Bryant 551J*07A/G Series, 551J*08D/K Series, 551J Series, 551J*07D/K Series, 551J*12D/K Series Installation Instructions Manual

...
551J
SINGLE PACKAGE ROOFTOP COOLING ONLY
SIZES 07, 08, 09, 11 AND 12 WITH PURONR(R--410A) REFRIGERANT
Installation Instructions
NOTE: Read the entire instruction manual before starting
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2....................
Rated Indoor Airflow (cfm) 3.....................
INSTALLATION 8...............................
Jobsite Survey 8................................
Step 1 -- Plan for Unit Location 8..................
Roof Mount 8...............................
Step 2 -- Plan for Sequence of Unit Installation 8......
Curb--Mounted Installation 9...................
Pad--Mounted Installation 9....................
Frame--Mounted Installation 9..................
Step 3 -- Inspect Unit 9...........................
Step 4 -- Provide Unit Support 9...................
Roof Curb Mount 9..........................
Slab Mount (Horizontal Units Only) 9...........
Alternate Unit Support
(In Lieu of Curb or Slab Mount) 11.............
Step 5 -- Field Fabricate Ductwork 11...............
For Units with Accessory Electric Heaters 11.....
Step 6 -- Rig and Place Unit 11....................
Positioning on Curb 12.......................
Step 7 -- Convert to Horizontal and Connect
Ductwork 12...........................
Step 8 -- Install Outside Air Hood 13...............
Economizer and Two Pos ition Damper Hood Package Removal and Setup — Factory Option 13..
Economizer Hood and Two--Position Hood 13.....
Step 9 -- Install External Condensate Trap and Line 14.
Step 10 -- Make Electrical Connections 14...........
Field Power Supply 14........................
Units With Factory--Installed
Non--Fused Disconnect 15.....................
Units Without Factory--Installed
Non--Fused Disconnect 16.....................
All Units 16................................
Convenience Outlets 17.......................
Factory Option Thru--Base Connections 18.......
Units Without Thru--Base Connections 18........
Field Control Wiring 18.......................
Thermostat 18...............................
Central Terminal Board 19....................
Unit Without Thru--Base Connection Kit 19.......
Heat Anticipator Settings 19...................
Electric Heaters 19............................
Single Point Boxes and Supplementary Fuses 20...
Single Point Boxes Without Fuses 20............
Low--Voltage Control Connections 21............
Low Ambient Control (Factory Option) 21.........
Variable Frequency Drive (VFD) 2--Speed
Indoor Fan Motor System (Factory--Installed) 21.....
Perfect Humidityt System Control Connections 21..
Perfect Humidity System -- Space RH Contr oller 21..
EconoMi$er
Product Description 23........................
System Components 23.......................
Specifications 23..............................
W7220 Economizer Module 23.................
Electrical 23................................
Inputs 23...................................
Outputs 24.................................
Environmental 24............................
Economizer Module Wiring Details 24...........
S--Bus Sensor Wiring 24......................
CO
Interface Overview 25..........................
User Interface 25............................
Keypad 25.................................
Menu Structure 26.............................
Setup and Configuration 26.....................
Time-- out and Screensaver 26..................
Sequence of Operation 32.......................
Enthalpy Settings 35...........................
Two--Speed Fan Operation 35....................
Checkout 36.................................
Power Up 36................................
Initial Menu Display 36.......................
Power Loss (Outage or Brownout) 37............
Status 37...................................
R
X (Factory--Installed Option) 23......
Sensor Wiring 25........................
2
Checkout Tests 37...........................
Troubleshooting 37............................
Alarms 37..................................
RTU Open Controller System 38.................
Supply Air Temperature (SAT) Sensor 41.........
Outdoor Air Temperature (OAT) Sensor 41.......
EconoMi$er
Field Connections 42..........................
Space Temperature (SPT) Sensors 42............
Indoor Air Quality (CO
Outdoor Air Quality Sensor 43.................
Space Humidity Sensor or Humidistat 44.........
