Bryant 549B User Manual

installation, start-up and service instructions
SINGLE PACKAGE ROOFTOP HIGH-EFFICIENCY HEAT PUMP UNITS
Cancels: II 549B-90-5 II 549B-90-6
Dura
Pac
Plus Series
Sizes 090-120
71/2 to 10 Tons
549B
10/15/05
IMPORTANT — READ BEFORE INSTALLING
Read and become familiar with these installation instruc­tions before installing this unit.
Be sure the ins tallation conforms to al l applicab le local an d national codes.
These instructions contain important information for the proper maintenance and repair of this equipment. Retain these instructions for future use.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-33
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 1
III. Step 3 — Install Condensate Drain Line and
External Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
IV. Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . 3
V. Step 5 — Make Electrical Connections . . . . . . . . . . 6
VI. Step 6 — Adjust Factory-Installed Options. . . . . . 10
VII. Step 7 — Adjust Indoor-Fan Speed . . . . . . . . . . . . 19
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-36
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36-39
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .40-42
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or servic e air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install lockout tag on disconnect. Electrical shock could cause personal injury.
CAUTION: Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
INSTALLATION
This unit is shipped in the vertical configuration. To convert to horizontal configuration, remove the side duct opening covers. Using the same screw s, install th e cover s on th e ver­tical duct openings with the insulation-side down. Seals around duct openings must be tight.
I. STEP 1 — PROVIDE UNIT SUPPORT A. Roof Curb
Assemble and install the accessory roof curb in acco rdance with instructions shipped wi th the curb. See Fig. 1. Install insulation, cant stri ps, roofing felt, and counter flashing as shown. Ductwork must be attached to the curb. If electric con­trol power will be routed through the basepan, use the appropriate accessory kit listed in Fig. 1, available from your local distributor. Attach the accessory thru-the-bottom ser­vice connections to the basepan in accordance with the acces­sory installa tion inst ruct ions. Conn ect ions m ust b e in stal led before the unit is set on the roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install the gasket supplied with the roof curb as shown i n Fig. 1. An imprope rly applie d gas­ket can also result in air leaks and poor unit performance.
The roof curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for the unit drain to func­tion properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that ex te nds a m ini mum o f 6 i n. beyond the unit cabinet. Install a gravel apron in front of the condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
C. Alternate Unit Support (Curb or Slab Mount)
A non-combustible sleeper ra il can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all duc ts to the roof cu rb and building structure. Do not connect ductwork to the unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openi ngs and all ductwork attached to the flanges. Insulate and weatherproof all e xter­nal ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through a n unco nditi one d spa ce mu st be ins u­lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply w ith appli­cable fire codes.
A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On horizontal dis­charge units, a minim um c learanc e of 1 in. is re quired for the
first 12 in. of ductwork. Cabinet return-air static pressure (a negative condition) shall not exceed 0.30 in. wg with econo­mizer or 0.45 in. wg without economize r.
CONNECTOR PKG.
ACCY.
CRBTMPWR001A01 CRBTMPWR002A01 1 CRBTMPWR003A01 CRBTMPWR004A01
B C D ALT DRAIN HOLE GAS POWER CONTROL ACCESSORY POWER
3
2-8
7
[827]
/16″
1-1015/16″
[583]
13/4″
[44.5]
ROOF CURB
ACCESSORY
CRRFCURB003A01 1-2 [356] CRRFCURB004A01 2-0 [610]
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT 11/4″ [31.7]
“A”
UNIT SIZE 549B
090-120
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″ NPT
[12.7]
1
/2″ NPT
[12.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam, 1 density.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
1
/2″ NPT
[12.7]
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for thru-the-curb gas type. Packages CRBTMPWR003A01 and 4A01 are for thru-the-bottom type gas connections.
3
/4 lb
Fig. 1 — Roof Curb Details
2
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 2 — Unit Leveling Tolerances
III. STEP 3 — INSTALL CONDENSATE DRAIN LINE AND EXTERNAL TRAP
Condensate drain connections are located on the botto m and end of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard end drain connection, make sure the red plug in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installa­tion, relocate the factory-installed red plug from the bottom connection to the end c onnectio n. The ce nter drai n plug looks like a star connection, but can be removed with a
1
/2-in. socket drive exten sion. See Fig. 3A. The pipin g for the con­densate dr ain and e xternal t rap can be completed after the unit is in place.
