Bryant 549B Series Installation, Start-up And Service Instructions Manual

installation, start-up and service instructions
SINGLE PACKAGE ROOFTOP HIGH-EFFICIENCY HEAT PUMP UNITS
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation in­structions before installing this unit (Fig. 1).
2. Be sure the installation conforms to all applicable local and national codes.
3. These instructionscontainimportant information for the proper maintenance and repair of this equipment. Retain these instructions for future use.
549B
Sizes 090,120
71⁄2and 10 Tons
Cancels: New II 549B-90-1
7/15/95
Page
SAFETY CONSIDERATIONS ........................1
INSTALLATION .................................1-16
I. Locate the Unit .............................3
II. Unit Duct Connections ......................3
III. Rig and Place Unit ..........................3
IV. Field Connections ..........................6
PRE-START-UP ................................16,17
START-UP ....................................17-24
I. Compressor Rotation .......................17
II. Heating Section Start-Up and Adjustments
For Units With Accessory Electric Heat .......17
III. Cooling Section Start-Up and Adjustments ....18
IV. Indoor Airflow and Airflow Adjustments .......19
CARE AND MAINTENANCE .......................25
I. Air Filter ..................................25
SERVICE .....................................25-27
I. Cleaning .................................25
II. Lubrication ...............................26
III. Outdoor-Fan Adjustment ....................26
IV. Economizer Adjustment ....................26
V. Refrigerant Charge .........................26
VI. Replacement Parts .........................27
TROUBLESHOOTING ...........................28-30
START-UP CHECKLIST ..........................CL-1
Fig.1—Typical Unit
WARNING:
nance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
1. The power supply (volts, hertz, and phase) must corre­spond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be suf­ficient to handle unit load.
3. Refer to Locate the Unit section on page 3 and Fig. 2 for locations of electrical inlets, condensate drain, duct con­nections, and required clearances before setting unit in place.
4. This installation must conform with local building codes and with NEC (National Electrical Code) or NFPA (National Fire Protection Association) 54 TIA-54-1. Refer to provincial and local plumbing or wastewater codes and other applicable local codes.
5. Approved for outdoor installation on wood flooring or on class A, B, or C roof covering materials.
Before performing service or mainte-
SAFETY CONSIDERATIONS
Recognize safety information. This is the safety-alert symbol ( ). When you see this symbol on the unit and in instruc­tions or manuals, be alert to the potential for personal injury.
Understand the signal words — DANGER, WARNING, and CAUTION. These words are used with the safety-alert sym­bol. Danger identifies the most serious hazards which will result in severe personal injury or death. Warning indicates a situation that could result in personal injury. Caution is used to identify unsafe practices which would result in minor personal injury or product and property damage.
INSTALLATION
Unit is shipped in the vertical airflow configuration (see Fig. 1). To convert to horizontal discharge, remove side duct opening covers. Using the same screws, install covers with insulation-side down (facing outside) on the unit over verti­cal duct openings. Seals around duct openings must be tight.
All units can be connected into existing duct systems that are
properly sized and designed to handle an airflow of 300 to 500 cfm per each 12,000 Btuh of rated cooling capacity.
UNIT 549B
STANDARD
UNIT
WEIGHT
CORNER
WEIGHT
(A)
CORNER
WEIGHT
(B)
CORNER
WEIGHT
(C)
CORNER
WEIGHT
(D)
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm
090 870 395 195 90 183 83 237 108 252 114 28-0 120 1000 454 231 105 214 97 269 122 286 130 28-10
NOTES:
CONNECTION SIZES
3
A 1 B 2 C 1 D E
⁄89 Dia. [35] Field Power Supply Hole
1
⁄29 Dia. [64] Power Supply Knock-Out
3
⁄49 Dia. [44] Charging Port Hole
7
⁄89 Dia. [22] Field Control Wiring Hole
3
⁄49-14 NPT Condensate Drain
F 29 Dia. [51] Power Supply Knock-Out
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail): a. Bottom to combustible surfaces (when not using curb) 0 in., on horizon-
tal discharge units with electric heat, 1 in. clearance to ductwork for 1 ft.
