Installation and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or servic e air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
WARNING: Before performing service or maintenance operations on unit, turn off main power switch
to unit and install lockout tag on disconnect. Electrical
shock could cause personal injury.
CAUTION: Ensure voltage listed on unit data
plate agrees with electrical supply provided for the
unit.
INSTALLATION
This unit is shipped in the vertical configuration. To convert
to horizontal configuration, remove the side duct opening
covers. Using the same screw s, install th e cover s on th e vertical duct openings with the insulation-side down. Seals
around duct openings must be tight.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install the accessory roof curb in acco rdance
with instructions shipped wi th the curb. See Fig. 1. Install
insulation, cant stri ps, roofing felt, and counter flashing as
shown. Ductwork must be attached to the curb. If electric control power will be routed through the basepan, use the
appropriate accessory kit listed in Fig. 1, available from your
local distributor. Attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installa tion inst ruct ions. Conn ect ions m ust b e in stal led
before the unit is set on the roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install the gasket supplied with
the roof curb as shown i n Fig. 1. An imprope rly applie d gasket can also result in air leaks and poor unit performance.
The roof curb should be level. Unit leveling tolerances are
shown in Fig. 2. This is necessary for the unit drain to function properly. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that ex te nds a m ini mum o f 6 i n.
beyond the unit cabinet. Install a gravel apron in front of the
condenser coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
C. Alternate Unit Support (Curb or Slab Mount)
A non-combustible sleeper ra il can be used in the unit curb
support area. If sleeper rails cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all duc ts to the roof cu rb
and building structure. Do not connect ductwork to the unit.
For horizontal applications, field-supplied flanges should be
attached to horizontal discharge openi ngs and all ductwork
attached to the flanges. Insulate and weatherproof all e xternal ductwork, joints, and roof openings with counter flashing
and mastic in accordance with applicable codes.
Ducts passing through a n unco nditi one d spa ce mu st be ins ulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply w ith applicable fire codes.
A minimum clearance to combustibles is not required around
ductwork on vertical discharge units. On horizontal discharge units, a minim um c learanc e of 1 in. is re quired for the
first 12 in. of ductwork. Cabinet return-air static pressure (a
negative condition) shall not exceed 0.30 in. wg with economizer or 0.45 in. wg without economize r.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
1
/2″ NPT
[12.7]
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01
are for thru-the-curb gas type. Packages
CRBTMPWR003A01 and 4A01 are for thru-the-bottom
type gas connections.
3
/4 lb
Fig. 1 — Roof Curb Details
—2—
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 2 — Unit Leveling Tolerances
III. STEP 3 — INSTALL CONDENSATE DRAIN LINE AND
EXTERNAL TRAP
Condensate drain connections are located on the botto m and
end of the unit. Unit discharge connections do not determine
the use of drain connections; either drain connection can be
used with vertical or horizontal applications.
When using the standard end drain connection, make sure
the red plug in the alternate bottom connection is tight
before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-installed red plug from the bottom
connection to the end c onnectio n. The ce nter drai n plug looks
like a star connection, but can be removed with a
1
/2-in.
socket drive exten sion. See Fig. 3A. The pipin g for the condensate dr ain and e xternal t rap can be completed after the
unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against
freeze-up. If a dra in line is installe d downstream from the
external trap, pitch the line away from the unit at 1 in. per
10 ft of run. Do not use a pipe size smaller than the unit
connection (
3
/4-in.). See Fig. 3B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect the unit for transportation dama ge. File any claim
with the transportation agency . Keep the unit upright and do
not drop it. Spreader bars are not required if top crating is
left on the unit. Rol lers may be used to move th e unit acro ss
a roof. Level by using the unit frame as a reference. See
Table 1 and Fig. 4 for additional information. Operating
weight is shown in Table 1 and Fig. 4.
Lifting holes are pr ovide d i n t he b ase rai ls as shown in Fig. 4
and 5. Refer to rigging instructions on the unit.
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 3A — Condensate Drain Connection (Side View)
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 3B — Condensate Drain Piping Details
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’
Holes in base rails are centered around the unit center of gravity. Use
wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for unit weight of
economizer.
4. Unit weights do not include skid.
CAUTION: All panels must be in place when rigging.
Fig. 4 — Rigging Details
UNIT
549B
09087039577.421966.541.5105442.121070
102,120 100045477.421966.541.5105442.121070
WEIGHT
lbkgin.mmin.mmin.mm
‘‘A’’‘‘B’’‘‘C’’
UNIT
OPERATING
DIMENSIONS
—3—
A. Positioning
Maintain clearance around and above the unit to provide
proper airflow and service access. See Fig. 5.
Position the unit on the roof curb so that the f oll ow in g clea rances are maintained:
1
/4-in. clearance between the roof curb
and the base rails on each side and the duct side of unit;
5
3
/16-in. clearance between t he roof cu rb and con denser s ide
of unit (see Fig. 1, section C-C).
Table 1 — Physical Data
Do not install the unit indoors. Do not locate the unit air inlet
near exhaust vents or other sources of contaminated air.
Although the unit is weatherproof, guard against water from
higher level runoff and overhangs.
After the unit is in position, remove the polyethylene shipping wrapper and rigging skid.
BASE UNIT 549B090102120
NOMINAL CAPACITY (tons)7
OPERATING WEIGHT (lb)
OUTDOOR-AIR INLET SCREENCleanable. Screen size and quantity vary by option selected.
RETURN-AIR FILTERSThrowaway
Quantity...Size (in.)4...16 x 20 x 24...20 x 20 x 2
LEGEND
Bhp — Brake Horsepower
—4—
Fig. 5 — Base Unit Dimensions
—5—
V. STEP 5 — MAKE ELECTRICAL CONNECTIONS
C
C
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the
possibility of personal injury if an electrical fault
should occur. This ground may consist of elec tric al wir e
connected to unit ground lug in control compartment,
or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (American National Standards
Institute/National Fire Protection Association), latest
edition, and local electrical codes. Failure to follow this
warning could result in the installer being liable for
3. For units with electric heat, refer to Table 2 and
Accessory Installation Instructions.
NOTE: During operation, voltage to compressor terminals
must be within the range indicated on the unit nameplate
(see Tables 3A-3D). On 3-phase units, voltages between
phases must be balanced within 2%, and the current within
10%. Use the formula shown in Tables 3A-3D, Note 2 on
page 9 to determine the percentage of voltage imbalance.
Operation on imp rop er lin e volt age or exc essiv e pha se imba lance constitutes abuse and may cause damage to electrical
components. (Such operation would invalidate any applicable Bryant warranty .)
personal injury of others.
A. Field Power Supply
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit will be
connected to a 208-v power supply, the transformer must be
rewired by moving the black wire from the 230-v
1
/4-in. male
spade terminal on the transformer and c onnecting it to the
1
200-v
/4-in. male spade terminal on the transformer.
Refer to the unit label diagram for additional information.
Pigtails are provided for fie ld wire connectio ns. Use factorysupplied splices or a UL (Underwriters’ Laboratories)
approved copper/aluminum connector.
When installing units, provide a disconnect per NEC.
All field wiring must comply wi th the N E C and lo cal require-
ments. In Canada, electrical connections must be in accordance with CSA (Canadian Standards Association) C22.1
Canadian Electrical Code Part One.
Install field wiring as foll ows:
1. Install conduit through the side panel openings. For
units without electric heat, install conduit between
the disconnect and control box.
2. Install power lines to terminal connections as shown
LEGEND
— Contactor
OMP — Compressor
IFC— Indoor Fan Contactor
NEC— National Electrical Code
Field Wiring
Factory Wiring
Splice Connection
(Factory-Supplied)
Fig. 6 — Power Wiring Connections
208/230-3-60
460-3-60
in Fig. 6.