Smoke Detector/Fire Shutdown (FSD) 45.........
Connecting Discrete Inputs 45..................
Communication Wiring -- Protocols 46............
General 46.................................
Local Access 47.............................
RTU Open Controller Troubleshooting 47........
Outdoor Air Enthalpy Control 48.................
Differential Enthalpy Control 48................
Return Air Enthalpy Sensor 48.................
Smoke Detectors 49...........................
Step 11 -- Adjust Factory--Installed Options 50........
Step 12 -- Install Accessories 50...................
Step 13 -- Check Belt Tension 51...................
START--UP CHECKLIST 55.......................
R
242...........................
)Sensor 43.............
2
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lock(s) and lockout tag(s). Ensure electrical service t o rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate a t higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA 70, National Electrical Code (NEC); in Cana da, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
. When you see this symbol on the
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Ware safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air--conditioning equipment.
CAUTION
2
Rated Indoor Airflow (cfm)
The table to the right lists the rated indoor airflow used for the AHRI efficiency rating for the units covered in thi s document.
Model Number Full Load Airflow (cfm)
551J*07A/G 2400
551J*07D/K 2400
551J*08D/K 3000
551J*09D/K 3000
551J*11D/K 3000
551J*12D/K 3000
1234567891011 12
551JE12D000A3A0AA
Model
551J = Cooling RTU with optional High Efficient Electric Heat
Voltage
E = 460-3-60 P = 208/230-3-60 T = 575-3-60
Cooling Tons
07 - 6 ton 08 - 7.5 ton 09 - 8.5 ton 11 - 10 ton (12.0 EER) 12 - 10 ton (11.7 EER)
Refrigerant System/Gas Heat Options
A = Standard One-Stage Cooling Models D = Two Stage Cooling Models G = Standard One Stage Cooling Models and Perfect Humidity K = Two Stage Cooling Models and Perfect Humidity
Heat Level (Field-installed electric heaters available)
000 = No Heat
Coil Options (Outdoor – Indoor – Hail Guard)
A = Al/Cu – Al/Cu B = Precoat Al/Cu – Al/Cu C = E-coat Al/Cu – Al/Cu D = E-coat Al/Cu – E-Coat Al/Cu E = Cu/Cu – Al/Cu F = Cu/Cu – Cu/Cu M = Al/Cu – Al/Cu – Louvered Hail Guards N = Precoat Al/Cu – Al/Cu – Louvered Hail Guards P = E-coat Al/Cu – Al/Cu – Louvered Hail Guards Q = E-coat Al/Cu – E-coat Al/Cu – Louvered Hail Guards R = Cu/Cu – Al/Cu – Louvered Hail Guards S = Cu/Cu – Cu/Cu – Louvered Hail Guards
Fig. 1 -- 551J*07--12 Model Number Nomenclature (Example)
13
14 15 16 17
Packaging and 2-Speed Indoor Fan Motor
A = Standard Packaging, electro-mechanical controls that require W7212 EconoMi$er B = LTL Packaging, electro-mechanical controls that require W7212 EconoMi$er IV C = Standard Packaging, electro-mechanical controls that require W7220 EconoMi$er X D = Standard Packaging and 2-speed Indoor Fan Motor (VFD) Controller E = LTL Packaging and 2-speed Indoor Fan Motor (VFD) Controller F = LTL Packaging, electro-mechanical controls that require W7220 EconoMi$er X
Factory-Installed Options
0A = None NOTE: See the 551J 3 to 15 ton Price Pages for a complete list of factory-installed options.