b. Outdoor coil, for proper airflow, 36 in. one side, 12 in. the other. The
side getting the greater clearance is optional. c. Overhead, 60 in. to assure proper outdoor fan operation. d. Between units, control box side, 42 in. per NEC (National Electrical Code). e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC. f. Between unit and block or concrete walls and other grounded surfaces,
control box side, 42 in. per NEC. g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the outdoor coil and combustible surfaces as stated in notes 5a, b, and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material.
8. The vertical center of gravity is 18-7 from the bottom of the base rail.
‘‘H’’ ‘‘J’’ ‘‘K’’
7
⁄89 632 38-55⁄169 1050 28-911⁄169 856
7
⁄89 885 48-15⁄169 1253 38-03⁄89 924
1
⁄29 [495] for 090, 28-69 [610] for 120 up
These holes req’d for use with accessory packages —
CRBTMPWR001A00 (
THREADED
CONDUIT SIZE
*Select either
BOTTOM POWER CHART
1
⁄29,3⁄49) or CRBTMPWR002A00 (1⁄29,11⁄49)
WIRE
1
⁄2( 24V
3
⁄4( Power* 11⁄89 [28.4]
1
⁄4( Power* 13⁄49 [44.4]
1
3
⁄49 or 11⁄49 for power, depending on wire size.
USE
REQ’D HOLE SIZES (MAX.)
7
⁄89 [22.2]
Fig. 2 — Base Unit Dimensions
—2—
NOTE: When installing any accessory item, see the manu­facturer’s installation instructions packaged with the acces­sory. A qualified installer or agency must use only factory­authorized kits or accessories when modifying this unit.
I. LOCATE THE UNIT A. Clearance
Maintain clearance around and above unit to provide mini­mum distance from combustible materials, proper airflow ,and service access. See Fig. 2 and 3.
Minimum clearance to combustibles (when not using curb) is 0 in. on vertical discharge units and 1 in. on horizontal dis­charge units.
Minimum clearance to block walls or any other grounded sur­face is 42 in. on all sides.
Minimum clearance of 42 in. should be provided between units on side with control box. Between unit and ungrounded sur­faces, control box side, clearance is 36 inches.
Minimum clearance around outdoor coil is 12 in. one side and 36 in. the other side (side getting greater clearance is optional).
Overhead minimum clearance is 60 in. Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contami­nated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Slab mounted units should be at least 4 in. above the highest expected water, flood, and runoff levels. Do not use the unit if it has been under water.
B. Roof Curb Mount
Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 4. Install insulation, cant strips, roofing felt, and counter flashing as shown. Duct- work must be attached to curb. If electric or control power is to be routed through the basepan, attach the accessory thru­the-bottom connections to the basepan in accordance with the accessory installation instructions. Accessory electric connec­tions must be installed before unit is in place on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for water integrity. Install gasket with the roof curb as shown in Fig. 4. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 5. This is necessary for unit drain to function properly.
C. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of outdoor-coil air inlet to prevent grass and foliage from ob­structing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
II. UNIT DUCT CONNECTIONS
On vertical units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. On horizontal units, duct flanges should be attached to horizontal openings and all ductwork should be secured to flanges.
Fig. 3 — Service and Operational Clearances
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in­sulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On horizontal discharge units, a minimum clearance of 1 in. is required for the first 12 in. of ductwork. Cabinet return-air static shall not exceed –0.35 in. wg with Varislide™ economizer
−0.20 in. wg with PARABLADE economizer, or –0.45 in. wg
without economizer. NOTE: Connection must be made to roof curb before unit is
set in place.
III. RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by us­ing unit frame as a reference. See Table 1 and Fig. 6 for ad­ditional information. Operating weight is shown in Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.
