SINGLE PACKAGE ROOFTOP
ELECTRIC HEATING/ELECTRICCOOLING UNITS
Cancels: II 558D-36-4II 558D-36-5
558D
Sizes 036-072
3to6Tons
2/1/99
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation instructions before installing this unit (see Fig. 1).
2. Be sure the installation conforms to all applicable local
and national codes.
3. These instructionscontainimportantinformation for the
proper maintenance and repair of this equipment. Retain these instructions for future use.
CONTENTS
Page
SAFETY CONSIDERATIONS ................... 1
INSTALLATION ...........................1-16
I. Locate the Unit ....................... 3
II. Unit Duct Connections .................. 3
III. Rig and Place Unit ..................... 3
IV. Field Connections ..................... 6
PRE-START-UP ............................17
START-UP ..............................17-28
I. Heating Section Start-Up and Adjustments ....17
II. Cooling Section Start-Up and Adjustments ....18
III. Indoor Airflow and Airflow Adjustments ......19
CARE AND MAINTENANCE ...................28
I. Air Filter ............................28
SERVICE ...............................28-31
I. Cleaning ............................28
II. Lubrication ..........................29
III. Condenser Fan Adjustment ...............29
IV. Refrigerant Charge .....................30
V. Replacement Parts .....................30
TROUBLESHOOTING ......................32-35
START-UP CHECKLIST .....................CL-1
WARNING:
nance operations on unit, turn off main power switch
to unit. Electrical shock could cause personal injury.
1. The power supply (volts, phase, and hertz) must correspond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.
3. Refer to Locate the Unit section on page 3 and Fig. 2 for
locations of electrical inlets, condensate drain, duct connections and required clearances before setting unit in
place.
4. This installation must conform with local building codes
and with NEC (National Electrical Code) or NFPA
(National Fire Protection Association) 54 TIA-54-84-1.
Refer to Provincial and local plumbing or wastewater
codes and other applicable local codes.
5. Approved for outdoor installation on wood flooring or on
class A, B, or C roof covering materials.
Unit is shipped in the vertical airflow configuration (see
Fig. 1). To convert tohorizontal discharge, remove horizontal
duct opening covers. Using the same screws, install covers
with insulation-side down (facing outside) over vertical duct
openings on the unit. Seals around duct openings must be
tight.
All units can be connected into existing duct systems that are
properly sized and designed to handle an airflow of 300 to
500 cfm per each 12,000 Btuh of rated cooling capacity.
NOTE: When installing any accessory item, see the manufacturer’s installation instructions packaged with the accessory. A qualified installer or agency must use only factoryauthorized kits or accessories when modifying this unit.
Before performing service or mainte-
INSTALLATION
SAFETY CONSIDERATIONS
Recognize safety information. This is the safety-alert symbol (). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words — DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol. Danger identifies the most serious hazards which will
result in severe personal injury or death. Warning indicates
a condition that could result in personal injury. Caution is
used to identify unsafe practices which would result in minor
personal injury or product and property damage.
Fig.1—Typical Unit
*Indicates horizontal center of gravity.
†Indicates vertical center of gravity.
NOTES:
1. Dimensions in [ ] are in millimeters.
2.Center of gravity.
3.Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom of basepan to combustible surfaces (when not using curb), 0 inches. On
horizontal discharge units with electric heat, 1 in. clearance to ductwork for 1 foot.
b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting
the greater clearance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per National Electrical Code (NEC).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box
side, 42 in. per NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearances as stated in Notes 5a, b, and c, a removable
fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or class A, B, or C roof
covering material.
Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow,and
service access (see Fig. 2 and 3).
Minimum clearance to combustibles is 0 in. on all sides.
Minimum clearance to block walls or any other grounded sur-
face is 42 in. on all sides.
Minimum clearance of 36 in. should be providedon side with
outdoor-air intake, if unit is so equipped.
Minimum clearance between unit and other electrically live
parts is 48 inches.
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Slab mounted units should be at least 4 in. above the highest
expected water, flood and runoff levels. Do not use theunit if
it has been under water.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket with the roof curb
as shown in Fig. 4. Improperly applied gasket can also result
in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 5. Correct leveling tolerance is necessary for unit drain
to function properly.
C. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of
6 in. beyond unit cabinet. Install a gravel apron in front of
condenser-coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb, if
required.
II. UNIT DUCT CONNECTIONS
On vertical units, secure all ducts to roof curb and building
structure. Do not connect ductwork to unit. On horizontal units,
duct flanges should be attached to horizontal openings and
all ductwork should be secured to flanges.
