Bryant 558D User Manual

installation, start-up and service instructions
SINGLE PACKAGE ROOFTOP ELECTRIC HEATING/ELECTRICCOOLING UNITS
Cancels: II 558D-36-4 II 558D-36-5
558D
Sizes 036-072
3to6Tons
2/1/99
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation in­structions before installing this unit (see Fig. 1).
2. Be sure the installation conforms to all applicable local and national codes.
3. These instructionscontainimportantinformation for the proper maintenance and repair of this equipment. Re­tain these instructions for future use.
Page
SAFETY CONSIDERATIONS ................... 1
INSTALLATION ...........................1-16
I. Locate the Unit ....................... 3
II. Unit Duct Connections .................. 3
III. Rig and Place Unit ..................... 3
IV. Field Connections ..................... 6
PRE-START-UP ............................17
START-UP ..............................17-28
I. Heating Section Start-Up and Adjustments ....17
II. Cooling Section Start-Up and Adjustments ....18
III. Indoor Airflow and Airflow Adjustments ......19
CARE AND MAINTENANCE ...................28
I. Air Filter ............................28
SERVICE ...............................28-31
I. Cleaning ............................28
II. Lubrication ..........................29
III. Condenser Fan Adjustment ...............29
IV. Refrigerant Charge .....................30
V. Replacement Parts .....................30
TROUBLESHOOTING ......................32-35
START-UP CHECKLIST .....................CL-1
WARNING:
nance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
1. The power supply (volts, phase, and hertz) must corre­spond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be suf­ficient to handle load imposed by this unit.
3. Refer to Locate the Unit section on page 3 and Fig. 2 for locations of electrical inlets, condensate drain, duct con­nections and required clearances before setting unit in place.
4. This installation must conform with local building codes and with NEC (National Electrical Code) or NFPA (National Fire Protection Association) 54 TIA-54-84-1. Refer to Provincial and local plumbing or wastewater codes and other applicable local codes.
5. Approved for outdoor installation on wood flooring or on class A, B, or C roof covering materials.
Unit is shipped in the vertical airflow configuration (see Fig. 1). To convert tohorizontal discharge, remove horizontal duct opening covers. Using the same screws, install covers with insulation-side down (facing outside) over vertical duct openings on the unit. Seals around duct openings must be tight.
All units can be connected into existing duct systems that are
properly sized and designed to handle an airflow of 300 to 500 cfm per each 12,000 Btuh of rated cooling capacity.
NOTE: When installing any accessory item, see the manu­facturer’s installation instructions packaged with the acces­sory. A qualified installer or agency must use only factory­authorized kits or accessories when modifying this unit.
Before performing service or mainte-
INSTALLATION
SAFETY CONSIDERATIONS
Recognize safety information. This is the safety-alert sym­bol ( ). When you see this symbol on the unit and in in­structions or manuals, be alert to the potential for personal injury.
Understand the signal words — DANGER, WARNING, and CAUTION. These words are used with the safety-alert sym­bol. Danger identifies the most serious hazards which will result in severe personal injury or death. Warning indicates a condition that could result in personal injury. Caution is used to identify unsafe practices which would result in minor personal injury or product and property damage.
Fig.1—Typical Unit
*Indicates horizontal center of gravity. †Indicates vertical center of gravity.
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail): a. Bottom of basepan to combustible surfaces (when not using curb), 0 inches. On
horizontal discharge units with electric heat, 1 in. clearance to ductwork for 1 foot.
b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting
the greater clearance is optional. c. Overhead, 60 in. to assure proper condenser fan operation. d. Between units, control box side, 42 in. per National Electrical Code (NEC). e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC. f. Between unit and block or concrete walls and other grounded surfaces, control box
side, 42 in. per NEC. g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearances as stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
CONNECTION SIZES
1
A 1
⁄89 dia [28.6] field power supply hole
3
B
⁄49-14 NPT condensate drain
3
C 1
⁄89 dia [35] power supply knockout
D 29 dia [50.8] power supply knockout
UNIT
STD UNIT
WEIGHT
ECONOMIZER WEIGHT
DURABLADE PARABLADE
CORNER WEIGHT
(A)
CORNER WEIGHT
(B)
CORNER WEIGHT
(C)
CORNER WEIGHT
(D)
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
558D036 365 165.6 34 15.4 42 19.1 126 57.2 89 40.4 111 50.3 39 17.7 558D048 375 170.1 34 15.4 42 19.1 128 58.1 90 40.8 114 51.7 43 19.5 558D060 395 179.2 34 15.4 42 19.1 132 59.9 94 42.6 120 54.4 49 22.2 558D072 470 213.2 34 15.4 42 19.1 148 67.1 103 46.7 155 70.3 64 29.0
Fig. 2 — Base Unit Dimensions
—2—
I. LOCATE THE UNIT A. Clearance
Maintain clearance around and above unit to provide mini­mum distance from combustible materials, proper airflow,and service access (see Fig. 2 and 3).