A properly positioned unit will have the following clearances between unit and roof curb: and base rails on each side and front of unit; 1
1
⁄4-in. clearance between roof curb
5
⁄32-in. clear­ance between roof curb and rear of unit. See Fig. 4, Views A-A and C-C.
After unit is in position, remove polyethylene shipping wrap­per and rigging skid.
—3—
UNIT SIZE
549B
090,120 28-8
‘‘B’’ ‘‘C’’
7
⁄169 [827] 18-1015⁄169 [583] 13⁄49 [45]
‘‘D’’ALT
DRAIN HOLE
POWER CONTROL
3
⁄49 NPT
1
1
⁄49 NPT
1
⁄29 NPT
1
⁄29 NPT
CONNECTOR ACCESSORY
PACKAGE
CRBTMPWR00A100
(Thru-the-Bottom)
CRBTMPWR00A200
(Thru-the-Bottom)
UNIT SIZE
549B
090,120
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
‘‘A’’
18-29 [356] CRRFCURB003A00 28-09 [610] CRRFCURB004A00
ROOF CURB
ACCESSORY
7. Direction of airflow.
Fig. 4 — Roof Curb Details
—4—
Table 1 — Specifications
UNIT 549B 090 120
1
1
⁄4...1100
7
8
2
Acutrol™ Feed Device
Acutrol Feed Device
1...16 x 25 x 1
NOMINAL CAPACITY (tons) 7 OPERATING WEIGHT (lb)
Unit 870 1000 With Varislide™ Economizer 914 1044 With PARABLADE Economizer 932 1062 Roof Curb 143 143
COMPRESSOR Scroll
Quantity 22 Oil (oz) (each compressor) 57 57
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1 5-3 9-11 Circuit 2 5-8 9-11
OUTDOOR FAN Propeller Type
Quantity...Diameter (in.) 2...22 2...22 Nominal Cfm 6500 7000 Motor Hp...Rpm Watts Input (Total) 650 650
OUTDOOR COIL
Rows...Fins/in. 2...17 2...17 Total Face Area (sq ft) 20.5 25.1
INDOOR FAN Centrifugal Type, Belt Drive
Size (in.) 1...15 x 15 1...15 x 15 Nominal Cfm 3000 4000 Maximum Continuous Bhp 2.90 4.20 Motor Frame 56 56 Fan Rpm Range 725-925 860-1080 Motor Bearing Type Ball Ball Maximum Fan Rpm 2100 2100 Motor Pulley Pitch Diameter A/B (in.) 3.4/4.4 4.0/5.0 Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) 8.0 8.0 Belt — Quantity...Type...Length (in.) 1...A...51 1...A...51 Pulley Center Line Distance (in.) 16.75-19.25 15.85-17.50 Speed Change per Full Turn of 50 45
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns 55
From Closed Position
Factory Setting — Full Turns Open 55 Factory Speed Setting (rpm) 725 860 Fan Shaft Diameter at Pulley (in.) 11
High-Efficiency Enhanced Copper Tubes, Lanced Aluminum Fins
INDOOR COIL High Efficiency Enhanced Copper Tubes, Aluminum Double-Wavy Fins,
Rows...Fins/in. 3...15 4...15 Total Face Area (sq ft) 8.9 11.1
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief 450±50 Cutout 428 Reset (Auto.) 320
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid Line) (psig) Cutout 7±3 Reset (Auto.) 22±7
FREEZE-PROTECTION THERMOSTAT
Opens (F) 30±5 Closes (F) 45±5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 1...20 x 25 x 1
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2
10
1
⁄4...1100
7
8
LEGEND
Bhp — Brake Horsepower
—5—
MAXIMUM ALLOWABLEDIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 5 — Unit Leveling Tolerances
IV. FIELD CONNECTIONS A. External Trap Condensate Drain
The unit’s
3
⁄4-in. condensate drain connections are located at the bottom and end of the unit. Unit discharge connec­tions do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard end drain connection, make sure the plug in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb instal­lation, relocate the factory-installed plug from the bottom connection to the end connection. See Fig. 7. The piping for
the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. deep and protect against freeze­up. See Fig. 8. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection.