If a plenum return is used on a vertical unit, the return should
be ducted through the roof deck to comply with applicable
fire codes.
Aminimum clearance is not required around ductwork. Cabinet return-air static shall not exceed −0.20 in. wgwith PARABLADE economizer, −0.35 in. wg with Durablade economizer,
or −0.45 in. wg without economizer.
NOTE: Connection must be made to roof curb before unit is
set in place.
Fig. 3 — Service and Operational Clearances
B. Roof Curb Mount
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 4. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-work must be attached to curb. If electric or control power is
to be routed through the curb, attach the accessorythru-thebottom connections to the basepan in accordance with the accessory installation instructions. Accessory electric connections
must be installed before unit is in place on roof curb.
III. RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit.
Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 6 for additional information. Operating weight and maximum weight
are shown in Table 1 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 6.
Refer to rigging instructions on unit.
IMPORTANT: If unit has forklift protection skids, be sure to
remove forklift protection skids from under unit before setting unit in place.
A properly positioned unit will have the following clearances
between unit and roof curb:
and base rails on each side and front of unit; 1
1
⁄4-in. clearance between roof curb
5
⁄32-in. clearance between roof curb and rear of unit. See Fig. 4, Views
A-A and C-C.
After unit is in position, remove shipping materials and rigging skids.
—3—
ROOF CURB
ACCESSORY
CRRFCURB001A00
CRRFCURB002A00
‘‘A’’UNIT SIZE
149
[356]
558D036-072
249
[610]
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb. (Flanges of duct rest on
curb.)
6. Service clearance 4 ft on each side.
7.Direction of airflow.
—4—
UNIT SIZE‘‘B’’‘‘C’’
11
⁄
16
9
558D036-072
21
[551]
169
[406]
‘‘D’’Alt
Drain Hole
13⁄
4
9
[44.5]
PowerControl Connector Package Accessory
3
⁄49 NPT1⁄29 NPT
1
⁄49 NPT1⁄29 NPT
1
CRBTMPWR001A00
(THRU-THE-BOTTOM)
CRBTMPWR002A00
(THRU-THE-BOTTOM)
Fig. 4 — Roof Curb
Table 1 — Specifications
BASE UNIT 558D036048060072
NOMINAL CAPACITY (tons)3456
OPERATING WEIGHT (lb)
CONDENSER COILEnhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.1...171...172...172...17
Total Face Area (sq ft)7.3613.1910.4210.42
CONDENSER FANPropeller Type
Nominal Cfm3500400040004000
Quantity...Diameter (in.)1...22.01...22.01...22.01...22.0
Motor Hp...Rpm
Watts Input (Total)325325325325
EVAPORATOR COILEnhanced Copper Tubes, Aluminum Double-Wavy Fins
Rows...Fins/in.2...152...153...154...15
Total Face Area (sq ft)4.175.55.55.5
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)Std1...10 x 101...10 x 101...11 x 101...10 x 10
Type DriveStdDirectDirectDirectBelt
Nominal CfmStd1200160020002400
Maximum Continuous BhpStd.34.751.202.40
Motor Frame SizeStd48484856
Nominal Rpm High/LowStd860/8001075/9701075/970—
Fan Rpm RangeStd———1070-1460
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm2100210021002100
Motor Pulley Pitch Diameter Min/Max (in.)Std———2.8/3.8
Nominal Motor Shaft Diameter (in.)Std
Fan Pulley Pitch Diameter (in.)Std———4.5
Belt, Quantity...Type...Length (in.)Std———1...A...40
Pulley Center Line Distance (in.)Std———14.7-15.5
Speed Change per Full Turn ofStd———80
Movable Pulley Flange (rpm)Alt657080—
Movable Pulley Maximum Full TurnsStd———5
From Closed PositionAlt555—
Factory SettingStd———3
Factory Speed Setting (rpm)Std———1225
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)†
Standard Compressor Internal Relief (Differential)450±50500±50
Cutout428428
Reset (Auto.)320320
Alt1...10 x 101...10 x 101...10 x 10—
AltBeltBeltBelt—
Alt120016002000—
Alt1.001.001.3/2.4*—
Alt484848/56*—
Alt————
Alt760-1090840-1185900-1300—
Alt1.9/2.91.9/2.92.4/3.4—
Alt
Alt4.54.04.5—
Alt1...A...391...A...361...A...39—
Alt10.0-12.410.0-12.414.7-15.5—
Alt333—
Alt8909801060—
LEGEND
Bhp — Brake Horsepower
*Single phase units — 1.3 bhp/48 frame.
