Transducer TRAN — Transformer
Terminal (PCB, Field) Terminal (PCB, Factory)
Terminal (Marked) Terminal (Unmarked)
Terminal Block Splice
Factory Wiring Field Control Wiring Field Power Wiring Option or Accessory Wire PCB Run
—11—
Page 12
LEGEND
C—Compressor FC — Fan Coil J, P — Connectors LED — Light-Emitting Diode SW — Switch
Fig. 12 — Outdoor Unit Microprocessor Control Board
—12—
Page 13
H. Reconfigure for One Fan Coil Unit per Compressor Circuit if Necessary
The control also provides the option of using either 1 or 2fan coil units per compressor (depending on the position of the jumpers on J3 and J4 on the control board). See Fig. 12. The control is preset to 2 fan coil units per compressor at the fac­tory. If only one fan coil per compressor is to be used, position a jumper between pins 1 and 2 on J3 and J4 (one jumper for each set of pins). Jumper J3 is associated with the compres­sor on the 538S_024 units and compressor number 1 on 538S_048 units (bottom compressor). Jumper J4 is associ­ated with compressor number 2 on the 538S_048 units.
START-UP
I. LEAK TEST
Field piping and all tubing connections must be leak tested by the pressure method. Use R-22 at approximately 25 psig backed up with an inert gas to reach a total system pressure not to exceed 245 psig.
II. EVACUATE AND DEHYDRATE
Field piping and fan coil must be evacuated and dehydrated to 1,000 microns using accepted practices.
WARNING:
Service valves must be fully backseated to close service port. There is no Schrader valve at the service port, and failure to backseat the valve could re­sult in loss of system charge or personal injury.
III. CHARGE SYSTEM
Release charge into system by opening (backseating) vapor supply and vapor return line service valves. Open ONL Ythose service valve sets which have fan coil unit sections connected to them. DO NOT open valves where no field tubing has been connected.
IV. PRELIMINARY CHECKS
Complete Start-Up Checklist on page CL-1 and the following checks prior to starting up unit.
1. Check condensate drainage system. T odo this, add a small amount of water into each fan coil unit condensate pan, and ensure that each pan drains freely. Inspect drain pans and lines, and clean as required.
2. Make sure that all wiring connections are correct and tight.
3. Check all barriers, covers, and panels to ensure they are in place.
4. Identify which fan coil unit valve sets have been connected.
IMPORTANT: DO NOT open valves which do not have fan coil units connected to them.
5. Unit is shipped with the valve stems frontseated and caps factory installed. Remove caps from all valves to which fan coil units have been connected. Replace caps and tighten until finger tight.
6. Fully backseat (open) the vapor supply and vapor re­turn tube service valves.
7. Turnon main disconnect switch(es) to indoor fan coil units and outdoor condensing unit.
8. Using the remote controller for each indoor fan coil unit, turn on each fan coil unit and operateeach unit in each mode (i.e., electric heat [if provided], and fan cooling) for 15 minutes to test for proper operation.
9. Test for proper refrigerant charge in each circuit using the subcooling method.
V. OPERATING SEQUENCE NOTE: AUTO. fan mode is used as the unit operation ex-
ample for ALL fan coil units in this section. Contact your lo­cal Carrier dealer for operationinformation in other fan modes.
A. Fan Coil Units
Each fan coil unit has a self-contained control system that determines the set point for fan coil operation, fan mode op­eration, and heating mode operation (if provided). The 619B and 619C fan coil units are equipped with either a wired or wireless remote controller set (remote controller is not avail­able for 619F fan coil units). Set points and fan modes may be determined separately for each fan coil unit.
Each fan coil unit may call for cooling operation indepen­dently. On a call for cooling operation by a single fan coil unit, a 24-v signal is sent to the 538S outdoor unit and energizes a control relay. The indoor blower starts according to the nor­mal fan coil unit sequence of operation. The control relay (in the outdoor unit) initiates operation of a cooling cycle for the respective indoor unit refrigerant circuit; including opening a liquid line solenoid valve in the outdoor unit.