B. Field Duct Connections NOTE: The design and installation of the duct system must
be in accordance with NFPA standards for the installation of nonresidence-type air conditioning and ventilating systems, NFPA No. 90A, or residence-type, NFPA No. 90B, and/or local codes and ordinances.
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Remove appropriate panels from unit to obtain either horizontal or vertical discharge. If units are installed in horizontal discharge applications, remove vertical dis­charge duct covers, save screws, and install covers on vertical duct openings.
2. Select and size ductwork, supply-air registers, and return­air grilles according to ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engi­neers) recommendations.
CAUTION:
When drilling the duct system fastening holes into the side of the unit for duct flanges, use ex­treme care not to puncture the coil or coil tubes. See Fig. 9.
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail 9A.9 Holes in base rails are centered around the unit center of grav­ity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
CAUTION: All panels must be in place when rigging.
Fig. 6 — Rigging Details
—6—
OPERATING
UNIT 549B
090 870 395 87.38 2219 40.25 1022 41.31 1050 120 1000 454 87.38 2219 40.25 1022 49.31 1253
WEIGHT lb kg in. mm in. mm in. mm
(A((B((C(
DIMENSIONS
NOTE: Drain plug is shown in factory-installed position.
Fig. 7 — Condensate Drain Pan
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gas­kets to ensure weather- and airtight seal.
4. When horizontal return is used, install external field­supplied air filters in return-air ductwork where they are easily accessible for service. Recommended filter sizes are shown in Table 1.
5. For horizontal applications, be sure ductwork does not cover nameplate.
6. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed.Avoidabrupt duct size increases or decreases.
7. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through uncon­ditioned space, and use vapor barrier in accordance with latest issue of SMACNA (Sheet Metal and Air Condi­tioning Contractors National Association) and ACCA (Air Conditioning Contractors of America) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On hori­zontal discharge units, a minimum clearance of 1 in. is required for the first 12 in. of ductwork.
8. Flash, weatherproof, and vibration isolate all openings in building structure in accordance with local codes and good building practices.
NOTE: Trap should be deep enough to offset maximum unit static dif­frence. A 4-in. trap is recommended.
Fig. 8 — External Trap Condensate Drain
Fig. 9 — Location of Coil Area
Not to be Drilled
C. Electrical Connections
WARNING:
The unit cabinet must have an un­interrupted, unbroken, electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire con­nected to the unit ground lug in the control compart­ment, or conduit approved for electrical ground when installed in accordance with NEC ANSI (American National Standards Institute)/NFPA70-1990(inCanada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1) and local electrical codes. Failure to adhere to this warning could result in personal injury.
CAUTION:
Failure to obey the following precau­tions could result in damage to the unit being installed:
Field Power Supply
1. Make all electrical connections in accordance with NEC ANSI/NFPA 70-1990 and local electrical codes gov­erning such wiring. In Canada, all electrical connec­tions must be in accordance with CSA Standard C22.1 Canadian Electrical Code Part One and applicable local codes. Refer to unit wiring diagram.
2. A unit disconnect switch is required within sight from the unit. The disconnect switch may be mounted on the unit corner post (see Fig. 2). When mounting dis­connect switch, be sure the unit rating plate is not obstructed.
NOTE: A factory-installed disconnect switch is available.
—7—
3. Use only copper or copper-clad conductor for connec­tions between field-supplied electrical disconnect switch and unit. The use of aluminum wire is not recom­mended. Maximum wire size is no. 2 AWG (American Wire Gage) on units with heat(up to 34 kW). The maxi­mum wire size is no. 2/0 AWG on units with heat (over 34 kW).