Minimum clearance to combustibles is 0 in. on all sides. Minimum clearance to block walls or any other grounded sur-
face is 42 in. on all sides. Minimum clearance of 36 in. should be providedon side with
outdoor-air intake, if unit is so equipped. Minimum clearance between unit and other electrically live
parts is 48 inches. Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contami­nated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Slab mounted units should be at least 4 in. above the highest expected water, flood and runoff levels. Do not use theunit if it has been under water.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 4. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 5. Correct leveling tolerance is necessary for unit drain to function properly.
C. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser-coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb, if required.
II. UNIT DUCT CONNECTIONS
On vertical units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. On horizontal units, duct flanges should be attached to horizontal openings and all ductwork should be secured to flanges.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
Aminimum clearance is not required around ductwork. Cabi­net return-air static shall not exceed −0.20 in. wgwith PARA­BLADE economizer, −0.35 in. wg with Durablade economizer, or −0.45 in. wg without economizer.
NOTE: Connection must be made to roof curb before unit is set in place.
Fig. 3 — Service and Operational Clearances
B. Roof Curb Mount
Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 4. Install insulation, cant strips, roofing felt, and counter flashing as shown. Duct- work must be attached to curb. If electric or control power is to be routed through the curb, attach the accessorythru-the­bottom connections to the basepan in accordance with the ac­cessory installation instructions. Accessory electric connections must be installed before unit is in place on roof curb.
III. RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by us­ing unit frame as a reference. See Table 1 and Fig. 6 for ad­ditional information. Operating weight and maximum weight are shown in Table 1 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.
IMPORTANT: If unit has forklift protection skids, be sure to remove forklift protection skids from under unit before set­ting unit in place.
A properly positioned unit will have the following clearances between unit and roof curb: and base rails on each side and front of unit; 1
1
⁄4-in. clearance between roof curb
5
⁄32-in. clear­ance between roof curb and rear of unit. See Fig. 4, Views A-A and C-C.
After unit is in position, remove shipping materials and rig­ging skids.
—3—
ROOF CURB ACCESSORY
CRRFCURB001A00
CRRFCURB002A00
‘‘A’’ UNIT SIZE
149
[356]
558D036-072
249
[610]
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb. (Flanges of duct rest on curb.)
6. Service clearance 4 ft on each side.
7. Direction of airflow.
—4—
UNIT SIZE ‘‘B’’ ‘‘C’’
11
16
9
558D036-072
21
[551]
169
[406]
‘‘D’’Alt
Drain Hole
13⁄
4
9
[44.5]
Power Control Connector Package Accessory
3
⁄49 NPT1⁄29 NPT
1
⁄49 NPT1⁄29 NPT
1
CRBTMPWR001A00
(THRU-THE-BOTTOM)
CRBTMPWR002A00
(THRU-THE-BOTTOM)
Fig. 4 — Roof Curb
Table 1 — Specifications
BASE UNIT 558D 036 048 060 072 NOMINAL CAPACITY (tons) 3456 OPERATING WEIGHT (lb)
Unit 365 375 395 470 Durablade Economizer 34 34 34 34 PARABLADE Economizer 42 42 42 42 Roof Curb 115 115 115 115
COMPRESSOR TYPE Reciprocating Reciprocating Reciprocating Scroll
Quantity 1111 Oil (oz) 50 50 50 54
REFRIGERANT TYPE R-22
Operating Charge (lb-oz) 3-6 5-8 7-0 7-11
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 1...17 1...17 2...17 2...17 Total Face Area (sq ft) 7.36 13.19 10.42 10.42
CONDENSER FAN Propeller Type
Nominal Cfm 3500 4000 4000 4000 Quantity...Diameter (in.) 1...22.0 1...22.0 1...22.0 1...22.0 Motor Hp...Rpm Watts Input (Total) 325 325 325 325