TM
Outdoor Air Options
A = None B = Temperature Economizer w/ Barometric Relief and W7212 Economizer Controller E = Temperature Economizer w/ Barometric Relief, CO and W7212 Economizer Controller H = Enthalpy Economizer w/ Barometric Relief and W7212 Economizer Controller L = Enthalpy Economizer w/ Barometric Relief, CO and W7212 Economizer Controller Q = Motorized 2 Position Damper w/ Barometric Relief U = Temperature Ultra Low Leak Economizer w/ Barometric Relief W = Enthalpy Ultra Low Leak Economizer w/ Barometric Relief
Indoor Fan Options
1 = Standard Static Option – Belt Drive 2 = Medium Static Option – Belt Drive 3 = High Static Option – Belt Drive
®
IV
2
2
a551J--- 008
3
Fig. 2 -- Dimensional Drawing — Sizes 07--09
C160142
4
Fig. 2 -- Unit Dimensional Drawing — Sizes 07--09 (cont.)
C160143
5
Fig. 3 -- Dimensional Drawing — Sizes 11 and 12
C13302A
6
Fig. 3 -- Unit Dimensional Drawing — Sizes 11 and 12 (cont.)
C13303A
7
C
D
B
A
LOCATION DIMENSION CONDITION
48--- in. (1219 mm)
A
B
C
D
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application
18--- in. (457 mm) 18--- in. (457 mm) 12--- in. (305 mm)
42--- in. (1067 mm) 36--- in. (914 mm)
36--- in. (914 mm) 18--- in. (457 mm)
42--- in. (1067 mm) 36--- in. (914 mm)
planning overhead obstruction or for vertical clearances.
Unit disconnect is mounted on panel No disconnect, convenience outlet option Recommended service clearance Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall) Surface behind servicer is electrically non ---conductive (e.g., wood, fiberglass)
Side condensate drain is used Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) Surface behind servicer is electrically non ---conductive (e.g., wood, fiberglass)
C08337
Fig. 4 -- Service Clearance Dimensional Drawing — Sizes 07--12
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) (ANSI/NFPA 70) for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for minimum clearances required for safety (including clearance to combustible surfaces), unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 4.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, avoid locations that perm it water from higher level runoff and ove rhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow installation of condensate trap pe r requirements.RefertoStep9—InstallExternal Condensate Trap and Line – for required trap dimensions.
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For exa mple, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
8
Table 1 – Operating Weights
551J
Base Unit 715 (324) 860 (390) 860 (390) 1025 (466)
Economizer
Vertical 75 (34) 75 (34) 75 (34) 75 (34)
Horizontal 122 (55) 122 (55) 122 (55) 122 (55)
Powered Outlet 35 (16) 35 (16) 35 (16) 35 (16)
Perfect Humidity™ System
Curb
14--- in./356 mm 143 (65) 143 (65) 143 (65) 143 (65)
24--- in./610 mm 245 (111) 245 (111) 245 (111) 245 (111)
1
Not available for size 11 units.
1
07 08 09 11/12
80 (36) 80 (36) 80 (36) 85 (39)
Curb--mounted Installation —
Install curb Install field--fabricated ductwork inside curb Install accessory thru --base service connection package
(affects curb and unit) (refer to accessory installation instructions for details)
Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 9 for details)
Rig and place unit Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Pad--mounted Installation —
Prepare pad and unit supports Check and tighten the bottom condensate drain
connection plug Rig and place unit Convert unit to side duct connection arrangement Install field--fabricated ductwork at unit duct openings Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latches are snug and in closed position.
Locate the carton containing the outside air hood parts; see Fig. 10. Do not remove carton until unit has been rigged and located in final position.
UNITS LB (KG)
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 6. Assemble and install accessory roof curb in accordance with instru ction s shipped with the curb.