All units must have an external trap for condensate drain­age. Install a trap at least 4-in. deep and protect against freeze-up. If a dra in line is installe d downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
3
/4-in.). See Fig. 3B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect the unit for transportation dama ge. File any claim with the transportation agency . Keep the unit upright and do not drop it. Spreader bars are not required if top crating is
left on the unit. Rol lers may be used to move th e unit acro ss a roof. Level by using the unit frame as a reference. See Table 1 and Fig. 4 for additional information. Operating weight is shown in Table 1 and Fig. 4.
Lifting holes are pr ovide d i n t he b ase rai ls as shown in Fig. 4 and 5. Refer to rigging instructions on the unit.
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 3A — Condensate Drain Connection (Side View)
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 3B — Condensate Drain Piping Details
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for unit weight of economizer.
4. Unit weights do not include skid.
CAUTION: All panels must be in place when rigging.
Fig. 4 — Rigging Details
UNIT 549B
090 870 395 77.42 1966.5 41.5 1054 42.12 1070
102,120 1000 454 77.42 1966.5 41.5 1054 42.12 1070
WEIGHT
lb kg in. mm in. mm in. mm
‘‘A’’ ‘‘B’’ ‘‘C’’
UNIT
OPERATING
DIMENSIONS
3
A. Positioning
Maintain clearance around and above the unit to provide proper airflow and service access. See Fig. 5.
Position the unit on the roof curb so that the f oll ow in g clea r­ances are maintained:
1
/4-in. clearance between the roof curb
and the base rails on each side and the duct side of unit;
5
3
/16-in. clearance between t he roof cu rb and con denser s ide
of unit (see Fig. 1, section C-C).
Table 1 — Physical Data
Do not install the unit indoors. Do not locate the unit air inlet near exhaust vents or other sources of contaminated air.
Although the unit is weatherproof, guard against water from higher level runoff and overhangs.
After the unit is in position, remove the polyethylene ship­ping wrapper and rigging skid.
BASE UNIT 549B 090 102 120 NOMINAL CAPACITY (tons) 7 OPERATING WEIGHT (lb)
Unit 870 1000 1000 EconoMi$er IV 75 75 75 Roof Curb 223 223 223
COMPRESSOR Scroll
Quantity 22 2 Oil (oz) (each compr) 57 70 57
REFRIGERANT TYPE R-22
Operating Charge (lb)
Circuit 1 9.5 11.0 10.7 Circuit 2 9.5 11.0 10.8
OUTDOOR FAN Propeller
Quantity...Diameter (in.) 2...22 2...22 2...22 Nominal Cfm 6500 6500 6500 Motor Hp...Rpm
OUTDOOR COIL Enhanced Copper Tubes, Aluminum Fins, Fixed Orifice Metering Device
Rows...Fins/in. 2...17 2...17 2...17 Total Face Area (sq ft) 20.5 25.1 25.1
INDOOR FAN Centrifugal Type
Quantity...Size (in.) Standard 1...15 x 15 1...15 x 15 1...15 x 15
Type Drive Standard Belt Belt Belt
Nominal Cfm 3000 3400 4000 Maximum Continuous Bhp Standard 2.90 2.90 3.70
Motor Frame Size Standard 56 56 56
Nominal Rpm Standard 1725 1725 1725
Fan Rpm Range Standard 730-950 840-1085 860-1080
Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Standard 3.4/4.4 3.4/4.4 4.0/5.0
Nominal Motor Shaft Diameter (in.) Standard
Fan Pulley Pitch Diameter (in.) Standard 8.0 7.0 8.0
Belt, Quantity...Type...Length (in.) Standard 1...A...51 1...A...51 1...A...53
Pulley Center Line Distance (in.) Standard 16.75-19.25 16.75-19.25 15.85-17.50
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting Standard 555
Factory Speed Setting (rpm) Standard 730 840 860
Fan Shaft Diameter at Pulley (in.) 111
High-Static 1...15 x 15 1...15 x 15 1...15 x 15
High-Static Belt Belt Belt
High-Static 4.20 4.20 5.25
High-Static 56 56 56
High-Static 1725 1725 1725
High-Static 860-1080 860-1080 830-1130
High-Static 4.0/5.0 4.0/5.0 2.8/3.8
High-Static
High-Static 8.0 8.0 5.8
High-Static 1...A...53 1...A...53 1...BX...48