4. Units with accessory electric heat must also have the correct single point box kit to meet UL (Underwriters’ Laboratories) requirements. Refer to installation instruc­tions shipped with the accessory for more details.
5. Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Tables 2A and 2B). On 3-phase units, voltages be­tween phases must be balanced within 2% and the cur­rent within 10%. Use the formula shown in Tables 2A and 2B, Note 2 to determine the percent voltage imbal­ance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause dam­age to electrical components. Such operation would in­validate any applicable warranty.
6. Insulate low-voltage wires for highest voltage con­tained within conduit when low-voltage control wires are run in same conduit as high-voltage wires. Install con­duit through side panel openings. For units without ac­cessory electric heat, install conduit between disconnect and control box.
7. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
8. Install power lines to terminal connections as shown in Fig. 10.
9. For units with accessory electric heat, refer to accessory installation instructions for wiring the accessory.
During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 2A and 2B). On 3-phase units, voltages between phases must bebal­anced within 2%, and the current within 10%. Use the for­mula shown in Tables 2A and 2B, Note 2 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable warranty.
High-Voltage Connections (Fig. 10) The unit must have a separate electrical service with a field-
supplied, waterproof fused disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. Be sure disconnect switch does not obstruct unit rating plate. A factory-installed disconnect is available.
The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet holein the control corner panel.
Proceed as follows to complete the high-voltage connections to the unit:
1. Connect ground lead to chassis ground connection when using separate ground wire.
LEGEND
C—Contactor COMP — Compressor IFC Indoor Fan Contactor NEC National Electrical Code
Field Wiring Factory Wiring
Splice Connection (Factory-Supplied)
Fig. 10 — Power Wiring Connections
2. Pigtails are provided for field power connection. Use factory-supplied splices or UL-approved copper/aluminum connector .Install conduit connectors in side panel power supply knockout openings indicated in Fig. 2. Route power lines through connector to unit control box.
NOTE: If accessory thru-the-bottom power connections are used, refer to the accessory installation instructions for in­formation on power wiring. Refer to Fig. 2 for drilling holes in basepan.
Special Procedures for 208-V Operation
DANGER: Make sure that the power supply to the unit is switched off before making any wiring changes. Electrical shock can cause personal injury or death.
For operation on 208 v, disconnect the black wire from the 230-v orange wire on the transformer and connect it to the 200-v red wire from the transformer. Insulate the end of the orange wire.
Control Voltage Connections Install a factory-approved room thermostat. See Table 3,
page 11.Locate the thermostat on an inside wall in the space to be conditioned where it will not be subjected to either a cooling or heating source or direct exposure to sunlight. Mount the thermostat 4 to 5 ft above the floor.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insu­lated wire (35 C minimum). For 76 to 155 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be connected directly tothe thermostat and will require a junction box and splice at the thermostat.
—8—
Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections on unit (shown in Fig. 11) as described in Steps 1 through 4 below.
1. If unit is mounted on roof curb and accessory thru-the­bottom service connections are used, route wire through basepan.
2. Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 2).
LEGEND
AHA — Adjustable Heat Anticipator CC Cooling Compensator RC 24 V Cooling RH 24 V Heating TC Thermostat-Cooling TH Thermostat-Heating
Field Wiring Factory Wiring
Fig. 11 — Low-Voltage Connections With or
Without Economizer
3. Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 12. The raceway provides the ULrequired clearance between the high- and low-voltage wiring.
