Bryant 549B User Manual

installation, start-up and service instructions
SINGLE PACKAGE ROOFTOP HIGH-EFFICIENCY HEAT PUMP UNITS
Cancels: II 549B-90-5 II 549B-90-6
Dura
Pac
Plus Series
Sizes 090-120
71/2 to 10 Tons
549B
10/15/05
IMPORTANT — READ BEFORE INSTALLING
Read and become familiar with these installation instruc­tions before installing this unit.
Be sure the ins tallation conforms to al l applicab le local an d national codes.
These instructions contain important information for the proper maintenance and repair of this equipment. Retain these instructions for future use.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-33
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 1
III. Step 3 — Install Condensate Drain Line and
External Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
IV. Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . 3
V. Step 5 — Make Electrical Connections . . . . . . . . . . 6
VI. Step 6 — Adjust Factory-Installed Options. . . . . . 10
VII. Step 7 — Adjust Indoor-Fan Speed . . . . . . . . . . . . 19
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-36
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36-39
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .40-42
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or servic e air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install lockout tag on disconnect. Electrical shock could cause personal injury.
CAUTION: Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
INSTALLATION
This unit is shipped in the vertical configuration. To convert to horizontal configuration, remove the side duct opening covers. Using the same screw s, install th e cover s on th e ver­tical duct openings with the insulation-side down. Seals around duct openings must be tight.
I. STEP 1 — PROVIDE UNIT SUPPORT A. Roof Curb
Assemble and install the accessory roof curb in acco rdance with instructions shipped wi th the curb. See Fig. 1. Install insulation, cant stri ps, roofing felt, and counter flashing as shown. Ductwork must be attached to the curb. If electric con­trol power will be routed through the basepan, use the appropriate accessory kit listed in Fig. 1, available from your local distributor. Attach the accessory thru-the-bottom ser­vice connections to the basepan in accordance with the acces­sory installa tion inst ruct ions. Conn ect ions m ust b e in stal led before the unit is set on the roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install the gasket supplied with the roof curb as shown i n Fig. 1. An imprope rly applie d gas­ket can also result in air leaks and poor unit performance.
The roof curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for the unit drain to func­tion properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that ex te nds a m ini mum o f 6 i n. beyond the unit cabinet. Install a gravel apron in front of the condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
C. Alternate Unit Support (Curb or Slab Mount)
A non-combustible sleeper ra il can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all duc ts to the roof cu rb and building structure. Do not connect ductwork to the unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openi ngs and all ductwork attached to the flanges. Insulate and weatherproof all e xter­nal ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through a n unco nditi one d spa ce mu st be ins u­lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply w ith appli­cable fire codes.
A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On horizontal dis­charge units, a minim um c learanc e of 1 in. is re quired for the
first 12 in. of ductwork. Cabinet return-air static pressure (a negative condition) shall not exceed 0.30 in. wg with econo­mizer or 0.45 in. wg without economize r.
CONNECTOR PKG.
ACCY.
CRBTMPWR001A01 CRBTMPWR002A01 1 CRBTMPWR003A01 CRBTMPWR004A01
B C D ALT DRAIN HOLE GAS POWER CONTROL ACCESSORY POWER
3
2-8
7
[827]
/16″
1-1015/16″
[583]
13/4″
[44.5]
ROOF CURB
ACCESSORY
CRRFCURB003A01 1-2 [356] CRRFCURB004A01 2-0 [610]
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT 11/4″ [31.7]
“A”
UNIT SIZE 549B
090-120
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″ NPT
[12.7]
1
/2″ NPT
[12.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam, 1 density.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
1
/2″ NPT
[12.7]
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for thru-the-curb gas type. Packages CRBTMPWR003A01 and 4A01 are for thru-the-bottom type gas connections.
3
/4 lb
Fig. 1 — Roof Curb Details
2
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 2 — Unit Leveling Tolerances
III. STEP 3 — INSTALL CONDENSATE DRAIN LINE AND EXTERNAL TRAP
Condensate drain connections are located on the botto m and end of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard end drain connection, make sure the red plug in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installa­tion, relocate the factory-installed red plug from the bottom connection to the end c onnectio n. The ce nter drai n plug looks like a star connection, but can be removed with a
1
/2-in. socket drive exten sion. See Fig. 3A. The pipin g for the con­densate dr ain and e xternal t rap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. deep and protect against freeze-up. If a dra in line is installe d downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
3
/4-in.). See Fig. 3B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect the unit for transportation dama ge. File any claim with the transportation agency . Keep the unit upright and do not drop it. Spreader bars are not required if top crating is
left on the unit. Rol lers may be used to move th e unit acro ss a roof. Level by using the unit frame as a reference. See Table 1 and Fig. 4 for additional information. Operating weight is shown in Table 1 and Fig. 4.
Lifting holes are pr ovide d i n t he b ase rai ls as shown in Fig. 4 and 5. Refer to rigging instructions on the unit.
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 3A — Condensate Drain Connection (Side View)
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 3B — Condensate Drain Piping Details
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for unit weight of economizer.
4. Unit weights do not include skid.
CAUTION: All panels must be in place when rigging.
Fig. 4 — Rigging Details
UNIT 549B
090 870 395 77.42 1966.5 41.5 1054 42.12 1070
102,120 1000 454 77.42 1966.5 41.5 1054 42.12 1070
WEIGHT
lb kg in. mm in. mm in. mm
‘‘A’’ ‘‘B’’ ‘‘C’’
UNIT
OPERATING
DIMENSIONS
3
A. Positioning
Maintain clearance around and above the unit to provide proper airflow and service access. See Fig. 5.
Position the unit on the roof curb so that the f oll ow in g clea r­ances are maintained:
1
/4-in. clearance between the roof curb
and the base rails on each side and the duct side of unit;
5
3
/16-in. clearance between t he roof cu rb and con denser s ide
of unit (see Fig. 1, section C-C).
Table 1 — Physical Data
Do not install the unit indoors. Do not locate the unit air inlet near exhaust vents or other sources of contaminated air.
Although the unit is weatherproof, guard against water from higher level runoff and overhangs.
After the unit is in position, remove the polyethylene ship­ping wrapper and rigging skid.
BASE UNIT 549B 090 102 120 NOMINAL CAPACITY (tons) 7 OPERATING WEIGHT (lb)
Unit 870 1000 1000 EconoMi$er IV 75 75 75 Roof Curb 223 223 223
COMPRESSOR Scroll
Quantity 22 2 Oil (oz) (each compr) 57 70 57
REFRIGERANT TYPE R-22
Operating Charge (lb)
Circuit 1 9.5 11.0 10.7 Circuit 2 9.5 11.0 10.8
OUTDOOR FAN Propeller
Quantity...Diameter (in.) 2...22 2...22 2...22 Nominal Cfm 6500 6500 6500 Motor Hp...Rpm
OUTDOOR COIL Enhanced Copper Tubes, Aluminum Fins, Fixed Orifice Metering Device
Rows...Fins/in. 2...17 2...17 2...17 Total Face Area (sq ft) 20.5 25.1 25.1
INDOOR FAN Centrifugal Type
Quantity...Size (in.) Standard 1...15 x 15 1...15 x 15 1...15 x 15
Type Drive Standard Belt Belt Belt
Nominal Cfm 3000 3400 4000 Maximum Continuous Bhp Standard 2.90 2.90 3.70
Motor Frame Size Standard 56 56 56
Nominal Rpm Standard 1725 1725 1725
Fan Rpm Range Standard 730-950 840-1085 860-1080
Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Standard 3.4/4.4 3.4/4.4 4.0/5.0
Nominal Motor Shaft Diameter (in.) Standard
Fan Pulley Pitch Diameter (in.) Standard 8.0 7.0 8.0
Belt, Quantity...Type...Length (in.) Standard 1...A...51 1...A...51 1...A...53
Pulley Center Line Distance (in.) Standard 16.75-19.25 16.75-19.25 15.85-17.50
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting Standard 555
Factory Speed Setting (rpm) Standard 730 840 860
Fan Shaft Diameter at Pulley (in.) 111
High-Static 1...15 x 15 1...15 x 15 1...15 x 15
High-Static Belt Belt Belt
High-Static 4.20 4.20 5.25
High-Static 56 56 56
High-Static 1725 1725 1725
High-Static 860-1080 860-1080 830-1130
High-Static 4.0/5.0 4.0/5.0 2.8/3.8
High-Static
High-Static 8.0 8.0 5.8
High-Static 1...A...53 1...A...53 1...BX...48
High-Static 16.75-19.25 16.75-19.25 15.85-17.50
Standard 45 45 45
High-Static 45 45 60
Standard 555
High-Static 556
High-Static 555
High-Static 860 860 887
INDOOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins,
Rows...Fins/in. 3...15 4...15 4...15 Total Face Area (sq ft) 8.9 11.1 11.1
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief 625 Cutout 428 Reset (Auto.) 320
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line) (psig)
Cutout 7 ± 3 Reset (Auto.) 22 ± 5
FREEZE PROTECTION THERMOSTAT
Opens (F) 30 Closes (F) 45
1
/
1
/4...1100
7
/
8
7
/
8
2
81/
1
/4...1100
7
/
8
7
/
8
2
10
1
/4...1100
7
/
8
7
/
8
Acutrol Metering Device
OUTDOOR-AIR INLET SCREEN Cleanable. Screen size and quantity vary by option selected. RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2
LEGEND
Bhp — Brake Horsepower
4
Fig. 5 — Base Unit Dimensions
5
V. STEP 5 — MAKE ELECTRICAL CONNECTIONS
C C
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of elec tric al wir e connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (American National Standards Institute/National Fire Protection Association), latest edition, and local electrical codes. Failure to follow this warning could result in the installer being liable for
3. For units with electric heat, refer to Table 2 and Accessory Installation Instructions.
NOTE: During operation, voltage to compressor terminals must be within the range indicated on the unit nameplate (see Tables 3A-3D). On 3-phase units, voltages between phases must be balanced within 2%, and the current within 10%. Use the formula shown in Tables 3A-3D, Note 2 on page 9 to determine the percentage of voltage imbalance. Operation on imp rop er lin e volt age or exc essiv e pha se imba l­ance constitutes abuse and may cause damage to electrical components. (Such operation would invalidate any applica­ble Bryant warranty .)
personal injury of others.
A. Field Power Supply
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit will be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v
1
/4-in. male
spade terminal on the transformer and c onnecting it to the
1
200-v
/4-in. male spade terminal on the transformer.
Refer to the unit label diagram for additional information. Pigtails are provided for fie ld wire connectio ns. Use factory­supplied splices or a UL (Underwriters’ Laboratories) approved copper/aluminum connector.
When installing units, provide a disconnect per NEC. All field wiring must comply wi th the N E C and lo cal require-
ments. In Canada, electrical connections must be in accor­dance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.
Install field wiring as foll ows:
1. Install conduit through the side panel openings. For units without electric heat, install conduit between the disconnect and control box.
2. Install power lines to terminal connections as shown
LEGEND
Contactor
OMP — Compressor IFC Indoor Fan Contactor NEC National Electrical Code
Field Wiring Factory Wiring Splice Connection (Factory-Supplied)
Fig. 6 — Power Wiring Connections
208/230-3-60
460-3-60
in Fig. 6.
Table 2 — Electric Heating Capacities
UNIT 549B
090
102
120
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kW
2
voltage)
UNIT VOLTAGE
(60 Hz)
208/230/240
(3 phase)
460/480
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
= Heater kW rated x (unit power distribution voltage/rated heater
new
ACCESSORY
kW
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
46.2/50.0*
ELECTRIC HEATER PART NUMBER
CRHEATER---A00
017 010 011 012 012 and 017
016 013 014 015 014 and 016
117 110 111 112 112, 117
116 113 114 115 114,116
017 010 012 012 and 017 010 and 012
013 014 015 014 and 016 013 and 015
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
= 16 kW (215/240)
kW
new
kW
= 12.8 kW (rating at 215 v)
new
SINGLE POINT BOX PACKAGE NO.
CRSINGLE---A00
2
007 007 009 009 013
006 006 008 008
012 012 015 015 017
011 011 014 014 016
012 012 015 017 017
011 014 014 016 016
6
UNIT 549B
090
102
120
Table 3A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet
NOMINAL
VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
460-3-60 414 508 6.4 44.0 0.7 3.4
208/230-3-60 187 254 13.9 105 1.4 7.5
460-3-60 414 508 7.9 55.0 0.7 3.4
208/230-3-60 187 254 19.3 123.0 1.4 10.6
460-3-60 414 508 10.0 62.0 0.7 4.8
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
(each)
IFM ELECTRIC HEAT* POWER SUPPLY
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
38.2/ 38.2
65.3/ 69.5
79.8/ 86.3
102.7/112.8
121.5/134.5
148.6/165.7
19.2
40.1
44.0
61.0
68.8
82.0
41.3/ 41.3
68.4/ 72.5
82.9/ 89.4
105.8/115.9
124.5/137.5
151.7/168.8
22.3
43.2
47.0
64.0
71.9
85.0
56.8/ 56.8
84.0/ 88.1
98.5/105.0
140.1/153.1
167.2/184.3
187.3/177.1
28.7
53.5
70.5
78.3
91.5
88.8
110/125 125/150 150/175
110/125 125/150 175/175
100/110 150/175 175/200 200/200
40/ 40†† 70/ 70†† 80/ 90
20†† 45†† 45†† 70 70 90
45/ 45†† 70/ 80†† 90/ 90
25†† 45†† 50†† 70 80 90
60/ 60†† 90/ 90
30†† 60†† 80
80 100 100
MINIMUM UNIT DISCONNECT
SIZE†
242/242
40/ 40
264/267
65/ 69
275/281***
79/ 85
20 39 43 59 66 78
43/ 43 68/ 72 82/ 88
23 43 46 62 69 81
60/ 60 85/ 89 98/104
30 53 69 76 88 99
294/302*** 309/319*** 330/344***
276/276 298/301 309/315*** 328/336*** 343/353*** 364/378***
337/337 358/362*** 370/375*** 403/414*** 425/439*** 441/457***
100/109 117/129 142/158
103/112 120/132 145/161
136/148 161/177 180/198
121 138 141 155 161 171
143 160 163 177 183 193
170 189 203 209 220*** 230***
Table 3B — Electrical Data — Standard Motor Units With Electrical Convenience Outlet
UNIT 549B
090
NOMINAL
VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
460-3-60 414 508 6.4 44.0 0.7 3.4
208/230-3-60 187 254 13.9 105 1.4 7.5
102
460-3-60 414 508 7.9 55.0 0.7 3.4
208/230-3-60 187 254 19.3 123.0 1.4 10.6
120
460-3-60 414 508 10.0 62.0 0.7 4.8
NOTE: See legend and notes on page 9.
