Third Party Networking27.............................
APPENDIX A - USER INTERFACE MENUS28............
APPENDIX B - THIRD PARTY POINTS LIST37...........
RTUOPENSTART-UPSHEET41.......................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
shouldinstall,repair,orserviceair-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves.
Follow all safety codes. Wear safety glasses and work
gloves. Have fire extinguisher available. Read these
instructions thoroughly and follow all warnings or
cautions attached to the unit. Consult local building codes
andNationalElectricalCode(NEC)forspecial
requirements.
Recognize safety information. This is the safety- alert
TS- 5580- 01
symbol
instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety-alert
symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect all power to the unit before performing
maintenance or service. Unit may automatically start
if power is disconnected.
. When you see this symbol on the unit and in
!
WARNING
GENERAL
The RTU Open controller is an integrated component of the
Bryant rooftop unit. Its internal application programming
provides optimum performance and energy efficiency. RTU
Open enables the unit to run in 100% stand- alone control
mode or a Third Party Building Automation System (BAS).
On- board DIP switches allow you to select your protocol
(and baud rate) of choice among the four most popular
protocols in use today: BACnet
LonWorks. (See Fig. 1.)
NOTE: Lon Works requires addition of LON option card.
Bryant’s diagnostic display tools such as Field Assistant,
BACview
with the RTU Open controller. Access is available via a
5- pin J12 access port.
6
Handheld or Virtual BACview can be used
R
, Modbus, Johnson N2 and
SENSOR/ACCESSORY
INSTALLATION
There are a variety of sensors and accessories available
for the RTU Open. Some of these can be factory or field
installed, while others are only field installable. The RTU
Open controller may also require connection to a building
network system or building zoning system. All field
control wiring that connects to the RTU Open must be
routed through the raceway built into the corner post of
the unit or secured to the unit control box with electrical
conduit. The unit raceway provides the UL required
clearance between high and low-voltage wiring. Pass the
control wires through the hole provided in the corner post,
then feed the wires thorough the raceway to the RTU
Open. Connect the wires to the removable Phoenix
connectors and then reconnect the connectors to the board.
See Fig. 1 and Table 1 for board connections and Fig. 2
for Typical Factory RTU Open wiring.
IMPORTANT: Refer to the specific sensor or accessory
instructions for its proper installation and for rooftop unit
installation refer to base unit installation instructions and
the unit’s wiring diagrams.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, death and/or equipment damage.
Disconnect electrical power and use lock- out tags
before wiring the RTU Open controller.
2
Input_2 (CO2/RH)
Input_1 (CO2/RH)
+24 VDC
Gnd
Gnd
+24 VDC
Board Power
24 VAC IN
DO-2 (W2)
DO-1 (G)
Gnd
Input_3 (X)
DO-3 (W1)
DO-4 (Y2)
DO-5 (Y1)
Input_5 (SMK)
Input_4 (R)
Input _8 (Enthalpy)
AO-1 (ECON)
Configurable - Input_8
Configurable - Input_5
Configurable - Input_3
Input_9 (Humidistat)
Gnd
24 VAC
(AO-1)
(OAT)
(SAT)
Gnd
Lonworks
Option Card
Port
J4
J12
J13
J22
J17
J2J1
Network Comm
0-10VDC
24 VAC
24 VAC
24 VAC
J3
4-20mA
J5J5
J11
DO-6 (H)
Dehumidification
DO-7
(Reversing Valve/High Speed Fan)
DO-8
(Power Exhaust)
24 VAC
TS- 5580- 01
Example set for
BACnet MS/TP
and 76.8K baud
(1, 2, and 4 ON)
J15
J20
Protocol SelectorSPT (temp input)BACnet, Modbus, or N2
*Remove
both for 0-5V
SPT (common)
SPT (offset input)
J19
(LON connection J15)
J14
Fig. 1 - RTU Open Control Module
C12744
3
Table 1 – RTU Open Inputs and Outputs
POINT NAME
Space Temp / Zone Tempzone_tempAI (10K Thermistor)J20- 1 & 2
Supply Air Temperaturesa_tempAI (10K Thermistor)J2- 1 & 2
Outdoor Air T emperatureoa_tempAI (10K Thermistor)J2- 3 & 4
Space Temperature Offset Potstpt_adj_offsetAI (100K Potentiometer)J20 - 3 & 4
Safety Chain Feedbacksafety_statusDI (24 VAC)J1- 9
Compressor Safety Statuscomp_statusDI (24 VAC)J1 - 2
Fire Shutdown Statusfiredown_statusDI (24 VAC)J1- 10
Enthalpy Statusenthalpy_statusDI (24 VAC)J2- 6 & 7
Humidistat Input Statushumstat_statusDI (24 VAC)J5- 7 & 8
Zone Temperaturen/an/aJ13- 1, 2, 3, 4
Indoor Air CO2iaqAI (4- 20 ma)
Outdoor Air CO2oaqAI (4 - 20 ma)
Space Relative Humidityspace_rhAI (4- 20 ma)
Supply Fan Status*sfan_statusDI (24 VAC)
Filter Status*filter_statusDI (24 VAC)
Door Contact Input*door_contact_statusDI (24 VAC)
Occupancy Contact*occ_contact_statusDI (24 VAC)
* These inputs (if installed) take the place of the default input on the speci fic channel
Parallel pins J5- 1 = J2 - 6, J5- 3 = J1 - 10, J5- 5 = J1 - 2 are used for filed installation.
Refer to the input configuration and accessory sections for more detail.
BACnet OBJECT
NAME
DEDICATED INPUTS
CONFIGURABLE INPUTS
TYPE OF I/O
J4- 2 & 3 or J4- 5 & 6
J5- 1 or J5- 3 or J5- 5
OUTPUTS
CONNECTION PIN
NUMBER(S)
Sensors and Accessories
The RTU Open controller is configurable with the
following field-supplied sensors:
NOTE: Supply air temperature sensor (33ZCSENSAT) is
factory-installed.
S Space temperature sensor (33ZCT55SPT, 33ZCT56SPT,
or 33ZCT59SPT)
S Indoor air quality sensor (33ZCSPTCO2- 01,
33ZCSPTCO2LCD- 01, 33ZCT55CO2, 33ZCT56CO2)
required for demand control ventilation.
S Outdoor air quality sensor (33ZCSPTCO2- 01,
33ZCSPTCO2LCD- 01)
aspirator box (C33ZCCASPCO2) required for CO
S CO
2
return duct/outside air applications
S Outdoor air enthalpy switch (33CSENTHSW)
S Return air enthalpy sensor (33CSENTSEN) required for
differential enthalpy control
S Space relative humidity sensor (33ZCSENSRH-02)
S Duct relative humidity (33ZCSENDRH-02)
S Humidistat (--HL--38MG-029)
S Smoke Detectors (CRSMKSEN002A00,
CRSMKKIT002A00)
S Fan and/or Filter Status (CRSTATUS001A00,
CRSTATUS005A00)
User Interfaces
S BACview6Handheld (BV6H)
S Virtual BACview (USB-L or USB-TKIT required)
S Field Assistant (USB-TKIT required)
Install Analog Sensors
Supply Air Sensor (SAT)
The factory supplies the discharge (supply) air sensor with
the unit and is pre- wired. On 04-16 size units, the SAT is
secured to the unit’s supply duct opening. This sensor
must be relocated into the supply duct during unit
installation. On 17-30 size units, the SAT is mounted
through the side of the heat chamber below the fan deck,
2
and does NOT require relocation.
OutdoorAirSensor(OAT)
The OAT is supplied with the economizer option or
accessory. It is wired through the 12-pin plug (PL6) in the
return air section of the unit and is mounted on the
economizer assembly.
Space Temperature Sensor (SPT)
SPT sensors available from Bryant are resistive input
non-communicating (T55, T56, and T59) sensors. These
sensors have a variety of options consisting of: timed
override button, set point adjustment, and a LCD screen.
Space temperature can be also be written to from a building
network or zoning system. However, it is still recommended
that return air duct sensor be installed to allow stand-alone
operation for back-up. Refer to the configuration section for
details on controller configurations associated with space
sensors.
4
TS- 5580- 01
Fig. 2 - Typical Factory Option Wiring
5
C12745
Resistive Non-Communicating Sensor Wiring
For sensor with setpoint adjustment up to 500 ft (152m),
use three-conductor shielded cable 20 gauge wire to
connect the sensor to the controller. For non set point
adjustment (slidebar) or return air duct sensor, an
unshielded, 18 or 20 gauge, two-conductor, twisted pair
cable may be used. Below is the list of the connections of
the SPT to the RTU Open, refer to Fig. 3 and 4 for typical
connections at the sensor.
S J20-1 = temperature sensor input (SEN)
S J20-2 = sensor common
S J20-3 = Setpoint adjustment input (SET)
NOTE: See Fig. 5 for space temperature sensor averaging.
T55/56 Override button will no longer function when sensors
are averaged. Only Sensor 1 T56 STO input can be used.
TS- 5580- 01
2
3
SW1
CoolWarm
45
SEN
61
SET
BLK
(T56)
BRN (GND)
BLU (SPT)
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
Fig. 3 - Space Temperature Sensor
Typical Wiring (33ZCT56SPT)
BLK (STO)
BRN (COM)
BLU (SPT)
J20-3
J20-2
J20-1
SENSOR
WIRING
C07131
Rnet Communicating Sensor Wiring
The Rnet bus allows local communication with the RTU
Open, including field supplied communicating sensors.
The Rnet bus can hold up to 6 devices, including up to 2
6
BACview
units,wiredindaisy-chainorhybrid
configuration.
6
NOTE: Additional BACview
Refer to the BACview
6
units must be addressed.
installation instructions for for
details on addressing.
For Rnet wiring up to 500ft (152m), use 18 AWG 4
conductor unshielded plenum rated cable. The RTU Open’s
J13-RNET connection has a 4 pin Phoenix connector wired
as described below, Fig. 6 shows sensor Rnet wiring.