As the set point at each fan coil is satisfied, its individual 24-v signal to the 538S unit stops, and the respective sole­noid valve for each fan coil unit closes. The indoor fan cycles off. The 619B and 619C fan coil units then begin room sam­pling operation after a 3-minute off period (during sampling, the fan motor runs at low speed for 1 minute to sample the demand in the space; then cycles off until the next sampling period if no demand is found).
B. 538S Outdoor Condensing Unit
The outdoor unit is equipped with a control that will monitor the indoor fan coil unit cooling request. The control will turn on solenoid valves for the appropriate indoor fan coil unit sys­tem. The control will also combine the cooling requests to con­trol up to 2 compressors.
The control provides a 2-minute compressor time-delay de­vice which disables the compressor for 2 minutes. The time delay device timers will be initialized when the unit is pow­ered up (for the first 2 minutes).
The 538S unit control includes an integral head pressure con­trol function. This function will maintain a minimum head pressure by cycling the outdoor fan motor in response to in­puts from the thermistor (for outdoor ambient temperature) and the transducers (for system discharge pressures in each compressor circuit).
The head pressure for the compressor(s)will be monitored to control the outdoor fan output. The control reads an outdoor temperature thermistor to determine if thehead pressure should be used to control the outdoor fan output.
Operation The 538S unit receives a 24-v control signal from each fan
coil unit as each fan coil unit initiates a demand for cooling. The 24-v signal energizes a control relay in the 538S unit (one relay per fan coil unit). The refrigerant flow to each fan coil unit is controlled through a solenoid valve (one valve per fan coil unit). The solenoid valve(s) will not open until compres­sor operation is initiated by the controller.
The microprocessor control inthe 538S unit includes a 2-minute, anti-short cycle, time-delay function. This function provides a minimum time-off delay between compressor run stages (2 minutes each from the end of the last on period to the be­ginning of the next on period). If more than 2 minutes have passed since the end of the last on period, the compressor will be ready to restart with initiation of demand from any fan coil unit on its circuit.
—13—
Page 14
Increased Demand for Cooling NOTE: There are 2 separate compressor circuits in the
538S_048 units (circuit A and circuit B). Each circuit oper­ates independently, and will operate as follows (as will the single-circuit 024 units) upon receiving the first 24-v cooling demand signal from a fan coil unit:
1. After the 2-minute time-delay function is satisfied, the appropriate compressor starts.
2. The solenoid valve connected to the fan coil sending the demand signal is energized (at the 538S units).
3. The outdoor fan starts, and its operation is controlled by the microprocessor as described in 538S Microproces­sor Control of Outdoor Fan section below.
When a second fan coil unit signals a demand for cooling, its associated solenoid valve is energized immediately, allowing refrigerant to flow to both fan coil units simultaneously.
Decreased Demand for Cooling When a fan coil unit’s demand for cooling ends, the 24-v sig-
nal to the 538S unit stops, and the appropriate solenoid valve closes. If the other fan coil unit on this circuit still has a de­mand, the appropriate compressor will continue to run as long as necessary for the second fan coil unit.
When the second fan coil unit’s demand for cooling ends, its solenoid valve closes, and the appropriate compressor stops. The compressor will not start for at least 2 minutes after the end of this cycle due to the time-delay function.
On size 024 units, when the compressor stops, the outdoor fan also stops. On size 048 units, outdoor fan operation may continue under control of the 538S microprocessor if the other refrigerant circuit is still operating. The outdoor fan will only stop when both compressors are off. Refer to 538S Micro­processor Control of Outdoor Fan section below for more details.
C. 538S Microprocessor Control of Outdoor Fan
The microprocessor control has a built-in head pressure con­trol system that will cycle the outdoor-fan motor to maintain a selected discharge pressure. The microprocessor senses out­door ambient temperature using a thermistor and refriger­ant pressure using a pressure transducer mounted on the compressor circuit discharge line. The 538S_024 units have one transducer, and the 048 units have two.
The factory set points for the head pressure control opera­tion are 55 F for outdoor ambient temperature and 250 psig for discharge pressure.
When the outdoor ambient temperature is above theoutdoor ambient set point and both fan coils on a compressor circuit are calling for cooling operation, the outdoor fan will run at
full speed whenever compressor operation is permitted. When only one fan coil on a circuit is calling for cooling, fan cycling is permitted at all ambients. Fan motor will becycled on and off to maintain set point discharge pressure.