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
IFM ELECTRIC HEAT* POWER SUPPLY
(each)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
43.0/ 43.0
70.1/ 74.3
84.6/ 91.1
107.5/117.6
126.3/139.3
153.4/170.5
46.1/ 46.1
73.2/ 77.3
87.7/ 94.2
110.6/120.7
129.3/142.3
156.5/173.6
61.6/ 61.6
88.8/ 92.9
103.3/109.8
144.9/157.9
172.0/189.1
192.1/181.9
21.4
42.3
46.1
63.1
71.0
84.1
24.5
45.3
49.2
66.2
74.1
87.2
30.9
55.6
72.6
80.5
93.6
91.0
45/ 45†† 80/ 80
90/100 110/125 150/150 175/175
25†† 45†† 50†† 70 80 90
50/ 50††
80/ 80
90/100 125/125 150/150 175/175
25†† 50†† 50†† 70 80 90
70/ 70
90/100 110/110 150/175 175/200 200/200
35†† 60†† 80
90 100 100
MINIMUM UNIT
DISCONNECT
SIZE†
247/247
46/ 46
269/272
71/ 75
280/285***
84/ 90
23 42 46 61 68 80
49/ 49 74/ 78 87/ 93
26 45 49 64 72 84
65/ 65 90/ 94
33 55 71 78 90
102
298/307*** 313/324*** 335/349***
281/281 303/306 314/319*** 332/341*** 347/358*** 369/383***
341/341 363/366*** 375/380*** 408/418*** 430/443*** 446/462***
105/115 122/134 147/163
108/118 126/138 151/166
104/110 142/154 167/183 185/204
123 140 143 157 163 174
145 162 165 179 185 196
172 191 205 211 222*** 232***
7
Table 3C — Electrical Data — High-Static Motor Units Without
Electrical Convenience Outlet
UNIT 549B
090
102
120
NOMINAL VOLTAGE (V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 10.6
460-3-60 414 508 6.4 44.0 0.7 4.8
208/230-3-60 187 254 13.9 105 1.4 10.6
460-3-60 414 508 7.9 55.0 0.7 4.8
208/230-3-60 187 254 19.3 123.0 1.4 15.0
460-3-60 414 508 10.0 62.0 0.7 7.4
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
IFM ELECTRIC HEAT* POWER SUPPLY
(each)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
41.3/ 41.3
68.4/ 72.6
82.9/ 89.4
105.8/115.9
124.6/137.6
151.7/168.8
20.6
41.5
45.4
62.4
70.2
83.4
44.4/ 44.4
71.5/ 75.6
86.0/ 92.5
108.9/119.0
127.6/140.6
154.8/171.9
23.7
44.6
48.4
65.4
73.3
86.4
61.2/ 61.2
88.4/ 92.5
102.9/109.4
144.5/157.5
171.6/188.7
191.7/181.5
31.3
56.1
73.1
80.9
94.1
96.4
45/ 45†† 70/ 80
90/ 90 110/125 125/150 175/175
25†† 45†† 50†† 70 80 90
45/ 45††
80/ 80
90/100 110/125 150/150 175/175
25†† 45†† 50†† 70 80 90
70/ 70
90/100 110/110 150/175 175/200 200/200
35†† 60†† 80
90 100 100
MINIMUM UNIT
DISCONNECT
SIZE†
267/267
44/ 44
288/292
69/ 73
300/305***
82/ 88
22 41 45 60 68 80
47/ 47 72/ 76 85/ 91
25 44 48 63 71 83
65/ 65 90/ 94
33 56 72 79 91
102
318/336*** 333/344*** 355/369***
301/301 322/326 334/339*** 352/360*** 367/378*** 389/403***
360/360 382/385*** 393/399*** 427/437*** 448/462*** 464/480***
103/113 121/132 145/169
106/116 124/136 149/164
103/109 141/153 166/182 185/203
134 150 153 167 173 184
156 172 175 189 195 206
181 201 215 221 231*** 241***
Table 3D — Electrical Data — High-Static Motor Units With Electrical Convenience Outlet
UNIT 549B
090
NOMINAL VOLTAGE (V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 10.6
460-3-60 414 508 6.4 44.0 0.7 4.8
208/230-3-60 187 254 13.9 105 1.4 10.6
102
460-3-60 414 508 7.9 55.0 0.7 4.8
208/230-3-60 187 254 19.3 123.0 1.4 15.0
120
460-3-60 414 508 10.0 62.0 0.7 7.4
NOTE: See legend and notes on page 9.
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
IFM ELECTRIC HEAT* POWER SUPPLY
(each)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
46.1/ 46.1
73.2/ 77.4
87.7/ 94.2
110.6/120.7
129.4/142.4
156.5/173.6
49.2/ 49.2
76.3/ 80.4
90.8/ 97.3
113.7/123.8
132.4/145.4
159.6/176.7
66.0/ 66.0
93.2/ 97.3
107.7/114.2
149.3/162.3
176.4/193.5
196.5/186.3
22.8
43.7
47.5
64.5
72.4
85.5
25.9
46.7
50.6
67.6
75.5
88.6
33.5
58.2
75.2
83.1
96.2
93.6
50/ 50†† 80/ 80
90/100 125/125 150/150 175/175
25†† 45†† 50†† 70 80 90
50/ 50††
80/ 90 100/100 125/125 150/150 175/200
30†† 50†† 60†† 70 80 90
70/ 70 100/100 110/125 150/175 200/200 200/200
35†† 60†† 80
90 100 100
MINIMUM UNIT
DISCONNECT
SIZE†
271/271
49/ 49
293/296
74/ 78
305/310***
88/ 94
24 44 47 63 70 82
53/ 53 78/ 81 91/ 97
27 47 50 66 73 85
70/ 70 95/ 99
36 58 74 81 93
105
323/331*** 338/348*** 360/373***
305/305 327/330 339/344*** 357/365*** 372/382*** 394/407***
365/365 387/390*** 398/403*** 431/442*** 453/467*** 469/485***
109/118 126/138 159/167
112/121 129/141 154/170
109/115 147/159 172/188 190/209
136 152 155 169 175 186***
158 174 177 191*** 197 208
183 203 217 223*** 234*** 243***
8
LEGEND AND NOTES FOR TABLES 3A-3D
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning
IFM Indoor Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent
NEC National Electrical Code OFM — Outdoor-Fan Motor RLA Rated Load Amps
*Heaters are field installed only.
†Minimum unit disconnect size is used to determine minimum discon-
nect per NEC.
**Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
††Fuse or HACR circuit breaker.
***Factory-installed disconnect is not available for these units when
electric heat package is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
2. Unbalanced 3-Phase Supply Voltage
and Refrigeration
Protection
tion load and equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
cent of voltage imbalance. % Voltage Imbalance
= 100 x
max voltage deviation from average voltage
Use the following formula to determine the per-
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance:
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
3. Non-fused disconnect switch cannot be used when rooftop unit electrical ratings exceed 80 amps.
452 + 464 + 455
3
1371
=
3
= 457
7 457
9
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate the thermostat assembly on a solid wall in the conditioned spac e to sense average temperature in accor­dance with thermostat installation instructions.
NOTE: If using a Bryant elect ronic therm ostat, set th e ther­mostat configuration for “non-heat pump operation.” This family of products does not require an “O” terminal to ener­gize the reversing valve.
Route the therm ostat ca ble or eq uivale nt singl e leads of col­ored wire from the subbase terminals to the low-voltage con­nections on the unit (shown in Fig. 7) as described in Steps 1 through 4 below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directl y c onnect ed to the thermostat and will require a junction box and splice at the thermostat.
1. If the unit is mounted on roof curb and accessory thru-the-curb service plate connection is used, route wire through the connection plate.
2. Pass control wires throug h the hole provided on the unit (see connection D in Connection Sizes table Fig. 5).
3. Feed wi re through the racew ay bu ilt into the co rner po st to the 24-v barrier located on the left side of the control box. See Fig. 8. The raceway provides the UL required clearance between the high-and low-voltage wiring.
4. Connect the thermostat wires to the screw termina ls of the low-voltage connector (se e Fig. 7).
NOTE: If thru-the-bottom power connections are used refer to the accessory installation instructions for information on power wiring. Refer to Fig. 5 for drilling holes in the basepan.
C. Defrost Board
The defrost board timer cycle is set to 30 minutes. To change the cycle time, remove the wire from defrost board connected to the 30 minute quick-connect. See Fig. 9. Connect the wire to the 50 to 90 minute quick-connects on the defrost board, depending on the desired defrost time.
D. Heat Anticipator Settings
For units with electric heat, set heat anticipator settings as shown in Table 4.
VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS
A. Disconnect Switch
The optional disconnect switch is non-fused. The switch can be locked in plac e for safety pur poses. The disconn ect has a maximum rating of 80 amperes and cannot be used if rooftop electrical rating exceeds 80 amperes.
B. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan at the bottom of the unit (for shipping).
Assembly:
1. Determine the amount of ventilation requi red for the building. Record the amount for use in Step 8.
2. Remove the filter access panel by raising the panel and swinging it outward. The panel is now disen­gaged from the track and can be removed. No tools are required to remove the filter access panel. Remove the outdoor-air opening panel. Save panels and screws. See Fig. 10.
3. Separate the hood and screen from the basepan by removing the screws and brackets securing them. Save all screws and discard brackets.
4. Replace the ou tdoor air opening pa nel.
5. Place the hood on the front of the outdoor air opening panel. See Fig. 11 for hood details. Secure the top of the hood with the 6 screws removed in Step 3. See Fig. 12.
6. Remove and save the 8 scre ws (4 on each side) from the sides of the manual outdoor-air damper.
7. Align the screw holes on the hood with the screw holes on the sid e of manual outdoor-air dam per. See Fig. 11 and 12. Secure the hood with the 8 screws from Step 6.
8. Adjust the minimum position setting of the damper blade by adjusting the manual outdoor-air adjust­ment screws on the front of the damper blade. See Fig. 10. Slide the blade vertically until it is in the appropriate position determined by Fig. 13. Tighten the screws.
9. Remove and save the screws cu rrent ly o n the si des of the hood. Insert the screen. Secure the screen to the hood using the screws. See Fig. 12.
10. Replace the filter access panel. Ensure that the filter access panel slides along the tracks and is securely engaged.
UNIT
Heater kW*
10.4, 16.0 0.3 NA NA
549B
*kW is based on 240 or 480 v.
24.8, 32.0 0.6 0.3 0.3
42.4, 50.0 0.9 0.6 0.3 41.7, 50.0 0.6 0.3 0.3
Table 4 — Heat Anticipator Settings
208/230 460
Configuration
1-Stage
2-Stage
Stage 1 Stage 2 Stage 1 Stage 2
UNIT VOLTAGE
Heater kW*
13.9, 16.5
27.8, 33.0
10
Configuration
1-Stage
0.3 NA NA
2-Stage
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS ON
OFF
B
A
C
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
D
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when con­figured for A/C operation.
Fig. 7 — Low-Voltage Connections With or
Without Economizer or Two-Position Damper
Fig. 9 — Defrost Board
DISCONNECT BOARD
DISCONNECT SWITCH (OPTIONAL)
RACEWAY
COMPRESSOR NO. 2
CONVENIENCE OUTLET
HOLE IN END PANEL
COMPRESSOR NO. 1
Fig. 8 — Typical Field Control Wiring Raceway
FILTER ACCESS PANEL
OUTDOOR AIR OPENING PANEL
SCREWS (SIDE)
MANUAL OUTDOOR-AIR ADJUSTMENT SCREWS
DAMPER BLADE
Fig. 10 — Damper Panel with Manual
Outdoor-Air Damper Installed
11
SCREW HOLES (TOP)
Fig. 11 — Outdoor-Air Hood Details
C. Optional EconoMi$er IV
See Fig. 14 for EconoMi$er IV component locations. NOTE: These instructions are for installing the optional
EconoMi$er IV. Refer to the accessory EconoMi$er IV in stal ­lation instr uctions when field inst alling an EconoMi$er I V accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 15.
2. The box with the economizer hood components is shipped in the compa rtment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 14. To remove the component box f rom it s shippi ng posi ­tion, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. See Fig. 16.
IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter
for use in the power exhaust hood assembly.
3. The indoor coi l acc ess pan el wi ll b e us ed a s the to p of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 17.
4. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws pro­vided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 18.
HOOD
HOOD SCREEN LOCATION (SCREEN NOT SHOWN)
Fig. 12 — Optional Manual Outdoor-Air
Damper with Hood Attached
ECONOMI$ER IV CONTROLLER
WIRING HARNESS
ACTUATOR
OUTSIDE AIR TEMPERATURE SENSOR
LOW AMBIENT SENSOR
Fig. 14 — EconoMi$er IV Component Locations
FILTER ACCESS PANEL
Fig. 13 — Outdoor Air Damper Position Setting
INDOOR COIL ACCESS PANEL
Fig. 15 — Typical Access Panel Locations
12
x
o
B
d
o
o
H
Fig. 16 — Hood Box Removal
HOOD BOX BRACKET
INDOOR COIL ACCESS PANEL
CAULK HERE
SIDE PANEL
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
5. Remove the shipping tape holding the economizer barometric relief damper in place.
6. Insert the hood divider between the hood sides. See Fig. 18 and 19. Secure hood divider with 2 screws on each hood side. The hood di vider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider) . Push the filter into position pa st th e op en fi lter c lip s . Cl ose the f ilt er c lip s to lock the filter into place. See Fig. 19.
8. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 17.
9. Replace the filter access panel.
10. Install all EconoMi$ er IV ac ces sori es. Ec onoM i$e r I V wiring is shown in Fig. 20.
Barometric flow capacity is shown in Fig. 21. Outdoor air leakage is shown in Fig. 22. Return air pressure drop is shown in Fig. 23.
D. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoo r-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor air­stream. See Fig. 14. The operating range of temperature measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 24. This sensor is factory installed. The operating range of temperature measurement is 0° to 158 F. See Table 5 for sensor temperature/resistance values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Outdoor Air Lockout Sensor The Economi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42 F ambient tem­perature. See Fig. 14.
Fig. 17 — Indoor Coil Access Panel Relocation
LEFT HOOD SIDE
B
24 9/16”
HOOD DIVIDER
SCREW
40 3/8”
Fig. 18 — Outdoor-Air Hood Construction
22 1/4”
DIVIDER
OUTSIDE AIR
HOOD
CLEANABLE
BAROMETRIC RELIEF
ALUMINUM FILTER
FILTER
Fig. 19 — Filter Installation
TOP PANEL
INDOOR COIL ACCESS PANEL
FILTER CLIP
13
FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK
LEGEND
DCV— Demand Controlled Ventilation IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT— Potentiometer RAT— Return-Air Temperature
Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
Table 5 — Supply Air Sensor
Temperature/Resistance Values
TEMPERATURE (F) RESISTANCE (ohms)
–58 200,250 –40 100,680 –22 53,010
–4 29,091 14 16,590 32 9,795 50 5,970 68 3,747 77 3,000
86 2,416 104 1,597 122 1,080 140 746 158 525 176 376 185 321 194 274 212 203 230 153 248 116 257 102 266 89 284 70 302 55
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT. to the minimum position.
Fig. 20 — EconoMi$er IV Wiring
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
30
25
20
15
10
5
0
FLOW IN CUBIC FEET PER MINUTE (cfm)
Fig. 22 — Outdoor Air Damper Leakage
0
0.05
0.15
STATIC PRESSURE (in. wg)
0.25
Fig. 21 — Barometric Flow Capacity
0.13 0.20 0.22 0. 25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
14
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0. 20 0.25 0.30 0.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 23 — Return Air Pressure Drop
SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION
SUPPLY AIR TEMPERATURE SENSOR
Fig. 24 — Supply Air Sensor Location
E. EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 6. The EconoMi$er IV is su pplied from the fa c­tory with a supply air temperature sensor and an outdoor air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit.
Table 6 — EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR
APPLICATION
Outdoor Air Dry Bulb
Differential Dry Bulb CRTEMPSN002A00*
Single Enthalpy HH57AC078
Differential Enthalpy
for DCV Control
CO
2
using a Wall-Mounted
Sensor
CO
2
CO
for DCV Control
2
using a Duct-Mounted
CO2 Sensor
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be needed for installation.
†33ZCSENCO2 is an accessory CO
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and
33ZCASPCO2 accessories.
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
and
sensor.