Table 2 — Electric Heating Capacities
UNIT
549B
090
102
120
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies
from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the
following formula:
Heater kW
2
voltage)
UNIT VOLTAGE
(60 Hz)
208/230/240
(3 phase)
460/480
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
= Heater kW rated x (unit power distribution voltage/rated heater
new
ACCESSORY
kW
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
46.2/50.0*
ELECTRIC HEATER PART NUMBER
CRHEATER---A00
017
010
011
012
012 and 017
016
013
014
015
014 and 016
117
110
111
112
112, 117
116
113
114
115
114,116
017
010
012
012 and 017
010 and 012
013
014
015
014 and 016
013 and 015
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
= 16 kW (215/240)
kW
new
kW
= 12.8 kW (rating at 215 v)
new
SINGLE POINT BOX PACKAGE NO.
CRSINGLE---A00
2
007
007
009
009
013
006
006
008
008
—
012
012
015
015
017
011
011
014
014
016
012
012
015
017
017
011
014
014
016
016
—6—
UNIT
549B
090
102
120
Table 3A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet
FLA— Full Load Amps
HACR — Heating, Air Conditioning
IFM— Indoor Fan Motor
LRA— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent
NEC— National Electrical Code
OFM — Outdoor-Fan Motor
RLA— Rated Load Amps
*Heaters are field installed only.
†Minimum unit disconnect size is used to determine minimum discon-
nect per NEC.
**Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
480 v. If power distribution voltage to unit varies from rated heater
voltage, heater kW will vary accordingly.
††Fuse or HACR circuit breaker.
***Factory-installed disconnect is not available for these units when
electric heat package is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
2. Unbalanced 3-Phase Supply Voltage
and Refrigeration
Protection
tion load and equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%.
cent of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
Use the following formula to determine the per-
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance:
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
3. Non-fused disconnect switch cannot be used when rooftop unit
electrical ratings exceed 80 amps.
452 + 464 + 455
3
1371
=
3
= 457
7
457
—9—
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the
accessory. Locate the thermostat assembly on a solid wall in
the conditioned spac e to sense average temperature in accordance with thermostat installation instructions.
NOTE: If using a Bryant elect ronic therm ostat, set th e thermostat configuration for “non-heat pump operation.” This
family of products does not require an “O” terminal to energize the reversing valve.
Route the therm ostat ca ble or eq uivale nt singl e leads of colored wire from the subbase terminals to the low-voltage connections on the unit (shown in Fig. 7) as described in Steps 1
through 4 below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directl y c onnect ed to
the thermostat and will require a junction box and splice at
the thermostat.
1. If the unit is mounted on roof curb and accessory
thru-the-curb service plate connection is used, route
wire through the connection plate.
2. Pass control wires throug h the hole provided on the
unit (see connection D in Connection Sizes table
Fig. 5).
3. Feed wi re through the racew ay bu ilt into the co rner po st
to the 24-v barrier located on the left side of the control
box. See Fig. 8. The raceway provides the UL required
clearance between the high-and low-voltage wiring.
4. Connect the thermostat wires to the screw termina ls
of the low-voltage connector (se e Fig. 7).
NOTE: If thru-the-bottom power connections are used refer
to the accessory installation instructions for information on
power wiring. Refer to Fig. 5 for drilling holes in the
basepan.
C. Defrost Board
The defrost board timer cycle is set to 30 minutes. To change
the cycle time, remove the wire from defrost board connected
to the 30 minute quick-connect. See Fig. 9. Connect the wire
to the 50 to 90 minute quick-connects on the defrost board,
depending on the desired defrost time.
D. Heat Anticipator Settings
For units with electric heat, set heat anticipator settings as
shown in Table 4.
VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS
A. Disconnect Switch
The optional disconnect switch is non-fused. The switch can
be locked in plac e for safety pur poses. The disconn ect has a
maximum rating of 80 amperes and cannot be used if rooftop
electrical rating exceeds 80 amperes.
B. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit (for shipping).
Assembly:
1. Determine the amount of ventilation requi red for the
building. Record the amount for use in Step 8.
2. Remove the filter access panel by raising the panel
and swinging it outward. The panel is now disengaged from the track and can be removed. No tools
are required to remove the filter access panel.
Remove the outdoor-air opening panel. Save panels
and screws. See Fig. 10.
3. Separate the hood and screen from the basepan by
removing the screws and brackets securing them.
Save all screws and discard brackets.
4. Replace the ou tdoor air opening pa nel.
5. Place the hood on the front of the outdoor air opening
panel. See Fig. 11 for hood details. Secure the top of
the hood with the 6 screws removed in Step 3. See
Fig. 12.
6. Remove and save the 8 scre ws (4 on each side) from
the sides of the manual outdoor-air damper.
7. Align the screw holes on the hood with the screw
holes on the sid e of manual outdoor-air dam per. See
Fig. 11 and 12. Secure the hood with the 8 screws
from Step 6.
8. Adjust the minimum position setting of the damper
blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See
Fig. 10. Slide the blade vertically until it is in the
appropriate position determined by Fig. 13. Tighten
the screws.
9. Remove and save the screws cu rrent ly o n the si des of
the hood. Insert the screen. Secure the screen to the
hood using the screws. See Fig. 12.
10. Replace the filter access panel. Ensure that the filter
access panel slides along the tracks and is securely
engaged.
UNIT
Heater kW*
10.4, 16.00.3NANA
549B
*kW is based on 240 or 480 v.
24.8, 32.00.60.30.3
42.4, 50.00.90.60.341.7, 50.00.60.30.3
Table 4 — Heat Anticipator Settings
208/230460
Configuration
1-Stage
2-Stage
Stage 1Stage 2Stage 1Stage 2
UNIT VOLTAGE
Heater kW*
13.9, 16.5
27.8, 33.0
—10—
Configuration
1-Stage
0.3NANA
2-Stage
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
B
A
C
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
D
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
(CONNECTION
BOARD)
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.
Fig. 7 — Low-Voltage Connections With or
Without Economizer or Two-Position Damper
Fig. 9 — Defrost Board
DISCONNECT
BOARD
DISCONNECT
SWITCH
(OPTIONAL)
RACEWAY
COMPRESSOR
NO. 2
CONVENIENCE
OUTLET
HOLE IN
END
PANEL
COMPRESSOR NO. 1
Fig. 8 — Typical Field Control Wiring Raceway
FILTER
ACCESS
PANEL
OUTDOOR AIR
OPENING
PANEL
SCREWS
(SIDE)
MANUAL
OUTDOOR-AIR
ADJUSTMENT
SCREWS
DAMPER
BLADE
Fig. 10 — Damper Panel with Manual
Outdoor-Air Damper Installed
—11—
SCREW
HOLES
(TOP)
Fig. 11 — Outdoor-Air Hood Details
C. Optional EconoMi$er IV
See Fig. 14 for EconoMi$er IV component locations.
NOTE: These instructions are for installing the optional
EconoMi$er IV. Refer to the accessory EconoMi$er IV in stal lation instr uctions when field inst alling an EconoMi$er I V
accessory.
1. To remove the existing unit filter access panel, raise
the panel and swing the bottom outward. The panel is
now disengaged from the track and can be removed.
See Fig. 15.
2. The box with the economizer hood components is
shipped in the compa rtment behind the economizer.
The EconoMi$er IV controller is mounted on top of
the EconoMi$er IV in the position shown in Fig. 14.
To remove the component box f rom it s shippi ng posi tion, remove the screw holding the hood box bracket
to the top of the economizer. Slide the hood box out of
the unit. See Fig. 16.
IMPORTANT: If the power exhaust accessory is to be
installed on the unit, the hood shipped with the unit will not
be used and must be discarded. Save the aluminum filter
for use in the power exhaust hood assembly.