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Rows...Fins/in. 2...15 2...15 3...15 4...15 Total Face Area (sq ft) 4.17 5.5 5.5 5.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 Type Drive Std Direct Direct Direct Belt Nominal Cfm Std 1200 1600 2000 2400 Maximum Continuous Bhp Std .34 .75 1.20 2.40 Motor Frame Size Std 48 48 48 56 Nominal Rpm High/Low Std 860/800 1075/970 1075/970 Fan Rpm Range Std 1070-1460 Motor Bearing Type Ball Ball Ball Ball
Maximum Allowable Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.8/3.8
Nominal Motor Shaft Diameter (in.) Std Fan Pulley Pitch Diameter (in.) Std ———4.5 Belt, Quantity...Type...Length (in.) Std 1...A...40 Pulley Center Line Distance (in.) Std 14.7-15.5 Speed Change per Full Turn of Std ———80
Movable Pulley Flange (rpm) Alt 65 70 80
Movable Pulley Maximum Full Turns Std ———5
From Closed Position Alt 555—
Factory Setting Std ———3 Factory Speed Setting (rpm) Std 1225 Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)†
Standard Compressor Internal Relief (Differential) 450±50 500±50 Cutout 428 428 Reset (Auto.) 320 320
LOW-PRESSURE/LOSS-OF-CHARGE SWITCH (Liquid Line)(psig)†
Cutout 7±3 Reset (Auto.) 22±7
FREEZE-PROTECTION THERMOSTAT (F)†
Opens 30±5 Closes 45±5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 1...20 x 24 x 1
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2
Alt 1...10 x 10 1...10 x 10 1...10 x 10 Alt Belt Belt Belt Alt 1200 1600 2000 Alt 1.00 1.00 1.3/2.4* Alt 48 48 48/56* Alt ———— Alt 760-1090 840-1185 900-1300
Alt 1.9/2.9 1.9/2.9 2.4/3.4 Alt Alt 4.5 4.0 4.5 Alt 1...A...39 1...A...36 1...A...39 Alt 10.0-12.4 10.0-12.4 14.7-15.5
Alt 333— Alt 890 980 1060
LEGEND
Bhp — Brake Horsepower
*Single phase units — 1.3 bhp/48 frame.
Three phase units — 2.4 bhp/56 frame.
†Requires an optional or accessory controls upgrade kit.
1
⁄4...1100
1
1
5
1
⁄4...1100
2 2
8
1
2
1
2
5
8
1
⁄4...1100
1
5
5
1
⁄4...1100
2 8
8
5
8
5
8
—5—
MAXIMUM ALLOWABLE DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 5 — Unit Leveling Tolerances IV. FIELD CONNECTIONS A. External Trap Condensate Drain
The unit’s
3
⁄4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connec­tions do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure the plug in the alternate bottom connection is tight before in­stalling the unit.
To use the bottom drain connection for a roof curb installa­tion, relocate the factory-installed plug from the bottom con­nection to the side connection. See Fig. 7. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. deep and protect against freeze­up. See Fig. 8. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection.
B. Field Duct Connections NOTE: The design and installation of the duct system must
be in accordance with NFPA standards for the installation of nonresidence-type air conditioning and ventilating systems, NFPANo. 90A or residence-type, NFPANo. 90B, and/or local codes and ordinances.
Adhere to the following criteria when selecting, sizing and installing the duct system:
1. Remove appropriate panels from unit to obtain either horizontal or vertical discharge. If units are installed in horizontal discharge applications, remove vertical dis­charge duct covers, save screws and install covers over vertical duct openings.
2. Select and size ductwork, supply-air registers and return­air grilles according to ASHRAE (American Society of Heating, Refrigeration and Air-Conditioning Engi­neers) recommendations.
CAUTION:
When drilling the duct system fastening holes into the side of the unit for duct flanges, be care­ful not to puncture the coil or coil tubes. See Fig. 9.
MAX
UNIT
558D036 415 188 558D048 425 193 558D060 445 202 558D072 520 236
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to pre­vent rigging straps from damaging unit.
3. Weights do not include economizer. See Table 1 for econo­mizer weights.
WEIGHT
Lb Kg in. mm in. mm in. mm
73.69 1872 35.00 889 33.35 847
Fig. 6 — Rigging Details
‘‘A’’ ‘‘B’’ ‘‘C’’
CAUTION: All panels must be in place when
rigging.