S RNET - 1 = Signal ground (GND)
S RNET - 2 = Signal (Rnet+)
S RNET - 3 = Signal (Rnet- )
S RNET - 4 = Power (+12v)
CO2Sensor(s) (IAQ and OAQ)
The indoor air quality (IAQ) and outdoor air quality
2
Sensor
) levels. This
2
(IAQ) sensor
sensor
2
(OAQ) sensors monitor carbon dioxide (CO
information is used to monitor the quality of air in terms
of parts per million (PPM). The same sensor is used for
inside, outside, and duct monitoring, except an aspirator
box is required for outside and duct mounting. The CO
sensor is preset for a range of 0 to 2000 ppm and a linear
mA output of 4 to 20. The rooftop unit may have a factory
installed CO
sensor on the side of the economizer
2
assembly in the return air section of the unit and is
pre-wired and pre-configured at the factory. For field
installed sensors, a field supplied transformer must be
used to power the sensor. Refer to the instructions
supplied with the CO
sensor for electrical requirements
2
and terminal locations. RTU Open configurations must be
changed after adding a CO
for typical CO
sensor wiring.
2
sensor. See below and Fig. 7
2
S J4- 2 or J4- 5 = 4- 20mA signal input
S J4- 3 or J4- 6 = signal common
NOTE: The factory used J4-2&3 for CO
inputs.
Combination Temperature and CO
2
If using a combination temperature and CO
(33ZCT55CO2 or 33ZCT56CO2), refer to the installation
instructions provided with the sensor.
2
ORSET SEN
OPB COM- PWR+
24 VAC
NOTE: Must use a separate isolated transformer.
Fig. 4 - Space Temperature Sensor
Typical Wiring (33ZCT59SPT)
POWER
WIRING
C10291
6
RED
r
BLK
RED
BLK
J20
1
2
J20
1
2
RED
BLK
LEGEND
Factory Wiring
Field Wiring
RED
BLK
RED
BLK
SENSOR 1SENSOR 2SENSOR 3SENSOR 4
RED
BLK
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
BLK
BLK
SENSOR 1
RED
SENSOR 4
RED
RED
BLK
SENSOR 2
RED
BLK
SENSOR 5
RED
BLK
RED
BLK
SENSOR 3
RED
BLK
SENSOR 6
RED
BLK
TS- 5580- 01
SENSOR 7
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
Fig. 5 - Space Temperature Averaging
C10820
Fig. 6 - Typical Rnet Communication Sensor Wiring
SENSOR 8
SENSOR 9
C07133
To controller
24 VacLine
-
8 7 6 5 4
+
2 1
24 Vac
or Vdc
Dedicated Transforme
SENSOR LEGEND
1 +24 Vac/Vdc
2 Gnd (-24 Vac/Vdc)
4 -Thermistor
5 +Thermistor
6 4-20 mA
7 SIG COM
8 0-5 Vdc
C12748
Fig. 7 - Indoor/Outdoor Air Quality (CO2)Sensor
(33ZCSPTCO2- 01 or 33ZCSPTCO2LCD- 01)
Typical Wiring Diagram
7
Relative Humidity Sensors (Space or Duct
Mounted)
The accessory space humidity sensor or duct humidity
sensor is used to measure the relative humidity of the air
within the space or return air duct. The RH reading is used
to control the Perfect Humidityt option of the rooftop
unit. For wiring distances up to 500 ft (152m), use a
3-conductor, 18 or 20 AWG shielded cable. The shield
must be removed from the sensor end of the cable and
grounded at the unit end. The current loop power for the
sensor is provided by the RTU Open controller as 24vdc.
Refer to the instructions supplied with the RH sensor for
electrical requirements and terminal locations. RTU Open
configurations must be changed after adding a RH sensor.
See below and Fig. 8 and 9 for typical RH sensor wiring.
S J4- 1 or J4- 4 = 24vdc loop power
S J4- 2 or J4- 5 = 4- 20mA signal input
NOTE: The factory default for dehumidification control
is a normally open humidistat.
Installing Discrete Inputs
TS- 5580- 01
Compressor Safety
The compressor safety input provides the RTU Open with
feedback to when the compressor is not running and
should be. This feedback is usually provided by a
Compressor Lock-Out (CLO) device. Compressor safety
is a dedicated input on the configurable input 3 and tells
the RTU Open when the compressor is locked out. The
normal condition for compressor safety is good operation.
A normally open compressor safety is the factory default
for all units. Follow specific accessory instructions if
installing a CLO device. The CLO should wire into the
unit’s central terminal Board (CTB).
NOTE: Input 3 can also be wired into J-5.
MOUNTING
HOLES
Io
Gnd
Vin
Vo
SW2
123456
ON
a33-9141
Vin - J4 -1 or J4 -4 24Vdc
Io - J4 -2 or J4 -5 4 -20mA output
Fig. 8 - Space Relative Humidity Sensor Typical Wiring
WIRING
OPENING
C07201
Humidistat
The accessory humidistat provides the RTU Open insight
to the relative humidity in the space. The humidistat reads
the RH level in the space and compares it to its setpoint to
operate a dry contact. The humidistat is a dedicated input
on the configurable input 9 and tells the RTU Open when
the RH level is HIGH or LOW. The normal condition for
humidity is LOW. A normally open humidistat is the
factory default control for the Perfect Humidityt option.
To wire in the field:
S J5- 8 = 24 VAC source for dry contact
S J5- 7 = Signal input
Single Enthalpy (Outdoor Enthalpy)
The outdoor enthalpy switch/receiver (33CSENTHSW)
senses temperature and humidity of the air surrounding
the device and calculates the enthalpy when used without
an enthalpy sensor. The relay is energized when enthalpy
is high (above 28 BTU/lb OR dry bulb temperature is
above 75_F) and de-energized when enthalpy is low
(below 27 BTU/lb AND dry bulb temperature is below
74.5_F). The enthalpy input is dedicated to input 8 and
tells the RTU Open when the outside air enthalpy is HIGH
or LOW. The normal condition for the enthalpy input is
HIGH. Enthalpy is configured on input 8 in the factory
when it is added as an option.
NOTE:The enthalpy calculation is done using an
average altitude of 1000 ft above sea level.
For field installation, refer to the enthalpy accessory
instructions. For wiring see below and Fig. 10. The RTU
Open board provides 24vac on one of the two loose grey
wires in the return air section of the rooftop near the
12-pin economizer plug. To determine the correct grey,
measure the voltage on the wires with power applied to
the unit. If 24-vac is sensed, then that is the grey wire that
is connected to the RTU Open board at J2-7. The other is
the signal for input 8, connect it to the LOW Enthalpy
terminal on the enthalpy switch/receiver. Tie into the
12-pin economizer plug on pin 4 or the black wire
connected to the actuator for the enthalpy’s GND
connection. Power can also be provided direct from the
unit transformer and J5 terminal on the RTU Open.
S J2- 7 or J5- 2 = 24 VAC for enthalpy switch power
S J2- 6 or J5- 1 = input signal
Differential Enthalpy
Differential enthalpy control requires both an enthalpy
switch/receiver (33CSENTHSW) and an enthalpy sensor
(33CSENTSEN). The enthalpy sensor must be installed in
the field as the factory can only provide single enthalpy.
The enthalpy sensor must be mounted in the return
airstream and calculates the enthalpy of the indoor air.
The relay is energized when the enthalpy detected by the
return air enthalpy sensor is less than the enthalpy at the
enthalpy switch/receiver. The relay is de-energized when
the enthalpy detected by the return air enthalpy sensor is
greater than the enthalpy at the enthalpy switch/receiver
(differential enthalpy control).
8
J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-)4 to 20 mA Current Loop Output
to RTU Open
To wire return air enthalpy sensor:--MP
Connect the 4-20 mA In terminal on the enthalpy switch/
receiver to the 4-20 mA Out terminal on the return air
enthalpy sensor. Connect the 24-36 VDC Out terminal on
the enthalpy switch/receiver to the 24-36 VDC In terminal
on the return air enthalpy sensor. (See Fig 10.)
Fire Shutdown
The fire shutdown input is provided for unit shutdown in
response to a fire alarm or smoke detector. The fire
shutdown input is dedicated to input 5 and tells the RTU
Open when to shutdown due to smoke detection or fire
alarm system. The normal condition for fire shutdown is
there is no fire alarm. The unit may have factory installed
smoke detector(s); refer to the base unit installation
instructions for details on any adjustments required during
unit installation.Fire shutdownis alwaysfactory
configured for a normally open smoke detector.
For field installation of a smoke detector see instructions
forthatspecificaccessory.Seebelowandthe
troubleshooting section for wiring at the unit’s Central
Terminal Board (CTB).
S CTB - UNIT SHUTDOWN - 24v OUT = 24 VAC
source
S CTB - UNIT SHUTDOWN - Smoke Alarm = Signal
input to RTU Open
NOTE: Input 5 can also be wired into J5- 3.
Relative Humidity Sensor
(Polarized Male Connector)
4-20mAVAC
VDC
or
GND 0-5V
0-10V
SPAN
ZERO
or
123456
ON
Filter Status
The filter status accessory is a field-installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must have a free input (input 3, 5,
8, or 9). One of the dedicated functions (Humidistat, Fire
shutdown, Enthalpy, or Compressor safety) must not be in
use to configure Filter Status. Refer to the configuration
section for details on configuring inputs for specific
functions and state. Refer to Fig. 1 for wire terminations
at J5.
Fan Status
The fan status accessory is a field-installed accessory.
This accessory detects when the indoor fan is moving air.
When installing this accessory, the unit must have a free
input (input 3, 5, 8, or 9). One of the dedicated functions
(Humidistat, Fire shutdown, Enthalpy, or Compressor
safety) must not be in use to configure Fan Status. Refer
to the configuration section for details on configuring
inputs for specific functions and state. Refer to Fig. 1 for
wire terminations at J5.