2
CRCBDIOX005A00††
OR
Outdoor Dry Bulb Changeover The standard controller is shipped from the factory configured
for outdoor dry bulb changeover control. The outdoor air and supply air tempe rature sensor s are included as standard. For this control mode, the outdoor temp erature is compa red to an adjustable set point sel ected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor-air dampers to minimum position. If the outdoor-air temperature is below the set point, the posi tion of the outdoor-air dampers will be con trol led to provi de free coo l­ing using outdoor air. When in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the cont rol. See Fig. 25. The scale on the potentiometer is A, B, C, and D. See Fig. 26 for the corre­sponding te mp e r ature changeover v a lue s.
Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional acces­sory dry bulb sensor (part number CRTEMPSN002A00). The accessory senso r must be mounted in the return airstream. See Fig. 27. Wiring is provided in th e EconoMi$e r IV wiring harness. See Fig. 20.
In this mode of operation, the outdoor-air temperature is compared to the return-air temper ature and the lower tem­perature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy set point potentiom­eter fully clockwise to the D setting. See Fig. 25.
Outdoor Enthalpy Changeover For enthalpy control, accessory enthalpy sensor (part num-
ber HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 14. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the ou tdoor enthalpy set poi nt potentiome­ter on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 28. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. See Fig. 14 and 29.
Differential Ent halpy Control For differential enthalpy control, the EconoMi$ er IV co ntrol -
ler uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return a ir enthalpy to de termine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sen­sor with the acc essor y enth alpy senso r in th e same mou nting location. See Fig. 14. Mount th e return air enthalpy sen sor in the return air duct. See Fig. 27. Wiring is provide d in the EconoMi$er IV wiring harness. See Fig. 20. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting.
15
Fig. 25 — EconoMi$er IV Controller Potentiometer
and LED Locations
19
LED ON
mA
14
18
17
16
15
13
12
11
10
9
40
LED OFF
45
D
50
60
55
DEGREES FAHRENHEIT
LED ON
C
LED OFF
65
70
LED ON
LED OFF
75
B
LED ON
A
LED OFF
100
90
95
85
80
Fig. 26 — Outside Air Temperature Changeover Set Points
ECONOMI$ER IV CONTROLLER
ECONOMI$ER IV
GROMMET
RETURN AIR SENSOR
RETURN DUCT (FIELD-PROVIDED)
Fig. 27 — Return Air Temperature or Enthalpy
Sensor Mounting Location
Indoor Air Quality (IAQ) Sensor Input The IAQ input can be used for demand control ventilation
control based on the l evel of CO
measured in the space or
2
return air duct. Mount the accessory IAQ s ensor according to ma nufacturer
specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. See Fig. 30.
If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.
Exhaust Set Point Adjustment The exhaust set point will determine when the exhaust fan
runs based on d am p er po sit i on ( if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 25. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unneces sary fan overload.
Minimum Position C o ntrol There is a minimum damper position potentiometer on the
EconoMi$er IV c o nt ro ll er. See Fig. 25. The minimum damper position maintains the minimum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper posi­tion represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occu­pied ventilation.
When demand ventilation control is not being used, the min­imum position potentiometer should be used to set the occu­pied ventilation position. The maximum demand ventilation position should be turned fully clock wi se.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F temperature difference betwee n the out­door and return-air temperatures.
To determine the minimum position setting, perform the following procedure:
1. Calculate the appropriate mixed air temperature using the following formula:
OA
(T T
x
O
O
)+ (TR x
100 100
= Outdoor-Air Temperature
RA
) = T
M
OA = Percent of Outdoor Air
= Return-Air Temperature
T
R
RA = Percent of Return Air TM = Mixed-Air Temperature As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F.
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper posi­tioning is being used, make sure that the terminals are wired according to Fig. 20 and that the minimum position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer until the measured mixed-air temperature matches the calculated value.
6. Reconnect the supply-air sensor to terminals T and T1.
16
CONTROL
CURVE
4
1
2
1
A B C D
8
1
6
1
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
P
L
HA
26
NT
E
4
2
2
2
0
2
40 (4)
35 (2)
Y
85
(29)90(32)95(35)
46
4
4
42
40
IR
8
3
Y A
6
DR
3
D
N
U
4
3
PO
R
32
E
P
TU
30
B
28
60
(16)
55
(13)
B
50
C
(10)
45
D
(7)
70
(21)
0
0
1
65
(18)
A
80
(27)
75
(24)
0
9
80
70
60
50
0
4
TIVE HUM
RELA
0
3
100 (38)
IDITY
20
(%
105
110
(41)
(43)
)
0
1
N1
P1
T1
AQ1
SO+
SR+
D
35
40
45
50
55
60
65
70
75
80
(2)
(4)
(7)
(10)
(13)
(16)
(18)
(21)
(24)
85
(27)
(29)90(32)95(35)
100 (38)
105
(41)
110 (43)
HIGH LIMIT CURVE
A
B
C
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 28 — Enthalpy Changeover Set Points
CO SENSOR MAX RANGE SETTING
2
TR1
EXH
2V 10V
EXH
Open
2V 10V
DCV
2V 10V
Free Cool
B
A
DCV
DCV
C
D
Set
Min Pos
Max
Set
N
P
T
AQ
SO
SR
TR
24
24 Vac
Vac
COM
HOT
_
+
12
5
4
3
EF1
EF
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
Fig. 30 — CO
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Sensor Maximum Range Setting
2
800 ppm 900 ppm 1000 ppm 1100 ppm
Fig. 29 — EconoMi$er IV Control
17
Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part num­ber S963B1128) is wired to the E co no Mi$er IV controller, the minimum position of the damper can be controlled from a remote location.
To control the minimum damper position remotely, remove the factory-insta lled jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied poten­tiometer to the P and P1 termina ls on the EconoMi$er IV controller. See Fig. 29.
Damper Movement Damper movement from full open to full closed (or vice
1
versa) takes 2
/2 minutes. Thermostats The EconoMi$er IV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
Occupancy Control The factor y default configuration for the EconoMi$er IV con-
trol is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccu­pied mode is desired, install a field-supplied timeclock func­tion in place of the jumper between TR and N. See Fig. 20. When the timeclock contacts are clos ed, the EconoMi$e r IV control will be in occupied mode. When the timeclock con­tacts are open (r emoving the 24-v signal from terminal N), the EconoMi$er IV will be in un occupied mode.
Demand Controlled Ventilation (DCV) When using the Ec onoM i $er I V for dem a nd cont roll e d ven ti -
lation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must b e eva lua ted for de sig n c ondi tions. T he maxi mum damper position must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.
A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipmen t that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate mea ns the equipmen t can conditi on air at a maximum ventilation rate that is great er than the required ventilation rate for maximum occupancy. A proportional­anticipatory strategy will cause the fresh air supplied to increase as the room CO CO
set point has not been reached. By the time the CO
2
level increases even though the
2
level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.
In order to have the CO
sensor control the economizer
2
damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventila tion is the ventilation required to remove contaminants during unoccupied periods. The following equation may be u sed to determine the percent of outside-air entering the building for a given damper position. For best results there should be at
least a 10 degree difference in outside and return-air temperatures.
OA
(T T
x
O
O
)+ (TR x
100 100
= Outdoor-Air Temperature
RA
) = T
M
OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature
Once base ventilation has been determined, set the mini­mum damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to th e ac t uato r provi des a ba se ve ntil at io n rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 30 to determine the maximum setting of the CO For example, a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 30 to find the point when the CO
sensor output will be 6.7 volts. Line up
2
the point on the graph with the left side of the chart to deter­mine that the range configuration for the CO
2
be 1800 ppm. The Eco noMi$er IV control ler will output the
6.7 volts f rom the CO
sensor to the actuator when the C O
2
concentration in the spac e is at 1100 ppm . The DC V set po int may be left at 2 volts since the CO2 sensor voltag e will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.
Once the fully occupied damper position has been deter­mined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maxim um position as this can result in over-ventilation to the space and potential high-humidity levels.
CO
Sensor Configuration
2
The CO2 sensor has preset standard voltage settings that can be selected anytime afte r the sensor is pow ered up. See Table 7.
Use setting 1 or 2 for Bryant equipment. See Table 7.
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See Table 7.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed any-
2
time after the sensor is en ergized. Follow the steps belo w to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec-
2
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
sensor.
2
sensor sho uld
2
18
Table 7 — CO2 Sensor Standard Settings
SETTING EQUIPMENT OUTPUT
1
Interface w/Standard
2 Proportional Any
Building Control System
3 Exponential Any
4
5 Proportional 20
Economizer
6 Exponential 15
7 Exponential 20
8 Health & Safety Proportional
Parking/Air Intakes/
9
Loading Docks
LEGEND
ppm — Parts Per Million
Proportional Any
Proportional 15
Proportional
VENTILATION
RATE
(cfm/Person)
Dehumidification of Fresh Air with DCV Control Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some applications, an energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the nor­mal heating and coolin g processe s are more than ade quate t o remove the humidity loads for most commercial applications.
If normal rooftop heating and cooling operation is not ade­quate for the outdoor humidity level, an energy recovery unit and/or a dehum idification opti on should be considered.
VII. STEP 7 — ADJUST INDOOR-FAN SPEED
Adjust the indoor -fa n spee d to me et j obsi te requir eme nts. For units with electric heat, required minimum cfm is
2250 for 549B090 and 102 and 3000 for 549B120 with the following except io ns :
UNIT
549B
120
UNIT
VO LTAGE
208/230 42.4 Horizontal 3200 208/230 50.0 Horizontal 3200
460 50.0
HEATER
kW
UNIT
CONFIG-
URATION
Horizontal
or
Vertical
REQUIRED
MINIMUM
CFM
3200
ANALOG
OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
CO
CONTROL RANGE
2
(ppm)
0-2000 1000 50
0-2000 1000 50
0-2000 1100 50
0-1100 1100 50
0- 900 900 50
0-1100 1100 50
0- 900 900 50
0-9999 5000 500
0-2000 700 50
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
Table 8 shows indoor-fan moto r data . Table 9 s hows fa n rpm at motor pulley settings for standard and alternate motors. Tables 10 and 11 show FIOP/accessory static pressure. Refer to Tables 12-23 to determine fan speed settings. Fan motor pulleys are factory set for speed shown in Table 1.
To change fan speed s:
1. Shut off the unit power supply and tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts See Fig. 31 and 32.
3. Loosen the movable pulley flange setscrew (see Fig. 33).
4. Screw the movable flange toward the fixed flange to increase speed and away from the fixed flange to decrease speed. Increasing fan speed increases the load on the motor. Do not exceed the maximum speed specified in Table 1.
5. Set the movable flange at the nea rest keyway of the pulley hub and tighten the setscrew. (See Table 1 for speed change for each full turn of the pulley flange.)
To align fan and motor pulleys:
1. Loosen the fan pulley setscrews.
2. Slide the fan pulley along the fan shaft.
3. Make angular alignm ent by loo se ning the mo t or fro m the mounting plate.
19
To adjust belt tension:
1. Loosen the fan motor mounting plate nuts.
2. Size 090 and 102 — Slide the motor mounting plate away from the fan scroll for prop er belt tension (5/8-in. deflection with 8 to 10 lb of force) and tighten the mounting nuts (see Fig. 31).
Size 120 — Slide the motor mounting plate down-
5
ward to tighten belt tension (
/8-in. deflection with 5 to 10 lb of force). Secure the motor mounting plate nuts. See Fig. 32.
3. Adjust the bolt and nut on the mounting plate to secure the motor in a fixed position.
MOTOR MOUNTING
PLATE NUTS
Fig. 32 — Typical Belt-Drive Motor
Mounting for Size 120
Fig. 31 — Typical Belt-Drive Motor
Mounting for Sizes 090 and 102
Fig. 33 — Indoor-Fan Pulley Adjustment
Table 8 — Indoor-Fan Motor Performance
UNIT
549B
090 and
102
120
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors
can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
INDOOR-FAN
MOTOR
Standard
High Static
Standard
High Static
UNIT
VOLTAGE
208/230
460 3.9
208/230
460 5.5
208/230
460 5.5
208/230
460 8.5
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
2.90 2615
4.20 3313
3.70 3313
5.25 4400
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
8.6
11.7
11.7
17.3
20
Table 9 — Fan Rpm at Motor Pulley Settings*
UNIT
549B
1
0
/
2
11
1
/
2
MOTOR PULLEY TURNS OPEN
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
090† 950 930 905 885 865 840 820 795 775 750 730 090** 1080 1060 1035 1015 990 970 950 925 905 880 860 102† 1085 1061 1036 1012 987 963 938 914 889 865 840 102** 1080 1058 1036 1014 992 970 948 926 904 882 860 120† 1080 1060 1035 1015 990 970 950 925 905 880 860 120** 1130 1112 1087 1062 1037 1212 987 962 937 912 887 862 830
*Approximate fan rpm shown.
†Indicates standard motor and drive package.
**Indicates high-static motor and drive package.
Table 10 — Accessory/FIOP Electric Heaters Static Pressure* (in. wg) — 549B090-120
COMPONENT
2250 2500 3000 3500 4000 4500 5000 5500 6000 6250 1 Heater Module 0.02 0.03 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.17 2 Heater Modules 0.03 0.05 0.07 0.09 0.12 0.14 0.16 0.19 0.21 0.20
LEGEND
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Fan Performance tables to deter­mine blower rpm and watts.
CFM
6
Table 11 — Accessory/FIOP EconoMi$er IV Static Pressure* (in. wg)
COMPONENT
2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 6250 Vertical EconoMi$er IV 0.06 0.075 0.09 0.115 0.13 0.15 0.17 0.195 0.22 0.25 0.285 0.325 0.36 Horizontal EconoMi$er IV 0.1 0.125 0.15 0.18 0.21 0.25 0.275 0.3 0.34 0.388
LEGEND FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm
should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.
CFM
GENERAL FAN PERFORMANCE NOTES
1. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional informa­tion on motor performance refer to Fan Motor Performance, Table 8.
2. Values include losses for filters, unit casing, and wet coils. See Tables 10 and 11 for FIOP/accessory static pressure information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.