3. The indoor coi l acc ess pan el wi ll b e us ed a s the to p of
the hood. Remove the screws along the sides and
bottom of the indoor coil access panel. See Fig. 17.
4. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws
provided to attach the hood sides to the unit. See Fig. 18.
HOOD
HOOD
SCREEN
LOCATION
(SCREEN
NOT
SHOWN)
Fig. 12 — Optional Manual Outdoor-Air
Damper with Hood Attached
ECONOMI$ER IV
CONTROLLER
WIRING
HARNESS
ACTUATOR
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
Fig. 14 — EconoMi$er IV Component Locations
FILTER ACCESS PANEL
Fig. 13 — Outdoor Air Damper Position Setting
INDOOR COIL ACCESS PANEL
Fig. 15 — Typical Access Panel Locations
—12—
x
o
B
d
o
o
H
Fig. 16 — Hood Box Removal
HOOD BOX
BRACKET
INDOOR
COIL
ACCESS
PANEL
CAULK
HERE
SIDE
PANEL
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
6. Insert the hood divider between the hood sides. See
Fig. 18 and 19. Secure hood divider with 2 screws on
each hood side. The hood di vider is also used as the
bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath
the hood top. Insert the aluminum filter into the
bottom filter rack (hood divider) . Push the filter into
position pa st th e op en fi lter c lip s . Cl ose the f ilt er c lip s
to lock the filter into place. See Fig. 19.
8. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 17.
9. Replace the filter access panel.
10. Install all EconoMi$ er IV ac ces sori es. Ec onoM i$e r I V
wiring is shown in Fig. 20.
Barometric flow capacity is shown in Fig. 21. Outdoor air
leakage is shown in Fig. 22. Return air pressure drop is
shown in Fig. 23.
D. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoo r-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is
factory-installed on the EconoMi$er IV in the outdoor airstream. See Fig. 14. The operating range of temperature
measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 24. This sensor
is factory installed. The operating range of temperature
measurement is 0° to 158 F. See Table 5 for sensor
temperature/resistance values.
The temperature sensor l ooks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is
used to lock out the compressors below a 42 F ambient temperature. See Fig. 14.
Fig. 17 — Indoor Coil Access Panel Relocation
LEFT
HOOD
SIDE
B
24 9/16”
HOOD DIVIDER
SCREW
40 3/8”
Fig. 18 — Outdoor-Air Hood Construction
22 1/4”
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
BAROMETRIC
RELIEF
ALUMINUM
FILTER
FILTER
Fig. 19 — Filter Installation
TOP
PANEL
INDOOR COIL
ACCESS PANEL
FILTER
CLIP
—13—
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK
LEGEND
DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT— Potentiometer
RAT— Return-Air Temperature
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT. to the minimum
position.
Fig. 20 — EconoMi$er IV Wiring
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
30
25
20
15
10
5
0
FLOW IN CUBIC FEET PER MINUTE (cfm)
Fig. 22 — Outdoor Air Damper Leakage
0
0.05
0.15
STATIC PRESSURE (in. wg)
0.25
Fig. 21 — Barometric Flow Capacity
0.13 0.20 0.22 0. 25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
—14—
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0. 20 0.25 0.30 0.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 23 — Return Air Pressure Drop
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 24 — Supply Air Sensor Location
E. EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different sensors.
Refer to Table 6. The EconoMi$er IV is su pplied from the fa ctory with a supply air temperature sensor and an outdoor air
temperature sensor. This allows for operation of the
EconoMi$er IV with outdoor air dry bulb changeover control.
Additional accessories can be added to allow for different
types of changeover control and operation of the EconoMi$er
IV and unit.
Table 6 — EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR
APPLICATION
Outdoor Air Dry Bulb
Differential Dry BulbCRTEMPSN002A00*
Single EnthalpyHH57AC078
Differential Enthalpy
for DCV Control
CO
2
using a Wall-Mounted
Sensor
CO
2
CO
for DCV Control
2
using a Duct-Mounted
CO2 Sensor
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be
needed for installation.
†33ZCSENCO2 is an accessory CO
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and
33ZCASPCO2 accessories.
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
and
sensor.
2
CRCBDIOX005A00††
OR
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured
for outdoor dry bulb changeover control. The outdoor air and
supply air tempe rature sensor s are included as standard. For
this control mode, the outdoor temp erature is compa red to an
adjustable set point sel ected on the control. If the outdoor-air
temperature is above the set point, the EconoMi$er IV will
adjust the outdoor-air dampers to minimum position. If the
outdoor-air temperature is below the set point, the posi tion of
the outdoor-air dampers will be con trol led to provi de free coo ling using outdoor air. When in this mode, the LED next to the
free cooling set point potentiometer will be on. The changeover
temperature set point is controlled by the free cooling set point
potentiometer located on the cont rol. See Fig. 25. The scale on
the potentiometer is A, B, C, and D. See Fig. 26 for the corresponding te mp e r ature changeover v a lue s.
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The
accessory senso r must be mounted in the return airstream.
See Fig. 27. Wiring is provided in th e EconoMi$e r IV wiring
harness. See Fig. 20.
In this mode of operation, the outdoor-air temperature is
compared to the return-air temper ature and the lower temperature airstream is used for cooling. When using this mode
of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 25.
ber HH57AC078) is required. Replace the standard outdoor
dry bulb temperature sensor with the accessory enthalpy
sensor in the same mounting location. See Fig. 14. When the
outdoor air enthalpy rises above the outdoor enthalpy
changeover set point, the outdoor-air damper moves to its
minimum position. The outdoor enthalpy changeover set
point is set with the ou tdoor enthalpy set poi nt potentiometer on the EconoMi$er IV controller. The set points are A, B,
C, and D. See Fig. 28. The factory-installed 620-ohm jumper
must be in place across terminals SR and SR+ on the
EconoMi$er IV controller. See Fig. 14 and 29.
Differential Ent halpy Control
For differential enthalpy control, the EconoMi$ er IV co ntrol -
ler uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in the outside air and one in the
return air duct. The EconoMi$er IV controller compares the
outdoor air enthalpy to the return a ir enthalpy to de termine
EconoMi$er IV use. The controller selects the lower enthalpy
air (return or outdoor) for cooling. For example, when the
outdoor air has a lower enthalpy than the return air, the
EconoMi$er IV opens to bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sensor with the acc essor y enth alpy senso r in th e same mou nting
location. See Fig. 14. Mount th e return air enthalpy sen sor
in the return air duct. See Fig. 27. Wiring is provide d in the
EconoMi$er IV wiring harness. See Fig. 20. The outdoor
enthalpy changeover set point is set with the outdoor
enthalpy set point potentiometer on the EconoMi$er IV
controller. When using this mode of changeover control, turn
the enthalpy set point potentiometer fully clockwise to the D
setting.
—15—
Fig. 25 — EconoMi$er IV Controller Potentiometer
and LED Locations
19
LED ON
mA
14
18
17
16
15
13
12
11
10
9
40
LED OFF
45
D
50
60
55
DEGREES FAHRENHEIT
LED ON
C
LED OFF
65
70
LED ON
LED OFF
75
B
LED ON
A
LED OFF
100
90
95
85
80
Fig. 26 — Outside Air Temperature Changeover Set Points
ECONOMI$ER IV
CONTROLLER
ECONOMI$ER IV
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
Fig. 27 — Return Air Temperature or Enthalpy
Sensor Mounting Location
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the l evel of CO
measured in the space or
2
return air duct.
Mount the accessory IAQ s ensor according to ma nufacturer
specifications. The IAQ sensor should be wired to the
AQ and AQ1 terminals of the controller. Adjust the DCV
potentiometers to correspond to the DCV voltage output of
the indoor air quality sensor at the user-determined set
point. See Fig. 30.