4. Connect thermostat wires to screw terminals of low­voltage connector (see Fig. 11).
Fig. 12 — Field Control Wiring Raceway
UNIT 549B
090
1
(7
⁄2Tons)
120
(10 Tons)
Table 2A — Electrical Data (Units Without Electrical Convenience Outlet)
NOMINAL VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
460-3-60 414 508 6.4 44.0 0.7 3.4
208/230-3-60 187 254 19.3 123.0 1.4 10.6
460-3-60 414 508 10.0 62.0 0.7 4.8
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA
COMPRESSOR OFM IFM ELECTRIC HEAT* POWER SUPPLY
—/—
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7
—/—
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0 —
16.5
27.8
33.0
41.7
50.0
—/—
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2
—/—
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
38.2/ 38.2
65.3/ 69.5
79.8/ 86.3
102.7/112.8
121.5/134.5
148.6/165.7
19.2
40.1
44.0
61.0
68.8
82.0
56.8/ 56.8
84.0/ 88.1
98.5/105.0
140.1/153.1
167.2/184.3
187.3/177.1
28.7
53.3
70.5
78.3
91.5
88.8
40/ 40** 70/ 70
80/ 90 110/125 125/150 150/175
20** 45** 45** 70 70 90
60/ 60**
90/ 90 100/110 150/175 175/200 200/200
30** 60** 80
80 100 100
MINIMUM UNIT
DISCONNECT
SIZE
40/ 40 65/ 69
79/ 85 100/109 117/129 142/158
60/ 60
85/ 89
98/104 136/148 161/177 180/198
20 39 43 59 66 78
30 53 69 76 88 99
242/242 264/267 275/281†† 294/302†† 309/319†† 330/344††
337/337 358/362†† 370/375†† 403/414†† 425/439†† 441/457††
121 138 141 155 161 171
170 189 203
209 220†† 230††
—9—
Table 2B — Electrical Data (Units With Electrical Convenience Outlet)
UNIT 549B
NOMINAL VOLTAGE (V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR OFM IFM ELECTRIC HEAT* POWER SUPPLY
Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA
208/230-3-60 187 254 12.4 88.0 1.4 7.5
009
1
(7
⁄2Tons)
460-3-60 414 508 6.4 44.0 0.7 3.4
208/230-3-60 187 254 19.3 123.0 1.4 10.6
120
(10 Tons)
460-3-60 414 508 10.0 62.0 0.7 4.8
LEGEND AND NOTES TO TABLES 2A AND 2B
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code OFM Outdoor Fan Motor RLA Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
or 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
**Fuse or HACR circuit breaker.
††Factory-installed disconnect is not available for these units when elec-
tric heat package is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combina­tion load and equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
age of voltage imbalance.
Use the following formula to determine the percent-
MINIMUM UNIT
DISCONNECT
SIZE
—/—
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7
—/—
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0 —
16.5
27.8
33.0
41.7
50.0
—/—
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2
—/—
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
43.0/ 43.0
70.1/ 74.3
84.6/ 91.1
107.5/117.6
126.3/139.3
153.4/170.5
21.4
42.3
46.1
63.1
71.0
84.1
61.6/ 61.6
88.8/ 92.9
103.3/109.6
144.9/157.9
172.0/189.1
192.1/181.9
30.9
55.6
72.6
80.5
93.6
91.0
45/ 45**
80/ 80 90/100
110/125 150/150 175/175
25** 45** 50**
70 80 90
70/ 70 90/100
110/110 150/175 175/200 200/200
35** 60** 80
90 100 100
46/ 46 71/ 75
84/ 90 105/115 122/134 147/163
23 42 46 61 68 80
65/ 65
90/ 94 104/110 142/154 167/183 185/204
33 55 71 78 90
102
247/247 269/272 280/285†† 298/307†† 313/324†† 335/349††
123 140 143 157 163 174
341/341 363/366†† 375/380†† 408/418†† 430/443†† 446/462††
172 191 205
211 222†† 232††
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
452 + 464 + 455 1371
=
3
3
= 457
Determine maximum deviation from average voltage:
(AB) 457 – 452=5v (BC) 464 – 457=7v
(AC) 457 – 455=2v Maximum deviation is 7 v. Determine percentage of voltage imbalance:
% Voltage imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company immediately.
—10—
Loading...
+ 22 hidden pages