—6—
Fig. 7 — Internal Trap Condensate Drain
Fig. 9 — Location of Coil Area Not to be Drilled
C. Electrical Connections
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 8 — External Trap Condensate Drain
3. Use flexibletransition between rigid ductwork andunit
to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gas­kets to ensure weather- and airtight seal.
4. When horizontal return is used, install external field-
supplied air filter(s) in return-air ductwork where it is easily accessible for service. Recommended filter sizes are shown in Table 1.
5. Size all ductwork for maximum required airflow(either
heating or cooling) for unit being installed.Avoidabrupt duct size increases or decreases.
6. Adequately insulate and weatherproof all ductwork
located outdoors. Insulate ducts passing through un­conditioned space, and use vapor barrier in accordance with latest issue of SMACNA (Sheet Metal and Air Con­ditioning Contractors National Association) and ACCA (Air Conditioning Contractors NationalAssociation) mini­mum installation standards for heating and air condi­tioning systems. Secure all ducts to building structure.
A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On hori­zontal discharge units, a minimum clearance of one in. is required for the first 12 in. of ductwork.
7. Flash, weatherproof and vibration-isolate all openings
in building structure in accordance with local codes and good building practices.
WARNING:
The unit cabinet must have an uninter­rupted, unbroken, electrical ground to minimize the pos­sibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire con­nected to the unit ground lug in the control compart­ment or conduit approved for electrical ground when installed in accordance with NEC ANSI (American National Standards Institute)/NFPA, latest edition, (in Canada, Canadian Electrical Code CSA [Canadian StandardsAssociation] C22.1); and local electrical codes. Failure to adhere to this warning could result in per­sonal injury.
CAUTION:
Failure to obey the following precau­tions could result in damage to the unit being installed:
Field Power Supply (Fig. 10 and 11)
1. Make allelectrical connections in accordance with NEC ANSI/NFPA,latest edition, and local electrical codes gov­erning such wiring. In Canada, all electrical connec­tions must be in accordance with CSA Standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. A unit disconnect switch is required within sight from the unit. The disconnectswitch may be mounted on the unit corner post. When mounting disconnect switch, be sure the unit rating plate is not obstructed.
3. Use only copper conductor for connections between field­supplied electrical disconnect switch and unit. The use of aluminum wire is not recommended. Maximum wire size is number 2 AWG (American Wire Gage) on units without heat. The maximum wire size is number 2/0 A WG on units with heat.
4. Insulate low-voltage wires for highest voltage con­tained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
High-Voltage Connections (Fig. 10) The unit must have a separate electrical service with a field-
supplied, waterproof, fused, disconnect switch mounted at, or within sight of, the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. Be sure disconnect switch does not obstruct unit rating plate.
—7—
The field-supplied disconnect switch box may be mounted on the unit’s end panel or on the corner post. Mount disconnect box on the left side of the rating platewhen mounting on the unit’s end panel. Do not mount the disconnect box over the unit rating plate. When mounting disconnect box on corner post, secure disconnect box to corner post and condenser coil top cover. See Fig. 12.
A disconnect box mounting space is available when an op­tional or accessory condenser coil grille is used. Mount the disconnect on the sheet metal provided with the condenser coil grille. The sheet metal is located adjacent to the corner post on the left side of the power wiring access panel.
Install field wiring as follows:
1. Connect ground lead to chassis ground connection when using separate ground wire.
2. Install conduit between disconnect and power wiring ac­cess panel. Insert conduit through power supply knock­out opening. See Fig. 12.
3. Install power lines to power wiring leads.
4. Pigtails are provided for field power connections and are located inside the power wiring access panel. See Fig. 11. Use factory-supplied splices or Underwriters’ Labo­ratories (UL) approved copper connector.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Table2). On 3-phase units, voltagesbetween phases must be balanced within 2% and the current within 10%. Usethe for­mula shown in the legend for Table 2, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable warranty.
Special Procedures for 208-V Operation
Control Voltage Connection Install a factory-approved room thermostat. Locate the ther-
mostat on an inside wall in the space to be conditioned where it will not be subjected to either a cooling or heating source or direct exposure to sunlight. Mount the thermostat 4 to 5 ft above the floor. See accessory installation instructions.