High-Static 16.75-19.25 16.75-19.25 15.85-17.50
Standard 45 45 45
High-Static 45 45 60
Standard 555
High-Static 556
High-Static 555
High-Static 860 860 887
INDOOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins,
Rows...Fins/in. 3...15 4...15 4...15 Total Face Area (sq ft) 8.9 11.1 11.1
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief 625 Cutout 428 Reset (Auto.) 320
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line) (psig)
Cutout 7 ± 3 Reset (Auto.) 22 ± 5
FREEZE PROTECTION THERMOSTAT
Opens (F) 30 Closes (F) 45
1
/
1
/4...1100
7
/
8
7
/
8
2
81/
1
/4...1100
7
/
8
7
/
8
2
10
1
/4...1100
7
/
8
7
/
8
Acutrol Metering Device
OUTDOOR-AIR INLET SCREEN Cleanable. Screen size and quantity vary by option selected. RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2
LEGEND
Bhp — Brake Horsepower
4
Fig. 5 — Base Unit Dimensions
5
V. STEP 5 — MAKE ELECTRICAL CONNECTIONS
C C
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of elec tric al wir e connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (American National Standards Institute/National Fire Protection Association), latest edition, and local electrical codes. Failure to follow this warning could result in the installer being liable for
3. For units with electric heat, refer to Table 2 and Accessory Installation Instructions.
NOTE: During operation, voltage to compressor terminals must be within the range indicated on the unit nameplate (see Tables 3A-3D). On 3-phase units, voltages between phases must be balanced within 2%, and the current within 10%. Use the formula shown in Tables 3A-3D, Note 2 on page 9 to determine the percentage of voltage imbalance. Operation on imp rop er lin e volt age or exc essiv e pha se imba l­ance constitutes abuse and may cause damage to electrical components. (Such operation would invalidate any applica­ble Bryant warranty .)
personal injury of others.
A. Field Power Supply
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit will be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v
1
/4-in. male
spade terminal on the transformer and c onnecting it to the
1
200-v
/4-in. male spade terminal on the transformer.
Refer to the unit label diagram for additional information. Pigtails are provided for fie ld wire connectio ns. Use factory­supplied splices or a UL (Underwriters’ Laboratories) approved copper/aluminum connector.
When installing units, provide a disconnect per NEC. All field wiring must comply wi th the N E C and lo cal require-
ments. In Canada, electrical connections must be in accor­dance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.
Install field wiring as foll ows:
1. Install conduit through the side panel openings. For units without electric heat, install conduit between the disconnect and control box.
2. Install power lines to terminal connections as shown
LEGEND
Contactor
OMP — Compressor IFC Indoor Fan Contactor NEC National Electrical Code
Field Wiring Factory Wiring Splice Connection (Factory-Supplied)
Fig. 6 — Power Wiring Connections
208/230-3-60
460-3-60
in Fig. 6.
Table 2 — Electric Heating Capacities
UNIT 549B
090
102
120
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula: Heater kW
2
voltage)
UNIT VOLTAGE
(60 Hz)
208/230/240
(3 phase)
460/480
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
208/230/240
(3 phase)
460/480
(3 phase)
= Heater kW rated x (unit power distribution voltage/rated heater
new
ACCESSORY
kW
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
46.2/50.0*
ELECTRIC HEATER PART NUMBER
CRHEATER---A00
017 010 011 012 012 and 017
016 013 014 015 014 and 016
117 110 111 112 112, 117
116 113 114 115 114,116
017 010 012 012 and 017 010 and 012
013 014 015 014 and 016 013 and 015
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
= 16 kW (215/240)
kW
new
kW
= 12.8 kW (rating at 215 v)
new
SINGLE POINT BOX PACKAGE NO.