NOTE: The gasketing of t he unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 6. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig. 5. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5″ (13)
Fig. 5 -- Unit Leveling Tolerances
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and
not to the unit. The accessory thru--the--base power package must be installed before the unit is set on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru--the--base service connections to the basepan in accordance with the accessory installation instructions.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
B-C
1.0″ (25)
A-C
1.0″ (25)
a50--- 9658
9
1-3/4"
TYP
[44.5]
C
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
FITTING
1/2" [12.7] NPT 1/2" [12.7] NPT
CONTROL WIRING
FITTING
POWER WIRING
3/4" [19] NPT 1 1/4" [31.7] NPT
THRU THE CURB
CRBTMPWR004A01 THRU THE BOTTOM
CRBTMPWR002A01
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
1 3/4"
[44.5]
1.00"
[25.4]
12-1/2" [317.5] WIDE
INSULATED DECK PANELS
INSULATED DECK PANEL
9-15/16" [252.4] WIDE
"A"
1 3/4"
[44.4]
SEE NOTE #2
2-3/8"
[61]
20-3/4"
[513]
INSIDE
GAS SERVICE PLATE
THRU THE CURB
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
SECTION THRU SIDE
RETURN AIR
SUPPLY AIR
UNIT
[1987.5]
6' 6-1/4"
4' 2"
[1270.0]
"A"
NAIL (FIELD SUPPLIED)
TYPICAL (4) SIDES
7/16"
CERTIFIED DRAWING
SEE VIEW "B"
ROOFING FELT
(FIELD SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
[11]
CURB ASY, ROOF
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
1029120
TOLERANCES ON:
AUTHORIZATION NUMBER TITLE
DIMENSIONS ARE IN INCHES
----
UNLESS OTHERWISE SPECIFIED
1 DEC 2 DEC 3 DEC ANG
PRODUCTION
---
MATERIAL
DRAWING RELEASE LEVEL:
THIRD ANGLE
PROJECTION
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
RIGID INSULATION
SHEET 5 OF 5
50HJ405012
SIZE DRAWING NUMBER REV
D
-
-
-
DRAFTER CHECKER
ENGINEERING MANUFACTURING
MMC 12/16/09 - -
-
-
T-005, Y-002
WEIGHT:
- PURCH - N/A -
ENGINEERING REQUIREMENTS
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
1067898--MMC4/22/13
(FIELD SUPPLIED)
2 1/4"
[57.2]
14 3/4"
[374.7]
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR002A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR004A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
53 1/2"
[1358.9]
11.42"
[290.0]
A
14"
24"
[356]
[610]
26"
[660.4]
6 3/64"
ROOF CURB
ACCESSORY #
CRRFCURB003A01
CRRFCURB004A01
[153.5]
1 3/4"
[44.4]
4 3/16"
[106.0]
81 3/4"
[827.1]
32 9/16"
[2076.3]
3"
40 3/16"
[76.2]
[1020.8]
VIEW "B"
CORNER DETAIL
[585.8]
23 1/16"
OPENING
RETURN AIR
OPENING
SUPPLY AIR
1 3/4"
[44.5]
[401.6]
15 13/16"
DUCT
GASKET
(FIELD SUPPLIED)
(SUPPLIED WITH CURB)
15 15/32
[392.9]
[800.9]
31 17/32"
1 3/4"
[44.5]
6' 61/4" WAS 6' 7 1/6", 4'2' WAS 4' 2 13/16";
18 GA WAS 16 GA.; 15 13/16" WAS 15 15/16"; NAIL
FIELD SUPPLIED WAS WITH CURB
C
SUPPLY AIR RETURN AIR
1/4"
[7.0]
[115.5]
4 9/16"
C13311
Fig. 6 -- Roof Curb Details — Sizes 07--12
10
Alternate Unit Support (InLieuofCurborSlabMount)—
!
WARNING
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side.
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structu re. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and masti c in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
PERSONAL INJURY HAZARD
Failure to follow this warning could cause personal injury.
For vertical supply a nd return units, tools or parts could drop into ductwork and cause an injury. Install a 90--degree turn in the return ductwork between the unit and the conditioned space. If a 90--degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling i nto the conditioned space. Due to electric heater, supply duct will require 90--degree elbow.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 7 for additional information.
Lifting holes are provided in base rails as shown in Fig. 7. Refer to rigging instructions on unit.
Rigging materials under unit (cardboard to prevent base pan damage) must be removed PRIOR to placing the unit on the roof curb.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roofing materials.
Membrane roofs can be cut by sharp shee t metal edges. Be careful when placing any sheet metal parts on such roof.