When the outdoor ambient temperature is below the speci­fied set point, the fan motor will be cycled on and off to main­tain a compressor discharge pressure at the specified pres­sure set point. On 538S_048 units with 2 compressors running, the compressor with the lower head pressure will control the fan operation. If only one compressor is running, that com­pressor will control the fan operation.
If the discharge pressure on either circuit exceeds 370 psig, the outdoor-fan motor will run continuously, and the fan cy­cling function will be bypassed until the discharge pressure decreases to 365 psig.
Units can be field configured to select head pressure control at 35 F outdoor ambient and/or 200 psig discharge pressure.
D. Status Indicator Lights
The 538S control board is equipped with LED indicators to aid in evaluating the status of the control system, including (see Table 3):
• time delay function status
• fan coil unit demand status
• head pressure control status
• current unit malfunctions
E. Unit Malfunction
Each compressor circuit isequipped with a high-pressure switch (HPS), a loss-of-pressure switch (LPS), and a discharge tem­perature switch (DTS). These safety devices are located in a Cycle-LOC™ device circuit that prevents compressor opera­tion if any of these safety devices is activated. The lockout can be reset by turning the main power to the 538S unit off, then on again.
Compressor overcurrent protection is achieved by an inter­nal linebreak overload, which will automatically reset when the motor temperature cools to a satisfactory level. Manual reset of Cycle-LOC circuit may also be required (turn main unit disconnect to OFF, then to ON position).
Pressure transducers and the outdoor ambient thermistor are monitored by the 538S controller. If a pressure transducer is found to be out of range, the LEDs will flash a code for this fault, but the control will continue to cycle the outdoor fan according to input from the other transducer.If only one trans­ducer is active and is determined to be out of range, the head pressure control will be bypassed and the fan will run con­tinuously. If the thermistor is found to be out of range, the control will allow fan cycling per transducer input, and the LEDs will flash a code for this failure. See Table 3.
Table 3 — System Status Red and Green LEDs and Fault Codes
GREEN LED RED LED
UNIT STATUS
Number of
Flashes On
Number of
Flashes Off
Number of
Flashes On
Number of
Flashes Off
1 1 — Always Off System Ready 1111 LowHead Pressure, Circuit 1 1122 High Head Pressure, Circuit 1 1133 LowHead Pressure, Circuit 2 2211 High Head Pressure, Circuit 2 2222LowOutdoor Ambient Temperature, Outdoor Thermistor 2233High Outdoor Ambient Temperature, Outdoor Thermistor 3311 Hardware Error 3322 TimeGuardT Device Active, Circuit 1 3333 TimeGuard Device Active, Circuit 2
LED — Light-Emitting Diode
—14—
Page 15
SERVICE
WARNING:
Before performing recommended main­tenance, be sure unit main power switch is turned off, and be sure all disconnects for indoor fan coil units are open. These systems typically have one disconnect per fan coil unit. Failure to turn off unit main power and open all disconnects may result in electrical shock or injury from rotating fan blade.
I. OUTDOOR FAN
A reinforced wire mount holds the outdoor fan assembly in position. See Fig. 13 for proper mounting positions.
II. SCROLL COMPRESSORS
The 538S condensing units use scroll compressors. The 538S_024 unit has one compressor, and the 538S_048 unit has 2 compressors which are stacked vertically (using a sheet metal stand to support the top compressor). In the event of a compressor failure, remove and replace the compressor(s) as follows:
1. Attach refrigerant hose to vapor return line service valve of the circuit related to the defective compressor.
2. Recover refrigerant using accepted techniques.
3. Remove discharge and suction piping from compressor by unsweating. Pass either nitrogen or another inert gas through the compressor.
4. Remove compressor mounting bolts. Use a swivel socket to remove the bolt in the rear.
5. Carefully pull compressor stand and piping away from the compressor to remove the compressor.
6. Reverse Steps 1-5 to install the new compressor.
A. Time-Delay Device Override
The time delay device can be overridden for easier unit ser­vicing by temporarily shorting the time delay device override connector (P9) located in the control box. See Fig. 12. The short MUST be removed before the time delay device timer can be cleared.