NOTE: For wire runs up to 50 ft, use number 18 AWG insu­lated wire (35 C minimum). For 51 to 75 ft, use number 16 AWG insulated wire (35 C minimum). For 76 to 150 ft, use number 14 AWGinsulated wire (35 C minimum). All wire larger than number 18 AWGcannot be connected directly to the ther­mostat and will require a junction box and splice at the thermostat. Feed control wires through the raceway located between the condenser coil top cover and power wiring access panel. See Fig. 12. Connect control wires to the low-voltage connections located inside low-voltage access panel. See Fig. 10, 11, and 13 for connections. The barrier provides the UL required clear­ance between high- and low-voltage wiring.
NOTE: If thru-the-bottom power connections are used refer to the accessory installation instructions for information on power wiring. Refer to Fig. 2 for drilling holes in basepan.
DANGER: Make sure that the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death.
For operation on 208 v, disconnect the transformer primary orange lead from the contactor.See the unit wiring label. Re­move the tape and cover from the terminal on the end of the transformer primary red lead. Save the cover. Connect the red lead to the contactor terminal from which the orange lead was disconnected.
Using the cover removed from the red lead, insulate the loose terminal on the orange lead. Wrap the cover with electrical tape so that the metal terminal cannot be seen.
LEGEND
C—Contactor CAP Capacitor GND Ground IFC Indoor (Evaporator) Fan Contactor IFR Indoor (Evaporator) Fan Relay NEC National Electrical Code OFC Outdoor (Condenser) Fan Contactor TB Terminal Block TDR Time-Delay Relay TRAN — Transformer
LEGEND
AHA — Adjustable Heat Anticipator CC Cooling Compensator TC Thermostat-Cooling
NOTES:
1. The Y2 wiring is connected when an economizer is used.
2. Connect W1 when unit is equipped with an accessory 1-module heater package. The W2 wiring is connected when unit is equipped with an accessory 2-module heater package.
TH — Thermostat-Heating
Field Wiring Factory Wiring
Fig. 11 — Low-Voltage Connections
Fig. 10 — Field Wiring Connections
—8—
UNIT DISCONNECT (NOT SHOWN)
FIELD CONTROL WIRING RACEWAY (HIDDEN)
CONTROL BOX ACCESS PANEL
POWER WIRING SIDE PANEL
LOW-VOLTAGE ACCESS PANEL
KNOCKOUT OPENING
POWER WIRING ACCESS PANEL
EVAPORATOR FAN ACCESS PANEL
END PANEL (HIDDEN)
CONDENSER FAN
RACEWAY (HIDDEN)
R
Y1
Y2
W1
W2
G
C X
LOW-VOLTAGE WIRING CONNECTION
FILTER ACCESS PANEL
COMPRESSOR (COMPRESSOR ACCESS PANEL NOT SHOWN)
REFRIGERANT SERVICE PORT ACCESS P ANEL (NOT SHOWN)
CONDENSER COIL
CONTROL BOX ACCESS PANEL
LEFT CORNER POST
CONDENSER COIL TOP COVER
RIGHT CORNER POST
CONTROL BOX
Fig. 13 — Low-Voltage Location
Transformer Circuit Breaker (Fig. 14) The unit transformer contains an automatic-reset overcur-
rent protector for control circuit protection. If this device trips, it may reset without warning and start the heating or cooling section of this product. Use caution when servicing: If overcurrent protector continues to trip, there is a problem in the low-voltage electrical circuit (i.e., electrical short, ground or transformer overload). Disconnect power, correct the con­dition, and check for normal unit operation.