Remote Occupancy
The remote occupancy accessory is a field-installed
accessory. This accessory provides an input to change the
units occupancy status. When installing this accessory, the
unit must have a free input (input 3, 5, 8, or 9). One of the
dedicated functions (Humidistat, Fire shutdown, Enthalpy,
or Compressor safety) must not be in use to configure
remote occupancy. Refer to the configuration section for
details on configuring inputs for specific functions and
state. Refer to Fig. 1 for wire terminations at J5.
C12756
TS- 5580- 01
9
C10821
TS- 5580- 01
Fig. 10 - Enthalpy Switch and Sensor Wiring
Communication Wiring- Protocols
General
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
The RTU Open can be set to communicate on four
different protocols: BACnet, Modbus, N2, and LonWorks.
Switch 3 (SW3) on the board is used to set protocol and
baud rate. Switches 1 and 2 (SW1 and SW2) are used to
set the board’s network address. See Fig. 11 and 12 for
protocol switch settings and address switches. The 3rd
party connection to the RTU Open is through plug J19.
See Fig. 13 for wiring. Contact Bryant applications
engineering for more detailed information on protocols,
3rd party wiring, and networking.
NOTE: Power must be cycled after changing the SW1- 3
switch settings.
BACnetRMS/TP
BACnet Master Slave/Token Passing (MS/TP) is used for
communicatingBACnetoverasub- networkof
BACnet- only controllers. This is the default Bryant
communications protocol. Each RTU Open module acts as
an MS/TP Master. The speed of an MS/TP network can
range from 9600 to 76.8K baud. Physical Addresses can
be set from 01 to 99.
10
SW3 Protocol Selection
PROTOCOLDS8DS7DS6DS5DS4DS3DS2DS1
BACnet MS/TP
(Master)
Modbus
(Slave)
N2
(Slave)
LonWorksUnusedONONOFFONOFFOFFON
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
BAUD RATEDS2DS1
9600OFFOFF
19,200ONOFF
38,400OFFON
76,800ONON
UnusedOFFOFFOFFONOFFSelect Baud Select Baud
UnusedOFFOFFONONOFFSelect Baud Select Baud
UnusedOFFOFFOFFONONOFFOFF
Baud Rate Selections
Fig. 11 - RTU Open SW3 Dip Switch Settings
Fig. 12 - RTU Open Address Switches
C10815
C07166
TS- 5580- 01
Modbus
The RTU Open module can speak the Modicon Modbus
RTU Protocol as described in the Modicon Modbus
Protocol Reference Guide, PI- -MBUS- -300 Rev. J. The
speed of a Modbus network can range from 9600 to 76.8K
baud. Physical Addresses can be set from 01 to 99.
Johnson N2
N2 is not a standard protocol, but one that was created by
Johnson Controls, Inc. that has been made open and
available to the public. The speed of N2 network is
limited to only 9600 baud. Physical Addresses can be set
from 01 to 99.
LonWorks
LonWorks is an open protocol that requires the use of
Echelon’s Neuron microprocessor to encode and decode
the LonWorks packets. In order to reduce the cost of
adding that hardware on every module, a separate
LonWorks Option Card (LON- OC) was designed to
connect to the RTU Open.
This accessory card is needed for LonWorks and has to be
ordered and connected using the ribbon cable to plug J15.
The RTU Open’s baud rate must be set to 38.4k to
communicate with the LON-OC. The address switches
(SW1 & SW2) are not used with LonWorks.
Fig. 13 - Network Wiring
C10816
11
LON OC Rev.4
COMM
OPTION
Network
Net
Connector
Local Access
TS- 5580- 01
BACview6Handheld
6
The BACview
connect to the RTU Open to access the control
information, read sensor values, and test the RTU. (See
Fig. 15.) This is an accessory interface that does not come
with the RTU Open controller. Youconnectthe
BACview
6
of the communicating space sensor’s access port. There
are 2 password protected levels in the display (User and
Admin). The user password is defaulted to 0000, but can
be changed. The Admin password is 1111 and cannot be
changed. There is a 10 minute auto logout if a screen is
left idle. See Appendix A for navigation and screen
content.
is a keypad/display interface used to
to the RTU Open’s J12 local access port or one
1 2
Fig. 14 - LON- OC and LON Network Wiring
J15
C12750
Virtual BACview
Virtual BACview is a freeware computer program that
functions as the BACview
interface (USB- L) is required to connect a computer to
the RTU Open board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identical to the handheld.
Field Assistant
Field Assistant is a computer program included with the
purchase of the USB Link Tech Kit (USB-TKIT). This is a
field Tech Tool to set-up, service, or download the RTU
Open controller. The link cable connects a USB port to
the J12 local access port. The menu structure is similar to
the BACview.
6
Handheld. The USB Link
Access Port
P1P1
J12
Cable
P5P5
Fig. 15 - BACview6Handheld Connections
12
BACview
Protocol Selector
RTU Open
6
Local Access Cable
C12749
START- UP
IMPORTANT: Follow the base unit’s start-up sequence
documented in its specific instructions. Use the base unit’s
start-up check list when performing the start-up. At the
end of this manual there is an additional RTU Open
Start-up Sheet to be completed and included with the base
unit check list.
Besides the base unit start-up, there are a few steps to take
to properly start-up the controls. RTU Open’s Service Test
function should be used to assist in the base unit start-up
andalsoallowsverificationofoutputoperation.
Controller configuration is also part of start-up. This is
especially important when field accessories have been
added to the unit. The factory pre-configures options
installed at the factory. There may also be additional
installation steps or inspection required during the start-up
process.
Additional Installation/Inspection
Inspectthe fieldinstalledaccessoriesfor proper
installation, making note of which ones do or do not
require configuration changes. Inspect the RTU Open’s
Alarms for initial insight to any potential issues. See
troubleshooting section for alarms. Inspect the SAT sensor
for relocation as intended during installation. Inspect
special wiring as directed below.
Perfect Humidityt Control Wiring
In units equipped with the optional Perfect Humidity
option there are 2loosewires (one pink and one
pink/black) in the control box used to control the
dehumidification function of the unit. These wires are
meant to be ties to a space humidistat or thermidistat on
an electromechanical unit. On RTU Open equipped units
these wires must be connected to J11-7 & 8 to allow the
Open board to operate the dehumidification function or
the unit. Disconnect the J11 Phoenix style connector form
the board and use the plug screws to secure the pink/black
wire in pin 7 and and the pink wire in pin 8, reconnect the
plug to the board at J11.
Power Exhaust Relay Power
The relay used by the RTU Open board to control power
exhaust is a dry contact which means it does not have
24vac. This 24vac must be connected to the relay to allow
it operate the power exhaust relay in the PE accessory. A
24vac source should be provided to the J11-2 pin on the
RTU Open. This can be provided by the unit’s transformer
from various sources. The “R” terminal on the unit’s
central terminal board (CTB) is a logical source.
Service Test
The Service Test function can be used to verify proper
operation of compressors, heating stages, indoor fan,
power exhaust fans, economizer, and dehumidification.
Use of Service Test is recommended at initial system start
up and during troubleshooting. See Appendix A for
Service Test Mode table.
Service Test mode has the following changes from normal
operation:
S Outdoor air temperature limits for cooling circuits,
economizer, and heating are ignored.
S Normal compressor time guards and other staging
delays are ignored.
S The status of Alarms (except Fire and Safety chain) is
ignored, but all alerts and alarms are still broadcasted
on the network.
Service Test can be turned ON/OFF at the unit display or
from the network. Once turned ON, other entries may be
made with the display or through the network. To turn
Service Test on, change the value of Test Mode to ON, to
turn Service Test off, change the value of Test Mode to
OFF.
NOTE: Service Test mode is password protected when
accessing from the display. Depending on the unit model,
factory-installed options, and field-installed accessories,
some of the Service Test functions may not apply.
Fan Test
This point allows the board’s fan output to be manually
turned On (Enable) and Off (Disable). Other test points
that require the fan for operation will automatically turn
the fan on and this point will still show “Disable.” Fan test
can operate simultaneously with other Service Test Points.
High Speed Fan Test
Use the High Speed Fan Test to activate and deactivate
the Supply Fan (BO-1) output.
NOTE: This output is only applicable if Fan Control is
set to Two Speed and Unit Type is not equal to HP O/B
Ctrl.
Compressor 1 and Compressor 2 Test
The compressor test points are used to change output
status for the individual compressors. Compressor starts
are not staggered. The fan and heating service test outputs
are reset to “Disable” for the compressor service tests.
The Indoor fan and outdoor fans are controlled normally
to maintain proper unit operation. All normal cooling
alarms and alerts are functional.
NOTE: Compressor 1 is always operated with Compressor
2 due to outdoor fan control on Compressor 1. Always test
Compressor 1 first, and leave it on to test Compressor 2.
Heat 1 and Heat 2 Test
The heat test points are used to change output status for
the individual heat stages, gas or electric. The fans and
cooling service test outputs are reset to “Disable” for the
heat service tests. Indoor and outdoor fans are controlled
normally to maintain proper unit operation. All normal
heating alarms and alerts are functional.
Reversing Valve Test
This test point activates the DO7 relay at J11. These
rooftop units do not use reversing valve control for heat
pumps, therefore this test is not used.
TS- 5580- 01
13
Dehumidification Test
ForunitswiththefactoryReheatoption,the
dehumidification relay is used to change the output status
to operate the circuits in different Reheat modes.
Dehumidification relay on by itself puts all circuits
running in Hot Gas Reheat dehumidification mode;
dehumidificationrelayonandthecoolingtest
(compressor test relays) on puts unit and or individual
circuits in subcooling dehumidification mode. The fans
and heating service test outputs are reset to “Disable” for
the dehumidification service test. Indoor and outdoor fans
are controlled normally to maintain proper unit operation.