B. System Status LEDs and Fault Codes
In normal operating mode, the green LED located on the out­door unit microprocessor board will flash on and off at a rate of once per second. Whenever a fan coil unit, compressor, or outdoor fan is energized, a red LED designated for each fan coil unit will be illuminated. If there is an error condition, a code will be displayed using the green and red system status LEDs. The green LED will blink its code first, followed by the red LED. The LEDs will flash at a rate of once every 2 seconds, with a 2-second pause between the last red LED flash and the first green LED flash of the next code. See Table 3.
III. HIGH-PRESSURE RELIEF VALVE
Valve is located in compressor. Relief valve opens at a pres­sure differentialof approximately 4506 50 psig between suc­tion (low side) and discharge (high side) to allow pressure equalization.
IV. INTERNAL CURRENT AND TEMPERATURE SENSITIVE OVERLOAD
Control resets automatically when internal compressor mo­tor temperature drops to a safe level (overloads may require up to 45 minutes to reset). When aninternal overload is sus­pected of being open, check by using an ohmmeter or conti­nuity tester.
V. HIGH-PRESSURE SWITCH
This switch, located on discharge line, protects against high discharge pressures caused by such events as overcharge, condenser-fan motor failure, system restriction, etc. It opens on pressure rise at about 426 psig. If system pressures go above this setting duringabnormal conditions, the switch opens.
WARNING:
DO NOT attempt to simulate these sys­tem abnormalities — high pressures pose a serious safety hazard.
High-pressure switch is checked with an ohmmeter. If sys­tem pressure is below approximately 320 psig, switch shows continuity. The high-pressure switch will reset automatically after CLO (compressor lockout switch) has been reset and time­delay device has completed its timing cycle.
NOTE: If pressure switch needs to be replaced, there is a Schrader valve located under the switch so that system will not need to be evacuated.
VI. LOW-PRESSURE SWITCH
This switch, mounted on the vapor return line, has fixed, non­adjustable settings. To check pressure switch, attach pres­sure gage to vapor return line service valve gage port. Slowly close liquid shutoff valve and allow compressor to pump down. Do not allow compressor to pump down below 2 psig. Com­pressor should shut down when suction pressure drops to about 7 psig, and should restart when pressure builds up to about 22 psig after CLO has been reset and time-delay device has completed its timing cycle.
NOTE: If pressure switch needs to be replaced, there is a Schrader valve located under the switch so that system will not need to be evacuated.
VII. SERVICE VALVES
The service valves in the outdoor unit are frontseated at the factory. This means the refrigerant charge is isolated from the line-set connection ports. Toprevent damage to the valve, use a wet cloth or other accepted heat sink material on the valve before brazing.
The service valves must be backseated (turned counter­clockwise until seated) before the service port caps are re­moved and the hoses of gage manifold connected. In this po­sition, refrigerant has access from and through outdoor and indoor unit. The service valve cannot be field repaired; only a complete valve or valve stem seal and service port caps are available for replacement.
NOTE: Do not open service valves which are not connected to a tubing set. Be sure any inactive circuits are capped off.
UNIT SIZE — in. (mm)
538S_024 538S_048
.709 (18) .16 (4)
Fig. 13 — Condenser-Fan Mounting Positions
—15—
Page 16
VIII. REFRIGERANT CHARGING
WARNING:
To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding.
WARNING:
Service valves must be fully backseated to close service port. There is no Schrader valve at the service port, and failure to backseat the valve could re­sult in loss of system charge or personal injury.
NOTE: Do not vent or depressurize unit refrigerant to atmo­sphere. Remove and recover refrigerant following accepted practices.
The 538S units are factory charged with a full operatingcharge. Check the system for proper charge level using the subcool­ing method.
If a refrigerant system must be opened for major service work, first recover refrigerant in system using accepted practices. Evacuate and dehydrate the system whenready to recharge; then weigh in the proper refrigerant quantity (as marked on the unit data plate for each circuit.)
A. Subcooling Charging Method
1. Operate the unit a minimum of 15 minutes before check­ing the charge.
2. Measure discharge pressure by attaching an accurate gage to the discharge service port. DO NOT use the ex­ternal service valves for this pressure reading.