For Units with Accessory Electric Heaters —
Horizontal applications require a minimum clearance to combustible surfaces of 1--in. (25 mm) from duct for first 12--in. (305 mm) away from unit. Vertical applications do not require a minimum clearance.
Minimum clearance is not required around ductwork.
Outlet grilles must not lie directly below unit discharge.
CAUTION
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a For further details see Step 9 -- Install External Condensate Trap and Line on page 14.
Before setting the unit onto the curb, recheck gasketing on curb.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck when panels or packaging are removed.
If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
1
/2--in. square socket drive extension.
CAUTION
11
UNIT
551J*07 1130 514 88.0 2235 43.0 1090 41.5 1055
551J*08 1340 609 88.0 2235 43.0 1090 49.5 1255
551J*09 1340 609 88.0 2235 43.0 1090 49.5 1255
551J*11/12 1580 718 88.0 2235 31.5 775 49.5 1255
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging st rap s from damag ing unit.
MAX WEIGHT
LB KG IN. MM IN. MM IN. MM
A B C
DIMENSIONS
Fig. 7 -- Rigging Details
C06005
PositioningonCurb—
Position unit on roof curb so that the following clearances
1
are maintained:
/4in. (6.4 mm) clearance between the roof curb and the base rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the
5
condenser end of the unit being approximately 3--
/16in.
(84 mm).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
After unit is in position, remove rigging skids and shipping materials.
Step 7 — Convert to Horizontal and Connect Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without factory--installed economizer or return air smoke detector option may be field--converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove
covers. Using the same screws, install covers on vertical duct openings with the insulation--side down. Seals around duct openings must be tight. See Fig. 8.
C06108
Fig. 8 -- Horizontal Conversion Panels
Field--supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all e xternal ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizont al ductwork.
12
Step 8 — Install Outside Air Hood
Economizer and Two Position Damper Hood Package Removal and Setup -- Factory Option
1. The hood is shipped in knock--down form and must be field assembled. The indoor coil access panel is used as the hood top while the hood sides, divider and filter are packaged together, attached to a metal support tray us­ing plastic stretch wrap, and shipped in the return air compartment behind the indoor coil access panel. The hood assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie-­wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 9.)
FILTER ACCESS PANEL
Economizer Hood and Two--Position Hood —
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The i ndoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bot­tom of the indoor coil access panel. See Fig. 11.
TOP PAN EL
TOP PAN EL
INDOOR COIL ACCESS PAN EL
INDOOR COIL ACCESS PAN EL
CAULK HERE
INDOOR COIL ACCESS PANEL
C10146
Fig. 9 -- Typical Access Panel Locations
3. Locate the (2) screws holding the metal tray to the basepan and remove. Locate and cut the (2) plastic tie--wraps securing the assembly to the damper. (See Fig. 10.) Be careful to not damage any wiring or cut tie--wraps securing any wiring.
Hood Parts
Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)
Fig. 11 -- Indoor Coil Access Panel Relocation
C06025
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 12.
TOP PANEL
INDOOR COIL ACCESS PANEL
LEFT HOOD SIDE
19 1/16
B
(483 mm)
HOOD DIVIDER
SCREW
33 3/8
(848 mm)
a50--- 9659
Fig. 12 -- Economizer Hood Construction
Fig. 10 -- Economizer and Two--Position Damper
Hood Parts Location
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps outlined in Economizer Hood and Two–Position Hood.
C08639
3. Remove the shipping tape hol ding the economizer barometric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See Fig. 12 and 13. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
13
5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 13.
6. Caulk the ends of the joint between the unit top panel and the hood top.
7. Replace the filter access panel.
DIVIDER
OUTSIDE AIR
MINIMUM PITCH 1˝ (25 mm) PER 1 (3 m) OF LINE
TO ROOF DRAIN
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4 in. (102 mm) trap is recommended.