Allnormalcooling/dehumalarmsandalertsare
functional.
Power Exhaust Test
This point allows the board’s power exhaust (PE) output
to be manually turned On (Enable) and Off (Disable).
Power Exhaust test can operate simultaneously with other
Service Test Points.
Economizer Test
TS- 5580- 01
This point allows the board’s economizer output to be
manually controlled from 0 to 100 % Open. Economizer
test can operate simultaneously with other Service Test
Points.
Analog Output 2 Test
This test point activates the AO2 0-10vdc analog output at
J22. These rooftops do not use this output, therefore this
test is not used.
NOTE: Service Test Mode does not timeout. Be sure to
turn off test mode or cycle power to the RTU to return to
normal operation.
Configuration
The RTU Open controller’s configuration points effect the
unit’s inputs and operation. Review and understand the
meaning and purpose of each configuration point before
changing it from the factory default value. Use the RTU
Open Start-up Sheet during configuration; fill in changed
values if changed from factory default. There are three
main configurations menus: SETPOINT, UNIT, and
SERVICE. Each configuration point is described below
under its according menu. See Appendix A for BACview
menu structure.
Setpoint
Occupied Heating Setpoint - The heating setpoint the
controller maintains during the occupied period.
Range = 40-90_FDefault = 70_F
Occupied Cooling Setpoint – The cooling setpoint the
controller maintains during the occupied period.
Range = 55-99_FDefault = 76_F
Unoccupied Heating Setpoint – The heating setpoint the
controller maintains during the unoccupied period.
Range = 40-90_FDefault = 55_F
Unoccupied Cooling Setpoint – The cooling setpoint the
controller maintains during the unoccupied period.
Range = 45-99_FDefault = 90_F
Effective Heating Setpoint – The current setpoint value
heating operation will control to.
Range = 0-120_F
Effective Cooling Setpoint – The current setpoint value
cooling operation will control to.
Range = 0-120_F
Optimal Start - The earliest time prior to occupancy, at
which the Optimal Start function may begin to adjust the
effective setpoints. Setting this to 0 will disable optimal
start.
Range = 0-4 hoursDefault = 4 hours
Occ Relative Humidity Setpoint – The space RH setpoint
the controller maintains during the occupied period.
Range = 0 to the Unocc RH setpoint
Default 60%
Unocc Relative Humidity Setpoint – The space RH
setpointthecontrollerwillmaintainduringthe
unoccupied period.
Range = 30-100%Default = 95%
DCV Max Ctrl Setpoint – The difference between indoor
and outdoor CO
ventilation damper position.
Range = 0-9999ppmDefault = 650ppm
Power Exhaust Setpoint – When the economizer damper
position opens above this point the power exhaust
operation will begin. When the damper position falls
below this point and 5% lower the power exhaust will
shutdown.
Range = 20-90%Default = 50%
NOTE:This point is only used when Continuous
Occupied Exhaust = NO
level which results in maximum
2
Unit
Fan Mode – Sets the operation of the indoor fan when not
in cooling or heating mode. Refer to fan operation for
details on each operation.
Range = Auto, Continuous, or Always On
Default = Continuous
Power Fail Restart Delay - Sets how long the controller
delays normal operation after the power is restored.
Typically used to prevent excessive demand when
recovering from a power failure
Range = 0-30 secDefault = 5 sec
Fan Off Delay – Time delay in which the fan will
continue run after being commanded off.
Range = 10-300secDefault = 90sec
Minimum Cooling SAT – The supply air temperature
must remain above this value to allow cooling with the
economizer and/or compressors. There is 5_Fplusand
minus deadband to this point. If the SAT falls below this
value during cooling a compressor stage will be removed
and/or the economizer will return to minimum position.
Range = 45-75_FDefault = 50_F
Maximum Heating SAT – The supply air temperature must
remain below this value to allow heating. There is 5_Fplus
and minus deadband to this point. If the SAT falls below this
value during heating the heat stages will begin to decrease
until the SAT has dropped below this value.
Range = 85-150_FDefault = 120_F
Vent Dmpr Pos / DCV Min Pos – Minimum damper
position for ventilation during the occupied period
Range = 0-100% openDefault = 20% open
14
DCV Max Vent Damper Pos – This is the greatest
position the economizer can open to while trying to
control the indoor air quality levels
Range = 0-75% openDefault = 50% open
S Fan Service Alarm Timer – The timer set for the Supply
Fan Runtime Alarm. After the number of hours set on this
point is exceeded the corresponding alarm will be generated,
and must be manually cleared in the maintenance menu after
the maintenance has been completed. The timer will then
begin counting its runtime again for the next due
maintenance.
Range = 0 to 9999 hrDefault = 600 hr
NOTE: If set to 0 hr this setpoint is disabled and its alarm
will never be generated.
Comp 1 Service Alarm Timer – The timer set for the
Compressor 1 Runtime Alarm. After the number of hours
set on this point is exceeded the corresponding alarm will
be generated, and must be manually cleared in the
maintenance menu after the maintenance has been
completed. The timer will then begin counting its runtime
again for the next due maintenance.
Range = 0 to 9999 hrDefault = 0 hr
NOTE:Default = 0 hours, if set = 0 hr this point is
disabled and its alarm will never be generated.
Comp 2 Service Alarm Timer – The timer set for the
Compressor 2 Runtime Alarm. After the number of hours
set on this point is exceeded the corresponding alarm will
be generated, and must be manually cleared in the
maintenance menu after the maintenance has been
completed. The timer will then begin counting its runtime
again for the next due maintenance.
Range = 0 to 9999 hrDefault = 0 hr
NOTE:Default = 0 hours, if set = 0 hr this point is
disabled and its alarm will never be generated.
Filter Service Alarm Timer – The timer set for the Dirty
Filter Alarm. After the number of hours set on this point is
exceeded the corresponding alarm will be generated, and
must be manually cleared in the maintenance menu after
the maintenance has been completed. The timer will then
begin counting its runtime again for the next due
maintenance.
Range = 0 to 9999 hrDefault = 600 hr
NOTE: Default = 600 hours, if set = 0 hr this point is
disabled and its alarm will never be generated.
Pushbutton Override – Set to enable or disable the pushbutton override function of the locally installed space sensor.
Range = Disable/EnableDefault = Enable
Setpoint Adjustment – Set to enable or disable the
setpoint adjustment function of the locally installed space
sensor.
Range = Disable/EnableDefault = Enable
Setpoint Adjustment Range - Sets the slider range of a
space sensor (with built in function). The slider is used to
offset the control setpoint.
Range = 0 to 5_FDefault = 5_F
Cooling Lockout Temperature -This defines the
minimum outdoor air temperature that cooling mode can
be enabled and run. If the OAT falls below this number
during cooling the compressors will be de-energized.
Range = 0-80_FDefault = 45_F
Economizer High OAT Lockout Temp – If the outdoor
air temperature rises above this value, economizer cooling
will be disabled and dampers will return and stay at
minimum position.
Range = 55-80_FDefault = 75_F
HP Rev Cycle Lockout Temp – If the outdoor air
temperature falls below this value, the compressors will
not be allowed to run for heating. Unit Type must be set to
Heat pump for this to be active.
Range = -20-30_FDefault = -3_
F
Heating Lockout Temperature – This defines the
maximum outdoor air temperature that heating mode can
be enabled and run. If the OAT rises above this number
during heating the heat stages will be de-energized.
Range = n/aDefault = 65_F
Pre- Occupancy Purge - Enables or disables the use of a
purge cycle immediately prior to the start of a scheduled
occupied period.
Range = Enable/DisableDefault = Disable
Purge Time - The maximum amount of time used for a
pre- occupancy purge.
Range = 0 to 240 minutes Default = 60 minutes
Unocc Free Cool Enable – Set to enable or disable the
economizer for night time free cooling (NTFC) operation.
Range = Disable/Enable Default = Disable
Setpoint Separation – Sets the minimum separation gap
in which setpoints can be set.
Range = 2-10_FDefault = 5_F
Occupancy Source – Tells the controller which method of
occupancy control to use in determining occupancy of the
rooftop. Refer to Occupancy in the operation section for
detail on each specific operation function.
Range = Always Occupied, BACnet Schedule,
BAS On/Off, or Remote Occ Input
Default =Always occupied
Inputs
Input 1 Function – This input is an analog input and can
be configured to be one of four different inputs: No
Sensor, IAQ Sensor, OAQ Sensor, or Space RH Sensor.
Input 1 is wired to pin J4- 4,5,6.
Default = No Sensor
Input 2 Function – This input is an analog input and can
be configured to be one of four different inputs: No
Sensor, IAQ Sensor, OAQ Sensor, or Space RH Sensor.
Input 2 is wired to pin J4- 1,2,3.
Software Default = No Sensor
Factory Default = IAQ Sensor with factory installed CO
sensor
NOTE:For Inputs 1 & 2, if using Bryant air quality
sensors do not use 24Vdc from RTU Open board. External
24Vdc power supply required.
Input 3 - This input is a discrete input and can be
configured to be one of six different functions: No
Function, Compressor Safety, Fan Status, Filter Status,
Remote Occupancy, or Door Contact. This input can also
be configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 3 is factory wired to
pin J1-2. Field accessories can be wired to its parallel pin
J5-5.
Factory Default = Compressor Safety and N/O
TS- 5580- 01
2
15
Input 5 - This input is a discrete input and can be
configured to be one of six different functions: No
Function, Fire Shutdown, Fan Status, Filter Status,
Remote Occupancy, or Door Contact. This input can also
be configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 5 is factory wired to
pin J1-10. Field accessories can be wired to its parallel pin
J5-3.
Software Default = Fire Shutdown and N/C
Factory Default = Fire Shutdown and N/O
Input 8 - This input is a discrete input and can be
configured to be one of six different functions: No
Function, Enthalpy Switch, Fan Status, Filter Status,
Remote Occupancy, or Door Contact. This input can also
be configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 8 is factory wired to
pin J2-6. Field accessories can be wired to its parallel pin
J5-1.