CONDENSER COIL
Fig. 12 — Typical Component Location
Fig. 14 — Transformer Label
—9—
UNIT 558D
036
(3 Ton)
048
(4 Ton)
NOMINAL
V-PH-Hz
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
Table 2 — Electrical Data
VOLTAGE
IFM
TYPE
Std
Alt 4.9
Std
Alt 4.9
Std
Alt 2.1
Std
Alt 2.1\ 7.4 15 7 34
Std
Alt 4.9
Std
Alt 4.9
Std
Alt 2.1
Std
Alt 2.1\ 10.9 15 11 43
RANGE
Min Max RLA LRA FLA FLA Nominal kW FLA MCA MOCP† FLA LRA
187 254 16.9 86.7 1.4
187 254 11.7 65.1 1.4
414 508 5.1 32.8 0.8
518 632 4.1 27.0 0.8\
187 254 23.3 118.0 1.4
187 254 15.4 90.0 1.4
414 508 8.3 45.0 0.8
518 632 6.4 36.0 0.8\
COMPR
(each)
OFM IFM ELECTRIC HEAT* POWER SUPPLY
25.3/ 25.3 35/ 35 24/ 24 97/ 97
3.3/ 4.4 15.9/18.3 25.3/ 26.4 35/ 35 24/ 24 97/ 97
2.8
2.8
1.3
1.3\ 6.8 15 7 31
3.5
3.5
1.8
1.8\ 10.6 15 10 42
4.9/ 6.5 23.8/27.3 32.8/ 37.4 35/ 40 30/ 34 97/ 97
6.5/ 8.7 31.4/36.2 42.8/ 48.8 45/ 50 39/ 45 97/ 97
7.9/10.5 37.9/43.8 50.9/ 58.2 60/ 60 47/ 54 97/ 97
9.8/13.0 47.1/54.6 62.2/ 71.2 70/ 80†† 57/ 66 97/ 97 — 27.4/ 27.4 35/ 35 27/ 27 102/102
3.3/ 4.4 15.9/18.3 27.4/ 29.0 35/ 35 27/ 27 102/102
4.9/ 6.5 23.5/27.1 35.5/ 40.0 35/ 40 33/ 37 102/102
6.5/ 8.7 31.4/36.3 45.4/ 51.4 45/ 60 42/ 47 102/102
7.9/10.5 37.9/43.8 53.5/ 60.8 60/ 60 49/ 56 102/102
9.8/13.0 46.9/54.2 64.8/ 73.8 70/ 80†† 60/ 68 102/102 — 18.8/ 18.8 25/ 25 18/ 18 76/ 76
3.3/ 4.4 9.2/10.6 18.8/ 18.8 25/ 25 18/ 18 76/ 76
4.9/ 6.5 13.6/15.6 20.4/ 23.0 25/ 25 19/ 21 76/ 76
6.5/ 8.7 18.1/20.9 26.2/ 29.7 30/ 30 24/ 27 76/ 76
7.9/10.5 21.9/25.3 30.9/ 35.1 35/ 40 28/ 32 76/ 76
12.0/16.0 33.5/38.6 45.3/ 51.7 50/ 60 42/ 48 76/ 76 — 20.9/ 20.9 25/ 25 21/ 21 80/ 80
3.3/ 4.4 9.2/10.6 20.9/ 20.9 25/ 25 21/ 21 80/ 80
4.9/ 6.5 13.6/15.6 23.1/ 25.7 25/ 25 21/ 24 80/ 80
6.5/ 8.7 18.1/20.9 28.8/ 32.3 30/ 35 26/ 30 80/ 80
7.9/10.5 21.9/25.3 33.5/ 37.7 35/ 40 31/ 35 80/ 80
12.1/16.0 33.5/38.6 47.9/ 54.4 50/ 60 44/ 50 80/ 80 — 8.5 15 8 38
6.0 7.2 10.6 15 10 38
8.8 10.6 14.9 15 14 38
11.5 13.8 18.9 20 17 38
14.0 16.8 22.7 25 21 38 — 9.3 15 9 41
6.0 7.2 11.6 15 10 41
8.8 10.6 15.9 20 15 41
11.5 13.8 19.9 20 18 41
14.0 16.8 23.7 25 22 41
34.0/ 34.0 40/ 40 32/ 32 128/128
3.3/ 4.4 15.9/18.3 34.0/ 34.0 40/ 40 32/ 32 128/128
6.5/ 8.7 31.4/36.3 43.6/ 49.7 45/ 50 40/ 46 128/128
9.8/13.0 46.9/54.2 63.0/ 72.1 70/ 80†† 58/ 66 128/128
13.1/17.4 62.8/72.5 82.9/ 95.0 90/100†† 76/ 87 128/128
15.8/21.0 75.8/87.5 99.2/113.8 100/125†† 91/105 128/128 — 35.4/ 35.4 40/ 40 34/ 34 129/129
3.3/ 4.4 15.9/18.3 35.4/ 35.4 40/ 40 34/ 34 129/129
6.5/ 8.7 31.4/36.3 45.4/ 51.4 45/ 60 42/ 47 129/129
9.8/13.0 46.9/54.2 64.8/ 73.8 70/ 80†† 60/ 68 129/129
13.1/17.4 62.8/72.5 84.7/ 96.8 90/100†† 78/ 89 129/129
15.8/21.0 75.8/87.5 100.9/115.5 100/125†† 93/106 129/129 — 24.2/ 24.2 30/ 30 24/ 24 100/100
4.9/ 6.5 13.6/15.6 24.2/ 24.2 30/ 30 24/ 25 100/100
6.5/ 8.7 18.1/20.9 27.0/ 30.5 30/ 35 27/ 30 100/100
12.0/16.0 33.4/38.5 46.1/ 52.5 50/ 60 45/ 51 100/100
15.8/21.0 43.8/50.5 59.1/ 67.5 60/ 70†† 58/ 64 100/100 — 25.6/ 25.6 30/ 30 24/ 24 101/101