4. Interpolation is permissible. Do not extrapolate.
21
Table 12 — Fan Performance 549B090 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
2250 511 0.53 492 591 0.73 680 660 0.95 885 722 1.19 1106 779 1.44 1342 2300 519 0.56 518 597 0.76 709 666 0.98 916 727 1.22 1140 784 1.48 1378 2400 534 0.61 571 611 0.82 768 678 1.05 982 739 1.30 1210 795 1.56 1453 2500 550 0.67 629 624 0.89 832 690 1.13 1051 750 1.38 1285 805 1.64 1533 2550 558 0.71 660 631 0.93 866 697 1.17 1088 756 1.42 1324 811 1.69 1574 2600 565 0.74 691 638 0.97 901 703 1.21 1125 762 1.46 1365 816 1.73 1617 2700 581 0.81 758 652 1.04 974 716 1.29 1204 774 1.55 1449 828 1.83 1707 2800 597 0.89 829 667 1.13 1051 729 1.38 1287 786 1.65 1538 839 1.93 1801 2900 613 0.97 905 681 1.22 1133 742 1.48 1376 799 1.75 1632 851 2.04 1900 3000 630 1.06 985 696 1.31 1220 756 1.58 1469 811 1.86 1731 863 2.15 2004 3100 646 1.15 1071 711 1.41 1313 770 1.68 1568 824 1.97 1835 875 2.27 2114 3200 663 1.25 1162 726 1.51 1411 784 1.79 1672 837 2.09 1944 888 2.39 2229 3300 679 1.35 1259 741 1.62 1514 798 1.91 1781 851 2.21 2060 900 2.52 2351 3400 696 1.46 1361 756 1.74 1623 812 2.03 1896 864 2.34 2181 913 2.66 2478 3500 713 1.58 1469 772 1.86 1737 827 2.16 2017 878 2.48 2308 926 2.80 2610 3600 729 1.70 1583 787 1.99 1857 841 2.30 2144 892 2.62 2441 3700 746 1.83 1703 803 2.13 1985 856 2.44 2277 906 2.77 2580 3750 755 1.89 1766 811 2.20 2051 864 2.52 2346 913 2.84 2653
AIRFLOW
CFM
2250 832 1.71 1592 882 1.99 1855 928 2.29 2131 973 2.59 2420 ——— 2300 837 1.75 1630 886 2.03 1896 933 2.33 2174 977 2.64 2463 ——— 2400 847 1.83 1710 896 2.12 1980 942 2.43 2262 986 2.74 2556 ——— 2500 857 1.92 1794 905 2.22 2069 951 2.52 2355 995 2.84 2653 ——— 2550 862 1.97 1838 910 2.27 2114 956 2.58 2403 999 2.90 2704 ——— 2600 867 2.02 1884 915 2.32 2162 961 2.63 2453 —————— 2700 878 2.12 1978 926 2.42 2261 971 2.74 2556 —————— 2800 889 2.23 2077 936 2.54 2365 981 2.86 2664 —————— 2900 900 2.34 2181 947 2.65 2474 3000 912 2.46 2290 958 2.78 2588 ————————— 3100 923 2.58 2406 969 2.90 2708 ————————— 3200 935 2.71 2526 3300 947 2.84 2652 3400 ——————————————— 3500 ——————————————— 3600 ——————————————— 3700 ——————————————— 3750 ———————————————
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 730 to 950 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 21 for general fan performance notes.
22
Table 13 — Fan Performance 549B090 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
2250 511 0.53 492 591 0.73 680 660 0.95 885 722 1.19 1106 779 1.44 1342 2300 519 0.56 518 597 0.76 709 666 0.98 916 727 1.22 1140 784 1.48 1378 2400 534 0.61 571 611 0.82 768 678 1.05 982 739 1.30 1210 795 1.56 1453 2500 550 0.67 629 624 0.89 832 690 1.13 1051 750 1.38 1285 805 1.64 1533 2550 558 0.71 660 631 0.93 866 697 1.17 1088 756 1.42 1324 811 1.69 1574 2600 565 0.74 691 638 0.97 901 703 1.21 1125 762 1.46 1365 816 1.73 1617 2700 581 0.81 758 652 1.04 974 716 1.29 1204 774 1.55 1449 828 1.83 1707 2800 597 0.89 829 667 1.13 1051 729 1.38 1287 786 1.65 1538 839 1.93 1801 2900 613 0.97 905 681 1.22 1133 742 1.48 1376 799 1.75 1632 851 2.04 1900 3000 630 1.06 985 696 1.31 1220 756 1.58 1469 811 1.86 1731 863 2.15 2004 3100 646 1.15 1071 711 1.41 1313 770 1.68 1568 824 1.97 1835 875 2.27 2114 3200 663 1.25 1162 726 1.51 1411 784 1.79 1672 837 2.09 1944 888 2.39 2229 3300 679 1.35 1259 741 1.62 1514 798 1.91 1781 851 2.21 2060 900 2.52 2351 3400 696 1.46 1361 756 1.74 1623 812 2.03 1896 864 2.34 2181 913 2.66 2478 3500 713 1.58 1469 772 1.86 1737 827 2.16 2017 878 2.48 2308 926 2.80 2610 3600 729 1.70 1583 787 1.99 1857 841 2.30 2144 892 2.62 2441 939 2.95 2749 3700 746 1.83 1703 803 2.13 1985 856 2.44 2277 906 2.77 2580 953 3.10 2894 3750 755 1.89 1766 811 2.20 2051 864 2.52 2346 913 2.84 2653 959 3.18 2969
AIRFLOW
CFM
2250 832 1.71 1592 882 1.99 1855 928 2.29 2131 973 2.59 2420 1015 2.92 2720 2300 837 1.75 1630 886 2.03 1896 933 2.33 2174 977 2.64 2463 1020 2.97 2766 2400 847 1.83 1710 896 2.12 1980 942 2.43 2262 986 2.74 2556 1028 3.07 2861 2500 857 1.92 1794 905 2.22 2069 951 2.52 2355 995 2.84 2653 1037 3.18 2962 2550 862 1.97 1838 910 2.27 2114 956 2.58 2403 999 2.90 2704 1041 3.23 3014 2600 867 2.02 1884 915 2.32 2162 961 2.63 2453 1004 2.95 2755 1045 3.29 3068 2700 878 2.12 1978 926 2.42 2261 971 2.74 2556 1013 3.07 2862 1055 3.41 3180 2800 889 2.23 2077 936 2.54 2365 981 2.86 2664 1023 3.19 2975 1064 3.54 3297 2900 900 2.34 2181 947 2.65 2474 991 2.98 2778 1033 3.32 3094 1073 3.67 3419 3000 912 2.46 2290 958 2.78 2588 1001 3.11 2897 1043 3.45 3217 1083 3.80 3547 3100 923 2.58 2406 969 2.90 2708 1012 3.24 3022 1053 3.59 3347 1093 3.95 3682 3200 935 2.71 2526 980 3.04 2834 1023 3.38 3152 1064 3.73 3482 1103 4.10 3821 3300 947 2.84 2652 992 3.18 2966 1034 3.53 3289 1075 3.89 3623 3400 959 2.99 2785 1003 3.33 3103 1045 3.68 3432 1086 4.04 3771 ——— 3500 972 3.13 2923 1015 3.48 3246 1057 3.84 3581 3600 984 3.29 3068 1027 3.64 3396 1068 4.01 3736 3700 997 3.45 3218 1040 3.81 3553 1080 4.18 3897 3750 1004 3.54 3296 1046 3.90 3633
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 21 for general fan performance notes.
23
Table 14 — Fan Performance 549B102 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
2500 489 0.41 386 564 0.54 506 629 0.67 625 688 0.80 745 741 0.93 866 2600 502 0.45 424 576 0.59 548 640 0.72 672 697 0.85 797 750 0.99 923 2700 515 0.50 465 587 0.64 594 650 0.77 723 707 0.91 852 760 1.05 982 2800 529 0.55 508 599 0.69 642 661 0.83 776 718 0.98 910 769 1.12 1044 2900 542 0.59 555 611 0.74 693 672 0.89 832 728 1.04 970 779 1.19 1109 3000 556 0.65 604 623 0.80 748 684 0.95 891 738 1.11 1034 789 1.26 1177 3100 569 0.70 656 636 0.86 805 695 1.02 953 749 1.18 1100 799 1.34 1249 3200 583 0.76 712 648 0.93 865 707 1.09 1018 760 1.26 1170 809 1.42 1323 3300 597 0.83 770 661 1.00 929 718 1.17 1086 771 1.33 1244 820 1.50 1401 3400 611 0.89 832 674 1.07 996 730 1.24 1158 782 1.42 1320 831 1.59 1483 3500 625 0.96 898 687 1.14 1066 742 1.32 1233 794 1.50 1400 841 1.68 1567 3600 639 1.04 967 700 1.22 1140 754 1.41 1312 805 1.59 1484 852 1.78 1656 3700 654 1.11 1040 713 1.31 1218 767 1.50 1395 817 1.69 1571 863 1.87 1748 3800 668 1.20 1116 726 1.39 1299 779 1.59 1481 828 1.78 1662 874 1.98 1844 3900 683 1.28 1197 739 1.48 1385 792 1.69 1572 840 1.88 1758 886 2.08 1943 4000 697 1.37 1281 753 1.58 1474 804 1.79 1666 852 1.99 1857 897 2.20 2048 4100 712 1.47 1370 766 1.68 1567 817 1.89 1764 864 2.10 1960 909 2.31 2155 4200 726 1.57 1462 780 1.79 1665 830 2.00 1866 876 2.22 2067 920 2.43 2268 4300 741 1.67 1559 794 1.89 1767 843 2.12 1973 889 2.34 2179 932 2.56 2384
AIRFLOW
CFM
2500 791 1.06 988 837 1.19 1112 881 1.33 1236 922 1.46 1362 962 1.60 1490 2600 799 1.12 1049 845 1.26 1177 889 1.40 1306 930 1.54 1436 969 1.68 1568 2700 808 1.19 1113 854 1.34 1245 897 1.48 1378 938 1.62 1513 977 1.77 1648 2800 817 1.26 1179 863 1.41 1316 905 1.56 1454 946 1.71 1592 985 1.86 1732 2900 827 1.34 1249 872 1.49 1390 914 1.64 1532 954 1.80 1675 993 1.95 1819 3000 836 1.42 1322 881 1.57 1467 923 1.73 1613 963 1.89 1761 1001 2.05 1909 3100 846 1.50 1398 890 1.66 1547 932 1.82 1698 972 1.98 1849 1010 2.15 2002 3200 856 1.58 1477 899 1.75 1631 941 1.92 1786 980 2.08 1942 1018 2.25 2099 3300 866 1.67 1559 909 1.84 1718 950 2.01 1878 989 2.19 2038 1027 2.36 2199 3400 876 1.76 1645 919 1.94 1808 960 2.12 1972 998 2.29 2137 1036 2.47 2303 3500 886 1.86 1734 929 2.04 1902 969 2.22 2071 1008 2.40 2240 1045 2.58 2410 3600 897 1.96 1827 939 2.14 2000 979 2.33 2173 1017 2.52 2347 1054 2.70 2521 3700 907 2.06 1924 949 2.25 2101 989 2.44 2279 1027 2.63 2457 1063 2.83 2636 3800 918 2.17 2025 959 2.37 2207 999 2.56 2389 1036 2.76 2571 3900 929 2.28 2130 970 2.48 2316 1009 2.68 2502 1046 2.88 2690 4000 940 2.40 2238 980 2.61 2429 1019 2.81 2620 4100 951 2.52 2351 991 2.73 2547 4200 962 2.65 2468 1002 2.86 2668 4300 973 2.78 2589
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 21 for general fan performance notes.
24
Table 15 — Fan Performance 549B102 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
2500 489 0.41 386 564 0.54 506 629 0.67 625 688 0.80 745 741 0.93 866 2600 502 0.45 424 576 0.59 548 640 0.72 672 697 0.85 797 750 0.99 923 2700 515 0.50 465 587 0.64 594 650 0.77 723 707 0.91 852 760 1.05 982 2800 529 0.55 508 599 0.69 642 661 0.83 776 718 0.98 910 769 1.12 1044 2900 542 0.59 555 611 0.74 693 672 0.89 832 728 1.04 970 779 1.19 1109 3000 556 0.65 604 623 0.80 748 684 0.95 891 738 1.11 1034 789 1.26 1177 3100 569 0.70 656 636 0.86 805 695 1.02 953 749 1.18 1100 799 1.34 1249 3200 583 0.76 712 648 0.93 865 707 1.09 1018 760 1.26 1170 809 1.42 1323 3300 597 0.83 770 661 1.00 929 718 1.17 1086 771 1.33 1244 820 1.50 1401 3400 611 0.89 832 674 1.07 996 730 1.24 1158 782 1.42 1320 831 1.59 1483 3500 625 0.96 898 687 1.14 1066 742 1.32 1233 794 1.50 1400 841 1.68 1567 3600 639 1.04 967 700 1.22 1140 754 1.41 1312 805 1.59 1484 852 1.78 1656 3700 654 1.11 1040 713 1.31 1218 767 1.50 1395 817 1.69 1571 863 1.87 1748 3800 668 1.20 1116 726 1.39 1299 779 1.59 1481 828 1.78 1662 874 1.98 1844 3900 683 1.28 1197 739 1.48 1385 792 1.69 1572 840 1.88 1758 886 2.08 1943 4000 697 1.37 1281 753 1.58 1474 804 1.79 1666 852 1.99 1857 897 2.20 2048 4100 712 1.47 1370 766 1.68 1567 817 1.89 1764 864 2.10 1960 909 2.31 2155 4200 726 1.57 1462 780 1.79 1665 830 2.00 1866 876 2.22 2067 920 2.43 2268 4300 741 1.67 1559 794 1.89 1767 843 2.12 1973 889 2.34 2179 932 2.56 2384
AIRFLOW
(Cfm)
2500 791 1.06 988 837 1.19 1112 881 1.33 1236 922 1.46 1362 962 1.60 1490 2600 799 1.12 1049 845 1.26 1177 889 1.40 1306 930 1.54 1436 969 1.68 1568 2700 808 1.19 1113 854 1.34 1245 897 1.48 1378 938 1.62 1513 977 1.77 1648 2800 817 1.26 1179 863 1.41 1316 905 1.56 1454 946 1.71 1592 985 1.86 1732 2900 827 1.34 1249 872 1.49 1390 914 1.64 1532 954 1.80 1675 993 1.95 1819 3000 836 1.42 1322 881 1.57 1467 923 1.73 1613 963 1.89 1761 1001 2.05 1909 3100 846 1.50 1398 890 1.66 1547 932 1.82 1698 972 1.98 1849 1010 2.15 2002 3200 856 1.58 1477 899 1.75 1631 941 1.92 1786 980 2.08 1942 1018 2.25 2099 3300 866 1.67 1559 909 1.84 1718 950 2.01 1878 989 2.19 2038 1027 2.36 2199 3400 876 1.76 1645 919 1.94 1808 960 2.12 1972 998 2.29 2137 1036 2.47 2303 3500 886 1.86 1734 929 2.04 1902 969 2.22 2071 1008 2.40 2240 1045 2.58 2410 3600 897 1.96 1827 939 2.14 2000 979 2.33 2173 1017 2.52 2347 1054 2.70 2521 3700 907 2.06 1924 949 2.25 2101 989 2.44 2279 1027 2.63 2457 1063 2.83 2636 3800 918 2.17 2025 959 2.37 2207 999 2.56 2389 1036 2.76 2571 1073 2.95 2755 3900 929 2.28 2130 970 2.48 2316 1009 2.68 2502 1046 2.88 2690 1082 3.09 2877 4000 940 2.40 2238 980 2.61 2429 1019 2.81 2620 1056 3.02 2812 1092 3.22 3004 4100 951 2.52 2351 991 2.73 2547 1029 2.94 2743 1066 3.15 2939 1102 3.36 3136 4200 962 2.65 2468 1002 2.86 2668 1040 3.08 2869 1076 3.29 3070 1112 3.51 3271 4300 973 2.78 2589 1013 3.00 2794 1050 3.22 2999 1087 3.44 3205 1122 3.66 3411
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.20.40.60.81.0
1.21.41.61.82.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 21 for general fan performance notes.