Software Default = Enthalpy Switch and N/O
Factory Default = No Function and N/O without
installed enthalpy sensor
TS- 5580- 01
Input 9 - This input is a discrete input and can be
configured to be one of six different functions: No
Function, Humidistat, Fan Status, Filter Status, Remote
Occupancy, or Door Contact. This input can also be
configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 9 is factory and field
wiredtopinJ5-7.
Factory Default = Humidistat and N/O
Space Sensor Type – This tells the controller what type
of space sensor is installed to run the unit. The three types
that can be used are: a standard 10k Type II thermistor
(T55), sensor with a setpoint offset slider bar (T56), or a
communicating sensor (SPT Sensor).
Range = T55, T56 (Use for T59), or SPT Sensor
Default = T55
T5x Override Duration – Sets the override time duration
the unit will change from unoccupied to occupied when
the override button is pushed on the space sensor.
Range = 0-24 hoursDefault = 1 hour
Service
Unit Type – This tells the control what type of unit it is
controlling. Heat/Cool refers to gas and electric heat units.
HP O/B Ctrl refers to a heat pump unit which requires
reversing valve control. HP Y1/W1 Ctrl refers to a heat
pump unit whose reversing valve is built in to the cooling
or heating call.
Factory Default = Heat/Cool for non-heat pump
units, or HP Y1/W1 Ctrl for heat pump units.
Compressor Stages – This refers to the number of
mechanical cooling stages available on a specific unit. Set
this point to “One Stage” if there is one compressor in the
specific unit, set to “Two Stage” if there are two
compressors in the unit, and set to “None” if economizer
cooling ONLY is desired.
Factory Default = “One Stage” for 1 compressor
units, or “Two Stages” for 2 compressor units
factory
Economizer Exists – This tells the controller if there is an
economizer installed on the unit.
Factory Default = NO if no economizer, or YES if
there is an economizer installed
Reversing Valve Output – Sets the heat pump’s (HP O/B
Ctrl type) reversing valve function. O output type refers to
a valve that is energized for cooling, and B output type
refers to a valve that is energized for heating. 548J and
549J heat pumps do not require O/B signals.
Default = O output type
Fan Control - The type of fan control used on the unit.
Range = Single Speed, Two Speed,
or Variable Speed
Default = Single Speed, or Two Speed for units
with the two speed fan option
Heat Type – Tells the controller which type of heat the unit
is capable of. Electric is any unit without gas and a Gas unit
is one which requires gas input for heating. 548J and 549J
heat pumps should be configured for Electric.
Factory Default = Electric for cooling only units
and heat pumps, or Gas for gas units.
Number of Heat Stages – Tells the controller how many
heat stages outputs are available for use. See configuration
in Appendix A for details on specific unit configuration.
Factory Default = 1 for single heat stage units,
2 for duel stage units, or 0 for cooling only units.
RH Controls - Enables dehumidification control if an RH
sensor is available and the unit has the Perfect Humidity
dehumidification option installed.
Range =Disable/Enable
Default = Disable
(Enabled with Perfect Humidity option)
Continuous Occupied Exhaust – This point tells the
controller when to run the power exhaust if equipped on
the unit.
If set to YES, the power exhaust will be on all the time
when in occupied mode and will be off when in
unoccupied mode. If set to NO the power exhaust will be
controlled by the Power Exhaust Setpoint.
Default = NO
DCV Control - Enables demand controlled ventilation
(DCV) if valid CO2 sensor value is available and the unit
has an economizer installed.
Range = Disable/Enable Default = Disable
Indoor CO
value when the board reads 4 mA at input 1 or 2.
CO
2
Sensor Value @ Min mA – Sets the indoor
2
Range = 0 to 9999 ppm Default = 0 ppm
Indoor CO
value when the board reads 20 mA at input 1 or 2.
CO
2
Sensor Value @ Max mA – Sets the indoor
2
Range = 0 to 9999 ppm Default = 2000 ppm
Outdoor CO
value when the board reads 4 mA at input 1 or 2.
CO
2
Sensor Value @ Min mA – Sets the outdoor
2
Range = 0 to 9999 ppmDefault = 0 ppm
Outdoor CO
value when the board reads 20 mA at input 1 or 2.
CO
2
Sensor Value @ Max mA – Sets the outdoor
2
Range = 0 to 9999 ppmDefault = 2000 ppm
NOTE: The indoor and outdoor min and max mA setting
are used to set the linear curve of mA vs. PPM.
16
Clockset
This submenu screen allows you to set the date and time
manually. The Daylight Savings Time (DST) can also be
changed here. The date and time is automatically set
whenever software is downloaded. The clock is a 24 hour
clock and not am/pm. The time should be verified (and
maybe changed) according to unit location and time zone.
Factory Default = Eastern Standard Time
USERPW
This submenu screen allows you to change the user
password to a four number password of choice. The User
password change screen is only accessible with the
Administrator Password (1111). The ADMIN password
will always override the user password.
Factory Default = 0000
Range = 0000-9999
OPERATION
The RTU Open will control the compressors, economizer
and heating outputs based on its space temperature input
and setpoints. It can also be controlled by a building
control system or zoning system. An optional CO
sensor mounted in the space can influence the economizer
minimum position. The RTU Open has a hardware clock
that can allow scheduling for stand-alone operation. The
RTU Open’s default is to control to occupied setpoints all
the time, until a type of occupancy control is set. The
following sections describe the operation for the functions
of the RTU Open.
Occupancy
Occupancyisthe fundamentaloverallcontrolof
equipment. The unit can be in one of two states: Occupied
or Unoccupied. These are usually referred to as periods
because they represent periods of any given day. Before
RTU Opencan operate specific functionsof the
equipment it is installed on,occupancy mustbe
determined. There are four different ways RTU Open can
determine occupancy. These are described below and
selected by the configuration point Occupancy Source.
Always Occupied (Default)
The unit will not determine occupancy and continuously
run in the occupied state or period. RTU Open ships from
the factory with this setting to allow immediate operation.
BACnet Schedule
When Occupancy Source is set to BACnet Schedule, RTU
Open will use a schedule to change occupancy based upon
a day of week and a time period. Local time and date
should be set in the RTU Open for this function to operate
properly. This function applies if setting a local schedule
in the RTU Open or an Open zoning system. An Open
network schedule can override a local schedule within the
unit. A space sensor push button override is only available
when running a local or Open schedule. The push button
will override an unoccupied period to occupied for the
specified time duration.
2
IAQ
BAS On/Off
When Occupancy Source is set to BAS On/Off, RTU
Open follows occupancy based on an On/Off command to
the BAS ON/OFF software point. An on command sets
the occupancy to occupied, and an off command sets it to
unoccupied. The Building Automation System can be
speaking BACnet, Modbus, N2, or LON and is writing to
the BAS On/Off point in the open protocol point map.
Remote Occ Input
When Occupancy Source is set to Remote Occ Input, RTU
Open follows occupancy based on the remote occupancy
switch input. Inputs 3, 5, 8, and 9 on plug J5 can be
hard-wired to command the unit’s occupancy. The
Occupancy Contact point show the status as on or off, on
is occupied and off is unoccupied.
Indoor (Supply) Fan
The indoor fan can be configured to operate in three
different manors. The configuration point Fan Mode
determines how the fan will run. The fan will always be
disabled if a fire shutdown or safety chain alarm is active.
A valid space temperature and supply air temperature
must be available for the fan to operate. There is a unit
start delay in effect when the unit is transitioning from
unoccupied to occupied. The following describes specific
fan operation based on the Fan Mode configuration value.
Auto
When Fan Mode is set to Auto, RTU Open will cycle the
fan on and off based on the demand for heating, cooling,
and dehumidification. There is a configurable fan off
delay that is upheld before shutting the fan off after
conditioning has ended.
Continuous
When Fan Mode is set to Continuous, RTU Open will
cycle the fan based on occupancy. The fan will run the
whole occupied period and operate in the auto mode
during the unoccupied period.
Always On
When Fan Mode is set to Always On, RTU Open will run
the fan all the time regardless of occupancy or demand.
The RTU Open has an optional Supply Fan Status input to
provide proof of airflow. If this is enabled, the point will
look for a contact change whenever the Supply Fan Relay
is on. If it is not enabled then it will always be the same
state as the Supply Fan Relay. The cooling, economizer,
heating,dehumidification, CO
routines will use this input point for fan status.
and powerexhaust
2
Cooling
The compressor outputs are controlled by the Cooling
Control PID Loop and Cooling Stages Capacity
algorithm. They will be used to calculate the desired
number of stages needed to satisfy the space by
comparing theSpace Temperature (SPT) to the
Occupied Cool Setpoint plus the T56 slider offset when
occupied and the Unoccupied Cool Setpoint (UCSP)
plus theT56 slideroffset, ifunoccupied. The
economizer, if available, will be used for cooling in
addition to the compressors. The following conditions
must be true in order for this algorithm to run:
S Indoor Fan has been ON for at least 30 seconds.
TS- 5580- 01
17
S Heat mode is not active and the time guard between
modes equals zero.
S If occupied and the SPT > (occupied cool setpoint plus
the T56 slider offset).
S Space Temperature and supply air temperature values
are available.
S If it is unoccupied and the SPT > (unoccupied cool
setpoint plus the T56 slider offset). The indoor fan will
be turned on by the staging algorithm.
S If economizer is available and active and economizer
open > 85% and SAT > (SAT low limit + 5_F) and SPT
> effective set point + 0.5_F.
OR
Economizer is available, but not active
OR
Economizer is not available
S OAT > DX Lockout temperature
If all of the above conditions are met, the controller uses a
TS- 5580- 01
PID logic loop to energize or de- energize compressors to
satisfy the cooling demand.