4.9/ 6.5 13.6/15.6 25.6/ 25.7 30/ 30 24/ 24 101/101
6.5/ 8.7 18.1/20.9 28.8/ 32.3 30/ 35 25/ 29 101/101
12.0/16.0 33.4/38.5 47.8/ 54.2 50/ 60 43/ 49 101/101
15.8/21.0 43.8/50.5 60.8/ 69.3 60/ 70†† 55/ 63 101/101 — 13.0 15 13 51
6.0 7.2 13.0 15 13 51
11.5 13.8 19.5 20 18 51
14.0 16.6 23.0 25 21 51
23.0 27.7 36.8 40 34 51 — 13.3 15 13 52
6.0 7.2 13.3 15 13 52
11.5 14.0 19.9 20 18 52
14.0 16.6 23.4 25 22 52
23.0 27.7 37.2 40 34 52
DISCONNECT
SIZE**
—10—
Table 2 — Electrical Data (Cont)
UNIT 558D
NOMINAL
V-PH-Hz
TYPE
VOLTAGE
IFM
RANGE
Min Max RLA LRA FLA FLA Nominal kW FLA MCA MOCP† FLA LRA
Std
208/230-1-60
187 254 28.8 147 1.4
Alt 8.8
Std
060
(5 Ton)
208/230-3-60
187 254 16.3 114 1.4
Alt 5.8
Std
460-3-60
414 508 7.4 64 0.8
Alt 2.6
575-3-60
Std
518 632 6.2 52 0.8\
Alt 2.6\ 11.2 15 12 59
208/230-3-60 Std 187 254 23.6 146.0 1.4 5.2
072
(6 Ton)
460-3-60 Std 414 508 10.6 73.0 0.8 2.6
575-3-60 Std 518 632 8.5 58.4 0.8\ 2.6\ 13.3 20 14 75
IMPORTANT: Optional, alternate evaporator-fan motor and drive are not available for 558D072 units. Contact your local representative for more information about field­installed motors.
COMPR — Compressor FLA Full Load Amps HACR Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection NEC National Electrical Code OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Available for field-installed accessory heaters only. Heater capacity (kW) is based on
heater voltage of 208 v,240 v or 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker.
**Used to determine minimum disconnect per NEC.
††Fusing single-point box provides the required branch circuit protection.
\Ampacities are based on 460 v. MCA and MOCP are based on 575 v.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip­ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
LEGEND
Use the following formula to determine the percent of voltage imbalance.
COMPR
(each)
OFM IFM ELECTRIC HEAT* POWER SUPPLY
DISCONNECT
SIZE**
43.3/ 43.3 60/ 60 42/ 42 159/159
4.9/ 6.5 23.5/27.1 43.3/ 43.3 60/ 60 42/ 42 159/159
5.9
5.9
3.2
6.5/ 8.7 31.4/36.3 46.6/ 52.7 60/ 60 43/ 49 159/159
9.8/13.0 46.9/54.2 66.0/ 75.1 70/ 80†† 61/ 69 159/159
13.0/17.4 62.8/72.5 85.9/ 98.0 90/100†† 79/ 90 159/159
15.8/21.0 75.8/87.5 102.2/116.8 110/125†† 94/107 159/159 — 46.2/ 46.2 60/ 60 45/ 45 162/162
4.9/ 6.5 23.5/27.1 46.2/ 46.2 60/ 60 45/ 45 162/162
6.5/ 8.7 31.4/36.3 49.9/ 55.9 60/ 60 46/ 52 162/162
9.8/13.0 46.9/54.2 69.3/ 78.3 70/ 80†† 64/ 72 162/162
13.0/17.4 62.8/72.5 89.2/101.3 90/110†† 82/ 93 162/162
15.8/21.0 75.8/87.5 105.5/120.0 110/125†† 97/110 162/162 — 27.7/ 27.7 35/ 35 27/ 27 126/126
4.9/ 6.5 13.6/15.6 27.7/ 27.7 35/ 35 27/ 27 126/126
7.9/10.5 21.9/25.3 34.7/ 38.9 40/ 40 32/ 36 126/126
12.0/16.0 33.4/38.5 49.1/ 55.5 50/ 60 46/ 51 126/126
15.8/21.0 43.8/50.5 62.1/ 70.5 70/ 80†† 57/ 65 126/126
19.9/26.5 55.2/63.8 76.4/ 87.1 80/ 90†† 70/ 80 126/126 — 26.8/ 26.8 40/ 40 27/ 27 125/125
4.9/ 6.5 13.6/15.6 26.8/ 26.8 40/ 40 27/ 27 125/125