BASE RAIL
OPEN VENT
3˝(76 mm)
MIN
DRAIN PLUG
Fig. 15 -- Condensate Drain Piping Details
SEE NOTE
ROOF CURB
a50--- 9660
HOOD
CLEANABLE
BAROMETRIC RELIEF
ALUMINUM FILTER
FILTER
FILTER CLIP
C08634
Fig. 13 -- Economizer Filter Installation
Step 9 — Install External Condensate Trap and Line
The unit has one3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 14. Unit airflow configuration does not determine which drai n connection to use. Either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan plug can
1
be tightened with a
/2--in. square socket drive extension.
To use the alternate bottom drain connect ion, remove the
1
red drain plug from the bottom connection (use a
/2-- i n . square socket drive extension) and install it in the side drain connection.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream fr om the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use
3
a pipe size smaller than the unit connection (
/4-in.).
Step 10 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC; ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association ] C22.1), and local electrical codes.
NOTE: Field--supplied wiring shall conform with the limitations of minimum 63_F(33_C) rise.
Field Power Supply —
CONDENSATE PAN (SIDE VIEW)
STANDARD SIDE DRAIN
DRAIN
PLUG
(FACTORY-INSTALLED)
Fig. 14 -- Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 15.
ALTERNATE BOTTOM DRAIN
C08021
If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always--energized convenience outlet operation is desired, connect the source leads to the line side of the unit--mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de--energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit--mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads (see Fig. 16).
14
L3
L2
L1
Ground
(GR)
Units Without Disconnect Option
CIFC
13 11 1 3
Disconnect
per
NEC
L1 L2 L3
208/230-3-60
460-3-60 575-3-60
Ground
(GR)
Equip
GR Lug
Units With Disconnect Option
L3
Optional
Disconnect
L2
L1
Disconnect factory test leads; discard.
Switch
T3
T2
T1
BLU
YEL
BLK
Equip GR Lug
Factory Wiring
Refer to Fig. 23 for power transformer connections and the discussion on connecting the convenience outlet on page 17.
Field power wires are connected to the unit at line--side pressure lugs on compressor contactor C and indoor fan contactor IFC (see wiring diagram label for control box component arrangement), at factory--installed option non--fused disconnect switch. Max wire size is #4 AWG (copper only) per pole on contactors and #2ga AWG (copper only) per pole on optional non--fused disconnect. See Fig. 16 and the unit label diagram for field power wiring connections.
NOTE: TEST LEADS -- Unit may be equipped with short leads (pigtails) on the field line connection points on contactor C or optional disconnect switch. These leads are for factory run--test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line connection pressure lugs only.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not connect aluminum wire between disconnect switch and 551J unit. Use only copper wire. (See Fig. 17.)
Units With Electric Heat Option with Single Point Box
and Without Disconnect Option
Single Point Box
Ground (GR)
L1
L2
L3
Terminal Block
Equip GR
Lug
BLK
YEL
BLU
— OR —
Single Point Box
L1
L2
L3
Ground (GR)
Fuse/Terminal Block
Fuse
Fuse
Fuse
Equip GR
Lug
BLK
YEL
BLU
Fig. 16 -- Power Wiring Connections
Factory Wiring
Factory Wiring
C12763
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
Fig. 17 -- Disconnect Switch and Unit
Units With Factory--Insta lled Non--Fused Disco n n ect —
The factory--install ed option non--fused disconnect (NFD) switch is located in a weatherproof enclosure located under the main control box (see Fig. 18). The manual switch handle and shaft are shipped in the disconnect enclosure. Assemble the shaft and handle to the switch at this point. Discard the factory test leads (see Fig. 16).
Connect field power supply conductors to LINE side terminals when the switch enclosure cover is removed to attach the handle.
15
C12278
Fig. 18 -- Location of Non--Fused Disconnect Enclosure
To field install the NFD shaft and handle:
1. Remove the unit front panel (see Fig. 2 or Fig. 3).
2. Remove (3) hex screws on the NFD enclosure -- (2) on the face of the cover and (1) on the left side cover. See Fig. 19.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at OFF position (the arrow on the black handle knob is at OFF) .