25
Table 16 — Fan Performance 549B120 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
3000 556 0.65 604 623 0.80 748 684 0.95 891 738 1.11 1034 789 1.26 1177 3100 569 0.70 656 636 0.86 805 695 1.02 953 749 1.18 1100 799 1.34 1249 3200 583 0.76 712 648 0.93 865 707 1.09 1018 760 1.26 1170 809 1.42 1323 3300 597 0.83 770 661 1.00 929 718 1.17 1086 771 1.33 1244 820 1.50 1401 3400 611 0.89 832 674 1.07 996 730 1.24 1158 782 1.42 1320 831 1.59 1483 3500 625 0.96 898 687 1.14 1066 742 1.32 1233 794 1.50 1400 841 1.68 1567 3600 639 1.04 967 700 1.22 1140 754 1.41 1312 805 1.59 1484 852 1.78 1656 3700 654 1.11 1040 713 1.31 1218 767 1.50 1395 817 1.69 1571 863 1.87 1748 3800 668 1.20 1116 726 1.39 1299 779 1.59 1481 828 1.78 1662 874 1.98 1844 3900 683 1.28 1197 739 1.48 1385 792 1.69 1572 840 1.88 1758 886 2.08 1943 4000 697 1.37 1281 753 1.58 1474 804 1.79 1666 852 1.99 1857 897 2.20 2048 4100 712 1.47 1370 766 1.68 1567 817 1.89 1764 864 2.10 1960 909 2.31 2155 4200 726 1.57 1462 780 1.79 1665 830 2.00 1866 876 2.22 2067 920 2.43 2268 4300 741 1.67 1559 794 1.89 1767 843 2.12 1973 889 2.34 2179 932 2.56 2384 4400 755 1.78 1660 807 2.01 1873 856 2.23 2084 901 2.46 2295 944 2.69 2505 4500 770 1.89 1766 821 2.13 1984 869 2.36 2200 914 2.59 2415 956 2.82 2630 4600 785 2.01 1876 835 2.25 2099 882 2.49 2320 926 2.72 2541 968 2.96 2760 4700 800 2.14 1991 849 2.38 2219 895 2.62 2445 939 2.86 2670 980 3.10 2895 4800 815 2.26 2111 863 2.51 2344 909 2.76 2575 952 3.01 2805 993 3.25 3034 4900 829 2.40 2235 877 2.65 2473 922 2.91 2709 965 3.16 2944 1005 3.41 3178 5000 844 2.54 2365 891 2.80 2608 936 3.06 2849 978 3.31 3089 1018 3.57 3328
AIRFLOW
(Cfm)
3000 836 1.42 1322 881 1.57 1467 923 1.73 1613 963 1.89 1761 1001 2.05 1909 3100 846 1.50 1398 890 1.66 1547 932 1.82 1698 972 1.98 1849 1010 2.15 2002 3200 856 1.58 1477 899 1.75 1631 941 1.92 1786 980 2.08 1942 1018 2.25 2099 3300 866 1.67 1559 909 1.84 1718 950 2.01 1878 989 2.19 2038 1027 2.36 2199 3400 876 1.76 1645 919 1.94 1808 960 2.12 1972 998 2.29 2137 1036 2.47 2303 3500 886 1.86 1734 929 2.04 1902 969 2.22 2071 1008 2.40 2240 1045 2.58 2410 3600 897 1.96 1827 939 2.14 2000 979 2.33 2173 1017 2.52 2347 1054 2.70 2521 3700 907 2.06 1924 949 2.25 2101 989 2.44 2279 1027 2.63 2457 1063 2.83 2636 3800 918 2.17 2025 959 2.37 2207 999 2.56 2389 1036 2.76 2571 1073 2.95 2755 3900 929 2.28 2130 970 2.48 2316 1009 2.68 2502 1046 2.88 2690 1082 3.09 2877 4000 940 2.40 2238 980 2.61 2429 1019 2.81 2620 1056 3.02 2812 1092 3.22 3004 4100 951 2.52 2351 991 2.73 2547 1029 2.94 2743 1066 3.15 2939 1102 3.36 3136 4200 962 2.65 2468 1002 2.86 2668 1040 3.08 2869 1076 3.29 3070 1112 3.51 3271 4300 973 2.78 2589 1013 3.00 2794 1050 3.22 2999 1087 3.44 3205 1122 3.66 3411 4400 985 2.91 2715 1024 3.14 2924 1061 3.36 3134 1097 3.59 3345 ——— 4500 996 3.05 2845 1035 3.28 3059 1072 3.51 3274 4600 1008 3.20 2979 1046 3.43 3199 1083 3.67 3418 —————— 4700 1020 3.34 3119 1058 3.58 3343 4800 1032 3.50 3263 4900 1044 3.66 3413 5000 ———————————————
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 21 for general fan performance notes.
26
Table 17 — Fan Performance 549B120 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
3000 556 0.65 604 623 0.80 748 684 0.95 891 738 1.11 1034 789 1.26 1177 3100 569 0.70 656 636 0.86 805 695 1.02 953 749 1.18 1100 799 1.34 1249 3200 583 0.76 712 648 0.93 865 707 1.09 1018 760 1.26 1170 809 1.42 1323 3300 597 0.83 770 661 1.00 929 718 1.17 1086 771 1.33 1244 820 1.50 1401 3400 611 0.89 832 674 1.07 996 730 1.24 1158 782 1.42 1320 831 1.59 1483 3500 625 0.96 898 687 1.14 1066 742 1.32 1233 794 1.50 1400 841 1.68 1567 3600 639 1.04 967 700 1.22 1140 754 1.41 1312 805 1.59 1484 852 1.78 1656 3700 654 1.11 1040 713 1.31 1218 767 1.50 1395 817 1.69 1571 863 1.87 1748 3800 668 1.20 1116 726 1.39 1299 779 1.59 1481 828 1.78 1662 874 1.98 1844 3900 683 1.28 1197 739 1.48 1385 792 1.69 1572 840 1.88 1758 886 2.08 1943 4000 697 1.37 1281 753 1.58 1474 804 1.79 1666 852 1.99 1857 897 2.20 2048 4100 712 1.47 1370 766 1.68 1567 817 1.89 1764 864 2.10 1960 909 2.31 2155 4200 726 1.57 1462 780 1.79 1665 830 2.00 1866 876 2.22 2067 920 2.43 2268 4300 741 1.67 1559 794 1.89 1767 843 2.12 1973 889 2.34 2179 932 2.56 2384 4400 755 1.78 1660 807 2.01 1873 856 2.23 2084 901 2.46 2295 944 2.69 2505 4500 770 1.89 1766 821 2.13 1984 869 2.36 2200 914 2.59 2415 956 2.82 2630 4600 785 2.01 1876 835 2.25 2099 882 2.49 2320 926 2.72 2541 968 2.96 2760 4700 800 2.14 1991 849 2.38 2219 895 2.62 2445 939 2.86 2670 980 3.10 2895 4800 815 2.26 2111 863 2.51 2344 909 2.76 2575 952 3.01 2805 993 3.25 3034 4900 829 2.40 2235 877 2.65 2473 922 2.91 2709 965 3.16 2944 1005 3.41 3178 5000 844 2.54 2365 891 2.80 2608 936 3.06 2849 978 3.31 3089 1018 3.57 3328
AIRFLOW
(Cfm)
3000 836 1.42 1322 881 1.57 1467 923 1.73 1613 963 1.89 1761 1001 2.05 1909 3100 846 1.50 1398 890 1.66 1547 932 1.82 1698 972 1.98 1849 1010 2.15 2002 3200 856 1.58 1477 899 1.75 1631 941 1.92 1786 980 2.08 1942 1018 2.25 2099 3300 866 1.67 1559 909 1.84 1718 950 2.01 1878 989 2.19 2038 1027 2.36 2199 3400 876 1.76 1645 919 1.94 1808 960 2.12 1972 998 2.29 2137 1036 2.47 2303 3500 886 1.86 1734 929 2.04 1902 969 2.22 2071 1008 2.40 2240 1045 2.58 2410 3600 897 1.96 1827 939 2.14 2000 979 2.33 2173 1017 2.52 2347 1054 2.70 2521 3700 907 2.06 1924 949 2.25 2101 989 2.44 2279 1027 2.63 2457 1063 2.83 2636 3800 918 2.17 2025 959 2.37 2207 999 2.56 2389 1036 2.76 2571 1073 2.95 2755 3900 929 2.28 2130 970 2.48 2316 1009 2.68 2502 1046 2.88 2690 1082 3.09 2877 4000 940 2.40 2238 980 2.61 2429 1019 2.81 2620 1056 3.02 2812 1092 3.22 3004 4100 951 2.52 2351 991 2.73 2547 1029 2.94 2743 1066 3.15 2939 1102 3.36 3136 4200 962 2.65 2468 1002 2.86 2668 1040 3.08 2869 1076 3.29 3070 1112 3.51 3271 4300 973 2.78 2589 1013 3.00 2794 1050 3.22 2999 1087 3.44 3205 1122 3.66 3411 4400 985 2.91 2715 1024 3.14 2924 1061 3.36 3134 1097 3.59 3345 1132 3.81 3555 4500 996 3.05 2845 1035 3.28 3059 1072 3.51 3274 1108 3.74 3489 1142 3.97 3704 4600 1008 3.20 2979 1046 3.43 3199 1083 3.67 3418 1118 3.90 3638 1152 4.14 3857 4700 1020 3.34 3119 1058 3.58 3343 1094 3.83 3567 1129 4.07 3792 1163 4.31 4016 4800 1032 3.50 3263 1069 3.74 3492 1105 3.99 3721 1140 4.24 3950 1174 4.48 4179 4900 1044 3.66 3413 1081 3.91 3646 1117 4.16 3880 1151 4.41 4113 1184 4.66 4347 5000 1056 3.82 3566 1093 4.08 3805 1128 4.34 4044 1162 4.59 4282 1195 4.85 4520
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.20.40.60.81.0
1.21.41.61.82.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 21 for general fan performance notes.
27
Table 18 — Fan Performance 549B090 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
2250 465 0.43 402 555 0.64 596 629 0.86 802 694 1.10 1021 753 1.34 1252 2300 471 0.45 421 560 0.66 618 634 0.89 828 699 1.13 1050 757 1.38 1283 2400 483 0.49 461 571 0.71 665 644 0.94 881 708 1.19 1109 766 1.45 1348 2500 495 0.54 503 581 0.77 715 654 1.01 937 717 1.26 1171 775 1.52 1416 2550 501 0.56 526 587 0.79 740 659 1.04 967 722 1.29 1204 779 1.56 1452 2600 507 0.59 549 592 0.82 767 664 1.07 996 727 1.33 1237 784 1.60 1488 2700 519 0.64 597 603 0.88 823 674 1.14 1059 737 1.40 1306 793 1.68 1563 2800 532 0.70 649 614 0.95 882 684 1.21 1125 746 1.48 1378 803 1.76 1641 2900 544 0.75 703 625 1.01 944 695 1.28 1194 756 1.56 1453 812 1.85 1723 3000 557 0.82 761 637 1.08 1009 705 1.36 1266 766 1.64 1533 822 1.94 1808 3100 570 0.88 823 648 1.16 1079 716 1.44 1342 776 1.73 1615 831 2.03 1897 3200 583 0.95 888 660 1.23 1151 727 1.53 1422 787 1.82 1702 841 2.13 1991 3300 596 1.03 957 672 1.32 1228 738 1.61 1506 797 1.92 1792 851 2.24 2088 3400 609 1.10 1030 684 1.40 1308 749 1.71 1593 808 2.02 1887 861 2.35 2188 3500 622 1.19 1106 696 1.49 1392 760 1.81 1685 818 2.13 1985 872 2.46 2294 3600 635 1.27 1187 708 1.59 1481 771 1.91 1781 829 2.24 2088 882 2.58 2403 3700 649 1.36 1272 720 1.69 1573 783 2.02 1881 840 2.35 2195 892 2.70 2517 3750 655 1.41 1316 726 1.74 1621 789 2.07 1932 845 2.41 2250 897 2.76 2575
AIRFLOW
(Cfm)
2250 806 1.60 1494 856 1.87 1747 903 2.15 2009 947 2.45 2282 988 2.75 2564 2300 811 1.64 1528 860 1.91 1784 907 2.20 2048 950 2.49 2323 992 2.80 2607 2400 819 1.71 1599 868 1.99 1859 915 2.28 2129 958 2.58 2410 1000 2.89 2698 2500 828 1.79 1672 877 2.08 1938 923 2.37 2214 966 2.68 2499 ——— 2550 832 1.83 1710 881 2.12 1979 927 2.42 2258 971 2.73 2545 ——— 2600 836 1.88 1749 885 2.17 2021 931 2.47 2302 975 2.78 2592 ——— 2700 845 1.96 1830 894 2.26 2107 940 2.57 2394 983 2.88 2689 ——— 2800 854 2.05 1914 903 2.36 2197 948 2.67 2488 2900 864 2.15 2002 912 2.46 2290 957 2.77 2587 —————— 3000 873 2.24 2093 921 2.56 2388 966 2.89 2691 —————— 3100 882 2.35 2189 930 2.67 2489 3200 892 2.45 2288 939 2.78 2595 3300 901 2.56 2391 948 2.90 2704 3400 911 2.68 2499 3500 921 2.80 2610 3600 ——————————————— 3700 ——————————————— 3750 ———————————————
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 730 to 950 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 21 for general fan performance notes.
28
Table 19 — Fan Performance 549B090 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
2250 465 0.43 402 555 0.64 596 629 0.86 802 694 1.10 1021 753 1.34 1252 2300 471 0.45 421 560 0.66 618 634 0.89 828 699 1.13 1050 757 1.38 1283 2400 483 0.49 461 571 0.71 665 644 0.94 881 708 1.19 1109 766 1.45 1348 2500 495 0.54 503 581 0.77 715 654 1.01 937 717 1.26 1171 775 1.52 1416 2550 501 0.56 526 587 0.79 740 659 1.04 967 722 1.29 1204 779 1.56 1452 2600 507 0.59 549 592 0.82 767 664 1.07 996 727 1.33 1237 784 1.60 1488 2700 519 0.64 597 603 0.88 823 674 1.14 1059 737 1.40 1306 793 1.68 1563 2800 532 0.70 649 614 0.95 882 684 1.21 1125 746 1.48 1378 803 1.76 1641 2900 544 0.75 703 625 1.01 944 695 1.28 1194 756 1.56 1453 812 1.85 1723 3000 557 0.82 761 637 1.08 1009 705 1.36 1266 766 1.64 1533 822 1.94 1808 3100 570 0.88 823 648 1.16 1079 716 1.44 1342 776 1.73 1615 831 2.03 1897 3200 583 0.95 888 660 1.23 1151 727 1.53 1422 787 1.82 1702 841 2.13 1991 3300 596 1.03 957 672 1.32 1228 738 1.61 1506 797 1.92 1792 851 2.24 2088 3400 609 1.10 1030 684 1.40 1308 749 1.71 1593 808 2.02 1887 861 2.35 2188 3500 622 1.19 1106 696 1.49 1392 760 1.81 1685 818 2.13 1985 872 2.46 2294 3600 635 1.27 1187 708 1.59 1481 771 1.91 1781 829 2.24 2088 882 2.58 2403 3700 649 1.36 1272 720 1.69 1573 783 2.02 1881 840 2.35 2195 892 2.70 2517 3750 655 1.41 1316 726 1.74 1621 789 2.07 1932 845 2.41 2250 897 2.76 2575
AIRFLOW
(Cfm)
2250 806 1.60 1494 856 1.87 1747 903 2.15 2009 947 2.45 2282 988 2.75 2564 2300 811 1.64 1528 860 1.91 1784 907 2.20 2048 950 2.49 2323 992 2.80 2607 2400 819 1.71 1599 868 1.99 1859 915 2.28 2129 958 2.58 2410 1000 2.89 2698 2500 828 1.79 1672 877 2.08 1938 923 2.37 2214 966 2.68 2499 1008 3.00 2793 2550 832 1.83 1710 881 2.12 1979 927 2.42 2258 971 2.73 2545 1012 3.05 2842 2600 836 1.88 1749 885 2.17 2021 931 2.47 2302 975 2.78 2592 1016 3.10 2891 2700 845 1.96 1830 894 2.26 2107 940 2.57 2394 983 2.88 2689 1024 3.21 2993 2800 854 2.05 1914 903 2.36 2197 948 2.67 2488 991 2.99 2790 1032 3.32 3099 2900 864 2.15 2002 912 2.46 2290 957 2.77 2587 1000 3.10 2894 1041 3.44 3209 3000 873 2.24 2093 921 2.56 2388 966 2.89 2691 1008 3.22 3003 1049 3.56 3323 3100 882 2.35 2189 930 2.67 2489 975 3.00 2798 1017 3.34 3115 1057 3.69 3441 3200 892 2.45 2288 939 2.78 2595 984 3.12 2909 1026 3.47 3233 1066 3.82 3564 3300 901 2.56 2391 948 2.90 2704 993 3.24 3024 1035 3.60 3353 1075 3.96 3690 3400 911 2.68 2499 958 3.02 2817 1002 3.37 3144 1044 3.73 3479 1084 4.10 3821 3500 921 2.80 2610 967 3.15 2935 1011 3.50 3268 1053 3.87 3608 3600 931 2.92 2726 977 3.28 3057 1021 3.64 3396 1062 4.01 3743 3700 941 3.05 2847 987 3.41 3184 1030 3.78 3529 1071 4.16 3882 3750 946 3.12 2908 992 3.48 3249 1035 3.86 3597
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.20.40.60.81.0
1.21.41.61.82.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 21 for general fan performance notes.