CRSINGLE---A00
2
007 007 009 009 013
006 006 008 008
012 012 015 015 017
011 011 014 014 016
012 012 015 017 017
011 014 014 016 016
6
UNIT 549B
090
102
120
Table 3A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet
NOMINAL
VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
460-3-60 414 508 6.4 44.0 0.7 3.4
208/230-3-60 187 254 13.9 105 1.4 7.5
460-3-60 414 508 7.9 55.0 0.7 3.4
208/230-3-60 187 254 19.3 123.0 1.4 10.6
460-3-60 414 508 10.0 62.0 0.7 4.8
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
(each)
IFM ELECTRIC HEAT* POWER SUPPLY
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
38.2/ 38.2
65.3/ 69.5
79.8/ 86.3
102.7/112.8
121.5/134.5
148.6/165.7
19.2
40.1
44.0
61.0
68.8
82.0
41.3/ 41.3
68.4/ 72.5
82.9/ 89.4
105.8/115.9
124.5/137.5
151.7/168.8
22.3
43.2
47.0
64.0
71.9
85.0
56.8/ 56.8
84.0/ 88.1
98.5/105.0
140.1/153.1
167.2/184.3
187.3/177.1
28.7
53.5
70.5
78.3
91.5
88.8
110/125 125/150 150/175
110/125 125/150 175/175
100/110 150/175 175/200 200/200
40/ 40†† 70/ 70†† 80/ 90
20†† 45†† 45†† 70 70 90
45/ 45†† 70/ 80†† 90/ 90
25†† 45†† 50†† 70 80 90
60/ 60†† 90/ 90
30†† 60†† 80
80 100 100
MINIMUM UNIT DISCONNECT
SIZE†
242/242
40/ 40
264/267
65/ 69
275/281***
79/ 85
20 39 43 59 66 78
43/ 43 68/ 72 82/ 88
23 43 46 62 69 81
60/ 60 85/ 89 98/104
30 53 69 76 88 99
294/302*** 309/319*** 330/344***
276/276 298/301 309/315*** 328/336*** 343/353*** 364/378***
337/337 358/362*** 370/375*** 403/414*** 425/439*** 441/457***
100/109 117/129 142/158
103/112 120/132 145/161
136/148 161/177 180/198
121 138 141 155 161 171
143 160 163 177 183 193
170 189 203 209 220*** 230***
Table 3B — Electrical Data — Standard Motor Units With Electrical Convenience Outlet
UNIT 549B
090
NOMINAL
VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
460-3-60 414 508 6.4 44.0 0.7 3.4
208/230-3-60 187 254 13.9 105 1.4 7.5
102
460-3-60 414 508 7.9 55.0 0.7 3.4
208/230-3-60 187 254 19.3 123.0 1.4 10.6
120
460-3-60 414 508 10.0 62.0 0.7 4.8
NOTE: See legend and notes on page 9.
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
IFM ELECTRIC HEAT* POWER SUPPLY
(each)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
43.0/ 43.0
70.1/ 74.3
84.6/ 91.1
107.5/117.6
126.3/139.3
153.4/170.5
46.1/ 46.1
73.2/ 77.3
87.7/ 94.2
110.6/120.7
129.3/142.3
156.5/173.6
61.6/ 61.6
88.8/ 92.9
103.3/109.8
144.9/157.9
172.0/189.1
192.1/181.9
21.4
42.3
46.1
63.1
71.0
84.1
24.5
45.3
49.2
66.2
74.1
87.2
30.9
55.6
72.6
80.5
93.6
91.0
45/ 45†† 80/ 80
90/100 110/125 150/150 175/175
25†† 45†† 50†† 70 80 90
50/ 50††
80/ 80
90/100 125/125 150/150 175/175
25†† 50†† 50†† 70 80 90
70/ 70
90/100 110/110 150/175 175/200 200/200
35†† 60†† 80
90 100 100
MINIMUM UNIT
DISCONNECT
SIZE†
247/247
46/ 46
269/272
71/ 75
280/285***
84/ 90
23 42 46 61 68 80
49/ 49 74/ 78 87/ 93
26 45 49 64 72 84
65/ 65 90/ 94
33 55 71 78 90
102
298/307*** 313/324*** 335/349***
281/281 303/306 314/319*** 332/341*** 347/358*** 369/383***
341/341 363/366*** 375/380*** 408/418*** 430/443*** 446/462***
105/115 122/134 147/163
108/118 126/138 151/166
104/110 142/154 167/183 185/204
123 140 143 157 163 174
145 162 165 179 185 196
172 191 205 211 222*** 232***
7
Table 3C — Electrical Data — High-Static Motor Units Without
Electrical Convenience Outlet
UNIT 549B
090
102
120
NOMINAL VOLTAGE (V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 10.6
460-3-60 414 508 6.4 44.0 0.7 4.8
208/230-3-60 187 254 13.9 105 1.4 10.6