If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
Exhaust Set Point Adjustment
The exhaust set point will determine when the exhaust fan
runs based on d am p er po sit i on ( if accessory power exhaust is
installed). The set point is modified with the Exhaust Fan
Set Point (EXH SET) potentiometer. See Fig. 25. The set
point represents the damper position above which the
exhaust fans will be turned on. When there is a call for
exhaust, the EconoMi$er IV controller provides a 45 ±
15 second delay before exhaust fan activation to allow the
dampers to open. This delay allows the damper to reach the
appropriate position to avoid unneces sary fan overload.
Minimum Position C o ntrol
There is a minimum damper position potentiometer on the
EconoMi$er IV c o nt ro ll er. See Fig. 25. The minimum damper
position maintains the minimum airflow into the building
during the occupied period.
When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC
(volatile organic compound) ventilation requirements. The
maximum demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation
position should be turned fully clock wi se.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes,
to enter the building. Make minimum position adjustments
with at least 10 F temperature difference betwee n the outdoor and return-air temperatures.
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed air temperature
using the following formula:
OA
(T
T
x
O
O
)+ (TR x
100100
= Outdoor-Air Temperature
RA
) = T
M
OA = Percent of Outdoor Air
= Return-Air Temperature
T
R
RA = Percent of Return Air
TM = Mixed-Air Temperature
As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor-air temperature
is 60 F, and return-air temperature is 75 F.
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the supply air sensor from terminals T
and T1.
3. Ensure that the factory-installed jumper is in place
across terminals P and P1. If remote damper positioning is being used, make sure that the terminals
are wired according to Fig. 20 and that the minimum
position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer
until the measured mixed-air temperature matches
the calculated value.
6. Reconnect the supply-air sensor to terminals T and T1.
—16—
CONTROL
CURVE
4
1
2
1
A
B
C
D
8
1
6
1
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
P
L
HA
26
NT
E
4
2
2
2
0
2
40
(4)
35
(2)
Y
—
85
(29)90(32)95(35)
46
4
4
42
40
IR
8
3
Y A
6
DR
3
D
N
U
4
3
PO
R
32
E
P
TU
30
B
28
60
(16)
55
(13)
B
50
C
(10)
45
D
(7)
70
(21)
0
0
1
65
(18)
A
80
(27)
75
(24)
0
9
80
70
60
50
0
4
TIVE HUM
RELA
0
3
100
(38)
IDITY
20
(%
105
110
(41)
(43)
)
0
1
N1
P1
T1
AQ1
SO+
SR+
D
35
40
45
50
55
60
65
70
75
80
(2)
(4)
(7)
(10)
(13)
(16)
(18)
(21)
(24)
85
(27)
(29)90(32)95(35)
100
(38)
105
(41)
110
(43)
HIGH LIMIT
CURVE
A
B
C
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 28 — Enthalpy Changeover Set Points
CO SENSOR MAX RANGE SETTING
2
TR1
EXH
2V10V
EXH
Open
2V10V
DCV
2V10V
Free
Cool
B
A
DCV
DCV
C
D
Set
Min
Pos
Max
Set
N
P
T
AQ
SO
SR
TR
24
24 Vac
Vac
COM
HOT
_
+
12
5
4
3
EF1
EF
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
Fig. 30 — CO
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Sensor Maximum Range Setting
2
800 ppm
900 ppm
1000 ppm
1100 ppm
Fig. 29 — EconoMi$er IV Control
—17—
Remote control of the EconoMi$er IV damper is desirable
when requiring additional temporary ventilation. If a
field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the E co no Mi$er IV controller, the
minimum position of the damper can be controlled from a
remote location.
To control the minimum damper position remotely, remove
the factory-insta lled jumper on the P and P1 terminals on
the EconoMi$er IV controller. Wire the field-supplied potentiometer to the P and P1 termina ls on the EconoMi$er IV
controller. See Fig. 29.
Damper Movement
Damper movement from full open to full closed (or vice
1
versa) takes 2
/2 minutes.
Thermostats
The EconoMi$er IV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1
(heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er IV control does not support space temperature
sensors. Connections are made at the thermostat terminal
connection board located in the main control box.
Occupancy Control
The factor y default configuration for the EconoMi$er IV con-
trol is occupied mode. Occupied status is provided by the
black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field-supplied timeclock function in place of the jumper between TR and N. See Fig. 20.
When the timeclock contacts are clos ed, the EconoMi$e r IV
control will be in occupied mode. When the timeclock contacts are open (r emoving the 24-v signal from terminal N),
the EconoMi$er IV will be in un occupied mode.
Demand Controlled Ventilation (DCV)
When using the Ec onoM i $er I V for dem a nd cont roll e d ven ti -
lation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and
cool capacity of the equipment, the maximum ventilation
rate must b e eva lua ted for de sig n c ondi tions. T he maxi mum
damper position must be calculated to provide the desired
fresh air.
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipmen t that cannot exceed the required
ventilation rate at design conditions. Exceeding the required
ventilation rate mea ns the equipmen t can conditi on air at a
maximum ventilation rate that is great er than the required
ventilation rate for maximum occupancy. A proportionalanticipatory strategy will cause the fresh air supplied to
increase as the room CO
CO
set point has not been reached. By the time the CO
2
level increases even though the
2
level reaches the set point, the damper will be at maximum
ventilation and should maintain the set point.
In order to have the CO
sensor control the economizer
2
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventila tion is
the ventilation required to remove contaminants during
unoccupied periods. The following equation may be u sed to
determine the percent of outside-air entering the building for
a given damper position. For best results there should be at
least a 10 degree difference in outside and return-air
temperatures.
OA
(T
T
x
O
O
)+ (TR x
100100
= Outdoor-Air Temperature
RA
) = T
M
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an
output of 3.6 volts to th e ac t uato r provi des a ba se ve ntil at io n
rate of 5% and an output of 6.7 volts provides the maximum
ventilation rate of 20% (or base plus 15 cfm per person). Use
Fig. 30 to determine the maximum setting of the CO
For example, a 1100 ppm set point relates to a 15 cfm per
person design. Use the 1100 ppm curve on Fig. 30 to find the
point when the CO
sensor output will be 6.7 volts. Line up
2
the point on the graph with the left side of the chart to determine that the range configuration for the CO
2
be 1800 ppm. The Eco noMi$er IV control ler will output the
6.7 volts f rom the CO
sensor to the actuator when the C O
2
concentration in the spac e is at 1100 ppm . The DC V set po int
may be left at 2 volts since the CO2 sensor voltag e will be
ignored by the EconoMi$er IV controller until it rises above
the 3.6 volt setting of the minimum position potentiometer.
Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation
potentiometer to this position. Do not set to the maxim um
position as this can result in over-ventilation to the space
and potential high-humidity levels.
CO
Sensor Configuration
2
The CO2 sensor has preset standard voltage settings that
can be selected anytime afte r the sensor is pow ered up. See
Table 7.
Use setting 1 or 2 for Bryant equipment. See Table 7.
1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
See Table 7.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed any-
2
time after the sensor is en ergized. Follow the steps belo w to
change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec-
2
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
sensor.
2
sensor sho uld
2
—18—
Table 7 — CO2 Sensor Standard Settings
SETTINGEQUIPMENTOUTPUT
1
Interface w/Standard
2ProportionalAny
Building Control System
3ExponentialAny
4
5Proportional20
Economizer
6Exponential15
7Exponential20
8Health & SafetyProportional—
Parking/Air Intakes/
9
Loading Docks
LEGEND
ppm — Parts Per Million
ProportionalAny
Proportional15
Proportional—
VENTILATION
RATE
(cfm/Person)
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some
applications, an energy recovery unit is added to reduce the
moisture content of the fresh air being brought into the
building when the enthalpy is high. In most cases, the normal heating and coolin g processe s are more than ade quate t o
remove the humidity loads for most commercial applications.