29
Table 20 — Fan Performance 549B102 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
2500 462 0.37 348 541 0.50 467 614 0.64 594 681 0.78 728 744 0.93 868 2600 474 0.41 381 551 0.54 505 622 0.68 635 688 0.83 773 750 0.98 916 2700 486 0.45 417 561 0.58 545 630 0.73 679 695 0.88 820 756 1.04 967 2800 498 0.49 456 571 0.63 587 639 0.78 725 702 0.93 870 762 1.09 1020 2900 510 0.53 497 581 0.68 632 648 0.83 774 710 0.99 922 768 1.15 1076 3000 523 0.58 541 592 0.73 680 657 0.88 825 718 1.05 977 775 1.22 1135 3100 536 0.63 587 603 0.78 730 666 0.94 879 726 1.11 1035 783 1.28 1196 3200 549 0.68 637 614 0.84 783 676 1.00 936 735 1.17 1096 790 1.35 1260 3300 562 0.74 689 626 0.90 839 686 1.07 996 743 1.24 1159 798 1.42 1328 3400 575 0.80 744 637 0.96 898 696 1.14 1059 752 1.31 1226 806 1.50 1398 3500 588 0.86 802 649 1.03 961 707 1.21 1125 762 1.39 1296 815 1.58 1472 3600 601 0.93 864 661 1.10 1026 717 1.28 1194 771 1.47 1369 823 1.66 1548 3700 614 1.00 929 673 1.17 1095 728 1.36 1267 781 1.55 1445 832 1.75 1629 3800 628 1.07 997 685 1.25 1167 739 1.44 1343 791 1.64 1525 841 1.84 1712 3900 641 1.15 1069 697 1.33 1243 750 1.53 1423 801 1.72 1608 850 1.93 1799 4000 655 1.23 1144 709 1.42 1322 761 1.61 1506 812 1.82 1695 860 2.03 1890 4100 668 1.31 1223 722 1.51 1405 773 1.71 1593 822 1.92 1786 870 2.13 1984 4200 682 1.40 1305 734 1.60 1492 784 1.80 1683 833 2.02 1880 880 2.23 2082 4300 696 1.49 1392 747 1.70 1582 796 1.91 1777 844 2.12 1979 890 2.34 2184
AIRFLOW
(Cfm)
2500 804 1.09 1013 861 1.25 1164 915 1.41 1319 967 1.59 1479 1017 1.76 1642 2600 809 1.14 1065 864 1.31 1219 918 1.48 1378 969 1.65 1541 1018 1.83 1708 2700 813 1.20 1119 869 1.37 1277 921 1.54 1439 972 1.72 1606 1021 1.90 1776 2800 819 1.26 1176 873 1.43 1337 925 1.61 1503 975 1.79 1673 1023 1.98 1847 2900 824 1.32 1235 878 1.50 1400 929 1.68 1569 978 1.87 1742 1026 2.06 1920 3000 830 1.39 1298 883 1.57 1466 934 1.76 1638 982 1.95 1815 1029 2.14 1996 3100 837 1.46 1363 889 1.65 1534 938 1.83 1710 986 2.03 1891 1033 2.23 2075 3200 843 1.53 1431 894 1.72 1606 944 1.91 1785 991 2.11 1969 1037 2.31 2157 3300 850 1.61 1502 901 1.80 1680 949 2.00 1863 996 2.20 2051 1041 2.40 2242 3400 858 1.69 1576 907 1.88 1758 955 2.09 1944 1001 2.29 2135 1046 2.50 2331 3500 865 1.77 1653 914 1.97 1838 961 2.18 2029 1007 2.38 2223 1051 2.60 2422 3600 873 1.86 1733 921 2.06 1922 967 2.27 2116 1012 2.48 2314 1056 2.70 2516 3700 881 1.95 1816 928 2.16 2010 974 2.37 2207 1019 2.58 2409 1062 2.80 2615 3800 889 2.04 1904 936 2.25 2100 981 2.47 2302 1025 2.69 2507 3900 898 2.14 1995 944 2.35 2195 988 2.57 2399 1032 2.80 2608 4000 907 2.24 2089 952 2.46 2293 996 2.68 2501 4100 916 2.35 2187 960 2.57 2395 1004 2.80 2607 4200 925 2.45 2289 969 2.68 2500 4300 934 2.57 2395 978 2.80 2610
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 21 for general fan performance notes.
30
Table 21 — Fan Performance 549B102 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
2500 462 0.37 348 541 0.50 467 614 0.64 594 681 0.78 728 744 0.93 868 2600 474 0.41 381 551 0.54 505 622 0.68 635 688 0.83 773 750 0.98 916 2700 486 0.45 417 561 0.58 545 630 0.73 679 695 0.88 820 756 1.04 967 2800 498 0.49 456 571 0.63 587 639 0.78 725 702 0.93 870 762 1.09 1020 2900 510 0.53 497 581 0.68 632 648 0.83 774 710 0.99 922 768 1.15 1076 3000 523 0.58 541 592 0.73 680 657 0.88 825 718 1.05 977 775 1.22 1135 3100 536 0.63 587 603 0.78 730 666 0.94 879 726 1.11 1035 783 1.28 1196 3200 549 0.68 637 614 0.84 783 676 1.00 936 735 1.17 1096 790 1.35 1260 3300 562 0.74 689 626 0.90 839 686 1.07 996 743 1.24 1159 798 1.42 1328 3400 575 0.80 744 637 0.96 898 696 1.14 1059 752 1.31 1226 806 1.50 1398 3500 588 0.86 802 649 1.03 961 707 1.21 1125 762 1.39 1296 815 1.58 1472 3600 601 0.93 864 661 1.10 1026 717 1.28 1194 771 1.47 1369 823 1.66 1548 3700 614 1.00 929 673 1.17 1095 728 1.36 1267 781 1.55 1445 832 1.75 1629 3800 628 1.07 997 685 1.25 1167 739 1.44 1343 791 1.64 1525 841 1.84 1712 3900 641 1.15 1069 697 1.33 1243 750 1.53 1423 801 1.72 1608 850 1.93 1799 4000 655 1.23 1144 709 1.42 1322 761 1.61 1506 812 1.82 1695 860 2.03 1890 4100 668 1.31 1223 722 1.51 1405 773 1.71 1593 822 1.92 1786 870 2.13 1984 4200 682 1.40 1305 734 1.60 1492 784 1.80 1683 833 2.02 1880 880 2.23 2082 4300 696 1.49 1392 747 1.70 1582 796 1.91 1777 844 2.12 1979 890 2.34 2184
AIRFLOW
(Cfm)
2500 804 1.09 1013 861 1.25 1164 915 1.41 1319 967 1.59 1479 1017 1.76 1642 2600 809 1.14 1065 864 1.31 1219 918 1.48 1378 969 1.65 1541 1018 1.83 1708 2700 813 1.20 1119 869 1.37 1277 921 1.54 1439 972 1.72 1606 1021 1.90 1776 2800 819 1.26 1176 873 1.43 1337 925 1.61 1503 975 1.79 1673 1023 1.98 1847 2900 824 1.32 1235 878 1.50 1400 929 1.68 1569 978 1.87 1742 1026 2.06 1920 3000 830 1.39 1298 883 1.57 1466 934 1.76 1638 982 1.95 1815 1029 2.14 1996 3100 837 1.46 1363 889 1.65 1534 938 1.83 1710 986 2.03 1891 1033 2.23 2075 3200 843 1.53 1431 894 1.72 1606 944 1.91 1785 991 2.11 1969 1037 2.31 2157 3300 850 1.61 1502 901 1.80 1680 949 2.00 1863 996 2.20 2051 1041 2.40 2242 3400 858 1.69 1576 907 1.88 1758 955 2.09 1944 1001 2.29 2135 1046 2.50 2331 3500 865 1.77 1653 914 1.97 1838 961 2.18 2029 1007 2.38 2223 1051 2.60 2422 3600 873 1.86 1733 921 2.06 1922 967 2.27 2116 1012 2.48 2314 1056 2.70 2516 3700 881 1.95 1816 928 2.16 2010 974 2.37 2207 1019 2.58 2409 1062 2.80 2615 3800 889 2.04 1904 936 2.25 2100 981 2.47 2302 1025 2.69 2507 1068 2.91 2716 3900 898 2.14 1995 944 2.35 2195 988 2.57 2399 1032 2.80 2608 1074 3.03 2821 4000 907 2.24 2089 952 2.46 2293 996 2.68 2501 1038 2.91 2713 1080 3.14 2930 4100 916 2.35 2187 960 2.57 2395 1004 2.80 2607 1046 3.03 2822 1087 3.26 3042 4200 925 2.45 2289 969 2.68 2500 1011 2.91 2716 1053 3.15 2935 1094 3.39 3159 4300 934 2.57 2395 978 2.80 2610 1020 3.03 2828 1061 3.27 3052 1101 3.52 3279
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.20.40.60.81.0
1.21.41.61.82.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 21 for general fan performance notes.
31
Table 22 — Fan Performance 549B120 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
3000 523 0.58 541 592 0.73 680 657 0.88 825 718 1.05 977 775 1.22 1135 3100 536 0.63 587 603 0.78 730 666 0.94 879 726 1.11 1035 783 1.28 1196 3200 549 0.68 637 614 0.84 783 676 1.00 936 735 1.17 1096 790 1.35 1260 3300 562 0.74 689 626 0.90 839 686 1.07 996 743 1.24 1159 798 1.42 1328 3400 575 0.80 744 637 0.96 898 696 1.14 1059 752 1.31 1226 806 1.50 1398 3500 588 0.86 802 649 1.03 961 707 1.21 1125 762 1.39 1296 815 1.58 1472 3600 601 0.93 864 661 1.10 1026 717 1.28 1194 771 1.47 1369 823 1.66 1548 3700 614 1.00 929 673 1.17 1095 728 1.36 1267 781 1.55 1445 832 1.75 1629 3800 628 1.07 997 685 1.25 1167 739 1.44 1343 791 1.64 1525 841 1.84 1712 3900 641 1.15 1069 697 1.33 1243 750 1.53 1423 801 1.72 1608 850 1.93 1799 4000 655 1.23 1144 709 1.42 1322 761 1.61 1506 812 1.82 1695 860 2.03 1890 4100 668 1.31 1223 722 1.51 1405 773 1.71 1593 822 1.92 1786 870 2.13 1984 4200 682 1.40 1305 734 1.60 1492 784 1.80 1683 833 2.02 1880 880 2.23 2082 4300 696 1.49 1392 747 1.70 1582 796 1.91 1777 844 2.12 1979 890 2.34 2184 4400 710 1.59 1482 760 1.80 1677 808 2.01 1876 855 2.23 2081 900 2.46 2290 4500 723 1.69 1577 773 1.90 1775 820 2.12 1978 866 2.35 2187 910 2.57 2400 4600 737 1.80 1675 785 2.01 1877 832 2.24 2085 877 2.46 2297 921 2.70 2514 4700 751 1.91 1778 798 2.13 1984 844 2.35 2195 889 2.59 2412 932 2.82 2633 4800 765 2.02 1885 812 2.25 2095 856 2.48 2310 900 2.71 2531 942 2.95 2756 4900 779 2.14 1996 825 2.37 2210 869 2.61 2430 912 2.85 2654 953 3.09 2883 5000 793 2.26 2112 838 2.50 2330 881 2.74 2554 923 2.98 2782 965 3.23 3014
AIRFLOW
(Cfm)
3000 830 1.39 1298 883 1.57 1466 934 1.76 1638 982 1.95 1815 1029 2.14 1996 3100 837 1.46 1363 889 1.65 1534 938 1.83 1710 986 2.03 1891 1033 2.23 2075 3200 843 1.53 1431 894 1.72 1606 944 1.91 1785 991 2.11 1969 1037 2.31 2157 3300 850 1.61 1502 901 1.80 1680 949 2.00 1863 996 2.20 2051 1041 2.40 2242 3400 858 1.69 1576 907 1.88 1758 955 2.09 1944 1001 2.29 2135 1046 2.50 2331 3500 865 1.77 1653 914 1.97 1838 961 2.18 2029 1007 2.38 2223 1051 2.60 2422 3600 873 1.86 1733 921 2.06 1922 967 2.27 2116 1012 2.48 2314 1056 2.70 2516 3700 881 1.95 1816 928 2.16 2010 974 2.37 2207 1019 2.58 2409 1062 2.80 2615 3800 889 2.04 1904 936 2.25 2100 981 2.47 2302 1025 2.69 2507 1068 2.91 2716 3900 898 2.14 1995 944 2.35 2195 988 2.57 2399 1032 2.80 2608 1074 3.03 2821 4000 907 2.24 2089 952 2.46 2293 996 2.68 2501 1038 2.91 2713 1080 3.14 2930 4100 916 2.35 2187 960 2.57 2395 1004 2.80 2607 1046 3.03 2822 1087 3.26 3042 4200 925 2.45 2289 969 2.68 2500 1011 2.91 2716 1053 3.15 2935 1094 3.39 3159 4300 934 2.57 2395 978 2.80 2610 1020 3.03 2828 1061 3.27 3052 1101 3.52 3279 4400 944 2.69 2504 986 2.92 2723 1028 3.16 2946 1068 3.40 3173 1108 3.65 3403 4500 954 2.81 2618 996 3.05 2840 1037 3.29 3067 1076 3.54 3297 4600 963 2.93 2736 1005 3.18 2962 1045 3.42 3192 1085 3.67 3426 ——— 4700 974 3.07 2858 1014 3.31 3088 1054 3.56 3322 4800 984 3.20 2985 1024 3.45 3219 4900 994 3.34 3116 1034 3.60 3353 5000 1005 3.49 3251
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 21 for general fan performance notes.