There is a fixed 3- minute minimum on time and a
5- minute off time for each compressor output and a
3- minute minimum time delay between staging up or
down.
Any time the compressors are running the RTU Open will
stage down the compressors if the SAT becomes less than
the cooling low supply air setpoint. After a compressor is
staged off, it may be started again after a normal
time- guard period and the supply air temperature has
increased above the low supply air setpoint.
Supply Fan
The RTU Open supply fan may be configured for 1 of 3
Fan Control modes:
S Single - The fan operates at one speed only and
provides on/off operation
S Two Speed - The fan operates at 1 of 2 speeds depending
on the mode of operation and load conditions. During fan
only or single stage cooling, the fan operates at low speed.
During heating, dehumidification, second stage cooling, or
if maximum economizer operation is required, the fan
operates at high speed.
S Variable Speed - The fan operates at a variable speed
to meet the load conditions and SAT safety
requirements to provide maximum energy savings by
minimizing fan horsepower consumption. Fan speed is
NOT controlled by static pressure.
The RTU Open supply fan may be configured for 1 of 3
Fan Modes:
S Auto - The fan cycles on/off in conjunction with
heating or cooling.
S Continuous - The fan runs continuously during
occupancy and intermittently during unoccupied
periods with heating and cooling.
S Always On - The fan runs continuously regardless of
occupancy or calls for heating and cooling.
Occupancy can be determined by BACnet schedules, BAS
schedules, or in response to a remote occupancy switch.
A Fan Off Delay allows the supply fan to continue
operating after heating or cooling stops.
If the following alarms are active, the fan turns off
immediately, regardless of the occupancy state or demand:
S Fire Shutdown
S Safety chain
S SAT alarm
S SPT alarms
The RTU Open does not include smoke-control functions
suchasasmoke- purge,zone- pressurization,or
smoke-ventilation. Each of these modes require a
field-designed circuit to operate the following by local
fine codes:
S RTU supply fan
S RTU economizer
S RTU power exhaust
The RTU Open many be configured to accept a Supply
Fan Status input to provide proof the supply fan is
operating. When enabled, a loss or lack of fan status will
stop heating and cooling operation.
A supply Fan Alarm Service Timer function is available to
track the number of supply fan run hours and generate an
alarm when the accumulated runtime exceeds the set
threshold.
Economizer
The Economizer dampers are used to provide free cooling
and Indoor Air Quality, if optional CO
when the outside conditions are suitable.
The following conditions must be true for economizer
operation:
S Indoor Fan has been on for at least 30 seconds.
S Enthalpy is Low if the Enthalpy input is enabled.
S SAT reading is available.
S OAT reading is available.
S SPT reading is available.
S OAT <= High OAT economizer lockout configuration
(default = 75).
S OAT <= SPT
If the RTU Open is configured for VFD or 2- speed fan,
and the fan is on high speed or is configured for
single- speed fan, and any of the preceding conditions are
not true, the economizer will be set to the Vent Dmpr
Pos/DCV Min Pos setpoint. If it is configured for VFD or
2- speed fan, and the fan is on low speed, and any of the
preceding conditions are not true, the economizer will be
set to the Low Fan Econ Min Pos.
If any of the mentioned conditions are not true, the
economizer will be set to its configured minimum position.
The minimum damper position can be overridden by the
IAQ routine described later in this section.
If the above conditions are true, the Economizer control
will calculate a damper position starting with a minimum
vent position and based on current space temperature and
sensor is installed,
2
18
a setpoint that is halfway between the effective cool and
heat setpoints. If the SAT drops below the cooling low
supply air setpoint (+ 5_F), the economizer will ramp
down to minimum position.
Power Exhaust
RTU Open may enable and disable an exhaust fan based
on either the controller’s occupancy or its economizer
damper position. If configured for continuous occupied
operation, it will be energized whenever the controller is
in the occupied mode and disabled when in the
unoccupied mode. If configured for damper position
control, it will be energized whenever the economizer
exceeds the power exhaust setpoint and disabled when the
economizer drops below the setpoint by a fixed hysteresis
of 10%. If the Fan Control is set to Two Speed or Variable
Speed, the Power Exhaust Setpoint is automatically
adjusted based on the fan’s air delivery. The Calculated
PE Setpoint used for control is displayed in the
Maintenance section.
Pre-Occupancy Purge
Pre- Occupancy Purge allow the rooftop equipment with
an economizer damper to utilize outdoor air to purge the
space of contaminates just prior to the beginning of the of
the occupied period.
The following conditions must be true for pre- occupancy
purge to operate:
S Pre- Occupancy Purge set to Enable
S Economizer Exists set to Yes
S A local time schedule is configured
S The local time schedule is currently unoccupied and the
remaining them is less than the configured Purge Time
When the RTU Open schedule is unoccupied and the
remaining unoccupied time is less than the purge time, the
supply fan starts. The economizer damper opens to the
configured Economizer Purge Min Pos. The RTU Open
continues to operate in this mode until the occupied start
time is reached. The Pre-Occ Purge state is displayed in
the Maintenance section.
Heating
The heat outputs are controlled by the Heating Control
PID Loop and Heating Stages Capacity algorithm. They
will be used to calculate the desired number of stages
needed to satisfy the space by comparing the SPT to the
Occupied Heat Setpoint the T56 slider offset when
occupied and the Unoccupied Heat Setpoint plus the T56
slider offset if unoccupied. The following conditions must
be true in order for this algorithm to run:
S Indoor Fan has been ON for at least 30 seconds.
S Cool mode is not active and the time guard between
modes equals zero.
S If occupied and SPT <(occupied heat setpoint plus T56
slider offset)
S SPT and supply air temperature values are available
S If it is unoccupied and the SPT < (unoccupied heat
setpoint plus T56 slider offset). The indoor fan will be
turned on by the staging algorithm.
S OAT < High OAT lockout temperature.
If all of the above conditions are met, the controller uses a
PID logic loop to energize or de- energize heat outputs to
satisfy the heat demand. If the SAT begins to exceed the
high supply air setpoint, a ramping function will cause the
Heat Stages Capacity algorithm to decrease the number of
stages until the SAT has dropped below the setpoint.
There is a fixed one minute minimum on time and a one
minute off time for each heat output. Heat staging has a 2
minute stage up and 30 second stage down delay.
Heat pump operation is the same as above except for what
is explained below. There is a fixed 3 minute on and 5
minute off time for the first heat stage output, and a one
minute on and one minute off time for the second heat
stage output. There is a 10 minute minimum stage up
delay if the heat demand is <= 3_F, and a 2 minute
minimum stage up delay if heat demand is > 3_F. T he
stage down delay is still 30 seconds. If the Compressor
Safety Alarm is active, the second heat stage will come on
with the first stage with no delay.
Indoor Air Quality
If the optional indoor air quality sensor is installed, the
RTU Open will maintain indoor air quality within the
space at the user configured differential set point. The set
point is the difference between the indoor air quality and
an optional outdoor air quality sensor. If the outdoor air
quality is not present then a fixed value of 400ppm is
used. The following conditions must be true in order for
this algorithm to run:
S The mode is occupied.
S Indoor Fan has been ON for at least 30 seconds.
S Indoor Air Quality sensor has a valid reading.
As air quality within the space changes, the minimum
position of the economizer damper will be changed thus
allowing more or less outdoor air into the space depending
on the relationship of the indoor air quality to the
differential setpoint. If all the above conditions are true,
the IAQ algorithm will run and calculates an IAQ
minimum position value using a PID loop. The IAQ
minimum damper position is then compared against the
user configured economizer minimum position and the
greatest value becomes the final minimum damper
position of the economizer output.
If the calculated IAQ minimum position is greater than
the DCV Max Vent Damper Pos configuration, then it will
be clamped to the configured value.
Dehumidification
The RTU Open will provide occupied and unoccupied
dehumidification only on units that are equipped with the
Perfect Humidityt option from the factory. This function
requires a space relative humidity sensor or a humidistat for
control. The space relative humidity senor can be installed
and configured as one of the two analog input channels
(inputs 1 or 2 on J4), or a humidistat can be installed and
configured as switch input 9 on J5. When using a relative
humidity sensor to control dehumidification, occupied or
unoccupied dehumidification setpoints are use accordingly.
When using a humidistat, setpoints are not used and the
dehumidification call comes when the humidistat indicates
high humidity.
TS- 5580- 01
19
When the indoor relative humidity becomes greater then
the dehumidification setpoint (or switches from low to
high), a dehumidification demand will acknowledged.
Compressor state is monitored and time guards are
honored. If a compressor was just turned off prior to the
dehum call the dehumidification output will be delayed
the 5 minute minimum off time of the compressor. When
ok to dehumidify, the dehumidification output (J11- 7, 8)
will be energized. This will bring on the supply fan (at
high fan speed if Fan Control is set to “Two Speed”), all
compressors, and the dehumidification relay placing the
unit in Hot Gas Reheat dehumidification mode. If
dehumidification is called for during cooling or cooling is
called for during dehumidification, the unit will run in
Subcoolingdehumidificationmode.Individualunit
circuits can be in different dehumidification modes based
on the demand. Refer to the base units operation for
additional information.
NOTE: There is a fixed 5% hysteresis that the indoor
relative humidity must drop below the active setpoint to
end the dehumidification mode and de-energize the
TS- 5580- 01
dehumidification output. The output will also de- energize
if the fan relay is de-energized.
Demand Limit
If the RTU Open receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will outwardly
expand theheating and cooling setpointsby the
configured demand limit setpoint value and remain in
effect until the BACnet demand limit variable receives a 0
value.
Unoccupied Free Cooling
When the unit is equipped with an economizer, the control
can run a night time free cooling (NTFC) mode called
Unocc Free Cooling. In this mode the damper is utilized
to bring in outdoor air for free cooling during unoccupied
periods. The following conditions must be true for
unoccupied free cooling to operate:
S Unocc Free Cool Enable set to Enable
S The system is unoccupied
S The outside air temperature is below the Economizer
High OAT Lockout Temp
S The outside air temperature is less than the space
temperature
S Enthalpy (if enabled) is Low
When the RTU Open schedule is unoccupied and the
space temperature rises at least 1 degree above the
Occupied Cooling Setpoint, the supply fan starts. The
economizer damper opens as necessary to cool the space.