If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit
and/or a dehum idification opti on should be considered.
VII. STEP 7 — ADJUST INDOOR-FAN SPEED
Adjust the indoor -fa n spee d to me et j obsi te requir eme nts.
For units with electric heat, required minimum cfm is
2250 for 549B090 and 102 and 3000 for 549B120 with the
following except io ns :
Table 8 shows indoor-fan moto r data . Table 9 s hows fa n rpm
at motor pulley settings for standard and alternate motors.
Tables 10 and 11 show FIOP/accessory static pressure. Refer
to Tables 12-23 to determine fan speed settings. Fan motor
pulleys are factory set for speed shown in Table 1.
To change fan speed s:
1. Shut off the unit power supply and tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts
See Fig. 31 and 32.
3. Loosen the movable pulley flange setscrew (see
Fig. 33).
4. Screw the movable flange toward the fixed flange to
increase speed and away from the fixed flange to
decrease speed. Increasing fan speed increases the
load on the motor. Do not exceed the maximum speed
specified in Table 1.
5. Set the movable flange at the nea rest keyway of the
pulley hub and tighten the setscrew. (See Table 1 for
speed change for each full turn of the pulley flange.)
To align fan and motor pulleys:
1. Loosen the fan pulley setscrews.
2. Slide the fan pulley along the fan shaft.
3. Make angular alignm ent by loo se ning the mo t or fro m
the mounting plate.
—19—
To adjust belt tension:
1. Loosen the fan motor mounting plate nuts.
2. Size 090 and 102 — Slide the motor mounting plate
away from the fan scroll for prop er belt tension (5/8-in.
deflection with 8 to 10 lb of force) and tighten the
mounting nuts (see Fig. 31).
Size 120 — Slide the motor mounting plate down-
5
ward to tighten belt tension (
/8-in. deflection with 5
to 10 lb of force). Secure the motor mounting plate
nuts. See Fig. 32.
3. Adjust the bolt and nut on the mounting plate to
secure the motor in a fixed position.
MOTOR MOUNTING
PLATE NUTS
Fig. 32 — Typical Belt-Drive Motor
Mounting for Size 120
Fig. 31 — Typical Belt-Drive Motor
Mounting for Sizes 090 and 102
Fig. 33 — Indoor-Fan Pulley Adjustment
Table 8 — Indoor-Fan Motor Performance
UNIT
549B
090 and
102
120
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors
can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not
result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm
should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.
CFM
GENERAL FAN PERFORMANCE NOTES
1. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using fan motors up
to the ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. For additional information on motor performance refer to Fan Motor Performance, Table 8.
2. Values include losses for filters, unit casing, and wet coils. See Tables 10
and 11 for FIOP/accessory static pressure information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant
representative to verify.
4. Interpolation is permissible. Do not extrapolate.
—21—
Table 12 — Fan Performance 549B090 — Vertical Discharge Units; Standard Motor (Belt Drive)*
1. Boldface indicates a field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 21 for general fan performance notes.
—33—
PRE-START-UP
WARNING: Failure to observe the following warn-
ings could result in serious personal injury:
1. Follow recognized safety practices and wear
protective goggles when checking or servicing
refrigerant system.
2. Do not operate th e compressor or provide any
electric power to the unit unless the compressor
terminal cover is in place and secured.
3. Do not remove the compressor terminal cover
until all electrical sources are disconnected and
tagged.
4. Relieve all pressure from the system before
touching or disturbing anything inside the compressor termin al b ox if a re fr ig e ran t le ak is suspected around the compressor terminals. Use
accepted methods to recover refrigerant.
5. Never attempt to repair a sol dered connection
while the refrigerant system is under pressure.
6. Do not use a torch to remove any component.
The system contains oil and refrigerant under
pressure. To remove a compone nt, wear prote ctive goggles and proceed as follows :
a. Shut off electrical power to the unit.
b. Recover refrigerant to relieve all pressure
from the system using both high-pressure
and low-pressure ports.
c. Cut the component connection tubing with a
tubing cutter, and remove the component
from the unit.
d. Carefully unsweat the remaining tubing
stubs when necessary. Oil can ignite when
exposed to torch flame.
Proceed as follows to ins pect and prep are the unit f or initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to or
shipped with the unit.
3. Make the following inspectio ns:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected wires.
b. Inspect for oil at all refrigerant tubing connections
and on the unit base. Detecting oil generally i ndicates a refrigerant leak. Leak-test all refrigerant
tubing connections using an electronic leak detector, halide torch, or liquid-soap solution.
c. Inspect all field-wiring a nd factory-wiring connec-
tions. Be sure that connections are completed and
tight. Ensure that electrical component wiring
does not come in contact with refrigerant tubing.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten the fins with a fin
comb.
4. Verify the following conditions:
a. Make sure that the outdoor-fan blades are cor-
rectly positioned in the fan orifice. Refer to the
Outdoor-Fan Adjustment section on page 37 for
more details.
b. Make sure that the air filter(s) is in place.
c. Make sure that the condensate drain trap is filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
I. UNIT PREPARATION
Make sure that the unit has been installed in accordance
with these installation instructions and applicable codes.
Make sure that the Start-Up Checklist, located on the back
page of this manual, has been completed and filled out.
II. RETURN-AIR FILTERS
Make sure that the correct air filters are installed in the unit
(see Table 1). Do not operate the unit without return-air
filters.
III. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screen must be in place b efore operat ing the
unit.
IV. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or
remove compressor holddown bolts.
V. INTERNAL WIRING
Check all electrical connections in the unit control boxes;
tighten as required.
VI. REFRIGERANT SERVICE PORTS
Each refrigerant system has 3 Schrader-type service gage
ports: one on the suction line, one on the cooling mode liquid
line, and one on the compressor discharge line.
Be sure that caps on the ports are tight. The port on the cooling mode liquid line and one port on the discharge line have
protective devices installed on them.
A. High-Flow Refrigerant Valves
These are two high flow va lves; on e is loca ted on th e hot gas
tube coming out of the compressor. The second is located on
the suction tube going in to the compressor. Large black plastic caps with O-rings inside identify these valves. No field
access to these valves is available at this time. Ensure that
the plastic caps remain on the valves and a re tight or the
possibility of refrigerant leakage could occur.
VII. COMPRESSOR ROTATION
It is important to be certain that the scroll compressor is
rotating in the proper direction. To determine whether or not
compressor is rotating in the proper direction:
1. Connect service gages to the suction and discharge
pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the indoor fan is probably also rotating in
the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and re-energize compressor.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide heating/
cooling. Compressor failure will occur if rotation direction is
not corrected.
—34—
VIII. COOLING
To start the unit, turn on main power supply. Set the system
selector switch at COOL pos ition and fan switch at AUTO
position. Adjust the thermostat to a setting below room
temperature. The compressor, reversing valve, outdoor-fan
contactor and indoor blower motor are energized.
Check the unit charge. Refer to Refrigerant Charge section
on page 37.
Reset the thermostat at a position above room tempera ture.
The compressor will shut off.
A. To Shut Off Unit
Set the system selector switch at OFF position. Resetting the
thermostat at a position above room temperature shuts unit
off temporarily until the space temperature exceeds the thermostat setting.
Compressor restart is a ccomplished by manual reset a t the
thermostat by turning the selector switch to OFF position
and then ON position.
IX. HEATING
To start the unit, turn on the main power supply.
Set thermostat at HEAT position and a setting above room
temperature, and set fan at AUTO. position.