460-3-60 414 508 7.9 55.0 0.7 4.8
208/230-3-60 187 254 19.3 123.0 1.4 15.0
460-3-60 414 508 10.0 62.0 0.7 7.4
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
IFM ELECTRIC HEAT* POWER SUPPLY
(each)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
41.3/ 41.3
68.4/ 72.6
82.9/ 89.4
105.8/115.9
124.6/137.6
151.7/168.8
20.6
41.5
45.4
62.4
70.2
83.4
44.4/ 44.4
71.5/ 75.6
86.0/ 92.5
108.9/119.0
127.6/140.6
154.8/171.9
23.7
44.6
48.4
65.4
73.3
86.4
61.2/ 61.2
88.4/ 92.5
102.9/109.4
144.5/157.5
171.6/188.7
191.7/181.5
31.3
56.1
73.1
80.9
94.1
96.4
45/ 45†† 70/ 80
90/ 90 110/125 125/150 175/175
25†† 45†† 50†† 70 80 90
45/ 45††
80/ 80
90/100 110/125 150/150 175/175
25†† 45†† 50†† 70 80 90
70/ 70
90/100 110/110 150/175 175/200 200/200
35†† 60†† 80
90 100 100
MINIMUM UNIT
DISCONNECT
SIZE†
267/267
44/ 44
288/292
69/ 73
300/305***
82/ 88
22 41 45 60 68 80
47/ 47 72/ 76 85/ 91
25 44 48 63 71 83
65/ 65 90/ 94
33 56 72 79 91
102
318/336*** 333/344*** 355/369***
301/301 322/326 334/339*** 352/360*** 367/378*** 389/403***
360/360 382/385*** 393/399*** 427/437*** 448/462*** 464/480***
103/113 121/132 145/169
106/116 124/136 149/164
103/109 141/153 166/182 185/203
134 150 153 167 173 184
156 172 175 189 195 206
181 201 215 221 231*** 241***
Table 3D — Electrical Data — High-Static Motor Units With Electrical Convenience Outlet
UNIT 549B
090
NOMINAL VOLTAGE (V-Ph-Hz)
208/230-3-60 187 254 12.4 88.0 1.4 10.6
460-3-60 414 508 6.4 44.0 0.7 4.8
208/230-3-60 187 254 13.9 105 1.4 10.6
102
460-3-60 414 508 7.9 55.0 0.7 4.8
208/230-3-60 187 254 19.3 123.0 1.4 15.0
120
460-3-60 414 508 10.0 62.0 0.7 7.4
NOTE: See legend and notes on page 9.
VOLTAGE
RANGE
Min Max RLA LRA FLA FLA kW** FLA MCA MOCP FLA LRA
COMPRESSOR
(each)
OFM
IFM ELECTRIC HEAT* POWER SUPPLY
(each)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4 —
13.9
16.5
27.8
33.0
41.7 —
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0 —
16.5
27.8
33.0
41.7
50.0
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0 —
16.7
19.8
33.4
39.7
50.2 —
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0
104.4/120.3 —
19.8
33.4
39.7
50.2
60.1
46.1/ 46.1
73.2/ 77.4
87.7/ 94.2
110.6/120.7
129.4/142.4
156.5/173.6
49.2/ 49.2
76.3/ 80.4
90.8/ 97.3
113.7/123.8
132.4/145.4
159.6/176.7
66.0/ 66.0
93.2/ 97.3
107.7/114.2
149.3/162.3
176.4/193.5
196.5/186.3
22.8
43.7
47.5
64.5
72.4
85.5
25.9
46.7
50.6
67.6
75.5
88.6
33.5
58.2
75.2
83.1
96.2
93.6
50/ 50†† 80/ 80
90/100 125/125 150/150 175/175
25†† 45†† 50†† 70 80 90
50/ 50††
80/ 90 100/100 125/125 150/150 175/200
30†† 50†† 60†† 70 80 90
70/ 70 100/100 110/125 150/175 200/200 200/200
35†† 60†† 80
90 100 100
MINIMUM UNIT
DISCONNECT
SIZE†
271/271
49/ 49
293/296
74/ 78
305/310***
88/ 94
24 44 47 63 70 82
53/ 53 78/ 81 91/ 97
27 47 50 66 73 85
70/ 70 95/ 99
36 58 74 81 93
105
323/331*** 338/348*** 360/373***
305/305 327/330 339/344*** 357/365*** 372/382*** 394/407***
365/365 387/390*** 398/403*** 431/442*** 453/467*** 469/485***
109/118 126/138 159/167
112/121 129/141 154/170
109/115 147/159 172/188 190/209
136 152 155 169 175 186***
158 174 177 191*** 197 208
183 203 217 223*** 234*** 243***
8
LEGEND AND NOTES FOR TABLES 3A-3D
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning
IFM Indoor Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent
NEC National Electrical Code OFM — Outdoor-Fan Motor RLA Rated Load Amps
*Heaters are field installed only.