The RTU Open continues to operate in this mode until the
space is satisfied or the outside air conditions are no
longer suitable for free cooling.
Optimal Start
The RTU Open may utilize Optimal Start, which adjusts
the effective setpoints to achieve the occupied setpoints
by the time scheduled occupancy begins. The Optimal
Start recovery period may begin as early as 4 hours prior
to occupancy. The algorithm works by moving the
unoccupied setpoints toward the occupied setpoints. The
rate at which the setpoints move is based on the outside
air temperature, design temperatures, and capacities. The
following conditions must be true for unoccupied free
cooling to operate:
S Under SETPOINT, Optimal Start Value must be set
greater than zero and less than or equal to four (0
disables Optimal Start.)
S The system is unoccupied
S The RTU Open has a valid outside air temperature
S The RTU Open is running occupancy based on a
schedule, were next time occupied is known.
Fire Shutdown
Fire Shutdown may be configured on Binary Input 5. A
typical application involves a smoke detector or fire
shutdown contact, which, when active, immediately shuts
down equipment operation.
Compressor Safety
Compressor Safety may be configured on Binary Input 3.
A compressor safety tripped indicator circuit is available
on most Bryant rooftop equipment. A Compressor Safety
Alarm indicates that the equipment requires attention.
Cooling, heating,and supply fan outputs are not
interrupted except where the RTU Open is configured for
Heat Pump operation. When configured for Heat Pump,
and in the heating mode, a compressor safety fault will
cause the available stages of electric heating to be enabled
in place of mechanical heating. Normal operation resumes
when the compressor safety circuit is de-energized.
Fan Status
Fan Status may be configured on any unused binary input
channel. A typical application would be an airflow switch,
current sensing relay, or other device that provides a
supply fan running verification. Enabling this function
displays the supply fan’s status on the equipment graphic.
If the controller loses fan status during operation, heating
and cooling are disabled, the economizer damper (if
available) is closed, and an alarm for loss of status is
indicated. If the fan status is on when the controller is
commanding the fan off, the unit remains in the off state.
An alarm is generated indicating that the fan is running
when it should be off.
Filter Status
Filter status may be configured on any unused binary input
channel. A typical application is a differential pressure
switch that senses the pressure drop across a filter bank.
When the pressure across the filter bank exceeds the setpoint
of the differential pressure switch, the Filter status is
displayed as Dirty on the controller graphic. An alarm
indicates a dirty filter.
Door Switch
A Door Contact may be configured on any unused binary
input. A typical application is an occupancy sensor mounted
within the space served by a single zone rooftop. Door
Contact disables mechanical cooling and electric or gas
heating, when active. Economizer cooling, if available,
continues to operate.
20
TROUBLESHOOTING
General
The RTU Open controller acts as an intelligent imbedded
thermostat to the rooftop unit, but can be monitored and
controlled from a 3rd party network. This causes the
system as a whole to be troubleshot from three points of
view. The three parts to the system are the rooftop unit,
theOpencontroller, andthenetworkconnected.
Determining which part needs to be troubleshot is the first
step.
The Open controller can be used to troubleshoot the
rooftop unit and/or itself with service test, communicating
LED’s, and built in alarms. Disconnecting the RTU Open
from the network may also help troubleshooting the
controller androoftopunit. ThirdPartyNetwork
troubleshooting may also be required. For base unit
troubleshooting, refer to specific base unit Service
Maintenance manual.
There is an on- board battery that is used for RAM and
clock back- up. It is a 3- volt lithium battery (CR2032).
The average life is 7 years with a minimum of 10,000
hours of back- up. When the RTU Open board is powered
up, the battery is not being used. If power is lost, the
battery backs up the time clock. Battery replacement
should be done with the board powered up.
Thermistor Troubleshooting
RTU Open uses thermistors to sense temperatures for
control operation of the unit. Resistances at various
temperatures are listed in Table 2. Thermistor pin
connections are shown in Table 1. Thermistors are used
for supply air temperature (SAT), outdoor air temperature
(OAT), and space temperature (SPT) and all must be a 10
kilo-ohm type II sensor.
Tocheckaccuracy,useahighqualitydigital
volt-ohmmeter. Connect the meter to the thermistor leads
to obtain a resistance value. Use Table 2 to convert that
resistance to a temperature. Next step is to measure
temperatureatprobelocationwithanaccurate
thermocouple-typetemperature-measuringinstrument.
Temperature measured by thermocouple and temperature
determined from thermistor voltage reading should be
close, within 5_F if care was taken in applying
thermocouple and taking readings. If a sensor must be
corrected, use the RTU Open’s calibration function to
offset the temperature reading.
Table 2 – Thermistor Resistance vs Temperature Values
for Space Temperature Sensor, Supply Air Temperature
During Start-up and throughout the life of the equipment,
it may be necessary to obtain the RTU Open’s software
version. To do this a Modstat must be run on the
controller. This can be done from the BACview user
interface by holding the function (FN) key and pressing
the period (.) key. An example of the beginning lines of a
Modstat is shown in Fig. 16. The application software
version shows the current running software of the board.
In this case the rtu_open-20100409 refers to RTU Open
software version 20100409. This 8 digit number refers to
a date (YYYYMMDD). The first 4 digits are the year
(2010) and the month and day (0409), so this version is
th
April 9
2010.
TS- 5580- 01
21
TS- 5580- 01
C10825
Fig. 16 - Example Modstat
22
Communication LED’s
The LED’s indicate if the controller is speaking to the
devices on the network. The LED’s should reflect
communication traffic based on the baud rate set. The
higher the baud rate the more solid the LED’s will appear.
Table 3 – LED’s
The LED’s on the RTU Open show the status of certain functions
If this LED is on...Status is...
PowerThe RTU Open has power
RxThe RTU Open is receiving data from the network segment
TxThe RTU Open is transmitting data over the network segment
DO#The digital output is active
The Run and Error LED’s indicate control module and network status
If Run LED shows...And Error LED shows...Status is...
2 flashes per secondOffNormal
2 flashes per second2 flashes, alternating with Run LEDFive minute auto - restart delay after system error
2 flashes per second3flashes,thenoffControl module has just been formatted
2 flashes per second4 flashes, then pauseTwo or more devices on this network have the same
2 flashes per secondOnExec halted after frequent system errors or control pro-
5 flashes per secondOnExec start- up aborted, Boot is running
5 flashes per secondOffFirmware transfer in progress, Boot is running
7 flashes per second7 flashes per second, alternating with
Run LED
14 flashes per second14 flashes per second, alternating with
Alarms are provided to indicate a possible problem with
the controller or unit. Alarms can be checked through a
network and/or the local access device. All alarms are
listed in Table 4 with name, object name, action taken by
control, reset method, and possible cause. Some alarms
can occur based on specific configurations.
Safety Chain Alarm
This alarm occurs immediately if the supply-fan internal
overload trips or if an electric-heat limit switch trips. The
Unit Status will be Shutdown and the System Mode will
be Disable. All unit operations stop immediately and will
not restart until the alarm automatically clears. There are
no configurations for this alarm; it is all based on internal
wiring. This alarm will not occur if Fire Shutdown Alarm
is active. Normal operation resumes when the safety chain
circuit is complete.
Fire/Smoke Shutdown Alarm
This alarm occurs immediately when the smoke detector
senses smoke. The Unit Status will be Shutdown and the
System Mode will be Disable. All unit operations stop
immediately and willnot restart until the alarm
automatically clears. If there is not a smoke detector
installed or the smoke detector did not trip, check input
configurations. NOTE: The default function for input 5 is
a normally open Fire Shutdown input.
Supply Fan Failure
This alarm occurs when the indoor fan is being command
on and the fan status switch feedback is showing the fan
off. This will end current operating mode and disable unit
operation. This alarm requires a fan status switch to be
configured on one of the inputs.
Supply Fan in Hand
This alarm occurs when the indoor fan is being
commanded off and the fan status switch feedback is
showing the fan is on. This will prevent any operating
mode and disable unit operation. This alarm requires a fan
status switch to be configured on one of the inputs.
Compressor Safety
This alarm indicates the base unit’s compressor safety
circuit is energized. Cooling, heating, and supply fan
outputs are not interrupted except when the RTU Open is
configured for Heat Pump. Normal operation resumes
when the compressor safety circuit is de-energized. If the
Heat Pump is in the heating mode, it will automatically
replace the compressor stage(s) with the equivalent
number of auxiliary heat stages, as available.
For Heat Pump’s with O/B, when configured for two
stages of aux heat and two compressors, Compressor 1 is
replaced by Aux Heat Stage 1 and Compressor 2 is
replaced by Aux Heat Stage 2. The compressor output
stays on when the safety alarm is present. For cooling, the
alarm indicates the compressors are down.
Space Temp Sensor
This alarm occurs if the space sensor wired to the RTU
Open is disconnected or shorted for more than 10 seconds.
When this occurs the Unit Status will be Shutdown and
the System Mode will be Run. Sensor, sensor connections,
wiring, board connection, and configurations should be
checkedforfaultsorerrors.Alarmwillreset
automatically when cause is fixed.
Supply Air Temp Sensor
This alarm occurs immediately when the supply air
temperaturesensorwiredtotheRTUOpenis
disconnected or shorted. When this occurs the Unit Status
will be Shutdown and the System Mode will be Run.
Sensor, sensor connections, wiring, board connection, and
configurations should be checked for faults or errors.
Alarm will reset automatically when cause is fixed.