The first stage of the thermostat energizes the indoor fan
motor, compress or, and outdoor fan; the second sta ge energizes the electr ic hea ter el emen ts i f inst all ed. Check h ea ti ng
effects at air supply grille(s).
If accessory el ectric heaters do not energize, reset the li mit
switch (located on indoor-fan scroll) by press ing the button
located between the terminals on the switch.
A. To Shut Off Unit
Set the system selector switch at OFF position. Resetting the
heating select or lever below room temp erature temporarily
shuts the unit off until the space temperature falls below the
thermostat setting.
X. SAFETY RELIEF
A soft solder joint in the suction line at the loss-of-charge/
low-pressure switch fitting provides pressure relief under
abnormal temperature and pressure conditions.
XI. VENTILATION (Continuous Fan)
Set the fan and system selector switches at ON and OFF
positions, respective ly. The indoor fan opera tes con tinuousl y
to provide constant air circulation.
XII. OPERATING SEQUENCE
A. Cooling, Units without Economizer
When thermost at calls for cooli ng, terminals G and Y1 ar e
energized. The indoor-fan contactor (IFC), reversing valve
solenoid (RVS1) and compressor contactor no. 1 (C1) are
energized and ind oor-fan motor, compressor no. 1, and outdoor fan(s) starts. The outdoor-fan motor(s) runs continuously while unit is cooling. If the thermostat calls for a
second stage of cooling by energ izing Y2, c ompres sor conta ctor no. 2 (C2) and reversing valve solenoid (RVS2) are energized and compressor no. 2 starts.
B. Heating, Units without Economizer
Upon a request for heating from the space thermostat, terminal W1 will be ener gized with 24 v. The IFC, outdoor-fan
contactor (OFC), C1, and C2 wil l be ener gized. Th e reve rs ing
valves switch position and the indoor fan, outdoor fan(s),
compressor no. 1, and compressor no. 2 are energized.
If the space temperature continues to fall while W1 is
energized, W2 will be energized with 24 v, and the heater
contactor(s) (HC) will be energized, which will energize the
electric heater(s).
When the space thermostat is satisfied, W2 will be deenergized first, and the electric heater(s) will be deenergized.
Upon a further rise in space temperature, W1 will be
deenergized, and the reversing valve solenoids (RVS1 and
RVS2) will be energized.
C. Cooling, Units With EconoMi$er IV
When free cool ing is not available, the com pressors will be
controlled b y th e zo ne th ermost at. When f re e cool ing i s a vailable, the outdoor-air damper is modulated by the
EconoMi$er IV control to provide a 50 to 55 F supply-air
temperature into the zone. As the supply-air temperature
fluctuates above 55 or be lo w 5 0 F, the dampers will be modulated (open or close) to bring the supply-air temperature
back within the set point limits.
For EconoMi$er IV operation, there must be a thermostat
call for the fan (G). This will move the damper to its minimum position during the occupied mode.
Above 50 F supply-air temperature, the dampers will modulate from 100% open to the minimum open position. From
50 F to 45 F supply-air temperature, the dampers will maintain at the minimum open position. Below 45 F the dampers
will be completely shut. As the supply-air temperature rises,
the dampers will come back open to the minimum open position once the supply air temperature rises to 48 F.
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized.
If field-installed accessory CO
sensors are connected to the
2
EconoMi$er IV control, a demand controlled ventilation
strategy will begin to opera te. As the CO
increases abo ve the CO
set point, the minimum position of
2
level in the zone
2
the damper will be increased proportionally. As the CO2 level
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed. Damper position will
follow the higher demand condition from DCV mode or free
cooling mode.
Damper movement from full closed to full open (or vice
versa) will take between 1
1
/2 and 21/2 minutes.
If free cooling can be used as determined from the appropriate changeover com mand (switch, dr y bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to
modulate the dampers open to maintain the supply a ir temperature set point at 50 to 55 F.
As the supply-air temperature drops below the set point range
of 50 to 55 F, the control will modulate the outdoor-air dampers closed to maintain the proper supply-air temperatur e .
D. Heating, Units with EconoMi$er IV
When the room temperature calls for heat through terminal
W1, the indoor fan contactor (IFC) and he ater contac tor no . 1
(HC1) are energized. On units equipped for 2 stages of heat,
when additional heat is needed, heater contactor no. 2 is
energized through W2. The ec onomizer damper moves to the
minimum position. When the thermostat is satisfied, the
damper moves to the fully closed position.
—35—
E. Defrost
When the temperature of the outdoor coil drops below 28 F as
sensed by the defrost thermostat (DFT2) and the defrost
timer is at the end of the timed period (adjustable at 30, 50, or
90 minutes), the reversing valve solenoids (RVS1 and RVS2)
are energized and the OFC is deenergized. This switches the
position of the reversing valves and shuts off the outdoor fans .
The electric heaters (if installed) will be energ iz ed.
The unit continues to defrost until the coil temperature as
measured by DFT2 reaches 65 F, or the defrost cycle completes a 10-minute period.
During the Defrost mode, if circuit 1 defrosts first, RVS1 will
oscillate betw een Heati ng and Coo ling mod es (dep ending on
DFT1 switch position) until the Defrost mode is complete.
At the end of the defrost cycle, the electric heaters (if
installed) will be dee nergized; the reversing valves deenergize and the outdoor-fan motors will be energized. The unit
will now operate in the Heating mode.
If the space thermostat is satisfied during a defrost cycle, the
unit will continue in the Defrost mode until the time or temperature constraints are s atisfied.
SERVICE
CAUTION: When servicing the unit, shut off all
electrical power to the unit a nd tag to avoid shock hazard or injury from rotating parts.
Clean 2-row coils as follows:
1. Turn off the unit power and install lockout tag on
disconnect.
2. Remove the top panel screws on the outdoor end of
the unit.
3. Remove the outdoor coil corner post. See Fig. 34. To
hold the top panel open, place the coil corner post
between the top panel and center post. See Fig. 35.
4. Remove the device holding the coil sect ions together
at the return end of the outdoor coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil
section. See Fig. 36.
5. Use a water hose or other suitable equipment to flush
down between the 2 coil s ections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
6. Secure the sectio ns together. Reposition the coil sections, and remove the c oil corner post from be tween
the top panel and center post. Install the coil corner
post and coil center post, and replace all screws.
I. CLEANING
Inspect the unit interior at the beginning of each heating
and cooling season or as operating con ditions require.
A. Indoor Coil
1. Turn the unit p o wer o ff and install lockout tag o n di sconnect. Remove the filter access panel and indoor
coil access panel.
2. If the economizer or accessory two-position damper is
installed, remove the economizer/two-position damper
by disconnecting the economizer plug and removing
mounting screws. Refer to Accessory Economizer or
Two-Position Damper Installation Instructions for
more details.
3. Slide filters out of unit.
4. Clean the coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister.
Wash both sides of the coil and flush with clean
water. For best results, backflush toward the returnair section to remove for eign material.
5. Flush the condensate pan after completion.
6. Reinstall the economizer/two-position damper and
filters.
7. Reconnect wiring.
8. Replace the access panels.
B. Outdoor Coil
Inspect the coil monthly. Clean the outdoor coil annually , and
as required by location and outdoor-air conditions.
Fig. 34 — Cleaning Outdoor Coil
Fig. 35 — Propping Up Top Panel
—36—
Fig. 36 — Separating Coil Sections
C. Condensate Drain
Check and clean each year at the start of the cooling season.
In winter, protect against freeze-up.
D. Filters
Clean or replace at the start of each heating and cooling
season, or more often if operating conditions require it.
Replacement filters must be the same dimensions as original
filters.