7.9/10.5 21.9/25.3 35.3/ 39.5 45/ 45 32/ 36 125/125
12.0/16.0 33.4/38.5 49.6/ 56.0 60/ 60 45/ 51 125/125
15.8/21.0 43.8/50.5 62.6/ 71.1 70/ 80†† 57/ 65 125/125
19.9/26.5 55.2/63.8 77.0/ 87.6 80/100†† 70/ 80 125/125 — 13.3 20 13 69
6.0 7.2 13.3 20 13 69
11.5 13.8 21.3 25 20 69
14.0 16.8 25.0 30 23 69
23.0 27.7 38.6 40 36 69
25.5 30.1 41.6 45 38 69 — 12.7 20 12 70
6.0 7.2 12.7 20 12 70
11.5 13.8 21.0 25 19 70
14.0 16.8 24.8 30 22 70
23.0 27.7 38.3 45 35 70
25.0 30.1 41.3 45 38 70
3.2\ 11.8 15 12 57
36.1/ 36.1 45/ 45 35/ 35 191/191
4.9/ 6.5 13.6/15.6 36.1/ 36.1 45/ 45 35/ 35 191/191
7.9/10.5 21.9/25.3 36.1/ 38.1 45/ 45 35/ 35 191/191
12.0/16.0 33.4/38.4 48.2/ 54.6 50/ 60 44/ 50 191/191
15.8/21.0 43.8/50.5 61.2/ 69.6 70/ 70†† 56/ 64 191/191
19.9/26.5 55.2/63.8 75.6/ 86.2 80/ 90†† 70/ 79 191/191 — 16.7 20 16 90
6.0 7.2 16.7 20 16 90
11.5 13.8 20.5 25 19 90
14.0 16.8 24.3 25 22 90
23.0 27.8 37.8 40 35 90
25.5 30.7 41.6 45 38 90
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
Example: Supply voltage is 460-3-60.
NOTE: The 575-v units are Canada only.
Determine maximum deviation from average voltage. (AB) 457 - 452=5v (BC) 464 - 457=7v (AC) 457 - 455=2v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allow­able 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
457
= 1.53%
452 + 464 + 455
3
1371
=
3
= 457
7
—11—
D. Accessory Installation
At this time, any required accessories should be installed on the unit. Control wiring information is provided in the unit wiring diagram. Refer to Accessory Installation Instructions provided with accessory.
E. Optional Outdoor-Air Damper Installation
The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove filter access panel by raising panel and swing­ing panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove fil­ter access panel. Remove and save outdoor-air opening panel and screws. See Fig. 15.
3. Separate hood and screen from basepan by removing the 4 screws and brackets securing them. Save all screws and discard brackets.
4. Replace outdoor-air opening panel.
5. Place hood on front of outdoor air opening panel. See Fig. 16 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 17.
6. Remove andsave 6 screws (3 on each side) from sides of the manual outdoor-air damper assembly.
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper assembly. See Fig. 16 and
17. Secure hood with 6 screws from Step 6.
8. For proper quantity of ventilation air, adjust minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 15. Slide blade vertically un­til it is in the appropriate position determined by Fig. 18. Tighten screws.
9. Remove and save 4 screws currently on sides of hood. Insert screen. Secure screen to hood using the4 screws. See Fig. 17.
Fig. 16 — Outdoor-Air Hood Details
OUTDOOR AIR OPENING PANEL
Fig. 15 — Damper Panel With Outdoor-Air
Damper Installed
Fig. 17 — Manual Outdoor-Air Damper With HoodAttached
Fig. 18 — Position Setting
—12—
Loading...
+ 28 hidden pages