Three phase units — 2.4 bhp/56 frame.
†Requires an optional or accessory controls upgrade kit.
1
⁄4...1100
1
⁄
1
⁄
5
⁄
1
⁄4...1100
2
2
8
1
⁄
2
1
⁄
2
5
⁄
8
1
⁄4...1100
1
⁄
5
⁄
5
⁄
1
⁄4...1100
2
8
8
5
⁄
8
—
5
⁄
8
—5—
MAXIMUM ALLOWABLE DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 5 — Unit Leveling Tolerances
IV. FIELD CONNECTIONS
A. External Trap Condensate Drain
The unit’s
3
⁄4-in. condensate drain connections are located
on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either
drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, make sure
the plug in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug from the bottom connection to the side connection. See Fig. 7. The piping for the
condensate drain and external trap can be completed after
the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against freezeup. See Fig. 8. If drain line is installed downstream from the
external trap, pitch the line away from the unit at 1 in. per
10 ft of run. Do not use a pipe size smaller than the unit
connection.
B. Field Duct Connections
NOTE: The design and installation of the duct system must
be in accordance with NFPA standards for the installation of
nonresidence-type air conditioning and ventilating systems,
NFPANo. 90A or residence-type, NFPANo. 90B, and/or local
codes and ordinances.
Adhere to the following criteria when selecting, sizing and
installing the duct system:
1. Remove appropriate panels from unit to obtain either
horizontal or vertical discharge. If units are installed in
horizontal discharge applications, remove vertical discharge duct covers, save screws and install covers over
vertical duct openings.
2. Select and size ductwork, supply-air registers and returnair grilles according to ASHRAE (American Society of
Heating, Refrigeration and Air-Conditioning Engineers) recommendations.
CAUTION:
When drilling the duct system fastening
holes into the side of the unit for duct flanges, be careful not to puncture the coil or coil tubes. See Fig. 9.
2. Hook rigging shackles through holes in base rail, as shown in
detail ‘‘A.’’ Holes in base rails are centered around the unit
center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Weights do not include economizer. See Table 1 for economizer weights.
WEIGHT
LbKgin.mmin.mmin.mm
73.69187235.0088933.35847
Fig. 6 — Rigging Details
‘‘A’’‘‘B’’‘‘C’’
CAUTION: All panels must be in place when
rigging.
—6—
Fig. 7 — Internal Trap Condensate Drain
Fig. 9 — Location of Coil Area Not to be Drilled
C. Electrical Connections
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 8 — External Trap Condensate Drain
3. Use flexibletransition between rigid ductwork andunit
to prevent transmission of vibration. The transition may
be screwed or bolted to duct flanges. Use suitable gaskets to ensure weather- and airtight seal.
4. When horizontal return is used, install external field-
supplied air filter(s) in return-air ductwork where it is
easily accessible for service. Recommended filter sizes
are shown in Table 1.
5. Size all ductwork for maximum required airflow(either
heating or cooling) for unit being installed.Avoidabrupt
duct size increases or decreases.
6. Adequately insulate and weatherproof all ductwork
located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance
with latest issue of SMACNA (Sheet Metal and Air Conditioning Contractors National Association) and ACCA
(Air Conditioning Contractors NationalAssociation) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
A minimum clearance to combustibles is not required
around ductwork on vertical discharge units. On horizontal discharge units, a minimum clearance of one in.
is required for the first 12 in. of ductwork.
7. Flash, weatherproof and vibration-isolate all openings
in building structure in accordance with local codes and
good building practices.
WARNING:
The unit cabinet must have an uninterrupted, unbroken, electrical ground to minimize the possibility of personal injury if an electrical fault should
occur. This ground may consist of electrical wire connected to the unit ground lug in the control compartment or conduit approved for electrical ground when
installed in accordance with NEC ANSI (American
National Standards Institute)/NFPA, latest edition,
(in Canada, Canadian Electrical Code CSA [Canadian
StandardsAssociation] C22.1); and local electrical codes.
Failure to adhere to this warning could result in personal injury.
CAUTION:
Failure to obey the following precautions could result in damage to the unit being
installed:
Field Power Supply (Fig. 10 and 11)
1. Make allelectrical connections in accordance with NEC
ANSI/NFPA,latest edition, and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA Standard C22.1
Canadian Electrical Code Part 1 and applicable local codes.