†Minimum unit disconnect size is used to determine minimum discon-
nect per NEC.
**Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
††Fuse or HACR circuit breaker.
***Factory-installed disconnect is not available for these units when
electric heat package is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
2. Unbalanced 3-Phase Supply Voltage
and Refrigeration
Protection
tion load and equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
cent of voltage imbalance. % Voltage Imbalance
= 100 x
max voltage deviation from average voltage
Use the following formula to determine the per-
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance:
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
3. Non-fused disconnect switch cannot be used when rooftop unit electrical ratings exceed 80 amps.
452 + 464 + 455
3
1371
=
3
= 457
7 457
9
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate the thermostat assembly on a solid wall in the conditioned spac e to sense average temperature in accor­dance with thermostat installation instructions.
NOTE: If using a Bryant elect ronic therm ostat, set th e ther­mostat configuration for “non-heat pump operation.” This family of products does not require an “O” terminal to ener­gize the reversing valve.
Route the therm ostat ca ble or eq uivale nt singl e leads of col­ored wire from the subbase terminals to the low-voltage con­nections on the unit (shown in Fig. 7) as described in Steps 1 through 4 below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directl y c onnect ed to the thermostat and will require a junction box and splice at the thermostat.
1. If the unit is mounted on roof curb and accessory thru-the-curb service plate connection is used, route wire through the connection plate.
2. Pass control wires throug h the hole provided on the unit (see connection D in Connection Sizes table Fig. 5).
3. Feed wi re through the racew ay bu ilt into the co rner po st to the 24-v barrier located on the left side of the control box. See Fig. 8. The raceway provides the UL required clearance between the high-and low-voltage wiring.
4. Connect the thermostat wires to the screw termina ls of the low-voltage connector (se e Fig. 7).
NOTE: If thru-the-bottom power connections are used refer to the accessory installation instructions for information on power wiring. Refer to Fig. 5 for drilling holes in the basepan.
C. Defrost Board
The defrost board timer cycle is set to 30 minutes. To change the cycle time, remove the wire from defrost board connected to the 30 minute quick-connect. See Fig. 9. Connect the wire to the 50 to 90 minute quick-connects on the defrost board, depending on the desired defrost time.
D. Heat Anticipator Settings
For units with electric heat, set heat anticipator settings as shown in Table 4.
VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS
A. Disconnect Switch
The optional disconnect switch is non-fused. The switch can be locked in plac e for safety pur poses. The disconn ect has a maximum rating of 80 amperes and cannot be used if rooftop electrical rating exceeds 80 amperes.
B. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan at the bottom of the unit (for shipping).
Assembly:
1. Determine the amount of ventilation requi red for the building. Record the amount for use in Step 8.
2. Remove the filter access panel by raising the panel and swinging it outward. The panel is now disen­gaged from the track and can be removed. No tools are required to remove the filter access panel. Remove the outdoor-air opening panel. Save panels and screws. See Fig. 10.
3. Separate the hood and screen from the basepan by removing the screws and brackets securing them. Save all screws and discard brackets.
4. Replace the ou tdoor air opening pa nel.
5. Place the hood on the front of the outdoor air opening panel. See Fig. 11 for hood details. Secure the top of the hood with the 6 screws removed in Step 3. See Fig. 12.
6. Remove and save the 8 scre ws (4 on each side) from the sides of the manual outdoor-air damper.
7. Align the screw holes on the hood with the screw holes on the sid e of manual outdoor-air dam per. See Fig. 11 and 12. Secure the hood with the 8 screws from Step 6.