32
Table 23 — Fan Performance 549B130 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
3000 523 0.58 541 592 0.73 680 657 0.88 825 718 1.05 977 775 1.22 1135 3100 536 0.63 587 603 0.78 730 666 0.94 879 726 1.11 1035 783 1.28 1196 3200 549 0.68 637 614 0.84 783 676 1.00 936 735 1.17 1096 790 1.35 1260 3300 562 0.74 689 626 0.90 839 686 1.07 996 743 1.24 1159 798 1.42 1328 3400 575 0.80 744 637 0.96 898 696 1.14 1059 752 1.31 1226 806 1.50 1398 3500 588 0.86 802 649 1.03 961 707 1.21 1125 762 1.39 1296 815 1.58 1472 3600 601 0.93 864 661 1.10 1026 717 1.28 1194 771 1.47 1369 823 1.66 1548 3700 614 1.00 929 673 1.17 1095 728 1.36 1267 781 1.55 1445 832 1.75 1629 3800 628 1.07 997 685 1.25 1167 739 1.44 1343 791 1.64 1525 841 1.84 1712 3900 641 1.15 1069 697 1.33 1243 750 1.53 1423 801 1.72 1608 850 1.93 1799 4000 655 1.23 1144 709 1.42 1322 761 1.61 1506 812 1.82 1695 860 2.03 1890 4100 668 1.31 1223 722 1.51 1405 773 1.71 1593 822 1.92 1786 870 2.13 1984 4200 682 1.40 1305 734 1.60 1492 784 1.80 1683 833 2.02 1880 880 2.23 2082 4300 696 1.49 1392 747 1.70 1582 796 1.91 1777 844 2.12 1979 890 2.34 2184 4400 710 1.59 1482 760 1.80 1677 808 2.01 1876 855 2.23 2081 900 2.46 2290 4500 723 1.69 1577 773 1.90 1775 820 2.12 1978 866 2.35 2187 910 2.57 2400 4600 737 1.80 1675 785 2.01 1877 832 2.24 2085 877 2.46 2297 921 2.70 2514 4700 751 1.91 1778 798 2.13 1984 844 2.35 2195 889 2.59 2412 932 2.82 2633 4800 765 2.02 1885 812 2.25 2095 856 2.48 2310 900 2.71 2531 942 2.95 2756 4900 779 2.14 1996 825 2.37 2210 869 2.61 2430 912 2.85 2654 953 3.09 2883 5000 793 2.26 2112 838 2.50 2330 881 2.74 2554 923 2.98 2782 965 3.23 3014
AIRFLOW
(Cfm)
3000 830 1.39 1298 883 1.57 1466 934 1.76 1638 982 1.95 1815 1029 2.14 1996 3100 837 1.46 1363 889 1.65 1534 938 1.83 1710 986 2.03 1891 1033 2.23 2075 3200 843 1.53 1431 894 1.72 1606 944 1.91 1785 991 2.11 1969 1037 2.31 2157 3300 850 1.61 1502 901 1.80 1680 949 2.00 1863 996 2.20 2051 1041 2.40 2242 3400 858 1.69 1576 907 1.88 1758 955 2.09 1944 1001 2.29 2135 1046 2.50 2331 3500 865 1.77 1653 914 1.97 1838 961 2.18 2029 1007 2.38 2223 1051 2.60 2422 3600 873 1.86 1733 921 2.06 1922 967 2.27 2116 1012 2.48 2314 1056 2.70 2516 3700 881 1.95 1816 928 2.16 2010 974 2.37 2207 1019 2.58 2409 1062 2.80 2615 3800 889 2.04 1904 936 2.25 2100 981 2.47 2302 1025 2.69 2507 1068 2.91 2716 3900 898 2.14 1995 944 2.35 2195 988 2.57 2399 1032 2.80 2608 1074 3.03 2821 4000 907 2.24 2089 952 2.46 2293 996 2.68 2501 1038 2.91 2713 1080 3.14 2930 4100 916 2.35 2187 960 2.57 2395 1004 2.80 2607 1046 3.03 2822 1087 3.26 3042 4200 925 2.45 2289 969 2.68 2500 1011 2.91 2716 1053 3.15 2935 1094 3.39 3159 4300 934 2.57 2395 978 2.80 2610 1020 3.03 2828 1061 3.27 3052 1101 3.52 3279 4400 944 2.69 2504 986 2.92 2723 1028 3.16 2946 1068 3.40 3173 1108 3.65 3403 4500 954 2.81 2618 996 3.05 2840 1037 3.29 3067 1076 3.54 3297 1115 3.79 3531 4600 963 2.93 2736 1005 3.18 2962 1045 3.42 3192 1085 3.67 3426 1123 3.93 3664 4700 974 3.07 2858 1014 3.31 3088 1054 3.56 3322 1093 3.82 3560 1131 4.08 3801 4800 984 3.20 2985 1024 3.45 3219 1063 3.71 3456 1102 3.96 3697 1139 4.23 3943 4900 994 3.34 3116 1034 3.60 3353 1073 3.85 3594 1111 4.12 3839 1148 4.38 4088 5000 1005 3.49 3251 1044 3.74 3492 1082 4.01 3737 1119 4.27 3986 1156 4.55 4238
Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
LEGEND
0.20.40.60.81.0
1.21.41.61.82.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 21 for general fan performance notes.
33
PRE-START-UP
WARNING: Failure to observe the following warn-
ings could result in serious personal injury:
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate th e compressor or provide any electric power to the unit unless the compressor terminal cover is in place and secured.
3. Do not remove the compressor terminal cover until all electrical sources are disconnected and tagged.
4. Relieve all pressure from the system before touching or disturbing anything inside the com­pressor termin al b ox if a re fr ig e ran t le ak is sus­pected around the compressor terminals. Use accepted methods to recover refrigerant.
5. Never attempt to repair a sol dered connection while the refrigerant system is under pressure.
6. Do not use a torch to remove any component. The system contains oil and refrigerant under pressure. To remove a compone nt, wear prote c­tive goggles and proceed as follows :
a. Shut off electrical power to the unit. b. Recover refrigerant to relieve all pressure
from the system using both high-pressure and low-pressure ports.
c. Cut the component connection tubing with a
tubing cutter, and remove the component from the unit.
d. Carefully unsweat the remaining tubing
stubs when necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to ins pect and prep are the unit f or initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU­TION, and INFORMATION labels attached to or shipped with the unit.
3. Make the following inspectio ns: a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected wires.
b. Inspect for oil at all refrigerant tubing connections
and on the unit base. Detecting oil generally i ndi­cates a refrigerant leak. Leak-test all refrigerant tubing connections using an electronic leak detec­tor, halide torch, or liquid-soap solution.
c. Inspect all field-wiring a nd factory-wiring connec-
tions. Be sure that connections are completed and tight. Ensure that electrical component wiring does not come in contact with refrigerant tubing.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten the fins with a fin comb.
4. Verify the following conditions: a. Make sure that the outdoor-fan blades are cor-
rectly positioned in the fan orifice. Refer to the Outdoor-Fan Adjustment section on page 37 for
more details. b. Make sure that the air filter(s) is in place. c. Make sure that the condensate drain trap is filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
I. UNIT PREPARATION
Make sure that the unit has been installed in accordance with these installation instructions and applicable codes. Make sure that the Start-Up Checklist, located on the back page of this manual, has been completed and filled out.
II. RETURN-AIR FILTERS
Make sure that the correct air filters are installed in the unit (see Table 1). Do not operate the unit without return-air filters.
III. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screen must be in place b efore operat ing the unit.
IV. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
V. INTERNAL WIRING
Check all electrical connections in the unit control boxes; tighten as required.
VI. REFRIGERANT SERVICE PORTS
Each refrigerant system has 3 Schrader-type service gage ports: one on the suction line, one on the cooling mode liquid line, and one on the compressor discharge line.
Be sure that caps on the ports are tight. The port on the cool­ing mode liquid line and one port on the discharge line have protective devices installed on them.
A. High-Flow Refrigerant Valves
These are two high flow va lves; on e is loca ted on th e hot gas tube coming out of the compressor. The second is located on the suction tube going in to the compressor. Large black plas­tic caps with O-rings inside identify these valves. No field access to these valves is available at this time. Ensure that the plastic caps remain on the valves and a re tight or the possibility of refrigerant leakage could occur.
VII. COMPRESSOR ROTATION
It is important to be certain that the scroll compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gages to the suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres­sure does not rise to normal levels:
1. Note that the indoor fan is probably also rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and re-energize compres­sor.
The suction and discharge pressure levels should now move to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc­tion, the unit makes more noise and does not provide heating/ cooling. Compressor failure will occur if rotation direction is not corrected.
34
VIII. COOLING
To start the unit, turn on main power supply. Set the system selector switch at COOL pos ition and fan switch at AUTO position. Adjust the thermostat to a setting below room temperature. The compressor, reversing valve, outdoor-fan contactor and indoor blower motor are energized.
Check the unit charge. Refer to Refrigerant Charge section on page 37.
Reset the thermostat at a position above room tempera ture. The compressor will shut off.
A. To Shut Off Unit
Set the system selector switch at OFF position. Resetting the thermostat at a position above room temperature shuts unit off temporarily until the space temperature exceeds the ther­mostat setting.
Compressor restart is a ccomplished by manual reset a t the thermostat by turning the selector switch to OFF position and then ON position.
IX. HEATING
To start the unit, turn on the main power supply. Set thermostat at HEAT position and a setting above room
temperature, and set fan at AUTO. position. The first stage of the thermostat energizes the indoor fan
motor, compress or, and outdoor fan; the second sta ge ener­gizes the electr ic hea ter el emen ts i f inst all ed. Check h ea ti ng effects at air supply grille(s).
If accessory el ectric heaters do not energize, reset the li mit switch (located on indoor-fan scroll) by press ing the button located between the terminals on the switch.
A. To Shut Off Unit
Set the system selector switch at OFF position. Resetting the heating select or lever below room temp erature temporarily shuts the unit off until the space temperature falls below the thermostat setting.
X. SAFETY RELIEF
A soft solder joint in the suction line at the loss-of-charge/ low-pressure switch fitting provides pressure relief under abnormal temperature and pressure conditions.
XI. VENTILATION (Continuous Fan)
Set the fan and system selector switches at ON and OFF positions, respective ly. The indoor fan opera tes con tinuousl y to provide constant air circulation.
XII. OPERATING SEQUENCE
A. Cooling, Units without Economizer
When thermost at calls for cooli ng, terminals G and Y1 ar e energized. The indoor-fan contactor (IFC), reversing valve solenoid (RVS1) and compressor contactor no. 1 (C1) are energized and ind oor-fan motor, compressor no. 1, and out­door fan(s) starts. The outdoor-fan motor(s) runs continu­ously while unit is cooling. If the thermostat calls for a second stage of cooling by energ izing Y2, c ompres sor conta c­tor no. 2 (C2) and reversing valve solenoid (RVS2) are ener­gized and compressor no. 2 starts.
B. Heating, Units without Economizer
Upon a request for heating from the space thermostat, ter­minal W1 will be ener gized with 24 v. The IFC, outdoor-fan contactor (OFC), C1, and C2 wil l be ener gized. Th e reve rs ing valves switch position and the indoor fan, outdoor fan(s), compressor no. 1, and compressor no. 2 are energized.
If the space temperature continues to fall while W1 is energized, W2 will be energized with 24 v, and the heater contactor(s) (HC) will be energized, which will energize the electric heater(s).
When the space thermostat is satisfied, W2 will be deener­gized first, and the electric heater(s) will be deenergized.
Upon a further rise in space temperature, W1 will be deenergized, and the reversing valve solenoids (RVS1 and RVS2) will be energized.
C. Cooling, Units With EconoMi$er IV
When free cool ing is not available, the com pressors will be controlled b y th e zo ne th ermost at. When f re e cool ing i s a vail­able, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50 to 55 F supply-air temperature into the zone. As the supply-air temperature fluctuates above 55 or be lo w 5 0 F, the dampers will be modu­lated (open or close) to bring the supply-air temperature back within the set point limits.
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its mini­mum position during the occupied mode.
Above 50 F supply-air temperature, the dampers will modu­late from 100% open to the minimum open position. From 50 F to 45 F supply-air temperature, the dampers will main­tain at the minimum open position. Below 45 F the dampers will be completely shut. As the supply-air temperature rises, the dampers will come back open to the minimum open posi­tion once the supply air temperature rises to 48 F.
If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.
If field-installed accessory CO
sensors are connected to the
2
EconoMi$er IV control, a demand controlled ventilation strategy will begin to opera te. As the CO increases abo ve the CO
set point, the minimum position of
2
level in the zone
2
the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode.
Damper movement from full closed to full open (or vice versa) will take between 1
1
/2 and 21/2 minutes.
If free cooling can be used as determined from the appropri­ate changeover com mand (switch, dr y bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cool­ing (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply a ir tem­perature set point at 50 to 55 F.
As the supply-air temperature drops below the set point range of 50 to 55 F, the control will modulate the outdoor-air damp­ers closed to maintain the proper supply-air temperatur e .
D. Heating, Units with EconoMi$er IV
When the room temperature calls for heat through terminal W1, the indoor fan contactor (IFC) and he ater contac tor no . 1 (HC1) are energized. On units equipped for 2 stages of heat, when additional heat is needed, heater contactor no. 2 is energized through W2. The ec onomizer damper moves to the minimum position. When the thermostat is satisfied, the damper moves to the fully closed position.
35
E. Defrost
When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT2) and the defrost timer is at the end of the timed period (adjustable at 30, 50, or 90 minutes), the reversing valve solenoids (RVS1 and RVS2) are energized and the OFC is deenergized. This switches the position of the reversing valves and shuts off the outdoor fans . The electric heaters (if installed) will be energ iz ed.
The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65 F, or the defrost cycle com­pletes a 10-minute period.
During the Defrost mode, if circuit 1 defrosts first, RVS1 will oscillate betw een Heati ng and Coo ling mod es (dep ending on DFT1 switch position) until the Defrost mode is complete.
At the end of the defrost cycle, the electric heaters (if installed) will be dee nergized; the reversing valves deener­gize and the outdoor-fan motors will be energized. The unit will now operate in the Heating mode.
If the space thermostat is satisfied during a defrost cycle, the unit will continue in the Defrost mode until the time or tem­perature constraints are s atisfied.
SERVICE
CAUTION: When servicing the unit, shut off all
electrical power to the unit a nd tag to avoid shock haz­ard or injury from rotating parts.
Clean 2-row coils as follows:
1. Turn off the unit power and install lockout tag on disconnect.
2. Remove the top panel screws on the outdoor end of the unit.
3. Remove the outdoor coil corner post. See Fig. 34. To hold the top panel open, place the coil corner post between the top panel and center post. See Fig. 35.
4. Remove the device holding the coil sect ions together at the return end of the outdoor coil. Carefully sepa­rate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 36.
5. Use a water hose or other suitable equipment to flush down between the 2 coil s ections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
6. Secure the sectio ns together. Reposition the coil sec­tions, and remove the c oil corner post from be tween the top panel and center post. Install the coil corner post and coil center post, and replace all screws.
I. CLEANING
Inspect the unit interior at the beginning of each heating and cooling season or as operating con ditions require.
A. Indoor Coil
1. Turn the unit p o wer o ff and install lockout tag o n di s­connect. Remove the filter access panel and indoor coil access panel.
2. If the economizer or accessory two-position damper is installed, remove the economizer/two-position damper by disconnecting the economizer plug and removing mounting screws. Refer to Accessory Economizer or Two-Position Damper Installation Instructions for more details.
3. Slide filters out of unit.
4. Clean the coil using a commercial coil cleaner or dish­washer detergent in a pressurized spray canister. Wash both sides of the coil and flush with clean water. For best results, backflush toward the return­air section to remove for eign material.
5. Flush the condensate pan after completion.
6. Reinstall the economizer/two-position damper and filters.
7. Reconnect wiring.
8. Replace the access panels.
B. Outdoor Coil
Inspect the coil monthly. Clean the outdoor coil annually , and as required by location and outdoor-air conditions.