E. Outdoor-Air Inlet Screen
Clean the screen with stream or hot water and a mild detergent. Do not use disposable filters in place of screens.
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at
the factory.
B. Fan-Motor Bearings
Fan-motor bearings are permanently lubricated. No lubrication of outdoor or indoor-fan motors is required.
III. OUTDOOR-FAN ADJUSTMENT (Fig. 37)
1. Shut off the unit power supply, and install lockout tag
on disconnect.
2. Remove the outdoor-fan assembly (grille, motor,
motor cover, and fan) and loosen the fan hub
setscrews.
3. Adjust the fan height as shown in Fig. 37.
4. Tighten the setscrews and replace the outdoor-fan
assembly.
IV. BLOWER BELT ADJUSTMENT
Inspect the blower belt for wear, proper belt tension, and
pulley alignment as conditions require or at the beginning of
each heating and air condition ing season.
Refer to Step 7 — Adjust I ndoor-Fan Speed on page 19 for
adjustment and alignment procedu r e.
V. ECONOMI$ER IV ADJUSTMENT
Refer to Optional EconoMi$er IV section on page 12.
VI. HIGH-PRESSURE SWITCH
Located on the compressor hot gas line is a high-pressure
switch with a Schrader core depressor. This switch opens at
428 psig and closes at 320 psig. No adjustment is necessary.
Refer to Table 1.
VII. LOSS OF CHARGE SWITCH
Located on the outdoor liquid line is a low-pressure switch
which functions as a loss-of-charge switch. This switch contains a Schrader core depressor. This switch opens at 7 psig
and closes at 22 psig. No adjustment is necessary. Refer to
Table 1.
VIII. FREEZESTAT
Located on the “hair pin” end of the indoor coil is a bimetal
temperature s ensing switch. T his swi tch prot ects the i ndoor
coil from free ze- up due to lack of airflow. The switch opens at
30 F and closes at 45 F. No adjustment is necessary. Refer to
Table 1.
IX. REFRIGERANT CHARGE
The amount of re fri ger an t char ge i s li s ted o n the u nit na m eplate (also refer to Table 1).
Unit panels must be in place when the unit is operating during charging procedure. The unit must operate for a minimum of 10 minutes before checking or adjusting the charge.
A. No Charge
Use standard evacuating techniques. After evacuating the
system to 500 microns, weigh in the specified amount of
refrigerant (refer to Table 1).
B. Low Charge Cooling
Use Cooling Charging Charts, Fig. 38-40. Vary refrigerant
until the conditions of the appropriate chart are met. Note
that charging charts are different from the type normally
used. The charts are b ased on charging the units to the correct superheat for the various operat ing cond iti ons. An accurate pressure gage and temperature sensing device are
required. Connect the pressure gage to th e service port on
the suction line. Mount the temperature sensing device on
the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be
within the normal operating range of the unit.
UNIT VOLTAGE‘‘A’’ in.
208/230 V2.75
460 V3.50
Fig. 37 — Outdoor Fan Adjustment
—37—
C. To Use Cooling Charging Charts
Take the outdoor ambient temperature and read the suction
pressure gage. Refer to the appropriate chart to determine
what the suction temperature should be. If the suction temperature is high, add refrigerant. If the suction temper ature
is low, carefully recover some of th e charge. Recheck the s uction pressure as the charge is adjusted.
Suction Temperature should be . . . . . . . . . . . . . . . . . . . .51 F
(Suction Temperature may vary ± 5° F.)
D. Heating Charge
Do not attempt to adjust the refrigerant charge while the
unit is operating in the Heating mode. If the charge amount
is believed to be incorrect, recover refrigerant and weigh in
the amount listed on the unit rating plate.
X. TYPICAL WIRING
Refer to Fig. 41 for a typical unit wiring diagram.
XI. REPLACEMENT PARTS
A complete list of replacement parts may be obtained from
any Bryant distributor.
100
689
95
621
90
85
552
80
75
483
70
SUCTION LINE PRESSURE PSIG
65
SUCTION LINE PRESSURE (KILOPASCALS)
414
60
42
32
47
SUCTION LINE TEMPERATURE DEG F
5
10
SUCTION LINE TEMPERATURE DEG F
57
52
62
15
Fig. 39 — Cooling Charging Chart, 549B102
OUTDOOR
TEMP
C
F
64
125
46
115
41
105
35
95
29
85
24
75
67
72
77
20
25
Fig. 38 — Cooling Charging Chart, 549B090
Fig. 40 — Cooling Charging Chart, 549B120
—38—
AWG— American Wire Gage
C—Contactor, Compressor
CAP— Capacitor
CB— Circuit Breaker
CLO— Compressor Lockout
COMP— Compressor Motor
DFT— Defrost Thermostat
EQUIP— Equipment
FPT— Freeze Up Protection Thermostat
FU— Fuse
GND— Ground
HC— Heat Contactor
HPS— High-Pressure Switch
HR— Heater Relay
IFC— Indoor-Fan Contactor
IFM— Indoor-Fan Motor
IFMOVL — Indoor Fan Motor Overload Switch
LPS— Low-Pressure Switch
Fig. 41 — Typical Wiring Schematic (208/230-3-60 Unit Shown)
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
TROUBLESHOOTING
I. UNIT TROUBLESHOOTING
Refer to Table 24 for troubleshooting information.
Table 24 — Heating and Cooling Troubleshooting
PROBLEMCAUSEREMEDY
Compressor and
Outdoor Fan
Will Not Start.
Compressor Will Not
Start But Outdoor Fan
Runs.
Compressor Cycles
(Other Than Normally
Satisfying Thermostat).
Compressor Operates
Continuously.
Excessive Head
Pressure
Head Pressure
Too Low.
Excessive Suction
Pressure.
Suction Pressure
Too Low.
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or control relay.Replace component.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room
High-pressure switch tripped.See problem ‘‘Excessive head pressure.’’
Low-pressure switch tripped.Check for leaks, repair, and recharge.
Freeze-up protection thermostat tripped.See problem ‘‘Suction pressure too low.’’
Faulty wiring or loose connections in compressor circuit.Check wiring and repair or replace.
Compressor motor burned out, seized, or internal
overload open.
Defective overload.Determine cause and replace.
One leg of 3-phase power dead.Replace fuse or reset circuit breaker.
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked outdoor coil or dirty air filter.Determine cause and correct.
Defective overload.Determine cause and replace.
Defective thermostat.Replace thermostat.
Faulty outdoor-fan (cooling) or indoor-fan (heating) motor or
capacitor.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak, repair, and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and
Outdoor coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty outdoor coil.Clean coil.
Refrigerant overcharged.Remove excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and
Condensing air restricted or air short-cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks, repair, and recharge.
Compressor valves leaking.Replace compressor.
Restriction in liquid tube.Remove restriction.
High heat load.Check for source and eliminate.
Compressor valves leaking.Replace compressor.
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter (cooling) or dirty outdoor coil (heating).Replace filter or clean coil.
Low refrigerant charge.Check for leaks, repair, and recharge.
Metering device or low side restrictedRemove source of restriction.
Insufficient indoor airflow (cooling mode).Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Field-installed filter drier restricted.Replace.
Outdoor ambient temperature below 25 F.Install low-ambient kit.
temperature.
Determine cause. Replace compressor.
Determine cause.
recharge to nameplate.
Replace.
recharge.
recharge.
necessary.
—40—
II. ECONOMI$ER IV TROUBLESHOOTING
See Table 25 for EconoMi$er IV logic.
A functiona l view of the EconoMi$er IV is shown in Fig. 42.
Typical settings, sensor ranges, and jumper positions are also
shown. An EconoMi$er IV simulator program is available
from Bryant to help with EconoMi$er IV training and
troubleshooting.
A. EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied
with the EconoMi$er IV.