8. Adjust the minimum position setting of the damper blade by adjusting the manual outdoor-air adjust­ment screws on the front of the damper blade. See Fig. 10. Slide the blade vertically until it is in the appropriate position determined by Fig. 13. Tighten the screws.
9. Remove and save the screws cu rrent ly o n the si des of the hood. Insert the screen. Secure the screen to the hood using the screws. See Fig. 12.
10. Replace the filter access panel. Ensure that the filter access panel slides along the tracks and is securely engaged.
UNIT
Heater kW*
10.4, 16.0 0.3 NA NA
549B
*kW is based on 240 or 480 v.
24.8, 32.0 0.6 0.3 0.3
42.4, 50.0 0.9 0.6 0.3 41.7, 50.0 0.6 0.3 0.3
Table 4 — Heat Anticipator Settings
208/230 460
Configuration
1-Stage
2-Stage
Stage 1 Stage 2 Stage 1 Stage 2
UNIT VOLTAGE
Heater kW*
13.9, 16.5
27.8, 33.0
10
Configuration
1-Stage
0.3 NA NA
2-Stage
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS ON
OFF
B
A
C
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
D
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when con­figured for A/C operation.
Fig. 7 — Low-Voltage Connections With or
Without Economizer or Two-Position Damper
Fig. 9 — Defrost Board
DISCONNECT BOARD
DISCONNECT SWITCH (OPTIONAL)
RACEWAY
COMPRESSOR NO. 2
CONVENIENCE OUTLET
HOLE IN END PANEL
COMPRESSOR NO. 1
Fig. 8 — Typical Field Control Wiring Raceway
FILTER ACCESS PANEL
OUTDOOR AIR OPENING PANEL
SCREWS (SIDE)
MANUAL OUTDOOR-AIR ADJUSTMENT SCREWS
DAMPER BLADE
Fig. 10 — Damper Panel with Manual
Outdoor-Air Damper Installed
11
SCREW HOLES (TOP)
Fig. 11 — Outdoor-Air Hood Details
C. Optional EconoMi$er IV
See Fig. 14 for EconoMi$er IV component locations. NOTE: These instructions are for installing the optional
EconoMi$er IV. Refer to the accessory EconoMi$er IV in stal ­lation instr uctions when field inst alling an EconoMi$er I V accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 15.
2. The box with the economizer hood components is shipped in the compa rtment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 14. To remove the component box f rom it s shippi ng posi ­tion, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. See Fig. 16.
IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter
for use in the power exhaust hood assembly.
3. The indoor coi l acc ess pan el wi ll b e us ed a s the to p of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 17.
4. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws pro­vided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 18.
HOOD
HOOD SCREEN LOCATION (SCREEN NOT SHOWN)
Fig. 12 — Optional Manual Outdoor-Air
Damper with Hood Attached
ECONOMI$ER IV CONTROLLER
WIRING HARNESS
ACTUATOR
OUTSIDE AIR TEMPERATURE SENSOR
LOW AMBIENT SENSOR
Fig. 14 — EconoMi$er IV Component Locations
FILTER ACCESS PANEL
Fig. 13 — Outdoor Air Damper Position Setting
INDOOR COIL ACCESS PANEL
Fig. 15 — Typical Access Panel Locations
12
x
o
B
d
o
o
H
Fig. 16 — Hood Box Removal
HOOD BOX BRACKET
INDOOR COIL ACCESS PANEL
CAULK HERE
SIDE PANEL
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
5. Remove the shipping tape holding the economizer barometric relief damper in place.
6. Insert the hood divider between the hood sides. See Fig. 18 and 19. Secure hood divider with 2 screws on each hood side. The hood di vider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider) . Push the filter into position pa st th e op en fi lter c lip s . Cl ose the f ilt er c lip s to lock the filter into place. See Fig. 19.
8. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 17.
9. Replace the filter access panel.
10. Install all EconoMi$ er IV ac ces sori es. Ec onoM i$e r I V wiring is shown in Fig. 20.
Barometric flow capacity is shown in Fig. 21. Outdoor air leakage is shown in Fig. 22. Return air pressure drop is shown in Fig. 23.
D. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoo r-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor air­stream. See Fig. 14. The operating range of temperature measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 24. This sensor is factory installed. The operating range of temperature measurement is 0° to 158 F. See Table 5 for sensor temperature/resistance values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Outdoor Air Lockout Sensor The Economi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42 F ambient tem­perature. See Fig. 14.