Outdoor Air Temp Sensor Alarm
This alarm indicates a shorted or open circuit in the OAT
input. Cooling, heating, andsupply fan operation
continues. OAT lockouts will not operate while the sensor
is in alarm. Economizer cooling and optimal start
functions are disabled. Normal operation resumes when
the controller detects a valid sensor.
Space Relative Humidity Sensor
This alarm indicates the mA input at the associated
channel falls below 3.5 mA or rises above 21 mA.
Cooling, heating, and supply fan operation continues,
however, the controller’s Perfect Humidityt binary
output is disabled until the fault condition is corrected.
IAQ Sensor
This alarm indicates the mA input at the associated
channel falls below 3.5 mA or rises above 21 mA.
Cooling, heating, and supply fan operation continues.
However, the controller’s IAQ control function is disabled
until the fault condition is corrected.
OAQ Sensor
This alarm indicates the mA input at the associated
channel falls below 3.5 mA or rises above 21 mA.
Cooling, heating, and supply fan operation continues.
However, the controller’s IAQ control function uses
400ppm as the fixed outdoor air CO2 level until the fault
condition is corrected.
Space Temperature
When Occupied, a Low Space Temperature alarm is
generated if the space temperature falls below the lower
limit or a High Space Temperature alarm is generated if
the space temperature rises above the upper limit.
When Unoccupied, an unoccupied low space temperature
alarm is generated when the space temperature falls below
the alarm configuration Unoccupied Low SPT Alarm
Limit or an unoccupied high space temperature alarm is
generated when the space temperature rises above the
alarm configuration Unoccupied High SPT Alarm Limit.
TS- 5580- 01
25
The following values are related to the Space Temperature
alarm:
Alarming Temperature – This variable displays the
value of the space temperature that is in alarm and is only
visible when the space temperature is in an alarm state.
Alarm Limit Exceeded – This variable displays the value
of the alarm setpoint that is exceeded by the alarming
space temperature and is only visible when the space
temperature is in an alarm state.
High Supply Air Temperature
This alarm indicates the supply air temperature exceeds
the alarm configuration High SAT Alarm Limit for 5
minutes. This alarm is inhibited until the RTU has been
running for 30 minutes to allow for system stabilization
after startup.
Low Supply Air Temperature
This alarm indicates the supply air temperature falls
below the alarm configuration Low SAT Alarm Limit for
5 minutes. This alarm is inhibited until the RTU has been
running for 30 minutes to allow for system stabilization
TS- 5580- 01
after startup.
Setpoint Slider
This alarm indicates an open circuit is detected at the
setpoint adjustment input. This can only occur if the
Space Sensor Type is set to T56. Note that only an open
circuit results in an alarm. A short across this input offsets
the setpoints negatively by the amount configured by
configuration Setpoint Adjustment Range.
Switch Configuration
This occurs if more than one binary input (inputs 3, 5, 8,
and 9) is configured for the same function. When this
happens the two inputs (or more) configured wrong will
be disabled as an inputs. This alarm will automatically be
cleared when configuration is corrected.
An example of this would be: Input 3 = Compressor
Safety, input 5 = Fan Status, input 8 = Fan Status, and
input 9 = Humidistat; the alarm would be active, unit
would run, compressor safety and humidistat would
function normally, and Fan Status (inputs 5 & 8) will be
interpreted as “No Function.”
Analog Input Configuration
This occurs if more than one analog input (inputs 1 & 2)
is configured for the same sensor. When this happens the
two inputs will be disabled as inputs. This alarm will
automatically be cleared when configuration is corrected.
An example of this would be: Input 1 = IAQ Sensor, input
2 = IAQ Sensor; the alarm would be active, unit would
run, but the IAQ Sensor (inputs 1 & 2) will be interpreted
as “No Function.”
High Space Relative Humidity
This alarm indicates the space humidity exceeds the alarm
configuration High Space Humidity Alarm Limit for 10
minutes. This alarm is inhibited until the RTU runs for 15
minutes to allow for system stabilization after startup.
Low Space Relative Humidity
This alarm indicates the space humidity falls below the
alarm configuration Low Space Humidity Alarm Limit for
5 minutes. This alarm is inhibited until the RTU runs for 5
minutes to allow for system stabilization after startup.
High CO
This alarm indicates the space CO2level exceeds the
alarm configuration Occupied High CO
1-minute. This alarm will be inhibited until the RTU has
been runningfor 2-minutesto allowfor system
stabilization after startup.
2
Alarm Limit for
2
Supply Fan Runtime
This alarm indicates the accumulated runtime exceeds the
unit configuration Supply Fan Service Alarm Timer value
(when not set to 0). This alarm is most commonly used to
indicate an equipment maintenance interval is due. The
supply fan runtime accumulator may be reset by setting
the maintenance point Reset Supply Fan Runtime Alarm
to Clear, and then back to Run – acknowledging each
selection by clicking the OK button when it appears.
Setting unit configuration Supply Fan Service Timer value
to 0 disables the supply fan runtime alarm function.
Compressor 1 Runtime
This alarm indicates the accumulated runtime exceeds the
unit configuration Compressor 1 Service Alarm Timer
value (when not set to 0). This alarm is most commonly
used to indicate an equipment maintenance interval is due.
The Compressor 1 Runtime accumulator may be reset by
setting the maintenance point Reset Comp 1 Runtime
Alarm to Clear, and then back to Run – acknowledging
each selection by clicking the OK button when it appears.
Setting unit configuration Compressor 1 Service Timer
value to 0 disables the Compressor 1 Runtime alarm
function.
Compressor 2 Runtime
This alarm indicates the accumulated runtime exceeds the
unit configuration Compressor 2 Service Alarm Timer
value (when not set to 0). This alarm is most commonly
used to indicate an equipment maintenance interval is due.
The Compressor 2 runtime accumulator may be reset by
setting the maintenance point Reset Comp 2 Runtime
Alarm to Clear, and then back to Run – acknowledging
each selection by clicking the OK button when it appears.
Setting unit configuration Compressor 2 Service Timer
value to 0 disables the Compressor 2 runtime alarm
function. Note that this function is unavailable if the
service configuration Compressor Stages value is not set
to Two Stages.
Filter
This alarm indicates the accumulated runtime exceeds the
unit configuration Filter Service Alarm Timer value
(when not set to 0). This alarm is most commonly used to
indicate a filter replacement is due. Reset the filter service
runtime accumulator by setting the maintenance point
Reset Filter Runtime Alarm to On, back to Off, and
clicking the OK button after each setting. Setting unit
configuration Filter Service Alarm Timer value to 0
disables the filter service alarm function.
26
Third Party Networking
Third party communication and networking troubleshooting
should be done by or with assistance from the front end 3rd
party technician. A Module Status Report (Modstat) can be
run from the BACview
6
or Virtual BACview (see Table 5 to
perform). This lists information about the board status and
networking state. For basic troubleshooting, see Table 6.
For further information about third party networking contact
Bryant applications engineering.
Table 5 – Manufacture Date
When troubleshooting, you may need to know a control module’s manufacture date.
Obtain the manufacture date from a...Notes
Module status report (modstat)To obtain a modstat with BACview6:
Sticker on the control board
“Serial No: ORTYMxxxxN”
(Bar Coded & Typed Number)
1. Press Function (FN) key and hold.
2. Then press period (.)
3. Release both buttons.
ThereportshowsthedateunderMain board hardware.
The serial numbers are unique and contain embedded information:
“ORT”-These first three digits are unique to RTU Open and are used as an identifier.
“YM”-These two digits identify the last digit of the year and month (in hex, A=10/Oct)
of manufacture. “74” would represent a date of manufacture of “April 2007”.
“xxxx”-These four digits represent the sequential number of units produced for a given
product for the mentioned manufacturing time period.
“N”-This final digit represents the decade and toggles between “N” and “M” every
ten years.
Table 6 – Basic Protocol Troubleshooting
ProblemPossible causeCorrective action
No communication with 3rd
party vendor
Incorrect settings on SW1, SW2 and SW3Verify and correct switch settings. Cycle
RS485 Port has no voltage output
(check with RTU Open disconnected from RS485
communication bus):
• Bacnet @ 9600/19.2K - .01 to .045vdc
• Bacnet @ 38.4K - .06 to .09vdc
• Bacnet @ 76.8K - .1vdc
• Modbus @ 9600 - 76.8K - .124vdc
• N2 @ 9600 - .124vdc
Verify devices are daisy chained and repeaters and bias
terminators are correctly installed.
powertoRTUOpenafterchangingswitch
settings.
Verify RTU Open has correct power
supply.
Possible bad driver on board.
Check RS485 bus for external voltage
before reconnecting to the bus.
Check 3rd party vendor RS485
communication wiring guidelines and
troubleshooting procedures.
TS- 5580- 01
27
APPENDIX A - USER INTERFACE MENUS
Field Assistant Navigation
Properties
Equipment
Status
Configuration
Unit Configuration
Setpoints
Alarm Configuration
Service Configuration
Maintenance
TS- 5580- 01
Alarms
BACview Navigation
NOTE: The Tables in Appendix A describe parameters of each of the menu levels shown below.
STANDBY
HOME
SYSTEM
SETTINGS
BACnet
Login
Modstat screen only reached by (FN + .)
Keypad
UserPw
Network
ClockSet
DST
TimeMstr
Clockset
SETPOINT
Sched
Weekly schedule
Exceptions
ALARMS
UNIT
SETPOINT
CALIBRATE
INPUT
SETPOINT
Sched
SERVICE
TEST
C12770
ALARMMAINTSTATUSCONFIG
Alarm
C12771
28
APPENDIX A - USER INTERFACE MENUS (CON’T)
System Settings Menu
BACview MenuPOINT NAMEBACnet ObjectRANGEDEFAULTField Assistant Menu
STANDBYRTU Open
System Moderun_status1=Off
Space Temperaturespa ce_te mpxxx ° F
Press any key to a ctivate
LOGIN/ LOGOUTAd min or User Password****User: 0000 Admin: 1111