IMPORTANT:
Be sure to record the positions of all potentiometers
before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm
resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
and +.
R
and +.
O
7. If connected, remove sensor from terminals S
Connect 1.2 kilo-ohm 4074EJM checkout resistor
across terminals S
and +.
O
8. Put 620-ohm resistor across terminals S
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
B. Differential Enthalpy
To check differential enthalpy:
1. Make sure Econ o Mi $er IV pr ep ar at io n pro ce d ur e h as
been performed.
2. Place 620-ohm resistor across S
3. Place 1.2 kilo-ohm resistor across S
and +.
O
and +. The Free
R
Cool LED should be lit.
4. Remove 620-ohm resistor across S
and +. The Free
O
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
C. Single Enthalpy
To check single enthalpy:
1. Make sure Econ o Mi $er IV pr ep ar at io n pro ce d ur e h as
been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit .
3. Set the enthalpy potentiometer to D (fully CW). The
Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
D. DCV (Demand Controlled Ventilation) and Power
Exhaust
To check DCV and Power Exhaust:
1. Make sure Econ o Mi $er IV pr ep ar at io n pro ce d ur e h as
been performed.
2. Ensure terminals AQ and AQ 1 a r e o pen . The LE D for
both DCV and Exhaust should be off. The actuator
should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The a ctua tor s hou ld dri ve to be tween
90 and 95% open.
4. Turn the Exhaust potentiometer CW until the
Exhaust LED turns off. The LED should turn off
when the potentiometer is approximately 90%. The
actuator should remain in position.
5. Turn the DCV set point potentiometer CW until the
DCV LED turns off. The DCV LED should turn off
when the potentiometer is approximately 9 v. The
actuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW
until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds afte r the Exhaust
LED turns on.
7. Return EconoMi$er IV settings and wiring to norm al
after completing troubleshooting.
E. DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
1. Make sure Econ o Mi$ er I V pr epa ra tio n pr oce dur e h as
been performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). Th e DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20
and 80% open.
4. Turn the DCV Maximum Position potentiometer to
fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint. The act uator should drive to be tween 20 and
80% open.
6. Turn the Minimum Position Potentiometer fully CW.
The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator
should drive fully closed.
8. Return EconoMi$er IV settings and wiring to norm al
after completing troubleshooting.
F. Supply-Air Input
To check supply-air input:
1. Make sure Econ o Mi$ er I V pr epa ra tio n pr oce dur e h as
been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool
LED turns on. The actuator should drive to between
20 and 80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1.
The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator
should drive fully closed.
5. Return EconoMi$er IV settings and wiring to norm al
after completing troubleshooting.
G. EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to operation. No trouble shooting or testi ng is done by performing the
following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous sett ing.
—41—
3. Set DCV maximum position po tentiometer to previous setting.
4. Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals S
and +.
R
6. Remove 1.2 kilo-ohm checkout resistor from terminals SO and +. If used, reconnect sensor from terminals SO and +.
Table 25 — EconoMi$er IV Input/Output Logic
INPUTSOUTPUTS
Demand Control
Ventilation (DCV)
Below set
(DCV LED Off)
Above set
(DCV LED On)
*For single enthalpy control, the module compares outdoor enthalpy
to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
High
(Free Cooling LED Off)
Low
(Free Cooling LED On)
High
(Free Cooling LED Off)
Low
(Free Cooling LED On)
Enthalpy*
OutdoorReturn
LowOn OnOnOnMinimum positionClosed
HighOn OnOnOffModulating** (between min.
LowOn OnOnOnModulating†† (between min.
HighOn OnOnOffModulating***Modulating†††
Y1Y2
On OffOnOff
Off OffOffOff
On OffOffOff
Off OffOffOffMinimum positionClosed
On OffOnOff
Off OffOffOff
On OffOffOff
Off OffOffOff
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect wires at T and T1.
10. Remove jumper from P to P1. Rec onnect device at P
and P1.
11. Apply power (24 vac) to terminals TR and TR1.
CompressorN Terminal†
Stage1Stage
2
position and full-open)
position and DCV maximum)
***Modulation is based on the greater of DCV and supply-air sensor
signals, between minimum position and either maximum position
(DCV) or fully open (supply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor
signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
OccupiedUnoccupied
Damper
Modulating** (between
closed and full-open)
Modulating†† (between
closed and DCV
maximum)
Fig. 42 — EconoMi$er IV Functional View
—42—
Access panels
12
Barometric flow capacity 14
Charging chart, refrigerant 38
Clearance 2, 5
CO2 sensor
Configuration 18
Settings 17, 19
Compressor
Lubrication 37
Mounting 34
Rotation 34
Condensate drain
Cleaning 37
Location 3
Control circuit
Wiring 10
Wiring raceway 11
Convenience outlet 7, 8
Defrost board 10, 11
Demand control ventilation 18
Dehumidification 19
Dimensions 2, 5
Ductwork 1
EconoMi$er IV 12-18
Adjustment 37
Components 12
Control mode 15
Damper movement 18
Demand ventilation control 18
Dry bulb temperature sensor 15
Enthalpy sensor 15
Troubleshooting 41, 42
Usage 15
Wiring 14
Electrical connections 6
Electrical data 7-9
Electric heat 6
Enthalpy changeover set points 17
Factory-installed options
Convenience outlet 7, 8
EconoMi$er IV 12-18
Manual outdoor air damper 10-12
Filter
Cleaning 37
Installation 13
Size 4
Freeze protection thermostat 4, 37
Heat anticipator settings 10
High flow valves 34
High pressure switch 4, 37
Horizontal units 1
Indoor air quality sensor 16
Indoor coil 4
Cleaning 36
Indoor fan motor
Lubrication 37
Motor data 20
Performance 22-33
Pulley adjustment 20
Pulley setting 4, 21
Speed 4
Low pressure switch 4, 37
Manual outdoor air damper 10-12
Mounting
Compressor 34
Unit 3, 4
Non-fused disconnect switch 10
INDEX
Operating sequence
Cooling 35
Defrost 36EconoMi$er IV 35
Heating 35
Outdoor air hood 12, 13
Outdoor air temperature sensor 13
Outdoor air inlet screens
Cleaning 37
Outdoor coil 4
Cleaning 36
Outdoor fan 4
Adjustment 37
Physical data 4
Power supply
Wiring 6
Pressure, drop
Heater 21
Pressure switches
High pressure 4, 37
Low pressure 4, 37
Pre-start-up 34
Refrigerant
Charge 4, 37
Type 4
Refrigerant service ports 34
Replacement parts 38
Return air filter 4, 34
Return air temperature sensor 16
Rigging unit 3
Roof curb
Assembly 1
Dimensions 2
Connector package 2
Leveling tolerances 3
Weight 4
Safety considerations 1
Safety relief 35
Service 36-39
Service ports 34
Slab mount 1
Start-up 34-36
Start-up checklist CL-1
Thermostat 10, 11, 18
Troubleshooting 40-42
Ventilation 35
Wei gh t
Corner 5
EconoMi$er IV 4, 5
Unit 4, 5
Wiring
EconoMi$er IV 14
Power connections 6
Thermostat 11
Unit 39
MODEL NO.:_______________________________________
DATE: _____________________________________________
SERIAL NO. _________________________________________ __
TECHNICIAN: _________________________________________
BUILDING LOCATION: ________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
ENSURE ELECTRICAL WIRING DOES NOT COME IN CONTACT WITH
REFRIGERANT TUBING OR SHARP EDGES
CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE
AND SETSCREW TIGHTNESS
CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
VERIFY CORRECT ROTATION OF SCROLL COMPRESSORS
VERIFY INSTALLATION OF ECONOMI$ER IV HOOD (IF EQUIPPED)