Fig. 34 — Cleaning Outdoor Coil
Fig. 35 — Propping Up Top Panel
36
Fig. 36 — Separating Coil Sections
C. Condensate Drain
Check and clean each year at the start of the cooling season. In winter, protect against freeze-up.
D. Filters
Clean or replace at the start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be the same dimensions as original filters.
E. Outdoor-Air Inlet Screen
Clean the screen with stream or hot water and a mild deter­gent. Do not use disposable filters in place of screens.
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at the factory.
B. Fan-Motor Bearings
Fan-motor bearings are permanently lubricated. No lubrica­tion of outdoor or indoor-fan motors is required.
III. OUTDOOR-FAN ADJUSTMENT (Fig. 37)
1. Shut off the unit power supply, and install lockout tag on disconnect.
2. Remove the outdoor-fan assembly (grille, motor, motor cover, and fan) and loosen the fan hub setscrews.
3. Adjust the fan height as shown in Fig. 37.
4. Tighten the setscrews and replace the outdoor-fan assembly.
IV. BLOWER BELT ADJUSTMENT
Refer to Step 7 — Adjust I ndoor-Fan Speed on page 19 for adjustment and alignment procedu r e.
V. ECONOMI$ER IV ADJUSTMENT
Refer to Optional EconoMi$er IV section on page 12.
VI. HIGH-PRESSURE SWITCH
Located on the compressor hot gas line is a high-pressure switch with a Schrader core depressor. This switch opens at 428 psig and closes at 320 psig. No adjustment is necessary. Refer to Table 1.
VII. LOSS OF CHARGE SWITCH
Located on the outdoor liquid line is a low-pressure switch which functions as a loss-of-charge switch. This switch con­tains a Schrader core depressor. This switch opens at 7 psig and closes at 22 psig. No adjustment is necessary. Refer to Table 1.
VIII. FREEZESTAT
Located on the “hair pin” end of the indoor coil is a bimetal temperature s ensing switch. T his swi tch prot ects the i ndoor coil from free ze- up due to lack of airflow. The switch opens at 30 F and closes at 45 F. No adjustment is necessary. Refer to Table 1.
IX. REFRIGERANT CHARGE
The amount of re fri ger an t char ge i s li s ted o n the u nit na m e­plate (also refer to Table 1).
Unit panels must be in place when the unit is operating dur­ing charging procedure. The unit must operate for a mini­mum of 10 minutes before checking or adjusting the charge.
A. No Charge
Use standard evacuating techniques. After evacuating the system to 500 microns, weigh in the specified amount of refrigerant (refer to Table 1).
B. Low Charge Cooling
Use Cooling Charging Charts, Fig. 38-40. Vary refrigerant until the conditions of the appropriate chart are met. Note that charging charts are different from the type normally used. The charts are b ased on charging the units to the cor­rect superheat for the various operat ing cond iti ons. An accu­rate pressure gage and temperature sensing device are required. Connect the pressure gage to th e service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient tem­perature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit.
UNIT VOLTAGE ‘‘A’’ in.
208/230 V 2.75
460 V 3.50
Fig. 37 — Outdoor Fan Adjustment
37
C. To Use Cooling Charging Charts
Take the outdoor ambient temperature and read the suction pressure gage. Refer to the appropriate chart to determine what the suction temperature should be. If the suction tem­perature is high, add refrigerant. If the suction temper ature is low, carefully recover some of th e charge. Recheck the s uc­tion pressure as the charge is adjusted.
EXAMPLE: (Fig. 38; Circuit 1)
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . .85 F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 psig
Suction Temperature should be . . . . . . . . . . . . . . . . . . . .51 F
(Suction Temperature may vary ± 5° F.)
D. Heating Charge
Do not attempt to adjust the refrigerant charge while the unit is operating in the Heating mode. If the charge amount is believed to be incorrect, recover refrigerant and weigh in the amount listed on the unit rating plate.
X. TYPICAL WIRING
Refer to Fig. 41 for a typical unit wiring diagram.
XI. REPLACEMENT PARTS
A complete list of replacement parts may be obtained from any Bryant distributor.
100
689
95
621
90
85
552
80
75
483
70
SUCTION LINE PRESSURE PSIG
65
SUCTION LINE PRESSURE (KILOPASCALS)
414
60
42
32
47
SUCTION LINE TEMPERATURE DEG F
5
10
SUCTION LINE TEMPERATURE DEG F
57
52
62
15
Fig. 39 — Cooling Charging Chart, 549B102
OUTDOOR
TEMP
C
F
64
125
46
115
41
105
35
95
29
85
24
75
67
72
77
20
25
Fig. 38 — Cooling Charging Chart, 549B090
Fig. 40 — Cooling Charging Chart, 549B120
38
AWG American Wire Gage C—Contactor, Compressor CAP Capacitor CB Circuit Breaker CLO Compressor Lockout COMP Compressor Motor DFT Defrost Thermostat EQUIP Equipment FPT Freeze Up Protection Thermostat FU Fuse GND Ground HC Heat Contactor HPS High-Pressure Switch HR Heater Relay IFC Indoor-Fan Contactor IFM Indoor-Fan Motor IFMOVL — Indoor Fan Motor Overload Switch LPS Low-Pressure Switch
Fig. 41 — Typical Wiring Schematic (208/230-3-60 Unit Shown)
LEGEND
LSM Limit Switch MCA Minimum Circuit Amps OFC Outdoor-Fan Contactor OFM Outdoor-Fan Motor P—Plug PL Plug Assembly QT Quadruple Terminal RVS Reversing Valve Solenoid SAT Supply Air Temperature Sensor TB Terminal Board TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
39
Terminal Block
Terminal Econ 2 Position Board
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring To indicate common potential only;
not to represent wiring.
TROUBLESHOOTING
I. UNIT TROUBLESHOOTING
Refer to Table 24 for troubleshooting information.
Table 24 — Heating and Cooling Troubleshooting
PROBLEM CAUSE REMEDY
Compressor and Outdoor Fan Will Not Start.
Compressor Will Not Start But Outdoor Fan Runs.
Compressor Cycles (Other Than Normally Satisfying Thermostat).
Compressor Operates Continuously.
Excessive Head Pressure
Head Pressure Too Low.
Excessive Suction Pressure.
Suction Pressure Too Low.
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or control relay. Replace component. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room
High-pressure switch tripped. See problem ‘‘Excessive head pressure.’’ Low-pressure switch tripped. Check for leaks, repair, and recharge. Freeze-up protection thermostat tripped. See problem ‘‘Suction pressure too low.’’ Faulty wiring or loose connections in compressor circuit. Check wiring and repair or replace. Compressor motor burned out, seized, or internal
overload open. Defective overload. Determine cause and replace. One leg of 3-phase power dead. Replace fuse or reset circuit breaker.
Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked outdoor coil or dirty air filter. Determine cause and correct. Defective overload. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty outdoor-fan (cooling) or indoor-fan (heating) motor or
capacitor. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and
Outdoor coil dirty or restricted. Clean coil or remove restriction. Dirty air filter. Replace filter. Dirty outdoor coil. Clean coil. Refrigerant overcharged. Remove excess refrigerant. Air in system. Recover refrigerant, evacuate system, and
Condensing air restricted or air short-cycling. Determine cause and correct. Low refrigerant charge. Check for leaks, repair, and recharge. Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction. High heat load. Check for source and eliminate. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Dirty air filter (cooling) or dirty outdoor coil (heating). Replace filter or clean coil. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted Remove source of restriction. Insufficient indoor airflow (cooling mode). Increase air quantity. Check filter and replace if
Temperature too low in conditioned area. Reset thermostat. Field-installed filter drier restricted. Replace. Outdoor ambient temperature below 25 F. Install low-ambient kit.
temperature.
Determine cause. Replace compressor.
Determine cause.
recharge to nameplate.
Replace.
recharge.
recharge.
necessary.
40
II. ECONOMI$ER IV TROUBLESHOOTING
See Table 25 for EconoMi$er IV logic. A functiona l view of the EconoMi$er IV is shown in Fig. 42.
Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available from Bryant to help with EconoMi$er IV training and troubleshooting.
A. EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.
IMPORTANT:
Be sure to record the positions of all potentiometers
before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
and +.
R
and +.
O
7. If connected, remove sensor from terminals S Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals S
and +.
O
8. Put 620-ohm resistor across terminals S
9. Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW (clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
B. Differential Enthalpy
To check differential enthalpy:
1. Make sure Econ o Mi $er IV pr ep ar at io n pro ce d ur e h as been performed.
2. Place 620-ohm resistor across S
3. Place 1.2 kilo-ohm resistor across S
and +.
O
and +. The Free
R
Cool LED should be lit.
4. Remove 620-ohm resistor across S
and +. The Free
O
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
C. Single Enthalpy
To check single enthalpy:
1. Make sure Econ o Mi $er IV pr ep ar at io n pro ce d ur e h as been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit .
3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
D. DCV (Demand Controlled Ventilation) and Power Exhaust
To check DCV and Power Exhaust:
1. Make sure Econ o Mi $er IV pr ep ar at io n pro ce d ur e h as been performed.
2. Ensure terminals AQ and AQ 1 a r e o pen . The LE D for both DCV and Exhaust should be off. The actuator should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The a ctua tor s hou ld dri ve to be tween 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position.
5. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9 v. The actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust con­tacts will close 30 to 120 seconds afte r the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to norm al after completing troubleshooting.
E. DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
1. Make sure Econ o Mi$ er I V pr epa ra tio n pr oce dur e h as been performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). Th e DCV LED should turn on. The actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to mid­point. The act uator should drive to be tween 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should drive fully closed.
8. Return EconoMi$er IV settings and wiring to norm al after completing troubleshooting.
F. Supply-Air Input
To check supply-air input:
1. Make sure Econ o Mi$ er I V pr epa ra tio n pr oce dur e h as been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should drive fully closed.
5. Return EconoMi$er IV settings and wiring to norm al after completing troubleshooting.
G. EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to opera­tion. No trouble shooting or testi ng is done by performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous sett ing.
41
3. Set DCV maximum position po tentiometer to previ­ous setting.
4. Set minimum position, DCV set point, and exhaust potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals S
and +.
R
6. Remove 1.2 kilo-ohm checkout resistor from termi­nals SO and +. If used, reconnect sensor from termi­nals SO and +.
Table 25 — EconoMi$er IV Input/Output Logic
INPUTS OUTPUTS
Demand Control
Ventilation (DCV)
Below set (DCV LED Off)
Above set (DCV LED On)
*For single enthalpy control, the module compares outdoor enthalpy
to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
High (Free Cooling LED Off)
Low (Free Cooling LED On)
High (Free Cooling LED Off)
Low (Free Cooling LED On)
Enthalpy*
Outdoor Return
Low On On On On Minimum position Closed
High On On On Off Modulating** (between min.
Low On On On On Modulating†† (between min.
High On On On Off Modulating*** Modulating†††
Y1 Y2
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off Minimum position Closed
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon­nect wires at T and T1.
10. Remove jumper from P to P1. Rec onnect device at P and P1.
11. Apply power (24 vac) to terminals TR and TR1.
Compressor N Terminal†
Stage1Stage
2
position and full-open)
position and DCV maximum)
***Modulation is based on the greater of DCV and supply-air sensor
signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor
signals, between closed and either maximum position (DCV) or fully open (supply-air signal).
Occupied Unoccupied
Damper
Modulating** (between closed and full-open)
Modulating†† (between closed and DCV maximum)
Fig. 42 — EconoMi$er IV Functional View
42
Access panels
12
Barometric flow capacity 14 Charging chart, refrigerant 38 Clearance 2, 5 CO2 sensor Configuration 18 Settings 17, 19 Compressor Lubrication 37 Mounting 34 Rotation 34 Condensate drain Cleaning 37 Location 3 Control circuit Wiring 10 Wiring raceway 11 Convenience outlet 7, 8 Defrost board 10, 11 Demand control ventilation 18 Dehumidification 19 Dimensions 2, 5 Ductwork 1 EconoMi$er IV 12-18 Adjustment 37 Components 12 Control mode 15 Damper movement 18 Demand ventilation control 18 Dry bulb temperature sensor 15 Enthalpy sensor 15 Troubleshooting 41, 42 Usage 15 Wiring 14 Electrical connections 6 Electrical data 7-9 Electric heat 6 Enthalpy changeover set points 17 Factory-installed options Convenience outlet 7, 8 EconoMi$er IV 12-18 Manual outdoor air damper 10-12 Filter Cleaning 37 Installation 13 Size 4 Freeze protection thermostat 4, 37 Heat anticipator settings 10 High flow valves 34 High pressure switch 4, 37 Horizontal units 1 Indoor air quality sensor 16 Indoor coil 4 Cleaning 36 Indoor fan motor Lubrication 37 Motor data 20 Performance 22-33 Pulley adjustment 20 Pulley setting 4, 21 Speed 4 Low pressure switch 4, 37 Manual outdoor air damper 10-12 Mounting Compressor 34 Unit 3, 4 Non-fused disconnect switch 10
INDEX
Operating sequence Cooling 35
Defrost 36 EconoMi$er IV 35
Heating 35 Outdoor air hood 12, 13 Outdoor air temperature sensor 13 Outdoor air inlet screens Cleaning 37 Outdoor coil 4 Cleaning 36 Outdoor fan 4 Adjustment 37 Physical data 4 Power supply Wiring 6 Pressure, drop Heater 21 Pressure switches High pressure 4, 37 Low pressure 4, 37 Pre-start-up 34 Refrigerant Charge 4, 37 Type 4 Refrigerant service ports 34 Replacement parts 38 Return air filter 4, 34 Return air temperature sensor 16 Rigging unit 3 Roof curb Assembly 1 Dimensions 2 Connector package 2 Leveling tolerances 3 Weight 4 Safety considerations 1 Safety relief 35 Service 36-39 Service ports 34 Slab mount 1 Start-up 34-36 Start-up checklist CL-1 Thermostat 10, 11, 18 Troubleshooting 40-42 Ventilation 35 Wei gh t Corner 5 EconoMi$er IV 4, 5 Unit 4, 5 Wiring EconoMi$er IV 14 Power connections 6 Thermostat 11 Unit 39
43
Copyright 2005 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 04-53549002-01
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:_______________________________________ DATE: _____________________________________________
SERIAL NO. _________________________________________ __ TECHNICIAN: _________________________________________ BUILDING LOCATION: ________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
ENSURE ELECTRICAL WIRING DOES NOT COME IN CONTACT WITH REFRIGERANT TUBING OR SHARP EDGES
CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
VERIFY CORRECT ROTATION OF SCROLL COMPRESSORS
VERIFY INSTALLATION OF ECONOMI$ER IV HOOD (IF EQUIPPED)
CUT ALONG DOTTED LINE
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 CIRCUIT NO. 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT NO. 2 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS L1 L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE DB WB RETURN-AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB
PRESSURES (COOLING MODE)
REFRIGERANT SUCTION, CIRCUIT 1 PSIG F REFRIGERANT SUCTION, CIRCUIT 2 PSIG F REFRIGERANT DISCHARGE, CIRCUIT 1 PSIG F REFRIGERANT DISCHARGE, CIRCUIT 2 PSIG F
VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGE 38.
CUT ALONG DOTTED LINE
GENERAL
SET ECONOMI$ER IV MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS (IF EQUIPPED)
Copyright 2005 Bryant Heating & Cooling Systems Printed in U.S.A. CL-1 CATALOG NO. 04-53549002-01
Loading...