Refer to unit wiring diagram.
2. A unit disconnect switch is required within sight from
the unit. The disconnectswitch may be mounted on the
unit corner post. When mounting disconnect switch, be
sure the unit rating plate is not obstructed.
3. Use only copper conductor for connections between fieldsupplied electrical disconnect switch and unit. The use
of aluminum wire is not recommended. Maximum wire
size is number 2 AWG (American Wire Gage) on units
without heat. The maximum wire size is number 2/0 A WG
on units with heat.
4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are
run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc.
High-Voltage Connections (Fig. 10)
The unit must have a separate electrical service with a field-
supplied, waterproof, fused, disconnect switch mounted at, or
within sight of, the unit. Refer to the unit rating plate for
maximum fuse/circuit breaker size and minimum circuit amps
(ampacity) for wire sizing. Be sure disconnect switch does not
obstruct unit rating plate.
—7—
The field-supplied disconnect switch box may be mounted on
the unit’s end panel or on the corner post. Mount disconnect
box on the left side of the rating platewhen mounting on the
unit’s end panel. Do not mount the disconnect box over the
unit rating plate. When mounting disconnect box on corner
post, secure disconnect box to corner post and condenser coil
top cover. See Fig. 12.
A disconnect box mounting space is available when an optional or accessory condenser coil grille is used. Mount the
disconnect on the sheet metal provided with the condenser
coil grille. The sheet metal is located adjacent to the corner
post on the left side of the power wiring access panel.
Install field wiring as follows:
1. Connect ground lead to chassis ground connection when
using separate ground wire.
2. Install conduit between disconnect and power wiring access panel. Insert conduit through power supply knockout opening. See Fig. 12.
3. Install power lines to power wiring leads.
4. Pigtails are provided for field power connections and are
located inside the power wiring access panel. See
Fig. 11. Use factory-supplied splices or Underwriters’ Laboratories (UL) approved copper connector.
Voltage to compressor terminals during operation must
be within voltage range indicated on unit nameplate (see
Table2). On 3-phase units, voltagesbetween phases must be
balanced within 2% and the current within 10%. Usethe formula shown in the legend for Table 2, Note 2 to determine
the percent of voltage imbalance. Operation on improper line
voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such operation
would invalidate any applicable warranty.
Special Procedures for 208-V Operation
Control Voltage Connection
Install a factory-approved room thermostat. Locate the ther-
mostat on an inside wall in the space to be conditioned where
it will not be subjected to either a cooling or heating source
or direct exposure to sunlight. Mount the thermostat 4 to 5 ft
above the floor. See accessory installation instructions.
NOTE: For wire runs up to 50 ft, use number 18 AWG insulated wire (35 C minimum). For 51 to 75 ft, use number 16
AWG insulated wire (35 C minimum). For 76 to 150 ft, use
number 14 AWGinsulated wire (35 C minimum). All wire larger
than number 18 AWGcannot be connected directly to the thermostat and will require a junction box and splice at the
thermostat.
Feed control wires through the raceway located between the
condenser coil top cover and power wiring access panel. See
Fig. 12. Connect control wires to the low-voltage connections
located inside low-voltage access panel. See Fig. 10, 11, and
13 for connections. The barrier provides the UL required clearance between high- and low-voltage wiring.
NOTE: If thru-the-bottom power connections are used refer
to the accessory installation instructions for information on
power wiring. Refer to Fig. 2 for drilling holes in basepan.
DANGER: Make sure that the power supply to the
unit is switched OFF before making any wiring changes.
Electrical shock can cause personal injury or death.
For operation on 208 v, disconnect the transformer primary
orange lead from the contactor.See the unit wiring label. Remove the tape and cover from the terminal on the end of the
transformer primary red lead. Save the cover. Connect the
red lead to the contactor terminal from which the orange lead
was disconnected.
Using the cover removed from the red lead, insulate the loose
terminal on the orange lead. Wrap the cover with electrical
tape so that the metal terminal cannot be seen.
LEGEND
C—Contactor
CAP— Capacitor
GND— Ground
IFC— Indoor (Evaporator) Fan Contactor
IFR— Indoor (Evaporator) Fan Relay
NEC— National Electrical Code
OFC— Outdoor (Condenser) Fan Contactor
TB— Terminal Block
TDR— Time-Delay Relay
TRAN — Transformer
LEGEND
AHA — Adjustable Heat Anticipator
CC— Cooling Compensator
TC— Thermostat-Cooling
NOTES:
1. The Y2 wiring is connected when an economizer is used.
2. Connect W1 when unit is equipped with an accessory 1-module heater
package. The W2 wiring is connected when unit is equipped with an
accessory 2-module heater package.