3. Measure the vapor supply line temperature by attach­ing an accurate thermistor-type or electronic thermom­eter to the vapor supply line near the outdoor coil. See Fig. 14.
4. Refer to Table 4 to find the required subcooling tempera­ture for the unit. Find the point at which the required subcooling temperature intersects the measured inter­nal discharge service port pressure in Table 5.
5. To obtain the requiredsubcooling temperature at a spe­cific discharge pressure, add refrigerant if vapor supply line temperature is higher than indicated, or remove re­frigerant if temperature is lower than indicated. Allow a tolerance of ± 3%.
IX. COMPRESSOR LOCKOUT SWITCH (CLO)
Units are provided with compressor lockout protective de­vice. If the compressor shuts down due to any safety device, a current loop monitoring the compressor current senses no current flow. The unit will lock out until the control power is interrupted to reset the lockout. Determine reason for safety trip. To restart, turn the 538S main disconnect to OFF, then to ON position.
Table 4 — Required Unit Subcooling
UNIT 538S
_
SUBCOOLING AT TXV INLET (F)
WITH ALL FANS OPERATING
024 19 048 16
TXV — Thermostatic Expansion Valve
Table 5 — Required Liquid Line Temperatures
PRESSURE
(Psig) AT SERVICE
FITTING
REQUIRED SUBCOOLING TEMPERATURE (F)
0 5 10 15 20 25
134 76 71 66 61 56 51 141 79 74 69 64 59 54 148 82 77 72 67 62 57 156 85 80 75 70 65 60
163 88 83 78 73 68 63 171 91 86 81 76 71 66 179 94 89 84 79 74 69 187 97 92 87 82 77 72
196 100 95 90 85 80 75 205 103 98 93 88 83 78 214 106 101 96 91 86 81 223 109 104 99 94 89 84
233 112 107 102 97 92 87 243 115 110 105 100 95 90 253 118 113 108 103 98 93 264 121 116 111 106 101 96
274 124 119 114 109 104 99 285 127 122 117 112 107 102 297 130 125 120 115 110 105 309 133 128 123 118 113 108
321 136 131 126 121 116 111 331 139 134 129 124 119 114 346 142 137 132 127 122 117 359 145 140 135 130 125 120
LEGEND
SV — Service Valve X—Measurement Location
Fig. 14 — Vapor Supplly Line Measurement
Locations (538S_048 Unit Shown)
—16—
Page 17
X. OUTDOOR-COIL TEMPERATURETHERMISTOR (OCT TH)
Thermistor is for use only with duct-free split systems em­ploying a microprocessor control (619B and 619C fan coil units only) as part of the system diagnostics. Refer to separate in­stallation instructions for the 619B and 619C indoor units. The thermistor is mounted in a well attached to the con­denser coil. See Table 6 for thermistor characteristics.
NOTE: The 619F in-ceiling fan coil units use 24-v electro­mechanical controls for system diagnostics. Refer to 619F in­stallation instructions for more details.
Table 6 — Thermistor Characteristics
TEMP (F)
RESISTANCE (OHM)
MIN NOMINAL MAX
20 36,230 37,100 37,980 30 28,330 28,930 29,540 32 26,870 27,430 27,990 40 22,320 22,740 23,160 50 17,710 17,990 18,280 60 14,230 14,420 14,620 70 11,490 11,630 11,760 77 9,900 10,000 10,100 80 9,340 9,440 9,540
90 7,610 7,700 7,800 100 6,230 6,320 6,410 110 5,130 5,220 5,310 120 4,250 4,340 4,420 130 3,550 3,620 3,690 140 2,960 3,030 3,100 150 2,500 2,560 2,620 160 2,120 2,170 2,230 170 1,810 1,850 1,900 180 1,540 1,580 1,630 190 1,320 1,360 1,400 200 1,140 1,170 1,210 210 980 1,020 1,050 212 954 986 1,019 220 853 882 912 230 742 769 796
NOTES:
1. A high quality digital volt-ohmmeter is required to check thermistor resistance.
2. Measure temperature at thermistor location with an accurate thermocouple­type temperature measuring instrument.
3. If a more accurate check is required, thermistor must be removed and checked at a known temperature (freezing point or boiling point of water).