Fig. 17 — Indoor Coil Access Panel Relocation
LEFT HOOD SIDE
B
24 9/16”
HOOD DIVIDER
SCREW
40 3/8”
Fig. 18 — Outdoor-Air Hood Construction
22 1/4”
DIVIDER
OUTSIDE AIR
HOOD
CLEANABLE
BAROMETRIC RELIEF
ALUMINUM FILTER
FILTER
Fig. 19 — Filter Installation
TOP PANEL
INDOOR COIL ACCESS PANEL
FILTER CLIP
13
FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK
LEGEND
DCV— Demand Controlled Ventilation IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT— Potentiometer RAT— Return-Air Temperature
Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
Table 5 — Supply Air Sensor
Temperature/Resistance Values
TEMPERATURE (F) RESISTANCE (ohms)
–58 200,250 –40 100,680 –22 53,010
–4 29,091 14 16,590 32 9,795 50 5,970 68 3,747 77 3,000
86 2,416 104 1,597 122 1,080 140 746 158 525 176 376 185 321 194 274 212 203 230 153 248 116 257 102 266 89 284 70 302 55
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT. to the minimum position.
Fig. 20 — EconoMi$er IV Wiring
2500
2000
1500
1000
500
FLOW IN CUBIC FEET PER MINUTE (cfm)
30
25
20
15
10
5
0
FLOW IN CUBIC FEET PER MINUTE (cfm)
Fig. 22 — Outdoor Air Damper Leakage
0
0.05
0.15
STATIC PRESSURE (in. wg)
0.25
Fig. 21 — Barometric Flow Capacity
0.13 0.20 0.22 0. 25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
14
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0. 20 0.25 0.30 0.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 23 — Return Air Pressure Drop
SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION
SUPPLY AIR TEMPERATURE SENSOR
Fig. 24 — Supply Air Sensor Location
E. EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 6. The EconoMi$er IV is su pplied from the fa c­tory with a supply air temperature sensor and an outdoor air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit.
Table 6 — EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR
APPLICATION
Outdoor Air Dry Bulb
Differential Dry Bulb CRTEMPSN002A00*
Single Enthalpy HH57AC078
Differential Enthalpy
for DCV Control
CO
2
using a Wall-Mounted
Sensor
CO
2
CO
for DCV Control
2
using a Duct-Mounted
CO2 Sensor
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be needed for installation.
†33ZCSENCO2 is an accessory CO
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and
33ZCASPCO2 accessories.
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
and
sensor.
2
CRCBDIOX005A00††
OR
Outdoor Dry Bulb Changeover The standard controller is shipped from the factory configured
for outdoor dry bulb changeover control. The outdoor air and supply air tempe rature sensor s are included as standard. For this control mode, the outdoor temp erature is compa red to an adjustable set point sel ected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor-air dampers to minimum position. If the outdoor-air temperature is below the set point, the posi tion of the outdoor-air dampers will be con trol led to provi de free coo l­ing using outdoor air. When in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the cont rol. See Fig. 25. The scale on the potentiometer is A, B, C, and D. See Fig. 26 for the corre­sponding te mp e r ature changeover v a lue s.
Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional acces­sory dry bulb sensor (part number CRTEMPSN002A00). The accessory senso r must be mounted in the return airstream. See Fig. 27. Wiring is provided in th e EconoMi$e r IV wiring harness. See Fig. 20.
In this mode of operation, the outdoor-air temperature is compared to the return-air temper ature and the lower tem­perature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy set point potentiom­eter fully clockwise to the D setting. See Fig. 25.
Outdoor Enthalpy Changeover For enthalpy control, accessory enthalpy sensor (part num-
ber HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 14. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the ou tdoor enthalpy set poi nt potentiome­ter on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 28. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. See Fig. 14 and 29.
Differential Ent halpy Control For differential enthalpy control, the EconoMi$ er IV co ntrol -
ler uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return a ir enthalpy to de termine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sen­sor with the acc essor y enth alpy senso r in th e same mou nting location. See Fig. 14. Mount th e return air enthalpy sen sor in the return air duct. See Fig. 27. Wiring is provide d in the EconoMi$er IV wiring harness. See Fig. 20. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting.
15
Loading...
+ 33 hidden pages