TH — Thermostat-Heating
Field Wiring
Factory Wiring
Fig. 11 — Low-Voltage Connections
Fig. 10 — Field Wiring Connections
—8—
UNIT DISCONNECT
(NOT SHOWN)
FIELD CONTROL
WIRING RACEWAY
(HIDDEN)
CONTROL BOX
ACCESS PANEL
POWER WIRING
SIDE PANEL
LOW-VOLTAGE
ACCESS PANEL
KNOCKOUT
OPENING
POWER WIRING
ACCESS PANEL
EVAPORATOR
FAN ACCESS
PANEL
END PANEL
(HIDDEN)
CONDENSER
FAN
RACEWAY
(HIDDEN)
R
Y1
Y2
W1
W2
G
C
X
LOW-VOLTAGE WIRING
CONNECTION
FILTER
ACCESS PANEL
COMPRESSOR
(COMPRESSOR
ACCESS PANEL
NOT SHOWN)
REFRIGERANT SERVICE
PORT ACCESS P ANEL
(NOT SHOWN)
CONDENSER
COIL
CONTROL BOX
ACCESS PANEL
LEFT
CORNER
POST
CONDENSER COIL
TOP COVER
RIGHT
CORNER
POST
CONTROL BOX
Fig. 13 — Low-Voltage Location
Transformer Circuit Breaker (Fig. 14)
The unit transformer contains an automatic-reset overcur-
rent protector for control circuit protection. If this device trips,
it may reset without warning and start the heating or
cooling section of this product. Use caution when servicing: If
overcurrent protector continues to trip, there is a problem in
the low-voltage electrical circuit (i.e., electrical short, ground
or transformer overload). Disconnect power, correct the condition, and check for normal unit operation.
IMPORTANT: Optional, alternate evaporator-fan motor and drive are not available for
558D072 units. Contact your local representative for more information about fieldinstalled motors.
COMPR — Compressor
FLA— Full Load Amps
HACR— Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Available for field-installed accessory heaters only. Heater capacity (kW) is based on
heater voltage of 208 v,240 v or 480 v. If power distribution voltage to unit varies from
rated heater voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker.
**Used to determine minimum disconnect per NEC.
††Fusing single-point box provides the required branch circuit protection.
\Ampacities are based on 460 v. MCA and MOCP are based on 575 v.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
LEGEND
Use the following formula to determine the percent of voltage imbalance.
Determine maximum deviation from average voltage.
(AB) 457 - 452=5v
(BC) 464 - 457=7v
(AC) 457 - 455=2v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
average voltage
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
457
= 1.53%
452 + 464 + 455
3
1371
=
3
= 457
7
—11—
D. Accessory Installation
At this time, any required accessories should be installed on
the unit. Control wiring information is provided in the unit
wiring diagram. Refer to Accessory Installation Instructions
provided with accessory.
E. Optional Outdoor-Air Damper Installation
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track
and can be removed. No tools are required to remove filter access panel. Remove and save outdoor-air opening
panel and screws. See Fig. 15.
3. Separate hood and screen from basepan by removing the
4 screws and brackets securing them. Save all screws
and discard brackets.
4. Replace outdoor-air opening panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 16 for hood details. Secure top of hood with the
4 screws removed in Step 3. See Fig. 17.
6. Remove andsave 6 screws (3 on each side) from sides of
the manual outdoor-air damper assembly.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper assembly. See Fig. 16 and
17. Secure hood with 6 screws from Step 6.
8. For proper quantity of ventilation air, adjust minimum
position setting of the damper blade by adjusting the
manual outdoor-air adjustment screws on the front of
the damper blade. See Fig. 15. Slide blade vertically until it is in the appropriate position determined by
Fig. 18. Tighten screws.
9. Remove and save 4 screws currently on sides of hood.
Insert screen. Secure screen to hood using the4 screws.
See Fig. 17.
Fig. 16 — Outdoor-Air Hood Details
OUTDOOR AIR
OPENING
PANEL
Fig. 15 — Damper Panel With Outdoor-Air
Damper Installed
Fig. 17 — Manual Outdoor-Air Damper With HoodAttached
Fig. 18 — Position Setting
—12—
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.