XI. LOW-AMBIENT CONTROL THERMISTOR (LAT)
The low-ambient control thermistor is located on the outdoor fan support bracket. See Operating Sequence section on page 13 and Fig. 12 for more information about the controls.
XII. PRESSURE TRANSDUCER
The pressure transducer activatesthe low-ambient control when discharge pressure drops to either 250 psig or 200 psig based on the setting of control jumper J1. See Operating Sequence section on page 13 for more information about the controls.
If transducer has to be removed for any reason, first discon­nect the snap lock plug. The transducer can now be un­screwed and removed without loss of refrigerant since there is a Schrader-type core valve in the transducer port. When reinserting the transducer, reverse this procedure. Be care­ful not to overtighten the transducer.
MAINTENANCE
WARNING:
Before performing recommended main­tenance, be sure unit main power switch is turned off. Failure to do so may result in electric shock or injury from rotating fan blade.
I. LUBRICATION A. Fan-Motor Bearings
Oiling holes are provided at each end of condenser-fan motor. Remove fan motor and lubricate motor with 32 drops (16 drops
per hole) of SAE-10 (Society of Automotive Engineers) non­detergent oil at the following intervals:
• Annually when environment is very dirty, ambient tem­perature is higher than 105 F, and average unit operating time exceeds 15 hours a day, or
• Every 3 years when environment is reasonably clean, am­bient temperature is less than 105 F, and unit operating time averages 8 to 15 hours a day, or
• Every 5 years when environment is clean, ambient tem­perature is less than 105 F, and unit operating time aver­ages less than 8 hours a day.
B. Compressor
Compressor contains factory oil charge; replace oil when lost. See Table 1 for oil recharge.
NOTE: Use only Cryol 150A oil in these units. II. CLEANING COILS
Coil should be washed out with water or blown out with com­pressed air. Note that the blow-thru design causes dirt and debris to build up on the inside of the coils.
Clean coil annually or as required by location and outdoor air conditions. Inspect coil monthly and clean as required. Fins are not continuous through coil sections. Dirt and debris may pass through first section, become trapped be­tween the rows of fins, and restrict condenser airflow. Use a flashlight to determine if dirt or debris has collected between coil sections. Clean coil as follows:
1. Turn off unit power.
2. Using a garden hose or other suitable equipment, flush coil from the outside to remove dirt. Be sure to flush all dirt and debris from drain holes in base of unit. Fan mo­tors are waterproof.
TROUBLESHOOTING
I. CHECKING COOLING CONTROL OPERATION
Check the system for proper control operation as follows (re­fer to Troubleshooting Chart on page 18 for more details):
1. Check status LED at the 538S control board. A green LED will flash on and off at one-second intervals when the unit is ready to run. If a time delay function is ac­tive (3 green LED flashes followed by 2 or 3 red LED flashes), wait 2 minutes for time delay to clear.
2. At a fan coil unit remote controller, (619B or 619C units) select AUTO fan mode, COOL system mode, and adjust set point down until thermometer segment is fully dis­played. Notice the snowflake display on the handset (sys­tem mode is COOL) and the compressor run display (demand signal is being sent to the outdoor unit). Note that the indoor fan starts at low speed.
For 619F units, position selector switch at subbase in each fan speed setting in sequence.
3. At the outdoor unit, check that the LED signal lamp for the indoor fan coil unit is illuminated, that the compres­sor and the outdoor-fan motor start and run, that the solenoid valve for the indoor fan coil is energized, and that refrigerant is flowing to the correct indoor unit.
4. Observe that cooling operation shuts down when con­trol setting at the fan coil unit is satisfied (compressor stops, outdoor fan stops, solenoid valve closes, andLED for fan coil demand is off).
5. Observe operation of indoor fan during the off period. The fan will be off for 3minutes, then turnon for 1minute at low speed (for occupied space air temperature sampling).
—17—
Page 18
LEGEND
HPS — High-Pressure Switch
LLSV — Liquid (Vapor Supply) Line Solenoid Valve
LPS — Low-Pressure Switch
TXV — Thermostatic Expansion Valve
TROUBLESHOOTING CHART
—18—
Page 19
Page 20
Copyright 1996 Carrier Corporation CATALOG NO. BDP-3353-801
Loading...