5. Insert the shaft with the cross pin on the top of the shaft in the horizontal position.
6. Measure from the tip of the shaft to the top surface of the black pointer; the measurement should be 3.75 to
3.88 in. (95 to 99 mm).
7. Tighten the locking screw to secure the shaft to the NFD.
8. Turn the handle to the OFF position with red arrow pointing at OFF.
9. Install the handle on to the painte d cover horizontally with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws and lock washers supplied.
11. Engaging the shaft into the handle socket, re--install (3) hex screws on the NFD enclosure.
12. Re--install the unit front panel.
Units Without Factory--Installed Non--Fused Disconnect —
When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconn ect on the unit cabinet.
All Units —
All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 16 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #4 ga AWG (copper only) per pole on contactors and #2ga AWG (copper onl y) per pole on optional non--fused disconnect.
Provide a ground--fault and short--circuit over--current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over--current Protection) device size.
All field wiring must comply with the NEC and local requirements.
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire
1
with the connection and moving it to the 208-v
/4-in. female spade connector from the 230--v
1
/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information.
Voltage to compressor terminals during operation must be within volt age range indicated on unit nameplate. On 3--phase units, voltages between phases must be balanc ed within 2% and the current within 10%. Use the formula below to determine the percent of voltage imbalance.
%Voltage Imbalance
Example: Supply voltage is 230-3-60
= 100 x
max voltage deviation from average voltage
average voltage
AB = 224 v BC = 231 v AC = 226 v
Fig. 20 -- Handle and Shaft Assembly for NFD
C12279
Average Voltage =
Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance.
%VoltageImbalance
This amount of phase im balance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
(224 + 231 + 226)
3
= 100 x
4
227
= 1.76%
681
=
3
=227
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to
16
electrical components. Such operation would invalidate any applicable Bryant warranty.
NOTE: Check all factory and field electrical connections for tightness.
Convenience Outlets —
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Units with convenience outlet circ uits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Lock--out and tag--out this switch, if necessary.
Tw o types of convenience outlets are offered on 551J models: Non--powered and unit--powered. Both types provide a 125--volt GFCI (ground--fault circuit--interrupter) duplex receptacle rated at 15--A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 21.
Pwd-CO
Convenience
Outlet
GFCI
Transformer
Remove the blank cover plate at the convenience outlet ; discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/2-in. (13 mm) under screw heads are exposed. Press t he gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).
Mount the wea therproof cover to the backing plate as shown in Fig. 22. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.
COVER – WHILE-IN-USE WEATHERPROOF
RECEPTACLE NOT INCLUDED
BASE PLATE FOR GFCI RECEPTACLE
C09022
Fig. 22 -- Weatherproof Cover Installation
Pwd-CO
Fuse
Switch
Control Box
Access Panel
C08128
Fig. 21 -- Convenience Outlet Location
Installing Wea therproof C o ver: A weatherproof
while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control box. The kit i ncludes the hinged cover, a backing plate and gasket.
DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET. LOCK--OUT AND TAG--OUT ALL POWER.
Non--powered type: This type requires the field installation of a general--purpose 125--volt 15--A circuit powered from a source elsewhere in the building. Observe national and loca l codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125--v power supply conductors into the bottom of the utility box containing the duplex receptacle.
Unit--powered type: A unit--mounted transformer is factory--installed to stepdown the main power supply voltage to the unit to 115--v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s c ontrol box access panel. See Fig. 21.
The primary leads to the convenience outlet transformer are not factory--connected. Selection of primary power source is a customer--option. If local codes permit, the transformer primary leads can be connected at the line--side terminals on the unit--mounted non--fused disconnect switch; this will provide service power to the unit when the unit disconnect switch is open. Other connection methods will result in the convenience outlet circuit being de--energized when the unit disconnect switch is open. See Fig. 23.
17
Loading...
+ 39 hidden pages